Top Banner
Technical Data Physical Data Performance Data Acousc Performance Data Construcon Code Descripon
11

Caice Cheetah Fan Coil Unit Technical Data Brochure · Cheetah Fan Coil Unit Technical Data Acous0c Data for Fan Coil Unit with Circular Discharge All the following data is based

Apr 01, 2018

Download

Documents

dangtram
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Caice Cheetah Fan Coil Unit Technical Data Brochure · Cheetah Fan Coil Unit Technical Data Acous0c Data for Fan Coil Unit with Circular Discharge All the following data is based

Technical Data Physical Data

Performance Data

Acous�c Performance Data

Construc�on Code Descrip�on

Page 2: Caice Cheetah Fan Coil Unit Technical Data Brochure · Cheetah Fan Coil Unit Technical Data Acous0c Data for Fan Coil Unit with Circular Discharge All the following data is based

0118 918 6470 · www.caice.co.uk · [email protected] · Follow @caiceUK

1

Cheetah Fan Coil Unit Technical Data

Fan Coil Physical Data

Size

Number of

Spigots

Width

(mm)

200Ø & 250Ø Units with Spigots

A

(mm)

B

(mm)

A

(mm)

B

(mm)

1 3 602 301 - 301 -

2 4 952 276 400 276 400

3 5 1252 276 350 276 350

4 6 1552 176 400 251 350

5 6 1902 201 500 276 450

315Ø Units with Spigots

Plan View

Side View

Pipe connec�ons 15mm for both hea�ng & cooling.

Le0 hand coil connec�on and control box shown.

Right hand connec�ons are also available (opposite as

shown).

Wid

th

A

A

B

365mm 55mm 55mm

23

5m

m

121mm

270mm

35mm 247mm

475mm 10mm 49mm

Page 3: Caice Cheetah Fan Coil Unit Technical Data Brochure · Cheetah Fan Coil Unit Technical Data Acous0c Data for Fan Coil Unit with Circular Discharge All the following data is based

0118 918 6470 · www.caice.co.uk · [email protected] · Follow @caiceUK

2

Cheetah Fan Coil Unit Technical Data

Plan View

Side View

Module Length (mm)

Fresh air plenum 250

Fresh air plenum with filter 260

Return air plenum 270 320 385

Return air plenum with filter 280 330 395

Inlet a:enuator 300 600 900

Inlet a:enuator with filter 310 610 910

Core fan coil unit 475

Core fan coil unit with filter 485

Module Physical Data

Module Length (mm)

Discharge a:enuator 300 600 900

Discharge standard (200mm)

plenum X 270 Y 121

Discharge drop (250mm) plenum X 320 Y 146

Discharge drop (315mm) plenum X 385 Y 171

Pres�ge rectangular discharge

a:enuated plenum 270 570 870

Inboard filter with underside access

for fully ducted systems 65

Electric heater 300

Electric heater with filter 310

Wid

th

A

A

B

55mm 55mm

Va

rio

us

Y

X

247mm

10mm 49mm 300mm

35mm

475mm 300mm

23

5m

m

235mm for 200Ø spigots, 285mm for 250Ø spigots,

340mm for 315Ø spigots

Page 4: Caice Cheetah Fan Coil Unit Technical Data Brochure · Cheetah Fan Coil Unit Technical Data Acous0c Data for Fan Coil Unit with Circular Discharge All the following data is based

0118 918 6470 · www.caice.co.uk · [email protected] · Follow @caiceUK

3

Pres0ge Cheetah Fan Coil Unit Technical Data

Fan Coil Physical Data

Size Width (mm)

1 602

2 952

3 1252

4 1552

5 1902

Width 1 (mm)

542

892

1192

1492

1842

Plan View

Side View

Le0 hand coil connec�on and control box shown.

Right hand connec�on are also available (opposite

as shown)

Wid

th

55mm 55mm

23

5m

m

270mm

35mm 247mm

475mm 10mm

End Eleva0on

Showing Fan Coil Unit Discharge

Width 1 30mm 30mm

23

5m

m

17

5m

m

Internal acous�c

lining

Addi�onal central

nutsert on

233/333 units and

above

M8 nutserts to suit

30mm Doby/Mez flange

With Rectangular Discharge Plenum

55mm

12

mm

Module Corner Unit Support

Each module has common drop rod

placement holes pre-drilled as shown

for easy on-site installa�on.

Page 5: Caice Cheetah Fan Coil Unit Technical Data Brochure · Cheetah Fan Coil Unit Technical Data Acous0c Data for Fan Coil Unit with Circular Discharge All the following data is based

0118 918 6470 · www.caice.co.uk · [email protected] · Follow @caiceUK

4

Cheetah Fan Coil Unit Technical Data

Performance Data Guide

The data on the following pages has been derived from tests undertaken at a third party acous�c test facility in

accordance with BS 4856: Part 4: 1997 “Determina�on of sound power levels of fan coil units, unit heaters and

unit coolers using reverbera�on rooms”.

A standard 200Ø spigo:ed fan coil unit was mounted in Reverbera�on Room 1 then ducted with 1000mm long

solid circular galvanised sheet steel ducts to a dividing wall / plate and into Reverbera�on Room 2. If solid

ducts are replaced by flexible ducts the discharge sound power levels (Lw) will reduce by:

Acous0c Reduc0on to Lw 125 250 500 1k 2k 4k 8k Hz

1000mm flexible duct 4 5 9 11 10 8 8 dB

Tes0ng Procedure

Guide NR levels are based on a number of assumed parameters and a typical office installa�on. We have listed

these parameters below, should these parameters not be applicable for a par�cular applica�on, then a

detailed acous�c assessment will be required.

Fan Coil Unit Size Room Size

Reverbera0on Time

(mid frequency)

Sizes 1 & 2 20m² 0.35 s

Sizes 3 & 4 30m² 0.45 s

Size 5 56m² 0.60 s

Ceiling Height

2.7m

2.7m

2.7m

The Guide NR level assumes that a single fan coil unit will be installed within a 600mm deep ceiling void above

a room with the aforemen�oned characteris�cs, and serving 1000 x 100mm slot diffusers with 50% free area.

A correc�on to the Guide NR level should be made where more than one unit is present in a room space.

Return air grilles should be located at least 1.5m from the fan coil inlet.

Representa�ve guide NR levels can be provided for Pres�ge units, based on a typical hotel bedroom

applica�on.

Please contact us for more informa�on

Acous0c Loss Allowed 125 250 500 1k 2k 4k 8k Hz

Discharge ducts & 90° lined diffuser plenums(1)

9 13 17 20 20 20 14 dB

False Ceiling SRI(2)

9 8 12 18 22 23 22 dB

Guide NR Levels

Notes 1 includes 1000mm long, 200mm diameter flexible duct. 2 ceiling performance based on “Armstrong Supreme” ceiling

Page 6: Caice Cheetah Fan Coil Unit Technical Data Brochure · Cheetah Fan Coil Unit Technical Data Acous0c Data for Fan Coil Unit with Circular Discharge All the following data is based

0118 918 6470 · www.caice.co.uk · [email protected] · Follow @caiceUK

5

Cheetah Fan Coil Unit Technical Data

Typical Performance Data

Performance Criteria

Electrical supply 230V, 1ph, 50Hz

Cooling air on temperature db 23°C

Cooling air on % RH 50%

Chilled water flow temperature 6°C

Chilled water return temperature

12°C

Hea�ng air on temperature 20°C

LPHW flow temperature 82°C

LPHW return temperature 71°C

External sta�c pressure 30 Pa

All data is based on a 4-row coil op�on

Size

Guide

NR Level

Air Flow

(l/s)

Specific Fan Power Air Off 11°C Air Off 12°C

AC

Version

(W/l/s)

EC

Version

(W/l/s)

Total

Cooling

Duty (kW)

Sensible

Cooling

Duty (kW)

Total

Cooling

Duty (kW)

Sensible

Cooling

Duty (kW)

1

34 107 0.77 0.31 1.84 1.53 1.69 1.40 1.94

35 114 0.82 0.32 1.96 1.63 1.80 1.50 2.06

35 130 0.81 0.35 2.22 1.86 2.04 1.71 2.35

35 140 0.84 0.37 2.40 2.01 2.19 1.84 2.53

2

30 155 0.79 0.25 2.69 2.22 2.47 2.04 2.81

32 185 0.79 0.26 3.19 2.65 2.93 2.43 3.35

35 228 0.80 0.29 3.90 3.26 3.59 3.00 4.13

39 280 0.85 0.35 4.78 4.02 4.38 3.68 5.07

3

30 202 0.77 0.25 3.52 2.90 3.22 2.65 3.66

32 235 0.77 0.26 4.07 3.37 3.73 3.09 4.26

35 297 0.82 0.28 5.10 4.26 4.69 3.91 5.38

37 330 0.83 0.30 5.65 4.73 5.18 4.34 5.98

41 402 0.85 0.36 6.85 5.77 6.28 5.29 7.28

4

29 227 0.77 0.25 3.96 3.25 3.63 2.98 4.11

31 277 0.74 0.23 4.80 3.97 4.41 3.64 5.02

34 369 0.76 0.24 6.34 5.29 5.81 4.85 6.69

35 398 0.79 0.26 6.83 5.71 6.27 5.24 7.21

39 477 0.86 0.32 8.13 6.84 7.47 6.28 8.64

5

32 384 0.77 0.26 6.65 5.51 6.09 5.05 6.96

33 430 0.79 0.28 7.42 6.17 6.80 5.66 7.79

34 483 0.81 0.30 8.30 6.93 7.61 6.35 8.75

Air Off

35°C

Heating

Duty (kW)

Please see page 4 for an explana�on of how Guide NR values have been derived.

These guide NR levels are not applicable for Pres�ge units.

Page 7: Caice Cheetah Fan Coil Unit Technical Data Brochure · Cheetah Fan Coil Unit Technical Data Acous0c Data for Fan Coil Unit with Circular Discharge All the following data is based

0118 918 6470 · www.caice.co.uk · [email protected] · Follow @caiceUK

6

Cheetah Fan Coil Unit Technical Data

Typical Performance Data

Performance Criteria

Electrical supply 230V, 1ph, 50Hz

Cooling air on temperature db 23°C

Cooling air on % RH 50%

Chilled water flow temperature 8°C

Chilled water return temperature

14°C

Hea�ng air on temperature 20°C

LPHW flow temperature 60°C

LPHW return temperature 40°C

External sta�c pressure 30 Pa

All data is based on a 4-row coil op�on

Size

Guide

NR Level

Air Flow

(l/s)

Specific Fan Power Air Off 13°C Air Off 15°C

AC

Version

(W/l/s)

EC

Version

(W/l/s)

Total

Cooling

Duty (kW)

Sensible

Cooling

Duty (kW)

Total

Cooling

Duty (kW)

Sensible

Cooling

Duty (kW)

1

34 107 0.77 0.31 1.40 1.27 1.12 1.02 1.29

35 114 0.82 0.32 1.49 1.36 1.19 1.08 1.37

35 130 0.81 0.35 1.70 1.55 1.36 1.24 1.56

35 140 0.84 0.37 1.82 1.67 1.45 1.33 1.68

2

30 155 0.79 0.25 2.04 1.84 1.63 1.47 1.87

32 185 0.79 0.26 2.43 2.20 1.94 1.76 2.23

35 228 0.80 0.29 2.98 2.72 2.37 2.16 2.83

39 280 0.85 0.35 3.64 3.34 2.90 2.66 3.37

3

30 202 0.77 0.25 2.65 2.41 2.13 1.92 2.43

32 235 0.77 0.26 3.07 2.80 2.46 2.23 2.83

35 297 0.82 0.28 3.88 3.54 3.10 2.83 3.58

37 330 0.83 0.30 4.30 3.93 3.43 3.14 3.98

41 402 0.85 0.36 5.20 4.78 4.15 3.82 4.84

4

29 227 0.77 0.25 3.01 2.70 2.41 2.16 2.73

31 277 0.74 0.23 3.65 3.30 2.91 2.63 3.34

34 369 0.76 0.24 4.82 4.39 3.85 3.51 4.45

35 398 0.79 0.26 5.19 4.74 4.15 3.79 4.79

39 477 0.86 0.32 6.19 5.68 4.94 4.54 5.75

5

32 384 0.77 0.26 5.09 4.57 4.06 3.65 4.63

33 430 0.79 0.28 5.68 5.12 4.54 4.09 5.18

34 483 0.81 0.30 6.36 5.75 5.07 4.59 5.82

Air Off

30°C

Heating

Duty (kW)

Please see page 4 for an explana�on of how Guide NR values have been derived.

These guide NR levels are not applicable for Pres�ge units.

Page 8: Caice Cheetah Fan Coil Unit Technical Data Brochure · Cheetah Fan Coil Unit Technical Data Acous0c Data for Fan Coil Unit with Circular Discharge All the following data is based

0118 918 6470 · www.caice.co.uk · [email protected] · Follow @caiceUK

7

Cheetah Fan Coil Unit Technical Data Acous0c Data for Fan Coil Unit with Circular Discharge

All the following data is based on the standard fan coil unit core module with inlet filter fi:ed and a 200Ø

discharge plenum.

EC Model

Air Flow

(l/s)

Ext Pressure

(pa)

Sound Power Levels (dB) at Mid Octave Band Frequencies (Hz)

125 250 500 1k 2k 4k 8k

301

107 30 Discharge 55 56 52 51 47 42 38

Inlet/Radiated 54 55 54 48 43 38 29

114 30 Discharge 55 57 53 51 48 43 40

Inlet/Radiated 55 56 55 49 44 39 31

130 30 Discharge 56 57 54 53 49 44 42

Inlet/Radiated 56 57 56 50 46 40 34

140 30 Discharge 58 57 55 54 51 46 45

Inlet/Radiated 57 56 57 51 47 42 36

302

155 30 Discharge 52 52 49 45 42 35 30

Inlet/Radiated 51 52 50 43 38 31 23

185 30 Discharge 54 54 51 49 46 40 34

Inlet/Radiated 53 54 53 46 41 35 26

228 30 Discharge 56 57 54 52 49 43 40

Inlet/Radiated 56 57 56 49 45 39 31

280 30 Discharge 59 60 56 55 52 48 46

Inlet/Radiated 59 60 58 52 48 43 37

303

202 30 Discharge 53 52 50 45 43 36 30

Inlet/Radiated 54 53 52 44 39 32 23

235 30 Discharge 55 54 52 47 45 38 33

Inlet/Radiated 56 55 53 45 41 35 25

297 30 Discharge 58 57 54 51 48 43 39

Inlet/Radiated 59 58 56 49 45 39 30

330 30 Discharge 59 59 55 53 50 45 42

Inlet/Radiated 60 59 57 50 47 42 33

402 30 Discharge 61 63 59 56 54 50 47

Inlet/Radiated 63 63 61 54 51 46 39

304

227 30 Discharge 50 51 48 43 40 32 27

Inlet/Radiated 52 52 50 42 36 28 22

277 30 Discharge 52 53 50 46 43 36 29

Inlet/Radiated 54 54 52 44 38 31 23

369 30 Discharge 55 56 53 49 47 41 35

Inlet/Radiated 57 57 55 48 43 37 27

398 30 Discharge 57 57 54 51 48 43 38

Inlet/Radiated 58 58 56 49 44 38 29

477 30 Discharge 60 60 57 55 53 48 44

Inlet/Radiated 62 61 58 52 48 43 35

384 30 Discharge 54 55 53 48 46 39 32

Inlet/Radiated 58 57 54 47 42 35 24

430 30 Discharge 56 56 54 49 47 41 35

Inlet/Radiated 59 58 55 48 43 37 26

483 30 Discharge 58 58 55 51 49 43 38

Inlet/Radiated 61 59 56 49 45 39 29

305

Page 9: Caice Cheetah Fan Coil Unit Technical Data Brochure · Cheetah Fan Coil Unit Technical Data Acous0c Data for Fan Coil Unit with Circular Discharge All the following data is based

0118 918 6470 · www.caice.co.uk · [email protected] · Follow @caiceUK

8

Cheetah Fan Coil Unit Technical Data Acous0c Data for Pres0ge Fan Coil Unit with Rectangular Discharge

All the following data is based on the standard fan coil unit core module with inlet filter fi:ed and a

rectangular discharge plenum.

EC Model

Air Flow

(l/s)

Ext Pressure

(pa)

Sound Power Levels (dB) at Mid Octave Band Frequencies (Hz)

125 250 500 1k 2k 4k 8k

331

107 20 Discharge 54 54 50 47 39 36 34

Inlet/Radiated 54 55 54 48 43 38 29

114 20 Discharge 54 55 51 47 40 37 36

Inlet/Radiated 55 56 55 49 44 39 31

130 20 Discharge 55 55 52 49 41 38 38

Inlet/Radiated 56 57 56 50 46 40 34

140 20 Discharge 57 55 53 50 43 40 41

Inlet/Radiated 57 56 57 51 47 42 36

332

155 20 Discharge 51 50 47 41 34 29 26

Inlet/Radiated 51 52 50 43 38 31 23

185 20 Discharge 53 52 49 45 38 34 30

Inlet/Radiated 53 54 53 46 41 35 26

228 20 Discharge 55 55 52 48 41 37 36

Inlet/Radiated 56 57 56 49 45 39 31

280 20 Discharge 58 58 54 51 44 42 42

Inlet/Radiated 59 60 58 52 48 43 37

333

202 20 Discharge 52 50 48 41 35 30 26

Inlet/Radiated 54 53 52 44 39 32 23

235 20 Discharge 54 52 50 43 37 32 29

Inlet/Radiated 56 55 53 45 41 35 25

297 20 Discharge 57 55 52 47 40 37 35

Inlet/Radiated 59 58 56 49 45 39 30

330 20 Discharge 58 57 53 49 42 39 38

Inlet/Radiated 60 59 57 50 47 42 33

402 20 Discharge 60 61 57 52 46 44 43

Inlet/Radiated 63 63 61 54 51 46 39

334

227 20 Discharge 49 49 46 39 32 26 23

Inlet/Radiated 52 52 50 42 36 28 22

277 20 Discharge 51 51 48 42 35 30 25

Inlet/Radiated 54 54 52 44 38 31 23

369 20 Discharge 54 54 51 45 39 35 31

Inlet/Radiated 57 57 55 48 43 37 27

398 20 Discharge 56 55 52 47 40 37 34

Inlet/Radiated 58 58 56 49 44 38 29

477 20 Discharge 59 58 55 51 45 42 40

Inlet/Radiated 62 61 58 52 48 43 35

384 20 Discharge 53 51 51 44 38 33 28

Inlet/Radiated 58 57 54 47 42 35 24

430 20 Discharge 55 54 52 45 39 35 31

Inlet/Radiated 59 58 55 48 43 37 26

483 20 Discharge 57 56 53 47 41 37 34

Inlet/Radiated 61 59 56 49 45 39 29

335

Should a Guide NR level be required, please contact us for more details

Page 10: Caice Cheetah Fan Coil Unit Technical Data Brochure · Cheetah Fan Coil Unit Technical Data Acous0c Data for Fan Coil Unit with Circular Discharge All the following data is based

0118 918 6470 · www.caice.co.uk · [email protected] · Follow @caiceUK

9

Cheetah Fan Coil Unit Technical Data

Construc0on Code Descrip0on

Controls

A Standard speed control

B Free issue hea�ng or cooling only

C Free issue hea�ng and cooling

D Stand alone hea�ng or cooling only

E Stand alone hea�ng and cooling

Models

1 Ver�cal EC Unit

3 Horizontal EC Unit

Discharge Configura0on

C Core Unit only

0 Core Unit + plenum with 200Ømm spigots

5 Core Unit + plenum with 250Ømm spigots

8 Core Unit + plenum with 315Ømm spigots

3 Pres�ge rectangular

1 Rectangular (ver�cal units)

Inlet Plenum Op0ons

G Fresh air - unlined

H Fresh air - lined

I 200mm spigot return air - unlined

J 250mm spigot return air - unlined

K 315mm spigot return air - unlined

L 200mm spigot return air - lined

M 250mm spigot return air - lined

N 315mm spigot return air - lined

B Basic waterside

U Uncased (chassis) waterside

C Cased waterside

Configura0on

2 0 1 B / 3 6 / B 5 N F P T Y E W / A X

Number of Fans

1 One fan unit

2 Two fan units

3 Three fan units

4 Four fan units

5 Five fan units

3 300mm a:enuator

6 600mm a:enuator

9 900mm a:enuator

Inlet A@enuator

3 300mm a:enuator

6 600mm a:enuator

9 900mm a:enuator

Discharge A@enuator

Coil Style

3 Three row coil

4 Four row coil

5 Five row coil

B Hea�ng & Cooling

C Cooling only

H Hea�ng only

Coil Opera0ng Mode

F Filter extension

P Standard condensate pump

T Traffolyte label

Op0ons

Y Painted drain tray

E Electric heater

S Peristal�c condensate pump

W Shrink wrap

X Any special features

Special Features

Page 11: Caice Cheetah Fan Coil Unit Technical Data Brochure · Cheetah Fan Coil Unit Technical Data Acous0c Data for Fan Coil Unit with Circular Discharge All the following data is based

Telephone

0118 918 6470

Facsimile

0118 918 6480

[email protected]

www.caice.co.uk

Caice Acoustic Air Movement Ltd.

Riverside House

3 Winnersh Fields

Gazelle Close

Winnersh

Wokingham

RG41 5QS

Registered office and

head office

Company Registration Number

2790667

VAT Registration Number

GB614683632

Important Informa�on

All published specifica�ons within this document were accurate as of 16 June 2015. As part of our policy

of con�nuous product improvement we reserve the right to change the specifica�ons of our products

without prior no�ce. Our latest product specifica�ons are available from our web site.