Top Banner
BRANTEC GLAZING SYSTEMS INC. TEST REPORT TEST REPORT ISSUED TO Brantec Glazing Systems Inc. 103 – 8288 North Fraser Way Burnaby, BC V3N 0E9 Canada SPECIFICATION AAMA/WDMA/CSA 101/I.S.2/A44008 AAMA/WDMA/CSA 101/I.S.2/A44011 A440S109 A440S117 PRODUCT SERIES & TYPE Aluminum Casement – Fixed Combination Window Wall System PRIMARY DESIGNATION Class AW – PG45 – Size Tested 2580 x 2615 mm (102 x 103 in) – Type C, FW SECONDARY DESIGNATION Positive Design Pressure = 2160 Pa (45.1 psf) Negative Design Pressure = 2160 Pa (45.1 psf) Water Penetration Resistance = 730 Pa (15.3 psf) Canadian Air Leakage Resistance = A3 REPORT NUMBER 103141992COQ001A REVISION ISSUE DATE 22May2019 ORIGINAL ISSUE DATE 22Sept2017 PAGES 42 DOCUMENT CONTROL NUMBER GFTOP10b (13March2017) © 2017 INTERTEK
42

BRANTEC GLAZING SYSTEMS INC. TEST REPORT€¦ · NAFS – North American Fenestration Standard/Specification for windows, doors, and skylights” and A440S1‐17 “Canadian Supplement

Oct 23, 2020

Download

Documents

dariahiddleston
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
  • BRANTEC GLAZING SYSTEMS INC. TEST REPORT TEST REPORT ISSUED TO Brantec Glazing Systems Inc. 103 – 8288 North Fraser Way Burnaby, BC   V3N 0E9 Canada  SPECIFICATION AAMA/WDMA/CSA 101/I.S.2/A440‐08 AAMA/WDMA/CSA 101/I.S.2/A440‐11 A440S1‐09 A440S1‐17 

    PRODUCT SERIES & TYPE Aluminum Casement – Fixed Combination Window Wall System 

    PRIMARY DESIGNATION Class AW – PG45 – Size Tested 2580 x 2615 mm (102 x 103 in) – Type C, FW 

    SECONDARY DESIGNATION Positive Design Pressure = 2160 Pa (45.1 psf) Negative Design Pressure = 2160 Pa (45.1 psf) Water Penetration Resistance = 730 Pa (15.3 psf) Canadian Air Leakage Resistance = A3   REPORT NUMBER   103141992COQ‐001A 

    REVISION ISSUE DATE      22‐May‐2019 

    ORIGINAL ISSUE DATE      22‐Sept‐2017 

    PAGES 42  DOCUMENT CONTROL NUMBER GFT‐OP‐10b (13‐March‐2017) © 2017 INTERTEK 

  • TEST REPORT FOR BRANTEC GLAZING SYSTEMS INC. Report No.: 103141992COQ‐001A Revision Date: 22‐May‐2019 

    1500 Brigantine Drive Coquitlam, BC, V3K 7C1  Telephone: 604‐520‐3321 Facsimile:  604‐524‐9186 www.intertek.com 

     

    This report  is  for the exclusive use of  Intertek's Client and  is provided pursuant to the agreement between  Intertek and  its Client.  Intertek's responsibility and  liability are limited  to  the  terms and conditions of  the agreement.  Intertek assumes no  liability  to any party, other  than  to  the Client  in accordance with  the agreement,  for any  loss, expense or damage occasioned by the use of this report. Only the Client is authorized to copy or distribute Intertek’s Reports and then only in their entirety, and the Client shall not use the Reports in a misleading manner.  In the event any portion of this report becomes public, including but not limited to press releases, articles, and marketing material, without prior written consent from Intertek, Intertek may enforce the reproduction of the report in its entirety by making the full report public.  Client further agrees and understands that reliance upon the Reports  is  limited to the representations made therein.    In the event any portion of this report becomes public,  including but not limited to press releases, articles, and marketing material, without prior written consent from Intertek, Intertek will enforce the reproduction of the report in its entirety by making the full report public. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material, product or service must first be approved in writing by Intertek. The observations and test results in this report are relevant only to the sample tested.  Should Customer use an Intertek Report, in whole or in part, in such a manner as to involve Intertek in legal controversy or to adversely affect Intertek’s reputation, it shall be Intertek’s right to utilize any and all Customer information, including, but not limited to, data, records, instructions, notations, samples or documents within Intertek’s custody and control which relate to the customer for the purpose of offering any necessary defense or rebuttal to such circumstances.     This report by  itself does not  imply that the material, product, or service  is or has ever been under an  Intertek certification program.  

    Version (13–March‐2017)  Page 2 of 42  GFT‐OP‐10b   

    CONCLUSION  

    The Aluminum Casement – Fixed Combination Window Wall System, submitted by Brantec Glazing Systems Inc., tested and described within this report, achieved the overall performance requirements of Class AW – PG45 when tested in accordance with NAFS‐08, NAFS‐11, A440S1‐09 and A440S1‐17.      

    _ _               ______     Jason Komorski  David Park 

    TECHNICIAN  REVIEWER BUILDING PRODUCTS  BUILDING PRODUCTS      

       

  • TEST REPORT FOR BRANTEC GLAZING SYSTEMS INC.       Report No.: 103141992COQ‐001A Revision Date: 22‐May‐2019    

    Version (13‐March‐2017)  Page 3 of 42  GFT‐OP‐10b 

     

    SECTION 1 SUMMARY OF RESULTS  

    A  summary  of  results  for AAMA/WDMA/CSA  101/I.S.2/A440‐08  “Standard/Specification  for windows, doors, and unit  skylights”, AAMA/WDMA/CSA 101/I.S.2/A440‐11 “Standard/Specification  for windows, doors,  and  unit  skylights”,  A440S1‐09  “Canadian  Supplement  to  AAMA/WDMA/CSA  101/I.S.2/A440, NAFS  –  North  American  Fenestration  Standard/Specification  for  windows,  doors,  and  skylights”  and A440S1‐17  “Canadian  Supplement  to  AAMA/WDMA/CSA  101/I.S.2/A440,  NAFS  –  North  American Fenestration  Standard/Specification  for  windows,  doors,  and  skylights”are  as  indicated  in  the  table below: 

    Evaluation Property  Results Operational Force (overall)  US – Pass; Can – Pass 

    Air Leakage Resistance @ 300 Pa (6.3 psf)  US – Pass; Can – Case = A3,  Fixed = Fixed Water Penetration Resistance (Static & Cyclic)  730 Pa (15.3 psf) 

    Vent / Sash / Door Leaf Cycling  Pass Locking Hardware Cycling  Pass 

    Misuse Test  Pass Thermal Cycling  Pass 

    Uniform Load – Deflection   2160 Pa (45.1 psf) Uniform Load – Structural   3240 Pa (67.7 psf) Forced Entry Resistance  Gr.20 

    Sash Vertical Deflection Test  Pass Sash and Hardware Load Test  Pass 

    Sash / Leaf Torsion Test  Pass Thermoplastic Corner Weld Test  N/A 

    Insect Screen Serviceability  N/A 

    Details of the tested results can be found in Section 7 of this report.  Primary and Secondary Designations are as indicated below: 

      

    Aluminum Casement – Fixed Combination Window Wall System     Class AW – PG45 – Size Tested 2580 x 2615 mm (102 x 103 in) – Type C, FW      Secondary Designator Positive Design Pressure = 2160 Pa (45.1 psf) Negative Design Pressure = 2160 Pa (45.1 psf) Water Penetration Resistance = 730 Pa (15.3 psf) Canadian Air Leakage Resistance = A3  

  • TEST REPORT FOR BRANTEC GLAZING SYSTEMS INC.       Report No.: 103141992COQ‐001A Revision Date: 22‐May‐2019    

    Version (13‐March‐2017)  Page 4 of 42  GFT‐OP‐10b 

     

    SECTION 2 INDEX   

                   

    SECTION NAMES  PAGE

     

    SUMMARY OF RESULTS .................................................................................................................. 3 

    INDEX ........................................................................................................................................... 4 

    OBJECTIVE .................................................................................................................................... 6 

    SAMPLE ASSEMBLY AND DESCRIPTION ............................................................................................ 6 

    TESTING AND EVALUATION METHODS .......................................................................................... 11 OPERATING FORCE ................................................................................................................................. 11 AIR LEAKAGE RESISTANCE ....................................................................................................................... 11 CYCLIC WATER PENETRATION RESISTANCE ............................................................................................... 11 STATIC WATER PENETRATION RESISTANCE .............................................................................................. 11 VENT / SASH / DOOR LEAF CYCLING (FIRST HALF) ..................................................................................... 11 LOCKING HARDWARE CYCLING (FIRST HALF) ............................................................................................ 12 MISUSE TEST.......................................................................................................................................... 12 VENT / SASH / DOOR LEAF CYCLING (SECOND HALF) ................................................................................. 12 LOCKING HARDWARE CYCLING (SECOND HALF) ........................................................................................ 12 OPERATING FORCE #2 ............................................................................................................................ 12 THERMAL CYCLING ................................................................................................................................. 12 UNIFORM LOAD DEFLECTION .................................................................................................................. 12 AIR LEAKAGE RESISTANCE #2 .................................................................................................................. 13 CYCLIC WATER PENETRATION RESISTANCE #2 .......................................................................................... 13 STATIC WATER PENETRATION RESISTANCE #2 .......................................................................................... 13 UNIFORM LOAD STRUCTURAL ................................................................................................................. 13 FORCED ENTRY RESISTANCE .................................................................................................................... 13 SASH VERTICAL DEFLECTION TEST ........................................................................................................... 13 SASH AND HARDWARE LOAD TEST .......................................................................................................... 13 SASH / LEAF TORSION TEST ..................................................................................................................... 14 THERMOPLASTIC CORNER WELD TEST ..................................................................................................... 14 INSECT SCREEN SERVICEABILITY .............................................................................................................. 14 DEVIATION FROM STANDARD METHOD ................................................................................................... 14 

    TEST EQUIPMENT ........................................................................................................................ 14 

    RESULTS AND OBSERVATIONS ...................................................................................................... 15 OPERATING FORCE ................................................................................................................................. 15 AIR LEAKAGE RESISTANCE ....................................................................................................................... 15 CYCLIC WATER PENETRATION RESISTANCE ............................................................................................... 15 STATIC WATER PENETRATION RESISTANCE .............................................................................................. 15 VENT / SASH / DOOR LEAF CYCLING (FIRST HALF) ..................................................................................... 16 

  • TEST REPORT FOR BRANTEC GLAZING SYSTEMS INC.       Report No.: 103141992COQ‐001A Revision Date: 22‐May‐2019    

    Version (13‐March‐2017)  Page 5 of 42  GFT‐OP‐10b 

     

    LOCKING HARDWARE CYCLING (FIRST HALF) ............................................................................................ 16 MISUSE TEST.......................................................................................................................................... 16 VENT / SASH / DOOR LEAF CYCLING (SECOND HALF) ................................................................................. 16 LOCKING HARDWARE CYCLING (SECOND HALF) ........................................................................................ 16 OPERATING FORCE #2 ............................................................................................................................ 16 THERMAL CYCLING ................................................................................................................................. 17 UNIFORM LOAD – DEFLECTION ............................................................................................................... 17 AIR LEAKAGE RESISTANCE #2 .................................................................................................................. 18 CYCLIC WATER PENETRATION RESISTANCE #2 .......................................................................................... 18 STATIC WATER PENETRATION RESISTANCE #2 .......................................................................................... 18 UNIFORM LOAD – STRUCTURAL .............................................................................................................. 18 FORCED ENTRY RESISTANCE .................................................................................................................... 19 SASH VERTICAL DEFLECTION TEST ........................................................................................................... 19 SASH AND HARDWARE LOAD TEST .......................................................................................................... 19 SASH / LEAF TORSION TEST ..................................................................................................................... 19 INSECT SCREEN SERVICEABILITY .............................................................................................................. 19 THERMOPLASTIC CORNER WELD TEST ..................................................................................................... 19 

    CONCLUSION .............................................................................................................................. 20 

    APPENDIX A: DRAWINGS .............................................................................................................. 21 

    APPENDIX B: PHOTOGRAPHS ........................................................................................................ 30 

    APPENDIX C: REVISION TABLE ....................................................................................................... 41  

  • TEST REPORT FOR BRANTEC GLAZING SYSTEMS INC.       Report No.: 103141992COQ‐001A Revision Date: 22‐May‐2019    

    Version (13‐March‐2017)  Page 6 of 42  GFT‐OP‐10b 

     

    SECTION 3 OBJECTIVE  

    Intertek  Testing  Services  NA  Ltd.  (Intertek)  has  conducted  testing  for  Brantec  Glazing  Systems  Inc. (Brantec) on a 2580 mm (101.6”) x 2615 mm (103.0”) Aluminum Casement – Fixed Combination Window Wall System.  Testing was conducted in accordance with following standard / specification: 

    AAMA/WDMA/CSA  101/I.S.2/  A440‐08  “Standard/Specification  for  windows,  doors,  and  unit skylights” (NAFS‐08)  

    A440S1‐09  “Canadian  Supplement  to  AAMA/WDMA/CSA  101/I.S.2/A440,  NAFS  –  North American Fenestration Standard/Specification for windows, doors, and skylights” (A440S1‐09)  

    AAMA/WDMA/CSA  101/I.S.2/  A440‐11  “Standard/Specification  for  windows,  doors,  and  unit skylights” (NAFS‐11)  

    A440S1‐17  “Canadian  Supplement  to  AAMA/WDMA/CSA  101/I.S.2/A440,  NAFS  –  North American Fenestration Standard/Specification for windows, doors, and skylights” (A440S1‐17)    

    This evaluation was started on July 19, 2017 and completed on August 18, 2017.  

     SECTION 4 SAMPLE ASSEMBLY AND DESCRIPTION Manufacturer Information 

    Brantec Glazing Systems Inc. 103 – 8288 North Fraser Way Burnaby, BC   V3N 0E9 Canada 

     Model Name  Aluminum Casement – Fixed Combination Window Wall System 

     Installation  Test Buck:   2x6, #2 & better spf, box w/ 2x12, #2 & better spf, cladding, butt  joints 

    secured with 2x #10 x 4" deck screws.  The 2x12 clad was also butt jointed together with 4x #10  x 4" deck  screws  and  secured  to  the 2x6 with #10  x 3‐1/2"  flat head screws  at  least  at every 305 mm  (12").   The buck was  lined with  a peel  and  stick membrane on the exterior side.    Specimen to Buck:  

    #12  x  2”  tek  screws  are  used  through  the  track  profile,  into  the  buck, oriented parallel to the plane of glass.  7x through each jamb and the head.  Each screw head is sealed with silicone. 

    The  sill  is  installed with  an  aluminum  angle,  approximately  3 mm  (0.12”) thick, 51 mm (2”) wide x 25 mm (1”) tall, the full width of the sample.   11x #10 x 2” Tek screws were used to secure the angle to the test buck.  12x #10 x 3/4"  self‐tapping pan‐head  screws were used  to  secure  the angle  to  the window frame. 

    Silicone was used to seal all joints of the test buck as well as the rough opening of 

  • TEST REPORT FOR BRANTEC GLAZING SYSTEMS INC.       Report No.: 103141992COQ‐001A Revision Date: 22‐May‐2019    

    Version (13‐March‐2017)  Page 7 of 42  GFT‐OP‐10b 

     

    the buck, full perimeter on both the interior and exterior side.  An  aluminum  length of 19 Gauge brakeshape  flashing was used under  the  full 

    width of the sample, approximately 140 mm (5‐1/2”) x 70 mm (2‐3/4”)  

    Size  

    Overall Size:  Width: 2580 mm (101.6”)  Height: 2615 mm (103.0”) 

    Casement Size:  Width: 995 mm (39.2”)  Height: 1595 mm (62.8”) 

    Large Fixed Size:  Width: 1585 mm (62.4”)  Height: 2615 mm (103.0”) 

    Small Fixed Size:  Width: 995 mm (39.2”)  Height: 1020 mm (40.2”) 

     Track  Material: Two‐piece aluminum that snap together, with pour and de‐bridge thermal 

    break by Azon.   One  style  track  assembly  used  along  the  jambs  and  another  style  used  along  the 

    head to support the main frame profile.    The head track contains two lengths of a splined EPDM gasket, see weather‐stripping 

    section for further detail.    

    Main Frame  

    Material:   Aluminum with pour and de‐bridge thermal break by Azon.   2x lengths of styrofoam  rectangle profiles with dimensions of  approximately 13 mm  (1/2”)  x 38 mm (1‐1/2”) used in the jambs, and 24 mm (1”) x 52 mm (2”) used in the head, each adhered to the rough‐opening side of the frame cavity. 

    Corners:  Frame corners are butt joined to the sill, jambs are secured to the sill with the use of 4x #12 x 1‐1/2” lag bolts.  The jambs are secured to the head with the use of two aluminum pieces, a sleeve and an end dam, welded together and slid in to the grooves of either profile, sealed to each profile with silicone. 

    Reinforcement: None  A  splined EPDM gasket  is used on  the exterior‐most and  interior‐most  face of  the 

    jamb profiles, to seal to the track.  The jambs and head are also sealed to the exterior side of the track profile with a cap bead of silicone.    

    Vent Frame  Material: Aluminum with pour and de‐bridge thermal break by Azon. Each profile has 1x  length of styrofoam rectangle profiles with dimensions of approximately 13 mm (1/2”) x 38 mm (1‐1/2”), each adhered to the inside cavity of the profile. 

    Corners: Frame corners are mitre cut and joined with the use of an aluminum corner key.  Corner key is secured in the profile by dimpling the step of the aluminum frame in to the corner key.  Silicone is used around the corner key as well as the inside edge 

  • TEST REPORT FOR BRANTEC GLAZING SYSTEMS INC.       Report No.: 103141992COQ‐001A Revision Date: 22‐May‐2019    

    Version (13‐March‐2017)  Page 8 of 42  GFT‐OP‐10b 

     

    of the mitre joint.   Secured  to  the main‐frame with  the use of #8 x 1‐1/2” pan‐head  screws.   3x used 

    along the head, approximately 127 mm (5”) from either corner, and through the hole of the swing limiter 305 mm (12”) from the hinge side.   2x along the hinge side, 152 mm (6”) and 686 mm (27”) from the bottom.  2x along the locking side, 102 mm (4”) and 533 mm (21”) from the bottom. 

    The vent  frame  is  sealed  to  the main  frame on  the  interior  side with  the use of a hollow bulb gasket as described in the weather‐stripping section, and on the exterior side with a full perimeter of silicone used in the gap between frame profiles.  

    Vertical Mullion 

    One vertical combination mullion  Reinforcement:  None.    Material:   2x aluminum profiles that snap together, each with a pour and de‐bridge 

    thermal break by Azon.   Each profile has 2x  lengths of styrofoam rectangle profiles with dimensions of approximately 13 mm (1/2”) x 38 mm (1‐1/2”), each adhered to the inside cavity of each profile. 

    Silicone  is used  in the  joint where the two profiles snap together, full  length on the exterior and interior side.   

     Horizontal Mullion 

    One horizontal integral mullion  Reinforcement:  None.    Material:  Aluminum with a pour and de‐bridge thermal break by Azon.  Secured to the jamb and intersecting vertical mullion with the use of 4x #12 x 1‐1/2” 

    lag bolts.  Silicone is used at either end connection of the mullion  

     Operable Vent  

    Material:  Interior side is aluminum with a snap‐on polyamide thermal profile on the exterior side of the sash.  

    Corners:  Mitre cut and joined with the use of a corner key. Corner key is secured in the profile by dimpling the step of the aluminum frame in to the corner key.  Silicone is used around the corner key as well as the inside edge of the mitre joint. 

    Sash Size:  Width:  845 mm (33.3")  Height: 1445 mm  (56.9")  

    Locks and Hardware 

    Multi‐point (3‐point) lock system controlled through a lock handle set located at 406 mm (16”) from the bottom inside edge of the sash.  Tie bar with 3 locking points slides in a slot on the outside perimeter of the sash.  Keepers: 3x keepers used on the  locking  jamb of the casement frame, centered 

    approximately 165 mm (6‐1/2”), 705 mm (27‐3/4”) and 1245 mm (49”) from the bottom  inside edge of  the  casement  frame.  Each  keeper  secured with 3x #8  x 5/8" pan‐head screws and sealed to the frame profile with silicone. 

    2x swing limiters are used, one on the top rail and one on the bottom rail of the sash.  

  • TEST REPORT FOR BRANTEC GLAZING SYSTEMS INC.       Report No.: 103141992COQ‐001A Revision Date: 22‐May‐2019    

    Version (13‐March‐2017)  Page 9 of 42  GFT‐OP‐10b 

     

    Secured  to  the sash with 3x #8 x 5/8” pan‐head screws.   Secured  to  the horizontal mullion of the frame with 4 x #8 x 5/8” pan‐head screws, and secured to the head of the  frame with 3x #8 x 5/8” pan‐head  screws and 1x #8 x 1‐1/2” pan‐head  screws which is also used to secure the casement frame in to the main‐frame.  Silicone was used between the swing limiter and the frame profile.    

    One  continuous hinge assembly was used along  the entire hinge  stile of  the  sash.  Secured to each the sash and the frame with 21x #8 x 3/4" flat‐head screws. 

    2x  sash alignment blocks with a  roller used on  the horizontal mullion of  the  sash.  Centered  approximately  133  mm  (5‐1/4”)  from  the  inside  edge  of  the  latching corner, and 197 mm (7‐3/4”) from the inside edge of the hinge corner.  Each secured to the frame with 2x #8 x 3/4” flat‐head screws.   Silicone  is used between the sash alignment blocks and  the  frame profile. 2x  stainless  steel  slides are  secured  to  the bottom of the sash, for the alignment blocks to slide on.  Each secured to the bottom rail of the sash with 2x #8 x 5/8” pan‐head screws.  

    Drainage  6mm  (0.24”)  diameter  drain  holes  in  various  locations  are  drilled  in  to  the main frame  jamb  profiles  and  vertical  mullion  profiles,  to  provide  drainage  down  the jambs and mullion.   1x  in each  jamb and  vertical mullion profile, aligned with  the lowest point of the top of the horizontal mullion, as well as 1x at the bottom of the exterior‐most cavity of  the horizontal mullion profile.   1x  in each  jamb and vertical mullion profile, aligned with the bottom of the cavity for the head main‐frame profile on each the interior and exterior side.    1x in each jamb and vertical mullion profile, aligned with the lowest point of the top of the sill, as well as 1x at the bottom of the exterior‐most cavity of the sill profile. 

    4x 25 mm (1”) wide slots were cut from the exterior side of the silicone between the sill flashing and sill profile to allow for drainage out from the bottom of the jamb and vertical mullion  profiles,  centered  approximately  89 mm  (3.50”)  from  the  outside edge of jamb or mullion profile.   

     Weather‐strip  The sash has an EPDM hollow bulb seal along the top and bottom rail and  latching 

    stile, around the exterior‐most edge, kerf inserted. Applied as 1 strip, turned around the corners. 

    The sash has an EPDM fin seal used, at the mid‐step on the outside perimeter of the sash inserted into a T‐slot.  Applied as 4 strips with the corners over‐lapped.  

    The  Casement  frame  has  2x  full  perimeters  of  interior  facing  EPDM  hollow  bulb gasket.  One full perimeter on the interior‐most surface is to seal the casement frame to the main‐frame.  A second full perimeter used to seal against the casement sash.  Corners are mitre cut and sealed with silicone.    

    The  mainframe  jamb  profiles  have  2x  lengths  of  EPDM  splined  gaskets  on  the exterior‐most and the interior‐most of the profile, to seal against the jamb tracks 

    The two‐piece head track has an EPDM gasket used on each piece.  The exterior side has an  interior  facing spline gasket.   The  interior side has an exterior  facing hollow bulb gasket. 

  • TEST REPORT FOR BRANTEC GLAZING SYSTEMS INC.       Report No.: 103141992COQ‐001A Revision Date: 22‐May‐2019    

    Version (13‐March‐2017)  Page 10 of 42  GFT‐OP‐10b 

     

    Fixed Glazing  

    IGU specification:  6  mm  /  6  mm  clear  annealed  with  a  12  mm  Stainless  Steel  Spacer,  sealed 

    together using hot melt butyl.    Overall thickness, 24 mm (~1") 

    Laid‐in,  interior glazed on top of a full perimeter of black butyl tape, approximately 10 mm (0.38”) x 3 mm (0.12”).  Silicone is used around the outside of the glazing tape perimeter at  the corners, extending approximately 150 mm  (5.9”) away  from each corner. 

    A white foam backer rod approximately 10 mm (3/8”) diameter was used around the entire glass unit, and a full perimeter silicone bead was applied on the interior side of the backer rod.   

    Glazing Blocks: 2x 6 mm (0.24”) x 102 mm (4.00”) x 22 mm (0.87”) neoprene setting blocks used.  Used under the glass, centered approximately 229 mm (9”) from either inside corner. 

    Glazing Stops:  Aluminum with an EPDM glazing gasket.  

    Casement Glazing  

    IGU specification:  6 mm  /  6  mm  clear  tempered  with  a  12 mm  Stainless  Steel  Spacer,  sealed 

    together using hot melt butyl.    Overall thickness, 24 mm (~1") 

    Laid‐in, exterior glazed on top of a full perimeter of glazing silicone and a black closed cell foam gasket, approximately 11 mm (0.43”) x 6 mm (0.25”). 

    A white foam backer rod approximately 10 mm (3/8”) diameter was used around the entire glass unit, and a full perimeter silicone bead was applied on the exterior side of the backer rod, flush with the exterior face of the glass unit.   

    Glazing Blocks: 2x 6 mm (0.24”) x 52 mm (2.00”) x 22 mm (0.87”) neoprene setting blocks used.  Used under the glass unit, adjacent to either side stile.   

    Glazing Stops:  None  

    Drawings  Copy of drawings supplied by Brantec Glazing Systems Inc. included in Appendix A.  

       

      

                         

  • TEST REPORT FOR BRANTEC GLAZING SYSTEMS INC.       Report No.: 103141992COQ‐001A Revision Date: 22‐May‐2019    

    Version (13‐March‐2017)  Page 11 of 42  GFT‐OP‐10b 

     

    SECTION 5 TESTING AND EVALUATION METHODS  OPERATING FORCE The  Operating  Force  Test  was  performed  on  the  sash  and  latch  in  accordance  with  ASTM  E2068‐00(2016).  The forces required initiate motion of the operable panel from both the fully open and fully closed positions, as well as the force required to maintain motion to the opposite limits of travel, were measured. The forces required to open and close the latches were also recorded.  AIR LEAKAGE RESISTANCE The Air Leakage Resistance Test was performed in accordance with ASTM E283‐04(2012), “Standard Test Method for Determining Rate of Air Leakage Through Exterior Windows, Curtain Walls, and Doors Under Specified  Pressure  Differences  Across  the  Specimen”.    Air  infiltration  and  exfiltration  tests  were performed using test pressures of 300 Pa (6.27 psf). The maximum air  leakage rate was calculated and compared to the allowable air leakage.  CYCLIC WATER PENETRATION RESISTANCE The Cyclic Water Penetration Resistance Test was performed  in accordance with ASTM E547‐00(2016) “Standard Test Method for Water Penetration of Exterior Windows, Skylights, Doors, and Curtain Walls by  Cyclic  Static  Air  Pressure  Difference”  (ASTM  E547).    The  test was  performed  using  the  specified pressure differential and a water  spray  rate of at  least 204  L/m2 per hour  (5.0 U.S. gal/ft2 per hour).  Each  cycle  consisted  of  five minutes  with  the  pressure  applied  and  one minute  with  the  pressure released, during which the water spray was continuously applied.  STATIC WATER PENETRATION RESISTANCE The Static Water Penetration Resistance Test was performed  in accordance with ASTM E331‐00(2016) “Standard Test Method for Water Penetration of Exterior Windows, Skylights, Doors, and Curtain Walls by Uniform Static Air Pressure Difference”  (ASTM E331).   The  test was performed using  the  specified pressure differential and a water  spray  rate of at  least 204  L/m2 per hour  (5.0 U.S. gal/ft2 per hour).  Duration of the test was 15 minutes, during which the water spray and air pressure was continuously applied.     VENT / SASH / DOOR LEAF CYCLING (FIRST HALF) The Vent / Sash / Door Leaf Cycling Test was performed  in accordance with AAMA 910‐16 “Voluntary “Life Cycle”  Specifications  and  Test Methods  for AW Class Architectural Windows and Doors”  (AAMA 910).  The Vent / Sash / Door Leaf was opened to at least 90° or the extent of its travel and then back to closed.  This was performed for 2000 cycles where one cycle is considered the single action of open then close.   

  • TEST REPORT FOR BRANTEC GLAZING SYSTEMS INC.       Report No.: 103141992COQ‐001A Revision Date: 22‐May‐2019    

    Version (13‐March‐2017)  Page 12 of 42  GFT‐OP‐10b 

     

    LOCKING HARDWARE CYCLING (FIRST HALF) The Locking Hardware Cycling Test was performed  in accordance with AAMA 910.   Each of the  locking hardware on the test specimen was operated for 2000 cycles where one cycle  is considered the single action of ‘lock’ then ‘unlock’ positions.     MISUSE TEST  The Misuse test was performed in accordance with Section 3.6 of AAMA 910.   VENT / SASH / DOOR LEAF CYCLING (SECOND HALF) The Vent / Sash / Door Leaf Cycling Test was performed in accordance with AAMA 910.  The second half of this test was performed for 2000 cycles.   LOCKING HARDWARE CYCLING (SECOND HALF) The Locking Hardware Cycling Test was performed  in accordance with AAMA 910.   The second half of this test was performed for 2000 cycles..  OPERATING FORCE #2 The Operating Force Test was  repeated at  the conclusion of  the  second half of  the  locking hardware cycling.    THERMAL CYCLING The  Thermal  Cycling  Test was  performed  in  general  accordance with AAMA  501.5  “Test Method  for Thermal Cycling of Exterior Walls” following the cycle and temperature requirements  in Section 3.7 of AAMA 910.  The test consisted of six cycles of hot, 82°C (180°F) and cold, ‐18°C (0°F).    UNIFORM LOAD DEFLECTION The Uniform Load Deflection tests were conducted in accordance with ASTM E330/E330M‐14 “Standard Test Method  for  Structural  Performance  of  Exterior Windows,  Skylights,  Doors  and  Curtain Walls  by Uniform Static Air Pressure Difference”  (ASTM E330), Procedure A.   The  tests were performed  in both the positive and negative directions.   After a 10 second preload  (50% of  the  test  load),  followed by 1 minute with the pressure released, the tests were conducted at the specified test pressure for a period of 10 seconds.  Deflections were measured at the mid‐span and at the ends.  The end deflections were averaged and subtracted from the mid‐span deflection (to eliminate deflections caused by movement at the ends of the structural supporting members).   Polyethylene film was used during the positive wind pressure sequences. 

  • TEST REPORT FOR BRANTEC GLAZING SYSTEMS INC.       Report No.: 103141992COQ‐001A Revision Date: 22‐May‐2019    

    Version (13‐March‐2017)  Page 13 of 42  GFT‐OP‐10b 

     

    AIR LEAKAGE RESISTANCE #2 The Air Leakage Resistance test was repeated.  CYCLIC WATER PENETRATION RESISTANCE #2 The Cyclic Water Penetration Resistance test was repeated.  STATIC WATER PENETRATION RESISTANCE #2 The Static Water Penetration Resistance test was repeated.     UNIFORM LOAD STRUCTURAL The Uniform Load Structural tests were conducted in accordance with ASTM E330/E330M‐14 “Standard Test Method  for  Structural  Performance  of  Exterior Windows,  Skylights,  Doors  and  Curtain Walls  by Uniform Static Air Pressure Difference” (ASTM E330), Procedure A.   After a 10 second preload (50% of test  load),  followed by 1 minute with  the pressure  released,  the  sample was  subjected  to a Uniform Load Structural test using a specified test pressure for a time of 10 seconds. The test was performed in both the positive and negative directions. After the test loads were released, the permanent deflections were recorded and the specimen was inspected for failure or permanent deformation of any part of the system that would cause any operational malfunction.   Polyethylene film was used during the positive wind pressure sequences.  FORCED ENTRY RESISTANCE The  Forced‐entry  Resistance  Test was  conducted  in  accordance with  ASTM  F588‐14  “Standard  Test Methods for Measuring the Forced Entry Resistance of Window Assemblies, Excluding Glazing  Impact”. This included the Disassembly, Sash Manipulation, Lock Hardware Manipulation, and Assembly Tests.  SASH VERTICAL DEFLECTION TEST The Sash Vertical Deflection Test was performed  in accordance with Section 5.3.6.4.3 of NAFS‐08 and Section 9.3.6.4.2 of NAFS‐11.  After the test load was released, the specimen was inspected for failure or permanent deformation of any part of the system that would cause any operational malfunction.  SASH AND HARDWARE LOAD TEST The Sash and Hardware Load (distributed load) Test was performed in accordance with Section 5.3.6.6.2 of  NAFS‐08  and  Section  9.3.6.5.2  of  NAFS‐11.    After  the  test  load was  released,  the  specimen was inspected  for  failure  or  permanent  deformation  of  any  part  of  the  system  that  would  cause  any operational malfunction. 

  • TEST REPORT FOR BRANTEC GLAZING SYSTEMS INC.       Report No.: 103141992COQ‐001A Revision Date: 22‐May‐2019    

    Version (13‐March‐2017)  Page 14 of 42  GFT‐OP‐10b 

     

    SASH / LEAF TORSION TEST The Sash / Leaf Torsion Test was performed in accordance with Section 5.3.6.4.2 of NAFS‐08 and Section 7.3.4.2  of  NAFS‐11.    After  the  test  load  was  released,  the  specimen  was  inspected  for  failure  or permanent deformation of any part of the system that would cause any operational malfunction.  THERMOPLASTIC CORNER WELD TEST Test not applicable  INSECT SCREEN SERVICEABILITY Test not applicable.  DEVIATION FROM STANDARD METHOD There were no noted deviations from the test standards used in the evaluation reported herein.    SECTION 6 TEST EQUIPMENT Equipment used during testing is listed as follows: 

    Test  Equipment  Intertek ID# 

    Air Leakage Resistance, 

    Water Penetration Resistance, and 

    Uniform Load Deflection / Structural 

    Fenestration Testing Control Unit  60650 

    Water spray assembly 60651 

    60652 

    20” Line Gauge 

    60673 

    64928 

    64926 

    64923 

    64920 

    64922 

    Forced‐entry Resistance 

    5000 lbs Load Cell  P60691 

    1000 lbs Load Cell P60688 

    P60689 

    200 lbs Load Cell  P60687 

    Sash Vertical Deflection Test and  

    Sash / Leaf Torsion Test 

    Digital Force Gauge  D2710 

    Mitutoyo Digital Deflection Gauge  P60175 

    Sash and Hardware Load Test   Digital Force Gauge  D2710 

     

  • TEST REPORT FOR BRANTEC GLAZING SYSTEMS INC.       Report No.: 103141992COQ‐001A Revision Date: 22‐May‐2019    

    Version (13‐March‐2017)  Page 15 of 42  GFT‐OP‐10b 

     

    SECTION 7 RESULTS AND OBSERVATIONS  OPERATING FORCE The forces required to operate the system: 

    Initiate Opening:  107.6 N (24.2 lbs)  Initiate Closing:  32.8 N (7.4 lbs) Maintain Opening:  48.6 N (10.9 lbs)  Maintain Closing:   110.6 N (24.9 lbs) Latch Opening:  86.4 N (19.4 lbs)  Latch Closing:  91.6 N (20.6 lbs) 

    Maximum allowable force to initiate motion:   155 N (34.9 lbs)   Maximum allowable force to maintain motion:  135 N (30.4 lbs) Maximum allowable force to open and close latch:  100 N (22.5 lbs) The tested specimen met the performance requirements of NAFS‐08, NAFS‐11, A440S1‐09 and A440S1‐17 for Operating Force.  AIR LEAKAGE RESISTANCE Air test data is indicated in the following table: 

    Property  Area m2 (ft2) Infiltration Rate L/s*m2 (cfm/ft2) 

    Exfiltration Rate L/s*m2 (cfm/ft2) 

    Compliance US (CAN) 

    Overall Assembly @ 300 Pa  6.75 (72.62)  0.01 (0.00)  0.05 (0.01)  Pass (A3) Casement @ 300 Pa  1.59 (17.08)  0.00 (0.00)  0.01 (0.00)  Pass (A3) Overall Fixed @ 300 Pa  5.16 (55.54)  0.01 (0.00)  0.06 (0.01)  Pass (Fixed) 

    Allowable Leakage Rates Maximum allowable air leakage rate (US):  1.5 L/s*m2, 0.3 cfm/ft2 Maximum allowable air leakage rate (CAN – A3):  0.5 L/s*m2, 0.1 cfm/ft2 Maximum allowable air leakage rate (CAN – Fixed):  0.1 L/s*m2, 0.05 cfm/ft2 

    The overall system met the US and Canadian performance requirements as reported above when evaluated under NAFS‐08, NAFS‐11, A440S1‐09 and A440S1‐17.  CYCLIC WATER PENETRATION RESISTANCE During the 24‐minute test period, using a pressure differential of 730 Pa (15.3 psf), there was no water leakage  observed.    The  system  met  the  (CAN)  PG100  Water  Penetration  Resistance  performance requirements under NAFS‐08, NAFS‐11, A440S1‐09 and A440S1‐17.  STATIC WATER PENETRATION RESISTANCE During the 15‐minute test period, using a pressure differential of 730 Pa (15.3 psf), there was no water leakage  observed.    The  system  met  the  (CAN)  PG100  Water  Penetration  Resistance  performance requirements under NAFS‐08, NAFS‐11, A440S1‐09 and A440S1‐17.  

  • TEST REPORT FOR BRANTEC GLAZING SYSTEMS INC.       Report No.: 103141992COQ‐001A Revision Date: 22‐May‐2019    

    Version (13‐March‐2017)  Page 16 of 42  GFT‐OP‐10b 

     

    VENT / SASH / DOOR LEAF CYCLING (FIRST HALF) After 2000 cycles, there was found to be no failure or permanent deformation to the system that would cause any operational malfunction.  The system met the Vent / Cycling / Door Leaf Cycling performance requirements of AAMA 910.   LOCKING HARDWARE CYCLING (FIRST HALF) After 2000 cycles, there was found to be no failure or permanent deformation to the system that would cause  any  operational  malfunction.    The  system  met  the  Locking  Hardware  Cycling  performance requirements of AAMA 910.   MISUSE TEST  After  the  loads were  removed,  there was  found  to  be  no  failure  or  permanent  deformation  to  the system  that would cause any operational malfunction.   The system met  the Misuse  test performance requirements of AAMA 910.  VENT / SASH / DOOR LEAF CYCLING (SECOND HALF) After 2000 cycles, there was found to be no failure or permanent deformation to the system that would cause any operational malfunction.  The system met the Vent / Cycling / Door Leaf Cycling performance requirements of AAMA 910.   LOCKING HARDWARE CYCLING (SECOND HALF) After 2000 cycles, there was found to be no failure or permanent deformation to the system that would cause  any  operational  malfunction.    The  system  met  the  Locking  Hardware  Cycling  performance requirements of AAMA 910.   OPERATING FORCE #2 The forces required to operate the system: 

    Initiate Opening:  118.0 N (26.5 lbs)  Initiate Closing:  6.4 N (1.4 lbs) Maintain Opening:  12.8 N (2.9 lbs)  Maintain Closing:   90.8 N (20.4 lbs) Latch Opening:  12.6 N (2.8 lbs)  Latch Closing:  13.8 N (3.1 lbs) 

    Maximum allowable force to initiate motion:   155 N (34.9 lbs)   Maximum allowable force to maintain motion:  135 N (30.4 lbs) Maximum allowable force to open and close latch:  100 N (22.5 lbs) The tested specimen met the performance requirements of NAFS‐08, NAFS‐11, A440S1‐09 and A440S1‐17 for Operating Force. 

  • TEST REPORT FOR BRANTEC GLAZING SYSTEMS INC.       Report No.: 103141992COQ‐001A Revision Date: 22‐May‐2019    

    Version (13‐March‐2017)  Page 17 of 42  GFT‐OP‐10b 

     

    THERMAL CYCLING 

    No. of Cycles  Exterior Conditions  Interior Conditions Hot Temperature  Cold Temperature 6  82°C (180°F)  ‐18°C (0°F)  24°C (74°F) 

    Upon completion of  the  thermal cycling,  there was  found  to be no  failure or permanent deformation due to the expansion and contraction of the system that would cause any operational malfunction.  The system met the Thermal Cycling performance requirements of AAMA 501.5 and AAMA 910.    UNIFORM LOAD – DEFLECTION  Operable sash Uniform Load Deflection data: 

    Test Pressure, Pa (psf) 

    Deflection Measurements, mm (in.) 

    Compliance Positive  Negative 

    Deflection  Residual  Deflection  Residual 

    2160 (45.1)  4.66 (0.18)  0.85 (0.03)  4.18 (0.16)  1.33 (0.05)  Pass DP45 

    Lock rail span, L = 1410 mm (55.51")  Deflection limit, L/175 = 8.06 mm (0.32”) Mullion Uniform Load Deflection data: 

    Test Pressure, Pa (psf) 

    Deflection Measurements, mm (in.) 

    Compliance Positive  Negative 

    Deflection  Residual  Deflection  Residual 

    2160 (45.1)  12.27 (0.48)  1.43 (0.06)  13.68 (0.54)  2.40 (0.09)  Pass DP45 

    Vert. Mullion span, L = 2530 mm (99.61")  Deflection limit, L/175 = 14.46 mm (0.57”) 

    After the test loads were released, the specimen was inspected and there was found to be no failure or permanent deformation of any part of the system that would cause any operational malfunction.   The system met the DP45 Uniform Load Deflection performance requirements under NAFS‐08 and NAFS‐11.  

  • TEST REPORT FOR BRANTEC GLAZING SYSTEMS INC.       Report No.: 103141992COQ‐001A Revision Date: 22‐May‐2019    

    Version (13‐March‐2017)  Page 18 of 42  GFT‐OP‐10b 

     

    AIR LEAKAGE RESISTANCE #2 Air test data is indicated in the following table: 

    Property  Area m2 (ft2) Infiltration Rate L/s*m2 (cfm/ft2) 

    Exfiltration Rate L/s*m2 (cfm/ft2) 

    Compliance US (CAN) 

    Overall Assembly @ 300 Pa  6.75 (72.62)  0.01 (0.00)  0.23 (0.05)  Pass (A3) Casement @ 300 Pa  1.59 (17.08)  0.04 (0.01)  0.15 (0.03)  Pass (A3) Overall Fixed @ 300 Pa  5.16 (55.54)  0.00 (0.00)  0.02 (0.00)  Pass (Fixed) 

    Allowable Leakage Rates Maximum allowable air leakage rate (US):  1.5 L/s*m2, 0.3 cfm/ft2 Maximum allowable air leakage rate (CAN – A3):  0.5 L/s*m2, 0.1 cfm/ft2 Maximum allowable air leakage rate (CAN – Fixed):  0.1 L/s*m2, 0.05 cfm/ft2 

    The overall system met the US and Canadian performance requirements as reported above when evaluated under NAFS‐08, NAFS‐11, A440S1‐09 and A440S1‐17.  CYCLIC WATER PENETRATION RESISTANCE #2 During the 24‐minute test period, using a pressure differential of 730 Pa (15.3 psf), there was no water leakage  observed.    The  system  met  the  (CAN)  PG100  Water  Penetration  Resistance  performance requirements under NAFS‐08, NAFS‐11, A440S1‐09 and A440S1‐17.  STATIC WATER PENETRATION RESISTANCE #2 During the 15‐minute test period, using a pressure differential of 730 Pa (15.3 psf), there was no water leakage  observed.    The  system  met  the  (CAN)  PG100  Water  Penetration  Resistance  performance requirements under NAFS‐08, NAFS‐11, A440S1‐09 and A440S1‐17.  UNIFORM LOAD – STRUCTURAL  Operable sash Uniform Load Deflection data: 

    Test Pressure, Pa (psf) 

    Residual Deflection Measurements, mm (in.) Compliance 

    Positive  Negative 3240 (67.7)  1.30 (0.05)  2.16 (0.09)  Pass DP45 

    Lock rail span, L = 1410 mm (55.51")  Residual deflection limit, L*0.2% = 2.82 mm (0.11") Mullion Uniform Load Deflection data: 

    Test Pressure, Pa (psf) 

    Residual Deflection Measurements, mm (in.) Compliance 

    Positive  Negative 3240 (67.7)  2.66 (0.10)  3.50 (0.14)  Pass DP45 Vert. Mullion span, L = 2530 mm (99.61")  Residual deflection limit, L*0.2% = 5.06 mm (0.20") 

    After the test loads were released, the specimen was inspected and there was found to be no failure or permanent  deformation  of  any  part  of  the  window  system  that  would  cause  any  operational malfunction.  The system met the overall DP45 Uniform Load performance requirements under NAFS‐08 and NAFS‐11.  

  • TEST REPORT FOR BRANTEC GLAZING SYSTEMS INC.       Report No.: 103141992COQ‐001A Revision Date: 22‐May‐2019    

    Version (13‐March‐2017)  Page 19 of 42  GFT‐OP‐10b 

     

    FORCED ENTRY RESISTANCE Attempts  to  gain  entry  by  opening  the  glazing  panel,  in  accordance with  the Disassembly  and  Sash Manipulation  tests  for a Type B assembly, were unsuccessful.   The  system met  the Grade 20 Forced‐entry Resistance performance requirements of NAFS‐08 and NAFS‐11.  SASH VERTICAL DEFLECTION TEST 

    Test Load  Max. Deflection  Max. Allowable Deflection 270 N (61 lbs)  1.52 mm (0.06”)  16.90 mm (0.67”) 

    After the test load was released the specimen was inspected for failure or permanent deformation that would  impair with  the  operation  of  the  system.    The  system met  the  performance  requirements  of NAFS‐08 and NAFS‐11 for the Sash Vertical Deflection test.  SASH AND HARDWARE LOAD TEST After the test load was released it was found that the hardware was strong enough to support the 300 Pa (6.3 psf) load over the 10 second period.  The system met the performance requirements of NAFS‐08 and NAFS‐11 for the Sash and Hardware Load Test.  SASH / LEAF TORSION TEST 

    Test Load  Max. Deflection  Max. Allowable Deflection 90 N (20 lbs)  8.25 mm (0.32”)  62.52 mm (2.46”) 

    After the test load was released the specimen was inspected for failure or permanent deformation that would  impair with  the  operation  of  the  system.    The  system met  the  performance  requirements  of NAFS‐08 and NAFS‐11 for the Sash/Leaf Torsion Test.  INSECT SCREEN SERVICEABILITY Test not applicable.  THERMOPLASTIC CORNER WELD TEST Test not applicable.   

  • TEST REPORT FOR BRANTEC GLAZING SYSTEMS INC.       Report No.: 103141992COQ‐001A Revision Date: 22‐May‐2019    

    Version (13‐March‐2017)  Page 20 of 42  GFT‐OP‐10b 

     

    SECTION 8 CONCLUSION  

    The Aluminum Casement – Fixed Combination Window Wall System, submitted by Brantec Glazing Systems Inc.,  tested and described within  this  report, achieved  the overall performance  requirements of Class AW – PG45 when tested in accordance with NAFS‐08, NAFS‐11, A440S1‐09 and A440S1‐17. 

  • TEST REPORT FOR BRANTEC GLAZING SYSTEMS INC.       Report No.: 103141992COQ‐001A Revision Date: 22‐May‐2019    

    Version (13‐March‐2017)  Page 21 of 42  GFT‐OP‐10b 

                   SECTION 9 APPENDIX A: DRAWINGS (8 Pages) 

  • TEST REPORT FOR BRANTEC GLAZING SYSTEMS INC.       Report No.: 103141992COQ‐001A Revision Date: 22‐May‐2019    

    Version (13‐March‐2017)  Page 30 of 42  GFT‐OP‐10b 

                   SECTION 10 APPENDIX B: PHOTOGRAPHS (10 Pages) 

  • TEST REPORT FOR BRANTEC GLAZING SYSTEMS INC.       Report No.: 103141992COQ‐001A Revision Date: 22‐May‐2019    

    Version (13‐March‐2017)  Page 31 of 42  GFT‐OP‐10b 

     Aluminum Casement – Fixed Combination Window Wall System – Exterior 

     

     Aluminum Casement – Fixed Combination Window Wall System ‐ Interior 

     

  • TEST REPORT FOR BRANTEC GLAZING SYSTEMS INC.       Report No.: 103141992COQ‐001A Revision Date: 22‐May‐2019    

    Version (13‐March‐2017)  Page 32 of 42  GFT‐OP‐10b 

     

     Track Assembly – Jambs 

     

     Main‐Frame Assembly – Jambs 

     

     Main‐Frame Assembly ‐ Sill 

     

  • TEST REPORT FOR BRANTEC GLAZING SYSTEMS INC.       Report No.: 103141992COQ‐001A Revision Date: 22‐May‐2019    

    Version (13‐March‐2017)  Page 33 of 42  GFT‐OP‐10b 

     Track Assembly – Head 

     

     Main‐Frame Assembly ‐ Head 

     

     Sash Stile/Rail Assembly 

  • TEST REPORT FOR BRANTEC GLAZING SYSTEMS INC.       Report No.: 103141992COQ‐001A Revision Date: 22‐May‐2019    

    Version (13‐March‐2017)  Page 34 of 42  GFT‐OP‐10b 

     

     

     Vertical Mullion Assembly – Coupler 

     

     Horizontal Integral Mullion Assembly 

     

  • TEST REPORT FOR BRANTEC GLAZING SYSTEMS INC.       Report No.: 103141992COQ‐001A Revision Date: 22‐May‐2019    

    Version (13‐March‐2017)  Page 35 of 42  GFT‐OP‐10b 

     Aluminum, Fixed Glazing Stop 

     

     Splined Main‐frame/Track Gasket  

     

     Glazing Gasket 

     

  • TEST REPORT FOR BRANTEC GLAZING SYSTEMS INC.       Report No.: 103141992COQ‐001A Revision Date: 22‐May‐2019    

    Version (13‐March‐2017)  Page 36 of 42  GFT‐OP‐10b 

     Vent Weather‐stripping profiles 

     

     Vent Frame Weather‐stripping 

     

     Sleeve and End Dam at Corners of Head 

  • TEST REPORT FOR BRANTEC GLAZING SYSTEMS INC.       Report No.: 103141992COQ‐001A Revision Date: 22‐May‐2019    

    Version (13‐March‐2017)  Page 37 of 42  GFT‐OP‐10b 

     Drainage Through Silicone at Sill 

     

     Locking Handle 

  • TEST REPORT FOR BRANTEC GLAZING SYSTEMS INC.       Report No.: 103141992COQ‐001A Revision Date: 22‐May‐2019    

    Version (13‐March‐2017)  Page 38 of 42  GFT‐OP‐10b 

     Locking Assembly 

     

     Strike Plate 

     

     Sash Alignment Block on Frame 

  • TEST REPORT FOR BRANTEC GLAZING SYSTEMS INC.       Report No.: 103141992COQ‐001A Revision Date: 22‐May‐2019    

    Version (13‐March‐2017)  Page 39 of 42  GFT‐OP‐10b 

     

     Sash Alignment Slide on Bottom Rail 

     

     Swing Limiter 

     

     Hinge Assembly 

  • TEST REPORT FOR BRANTEC GLAZING SYSTEMS INC.       Report No.: 103141992COQ‐001A Revision Date: 22‐May‐2019    

    Version (13‐March‐2017)  Page 40 of 42  GFT‐OP‐10b 

     

     Vent Bulb Weather‐stripping 

     

     Vent Fin Seal Weather‐stripping 

     

  • TEST REPORT FOR BRANTEC GLAZING SYSTEMS INC.       Report No.: 103141992COQ‐001A Revision Date: 22‐May‐2019    

    Version (13‐March‐2017)  Page 41 of 42  GFT‐OP‐10b 

     

     

     

     

     

     

     

     

     

     

    SECTION 11 APPENDIX C: REVISION TABLE (1 Page) 

  • TEST REPORT FOR BRANTEC GLAZING SYSTEMS INC.       Report No.: 103141992COQ‐001A Revision Date: 22‐May‐2019    

    Version (13‐March‐2017)  Page 42 of 42  GFT‐OP‐10b 

      

    Revision Table 

    Date  Section  Description  Technician  Reviewer 

    22‐Sept‐2017  ‐‐‐  Original Issue Date  ‐‐‐  ‐‐‐ 

    22‐May‐2019 

    General Updated company name from CBM Windows II Inc. to Brantec Glazing Systems Inc. 

       Cover Page  Added ‘Test Report Issued To’ 

    4  ‘Manufacturer Information’ updated