1 CABLE TESTING STANDARDS: O V E R V I E W O F T H E CABLE TESTING STANDARDS: O V E R V I E W O F T H E IEEE 400 BUNDLE
40

CABLE TESTING STANDARDS · IEEE 400.2 - 2013 IEEE Guide for Field Testing of Shielded Power Cable Systems Using Very Low Frequency (VLF) (Less Than 1 Hz) VLF Test . 35 • Background

Aug 23, 2021

Download

Documents

dariahiddleston
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: CABLE TESTING STANDARDS · IEEE 400.2 - 2013 IEEE Guide for Field Testing of Shielded Power Cable Systems Using Very Low Frequency (VLF) (Less Than 1 Hz) VLF Test . 35 • Background

1

CABLE TESTING STANDARDS: O V E R V I E W O F T H E

CABLE TESTING STANDARDS: O V E R V I E W O F T H E IEEE 400™ BUNDLE

Page 2: CABLE TESTING STANDARDS · IEEE 400.2 - 2013 IEEE Guide for Field Testing of Shielded Power Cable Systems Using Very Low Frequency (VLF) (Less Than 1 Hz) VLF Test . 35 • Background

2

Moderator n  Ron Spataro

AVO Training Institute Marketing Manager

Page 3: CABLE TESTING STANDARDS · IEEE 400.2 - 2013 IEEE Guide for Field Testing of Shielded Power Cable Systems Using Very Low Frequency (VLF) (Less Than 1 Hz) VLF Test . 35 • Background

3

Q&A n  Send us your

questions and comments during the presentation

Page 4: CABLE TESTING STANDARDS · IEEE 400.2 - 2013 IEEE Guide for Field Testing of Shielded Power Cable Systems Using Very Low Frequency (VLF) (Less Than 1 Hz) VLF Test . 35 • Background

4

Today’s Presenter: Alan Mark Franks AVO Training Institute, Senior Cable Instructor and Curriculum Advisor

CABLE TESTING STANDARDS: O V E R V I E W

IEEE 400™ BUNDLE

Page 5: CABLE TESTING STANDARDS · IEEE 400.2 - 2013 IEEE Guide for Field Testing of Shielded Power Cable Systems Using Very Low Frequency (VLF) (Less Than 1 Hz) VLF Test . 35 • Background

5

n  Institute of Electrical and Electronic Engineers •  IEEE-world’s largest technical professional organization

•  U. S. and global standards

•  Hundreds of standards including cable testing standards

•  Need for cable testing has existed the 1800’s

•  Guided IEEE 400 Series (Bundle) Standards

IEEE Cable Testing Standards

Page 6: CABLE TESTING STANDARDS · IEEE 400.2 - 2013 IEEE Guide for Field Testing of Shielded Power Cable Systems Using Very Low Frequency (VLF) (Less Than 1 Hz) VLF Test . 35 • Background

6

n  Cable Outage Research U.S. •  Studies National Electric Energy Testing Research and

Applications Center ( NEETRAC) •  Georgia Institute of Technology •  Indicate significant concern for U.S. cable installations •  Service-aged and new cable installations subject to same

workmanship issues •  50% U.S. cable outages due to poor workmanship

Need for Cable Testing Standards

Page 7: CABLE TESTING STANDARDS · IEEE 400.2 - 2013 IEEE Guide for Field Testing of Shielded Power Cable Systems Using Very Low Frequency (VLF) (Less Than 1 Hz) VLF Test . 35 • Background

7

U.S. Cable Failures

Outages by equipment type

n  Causes of Cable Failure –  Inadequate cable prep –  Poor assembly techniques –  Not following instructions –  Lack of training and experience –  Inadequate cable installation –  Environment not controlled

Page 8: CABLE TESTING STANDARDS · IEEE 400.2 - 2013 IEEE Guide for Field Testing of Shielded Power Cable Systems Using Very Low Frequency (VLF) (Less Than 1 Hz) VLF Test . 35 • Background

8

•  Outages and repairs are costly •  Negative effects on system reliability •  Need for proactive maintenance •  Find “bad actors” prior to failure •  Best return on cable investment •  Test after repairs •  Test new installations

Why Test?

Page 9: CABLE TESTING STANDARDS · IEEE 400.2 - 2013 IEEE Guide for Field Testing of Shielded Power Cable Systems Using Very Low Frequency (VLF) (Less Than 1 Hz) VLF Test . 35 • Background

9

•  Identify status of existing cables •  Prove new cable installations •  Identify installation quality issues •  Baselines for future cable testing •  Basis for Condition Based Maintenance •  Solutions for complex cable problems

Where Do You Start

Page 10: CABLE TESTING STANDARDS · IEEE 400.2 - 2013 IEEE Guide for Field Testing of Shielded Power Cable Systems Using Very Low Frequency (VLF) (Less Than 1 Hz) VLF Test . 35 • Background

10

•  Five major standards •  Guidelines for testing old and new cables •  Current tests being utilized industry •  “Living documents” •  Provides methods, parameters, some evaluation criteria •  Through examination specific to organizations needs

IEEE 400 Series ( Bundle)

Page 11: CABLE TESTING STANDARDS · IEEE 400.2 - 2013 IEEE Guide for Field Testing of Shielded Power Cable Systems Using Very Low Frequency (VLF) (Less Than 1 Hz) VLF Test . 35 • Background

11

§  IEEE 400 - 2012 (Omnibus) •  IEEE Guide for Field Testing and Evaluation of the Insulation of Shielded Power Cable

Systems Rated 5 kV and Above.

§  IEEE400.1 - 2007 •  IEEE Guide for Field Testing of Laminated Dielectric, Shielded Power Cable Systems

Rated 5 kV and Above with High Direct Current Voltage.

§  IEEE 400.2 - 2013 •  IEEE Guide for Field Testing of Shielded Power Cable Systems Using Very Low

Frequency (VLF) (Less Than 1 Hz).

§  IEEE 400.3 - 2006 •  IEEE Guide for PARTIAL Discharge Testing of Shielded Power Cable Systems in a Field

Environment.

§  IEEE 400.4 - 2015 •  IEEE Guide for Field Testing of Shielded Power Cable Systems Rated 5 kV and Above

with Damped Alternating Current (DAC) Voltage.

IEEE 400 Series ( Bundle)

Page 12: CABLE TESTING STANDARDS · IEEE 400.2 - 2013 IEEE Guide for Field Testing of Shielded Power Cable Systems Using Very Low Frequency (VLF) (Less Than 1 Hz) VLF Test . 35 • Background

12

•  Evolved with cable and testing technology •  Field Tests identified major categories

–  Installation –  Acceptance –  Maintenance

•  Further divided depending on user needs –  Withstand –  Diagnostic

IEEE Cable Testing Standards

Page 13: CABLE TESTING STANDARDS · IEEE 400.2 - 2013 IEEE Guide for Field Testing of Shielded Power Cable Systems Using Very Low Frequency (VLF) (Less Than 1 Hz) VLF Test . 35 • Background

13

•  The “omnibus” guide revised from 2001 •  Overview of available test methods •  Description of test sources with discussion of tests •  Does not address test results or parameters •  Refers to “point” documents as definitive reference

IEEE 400 - 2012 (Omnibus) IEEE Guide for Field Testing and Evaluation of the Insulation of Shielded Power Cable Systems Rated 5 kV and Above.

Page 14: CABLE TESTING STANDARDS · IEEE 400.2 - 2013 IEEE Guide for Field Testing of Shielded Power Cable Systems Using Very Low Frequency (VLF) (Less Than 1 Hz) VLF Test . 35 • Background

14

•  Includes safety awareness •  General discussions for field testing of cables •  Field testing methods •  Applicability testing methods & advantages/disadvantages

IEEE 400 – 2012 (Omnibus) IEEE Guide for Field Testing and Evaluation of the Insulation of Shielded Power Cable Systems Rated 5 kV and Above.

Page 15: CABLE TESTING STANDARDS · IEEE 400.2 - 2013 IEEE Guide for Field Testing of Shielded Power Cable Systems Using Very Low Frequency (VLF) (Less Than 1 Hz) VLF Test . 35 • Background

15

•  Safety Awareness –  Regulations and standards observed –  Same factors as energized work –  Unique issues to testing present –  Work area protection and guarding –  Voltage verification required –  Grounding equipment required –  Voltage clearances maintained

IEEE 400 – 2012 (Omnibus) IEEE Guide for Field Testing and Evaluation of the Insulation of Shielded Power Cable Systems Rated 5 kV and Above.

Page 16: CABLE TESTING STANDARDS · IEEE 400.2 - 2013 IEEE Guide for Field Testing of Shielded Power Cable Systems Using Very Low Frequency (VLF) (Less Than 1 Hz) VLF Test . 35 • Background

16

•  Protective grounding •  Rated and tested •  PPE required

•  Work area protection/guarding •  Minimum Approach Distances •  Insulation required

IEEE 400 – 2012 (Omnibus) IEEE Guide for Field Testing and Evaluation of the Insulation of Shielded Power Cable Systems Rated 5 kV and Above.

15-0144

Grounding

M.A.D.

Page 17: CABLE TESTING STANDARDS · IEEE 400.2 - 2013 IEEE Guide for Field Testing of Shielded Power Cable Systems Using Very Low Frequency (VLF) (Less Than 1 Hz) VLF Test . 35 • Background

17

General discussions for field testing of cables –  Testing objectives. –  Cable systems to be tested. –  Operating conditions of cable and system components –  Suitable field tests. –  Documentation for analysis. –  Corrective actions on cable system.

IEEE 400 - 2012 (Omnibus) IEEE Guide for Field Testing and Evaluation of the Insulation of Shielded Power Cable Systems Rated 5 kV and Above.

Page 18: CABLE TESTING STANDARDS · IEEE 400.2 - 2013 IEEE Guide for Field Testing of Shielded Power Cable Systems Using Very Low Frequency (VLF) (Less Than 1 Hz) VLF Test . 35 • Background

18

Field Testing Methods (5) 1.  Voltage Withstand 2.  Dielectric Response

–  Dissipation Factor (tan delta) –  Leakage current –  Recovery Voltage –  Polarization/Depolarization current –  Dielectric spectroscopy

IEEE 400 – 2012 (Omnibus) IEEE Guide for Field Testing and Evaluation of the Insulation of Shielded Power Cable Systems Rated 5 kV and Above.

Page 19: CABLE TESTING STANDARDS · IEEE 400.2 - 2013 IEEE Guide for Field Testing of Shielded Power Cable Systems Using Very Low Frequency (VLF) (Less Than 1 Hz) VLF Test . 35 • Background

19

Field Testing Methods (continued) 3.  Partial discharge

–  Electrical measurement –  Acoustical measurement

4.  Time-domain reflectometry (TDR) 5.  Thermal infrared imaging

IEEE 400 – 2012 (Omnibus) IEEE Guide for Field Testing and Evaluation of the Insulation of Shielded Power Cable Systems Rated 5 kV and Above.

Page 20: CABLE TESTING STANDARDS · IEEE 400.2 - 2013 IEEE Guide for Field Testing of Shielded Power Cable Systems Using Very Low Frequency (VLF) (Less Than 1 Hz) VLF Test . 35 • Background

20

Field Testing Methods 1. Voltage Withstand

•  Simple (non-monitored ) withstand –  Ability to hold voltage is recorded –  Go/no-go test

•  Monitored Withstand –  Other attributes monitored during test –  Dielectric response or PD –  Temporal stability

Very Low Frequency (VLF) Withstand Test

IEEE 400 – 2012 (Omnibus) IEEE Guide for Field Testing and Evaluation of the Insulation of Shielded Power Cable Systems Rated 5 kV and Above.

Page 21: CABLE TESTING STANDARDS · IEEE 400.2 - 2013 IEEE Guide for Field Testing of Shielded Power Cable Systems Using Very Low Frequency (VLF) (Less Than 1 Hz) VLF Test . 35 • Background

21

Field Testing Methods 2.  Dielectric Response (5 tests)

I.  Dissipation factor (tan delta) II.  DC Leakage Current III.  Recovery Voltage IV.  Polarization/Depolarization Current V.  Spectroscopy

IEEE 400 – 2012 (Omnibus) IEEE Guide for Field Testing and Evaluation of the Insulation of Shielded Power Cable Systems Rated 5 kV and Above.

Page 22: CABLE TESTING STANDARDS · IEEE 400.2 - 2013 IEEE Guide for Field Testing of Shielded Power Cable Systems Using Very Low Frequency (VLF) (Less Than 1 Hz) VLF Test . 35 • Background

22

Dielectric Response (Continued) –  Provides overall insulation diagnosis –  Can be made at different frequencies or in different time domain –  Analyze effects but not locate defects –  Commonly measured termination to termination –  Values primarily influenced by condition, age etc. –  Results can be compared & used for trending

IEEE 400 - 2012 (Omnibus) IEEE Guide for Field Testing and Evaluation of the Insulation of Shielded Power Cable Systems Rated 5 kV and Above.

Page 23: CABLE TESTING STANDARDS · IEEE 400.2 - 2013 IEEE Guide for Field Testing of Shielded Power Cable Systems Using Very Low Frequency (VLF) (Less Than 1 Hz) VLF Test . 35 • Background

23

Dielectric Response (Continued) I.  Dissipation factor (Tan Delta)

–  Loss factor increases as cable ages –  Tan delta measurement used as a diagnostic –  Ratio between loss current and charging current –  Loss current increases as cable ages increasing tan delta angle –  Absolute tan delta, tip-up and stability values are derived

IEEE 400 - 2012 (Omnibus) IEEE Guide for Field Testing and Evaluation of the Insulation of Shielded Power Cable Systems Rated 5 kV and Above.

Page 24: CABLE TESTING STANDARDS · IEEE 400.2 - 2013 IEEE Guide for Field Testing of Shielded Power Cable Systems Using Very Low Frequency (VLF) (Less Than 1 Hz) VLF Test . 35 • Background

24

Dielectric Response (Continued) II.  DC leakage current

–  DC voltage lower than withstand applied –  Measures current flowing through insulation –  HVDC not recommended for aged extruded

cables –  Measurements taken at steady state

voltage –  Performed as a step test –  Cables discharged 4 times test duration

after test

IEEE 400 – 2012 (Omnibus) IEEE Guide for Field Testing and Evaluation of the Insulation of Shielded Power Cable Systems Rated 5 kV and Above.

Page 25: CABLE TESTING STANDARDS · IEEE 400.2 - 2013 IEEE Guide for Field Testing of Shielded Power Cable Systems Using Very Low Frequency (VLF) (Less Than 1 Hz) VLF Test . 35 • Background

25

IEEE 400 – 2012 (Omnibus) IEEE Guide for Field Testing and Evaluation of the Insulation of Shielded Power Cable Systems Rated 5 kV and Above.

Dielectric Response (Continued) III.  Voltage recovery

–  Charged with DC voltage for given time –  Discharged with ground resistor –  Open circuit voltage recorded versus time –  Can indicate moisture in PILC cables –  Uses to indicate water tree degradation

Page 26: CABLE TESTING STANDARDS · IEEE 400.2 - 2013 IEEE Guide for Field Testing of Shielded Power Cable Systems Using Very Low Frequency (VLF) (Less Than 1 Hz) VLF Test . 35 • Background

26

IEEE 400 – 2012 (Omnibus) IEEE Guide for Field Testing and Evaluation of the Insulation of Shielded Power Cable Systems Rated 5 kV and Above.

Charging Current Polarize/De-polarize

Dielectric Response (Continued) IV.  Polarization/depolarization

–  Uses polarizing and depolarizing current per time –  Also used to calculate Polarization Index (PI) –  Can compare new and aged insulation

Page 27: CABLE TESTING STANDARDS · IEEE 400.2 - 2013 IEEE Guide for Field Testing of Shielded Power Cable Systems Using Very Low Frequency (VLF) (Less Than 1 Hz) VLF Test . 35 • Background

27

Dielectric Response (Continued) V.  Dielectric spectroscopy

–  Displacement and loss currents measured at a range of frequencies –  Can calculate tan delta –  Can be used in time domain for tan delta vs, frequency

IEEE 400 – 2012 (Omnibus) IEEE Guide for Field Testing and Evaluation of the Insulation of Shielded Power Cable Systems Rated 5 kV and Above.

Page 28: CABLE TESTING STANDARDS · IEEE 400.2 - 2013 IEEE Guide for Field Testing of Shielded Power Cable Systems Using Very Low Frequency (VLF) (Less Than 1 Hz) VLF Test . 35 • Background

28

Field Testing Methods 3.  Partial Discharge-Electrical Measurement

–  Locate potential weak spots –  Partial discharges are initiated –  Conducted at Uo or higher voltages –  Determine voltage level PD inception and PD extension –  Above Uo used to verify no PD at acceptance test level. –  Accurate interpretation requires strong understanding of PD behavior

IEEE 400 – 2012 (Omnibus) IEEE Guide for Field Testing and Evaluation of the Insulation of Shielded Power Cable Systems Rated 5 kV and Above.

Page 29: CABLE TESTING STANDARDS · IEEE 400.2 - 2013 IEEE Guide for Field Testing of Shielded Power Cable Systems Using Very Low Frequency (VLF) (Less Than 1 Hz) VLF Test . 35 • Background

29

IEEE 400 – 2012 (Omnibus) IEEE Guide for Field Testing and Evaluation of the Insulation of Shielded Power Cable Systems Rated 5 kV and Above.

Partial Discharge Test

Inception/ extension Voltage

PD Event

PD Event Location

Page 30: CABLE TESTING STANDARDS · IEEE 400.2 - 2013 IEEE Guide for Field Testing of Shielded Power Cable Systems Using Very Low Frequency (VLF) (Less Than 1 Hz) VLF Test . 35 • Background

30

Field Testing Methods 3.  Partial Discharge-Acoustic Measurement

–  PD site acts like acoustic wave source –  Can be externally detected –  Sensor normally has to make contact

IEEE 400 – 2012 (Omnibus) IEEE Guide for Field Testing and Evaluation of the Insulation of Shielded Power Cable Systems Rated 5 kV and Above.

PD Acoustic Measurement

Page 31: CABLE TESTING STANDARDS · IEEE 400.2 - 2013 IEEE Guide for Field Testing of Shielded Power Cable Systems Using Very Low Frequency (VLF) (Less Than 1 Hz) VLF Test . 35 • Background

31

Field Testing Methods 4.  Time Domain Reflectometry

–  Does not measure dielectric properties –  Used to characterize changes in impedance –  Locates discontinuities –  Shape of reflected pulse assists in identification

IEEE 400 – 2012 (Omnibus) IEEE Guide for Field Testing and Evaluation of the Insulation of Shielded Power Cable Systems Rated 5 kV and Above.

TDR Measurement

Page 32: CABLE TESTING STANDARDS · IEEE 400.2 - 2013 IEEE Guide for Field Testing of Shielded Power Cable Systems Using Very Low Frequency (VLF) (Less Than 1 Hz) VLF Test . 35 • Background

32

Field Testing Methods 5.  Thermal Infrared Imaging

–  Measure surface temperatures of accessories –  Detects connector high resistivity –  Unusual heating of an accessory

IEEE 400 – 2012 (Omnibus) IEEE Guide for Field Testing and Evaluation of the Insulation of Shielded Power Cable Systems Rated 5 kV and Above.

Thermal Scans

Page 33: CABLE TESTING STANDARDS · IEEE 400.2 - 2013 IEEE Guide for Field Testing of Shielded Power Cable Systems Using Very Low Frequency (VLF) (Less Than 1 Hz) VLF Test . 35 • Background

33

•  Point standard for testing laminated insulated cables with HVDC

•  Includes testing procedures •  Provides guidelines for test voltages •  Methods of evaluation

– Current-time relationship – Resistance values

•  Not recommend for service aged solid dielectric cables

IEEE400.1 - 2007 IEEE Guide for Field Testing of Laminated Dielectric, Shielded Power Cable Systems Rated 5 kV and Above with High Direct Current Voltage

DC Test

Page 34: CABLE TESTING STANDARDS · IEEE 400.2 - 2013 IEEE Guide for Field Testing of Shielded Power Cable Systems Using Very Low Frequency (VLF) (Less Than 1 Hz) VLF Test . 35 • Background

34

•  Point standard for VLF withstand tests •  Presents rational for VLF versus DC •  Test parameters for tan delta •  Test values in appendix

IEEE 400.2 - 2013 IEEE Guide for Field Testing of Shielded Power Cable Systems Using Very Low Frequency (VLF) (Less Than 1 Hz)

VLF Test

Page 35: CABLE TESTING STANDARDS · IEEE 400.2 - 2013 IEEE Guide for Field Testing of Shielded Power Cable Systems Using Very Low Frequency (VLF) (Less Than 1 Hz) VLF Test . 35 • Background

35

•  Background information on partial discharge detection and location •  Interpretive guidance provided •  Technology has improved sensitivity of measurements •  Very good and very bad cables identified •  Remaining life cannot be predicted with great accuracy

IEEE 400.3 - 2006 IEEE Guide for Partial Discharge Testing of Shielded Power Cable Systems in a Field Environment

Partial Discharge

Page 36: CABLE TESTING STANDARDS · IEEE 400.2 - 2013 IEEE Guide for Field Testing of Shielded Power Cable Systems Using Very Low Frequency (VLF) (Less Than 1 Hz) VLF Test . 35 • Background

36

•  Provides for use of damped alternating current voltages for field testing

•  Guidelines for evaluation of test results •  DAC applications advanced diagnostic testing •  Most common use partial discharge and dissipation factor

IEEE 400.4 - 2015 IEEE Guide for Field Testing of Shielded Power Cable Systems Rated 5 kV and Above with Damped Alternating Current (DAC) Voltage.

Simulated DAC Wave

Page 37: CABLE TESTING STANDARDS · IEEE 400.2 - 2013 IEEE Guide for Field Testing of Shielded Power Cable Systems Using Very Low Frequency (VLF) (Less Than 1 Hz) VLF Test . 35 • Background

37

ü Cable outages & repairs are costly ü 50% of U.S. cable outages due to poor workmanship ü Need for testing new and service-aged cable systems ü The “omnibus” IEEE 400TM 2012 standard provides guidelines ü Specific testing requirements in the “point” standards ü End user history and specific test data is key

Summary

Page 38: CABLE TESTING STANDARDS · IEEE 400.2 - 2013 IEEE Guide for Field Testing of Shielded Power Cable Systems Using Very Low Frequency (VLF) (Less Than 1 Hz) VLF Test . 35 • Background

38

Join Us For Our Next Webinar

n  AVO Electrical Cable Webinar Series Part 2: Mark Franks

n  Tuesday, June 13, 2017 at 1 PM CST

Register here: https://attendee.gotowebinar.com/register/3740472969103358979

“The Trillion Dollar Problem – Power Cable Outages And The Training Connection”

Page 39: CABLE TESTING STANDARDS · IEEE 400.2 - 2013 IEEE Guide for Field Testing of Shielded Power Cable Systems Using Very Low Frequency (VLF) (Less Than 1 Hz) VLF Test . 35 • Background

39

Electrical Cable Training

n  AVO Cable U was designed as a technologically advanced “real world” place for every electrical cable installation, testing and diagnostic application.

n  Medium-Voltage Cable Technician Certification: •  Cable Splicing & Terminating, Medium-Voltage, •  Cable Fault Location & Tracing, Medium-Voltage

§  Medium-Voltage Cable Diagnostics & Testing: •  Certification Cable Testing & Diagnostics, Medium-Voltage

Page 40: CABLE TESTING STANDARDS · IEEE 400.2 - 2013 IEEE Guide for Field Testing of Shielded Power Cable Systems Using Very Low Frequency (VLF) (Less Than 1 Hz) VLF Test . 35 • Background

40

Questions? After more than 50 years, AVO Training remains a global leader in safety and maintenance training for the electrical industry. We deliver an engaging, hands-on experience for our clients in a professional, real-world environment. We strive to provide industry relevant courses in a practical and flexible learning environment through an ongoing commitment to quality service, integrity, instruction, and client satisfaction. Our goal is to convey practical job skills and career development for our clients and students by saving lives through a world-class learning experience.