Top Banner
Installation Test Base Transceiver Station Equipment ITMN:BTSE BS-241/241 II A30808-X3247-M357-04-7630
70

bs241it.pdf

Oct 26, 2015

Download

Documents

arashh_soltani

Installation Test
Base Transceiver Station Equipment

ITMN:BTSE
BS-240/240 II/240XL/240XL II
A30808-X3247-M356-04-7630
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
  • Installation Test

    Base Transceiver Station Equipment

    ITMN:BTSE BS-241/241 II

    A30808-X3247-M357-04-7630

  • 2 A30808-X3247-M357-04-7630

    ITMN:BTSE BS-241/241 II

    Id:0900d805800c6ed3

    Copyright (C) Siemens AG 2006Issued by the Communications GroupHofmannstrae 51D-81359 Mnchen

    Technical modifications possible.Technical specifications and features are binding only insofar as they are specifically and expressly agreed upon in a written contract.

    Copyright (C) Siemens AG 2006Issued by the Communications GroupHofmannstrae 51D-81359 Mnchen

    Technical modifications possible.Technical specifications and features are binding only insofar as they are specifically and expressly agreed upon in a written contract.

    f Important Notice on Product SafetyDANGER - RISK OF ELECTRICAL SHOCK OR DEATH - FOLLOW ALL INSTALLATION INSTRUCTIONS.The system complies with the standard EN 60950 / IEC 60950. All equipment connected to the system must comply with the applicable safety standards.Hazardous voltages are present at the AC power supply lines in this electrical equipment. Some components may also have high operating temperatures.Failure to observe and follow all installation and safety instructions can result in serious personal injury or property damage.Therefore, only trained and qualified personnel may install and maintain the system.

    The same text in German:Wichtiger Hinweis zur ProduktsicherheitLEBENSGEFAHR - BEACHTEN SIE ALLE INSTALLATIONSHINWEISE.Das System entspricht den Anforderungen der EN 60950 / IEC 60950. Alle an das System angeschlossenen Gerte mssen die zutreffenden Sicherheitsbestimmungen erfllen.In diesen Anlagen stehen die Netzversorgungsleitungen unter gefhrlicher Spannung. Einige Komponenten knnen auch eine hohe Betriebstemperatur aufweisen.Nichtbeachtung der Installations- und Sicherheitshinweise kann zu schweren Krperverletzungen oder Sachschden fhren.Deshalb darf nur geschultes und qualifiziertes Personal das System installieren und warten.

    Caution:This equipment has been tested and found to comply with EN 301489. Its class of conformity is defined in table A30808-X3247-X910-*-7618, which is shipped with each product. This class also corresponds to the limits for a Class A digital device, pursuant to part 15 of the FCC Rules.These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment.This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accor-dance with the relevant standards referenced in the manual Guide to Documentation, may cause harmful inter-ference to radio communications.For system installations it is strictly required to choose all installation sites according to national and local require-ments concerning construction rules and static load capacities of buildings and roofs.For all sites, in particular in residential areas it is mandatory to observe all respectively applicable electromagnetic field / force (EMF) limits. Otherwise harmful personal interference is possible.

    Trademarks:All designations used in this document can be trademarks, the use of which by third parties for their own purposes could violate the rights of their owners.

  • A30808-X3247-M357-04-7630

    3

    ITMN:BTSE BS-241/241 II

    Id:0900d805800c6ed3

    Table of ContentsThis document has 70 pages.

    Reason for Update . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

    1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91.1 Aims of Installation and Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91.2 Pre-Commissioning and Pre-Acceptance . . . . . . . . . . . . . . . . . . . . . . . . . . . 91.3 Optional Measurements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91.4 Using the ITMN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101.4.1 Required Knowledge. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101.4.2 Test Equipment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101.4.3 Installation Test Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101.4.4 Procedure in the Event of Faults after Commissioning. . . . . . . . . . . . . . . . 111.4.5 Procedure in the Event of Faults not Described in the Manuals . . . . . . . . . 121.4.6 Dealing with Defective Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121.5 CE and UL Declaration of Conformity. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121.6 LMT Use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131.6.1 LMT Graphic View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131.6.2 LMT Tree View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

    2 Safety Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 192.1 Electrostatically Sensitive Components . . . . . . . . . . . . . . . . . . . . . . . . . . . 192.2 Warnings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202.3 Symbols Used. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202.4 System Voltages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202.5 Changing Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 212.6 Grounding of Modules / Racks / Shelters . . . . . . . . . . . . . . . . . . . . . . . . . . 212.7 Handling Moist Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

    3 Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 223.1 Visual Inspection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 223.1.1 Visual Inspection of BTSE Mechanics . . . . . . . . . . . . . . . . . . . . . . . . . . . . 223.1.1.1 Shelters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 223.1.1.2 Mounting and Installation of BTSE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 243.1.1.3 Check of Base Transceiver Station BTSE . . . . . . . . . . . . . . . . . . . . . . . . . 243.1.1.4 Check of BTSE Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 243.1.1.5 Antenna and Feeder Cable. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 263.1.2 Visual Inspection of BTSE Electrics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 273.1.2.1 Polarity of DC Input and Tolerance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 273.1.2.2 Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 273.1.2.3 Alarms. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 273.1.2.4 DC Connector for Network Termination (NT) . . . . . . . . . . . . . . . . . . . . . . . 283.1.3 Visual Inspection of BTSE Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 293.1.3.1 Abis Configurations to the BTS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 293.1.3.2 Tower Mounted Amplifier (TMA) Connection . . . . . . . . . . . . . . . . . . . . . . . 293.1.3.3 Adjustable Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 303.1.3.4 Antenna Combining . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 403.1.3.5 Antenna Multicoupling. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41

  • 4 A30808-X3247-M357-04-7630

    ITMN:BTSE BS-241/241 II

    Id:0900d805800c6ed3

    3.1.3.6 HPDU. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 453.2 Preparation for Offline Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 463.2.1 Recommended Test Equipment and Tools . . . . . . . . . . . . . . . . . . . . . . . . . 463.2.1.1 Test Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 463.2.1.2 Preparation and Presetting of Test Equipment . . . . . . . . . . . . . . . . . . . . . . 473.2.2 BTSE Power-On . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 483.2.2.1 Check Polarity of DC Input and Tolerance. . . . . . . . . . . . . . . . . . . . . . . . . . 483.2.2.2 Breakers before BTSE Power-On . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 483.3 Checking the State of all Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 493.4 Checking the Environmental Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 523.5 Replacing Failed HW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 533.6 Generating BTS Backup Files . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 543.7 Remote Inventory. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 553.8 Switch to Phase 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 623.9 SW Download and Activation (optional). . . . . . . . . . . . . . . . . . . . . . . . . . . . 643.10 Setting the Attributes for the BTSE (optional) . . . . . . . . . . . . . . . . . . . . . . . 663.11 Setting BTSM (optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 673.12 Closing the Rack/Shelter Door. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68

    4 Appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 694.1 Power/Level Conversion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 694.2 Used Expressions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 704.3 Module Identification by Inventory Data and Label . . . . . . . . . . . . . . . . . . . 70

  • A30808-X3247-M357-04-7630

    5

    ITMN:BTSE BS-241/241 II

    Id:0900d805800c6ed3

    List of FiguresFigure 1 Installation Test Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11Figure 2 CE and UL Symbol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12Figure 3 LMT Graphic View - Window . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13Figure 4 LMT Graphic View lower level- Window . . . . . . . . . . . . . . . . . . . . . . . . 14Figure 5 Parameters and Parameter Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15Figure 6 LMT Tree View Window. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16Figure 7 LMT Tree View lower level - Window. . . . . . . . . . . . . . . . . . . . . . . . . . . 17Figure 8 ESD Symbol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19Figure 9 Symbols Used . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20Figure 10 Example for BS-241 (Front View) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23Figure 11 Abis Connections to the BTS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29Figure 12 TMA, e.g. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30Figure 13 COBA2P8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32Figure 14 COBA4P12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34Figure 15 COSA. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36Figure 16 DIP Switches for Battery Type, Battery Capacities and Slot-ID. . . . . . . 38Figure 17 DIAMCO Antenna Connection and DIP Switches . . . . . . . . . . . . . . . . . 42Figure 18 (F)DUAMCO DIP Switch abd Antenna Connection . . . . . . . . . . . . . . . . 44Figure 19 Setting the SBS Equipment Position . . . . . . . . . . . . . . . . . . . . . . . . . . . 56Figure 20 Editing Nob-RIU Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58Figure 21 Closing the Rack/Shelter Door. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68Figure 22 Labels and Inventory Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70

  • 6 A30808-X3247-M357-04-7630

    ITMN:BTSE BS-241/241 II

    Id:0900d805800c6ed3

    List of TablesTable 1 BS-241/241 II Shelter Numbering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22Table 2 Adjustable Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30Table 3 Boot Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31Table 4 Software Images SWI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31Table 5 Battery Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37Table 6 Battery Capacity DIP Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38Table 7 Slot-ID . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39Table 8 Switch Settings for DIAMCO / DUAMCO / FDUAMCO. . . . . . . . . . . . . . 42Table 9 Cascading of Multicouplers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44Table 10 Additional Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66Table 11 Power Conversion Table. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69

  • A30808-X3247-M357-04-7630

    7

    ITMN:BTSE BS-241/241 II Reason for Update

    Id:0900d805800c67dd

    Reason for Update

    Issue 04 for Release BR8.0(2006/20/11)

    Issue Date Summary01 09/2006 First edition for new release BR8.002 04/2005 More instructions for adjusting of the DIAMCO,(F)DUAMCO.

    Revised tables.03 07/2005 Revised tables.04 09/2006 The structure of the document adapted to Lean Implementa-

    tion.

  • 8 A30808-X3247-M357-04-7630

    ITMN:BTSE BS-241/241 II

    Id:0900d805800c67dd

    Reason for Update

  • A30808-X3247-M357-04-7630

    9

    ITMN:BTSE BS-241/241 II Introduction

    Id:0900d8058006c54a

    1 Introduction

    1.1 Aims of Installation and CommissioningInstallation and commissioning is based on extensive, high quality final factory tests. In the factory, each module is tested during its production process; all Radio Frequency (RF) parameters such as the power and modulation spectrum are measured in the complete BTSE rack in customer configuration.The final Factory Tests comply with the tests and measurements required by GSM spec-ifications.The installation test can therefore concentrate on functional tests of the delivered hardware (HW).The installation and commissioning of a network element followed by unit acceptance is proof of: A correct and complete delivery according to the network planning and the customer

    order. A correct mechanical and electrical installation according to the installation docu-

    ments. The functional ability of the supplied Hardware (HW).

    (correct functioning of the NEs at an interface in relation to other network elements).The test subdivision in step, allows a quick, efficient and reliable commissioning proce-dure. The test steps are as follows: Final Factory Test Installation/commissioning (HW-test) Network integration (data base test)

    1.2 Pre-Commissioning and Pre-AcceptanceThe BTSE may also be delivered partly or completely pre-commissioned and pre-accepted. If the BTSE is pre-commissioned and pre-accepted, some procedures that usually are performed on site have already been performed in the factory. In this case, these par-ticular procedures do not need to be performed again during the installation test phase.It depends on the contract to what extent the BTSE is pre-commissioned and pre-accepted.All set parameters are listed in the Pre-Commissioning Paper. All executed tests and their results are documented in the Final Factory Test protocol. Both documents are delivered together with the site-specific documentation.Consult these documents to find out which procedures can be left out.g It is important, however, not to change the order of the remaining procedures.

    1.3 Optional MeasurementsRadio Frequency (RF) measurements can be performed by means of a spectrum analyzer or other test equipment. RF measurements may be used as an option for locating suspected faults.They do not need to be done in every BTSE as regular measurements.

  • 10 A30808-X3247-M357-04-7630

    ITMN:BTSE BS-241/241 II

    Id:0900d8058006c54a

    Introduction

    1.4 Using the ITMN

    1.4.1 Required KnowledgeOnly trained personnel should carry out the installation and installation tests.The SIEMENS training center offers the necessary courses.

    1.4.2 Test EquipmentThe test equipment and tools required for the tests are described in the corresponding chapter.

    1.4.3 Installation Test SequenceInstallation test sequence is organized in tasks, as shown in Figure 1, Installation Test Sequence. Each single task is described in an own procedure, see Chapter Proce-dures. Perform procedures continuously.

  • A30808-X3247-M357-04-7630

    11

    ITMN:BTSE BS-241/241 II Introduction

    Id:0900d8058006c54a

    Figure 1 Installation Test Sequence

    Execution of Function test (Offline) and On-Line Test are not included in this manual.

    1.4.4 Procedure in the Event of Faults after CommissioningIf faults occur in on-line operation, they should be localized and cleared in accordance with the instructions in the Maintenance Manual.

    9LVXDO&KHFNRI%760HFKDQLFV

    9LVXDO&KHFNRI%76(OHFWULFV

    9LVXDO&KHFNRI%RDUGV

    3UHSDUDWLRQIRU)XQFWLRQ7HVW

    ([HFXWLRQRI)XQFWLRQ7HVW

    1SFQBSBUJPO&YFDVUJPORI2QOLQH7HVWV

    67$57

    ??????

    ?????

    ???????

    ??????

    (1'

  • 12 A30808-X3247-M357-04-7630

    ITMN:BTSE BS-241/241 II

    Id:0900d8058006c54a

    Introduction

    1.4.5 Procedure in the Event of Faults not Described in the ManualsFirst the specialist in the installation team should try to clear the fault. If the fault cannot be cleared, a fault report must be filled in, providing the following information in detail: Description of the test step attempted Description of the system response(s) Description of any system activities taking place at the same time, e.g. work done

    by other testers during modification of hardware or software.Send the fault report to the Technical Assistance Center TAC.g Always write a fault report, if a software error occurs.

    1.4.6 Dealing with Defective ModulesIf a module proves to be defective, send it in an appropriate packaging to the repair center with the following information: Name and code of the site Name and code number of the module Description of the fault

    1.5 CE and UL Declaration of Conformity

    Figure 2 CE and UL Symbol

    The CE and UL declaration of conformity for the product will be fulfilled if you setup and cable, according to the specification in the manual. See mounting instructions, cable lists. If it is necessary take description of project-specific documentation.Deviations from the specifications or independent changes during setup, such as use of cable types with lower screening values, for example, can lead to the violation of CE requirements. In such cases the CE declaration of conformity is invalidated and the responsibility passes to the person who caused the deviations.

  • A30808-X3247-M357-04-7630

    13

    ITMN:BTSE BS-241/241 II Introduction

    Id:0900d8058006c54a

    1.6 LMT UseThe following chapter LMT Use is a limited LMT description. The purpose of this chapter is to explain the procedures use in this manual. For a detailed explanation about LMT see the OLG:LMT.If the BTSE is not pre-commissioned and not pre-accepted, some tasks have to be per-formed on site. Every single task is described in a procedure which is organized in steps. Procedures start with common part, including notes or other information. To perform the taks use the current LMT software release.There are two ways to perform the task using the LMT:1. Tree View2. Graphic ViewIn procedures of this document the Graphic View will be used.

    1.6.1 LMT Graphic ViewIn the LMT Evolution online window choose the menu File. In the menu File start the Training Script. It pops up the Start Training Script window. Click the Family: BTS. Select the right BTS type and the available, corresponding BTS profile. It pops up the LMT Evolution Start Training Script window, the Graphic View. See Figure 3, LMT Graphic View - Window.

    Figure 3 LMT Graphic View - Window

    In order to perform the command consider following instructions: Select BTS module by double left-click (e.g COSA:0) Perform command by double right-click (e.g. LOCK)

    PHQXEDUWRROEDUZLWKLFRQV

    JUDSKLFYLHZPHQX

    VXEGLUHFWRU\

    FRPPDQG

    %76W\SH

  • 14 A30808-X3247-M357-04-7630

    ITMN:BTSE BS-241/241 II

    Id:0900d8058006c54a

    Introduction

    If the module is not located at the upper level, select the corresponding module by the double left-click (e.g FLEXCU:0). It pops up the LMT Evolution Start Training Script window - lower level. See Figure 4, LMT Graphic View lower level- Window. Perform command by double right-click (e.g.LOCK)

    Figure 4 LMT Graphic View lower level- Window

    After performing the task, the system may give test outcome. In that case note the test outcome, because it could be important for the next task.

    Parameters and Parameter ValuesAfterwards set the parameters and parameter values if necessary.A Select the Parameter Value window pops up. Enter the parameter values (RXLEVADJ(-24.0 ... 24.0 step 1.0), e.g. 15), see Figure

    5, Parameters and Parameter Values. Click on the Submit button

    %76PRGXOH

    FRPPDQG

  • A30808-X3247-M357-04-7630

    15

    ITMN:BTSE BS-241/241 II Introduction

    Id:0900d8058006c54a

    Figure 5 Parameters and Parameter Values

    Procedures are organized in steps. See an example of a possible procedure in this manual.If the module is located at the upper level of Graphic View, step 2 will be used in the procedure. If the module is not located at the upper level of Graphic View, step 3 will be used in the procedure.

    1 Log on LMTConnect the LMT to the BTSE and start the log on procedure.

    2 Lock Suspected Moduleb LOCK COSA

    3 Lock Suspected Moduleb FLEXCU LOCK FCUMAIN1. A Select the Parameter Value window pops up:

    1.1 Enter the parameter values. (RXLEVADJ(-24.0 ... 24.0 step 1.0), e.g. 15)2. Click on the Submit button

    4 END

    SDUDPHWHU SDUDPHWHUYDOXHV

  • 16 A30808-X3247-M357-04-7630

    ITMN:BTSE BS-241/241 II

    Id:0900d8058006c54a

    Introduction

    1.6.2 LMT Tree ViewThe following chapter explains the using of LMT Tree View.In the LMT Evolution online window choose the menu File. In the menu File start the Training Script. It pops up the Start Training Script window. Click the Family: BTS. Select the right BTS type and the available, corresponding BTS profile. It pops up the LMT Evolution Start Training Script window. Click on the Tree View. See Figure 6, LMT Tree View Window.

    Figure 6 LMT Tree View Window

    PHQXEDUWRROEDUZLWKLFRQV

    JUDSKLFYLHZPHQX

    %76W\SH

    VXEGLUHFWRU\

  • A30808-X3247-M357-04-7630

    17

    ITMN:BTSE BS-241/241 II Introduction

    Id:0900d8058006c54a

    Figure 7 LMT Tree View lower level - Window

    In order to perform the command consider following instructions: Select BSS- EQUIPMENT or BSS-FUNCTIONAL by double left-click Select a BTS by double left-click (e.g. BTSEP) Select BTS relevant subdirectory by double left-click (e.g RACK) Select BTS module by double left-click (e.g FCUMAIN:0), see Figure 7, LMT Tree

    View lower level - Window. Perform command by double right-click (e.g. LOCK)After performing the task, the system may give test outcome. In that case note the test outcome, because it could be important for the next task.

    Parameters and Parameter ValuesAfterwards set the parameters and parameter values if necessary. See , Parameters and Parameter Values.Procedures are organized in steps. See an example of a possible procedure in this manual.

    1 Log on LMTConnect the LMT to the BTSE and start the log on procedure.

    %76PRGXOH

    FRPPDQG

  • 18 A30808-X3247-M357-04-7630

    ITMN:BTSE BS-241/241 II

    Id:0900d8058006c54a

    Introduction

    2 Lock Suspected Moduleb ManagedElement BSS-EQUIPMENT BTSEP BTSEP: RACK FCUMAIN FCUMAIN: LOCK FCUMAIN1. A Select the Parameter Value window pops up:

    1.1 Enter the parameter values (RXLEVADJ(-24.0 ... 24.0 step 1.0), e.g. 15)2. Click on the Submit button

    3 END

  • A30808-X3247-M357-04-7630

    19

    ITMN:BTSE BS-241/241 II Safety Instructions

    Id:0900d8058006eaf5

    2 Safety Instructions

    2.1 Electrostatically Sensitive ComponentsGeneralHandel all modules with extreme care, bacause each one contains many electrostati-cally sensitive devices (ESD).All modules which contain ESD are marked with the ESD symbol on the faceplate or inside.

    Figure 8 ESD Symbol

    Rules for HandlingObserve the following safety instructions: Personnel should avoid wearing synthetic clothing and shoes with plastic soles, as

    these encourage the build-up of electrostatic charge. Before handling modules, personnel should be discharged of electrostatic charging.

    For this reason personnel should always put on a grounded wrist strap before changing a module.

    ESDs should not be brought in contact with electrostatically charged or chargeable objects.

    ESDs should only come in contact with high valued discharging material ("gentle" discharging), i.e., should not be made subject to "harsh" discharging with, for example, a metal plate.

    ESDs should be set down on grounded surfaces only (flexible bases with a ground-ing connection for servicing purposes)

    ESDs should not be brought into the vicinity of strong DC electrical fields, e.g. cathode ray tubes/monitors (safety distance at least 10 cm/~4 inches).

    All tools and test equipment should be discharged of electrostatic charging before handling modules.

    ESDs should only be transported in appropriate packing. A grounded wrist strap must be put on before removing ESDs.

    Modules should only be touched by their edges. Components or printed circuits should not be touched.

  • 20 A30808-X3247-M357-04-7630

    ITMN:BTSE BS-241/241 II

    Id:0900d8058006eaf5

    Safety Instructions

    2.2 WarningsThe following warnings appear in the document:

    2.3 Symbols UsedThe following symbols are used in this manual:

    Figure 9 Symbols Used

    2.4 System Voltages In case of: BS-240/240 II/240XL/240XL II, BS-241, BS-40, BS-41, BS-240XS and

    BS-288 all system units require a power supply of 230V AC, which are converted to -48V DC (positive pole grounded).

    In case of: 240U II/240XLU/240XLU II, BS-241U, BS-40U, BS-41U all system units require a power supply of 207V AC.

    In case of: BS-82 II eMicro all the system units require a power supply between 88V-300V AC, which are converted to -48V DC (positive pole grounded).

    In case of: BS-82 eMicro the following types of power supply are available: -115 V AC (ACPSC/U) -230V AC (ACPSC) or -48V DC (DCPSC)

    Some parts are supplied with the line voltage directly and are to be handled with safety tools with extreme care. Only trained personnel should carry out those jobs. Take care, some parts produce a high operating temperature.This warning must appear in the original German text:Alle Systemeinheiten bentigen eine Wechselspannung von 230V AC, die in eine Gle-ichspannung von -48V DC (positiver Pol an Masse) umgesetzt wird.Einige Teile fhren Netzspannung und sind mit besonderer Sorgfalt zu behandeln. Nur

    !CAUTION Electrostatically Sensitive ComponentsModules are susceptible to damage by electrostatic discharge.Follow ESD precautions when removing and inserting modules. Refer to Chapter 2.1, Electrostatically Sensitive Components.

    Symbol Meaning

    Reference to another procedure/procedure step

    Safety note; the notes given here are to be followed with care. Non-observance can lead to personal injury and property damage.

    ESD (Electrostatic Sensitive Device) precautions to be taken

    Note; important information

    Use the LMT to enter commands

  • A30808-X3247-M357-04-7630

    21

    ITMN:BTSE BS-241/241 II Safety Instructions

    Id:0900d8058006eaf5

    ausgebildetes Personal darf entsprechende Arbeiten bernehmen.Weiterhin ist zu beachten, dass sich einige Bauteile stark erhitzen.

    2.5 Changing BreakersBreakers may only be changed by operator. Only allowed breakers, as given in the manual may be used. Change the breakers as described in this manual.

    2.6 Grounding of Modules / Racks / SheltersBefore you switch the power on, plug in all modules to ground correctly. Also plug in ground connections between the racks/shelters correctly.

    2.7 Handling Moist ModulesAfter storage in an humid environment, dry the modules with condensation moisture, before the used. This is necessary, otherwise the modules could be damaged or destroyed.

  • 22 A30808-X3247-M357-04-7630

    ITMN:BTSE BS-241/241 II

    Id:0900d805800c67d3

    Procedures

    3 ProceduresPerform procedures continuously.

    3.1 Visual Inspection

    3.1.1 Visual Inspection of BTSE MechanicsMake a visual inspection of all delivered shelters. Check the shelters of damage, quantity and location of the modules.

    3.1.1.1 SheltersBS-241/241 IIA BS-241/241 II consists of: 1 Base Shelter 1-5 Service Shelter(s) 1-2 Extension Shelter(s)The numbering of the shelters is shown in the following table:.

    g The numbering of the Service Shelter always begins with 3, even if there is no Extension Shelter. Exception: The numbering of the Service Shelter for BS- 241 II begins with 4.

    For setting the correct shelter number, refer to Hardware Manual (see HW:BTSE Modules, ACTP Switch Settings).

    Shelter Num-bering

    Type of Shelter

    0 Base Shelter1, 2 Extension Shelter(s)3 Service 1 Shelter (BS-241) with AC/DC modules47 Service 1A Shelter (BS-241 II) with AC/DC modules; in this case,

    there is no shelter #3

    47 Service 2 Shelter with link equipment and backup batteries

    Table 1 BS-241/241 II Shelter Numbering

  • A30808-X3247-M357-04-7630

    23

    ITMN:BTSE BS-241/241 II Procedures

    Id:0900d805800c67d3

    Figure 10 Example for BS-241 (Front View)For more detailed information about shelter, refer to HW:BTSE Shelters.

    Base Shelter Extension Shelter Extension Shelter

    LMT

    FAN#0 FAN#1

    FAN#2 FAN#3

    FAN#4 FAN#5

    BS-241

    DCP

    CU#0

    CU#1

    CU#2

    CU#3

    CU#4

    CU#5

    CU#6

    CU#7

    DIA

    MC

    O#

    0

    DIA

    MC

    O#

    1

    CO

    RE

    #0

    CO

    RE

    #2

    CO

    RE

    #1

    CO

    RE

    #3

    Plinth

    OVPT

    BS-241 BS-241

    HPD

    U

    HPD

    UH

    PDU

    HPD

    UH

    PDU

    HPD

    U

    Plinth Plinth

    FAN#0 FAN#1

    FAN#2 FAN#3

    FAN#4 FAN#5

    DCP

    CU#0

    CU#1

    CU#2

    CU#3

    CU#4

    CU#5

    CU#6

    CU#7

    DIA

    MC

    O#0

    DIA

    MC

    O#1

    FAN#0 FAN#1

    FAN#2 FAN#3

    FAN#4 FAN#5

    DCP

    CU#0

    CU#1

    CU#2

    CU#3

    CU#4

    CU#5

    CU#6

    CU#7

    DIA

    MC

    O#0

    DIA

    MC

    O#1

    (F)D

    UA

    MC

    O#

    1

    or

    FIC

    OM

    #1

    (F)D

    UA

    MC

    O#

    2

    or

    FIC

    OM

    #2

    (F)D

    UA

    MC

    O#

    3

    or

    FIC

    OM

    #3

    or

    FIC

    OM

    #0

    CO

    AM

    CO

    (F)D

    UA

    MC

    O#

    0

    CO

    AM

    CO

    CO

    AM

    CO

    CO

    AM

    CO

    (F)D

    UA

    MC

    O#1

    or

    FIC

    OM

    #1

    (F)D

    UA

    MC

    O#2

    or

    FIC

    OM

    #2

    (F)D

    UA

    MC

    O#3

    or

    FIC

    OM

    #3

    or

    FIC

    OM

    #0

    CO

    AM

    CO

    (F)D

    UA

    MC

    O#0

    CO

    AM

    CO

    CO

    AM

    CO

    CO

    AM

    CO

    (F)D

    UA

    MC

    O#1

    or

    FIC

    OM

    #1

    (F)D

    UA

    MC

    O#2

    or

    FIC

    OM

    #2

    (F)D

    UA

    MC

    O#3

    or

    FIC

    OM

    #3

    or

    FIC

    OM

    #0

    CO

    AM

    CO

    (F)D

    UA

    MC

    O#0

    CO

    AM

    CO

    CO

    AM

    CO

    CO

    AM

    CO

    TMA7

    TMA6

    TMA0

    TMA7

    TMA6

    TMA0

    TMA7

    TMA6

    TMA0

  • 24 A30808-X3247-M357-04-7630

    ITMN:BTSE BS-241/241 II

    Id:0900d805800c67d3

    Procedures

    3.1.1.2 Mounting and Installation of BTSECheck the internal/external interfaces and least replaceable units (LRU). For more detailed information, refer to MMN:BTSE BS-241.

    3.1.1.3 Check of Base Transceiver Station BTSECheck for delivery quality and quantity on site: Installation of BTS shelter (shelter fixing, fixed boards) Damage to shelter (paintwork, dents) Correct insertion of modules System cabling (shelter cabling) Grounding, earthing Main breakers External interfaces: power supply, antenna, and Abis wiring

    3.1.1.4 Check of BTSE Modules

    Modules in the ShelterYou can find an overview of possible installed modules in the rack type of: BS-241 : refer to TED:BS-240/241 BS-241 II: refer to TED:BS-240/241 IIFor more about modules identification see Chapter 4.3, Module Identification by Inven-tory Data and Label.

  • A30808-X3247-M357-04-7630

    25

    ITMN:BTSE BS-241/241 II Procedures

    Id:0900d805800c67d3

    BTSE ModulesThe entire BTSE contains several cells called BTS.Up to 12 cells are available for BS-241/241 II.Check whether the BTSE modules are configured correctly.

    Redundancy CORE redundancy can be installed. In the CORE, the functionality of clock genera-

    tion, link interface, and Call Control is implemented. The BCCH redundancy is matter of software. The task "BCCH reconfiguration" runs

    in the BTSEplus and the functionality is independent of the type of antenna combin-ing.

    AC/DC redundancy is carried out as n+1 redundancy. N+1 AC/DC Converters operate in load sharing, but n AC/DCs are able to supply the whole BTSEplus.

    Hardware (HW) related modules:

    Per CELL:(F)DUAMCO (Flexible)Duplexer Amplifier MulticouplerDIAMCO Dual Integrated Amplifier MulticouplerFICOM Filter CombinerCOAMCO Co-Duplexer and MulticouplerTMA Tower Mounted AmplifierHPDU High Power Duplexer

    Per Transceiver TRX:

    CU Carrier UnitFlexCU Flexible carrier unit

    In addition there are common modules:COBA Core BasisCOSA Core SatelliteACT Alarm Collection Terminal

    Basic-Modules:DCP DC PanelFAN Fan

    OVPT Overvoltage ProtectionAC/DC AC/DC converter (rectifier)DCBCTRL DC and Battery ControllerBB Backup Battery

  • 26 A30808-X3247-M357-04-7630

    ITMN:BTSE BS-241/241 II

    Id:0900d805800c67d3

    Procedures

    3.1.1.5 Antenna and Feeder CableTest all antennas and feeder cables in advance.

  • A30808-X3247-M357-04-7630

    27

    ITMN:BTSE BS-241/241 II Procedures

    Id:0900d805800c67d3

    3.1.2 Visual Inspection of BTSE Electrics

    3.1.2.1 Polarity of DC Input and ToleranceThe BTSE requires -48 V DC with a tolerance of -15% to +20% (-40,8V/-57,6V) for correct operation (positive pole is grounded). Use the SIEMENS Multimeter to check the voltage.

    3.1.2.2 Circuit BreakersShelter internal breakers are available at the DC Panel in order to supply direct current (DC) to the several modules.The breakers are mounted at the DC Panel on the top of the shelter. There are different types of DC Panel for Base Shelter, Extension Shelter, Service 1 and Service 2 Shelter. There also could be different types of DC Panels for every BS.For more detailed information about DC Breakers for BS-241 refer to HW:BTSE Frames/Panels.

    3.1.2.3 AlarmsInternal and external alarms of all racks are collected by ACT (Alarm Collection Termi-nal) modules and channeled to the COBA in the base rack.There are three types of ACT modules: ACTC is the standard alarm connection module, for every rack and it is a part of the

    DC Panel. ACTM (ACT Master) is an optional alarm connection module for the base racks/shel-

    ters. ACTP provides a connection to the COBA via the CAN BUS. ACTP is for extension

    and service rack/shelter.

    Internal and External AlarmsAll racks are equipped with one ACTC, which provides the rack alarms and the environ-mental alarms (ENVAs). The ACTC in the base rack is directly connected to the COBA, in every other rack it is connected to ACTP. ACTC provides 16 alarms. There are 7 Rack Alarms (RAL), created automatically during the creation of RACK and FAN, and 9 Operator Alarms (OAL). The OAL are numbered ENVA 0 - ENVA 8. ENVAs alarms can be customized. For detailed information refer to IMN:BTSE BS - 241/241 II, section Alarm Collection Terminal ACTC - internal Alarms/DC Supply.The Base Rack can be equipped with ACTM, which is used for connecting of additional environmental alarms (ENVAs). The ACTM supports 48 ENVAs, numbered ENVA 9ENVA 56, and 8 Operator Commands (not supported by SW of BR5.5). The installation of ACTM is optional. If no ACTM is installed, there are 16 Alarms available in the Base Rack.For detailed information refer to IMN:BTSE BS - 241/241 II, section Alarm Collection Terminal - external Alarm Sensors.Alarms can be checked by using the LMT after BTSE Power-On.

  • 28 A30808-X3247-M357-04-7630

    ITMN:BTSE BS-241/241 II

    Id:0900d805800c67d3

    Procedures

    3.1.2.4 DC Connector for Network Termination (NT)The power supply (-48 V DC, max. 1A) at the SubD9 connector is free for operator use.

  • A30808-X3247-M357-04-7630

    29

    ITMN:BTSE BS-241/241 II Procedures

    Id:0900d805800c67d3

    3.1.3 Visual Inspection of BTSE Modules

    3.1.3.1 Abis Configurations to the BTSThe following figure shows four possible Abis configurations to connect the BTS to the BSC. These configurations are called Star (single), Loop (several in circle), Multidrop (several), and Cross Connect.

    Figure 11 Abis Connections to the BTS

    In case of a Star link, only PCM1 must be wired. For Loop and Multidrop links, PCM one and two are necessary.For pinning see IMN:BTSE Chapter Abis-InterfacePCM Link Terminal.For the settings of Abis Interface to match 120 , 100 or 75 line impedance, see Chapters , Switch Settings on COBA2P8 and , Switch Settings on COSA.

    3.1.3.2 Tower Mounted Amplifier (TMA) ConnectionIf an antenna is present check for correct RF cabling connections of TMA. The (F)DUA-MCO/DIAMCO supply the DC power for TMA at their antenna ports via the RF coax cable.

    %6&

    %76( %76(%76(

    6WDU

    %6&

    %76( %76(%76(

    0XOWLGURS

    %76( %76(%76(

    /RRS

    %6&

    &URVV&RQQHFW

    %6&

    %76( %76(

    %76(

    %76(

  • 30 A30808-X3247-M357-04-7630

    ITMN:BTSE BS-241/241 II

    Id:0900d805800c67d3

    Procedures

    Figure 12 TMA, e.g.

    3.1.3.3 Adjustable ModulesThere are several modules containing adjustable devices. Check the default states or special project settings. The software image SWI is only adjustable via LMT.The following table gives an overview:

    Boot Software (FW)Some modules contain special on board boot software on EEPROMs.

    ANT

    BTS

    No MODULE see1 ACT HW:BTSE Modules, ACTP 2 COBA Figure 133 COSA Figure 154 DCBCTRL Figure 165 DIAMCO Table 86 (F)DUAMCO Table 8

    Table 2 Adjustable Modules

  • A30808-X3247-M357-04-7630

    31

    ITMN:BTSE BS-241/241 II Procedures

    Id:0900d805800c67d3

    The allocation of the EPROMs is listed in the Release Note. The new boot software can be downloaded via LMT.

    Software Images SWISome modules receive the SWI via the LMT.

    Switch Settings on COBA2P8The COBA contains three transceiver submodules for 75 , 100 , or 120 impedance matching.

    Module Board FILE NAMECOBA COBA2P8 btbbcx01.swi

    COBA4P12 btbbcx03.swiCU CUxxx btbbix01.swi

    ECU/FCU btbbix07.swiGCU btbbix10.swi

    Table 3 Boot Software

    OBJECT FILE NAMESWL HSxxxxxx.SWL

    depending on variant of cipheringVAM VSxxxxxx.VAM

    depending on variant of cipheringCOBA2P8 BTSBCX01.SWICOBA4P12 BTSBCX03.SWICU BTSBIX01.SWIGCU/ECU/FCU BTSBIX07.SWI

    Table 4 Software Images SWI

  • 32 A30808-X3247-M357-04-7630

    ITMN:BTSE BS-241/241 II

    Id:0900d805800c67d3

    Procedures

    Figure 13 COBA2P8

    Port 2 Port 1

    S2 S1

    External ClockSynchronization

  • A30808-X3247-M357-04-7630

    33

    ITMN:BTSE BS-241/241 II Procedures

    Id:0900d805800c67d3

    Switch Settings of Port 1 and Port 2

    External Clock Synchronization

    For more detailed information about Settings on COBA2P8 refer to HW:BTSE Modules, COBA.

    Impedance Switch 1 Switch 2 Switch 3 Switch 4 Switch 5 Switch 6PCM30 120 off off off off off offPCM30 75 on on on off off offPCM24 100 off off off on on on

    Impedance Switch 1 Switch 2 Switch 3 Switch 4 Switch 5 Switch 675 on off off on on on100 off on off off on on120 off off on off on onhigh (TTL) f=< 2 MHz

    off off off on off off

    high (TTL) f=> 2 MHz

    off off off on on on

  • 34 A30808-X3247-M357-04-7630

    ITMN:BTSE BS-241/241 II

    Id:0900d805800c67d3

    Procedures

    Switch Settings on COBA4P12

    Figure 14 COBA4P12

    g Settings for port 0 up to port 7 are made with the LMT. For example: Create BPORT:NAME=BPORT:0,L1PT=pcm30crc4,L1RAT=ProtocolSignalling, LCONF=star, LIMP=Imp100 or 120 ;

    External Clock Synchronization

    External ClockSynchronization

    Impedance Switch 1

    Switch 2

    Switch 3

    Switch 4

    Switch 5

    Switch 6

    Switch 7

    Switch 8

    75 coaxial pair on off off on on on off off100 balanced twisted pair off on off off on on off off120 balanced twisted pair off off on off on on off off

  • A30808-X3247-M357-04-7630

    35

    ITMN:BTSE BS-241/241 II Procedures

    Id:0900d805800c67d3

    For more detailed information about Settings on COBA4P12 refer to HW:BTSE Mod-ules,COBA.

    high (TTL) f< 100 kHz off off off on off off off offhigh (TTL) f> 100 kHz off off off on on on off off

    Impedance Switch 1

    Switch 2

    Switch 3

    Switch 4

    Switch 5

    Switch 6

    Switch 7

    Switch 8

  • 36 A30808-X3247-M357-04-7630

    ITMN:BTSE BS-241/241 II

    Id:0900d805800c67d3

    Procedures

    Switch Settings on COSA

    Figure 15 COSA

    Port 1Port 2Port 3Port 4Port 5Port 6

    S1S2S3S4S5S6

  • A30808-X3247-M357-04-7630

    37

    ITMN:BTSE BS-241/241 II Procedures

    Id:0900d805800c67d3

    Switch Settings of Port 1 to Port 6

    For more detailed information about Settings on COSA refer to HW:BTSE Modules, COSA.

    DCBCTRLEach power supply sub-rack has its own DCBCTRL module. It indicates the status ofthe power supply system with LEDs.The DCBCTRL supervises the AC/DC modules and the DC outputs of the AC/DC system.

    Switch Settings on DCBCTRL for BS-241, Service 1 ShelterBattery TypeSelect a proper characteristic curve for battery charging.

    Impedance Switch 1 Switch 2 Switch 3 Switch 4 Switch 5 Switch 6PCM30 120 off off off off off offPCM30 75 on on on off off offPCM24 100 off off off on on on

    Type Bit 0 Bit 1Oerlikon on not usedSonnenchein/Exite/Hawker off not used

    Table 5 Battery Type

  • 38 A30808-X3247-M357-04-7630

    ITMN:BTSE BS-241/241 II

    Id:0900d805800c67d3

    Procedures

    Figure 16 DIP Switches for Battery Type, Battery Capacities and Slot-ID

    Battery TypeBattery CapacitySelectable battery capacities: 0 Ah (no battery), 5 Ah, 10 Ah,...1275 Ah. The battery capacities can be set with two 8 bit DIP switches, one for each battery block;1 LSB = 5Ah. The setting is calculated by adding all values where the contacts of the DIP switch are set to "ON".

    g The state of the object BATTERY does not depend on the existence of a real battery. It depends on the Battery Capacity DIP switch settings on the DCBCTRL

    640 Ah on

    320 Ah on

    160 Ah on

    80 Ah on

    40 Ah on

    20 Ah on

    10 Ah on

    5 Ah on

    Table 6 Battery Capacity DIP Switch

    6ZLWFK6ORW,'

    6ZLWFK%DWWHU\&DSDFLW\

    6ZLWFK%DWWHU\&DSDFLW\

    9

    6ZLWFK%DWWHU\7\SH

    %$7

  • A30808-X3247-M357-04-7630

    39

    ITMN:BTSE BS-241/241 II Procedures

    Id:0900d805800c67d3

    module. If one of these two DIP switches is set to a value different from 0 Ah, the respective HMO BATTERY goes to enabled.

    Slot-IDSelectable Slot-ID: The CAN-Bus address can be set with a 2 bit DIP switch in order to distinguish between different AC/DC frames mounted to one rack.

    Both switches must be in different positions.Some DCBCTRL versions dont have DIP switches, but are programmable by means of a special software application. For more information see HW:BTSE Modules, DCBCTRL.

    Address Bit 0 Bit 1ACDCP0 on offACDCP1 off on

    Table 7 Slot-ID

  • 40 A30808-X3247-M357-04-7630

    ITMN:BTSE BS-241/241 II

    Id:0900d805800c67d3

    Procedures

    Switch Settings on DCBCTRLDVx for BS-241 II, Service 1A ShelterOne DCBCTRLDVx/DCBCTRLAVx module shall be installed into BS-40 II Base Rack.This DCBCTRL version has a default setting of 92 Ah for Hawker batteries. If battery type or capacity changes are required, the DCBCTRLs charging characteristic must be adapted accordingly by means of a special software application. This also applies to new DCBCTRL modules that are used as replacement units for formerly adapted DCBCTRLs.This DCBCTRL version does not have DIP switches (because of no CAN interface), but are programmable by means of a special software application. For more information see HW:BTSE Modules, DCBCTRL.The software application and its corresponding user manual can be obtained via the Siemens Tools and Test Equipment (TTE) website.

    3.1.3.4 Antenna CombiningThe (F)DUAMCO/FICOM must be installed in the ACOM slots. To achieve short cabling between CU and ACOM, the ACOM slots are assigned to definite CU slots.g All unused RX and RXCA connectors must be terminated with a 50 load when the

    corresponding antenna port of the (F)DUAMCO is connected to an antenna or cas-cading output of (F)DUAMCO/DIAMCO/COAMCO.The open TX inputs of (F)DUAMCO/COAMCO do not need to be terminated in normal operation.

    DUAMCOThe DUAMCO 2:2 and 4:2 occupy one ACOM slot each and are installed in the assigned slot for the CU that must be combined.The DUAMCO 8:2 occupies two ACOM slots and is installed either on the left or on the right two slots.

    FDUAMCOFor each system GSM 850, GSM 900, GSM 1800 and GSM 1900 one type of FDUAMCO units is available, which can be configured by jumper cables for One-To-One mode (= FDUAMCO 2:2) or Two-To-One mode (= FDUAMCO 4:2).The FDUAMCO unit can be configured to different modes by application of two jumpers.FDUAMCO 2:2The FDUAMCO in 2:2 configurations is used for 2 antennas with 1 carrier each.For this configuration, the connectors 2 and 3 have to be jumpered.The second free jumper per module can be placed at connector 4.FDUAMCO 4:2The FDUAMCO in 4:2 configurations is used for 2 antennas with 2 carriers each.For this configuration, the connectors TX 0 and TX 1 are used as TX inputs. One jumper is applied for the connectors 1 and 2. The second jumper is placed between connectors 3 and 4.

  • A30808-X3247-M357-04-7630

    41

    ITMN:BTSE BS-241/241 II Procedures

    Id:0900d805800c67d3

    FDUAMCO 8:2For an 8:2 configuration a COAMCO can be used in conjunction with a FDUAMCO in 4:2 configuration.

    COAMCOThe COAMCO consists of two identical Modules (0/1), each having a transmit and a receive path. A COAMCO is used in conjunction with a FDUAMCO in 4:2 configuration to provide an 8:2 configuration. The COAMCO combines 2 additional carriers per module with the 2 carriers from the output 4 of the FDUAMCO and feeds the 4 carriers back to the input 3 of the FDUAMCO.g No specific alarm exists for a defective COAMCO module. Check the LEDs

    POWER/ALARM at the COAMCO module. Red LED lights signal a defective COAMCO module.

    FICOMUsage of FICOM modules of different variantsThere are several different FICOM modules: FIPLUB2RV3, FIPLUB2RV4, FIPLUX2RV3, FIPLUX2RV4.One Base Module can be expanded by 3 Expansion Modules, all modules in this com-bination must have the same variant (all ...V3 or all ...V4).Installation of FICOM ModulesFor each cell, install 1 FICOM plus base module (FIPLUB). To combine more than 2 car-riers, the base module can be expanded by the FICOM plus expansion module (FIPLUX). The expansion can be done to one side only per base module.Expansion of FICOM can only be done inside each rack. To combine more than 8 car-riers, a base module must be installed in the extension rack.

    g Open expansion connectors RF EXP of FICOM modules must be terminated with the terminator delivered with the FICOM base module.

    It is suggested to fix the jumper cable very carefully, do not torque too strong. The cable should not move. Otherwise the cables inner conductor will tear.The mounting location of the FICOM modules depends on the Cell configuration and antenna combining. It is possible to have a mixed installation of (F)DUAMCO and FICOM modules, within one rack.

    3.1.3.5 Antenna MulticouplingMulticoupling can be done by DIAMCO, (F)DUAMCO or COAMCO. Each DIAMCO/(F)DUAMCO/COAMCO can drive as many CUs as RX output connectors are available.

    DIAMCOAll unused RX and RXCA connectors must be terminated with a 50 load when the cor-responding antenna port of the DIAMCO is connected to an antenna or cascading output of DIAMCO / (F)DUAMCO/COAMCO.

  • 42 A30808-X3247-M357-04-7630

    ITMN:BTSE BS-241/241 II

    Id:0900d805800c67d3

    Procedures

    Figure 17 DIAMCO Antenna Connection and DIP Switches

    The DIP switch is used for setting the TMA configuration of the DIAMCO/(F)DUAMCO. Switch 1 must be set to "on" if a TMA is installed. If no TMA is installed, switch 1 must be set to "off".

    g The setting of switches 2-4 determines the DIAMCO/(F)DUAMCO attenuation.The total attenuation of the feeder cable (between TMA and DIAMCO/(F)DUAMCO) and the DIP switch must be 6 dB.That means, the following formula applies:DIP switch value = 6 dB minus measured insertion loss of feeder cable.

    Function Switch 1 Switch 2 Switch 3 Switch 4 TMA off / AMCO mode off X X XTMA on / MUCO mode on X X Xattenuator LNA 0 dB off X X X

    Table 8 Switch Settings for DIAMCO / DUAMCO / FDUAMCO

    0RGXOH 0RGXOH

    $17 $17

    5;

    5;

    5;

    5;

    5;

    5;

    5;

    5;

    5;

    5;

    5;

    5;

    5;

    5;

    5;

    5;

    5;&$ 5;&$

    6ZLWFKHV

    $QWHQQD&RQQHFWRU

  • A30808-X3247-M357-04-7630

    43

    ITMN:BTSE BS-241/241 II Procedures

    Id:0900d805800c67d3

    "X": any position allowedg Switch 1 does not work when a TMA Alarm is present.

    DUAMCO/FDUAMCOThe switch settings for (F)DUAMCO is the same as for DIAMCO, described in Table 8.

    attenuator LNA 0 dB on off off offattenuator LNA 1 dB on on off offattenuator LNA 2 dB on off on offattenuator LNA 3 dB on on on offattenuator LNA 4 dB on off off onattenuator LNA 5 dB on on off onattenuator LNA 6 dB on off on onattenuator LNA 7 dB on on on onfactory setting off off off off

    Function Switch 1 Switch 2 Switch 3 Switch 4

    Table 8 Switch Settings for DIAMCO / DUAMCO / FDUAMCO

  • 44 A30808-X3247-M357-04-7630

    ITMN:BTSE BS-241/241 II

    Id:0900d805800c67d3

    Procedures

    Figure 18 (F)DUAMCO DIP Switch abd Antenna Connection

    Cascading MulticouplersFor supplying more receiver inputs, the multicoupler can be cascaded to save antennas in the RX path. Cascading can be done twice, the possible configurations are shown in Table 9.The chain goes from the antenna to the BTSE, so the first device is the one nearest to the antenna. The Parameter LNAPRED must be set if there is a TMA installed to activate the TMA. If there is no TMA, LNAPRED must be set for the 1. and 2. Cascade.

    $17 $17

    7HVWRXW 7HVWRXW

    7; 7;

    7; 7;

    5;&$

    5;

    5;

    5;

    5;

    5;

    5;

    5;

    5;

    5;&$

    $QWHQQD&RQQHFWRU

    First Device 1. Cascade 2. CascadeDIAMCO DIAMCODIAMCO DIAMCO DIAMCO(F)DUAMCO DIAMCO(F)DUAMCO (F)DUAMCO

    Table 9 Cascading of Multicouplers

  • A30808-X3247-M357-04-7630

    45

    ITMN:BTSE BS-241/241 II Procedures

    Id:0900d805800c67d3

    g The first device in the chain must be switched into the high amplifying AMCO mode, the cascaded devices into MUCO mode.To install TMA, all other devices have to be set in MUCO mode.

    3.1.3.6 HPDUThe High Power Duplexer is an RF module with the requirement to save antennas in the TX path. For FICOM use is one antenna for TX necessary. Also are two antennas per cell for RX diversity necessary.The main functions of HPDU is combining RX and TX signal. In the TX path, the HPDU is filtering the TX signals coming from the shelter and feeding them to the TX/RX antenna. In the RX path, the function is filtering the incoming signal.The HPDU is placed between antenna and FICOM/DIAMCO.

    TMADIAMCO DIAMCOTMADIAMCO DIAMCO DIAMCOTMA(F)DUAMCO DIAMCOTMA(F)DUAMCO (F)DUAMCOIf the cascaded element is a (F)DUAMCO, a special cable must be used with an SMA connector at one end and a 7/16 connector at the other end. (This cable is not avail-able as part of the system cabling).

    First Device 1. Cascade 2. Cascade

    Table 9 Cascading of Multicouplers

  • 46 A30808-X3247-M357-04-7630

    ITMN:BTSE BS-241/241 II

    Id:0900d805800c67d3

    Procedures

    3.2 Preparation for Offline TestsThe purpose of this module is to execute all commissioning activities for checking the delivery quality and quantity of the BTSE on site. The following steps must be executed to start the system:1. Obtain the recommended tests and test equipment2. Preparation of tests and test equipment3. Check Polarity of DC Input and Tolerance4. BTSE power on5. Start of LMT6. Offline testsFinally all documents must be filled in and all activities must be confirmed by the cus-tomer.

    3.2.1 Recommended Test Equipment and ToolsSeveral devices, instruments, accessories, and utensils must be provided and prepared for commissioning on site.

    3.2.1.1 Test EquipmentThe equipment, especially the available options change quickly. Therefore, the listed equipment may not be currently available. It is suggested that the equipment listed below or equivalent must be present for call simulation and verification of correct oper-ation.

    Multimeter HW

    SIEMENS Multimeter

    Local Maintenance Terminal LMTFor detailed requirements, refer to manual OGL:LMT Evolution.

    RF TerminationDepending on the BTSE and the equipped modules, some RF terminations must be present. TX

    50 SMA ((F)DUAMCO,FICOM) RX

    50 SMC (DIAMCO,(F)DUAMCO) RXCA

    50 SMA (DIAMCO cascading output)Mobile Station MS HW

    GSM 900/1800 mobile phone, e.g. S45 GSM 1900 mobile phone, e.g. S55 Test Plug-In SIM

  • A30808-X3247-M357-04-7630

    47

    ITMN:BTSE BS-241/241 II Procedures

    Id:0900d805800c67d3

    ToolsSpecial tools for commissioning activities on site are listed below. Antistatic Set

    for ESD Module Handling SMA Tool

    with torque wrench for semi-rigid/flexi Cable Connectors SMC Tool

    with torque wrench for semi-rigid/flexi Cable Connectors Semi-Rigid Bending Tool

    for semi-rigid cable connection TDMA Measuring Tools (Tests with HP 8594A/E) and Trigger Adapter- HW

    GSM 1900: HP 8594 Personality Card 2 Measuring cables with BNC-Plugs male (sufficient length) Adapter SMA maleBNC female Trigger Adapter TAD-L S30861-U2003-X-*

    (100-pins AMP-Plug with 4 x BNC-Plug female 1 Adapter N-Connector maleBNC female HP 8590 series spectrum analyzer operating manual Users Guide HP85715B GSM 850 - 900 Transmitter Measurement Personality Users Guide HP 85722B GSM 1800 Transmitter Measurement Personality

    3.2.1.2 Preparation and Presetting of Test Equipment

    Test EquipmentFor minimum test time and correct test results, the devices must be prepared on site.

    RF Termination HW: Before RF measurements are executed, the following connectors must be ter-

    minated with 50 SMA/SMC resistors: TX: open FICOM/(F)/DUAMCO inputs (SMA) RX: open (F)DUAMCO/DIAMCO outputs (SMC) RXCA: open (F)DUAMCO/DIAMCO outputs (SMA) TESTOUT: open (F)DUAMCO/FICOM outputs (SMA)

    Software (SW)For all tests, only released SW (corresponding to the BTSE HW/SW release) is allowed to be running on the test equipment (TE).

    Boot Software/Firmware (SW/FW)For all tests, only the released SW is allowed to be running on the BTSE corresponding to the BTSE HW/SW/FW release/revision.

  • 48 A30808-X3247-M357-04-7630

    ITMN:BTSE BS-241/241 II

    Id:0900d805800c67d3

    Procedures

    3.2.2 BTSE Power-On

    3.2.2.1 Check Polarity of DC Input and Tolerance

    The BTSE requires -48 V DC with a tolerance of -15% to +20% (-40,8V/-57,6V) for correct operation (positive pole is grounded). Use the SIEMENS Multimeter to check the voltage.

    3.2.2.2 Breakers before BTSE Power-OnDepending on the configuration of equipped modules, only the corresponding breakers must be switched on. All other breakers are switched off.For more detailed information about DC Breakers for BS-241 refer to HW:BTSE Frames/Panels.g In case of supervising all breakers with one common alarm sensor, all breakers

    must be switched on, independent of the configuration.

    Power-On

    1 Turn on the power switch for power supply to the BTSE.

    2 The BTSE requires -48 V DC with a tolerance of -15% to +20% (-40,8V/-57,6V) for correct operation (positive pole is grounded). Check this voltage.

    END

    !CAUTION Electrostatically Sensitive ComponentsModules are susceptible to damage by electrostatic discharge.Follow ESD precautions when removing and inserting modules. Refer to Chapter 2.1, Electrostatically Sensitive Components.

  • A30808-X3247-M357-04-7630

    49

    ITMN:BTSE BS-241/241 II Procedures

    Id:0900d805800c67d3

    3.3 Checking the State of all Modules

    1 Check the State of all ModulesThe State of Modules checked via LMT:All images have been loaded. This is confirmed by a state event report: Administrative State = UNLOCKED, Operational State = ENABLED for all successfully created objects. This can be verified via logfile in browser mode or via LMT commands with: b BSSNE Btseep Br:BSS-EQUIPMENTBTSEPBTSEP:RACKRACK:

    :GETNAME=RACK:/:

    The State of Modules checked via LEDsAll red LEDs (except the PA LED on the CU) are switched off. If no Abis is connected, the coresponding LED on the COBA/COSA (if installed) is red. The files can be viewed in the Message Browser window.The following LED description is only valid for the software installation.The modules have the normal LED indication set as shown below for normal operation.1. DIAMCO

    2. FICOM

    OK off off ALOK green off RS

    FICOM (base module) FIBLUB2*V4TNF ALM off off TNF ALM

    green DC ONVSWR off off RESET

    FICOM (expansion module) FIBLUX2*V4TNF ALM off off TNF ALM

    green DC ON

  • 50 A30808-X3247-M357-04-7630

    ITMN:BTSE BS-241/241 II

    Id:0900d805800c67d3

    Procedures

    3. DUAMCO/FDUAMCO

    4. CU

    4. FlexCU

    5. COBA2P8

    5. COBA4P12

    off RESET

    FICOM (base module) FIBLUX2*V3VSWR ALM off off TNF ALM 0DC ON green off TNF ALM 1RESET off

    FICOM (expansion module) FIBLUX2*V3off TNF ALM 0

    DC ON green off TNF ALM 1

    TMA0 off off TMA 1RESET o off off RESET 1VSWR 0 off off VSWR 1POWER 0 green green POWER 1

    OK flashing green off SWRES off red PA

    OK flashing green off RESSW 0 off off SW 1PA 0 red red PA 1

    ACT flashing green flashing red RCOBAFLOC off off HMOABIS 1 off off ABIS 2

    ACT flashing green flashing red RCOBAFLOC off off HMOABIS 1 off off ABIS 2ABIS 3 off off ABIS 4

    FICOM (expansion module) FIBLUX2*V4

  • A30808-X3247-M357-04-7630

    51

    ITMN:BTSE BS-241/241 II Procedures

    Id:0900d805800c67d3

    6. COSA6P16

    6. COSA4P12

    7. ACT

    For more information about LED position see HW:BTSE Modules.

    END

    ACT flashing green flashing red RCOSAABIS 7 off off ABIS 8ABIS 5 off off ABIS 6ABIS 3 off off ABIS 4

    ACT flashing green flashing red RCOSAABIS 5 off off ABIS 6ABIS 7 off off ABIS 8

    To be activated by SW off off Reset of C

  • 52 A30808-X3247-M357-04-7630

    ITMN:BTSE BS-241/241 II

    Id:0900d805800c67d3

    Procedures

    3.4 Checking the Environmental Alarms

    Check the Operator Alarm Interface. The environmental alarms must have been config-ured previously.

    1 For every couple of alarm terminals on the alarm collecting point, alternatively close/open the contact and check the corresponding alarm message on the LMT. If the alarm is configured as high, an alarm start message will be displayed first. If it is con-figured as low, an alarm cease message will be displayed first (provided that the alarm was active before). g Important: The test should not be done before the completion of ACT config-

    uration.For more information about alarms for: BS-240/240 II/240XL/240XL II refer to IMN BS-241/241 II refer to IMN BS-40/40 II refer to IMN BS-41 refer to IMN BS-288 refer to IMN BS-240XS refer to IMN BS-82 eMicro refer to IMN BS-82 II eMicro refer to IMN

    END

  • A30808-X3247-M357-04-7630

    53

    ITMN:BTSE BS-241/241 II Procedures

    Id:0900d805800c67d3

    3.5 Replacing Failed HW

    1 Test Replaced ModulesAfter replacing a failed HW unit, it is necessary to enable this new HW unit via TEST or DELETE/CREATE command before starting any other activities (e. g. downloading or activating SW). The reason for this is that the PID of a new module is only updated after the command TEST or DELETE/CREATE was performed and it is necessary during download to have the actual PID of all modules stored on the COBA.Test any replaced module.If the BTSM is unlocked, a full BTS alignment is caused. If any BTSE configuration commands are performed during an alignment, a new alignment will be started.For more information refer to Maintenance Manual.

    END

  • 54 A30808-X3247-M357-04-7630

    ITMN:BTSE BS-241/241 II

    Id:0900d805800c67d3

    Procedures

    3.6 Generating BTS Backup FilesVia the backup files (script files) a quick reconfiguration of the BTSE is possible (for example necessary after a COBA replacement).For generating BTS backup files with the LMT Evolution, refer to the operator guidelines OGL:LMT Evolution.

    1 Generate BTS Backup FilesTo generate BTS Backup Files:1. Select File Backup Bts from the LMT Evolution menu or click on the correspond-

    ing icon in the tool bar.2. Click on the Get button in the appearing window.3. Enter a name for the saved configuration (e.g. Backup1) and confirm by clicking on

    the OK buttoon.The scripts will produce the following files on the [LMT_ROOT]\BKBTS\subdirectory: For BTS PLUS: BS240, BS240XL, BS241, BS40, BS41, BS40II, BS82II For BTS XS: BS240XS, BS288System Response: For BTS PLUS (BS240, BS240XL, BS241, BS40, BS41, BS40II, BS82II):The con-

    figuration data of the BTSE are loaded to the LMT PC and are then converted to script files: SCRIPT1P.LMT, SCRIPT2P.LMT, SCRIPT3P.LMT, SCRIPT4P.LMT, SCRIPT5P.LMT, SCRIPT6P.LMT. These files are written into the [LMT_ROOT]\BKBTS\subdirectory. After this process, the following message is displayed: Get HW operation is completed.

    For BTS XS (BS240XS, BS288):The configuration data of the BTSE are loaded to the LMT PC and are then converted to script files: SCRIPT1XS.LMT, SCRIPTX2.LMT, SCRIPT3XS.LMT, SCRIPT4XS.LMT, SCRIPT5XS.LMT, SCRIPT6XS.LMT. These files are written into the [LMT_ROOT]\BKBTS\subdirec-tory. After this process, the following message is displayed: Get HW operation is completed.

    2 Copy the Script Files to DiskCopy the script files from [Drive]:\[LMT_ROOT]\BKBTS\subdirectory to some storage media and keep it at the site, in case of need.

    END

  • A30808-X3247-M357-04-7630

    55

    ITMN:BTSE BS-241/241 II Procedures

    Id:0900d805800c67d3

    3.7 Remote InventoryThe function Remote Inventory of the Siemens Basestation System performs elec-tronic, non-volatile storing of the complete, individual product identification data (PID) of each inventory object.Modules that have their inventory data on board are called on-board Remote Inventory Units (ob_RIUs). The PID of these ob_RIUs are automatically loaded to an Inventory Data Table (IDT) file if you upload the inventory data from the BTSE.In order to include inventory data of objects without a non-volatile storage (e.g. frames, racks, OEM components), the data of these not on-board Remote Inventory Units (nob_RIUs) must be entered via the offline tool IDF Evolution, and downloaded to the BTSE where they are stored on the COBA.The complete Remote Inventory Data of each rack are provided on a disk as an Inven-tory Data File (IDF) by the Regional Logistic Center (RLC). The file name is composed of the serial number of the rack ( / replaced by _) and the extension IDF, for example: CN+_JD100001.IDF. However, since the RLC does not know the site specific values (such as the Sales Unique Name, the SBS equipment position or the rack position), these values are set to default numbers. Therefore, the provided IDF file must be modified. Afterwards, it is necessary to create an up-to-date IDF file for backup and to download the modified data to the BTSE.

    1 Start IDF EvolutionTo start the IDF Evolution select Tools IDF EVOLUTION from the LMT Evolution menu.

    2 Open IDF FileThe IDF file is stored on a disk that is delivered with each rack of the BTSE. To open the IDF file:1. Copy the IDF file from the storage media to the harddisk of the LMT, e.g.

    C:\LMT\ldf\*.idf.2. Select File Open from the menu of the IDF Evolution.3. Select the file from the list in the appearing window.4. Double-click on the file name or click on the Open button.

    3 Set SBS Equipment PositionTo set the SBS Equipment Position:1. Select File Set SBS_Eq_Pos from the menu.2. Enter the SBS equipment position in the appearing window and click on the Replace

    All " button.

  • 56 A30808-X3247-M357-04-7630

    ITMN:BTSE BS-241/241 II

    Id:0900d805800c67d3

    Procedures

    Figure 19 Setting the SBS Equipment Position3. A message window opens that tells you that the search was completed and how

    many replacements were made. Confirm this message window by clicking on the OK button.

    4 Set Rack PositionTo set the rack position:1. Select File Set F. A. Rack Pos from the menu.2. Enter the rack position RACK_Pos in the appearing window and click on the

    Replace All button.3. A message window opens that tells you that the search was completed and how

    many replacements were made. Confirm this message window by clicking on the OK button.

    5 Check nob_RIU DataAre the data of the nob_RIU units O.K.?Y h.......... 7N h.......... 6

  • A30808-X3247-M357-04-7630

    57

    ITMN:BTSE BS-241/241 II Procedures

    Id:0900d805800c67d3

    For a complete list of all nob_RIUs refer to...See ........... MMN:BTSE BS-240/240 II/240XL/240XL II

    ........... MMN:BTSE BS-241/241 II

    ........... MMN:BTSE BS-240XS

    ........... MMN:BTSE BS-288

    ........... MMN:BTSE BS-40/40 II

    ........... MMN:BTSE BS-41

    ........... MMN:BTSE BS-82

    ........... MMN:BTSE BS-82 II

    6 Edit Remote Inventory Data of nob_RIU UnitsThe records of the nob-RIUs are shown in bold letters. Only these records are editable.The data can be edited manually or automatically via the 2D-Code Reader.To edit the Remote Inventory Data of the nob_RIU units:1. Select the I-Record of the unit you need to edit and click the right mouse button.2. Click on the appearing Edit button.

  • 58 A30808-X3247-M357-04-7630

    ITMN:BTSE BS-241/241 II

    Id:0900d805800c67d3

    Procedures

    Figure 20 Editing Nob-RIU Units3. Edit the data manually, or click on the Scan button to use the 2D-Code Reader.4. If the 2D-Code Reader is used for the first time, select the serial port in the appearing

    window.5. To start the scanning process, press the button on the 2D-Code Reader.6. The data will be inserted into the corresponding fields. Confirm the data by clicking

    on the OK button.7. Select File Save.

    7 Export Nob_RIU DataThe nob_RIU data of the IDF file must be attached to the Remote Inventory Data stored in the BTSE (IDT file). In order to attach the nob_RIU data to the IDT file of the BTSE, you must export them into a NOB file.To export the nob_RIU data:

  • A30808-X3247-M357-04-7630

    59

    ITMN:BTSE BS-241/241 II Procedures

    Id:0900d805800c67d3

    1. Select Export NOB from the menu.2. A window opens in which you can edit the file name and select the directory in which

    the file is saved. By default, the file name is composed of the SalesUniqueName with the extension .nob. Edit the file name and select the source directory or confirm the default name and directory by clicking on the Save button.

    3. The nob_RIU data are exported to the NOB file. The selected destination path of this file is displayed in an attention window. Confirm by clicking on the OK button.

    4. A question window is displayed: Create BTSE_NRIU for download? At present, it is not required to create this file. Click on the No button.

    8 Upload IDT File from BTSENow you must upload the Remote Inventory Data that are stored in the BTSE (IDT file) to the LMT PC.Change to the LMT Evolution main window.b UPLLIDF REMINV1. A Select the Parameter Value window pops up:

    1.1 Enter the path (DESTDIR).1.2 Enter the file name1.3 Enter the parameter (OVERWRITE, e.g.yes/no)

    2. Click on the Submit buttonAdditional Information: The attributes DESTDIR and FILE are optional. If no special path or file name is entered, the file is uploaded to the default directory of the IDF Editor. If the attribute OVERWRITE= is selected, a former version of an uploaded IDT file will be overwritten.System Response: In the Message Viewer window, the command result is displayed: Operation successful.

    9 Open IDT FileTo open the IDT file:1. Change to the IDF Evolution window.2. Select File Open from the menu.3. Select the uploaded file from the list in the appearing window; e.g.: .4. Click on the Open button.

    10 Attach nob_RIU data to Actually Loaded IDTTo attach the nob_RIU data:1. Select File Attach from the menu.2. Select the exported nob_RIU file from the list in the appearing window (the file and

    destination path was selected in step 7); e.g.: .

    3. Click on the Open button.4. A window opens that tells you how many attachments were made. Confirm by

    clicking on the OK button.

  • 60 A30808-X3247-M357-04-7630

    ITMN:BTSE BS-241/241 II

    Id:0900d805800c67d3

    Procedures

    11 Remove Redundant Nob_RIU Files In the IDF file that is delivered with the rack, all units are considered as nob_RIUs even if they are in fact ob_RIUs. All nob_RIUs that are in fact ob_RIUs and are therefore redundant can be removed automatically after they were attached to the IDT file of the BTSE.To remove the redundant nob_RIU files:1. Select File Remove nob_RIUs from the menu.2. Click on the Yes button in the appearing window to confirm the deletion of all redun-

    dant nob_RIUs.3. A window opens that tells you how many records were deleted. Confirm by clicking

    on the OK button.4. Select File Save from the menu. An attention window is displayed that informs

    you on the destination path and file name to which the changes are saved. Confirm by clicking on the OK button.

    12 Export Remote Inventory Data for BackupNow you must create an IDF file for backup. This new IDF file replaces the IDF file deliv-ered with the rack. It contains the modifications you have just made.To export the Remote Inventory Data for backup:1. Select Export IDF from the menu.2. Select the destination path in the appearing window, preferably A:\. The file name

    is automatically composed of the SalesUniqueName with the extension .idf.3. Click on the Save button.4. An attention window opens that tells you the destination path of the saved file.

    Confirm by clicking on the OK button.5. Put the disk with the backup file of the inventory data to the site specific documen-

    tation.

    13 Export Nob_RIU Data for Download to the BTSEThe nob_RIU data must be downloaded to the BTSE. In order to download them, you must export the nob_RIU data again into a NOB file. This new NOB file now contains all modified data without the redundant nob_RIUs.1. Select Export NOB from the menu.2. A window opens in which you can edit the file name and select the directory in which

    the file is saved. By default, the file name is composed of the SalesUniqueName with the extension .nob. Edit the file name and select the source directory or confirm the default name and directory by clicking on the Save button.

    3. The nob_RIU data are exported to the NOB file. The selected destination path of this file is displayed in an attention window. Confirm by clicking on the OK button.

    4. A question window is displayed: Create BTSE_NRIU for download? Confirm by clicking on the YES button. An attention window is displayed that informs you on the destination path and file name to which the BTS_NRIU downloads saved. Confirm by clicking on the OK button.

    14 Download the Nob_RIU File to the BTSEChange to the LMT Evolution main window.

  • A30808-X3247-M357-04-7630

    61

    ITMN:BTSE BS-241/241 II Procedures

    Id:0900d805800c67d3

    b DNLIDFD REMINV1. A Select the Parameter Value window pops up:

    1.1 Enter the parameter (SRCDIR, e.g.source directory).1.2 Enter the parameter (SRCDIR, the source directory in which the exported NOB

    file was saved).2. Click on the Submit buttonSystem Response: In the Message Viewer window, the command result is displayed: Operation successful.

    END

  • 62 A30808-X3247-M357-04-7630

    ITMN:BTSE BS-241/241 II

    Id:0900d805800c67d3

    Procedures

    3.8 Switch to Phase 3

    1 Manual Switch to Phase 3For forced switchover to Phase 3, a special command may be entered at the LMT.b CONNBSC BTSM

    2 LogonTo log on LMT:1. Click on the LogOn button in the tool bar.2. Enter user ID and password in the appearing LogOn window.3. Click on the OK button.The BTSE is now in phase 3. In this phase, the BTSE is connected to the BSC.Only the specified LEDs are relevant for this step.

    The LED indication on the COB2P8/COBA4P12A changes to:ACT fl (G)FLOC fl (G)

    The LED indication on the COSA6P16/COSA4P12 changes to:ACT fl (G)

    The LED indication on the CU changes to:OK fl (G) fl (G) SW

    Checklist in Case of Problems Switching over to Phase 3Minimal BTSE configuration with preconditions for a successful switchover to Phase 3:

    COBA-0 = unlocked.enabled COBA-0 is always created and always enabled.

    Here the Administrative State (AST*) is relevant.Minimal parameters of RACK-0:

    available

    This means that TypeOfBTSE (TYPRACK) must be set first before any HMO can be created.

    LAPDLE-0 = createdMinimal parameters of LAPDLE-0:

    available

    This means that the LAPD channel (LAPDCH) must be defined.

    Accuracy of CCLK >= medium (at least !)

  • A30808-X3247-M357-04-7630

    63

    ITMN:BTSE BS-241/241 II Procedures

    Id:0900d805800c67d3

    END

    The current CCLK accuracy can be determined by performing the LMT command Get COBA ---> REQATTL ---> CCLKACC.

    Minimal parameters of BTSM:

    available

    This means that the TEI must be defined.

    Minimal parameters of BPORT-0:

    available

    This means that the layer1ProtocolType (L1PT) and lineConfiguration (LCONF) must be defined

    *) For more information on the Administrative State (AST), refer to: MMN:BTSE BS-240/240 II/240XL/240XL II MMN:BTSE BS-241/241 II MMN:BTSE BS-40/40 II MMN:BTSE BS-41

    Checklist in Case of Problems Switching over to Phase 3

  • 64 A30808-X3247-M357-04-7630

    ITMN:BTSE BS-241/241 II

    Id:0900d805800c67d3

    Procedures

    3.9 SW Download and Activation (optional)

    This procedure is optional.g Make sure that all files of the relevant software load are present in a directory on the

    harddisk of the LMT.The V.11/X.21 interface (HDLC-Adapter, DLHC) has been installed and tested in advance.

    1 Reset the COBAReset the COBA by pressing the reset button on the module.After about 15 seconds the COBA reaches the start connection status.

    2 Connect LMTConnect the LMT cable to the LMT 15-pin SUB-D connector on the DC panel.

    3 Log on LMTTo log on LMT:1. Start the LMT program in the corresponding directory of Start menu (Start:\Pro-

    grams\LMT Evolution (string of version)\LMT Evolution).2. Enter your user ID and password in the appearing "LogOn" window.3. Click on the OK button.System Response: Several changed state event reports follow. They can be examined in the Message Viewer window.The BTSE is now in phase 1. In this phase, you can download and activate the software.

    4 SW Downloadb DNLALLEXE SOFTWARE-MANAGEMENT1. A Select the Parameter Value window pops up:

    1.1 Enter the path where the SW Load is stored on the LMT (SRCPATH).1.2 Enter the parameter values (OVERWRITE = ).

    2. Click on the Submit buttonSystem Response: Several messages are displayed that provide information on the progress and the end of the download for each file.The LMT performs an automatic logoff after a few minutes. If the session is closed, please log on again.

    LED indication on COBA:ACT fl (G) (R) RCOBAFLOG o (R) o (R) HMOABIS 1 o (R) o (R) ABIS 2

  • A30808-X3247-M357-04-7630

    65

    ITMN:BTSE BS-241/241 II Procedures

    Id:0900d805800c67d3

    5 SW Activationb ACTIVATE BTSM1. A Select the Parameter Value window pops up:

    1.1 Enter the header according to the SW Load (FILEID, e.g. HS010808.SWL)1.2 Enter the file version string (FILESWV, e.g.: 01-01-08-06-08-00_98-08-21).

    2. Click on the Submit button

    System Response: In the "Message Viewer" window, the command result is displayed: "Operation successful". The session will be closed.

    6 Log On LMTTo log on LMT:1. Click on the LogOn icon in the tool bar.2. Enter your user ID and password in the appearing "LogOn" window.3. Click on the OK button.System Response: The BTSE is now in phase 2. In this phase, the operation & main-tenance software and the call processing software is running, but the BTSE is not yet connected to the BSC. Call processing is disabled.

    END

    LED indication on COBA:ACT fl (G) (R) RCOBAFLOC o (R) o (R) HMOABIS 1 o (R) o (R) ABIS 2

  • 66 A30808-X3247-M357-04-7630

    ITMN:BTSE BS-241/241 II

    Id:0900d805800c67d3

    Procedures

    3.10 Setting the Attributes for the BTSE (optional)This procedure is optional.The location name, vendor name, sales unique name and software load safety must be set. For more information, refer to CML:BS-4x/82II/240/241/240XL. g For Remote Inventory, the SALUNAME and EQUPOS must be set correctly.

    1 Set Attributes for BTSE Equipmentb SET BTSEP1. A Select the Parameter Value window pops up:

    1.1 Enter the parameter (NAME, e.g. BTSEP:0).1.2 Enter the parameter (EQUPOS, e.g. SBS_Equipment_Position).1.3 Enter the parameter (CHIDT, e.g. noChangeOnIDT/IDTWasChanged).1.4 Enter the parameter (EAUTOREC, e.g. enabled/disableAutomaticRecovery).1.5 Enter the parameter (LOCNAME, e.g. locationName).1.6 Enter the parameter (RXDIVSV, e.g. enable/disableRxDiversitySupervision).1.7 Enter the parameter (SALUNAME, e.g. salesUniqueName).1.8 Enter the parameter (VENDNA, e.g. vendorName).1.9 Enter the parameter (OVPTINS, e.g. true/false).1.10 Enter the parameter (ALRMSEVxxx, e.g.CRITI-

    CAL/MAJOR/MINOR/DEFAULT_DB).1.11 Enter the parameter (ALRMSEVxxx, e.g.CRITI-

    CAL/MAJOR/MINOR/DEFAULT_DB).1.12 Enter the parameter (SWLDSAF, e.g.swLoadSafety: swLoadSafetyField,

    swLoadSafetyVersion).2. Click on the Submit button

    END

    Attribute CommentSALUNAME The Sales unique name is an ASCII character string

    with length 11, e.g: "AD042S7449E". The SALUNAME must be the same in the BSC database and the local BTSE database.

    ALRMSEV Select one or more parameters and enter the appropriate severity of the alarms for the following modules/HMOs: ACDCP, ACT, COBA, BATTERY, COSA, CU, DIDCTMA, DILNA, DUDCTMA, DULNA, DUVSWR, FANP, FTNFP, FVSWRP, and TMA.

    SWLDSAF The SWLDSAF must be set after connecting the BTSE with the BSC. SWLDSAF can only be set after at least one transmission.

    Table 10 Additional Information

  • A30808-X3247-M357-04-7630

    67

    ITMN:BTSE BS-241/241 II Procedures

    Id:0900d805800c67d3

    3.11 Setting BTSM (optional)This procedure is optional.In Phase two, the LMT prepares for the establishment of the Abis interface to the BSC. The O&M terminal endpoint identifier (TEI), the kind of connection and the Abis Time must be programmed for the BTS manager (BTSM). Obtain the corresponding data from the configuration data.

    1 Set BTSMb SET BTSM1. A Select the Parameter Value window pops up:

    1.1 Enter the parameter (ABISLKSAT=).1.2 Enter the parameter (ABISTIME=).1.3 Enter the parameter (TEI=).

    2. Click on the Submit buttonFor more information refer to CML:BS-4x/82II/240/241/240XL.

    END

  • 68 A30808-X3247-M357-04-7630

    ITMN:BTSE BS-241/241 II

    Id:0900d805800c67d3

    Procedures

    3.12 Closing the Rack/Shelter Door

    After performing any work at the BTSE it is necessary to close the rack/shelter door. Close the rack/shelter door in the following way:

    1 Close the door.

    2 Turn the door handle in the clockwise direction and pass over the normal locking position (vertical to the ground), until you feel that it can not be turned any further.

    3 Bring back the handle to the normal locking position (vertical to the ground) and press it into the handle latch. The Door Open alarm goes off.

    Figure 21 Closing the Rack/Shelter Door

    g Make sure that the Door Open alarm is deactivated after closing the rack/shelter door.

    1

    2

    LOCK

    ING

    PO

    SITI

    ON

    DOOR OPEN

    3

  • A30808-X3247-M357-04-7630

    69

    ITMN:BTSE BS-241/241 II Appendix

    Id:0900d8058007a741

    4 Appendix

    4.1 Power/Level ConversionThe formula for power calculation:Lp[dBm] = 10lg(Px/P0)P0[Watt] = 10-3

    Lp[dBm] Px[Watt]0 10-3

    10 10-2

    20 10-1

    30 1

    33 2

    37 5

    39 8

    40 10

    44 25

    46 40

    47 50

    48 63

    50 100

    Table 11 Power Conversion Table

    +3 dB factor 2+5 dB factor 3 1/3+10 dB factor 10

  • 70 A30808-X3247-M357-04-7630

    ITMN:BTSE BS-241/241 II

    Id:0900d8058007a741

    Appendix

    4.2 Used Expressions

    4.3 Module Identification by Inventory Data and LabelEvery module in the BTSE is identified by one or more labels, depending of the type (e.g. with/without FW, OEM, ...) and the used labeling scheme. In general, the HW code number including the HW issue is printed as a 4 code block separated by hyphens, followed by the functional state after a slash mark as separator, and can be found on any module. If a FW is included, a second number with the same structure is shown on a common or another label. A bar-code (or 2D-code) and a mnemonic name complete the identification of the module and they are usually fixed at the front or on the levers.HW and FW code numbers including issue and functional state can also be received electronically via the LMT and the offline tool IDF Evolution. The so called Inventory Data consists, among HW and FW code numbers, of many other information items about the module like series number of the PCB or HW/SW compatibilityUsing the IDF Evolution, the relevant information of each module respectively inventory taken unit can be displayed and compared with the one on the labels. The procedure of reading the appropriate data is described in the Maintenance Manual Updating the Remote Inventory Data.

    Figure 22 Labels and Inventory Data

    -48 V -48 V for test adapter12 V +12 Volt

    1ER-3 bit error rate >10-3 port 11ER-6 bit error rate >10-6 port 11RAI remote alarm indication port 12RAI remote alarm indication port 22ER-3 bit error rate >10-3 port 22ER-6 bit error rate >10-6 port 25 V +5 Volt

    S30861-Q2015-X-02/01

    M:COSA6P16V1+HW code HW issue

    functional state

    function designation

    Label Lettering2D-code

    RX+/LN325322serial number

    ITMN:BTSE BS-241/241 IITable of ContentsList of FiguresList of TablesReason for Update1Introduction1.1Aims of Installation and Commissioning1.2Pre-Commissioning and Pre-Acceptance1.3Optional Measurements1.4Using the ITMN1.4.1Required Knowledge1.4.2Test Equipment1.4.3Installation Test Sequence1.4.4Procedure in the Event of Faults after Commissioning1.4.5Procedure in the Event of Faults not Described in the Manuals1.4.6Dealing with Defective Modules

    1.5CE and UL Declaration of Conformity1.6LMT Use1.6.1LMT Graphic View1.6.2LMT Tree View

    2Safety Instructions2.1Electrostatically Sensitive Components2.2Warnings2.3Symbols Used2.4System Voltages2.5Changing Breakers2.6Grounding of Modules / Racks / Shelters2.7Handling Moist Modules

    3Procedures3.1Visual Inspection3.1.1Visual Inspection of BTSE Mechanics3.1.1.1Shelters3.1.1.2Mounting and Installation of BTSE3.1.1.3Check of Base Transceiver Station BTSE3.1.1.4Check of BTSE Modules3.1.1.4.1Modules in the Shelter3.1.1.4.2BTSE Modules

    3.1.1.5Antenna and Feeder Cable

    3.1.2Visual Inspection of BTSE Electrics3.1.2.1Polarity of DC Input and Tolerance3.1.2.2Circuit Breakers3.1.2.3Alarms3.1.2.4DC Connector for Network Termination (NT)

    3.1.3Visual Inspection of BTSE Modules3.1.3.1Abis Configurations to the BTS3.1.3.2Tower Mounted Amplifier (TMA) Connection3.1.3.3Adjustable Modules3.1.3.3.1Boot Software (FW)3.1.3.3.2Software Images SWI3.1.3.3.3Switch Settings on COBA2P83.1.3.3.4Switch Settings on COBA4P123.1.3.3.5Switch Settings on COSA3.1.3.3.6DCBCTRL3.1.3.3.6.1Switch Settings on DCBCTRL for BS-241, Service 1 Shelter3.1.3.3.6.2Switch Settings on DCBCTRLDVx for BS-241 II, Service 1A Shelter

    3.1.3.4Antenna Combining3.1.3.4.1DUAMCO3.1.3.4.2FDUAMCO3.1.3.4.3COAMCO3.1.3.4.4FICOM

    3.1.3.5Antenna Multicoupling3.1.3.5.1DIAMCO3.1.3.5.2DUAMCO/FDUAMCO3.1.3.5.3Cascading Multicouplers

    3.1.3.6HPDU

    3.2Preparation for Offline Tests3.2.1Recommended Test Equipment and Tools3.2.1.1Test Equipment3.2.1.1.1Tools

    3.2.1.2Preparation and Presetting of Test Equipment3.2.1.