CUADRO DE CARGAR DEL TABLERO TAN-14 CON INT PPAL. 3x30 No. Cto 65 w Watts X fase WATTS TOT. AMPERES (Ic) LONG. METROS % e (caída de tension ) Cal. De conductor A B C CN -18 (1) 4 260 260 2.84 66 1.78 10 CN – 21 (3) 10 650 650 CN – 20 (5) 6 390 390 CN – 18A 3 195 195
14

Calculo de Circuitos Derivados Del Tablero de Alumbrado Normal

Aug 26, 2014

Download

Documents

cancerigena
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Calculo de Circuitos Derivados Del Tablero de Alumbrado Normal

CUADRO DE CARGAR DEL TABLERO TAN-14 CON INT PPAL. 3x30No. Cto 65

wWatts X fase WATTS

TOT.AMPERES

(Ic)LONG.

METROS% e

(caída de tension)

Cal. De conductorA B C

CN -18 (1) 4 260 260 2.84 66 1.78 10CN – 21 (3) 10 650 650CN – 20 (5) 6 390 390CN – 18A 3 195 195CN – 21A 7 445 445CN – 20 4 260 260CN – 19 6 390 390

CN – 22 (17) 8 520 520CN – 19A 5 325 325CN – 19B 6 390 390

Page 2: Calculo de Circuitos Derivados Del Tablero de Alumbrado Normal

TOTALES 59 1170 1105 1560 3835

Ejemplo del CALCULO DE CIRCUITOS DERIVADOS DEL TABLERO DE ALUMBRADO NORMAL "TAN-14"

CIRCUITO DERIVADO EMERGENTE "CN-18"1) Caracteristicas:

* Carga: 260 Watts. (CARGA TOTAL INSTALADA)

* Generales

Volts. 127 Longitud. 66 mCanalizacion

GALV. P/G.

Fases. 1 F

Hilos 1F,1N, 1t F.C.A. 0.8 F.C.T. 0.88 F.P. 0.9 F.D. 1.0

Page 3: Calculo de Circuitos Derivados Del Tablero de Alumbrado Normal

2) Calculo de Corriente Nominal del Circuito

W x F.D 260.0 1.00 2.27Amps.

V x F.P. 127 0.9

3) Calculo de Corriente corregida del CircuitoDe acuerdo al Art. 220-3(a) de la NOM-001-SEDE-2005. Por ser cargas continuas 125%

InX1.25 2.27 1.25 2.84Amps.

4) Corrigiendo por temperatura (F:C:T) de 36 a 40 ºC. Y por agrupamiento.Tabla 310-16 NOM-001-SEDE-2005

In 2.84 Amp. 3.23Amps.

(F.C.T.) 0.88

Tabla A- 310-11 NOM-001-SEDE-2005

IcT 3.23 Amp. 4.04Amps.

(F.C.A.) 0.8

5) Selección del conductor por corriente (ampacidad) de la tabla NOM 310-16 para 4.04 Amps. le corresponde conductores del calibre No. 2.08 mm2 (14 AWG). Que soporta 20 Amps.

6) Selección del conductor por caida de tension.

In =In =In = = = =XXX

XXX = = =

Ic =Ic =Ic =

IcT =IcT =IcT = = = =

IcTA =IcTA =IcTA = = = =

Page 4: Calculo de Circuitos Derivados Del Tablero de Alumbrado Normal

Art. 210-19(a) De la NOM-001-SEDE-2005. Considerando el 3% en CIRCUITOS DERIVADOS.

4L Ic 4 66 2.84 1.97 mmV x e% 127 3

Para lo cual le corresponde un conductor del calibre: 5.26 mm2 (10 AWG)

7) De los pasos 5 y 6 concluimos que corresponden conductores del calibre No. 5.26 mm2 (10 AWG)

THW, Cu con S = 5.26 mm2 y R = 3.97ohms/km. Soporta 35 Amps.

según la tabla 310-16 y 10-8; repespectivamente de la NOM-001-SEDE-2005

8) Comprobacion de la caida de tension.

4L Ic 4 66 2.84 1.12 %V x S 127 5.26

7) Porciento de regulacion y caida de voltaje.

* Regulacion

4L Ic 4 66 2.84 1.12 %V x S 127 5.26

* Caida de voltaje (C.V)

2 2 2

S =S =S = = = = XXXXXX

XXX = = =

e% =e% =e% = = = = X XX

X XX

X XX

= = =

e% =e% =e% =

e% =e% =e% =

= = = XXX

XXX

XXX

= = = XXX XXX

= = =

Page 5: Calculo de Circuitos Derivados Del Tablero de Alumbrado Normal

CV= (V - Circuito)(e%) 127 X 1.12

CV = 1.43 Volts.

8) Perdidas de potencia. (KW)

R L Ic2 3.970 0.066 2.841000 1000

Perd. Pot. (KW) = 0.002 Kw.

9) Porciento de perdidas (%Perd.)

Perd. Pot. (Kw) 0.002KW - Circuito 0.26

0.81 %

10) La proteccion del circuito que alimenta al circuito CN-18 sera con ITM Capacidad del ITM=ICTA x 1.25 = 5.05 Amp., por tanto se selecciona un ITM de 1 polos x 15 Amps.

11) Tamaño del cable de tierra. Según la tabla NOM-250-95, para una proteccion que no exceda 15 Amps. En ITM le

X X 2

X X 2

X X 2

KW =KW =KW = = = =

% Perd. =% Perd. =% Perd. = X 100 = X 100 = X 100 = X 100 X 100 X 100

% Perd. =% Perd. =% Perd. =

Page 6: Calculo de Circuitos Derivados Del Tablero de Alumbrado Normal

corresponde un calibre de cable de tierra del No. 2.08 mm2 (14 AWG).

12) Tamaño de la canalizacion.

Para 1CF - 10 AWG, CN - 10 AWG y 1CT - 14 AWG, OCUPAN UN AREA DE: 58.48 mm2

TOTAL: 58.48 mm2De acuerdo ala tabla 10-4 de la NOM-001-SEDE-2005. UTILIZANDO UN 40% de ocupacion.Corresponde una tuberia de 16 mm (1/2") de diametro como minimo.

Page 7: Calculo de Circuitos Derivados Del Tablero de Alumbrado Normal

PROTECCION

AMPERES(Ic)) WATTS TOT

UBICACION CAL. DE COND. AWG

TABLERO

%e CAIDA DE TENSION

NUMERO DE CIRCUITO

WATTS X FASE

220-3. Cálculo de los circuitos derivados. Las cargas de los circuitos derivados deben

calcularse como se indica en los siguientes incisos:

a) Cargas continuas y no continuas. La capacidad nominal del circuito derivado no debe ser

inferior a la suma de la carga no continua más el 125% de la carga continua. El tamaño nominal

mínimo de los conductores del circuito derivado, sin aplicar ningún factor de ajuste o corrección,

debe permitir una capacidad de conducción de corriente igual o mayor que la de la suma de la

carga no continua, más el 125% de la carga continua.

Excepción: Cuando el equipo, incluidos los dispositivos de protección contra sobrecorriente,

esté aprobado para funcionamiento continuo a 100% de su capacidad nominal.

Page 8: Calculo de Circuitos Derivados Del Tablero de Alumbrado Normal
Page 9: Calculo de Circuitos Derivados Del Tablero de Alumbrado Normal
Page 10: Calculo de Circuitos Derivados Del Tablero de Alumbrado Normal
Page 11: Calculo de Circuitos Derivados Del Tablero de Alumbrado Normal
Page 12: Calculo de Circuitos Derivados Del Tablero de Alumbrado Normal