Top Banner
Calculation of PFP Thickness Friday, June 10, 2022
10

Calculation of PFP Thickness Friday, 28 August 2015.

Dec 25, 2015

Download

Documents

Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Calculation of PFP Thickness Friday, 28 August 2015.

Calculation of PFP ThicknessWednesday, April 19, 2023

Page 2: Calculation of PFP Thickness Friday, 28 August 2015.

The thickness of fire protection required is determined by:

1. Duration

2. Critical Steel Temperature

3. Steel section size and type

Hp/A ratio

4. Thickness stated in the local or international approval

Page 3: Calculation of PFP Thickness Friday, 28 August 2015.

SI Units:

Hp/A =

M/D =

A/V =

Imperial (US) Units:

W/D =

A/P =

Heated Perimeter

Cross Section Area=

metres

metres²= m-1 or /m

Heated Perimeter

Weight of section= inches

Pounds/foot= lb/ft/in

Heated Perimeter =Square inches =Cross Section Area

in2/ininches

All express the relationship between the amount of steel capable of absorbing heat to the area of steel surface exposed to the fire.

Heated Surface Area=

metres²

metres³= m-1 or /m

Volume of Steel

Mass of Section

Heated Perimeter=

Kilograms / metre

metres= kg/m²

Page 4: Calculation of PFP Thickness Friday, 28 August 2015.

How much PFP do I need?

Hp/A - Section Factors

Cross Sectional

Area (A = m²)

Heated Perimeter (Hp = m)

Low Hp/A = Thinner PFP305 x 305 x 240 kg/m

Hp/A = 1.905m / 0.0305m²Hp/A = 62 m-1

For H120 (400°C): Chartek 7 = 11 mm

High Hp/A = Thicker PFP305 x 305 x 97 kg/m

Hp/A = 1.789m / 0.0123m²Hp/A = 145 m-1

For H120 (400°C): Chartek 7 = 16 mm

Page 5: Calculation of PFP Thickness Friday, 28 August 2015.

How much PFP do I need?

How Hp/A changes with sides exposed to fire.(Example 305 x 305 x240 Kg/m UC)

Note: Cross Sectional Area Remains the same in all cases!

Wall, Floor or Deck Wall, Floor or Deck

4 Sides exposed

Hp/A=

Hp/A = 62 m-1

0.0305 m²

1.905 m

3 Sides exposed

Hp/A=

Hp/A = 52 m-1

0.0305 m²

1.587 m

Flange only exposed

Hp/A=

Hp/A = 13 m-1

0.0305 m²

0.393 m

Page 6: Calculation of PFP Thickness Friday, 28 August 2015.

How to calculate an Hp/A?

www.asfp.org.uk

TheYellowBook!

Page 7: Calculation of PFP Thickness Friday, 28 August 2015.

How to calculate an Hp/A?

Page 8: Calculation of PFP Thickness Friday, 28 August 2015.

What do I do with my Hp/A?

Example of Certificate of Fire Approval with table of Hp/A v required PFP thickness

Chartek 7 Certificate Interchar 963 loadings

Page 9: Calculation of PFP Thickness Friday, 28 August 2015.

What do I do with my Hp/A?

Interchar 963 loadings

Page 10: Calculation of PFP Thickness Friday, 28 August 2015.

What about other section shapes?

Wall, Floor or Deck Wall, Floor or Deck

Decreasing Hp/A = Lower PFP thickness required