FACP FSCU VS WF FAA DH 2 E4.2 F FIRE ALARM PULL STATION. WALL MOUNTED 46" ABOVE FLOOR. FIRE ALARM SIGNAL, SPEAKER AND FLASHING LIGHT, 6'-8" AFF. FIRE ALARM STROBE LIGHT, 6'-8" IN. MOUNTING HEIGHT. FIRE ALARM CONNECTION, HOOD EXTINGUISHING SYSTEM, SEE MECHANICAL DRAWINGS FOR LOCATION. INTERLOCK WITH SHUNT TRIP BREAKERS FOR EQUIPMENT UNDER HOOD. FIRE ALARM REMOTE LCD ANNUNCIATOR PANEL. FLUSH RECESSED WALL MOUNTED. FIRE ALARM DOOR HOLDER, WALL MOUNTED, CONSULT ARCHITECTURAL DRAWINGS TO DETERMINE TYPE REQUIRED. PROVIDE POWER FROM NEAREST RECEPTACLE CIRCUIT AND CONNECT TO FIRE ALARM SYSTEM. TAMPER SWITCH, FURNISHED AND INSTALLED WITH SPRINKLER SYSTEM. INTERLOCK WITH FIRE ALARM SYSTEM BY ELECTRICAL. FLOW SWITCH, FURNISHED AND INSTALLED WITH SPRINKLER SYSTEM. INTERLOCK WITH FIRE ALARM SYSTEM BY ELECTRICAL. FIRE ALARM SMOKE DETECTOR, CEILING MOUNTED. FIRE ALARM DUCT SMOKE DETECTOR LOCATED IN HVAC DUCT. FIRE ALARM CONTROL PANEL, FLUSH RECESSED WALL MOUNTED. FIRE ALARM SIGNAL, HORN. 6 FT.-8 IN. MOUNTING HEIGHT. FIRE ALARM HEAT DETECTOR, 135 DEG, OPERATION. P WEATHER PROOF. FIRE ALARM STROBE LIGHT, CEILING MOUNTED. S M FIRE ALARM: H S WP IC AD AC S 2. COORDINATE MOUNTING HEIGHTS, DEVICE LOCATIONS & POWER/CONTROL REQUIREMENTS WITH ARCHITECTURAL DRAWINGS AND SYSTEM INSTALLER. INTRUSION DETECTION SYSTEM: CONDUIT SLEEVE: NUMBER & SIZE, (2)-2" FOR ALL CLASSROOMS, (1)-2" FOR ALL OFFICES, UNO CABLE TRAY: SIZE AS INDICATED, 18"W x 4"H TYP. INTERCOM SPEAKER: WEATHERPROOF WALL MOUNTED AT 96"AFF. MICROPHONE JACK: WALL MOUNTED AT 18" AFF, UNO. ENHANCED STAFF PHONE: WALL MOUNTED 48" AFF ADMINISTRATIVE DISPLAY PHONE: WALL MOUNT AT 48" AFF INTRUSION SYSTEM: KEY-PAD, MOUNT 48"AFF SECURITY ACCESS: MOUNT ABOVE CEILING AT ENTRY WAY INTRUSION DETECTION DEVICE: WALL MTD. ACCESS CONTROL SYSTEMS SEE DETAIL 1/T0.0 FOR POWER, POWER DISCONNECT, LOW VOLTAGE CABLING, BOXES AND CONDUIT REQUIREMENTS. REFER TO ARCHITECTURAL PLANS AND DOOR SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS. INTERCOM SPEAKER: 2' X 2' SQUARE CEILING MOUNTED COORDINATE MOUNTING HEIGHTS, DEVICE LOCATIONS & POWER/CONTROL REQUIREMENTS WITH ARCHITECTURAL DRAWINGS AND SYSTEM INSTALLER. SPEAKER SYSTEM: CABLING COMPONENTS: THE CONTRACTOR SHALL PROVIDE ROUGH-IN FOR ALL DEVICES AND WIRING. ROUGH-IN REQUIREMENTS ARE SPECIFIED IN SECTION 261010. VERIFY ADJACENCY TO CORRESPONDING POWER RECEPTACLES. OTHER DEVICES WHOSE LOCATIONS ARE NOT DEPENDENT ON RECEPTACLE PLACEMENT SHALL BE COORDINATED WITH SYSTEM INSTALLER. WALL MTD. TELECOMMUNICATION JUNCTION BOX AND CONDUIT ROUGH-IN TO NEAREST ACCESSIBLE CEILING CEILING MTD. TELECOMMUNICATION JUNCTION BOX WALL MTD. TELECOMMUNICATION JUNCTION BOX AND CONDUIT ROUGH-IN TO NEAREST ACCESSIBLE CEILING CEILING MTD. TELECOMMUNICATION JUNCTION BOX AND CONDUIT ROUGH-IN TO NEAREST ACCESSIBLE CEILING CEILING MTD. TELECOMMUNICATION JUNCTION BOX AND CONDUIT ROUGH-IN TO NEAREST ACCESSIBLE CEILING ROUGH-IN FOR LOW VOLTAGE SYSTEMS: SA K P J J O S O S OS W HD C PC XX-1 T M ABBREVIATIONS: LEGEND: LIGHTING FIXTURES: UPPERCASE LETTER ADJACENT TO FIXTURE DENOTES DESIGNATION PER THE LIGHTING FIXTURE SCHEDULE. LOWERCASE LETTER DENOTES SWITCHLEG. THE RESPECTIVE SWITCH WILL HAVE THE SAME DESTINATIONS. NUMERAL DENOTES BRANCH CIRCUIT CONNECTION. FIXTURE TYPE ENDING WITH 'D' SUFFIX INDICATES FIXTURE THAT REQUIRES DIMMING BALLAST. (EXAMPLE: FIXTURE TYP 'A3D') REFER TO THE FIXTURE SCHEDULE FOR THE SPECIFIC FIXTURE INFORMATION. EMERGENCY FIXTURES SHALL HAVE FACTORY INSTALLED INTERNAL BATTERIES, PER SPECIFICATIONS. NL SUFFIX ADJACENT TO FIXTURE TYPE DENOTES NIGHT LIGHT. DO NOT SWITCH THESE FIXTURES. NON- EMERGENCY EMERGENCY/ BATTERY BACKUP LIGHTING FIXTURE: LINEAR FLUORESCENT ELECTRICAL EQUIPMENT: REFER TO ONE-LINE DIAGRAM AND EQUIPMENT CONNECTION SCHEDULE FOR LOAD DATA USED AS THE BASIS OF DESIGN AND REQUIRED CONNECTIONS. VERIFY LOAD AND LOCATION WITH EQUIPMENT CUT-SHEETS AND INSTALLER. GENERAL NOTES: DEVICE IDENTIFIER TAGS: NUMERAL ADJACENT TO DEVICE DENOTES BRANCH CIRCUIT CONNECTION. IDENTIFIER TAGS ADJACENT TO DEVICES INDICATE: WIRING DEVICES: RECEPTACLES: NOMINAL MOUNTING HEIGHT OF RECEPTACLES SHALL BE 18" TO CENTER, UNO. IF APPLICABLE, ADJUST SO DEVICE COVER IS IN THE CENTER OF MASONRY COURSE NEAREST THAT HEIGHT. THE HEIGHT ESTABLISHED SHALL GOVERN FOR ALL BOX INSTALLATIONS, WHERE INSTALLED IN MASONRY OR FRAMED WALLS. SWITCHES: MOUNTING HEIGHT OF SWITCHES SHALL BE 46" NOMINAL, ADJUSTED IN THE SAME MANNER AS SPECIFIED ABOVE, FOR RECEPTACLES. LOWERCASE LETTER INDICATES SWITCHLEG CONNECTION. THE RESPECTIVE FIXTURE(S) WILL HAVE THE SAME DESIGNATION. BRANCH CIRCUITS: CONDUCTOR COUNTS ARE SHOWN ON THE HOMERUNS ONLY. CONTRACTOR SHALL DETERMINE COUNTS FOR INTERMEDIATE RUNS BASED ON THE MANNER IN WHICH THE CIRCUIT ELEMENTS ARE CONNECTED. REFER TO THE SPECIFICATION SECTIONS 262010, 262080, & 26030 FOR SPECIAL REQUIREMENTS. LA-1,3,5 MISCELLANEOUS COMPONENTS: 3 4 V K O LIGHTING FIXTURE: LINEAR FLUORESCENT LIGHTING FIXTURE: LINEAR FLUORESCENT LIGHTING FIXTURE: FLUORESCENT STRIP LIGHTING FIXTURE: FLUORESCENT, WALL MTD. DOWNLIGHT/SCONCE FIXTURE EXIT AREA OF REFUGE LIGHT: UNIVERSAL MTD. DIRECTIONAL FIXTURES: EMERGENCY TYPE LIGHT TRACK: LENGTH AS SHOWN MOUNT ABOVE COUNTERTOP OR BACKSPLASH, 9" ABOVE WORK SURFACE TO CENTER MOUNT DEVICE AT HEIGHT INDICATED PROVIDE WEATHER-PROOF COVER RECEPTACLE: SIMPLEX RECEPTACLE: DUPLEX RECEPTACLE: GROUND-FAULT-INTERRUPTING TYPE IN-SLAB FLOOR BOX: SEE SPECIFICATIONS RECEPTACLE: DRYER, 30 AMP, 120/250 VOLT RECEPTACLE: SPECIAL PURPOSE , COORDINATE NEMA RATING WITH SPECIFIED EQUIPMENT ELECTRIC WATER COOLER POWER CONNECTION, GFCI OUTLET. HAND DRYER POWER CONNECTION: COORDINATE MOUNTING HEIGHT W/ ARCHITECTURAL ELEVATIONS SEE DETAIL 1/E7.1. RECEPTACLE FOR CLOCK (RECESSED) AND CLOCK; COORDINATE MOUNTING HEIGHT & LOCATION WITH ARCHITECTURAL FLOOR PLAN AND ELEVATIONS RECEPTACLE: CEILING MOUNTED SWITCH: SINGLE-POLE SWITCH: THREE-WAY TYPE SWITCH: FOUR-WAY TYPE SWITCH: LOW VOLTAGE OVERRIDE SWITCH FOR VACANCY SENSOR. WHERE MULTIPLE SUBSCRIPTS ARE INDICATED ("ab" FOR EXAMPLE) PROVIDE A PUSHBUTTON FOR EACH CORRESPONDING GROUP OF FIXTURES TO BE CONTROLLED (2 BUTTON SWITCH FOR "ab" FOR EXAMPLE). THE PUSHBUTTONS SHALL BE MOUNTED UNDER A SINGLE GANG FACEPLATE. SWITCH: DIMMER, DIMMER SHALL BE COMPATIBLE WITH BALLAST INSTALLED. PROVIDE ALL LOW VOLTAGE CABLING AND CONNECTIONS FOR 0 TO 10 VOLT DIMMING. SWITCH: KEY-OPERATED SWITCH: OVERRIDE SWITCH: OCCUPANCY SENSOR, CEILING MOUNTED SWITCH: OCCUPANCY SENSOR, CORNER MOUNTED SWITCH: OCCUPANCY SENSOR, WALL MOUNTED SWITCH: MOTOR RATED, WITHOUT OVERLOAD PROTECTION DISCONNECT SWITCH DRY-TYPE TRANSFORMER PANELBOARD: SURFACE MOUNTED EQUIPMENT AS NOTED, SEE ABBREVIATIONS, THIS SHEET PHOTOCELL: LOCATE UNDER EAVES, FACING NORTH, AVOID ANY OTHER OUTSIDE LIGHT SOURCE BRANCH CIRCUIT: CONCEALED BRANCH CIRCUIT: CONCEALED IN FLOOR SLAB BRANCH CIRCUIT: EXPOSED 'HOMERUN' TO PANEL: NUMBER OF HASH MARKS INDICATES QUANTITY OF No. 12 AWG UNGROUNDED CONDUCTORS IN 3/4" RACEWAY. GROUNDED CONDUCTORS (NEUTRALS) ARE NOT SHOWN - ONE DEDICATED NEUTRAL IS REQUIRED FOR EACH UNGROUNDED CONDUCTOR INSTALLED, SEE SPECIFICATIONS. EACH CONDUCTOR SHALL BE MIN. No. 12 AWG UNLESS NOTED OTHERWISE. JUNCTION BOX: MTD. ABOVE CEILING JUNCTION BOX: WALL MTD. 7. WHERE COMPLETE BRANCH CIRCUIT WIRING IS NOT SHOWN, PROVIDE ACCORDING TO HOMERUNS SHOWN AND CORRESPONDING CIRCUIT NUMBERS ADJACENT TO THE DEVICE OR FIXTURE. REFER TO THE SPECIFICATIONS FOR THE WIRING METHODS. BRANCH CIRCUIT RATINGS SHALL BE BASED ON OVERCURRENT DEVICE RATINGS SHOWN IN THE PANEL SCHEDULES. 8. REFER TO THE ELECTRICAL PANELBOARD SCHEDULES AND EQUIPMENT RATINGS & CONNECTIONS SCHEDULE FOR VOLTAGE, BRANCH CIRCUITS REQUIREMENTS, BREAKERS SIZES AND OTHER RELATED ELECTRICAL EQUIPMENT TO BE PROVIDED AND/OR INSTALLED BY THE ELECTRICAL CONTRACTOR. C XX" WP A AMPERES AFF ABOVE FINISHED FLOOR AFG ABOVE FINISHED GRADE AH AIR HANDLER AIC AMPERAGE INTERRUPT CAPABILITY ATU AIR TERMINAL UNIT A/V AUDIO/VISUAL AWG AMERICAN WIRE GAUGE BFG BELOW FINISHED GRADE B.E. BOTTOM EDGE C. CONDUIT CU CONDENSING UNIT DAH DUCTLESS AIR HANDLER DHP DUCTLESS HEAT PUMP DIA. DIAMETER E.C.B. ENCLOSED CIRCUIT BREAKER V S V S VS SWITCH: VACANCY SENSOR, CEILING MOUNTED SWITCH: VACANCY SENSOR, CORNER MOUNTED SWITCH: VACANCY SENSOR, WALL MOUNTED THE ELECTRICAL DRAWINGS ARE ONLY PART OF THE CONTRACT DOCUMENTS. THE CONTRACTOR SHALL REVIEW ALL OF THE DRAWINGS AND SPECIFICATIONS FOR THEIR INTERRELATIONSHIP AND REQUIRED COORDINATION BETWEEN DISCIPLINES. SYMBOL WHERE SHOWN AT OR NEAR A ROOM INDICATES THAT ROOM IS SHOWN AS A TYPICAL LARGE SCALE. (2) INDICATES THE DETAIL NUMBER AND (E4.2) INDICATES THE SHEET NUMBER. ALL CONDUCTORS SHALL BE COPPER UNLESS NOTED WITH THE WORD "ALUMINUM" IN THE DESCRIPTION. EACH DOOR SHALL HAVE ONE 3/4"C. FROM DOOR FRAME TO DOOR CONTROLLER ENCLOSURE (ASSUME WITHIN 50' OF DOOR), ONE DEDICATED 20A, 120 VOLT CIRCUIT TO SAME CONTROLLER ENCLOSURE. PRIOR TO RUNNING ANY CONDUIT, COORDINATE LOCATIONS OF ALL WALL MOUNTED DEVICES WITH WALL MOUNTED ACOUSTICAL PANELS. SEE ARCHITECTURAL DRAWINGS FOR SPACES IN WHICH WALL PANELS ARE INSTALLED. PRIOR TO RUNNING CONDUIT, COORDINATE LOCATIONS OF ALL WALL MOUNTED DEVICES WITH WALL MOUNTED SAFETY PADS IN GYMNASIUM. 1. 3. 4. 5. 6. EF EXHAUST FAN EH ELECTRIC HEATER EMCS ENERGY MANAGEMENT CONTROL UNIT FAAP FIRE ALARM ANNUNCIATOR PANEL FACP FIRE ALARM CONTROL PANEL G GROUND GFI GROUND-FAULT INTERRUPTING HP HORSE POWER HRVU HEAT RECOVERY VENTILATING UNIT HWCP HOT WATER CIRCULATING PUMP KCMIL KILO CIRCULAR MIL MAH MAKEUP AIR HEATER MB MAIN BREAKER MCA MINIMUM CIRCUIT AMPS MCC MOTOR CONTROL CENTER MIN MINIMUM MOCP MAXIMUM OVERCURRENT PROTECTION MTD MOUNTED No. NUMBER NEC NATIONAL ELECTRIC CODE NTS NOT TO SCALE PIV POST INDICATOR VALVE RGS RIGID GALVANIZED STEEL RTU ROOFTOP UNIT SF SUPPLY FAN SPD SURGE PROTECTION DEVICE SWBD SWITCHBOARD TTW THROUGH-THE-WALL HEAT PUMP TYP TYPICAL UH UNIT HEATER UNO UNLESS NOTED OTHERWISE V VOLTAGE W WATTAGE W/ WITH WH WATER HEATER WHP WALL-MOUNTED HEAT PUMP WP WEATHER PROOF XFMR TRANSFORMER SMOKE DAMPER, 120V, PROVIDE POWER CONNECTION AND ALL NEEDED SMOKE DETECTION AND CONTROL MODULES AS REQUIRED BY NFPA 72 FOR PROPER OPERATION. SD FIRE ALARM REMOTE VOICE EVACUATION MICROPHONE, RECESSED WALL MOUNTED. MIC "C" DESIGNATION INDICATES CEILING MOUNTED. S SPEAKER - SEE DRAWINGS AND SPECIFICATIONS FOR TYPE. LA-1,3,5 'HOMERUN' TO PANEL FOR EQUIPMENT: SEE EQUIPMENT CONNECTION SCHEDULES FOR SIZE OF FEEDER AND NUMBER OF CONDUCTORS. a SWITCH: SUBSCRIPT THAT INDICATES CORRESPONDING FIXTURES THAT SWITCH CONTROLS D RECEPTACLE: QUADRUPLEX DRAWING NUMBER DRAWINGS MAY NOT BE REPRODUCED IN ANY FORM WITHOUT WRITTEN PERMISSION ALL RIGHTS RESERVED COPYRIGHT 2014 DATE: FULL TIME ENROLLMENT (FTE) 650 CURRENT 900 FUTURE DATE: JOB NO. SCALE: DESIGNED DRAWN CHECKED 12-18-15 REVISION SCHEDULE DD SUBMITTAL 12/29/2015 10:49:10 AM 12" = 1'-0" JULIET TE LOW ELEMENTARY SCHOOL 15 Blue Ridge Ave Savannah, GA 31401 SAVANNAH CHATHAM COUNTY PUBLIC SCHOOL SYSTEM ELECTRICAL LEGEND & LIGHT FIXTURE SCHEDULE E0.0 215-2001-07 GJC WAL GJC LIGHT FIXTURE SCHEDULE TYPE Coun t DESCRIPTION LAMPS MANUFACTURER / SERIES FINISH MOUNTING NOTES A1 49 2'X4' LENSED TROFFER WITH 0.125" MIN. #A12 LENS AND FLUSH STEEL DOOR WITH MITERED CORNERS. LED: 4000 LUMEN, 4000K LITHONIA "GTL" SERIES, METALUX, DAYBRITE, H.E. WILLIAMS WHITE RECESSED A2 47 KITCHEN 2'X4' LENSED TROFFER WITH 0.125" MIN. #A12 LENS AND FLUSH STEEL DOOR WITH MITERED CORNERS. PROVIDE GASKETING BETWEEN LENS AND DOOR FRAME. LED: 4000 LUMEN, 4000K LITHONIA "GTL" SERIES, METALUX, DAYBRITE, H.E. WILLIAMS WHITE RECESSED A3 13 1'X4' RECESSED TROFFER WITH PRISMATIC ACRLIC LENS (.0125" THICKNESS, MIN.) FLUSH STEEL DOOR W/MITERED CORNERS. LED: 4000 LUMEN, 4000K LITHONIA "GTL" SERIES, METALUX, DAYBRITE, H.E. WILLIAMS WHITE RECESSED B1 433 2'X4' VOLUMETRIC TROFFER WITH LINEAR FACETED REFLECTOR AND REGRESSED REFRACTIVE SYSTEM. LED: 4000 LUMEN, 4000K LITHONIA "BTL" SERIES, METALUX, DAYBRITE, H.E. WILLIAMS WHITE RECESSED B2 118 2'X4' VOLUMETRIC TROFFER WITH LINEAR FACETED REFLECTOR AND REGRESSED REFRACTIVE SYSTEM. LED: 5000 LUMEN, 4000K LITHONIA "BTL" SERIES, METALUX, DAYBRITE, H.E. WILLIAMS WHITE RECESSED B4 39 VOLUMETRIC RECESSED FIXTURE, 2'X2', LINEAR FACETED REFLECTOR, AND REGRESSED REFRACTIVE SYSTEM. LED, 40.1 WATT, 4000 LUMEN, 4000 DEGREE K LITHONIA "BTL" SERIES, METALUX, DAYBRITE, H.E. WILLIAMS WHITE RECESSED C1 2 1'X4' SURFACE FIXTURE WITH ACRYLIC DIFFUSER. LED: 4600 LUMEN, 4000K LITHONIA "LBLED" SERIES, METALUX, DAYBRITE, H.E. WILLIAMS WHITE SURFACE D1 20 8" DIAMETER CYLINDER, 33" LENGTH, OPAL ACRYLIC SANDBLASTED DIFFUSER, VARIOUS PENDANT LENGTHS TO BE DETERMINED BY ARCHITECT (MAXIMUM STEM LENGTH 8'-0") LED 29 WATT, 4000 DEGREE K DELRAY "BIG LIGHT 6341" SERIES, WINONA, BETA CALCO "CYLINDRA", VISA "SEQUENCE" SELECTED BY ARCHITECT PENDANT 0-10 VOLT DIMMING E1 57 STANDARD STRIP WITH 14 GUAGE WIRE GUARD. 2-32 WATT, T8, 4100 DEGREE K LITHONIA "C" SERIES, METALUX "SS" SERIES, COLUMBIA "CS" SERIES, HE WILLIAMS "76" SERIES WHITE SURFACE NOTE 2 F1 2 ELEVATOR PIT LIGHT, CLEAR GLASS GLOBE WITH DIE CAST ALUMINUM GUARD. 1-42 WATT TTT, 4100 DEGREE K RIG-A-LITE "CVPW" SERIES, STONECO "VWXL" SERIES, EXCELINE "RLW" SERIES, DAYBRITE "VFSW" SERIES, BASELITE "W2" SERIES EXPOSED PARTS CORROSION RESISTANT WALL G1 11 DOWNLIGHT, RECESSED SELF FLANGED, 6" APERTURE CLEAR MATT DIFFUSE REFLECTOR. SHOWER LIGHT SUITABLE FOR WET LOCATION. LED: 2000 LUMEN, 4000K HALO COMMERCIAL "PD6" SERIES, LITHONIA, DAYBRITE, LIGHTOLIER,PRESCOLI TE WHITE TRIM RING RECESSED HB 24 HIGHBAY LED WITH WIDE DISTRIBUTION. PROVIDE WITH DOORFRAME ACRYLIC LENS AND WIRE GUARD. CHAIN MOUNT FIXTURE TO STRUCTURE, SUSPEND TO BOTTOM OF TRUSS. 18000 LUMENS, 4000 DEGREE K METALUX "HBLED" SERIES, DAYBRITE, LITHONIA, H.E. WILLIAMS WHITE CHAIN 0-10 VOLT DIMMING M1 8 WALL MOUNTED UP-LIGHT WITH INTEGRAL DRIVER, EXTERNAL YOKE ON CANOPY MOUNTING, CUT OFF VISOR. LED 18 WATT, 750 LUMENS, 4000 DEGREE K ELLIPTIPAR "STYLE S122" SERIES, WINONA, SPI, FORUM WHITE WALL AT 20'-0" 0-10 VOLT DIMMING OA 20 WALL MOUNTED, WEDGE SHAPE EXTERIOR GRADE FIXTURE. LED: 2000 LUMEN, 4000K LUMINAIRE LED "ARV13" SERIES, LITHONIA, HUBBELL, McGRAW EDISON, PHILLIPS BY ARCHITECT WALL - SURFACE PROVIDE FIXTURE WITH 90 MINUTE BATTERY. OB 103 ROUND, CANOPY CEILING MOUNTED LED LIGHT, MAX 14" DIAMETER, 4" DEEP, OPAL LENS. LED: 2385 LUMEN, 4000K LUMINAIRE LED "ARV13" SERIES, LITHONIA, HUBBELL, McGRAW EDISON, PHILLIPS BY ARCHITECT SURFACE OC 1 BUILDING MOUNTED FLOOD LIGHT WITH MOUNTING BRACKET AND ASSOCIATED HARDWARE. WIDE SYMETRIC FLOOD. LED, 79 WATT, 7150 LUMEN, 4000 DEGREE K COOPER "NIGHT FALCON" SERIES, LITHONIA "D" SERIES, BETA, PHILLIPS BRONZE WALL/VERTICAL SURFACE S2 3 CYLINDRICAL 26" PENDANT, 5" DEPTH, SINGLE POINT QUADPOD SUSPENSION, 10% UPLIGHT. LED: 4200 LUMENS, 59 WATT, 4000K IMPACT "WAF.R", BETA CALCO, SOLERA TO BE SELECTED BY ARCHITECT PENDANT PENDANT HEIGHT: 9'-0" A.F.F. W1 16 1'X4' FIXTURE, SURFACE MOUNT, LOW PROFILE, VANDLE RESISTANT. FIXTURE SHALL BE EQUIPPED WITH MOTION SENSOR. LED: 4000 LUMEN, 4000K LUMINAIRE "TSL" SERIES, LITHONIA, METALUX, H.E. WILLIAMS WHITE WALL - SURFACE XA 56 SINGLE FACE EXIT LIGHT, DIE CAST ALUMINUM, UNIVERSAL MOUNTING, GREEN LETTERS - DIRECTION OF ARROWS AS INDICATED. LED LITHONIA "LE" SERIES, BEGHELLI "LC1E" SERIES, DUAL LITE "CVD" SERIES, SURE-LIGHT "CX" SERIES BRUSHED STAINLESS WALL 90 MINUTE BATTERY XB 20 DOUBLE FACE EXIT LIGHT, DIE CAST ALUMINUM, UNIVERSAL MOUNTING, GREEN LETTERS - DIRECTION OF ARROWS AS INDICATED LED LITHONIA "LE" SERIES, BEGHELLI "LC1E" SERIES, DUAL LITE "CVD" SERIES, SURE-LIGHT "CX" SERIES BRUSHED STAINLESS CEILING 90 MINUTE BATTERY XEM 10 2 HEAD, WALL MOUNT EMERGENCY BATTERY WITH FIXTURE LITHONIA "ELM" SERIES, CHLORIDE, SURELITE, DUALITE WHITE WALL 90 MINUTE BATTERY LIGHT FIXTURE SCHEDULE NOTES: 1. GENERAL: REFER TO LIGHTING PLANS FOR BALLAST VOLTAGES AND CONFIGURATION OF FIXTURES. FIXTURES CONTROLLED BY MULTIPLE SWITCHES SHALL HAVE CORRESPONDING QUANTITY OF BALLASTS. 2. FIXTURES SHALL BE MOUNTED SUSPENDED OR SURFACE, GIVING RIGHT OF WAY TO HVAC DUCT WORK AND/OR EQUIPMENT. 3. PROVIDE BACKBOX ON ALL FIXTURES OF THIS TYPE SO THAT FIXTURES WITH AND WITHOUT EMERGENCY BALLAST ARE AT THE SAME DEPTH. 4. GENERAL: COORINATE ALL MOUNTING OF FIXTURES (GRID/FLANGE) WITH ARCHITECTURAL RCP. NO. DATE DESCRIPTION 57 481 550 103