18.04.2011 1 © BU Motors and Generators April 18, 2011 | Slide 1 Start here menu BU Motors and Generators training
130

BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

Apr 12, 2018

Download

Documents

truonghanh
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

1

© BU Motors and Generators April 18, 2011 | Slide 1

Start here menuBU Motors and Generators training

Page 2: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

2

© BU Motors and GeneratorsApril 18, 2011 | Slide 2

Dear Student,

Welcome to Technical introduction to motors and generators e-learningcourse program!

K110e

K111e

K112e

K113e

K114e

Database needed:

ABB Library, http://inside.abb.com/library (for ABB personnel only)

Inside web pages, http://inside.abb.com/ (for ABB personnel only)

External web pages: http://www.abb.com/motors&generators

Course administration:BU Motors and generators training

[email protected]

Questions and discussions

Technical assistance

•K115e

•K116e

•K117e

•K118e

Welcome to the Technical introduction to motors and generators e-learning course program!

This course program has been developed as an introduction to our products for new sales person in BU Motors and generators. It leads you to the basic electrical and mechanical structure of our motors and explains the technical details of the different types of motors and generators.

To study the courses, you will need access to ABB Library, ABB Inside and our external web pages.

Course consist of courses from K110e to K118e.

Even though this course is on the Internet and you can study alone where and whenever your want, please be active and ask questions. Our training team will assist you in this training, please send an e-mail to [email protected]

Page 3: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

3

© BU Motors and GeneratorsApril 18, 2011 | Slide 3

Course description

Course duration

Course type

Prerequisites and Recommendations

Main topics:

Basics of electrical motors and standards

DC Motors

HV Motors

LV Motors

Motors for explosive atmospheres

Servomotors

Synchronous motors and generators

Generators for wind turbine applications

Permanent magnet motors

These are a web-based training courses, which are designed to be studied according to your individual plan, usually within five weeks. The duration of the course depends on the participant. Each course is equivalent to 0,5 days classroom training.

The language of the course is English.

A basic knowledge and experience with using PCs and the Windows environment is recommended before attending the course. It is assumed users are new to e-learning software and methods. Course program K100e-K105e is recommended before studying Technical introduction to motors and generators course program.

Main topics are:

Basics of electrical motors and standards

DC Motors

HV Motors

LV Motors

Motors for explosive atmospheres

Servomotors

Synchronous motors and generators

Generators for wind turbine applications

Permanent magnet motors

Page 4: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

4

© BU Motors and GeneratorsApril 18, 2011 | Slide 4

Course material

Access to course material / See Notes page-text andattachments

Course material

Final exam

Course evaluation / feedback form

Turn on the volume to hear the recorded material

Choose Notes to see the whole course material. To exit from the unit, click Exit in the upper, right corner and Exit now. If you want to take a break in your studies, you can continue afterwards from were you left off by choosing Review and yes to resume your presentation. Once you start studying and open a unit, the status of this unit changes from Not Attempted to Incomplete. The status changes from Incomplete into Complete when you have studied all the material.

The Student binder for this course can be found from the course in the Attachments. In connection to this course there is a final exam. 50% of the questions have to be answered correctly to pass the course. Remember to turn on the volume if you want to hear the recordedmaterial

Please remember to fill in the course evaluation form. We highly appreciate your feedback since it helps us to improve the quality of the course. The information you give is treated in strict confidence.

Page 5: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

5

© BU Motors and GeneratorsApril 18, 2011 | Slide 5

Learning paths for motors and generators:http://fi.inside.abb.com/product/ap/seitp322/0e41c4bb2bfb6ceac12578080

05495d9.aspxCourse K110e is mandatory for all technical sales persons in BU Motorsand Generators

Learning paths

Please look up a terminology in TermBank

New employees in our motors sales have different educational backgrounds and work experience. Learning paths have been designed to help you to choose the correct courses for your individual needs.

This course program has been developed as an introduction to our products for new sales person in BU Motors and Generators. We recommend to start your studies with K110e Basics of electrical motors and standards e-learning course which is a mandatory course for all sales people. It leads you to the basic electrical and mechanical structure of our motors and explains the technical details of the different types of motors and generators. After completing this first course, you may continue with other courses within this course program starting from K111e to K118e. You are recommended to select the courses you deal with in your job area.

During your studies, you can look up a terminology through the Termbank linked in ABB Intranet.

Page 6: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

66

© BU Motors and GeneratorsApril 18, 2011 | Slide 6

Learning pathsTechnical introduction

K110e

G951e1_2

K111e E-learning courses

Seminars G977 G978

K112e G954/G982

K113e G952/G953/G982

K114e

K115e

K116e

K117e

K118e

Course program G951e Technical introduction has been replaced by course program K110e – K118e.

© ABB BU Motors and Generators April 18, 2011 | Slide 6

BU Motors and Generators training offers technical introduction for motors and generators e-learning course program: K110e-K118e (former G951e1_2-G951e10). You may still find some of these courses with the old code G951e. For more information about our learning paths, please see our web pages.

Code explanations:

K110e Basics of electrical motors and standards (G951e1_2)

K111e DC Motors (G951e3)

K112e High voltage motors (G951e4)

K113e Low voltage motors (G951e5)

K114e Motors and Generators for explosive atmospheres (G951e6)

K115e Servomotors (G951e7)

K116e Synchronous motors and generators (G951e8)

K117e Generators for wind turbine applications (G951e9)

K118e Permanent magnet motors (G951e10)

Former G951e Course program (G951e1_2 – G951e10) equals to courses K110e – K118e

G977 DC Motor sales tool training

G978 DC Motor hands-on training

G953 LV Motor training

G952 LV Motor technical training

G954 HV Motors and generators technical training

Page 7: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

7

© BU Motors and GeneratorsApril 18, 2011 | Slide 7

Reference materials to Motors:

http://inside.abb.com/product/us/9AAC133417.aspx

www.abb.com/motors&generators

Motor Guide

Low voltage Process performance motors

Low voltage Industrial performance motors

Low voltage General performance motors

High voltage induction motors technical catalogue

High voltage induction motors for Chemical, Oil andGas EN 02-2008

Motors for explosive atmospheres

DMI Catalogue

Reference material

During the courses you will need to refer to ABB’s internal or external web sites. Here you can also find links to catalogues which you can use during the course.

Page 8: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

8

© BU Motors and GeneratorsApril 18, 2011 | Slide 8

For information on our training events, please see:http://inside.abb.com/product/ap/seitp322/2e061a8c3afe448fc12578010026cede.aspx

K110e – K118e, produced for ABB, BU Motors and Generators,2011. First Edition (v.1.0)

Contact information:

Introduction to Motors and Generators

BU Motors and Generators trainingP.O.Box 633, FIN-65101 Vaasa, FinlandTel. +358-50 33 44350Fax. +358-10 22 47372e-mail:[email protected]

For information on our training events, visit us at motors and generators training web site.

The course program has been produced for ABB Business Unit Motors and Generators in 2011. This is the first edition, version 1.0, copyright 2011 by ABB, BU Motors and Generators

All rights reserved. No part of this document may be reproduced or copied without permission of ABB, BU Motors and Generators

Good luck and have fun in learning!

Page 9: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

9

© BU Motors and GeneratorsApril 18, 2011 | Slide 9

Page 10: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

10

© BU Motors and Generators April 18, 2011 | Slide 10

K110e Unit 1 Basics of electrical motors and generators

Page 11: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

11

© BU Motors and GeneratorsApril 18, 2011 | Slide 11

After completing this course module you will understand:

the basics of the electrical motor

the structure and demands of a motor

the physical background of the induction motor

the electrical structure of ABB's low and high voltage induction motors and generators

Objectives

After successfully completing this course module you will be able to describe the basics of the electrical motors and understand the structure and demands of a motor.

This module will also explain the physical background of the induction motor and the electrical structure of ABB's low and high voltage induction motors and generators, including the electrical motor components, torque and speed, power factor, efficiency, rating plate, winding, and insulation.

Page 12: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

12

© BU Motors and GeneratorsApril 18, 2011 | Slide 12

Electrical motor

More than half of the electrical energy produced is used by electrical motors

Electrical motors are used worldwide in many industrial, utility, commercial, or residential applications

Electricity is an important source of energy in our society. More than half of the electrical energy produced is used by electrical motors. Electrical motors are used worldwide in many industrial, utility, commercial, or residential applications.

Page 13: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

13

© BU Motors and GeneratorsApril 18, 2011 | Slide 13

Principles of action of electrical motors and generators

Used to convert mechanical power into electrical energy or vice versa

All rely on electromagnetic induction

Rotating electrical machines are used to convert mechanical power into electrical energy or vice versa. All electrical machines, whether motors or generators using direct or alternating current, rely on the principles of electromagnetic induction for their action.

Page 14: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

14

© BU Motors and GeneratorsApril 18, 2011 | Slide 14

Principles of action of electrical motors and generators

A conductor moving across a magnetic field creates an electromotive force (emf)

Resulting current flow and magnetic field around the conductor tend to oppose the motion that is producing the emf

A conductor moving across a magnetic field becomes the seat of an electromotive force (emf). The direction of the emf is in the right angle to both the direction of the motion and the direction of the magnetic field.

The amount of "induced“ voltage depends upon the length of the conductor actually in the field, the speed of the relative motion between the conductor and the magnetic field, and the strength of the magnetic field.

Because of the direction or polarity of the induced emf, the resulting current flow and the magnetic field around the conductor produced by it tend to oppose the motion that is producing the emf. The principle of this action can be presented in best for instance, an elementary generator consisting of a loop of wire that is mechanically rotated within a magnetic field.

Page 15: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

15

© BU Motors and GeneratorsApril 18, 2011 | Slide 15

Principles of action of electrical motors and generators

single-phase machinedelta connection

In the illustration, A will always be moving in the opposite direction of B, relative to the magnetic field, and hence emf induced in A will be in the opposite direction to that of B.

These two emfs, therefore, add up when the coil sides are connected as shown. When the coil side A is in position 1, it will be moving parallel to the direction of the magnetic field. There is no relative motion across the field and no emf is induced. When the coil has rotated 90° to position 2, it will be moving at right angles to the field and an emf is induced towards the observer’s direction, as shown by the arrows. Slip ring R1 will, therefore, appear to have positive polarity with regard to R2.

After a further 90° rotation, coil side A will again be moving parallel to the direction of the field and no emf will be induced. After a 270° rotation, in position 4, the coil side will again be moving at right angles to the field and an emf will be induced in the opposite direction to that of position 2 since the direction of movement is now reversed. Slip ring R1 will now appear to have negative polarity with regard to R2. This elementary generator produces an emf that is alternating in direction with a complete cycle of positive and negative changes taking place once per revolution. Since it is relative motion between conductor and field, which includes the emf, it matters little whether the conductor is moving in a stationary field system or whether the field system is moving within stationary conductors.

The alternator described in this example is known as a single-phase machine because there is only one circuit where the emf is induced. It is possible to install 3 separate groups. Now the stator has three separate groups of coils spaced 120 electrical degrees apart round the stator core. The voltages in each of these "phases" reach maximum values at different times as the magnetic field passes them in succession. The voltage, which appears between any of the 3 machine terminals, is that of two-phase windings in series. Since these are 120° out of phase, the terminal voltage is 1.73 times that of the voltage of one phase.

Alternatively, the end of one coil group can be connected to the start of another to form a closed loop, the joints forming the terminal connections. This is known as the delta connection. The terminal voltage is the same as that of each phase and the line current is shared between the phase windings.

Page 16: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

16

© BU Motors and GeneratorsApril 18, 2011 | Slide 16

Principles of action of electrical motors and generators

Video: rotation

Created by:Roger BusqueIngeniero Industrial & Master Project Manager por La Salle.Industrial Engineer & Master Project Manager by La Salle

Here is a video clip showing the rotation phase described in the previous page.

Page 17: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

17

© BU Motors and GeneratorsApril 18, 2011 | Slide 17

Principles of action of electrical motors and generators

To understand the basics, see:

Faraday's law

Fleming's left hand rule

The illustration shows voltage in three phases of a three-phase alternator. To understand the basics more deeply, take a look at the following web pages: About Faraday's law: http://en.wikipedia.org/wiki/Faraday's_law_of_induction and http://lectureonline.cl.msu.edu/~mmp/applist/induct/faraday.htm; About Fleming's left hand rule: http://en.wikipedia.org/wiki/Fleming's_left_hand_rule_for_motors It is not necessary to memorize the formulas, instead, try to understand the idea behind the theory.

Page 18: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

18

© BU Motors and GeneratorsApril 18, 2011 | Slide 18

Electrical motor componentsActive parts of an HV motor

Stator

Bearing

Bearing

Rotor

Here a high voltage motor/generator is illustrated. The basic construction of the AC induction motor is simple and has changed very little over the years. Next, we will discuss the basic components of a motor.

The stator windings are insulated copper wire, which are inserted into slots in the stator laminations. These slots have insulation between the windings and the steel laminations. This is called the "stator core". The different winding designs provide different output and speed combinations. The stator core is inserted into the stator frame. The ends of the winding are brought out through the motor casing to the terminal board in a terminal box mounted on the frame. This is where the mains leads are connected.

The rotor consists of laminations, the shaft, and the rotor winding or bars. The type of winding will depend on the type of motor required. If the rotor has a winding similar to that of the stator, it is known as a "wound rotor motor" (also known as a slip-ring motor). If the "winding" consists of solid bars that are joined at either end by a short-circuit ring, it is known as a "squirrel cage" motor. This is because the cage of the rotor resembles the cage that squirrels play with when in captivity. The bars are generally aluminum, but can be copper or any such material.

Aluminum is commonly used for LV induction motors and copper for HV motors and generators. The squirrel cage rotor motor is the most common type in use today as it requires simple control gear and, in most cases, can be used instead of a wound rotor motor. The stator core and rotor core constitute the active part of a motor. The bearings are used to support the shaft and to enable it to rotate.

Page 19: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

19

© BU Motors and GeneratorsApril 18, 2011 | Slide 19

Electrical motor componentsActive parts of an HV motor

Video: the rotor packet

Created by:Roger Busque

Here is a video clip showing the stator packet and rotor packet, which constitute the active part of a motor.

Page 20: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

20

© BU Motors and GeneratorsApril 18, 2011 | Slide 20

Electrical motor componentsActive parts of a LV motor

Rotor

Stator

Bearing

Bearing

The illustration shows an example of a low voltage motor. The main difference between a low voltage motor and a high voltage motor is the stator winding. The LV Motor is random-wounded, the HV Motor is form-wounded.

Page 21: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

21

© BU Motors and GeneratorsApril 18, 2011 | Slide 21

Electrical motor componentsActive parts of a LV motor

Video: rotorCreated by:Roger Busque

The rotor consists of laminations, the shaft, and the rotor winding or bars.

Page 22: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

22

© BU Motors and GeneratorsApril 18, 2011 | Slide 22

Voltage of a LV/HV motor and generator

Low voltage 0 < U ≤ 1 kV

Medium voltage 1 < U ≤ 6.6 kV

High voltage 6.6 < U ≤ 11.5 kV

Generator: Low Voltage: 0 – 1kVMedium Voltage: 1kV – 15 kV

Motors:

Internally, sometimes the terms 'medium voltage' and 'high voltage' motors/generators can be used. It is good to know the difference between them.

Page 23: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

23

© BU Motors and GeneratorsApril 18, 2011 | Slide 23© ABB BU Motors and GeneratorsApril 18, 2011 | Slide 23

Components of a HV motor/generator

© ABB BU Motors and GeneratorsApril 18, 2011 | Slide 23

The illustration shows an explosion view of a high voltage motor/generator (AMA).

Page 24: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

24

© BU Motors and GeneratorsApril 18, 2011 | Slide 24

Components of a LV motor

Fan cover

Fan

N-end

Rotor

Stator core &stator winding

Shaft

Bearing

Terminal box lid

Bearing

Frame

D-end

Terminal block

Terminal box

The illustration shows the main components of a low voltage motor. The active parts of the motor are: rotor, stator core, and stator winding.

Page 25: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

25

© BU Motors and GeneratorsApril 18, 2011 | Slide 25

Magnetism

The illustration shows the equivalence between apermanent magnet and a current.

A magnetic flux is created by the presence of magnetic poles, for example the north and south poles of a magnet. ‘Flux’ is a term for the magnetic flow from the north to the south pole. The illustration shows the equivalence between a permanent magnet and a current.

Page 26: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

26

© BU Motors and GeneratorsApril 18, 2011 | Slide 26

Magnetism

Video: Magnetic flux 1Created by:Roger Busque

Video: Magnetic flux 2Created by:Roger Busque

Video clips of Magnetic flux 1 and 2.

Page 27: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

27

© BU Motors and GeneratorsApril 18, 2011 | Slide 27

Magnetic field in a motor

FLUX

Stator core

Stator winding

Rotor packet

Rotor bar

Air gap betweenstator and rotor

When a three-phase AC voltage supply is connected to the stator windings, a rotating magnetic field is formed. This results a magnetic flux in the air gap where the torque of the motor is produced. The rotating magnetic fields produced by the stator induce a current into the conductive loops of the rotor. The rotor has conductive bars, which are short-circuited to form conductive closed loops.

The resulting form is similar to a squirrel cage. Once that occurs, the magnetic field causes forces to act on the current-carrying conductors, which results in a torque on the rotor.

Page 28: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

28

© BU Motors and GeneratorsApril 18, 2011 | Slide 28

Pole number

The pole number is the number of magnetizing poles generated by the stator winding

The pole number is the number of magnetizing poles generated by the stator winding. Poles exist in pairs, north and south poles, by the direction of the magnetic field, so the pole number is always an even number. One north pole (N) and one south pole (S) form one pole pair (p), and they follow each other.

Stator winding produces a rotating magnetic field when supplied with a three-phase AC system.

Page 29: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

29

© BU Motors and GeneratorsApril 18, 2011 | Slide 29

Magnetic field in a motor

The speed of the magnetic field rotating under a certain supply frequency depends on the pole number of the winding. Windings with different pole numbers differ from each other with regard to coil shape and location in the stator slots. Rotational speed of the magnetic field dependent on the winding pole number at 50 Hz supply frequency in the following way: 2-pole (2p=2) winding produces 3,000 rpm speed; 4-pole (2p=4) winding produces 1,500 rpm speed; 6-pole (2p=6) winding produces 1,000 rpm speed; and 8-pole (2p=8) winding produces 750 rpm speed. At 60 Hz supply frequency the speed values are 20 % higher. The abbreviation p stands for “pole pair number” and the abbreviation 2p means “pole number”.

Page 30: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

30

© BU Motors and GeneratorsApril 18, 2011 | Slide 30

Windings

Windings designed for a specific voltage and frequency

Slot windings used as

stator windings

rotor windings in the induction motors/generators

The windings are designed for a given voltage and frequency. Slot windings are used as stator windings and also as rotor windings in the induction motors/generators.

Page 31: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

31

© BU Motors and GeneratorsApril 18, 2011 | Slide 31

Stator winding

Random winding

Form wound winding

Windings in a motor provide a path for the AC current to flow along, which, in turn, produces the rotating magnetic field that causes the rotor to rotate.

Winding is done by putting conductive copper into the stator slots so that the current flowing in the copper generates a rotating magnetic field in the air gap between the stator and the rotor. This magnetic field grabs the rotor bars and forces the rotor to rotate along with the magnetic field. In one slot there can be up to 150 turns of copper in random wound winding and up to 50 in form wound winding.

There are two basic stator winding styles: random winding and form wound winding.

In random winding the copper used in the winding is in the form of wire and in any one slot the turns are more or less in random order. There are many different ways of doing random winding - some are more suitable for machine winding, others have superior mechanical strength or desirable effects on efficiency. Random winding is the winding style used for most low voltage motors.

In form wound winding rectangular copper wires are used instead of round wires. Form wound winding is used when high voltage motors and generators are wound.

The stator winding design of the HV motors and generators combines the class F insulation system with vacuum pressure impregnation (VPI). This method has been used since 1977 and is well known for its high reliability. While the insulation meets the requirements of the thermal class F (temperature limit 155oC), the motors are normally rated to class B, which gives a good overload margin and provides a long life. The basic impulse level exceeds IEC requirements. The windings are designed to cope with the highest mechanical stresses, including the effects of rapid auto-reclosure in phase opposition.

Page 32: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

32

© BU Motors and GeneratorsApril 18, 2011 | Slide 32

Poles Winding Diagram

Single layer

2p = 4 poles

Q1 = 72 slots

q1 = 6 slots (for every pole of every phase)

W = 15 teeth (between entrance and exit of one turn)

The diagram is a tool for transferring information between the designer and manufacturing. For different pole numbers there are different winding diagrams to indicate the order of the wires. In a winding diagram every phase is marked with a different color.

Page 33: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

33

© BU Motors and GeneratorsApril 18, 2011 | Slide 33

Insulation

Insulation systems are dimensioned according to:

voltage level

Supply voltage type

environmental conditions

Endurance tests when new insulation systems are developed:

electrical aging

thermal aging

mechanical aging

aging due to surrounding conditions

combined aging

Insulation systems are dimensioned according to several factors: voltage level, supply voltage type (DOL = Direct On Line, PWM-converter, cycloconverter), environmental conditions, for example, height of the site above sea level, temperature, and humidity.

Endurance tests are needed when new insulation systems are developed. Typical endurance tests are electrical aging, thermal aging, mechanical aging (for example vibration), aging due to surrounding conditions, and combined aging (for example, thermal and electrical). Aging tests are typically very long lasting, even years. To reduce the time, they are normally done as so-called accelerated tests with higher stresses (for example, voltage and frequency and temperature) than in real operation. The life-times corresponding to the stresses in real operation can be calculated from these results.

When developing insulation systems, the manufacturing point of view also has to be taken into account, in other words, how to manufacture reliably and economically without occupational safety problems.

Page 34: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

34

© BU Motors and GeneratorsApril 18, 2011 | Slide 34

DC motors winding and insulation

Windings designed for a specific voltage

Coils used as stator windings

Slot windings used as rotor windings

The windings are designed for a given voltage. Coils are used as stator windings, and slot windings are used as rotor windings in these motors or generators.

Page 35: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

35

© BU Motors and GeneratorsApril 18, 2011 | Slide 35

DC Motor stator winding

The main tasks of the DC motor stator:

produce a fixed magnetic flux to interact with the armature

house the commutating windings and compensation windings

Main components of the stator:

frame of laminated electroplates

main poles and interpoles of laminated electroplates,

stator windings and commutation windings of varnish-insulated copper wire

compensation windings (not DMI 180-225)

The windings in the motor provide a path for the DC current to flow along, which, in turn, produces the rotating magnetic field that causes the rotor to rotate.

The main task of the DC motor stator is to produce a fixed magnetic flux to interact with the armature. This is done by the excitation winding. The stator also houses the commutating windings and compensation windings, which are auxiliary devices that are used to prevent deformation of the main flux.

A compensation winding is installed on the magnetic poles of the stator to smoothen the field across the pole. Without the compensation winding the left side of the N-pole would get saturated because of the additional magnetic field.

Commutating windings or interpoles are installed between the magnetic poles to straighten the magnetic field.

Because of armature reaction, the magnetic field bends and causes misplacement in the inducted voltage at the armature winding.

The main components of the stator are: frame of laminated electroplates; main poles and interpoles of laminated electroplates; stator windings and commutation windings of varnish-insulated copper wire; and compensation windings (not DMI 180-225).

Page 36: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

36

© BU Motors and GeneratorsApril 18, 2011 | Slide 36

DC 6 Poles winding diagram

The winding diagram indicates the order of the wires, as shown in this diagram for 6 poles.

Page 37: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

37

© BU Motors and GeneratorsApril 18, 2011 | Slide 37

DC Insulation

Insulation system:

moisture-resistant

suitable for use in tropical climates without modification

Armature coils and stator windings have dual insulation coats

Copper wire insulation, the Nomex and the impregnation varnish have a temperature index above class H

The motors comply with the requirements of Class 200 /H insulation. The insulation system is moisture-resistant and is suitable for use in tropical climates without modification. The armature coils and stator windings have dual insulation coats. The base coat is a polyesterimide with a top coat of polyamide-imideenamel. The insulation to earth is of amid fiber (Nomex). All windings are impregnated with varnish, which gives high mechanical strength.

The copper wire insulation, the Nomex and the impregnation varnish have a temperature index well above class H. There is, therefore, a high margin of safety in addition to the high overload capacity.

Page 38: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

38

© BU Motors and GeneratorsApril 18, 2011 | Slide 38

Page 39: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

39

© BU Motors and Generators April 18, 2011 | Slide 39

K110e Unit 2 Torque, speed and formulas

Page 40: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

40

© BU Motors and GeneratorsApril 18, 2011 | Slide 40

Torque and speed of an AC motor

locked-rotor torque

pull-up torque

breakdown torque

An asynchronous motor is a motor whose rotor does not rotate at exactly the same speed as the stator field. The locked-rotor torque is the minimum measured torque the motor develops at its shaft extension with the rotor stationary and the rated voltage and frequency applied.

The pull-up torque is the smallest torque the motor develops between zero speed and the speed corresponding to the breakdown torque when the motor is supplied with the rated voltage and frequency. This definition does not apply to induction motors, whose torque continuously decreases with increasing speed. This value applies to the usual mean torque characteristic, which excludes transient effects. The breakdown torque is the maximum torque the motor develops with the rated voltage and frequency applied at the operating temperature and when constantly loaded. This term does not apply to motors whose torque steadily decreases with increasing speed. They do not have definite breakdown torque. If the rotor is mechanically driven by an external machine at a speed that is greater than that of the rotating magnetic field, with the machine connected to the power network and the direction of rotation the same as that of the stator field, the asynchronous machine becomes an asynchronous generator. The asynchronous generator returns the power applied mechanically to its rotor as electric power to the network, in this case over-synchronously because the slip is negative. The rotor currents are reversed and the torque produced opposes the rotation of the machine, that is, it tends to retard it.

Page 41: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

41

© BU Motors and GeneratorsApril 18, 2011 | Slide 41

AC Speed - magnetic field

[ ][ ]

numberpole120f

n HzRPMs

×=

The synchronous speed can be calculated with the formulas

The speed of the rotating field is constant and it rotates at synchronous speed. The synchronous speed is dependent on the frequency and the pole number of the winding. The synchronous speed can be calculated with the formula shown in this slide. The synchronous speed of the motor is determined by the frequency of the supply voltage and the pole number of the motor. f in the formula stands for Electrical frequency in Hz (50Hz or 60 Hz).

Page 42: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

42

© BU Motors and GeneratorsApril 18, 2011 | Slide 42

AC Voltage versus time

An AC Voltage is defined by the value of volts and the frequency. p = Number of pole pairs (=number of poles / 2). The flux is rotated at a speed called "synchronous speed", corresponding to the electrical frequency of the network and to the number of pole pairs. As long as the rotor is rotated at synchronous speed, no current is induced in the rotor bar, and consequently no torque is developed by the motor. Current only exists in the rotor bar if the speed of the rotor (n) is below the synchronous speed (as soon as a load torque is applied to the shaft), which means that the speed of the rotor does not rotate at synchronous speed, and the rotor speed lags behind the speed of the magnetic field. In a case of generating, the speed of the rotor is above the synchronous speed.

Page 43: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

43

© BU Motors and GeneratorsApril 18, 2011 | Slide 43

AC Torque curve

The difference between the rotating speed of the flux and the rotating speed of the rotor is called the slip of an asynchronous motor (the opposite of synchronous machines, where no slip exists, even in the presence of load torque).

Page 44: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

44

© BU Motors and GeneratorsApril 18, 2011 | Slide 44

Slip

The slip can be expressed in either rpm or per unit

n = nominal speed

ns = synchronous speed

[ ] nnSlip sRPM −=

[ ]s

s% n

nnSlip −=

e.g. 1000 rmp – 992rpm

e.g. 1000 rmp – 992rpm1000 rmp

The slip can be expressed in either rpm or per unit, as is shown in the formulas. n stands for nominal speed and ns stands for synchronous speed.

Page 45: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

45

© BU Motors and GeneratorsApril 18, 2011 | Slide 45

Torque v.s. speed for Asynchronous motor

The illustration shows the effect of increased speed on torque for an asynchronous motor. The magnitude of the (mechanical) torque available at the shaft depends on the magnitude of the slip – that is, on the amount the rotor speed lags behind the speed of the rotating magnetic field. The relationship between the torque and the speed of the motor is illustrated by the speed-torque characteristic.

Page 46: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

46

© BU Motors and GeneratorsApril 18, 2011 | Slide 46

Torque v.s. speed for Synchronous motor

The illustration shows the effect of increased speed on torque for a synchronous motor.

Page 47: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

47

© BU Motors and GeneratorsApril 18, 2011 | Slide 47

Torque

An increase in power increases the torque, whereas an increase in speed decreases the torque

T = Torque (Nm)

P = Output power (kW)

n = Speed (r/min)

Torque is generated when the magnetic field of the stator winding forces the rotor bars to turn around the centre of the axis shaft. From the equation one can see that an increase in power increases the torque, whereas an increase in speed decreases the torque. These three features are bound by the fact that T * n / P is always 9550. In the equation: T = Torque (Nm); P = Output power (kW); and n = Speed (r/min). When calculating torque, it is important to take into account: the starting torque; the maximum torque; the starting current; and the minimum torque.

Page 48: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

48

© BU Motors and GeneratorsApril 18, 2011 | Slide 48

Torque

This graph is typical for an LV motor. It shows the Torque/speed curve. The shape of the torque/speed curve is determined by the slot shapes and slot alignment in the stator and rotor. The level of the Nominal torque is determined by the winding (number of turns). According to IEC, the maximum torque (Tmax) of the motor should always be more than 1.6 times the nominal torque (Tn). At a speed of 0 rpm the motor can give starting torque (Ts). This Ts should be big enough to counter the decelerating masses of the load and rotating rotor body in less than the given maximum permitted starting time.

Page 49: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

49

© BU Motors and GeneratorsApril 18, 2011 | Slide 49

Torque

This graph is typical for an MV or large motor. The minimum torque (Tmin) is not always at 0 rpm, for example a double cage rotor has minimum torque at around 0.7 times the nominal speed. This should be taken into account when dimensioning motors for constant torque applications. At direct-on-line start the torque produced by the motor has to be greater than the load torque (with reasonable gap) at any speed. If the load torque at any speed is greater than the torque created by the motor, the motor will not be able to start or achieve nominal speed.

Page 50: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

50

© BU Motors and GeneratorsApril 18, 2011 | Slide 50

Torque

The starting current of large motors may cause voltage dips, especially in weak grids. Therefore, motors have to be able to start with reasonable under voltage.

Page 51: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

51

© BU Motors and GeneratorsApril 18, 2011 | Slide 51

Torque

Page 52: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

52

© BU Motors and GeneratorsApril 18, 2011 | Slide 52

Torque

A high current is generated when an asynchronous motor is switched on. The starting current depends on the motor design; the value is usually between 6.5 and 7.5 times the nominal current and the shape is determined by the same parameters as the torque design.

The illustration shows the "shape" of torque and current versus speed for small motors.

Page 53: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

53

© BU Motors and GeneratorsApril 18, 2011 | Slide 53

Torque

The illustration shows the "shape" of torque and current versus speed for large motors.

Page 54: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

54

© BU Motors and GeneratorsApril 18, 2011 | Slide 54

Formulas

T(Nm) =60 000

2π[ ]x[ ]P(kW)

n

T(Nm) = 9549.30[ ]x[ ]P(kW)

n

P(kW) = T(Nm) x w(rd/s) / 1000

ω(rd/s) = 2pn / 60 (where n is rpm)

P(kW) = T(Nm) x n x 2p / 60 000or

Torque is the rotational equivalent of linear force and, for any rotating machine, if Power and Speed are known, the Torque is given by the formula shown in the blue background. In the formula: T = Torque (Nm), P= Output power (kW), and n= Speed (r/min).

In the formula , 9550 is a constant, which can be calculated with the either of the formulas shown on the right.

Page 55: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

55

© BU Motors and GeneratorsApril 18, 2011 | Slide 55

Operation

DCMotor

IA

If

Ud E

Φ

( )

( )

( )( )φ××−=

×+=φ××=

−=

−==φ

×φ×=

kIRUn.7

IREU.6nkE.5R

EUI.4

TTT.3If.2

IkT.1

Aid

Aid

i

dA

loadoutputAcc

f

Aoutput

(1) The output torque of the motor is proportional to the armature current as long as (2)the excitation is kept constant.

(3) If the output torque exceeds the load torque, there is acceleration torque and the speed of the motor starts to increase.

(4) The armature current and, accordingly, the output torque can be increased by increasing the voltage supplied by the DC converter.

(5) When the armature starts to rotate through the magnetic flux of the stator, a voltage (emf) is induced, the polarity of which is the opposite of the supply voltage.

(6) To maintain the current (and torque), the supply voltage has to be increased as the speed and armature emf increase. The speed can be controlled by the supply voltage until the nominal armature voltage has been reached.

(7) This normally coincides with reaching the maximum output voltage of the supplying DC converter. The speed range from standstill up to this point is called the basic speed range. To increase the speed above the basic speed range, the armature emf has to be decreased.

As we have seen (5), the armature emf depends on excitation as well as speed. The speed can be further increased by decreasing the excitation (7). However, since torque is a direct function of excitation (2), from this point on the available torque decreases in inverse proportion to the speed. This speed range is called the field weakening speed range. For motors without compensation windings the relationship between basic and field weakening speed range is 1:3, and for compensated motors 1:5. The ultimate speed limit of a DC motor is set by mechanical parameters.

Page 56: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

56

© BU Motors and GeneratorsApril 18, 2011 | Slide 56

Controlling torque and speed by excitation

Basic Speed FieldWeakeningSpeed

nb nmax

UN

IN

IN

TN

PN

UA

IA

If

T

P

n

Armature Voltage

Armature Current

Excitation Current

Torque

Power

As is evident from equations 1 and 2, it is also possible to control the magnitude and direction of the torque entirely by varying the field current. Nevertheless, this is rarely done in modern drives, because the excitation winding has a much higher impedance than the armature, which makes torque by this method slower.

Page 57: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

57

© BU Motors and GeneratorsApril 18, 2011 | Slide 57

DMI Motor characteristicsTorque as a function of speed

0

0,2

0,4

0,6

0,8

1

1,2

0 1 2 3 4 5 6

Speed [rpm]

Torq

ue (N

m)

Constant Torque(P=k x n)

Constant Power(P=k)

Commutation limit(P=k/n)

Commutation Limit(compensationwinding)Mechanical Limit

Torque

Basic Field Weakening

This graph demonstrates the relationship between torque and rotational speed (RPM).

Maximum torque is generated when the rotor is stationary and to a very low speed. In the range for Constant power, torque drops off sharply, while the power generated is at a maximum.

The commutation limit is where both torque and power fall due to limitation of current flow by the resistance of commutator brushes and the maximum voltage that can be applied across each winding.

The mechanical limit is the maximum safe speed of the rotor.

Page 58: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

58

© BU Motors and GeneratorsApril 18, 2011 | Slide 58

DMI Motor characteristicsPower as a function of speed

0

0,2

0,4

0,6

0,8

1

1,2

0 1 2 3 4 5 6

Speed [rpm]

Pow

er (k

W)

Constant Torque(P=k x n)

Constant Power(P=k)

Commutation Limit(P=k/n)

Commutation Limit(compensationwinding)Mechanical Limit

Power

Basic Field Weakening Speed Range

This graph demonstrates the relationship between power and rotational speed (RPM).

Maximum torque is generated when the rotor is at an optimum speed.

In the Constant Torque range, power developed rises sharply until it reaches its maximum. This maximum power output is maintained across a range of rotation speed.

Again, the limitations of the commutator design for DC motors is shown by the fall of the power generated even as the motor speed increases.

Page 59: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

59

© BU Motors and GeneratorsApril 18, 2011 | Slide 59

Speed trimming

UN

IN

IN

TN

PN

UA

IA

If

T

P

n

Armature Voltage

Armature Current

Excitation Current

Torque

Power

Nominal Speed Trimmed Speed

nmax

If the basic speed range is too low but the available torque is sufficient, permanently field weakening the motor can expand the basic speed range. This is referred to as trimming. Adjustment of the base speed of DMI motors by speed trimming should not exceed 30% of the nominal base speed.

Page 60: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

60

© BU Motors and GeneratorsApril 18, 2011 | Slide 60

Electrical formulas

Calculation of the torque [Nm]:

Calculation of the nominal speed [rpm]:

T = Torque [Nm]

P = Output power [kW]

n = Speed [r/min]

[ ][ ]

[ ]RPM

kWNm n

9550PT

×=

[ ][ ]

numberpole120f

n HzRPM

×=

In many cases motor selection can be calculated manually. The most important formulas can be found in this section.

The basic formulas for calculating the torque and the nominal speed are shown in the slide.

In the formulas: T = Torque [Nm], P = Output power [kW], and n = Speed [r/min]. If there is a gearbox between the driven equipment and the motor, the following things should be taken into consideration when selecting a motor: the power [kW] is equal for the both speeds, the torque [Nm] will vary according to the ratio, and the moment of inertia J [kgm2] varies quadratically to the ratio.

Page 61: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

61

© BU Motors and GeneratorsApril 18, 2011 | Slide 61

Formulas

Load torque

Motor torque

0

0,5

1

1,5

2

2,5

3

3,5

0 500 1000 1500 2000

Speed r/min

Resultant operating pointwhere load torque curvecrosses motor torque /speed curve

TL

T / TN

In this example case we select a suitable motor according to the following criteria:

Fan or Pump duty = Quadratic torque

LV cast iron motor

Supply Frequency is 50Hz

Supply Voltage is 400V

Load speed range is 0 - 1 500 r/min, and

Load is 108 kW at approximately 1500 r/min.

To choose the right motor,

Calculate the torque with the formula T = 108kW x 9550 / 1500rpm) = 688NM.

Check the catalogue. The nominal torque at least 688Nm.

The correct motor type is M3BP 315SMA 4.

Page 62: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

62

© BU Motors and GeneratorsApril 18, 2011 | Slide 62

Different environments

To choose the correct motor:

1. Calculate the efficiency and power factor.

2. Check the Motor guide for ambient factors.

3. Calculate the required output.

4. Check the efficiency in the Motor Guide.

5. Check the power factor in the Motor Guide.

In this example we select the suitable motor type according to the following criteria and environmental conditions: LV cast iron motor, Ambient temperature +50oC, Altitude 2500 m, Class B temperature rise, 380 V, 50 Hz supply, and 55 kW, 988 RPM. To choose the correct motor: 1. Calculate the efficiency and power factor. 2. Check the Motor guide for ambient factors: Temperature x Altitude = 0.93 x 0.88 = 0.8184. 3. Calculate the required output: At least (55kW / 0.8184) = 67.2 kW. Motor: M3BP 315SMA 6 (Nominal output 75kW). 4. Check the efficiency in the Motor Guide, page 66, table for Efficiency: 55kW / 75kW = 73% --> 75% Efficiency = 0.95. 5. Check the power factor in the Motor Guide page 69, table for Power Factor: 55kW / 75kW = 73% --> 75% Power Factor = 0.76. Note that MotSize can be used for making the calculations and datasheets for LV motors, and Cuusamo for HV motors and generators.

Page 63: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

63

© BU Motors and GeneratorsApril 18, 2011 | Slide 63

Some useful conversion factors (US -> SI)

Power: 1hp (UK, US) = 0.746 kW

Inertia: 1lb - ft2 = 0.04214 kgm2

Torque: 1 lb - ft = 1.355818 Nm

Temperature:

Mass: 1 lb = 0.454 kg

°C = (°F-32)59

Here are some useful conversion factors from US to SI units. The conversion factors for power, inertia, torque, temperature, and mass are shown.

Page 64: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

64

© BU Motors and GeneratorsApril 18, 2011 | Slide 64

Starting methods: Direct-On-Line (DOL) starting

Direct-on-line starter only required starting method when motor is connected directly to the mains supply

Preferred starting method

Limitation: high starting current

The simplest way to start a squirrel cage motor is to connect it directly to the mains supply. When it is connected directly to the mains supply, a direct-on-line (DOL) starter is the only starting equipment required. However, the limitation with this method is that it results in a high starting current. Still, it is the preferred method, unless there are special reasons for avoiding it.

Page 65: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

65

© BU Motors and GeneratorsApril 18, 2011 | Slide 65

Starting methods: Y/D starting

The graph shows a Y-D start where the starting current is about 2,2 times the nominal current. The torque values in the Y connection are much lower than in the D connection, which is why dimensioning motors for Y-D starts should be done with care, especially in bigger motors.

If it is necessary to restrict the starting current of a motor due to supply limitations, the Y/D method can be employed. This method where, for instance, a motor wound 400 VD is started with the winding Y connected will reduce the starting current to about 30 per cent of the value for direct starting. The starting torque will be reduced to about 27 per cent of the DOL value.

However, before using this method, one must first determine whether the reduced motor torque is sufficient to accelerate the load over the whole speed range.

The starting time depends on the characteristics of the load and on the starting method. Large inertias of the load will cause long starting times, which can cause overheating in the motor.

It is important to remember that the term ‘starting current’ refers to the steady-state rms value. This is the value measured when, after a few cycles, the transient phenomena have died out. The transient current, the peak value, may be about 2.5 times the steady-state starting current, but it decays rapidly. The starting torque of the motor behaves in a similar way, and this should be taken into account if the moment of inertia of the driven machine is high, since the stresses on the shaft and coupling can be very great.

Please contact your nearest sales office for the MotSize calculation program.

Page 66: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

66

© BU Motors and GeneratorsApril 18, 2011 | Slide 66

Starting methods

The different starting methods of a motor are evaluated to satisfy the voltage drop requirement.

Page 67: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

67

© BU Motors and GeneratorsApril 18, 2011 | Slide 67

Power factor

ϕ= cos*FF APPARENTUSEFUL

The relationship between the useful force and the apparent force is calculated as shown in the formula.

Page 68: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

68

© BU Motors and GeneratorsApril 18, 2011 | Slide 68

Power factor

Active power (W)

Reactivepower (VAR)

heat

ϕ

magnetic field

Q

P

Apparent power (VA)

S

The power factor (=cos j) is a relevant characteristic of each motor, defining the active power used for running the motor. This factor also depends on the need for a magnetic field to create the flux: reactive power.

Page 69: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

69

© BU Motors and GeneratorsApril 18, 2011 | Slide 69

Power factor

ϕ= cos*I*U*3PINPUT

The power factor indicates the need of reactive power Q compared with effective power P. A power factor of 1.0 means that the machine only draws effective power from the supplying network. The power factor of the induction motor should be 0.85-0.95. Power factors are likely to be lower in certain special cases, for example with multi-speed motors, motors with a high pole number, down-rated motors, and motors with frame sizes below 100. The power factor is determined by measuring the input power, voltage, and current at the rated output. The effective input power (active power) in the motor is given by the formula.

Page 70: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

70

© BU Motors and GeneratorsApril 18, 2011 | Slide 70

Benefits of a high power factor

Feasible to transmit only effective power through the electrical network

Production or compensation can be made with synchronous machines or capacitors

A high power factor has the following benefits:

It is feasible to transmit only effective power through the electrical network, so if the motor draws reactive power from the network, Q should be produced somewhere near the load. Production or compensation can be made with synchronous machines or capacitors. Power companies charge more for this compensation than the price of effective power P, hence a high power factor is a desirable feature in an electrical motor.

Page 71: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

71

© BU Motors and GeneratorsApril 18, 2011 | Slide 71

Page 72: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

72

© BU Motors and Generators April 18, 2011 | Slide 72

K110e Unit 3 Basics of efficiency

Page 73: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

73

© BU Motors and GeneratorsApril 18, 2011 | Slide 73

Efficiency

ABB Motors are designed to meet changing world attitudes towards energy efficiency and motor performance. For instance, by increasing the efficiency in the production processes, and installing energy-efficient devices, industrial processes will consume less electricity and by this play a significant part in reducing CO2 emissions. An energy-efficient motor produces the same output power (torque) but uses less electrical input power (kW) than a motor with lower efficiency

Page 74: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

7474

© BU Motors and GeneratorsApril 18, 2011 | Slide 74

Efficiency, definition

Efficiency is ratio between mechanical output and electrical input High efficiency means that the motor is converting electrical power to mechanical power with small losses

U I P cosφ

PPOutput

rpm

loadload

PPInput

LossesP∑

P Output=η

InputP

=ηPOutput

Σ PLossesPOutput +

PInput

=ηΣ−PInput PLosses

Energy supply

Efficiency is ratio between mechanical output and electrical input. To the left you can find the formula for energy efficiency.

High efficiency means that the motor is converting electrical power to mechanical power with small losses.

Page 75: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

7575

© BU Motors and GeneratorsApril 18, 2011 | Slide 75

Pinput = Electrical power inputPoutput = Mechanical power

output

Pfriction & windage

Poutput

PLL

Pwinding

Pinput Piron

Protor

Stator winding losses (Pws)Rotor losses (Pwr) Iron losses (Pfe)

Additional load losses (PLL)

Additional load losses are due to:Friction + Windage losses (Pfw) leakage flux, mechanical imperfections

in the air gap and irregularities in the air gap flux density

Losses split into five major areas

Additional load losses (PLL): Stray losses, all other losses ( ~ 15% of all losses). Additional load losses are losses that are not clearly or easily measured. “indefinite”.

Page 76: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

7676

© BU Motors and GeneratorsApril 18, 2011 | Slide 76

Losses and efficiency in electrical motors

Electrical energy in(Pin)

Mechanical energy out (Pout)

Pcu1 35 %Stator winding

Pcu2 20 %Rotor winding

PFe 20%Iron

PFr Friction 10 %

PLL 15 %Additional

Pout 94 %

Mechanical energy out

Losses 6 %

PoutηPin

= 100 x [%]

Description of typical losses for a LV motor, the percentage of all losses are given based on the old standard:

Friction (P friction): Caused by the fan and bearings. This loss is independent of the load (P output) ( ~ 10% of all losses)

Iron (P iron): Needed energy to magnetize the motor ( ~ 20% of all losses)

Winding (P winding): Heat created by the current running in the windings ( ~ 35% of all losses)

Rotor (P rotor): Heat created in the rotor ( ~ 20% of all losses)

Additional load losses (PLL): All other losses ( ~ 15% of all losses). Additional load losses are losses that are not clearly or easily measured.

Page 77: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

7777

© BU Motors and GeneratorsApril 18, 2011 | Slide 77

Efficiency measurement methodsIEC 60034-2-1; 2007

IEC/EN 60034-2-1: 2007 establishes harmonized methods for determining efficiencies of rotating electrical machines and also the methods of obtaining specific losses

Covers asynchronous, synchronous and DC electrical machines

Published by the International Electrotechnical Commission in September, 2007

The efficiency measure method was published by the International Electrotechnical Commission in September, 2007.

The standard establishes harmonized methods for determining efficiencies of rotating electrical machines and also the methods of obtaining specific losses. It covers asynchronous, synchronous and DC electrical machines

Page 78: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

7878

© BU Motors and GeneratorsApril 18, 2011 | Slide 78

IEC offers two ways of measuring efficiencyDirect method

Measurement of the input power based on voltage and current, and the output power based on rotational speed and torgueNo change compared to the old IEC 60034-2

Indirect methodMeasurement of the input power and calculation of the output power based on the losses of motor

Specifies following parameters for measuring efficiency according to indirect method:

Reference temperatureThree alternatives for determining additional load losses

MeasurementAssigned valueMathematical calculation

Efficiency measurement methods IEC 60034-2-1; 2007

Using the direct method, the MECHANICAL power on the shaft and the ELECTRICAL power on the terminals have to be measured.

The efficiency is then calculated as the ratio between the mechanical and the electrical power.

As it is very difficult and expensive to purchase and maintain equipment to measure the exact mechanical power, the indirect method is used.

Using indirect method, measurement of the torque and speed is carried out at different loads. Based on these measurements, the additional load losses are calculated.

Indirect method is also called the summation of losses method.

IEC’s new method is closer to the IEEE method

Page 79: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

7979

© BU Motors and GeneratorsApril 18, 2011 | Slide 79

Winding, rotor, iron and frictions losses can be determined from input power, voltage, current, rotational speed and torgue

Additional losses PLL are much more difficult to determine

IEC/EN 60034-2-1 specifies different methods to determine the additional losses :

Low uncertainty – measurement (IEEE 112-B & CSA390-98)

Medium uncertainty – assigned value and/or mathematical calculation

High uncertainty – assigned value

Which method can be used depends on the motor efficiency class determined by IEC/EN 60034-30

IEC 60034-2-1; 2007Losses and uncertainty of measurement

You can find more detailed information about the low, medium and high uncertainty from Table 2 in the IEC/EN 60034-2-1 standard.

IEC/EN 60034-30 defines which IE classes are connected to which method.

Page 80: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

80

© BU Motors and GeneratorsApril 18, 2011 | Slide 80

Page 81: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

81

© BU Motors and Generators April 18, 2011 | Slide 81

K110eUnit 4 General about standards

Page 82: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

82

© BU Motors and GeneratorsApril 18, 2011 | Slide 82

Objectives

This course module gives an overview of the standards concerning electrical motors and generators

After successfully completing this module, you will be able to recognize the different electrical and mechanical requirements of the commonly used standards (IEC, NEMA)

This course module presents a brief overview of the standards concerning electrical motors and generators.

After successfully completing this module you will be able to recognize the different electrical and mechanical requirements of the commonly used standards IEC and NEMA.

Page 83: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

83

© BU Motors and GeneratorsApril 18, 2011 | Slide 83

Standard definitions

Standard:

technical specification or other document available to the public

based on the consolidated results of science, technology and experience

aimed at the promotion of optimum community benefits and approved by a body recognized on the national, regional or international level

The most common standards in the motor business:

IEC

EN

NEMA

Standard is defined in the following way:

"A technical specification or other document available to the public, drawn up with the cooperation and consensus or general approval of all interests affected by it based on the consolidated results of science, technology and experience, aimed at the promotion of optimum community benefits and approved by a body recognized on the national, regional or international level. In some languages the word "standard" is often used with another meaning than in this definition, and in such cases, it may refer to a technical specification which does not satisfy all the conditions given in the definition, for example: "company standard". (www.tsk.fi)

ABB low voltage standard motors and generators are of the totally enclosed, three phase squirrel cage type, built to comply with international standard IEC-standards, CENELEC and relevant VDE-regulations, and DIN-standards. Motors conforming to other national and international specifications are also available on request.

All ABB motor production units are certified to ISO 14001 international quality standard and conform to all applicable EU Directives.

ABB strongly supports the drive to harmonize European standards and actively contributes to various working groups within both IEC and CENELEC.

Page 84: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

84

© BU Motors and GeneratorsApril 18, 2011 | Slide 84

Standard definitions

Directive:

EC document issued by the European Community

aimed at harmonizing national provisions to ensure the environment and safety aspects within each State

published in the Official Journal of European Communities (OJEC)

CE as proof of conformity to the following directives:

Low Voltage Directive 73/23/EEC, amended by 93/68/EEC

EMC Directive 89/336/EEC, amended by 92/31/EEC and 93/68/EEC

A directive is an EC document issued by the European Community, the aim of which is to harmonize national provisions to ensure the environment and safety aspects within each State. A directive is published in the Official Journal of European Communities (OJEC).

Products are stamped "CE" as proof of conformity to the following directives: Low Voltage Directive 73/23/EEC, amended by 93/68/EEC and EMC Directive 89/336/EEC, amended by 92/31/EEC and 93/68/EEC. Refer to the EC Declaration of Conformity delivered with each motor.

Page 85: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

85

© BU Motors and GeneratorsApril 18, 2011 | Slide 85

IECEx System

The IECEx System is the International ElectrotechnicalCommission (IEC) System for the certification of equipment andservices for use in explosive atmospheres

The IECEx System was created in September 1999

IECEx certification is not the same as IEC certification, eventhough both relate to the same IEC standards

The final objective of the IECEx System is worldwide acceptanceof one standard, one certificate and one mark

Four different certification Systems available

More information about IECEx: http://www.iecex.com/

The IECEx System is the International Electrotechnical Commission (IEC) System for the certification ofequipment and services for use in explosive atmospheres.

The IECEx System was created in September 1999.

IECEx certification is not the same as IEC certification, even though both relate to the same IEC standards. The final objective of the IECEx System is worldwide acceptance of one standard, one certificate and onemark.

There are four different certification Systems available:

IECEx Certified Equipment System

IECEx Certified Service Facilities System

IECEx Conformity Mark Licensing System

IECEx Certification of Personnel Competencies System

More information about IECEx can be found from http://www.iecex.com/

Page 86: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

86

© BU Motors and GeneratorsApril 18, 2011 | Slide 86

Standard definitions

The International Electrotechnical Commission (IEC):

International standards and conformity assessment body for all fields of electrotechnology

Created in 1906

Head office in Geneva, Switzerland

Standards cover the whole electromechanical branch

Status of the IEC standards not strong: national electrical standards are in common use in many countries

The International Electrotechnical Commission (IEC) is the international standards and conformity assessment body for all fields of electrotechnology. It was created in 1906 and the commission's head office is situated in Geneva, Switzerland. The membership consists of more than 50 participating countries, including all the world's major trading nations and a growing number of industrializing countries.

(http://www.iec.ch/home-e.htm). The standards cover the whole electromechanical branch. The essential content of the rotating electrical machine standardization is in section 34 "Rotating electrical machines", where there are 18 parts. Each part covers a particular issue in the rotating electrical machine’s construction or performance. The main problem with the IEC standards is that their status in the world is not strong enough; national electrical standards are in common use in many countries.

Page 87: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

87

© BU Motors and GeneratorsApril 18, 2011 | Slide 87

Standard definitions

The International Organization for Standardization (ISO):

worldwide federation of national standards

non-governmental organization established in 1947

The mission:

to promote the development of standardization and related activities in the world

to facilitate the international exchange of goods and services

to develop cooperation in the spheres of intellectual, scientific, technological and economic activity

The International Organization for Standardization (ISO) is a worldwide federation of national standards bodies from approximately 140 countries, one from each country. ISO is a non-governmental organization established in 1947.

The mission of ISO is to promote the development of standardization and related activities in the world with a view to facilitating the international exchange of goods and services, and to developing cooperation in the spheres of intellectual, scientific, technological and economic activity. ISO's work results in international agreements that are published as International Standards.

The scope of ISO is not limited to any particular branch; it covers all technical fields except electrical and electronic engineering, which is the responsibility of IEC. The work in the field of information technology is carried out by a joint ISO/IEC technical committee.

Page 88: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

88

© BU Motors and GeneratorsApril 18, 2011 | Slide 88

Standard definitions

CENELEC:

the European Committee for Electrotechnical Standardization

established in 1973 as a non-profit-making organization under Belgian Law

officially recognized by the European Commission as the EuropeanStandards Organization in its field in Directive 83/189/EEC

works with 35,000 technical experts from 19 European countries to publish standards for the European market

CENELEC standards covering the rotating electrical machines are harmonized with the IEC standards

CENELEC is the European Committee for Electrotechnical Standardization. It was set up in 1973 as a non-profit-making organization under Belgian Law. It was officially recognized by the European Commission as the European Standards Organization in its field in Directive 83/189/EEC. Its members have worked together in the interests of European harmonization since the late 1950s, developing alongside the European Economic Community. CENELEC works with 35,000 technical experts from 19 European countries to publish standards for the European market (http://www.cenelec.org).

CENELEC standards covering the rotating electrical machines are harmonized with the IEC standards. CENELEC also includes standards for the construction and testing of electrical apparatus for use in potentially explosive atmospheres.

Page 89: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

89

© BU Motors and GeneratorsApril 18, 2011 | Slide 89

Standard definitions

The National Electrical Manufacturers Association (NEMA):

one of the leading standards development organizations in the world

attempts to promote:

the competitiveness of its member companies

the establishment and advocacy of industry policies on legislative and regulatory matters

the collection, analysis and dissemination of industry data

The National Electrical Manufacturers Association (NEMA) has been developing standards for the electrical manufacturing industry for more than 70 years and is today one of the leading standards development organizations in the world. NEMA contributes to an orderly marketplace and helps ensure public safety.

NEMA also attempts to promote: the competitiveness of its member companies by providing a forum for the development of technical standards that are in the best interests of the industry and the users of its products; the establishment and advocacy of industry policies on legislative and regulatory matters that might affect the industry and those it serves; and the collection, analysis and dissemination of industry data.

NEMA publishes over 200 standards and offers them for sale along with certain standards originally developed by the American National Standards Institute (ANSI) and the International ElectrotechnicalCommission. The association promotes safety in the manufacture and use of electrical products, provides information about NEMA to the media and the public, and represents industry interests in new and developing technologies (http://www.nema.org).

Page 90: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

90

© BU Motors and GeneratorsApril 18, 2011 | Slide 90

IEC compared to NEMA

Temperature rise:

similar rules

Tolerances:

IEC defines some tolerances, but in NEMA standards these are so-called guaranteed values

Methods of cooling and enclosure:

IEC defines a very detailed numeric coding system, but NEMA standards are more general

Starting characteristics:

differences in the starting characteristics for normal starting torque cage motors; locked rotor apparent power versus kW rating is also different.

Normally, if the NEMA standards are fulfilled, the corresponding IEC standards are also fulfilled. However, if the IEC standards are fulfilled, the corresponding NEMA standards are not necessarily fulfilled. The main differences and some comments on the similarities are discussed in the following:

1. Temperature rise: IEC and NEMA include similar rules for the adjustment of temperature rise as a function of non-standard coolant air, coolant water and/or altitude. There are some variations in the allowed temperature rise: a higher temperature rise is allowed in service factor 1.15 of the NEMA standard. Generally, a higher or equal temperature rise is allowed in the NEMA standards than in the IEC standards. Note that IEC and NEMA define the maximum allowed temperature rise in a different way when the ambient temperature is more than 40 ºC.

2. Tolerances: IEC defines some tolerances in efficiency, locked rotor current and power factor, but in the NEMA standards these are so-called guaranteed values.

3. Methods of cooling and enclosure: The IEC standards define a very detailed numeric coding system whereas the NEMA standards describe the cooling and enclosure systems more generally.

4. Starting characteristics: There are some differences in the starting characteristics for normal starting torque cage motors; locked rotor apparent power versus kW rating is also different. BU Motors and Generators strongly support the drive to harmonize European standards and actively contribute to various working groups within both the IEC and CENELEC.

Page 91: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

91

© BU Motors and GeneratorsApril 18, 2011 | Slide 91

Page 92: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

92

© BU Motors and Generators April 18, 2011 | Slide 92

K110e Unit 5 Electrical standards

Page 93: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

93

© BU Motors and GeneratorsApril 18, 2011 | Slide 93

Electrical standards

IEC Electrical standards:

IEC 60034-1: Rating and performance

IEC 60034-2-1: Methods for determining the losses andefficiency of rotating electrical machinery

IEC 60034-8: Terminal markings and direction of rotationof rotating machines

IEC 60034-12: (for LV only) Starting performance ofsingle-speed three phase cage induction motors

IEC/EN 60034-30: 2008: Harmonization of efficiencyclassification standards

Here is a list of the IEC Electrical standards. The IEC/EN 60034-30 standard was published by the International Electrotechnical Commission in October 2008. The standard defines new efficiency classes for motors. Target is to harmonize the different requirements for induction motor efficiency levels around the world. It provides a single international scheme for motor energy efficiency rating, measured by a common test method.

Page 94: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

94

© BU Motors and GeneratorsApril 18, 2011 | Slide 94

Motors covered in IEC/EN 60034-30: 2008

IEC/EN 60034-30 covers almost all motors (for example standard, hazardous area, marine, brake motors):

Single-speed, three-phase, 50 and 60 Hz

2, 4 or 6-pole

Rated output from 0.75 to 375 kW

Rated voltage UN up to 1000 V

Duty type S1 (continuous duty) or S3 (intermittent periodic duty) with a rated cyclic duration factor of 80% or higher

Excluded are:

Motors made solely for converter operation

Motors completely integrated into a machine (for example, pump fan or compressor) that cannot be tested separately from the machine

IEC/EN 60034-30 covers almost all motors. Excluded are motors made solely for converter operation and motors completely integrated into a machine (for example, pump fan or compressor).

Page 95: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

95

© BU Motors and GeneratorsApril 18, 2011 | Slide 95

New efficiency classes defined by IEC/EN 60034-30

Premium efficiency IE3 Premium

High efficiency IE2 Comparable to

EFF1

Standard efficiency IE1 Comparable to

EFF2

The standard also introduces IE4 (Super Premium Efficiency), a future level above IE3 – efficiency values have yet to be defined for this class.

The table shows the new efficiency classes defined by IEC/EN 60034-30.

Page 96: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

96

© BU Motors and GeneratorsApril 18, 2011 | Slide 96

IE efficiency classes for 50 Hz 4-pole motors

IE Classes – 4 pole

EFF Classes – 4 pole

Here are the EFF- and IE efficiency classes for 4-pole motors illustrated.

The standard also introduces IE4 (Super Premium Efficiency), a level above IE3.

Please note that there is now a lowest level in efficiency, which was missing in the old CEMEP classification.

Page 97: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

97

© BU Motors and GeneratorsApril 18, 2011 | Slide 97

Electrical standards

Type Tolerance NoteVoltage deviation ±5%

(+10K)±10%

Continuous

Short timePower factor -1/6 of (1-cos�) Min.0,02/Max.0,07Efficiency -15% of (1- �)

10% of (1- �) P2 < 50 kWP2 > 50 kW

Speed ± 20% of guaranteed slip

Overspeed 120% for 2 min.Start torque 15 to + 25%Pull-up torque -15 %Maximum torque -10% Min. 160% of MnLocked rotor current(or starting current)

+20%

The nominal tolerances given by the IEC are large and easily met; with the current manufacturing technology, the quality variation is smaller than that allowed by IEC. Some of our competitors may use this and ride with the IEC tolerances to gain benefit or hide their weaknesses. This line is not encouraged by ABB but is something worth keeping in mind.

The table shows the eelectric tolerances according to IEC 60034-1. See the graph in the next slide for term definitions.

Page 98: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

98

© BU Motors and GeneratorsApril 18, 2011 | Slide 98

Electrical standards

Starting torque Ts

Maximum torque TMAX

Nominal torque TN

Minimum torque TMIN

Names in blue are IEC designationsNames in black are NEMA designations

Starting current IsLocked-rotor current

The graph includes definitions for the terms used in the table shown in the previous slide. The graph illustrates the starting performance of an LV motor.

Page 99: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

99

© BU Motors and GeneratorsApril 18, 2011 | Slide 99

Electrical standards

Θ

Θ Θ Θ

The duty types S1-S3 will be discussed in the following.

S1 is a continuous duty that is an operation at constant load long enough for thermal equilibrium to be reached.

S2 is a short time duty that is an operation at constant load for a given time that is shorter than the time needed to reach thermal equilibrium, followed by a rest and a de-energized period that is long enough to allow the motor to reach a temperature within 2 K of that of the coolant.

S3 is an intermittent duty that is a sequence of identical duty cycles, each including a period of operation at constant load and a rest and a de-energized period. In this duty type the cycle of the starting current does not significantly affect the temperature rise. The load period is generally not long enough for thermal equilibrium to be reached.

The illustration shows the characteristics of duty types S1, S2 and S3.

In the illustration: P = output, PV = power losses, Q = temperature, tB = load period, tS = cycle duration, and tSt = rest period.

Page 100: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

100

© BU Motors and GeneratorsApril 18, 2011 | Slide 100

NEMA MG 1

NEMA MG 1, Part 4 defines symbols for mounting dimensions

Section I - General Standard Applicable to All Machines

Section II - Small (Fractional) and Medium (Integral) Machines

Section III - Large Machines

NEMA MG 1, Part 4 defines symbols for mounting dimensions. It only defines dimensions up to frame number series 500 (shaft height 12.5" = 317.5 mm).

NEMA MG 1 consists of four sections, which are as follows:

Section I, - General Standard Applicable to All Machines includes:

Reference Standards and Definitions

Terminal Markings

Dimensions, Tolerances and Mounting

Rotating Electrical Machines - Classification of Degree of Protection Provided by Enclosures for Rotating Machines

Methods of Cooling (IC Code) and

Mechanical Vibration - Measurement, Evaluation and Limits.

Section II - Small (Fractional) and Medium (Integral) Machines includes:

Small and Medium AC Motors

Tests and Performance - AC and DC Motors

Tests and Performance - AC Motors and

Frame Assignments for Alternating Current Integral Horsepower Induction Machines.

Section III - Large Machines:

Induction Machines

Page 101: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

101

© BU Motors and GeneratorsApril 18, 2011 | Slide 101

How is the IE class marked ?

Example of the ABB’s new rating plate

Rating plate marking required

The lowest efficiency value and theassociated IE-code

Efficiency at the full rated load andvoltage (%), 75% and 50%

Year of manufacture

ABB has taken the new rating platedesign into use in 2009 for all themotors valid according to IEC/EN60034-30

As standard ABB will stamp 400V,415V and 690V 50Hz and theefficiency value is given for 400V

Material stainless steel

IEC/EN 60034-30 defines:

As a minimum, the lowest efficiency value and the associated IE-code (of all rated voltage/frequency/output combinations) shall always be printed on the rating plate.

ABB will follow the standard.

ABB motor design is normally optimized to 400V/50Hz operating point, and has highest efficiency in that point. Therefore 400V/50Hz value shall be the one we mark. If the motor is designed to other voltage/frequency, that will be the IE value stamped on the rating plate. All other voltage ratings, which have the same or higher efficiency may be in the same rating plate. Other ratings having lower IE value, need their own separate rating plate.

ABB has taken the new rating plate design into use in 2009. Efficiency logo eff1 or eff2 has been removed and new IEC/EN 60034-30 defined IE rating must be in all our motors.

Page 102: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

102

© BU Motors and GeneratorsApril 18, 2011 | Slide 102

Rating plates

The illustration shows examples of rating plates. The rating plate on the left is for an HV motor/generator according to IEC. The rating plate on the right is a typical rating plate of an AMA motor/generator according to NEMA.

Page 103: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

103

© BU Motors and GeneratorsApril 18, 2011 | Slide 103

Rating plates

The rating plates are for LV motor according to NEMA.

Page 104: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

104

© BU Motors and GeneratorsApril 18, 2011 | Slide 104

Direction of rotation and terminal marking

According to the IEC 60034-8 standard, the followingterminal markings are required:

windings are marked by letters (U, V, W),

end points are marked with an additional numericalsuffix (U1, V1, W1), and

similar windings of a group are marked with a numericalprefix (1U, 1V, 1W).

Direction of rotation is the one observed or clockwise

According to the IEC 60034-8 standard, the following terminal markings are required: windings are marked byletters, end points are marked with an additional numerical suffix and similar windings of a group are markedwith a numerical prefix. Direction of rotation is the one observed or clockwise.

Page 105: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

105

© BU Motors and GeneratorsApril 18, 2011 | Slide 105

Direction of rotation and terminal marking

The illustration shows the connection diagram for main and auxiliary terminal boxes (HV motors).

The connection diagram for the main and auxiliary terminal boxes gives the customer the necessary information for the main terminal cabling, control device cabling and layout. The following connections are shown in the connection diagrams: phases U, V, W (or T1, T2, T3 acc. to NEMA); temperature detectors in windings; anti condensation heaters; bearing temperature detectors; wire numbering (the same numbers are stuck onto the terminal blocks); and other specific order-related accessories.

Page 106: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

106

© BU Motors and GeneratorsApril 18, 2011 | Slide 106

Direction of rotation and terminal marking

L3L2L1

W1V1U1

PE

V2U2W2

U1 V1 W1

L3L2L1

W1V1U1

PE

Connection triangleD-SchaltungD-connection

Schema de branchementAnschluss-SchemaDiagram of connection

Branchement des bornesAnschluss des MotorsConnection of terminals

W2 U2 V2V2U2W2

No du moteurMaschine NrMotor No

ABB Oy, Electrical Machines3GZF321100-1 C

Direction de rotation avec branchement ci-dessusDrehrichtung nach SchaltbildDirection of rotation with phase sequence shown in picture

Connection etoileY-SchaltungY-connection

Direction de rotation avec sequence de phase reverséeDrehrichtung mit umgekehrter PhasenfolgeDirection of rotation with reversed phase sequence

LV Motors

The illustration shows a connection diagram for a main terminal box (LV motors). LV motors are supplied with a separate connection diagram for auxiliaries.

Page 107: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

107

© BU Motors and GeneratorsApril 18, 2011 | Slide 107

NEMA MG 1, Part 2 - Terminal Marking

Terminal markings:

line - L1, L2, L3, L4, etc.

stator - T1, T2, T3, T4, etc.

auxiliary markings, e.g. space heater H1, H2, H3, H4

NEMA MG 1, Part 2 covers terminal markings, direction of rotation, and the relation between the terminal markings and the direction of the rotation. The following terminal markings are covered: line (L1, L2, L3, L4, etc.); stator (T1, T2, T3, T4, etc.); also covers auxiliary markings, e.g. space heater H1, H2, H3, H4. The standard direction of rotation for AC generators is clockwise when facing the end of the motor/generator opposite the drive end (standard ABB practice is the IEC method). Terminal marking of polyphase induction motors/generators are not related to the direction of rotation.

Page 108: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

108

© BU Motors and GeneratorsApril 18, 2011 | Slide 108

Direction of rotation and terminal marking

The illustration shows the connection diagram for main terminal box according to NEMA (LV motors).

Page 109: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

109

© BU Motors and GeneratorsApril 18, 2011 | Slide 109

Page 110: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

110

© BU Motors and Generators April 18, 2011 | Slide 110

K110e Unit 6 Mechanical standards

Page 111: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

111

© BU Motors and GeneratorsApril 18, 2011 | Slide 111

Mechanical standardsShaft height

Shaftheight

Shaft height is the distance from the centre line of the shaft to the bottom of the feet. For example, the motor type M3BP 315SMB 4 B3 has a shaft height of 315 mm.

Page 112: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

112

© BU Motors and GeneratorsApril 18, 2011 | Slide 112

Mechanical standardsIM mounting arrangements

IEC 60072-1: Dimensions and output series for rotating electricalmachines - Part1

IEC 60072-2: Dimensions and output series for rotating electricalmachines - Part2

IEC 60034-5: Classifications of degrees of protection

IEC 60034-6: Methods of cooling

IEC 60034-7: Classification of types of construction, mountingarrangements and terminal box position (IM code)

IEC 60034-9: Noise limits (only low voltage motors)

IEC 60034-14: Measurement, evaluation and limits of vibration

IM is an abbreviation for ”International Mounting”.

IEC defines the following mechanical standards:

IEC 60072-1 covers the dimensions and output series for rotating electrical machines, part 1, frame numbers from 56 to 400 and flange numbers from 55 to 1080.

IEC 60072-2 covers the dimensions and output series for rotating electrical machines, part 2, frame numbers from 355 to 1000 and flange numbers from 1180 to 2360.

IEC 60034-5 covers degrees of protection provided by the integral design of rotating electrical machines (IP code) and classifications.

IEC 60034-6 covers the methods of cooling.

IEC 60034-7 covers the classification of types of construction, mounting arrangements, and terminal box position (IM code).

IEC 60034-9 covers noise limits (only low voltage motors)

IEC 60034-14 covers mechanical vibration of certain machines with shaft heights of 56 mm and higher, as well as measurement, evaluation, and limits of vibration.

IEC 60072 defines symbols for the mounting dimensions and several different dimensions for symbols (foot-mounted: A, B, C; flange-mounted: M, N, P, R, S, T; shaft extension: D, E, F, GD, GE, GA).

Page 113: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

113

© BU Motors and GeneratorsApril 18, 2011 | Slide 113

Mechanical standardsIM mounting arrangements

The diagram shows an example of designations according to Code II.

The first characteristic numeral indicates the basic construction of the motor/generator (mounting to foundation, bearing arrangement). The second and third numerals indicate more detailed construction, depending on the first numeral. The fourth numeral indicates the amount and shape of the shaft extension(s).

IEC 60034-7 specifies two ways of stating how a motor is mounted.

According to Code I, an alpha-numeric designation is applicable to motors/generators with end shield bearing(s) and only one shaft extension.

According to Code II, an all-numeric designation is applicable to a wider range of types of motors/generators, including types covered by Code I.

Page 114: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

114

© BU Motors and GeneratorsApril 18, 2011 | Slide 114

Mechanical standardsIM mounting arrangements

Code II First numeral Second and third numeral

Fourth numeral

Motor/generator type

Code I Sketch

IM 1001 Foot-mounted motors/generators with end shield bearing(s) only

Two bearings, normal feet, feet down, shaft horizontal

One cylindrical shaft extension

HXR, AMA, AMK

IM B3

IM 3011 Flange-mounted motors/generators with end shield bearing(s) only, with a flange as part of an end shield

Two bearings, flange at D-end, access to back of flange, face of flange faces towards D-end, shaft vertical downwards

One cylindrical shaft extension

HXR IM V1

IM 4011 Flange-mounted motors/generators with end shield bearing(s) only, with a flange not part of an end shield but an integral part of the frame or other component

Two bearings, flange at D-end, access to back of flange, face of flange faces towards D-end, shaft vertical downwards

One cylindrical shaft extension

AMA, AMK IM V10

The table shows examples of common HV motor mounting arrangements.

Page 115: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

115

© BU Motors and GeneratorsApril 18, 2011 | Slide 115

Mechanical standardsIM mounting arrangements

Examples of common LV motor mounting arrangements are shown in this slide.

Page 116: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

116

© BU Motors and GeneratorsApril 18, 2011 | Slide 116

Mechanical standardsIM mounting arrangements

LetterNumeral

F - 1

The diagram above shows symbols for mounting arrangement for high voltage motors and generators according to NEMA MG 1. The letter indicates the mounting to the foundation, the numeral indicates the location of the terminal box.

The illustrations below the diagram are examples of standard mountings (floor mounting).

Page 117: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

117

© BU Motors and GeneratorsApril 18, 2011 | Slide 117

International StandardsMethod of Cooling (IC code, short one normally used)

IC = International coolingA = Air as coolantW = Water as coolant

The diagram shows the method of cooling for low voltage motors according to IEC 60034-6.

ABB can deliver motors as below:

IC 410 Totally enclosed motor without fan

IC 411: Totally enclosed standard motor, frame surface cooled with fan

IC 416: Totally enclosed motor with auxiliary fan motor

IC 418: Totally enclosed motor, frame surface cooled without fan

IC 01 : Open motors

IC 31W: Inlet and outlet pipe or duct circulated: water cooled

Note: Motors without fan can deliver same output power provided installation are according to IC 418.

Page 118: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

118

© BU Motors and GeneratorsApril 18, 2011 | Slide 118

International StandardsMethod of Cooling

COMPLETE DESIGNATION

SIMPLIFIED DESIGNATION

IC 8 A

IC 8

1 W 7

1 W

Code lettersCircuit arrangementPrimary coolantMethod of movement of primary coolantSecondary coolantMethod of movement of secondary coolant

The diagram shows the method of cooling for high voltage motors and generators.

Page 119: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

119

© BU Motors and GeneratorsApril 18, 2011 | Slide 119

International StandardsMethod of Cooling

Characteristic numeral

Circuit arrangement Method of movement

0 Free circulation Free circulation

1 Inlet pipe or inlet duct-circulated Self-circulation

2 Outlet pipe or outlet duct-circulated - (reserved for future use)

3 Inlet and outlet pipe or duct-circulated -

4 Frame surface-cooled -

5 Integral heat exchanger (using surrounding medium) Integral independent component

6 Motor/generator mounted heat exchanger (using surrounding medium)

Motor/generator-mounted independent component

7 Integral heat exchanger (using remote medium) Separate and independent component or coolant system pressure

8 Motor/generator-mounted heat exchanger (using remote medium)

Relative displacement

9 Separate heat exchanger (using surrounding or remote medium)

All other components

The table shows the characteristic numeral for circuit arrangement as well as the method of movement.

Page 120: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

120

© BU Motors and GeneratorsApril 18, 2011 | Slide 120

International StandardsMethod of Cooling

Characteristic letter CoolantA AirF FreonH HydrogenN NitrogenC Carbon dioxideW WaterU OilS Any other coolantY Coolant not yet selected

The table shows the characteristic letter for each coolant.

Page 121: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

121

© BU Motors and GeneratorsApril 18, 2011 | Slide 121

Symbols for degree and protectionIP code

IEC 60034-5 and NEMA MG 1 Part 5

In the International Protection code (IP code), the first characteristic numeral indicates the degree of protection against contact and ingress of foreign bodies and the second indicates the degree of protection against ingress of water.

When necessary, the degrees of protection for electrical motors/generators may have the following letters added after the second numeral:

W = open weather-protected motor/generator (NEMA specifies after the IP Code),

S = motor/generator tested for harmful ingress of water at standstill, and

M = motor/generator tested for harmful ingress of water when running.

IP protection is protection of persons against getting in contact with (or approaching) live parts and against contact with moving parts inside the enclosure. Also protection of the machine against ingress of solid foreign objects. Protection of machines aginst the harmful effects due to the ingress of water.

Classification of degrees fo protection provided by enclosures of rotating machines refers to Standard IEC 60034-5 or EN 60529 for IP code.

Page 122: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

122

© BU Motors and GeneratorsApril 18, 2011 | Slide 122

Protection Classes (IEC 60034-5)

The table shows the explanations of the protection codes.

Page 123: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

123

© BU Motors and GeneratorsApril 18, 2011 | Slide 123

Protection Classes (IEC 60034-5)

Protection Brief Description Definition Cooling Motor/generator type

NEMA

IP23 Motor/generator protectedagainst solid objectsgreater than 50 mm(1.9685 in)

Motor/generator protectedagainst sprayingwater

Contact with or approach to live or moving parts inside theenclosure by fingers or similar objects not exceeding 80mm (3.1496 in) in length.Ingress of solid objects exceeding 12 mm (0.4724 in) indiameter.Water falling as a spray at an angle up to 60° from verticalshall have no harmful effect.

IC01 AMA, AMK ODP

IP24W(IEC)

IPW24(NEMA)

Motor/generator protectedagainst solid objectsgreater than 50 mm(1.9685 in)

Motor/generator protectedagainst sprayingwater

Contact with or approach to live or moving parts inside theenclosure by fingers or similar objects not exceeding 80mm (3.1496 in) in length.Ingress of solid objects exceeding 12 mm (0.4724 in) indiameter.Water splashing against the machine from any directionshall have no harmful effect.Weather-protected so designed that ingress of rain, snowand airborne particles into the electrical parts is reduced.

IC01 AMA, AMK WP IWP II

IP55 Dust-protectedmotor/generator

Motor/generator protectedagainst water jets

Contact with or approach to live or moving parts inside theenclosure.Ingress of dust is not totally prevented but dust does notenter in sufficient quantity to interfere with satisfactoryoperation of the machine.Water projected by a nozzle against the machine from anydirection shall have no harmful effect.

IC411

IC611

IC81W

HXR

AMA, AMK

AMA, AMK

TEFC

TEAAC

TEWAC

The table shows the standard IP protection for high voltage motors and generators.

Page 124: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

124

© BU Motors and GeneratorsApril 18, 2011 | Slide 124

Degrees of protectionIK code

IK code is the classification of degrees or protection provided by enclosure for motors against external mechanical impacts.

Classification of degrees fo protection provided by enclosures of rotating machines refers to Standard EN 50102 for IK code.

Page 125: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

125

© BU Motors and GeneratorsApril 18, 2011 | Slide 125

Insulation

ABB uses class F insulation systems, which, with temperature rise B, is the most common requirement among industry today.

The use of Class F insulation with Class B temperature rise gives ABB products a 25° C safety margin. This can be used to increase the loading by up to 12 per cent for limited periods, to operate at higher ambient temperatures or altitudes, or with greater voltage and frequency

tolerances. It can also be used to extend insulation life. For instance, a 10 K temperature reduction will extend the insulation life.

Class F insulation system

– Max ambient temperature 40° C

– Max permissible temperature rise 105 K

– Hotspot temperature margin + 10 K

Class B rise

•Max ambient temperature 40° C

•Max permissible temperature rise 80 K

•Hotspot temperature margin + 10 K

Insulation system temperature class

•Class F 155° C

•Class B 130° C

•Class H 180° C

Page 126: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

126

© BU Motors and GeneratorsApril 18, 2011 | Slide 126

Frequency converter drives Customer values

Squirrel cage induction motors offer excellent availability, reliability and efficiency. With a frequency converter – a variable speed drive (VSD) – the motor will deliver even better value. A variable speed drive motor can be started softly with low starting current, and the speed can be controlled and adjusted to suit the application demand without steps over a wide range. Also the use of a frequency converter together with a squirrel cage motor usually leads to remarkable energy and environmental savings.

Speed control has several benefits: it allows accurate process control, and thus creates better end product quality. Speed control also creates less stress to mechanics and electrical network due to soft starting and precise control. It increases production capacity without additional investments.

An AC induction motor, that is, an asynchronous squirrel cage AC motor, is most commonly used in industry. It has some basic advantages like robust design, simple construction, high IP class, and so on. An asynchronous motor needs frequency converter to control its speed.

A modern frequency converter has many advanced protection features that protect the drive itself, equipment connected to the drive and even the production process. It has inbuilt programmability that allows it to control a production process without an additional external controller, or PLC. Programmability means the user can fine tune the variable speed drive, or VSD, to get the most out of the whole equipment.

Requirements for the flexibility and accuracy of external control methods can best be fulfilled with a modern VSD which can be connected to just about any fieldbus or analog or digital control signal. Even remote monitoring via the Internet is possible.

Page 127: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

127

© BU Motors and GeneratorsApril 18, 2011 | Slide 127

Rotor Construction – Balancing

Standards for mechanical vibration:

ISO 1940/1: Balance quality requirements for rigidrotors, Part 1

ISO 1940/2: Balance quality requirements for rigidrotors, Part 2

ISO 11342: Methods and criteria for the balancing offlexible rotors

Balancing quality grades:

G2, 5 for medium and large armatures with specialrequirements

G6, 3 for medium and large armatures without specialrequirements

The following standards cover the balancing of the rotor construction:

ISO 1940/1 for mechanical vibration covers the balance quality requirements for rigid rotors in Part 1: Determination of permissible residual unbalance.

ISO 1940/2 for mechanical vibration covers the balance quality requirements for rigid rotors in Part 2: Balance errors.

ISO 11342 for mechanical vibration covers the methods and criteria for the balancing of flexible rotors.

Imbalance is a condition, which exists in a rotor when a vibratory force or motion is imparted to its bearings as a result of centrifugal forces.

The balancing quality grades are:

G2, 5 for medium and large armatures with special requirements and

G6, 3 for medium and large armatures without special requirements.

As standard, rotors are balanced with half key; the coupling must also be balanced with half key. The balancing procedure is permanently marked on the shaft end with 'H' (H = half key, F = full key).

Page 128: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

128

© BU Motors and GeneratorsApril 18, 2011 | Slide 128

Vibration

Vibration is a response of a system to an internal orexternal stimulus causing it to oscillate or pulsate

Three important parameters:

frequency

amplitude

phase

Vibration is the response of a system to an internal or external stimulus causing it to oscillate or pulsate. While it is commonly thought that vibration itself damages motors and structures, it does not. The damage is done by dynamic stresses that cause fatigue in the materials. The dynamic stresses are included in the vibration.

Vibration has three important parameters, which can be measured:

Frequency, that is, how many times does the motor or structure vibrate per minute or per second.

Amplitude, that is, how much is the vibration in microns, mm/s or g's.

Phase, that is, how is the member vibrating in relation to the reference point.

The following standards cover mechanical vibration:

ISO 10816- Mechanical vibration: Evaluation of machine vibration by measurement of non-rotating parts,

NEMA MG 1, Part 7: Mechanical vibration - Measurement, evaluation and limits,

ISO 7919: Mechanical vibration of non-reciprocating machines - Measurement of rotating shafts and evaluation criteria, and

IEC 60034-14: Mechanical vibration of certain machines with shaft heights of 56 mm and higher -Measurement, evaluation and limits.

Page 129: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

129

© BU Motors and GeneratorsApril 18, 2011 | Slide 129

M, IP, IC

International Standards CEI EN 60034:

CEI EN 60034- 5: degrees of protection provided bythe integral design of rotating electrical machines (IPcode) – Classification,

CEI EN 60034- 5: degrees of protection provided bythe integral design of rotating electrical machines (IPcode) – Classification, and

CEI EN 60034- 7: classification of types ofconstruction, mounting arrangements and terminal boxposition (IM Code).

The following issues are covered by the International Standards CEI EN 60034:

CEI EN 60034-5 covers the degrees of protection provided by the integral design of rotating electrical machines (IP code) – Classification,

CEI EN 60034-5 covers the degrees of protection provided by the integral design of rotating electrical machines (IP code) – Classification, and

CEI EN 60034-7 covers the classification of types of construction, mounting arrangements and terminal box position (IM Code).

Page 130: BU Motors and Generators training Start here menu here menu/data/downloads/k… · We recommend to start your studies with K110e Basics of electrical motors and standards e-learning

18.04.2011

130

© BU Motors and GeneratorsApril 18, 2011 | Slide 130