> Three conductor cable with stranded copper conductors, extruded insulation system consisting of a thermosetting semiconducting conductor screen, high dielectric strength EPR insulation, thermosetting semiconducting insulation screen, helically applied bare copper tape screen, cabled with fillers and ground conductors, overall binder tape, foamed polymeric layer for superior mechanical protection, longitudinally applied aluminium tape, extruded oil and hydrocarbon resistant polymeric layer, and overall sun resistant PVC jacket. > Conductors Plain annealed stranded copper wires according to IEC 60228, Class 2 > Conductor Screen Extruded semi conducting layer > Insulation EPR (Ethylene Propylene Rubber) insulation in accordance with IEC 60092-351 > Insulation Screen Extruded semi conducting layer > Metallic Screen Uncoated copper tape helically applied with a nominal 15% overlap > Earth conductors Plain annealed stranded copper wires according to IEC 60228, Class 2 > Assembly The cable interstices are filled with either an extruded halogen free non hydroscopic polymeric bedding or non hydroscopic filler yarns > Armour System An layer is extruded around the cable assembly. On top of this is a longitudinally applied aluminium tape with a nominal 10% overlap combined with an extruded oil and hydrocarbon resistant polymeric layer > Sheath A low temperature, flame retardant, moisture and sunlight resistant PVC jacket, ST2 quality. Standard colour red, other colours available on request. An optional LSOH outer jacket compound ST8 quality is also available Cable construction IEC 60332-3C VERY GOOD VERY GOOD -40 °C +90 °C GOOD r R=10D OFFSHORE & INDUSTRIAL THE RIGHT CHOICE AIR BAG TM 20 kV 3 Core Copper Conductors 90 °C rated, 3 Earth Conductors AIRGUARD TM CABLE SYSTEM Description
18
Embed
CABLE SYSTEM & INDUSTRIAL 3 Earth Conductors · 2009-02-11 · >Three conductor cable with stranded copper conductors, extruded insulation system consisting of a thermosetting semiconducting
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
> Three conductor cable with stranded copper conductors,extruded insulation system consisting of a thermosettingsemiconducting conductor screen, high dielectricstrength EPR insulation, thermosetting semiconductinginsulation screen, helically applied bare copper tapescreen, cabled with fillers and ground conductors, overallbinder tape, foamed polymeric layer for superiormechanical protection, longitudinally applied aluminiumtape, extruded oil and hydrocarbon resistant polymericlayer, and overall sun resistant PVC jacket.
> ConductorsPlain annealed stranded copper wires according toIEC 60228, Class 2
> Conductor ScreenExtruded semi conducting layer
> InsulationEPR (Ethylene Propylene Rubber) insulation in accordancewith IEC 60092-351
> Insulation ScreenExtruded semi conducting layer
> Metallic ScreenUncoated copper tape helically applied with a nominal15% overlap
> Earth conductorsPlain annealed stranded copper wires according toIEC 60228, Class 2
> AssemblyThe cable interstices are filled with either an extrudedhalogen free non hydroscopic polymeric bedding or nonhydroscopic filler yarns
> Armour SystemAn layer is extruded around the cable assembly.On top of this is a longitudinally applied aluminium tapewith a nominal 10% overlap combined with an extrudedoil and hydrocarbon resistant polymeric layer
> SheathA low temperature, flame retardant, moisture andsunlight resistant PVC jacket, ST2 quality. Standardcolour red, other colours available on request. Anoptional LSOH outer jacket compound ST8 quality isalso available
Prysmian reserves the right to modify at any time the technical, dimensional and weight characteristics shown in this catalogue with in accordance the mentionedstandards in case it improves the features of its products. There is no responsibility of the manufacturer for any damages to persons and properties in caseof improper use and/or neglecting the recommendations for using cables and norms contained in this catalogue, relevant to installation and operation in shipand offshore applications.
APPLICATIONS• Directly buried or embedded in concrete• Offshore applications • Suitable for variable frequency drive applications• Suitable for vertical installation• Economical alternative to traditional conduit systems• Suitable for harsh chemical and industrial environments • For direct burial, use in cable tray, indoor and outdoor
applications
> Three conductor cable with stranded copper conductors,extruded insulation system consisting of a thermosettingsemiconducting conductor shield, high dielectricstrength EPROTENAX™ EPR insulation, thermosettingsemiconducting insulation shield, helically applied barecopper tape shield, cabled with fillers and groundingconductors, overall binder tape, foamed polymeric layerfor superior mechanical protection, longitudinally appliedaluminium tape, extruded oil and hydrocarbon resistantpolymeric layer, and overall sun resistant PVC jacket.
> ConductorsClass B Compact concentric strand soft drawn annealedcopper as per ASTM requirements
> Conductor ShieldExtruded thermosetting semiconducting shield which is freestripping from the conductor and bonded to the insulation
> InsulationNatural high dielectric strength EPROTENAX™ EPR-basedinsulation, combined with other materials and agents thatenhance the electrical and mechanical characteristicsassuring extended cable life
> Insulation ShieldExtruded thermoset semi-conducting stress control layer, free stripping from the EPR insulation.Meets ICEA S-93-639/NEMA WC74 and UL1072
> Metallic ShieldHelically applied non-magnetic copper tape(s) over the insulationshield with a minimum overlap of 15%. A Mylar ribbon islongitudinally applied under the copper tape shield for phaseidentification - 1C w/ Red, 1C w/ Blue, and 1C w/ Black
> Ground ConductorsBare stranded copper conductor, one in each interstice, as perUL, ICEA, and ASTM requirements
> AssemblyBare stranded copper conductor, one in each interstice,as per UL, ICEA, and ASTM requirements
> Mechanical ProtectionHigh strength and high crush resistant layerextruded over the core assembly
> Chemical ProtectionA longitudinal aluminium tape with a nominal 10% overlapoverwhich a chemical resistant extruded polymer layer is applied
> JacketA low temperature, flame retardant moisture and sunlightresistant PVC jacket. UL listed as type MV-105. An optional LSOH outer jacket is available on request
APPLICABLE STANDARDS AND APPROVALS• UL listed Type MV-105 “For CT Use” in accordance with UL 1072• CSA FT4 Flame Test, IEEE 383 Flame Test, and IEEE 1202
Flame Test• ICEA T-29-520 at 210,000 BTU/hr• CSA 22.2 cold impact test (-40°C) and cold bend test (-40°C)• ABS approved for offshore applications• BV witness of accessories testing to IEEE 48 & 404• US Coast Guard Approved• Oil Resistant I & II
PRODUCT FEATURES• Cable is rated 105 °C as defined in UL1072• Chemical and oil resistant to a wide range of fluids• Suitable for direct burial as defined in NEC section 310-7
and 300-50• Lighter, smaller and more flexible than equivalent rated
Continuous Corrugated Welded Aluminium cable• Improved impact performance compared with the Continuous
Corrugated Welded Aluminium cable• Compatible with standard jointing technology
Prysmian reserves the right to modify at any time the technical, dimensional and weight characteristics shown in this catalogue with in accordance the mentionedstandards in case it improves the features of its products. There is no responsibility of the manufacturer for any damages to persons and properties in caseof improper use and/or neglecting the recommendations for using cables and norms contained in this catalogue, relevant to installation and operation in shipand offshore applications.
Ampacities are based on the followingDuct: Cable in underground electrical ducts; one cable per duct; based on an ambient temperature of 20°C; per NEC Table 310.79Air: Cable isolated in air and an ambient temperature of 40°C; per NEC Table 310.71
quantity
APPLICATIONS• Installations in both exposed and concealed locations in
accordance with NEC• Wet and dry locations in accordance with NEC • Directly buried or embedded in concrete• Installations on cable trays, troughs, metal racks, aerial
installations and continuous rigid cable supports inaccordance with NEC
• Economical alternative to traditional conduit systems• Suitable for variable frequency drive applications (VFD)• Suitable for vertical risers
size
conductor diameter
(in) (mm)
insulation thickness
(mils) (mm)
insulation diameter
(in) (mm)
insulation shield
diameter
(in) (mm)
approx jacket
diameter
(in) (mm)
approx cable
weight
(lbs/kft) (kg/km)
ampacity(amps)
105°C in duct
105°C in air
> Three conductor cable with stranded copper conductors,extruded insulation system consisting of a thermosettingsemiconducting conductor screen, high dielectric strengthEPR insulation, thermosetting semiconducting insulationscreen, helically applied bare copper tape screen, cabledwith fillers and ground conductors, overall binder tape,foamed polymeric layer for superior mechanical protection,longitudinally applied aluminium tape, extruded oil andhydrocarbon resistant polymeric layer, and overall sunresistant PVC jacket.
> ConductorsPlain annealed stranded copper wires according toIEC 60228, Class 2
> Conductor ScreenExtruded semi conducting layer
> InsulationEPR (Ethylene Propylene Rubber) insulation inaccordance with IEC 60092-351
> Insulation ScreenExtruded semi conducting layer
> Metallic ScreenUncoated copper tape helically applied with a nominal15% overlap
> Earth ConductorsPlain annealed stranded copper wires according toIEC 60228, Class 2
> AssemblyThe cable interstices are filled with either an extrudedhalogen free non hydroscopic polymeric bedding or nonhydroscopic filler yarns.
> Armour SystemAn layer is extruded around the cable assembly.On top of this is a longitudinally applied aluminium tapewith a nominal 10% overlap combined with an extrudedoil and hydrocarbon resistant polymeric layer
> SheathA low temperature, flame retardant, moisture andsunlight resistant PVC jacket, ST2 quality.Standard colour red, other colours available onrequest. An optional LSOH outer jacket compoundST8 quality is also available
APPLICATIONS• Directly buried or embedded in concrete• Offshore applications • Suitable for variable frequency drive applications• Suitable for vertical installation• Economical alternative to traditional conduit systems• Suitable for harsh chemical and industrial environments• For direct burial, use in cable tray, indoor and outdoor
applications
Prysmian reserves the right to modify at any time the technical, dimensional and weight characteristics shown in this catalogue with in accordance the mentionedstandards in case it improves the features of its products. There is no responsibility of the manufacturer for any damages to persons and properties in caseof improper use and/or neglecting the recommendations for using cables and norms contained in this catalogue, relevant to installation and operation in shipand offshore applications.
> Three conductor cable with stranded copper conductors,extruded insulation system consisting of a thermosettingsemiconducting conductor screen, high dielectric strengthEPR insulation, thermosetting semiconducting insulationscreen, helically applied bare copper tape screen, cabledwith fillers and ground conductors, overall binder tape,foamed polymeric layer for superior mechanical protection,longitudinally applied aluminium tape, extruded oil andhydrocarbon resistant polymeric layer, and overall sunresistant PVC jacket.
> ConductorsPlain annealed stranded copper wires according toIEC 60228, Class 2
> Conductor ScreenExtruded semi conducting layer
> InsulationEPR (Ethylene Propylene Rubber) insulation inaccordance with IEC 60092-351
> Insulation ScreenExtruded semi conducting layer
> Metallic ScreenUncoated copper tape helically applied with a nominal15% overlap
> Earth ConductorsPlain annealed stranded copper wires according toIEC 60228, Class 2
> AssemblyThe cable interstices are filled with either an extrudedhalogen free non hydroscopic polymeric bedding or nonhydroscopic filler yarns
> Armour SystemAn layer is extruded around the cable assembly.On top of this is a longitudinally applied aluminium tapewith a nominal 10% overlap combined with an extrudedoil and hydrocarbon resistant polymeric layer
> SheathA low temperature, flame retardant, moisture andsunlight resistant PVC jacket, ST2 quality.Standard colour red, other colours available onrequest. An optional LSOH outer jacket compoundST8 quality is also available
APPLICATIONS• Directly buried or embedded in concrete• Offshore applications • Suitable for variable frequency drive applications• Suitable for vertical installation• Economical alternative to traditional conduit systems• Suitable for harsh chemical environments • For direct burial, use in cable tray, indoor and
outdoor applications
Prysmian reserves the right to modify at any time the technical, dimensional and weight characteristics shown in this catalogue with in accordance the mentionedstandards in case it improves the features of its products. There is no responsibility of the manufacturer for any damages to persons and properties in caseof improper use and/or neglecting the recommendations for using cables and norms contained in this catalogue, relevant to installation and operation in shipand offshore applications.
> Three conductor cable with stranded copper conductors,extruded insulation system consisting of a thermosettingsemiconducting conductor screen, high dielectric strengthEPR insulation, thermosetting semiconducting insulationscreen, helically applied bare copper tape screen, cabledwith fillers and ground conductors, overall binder tape,foamed polymeric layer for superior mechanical protection,longitudinally applied aluminium tape, extruded oil andhydrocarbon resistant polymeric layer, and overall sunresistant PVC jacket.
> ConductorsPlain annealed stranded copper wires according toIEC 60228, Class 2
> Conductor ScreenExtruded semi conducting layer
> InsulationEPR (Ethylene Propylene Rubber) insulation inaccordance with IEC 60092-351
> Insulation ScreenExtruded semi conducting layer
> Metallic ScreenUncoated copper tape helically applied with a nominal 15% overlap
> Earth ConductorsPlain annealed stranded copper wires according toIEC 60228, Class 2
> AssemblyThe cable interstices are filled with either an extrudedhalogen free non hydroscopic polymeric bedding or nonhydroscopic filler yarns
> Armour SystemAn layer is extruded around the cable assembly.On top of this is a longitudinally applied aluminium tapewith a nominal 10% overlap combined with an extrudedoil and hydrocarbon resistant polymeric layer
> SheathA low temperature, flame retardant, moisture andsunlight resistant PVC jacket, ST2 quality.Standard colour red, other colours available onrequest. An optional LSOH outer jacket compoundST8 quality is also available
Prysmian reserves the right to modify at any time the technical, dimensional and weight characteristics shown in this catalogue with in accordance the mentionedstandards in case it improves the features of its products. There is no responsibility of the manufacturer for any damages to persons and properties in caseof improper use and/or neglecting the recommendations for using cables and norms contained in this catalogue, relevant to installation and operation in shipand offshore applications.
APPLICATIONS• Directly buried or embedded in concrete• Offshore applications • Suitable for variable frequency drive applications• Suitable for vertical installation• Economical alternative to traditional conduit systems• Suitable for harsh chemical and industrial environments • For direct burial, use in cable tray, indoor and outdoor
applications
> Three conductor cable with stranded copper conductors,extruded insulation system consisting of a thermosettingsemiconducting conductor shield, high dielectri strengthEPROTENAX™ EPR insulation, thermosetting semiconductinginsulation shield, helically applied bare copper tape shield,cabled with fillers and grounding conductors, overallbinder tape, foamed polymeric layer for superior mechanicalprotection, longitudinally applied aluminium tape, extrudedoil and hydrocarbon resistant polymeric layer, andoverall sun resistant PVC jacket.
> ConductorsClass B Compact concentric strand soft drawn annealedcopper as per ASTM requirements
> Strand ShieldExtruded thermosetting semiconducting shield which isfree stripping from the conductor and bonded to theinsulation
> InsulationNatural high dielectric strength EPROTENAX™ EPR-basedinsulation, combined with other materials and agents thatenhance the electrical and mechanical characteristicsassuring extended cable life
> Insulation ShieldExtruded thermosetting semiconducting shield withcontrolled adhesion to the insulation providing therequired balance between electrical integrity and easeof stripping
> Metallic ShieldHelically applied non-magnetic copper tape(s) over theinsulation shield with a minimum overlap of 15%. AMylar ribbon is longitudinally applied under the coppertape shield for phase identification - 1C w/ Red, 1C w/Blue, and 1C w/ Black
> Ground conductorsBare stranded copper conductor, one in each interstice,as per UL, ICEA, and ASTM requirements
> AssemblyPhase identified shielded conductors cabled with fillersand grounding conductors (as specified), forming a firmand cylindrical cable core. A binder tape is applied tomaintain core symmetry and mechanical stability
> Mechanical ProtectionHigh strength and high crush resistant layerextruded over the core assembly
> Chemical ProtectionA longitudinal aluminium tape with a nominal 10% overlapover which a chemical resistant extruded polymer layeris applied
> JacketA low temperature, flame retardant moisture and sunlightresistant PVC jacket. UL listed as type MV-105. Anoptional LSOH outer jacket is available on request
APPLICABLE STANDARDS AND APPROVALS• UL listed Type MV-105 “For CT Use” in accordance with
UL 1072• CSA FT4 Flame Test, IEEE 383 Flame Test, and IEEE 1202
Flame Test• ICEA T-29-520 at 210,000 BTU/hr• CSA 22.2 cold impact test (-40°C) and cold bend test (-40°C)• ABS approved for offshore applications• BV witness of accessories testing to IEEE 48 & 404• US Coast Guard Approved• Oil Resistant I & II
PRODUCT FEATURES• Cable is rated 105 °C as defined in UL1072• Chemical and oil resistant to a wide range of fluids• Suitable for direct burial as defined in NEC section 310-7
and 300-50• Lighter, smaller and more flexible than equivalent rated
Continuous Corrugated Welded Aluminium cable• Improved impact performance compared with the Continuous
Corrugated Welded Aluminium cable• Compatible with standard jointing technology
APPLICATIONS• Installations in both exposed and concealed locations in
accordance with NEC• Wet and dry locations in accordance with NEC• Directly buried or embedded in concrete• Installations on cable trays, troughs, metal racks, aerial
installations and continuous rigid cable supports in accordancewith NEC
• Economical alternative to traditional conduit systems• Suitable for variable frequency drive applications (VFD)• Suitable for vertical risers
Ampacities are based on the followingDuct: Cable in underground electrical ducts; one cable per duct; based on an ambient temperature of 20°C; per NEC Table 310.79Air: Cable isolated in air and an ambient temperature of 40°C; per NEC Table 310.71
quantity size
conductor diameter
(in) (mm)
insulation thickness
(mils) (mm)
insulation diameter
(in) (mm)
insulation shield
diameter
(in) (mm)
approx jacket
diameter
(in) (mm)
approx cable
weight
(lbs/kft) (kg/km)
ampacity(amps)
105°C in duct
105°C in air
Prysmian reserves the right to modify at any time the technical, dimensional and weight characteristics shown in this catalogue with in accordance the mentionedstandards in case it improves the features of its products. There is no responsibility of the manufacturer for any damages to persons and properties in caseof improper use and/or neglecting the recommendations for using cables and norms contained in this catalogue, relevant to installation and operation in shipand offshore applications.
> Three conductor cable with stranded copper conductors,extruded insulation system consisting of a thermosettingsemiconducting conductor shield, high dielectric strengthEPROTENAX™ EPR insulation, thermosetting semiconducting insulation shield, helically applied bare coppertape shield, cabled with fillers and grounding conductors,overall binder tape, foamed polymeric layer for superiormechanical protection, longitudinally applied aluminiumtape, extruded oil and hydrocarbon resistant polymericlayer, and overall sun resistant PVC jacket.
> ConductorsClass B Compact concentric strand soft drawn annealedcopper as per ASTM requirements
> Strand ShieldExtruded thermosetting semiconducting shield which is freestripping from the conductor and bonded to the insulation
> InsulationNatural high dielectric strength EPROTENAX™ EPR-basedinsulation, combined with other materials and agentsthat enhance the electrical and mechanical characteristicsassuring extended cable life
> Insulation ShieldExtruded thermosetting semiconducting shield with controlled adhesion to the insulation providing the requiredbalance between electrical integrity and ease of stripping
> Metallic ShieldHelically applied non-magnetic copper tape(s) over theinsulation shield with a minimum overlap of 15%. A Mylarribbon is longitudinally applied under the copper tape shield forphase identification - 1C w/ Red, 1C w/ Blue, and 1C w/ Black
> Ground ConductorsBare stranded copper conductor, one in each interstice,as per UL, ICEA, and ASTM requirements
> AssemblyPhase identified shielded conductors cabled with fillersand grounding conductors (as specified), forming a firmand cylindrical cable core. A binder tape is applied tomaintain core symmetry and mechanical stability
> Mechanical ProtectionHigh strength and high crush resistant layerextruded over the core assembly
> Chemical ProtectionA longitudinal aluminium tape with a nominal 10% overlapover which a chemical resistant extruded polymer layeris applied
> JacketA low temperature, flame retardant moisture and sunlightresistant PVC jacket. UL listed as type MV-105. Anoptional LSOH outer jacket is available on request
APPLICABLE STANDARDS AND APPROVALS• UL listed Type MV-105 “For CT Use” in accordance with
UL 1072• CSA FT4 Flame Test, IEEE 383 Flame Test, and IEEE 1202
Flame Test• ICEA T-29-520 at 210,000 BTU/hr• CSA 22.2 cold impact test (-40°C) and cold bend test (-40°C)• ABS approved for offshore applications• BV witness of accessories testing to IEEE 48 & 404• US Coast Guard Approved• Oil Resistant I & II
PRODUCT FEATURES• Cable is rated 105 °C as defined in UL1072• Chemical and oil resistant to a wide range of fluids• Suitable for direct burial as defined in NEC section 310-7
and 300-50• Lighter, smaller and more flexible than equivalent rated
Continuous Corrugated Welded Aluminium cable• Improved impact performance compared with the
Continuous Corrugated Welded Aluminium cable• Compatible with standard jointing technology
APPLICATIONS• Installations in both exposed and concealed locations in
accordance with NEC• Wet and dry locations in accordance with NEC• Directly buried or embedded in concrete• Installations on cable trays, troughs, metal racks, aerial
installations and continuous rigid cable supports inaccordance with NEC
• Economical alternative to traditional conduit systems• Suitable for variable frequency drive applications (VFD)• Suitable for vertical risers
21216 3 x 1 AWG CU 3 8 0,30 7,65 345 8,76 1,02 25,91 1,09 27,56 2,96 75 5260 7830 185 21021218 3 x 1/0 AWG CU 3 8 0,34 8,59 345 8,76 1,06 26,80 1,12 28,45 3,09 78 5810 8650 210 24021220 3 x 2/0 AWG CU 3 8 0,38 9,63 345 8,76 1,09 27,81 1,16 29,46 3,17 81 6310 9390 235 27521222 3 x 4/0 AWG CU 3 7 0,48 12,19 345 8,76 1,19 30,35 1,26 32,00 3,39 86 7660 11400 305 36021223 3 x 250 MCM CU 3 7 0,52 13,31 345 8,76 1,26 32,00 1,33 33,66 3,51 89 8370 12460 335 40021224 3 x 350 CM CU 3 6 0,62 15,80 345 8,76 1,36 34,42 1,42 36,07 3,72 94 9950 14810 400 49021225 3 x 500 MCM CU 3 5 0,74 18,85 345 8,76 1,48 37,47 1,54 39,12 3,98 101 12150 18080 485 60021226 3 x 750 MCM CU 3 4 0,91 23,19 345 8,76 1,66 42,16 1,75 44,45 4,33 110 15950 23740 585 74521227 3 x 1000 MCM CU 3 4 1,06 26,90 345 8,76 1,81 45,97 1,90 48,26 4,65 118 19330 28770 660 860
product number
conductor ground wiresAWG
Ampacities are based on the followingDuct: Cable in underground electrical ducts; one cable per duct; based on an ambient temperature of 20°C; per NEC Table 310.79Air: Cable isolated in air and an ambient temperature of 40°C; per NEC Table 310.71
quantity size
conductor diameter
(in) (mm)
insulation thickness
(mils) (mm)
insulation diameter
(in) (mm)
insulation shield
diameter
(in) (mm)
approx jacket
diameter
(in) (mm)
approx cable
weight
(lbs/kft) (kg/km)
ampacity(amps)
105°C in duct
105°C in air
Prysmian reserves the right to modify at any time the technical, dimensional and weight characteristics shown in this catalogue with in accordance the mentionedstandards in case it improves the features of its products. There is no responsibility of the manufacturer for any damages to persons and properties in caseof improper use and/or neglecting the recommendations for using cables and norms contained in this catalogue, relevant to installation and operation in shipand offshore applications.
> Three conductor cable with stranded copper conductors,extruded insulation system consisting of a thermosettingsemiconducting conductor shield, high dielectricstrength EPROTENAX™ EPR insulation, thermosettingsemiconducting insulation shield, helically applied barecopper tape shield, cabled with fillers and groundingconductors, overall binder tape, foamed polymeric layerfor superior mechanical protection, longitudinally appliedaluminium tape, extruded oil and hydrocarbon resistantpolymeric layer, and overall sun resistant PVC jacket.
> ConductorsClass B Compact concentric strand soft drawn annealedcopper as per ASTM requirements
> Strand ShieldExtruded thermosetting semiconducting shield which is freestripping from the conductor and bonded to the insulation
> InsulationNatural high dielectric strength EPROTENAX™ EPR-basedinsulation, combined with other materials and agents thatenhance the electrical and mechanical characteristicsassuring extended cable life
> Insulation ShieldExtruded thermosetting semiconducting shield with controlledadhesion to the insulation providing the required balancebetween electrical integrity and ease of stripping
> Metallic ShieldHelically applied non-magnetic copper tape(s) over the insulationshield with a minimum overlap of 15%. A Mylar ribbon is longitudinally applied under the copper tape shield for phaseidentification - 1C w/ Red, 1C w/ Blue, and 1C w/ Black
> Ground conductorsBare stranded copper conductor, one in each interstice,as per UL, ICEA, and ASTM requirements
> AssemblyPhase identified shielded conductors cabled with fillersand grounding conductors (as specified), forming a firmand cylindrical cable core. A binder tape is applied tomaintain core symmetry and mechanical stability
> Mechanical ProtectionHigh strength and high crush resistant layer extruded over the core assembly
> Chemical ProtectionA longitudinal aluminium tape with a nominal 10% overlapover which a chemical resistant extruded polymer layer is applied
> JacketA low temperature, flame retardant moisture and sunlightresistant PVC jacket. UL listed as type MV-105. Anoptional LSOH outer jacket is available on request
APPLICABLE STANDARDS AND APPROVALS• UL listed Type MV-105 “For CT Use” in accordance with
UL 1072• CSA FT4 Flame Test, IEEE 383 Flame Test, and IEEE 1202
Flame Test• ICEA T-29-520 at 210,000 BTU/hr• CSA 22.2 cold impact test (-40°C) and cold bend test (-40°C)• ABS approved for offshore applications• BV witness of accessories testing to IEEE 48 & 404• US Coast Guard Approved• Oil Resistant I & II
PRODUCT FEATURES• Cable is rated 105 °C as defined in UL1072• Chemical and oil resistant to a wide range of fluids• Suitable for direct burial as defined in NEC section 310-7
and 300-50• Lighter, smaller and more flexible than equivalent rated
Continuous Corrugated Welded Aluminium cable• Improved impact performance compared with the Continuous
Corrugated Welded Aluminium cable• Compatible with standard jointing technology
APPLICATIONS• Installations in both exposed and concealed locations in
accordance with NEC• Wet and dry locations in accordance with NEC• Directly buried or embedded in concrete• Installations on cable trays, troughs, metal racks, aerial
installations and continuous rigid cable supports inaccordance with NEC
• Economical alternative to traditional conduit systems• Suitable for variable frequency drive applications (VFD)• Suitable for vertical risers
Prysmian reserves the right to modify at any time the technical, dimensional and weight characteristics shown in this catalogue with in accordance the mentionedstandards in case it improves the features of its products. There is no responsibility of the manufacturer for any damages to persons and properties in caseof improper use and/or neglecting the recommendations for using cables and norms contained in this catalogue, relevant to installation and operation in shipand offshore applications.
Ampacities are based on the followingDuct: Cable in underground electrical ducts; one cable per duct; based on an ambient temperature of 20°C; per NEC Table 310.79Air: Cable isolated in air and an ambient temperature of 40°C; per NEC Table 310.71
quantity size
conductor diameter
(in) (mm)
insulation thickness
(mils) (mm)
insulation diameter
(in) (mm)
insulation shield
diameter
(in) (mm)
approx jacket
diameter
(in) (mm)
approx cable
weight
(lbs/kft) (kg/km)
ampacity(amps)
105°Cin duct
105°Cin air
> Three or four conductor cable with stranded copperconductors, extruded insulation system consisting ofhigh dielectric strength crosslinked polyethylene, cabledwith fillers and grounding conductors, foamed polymericlayer for superior mechanical protection, longitudinallyapplied aluminium tape, extruded oil and hydrocarbonresistant polymeric layer, and overall moisture and sunresistant black PVC jacket.
> ConductorsClass B compact concentric strand soft drawn annealedcopper as per ASTM requirements
> InsulationHigh dielectric strength cross link polyethylene insulationto ICEA S-95-658/NEMA WC70 and UL Standard 44 fortype XHHW-2
> Grounding ConductorsBare stranded copper conductor, one in each interstice,as per UL, ICEA, and ASTM requirements
> AssemblyPhase identified shielded conductors cabled with fillersand grounding conductors (as specified), forming a firmand cylindrical cable core
> Mechanical ProtectionHigh strength and high crush resistant layerextruded over the core assembly
> JacketA low temperature, flame retardant moisture and sunlightresistant black PVC jacket in accordance with UL standards.An optional LSOH outer jacket is available on request
APPLICABLE STANDARDS AND APPROVALS• UL listed as Type TC cable, UL 44• Single Conductor listed as XHHW-2• Fire performance rated IEEE 1202, IEEE 383 and IEC 332-3 Cat C• ICEA T-29-520 at 210,000BTU/hr• Meets CSA-C22.2 No. 3 cold impact and cold bend test (-40 °C)• ER "Exposed Run" Rated• ABS approved for offshore applications• US Coast Guard Approved• Oil Resistant I & II
PRODUCT FEATURES• Cable is rated 90°C as defined in UL44• Chemical and oil resistant to a wide range of fluids• Lighter, smaller and more flexible than equivalent rated
Continuous Corrugated Welded Aluminium cable• Improved impact performance compared with the Continuous
Corrugated Welded Aluminium cable• Compatible with standard jointing technology
sizequantity
APPLICATIONS• Replacement for MC cables• Installation in wet and dry locations in accordance with NEC• Installed directly buried or embedded in concrete• Installations on cable trays, troughs, metal racks, aerial
installations and continuous rigid cable supports inaccordance with NEC
• Economical alternative to traditional conduit systems• Suitable for variable frequency drive applications (VFD)• Suitable for vertical risers
Prysmian reserves the right to modify at any time the technical, dimensional and weight characteristics shown in this catalogue with in accordance the mentionedstandards in case it improves the features of its products. There is no responsibility of the manufacturer for any damages to persons and properties in caseof improper use and/or neglecting the recommendations for using cables and norms contained in this catalogue, relevant to installation and operation in shipand offshore applications.
Ampacities are based on the followingDuct: Not more than three current caryying conductors in raceway, cable, or earth (directly buried), Based on ambient temperature of 30°C (86°F) Per NEC Table 310.16