Building Automation

DESIGO™ Building automation and control system System description Version 2.2

Page 2: Building Management Systems

The following product names are registered trademarks:

BACnet– American National Standard (ANSI/ASHRAE 135) LON, LONMARK, LonTalk – Echelon Corporation OPC Ethernet EIB – EIBA Modbus M-bus Citect (Citect Pty. Ltd.) Grundfos Wilo Windows – Microsoft

Page 3: Building Management Systems

Contents

The DESIGO building automation and control system: the powerful, open system ................................................................................5 Distinguishing features of the DESIGO system...............................................................6

DESIGO system topologies ..........................................................................................7 System design for small buildings ...................................................................................8 System design for small to medium-sized buildings ........................................................8 System design for medium-sized to large building complexes........................................9 Distributed buildings ......................................................................................................10

System functions.........................................................................................................11 Trend/History .................................................................................................................11 Alarm management .......................................................................................................12 Scheduler / Calendar .....................................................................................................13 Access rights .................................................................................................................14 Communication – Networks...........................................................................................15

The management level: DESIGO INSIGHT ................................................................17 Shell and Taskbar..........................................................................................................17 Plant Viewer ..................................................................................................................18 Alarm management .......................................................................................................19 Time Scheduler .............................................................................................................21 Trend logging.................................................................................................................21 Log Viewer.....................................................................................................................23 Object Viewer ................................................................................................................24 Web Access...................................................................................................................26

DESIGO PX: the scaleable automation and control system....................................29 A family of programmable automation stations .............................................................29 Automation stations: the compact series .......................................................................30 Automation stations: the modular series........................................................................31 I/O modules ...................................................................................................................31 Programming with D-MAP .............................................................................................33 Libraries.........................................................................................................................33 Made-to-measure operator units ...................................................................................34 Operation via Web client ...............................................................................................35

DESIGO RXC ................................................................................................................36 Range overview.............................................................................................................37 The room unit: the key to individual comfort ..................................................................38 Integration into the building automation and control system .........................................39

3

Page 4: Building Management Systems

Integration using DESIGO OPEN................................................................................40 Some of the current solutions ........................................................................................41

DESIGO TOOLSET and application blocks ..............................................................42 DESIGO TOOLSET .......................................................................................................42 Application blocks ..........................................................................................................44

Technical data ..............................................................................................................45

4

Page 5: Building Management Systems

The DESIGO building automation and control system: the powerful, open system

With its modular design, the DESIGO building automation and control system offers virtually unlimited scope for operation, monitoring and control. The scaleable system covers everything from small, stand-alone buildings to large, networked building complexes. DESIGO is ideal not only for typical HVAC systems, such as heating, ventilation, air conditioning and sanitation, but also for all other building services, such as lighting and electricity, or fire and security.

Assicurazioni Generali SpA – Project implemented with DESIGO

5/48

Page 6: Building Management Systems

Distinguishing features of the DESIGO system

Open to integration The open system architecture is widely supported, making it possible to integrate third-party systems at all three levels of the system. Even for the exchange of information between system components, DESIGO uses well-established standard protocols, adopted throughout the world: the BACnet standard, both for communication between the management and automation stations, and for communication from one automation station to another, and LONMARK for room automation. DESIGO also supports components and systems with interfaces such as OPC, Ethernet, LON, EIB, Modbus and M-bus.

Easy to operate DESIGO is distinguished by its exceptional ease of operation. The attractive local operator units offer large fonts, and provide clear user guidance and a graphics-based display. Operation from the management station is based on the Microsoft Windows operating system and designed to take account of ergonomic principles.

Innovative Web access With PX Web operation, and DESIGO WEB, the DESIGO system makes use of Web technology both at the automation level and at the management level. Fault messages can be received and acknowledged with cost-efficient standard equipment such as Web-Pad, PC or mobile phone. The same technology can be used to retrieve data, trend information, statistics and other HTML reports, irrespective of the location of the user. In this way, those responsible for the system can be kept up to date at all times.

The scaleable system: for all projects from small to large DESIGO is the perfect choice for all projects, no matter how small or large. An extensive, modular range of automation stations, a variety of operator units, modular application software and a flat system topology all combine to ensure low start-up costs for small systems. At the same time these systems can be extended at any time, and expanded into comprehensive large-scale systems.

Economical in every phase The installation of highly automated building services plant is increasingly taken for granted. Due to technological advances and improved project handling, costs per data point are falling steadily. A prime concern in the field of building services, however, is the overall cost over the life cycle of the plant. With sensible start-up costs, efficient and cost-effective support during operation, plus flexible service options, the DESIGO building automation and control system is the right choice for the economy-minded building operator.

6

Page 7: Building Management Systems

DESIGO system topologies The DESIGO system can be divided into three levels: the management level, the automation level and the field level. By virtue of distributed intelligence, each of these levels operates both autonomously and in a network. Within the network, the DESIGO building automation and control system uses manufacturer-neutral standard protocols for communications, specifically BACnet for the management level and automation level, and LONMARK for the field level.

The principle DESIGO system components: • DESIGO INSIGHT, the management

station, for higher-level operation and monitoring, graphics-based display of the process, automatic alarm distribution and a wide range of different data analysis options.

• DESIGO PX, the automation system for local operation and control, and for monitoring of the primary plant.

• DESIGO RXC, the room automation system, for control of comfort conditions in individual rooms, including the operation of lighting and blinds.

• DESIGO OPEN modules, for the integration of a wide variety of plant at all levels of the system.

Drag

Drag + Drop

The principle DESIGO system components within the system topology

One of the key benefits of DESIGO is its scope for gradual expansion, from the smallest system through to large distributed systems. Some examples are shown on the next few pages.

7/48

Page 8: Building Management Systems

System design for small buildings A small automation system can even be implemented with just a small number of individual PX modular or compact automation stations. As an option, this system can be expanded by adding one or more type QAX34 or PXM20 operator units.

DESIGO RXC

PXR

01622

PXC..-U

PXM20

I/O Module

QAX34(OPTIONAL)

(OPTIONAL)

PXC...

PXM20

QAX34(OPTIONAL)

(OPTIONAL)

QAX33.1

PXC22

PXM20

A small restaurant ventilation system can be implemented, for example, with a PX compact-series automation station

For individual rooms, a small system with shared HVAC can be implemented for the classrooms in a local authority school, for example.

System design for small to medium-sized buildings A number of PX automation stations and RXC room controllers can be interconnected without difficulty via BACnet over LON and, depending on the size of the system, monitored and operated with one or more graphics-based, network-compatible PXM20 operator units. For remote operation, the system can be extended to include Web operation with the PX-WEB software. This Web solution presents the resident engineer with all the functions of the PXM20 operator unit whenever required, with the advantage of access from home, for example. In the event of a fault, alarm notification can be arranged via SMS or e-mail.

QAX50 DESIGO RXC

PXM20

PXC..

TelephoneLine

BACnet over LON

01623

PX WEB

WEB-client

PXR

Small system with remote Web operation

8

Page 9: Building Management Systems

System design for medium-sized to large building complexes The DESIGO INSIGHT management station lets you get the most out of your plant. Even in systems with a hundred data points or fewer, it proves its worth. The plant is operated using highly informative, animated graphics. Optimum building operation is ensured with scheduler programs that can be centrally operated, a clear, consolidated alarm handling system and a wide range of other options. The DESIGO system can be embedded without difficulty in existing IT Ethernet/LAN infrastructures. Naturally, DESIGO can be expanded into a multi-user system. Remote operation via the Web should also be mentioned here: this is an option which can be implemented with DESIGO WEB and the PX-WEB solution for Web operation.

DESIGO INSIGHT

3rd party

E-mail

Pager

MobilePhone

Fax

BACnet router

DESIGO INSIGHT OPEN

BACnet over Ethernet / IP

DESIGO INSIGHT

BACnet router

DESIGO INSIGHT

PXM20

PXC...-U with PXM20

I/O modules

QAX34PX-OPEN

PXM20

PXC...

I/O moduleswith I/O OPEN

BACnet via LON

QAX50

PXC...

DESIGO RXC

01660

PXRPX-WEB

DESIGO WEBWeb client

Third-party

THird-party

Medium-sized to large systems with the DESIGO INSIGHT management station

9/48

Edith Ruth Lagler
\(noch ein 3rd party device an BACnet/Ethernet IP anhängen\)
Page 10: Building Management Systems

Distributed buildings Up to 1,000 remote sites can be operated and monitored by telephone from a DESIGO INSIGHT management station. In the event of a fault, the automation stations automatically call the higher-level management station, which displays the fault to the user in a "pop-up" window. The user simply clicks a button to navigate to the associated graphics. In the case of the "life-safety" feature, the modem connections are checked at regular intervals. For remote access, connections can be established not only by modem, but also via Ethernet/LAN. The management station can be connected anywhere on the in-house LAN, from where it has access to the automation system via the router.

DESIGO INSIGHT

E-mail

Pager

MobilePhone

Fax

BACnet via Ethernet / IP

PXM20

PXC...-U with PXM20

I/O module

PXC...

BACnet via LON

QAX50

PXC...

DESIGO RXC

01661

PXR

DESIGO INSIGHT

PXC...-U with PXM20

I/O module

BACnet router

System for geographically distributed buildings with a central management station

10

Page 11: Building Management Systems

System functions

Trend/History Fully integrated trend data processing allows effortless evaluation and analysis of real-time (online) data and (offline) historical data. The trend feature facilitates the monitoring and fine-tuning of the plant. In the DESIGO system this feature is implemented in compliance with BACnet standard. This means that nothing now stands in the way of displaying BACnet data from other manufacturers. Data for trend analysis can be logged in a variety of different ways:

Trend logging options: • Continuous logging • Single run • Transient run

• Polling • COV polling (Change of Value) • Event-driven polling

Drag

Drag + Drop

Trend Viewer on the PXM20 operator unit and on the DESIGO INSIGHT management station

With the Online Trend option, individual data points are registered on a COV basis or through polling, and displayed immediately. The values are stored temporarily, in order to observe transient response patterns, for example.

Online trend

Features of Online Trend: • Real-time display of process data • Short time periods (seconds, minutes, hours)

• COV-driven data • Temporary data, not normally stored.

Offline Trend by contrast, does not depend on a permanent connection between the automation station and operator unit, because the values in the automation station can be stored temporarily for retrieval on the operator unit as needed.

Offline trend

11/48

Page 12: Building Management Systems

Features of Offline Trend:

• Offline data display, no connection required • Longer periods of time (days, months)

• Cyclical acquisition of data • Data acquisition in the automation system.

The data is uploaded periodically to a database at the management level.

Graphs can be displayed on both the PXM20 operator unit and the management station, in the latter case as 2d or 3d graphs and in color.

Alarm management One of the most important features of a building automation and control system is the ability to generate alarms automatically in the event of faults; these faults may occur in the HVAC and other systems or in the automation system itself. The management of alarms (generation, display and handling) must be simple, efficient and consistent at all levels of the system. In this context, DESIGO makes full use of the BACnet standard as a basis, and supports the following three types of alarm: • Simple Alarms (for alarms not requiring user interaction) • Basic Alarms (for alarms requiring acknowledgement) • Extended Alarms (for alarms requiring acknowledgement and reset)

DESIGO also supports the 256 alarm priority levels of the BACnet standard, which can, for example, be consolidated at the management station into ten priority levels.

When an alarm occurs, it is automatically detected, registered and transferred to operator units such as the PXM20, to PX Web for Web operation or to the DESIGO INSIGHT management station. Informative alarm messages are also transmitted to remote devices such as mobile phones, fax machines, printers, PCs and Web browsers, via SMS and e-mail. Clear alarm lists provide a view of all pending and time-stamped alarms at a glance, and permit straightforward processing. Pop-up windows and audible and visual signals alert operators to incoming and pending alarms.

Alarm messages

Alarms are transferred on the basis of time, priority and/or plant type with an outstandingly powerful alarm routing system at the management station. In this way, important messages reach their destination 24 hours a day throughout the year, whether or not there is an operator sitting at the management station. Users are supported in their work by various overview options which help ensure a fast and correct response even in critical alarm situations.

Alarm routing

Alarm Viewer on the PXM20 operator unit and the DESIGO INSIGHT management station

12

Page 13: Building Management Systems

Scheduler / Calendar One of the basic functions of a building automation and control system is time control of procedures and processes. Ventilation, heating, air conditioning, lighting, door locks etc, are controlled on the basis of opening times and working hours in buildings such as offices, banks, restaurants, department stores and schools. Scheduler programs ensure that the heating and lighting are switched off automatically at the end of the working day, that the temperature in the building is reduced at night, and that the plant is not kept running for longer than necessary. They can also be used to switch off the air conditioning in certain rooms during holidays.

The ideal scheduler programs help save energy and increase the service life of the plant.

Saving energy

Research has shown that scheduler programs are rarely used to best effect to save energy and extend the service life of plant, because the programming operations required are too complex. This is another area where DESIGO excels with its straightforward and exceptionally user-friendly operation.

Increasing the service life of plant

DESIGO is based on the worldwide BACnet standard, in which even complex functions such as scheduler programs are standardized. Time-switching operations in the DESIGO building automation and control system are implemented in accordance with this standard, using the BACnet objects "Schedule" and "Calendar". These powerful functions can be operated flexibly, from simple 7-day programs for standard operation from Monday to Sunday, to more sophisticated, recurring exceptions, such as business opening times every second and fourth Saturday in the month.

Standard BACnet functions

With the standard BACnet functions, even BACnet schedules from third-party manufacturers can now be monitored for the first time via the easy-to-use PXM20 operator unit, the PX Web controller and the DESIGO INSIGHT management station.

Scheduler program in the PXM20 operator unit and on the DESIGO INSIGHT management station

For safety reasons, schedules and calendars are stored in the automation station, so that in the event of a network or PC failure, the automation level can continue to operate autonomously.

13/48

Page 14: Building Management Systems

Access rights Access rights can be used to filter information from the plant and system based on the individual requirements of a user. The resident engineer or the service engineers, for example, only have access to the information they strictly need. A distinction can also be made between read access and write access. Certain users may be able to read a value but not modify it, while other users may have extended access rights, enabling them both to read and to modify values.

Only authorized personnel are granted access to the system via the operator units and the management station. When a user enters a user name and password, the system verifies the associated access rights and enables access to the relevant plant and programs. Read and write access rights can be defined in detail, down to individual information points.

Freely-definable access rights

These are assigned to one of the seven following access classes.

Internal Advanced service activities Adaptation Service Basic service activities Administration Expert Extended operation Standard Basic operation Customer

In addition to the above, it is possible to enable or disable he use of the various applications, access to individual graphics pages and access to entire sites from the management station for specific user groups. The tailoring of the environment to each user ensures clear areas of responsibility and answerability, so simplifying cooperation between the various user groups.

14

Page 15: Building Management Systems

Communication – Networks

Technical designation Unique addressing of all elements is essential for the identification of the plant and the associated elements. In this area DESIGO has introduced an innovation, the "Technical View", which is based on the user's viewpoint. This standardized hierarchically structured view is based on the needs of the users of the plant. Addressing is thus not based on the device-focused viewpoint of the automation stations (e.g. "Controller08/DigitalOutput02"), but on the user's viewpoint, e.g.: "Location Kingston/Ventilation, Building 6/Air handling, 3rd floor/Supply air fan/Fan switch".

Clear-text designation 11

0013

-02-

04

TT H

Plant

Site

Component

Partial plant

Aggregate

Ventilation plant, Building 6

Air handling, 3rd floor

Kingston premises

Sched

Plant

V H

Example of the hierarchical classification of the plant elements

The hierarchical structure is ideally suited to various types of plant, such as primary plant, room systems and integrated systems, for example. Naturally, clear-text designations are used throughout the system, appearing for example in alarm messages, facilitating fast location of faults.

Fast location of alarms

Communication standards: specifically designed for building services Building automation and control system projects are increasingly engineered without recourse to costly gateway solutions for the exchange of information. With the BACnet open communications protocol, compliant devices can be interconnected at low cost. The worldwide BACnet standard was developed under the auspices of ASHRAE specifically for the needs of building services. BACnet networks provide all subscribers with access to all the data and functions of the connected devices.

DESIGO uses the two worldwide standard protocols BACnet and LONMARK for the exchange of information among its own system components. The BACnet communication protocol is used for the exchange of information between one PX automation station and another, and between DESIGO PX and DESIGO INSIGHT. DESIGO uses Ethernet/IP, LON or PTP (point-to-point) as the transport medium. At the field level, DESIGO RXC uses LONMARK, the standard ideally suited to the requirements at this level.

BACnet and LONMARK

15/48

Page 16: Building Management Systems

Features of BACnet The open BACnet communications protocol, a worldwide standard, has the following special features: • BACnet supports modern networks such as Ethernet, ARCnet, LONTALK, RS485 and

point-to-point connections. • BACnet provides 23 predefined standard objects, including special objects for

applications such as trend logging, averaging, alarm distribution, time scheduling and the connection of fire and safety systems, including fire detection systems etc.

• BACnet systems offer maximum interoperability with minimum engineering. • BACnet supports decentralized systems with distributed intelligence. • There are no user fees associated with BACnet – anyone can develop and use

BACnet solutions.

BACnet Application Layer

BACnet Network Layer

MS / TPISO 8802-2IP Dial-up

PTPLonTalk

ETHERNET ARCNET RS 485 RS 232

Supported by Siemens Building Technologies

In widespread use primarily in USA

BACnet protocol stack

16

Page 17: Building Management Systems

The management level: DESIGO INSIGHT The clearly structured, modular, object-oriented software of the DESIGO INSIGHT management station is based on Windows standard 32-bit technology. The functional scope and ease of use of the software reduces operating costs and the time required to become familiar with the system, while at the same time increasing operational reliability. The DESIGO INSIGHT applications are available in a basic "Start-feature" package, with other applications available as options:

• Basic shell software via the taskbar: Provides a quick overall view of the system and is used to start whichever user applications are required.

Start-feature package

• System Configurator: Used to configure the general setup of the DESIGO INSIGHT management station and the associated applications.

• Object Viewer: An efficient tool for navigation through the hierarchical tree-structure to all the data points in the system. These points can then be read or manipulated, depending on the access rights of the user concerned.

• Time Scheduler: Central programming of all time-controlled building services functions.

• Alarm Viewer: Provides a detailed overall view of alarms from between one and 1,000 buildings for the fast location and elimination of faults.

• Alarm Router: Flexible transmission of alarms to printers, fax machines, mobile phones and e-mail.

• Plant Viewer: Realistic plant graphics allowing fast, targeted monitoring and operation of the system

Options

• Trend Viewer: Convenient analysis of trend data for fine-tuning the operation of plant

• Log Viewer: Alarms, errors and user activities are logged in chronological order, and can be displayed for further evaluation, as needed.

• Web Access: Provides access to the Web applications "Web Graphics", "Web Alarms", "Web Log" and "Web Reports".

• Graphics Builder: Powerful tool for efficient creation of customized plant graphics • Open drivers such as OPC, EIB, LON etc.: For direct integration of OPC, EIB,

LON and other interfaces into the management station. • Various alarm receivers

Pagers / SMS, Fax and e-mail

Shell and Taskbar The shell is the first application to appear when DESIGO INSIGHT is started. It is displayed with a taskbar. It provides fast and direct access to all the user applications, and displays important status information. In systems with several remote installations, it is possible to switch from one plant to another via the taskbar, subject, here too, to the appropriate access rights. This ensures clear demarcation lines between the various areas of responsibility and answerability. The user's entry into the system is simplified by user-specific start-sequences with preselected programs and plant.

17/48

Page 18: Building Management Systems

Background functions in DESIGO INSIGHT:

• Life Check feature for checking the connection to the automation systems

• Alarm upload after system start • Check for correct running of the other

applications of DESIGO INSIGHT V2

• Time synchronization between management station and site. DESIGO INSIGHT can be configured as the time master for the system

• Hard-disk memory capacity check • Database availability check

Plant Viewer Plant Viewer displays the areas of a building and the associated plant in graphical form. The user works interactively with these views to monitor and control the data points throughout the building. Plant Viewer is based on the Citect process display software supplied by Citect Pty Ltd. Citect is a world leader in the supply of SCADA systems.

Process display

Numerous windows of different sizes can be displayed simultaneously (overlapping or tiled). Even large graphics, such as floor plans etc. can be accommodated, and the freely definable page size makes them easy to view. Setpoints, alarms etc. can be manipulated directly in the graphics. The user can modify a value or acknowledge an alarm simply by clicking on the relevant object.

Measured values, setpoints, operating modes and alarms are displayed on the screen in real-time, and updated continuously. The form of display is determined in the engineering phase. Changes are indicated either by the object symbol, e.g. through animation or a change in shape or color, or by a change in color, shape, text or movement of the values affected.

Real-time display

18

Page 19: Building Management Systems

Other features of Plant Viewer:

• Genuine multitasking with fully dynamic functioning of all active pages

• Object-oriented plant monitoring and operation

• Freely definable page size option for versatile handling of several pages in the same screen

• Page selection via Page list dialog box, or context menu or engineered buttons (hyperlinks). Integrated standard page selection features based on the page naming strategy. Standard functions such as Last/Next/Top etc.

• Object-oriented navigation between applications

• Definition of, and quick access to "Favorite" pages

• ToolTips for all dynamic objects, with the option of User, Technical or System Designation

• Context-specific information such as text, photos or maintenance information can be added to each dynamic symbol

• Black-and-white or color graphics printing • Import of Windows 32-bit supported graphics

file formats, such as AutoCad, PXC etc.

Alarm management

Alarm Viewer The Alarm Viewer application displays alarms by type, and provides the user with helpful information as to the type of action required by the system. With its extensive filter and search functions, Alarm Viewer facilitates fast and well-targeted access to the required information. In larger systems with more than one management station, all management stations access the same alarm database. An alarm for any given management station is entered in this database and automatically displayed on all other management stations.

The processing is different from one management station to another: • Only the management station defined as a destination for the alarm can forward the

event and display an alarm window ("pop-up"). • Pop-up windows are configured specifically in the Alarm Router on each

management station. • To acknowledge or reset an alarm, a management station must be connected to the

site to which the alarm object belongs.

Functions in Alarm Viewer: • View, acknowledge and reset single or

multiple alarms • Display the associated alarm property

sheet with detailed data point information

• Read associated alarm help text with operating instructions or additional information in text form

• Object-oriented navigation to other applications, such as Plant Viewer and Log Viewer

19/48

Page 20: Building Management Systems

Pop-up windows The pop-up window is an important means of attracting the attention of the user in the event of an alarm. Incoming alarms are displayed in a pop-up window that opens on the Windows desktop and appears in the foreground of all other applications (including third-party applications). If several alarms occur, they are displayed one after the other. To further alert the user to the alarm with an audible signal, an audio file (.wav) can be added to each alarm window definition.

Alarm Router The Alarm Router application provides for highly effective building management: important messages or events in the building automation and control system are transferred to specific receivers without the need for any user action at the management station. Alarm Router is a background application which starts when DESIGO INSIGHT is started, whether or not a user or site is connected. Alarms and important system events can be transferred via the following media: • Printers • Fax machines • Pagers • Mobile phones • E-mail systems

Alarms can be grouped according to various criteria. A routing table defines the conditions under which these alarm groups are to be routed to the assigned receivers. In the event of connection problems, the alarm messages can be transmitted to alternative receivers. The criteria include the following, for example:

Criteria for the transfer of alarms

• Time (e.g. at night, switch to the printer in the night security guard's office) • Responsibility for the site (e.g. send a fax to the company responsible for

maintaining the air conditioning) • Urgency of the alarm (e.g. only call resident engineer by pager in the case of high

priority alarms)

20

Page 21: Building Management Systems

Time Scheduler The Time Scheduler application in DESIGO INSIGHT can be used for central programming of all time-controlled functions in the building services plant, including the individual room control system. The facilities for graphics-based operation of the weekly schedules and exception programs, the user can modify and optimize scheduler programs at any time and without difficulty.

Graphics-based operation

Principle functions:

• Graphics-based overview and manipulation of all scheduler programs in the system

• Direct entry of various operating modes (e.g. Comfort, Standby, Energy Hold-Off)

• Easy graphics-based programming of switch times

• Storage and processing are independent of the management station

• Programs invoked directly from the plant graphics

• Report printed in different display formats

System Browser view, and overview of daily profiles in the Time Scheduler application

Trend logging

Trend Viewer The Trend Viewer application is used to review current process data in real time (online) and past process data (offline) over a period of time. Trend Viewer is an easy-to-handle tool used to optimize the operation of plant and reduce costs.

Activities in Trend Viewer: • Log process values over a period of time • Track energy consumption

• Monitor current plant conditions • Plant optimization and fine-tuning

21/48

Page 22: Building Management Systems

Up to ten process values can be displayed in 2D and 3D graphs in a single trend view. Several trend views can be displayed simultaneously in different, overlapping windows. Both online and offline data (and even data from the archive) can be displayed simultaneously in separate windows, enabling the user to compare past and current situations.

Drag

Drop

Objects can be dragged from the System Browser and dropped directly into Trend Viewer

Essentially, trend data can be displayed in three different modes:

• Online trend logging: displays real-time process data which is updated whenever a change of value (COV) occurs, or as the result of a time-based scan

• Offline trend logging: displays past process data which has been uploaded to a database at the management level.

• Archive data: displays older data which has been moved from the trend database into archive files

The trend views can be saved and invoked at a later date. Online trend data is continuously logged and stored in the trend database.

Advanced Data Processing (ADP), Consumption Control (CC) ADP and CC are add-on software packages. These add-ons are used for effective storage, archiving and evaluation of process data, and are especially suitable for medium-sized and large projects where there is a requirement for long-term storage and flexible, customized evaluation of data. Process values can be displayed in the form of lists, reports or graphs (trend views). ADP and CC use their own standard database, which is fully independent of the DESIGO INSIGHT offline database.

22

Page 23: Building Management Systems

Log Viewer The Log Viewer provides a view of the events and user activities archived in chronological order in the log database. Users thus have access whenever required to all past events. The data logging system is a background service performed by the Event Handler in DESIGO INSIGHT V2, which continuously logs reported events as follows:

Event Handler

• Alarm events from the process level such as plant alarms, high priority warnings, frost alarms etc. The alarm is logged when it occurs, and thereafter upon acknowledgement, reset and return to normal.

• System events from DESIGO INSIGHT management stations and PX automation stations. Examples are communication problems, selection procedures, start-up, shutdown, hard-disk monitoring, battery checks etc.

• User events for reporting user activities on management station. These include authorized and unauthorized user log-in procedures and the modification of values, parameters and setpoints etc.

• Status events from the process level, such as plant ON/OFF etc.

The two user interfaces of Log Viewer and Alarm Viewer use tables with the same "look and feel" and with a versatile range of options for sorting and filtering.

Functions in Log Viewer: • Query-configurations can be stored and re-

used. The status bar displays the current filter and sort status

• The Log Viewer display is divided into five tabs: All, Alarm, System, User and Status, enabling the user to pre-select events of a particular category

• Columns can be flexibly rearranged, re-sized or hidden as required

• The events logged for a specific object, such as events associated with a given site, automation station or data point, can be located quickly in the left pane (System Browser). The System Browser can be hidden to make more room for displaying the columns

The logged data is stored on a Microsoft SQL server or in an MSDE database. Password protection prevents unauthorized access.

Log and trend data archiving The archiving function serves to remove data from the runtime databases. This is necessary firstly to create space for new data in cases where storage capacity is normally limited, and secondly, to store the data in a suitable form for retrieval at a later date. The removed data is archived in a safe location for later retrieval and display if required.

The criteria for archiving in DESIGO INSIGHT are as follows: • Automatic archiving at specific time intervals • Automatic archiving based on the volume of data accumulated • Manual archiving initiated by a user command

23/48

Page 24: Building Management Systems

Object Viewer Object Viewer helps users of the building automation and control system to navigate efficiently through the entire structure. The hierarchically organized data objects are easy to select, view and modify.

Object Viewer supports three different hierarchical views: • Technical View

The technical view is the plant-related standard view associated with the technical designation.

• User View The user view is based on customer-specific user designations (user addresses). The address structure and contents are defined as part of the DESIGO PX engineering process. The engineering of a user view is relatively time-consuming, but does make it possible to combine a geographical and a plant-based structure, which can be useful in larger projects.

• System View The system view is a standard hierarchical view, representing the topology of the BACnet network, whereby a site contains devices and each device contains objects (Site.Device.Object).

System Browser The left pane of Object Viewer contains the System Browser, which displays a hierarchically structured view of the system (in a tree-structure). The right pane of Object Viewer displays the contents of the currently selected object.

24

Page 25: Building Management Systems

Functions in Object Viewer:

• Fast navigation through the building automation and control system

• Fast location of objects and alarms • Detailed information on the properties of

each object • Display of real-time data from the process. • Modification of setpoints and parameters,

and manual override of outputs (assuming that the user has the necessary Write privileges)

• Jump functions Back / Forward

• Modification and definition of object-related text

• Find function with wildcarding for quick and direct access to certain objects

• Object search in other views by changing view in context-menu

• Read/Write access levels are supported. Users only see objects in locations to which they have Read access. They can only modify objects to which they have Write access

• Object Editor: An exceptionally user-friendly user interface for editing sophisticated D-MAP objects

25/48

Page 26: Building Management Systems

Web Access Web Access is an interface to the building, based on a browser and using integrated Web technology. Web Access can be used for roaming, and for remote access to and control of important building-related information managed by DESIGO INSIGHT.

Home page

Given the now widespread familiarity with Web browsers, even occasional users can access the required data quickly. This cost-effective solution reduces the cost of training, software installation and maintenance. The Web Access software facilitates and encourages the simple distribution of building information to those who need it, and at the point where they need it. Given the modular structure of DESIGO INSIGHT, new and existing DESIGO INSIGHT systems can be upgraded with Web Access at any time. The principles of Web Access can be applied in a building network, over the company intranet and on the Internet. Using technology based on Microsoft Active Server Pages, Web pages work together with DESIGO INSIGHT to exchange data between the browser and the system. There are two methods of data exchange: • Via the Citect interface, for the exchange of dynamic data and for alarm handling • Via ODBC queries to the SQL databases

Unlike many other Web-based solutions, Web Access does not use any script components on the client side. All processing takes place on the Web server. This means that client browsers can work with Web Access without having to download any browser add-ons. Many customer networks inhibit or even forbid the dowloading of Active-X or similar scripts.

26

Page 27: Building Management Systems

User authentication is achieved by integrating Windows network access and the authorized DESIGO INSIGHT users. Each time a user accesses the system, the appropriate DESIGO INSIGHT user access rights are automatically assigned to the Web pages displayed. Web Access provides access to the system via a browser. This maintains the familiar format based on the successful operability guidelines of DESIGO INSIGHT. • Index Page is the equivalent of the familiar "Home Page". From here, the user can

obtain a quick overall view of the system, or start navigating around the site. • Graphics-based view of the plant at the automation level, including dynamic

updates of status and alarms, and navigation through the hierarchy. Data points can be operated and alarms can be manipulated directly in the graphics. The pages can be generated with the standard graphics in Plant Viewer, so retaining the familiar DESIGO INSIGHT look and feel. No special Web authoring tools are required.

• Alarms from the DESIGO INSIGHT database are collated in tables. "Sort" and "Filter" procedures can be predefined or carried out dynamically. Users can process alarms and receive dynamic feedback from the system.

• Log data logged on the management station can be retrieved via a browser. All activities in the browser are added, with the relevant user name, to the normal DESIGO INSIGHT entries in the central log database.

• Reports can be displayed dynamically and used for data point control. The limited performance of some handheld Web browsers can be overcome by use of reports.

• The User information option provides an overview of the Read and Write privileges of a logged-in user.

Graphical view of the plant

27/48

Page 28: Building Management Systems

Alarm handling

Features of Web Access (via the Web browser): • Fast access to important user functions • Display and edit plant graphics • Possibility of immediate display and

processing of alarms • Logging in the log database of remote users

and activities for later evaluation in the browser

• Filtering and sorting of data in the alarm and log databases, for fast access to the information required

• The integration of the DESIGO INSIGHT access rights into the Windows network ensures access security based on predefined access rights

• Cost-effective distribution of information to an even greater number of users is now possible

• Integration of e-mail and SMS messaging systems permits roaming access to the building system

28

Page 29: Building Management Systems

DESIGO PX: the scaleable automation and control system The DESIGO PX automation system meets all the requirements associated with the control and monitoring of heating, ventilation, air conditioning systems and other building services. The most striking features of DESIGO PX are the scalability of the system with its programmable automation stations and graded range of operator units, and the system's openness.

A family of programmable automation stations There are two series of automation stations in the range: compact and modular The essential difference between the two series is the flexibility of their data point mix,

This strategy ensures optimum adaptability to customer requirements and to the building services plant.

00213

PXC52PXC36

PXC12,22/-T

PXC128-U

PXC64-U

PXC10-TL

I/O modules

Cost

Number of inputs and outputs A family of programmable automation stations Modular

series (PXC…-U)

Compact series (PXC…)

PXR… system controllers

PXE… system controllers

User interfaces at the automation level

Web client • • • • PXM20 • • • • QAX3x • •

System functions (BACnet) Alarms • • • • Time schedules • • • • Trend • • • • I/O and value objects • • • •

Programming with D-MAP • • • • I/O subsystem P bus Direct

connection via inputs/outputs

LONMARK RS232/485 Programming with SCL for specialists

Additional functions Grouping •

Overview of the DESIGO PX automation stations with various subsystems

29/48

Page 30: Building Management Systems

Automation stations: the compact series The compact series of automation stations is ideal for all control and monitoring activities in distributed HVAC systems. The compact-series automation stations have built-in I/O terminals and can be used in packaged-unit (e.g. AHU) control panels and standard installations, even where space is very limited. All compact automation stations are freely programmable and incorporate the full range of system functions. The operator units are easily connected using standard cables. In addition, up to five QAX… room units can be linked via a two-wire connection directly to the PPS2 interface.

PXC36-S automation station PXC10-TL automation station Type PXC10-TL

PXC12 PXC12-T

PXC22 PXC22-T

PXC36 PXC36-S

PXC52

I/O Total 10 12 22 36 52 UI 4 6 8 12 16 DI 4 4 12 16 AO 4 4 6 8 DO 2 2 6 6 12

Types

I/O configuration of the compact-series automation stations UI Universal inputs, which can be connected to passive (LG-Ni 1000) and active (DC 0…10 V)

sensor elements, or to binary volt-free contacts, for signaling functions. DI Binary-only inputs for signaling and counting functions (max. 4 x 20 Hz counters per PXC…). AO Analog outputs for the connection of 0 ... 10 V actuators or for binary control. Via the program

structure, analog outputs can also be programmed as binary switch functions and connected to 24 V/20 mA loads.

DO AC 230 V / 2A relay outputs for binary control

Ports/interfaces PPS2 For the connection of up to 5 QAX3x room units LON For BACnet communications between automation stations

The PXC36-S automation station also incorporates a manual switch and further LED indicators. Manual operation via the switch positions Auto/Stop/Manual can be used for direct switch control of spring-return actuators, and for control of switch functions which are logically interconnected via the program structure. The PXC10-TL, PXC12-T and PXC22-T automation stations also have an integral remote management feature, allowing remote alarm transmission and remote operation via the public telephone network in conjunction with DESIGO INSIGHT. Further, the PXC10-TL automation station is optimized for wall mounting and has a built-in 230 V supply.

30

Page 31: Building Management Systems

Automation stations: the modular series The modular series of automation stations is particularly suitable for all control and monitoring tasks in large and sophisticated systems for HVAC and other building services. With their graded range of functions, the modular automation stations offer a high degree of flexibility. A wide range of I/O modules makes it possible to adapt the data points individually to the field devices.

PXC...-U modular automation stations Extension module PXA30-T

Types PXC64-U Basic types for 64 load units, LON connection, PPS interface, P-bus

connection and snap-mounting for PXM20 operator unit PXC128-U Basic types for 128 load units, LON connection, PPS interface, P-bus

connection and snap-mounting for PXM20 operator unit

PXA30-T Extension module for remote management

I/O modules The I/O modules provide the interface to the equipment at the field level. The I/O modules are connected to the automation stations via the P-bus bar and can be interconnected in application-specific configurations. The I/O modules have LEDs to indicate the status of the plant and, depending on type, some have controls for manual or emergency operation. Third-party systems and components can be integrated via the "intelligent" PTM… I/O modules. For example, when pumps are connected, access to the following information is available: control of operating mode, setpoint adjustment, fault and status codes, delivery head, delivery and speed. Up to 128 modules can be connected to the modular automation stations, depending on the basic type selected and the total number of load units.

I/O modules with and without manual controls

31/48

Page 32: Building Management Systems

Overview of I/O modules

Basic function Signal amplitude and range

Signal type and function

LED

dis

play

Man

ual o

pera

tion

Num

ber o

f I/O

s

Load

uni

ts a

t 12.

5

mA

eac

h

Type ASN No.

Normally-open • 2 2 PTM1.2D10 Normally-open • 4 1 PTM1.4D20 Normally-closed • 4 1 PTM1.4D20R

Volt-free maintained contact

Normally-open • 8 1 PTM1.8D20E Volt-free pulse contact N/O or N/C • 2 2 PTM1.2D20S AC 24 V / DC 42 V Extra low voltage • 2 2 PTM1.2D42

Signaling

AC 250 V / DC 100 V Voltage • 2 2 PTM1.2D250

LG-Ni 1000 Temperature, passive 2 1 PTM1.2R1K LG-Ni 1000 Temperature, passive 4 1 PTM1.4R1K 0…250 Ω / Pt100 / Ni100 Resistance, passive 2 2 PTM1.2P100 0…2500 Ω / Pt1000 / Ni1000 Resistance, passive 2 2 PTM1.2P1K DC 0..10 V Voltage

measurement 2 1 PTM1.2U10

DC 0…max. 25 mA Current measurement 2 1 PTM1.2I25/020

Measuring

DC 4…20 mA (fixed) Current measurement 2 1 PTM1.2I420

Counting Volt-free (max. 25 Hz) Counter-value pulse 2 2 PTM1.2C Single-stage • 2 2 PTM1.2Q250 1-stage (bistable) • 2 2 PTM1.2Q250B

Volt-free maintained contact

Single-stage • • 2 2 PTM1.2Q250-M

Single-stage with feedback

• 2 2 PTM1.2QD

Single-stage with feedback

• 4 4 PTM1.4QD

Single-stage with feedback

• • 2 2 PTM1.2QD-M

2-stage with feedback • • 4 2 PTM1.4QD-M2

Non-floating maintained contact

3-stage • • 3 2 PTM1.3Q-M3 Single-stage • 4 2 PTM1.4Q250-PSingle-stage • 4 2 PTM1.4Q250A-

P

Switching

Volt-free pulse contact

3-stage • 4 2 PTM1.4Q250-P3

Positioning signal • 2 1 PTM1.2Y10S Positioning signal • 4 1 PTM1.4Y10S

DC 0…10 V (modulating)

Positioning signal • • 2 1 PTM1.2Y10S-M

Positioning signal • 2 1 PTM1.2Y420 Positioning signal • 2 2 PTM1.2Y250T

DC 4…20 mA (modulating)

Positioning signal • • 2 2 PTM1.2Y250T-M

Positioning

Pneumatic (0 ... 138 kPa) Positioning signal • • 1 2 PTM6.1PSI20-M

Grundfos 4 pumps • 8 PTM52.32V01 Interface modules

Wilo 4 single / 2 twin pumps

• 8 PTM50.32V01

32

Page 33: Building Management Systems

Programming with D-MAP The D-MAP programming language (= DESIGO Modular Application Programming) for DESIGO PX ensures efficient programming and parameter setting for building services plant. The new programming language, D-MAP, based on standard IEC1131, is optimized for building services. The control strategies required for and best suited to efficient operation are implemented using graphics-based data flow programming.

Efficient engineering with blocks and compounds The project-specific HVAC applications are configured, programmed, commissioned and maintained using the CFC Editor in PX Design. The CFC Editor is a graphics editor based on block programming and data flow techniques (see also "Commissioning and engineering with DESIGO TOOLSET").

CFC chart

110013-04-15en

Blocks

Compounds Compound

CFC EditorLibraries

Instantiate

Copy

Creating the CFC chart with the CFC Editor

The characteristic features of D-MAP programming are as follows: • The elements of D-MAP programming are blocks and "compounds" (compound

functional units). These are stored in libraries. • To create a D-MAP program, the blocks and compounds which provide the required

functions are combined in the CFC Editor. This process involves creating instances (of blocks) or copies (of compounds) from the libraries.

• The flow of data between blocks is programmed by interconnecting the "pins" (inputs and outputs) of various blocks.

Libraries PX Design incorporates libraries in which the functions, function blocks and compounds are stored. The libraries contain images of actual plant, aggregates and components in a structure which can be used equally for design engineering, control, operation and monitoring and display.

33/48

Page 34: Building Management Systems

Made-to-measure operator units The various operator units in the DESIGO PX range more than satisfy all the various requirements in terms of location and function.

PXM20 operator unit The PXM20 operator unit allows uniform operation of various building services at the automation level. The operator unit incorporates buttons for operation, and a high-resolution display panel for displays in graphics-based and text format. The PXM20 can be used either locally or for remote access to all the plant connected in a network. The handheld operator unit can either be installed in a control panel or plugged into an automation station.

PXM20 operator unit Graphics-based display of the heating curve

The clearly arranged function buttons and fast access buttons ensure correct operation, even by inexperienced users. Operator functions with the PXM20 include the following: • Alarm display and acknowledgment • Overview of plant status • Display and modification of scheduler functions • Manual operation, e.g. to change fan speed • Graphics-based display of trend data

Room units Up to 5 bus-compatible QXA... room operator units can be connected to the PPS bus of each automation station. The various options include: • Digital display options • Status display • Plant switching functions

QAX30.1 QAX31.1 QAX32.1(*) QAX33.1(*) QAX34.1(*)

(*) When these devices are connected to the PXC, they display the comfort requirements of the user, which may not necessarily correspond to the actual room status. QAX30.1 QAX31.1 QAX32.1 QAX33.1 QAX34.1

• • • • • Measured room temperature

• • • • Setpoint correction

• • • Operating mode switch

• • Fan speed switch

• LCD for room temperature and operating mode

Overview of the QAX... room unit functions

34

Page 35: Building Management Systems

Operation via Web client The PXC, PXR and PXE automation stations can be operated from a Web client by means of a Web controller.

-

Operation and monitoring from a Web client: Plant overview

PXG80-W/WN Web controller

Main functions: • Depth of operation based on access rights • Alarms via SMS (to specified telephone number) or by e-mail • Generic operation via Web browser • Access to all setpoints, measured values, and to plant status • Overview of pending alarms • Overview and modification of 7-day and date programs

(Schedule / Calendar) • Modification of setpoints and overwriting of measured values

(e.g. temporary adjustment in the event of a faulty sensor) • Modification of parameters (e.g. heating curve if defined as BACnet object) • Graphical overview of plant • Easy creation and modification of plant graphics using standard graphics software. Trend data logging, with the facility to export data to Microsoft Excel for evaluation purposes.

PX-WEB type summary

PXG80-W Automatic alarms via SMS Web browser access via analog or ISDN modem, or null modem.

PXG80-WN Automatic alarms via SMS or e-mail Web browser access via Ethernet/IP

35/48

Page 36: Building Management Systems

DESIGO RXC The DESIGO RXC room automation system provides individual demand-based comfort for building users in public buildings, offices, schools, hotels, etc.

The DESIGO RXC equipment controls and monitors defined comfort conditions in rooms and other enclosed spaces. These functions are finely tuned to satisfy specific requirements in each room or zone. This makes it possible to take account of individual comfort requirements while simultaneously saving energy.

Easy control of HVAC, lighting and blinds The modular design of DESIGO RXC makes it possible to combine the operation of lighting and blinds with the HVAC control system. Using just one operator unit, room users can adjust all the room functions to suit their requirements.

Stand-alone operation at field level, or integration into the building automation and control system The devices in the DESIGO RXC range communicate with each other and with other LONMARK-compatible devices using a standard protocol (LONMARK over LON bus). Seamless integration into the DESIGO building automation and control system makes available the additional functions of building management.

01715

M

Integrated operation of HVAC, lighting and blinds

36

Page 37: Building Management Systems

Range overview DESIGO RXC is an innovative range of room controllers, extension modules and room units. Data communications are based on LONWORKS technology.

The DESIGO RXC hardware The range comprises compact and modular room controllers, easy-to-operate room units and controllers in room-style housings.

RXC20.1RXC21.1RXC22.1

01534de

RXC32.1

RXC10.1

QAX3...QAX9...

RXC30.1RXC40.1RXC41.1

RXC31.1RXC40.1RXC41.1

QAX50.1QAX51.1

Elec

tric

alHV

AC

Fan coilsystems

Radiators

Chilledceiling

Blinds

Lighting

Room units

ModularCompact

Controllers

Standardwireless

VAV

Controller inroom-stylehousing

Flexible

The DESIGO RXC software Each device is loaded with application software (referred to elsewhere in this section simply as the "application") which contains the control program for the associated room or area. Siemens Building Automation maintains a comprehensive library of applications covering a wide range of HVAC and electrical applications.

The room controllers RXC10.1, the controller in a room-style housing: This controller is a cost-effective combination of a room unit and an HVAC controller.

Compact-series room controllers, RXC20.1, RXC21.1, RXC22.1 and RXC32.1 The input/output configuration and mounting options of these controllers make them ideal for fan coil applications. The RXC32.1 controller is particularly suitable for standard single-duct VAV systems. It comes with a built-in volume sensor.

Modular-series room controllers, RXC30/31 The basic units provide flexible control solutions which can be further enhanced with extension modules (RXC40/41) for lighting and blinds.

37/48

Page 38: Building Management Systems

The room unit: the key to individual comfort The DESIGO RXC range of room units covers the widely differing needs of room occupants. The designers of these stylish room units also took account of ergonomic factors.

The HVAC system, lighting and blinds can be operated in various ways: • In the conventional manner, with standard room units for HVAC and electric switches

to control lighting and blinds

Examples from the QAX3… range ... and the QAX50 range • The integrated room unit combines the operation of HVAC, lighting and blinds in a

single device. The keypad can be configured with the combination of buttons and switches best suited to the application.

Applications A range of predefined, downloadable applications makes DESIGO RXC highly versatile. The standard applications are available in a library covering various fields of application such as fan-coil units, radiators, chilled ceilings and integrated applications incorporating lighting and blinds.

Due to the fact that these applications are largely pre-defined, engineering is reduced to the definition of a small number of parameters.

Example of integrated applications The HVAC applications covered by the basic controllers RXC30.1 and RXC31.1 can be combined with control of lighting and blinds.

Electrical function Lighting zone Blind

Application HVAC application

On/Off1) Dimming control

Up/Down2)

INT01 CLC 2 x

INT03 CLC 2 x 2 x

INT05 CLC 2 x 4 x

INT15 VAV 2 x 2 x

INT17 VAV 2 x CLC: Chilled ceiling and radiator-type heating

T

Lux

70225

LON Controller + Extension modules

VAV: Variable air volume system

38

Page 39: Building Management Systems

Integration into the building automation and control system

QAX...PXC...

PXR

PPS2

01517

PXM20

BACnet / LON

DESIGO INSIGHT

RXC... QAX5...

PPS2

QAX...

LONMARK / LON

RXC...

QAX...

PPS2

PXC...-U

BACnet / Ethernet / IP

BACnetRouter

LONMARK

Management level

Automation level

Field level

Stand-alone operation at field level The room automation system can operate as a stand-alone system. All the required functions are achieved through LONMARK communications between the RXC devices.

Integration into the automation level DESIGO RXC can be integrated into the automation level via the PXR system controller, making possible a whole range of additional functions. The PXR converts LONMARK objects into BACnet objects and provides a comprehensive range of grouping functions.

The PXR system controller makes the following functions possible: • Concentration of data at room level, and easy manipulation of this data • Simple definition of groups • Implementation of system functions (time schedules, trends, alarm generation etc.) • Coordination with the primary plant

Integration into the management level Because it is integrated into the automation level, the room level can also be displayed and operated at the management level.

The control and operation of the RXC devices with DESIGO INSIGHT opens the way to a range of additional functions including the following: • Monitoring and operation of rooms, plus trend logging • Time schedules for building use and room occupancy • Integration of controller data into plant graphics • Central control of setpoints, operating modes, lighting, blinds etc.

39/48

Page 40: Building Management Systems

Integration using DESIGO OPEN The integration of third-party systems and equipment by use of DESIGO OPEN covers a wide range of building services including, for example, HVAC controllers, boilers, pumps and chillers, VSDs, energy metering and data analysis, fire detection, access control and security, electrical distribution, hotel booking systems, lighting, SCADA and many others.

Information can be exchanged as follows: • I/O-OPEN • via PX-OPEN system controller (PXE…) • via DESIGO INSIGHT-OPEN OPC • via standard BACnet communications (peer-to-peer)

01807de

PXC22PXC64-U mit PXM20

I/O open

BACnet auf LON oder Ethernet / IP

PXE

Drittsystem

RS232RS485

ev. Router ev. Router ev. Router

Drittsystem

DrittsystemBACnet conform

RS232

BACnet

ev. Router

Drittsystem

DESIGO INSIGHT

Querkommunikation via BACnet

Peer-to-peer communication Integration of third-party systems

The integration solutions offer numerous possibilities: • Mapping of data points to BACnet • Reporting and alarm functions • Time schedules and Calendar • Trend • Interaction with other PX automation

stations and system controllers

• Uniform operation at the automation level, using the PXM20 and/or PX-WEB

• Integration of standard protocols such as EIB, LON, PROFIBUS, M-bus and MODBUS

• Monitoring and management of third-party products with single-seat operation

40

Page 41: Building Management Systems

Some of the current solutions

Solutions at the management level INSIGHT-OPEN OPC-Client Integration of numerous OPC Server

applications INSIGHT-OPEN BACnet-Client Integration of BACnet devices using

OPC INSIGHT-OPEN EIB-Client Integration of EIB devices using OPC INSIGHT-OPEN LONWORKS-Client Integration of LON devices using OPC INSIGHT OPEN S7 Integration of the S7 PLC INSIGHT-OPEN Cerberus MK8000 Client Integration of the Siemens SBT fire and

security systems INSIGHT OPEN DEV Integration development kit

Solutions at the automation level PXE CRS hardware RS232 and RS485 physical connection PX-OPEN SCL Integration of simple protocols PX-OPEN Modbus MODBUS Master and Slave PX-OPEN MONITOR Communication analyzer PX-OPEN DEV Integration development kit

Solutions at the field level PTM1.RS… hardware platform RS232 or RS485 physical connection I/O–OPEN M-bus Integration of M-bus heat meters I/O–OPEN Grundfos Integration of Grundfos pumps I/O–OPEN Wilo Integration of Wilo devices I/O–OPEN DEV Integration development kit

41/48

Page 42: Building Management Systems

DESIGO TOOLSET and application blocks Professional software tools and a wide range of proven application blocks are available for engineering and processing the automation stations. The new programming language, D-MAP, based on standard IEC1131, is optimized for building services.

DESIGO TOOLSET DESIGO TOOLSET incorporates the following components:

Tool Function System Design Management of project data, selection and adaptation of

solutions, creation of system topology

PX Design Programming and commissioning

Router Design Commissioning of the BACnet routers

System Design Solution Browser System-Topologie Raumautomation

PX Design

BACnet Generator

Graphics Generator

DESIGO INSIGHT

Libraries Modified views

Router Design

PXC PXR PXE PXG

RXT10

Project Management

42

Page 43: Building Management Systems

System Design (with Project Management and Solution Browser) System Design includes project management functions such as the setting up and archiving of projects and the storage and relocation of project data for the commissioning phase. System Design is used to structure and specify plant and partial plant. From the library of pre-programmed and tested solutions, the engineer can use the Solution Browser to select and configure the solution best suited to customer requirements. System Design is also used to define the network topology, and to design any room management solutions and the integration of third-party systems. The number of automation stations required for the partial plant is calculated automatically. This is followed by the addressing of the data points.

PX Design PX Design is the graphics programming and configuration tool for DESIGO PX. PX Design supports the downloading of the application programs and the commissioning of the system.

The compounds, which themselves contain function blocks, represent tested solutions, selected via the Solution Browser. Where objects have been added or removed in System Design, it may be necessary to use PX Design to modify the compounds accordingly.

Router Design Router Design is used to configure the routers in the system.

43/48

Page 44: Building Management Systems

Application blocks The application libraries contain preconfigured and tested programs which can be used as the basis for individual customer solutions. The HVAC application architecture offers an overall view of typical heating, ventilation and air conditioning systems with distributed applications. It is structured in accordance with the "supply chains" (the flow of energy and media) in building services systems. The HVAC application architecture comprises application-specific functional units (software blocks) specifically designed to provide the user with the same "look and feel": • in a wide range of different types of building • for widely differing building services systems

in conjunction with automation systems from different manufacturers The building services plant is structured as follows:

1 Plant Examples: ventilation system, heating system 2 Partial plant Central supply air treatment, air distribution, hot water

supply (one or more boilers) 3 Aggregates Heating coil, energy recovery system, heating zone (as

part of the hot water distribution circuit) 4 Components Pumps (motors), dampers, valves, sensors, detectors,

limit switches, contactors, selector switches, remote/local switches

Room-based structures are as follows: 1 2 3 4

Components Sub-area Section Room

Building, Building wing, staircase, area Floor Individual room, hall

44

Page 45: Building Management Systems

Technical data

System View • Max. number of physical data points in the system 10000 ** • Max. number of sites specifiable in DESIGO INSIGHT 1000 * • Max. number of DESIGO INSIGHT management stations in the system 5 ** • Max. number of sites connected simultaneously to the

management station 10 **

Date per site: • Max. number of physical data points per site 6000 ** • Max. number of BACnet routers per site 50 ** • Max. number of PXC.., PXE.., PXR.. automation stations per site 50 ** • Max. number of PXM20 operator units per site 15 ** • Max. number of sites addressable from the PXM20 10 ** LON network • Max. number of PXC..., PXE..., PXR... automation stations per LON

network 30 **

• Max. number of physical data points per LON network 3000 ** • Max. number of PXM20 operator units per LON network 10 ** • Max. distance in meters per LON network 900 m* • Max. number of BACnet routers per LON network 1 * Automation station (PXC…, PXE…, PXR… or third-party device) • Max. number of physical data points per PXC… automation station 150 ** • Max. number of RXC… room controllers per PXR

– PXR 11 – PXR 12

60 *

120 * • Max. number of QAX units per PXC… 5 * • Max. number of COVs per PXC…, PXE… or PXR… 400 * Management station Operating system: Windows 2000 Notebook (typical) • Pentium processor 450 MHz • RAM 256 MB • Hard disk (storage capacity required by DESIGO INSIGHT <200 MB) 2 GB • CD drive Desktop computer (typical) • Pentium processor (700 MHz for PC with SQL server and shared

projects) 450 MHz

• RAM (for PC with SQL server and shared projects 512 MB) 256 MB • Hard disk >5 GB • CD drive • Monitor (17" or 21") • Back-up device (optional, e.g. MO, ZIP drive, CD RW etc.) File / Web server • Pentium processor >700 MHz • RAM 512 MB • Hard disk >5 GB • Communication via Ethernet or Token Ring Board • CD drive

* Hard-coded limitation

** Limitation based on test specifications

45/48

Page 46: Building Management Systems
Page 47: Building Management Systems

47/48

Page 48: Building Management Systems