-
BRANTEC GLAZING SYSTEMS INC. TEST REPORT TEST REPORT ISSUED TO Brantec Glazing Systems Inc. 103 – 8288 North Fraser Way Burnaby, BC V3N 0E9 Canada SPECIFICATION AAMA/WDMA/CSA 101/I.S.2/A440‐08 AAMA/WDMA/CSA 101/I.S.2/A440‐11 A440S1‐09 A440S1‐17
PRODUCT SERIES & TYPE Aluminum Casement – Fixed Combination Window Wall System
PRIMARY DESIGNATION Class AW – PG45 – Size Tested 2580 x 2615 mm (102 x 103 in) – Type C, FW
SECONDARY DESIGNATION Positive Design Pressure = 2160 Pa (45.1 psf) Negative Design Pressure = 2160 Pa (45.1 psf) Water Penetration Resistance = 730 Pa (15.3 psf) Canadian Air Leakage Resistance = A3 REPORT NUMBER
103141992COQ‐001A
REVISION ISSUE DATE
22‐May‐2019
ORIGINAL ISSUE DATE
22‐Sept‐2017
PAGES 42 DOCUMENT CONTROL NUMBER GFT‐OP‐10b (13‐March‐2017) © 2017 INTERTEK
-
TEST REPORT FOR BRANTEC GLAZING SYSTEMS INC. Report No.: 103141992COQ‐001A Revision Date: 22‐May‐2019
1500 Brigantine Drive Coquitlam, BC, V3K 7C1 Telephone: 604‐520‐3321 Facsimile:
604‐524‐9186 www.intertek.com
This report is
for the exclusive use of
Intertek's Client and
is provided pursuant to the agreement between
Intertek and its Client.
Intertek's responsibility and
liability are limited to the
terms and conditions of
the agreement. Intertek assumes no
liability to any party, other than
to the Client in accordance with
the agreement, for any
loss, expense or damage occasioned by the use of this report. Only the Client is authorized to copy or distribute Intertek’s Reports and then only in their entirety, and the Client shall not use the Reports in a misleading manner. In the event any portion of this report becomes public, including but not limited to press releases, articles, and marketing material, without prior written consent from Intertek, Intertek may enforce the reproduction of the report in its entirety by making the full report public. Client further agrees and understands that reliance upon the Reports
is
limited to the representations made therein.
In the event any portion of this report becomes public,
including but not limited to press releases, articles, and marketing material, without prior written consent from Intertek, Intertek will enforce the reproduction of the report in its entirety by making the full report public. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material, product or service must first be approved in writing by Intertek. The observations and test results in this report are relevant only to the sample tested. Should Customer use an Intertek Report, in whole or in part, in such a manner as to involve Intertek in legal controversy or to adversely affect Intertek’s reputation, it shall be Intertek’s right to utilize any and all Customer information, including, but not limited to, data, records, instructions, notations, samples or documents within Intertek’s custody and control which relate to the customer for the purpose of offering any necessary defense or rebuttal to such circumstances.
This report by
itself does not
imply that the material, product, or service
is or has ever been under an
Intertek certification program.
Version (13–March‐2017)
Page 2 of 42 GFT‐OP‐10b
CONCLUSION
The Aluminum Casement – Fixed Combination Window Wall System, submitted by Brantec Glazing Systems Inc., tested and described within this report, achieved the overall performance requirements of Class AW – PG45 when tested in accordance with NAFS‐08, NAFS‐11, A440S1‐09 and A440S1‐17.
_ _
______
Jason Komorski David Park
TECHNICIAN REVIEWER BUILDING PRODUCTS
BUILDING PRODUCTS
-
TEST REPORT FOR BRANTEC GLAZING SYSTEMS INC.
Report No.: 103141992COQ‐001A Revision Date: 22‐May‐2019
Version (13‐March‐2017)
Page 3 of 42 GFT‐OP‐10b
SECTION 1 SUMMARY OF RESULTS
A summary of results
for AAMA/WDMA/CSA 101/I.S.2/A440‐08
“Standard/Specification
for windows, doors, and unit
skylights”, AAMA/WDMA/CSA 101/I.S.2/A440‐11 “Standard/Specification
for windows, doors, and unit
skylights”, A440S1‐09 “Canadian Supplement
to AAMA/WDMA/CSA 101/I.S.2/A440, NAFS
– North American Fenestration
Standard/Specification for windows, doors,
and skylights” and A440S1‐17 “Canadian
Supplement to AAMA/WDMA/CSA 101/I.S.2/A440,
NAFS – North American Fenestration
Standard/Specification for windows, doors,
and skylights”are as indicated in
the table below:
Evaluation Property
Results Operational Force (overall)
US – Pass; Can – Pass
Air Leakage Resistance @ 300 Pa (6.3 psf)
US – Pass; Can –
Case = A3, Fixed = Fixed Water Penetration Resistance (Static & Cyclic)
730 Pa (15.3 psf)
Vent / Sash / Door Leaf Cycling
Pass Locking Hardware Cycling Pass
Misuse Test Pass Thermal Cycling
Pass
Uniform Load – Deflection
2160 Pa (45.1 psf) Uniform Load – Structural
3240 Pa (67.7 psf) Forced Entry Resistance
Gr.20
Sash Vertical Deflection Test
Pass Sash and Hardware Load Test
Pass
Sash / Leaf Torsion Test
Pass Thermoplastic Corner Weld Test
N/A
Insect Screen Serviceability N/A
Details of the tested results can be found in Section 7 of this report. Primary and Secondary Designations are as indicated below:
Aluminum Casement – Fixed Combination Window Wall System
Class AW – PG45 – Size Tested 2580 x 2615 mm (102 x 103 in) – Type C, FW
Secondary Designator Positive Design Pressure = 2160 Pa (45.1 psf) Negative Design Pressure = 2160 Pa (45.1 psf) Water Penetration Resistance = 730 Pa (15.3 psf) Canadian Air Leakage Resistance = A3
-
TEST REPORT FOR BRANTEC GLAZING SYSTEMS INC.
Report No.: 103141992COQ‐001A Revision Date: 22‐May‐2019
Version (13‐March‐2017)
Page 4 of 42 GFT‐OP‐10b
SECTION 2 INDEX
SECTION NAMES PAGE
SUMMARY OF RESULTS
..................................................................................................................
3
INDEX
...........................................................................................................................................
4
OBJECTIVE
....................................................................................................................................
6
SAMPLE ASSEMBLY AND DESCRIPTION
............................................................................................
6
TESTING AND EVALUATION METHODS
..........................................................................................
11 OPERATING FORCE
.................................................................................................................................
11 AIR LEAKAGE RESISTANCE
.......................................................................................................................
11 CYCLIC WATER PENETRATION RESISTANCE
...............................................................................................
11 STATIC WATER PENETRATION RESISTANCE
..............................................................................................
11 VENT / SASH / DOOR LEAF CYCLING (FIRST HALF)
.....................................................................................
11 LOCKING HARDWARE CYCLING (FIRST HALF)
............................................................................................
12 MISUSE TEST..........................................................................................................................................
12 VENT / SASH / DOOR LEAF CYCLING (SECOND HALF)
.................................................................................
12 LOCKING HARDWARE CYCLING (SECOND HALF)
........................................................................................
12 OPERATING FORCE #2
............................................................................................................................
12 THERMAL CYCLING
.................................................................................................................................
12 UNIFORM LOAD DEFLECTION
..................................................................................................................
12 AIR LEAKAGE RESISTANCE #2
..................................................................................................................
13 CYCLIC WATER PENETRATION RESISTANCE #2
..........................................................................................
13 STATIC WATER PENETRATION RESISTANCE #2
..........................................................................................
13 UNIFORM LOAD STRUCTURAL
.................................................................................................................
13 FORCED ENTRY RESISTANCE
....................................................................................................................
13 SASH VERTICAL DEFLECTION TEST
...........................................................................................................
13 SASH AND HARDWARE LOAD TEST
..........................................................................................................
13 SASH / LEAF TORSION TEST
.....................................................................................................................
14 THERMOPLASTIC CORNER WELD TEST
.....................................................................................................
14 INSECT SCREEN SERVICEABILITY
..............................................................................................................
14 DEVIATION FROM STANDARD METHOD
...................................................................................................
14
TEST EQUIPMENT
........................................................................................................................
14
RESULTS AND OBSERVATIONS
......................................................................................................
15 OPERATING FORCE
.................................................................................................................................
15 AIR LEAKAGE RESISTANCE
.......................................................................................................................
15 CYCLIC WATER PENETRATION RESISTANCE
...............................................................................................
15 STATIC WATER PENETRATION RESISTANCE
..............................................................................................
15 VENT / SASH / DOOR LEAF CYCLING (FIRST HALF)
.....................................................................................
16
-
TEST REPORT FOR BRANTEC GLAZING SYSTEMS INC.
Report No.: 103141992COQ‐001A Revision Date: 22‐May‐2019
Version (13‐March‐2017)
Page 5 of 42 GFT‐OP‐10b
LOCKING HARDWARE CYCLING (FIRST HALF)
............................................................................................
16 MISUSE TEST..........................................................................................................................................
16 VENT / SASH / DOOR LEAF CYCLING (SECOND HALF)
.................................................................................
16 LOCKING HARDWARE CYCLING (SECOND HALF)
........................................................................................
16 OPERATING FORCE #2
............................................................................................................................
16 THERMAL CYCLING
.................................................................................................................................
17 UNIFORM LOAD – DEFLECTION
...............................................................................................................
17 AIR LEAKAGE RESISTANCE #2
..................................................................................................................
18 CYCLIC WATER PENETRATION RESISTANCE #2
..........................................................................................
18 STATIC WATER PENETRATION RESISTANCE #2
..........................................................................................
18 UNIFORM LOAD – STRUCTURAL
..............................................................................................................
18 FORCED ENTRY RESISTANCE
....................................................................................................................
19 SASH VERTICAL DEFLECTION TEST
...........................................................................................................
19 SASH AND HARDWARE LOAD TEST
..........................................................................................................
19 SASH / LEAF TORSION TEST
.....................................................................................................................
19 INSECT SCREEN SERVICEABILITY
..............................................................................................................
19 THERMOPLASTIC CORNER WELD TEST
.....................................................................................................
19
CONCLUSION
..............................................................................................................................
20
APPENDIX A: DRAWINGS
..............................................................................................................
21
APPENDIX B: PHOTOGRAPHS
........................................................................................................
30
APPENDIX C: REVISION TABLE
.......................................................................................................
41
-
TEST REPORT FOR BRANTEC GLAZING SYSTEMS INC.
Report No.: 103141992COQ‐001A Revision Date: 22‐May‐2019
Version (13‐March‐2017)
Page 6 of 42 GFT‐OP‐10b
SECTION 3 OBJECTIVE
Intertek Testing Services NA Ltd.
(Intertek) has conducted testing for
Brantec Glazing Systems
Inc. (Brantec) on a 2580 mm (101.6”) x 2615 mm (103.0”) Aluminum Casement – Fixed Combination Window Wall System. Testing was conducted in accordance with following standard / specification:
AAMA/WDMA/CSA 101/I.S.2/ A440‐08
“Standard/Specification for windows, doors,
and unit skylights” (NAFS‐08)
A440S1‐09 “Canadian Supplement to
AAMA/WDMA/CSA 101/I.S.2/A440, NAFS –
North American Fenestration Standard/Specification for windows, doors, and skylights” (A440S1‐09)
AAMA/WDMA/CSA 101/I.S.2/ A440‐11
“Standard/Specification for windows, doors,
and unit skylights” (NAFS‐11)
A440S1‐17 “Canadian Supplement to
AAMA/WDMA/CSA 101/I.S.2/A440, NAFS –
North American Fenestration Standard/Specification for windows, doors, and skylights” (A440S1‐17)
This evaluation was started on July 19, 2017 and completed on August 18, 2017.
SECTION 4 SAMPLE ASSEMBLY AND DESCRIPTION Manufacturer Information
Brantec Glazing Systems Inc. 103 – 8288 North Fraser Way Burnaby, BC V3N 0E9 Canada
Model Name
Aluminum Casement – Fixed Combination Window Wall System
Installation Test Buck:
2x6, #2 & better spf, box w/ 2x12, #2 & better spf, cladding, butt
joints
secured with 2x #10 x 4" deck screws. The 2x12 clad was also butt jointed together with 4x #10
x 4" deck screws and secured
to the 2x6 with #10 x 3‐1/2"
flat head screws at least
at every 305 mm (12").
The buck was lined with
a peel and
stick membrane on the exterior side.
Specimen to Buck:
#12 x 2” tek screws are
used through the track profile,
into the
buck, oriented parallel to the plane of glass. 7x through each jamb and the head. Each screw head is sealed with silicone.
The sill is installed with an
aluminum angle, approximately 3 mm
(0.12”) thick, 51 mm (2”) wide x 25 mm (1”) tall, the full width of the sample.
11x #10 x 2” Tek screws were used to secure the angle to the test buck. 12x #10 x 3/4"
self‐tapping pan‐head screws were used
to secure the angle to
the window frame.
Silicone was used to seal all joints of the test buck as well as the rough opening of
-
TEST REPORT FOR BRANTEC GLAZING SYSTEMS INC.
Report No.: 103141992COQ‐001A Revision Date: 22‐May‐2019
Version (13‐March‐2017)
Page 7 of 42 GFT‐OP‐10b
the buck, full perimeter on both the interior and exterior side.
An aluminum
length of 19 Gauge brakeshape
flashing was used under the
full
width of the sample, approximately 140 mm (5‐1/2”) x 70 mm (2‐3/4”)
Size
Overall Size:
Width: 2580 mm (101.6”)
Height: 2615 mm (103.0”)
Casement Size:
Width: 995 mm (39.2”)
Height: 1595 mm (62.8”)
Large Fixed Size:
Width: 1585 mm (62.4”)
Height: 2615 mm (103.0”)
Small Fixed Size:
Width: 995 mm (39.2”)
Height: 1020 mm (40.2”)
Track
Material: Two‐piece aluminum that snap together, with pour and de‐bridge thermal
break by Azon. One style
track assembly used along the
jambs and another style used
along the
head to support the main frame profile.
The head track contains two lengths of a splined EPDM gasket, see weather‐stripping
section for further detail.
Main Frame
Material:
Aluminum with pour and de‐bridge thermal break by Azon.
2x lengths of styrofoam
rectangle profiles with dimensions of
approximately 13 mm (1/2”)
x 38 mm (1‐1/2”) used in the jambs, and 24 mm (1”) x 52 mm (2”) used in the head, each adhered to the rough‐opening side of the frame cavity.
Corners: Frame corners are butt joined to the sill, jambs are secured to the sill with the use of 4x #12 x 1‐1/2” lag bolts. The jambs are secured to the head with the use of two aluminum pieces, a sleeve and an end dam, welded together and slid in to the grooves of either profile, sealed to each profile with silicone.
Reinforcement: None A
splined EPDM gasket is used on
the exterior‐most and interior‐most
face of the
jamb profiles, to seal to the track. The jambs and head are also sealed to the exterior side of the track profile with a cap bead of silicone.
Vent Frame
Material: Aluminum with pour and de‐bridge thermal break by Azon. Each profile has 1x
length of styrofoam rectangle profiles with dimensions of approximately 13 mm (1/2”) x 38 mm (1‐1/2”), each adhered to the inside cavity of the profile.
Corners: Frame corners are mitre cut and joined with the use of an aluminum corner key. Corner key is secured in the profile by dimpling the step of the aluminum frame in to the corner key. Silicone is used around the corner key as well as the inside edge
-
TEST REPORT FOR BRANTEC GLAZING SYSTEMS INC.
Report No.: 103141992COQ‐001A Revision Date: 22‐May‐2019
Version (13‐March‐2017)
Page 8 of 42 GFT‐OP‐10b
of the mitre joint. Secured
to the main‐frame with
the use of #8 x 1‐1/2” pan‐head
screws. 3x used
along the head, approximately 127 mm (5”) from either corner, and through the hole of the swing limiter 305 mm (12”) from the hinge side. 2x along the hinge side, 152 mm (6”) and 686 mm (27”) from the bottom. 2x along the locking side, 102 mm (4”) and 533 mm (21”) from the bottom.
The vent frame is sealed to
the main frame on the interior
side with
the use of a hollow bulb gasket as described in the weather‐stripping section, and on the exterior side with a full perimeter of silicone used in the gap between frame profiles.
Vertical Mullion
One vertical combination mullion
Reinforcement: None. Material:
2x aluminum profiles that snap together, each with a pour and de‐bridge
thermal break by Azon.
Each profile has 2x
lengths of styrofoam rectangle profiles with dimensions of approximately 13 mm (1/2”) x 38 mm (1‐1/2”), each adhered to the inside cavity of each profile.
Silicone is used in the
joint where the two profiles snap together, full
length on the exterior and interior side.
Horizontal Mullion
One horizontal integral mullion
Reinforcement: None.
Material: Aluminum with a pour and de‐bridge thermal break by Azon.
Secured to the jamb and intersecting vertical mullion with the use of 4x #12 x 1‐1/2”
lag bolts.
Silicone is used at either end connection of the mullion
Operable Vent
Material: Interior side is aluminum with a snap‐on polyamide thermal profile on the exterior side of the sash.
Corners: Mitre cut and joined with the use of a corner key. Corner key is secured in the profile by dimpling the step of the aluminum frame in to the corner key. Silicone is used around the corner key as well as the inside edge of the mitre joint.
Sash Size:
Width: 845 mm (33.3")
Height: 1445 mm (56.9")
Locks and Hardware
Multi‐point (3‐point) lock system controlled through a lock handle set located at 406 mm (16”) from the bottom inside edge of the sash.
Tie bar with 3 locking points slides in a slot on the outside perimeter of the sash.
Keepers: 3x keepers used on the
locking
jamb of the casement frame, centered
approximately 165 mm (6‐1/2”), 705 mm (27‐3/4”) and 1245 mm (49”) from the bottom
inside edge of the casement
frame. Each keeper
secured with 3x #8
x 5/8" pan‐head screws and sealed to the frame profile with silicone.
2x swing limiters are used, one on the top rail and one on the bottom rail of the sash.
-
TEST REPORT FOR BRANTEC GLAZING SYSTEMS INC.
Report No.: 103141992COQ‐001A Revision Date: 22‐May‐2019
Version (13‐March‐2017)
Page 9 of 42 GFT‐OP‐10b
Secured to
the sash with 3x #8 x 5/8” pan‐head screws.
Secured to
the horizontal mullion of the frame with 4 x #8 x 5/8” pan‐head screws, and secured to the head of the
frame with 3x #8 x 5/8” pan‐head
screws and 1x #8 x 1‐1/2” pan‐head
screws which is also used to secure the casement frame in to the main‐frame. Silicone was used between the swing limiter and the frame profile.
One
continuous hinge assembly was used along
the entire hinge stile of the
sash. Secured to each the sash and the frame with 21x #8 x 3/4" flat‐head screws.
2x sash alignment blocks with a
roller used on
the horizontal mullion of the
sash. Centered approximately 133
mm (5‐1/4”) from the inside
edge of the
latching corner, and 197 mm (7‐3/4”) from the inside edge of the hinge corner. Each secured to the frame with 2x #8 x 3/4” flat‐head screws.
Silicone
is used between the sash alignment blocks and
the frame profile. 2x stainless
steel slides are secured to
the bottom of the sash, for the alignment blocks to slide on. Each secured to the bottom rail of the sash with 2x #8 x 5/8” pan‐head screws.
Drainage 6mm (0.24”) diameter
drain holes in various locations
are drilled in to
the main frame jamb profiles and
vertical mullion profiles, to provide
drainage down
the jambs and mullion. 1x
in each jamb and
vertical mullion profile, aligned with
the lowest point of the top of the horizontal mullion, as well as 1x at the bottom of the exterior‐most cavity of
the horizontal mullion profile. 1x
in each
jamb and vertical mullion profile, aligned with the bottom of the cavity for the head main‐frame profile on each the interior and exterior side. 1x in each jamb and vertical mullion profile, aligned with the lowest point of the top of the sill, as well as 1x at the bottom of the exterior‐most cavity of the sill profile.
4x 25 mm (1”) wide slots were cut from the exterior side of the silicone between the sill flashing and sill profile to allow for drainage out from the bottom of the jamb and vertical mullion
profiles, centered approximately 89 mm
(3.50”) from the
outside edge of jamb or mullion profile.
Weather‐strip
The sash has an EPDM hollow bulb seal along the top and bottom rail and
latching
stile, around the exterior‐most edge, kerf inserted. Applied as 1 strip, turned around the corners.
The sash has an EPDM fin seal used, at the mid‐step on the outside perimeter of the sash inserted into a T‐slot. Applied as 4 strips with the corners over‐lapped.
The Casement frame has 2x
full perimeters of interior facing
EPDM hollow
bulb gasket. One full perimeter on the interior‐most surface is to seal the casement frame to the main‐frame. A second full perimeter used to seal against the casement sash. Corners are mitre cut and sealed with silicone.
The mainframe jamb profiles have
2x lengths of EPDM splined
gaskets on
the exterior‐most and the interior‐most of the profile, to seal against the jamb tracks
The two‐piece head track has an EPDM gasket used on each piece. The exterior side has an
interior facing spline gasket.
The
interior side has an exterior
facing hollow bulb gasket.
-
TEST REPORT FOR BRANTEC GLAZING SYSTEMS INC.
Report No.: 103141992COQ‐001A Revision Date: 22‐May‐2019
Version (13‐March‐2017)
Page 10 of 42 GFT‐OP‐10b
Fixed Glazing
IGU specification: 6 mm / 6
mm clear annealed with a 12
mm Stainless Steel Spacer, sealed
together using hot melt butyl.
Overall thickness, 24 mm (~1")
Laid‐in,
interior glazed on top of a full perimeter of black butyl tape, approximately 10 mm (0.38”) x 3 mm (0.12”). Silicone is used around the outside of the glazing tape perimeter at
the corners, extending approximately 150 mm
(5.9”) away from each corner.
A white foam backer rod approximately 10 mm (3/8”) diameter was used around the entire glass unit, and a full perimeter silicone bead was applied on the interior side of the backer rod.
Glazing Blocks: 2x 6 mm (0.24”) x 102 mm (4.00”) x 22 mm (0.87”) neoprene setting blocks used. Used under the glass, centered approximately 229 mm (9”) from either inside corner.
Glazing Stops: Aluminum with an EPDM glazing gasket.
Casement Glazing
IGU specification: 6 mm / 6
mm clear tempered with a
12 mm Stainless Steel Spacer,
sealed
together using hot melt butyl.
Overall thickness, 24 mm (~1")
Laid‐in, exterior glazed on top of a full perimeter of glazing silicone and a black closed cell foam gasket, approximately 11 mm (0.43”) x 6 mm (0.25”).
A white foam backer rod approximately 10 mm (3/8”) diameter was used around the entire glass unit, and a full perimeter silicone bead was applied on the exterior side of the backer rod, flush with the exterior face of the glass unit.
Glazing Blocks: 2x 6 mm (0.24”) x 52 mm (2.00”) x 22 mm (0.87”) neoprene setting blocks used. Used under the glass unit, adjacent to either side stile.
Glazing Stops: None
Drawings
Copy of drawings supplied by Brantec Glazing Systems Inc. included in Appendix A.
-
TEST REPORT FOR BRANTEC GLAZING SYSTEMS INC.
Report No.: 103141992COQ‐001A Revision Date: 22‐May‐2019
Version (13‐March‐2017)
Page 11 of 42 GFT‐OP‐10b
SECTION 5 TESTING AND EVALUATION METHODS OPERATING FORCE The
Operating Force Test was performed
on the sash and latch in
accordance with ASTM
E2068‐00(2016). The forces required initiate motion of the operable panel from both the fully open and fully closed positions, as well as the force required to maintain motion to the opposite limits of travel, were measured. The forces required to open and close the latches were also recorded. AIR LEAKAGE RESISTANCE The Air Leakage Resistance Test was performed in accordance with ASTM E283‐04(2012), “Standard Test Method for Determining Rate of Air Leakage Through Exterior Windows, Curtain Walls, and Doors Under Specified
Pressure Differences Across the
Specimen”. Air infiltration and
exfiltration tests
were performed using test pressures of 300 Pa (6.27 psf). The maximum air
leakage rate was calculated and compared to the allowable air leakage. CYCLIC WATER PENETRATION RESISTANCE The Cyclic Water Penetration Resistance Test was performed
in accordance with ASTM E547‐00(2016) “Standard Test Method for Water Penetration of Exterior Windows, Skylights, Doors, and Curtain Walls by
Cyclic Static Air Pressure
Difference” (ASTM E547). The
test was performed using the
specified pressure differential and a water
spray rate of at least 204
L/m2 per hour
(5.0 U.S. gal/ft2 per hour). Each
cycle consisted of five minutes
with the pressure applied and
one minute with the
pressure released, during which the water spray was continuously applied. STATIC WATER PENETRATION RESISTANCE The Static Water Penetration Resistance Test was performed
in accordance with ASTM E331‐00(2016) “Standard Test Method for Water Penetration of Exterior Windows, Skylights, Doors, and Curtain Walls by Uniform Static Air Pressure Difference”
(ASTM E331). The
test was performed using the
specified pressure differential and a water
spray rate of at least 204
L/m2 per hour
(5.0 U.S. gal/ft2 per hour). Duration of the test was 15 minutes, during which the water spray and air pressure was continuously applied. VENT / SASH / DOOR LEAF CYCLING (FIRST HALF) The Vent / Sash / Door Leaf Cycling Test was performed
in accordance with AAMA 910‐16 “Voluntary “Life Cycle”
Specifications and Test Methods
for AW Class Architectural Windows and Doors”
(AAMA 910). The Vent / Sash / Door Leaf was opened to at least 90° or the extent of its travel and then back to closed. This was performed for 2000 cycles where one cycle is considered the single action of open then close.
-
TEST REPORT FOR BRANTEC GLAZING SYSTEMS INC.
Report No.: 103141992COQ‐001A Revision Date: 22‐May‐2019
Version (13‐March‐2017)
Page 12 of 42 GFT‐OP‐10b
LOCKING HARDWARE CYCLING (FIRST HALF) The Locking Hardware Cycling Test was performed
in accordance with AAMA 910.
Each of the
locking hardware on the test specimen was operated for 2000 cycles where one cycle
is considered the single action of ‘lock’ then ‘unlock’ positions. MISUSE TEST The Misuse test was performed in accordance with Section 3.6 of AAMA 910. VENT / SASH / DOOR LEAF CYCLING (SECOND HALF) The Vent / Sash / Door Leaf Cycling Test was performed in accordance with AAMA 910. The second half of this test was performed for 2000 cycles. LOCKING HARDWARE CYCLING (SECOND HALF) The Locking Hardware Cycling Test was performed
in accordance with AAMA 910.
The second half of this test was performed for 2000 cycles.. OPERATING FORCE #2 The Operating Force Test was
repeated at the conclusion of the
second half of the
locking hardware cycling. THERMAL CYCLING The
Thermal Cycling Test was performed
in general accordance with AAMA
501.5 “Test Method
for Thermal Cycling of Exterior Walls” following the cycle and temperature requirements
in Section 3.7 of AAMA 910. The test consisted of six cycles of hot, 82°C (180°F) and cold, ‐18°C (0°F). UNIFORM LOAD DEFLECTION The Uniform Load Deflection tests were conducted in accordance with ASTM E330/E330M‐14 “Standard Test Method
for Structural Performance of
Exterior Windows, Skylights, Doors and
Curtain Walls
by Uniform Static Air Pressure Difference”
(ASTM E330), Procedure A. The
tests were performed
in both the positive and negative directions.
After a 10 second preload
(50% of the test load),
followed by 1 minute with the pressure released, the tests were conducted at the specified test pressure for a period of 10 seconds. Deflections were measured at the mid‐span and at the ends. The end deflections were averaged and subtracted from the mid‐span deflection (to eliminate deflections caused by movement at the ends of the structural supporting members).
Polyethylene film was used during the positive wind pressure sequences.
-
TEST REPORT FOR BRANTEC GLAZING SYSTEMS INC.
Report No.: 103141992COQ‐001A Revision Date: 22‐May‐2019
Version (13‐March‐2017)
Page 13 of 42 GFT‐OP‐10b
AIR LEAKAGE RESISTANCE #2 The Air Leakage Resistance test was repeated. CYCLIC WATER PENETRATION RESISTANCE #2 The Cyclic Water Penetration Resistance test was repeated. STATIC WATER PENETRATION RESISTANCE #2 The Static Water Penetration Resistance test was repeated. UNIFORM LOAD STRUCTURAL The Uniform Load Structural tests were conducted in accordance with ASTM E330/E330M‐14 “Standard Test Method
for Structural Performance of
Exterior Windows, Skylights, Doors and
Curtain Walls
by Uniform Static Air Pressure Difference” (ASTM E330), Procedure A.
After a 10 second preload (50% of test
load), followed by 1 minute with
the pressure released, the
sample was subjected
to a Uniform Load Structural test using a specified test pressure for a time of 10 seconds. The test was performed in both the positive and negative directions. After the test loads were released, the permanent deflections were recorded and the specimen was inspected for failure or permanent deformation of any part of the system that would cause any operational malfunction.
Polyethylene film was used during the positive wind pressure sequences. FORCED ENTRY RESISTANCE The
Forced‐entry Resistance Test was
conducted in accordance with ASTM
F588‐14 “Standard
Test Methods for Measuring the Forced Entry Resistance of Window Assemblies, Excluding Glazing
Impact”. This included the Disassembly, Sash Manipulation, Lock Hardware Manipulation, and Assembly Tests.
SASH VERTICAL DEFLECTION TEST The Sash Vertical Deflection Test was performed
in accordance with Section 5.3.6.4.3 of NAFS‐08 and Section 9.3.6.4.2 of NAFS‐11. After the test load was released, the specimen was inspected for failure or permanent deformation of any part of the system that would cause any operational malfunction. SASH AND HARDWARE LOAD TEST The Sash and Hardware Load (distributed load) Test was performed in accordance with Section 5.3.6.6.2 of
NAFS‐08 and Section 9.3.6.5.2 of
NAFS‐11. After the test
load was released, the
specimen was inspected for failure
or permanent deformation of any
part of the system that would
cause any operational malfunction.
-
TEST REPORT FOR BRANTEC GLAZING SYSTEMS INC.
Report No.: 103141992COQ‐001A Revision Date: 22‐May‐2019
Version (13‐March‐2017)
Page 14 of 42 GFT‐OP‐10b
SASH / LEAF TORSION TEST The Sash / Leaf Torsion Test was performed in accordance with Section 5.3.6.4.2 of NAFS‐08 and Section 7.3.4.2
of NAFS‐11. After the test
load was released, the specimen
was inspected for failure
or permanent deformation of any part of the system that would cause any operational malfunction. THERMOPLASTIC CORNER WELD TEST Test not applicable INSECT SCREEN SERVICEABILITY Test not applicable. DEVIATION FROM STANDARD METHOD There were no noted deviations from the test standards used in the evaluation reported herein. SECTION 6 TEST EQUIPMENT Equipment used during testing is listed as follows:
Test Equipment Intertek ID#
Air Leakage Resistance,
Water Penetration Resistance, and
Uniform Load Deflection / Structural
Fenestration Testing Control Unit
60650
Water spray assembly 60651
60652
20” Line Gauge
60673
64928
64926
64923
64920
64922
Forced‐entry Resistance
5000 lbs Load Cell P60691
1000 lbs Load Cell P60688
P60689
200 lbs Load Cell P60687
Sash Vertical Deflection Test and
Sash / Leaf Torsion Test
Digital Force Gauge D2710
Mitutoyo Digital Deflection Gauge
P60175
Sash and Hardware Load Test
Digital Force Gauge D2710
-
TEST REPORT FOR BRANTEC GLAZING SYSTEMS INC.
Report No.: 103141992COQ‐001A Revision Date: 22‐May‐2019
Version (13‐March‐2017)
Page 15 of 42 GFT‐OP‐10b
SECTION 7 RESULTS AND OBSERVATIONS OPERATING FORCE The forces required to operate the system:
Initiate Opening:
107.6 N (24.2 lbs)
Initiate Closing:
32.8 N (7.4 lbs) Maintain Opening:
48.6 N (10.9 lbs)
Maintain Closing:
110.6 N (24.9 lbs) Latch Opening:
86.4 N (19.4 lbs) Latch Closing:
91.6 N (20.6 lbs)
Maximum allowable force to initiate motion:
155 N (34.9 lbs)
Maximum allowable force to maintain motion:
135 N (30.4 lbs) Maximum allowable force to open and close latch:
100 N (22.5 lbs) The tested specimen met the performance requirements of NAFS‐08, NAFS‐11, A440S1‐09 and A440S1‐17 for Operating Force. AIR LEAKAGE RESISTANCE Air test data is indicated in the following table:
Property
Area m2 (ft2) Infiltration Rate L/s*m2 (cfm/ft2)
Exfiltration Rate L/s*m2 (cfm/ft2)
Compliance US (CAN)
Overall Assembly @ 300 Pa
6.75 (72.62) 0.01 (0.00)
0.05 (0.01)
Pass (A3) Casement @ 300 Pa
1.59 (17.08) 0.00 (0.00)
0.01 (0.00)
Pass (A3) Overall Fixed @ 300 Pa
5.16 (55.54) 0.01 (0.00)
0.06 (0.01) Pass (Fixed)
Allowable Leakage Rates Maximum allowable air leakage rate (US):
1.5 L/s*m2, 0.3 cfm/ft2 Maximum allowable air leakage rate (CAN – A3):
0.5 L/s*m2, 0.1 cfm/ft2 Maximum allowable air leakage rate (CAN – Fixed):
0.1 L/s*m2, 0.05 cfm/ft2
The overall system met the US and Canadian performance requirements as reported above when evaluated under NAFS‐08, NAFS‐11, A440S1‐09 and A440S1‐17. CYCLIC WATER PENETRATION RESISTANCE During the 24‐minute test period, using a pressure differential of 730 Pa (15.3 psf), there was no water leakage
observed. The system met the
(CAN) PG100 Water Penetration
Resistance
performance requirements under NAFS‐08, NAFS‐11, A440S1‐09 and A440S1‐17. STATIC WATER PENETRATION RESISTANCE During the 15‐minute test period, using a pressure differential of 730 Pa (15.3 psf), there was no water leakage
observed. The system met the
(CAN) PG100 Water Penetration
Resistance
performance requirements under NAFS‐08, NAFS‐11, A440S1‐09 and A440S1‐17.
-
TEST REPORT FOR BRANTEC GLAZING SYSTEMS INC.
Report No.: 103141992COQ‐001A Revision Date: 22‐May‐2019
Version (13‐March‐2017)
Page 16 of 42 GFT‐OP‐10b
VENT / SASH / DOOR LEAF CYCLING (FIRST HALF) After 2000 cycles, there was found to be no failure or permanent deformation to the system that would cause any operational malfunction. The system met the Vent / Cycling / Door Leaf Cycling performance requirements of AAMA 910. LOCKING HARDWARE CYCLING (FIRST HALF) After 2000 cycles, there was found to be no failure or permanent deformation to the system that would cause
any operational malfunction. The
system met the Locking Hardware
Cycling
performance requirements of AAMA 910. MISUSE TEST After
the loads were removed, there was
found to be no failure or
permanent deformation to the system
that would cause any operational malfunction.
The system met the Misuse
test performance requirements of AAMA 910. VENT / SASH / DOOR LEAF CYCLING (SECOND HALF) After 2000 cycles, there was found to be no failure or permanent deformation to the system that would cause any operational malfunction. The system met the Vent / Cycling / Door Leaf Cycling performance requirements of AAMA 910. LOCKING HARDWARE CYCLING (SECOND HALF) After 2000 cycles, there was found to be no failure or permanent deformation to the system that would cause
any operational malfunction. The
system met the Locking Hardware
Cycling
performance requirements of AAMA 910. OPERATING FORCE #2 The forces required to operate the system:
Initiate Opening:
118.0 N (26.5 lbs)
Initiate Closing:
6.4 N (1.4 lbs) Maintain Opening:
12.8 N (2.9 lbs)
Maintain Closing:
90.8 N (20.4 lbs) Latch Opening:
12.6 N (2.8 lbs) Latch Closing:
13.8 N (3.1 lbs)
Maximum allowable force to initiate motion:
155 N (34.9 lbs)
Maximum allowable force to maintain motion:
135 N (30.4 lbs) Maximum allowable force to open and close latch:
100 N (22.5 lbs) The tested specimen met the performance requirements of NAFS‐08, NAFS‐11, A440S1‐09 and A440S1‐17 for Operating Force.
-
TEST REPORT FOR BRANTEC GLAZING SYSTEMS INC.
Report No.: 103141992COQ‐001A Revision Date: 22‐May‐2019
Version (13‐March‐2017)
Page 17 of 42 GFT‐OP‐10b
THERMAL CYCLING
No. of Cycles Exterior Conditions
Interior Conditions Hot Temperature
Cold Temperature 6 82°C (180°F)
‐18°C (0°F) 24°C (74°F)
Upon completion of the
thermal cycling, there was found
to be no
failure or permanent deformation due to the expansion and contraction of the system that would cause any operational malfunction. The system met the Thermal Cycling performance requirements of AAMA 501.5 and AAMA 910. UNIFORM LOAD – DEFLECTION Operable sash Uniform Load Deflection data:
Test Pressure, Pa (psf)
Deflection Measurements, mm (in.)
Compliance Positive Negative
Deflection Residual Deflection
Residual
2160 (45.1) 4.66 (0.18)
0.85 (0.03) 4.18 (0.16)
1.33 (0.05) Pass DP45
Lock rail span, L = 1410 mm (55.51")
Deflection limit, L/175 = 8.06 mm (0.32”) Mullion Uniform Load Deflection data:
Test Pressure, Pa (psf)
Deflection Measurements, mm (in.)
Compliance Positive Negative
Deflection Residual Deflection
Residual
2160 (45.1) 12.27 (0.48)
1.43 (0.06) 13.68 (0.54)
2.40 (0.09) Pass DP45
Vert. Mullion span, L = 2530 mm (99.61")
Deflection limit, L/175 = 14.46 mm (0.57”)
After the test loads were released, the specimen was inspected and there was found to be no failure or permanent deformation of any part of the system that would cause any operational malfunction.
The system met the DP45 Uniform Load Deflection performance requirements under NAFS‐08 and NAFS‐11.
-
TEST REPORT FOR BRANTEC GLAZING SYSTEMS INC.
Report No.: 103141992COQ‐001A Revision Date: 22‐May‐2019
Version (13‐March‐2017)
Page 18 of 42 GFT‐OP‐10b
AIR LEAKAGE RESISTANCE #2 Air test data is indicated in the following table:
Property
Area m2 (ft2) Infiltration Rate L/s*m2 (cfm/ft2)
Exfiltration Rate L/s*m2 (cfm/ft2)
Compliance US (CAN)
Overall Assembly @ 300 Pa
6.75 (72.62) 0.01 (0.00)
0.23 (0.05)
Pass (A3) Casement @ 300 Pa
1.59 (17.08) 0.04 (0.01)
0.15 (0.03)
Pass (A3) Overall Fixed @ 300 Pa
5.16 (55.54) 0.00 (0.00)
0.02 (0.00) Pass (Fixed)
Allowable Leakage Rates Maximum allowable air leakage rate (US):
1.5 L/s*m2, 0.3 cfm/ft2 Maximum allowable air leakage rate (CAN – A3):
0.5 L/s*m2, 0.1 cfm/ft2 Maximum allowable air leakage rate (CAN – Fixed):
0.1 L/s*m2, 0.05 cfm/ft2
The overall system met the US and Canadian performance requirements as reported above when evaluated under NAFS‐08, NAFS‐11, A440S1‐09 and A440S1‐17. CYCLIC WATER PENETRATION RESISTANCE #2 During the 24‐minute test period, using a pressure differential of 730 Pa (15.3 psf), there was no water leakage
observed. The system met the
(CAN) PG100 Water Penetration
Resistance
performance requirements under NAFS‐08, NAFS‐11, A440S1‐09 and A440S1‐17. STATIC WATER PENETRATION RESISTANCE #2 During the 15‐minute test period, using a pressure differential of 730 Pa (15.3 psf), there was no water leakage
observed. The system met the
(CAN) PG100 Water Penetration
Resistance
performance requirements under NAFS‐08, NAFS‐11, A440S1‐09 and A440S1‐17. UNIFORM LOAD – STRUCTURAL Operable sash Uniform Load Deflection data:
Test Pressure, Pa (psf)
Residual Deflection Measurements, mm (in.) Compliance
Positive Negative 3240 (67.7)
1.30 (0.05) 2.16 (0.09)
Pass DP45
Lock rail span, L = 1410 mm (55.51")
Residual deflection limit, L*0.2% = 2.82 mm (0.11") Mullion Uniform Load Deflection data:
Test Pressure, Pa (psf)
Residual Deflection Measurements, mm (in.) Compliance
Positive Negative 3240 (67.7)
2.66 (0.10) 3.50 (0.14)
Pass DP45 Vert. Mullion span, L = 2530 mm (99.61")
Residual deflection limit, L*0.2% = 5.06 mm (0.20")
After the test loads were released, the specimen was inspected and there was found to be no failure or permanent
deformation of any part of the
window system that would cause
any
operational malfunction. The system met the overall DP45 Uniform Load performance requirements under NAFS‐08 and NAFS‐11.
-
TEST REPORT FOR BRANTEC GLAZING SYSTEMS INC.
Report No.: 103141992COQ‐001A Revision Date: 22‐May‐2019
Version (13‐March‐2017)
Page 19 of 42 GFT‐OP‐10b
FORCED ENTRY RESISTANCE Attempts to
gain entry by opening the
glazing panel, in accordance with
the Disassembly and Sash Manipulation
tests
for a Type B assembly, were unsuccessful.
The system met
the Grade 20 Forced‐entry Resistance performance requirements of NAFS‐08 and NAFS‐11. SASH VERTICAL DEFLECTION TEST
Test Load Max. Deflection
Max. Allowable Deflection 270 N (61 lbs)
1.52 mm (0.06”)
16.90 mm (0.67”)
After the test load was released the specimen was inspected for failure or permanent deformation that would
impair with the operation of the
system. The system met the
performance requirements
of NAFS‐08 and NAFS‐11 for the Sash Vertical Deflection test. SASH AND HARDWARE LOAD TEST After the test load was released it was found that the hardware was strong enough to support the 300 Pa (6.3 psf) load over the 10 second period. The system met the performance requirements of NAFS‐08 and NAFS‐11 for the Sash and Hardware Load Test. SASH / LEAF TORSION TEST
Test Load Max. Deflection
Max. Allowable Deflection 90 N (20 lbs)
8.25 mm (0.32”)
62.52 mm (2.46”)
After the test load was released the specimen was inspected for failure or permanent deformation that would
impair with the operation of the
system. The system met the
performance requirements
of NAFS‐08 and NAFS‐11 for the Sash/Leaf Torsion Test. INSECT SCREEN SERVICEABILITY Test not applicable. THERMOPLASTIC CORNER WELD TEST Test not applicable.
-
TEST REPORT FOR BRANTEC GLAZING SYSTEMS INC.
Report No.: 103141992COQ‐001A Revision Date: 22‐May‐2019
Version (13‐March‐2017)
Page 20 of 42 GFT‐OP‐10b
SECTION 8 CONCLUSION
The Aluminum Casement – Fixed Combination Window Wall System, submitted by Brantec Glazing Systems Inc.,
tested and described within this
report, achieved the overall performance
requirements of Class AW – PG45 when tested in accordance with NAFS‐08, NAFS‐11, A440S1‐09 and A440S1‐17.
-
TEST REPORT FOR BRANTEC GLAZING SYSTEMS INC.
Report No.: 103141992COQ‐001A Revision Date: 22‐May‐2019
Version (13‐March‐2017)
Page 21 of 42 GFT‐OP‐10b
`
SECTION 9 APPENDIX A: DRAWINGS (8 Pages)
-
TEST REPORT FOR BRANTEC GLAZING SYSTEMS INC.
Report No.: 103141992COQ‐001A Revision Date: 22‐May‐2019
Version (13‐March‐2017)
Page 30 of 42 GFT‐OP‐10b
`
SECTION 10 APPENDIX B: PHOTOGRAPHS (10 Pages)
-
TEST REPORT FOR BRANTEC GLAZING SYSTEMS INC.
Report No.: 103141992COQ‐001A Revision Date: 22‐May‐2019
Version (13‐March‐2017)
Page 31 of 42 GFT‐OP‐10b
`
Aluminum Casement – Fixed Combination Window Wall System – Exterior
Aluminum Casement – Fixed Combination Window Wall System ‐ Interior
-
TEST REPORT FOR BRANTEC GLAZING SYSTEMS INC.
Report No.: 103141992COQ‐001A Revision Date: 22‐May‐2019
Version (13‐March‐2017)
Page 32 of 42 GFT‐OP‐10b
`
Track Assembly – Jambs
Main‐Frame Assembly – Jambs
Main‐Frame Assembly ‐ Sill
-
TEST REPORT FOR BRANTEC GLAZING SYSTEMS INC.
Report No.: 103141992COQ‐001A Revision Date: 22‐May‐2019
Version (13‐March‐2017)
Page 33 of 42 GFT‐OP‐10b
`
Track Assembly – Head
Main‐Frame Assembly ‐ Head
Sash Stile/Rail Assembly
-
TEST REPORT FOR BRANTEC GLAZING SYSTEMS INC.
Report No.: 103141992COQ‐001A Revision Date: 22‐May‐2019
Version (13‐March‐2017)
Page 34 of 42 GFT‐OP‐10b
`
Vertical Mullion Assembly – Coupler
Horizontal Integral Mullion Assembly
-
TEST REPORT FOR BRANTEC GLAZING SYSTEMS INC.
Report No.: 103141992COQ‐001A Revision Date: 22‐May‐2019
Version (13‐March‐2017)
Page 35 of 42 GFT‐OP‐10b
`
Aluminum, Fixed Glazing Stop
Splined Main‐frame/Track Gasket
Glazing Gasket
-
TEST REPORT FOR BRANTEC GLAZING SYSTEMS INC.
Report No.: 103141992COQ‐001A Revision Date: 22‐May‐2019
Version (13‐March‐2017)
Page 36 of 42 GFT‐OP‐10b
`
Vent Weather‐stripping profiles
Vent Frame Weather‐stripping
Sleeve and End Dam at Corners of Head
-
TEST REPORT FOR BRANTEC GLAZING SYSTEMS INC.
Report No.: 103141992COQ‐001A Revision Date: 22‐May‐2019
Version (13‐March‐2017)
Page 37 of 42 GFT‐OP‐10b
`
Drainage Through Silicone at Sill
Locking Handle
-
TEST REPORT FOR BRANTEC GLAZING SYSTEMS INC.
Report No.: 103141992COQ‐001A Revision Date: 22‐May‐2019
Version (13‐March‐2017)
Page 38 of 42 GFT‐OP‐10b
`
Locking Assembly
Strike Plate
Sash Alignment Block on Frame
-
TEST REPORT FOR BRANTEC GLAZING SYSTEMS INC.
Report No.: 103141992COQ‐001A Revision Date: 22‐May‐2019
Version (13‐March‐2017)
Page 39 of 42 GFT‐OP‐10b
`
Sash Alignment Slide on Bottom Rail
Swing Limiter
Hinge Assembly
-
TEST REPORT FOR BRANTEC GLAZING SYSTEMS INC.
Report No.: 103141992COQ‐001A Revision Date: 22‐May‐2019
Version (13‐March‐2017)
Page 40 of 42 GFT‐OP‐10b
`
Vent Bulb Weather‐stripping
Vent Fin Seal Weather‐stripping
-
TEST REPORT FOR BRANTEC GLAZING SYSTEMS INC.
Report No.: 103141992COQ‐001A Revision Date: 22‐May‐2019
Version (13‐March‐2017)
Page 41 of 42 GFT‐OP‐10b
`
SECTION 11 APPENDIX C: REVISION TABLE (1 Page)
-
TEST REPORT FOR BRANTEC GLAZING SYSTEMS INC.
Report No.: 103141992COQ‐001A Revision Date: 22‐May‐2019
Version (13‐March‐2017)
Page 42 of 42 GFT‐OP‐10b
`
Revision Table
Date Section Description Technician
Reviewer
22‐Sept‐2017 ‐‐‐ Original Issue Date
‐‐‐ ‐‐‐
22‐May‐2019
General Updated company name from CBM Windows II Inc. to Brantec Glazing Systems Inc.
Cover Page
Added ‘Test Report Issued To’
4 ‘Manufacturer Information’ updated