Top Banner
WFM Big Box Retail “CCHP”
35

broad wfm CHP

Aug 12, 2015

Download

Documents

douglas davis
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: broad wfm CHP

WFM Big Box Retail “CCHP”

Page 2: broad wfm CHP

Integrating CHP with DG “Big Box Store CCHP” 11/14/14 Washington DC Douglas Davis Director – Broad USA Hackensack NJ 201 951 5713 [email protected]

Page 3: broad wfm CHP

1/29/2015 CHP ASSOCIATION PAGE 3

AGENDA

• Modern Absorption/CCHP Technology • Focus on a “Modern Grocery Store in

Brooklyn NYC that combines HVAC and CCHP, Solar PV, Wind Power LEED …….”

• Sustainable Leadership by Design

3

Page 4: broad wfm CHP

1/29/2015 CHP ASSOCIATION PAGE 4

ABSORPTION CHILLERS

• Thermally driven non-electric chillers – 30-3,300 ton indoor or outdoor packages

• Two primary markets – HVAC

• “Typical” utility natural gas pressure

– Waste heat recovery co-generation CCHP • Exhaust, Jacket - hot water with Natural Gas

4

Page 5: broad wfm CHP

1/29/2015 CHP ASSOCIATION PAGE 5

THE ABSORPTION CYCLE

5

Page 6: broad wfm CHP

1/29/2015 CHP ASSOCIATION PAGE 6

ABSORPTION CYCLE

CONDENSER

EVAPORATOR

GENERATOR

ABSORBER

HEAT

EN

ERGY

REJE

CT

HEAT

AB

SORB

HE

AT

REJE

CT

HEAT

EXPANSION DEVICE PUMP

HIG

H SI

DE

LOW

SID

E

-14.6 psig 6 mm

-13.6 psig 57 mm

6

Page 7: broad wfm CHP

1/29/2015 CHP ASSOCIATION PAGE 7

ABSORPTION COOLING THEORY

• Evaporator with water as a refrigerant – Refrigerant water sprays on copper tubes of

chilled water system • Changes state (boils) and absorbs large amounts of

energy – Water evaporates at 212°F at 14.7 psia – Water evaporates at 40°F at 0.118 psia

CONDENSER

EVAPORATOR

GENERATOR

ABSORBER

HEAT

EN

ERG

Y

REJ

ECT

HEAT

AB

SOR

B HE

AT

REJ

ECT

HEAT

EXPANSION DEVICE PUMP CFC refrigerant changes state and absorbs large amounts of energy for ex. R134 evaporates at 40º at 35 psig

7

Page 8: broad wfm CHP

1/29/2015 CHP ASSOCIATION PAGE 8

REFRIGERANT H2O NO ODP/GWP - PHASE OUTDATE

• Distilled water – Stable – Nontoxic – Low cost – Readily available – Environmentally friendly – High latent heat of

vaporization – R718 = H2O

– http://www.r718.com/ – LEED POINT = 1

Page 9: broad wfm CHP

1/29/2015 CHP ASSOCIATION PAGE 9

SINGLE EFFECT (0.7-0.8 COP)

TO T

OW

ER

TO T

OW

ER

CONDENSER

ABSORBER EVAPORATOR

TO L

OAD

STRONG SOLUTION

WEAK SOLUTION

WATER VAPOR

WATER VAPOR

GENERATOR

FRO

M B

OIL

ER

EXPANSION DEVICE

PUMP

HEAT EXCHANGER

WATER

100° 40°

200°

PUMP

9

Page 10: broad wfm CHP

1/29/2015 CHP ASSOCIATION PAGE 10

DOUBLE EFFECT (1.3-1.4 COP)

TO T

OW

ER

EVAPORATOR

TO L

OAD

WATER VAPOR

WATER VAPOR

EXPANSION DEVICE

PUMP

WATER

40°

CONDENSER

TO T

OW

ER

ABSORBER

STRONG SOLUTION

WEAK SOLUTION

LOW TEMP HEAT EXCHANGER 100°

200° PUMP

LOW TEMP GENERATOR

STRONG SOLUTION

WEAK SOLUTION

FRO

M B

OIL

ER

HIGH TEMP HEAT EXCHANGER

310° PUMP

HIGH TEMP GENERATOR

WATER

110°

100°

10

Page 11: broad wfm CHP

1/29/2015 CHP ASSOCIATION PAGE 11

MODERN CCHP SYSTEMS

11

Page 12: broad wfm CHP

1/29/2015 CHP ASSOCIATION PAGE 12

RAPID EVOLUTION OF TECHNOLOGY

Evolution of Absorption chillers 10 models improvements in 25 years

12

Page 13: broad wfm CHP

1/29/2015 CHP ASSOCIATION PAGE 13

CHILLER/HEATER OPERATING MODES • Cooling only • Heating only • Simultaneous cooling/heating • Domestic Hot Water • Great for System COP! • Great for reducing capital costs • Eliminates or reduces the need for separate

dedicated cw/hw/dhw systems • Reduces MER size

Page 14: broad wfm CHP

1/29/2015 CHP ASSOCIATION PAGE 14

BIG BOX RETAIL CCHP

Page 15: broad wfm CHP

1/29/2015 CHP ASSOCIATION PAGE 15

“GROCERY STORE CCHP PACKAGED PLANT”

15

Model: BZHE and BZ Cooling Capacity: 260 RT Energy Source: Natural Gas & Waste Heat from recip 150 KW CHP 250 KW of demand response

Page 16: broad wfm CHP

1/29/2015 CHP ASSOCIATION PAGE 16

PRE-PACKAGED AND TESTED CCHP WAITING TO GO OVER THE GOVERNOR’S FAVORITE BRIDGE IN FORT LEE NJ

Page 17: broad wfm CHP

1/29/2015 CHP ASSOCIATION PAGE 17

CO2 LOW AND MEDIUM TEMP REFRIGERATION SUB COOLED BY CCHP ( ADDITIONAL HEAT SINK)

Page 18: broad wfm CHP

1/29/2015 CHP ASSOCIATION PAGE 18

GROCERY STORE SUMMARY

• Brooklyn NY (USA) • Store can operate in a Black Out / “Black Start” • 150 kw of CCHP / 250 kw of “Demand Response” • 100 & 168 tons of Chiller /Heaters/DHW • Solar PV with rain water capture 350 KW • No man made chemical refrigerants • CO2 low temperature refrigeration • Sub cooling low temp via CCHP • NYSERDA incentive participant (six figures) • LEED - Platinum or Gold pending!

Page 19: broad wfm CHP

1/29/2015 CHP ASSOCIATION PAGE 19

STORE DESIGN CONSIDERATIONS

• All Mechanical equipment on roof ( resiliency ) • Gowanus canal “water management” • “Beckwith relay” does not allow exporting power • Transfer switches allow store to shed non-critical loads

during a “island mode operation” • System was “pre-packaged and tested” FAT! • FAT Made for a simple start up • 24/7/365 monitoring via store BMS and CCHP suppliers

PLCs and internet. • Grid independence - run business with or without grid –

product loss mitigation – keep the register ringing – be an asset to the community they serve.

Page 20: broad wfm CHP

1/29/2015 CHP ASSOCIATION PAGE 20

BIRDS EYE VIEW OF THE NEW PLANT(S) THAT GREW IN BROOKLYN NYC ( YES THEY GROW ORGANIC VEGETABLE ON THE ROOF FOR SALE IN THEIR STORES IN NYC )GREENHOUSE PRODUCES THE EQUIVINANT OF 40 ACRES.

Page 21: broad wfm CHP

1/29/2015 CHP ASSOCIATION PAGE 21

INSIDE ELECTRICAL ROOM PRE-PACKAGED MER BOX ( BECKWITH RELAY )

Page 22: broad wfm CHP

1/29/2015 CHP ASSOCIATION PAGE 22

STORE OPENS ON SCHEDULE AND IT WORKS! DECEMBER 20TH 2013

Page 23: broad wfm CHP

1/29/2015 CHP ASSOCIATION PAGE 23

CCHP TURNS ON 2/20/2014

• Hi folks, • Congratulations to everyone on 2 huge milestones today: we got National Grid’s sign off and

passed ConEdison’s witness test! The generators started up successfully, and we will be working tomorrow to dial in synchronicity on all systems. I appreciate everyone’s hard work to get to this point. Please let me know if you have any questions.

• Thanks! • J'aime Mitchell, LEED Green Associate • Associate Coordinator of Construction | Green Mission Specialist

• 56,000-square-foot structure is 60 percent more energy efficient than the building code requires. That's right: 60 percent more efficient, making it one of the most energy efficient supermarkets in the nation, Whole Foods says.( source greenbiz.com )

Page 24: broad wfm CHP

1/29/2015 CHP ASSOCIATION PAGE 24

SOLAR PV CANOPY FOR PARKING AND RAIN WATER CAPTURE SYSTEM

Page 25: broad wfm CHP

1/29/2015 CHP ASSOCIATION PAGE 25

PLC CONTROLS RECIPROCATING ENGINE

Page 26: broad wfm CHP

1/29/2015 CHP ASSOCIATION PAGE 26

THE CCHP “PRIME MOVER” 150 KW RECIPROCATING ENGINE / QUIET BY DESIGN OF PRE-PACKED BOX

Page 27: broad wfm CHP

1/29/2015 CHP ASSOCIATION PAGE 27

PLC CONTROLS ON CCHP PLANT

• Touch screens

Page 28: broad wfm CHP

1/29/2015 CHP ASSOCIATION PAGE 28

PLC 27/7/365 MONITORING OF THE CHILLERS FROM ANY PC OR SMART PHONE IN THE WORLD VIA THE INTERNET

Exhaust temp. 820/266℉,maintain chilled water delta T 2.5~3 ℉ only by Exhaust. Regards

Bill Huang Technical manager Broad USA Inc.

Page 29: broad wfm CHP

1/29/2015 CHP ASSOCIATION PAGE 29

EASY TO COMMISSION VIA FACTORY TESTING

Page 30: broad wfm CHP

1/29/2015 CHP ASSOCIATION PAGE 30

FEEL FREE TO EMAIL DENIS ?

• Jordan Melton • Physical Plant Coordinator • WFM • 214 3rd St, • Brooklyn, New York 11215 • (718) 907-3622 • or Denis Boyle Project Manager (NE NEO) ([email protected])

Page 31: broad wfm CHP

1/29/2015 CHP ASSOCIATION PAGE 31

TOUR LAST MONTH -ICF

Page 32: broad wfm CHP

1/29/2015 CHP ASSOCIATION PAGE 32

TOUR LAST MONTH

Page 33: broad wfm CHP

1/29/2015 CHP ASSOCIATION PAGE 33

TOUR LAST MONTH

Page 34: broad wfm CHP

1/29/2015 CHP ASSOCIATION PAGE 34

SIMULTANEOUS CHW, HW & DHW • Typically a lower capital cost system • Offers Better “System Efficiency” • Up to three energy inputs…great for simple CCHP intergration with hvac

34

Page 35: broad wfm CHP

Questions?