TABLERO DE DISTRIBUCIONDIAGRAMA UNIFILARDEL TABLERO DE
DISTRIBUCION GENERAL1TABLERO ST - 1In =Pot.x HPV3
x220xCosxAlumbrado4480.00WTomacorriente1680.00WCalentador de
agua1500.00WSecadora de mano de SS.HH.10350.00WSecadora de mano de
SS.HH.- Discapacitado 1er sotano10350.00WExtractor de
Aire99.20WReservaPot. Total =28459.20WTension =220Cos =0.85
=1.00Carga 3 =1.73In =87.97Id =109.96Seccion.calculada =35mm2Sec.
proyecto =35Seccion Obra =35mm21NTD - 1In =Pot. X HPV3
x220xCosxAlumbrado9644.18wTomacorriente4536.00wSubtablero
ST-A1927.20wSecadora de mano de SS.HH. Mujeres10350.00wSecadora de
mano de SS.HH.- Hombre10350.00wReservaPot. Total =36807.38wTension
=220Cos =0.85 =1.00Carga 3=1.73In =113.78Id =142.22Sec. calculada
=50mm2Sec. proyecto =35Seccion Obra =35mm22NTD - 2In =Pot. X HPV3
x220xCosxAlumbrado11105.84wTomacorriente3864.00wSecadora de mano de
SS.HH. Mujeres10350.00wCalentador de agua c1500.00wReservawPot.
Total =26819.84wTension =220Cos =0.85 =1.00Carga 3=1.73In =82.90Id
=103.63Sec.calculada =35mm2Sec.proyecto =35Seccion Obra =35mm23NTD
- 3In =Pot. X
HP1x220xCosxAlumbrado13497.60wTomacorriente3528.00wSecadora de mano
de SS.HH. Mujeres10350.00wSecadora de mano de SS.HH.-
Hombre10350.00wCalentador de agua c1500.00wReservawPot. Total
=39225.60wTension =220Cos =0.85 =1.00Carga 3=1.73In =121.25Id
=151.56Sec.calculada =70mm2Sec. proyecto =35Seccion Obra =35mm24NTD
- 4In =Pot. X
HP1.73x220xCosxAlumbrado10685.72wTomacorriente2352.00wSecadora de
mano de SS.HH. Mujeres10350.00wSecadora de mano de SS.HH.-
Hombre10350.00wCalentador de agua c1500.00wReservawPot. Total
=35237.72wTension =220Cos =0.85 =1.00Carga 3=1.73In =108.92Id
=136.15Sec.calculada =50mm2Sec. proyecto =35Seccion Obra
=35mm2E1UPS (TG - E)In =Pot.Total1.73x220xCosxTomacorriente Estab.
014032WTomacorriente Estab. 022520wTomacorriente Estab.
039912wTomacorriente Estab. 044032wServidor 1500wServidor
2500wServidor 3500wCentral Telefonica300wCentral de
alarma350wCentral de alarma300wrack de comunicaciones500central de
adm. de video300wReserva1000wPot. Total =24746wTension =220Cos
=0.85 =1.00Carga 3=1.73In =76.49Id =95.62Sec. calculada =35mm2Sec.
proyecto =70Seccion Obra =70mm2
TABLERO DE FUERZADIAGRAMA UNIFILAR DEL TABLERO GENERAL DE
FUERZACALCULO DE ALIMENTADORES - LOCAL UNIQUETGF - 1AIRE
ACONDICIONADO TABLERO TF-11FTF - 1 ( AA 1er PISO)C - 1FEquipo AA-1
( 3/4 HP)In =Pot.x HPIn =Pot.x HPV3 x220xCosxV3 x220xCosx1 HP
=746W1 HP =746W1.-Equipo AA -1559.50.75HPPot. HP =0.752.-Equipo AA
-2559.50.75HPTension =2203.-Equipo AA - 3559.50.75HPCos
=0.854.-Equipo AA - 4559.50.75HP =0.95.-Extractor en
linea3730.5HPCarga 3=1.73Puerta Levadiza559.50.75HPPuerta
Corrediza559.50.75HPIn =1.92Reserva2000WId =2.40Pot. Total
=5730wTension =220Sec.calculada =1.5mm2Cos =0.85Sec.proyecto =6mm2
=0.9Seccion Obra =6mm2Carga 3 =1.73u =1.73 xxLxIxCosIn =19.68SId
=24.60 = Resisitividad de Cu0.00172Sec.calculada =4mm2L = Longitud
(M)7.1Sec. proyecto =I = Corriente (A)2.40Seccion Obra =16mm2Cos =
factor de potencia0.85u = caida de tension 5%112FTF - 2 (AA 2do
PISO)S =1.73 xxLxIxCosIn =Pot. X HPuV3 x220xCosxS =1.101 HP
=746w1.-Equipo AA2 -1559.50.75HPSeccion U =1.5 mm22.-Equipo AA2
-2559.50.75HP3.-Equipo AA2 - 3559.50.75HPC - 2FEquipo AA-2 ( 3/4
HP)4.-Equipo AA2 - 4559.50.75HP5.-Reserva2000WIn =Pot. X HPPot.
Total =4238WV3 x220xCosxTension =220Cos =0.851 HP =746w =0.9Pot. HP
=0.75Carga 3=1.73Tension =220Cos =0.85In =14.56 =0.9Id =18.19Carga
3=1.73Sec. calculada =2.5mm2In =1.92Sec. proyecto =Id =2.40Seccion
Obra =16mm2Sec.calculada =2.5mm23FTF - 3 (AA 3er PISO)Sec. proyecto
=6mm2Seccion Obra =6mm2In =Pot. X HPV3 x220xCosxu =1.73 xxLxIxCos1
HP =746WS1.-Equipo AA3 - 3559.50.75HP2.-Equipo AA cto de
servidores22383HP = Resisitividad de Cu0.001723.-Reserva2000WL =
Longitud (M)6.00Pot. Total =4797.5WI = Corriente (A)2.40Tension
=220Cos = factor de potencia0.85Cos =0.85u = caida de tension 5%11
=0.9Carga 3=1.73S =1.73 xxLxIxCosuIn =16.48Id =20.60S
=1.00Sec.calculada =4mm2Seccion U =1.5 mm2Sec.proyecto =Seccion
Obra =25mm2C - 3FEquipo AA-3 ( 3/4 HP)4FTF - 3 (AA 4to PISO)In
=Pot. X HPV3 x220xCosxIn =Pot. X HP1x220xCosx1 HP =746WPot. HP
=0.751 HP =746WTension =220Equipo AA4 -1559.50.75HPCos =0.85Equipo
AA4 - 2559.50.75HP =0.9Equipo AA4 - 3559.50.75HPCarga
3=1.73Reserva2000WPot. Total =3678.5WIn =1.92Tension =220Id
=2.40Cos =0.85 =0.9Sec.calculada =1.5mm2Carga 3=1.73Sec. proyecto
=6mm2Seccion Obra =6mm2In =12.63Id =15.79u =1.73
xxLxIxCosSSec.calculada =2.5mm2Sec. proyecto = = Resisitividad de
Cu0.00172Seccion Obra =16mm2L = Longitud (M)12.12I = Corriente
(A)2.405FTF - 5 (AA Y EXTRACCION DE TECHO)Cos = factor de
potencia0.85u = caida de tension 5%11In =Pot. X HP1.73x220xCosxS
=1.73 xxLxIxCosu1 HP =746WEquipo EC - 33730.5HPS =1.55Equipo EC -
23730.5HPEquipo UC - 122383HPSeccion U =1.5 mm2Equipo 1C -
100HPEquipo IC - 200HPC - 4FExtractor en Linea ( 1/2 HP)Equipo EC -
101HPEquipo EC - 43730.5HPIn =Pot. X HPReserva2000W1x220xCosxPot.
Total =5357WTension =2201 HP =746WCos =0.85Pot. HP =0.5 =0.9Tension
=220Carga 3=1.73Cos =0.85 =0.9In =18.40Carga 1=1Id =23.00In
=2.22Sec.calculada =4mm2Id =2.77Sec. proyecto =Seccion Obra
=35mm2Sec.calculada =1.5mm2Sec. proyecto =4mm26FTF - 6 (TABLERO DE
CONTROL PARA CHILLER)Seccion Obra =4mm2In =Pot.TotalC - 5FPuerta
Levadiza (1 HP) Av. Bayovar1x220xCosxIn =Pot. X HP1 HP
=746W1x220xCosxElectrob. 01895212HPElectrob. 02895212HP1 HP
=746Wchiller108200WPot. HP =1Reserva2000WTension =220Pot. Total
=128104WCos =0.85Tension =220 =0.9Cos =0.85Carga 1=1 =0.9Carga
3=1.73In =4.43Id =5.54In =439.98Id =549.97Sec.calculada =1.5mm2Sec.
proyecto =0mm2Sec. calculada =1.5mm2Seccion Obra =4mm2Sec. proyecto
=Seccion Obra =400mm2C - 6FPuerta Corrediza (1 HP) Av. MarzanoIn
=Pot. X HP7FTF - 7 (EXTRACTOR DE CO 5 HP)1x220xCosxIn =Pot. X HP1
HP =746W1.73x220xCosxPot. HP =1.51.-Tension =2202.-1 HP =746WCos
=0.853.-Pot.HP =5 =0.94.-Tension =220Carga 1=1.005.-Cos =0.85In
=6.656.- =0.9Id =8.317.-Carga 3=1.738.-Sec.calculada =1.5mm2In
=12.81Sec. proyecto =0mm2Id =16.01Seccion Obra =4mm2Sec.calculada
=2.5mm2Sec. proyecto =AIRE ACONDICIONADO TABLERO TF-2Seccion Obra
=16mm2C - 1FEquipo AA3-1 ( 3/4 HP)8FTF - 8 (TC ELECTROBOMBAS DE
DESAGUE)In =Pot. X HPIn =Pot. TotalV3 x220xCosx1.73x220xCosx1 HP
=746W1 HP =746WPot. HP =0.75Electrob. 0114922HPTension
=220Electrob. 0214922HPCos =0.85Reserva1500w =0.9Pot. Total
=4484WCarga 3=1.73Tension =220Cos =0.85In =1.92 =0.9Id =2.40Carga
3=1.73Sec.calculada =1.5mm2In =15.40Sec.proyecto =6mm2Id
=19.25Seccion Obra =6mm2Sec.calculada =2.5mm2C - 2FEquipo AA2-1(
3/4 HP)Sec. proyecto =Seccion Obra =10mm2In =Pot. X HPV3
x220xCosx9FTF - 9 (TC ELECTROBOMBAS DE AGUA)1 HP =746WIn
=Pot.TotalPot. HP =0.751.73x220xCosxTension =220Cos =0.851 HP =746W
=0.9Electrob. 0137305HPCarga 3=1.73Electrob.
0237305HPReserva2000wIn =1.92Pot. Total =9460WId =2.40Tension
=220Cos =0.85Sec.calculada =1.5mm2 =0.9Sec. proyecto =6mm2Carga
3=1.73Seccion Obra =6mm2In =32.49Id =40.61C - 3FEquipo AA2-3 ( 3/4
HP)Sec.calculada =10mm2In =Pot. X HPSec. proyecto =V3
x220xCosxSeccion Obra =16mm21 HP =746WPot. HP =0.7510FTF - 10
(ASCENSOR 10HP)Tension =220Cos =0.85In =Pot. X HP
=0.91.73x220xCosxCarga 3=1.731 HP =746WIn =1.92Pot. HP =10Id
=2.40Tension =220Cos =0.85Sec.calculada =1.5mm2 =0.9Sec. proyecto
=6mm2Carga 3=1.73Seccion Obra =6mm2In =25.62Id =32.03C - 4FEquipo
AA2 - 4 ( 3/4 HP)Sec.calculada =6mm2In =Pot. X HPSec. proyecto
=220xCosxSeccion Obra =25mm21 HP =746WPot. HP =0.75Tension =220Cos
=0.85 =0.9Carga 1=1.73In =1.92Id =2.40Sec.calculada =1.5mm2Sec.
proyecto =6mm2Seccion Obra =6mm2AIRE ACONDICIONADO TABLERO TF- 3C -
1FEquipo AA3-1 ( 3/4 HP)In =Pot. X HPV3 x220xCosx1 HP =746WPot. HP
=0.75Tension =220Cos =0.85 =0.9Carga 3=1.73In =1.92Id
=2.40Sec.calculada =1.5Sec.proyecto =6mm2Seccion Obra =6mm2C -
2FEquipo AA3-2 ( 3/4 HP)In =Pot. X HPV3 x220xCosx1 HP =746WPot. HP
=0.75Tension =220Cos =0.85 =0.9Carga 3=1.73In =1.92Id
=2.40Sec.calculada =1.5Sec.proyecto =6mm2Seccion Obra =6mm2C -
3FEquipo AA3-3 ( 3/4 HP)In =Pot. X HPV3 x220xCosx1 HP =746WPot. HP
=0.75Tension =220Cos =0.85 =0.9Carga 3=1.73In =1.92Id
=2.40Sec.calculada =1.5Sec.proyecto =6mm2Seccion Obra =6mm2C -
4FEquipo AA CTO DE SERVIDORES( 3 HP)In =Pot. X HPV3x220xCosx1 HP
=746WPot. HP =3Tension =220Cos =0.85 =0.9Carga 3=1.73In =7.69Id
=9.61Sec.calculada =1.5mm2Sec.proyecto =10mm2Seccion Obra
=10mm2AIRE ACONDICIONADO TABLERO TF- 4C - 1FEquipo AA4-1 ( 3/4
HP)In =Pot. X HPV3 x220xCosx1 HP =746WPot. HP =0.75Tension =220Cos
=0.85 =0.9Carga 3=1.73In =1.92Id =2.40Sec.calculada =1.5 mm2Sec.
proyecto =6mm2Seccion Obra =6 mm2C - 2FEquipo AA4-2 ( 3/4 HP)In
=Pot. X HPV3 x220xCosxHP =746Pot. HP =0.75Tension =220Cos =0.85
=0.9Carga 3=1.73In =1.92Id =2.40Sec.calculada =1.5mm2Sec.proyecto
=6mm2Seccion Obra =6mm2C - 3FEquipo AA4-3 ( 3/4 HP)In =Pot. X HPV3
x220xCosx1 HP =746WPot. HP =0.75Tension =220Cos =0.85 =0.9Carga
3=1.73In =1.92Id =2.40Sec.calculada =1.5mm2Sec.proyecto
=6mm2Seccion Obra =6mm2EXTRACCION DE AIRE TABLERO TF- 5C - 1FEquipo
EC - 3 ( 1/2 HP)In =Pot. X HP1x220xCosx1 HP =746WPot. HP
=0.5Tension =220Cos =0.85 =0.9Carga 1=1.00In =2.22Id
=2.77Sec.calculada =1.5mm2Sec.proyecto =4mm2Seccion Obra =4mm2C -
2FEquipo EC -2 ( 1/2 HP)In =Pot. X HP1x220xCosx1 HP =746WPot. HP
=0.5Tension =220Cos =0.85 =0.9Carga 1=1.00In =2.22Id
=2.77Sec.calculada =1.5mm2Sec.proyecto =4mm2Seccion Obra =4mm2C -
3FEquipo UC- 1 ( 3 HP)In =Pot. X HPV3 x220xCosx1 HP =746WPot.
=3.00Tension =220Cos =0.85 =0.9Carga 3=1.73In =7.69Id
=9.61Sec.calculada =1.5mm2Sec.proyecto =6mm2Seccion Obra =6mm2C -
4FEquipo IC- 1 ( PRESURIZACION ESCALERA)In =Pot. X HPV3 x220xCosx1
HP =746WPot. =1.50Tension =220Cos =0.85 =0.9Carga 3=1.73In =3.84Id
=4.80Sec.calculada =1.5mm2Sec.proyecto =6mm2Seccion Obra =6mm2C -
5FEquipo IC- 2 ( INYECTOR AIRE FRESCO)In =Pot. X HPV3 x220xCosx1 HP
=746WPot. HP =0.00Tension =220Cos =0.85 =0.9Carga 3=1.73In =0.00Id
=0.00Sec.calculada =Sec.proyecto =6mm2Seccion Obra =6mm2C -
6FEquipo EC- 1 (1HP)In =Pot. X HPV3 x220xCosx1 HP =746WPot. HP
=1.00Tension =220Cos =0.85 =0.9Carga 3=1.73In =2.56Id
=3.20Sec.calculada =1.5mm2Sec.proyecto =4mm2Seccion Obra =4mm2C -
7FEquipo EC- 4 ( 1/2 HP)In =Pot. X HP1.0 x220xCosx1 HP =746WPot. HP
=0.50Tension =220Cos =0.85 =0.9Carga 1=1In =2.22Id
=2.77Sec.calculada =1.5mm2Sec.proyecto =4mm2Seccion Obra
=4mm2CHILLER TABLERO TF- 6C - 1FELECTROBOMBA 1 ( 12 HP)In =Pot. X
HP1.73x220xCosx1 HP =746WPot. HP =12Tension =220Cos =0.85 =0.9Carga
3=1.73In =30.75Id =38.43Sec.calculada =10mm2Sec.proyecto
=16mm2Seccion Obra =16mm2C - 2FELECTROBOMBA 2 ( 12 HP)In =Pot. X
HP1.73x220xCosx1 HP =746WPot. HP =12Tension =220Cos =0.85 =0.9Carga
3=1.73In =30.75Id =38.43Sec.calculada =10mm2Sec.proyecto
=16mm2Seccion Obra =16mm2C - 3FCHILLER ( 108.2Kw)In =Pot. X HPV3
x220xCosxPot. =108200.00Tension =220Cos =0.85 =0.9Carga 3=1.73In
=371.62Id =464.52Sec.calculada =400mm2Sec.proyecto =120mm2Seccion
Obra =240mm2ELECTROBOMBAS DE DESAGUE TABLERO TF- 8C - 1ELECTROBOMBA
1 - DESAGUE ( 2 HP)In =Pot. X HP1.73x220xCosx1 HP =746WPot. HP
=2Tension =220Cos =0.85 =0.9Carga 3=1.73In =5.12Id
=6.41Sec.calculada =1.5mm2Sec.proyecto =6mm2Seccion Obra =6mm2C -
2ELECTROBOMBA 2 - DESAGUE ( 2 HP)In =Pot. X HP220xCosx1 HP
=746WPot. HP =2Tension =220Cos =0.85 =0.9Carga 3=1.73In =5.12Id
=6.41Sec.calculada =1.5mm2Sec.proyecto =6mm2Seccion Obra
=6mm2ELECTROBOMBAS DE AGUA TABLERO TF- 9C - 1ELECTROBOMBA 1 - AGUA
( 5 HP)In =Pot. X HP1.73x220xCosx1 HP =746WPot. HP =5Tension
=220Cos =0.85 =0.9Carga 3=1.73In =12.81Id =16.01Sec.calculada
=2.5mm2Sec.proyecto =10mm2Seccion Obra =10mm2C - 2ELECTROBOMBA 2 -
AGUA ( 5 HP)In =Pot. X HP220xCosx1 HP =746WPot. HP =5Tension
=220Cos =0.85 =0.9Carga 3=1.73In =12.81Id =16.01Sec.calculada
=2.5mm2Sec.proyecto =10mm2Seccion Obra =10mm2