7/30/2019 Blaze Ng http://slidepdf.com/reader/full/blaze-ng 1/32  I  n  s  t  a  l  l  a  t  i  o  n   &   S  p  e  c  i  f i c a ti o n   M  a  n  u  a  l   for Archi t ectural Engine ers  F ir e  S ri n le r C tr a to rs Now Listed and Approved for more types of applications than any other non-metallic system 
32

Blaze Ng

Apr 14, 2018

Download

Documents

Nabil Rameh
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Blaze Ng

7/30/2019 Blaze Ng

http://slidepdf.com/reader/full/blaze-ng 1/32

 I n s t a l l a

 t i o n  &  S

 p e c i f i c a t i o n

  M a n u a

 l

  for Archi t ec tural Engin e ers

a n d  F i r e  S p r i n k l e r  C o n t r a c t o r s 

Now Listed and Approved 

for more types of 

applications than any other 

non-metallic system 

Page 2: Blaze Ng

7/30/2019 Blaze Ng

http://slidepdf.com/reader/full/blaze-ng 2/32

Introduction.3

Combination.of.BlazeMaster ® .Products..with.Other.CPvC.and.Solent.Cements .3

Where.to.Use.BlazeMaster ® ..Fire.Sprinkler.Systems. 3

Concealed.Installations.4

Exposed.Installations.(Where.Sprinklers.are.Required).4

Standard Coverage and Residential Sprinklers .......................4

Light Hazard or Residential Pendent Sprinklers ...................4

Light Hazard or Residential Horizontal 

Sidewall Sprinklers ...................................................................4

Light Hazard Upright Sprinklers ..............................................4

Light Hazard Extended Coverage 

and Residential Sprinklers ...........................................................4

Light Hazard Extended Coverage or 

Residential Pendent Sprinklers ..............................................5

Light Hazard Extended Coverage or Residential Horizontal Sidewall Sprinklers .............................5 

Unfinished Basements 5

Factory.Mutual.10

The.Loss.Preention.Council.10

Sprinkler.Head.Temperature.Ratings.11

Temperature/Pressure.Ratings.11

Combustible.Concealed.Installations.11

NFPA 13R and 13D .11

Air.Plenums. 11

Canadian Installations .11

Ordinary.Hazard.Installations. 12

Garage.Installations. 12

System.Risers.in.NFPA.13,.13R..and.13D.Applications.12

Underground.Water.Pressure.Serice.13

Thrust Blocking . 13

Trenching .14

Snaking of Pipe .14

Backfilling .15

Outdoor. Installations. 15

Updated.UL.Listing.Information.15

Product.Rating,.Capabilities.and..Material.Properties. 15

Pressure.Rating.15

Pipe.Dimensions.and.Weights.15

Physical.and.Thermal.Properties.of.BlazeMaster ® .CPvC.16

Hydraulic.Design.16

C Factor .16

Pipe Friction Loss .16

Fittings Friction Loss .16

Thermal.Expansion.and.Contraction.17

Pipe.Deflection.18

Handling.and.Storage.20

Joining.BlazeMaster ® .Pipe.and.Fittings.with..Red.One-Step.Solent.Cement.20

Cutting. 20

Deburring.20Fitting.Preparation. 20

Solent.Cement.Application.20

Assembly.21

Set.and.Cure.Times.21

Pressure.Testing.23

Estimating.One-Step.Solent.Cement.Requirements.23

Cut-In.Procedure.for.System..Modification.or.Repairs. 24

Hangers.and.Supports .26

Penetration.of.Studs.and.Joists.27Wooden.Studs.and.Joists.27

Metal.Studs.27

Transition.to.Other.Materials .27

Support.27

Threaded.Connections.27

Flanged.Connections. 27

Recommended Bolt Torque .27

Grooed.Coupling.Adapters.28

Other.Design.Criteria . 28

Chemical.Compatibility.28

A.Note.on.Microbiologically.Influenced.Corrosion.(MIC)29

Freeze.Protection.29

Batt Insulation . 29

Antifreeze Solutions .29

Estimating Antifreeze Solution Requirements .29

Painting30

Maintenance. 30

Penetrating.Fire.Rated.Walls.and.Partitions.30

Earthquake.Bracing.30

Summary.30

Dos.and.Don’ts. 31

2Lubrizol

Table of Contents

Page 3: Blaze Ng

7/30/2019 Blaze Ng

http://slidepdf.com/reader/full/blaze-ng 3/32

Introduction

BlazeMaster ® .pipe.and.fittings.are.designed.

specifically.for.fire.sprinkler.systems..They.are.

made.from.a.specialty.thermoplastic.known.

chemically.as.post-chlorinated.polyinyl.chloride.

(CPvC)..BlazeMaster ® .pipe.and.fittings.proide.

unique.adantages.in.sprinkler.installations.

including.superior.hydraulics,.ease.of.joining,.

increased.hanger.spacing.in.comparison.to.other.

thermoplastics.and.ease.of.assembly..They.also.

are.based.on.a.technology.with.a.continuous.and.

proen.serice.history.of.more.than.40.years..

This.installation.manual.proides.instructions.for.

handling.and.installing.a.BlazeMaster ® .fire.sprinkler.

system.as.well.as.information.regarding.system.

design..It.is.intended.as.a.supplement.to.basic,.

fundamental.knowledge.relating.to.the.installation.and/or.repair.of.CPvC.fire.sprinkler.systems..It.also.

is.intended.to.supplement.installation.instructions.

published.by.manufacturers.of.pipe.and.fittings..

Before.commencing.installation,.a.user.should.

understand.and.confirm.applicable.National.Fire.

Protection.Association.(NFPA).guidelines.and.local.

code.approal.and.installation.requirements.for.

CPvC.fire.sprinkler.systems..

BlazeMaster ® .CPvC.pipe.and.fittings.carry.the.

markings.of.Underwriters.Laboratories,.Inc.(UL.&.C-UL).and.Underwriters’.Laboratories.of.Canada.

(ULC),.Factory.Mutual.(FM)*,.The.Loss.Preention.

Council.(LPC),.and.the.NSF.International.(NSF).

for.use.with.potable.water..Refer.to.indiidual.

manufacturers’.installation.instructions.for..

specific.listings.and.approals

Lubrizol.produces.and.sells.CPvC.compounds..

to.licensed.manufacturers.of.BlazeMaster ® .pipe.&.

fittings.(see.back.coer.for.contact.information)..

When.this.design.manual.states,."refer.to.manufacturer’s.installation.instructions".please.refer.

to.the.indiidual.installation.instructions.published.

by.each.pipe.and/or.fittings.manufacturer

For.additional.information.regarding.the.

BlazeMaster ® .product.line,.please.refer.to.the.

internet.website,.wwwblazemastercom..An.

electronic.ersion.of.this.installation.guide,.the.

most.current.product.compatibility.information,.

the.BlazeMaster ® .Blaster.newsletter,.and.other.

BlazeMaster ® .fire.sprinkler.systems.information.can.

be.found.at.this.site

Combination of BlazeMaster® Products

with Other CPVC and Solvent Cements

All.BlazeMaster ® .pipe,.fittings.and.solent.cements.hae.been.ealuated.and.are.listed.

for.combination.regardless.of.the.licensed.

manufacturer.that.produces.the.products

The.BlazeMaster ® .products’.listing.does.not.include.

the.combination.of.BlazeMaster ® .CPvC.pipe.with.

other.types.of.specially.listed.CPvC.fire.sprinkler.

pipes,.fittings.and.solent.cements

Where to Use BlazeMaster® 

Fire Sprinkler Systems

BlazeMaster ® .CPvC.pipe.and.fittings.are..

Listed by Underwriters Laboratories (UL & C-UL) 

and Underwriters Laboratories of Canada (ULC) 

for use in: 

•. Light.Hazard.occupancies.as.defined.in.the.

Standard.for.Installation.of.Sprinkler.Systems,.NFPA.

13

•. Residential.occupancies.as.defined.in.the.

Standard.for.Installation.of.Sprinkler.Systems.in.

Residential.Occupancies.up.to.Four.Stories.in.

Height,.NFPA.13R

•. Residential.occupancies.as.defined.in.the.

Standard.for.Sprinkler.Systems.in.One.and.Two.

Family.Dwellings.and.Manufactured.Homes,.NFPA.

13D

•. Air.plenums,.as.defined.by.the.Installation.of.Air.

Conditioning.and.ventilating.Systems,.NFPA.90A

•. Installation.of.Priate.Fire.Serice.Mains.and.Their.

Appurtenances,.NFPA.24.

•. System.risers.in.residential.buildings.up.to.four.

stories.in.height,.NFPA.13R.and.13D

•. See.UL.Fire.Protection.Equipment.Directory,.

categories.vIWT.and.HFYH

BlazeMaster ® .fire.sprinkler.systems.shall.be.employed.

in.wet-pipe.systems.(A.wet-pipe.system.contains.

water.and.is.connected.to.a.water.supply.so.

that.the.water.will.discharge.immediately.when.

3 Lubrizol

*As.manufactured.by.Harel,.IPEX,.Nibco,.Tyco.and.viking

Page 4: Blaze Ng

7/30/2019 Blaze Ng

http://slidepdf.com/reader/full/blaze-ng 4/32

the.sprinkler.is.opened).BlazeMaster ® .CPvC.

pipe.and.fittings.must.neer.be.used.in.a.system.

using.compressed.air.or.other.gases..National.

Fire.Protection.Association.Standards.13,.13R,.13D,.

and.NFPA.24.must.be.referenced.and.followed.for.

design.and.installation.requirements.in.conjunction.

with.this.design.manual

Concealed Installations

With.concealed.installation.the.minimum.

protection.shall.consist.of.one.layer.of.3/8".(95.mm).

gypsum.wallboard,.or.a.suspended.membrane.

ceiling.with.lay-in.panels.or.tiles.haing.a.weight.

of.not.less.than.035.pounds.per.square.foot.(17.

kg.per.square.meter).when.installed.with.metallic.

support.grids,.or.1/2".(127.mm).plywood.soffits..

For.residential.occupancies.defined.in.NFPA.13R.

and.13D,.the.minimum.protection.may.consist.of.one.layer.of.1/2".(127.mm).plywood..During.

periods.of.remodeling.and.renoation,.appropriate.

steps.must.be.taken.to.protect.the.piping.from.fire.

exposure.if.the.ceiling.is.temporarily.remoed.

Exposed Installations

(Where Sprinklers are Required)

Note:..It.is.always.acceptable.to.install.

BlazeMaster ® .products.in.areas.where.sprinklers..

are.not.required..Refer.to.the.manufacturer’s.

installation.instructions

As.an.alternatie.to.the.protection.requirements,.

BlazeMaster ® .CPvC.pipe.and.fittings.may.be.

installed.without.protection.(exposed).when.

subject.to.the.following.additional.limitations:

A. Standard Coverage and Residential Sprinklers 

. These.installations.shall.be.below.a.smooth,..

flat,.horizontal.ceiling.construction.and.require.

the.use.of.BM-5,.CSC-500,.TFP-500.or.HvC-

500.one.step.solent.cement..Pendent.and.horizontal.sidewall.sprinkler.[170°F.(77°C).

maximum.temperature.rated].installations..

may.use.CSC-400.or.TFP-400.one.step.

solent.cement..Upright.sprinkler.installations.

[155°F(68°C).maximum.temperature.rated].may.

use.CSC-400.or.TFP-400.one.step.solent.cement

1.. Light Hazard or Residential Pendent

Sprinklers

. Listed.quick.response,.170°F.(77°C).maximum.

temperature.rated,.pendent.sprinklers.haing.

deflectors.installed.within.8.inches.(203.mm).

from.the.ceiling.or.Listed.residential,.170°F.

(77°C).maximum.temperature.rated,.pendent.

sprinklers.located.in.accordance.with.their.Listing.and.a.maximum.distance.between.

sprinklers.not.to.exceed.15.feet.(457.m)..The.

piping.shall.be.mounted.directly.to.the.ceiling

2.. Light Hazard or Residential Horizontal

Sidewall Sprinklers

. Listed.quick.response,.200°F.(93°C).

maximum.temperature.rated,.horizontal.

sidewall.sprinklers.haing.deflectors.installed.

within.12.inches.(304.mm).from.the.ceiling.

and.within.6.inches.(152.mm).from.the.sidewall.or.Listed.residential,.200°F.(93°C).

maximum.temperature.rated,.horizontal.

sidewall.sprinklers.located.in.accordance.

with.their.Listing.and.a.maximum.distance.

between.sprinklers.not.to.exceed.14.feet.

(427.m)..The.piping.shall.be.mounted.

directly.to.the.sidewall

3.. Light Hazard Upright Sprinklers

. Listed.quick.response,.155°F.(68°C).maximum.

temperature.rated,.upright.sprinklers.haing.deflectors.installed.within.4.inches.(101.mm).

from.the.ceiling.and.a.maximum.distance.

between.sprinklers.not.to.exceed.15.feet.

(457.m)..The.maximum.distance.from.the.

ceiling.to.the.centerline.of.the.main.run.of.

pipe.shall.not.exceed.7-1/2.inches.(190.mm).

and.the.distance.from.the.centerline.of.a.

sprinkler.head.to.a.hanger.shall.be..

3.inches.(76.mm)

B. Light Hazard Extended Coverage and Residential Sprinklers 

. These.installations.shall.be.below.a.smooth,..

flat,.horizontal.ceiling.construction,.are.limited.to.

unobstructed.construction,.require.the.use..

of.Schedule.80.fittings.for.sizes.1-1/2.in.and.

greater,.and.require.the.use.of.BM-5,.CSC-500,..

.

.

.

.

4Lubrizol

Page 5: Blaze Ng

7/30/2019 Blaze Ng

http://slidepdf.com/reader/full/blaze-ng 5/32

TFP-500,.or.HvC-500.one.step.solent.cement...

For.pendent.sprinkler.installations,.the.piping.

shall.be.mounted.directly.to.the.ceiling...

For.horizontal.sidewall.sprinkler.installations,.the.

piping.shall.be.mounted.directly.to.the.sidewall

1.. Light Hazard Extended Coverage or

Residential Pendent Sprinklers. Listed.light.hazard,.extended.coerage,.

quick.response,.155°F.(68°C).maximum.

temperature.rated,.pendent.sprinklers.

haing.deflectors.installed.within.8.inches.

(203.mm).from.the.ceiling,.a.maximum.

distance.between.sprinklers.not.to.exceed.

20.feet.(609.m),.and.an.application.density.

not.less.than.010.gpm/ft2.(408.ml/min)

. Listed.residential,.155°F.(68°C).maximum.

temperature.rated,.pendent.sprinklers.haing.deflectors.installed.within.8.inches.

(203.mm).from.the.ceiling,.a.maximum.

distance.between.sprinklers.not.to.exceed.

20.feet.(609.m),.and.an.application.density.

not.less.than.010.gpm/ft2.(408.ml/min)

2.. Light Hazard Extended Coverage or

Residential Horizontal Sidewall Sprinklers

. Listed.light.hazard,.extended.coerage,.

quick.response,.175°F.(79°C).maximum.

temperature.rated,.horizontal.sidewall.sprinklers.haing.deflectors.installed.within.

12.inches.(304.mm).from.the.ceiling.and.

within.6.inches.(152.mm).from.the.sidewall,.a.

maximum.distance.between.sprinklers..

not.to.exceed.16.feet.(487.m),.and.an.

application.density.not.less.than..

010.gpm/ft2.(408.ml/min)

. Listed.residential,.165°F.(74°C).maximum.

temperature.rated,.horizontal.sidewall.

sprinklers.haing.deflectors.installed.within.12.inches.(304.mm).from.the.ceiling.and.

within.6.inches.(152.mm).from.the.sidewall,.

a.maximum.distance.between.sprinklers.

not.to.exceed.18.feet.(548.m),.and.an.

application.density.not.less.than.010.gpm/

ft2.(408.ml/min)

. .

.

Listed.light.hazard,.extended.coerage,.

quick-response,.165°F.(74°C).maximum.

temperature.rated,.horizontal.sidewall.

sprinklers.haing.deflectors.installed.within.

12.inches.(304.mm).from.the.ceiling.and.

within.6.inches.(152.mm).from.the.sidewall,.

a.maximum.distance.between.sprinklers.

not.to.exceed.18.feet.(548.m),.and.an.application.density.not.less.than.010.gpm/

ft2.(408.ml/min)

. Listed.light.hazard,.extended.coerage,..

quick.response,.155°F.(68°C).maximum.

temperature.rated,.horizontal.sidewall.

sprinklers.(manufactured.by.Reliable.

Automatic.Sprinkler.Co.Inc,.SIN.RA0362).

haing.deflectors.installed.within.12.inches.

(304.mm).from.the.ceiling.and.within.

6.inches.(152.mm).from.the.sidewall,.a.maximum.distance.between.sprinklers.not.

to.exceed.24.feet.(731.m),.and.a.flow.not.

less.than.40.gpm.(152.L/min).per.sprinkler

C. Unfinished Basements 

. BlazeMaster ® .CPvC.pipe.and.fittings.may..

be.installed.without.protection.(exposed).in.

unfinished.basements.in.accordance.with..

NFPA.13D.when.subject.to.the.following.

additional.limitations:

1. .The.ceiling.shall.be.horizontal.and.

constructed.utilizing.nominal.2.in.x.10.in.

solid.wood.joists.on.16.in.centers

. OR

. .The.ceiling.shall.be.horizontal.and.

constructed.utilizing.nominal.2.in.x.12.in.

solid.wood.joists.on.16.in.centers.When.

installing.BlazeMaster ® .CPvC.pipe.and.

fittings.in.conjunction.with.2.in.x.12.in.solid.

wood.joists,.the.maximum.system.working.

pressure.under.flowing.conditions.shall.not.

exceed.100.psi.and.the.maximum.system.

working.pressure.under.static.(nonflowing).

conditions.shall.not.exceed.175.psi

2. .The.distance.from.the.floor.to.the.bottom..

of.the.solid.wood.joists.shall.be.between..

7.ft.and.8.ft

.

5 Lubrizol

Page 6: Blaze Ng

7/30/2019 Blaze Ng

http://slidepdf.com/reader/full/blaze-ng 6/32

For Exposed BlazeMaster ® Applications

(Use in unfinished basements, system risers and mechanical tees and crosses are not included by this table)

Maximum Maximum Maximum

Spacing Deflector Deflector Sprinkler Application

Sprinkler Typeof Between DistanceFrom DistanceFrom Temperature Density Additional

Configuration Sprinkler Sprinklers(ft.) Ceiling(in.) Sidewall(in.) Rating(°F) (gpm/sq.ft.) Limitations

ExtendedCoverageSprinklers

Pendent LightHazard, ≤20 8 n/a 155 0.10

QuickResponse

Horizontal LightHazard ≤16 12 6 175 0.10

Sidewall QuickResponse

≤18 12 6 165 0.10

LightHazard, ≤24 12 6 155 flowrateof

QuickResponse 40gpmand

ListedReliable maximum

Sprinkler coverageareaof (SINRA0362) 24'x14'

ResidentialSprinklers

Pendent Residential ≤15 persprinkler n/a 170

Listing

≤20 8 n/a 155 0.10

Horizontal Residential ≤14 persprinkler persprinkler 200

Sidewall Listing Listing

≤18 12 6 165 0.10

StandardCoverageSprinklers

Pendent QuickResponse ≤15 8 n/a 170

Horizontal QuickResponse ≤14 12 6 200

Sidewall

Upright QuickResponse ≤15 4 155

inadditionthe ahangermust

distancefrom beinstalled

theceilingto 3inchesfromthe

centerlineof centerlineofthe

pipemustbea sprinklerhead

maximumof

71/2inches

6Lubrizol

Page 7: Blaze Ng

7/30/2019 Blaze Ng

http://slidepdf.com/reader/full/blaze-ng 7/32

3. .Listed.residential.pendent.sprinklers.with.a.

maximum.temperature.rating.of.155°F.and.

a.minimum.K-factor.of.30.are.to.be.used.

for.this.type.of.installation.The.maximum.

sprinkler.spacing.shall.not.exceed.

12.feet.The.system.is.to.be.designed.

based.upon.the.Listed.flows.for.the.

sprinkler.selected.except.that.the.flow.for.

a.single.sprinkler.or.for.multiple.sprinklers.

flowing.is.to.be.not.less.than.11.gpm.per.

sprinkler.The.sprinklers.are.to.be.installed..

with.their.deflectors.a.maximum.of.13/4.in.

below.the.bottom.of.the.solid.wood.joists..

in.anticipation.of.future.installation.of.a..

finished.ceiling.(reference.NFPA.13D,..

Section.824,.2007.Edition)

4. .All.system.mains.shall.be.run.perpendicular..

to.the.joists.All.branch.lines.shall.be.run..

parallel.to.the.joists..Schedule.80.fittings.shall.be.used.for.sizes.1-1/2.inch.and.larger.

5. .All.solent.cement.joints.shall.be.made.

with.BlazeMaster.One.Step.Solent.

Cement.(TFP-500,.BM-5,.CSC-500,.or.HvC-500)

6. .When.the.total.protected.area.exceeds..

1,000.square.feet,.blocking.shall.be.utilized.

to.diide.the.area.into.indiidual.compart-

ments.not.exceeding.1,000.square.feet..

The.maximum.length.along.the.joist.shall.not.

exceed.32.feet.When.the.length.exceeds..

32.feet,.blocking.shall.be.utilized.The.

blocking.shall.be.constructed.of.minimum.1/2.in.plywood.and.shall.be.the.full.depth.

of.the.wood.joists.

7 Lubrizol

Basement Installation

with Center Wall Riser

with Center Room

Main

Page 8: Blaze Ng

7/30/2019 Blaze Ng

http://slidepdf.com/reader/full/blaze-ng 8/32

Lubrizol 8

Basement Installation

with Riser in Corner

Basement Installation

with Center Wall Riser

with Main at Wall

Page 9: Blaze Ng

7/30/2019 Blaze Ng

http://slidepdf.com/reader/full/blaze-ng 9/32

. .It.is.acceptable.for.items.such.as.piping,.

wires,.ducts,.etc.to.penetrate.the.blocking.

The.gap.between.the.item.penetrating.

the.blocking.and.the.blocking.should.be.

minimized.For.installations.where.the.gap.

exceeds.1/4.in,.the.gap.shall.be.filled..

with.insulation,.caulking,.or.other..

suitable.material

7. .When.installing.BlazeMaster ® .CPvC.pipe.

and.fittings.perpendicular.(system.mains)..

to.the.solid.wood.joists,.listed.support.

deices.for.thermoplastic.sprinkler.piping..

or.other.listed.support.deices.shall.be..

used.which.mount.the.piping.directly.to..

the.bottom.of.the.solid.wood.joists.As.an.

alternatie.to.mounting.the.pipe.and..

fittings.below.the.solid.wood.joists,.it.is.also.

acceptable.to.cut.holes.in.the.solid.wood.

 joists.at.or.below.the.center.of.the.depth..of.the.solid.wood.joist.for.support.-.the..

holes.should.be.oersized.to.allow.for.

moement.and.located.to.not.impair..

the.structural.integrity.of.the.joists.

. .CAUTION:.When.drilling.holes.in.the.solid..

wood.joists,.the.structural.integrity.must..

be.maintained.Consult.the.Authority..

Haing.Jurisdiction.(AHJ).or.building.code..

for.requirements

8. .When.installing.BlazeMaster ® .CPvC.pipe.

and.fittings.parallel.(branch.lines).to.the.

solid.wood.joists,.the.pipe.and.fittings.shall.

be.installed.in.the.caity.below.the.bottom.

of.the.ceiling.and.aboe.the.bottom.of.the.

 joist.The.branch.lines.shall.be.located.at.or.

below.the.center.of.the.depth.of.the.solid.

wood.joist.The.pipe.shall.be.installed.utilizing.

listed.support.deices.for.thermoplastic.

sprinkler.piping.or.other.listed.support.

deices.which.mount.the.piping.directly.to.

nominal.2.in.wood.blocking.or.listed.support.

deices.for.thermoplastic.sprinkler.piping.

which.offset.the.pipe.a.nominal.distance.of.

11/2.in.from.the.solid.wood.joists.

. .Use.of.BlazeMaster ® .CPvC.pipe.and.fittings.

is.limited.to.basements.where.the.quantity.

and.combustibility.of.contents.is.low.and.

fires.with.relatiely.low.rates.of.heat.release.

are.expected.For.additional.information.

regarding.the.assembly.and.installation.of.

BlazeMaster ® .CPvC.pipe.and.fittings,..

please.refer.to.the.manufacturer's.

installation.instructions

9 Lubrizol

Branches Supported with Blocking

Branches Supported with Hangers

Page 10: Blaze Ng

7/30/2019 Blaze Ng

http://slidepdf.com/reader/full/blaze-ng 10/32

Factory Mutual.

In.Factory.Mutual.insured.properties.BlazeMaster ® .

CPvC.pipe.and.fittings.are.permitted.to.be.

installed.exposed.(without.protection).when.the.

following.conditions.are.met

•.The.occupancy.classification.must.be.....

...Miscellaneous.Nonmanufacturing.as.defined.in..

...FM.Data.Sheet.3-26,.Fire.protection.Water..

...Demands.for.Nonstorage.Sprinklered.Properties,..

...Table.2,.section.L..

•.Only.wet.pipe.sprinkler.systems.are.to.be.used..

...with.BlazeMaster ® .pipe.and.fittings

•.Sprinklers.must.hae.quick.response.thermal..

...sensing.elements

Factory.Mutual.standards.do.not.permit.the.use.

of.nonmetallic.fire.sprinkler.piping.in.areas.where.

seismic.protection.is.required

The.design.and.installation.details.are.as.follows:

(a)..Occupancy.must.be.per.Data.Sheet.3-26,.Table..

2,.Section.L,.with.smooth.flat.horizontal.ceilings,..

a.maximum.ceiling.height.of.10.ft.(3.m),.and..

other.installation.details.per.FM.Data.Sheet.2-.

8N,.Installation.of.Sprinkler.Systems..Examples.of..

these.occupancies.include.apartments,..

restaurants,.schools,.hospitals,.libraries,.offices,.etc

(b).The.following.FM.Approed.sprinklers.must.be.used:

. 1).Extended.coerage.light.hazard.(ECLH)..

. control.mode.specific.application..

. sprinklers.with.minimum.flow.or.pressure..

. established.for.the.sprinkler.as.coered..

. in.Data.Sheet.2-8N

. 2).Quick.response.control.mode.density..

. area.sprinklers.with.a.minimum.density..

. of.01.gpm/ft2.(4.mm/min)

. 3).Residential.sprinklers.with.a.minimum.

. 01.gpm/ft2.(4.mm/min)

Note:.The.EC-25.extended.coerage.control.mode.

density.area.sprinkler.is.excluded

For.extended.coerage,.light.hazard.sprinklers,.

locate.the.sprinklers.as.recommended.in.Data.

Sheet.2-8N.For.quick.response,.non-extended.

coerage.sprinklers,.locate.the.sprinklers.so.the.

deflectors.are.no.more.than.8.in.(100.mm).below.

the.ceiling.For.residential.sprinklers,.locate.the.

sprinklers.per.the.manufacturer’s.instructions

. (c).BlazeMaster ® .fire.sprinkler.products.may.

be.used.exposed.as.a.ertical.riser..In.this.

installation,.there.needs.to.be.a.sprinkler.(of.

the.same.type.as.in.the.area.being.protected).

located.adjacent.to.and.no.further.than.1.ft.

(03.m).from.the.riser.The.design.flow.is.the...

same.as.for.the.other.sprinklers;.howeer,.this.

sprinkler.cannot.be.used.as.part.of.the.design.

area,.but.its.flow.must.be.included.in.the.total.

hydraulic.design

. Fire-rated,.non-remoable.ceilings.are.not.

required.

. In.addition.Factory.Mutual.has.approed.the.

use.of.BlazeMaster ® .CPvC.pipe.in.combination.

with.the.Soffi-SteelTM*.coering.system.Soffi-Steel.

is.manufactured.by.Grice.Engineering.

The Loss Prevention Council

Use of BlazeMaster ® CPVC Fire Sprinkler Systems

in Accordance with The Loss Prevention Council

(LPC) Section 21.1: Part 5 “List of Approved Fire and

Security Products and Services” and Section 5 of BS

5306: Part II

The.Loss.Preention.Certification.Board.Listing.is.as.

follows:.

1..The.‘scope.of.use’.of.plastic.pipe.should.be...

agreed.between.the.purchaser,.authority.haing..

 jurisdiction,.and/or.insurer.

2..Use.of.plastic.pipe.and.fittings.is.subject.to.water..

authority.agreement.for.the.territory.concerned.

3..LPCB.Approed.quick.response.sprinklers.shall.be...

used.with.exposed.(ie.fire.exposure).plastic..

pipe.and.fittings.

4..Plastic.pipe.and.fittings.are.suitable.for.use.only..

with.wet.pipe.systems.

5..Care.should.be.exercised.to.ensure.that.joints..

are.adequately.cured,.in.accordance.with.the..

manufacturer’s.installation.instructions,.prior.to..

pressurization.

6..Plastic.pipe.and.fittings.shall.not.be.installed..

outdoors.

7..Where.plastic.pipe.and.fittings.are.exposed..

(ie.fire.exposure),.the.system.shall.be.installed.

close.to.a.flat.ceiling.construction.

10Lubrizol

*Soffi-Steel.is.a.trademark.of.Grice.Engineering

Page 11: Blaze Ng

7/30/2019 Blaze Ng

http://slidepdf.com/reader/full/blaze-ng 11/32

8..Sprinkler.systems.which.employ.plastic.pipe.and..

fittings.shall.be.designed.where.possible.to..

ensure.no.‘no.flow’.sections.of.pipework.in.the..

eent.of.sprinkler.operation

The.Loss.Preention.Certification.Board.listing.applies.

to.Light.Hazard.Classifications.BS.5306:.Part.2,.Section.

two,.paragraph.52.which.fall.within.the.scope.of.

NFPA.13,.13R.and.13D

In.addition,.BlazeMaster ® .fire.sprinkler.systems..

can.be.installed.in.certain.ordinary.classification..

(BS.5306:.Part.2,.Section.two,.paragraph.53).such.

as.offices,.retail.shops.and.department.stores.when.

installed.in.accordance.with.Section.211:.Part.5.

of.LPC.“List.of.Approed.Fire.and.Security.Products.

and.Serices”

BlazeMaster ® .pipe.and.fittings.should.not.be..

used.in.high.hazard.applications.(BS.5306:.Part.2,..

Section.two,.paragraph.54).and.ordinary.hazard.

applications.where.the.fuel.load.or.rate.of.heat.

release.is.high,.such.as.boiler.rooms,.kitchens,.

manufacturing.areas,.and.certain.warehouse.

applications

Sprinkler Head Temperature Ratings

BlazeMaster ® .pipe.and.fittings.shall.be.used.

in.sprinkler.systems.employing.sprinkler.heads.

rated.225°F.(107°C).when.installed.concealed.

(protected).in.accordance.with.the.Listing.Sprinkler.

temperature.ratings.for.exposed.installations.are.indicated.in.the.indiidual.sections.of.this.manual

Temperature/Pressure Rating

BlazeMaster ® .pipe.and.fittings.(3/4".–.3".(20.–.80.mm).

are.rated.for.continuous.serice.of.175.psi.(1207.

kPa).at.150°F.(65°C)..BlazeMaster ® .pipe.and..

fittings.are.suitable.for.use.in.areas.where.ambient.

temperatures.are.within.the.range.of.35°F.(2°C).to.

150°F.(65°C)..BlazeMaster ® .pipe.can.be.installed.in.

an.area,.such.as.an.attic,.where.the.temperature.

will.exceed.150°F.(65°C).if.entilation.is.proided.or.

if.insulation.is.used.around.the.pipe.to.maintain.a.

cooler.enironment..BlazeMaster ® .piping.systems.

must.be.laid.out.so.that.the.piping.is.not.closely.

exposed.to.deices.that.generate.heat.in.excess..

of.150°F.(65°C).such.as.light.fixtures,.ballasts.and.

steam.lines..If.the.installation.is.in.an.area.subject.

to.freezing.temperatures,.the.sprinkler.system.must..

be.protected.from.freezing..A.frozen.system.will.not.

only.be.deactiated,.but.the.pressures.that.may.

build.up.can.cause.the.sprinkler.heads.to.open.or.

damage.the.pipes.

Combustible Concealed Installations

BlazeMaster ® .pipe.and.fittings.must.neer.be.

installed.in.combustible.concealed.spaces.

requiring.sprinklers,.as.referenced.in.NFPA.13..

EXCEPTION:.Specially.listed.sprinkler.heads.exist.that.hae.been.tested.and.are.listed.for.

use.with.BlazeMaster ® .products.in.combustible.

concealed.spaces.requiring.sprinklers..

When.using.BlazeMaster ® .products.in.these.

applications.always.follow.the.sprinkler.head.

manufacturers’.installation.guidelines.

Similarly.there.are.specially.listed.sprinkler.

heads.that.hae.been.tested.and.are.listed.

for.use.with.BlazeMaster ® .products.in.attics.

that.require.sprinklers.The.sprinkler.head.

manufacturers’.installation.guidelines.must.be.followed.when.using.BlazeMaster ® .pipe.and.

fittings.with.these.sprinkler.heads

NFPA 13R and 13D 

NFPA.13R.and.13D.permit.the.omission.of.sprinklers.

from.combustible.concealed.spaces.and.

BlazeMaster ® .pipe.and.fittings.may.be.installed.

in.these.areas.when.sprinklering.residential.

occupancies.according.to.these.standards

Air PlenumsBlazeMaster ® .pipe.and.fittings.are.approed.for.use.

in.air.plenums..BlazeMaster ® .pipe.and.fittings.hae.

been.inestigated.by.UL.per.the.requirements.of.UL.

1887.and.found.to.comply.with.the.combustibility.

requirements.for.thermoplastic.sprinkler.pipe.as.

described.in.the.Standard.for.Installation.of.Air.

Conditioning.and.ventilating.Systems,.NFPA.90A.

and.arious.model.mechanical.codes

Note:.BlazeMaster ® .pipe.and.fittings.may.be.

installed.in.the.plenum.adjacent.to,.but.not.oer,.an.opening.in.the.ceiling.such.as.entilation.grills

Canadian Installations (ULC & C-UL) 

BlazeMaster ® .CPvC.products.are.listed.under.CAN/

ULC.Standard.S1022M.for.flame.spread.of.5,.smoke.

deelopment.of.15,.and.fuel.contribution.of.

0,.meeting.the.National.Building.Code.of.Canada

11 Lubrizol

Page 12: Blaze Ng

7/30/2019 Blaze Ng

http://slidepdf.com/reader/full/blaze-ng 12/32

Ordinary Hazard Installations

Section.6362.of.NFPA.13.(2007.Edition).permits..

the.use.of.pipe.or.tube.listed.for.light.hazard.

occupancies.to.be.installed.in.ordinary.hazard.

rooms.of.otherwise.light.hazard.occupancies.

where.the.room.does.not.exceed.400.ft 2.(37.

m2)..BlazeMaster ® .CPvC.pipe.and.fittings.can.be.

installed.in.these.installations.in.accordance.with.

the.manufacturer’s.installation.instructions.and.this.

design.manual

Garage Installations

When.installed.concealed,.BlazeMaster ® .CPvC.

pipe.and.fittings.may.be.used.to.protect.13R.

garages.per.the.following.requirements:

1. Minimum.protection.shall.consist.of.either..

one.layer.of.3/8".(95.mm).thick.gypsum.or..

1/2".(127.mm).thick.plywood

2. Listed.pendent.or.sidewall.sprinklers.with.a.

maximum.temperature.rating.of.225°F.(107°C).

shall.be.utilized..All.sprinklers.shall.be..

installed.per.the.manufacturer’s.published.

installation.instructions

3. The.system.shall.be.installed.per.the.

requirements.of.NFPA.13R

4. The.BlazeMaster ® .CPvC.sprinkler.pipe.and.

fittings.shall.be.installed.per.the.manufacturer’s.installation.instructions.and.this.design.manual

Note:..NFPA.13D,.Section.864.(2007.Edition)..

states:.“Sprinklers.shall.not.be.required.in.garages,.

open.attached.porches,.carports,.and.similar.

structures"..Since.sprinklers.are.not.required.in.NFPA.

13D.garages,.these.installations.do.not.fall.within.

the.scope.of.the.Listing..Howeer,.BlazeMaster ® .

CPvC.pipe.and.fittings.may.be.installed.in.NFPA.13D.

garages.with.the.approal.of.the.local.authority.

haing.jurisdiction

System Risers in NFPA 13, 13R and13D Applications

BlazeMaster ® .CPvC.pipe.and.fittings.may.be.used.

as.system.risers.in.accordance.with.NFPA.13,.13D.

and.13R.when.subject.to.the.following.limitations:

1. When.installed.protected.(concealed),.the.

minimum.protection.shall.consist.of.either.one.

layer.of.3/8.in.(95.mm).thick.gypsum.wallboard.

or.1/2.in.(127.mm).thick.plywood

2. When.installed.without.protection.(exposed),.

the.following.limitations.shall.apply:

Note:.Only.NFPA.13R.and.13D.applications.may.be.

installed.without.protection.(exposed)

a). The.riser.shall.be.installed.below.a.smooth,..

flat,.horizontal.ceiling.construction.A.Listed.

residential.pendent.sprinkler.is.to.be.installed.

with.its.deflector.at.the.distance.from.the.

ceiling.specified.in.the.sprinkler.Listing

OR

. The.riser.shall.be.installed.below.a.horizontal.

unfinished.basement.ceiling.(in.accordance.

with.NFPA.13D).constructed.utilizing.nominal..

2.in.x.10.in.or.nominal.2.in.x.12.in.exposed.solid.

wood.joists.on.16.in.centers..A.Listed.residential.pendent.sprinkler.is.to.be.installed.with.its.

deflector.a.maximum.of.1-3/4.in..

below.the.bottom.of.the.solid.wood.joist..

in.anticipation.of.future.installation.of.a..

finished.ceiling

. •..When.installing.BlazeMaster ® .CPvC.pipe.and..

fittings.in.conjunction.with.2.in.x.12.in.solid..

wood.joists,.the.maximum.system.working.

pressure.under.flowing.conditions.shall.not.

exceed.100.psi.and.the.maximum.system.working.pressure.under.static.(nonflowing).

conditions.shall.not.exceed.175.psi.

b). A.Listed.residential.pendent.sprinkler.is.to.hae.

a.maximum.temperature.rating.of.155°F.and.a.

minimum.K-factor.of.30.and.is.to.be.installed.

at.a.maximum.horizontal.distance.of.12.inches.

from.the.centerline.of.the.riser.The.system.is.to.

be.designed.based.upon.the.Listed.flows.for.

the.sprinkler.selected.except.that.the.flow.for.a.

single.sprinkler.or.for.multiple.sprinklers.flowing..

is.to.be.not.less.than.11.gpm.per.sprinkler.

c). The.riser.shall.be.supported.ertically.within..

2.feet.of.the.ceiling.or.bottom.of.the.joist.

d). The.minimum.riser.diameter.shall.be.1.in.and.

the.maximum.riser.diameter.shall.be.2.in

e). The.maximum.distance.between.the.wall(s)..

and.the.outside.surface.of.the.riser.pipe.shall..

be.11 ⁄ 2.in

12Lubrizol

Page 13: Blaze Ng

7/30/2019 Blaze Ng

http://slidepdf.com/reader/full/blaze-ng 13/32

f). All.solent.cement.joints.shall.be.made.with.

BlazeMaster ® .One.Step.Solent.Cement..

(TFP-500,.CSC-500,.HvC-500,.BM-5)

3. The.system.shall.be.installed.per.the.

requirements.of.NFPA.13,.Sections.925..

(2007.Edition),.Support.of.Risers

4. The.BlazeMaster ® .CPvC.sprinkler.pipe.and.

fittings.shall.be.installed.per.the.manufacturer's.

installation.and.design.manual

5. Risers.shall.be.supported.by.pipe.clamps.or.by.

hangers.located.on.the.horizontal.connection.

close.to.the.riser.Only.Listed.hangers.and.

clamps.shall.be.used

6. vertical.lines.must.be.supported.at.interals,.

described.in.7.&.8.below,.to.aoid.placing.

excessie.load.on.a.fitting.at.the.lower.end..

Do.this.by.using.riser.clamps.or.double.bolt.pipe.

clamps.Listed.for.this.serice.The.clamps.must.not.exert.compressie.stresses.on.the.pipe..

It.is.recommended.that.the.clamps.should..

be.located.just.below.a.fitting.so.that.the.

shoulder.of.the.fitting.rests.against.the.clamp..

If.necessary,.a.coupling.can.be.modified..

and.adhered.to.the.pipe.as.a.bearing.support.

such.that.the.shoulder.of.the.fitting.rests.on..

the.clamp.Follow.the.manufacturer's.

recommended.cure.time

.

WARNING:.Modified.riser.collar.shall.only.be.

used.to.proide.support.to.the.riser.and.shall.not.be.used.to.join.two.pieces.of.pipe

7. Do.not.use.riser.clamps.that.squeeze.the.pipe.

and.depend.on.compression.of.the.pipe.to.

support.the.weight

8. Hangers.and.straps.shall.not.compress,.distort,.

cut.or.abrade.the.piping.and.shall.allow.for.

free.moement.of.the.pipe.to.allow.for.thermal.

expansion.and.contraction

9. Maintain.ertical.piping.in.straight.alignment.

with.supports.at.each.floor.leel,.or.at.10.feet.

(305.m).interals,.whicheer.is.less

10. CPvC.risers.in.ertical.shafts.or.in.buildings.with.

ceilings.oer.25.feet.(762.m),.shall.be.aligned.

straightly.and.supported.at.each.floor.leel,.or.at.10.feet.(305.m).interals,.whicheer.is.less

Underground Water Pressure Service

Both.pipe.and.fittings.may.be.used.in.underground.

water.pressure.serice.installations.per.the.following.

requirements:

1. ASTM.D.2774,.Standard.Recommended.

Practice.for.Underground.Installation.of.

Thermoplastic.Pressure.Piping,

2. ASTM.F.645,.Standard.Guide.for.Selection,.

Design.and.Installation.of.Thermoplastic.Water.

Pressure.Piping.Systems

3. The.system.shall.be.installed.per.the.

requirements.of.NFPA.24

4. The.BlazeMaster ® .CPvC.sprinkler.pipe.and.

fittings.shall.be.installed.per.the.manufacturer’s.

installation.instructions.and.this.design.manual

Thrust Blocking 

If.thrust.blocks.are.utilized.they.should.be.designed.

per.NFPA.24,.Section.1082.(2007.Edition)

Note:..BlazeMaster ® .fire.sprinkler.systems.utilize.a.

solent.cement.joining.method..As.such,.thrust.

blocks.are.not.required.with.BlazeMaster ® .CPvC.

pipe.and.fittings.in.underground.water.pressure.

serice..Reference.NFPA.24,.Section.A10811..

(2007.Edition).

13 Lubrizol

Side View

Cut Perpendicular to Seat

Top View

CutAboveSeat

Figure 1: Field Modification for Riser Collar for Vertical Use

Figure 2: Coupling Modification for Riser Collar

Modified

BlazeMaster ® CPVC

Coupling Adhered

to Pipe

Snug but not Tight

Strut to Wall

Plastic

Coupling

or Collar

Adhered

to Pipe

Page 14: Blaze Ng

7/30/2019 Blaze Ng

http://slidepdf.com/reader/full/blaze-ng 14/32

Trenching 

The.trench.should.be.of.adequate.width.to.allow.

conenient.installation,.while.at.the.same.time.

being.as.narrow.as.possible..Minimum.trench.

widths.may.be.utilized.by.joining.pipe.outside.of.

the.trench.and.lowering.it.into.the.trench.after.

adequate.joint.strength.has.been.achieed..

(NOTE:.Refer.to.the.recommended.set.and.cure.time.tables.for.solent.cement.joints)..Trench.widths.

will.hae.to.be.wider.where.pipe.is.joined..

in.the.trench.or.where.thermal.expansion.and.

contraction.is.a.factor.See.section.titled.“Snaking..

of.Pipe”

•. Water.filled.pipe.should.be.buried.at.least..

12.inches.(305.mm).below.the.maximum.

expected.frost.line

•. It.is.recommended.that.BlazeMaster ® .piping.

be.run.within.a.metal.or.concrete.casing.when.it.is.installed.beneath.surfaces.that.are.subject.

to.heay-weight.or.constant.traffic.such.as.

roadways.and.railroad.tracks

The.trench.bottom.should.be.continuous,.

relatiely.smooth.and.free.of.rocks..Where.ledge.

rock,.hardpan.or.boulders.are.encountered,.it.is.

necessary.to.protect.the.pipe.from.damage..Use..

a.minimum.of.4.inches.(102.mm).of.clean.soil,..

sand,.crushed.stone.or.other.approed.material.as.

referenced.in.ASTM.D.2774

Sufficient.coer.must.be.maintained.to.keep.external.

stress.leels.below.acceptable.design.stress.Reliability.

and.safety.of.serice.is.of.major.importance.in.

determining.minimum.coer..Local,.state.and.

national.codes.may.also.goern

Snaking of Pipe 

After.BlazeMaster ® .CPvC.pipe.has.been.solent.

welded,.it.is.adisable.to.snake.the.pipe.according.

to.the.below.recommendations.beside.the.trench.

during.its.required.curing.time..BE ESPECIALLY

CAREFUL NOT TO APPLY ANY STRESS THAT WILL

DISTURB THE UNDRIED JOINT...This.snaking.is.

necessary.in.order.to.allow.for.any.anticipated.

thermal.moement.that.could.take.place.in.the.

newly.joined.pipeline

Snaking.is.particularly.necessary.on.the.lengths.

that.hae.been.solent.welded.during.the.late.

afternoon.of.a.hot.day,.because.their.drying.time.

will.extend.through.the.cool.of.the.night.when.

thermal.contraction.of.the.pipe.could.stress.

the.joints.to.the.point.of.pull.out..This.snaking.is.

also.especially.necessary.with.pipe.that.is.laid.in.its.trench.(necessitating.wider.trenches.than.

recommended).and.is.back-filled.with.cool.earth.

before.the.joints.are.thoroughly.dry

14Lubrizol

2 Loop Lengths

1 Loop Length

Offset

Offset

CenterlinePipe

Figure 3: Snaking of Pipe

Loop Offset in Inches for Contraction:

Maximum Temperature Variation, °F, Between Time of Solvent Welding and Final Use

Loop Length 10° 20° 30° 40° 50° 60° 70° 80° 90° 100°

.20.Feet. 3". 4". 5". 5". 6". 6". 7". 7". 8". 8"

.50.Feet. 7". 9". 11". 13". 14". 16". 17". 18". 19". 20"

.100.Feet. 13". 18". 22". 26". 29". 32". 35". 37". 40". 42"

Loop Offset in mm for Contraction:

Maximum Temperature Variation, °C, Between Time of Solvent Welding and Final Use

Loop Length 5° 10° 15° 20° 25° 30° 35° 40° 45° 50°

.5.Meters. 65. 83. 95. 105. 114. 123. 133. 143. 154. 164

.15.Meters. 164. 219. 266. 307. 343. 377. 409. 440. 469. 498

.30.Meters. 314. 424. 522. 609. 687. 758. 823. 884. 943. 999

Page 15: Blaze Ng

7/30/2019 Blaze Ng

http://slidepdf.com/reader/full/blaze-ng 15/32

Backfilling 

Note: Underground pipe shall be thoroughly

inspected and tested for leaks prior to backfilling.

Backfill material should be placed over pipe

sections only, leaving the joints exposed during

testing...

Ideally,.backfilling.should.only.be.done.early.in.the.

morning.during.hot.weather.when.the.line.is.fully.

contracted.and.there.is.no.chance.of.insufficiently.

dried.joints.being.subjected.to.contraction.stresses

The.pipe.should.be.uniformly.and.continuously.

supported.oer.its.entire.length.on.firm,.stable.

material..Blocking.should.not.be.used.to.change.

pipe.grade.or.to.intermittently.support.pipe.across.

excaated.sections

Pipe.is.installed.in.a.wide.range.of.sub-soils..These.

soils.should.not.only.be.stable.but.applied.in.such.a.

manner.to.physically.shield.the.pipe.from.damage..

Attention.should.be.gien.to.local.pipe.laying.

experience.that.may.indicate.particular.pipe.

bedding.problems

Backfill.materials.free.of.rocks.with.a.particle.

size.of..1/2".(127.mm).or.less.should.be.used.to.

surround.the.pipe.with.6".(152.mm).to.8".(203.mm).

of.coer..It.should.be.placed.in.layers..Each.soil.

layer.should.be.sufficiently.compacted.to.uniformly.

deelop.lateral.passie.soil.forces.during.the.backfill.

operation..It.may.be.adisable.to.hae.the..

pipe.under.hydraulic.pressure,.15.to.25.psi..

(103.–.172.kPa).during.the.backfilling..

vibratory.methods.are.preferred.when.compacting.

sand.or.grael.Best.results.are.obtained.when.the.

soils.are.in.a.nearly.saturated.condition..Where.

water.flooding.is.used,.the.initial.backfill.should.be.

sufficient.to.insure.complete.coerage.of.the.pipe..

Additional.material.should.not.be.added.until.the.

water.flooded.backfill.is.firm.enough.to.walk.on..

Care.should.be.taken.to.aoid.floating.the.pipe

Sand.and.grael.containing.a.significant..

proportion.of.fine-grained.material,.such.as.silt.and.

clay,.should.be.compacted.by.hand.or,.preferably.

by.mechanical.tamper

The.remainder.of.the.backfill.should.be.placed..

and.spread.in.approximately.uniform.layers.in.such.

a.manner.to.fill.the.trench.completely.so.that.there.will.be.no.unfilled.spaces.under.or.about.the.rocks.

or.lumps.of.earth.in.the.backfill..Large.or.sharp.

rocks,.frozen.clods.and.other.debris.greater.than..

4".(102.mm).in.diameter.should.be.remoed..

Rolling.equipment.or.heay.tampers.should.only..

be.used.to.consolidate.the.final.backfill

Outdoor Installations

BlazeMaster ® .pipe.and.fittings.are.not.listed.for.

exposed,.outdoor.applications

Updated UL Listing Information

BlazeMaster ® .fire.sprinkler.system’s.listings..

can.change.For.a.current.list.log.on.to.www

blazemastercom

Product Rating, Capabilities andMaterial Properties

Pressure Rating

BlazeMaster ® .pipe.and.fittings.(3/4".(20mm).–..

3".(80.mm)).are.rated.for.continuous.serice.of..175.psi.(1207.kPa).at.150°F.(65°C)

Pipe Dimensions and Weights

BlazeMaster ® .pipe.is.produced.in.SDR.135.

dimensions.SDR,.or.standard.dimensional.

ratio,.means.the.pipe.wall.thickness.is.directly.

proportional.to.the.outside.diameter..This.results.in.

all.diameters.carrying.the.same.pressure.capability..

BlazeMaster ® .pipe.is.produced.to.the.specifications.

of.ASTM.F.442..BlazeMaster ® .fittings.are.produced.

to.ASTM.F.437,.F.438,.or.F.439.specifications.depending.on.the.size.and.configuration

15 Lubrizol

Page 16: Blaze Ng

7/30/2019 Blaze Ng

http://slidepdf.com/reader/full/blaze-ng 16/32

Hydraulic Design

C Factor  

Hydraulic.calculations.for.the.sizing.of.BlazeMaster ® .

pipe.and.fitting.shall.be.calculated.using.the.

Hazen-Williams.C.factor.of.150

Pipe Friction Loss 

Pipe.friction.loss.calculations.shall.be.made.

according.to.NFPA.13.Section.224.(2007.Edition)

Fittings Friction Loss 

The.following.table.shows.the.allowance.for.friction.

loss.for.fittings,.expressed.as.equialent.length..

of.pipe

16Lubrizol

Physical and Thermal Properties of BlazeMaster ® CPVC

Property CPVC ASTM

.Specific.Graity. 153. D.792

.IZOD.Impact.Strength.(ft.lbs/inch,.notched). 30. D.256A

.Modulus.of.Elasticity,[email protected]°F,.psi. 423.x.105. D.638

.Ultimate.Tensile.Strength,.psi. 8,000. D.638

.Compressie.Strength,.psi. 9,600. D.695

.Poisson’s.Ratio. 35.-.38. -

[email protected]°F,.psi. 2,000. D.1598

.Hazen-Williams.C.Factor. 150. _

.Coefficient.of.Linear.Expansion.in/(in.°F). 34.x.10-5.. D.696

.Thermal.Conductiity.BTU/hr/ft2/°F/in. 095.. C.177

.Limiting.Oxygen.Index. 60%. D.2863

.Electrical.Conductiity. Non.Conductor

Allowance for Friction Loss in Fittings

(SDR 13.5 Equivalent Pipe)

  3/4" (20mm) 1" (25mm) 1 1/4" (32mm) 1 1/2" (40mm) 2" (50mm) 2 1/2" (65mm) 3" (80mm)

.Tee.Branch. 3'.(0914m). 5'.(152m). 6'.(183.m). 8'.(244m). 10'.(305m). 12'.(366m). 15'.(457m)

.Elbow.90°. 7'.(213m). 7'.(213m). 8'.(244m). 9'.(274m). 11'.(335m). 12'.(366m). 13'.(396m)

.Elbow.45°. 1'.(0305m). 1'.(0305m). 2'.(0610m). 2'.(0610m). 2'.(0610m). 3'.(0914m). 4'.(1220m)

.Coupling. 1'.(0305m). 1'.(0305m). 1'.(0305m). 1'.(0305m). 1'.(0305m). 2'.(0610m). 2'.(0610m)

.Tee.Run. 1'.(0305m). 1'.(0305m). 1'.(0305m). 1'.(0305m). 1'.(0305m). 2'.(0610m). 2'.(0610m)

BlazeMaster ® Pipe Dimensions and Weights

SDR 13.5 (ASTM F 442)

Nominal Average Average Pounds Kilograms Pounds Kilograms

Size OD ID Per Foot Per Meter Per Foot Per Meter

Inches mm Inches mm Inches mm Empty Empty H2O Filled H2O Filled

. 3/4. 200. 1050. 267. 874. 222. 0168. 0250. 0428. 0637

. 1. 250. 1315. 334. 1101. 280. 0262. 0390. 0675. 1005

. 1.1/4. 320. 1660. 422. 1394. 354. 0418. 0622. 1079. 1606

. 1.1/2. 400. 1900. 483. 1598. 406. 0548. 0816. 1417. 2109

. 2. 500. 2375. 603. 2003. 509. 0859. 1278. 2224. 3310

. 2.1/2. 650. 2875. 730. 2423. 615. 1257. 1871. 3255. 4844

. 3. 800. 3500. 889. 2950. 750. 1867. 2778. 4829. 7186

Note:.The.aboe.aerage.OD.and.aerage.ID.information.is.per.ASTM.F442.Check.with.indiidual.manufacturers.for.actual.OD.and.ID.information

Page 17: Blaze Ng

7/30/2019 Blaze Ng

http://slidepdf.com/reader/full/blaze-ng 17/32

Lubrizol17

Thermal Expansion and Contraction

BlazeMaster ® .CPvC.pipe,.like.all.piping.materials,.

expand.and.contract.with.changes.in.temperature.

The.coefficient.of.linear.expansion.is:..00000340.

inch/inch-°F.(0000061.cm./.cm.°C)..Lineal.

expansion.is.the.same.for.all.pipe.diameters

A 25°F change in temperature will cause an

expansion of 1/2 inch for a 50 foot straight run

of BlazeMaster ® pipe...For.most.operating.and.

installation.conditions,.expansion.and.contraction.

can.be.accommodated.at.changes.in.direction.

of.the.pipe.run..Howeer,.in.certain.instances,.

expansion.loops.or.offsets.may.be.required.when.

installing.long,.straight.runs.of.pipe

Thermal Expansion in Centimeters

Length of Run in Meters

. 1. 2. 4. 6. 8. 10. 12. 14. 16. 18. 20. 30. 40. 50

Thermal Expansion ∆ L (cm.)

. 10. 006. 012. 024. 037. 049. 061. 073. 086. 098. 110. 122. 184. 245. 306

.. 15. 009. 018. 037. 055. 073. 092. 110. 129. 147. 165. 184. 275. 367. 459.

. 20. 012. 024. 049. 073. 098. 122. 147. 171. 196. 220. 245. 367. 490. 612.

. 25. 015. 031. 061. 092. 122. 153. 184. 214. 245. 275. 306. 459. 612. 765.

. 30. 018. 037. 073. 110. 147. 184. 220. 257. 294. 330. 367. 551. 734. 918.

. 35. 021. 043. 086. 129. 171. 214. 257. 300. 343. 386. 428. 643. 857. 1071.

. 40. 024. 049. 098. 147. 196. 245. 294. 343. 392. 441. 490. 734. 979. 1224.

Temp.Change∆ T °C

Thermal Expansion in Inches

Length of Run in Feet

. 5. 10. 15. 20. 25. 30. 35. 40. 45. 50. 70. 90. 120. 160

Thermal Expansion ∆ L (in.)

. 20. 04. 08. 12. 16. 20. 24. 29. 33. 37. 41. 57. 73. 98. 131

. 30. 06. 12. 18. 24. 31. 37. 43. 49. 55. 61. 86. 110. 147. 196

. 40. 08. 16. 24. 33. 41. 49. 57. 65. 73. 82. 114. 147. 196. 261

. 50. 10. 20. 31. 41. 51. 61. 71. 82. 92. 102. 143. 184. 245. 326

. 60. 12. 24. 37. 49. 61. 73. 86. 98. 110. 122. 171. 220. 294. 392

. 70. 14. 29. 43. 57. 71. 86. 100. 114. 129. 143. 200. 257. 343. 457

. 80. 16. 33. 49. 65. 82. 98. 114. 131. 147. 163. 228. 294. 392. 522

. 90. 18. 37. 55. 73. 92. 110. 129. 147. 165. 184. 257. 330. 441. 588

. 100. 20. 41. 61. 82. 102. 122. 143. 163. 184. 204. 286. 367. 490. 653

Temp.Change∆ T °F

The formula to calculate the amount of thermal expansion or contraction is ∆L = 12 x e x L x ∆T

Where:.e.=.34.x.10-5.inch/inch-°F;.L.=.Length.of.run.in.feet;.

............∆T.=.Temperature.change.°F;.∆L.=.Change.in.length.due.to.change.in.temperature.

Page 18: Blaze Ng

7/30/2019 Blaze Ng

http://slidepdf.com/reader/full/blaze-ng 18/32

Lubrizol

Pipe Deflection

BlazeMaster ® .fire.sprinkler.piping.is.inherently.

ductile.allowing.it.to.be.deflected,.within.

permissible.limits,.around.or.away.from.objects.

during.installation,.which.can.reduce.installation.

time..This.ductility.allows.for.greater.freedom.of.

design.and.lower.installed.cost..The.maximum.

installed.deflections.for.BlazeMaster ® .piping.are.as.

follows:

Maximum Installed Deflections

(One End Restrained)

18

6"

MIN

6"

MIN

= Hanger or Guide

= Restraint

Long Run of Pipe

Loop Offset Change of Direction

2/5

1/4

1/41/5

1/2

Figure 4: Expansion Loop and Offset Configuration

Figure 5: One End Restrained

L ft. (m)

d in.(cm)

Modulus of Elasticity & Stress vs. Temperature

Temperature F 73 80 90 100 110 120 140 150

Modulus ofElasticity 4.23 4.14 3.99 3.85 3.70 3.55 3.23 3.08“E” x 105 (psi)

WorkingStress 2,000 1,875 1,715 1,560 1,415 1,275 1,000 875

“S” (psi)

=

= Loop length (in.)

= Modulus of elasticity at maximum temperature (psi)

= Working stress at maximum temperature (psi)

= Outside diameter of the pipe (in.)

= Change in length due to change in temperature (in.)

3 ED (∆L)

2S

∆L

E

S

D

Expansion Loop Formula

Page 19: Blaze Ng

7/30/2019 Blaze Ng

http://slidepdf.com/reader/full/blaze-ng 19/32

Lubrizol19

. 2’. 5’. 7’. 10’. 12’. 15’. 17’. 20’. 25’. 30’. 35’. 40’. 45’. 50’

Permissible Bending Deflections SDR 13.5 (73°F) in Inches

. 13. 78. 154. 313. 451. 705. 906. 1254. 1959. 2821. 3839

. 10. 63. 123. 250. 360. 563. 723. 1001. 1564. 2252. 3066. 4004

. 08. 50. 97. 198. 285. 446. 573. 793. 1239. 1784. 2428. 3172. 4014

. 07. 43. 85. 173. 249. 390. 501. 693. 1082. 1559. 2122. 2771. 3507. 4330

. 06. 35. 68. 139. 200. 312. 400. 554. 866. 1247. 1697. 2217. 2806. 3464

. 05. 29. 56. 114. 165. 258. 331. 458. 715. 1030. 1402. 1831. 2318. 2862

. 04. 24. .46. 94. 135. 212. 272. 376. 588. 846. 1152. 1504. 1904. 2351

Pipe Length in Feet

Pipe

Size

3/4"

1"

1.1/4"

1.1/2"

2"

2.1/2"

3"

Pipe Length in Meters

. 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14

Permissible Bending Deflections SDR 13.5 (23°C) in cm

20.mm. 86. 343. 771. 1371. 2142. 3084. 4198. 5483. 6940. 8567.1,0367

25.mm. 68. 274. 616. 1095. 1710. 2463. 3352. 4378. 5541. 6841. 8278. 9851

32.mm. 54. 217. 488. 867. 1355. 1951. 2655. 3468. 4390. 5419. 6557. 7804. 9158

40.mm. 47. 189. 426. 758. 1184. 1704. 2320. 3030. 3835. 4735. 5729. 6818. 8002. 9280

50.mm. 38. 152. 341. 606. 947. 1364. 1856. 2424. 3068. 3788. 4583. 5454. 6401. 7424

65.mm. 31. 125. 282. 501. 782. 1126. 1533. 2003. 2534. 3129. 3786. 4506. 5288. 6133

80.mm. 26. 103. 231. 411. 643. 925. 1259. 1645. 2082. 2570. 3110. 3701. 4344. 5038

. 3. 20. 38. 78. 113. 176. 226. 311. 490. 705. 960. 1254. 1587. 1959

. 3. 16. 31. 63. 90. 141. 181. 250. 391. 563. 766. 1001. 1267. 1564

. 2. 12. 24. 50. 71. 112. 143. 198. 310. 446. 607. 793. 1004. 1239

. 2. 11. 21. 43. 62. 97. 125. 173. 271. 390. 530. 693. 877. 1082

. 1. 9. 17. 35. 50. 78. 100. 139. 216. 312. 424. 554. 701. 866

. 1. 7. 14. 29. 41. 64. 83. 114. 179. 258. 351. 458. 579. 715

. 1. 6. 12. 24. 34. 53. 68. 94. 147. 212. 288. 376. 476. 588

Pipe Length in Feet

Pipe

Size

3/4"

1"

1.1/4"

1.1/2"

2"

2.1/2"

3"

. 2'. 5'. 7'. 10'. 12'. 15'. 17'. 20'. 25'. 30'. 35'. 40'. 45'. 50'

Permissible Bending Deflections SDR 13.5 (73°F) in Inches

Maximum Installed Deflections

(Both Ends Restrained)

Figure 6: Both Ends Restrained

L ft.(m)

d in.(cm)

Pipe

Size

Page 20: Blaze Ng

7/30/2019 Blaze Ng

http://slidepdf.com/reader/full/blaze-ng 20/3220Lubrizol

Pipe Length in Meters

. 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14

Permissible Bending Deflections SDR 13.5 (23°C) in cm

20.mm. 21. 86. 193. 342. 535. 771. 1049. 1370. 1734. 2141. 2590. 3082. 3618. 4195

25.mm. 17. 68. 154. 274. 428. 616. 838. 1095. 1386. 1711. 2071. 2464. 2892. 3354

32.mm. 14. 54. 122. 217. 339. 488. 664. 867. 1097. 1354. 1639. 1950. 2289. 2654

40.mm. 12. 47. 106. 189. 296. 426. 580. 757. 958. 1183. 1432. 1704. 2000. 2319

50.mm. 09. 38. 85. 152. 237. 341. 464. 607. 768. 948. 1147. 1365. 1602. 1858

65.mm. 08. 31. 70. 125. 196. 282. 384. 501. 634. 783. 947. 1127. 1323. 1535

80.mm. 06. 26. 58. 103. 161. 231. 315. 411. 521. 643. 778. 926. 1086. 1260

Handling and Storage

BlazeMaster ® .CPvC.is.a.tough,.corrosion.resistant.

material,.but.does.not.hae.the.mechanical.

strength.of.steel..Reasonable.care.must.be.

exercised.in.handling.BlazeMaster ® .pipe.and.

fittings..They.must.not.be.dropped.or.hae.objects.

dropped.on.them..If.improper.handling.results.in.

scratches,.splits,.or.gouges,.the.damaged.section.

shall.be.cut.out.and.discarded

BlazeMaster ® .pipe.must.be.coered.with.a.non-

transparent.material.when.stored.out.of.doors.for.

extended.periods.of.time..Brief.exposure.to.direct.

sunlight.on.the.job.site.may.result.in.color.fade.but.

will.not.affect.physical.properties..BlazeMaster ® .

fittings.should.be.stored.in.their.original.containers.

to.keep.them.free.from.dirt.and.reduce.the.

possibility.of.damage..Caution.should.be.taken.

not.to.oerstack.boxes.of.BlazeMaster ® .fittings.in.

extreme.temperature.enironments.(>150°F)

Joining BlazeMaster® Pipe and Fittings

with Red One-Step Solvent Cement

Note: One-Step Cement requires no cleaner

or primer. Refer to individual manufacturers’installation instructions.

Cutting

BlazeMaster ® .pipe.can.

be.easily.cut.with.a.

ratchet.cutter,.a..

wheel-type.plastic.

tubing.cutter,.a.power.

saw.or.a.fine.toothed.

saw..To.ensure.the.pipe.

is.cut.square,.a.miter.box.is.recommended.when.

using.a.saw..A.square.cut.proides.the.surface.of.the.

pipe.with.maximum.bonding.area..If.any.indication.

of.damage.or.cracking.is.eident.at.the.pipe.end,.cut.

off.at.least..

2.inches.(508.mm).beyond.any.isible.crack.

Deburring

Burrs.and.filings.can.

preent.proper.

contact.between.

pipe.and.fitting..

during.assembly,.and.

must.be.remoed.

from.the.outside.and.

the.inside.of.the.pipe..

A.chamfering.tool.or.a.file.is.suitable.for.this.

purpose..A.slight.beel..

shall.be.placed.at.the.end.of.the.pipe.to.ease.

entry.of.the.pipe.into.the.socket.and.minimize.the.

chances.of.wiping.solent.cement.from.the.fitting.

during.insertion

Fitting Preparation

Using.a.clean,.dry.rag,.wipe.loose.dirt.and.moisture.

from.the.fitting.socket.and.pipe.end..Moisture.can.

slow.the.cure.time.and.at.this.stage.of.assembly,.

excessie.water.can.reduce.joint.strength..Check.

the.interference.fit.of.the.pipe.and.fitting..The.pipe.

should.enter.the.fitting.socket.easily.1/4.to.3/4.of.the.

way..At.this.stage,.the.pipe.should.not.bottom.out.in..

the.socket

Solvent Cement Application

Cement.shall.be.applied.(worked.into.pipe).with.an.

applicator.half.the.nominal.size.of.the.pipe.diameter..

Apply.a.heay,.een.coat.of.cement.to.the.outside.

Pipe

Size

Page 21: Blaze Ng

7/30/2019 Blaze Ng

http://slidepdf.com/reader/full/blaze-ng 21/3221 Lubrizol

pipe.end.Apply.a.medium.

coat.to.the.fitting.socket..

Pipe.sizes.11/4.inches..

(32.mm).and.aboe.shall.

always.receie.a.second.

cement.application.on.the.

pipe.end..(Apply.cement.

on.the.pipe.end,.in.the.fitting.socket,.and.on.the.pipe.again)..Only.use.solent.cements.that.hae.

been.specifically.inestigated.and.tested.for.use.with.

BlazeMaster ® .CPvC.systems.

and.approed.by.the.pipe.

and.fitting.manufacturers..

Too.much.cement.can.

cause.clogged.waterways..

Do.not.allow.excess.cement.

to.puddle.in.the.pipe.and.

fitting.assembly

Special.care.shall.be.exercised.when.assembling.BlazeMaster ® .systems.in.extremely.low.temperatures.

(below.40°F.(4°C)).or.extremely.high.temperatures.

(aboe.100°F.(38°C))..Extra.set.time.shall.be.allowed.

in.colder.temperatures..When.cementing.pipe..

and.fittings.in.extremely.cold.temperatures,.make.

certain.that.the.cement.has.not.become.lumpy.or.

has.“gelled”..Gelled.cement.must.be.discarded..In.

extremely.hot.temperatures,.make.sure.both.surfaces.

to.be.joined.are.still.wet.with.cement.when.putting..

them.together

Assembly

After.applying.

cement,.immediately.

insert.the.pipe.into.

the.fitting.socket,.

while.rotating.the.

pipe.one-quarter.

turn..Properly.align.

the.fitting.for.the.

installation.at.this.time..Pipe.must.bottom.to.the.

stop..Holding.the.assembly.for.10.to.15.seconds.to.ensure.initial.bonding..A bead of cement should be

evident around the pipe and fitting juncture. If this

bead is not continuous around the socket shoulder,

it may indicate that insufficient cement was applied...

If.insufficient.cement.is.applied,.the.fitting.must.be.

cut.out.and.discarded.

Cement.in.excess.of.the.bead.can.be.wiped.off..

with.a.rag..Care.shall.be.exercised.when.installing.

sprinkler.heads..Sprinkler.head.fittings.shall.be.

allowed.to.cure.for.a.minimum.of.30.minutes.prior.to.

installing.the.sprinkler.head..When.installing.sprinkler.

heads,.be.sure.to.anchor.or.hold.the.pipe.drop.

securely.to.aoid.rotating.the.pipe.in.preiously.

cemented.connections..Preiously.cemented.fittings.shall.also.be.permitted.to.cure.for.a.minimum.of..

30.minutes

Warning:.Sprinkler.heads.shall.be.installed.only.after.

all.the.CPvC.pipe.and.fittings,.including.the.sprinkler.

head.adapters,.are.solent.welded.and.allowed.to.

cure.for.a.minimum.of.30.minutes..Sprinkler.head.

fittings.should.be.isually.inspected.and.probed.with.

a.wooden.dowel.to.ensure.that.the.water.way.and.

threads.are.clear.of.any.excess.cement..Once.the.

installation.is.complete.and.cured.per.Table.I,.II.or.III,.

the.system.shall.be.hydrostatically.tested..Sprinklers.shall.not.be.installed.in.the.fittings.prior.to.the.fittings.

being.cemented.in.place

Note:.Safety.and.Health.Precautions..Prior.to.

using.CPvC.solent.cements,.reiew.and.follow.all.

precautions.found.on.the.container.labels,.material.

safety.data.sheet,.and.Standard.Practice.for.Safe.

Handling.ASTM.F.402

Set and Cure Times

Solent.cement.set.

and.cure.times.are.a.function.of.pipe.

size,.temperature,.

relatie.humidity,.and.

tightness.of.fit..Curing.

time.is.faster.for.drier.

enironments,.smaller.

pipe.sizes,.higher.

temperatures.and.tighter.fits..Cure.times.should.be.

increased.when.moisture.is.present.such.as.during.

cut-ins.to.lie.sprinkler.lines..The.assembly.must.be.

allowed.to.set,.without.any.stress.on.the.joint,.for.1.to.5.minutes,.depending.on.pipe.size.and.temperature..

Following.the.initial.set.period,.the.assembly.can.be.

handled.carefully, avoiding significant stresses to 

the joint...Refer.to.the..

following.tables.for.minimum.cure.times.prior.to.

pressure.testing

Page 22: Blaze Ng

7/30/2019 Blaze Ng

http://slidepdf.com/reader/full/blaze-ng 22/32

Note.1:.For.these.sizes,.the.solent.cement.can..

be.applied.at.temperatures.below.40°F.(45°C),.

howeer,.the.sprinkler.system.temperature.must..be.raised.to.a.temperature.of.40°F.(45°C).or..

aboe.and.allowed.to.cure.per.the.aboe.

recommendations.prior.to.pressure.testing

22Lubrizol

TABLE I

225 psi (1552 kPa) Test Pressure (maximum)

Ambient Temperature During Cure Period..

. 60°F.to.120°F. 40°F.to.59°F. 0°F.to.39°F.

Pipe.Size. (16°C.to.49°C). (4°C.to.15°C). (-18°C.to.4°C)

3/4".(20.mm). 1.hr. 4.hrs. 48.hrs

1".(25.mm). 11/2.hrs. 4.hrs. 48.hrs

11/4".&.11/2".(32.&.40.mm). 3.hrs. 32.hrs. 10.days

2".(50.mm). 8.hrs. 48.hrs. Note.1

21/2".&.3".(65.&.80.mm). 24.hrs. 96.hrs. Note.1

TABLE II

200 psi (1379 kPa) Test Pressure (maximum)

Ambient Temperature During Cure Period..

. 60°F.to.120°F. 40°F.to.59°F. 0°F.to.39°F.

Pipe.Size. (16°C.to.49°C). (4°C.to.15°C). (-18°C.to.4°C)

3/4".(20.mm). 45.mins. 11/2.hrs. 24.hrs

1".(25.mm). 45.mins. 11/2.hrs. 24.hrs

11/4".&.11/2".(32.&.40.mm). 11/2.hrs. 16.hrs. 120.hrs

2".(50.mm). 6.hrs. 36.hrs. Note.1

21/2".&.3".(65.&.80.mm). 8.hrs. 72.hrs. Note.1

TABLE III

100 psi (690 kPa) Test Pressure (maximum)

Ambient Temperature During Cure Period..

. 60°F.to.120°F. 40°F.to.59°F. 0°F.to.39°F.

Pipe.Size. (16°C.to.49°C). (4°C.to.15°C). (-18°C.to.4°C)

3/4".(20.mm). 15.mins. 15.mins. 30.mins

1".(25.mm). 15.mins. 30.mins. 30.mins

11/4".(32.mm). 15.mins. 30.mins. 2.hrs

Page 23: Blaze Ng

7/30/2019 Blaze Ng

http://slidepdf.com/reader/full/blaze-ng 23/3223 Lubrizol

Pressure Testing

Once.an.installation.is.completed.and.cured,.per.

the.aboe.recommendations,.the.system.should.be.

pressure.tested.at.200.psi.(1379.kPa).for.2.hours..

See.Table.II.for.curing.conditions.in.this.case..The.

system.should.be.pressure.tested.at.50.psi.(345.kPa).

in.excess.of.maximum.pressure.when.the.maximum.

system.pressure.is.to.be.maintained.in.excess.of..150.psi.(1034.kPa)..See.Table.I.for.curing.conditions.

in.this.case..This.is.in.accordance.with.the.

requirements.established.by.NFPA.Standard.13,.

Section.2421.(2007.Edition)..Sprinkler.systems.in.

one-.and.two-family.dwellings.and.mobile.homes.

may.be.tested.at.line.pressure,.Table.III.curing.

conditions,.in.accordance.with.the.requirements.

established.by.NFPA.13D,.Section.43.(2007.Edition)..

When.pressure.testing,.the.sprinkler.system.shall.be.

slowly.filled.with.water.and.the.air.bled.from.the.

highest.and.farthest.sprinkler.heads.before.pressure.testing.is.applied..Air.must.be.remoed.from.piping.

systems.(plastic.or.metal).to.preent.it.from.being.

locked.in.the.system.when.pressure.is.applied..

Entrapped.air.can.generate.excessie.surge.

pressures.that.are.potentially.damaging,.regardless.

of.the.piping.materials.used..Air.or.compressed.gas.

should.neer.be.used.for.pressure.testing..If.a.leak.

is.found,.the.fitting.must.be.cut.out.and.discarded..

A.new.section.can.be.installed.using.couplings.or.

a.union.Unions.should.be.used.in.accessible.areas.only

Estimating One-Step Solvent Cement Requirements

The.following.guidelines.are.proided.to.allow.

estimation.of.one-step.solent.cement.quantities.

needed

Fitting Size Number Number

of Joints of Joints

Per Quart Per Liter

. 3/4".(20.mm). 270. 285

. 1".(25.mm). 180. 190

.11/4".(32.mm). 130. 137

.11/2".(40.mm). 100. 106

. 2".(50.mm). 70. 74

.21/2".(65mm). 50. 53

. 3".(80mm). 40. 42

Page 24: Blaze Ng

7/30/2019 Blaze Ng

http://slidepdf.com/reader/full/blaze-ng 24/32

At.times.it.may.become.necessary.to.make.

modifications.to.existing.CPvC.fire.sprinkler..

systems.This.can.be.done.safely.when.the..

proper.procedures.are.followed.The.following.

procedure.has.been.deeloped.to.assure.that..

the.modifications.are.done.successfully

Prior.to.making.system.cut-ins.on.existing.

systems,.care.should.be.used.to.reiew.proper.

 joining.procedures.and.to.FOLLOW.CUT-IN.CURE.

SCHEDULES.to.ensure.the.highest.system.integrity.

Seeral.methods.can.be.utilized.to.tie.into.an.

existing.system.using.a.socket.style.tee.fitting.in.

combination.with.the.use.of.socket.unions,.grooed.

coupling.adapters,.and.flanges.Regardless.of.the.

method.used,.the.following.points.must.be.followed.

to.ensure.the.highest.integrity:

•. Using.proper.tools,.the.cut-in.should.be.made.

on.the.smallest.diameter.pipe.section.(that.is.

capable.of.adequately.supplying.the.system.

changes).in.close.proximity.to.the.modification.

being.made.This.approach.will.expedite.cure.

times.prior.to.pressure.testing

•. The.cut-in.connection.to.the.existing.system.

should.be.made.first,.prior.to.proceeding.with.

additional.work

•. Existing.lines.must.be.drained.adequately.prior.

to.solent.cementing.Use.a.Drain.vac.unit.to.

be.sure.all.water.is.remoed.from.the.system.

(moisture.can.slow.the.cure.time.and.reduce.

 joint.strength)..One.method.to.erify.that.the.

water.has.been.drained.from.the.system.is.to.

remoe.the.sprinkler.heads.on.each.side.of.the.

cut-in.and.allow.any.remaining.water.to.drain

•. Carefully.reiew.and.follow.manufacturer’s.

solent.cementing.procedures.for.proper.joining.

techniques.prior.to.commencing.with.cut-in.

(pipe.must.be.cut.square.to.proper.length,.

deburred,.beeled.and.dry.to.ensure.proper.

insertion.depth.and.highest.integrity)

•. Carefully.measure.and.cut.pipe.to.proper..

length.to.ensure.complete.insertion.during.

assembly.(check.the.interference.fit.of.the.

components.being.joined)

•. Note:.During.assembly.of.the.cut-in.tee.(and.

other.components).it.is.important.to.make.a..

one-quarter.turn.when.inserting.the.pipe.into..

the.fitting.per.the.manufacturer’s.assembly.

instructions,.particularly.on.11

 ⁄ 2

".pipe.sizes.and.larger.This.may.require.the.use.of.seeral.

components.assembled.in.combination.with..

the.cut-in.tee.to.create.a.short.spool.piece.

assembly.This.can.be.accomplished.by.using.

socket.unions,.flanges,.or.grooed.coupling.

adapters.that.will.ensure.that.a.one-quarter..

turn.can.be.obtained.on.all.pipe.connections.

being.joined

•. Prior.to.applying.the.solent.cement,.use.a.

clean.dry .rag.to.wipe.moisture.and.dirt.from.the.fitting.socket.and.the.pipe.end.(the.presence.of.

moisture.on.the.joining.surfaces.will.reduce..

 joint.integrity)

•. Use.a.new.can.of.solent.cement.when.making.

cut-in.connections.(erify.expiration.dates.

stamped.on.can.prior.to.use)

24Lubrizol

Cut-In Procedure for System Modification or Repairs

Page 25: Blaze Ng

7/30/2019 Blaze Ng

http://slidepdf.com/reader/full/blaze-ng 25/32

•. After.all.work.is.completed,.the.cut-in.joints.must.

be.allowed.to.cure.properly.prior.to.pressure.

testing.as.shown.in.the.table.below

•. After.work.is.completed.and.cut-in.cure.times.

are.met,.inspect.work.for.proper.alignment.and.

hanger.placement.prior.to.pressure.testing•. After cut-in cure times are met,.the.system..

must.be.slowly.filled.with.water.and.the.air..

bled.from.the.furthest.and.highest.sprinkler..

heads.before.test.pressure.is.applied.(refer..

to.manufacturer’s.installation.instructions.

regarding.Hydrostatic.Testing)

•. After cut-in cure times are met and the air is bled 

from the system,.it.is.recommended.that.portion.

of.the.sprinkler.system.containing.the.cut-in.tee.

be.pressure.tested.Prior.to.pressure.testing,.the.

system.must.be.sectioned.off.to.its.smallest.area.

using.floor.ales,.etc,.to.isolate.the.cut-in.area.

It.is.further.recommended.that.the.test.pressure.

applied.should.not.exceed.50.psi.oer.the.

system.pressure.This.approach.will.minimize.the.

potential.for.water.damage.should.a.leak.occur

. WARNING: AIR OR COMPRESSED GAS MUST NEVER

BE USED FOR PRESSURE TESTING

25 Lubrizol

Cut-In Procedure for System Modification or Repairs cont.

Cut-InsMinimum Cure Prior to Pressure Testing

Ambient Temperature During Cure

Pipe Size 60°F to 120°F 40°F to 59°F 0°F to 39°F

3/4". 1.hour. 4.hour. 48.hour

1". 11 ⁄ 2.hour. 4.hour. 48.hour

11 ⁄ 4".&.11 ⁄ 2". 3.hour. 32.hour. 10.days

2". 8.hour. 48.hour. *

21 ⁄ 2".&.3". 24.hour. 96.hour. *

*..Solent.cement.can.be.applied.at.temperatures.below.40°F.for.pipe.2".in.size.and.larger,.howeer.the.temperature.of.the.system.must.be.raised..

to.40°F.or.higher.and.allowed.to.cure.per.the.aboe.recommendations.prior.to.pressure.testing.When.bringing.cement,.pipe.or.fittings.in.from.the..

outside,.be.sure.they.are.brought.up.to.room.temperature.before.using.the.60°F.to.120°F.cure.schedule

Page 26: Blaze Ng

7/30/2019 Blaze Ng

http://slidepdf.com/reader/full/blaze-ng 26/32

Hangers and Supports

Because.BlazeMaster ® .pipe.is.rigid,.it.requires.fewer.

supports.than.flexible.plastic.systems.The.support.

spacing.is.shown.in.the.following.table

Most.hangers.designed.for.metal.pipe.are.

suitable.for.BlazeMaster ® .pipe.Do.not.use.

undersized.hangers.Hangers.with.sufficient.

load.bearing.surface.shall.be.selected.based.

on.pipe.size,.ie,.1.1/2".hangers.for.1.1/2".

pipe..The.hanger.shall.not.hae.rough.or.

sharp.edges.that.come.in.contact.with.the.

pipe..The.pipe.hangers.must.comply.with.the.

requirements.in.NFPA.13,.13R,.and.13D..

For.Quick.Response.upright.sprinkler.heads,.rigid.

hangers.secured.to.the.ceiling.shall.be.used

When.a.sprinkler.head.actiates,.a.significant.

reactie.force.can.be.exerted.on.the.pipe..With.

a.pendent.head,.this.reactie.force.can.cause.

the.pipe.to.lift.ertically.if.it.is.not.properly.secured,.

especially.if.the.sprinkler.drop.is.from.small.diameter.pipe..The.closest.hanger.shall.brace.the.pipe.

against.ertical.lift-up..See.Tables.B.&.C

Any.of.a.number.of.techniques.can.be.used.to.

brace.the.pipe..Four.acceptable.approaches.

would.be.to.use.a.standard.band.hanger.

positioning.the.threaded.support.rod.to.1/16.inch.

(1588.mm).aboe.the.pipe,.a.split-ring.hanger,.a.

wrap-around.U.hanger,.or.a.special.escutcheon.

which.preents.upward.moement.of.the.sprinkler.

through.the.ceiling

26Lubrizol

Any distance

between supports

(Reference Table B)

(Reference Table A)

(Ref. Table C)

Support Support

Finished Ceiling Line

Figure 7: Support Spacing Drop Elbow and Drop Tee

TABLE C

Maximum Support Spacing Distance End Line

Sprinkler Head Drop Elbow

Nominal Pipe Size Less than 100 psi (690 kPa) More than 100 psi (690 kPa)

. 3/4".(20.mm). 9".(229.mm). 6".(152.mm)

. 1".(25.mm). 12".(305.mm). 9".(229.mm)

. 11/4".(32.mm). 16".(406.mm). 12".(305.mm)

. 11/2".-.3".(40.–.80.mm). 24".(610.mm). 12".(305.mm)

TABLE B

Maximum Support Spacing Distance In Line

Sprinkler Head Drop Tee

Nominal Pipe Size Less than 100 psi (690 kPa) More than 100 psi (690 kPa)

. 3/4".(20.mm). 4'.(122.m). 3'.(091.m)

. 1".(25.mm). 5'.(152.m). 4'.(122.m)

. 11/4".(32.mm). 6'.(183.m). 5'.(152.m)

. 11/2".-.3".(40.–.80.mm). 7'.(213.m). 7'.(213.m)

. Nominal MaximumSize Support Spacing

inches mm feet meters

. 3/4. 200. 51/2. 17

. 1. .250. 6. 18

. 11/4. 320. 61/2. 20

. 11/2. 400. 7. 21

. 2. 500. 8. 24

. 21/2. 650. 9. 27

. 3. 800. 10. 30.

TABLE A

Page 27: Blaze Ng

7/30/2019 Blaze Ng

http://slidepdf.com/reader/full/blaze-ng 27/32

Penetration of Studs and Joists

Wooden Studs and Joists

It.is.acceptable.to.cut.holes.in.wood.studs.for.

support.The.holes.should.be.oersized.to.allow..

for.moement.

Metal StudsBlazeMaster ® .pipe.and.fittings.should.be.protected.

from.sharp.edges.when.passing.through.metal.studs.

Transition to Other Materials

Support

Additional.support.should.be.added.at.the.metal.

side.of.a.BlazeMaster ® .CPvC-metal.transition.to.

support.the.weight.of.the.metal.system

Threaded ConnectionsBlazeMaster ® .CPvC.male.and.female.threaded.

adapters.or.flanges.are.listed.for.connecting.a.

BlazeMaster ® .fire.sprinkler.system.to.other.materials,.

ales,.and.appurtenances.

A.thread.sealant.shall.be.used.in.making.threaded.

connections..TFE.(Teflon ® ).thread.tape.is.the.

recommended.sealant..Some thread sealants

other than TFE thread tape contain solvents or other

materials that may be damaging to CPVC. Refer

to manufacturers’ installation instructions for specificrecommendations on thread sealants. Always

consult with the manufacturer of the material for

compatibility with BlazeMaster ® CPVC pipe and

fittings or reference the Chemical Compatibility

and FGG/BM ® System Compatible program

sections of www.blazemaster.com for additional

information.

Care.shall.be.exercised.when.

transitioning.between.BlazeMaster ® ..

pipe.and.fittings.and.metal..Care..must.be.taken.to.aoid.oer-torquing...

Refer.to.manufacturers’.installation.

instructions.for.torque.requirements

Flanged Connections

Flange.Make-Up:..Once.a.flange.is.joined.to.pipe,.

the.method.for.joining.two.flanges.is.as.follows:

1. Piping.runs.joined.to.the.flanges.must.be.

installed.in.a.straight.line.position.to.the.

flange.to.aoid.stress.at.the.flange.due.to.

misalignment..Piping.must.also.be.secured.and.supported.to.preent.lateral.moement.that.

can.create.stress.and.damage.the.flange

2. With.gasket.in.place,.align.the.bolt.holes.of.the.

mating.flanges.by.rotating.the.ring.into.position..

(Consideration.should.be.gien.to.alignment.of.

one-piece.flange.prior.to.joining.with.pipe)

3. Insert.all.bolts,.washers.(two.standard.flat.

washers.per.bolt),.and.nuts

4. Make.sure.the.faces.of.the.mating.surfaces..

are.flush.against.gasket.prior.to.bolting.down.

the.flanges

5. Tighten.the.nuts.by.hand.until.they.are.snug..

Establish.uniform.pressure.oer.the.flange.face.

by.tightening.the.bolts.in.5.ft-lb.(68.Newton-m).

increments.according.to.the.sequence.shown.

in.Figure 8: Bolt Tightening Sequence .following.a.

180°.opposing.sequence

6. Care.must.be.taken.to.aoid.“bending”.the.

flange.when.joining.a.flange.to.a.“raised.face”.

flange,.or.a.wafer-style.ale..Do.not.use.bolts.

to.bring.together.improperly.mated.flanges

Caution:..Oer-torquing.will.damage.the.flange.

Torque.gien.is.for.dry,.non-lubricated.bolt,.

standard.washers,.neoprene..

1/8".(318.mm).thick.full.face.gasket..

If.lubricant..(non-petroleum.based).is.used,.torque.leels.may.ary..Actual..

field.conditions.may.require.a.ariation..

in.these.recommendations

27 Lubrizol

Recommended Bolt Torque 

Flange Size Bolt Diameter Torque

. 3/4".-.1.1/2".(20.–.40mm). 1/2".(127.mm). 10.–.15.ft.lbs.(136.–.203.Newton-m)

. 2".–.3".(50.–.80.mm). 5/8".(159.mm). 20.–.30.ft.lbs.(271.–.407.Newton-m)

1

43

2

Figure 8: Bolt

Tightening Sequence

Page 28: Blaze Ng

7/30/2019 Blaze Ng

http://slidepdf.com/reader/full/blaze-ng 28/32

Grooved Coupling Adapters

The.following.procedures.are.recommended.for.

proper.assembly.of.the.Grooed.Coupling.Adapter..

READ THESE INSTRUCTIONS CAREFULLY BEFORE

BEGINNING INSTALLATION.

1. Inspect.the.fittings.and.pipe.to.insure.that.

they.are.sufficiently.free.from.indentations,.projections.or.roll-marks.on.the.gasket.seating.

areas.of.the.fitting.and.pipe..The.pipe.should.

be.squarely.cut.with.any.loose.scale,.paint,.

and/or.dirt.remoed.from.the.grooe..

and.seating.surface..Use a standard grade

E*, EPDM compound that is suitable for wet fire

sprinkler service. A flexible coupling shall

be used with grooved coupling adapters.

Caution: Use of rigid style couplings may

damage the grooved coupling adapter.

Consult the coupling manufacturer forproper selection.

. *See.manufacturer.for.temperature.ratings

2. Make.sure.the.gasket.is.clean.and.free.of.any.

cracks,.cuts.or.other.defects..which.may.cause.

leaks..Lubricate.the.gasket.with.a.egetable.

soap-based.gasket.lubricant..Caution: Use of

petroleum based lubricants will damage the

gasket and adapter resulting in stress failure of

the CPVC adapter. A gasket/joint lubricant isrecommended to prevent pinching the gasket

and to assist in seating the gasket during the

alignment process. Apply the appropriate

lubricant to the gasket lips and exterior surface

of the gasket.

3. Place.the.gasket.oer.the.metal.pipe.ends,.

being.sure.gasket.lip.does.not.oerhang.the.

pipe.end..Insert.the.CPvC.grooed.coupling.

adapter.into.the.gasket..Make.sure.that.the.

gasket.is.centered.between.the.two.grooes..No.portion.of.the.gasket.should.extend.into.the.

grooes..Caution: Make sure the gasket is not

pinched between the pipe and the fitting.

4. Place.the.metal.housing.oer.the.gasket,.

making.sure.the.metal.housing.key.is.into.the.

grooes.on.the.metal.pipe.and.the.CPvC.

coupling.adapter..Insert.the.bolts.and.hand..

tighten..Tighten.the.bolts.alternately.and.

equally.until.the.bolt.pads.are.touching.metal-

to-metal..In.completing.a.proper.joint,.the.

gasket.is.also.slightly.compressed,.adding.

to.the.strength.of.the.seal.from.the..

gasket’s.durometer

5. Inspect.the.joints.before.and.after.pressure.

testing..Look.for.gaps.between.the.bolt..

pads.and.for.housing.keys.that.are.not.inside.

the.grooes

Other Design Criteria

Chemical Compatibility

CPvC.domestic.water,.fire.sprinkler,.and.industrial.

piping.systems.hae.been.used.successfully.for.more.

than.40.years.in.new.construction,.re-pipe.and.repair..

CPvC.products.are.ideally.suited.for.these.applications.

due.to.their.outstanding.corrosion.resistance..

Occasionally,.howeer,.CPvC.can.be.damaged.by.

contact.with.chemicals.found.in.some.construction.

products.(and.site.preparations)..This.may.result.in.

damage.to.property,.people,.or.the.BlazeMaster ® .

CPvC.fire.sprinkler.system.Reasonable care needs to

be taken to insure that products coming into contact

with CPVC systems are chemically compatible.

Lubrizol.recommends.that.chemical.compatibility.

with.CPvC.be.confirmed.with.the.manufacturer.of.

the.product.in.contact.with.CPvC.piping.systems.

If.chemical.compatibility.with.CPvC.is.in.question,.

Lubrizol.recommends.isolating.the.suspect.product.

from.contact.with.CPvC.pipe.or.fittings.

Lubrizol.maintains.a.list.of.products.that.hae.been.

shown.to.be.UNACCEPTABLE.for.(unprotected.use).

contact.with.CPvC.systems.Chemically.incompatible.

products.are.added.to.this.list.as.they.are.brought.to.

our.attention.For.the.most.current.list.of.chemically.

incompatible.products,.contact.Lubrizol.or.refer.to.the.Chemical.Compatibility.Section.under.Design.

&.Installation.at.www.blazemaster.com.A.product's.

absence.from.this.list.does.not.imply.or.insure.CPvC.

chemical.compatibility

The.FGG/BM ® .System.Compatible.program.

identifies.products.that.hae.been.determined.

to.be.compatible.with.CPvC.compounds.

28Lubrizol

Page 29: Blaze Ng

7/30/2019 Blaze Ng

http://slidepdf.com/reader/full/blaze-ng 29/32

manufactured.by.Lubrizol,.such.as.BlazeMaster ® .

CPvC.Products.included.in.this.program.carry.

the.FGG/BM ® .System.Compatible.logo.on.their.

label..Additional.information.on.this.program.can.

be.found.on.the.internet.at.wwwblazemastercom.

under.Design.and.Specifications

ALWAYS CHECK THE PRODUCT MANUFACTURER'S RECOMMENDATION IN THIS REGARD.

A Note on Microbiologically Influenced

Corrosion (MIC).

In.areas.where.water.supplies.are.known.to.hae.

contributed.to.MIC,.NFPA.requires.metallic.fire.

sprinkler.system.water.supplies.to.be.tested.and.

appropriately.treated..Reference.Section.2315.of.

NFPA.13.(2007.Edition)..This.testing.and.treatment.

is.not.required.when.using.BlazeMaster ® .CPvC.

products..BlazeMaster ® .CPvC.is.not.susceptible.to.

MIC.because:

1. CPvC.surfaces.discourage.the.adherence.of.

the.bacteria.associated.with.MIC..In.metallic..

systems,.colonies.form.around.the.bacteria.that.

entrap.organic.acids.against.the.wall,.causing.

the.pitting.which.is.common.with.MIC

2. As.the.bacteria.associated.with.MIC.cannot.

adhere.to.the.inner.surface.of.CPvC,.the.

bacteria.will.not.propagate.as.rapidly

3. The.organic.acids.produced.by.the.MIC.

bacteria.promote.the.oxidation.of.metals.but.

do.not.affect.CPvC..In.fact,.the.compounds.

that.comprise.BlazeMaster ® .pipe.and.fittings..

are.known.to.be.unaffected.in.extreme.acid.

enironments.far.more.seere.than.those.

enironments.associated.with.MIC.

Note: Metal.components.within.non-metallic.fire.

sprinkler.systems.are.not.immune.to.MIC

Freeze Protection

Freeze.protection.can.be.proided.in.a.ariety..

of.methods.including.system.design,.insulation,..

and.antifreeze..

Batt Insulation 

Many.jurisdictions.recommend.the.use.of.batt.

insulation.for.freeze.protection.in.place.of.

antifreeze.solutions.These.jurisdictions.typically.

publish.batt.insulation.guidelines.that.proide.

the.minimum.thickness.of.insulation.to.be.utilized.

Reference.NFPA.13D.Section.831.(2007.Edition).for.

additional.recommendations

Antifreeze Solutions 

Glycerin.antifreeze.solutions.are.acceptable.for..

use.with.BlazeMaster

 ® 

.piping.Glycol.antifreeze.solutions.are.not.recommended.for.use.with.

BlazeMaster ® .pipe.and.fittings..Always.install.

antifreeze.systems.per.the.NFPA.guidelines..Refer.to.

Section.762.of.NFPA.13.(2007.Edition)

The.following.considerations.should.be.

incorporated.into.the.system.design.when.

proiding.for.freeze.protection:

•. Always.follow.the.manufacturers’.installation.

instructions.proided.by.the.BlazeMaster ® .pipe.

and.fittings.manufacturer..This.is.especially.important.with.regard.to.the.torque..

requirements.for.sprinkler.installation,.the.specific.

type.and.use.of.Teflon ® .tape,.and.the.specific.

type.and.use.of.a.thread.paste.sealant

•. Use.only.high.quality.Teflon ® .tape.or.a.thread.

paste.sealant.that.is.chemically.compatible..

with.CPvC.and.recommended.by.the.sealant.

manufacturer..Reference.the.Chemical.

Compatibility.and.FGG/BM ® .System.Compatible.

program.sections.of.wwwblazemastercom.for.

additional.information..Neer.combine.both.Teflon ® .tape.and.thread.paste.sealants

•. Follow.NFPA.13.Section.7633.(2007.Edition).

requirement.regarding.the.installation.and.use.of.

expansion.chambers.when.backflow.preention.

deices.are.installed.with.steel,.copper,.and.

CPvC..NOTE:.Most.existing.backflow.preention.

deices.do.not.allow.entrapped.pressure.to.be.

relieed

•. Consider.the.use.of.glycerin.and.water.solution.

antifreeze.loops.rather.than.the.practice.of.installing.glycerin.and.water.solutions.into.the.

entire.sprinkler.system

29 Lubrizol

Page 30: Blaze Ng

7/30/2019 Blaze Ng

http://slidepdf.com/reader/full/blaze-ng 30/32

Estimating Antifreeze Solution Requirements 

Painting

Water-based.acrylic.latex.paint.is.the.preferred.and.

recommended.paint.to.use.on.BlazeMaster ® .CPvC.

pipe.and.fittings.Oil.or.solent-based.paints.may.

be.chemically.incompatible

Certain.types.of.oil.or.solent-based.paints.

may,.howeer,.be.used.proided.that.it.is.a. light.

coating.that.dries.quickly..These.paints.should.

not.be.allowed.to.puddle.or.pool.on.the.surface..

Application.of.solent-based.paints.must.be.

indiidually.reiewed.as.there.are.certain.types.

of.paints.and.stains.that.contain.drying.oils.and.

should.not.be.used.at.all.on.CPvC.

Maintenance

Maintenance.of.a.BlazeMaster ® .fire.sprinkler.system.shall.be.in.accordance.with.the.Standard.

for.Inspection,.Testing.and.Maintenance.of.Water.

Based.Extinguishing.Systems.as.defined.by.NFPA.25

Penetrating Fire Rated Walls and Partitions

Before.penetrating.fire.rated.walls.and.partitions,.

consult.building.codes.and.authorities.haing.

 jurisdiction.in.your.area..Seeral.classified.through-

penetration.firestop.systems.are.approed.for.use.

with.CPvC.pipe..Consult.the.pipe.manufacturer.or.

BlazeMaster ® .fire.sprinkler.system.representatie.for.further.information..Warning: Some firestop sealants

or wrap strips contain solvents or plasticizers that

may be damaging to CPVC. Always consult

the manufacturer of the firestop material for

compatibility with BlazeMaster ® CPVC pipe and

fittings. To avoid compatibility issues, reference

the Chemical Compatibility and FGG/BM ® System

Compatible program sections of www.blazemaster.

com for additional information.

Earthquake Bracing

Since.BlazeMaster ® .CPvC.pipe.is.more.ductile.than.

metallic.sprinkler.pipe,.it.has.a.greater.capacity.to.

withstand.earthquake.damage..In.areas.subject..

to.earthquakes,.BlazeMaster ® .fire.sprinkler.systems.

shall.be.designed.and.braced.in.accordance.with.

local.codes.or.NFPA.13,.Section.93.(2007.Edition)

NFPA.13.recognizes.the.unique.properties.of.

nonmetallic.fire.sprinkler.piping..Section.9347.of.

the.2007.edition.of.NFPA.13.permits.nonmetallic.fire.

sprinkler.pipe.to.penetrate.a.wall,.floor,.platform,.

or.foundation.without.allowing.for.clearance.in.an.

opening.if.the.pipe.has.the.inherent.flexibility.equal.

to.or.greater.than.the.flexibility.proided.by.flexible.

couplings.located.within.1.foot.of.each.side.of.the.

wall,.floor,.platform,.or.foundation

BlazeMaster ® .CPvC.fire.sprinkler.pipe.has.the.

flexibility.to.meet.this.criteria..The.permissible.

bending.deflection.alues.for.BlazeMaster ® .

CPvC.pipe.can.be.found.in.the.tables.in.the.Pipe.

Deflection.section.of.this.manual

When it is required to earthquake brace

BlazeMaster ® piping, it is important to use fittings,

fasteners or clamps that do not have sharp edges

or apply excessive compressive forces sufficient to

distort the pipe.

Copyright Notice...All.pages.of.this.Manual.are:..Copyright.2007.The.

Lubrizol.Corporation..All.rights.resered.

Warranty Disclaimer...This.Manual.and.all.of.the.information.it.contains.are.

proided."as.is".without.warranty.of.any.kind,.whether.express.or.implied...

It.may.contain.generalizations,.technical.inaccuracies,.or.typographical.

errors..LUBRIZOL DISCLAIMS ALL WARRANTIES, EXPRESS OR IMPLIED,

INCLUDING, WITHOUT LIMITATION, THE IMPLIED WARRANTIES OF

MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, AND ANY

WARRANTY OF NONINFRINGEMENT.

Limitation of Liability. USE OF THIS MANUAL OR ANY INFORMATION IT

CONTAINS IS AT THE SOLE RISK OF THE USER...Under.no.circumstances.will.

Lubrizol.be.liable.to.any.party.for.any.direct,.indirect,.special.incidental,.consequential.or.other.damages.based.on.any.use.of.this.Manual.

including,.without.limitation,.any.lost.profits.or.business.interruption,.een.if.

Lubrizol.has.been.specifically.adised.of.the.possibility.of.such.damages

No rights or license...Information.proided.herein.is.for.the.conenience.of.

users.of.BlazeMaster ® .fire.sprinkler.systems.and.is.not.being.published.for.

commercial.use..No.rights.are.granted.to.users.in.any.Lubrizol.trademarks,.

copyrights.or.other.intellectual.property.or.technical.data

Summary

BlazeMaster ® .pipe.and.fittings,.designed.specifically.for.fire.sprinkler.

systems,.proide.unique.adantages..Long-term.performance.of.a.

BlazeMaster ® .system.will.be.maximized.if.it.is.properly.installed.and.

maintained.in.accordance.with.applicable.NFPA.guidelines

30Lubrizol

. Fitting Gallons per Liters per

Size Foot of Pipe Meter of Pipe

3/4".(20.mm). 0031. 0387

1".(25.mm). 0049. 0614

1.1/4".(32.mm). 0079. 0985

1.1/2".(40.mm). 0104. 1294

2".(50.mm). 0164. 2033

2.1/2".(65mm). 0240. 2975

3".(80mm). 0355. 4409

Page 31: Blaze Ng

7/30/2019 Blaze Ng

http://slidepdf.com/reader/full/blaze-ng 31/32

Dos◆. Install.product.according.to.the.manufacturer’s..

installation.instructions

◆. Follow.recommended.safe.work.practices

◆. Make.certain.that.thread.sealants,.gasket.lubricants,..

or.fire.stop.materials.are.compatible.with..

BlazeMaster ® .CPvC

◆. Use.only.latex-based.paints.if.painting.is.desired

◆. Keep.pipe.and.fittings.in.original.packaging.until.needed

◆. Coer.pipe.and.fittings.with.an.opaque.tarp.if..

stored.outdoors

◆. Follow.proper.handling.procedures

◆. Use.tools.specifically.designed.for.use.with.plastic..

pipe.and.fittings

◆. Use.proper.solent.cement.and.follow.application..

instructions

◆. Use.a.drop.cloth.to.protect.interior.finishes

◆. Cut.the.pipe.ends.square

◆. Deburr.and.beel.the.pipe.end.before.solent.cementing

◆. Rotate.the.pipe.1/4.turn.when.bottoming.pipe.in..

fitting.socket

◆. Aoid.puddling.of.solent.cement.in.fittings.and.pipe

◆. Make.certain.that.solent.cement.does.not.run.and..

plug.the.sprinkler.head.orifice

◆. Follow.the.manufacturer’s.recommended.cure.times.prior.to.

pressure.testing

◆. Fill.lines.slowly.and.bleed.the.air.from.the.system.prior.to.

pressure.testing

◆. Support.sprinkler.head.properly.to.preent.lift.up.of.

the.head.through.the.ceiling.when.actiated

◆. Keep.threaded.rod.within.1⁄16".of.the.pipe

◆. Install.BlazeMaster ® .CPvC.pipe.and.fittings.in.wet..

systems.only

◆. Use.only.insulation.and/or.glycerin.&.water.solutions..for.freeze.

protection

◆. Allow.for.moement.due.to.expansion.and.contraction

◆. Renew.your.BlazeMaster ® .CPvC.pipe.and.fittings..

installation.training.eery.two.years

Don’ts

◆. Do.not.use.edible.oils.such.as.Crisco

 ® 

.as.a..gasket.lubricant

◆. Do.not.use.petroleum.or.solent-based.paints,.sealants,.

lubricants.or.fire.stop.materials

◆. Do.not.use.any.glycol-based.solutions.as.an.anti-freeze

◆. Do.not.mix.glycerin.and.water.solution.in.contaminated.

containers

◆. Do.not.use.both.Teflon ® .tape.and.thread.sealants..

simultaneously

◆. Do.not.use.solent.cement.that.exceeds.its.shelf.life..

or.has.become.discolored.or.gelled

◆. Do.not.allow.solent.cement.to.plug.the.sprinkler..

head.orifice

◆. Do.not.connect.rigid.metal.couplers.to.BlazeMaster ® .CPvC.

grooed.adapters

◆. Do.not.thread.or.grooe.BlazeMaster ® .CPvC.pipe

◆. Do.not.use.solent.cement.near.sources.of.heat,..

open.flame,.or.when.smoking

◆. Do.not.pressure.test.until.recommended.cure..

times.are.met

◆. Do.not.use.dull.or.broken.cutting.tool.blades..

when.cutting.pipe

◆. Do.not.use.BlazeMaster ® .CPvC.pipe.that.has.been.stored.

outdoors,.unprotected.and.is.faded.in.color

◆. Do.not.allow.threaded.rod.to.come.in.contact..

with.the.pipe

◆. Do.not.install.BlazeMaster ® .CPvC.pipe.in.cold.weather.

without.allowing.for.expansion

◆. Do.not.install.BlazeMaster ® .CPvC.pipe.and.fittings..

in.dry.systems

31 Lubrizol

Dos and Don’ts

While.not.a.complete.list,.the.following.is.intended.to.highlight.many.of.the.“Dos”.and.“Don’ts”.addressed.

in.this.manual

Page 32: Blaze Ng

7/30/2019 Blaze Ng

http://slidepdf.com/reader/full/blaze-ng 32/32

Lubrizol Advanced Materials, Inc.BlazeMaster ® .CPvC.Marketing.Department9911.Brecksille.RoadCleeland.OH.44141-3201.USA

216-447-5000.1-888-234-2436.

Fax:.216-447-5750

Chaussée.de.Ware,.19451160.BrusselsBelgium

32-2-678-19-11Fax:.32-2-678-19-90

1107-1110.Shui.On.Centre.6-8.Harbour.Road.Wan.Chai,.Hong Kong

852-2508-1021.Fax:.852-2512-2241

The.information.contained.herein.is.belieed.to.be.reliable,.based.on.extensie.laboratory.testing.and.thousands.of.successful.CPvC.system.installations.dating. from. 1960,. but.no. representations,. guarantees. or.warranties. of. any.kind. are.made. as. to. its.accuracy,. suitability. for. particular.application.or.the. results. to. be. obtained. therefrom. The. information. is. based. on. laboratory. work. with. small-scale. equipment. and. does. not. necessarily. indicate.end.product. performance. Because. of. the. ariations. in. methods,. conditions. and. equipment. used. commercially. in. processing. these. materials,. no.warranties.or.guarantees.are.made.as. to.the.suitability.of. the.products.for.the.applications.disclosed.Full-scale.testing.and.end.product.performance.are. the. responsibility. of.the. user. Lubrizol.Adanced.Materials,. Inc. shall. not. be.liable.for.and. the. customer.assumes.all. risk. and. liability. of.any. use.or. handling. of. any. material. beyond. Lubrizol. Adanced. Materials,. Inc’s. direct. control. THE. SELLER. MAKES. NO.WARRANTIES,. EXPRESS. OR. IMPLIED,.INCLUDING BUT NOT LIMITED TO THE IMPLIED WARRANTIES OF MERCHANTABILITYAND FITNESS FOR A PARTICULAR PURPOSE Nothing contained herein is

Harvel Plastics, Inc.P.0. Box 757Kuebler RoadEaston, PA 18044610/252-7355

Fax: 610/253-4436www.harvel.com

Tyco Fire & Building Products451 N. Cannon AvenueLansdale, PA 19446215/362-0700Fax: 215/362-5385www.tyco-fire.com

IPEX, Inc.2441 Royal Windsor DriveMississauga, OntarioCanada, L5J 4C7905/403-0264

Fax: 905/403-9195www.ipexinc.com

NIBCO, Inc.1516 Middlebury StreetP.O. Box 1167Elkhart, IN 46515-1167800-343-5455

FAX: 800-541-3841www.nibco.com

The Viking Corporation210 N. Industrial Park DriveHastings, MI 49058269.945.9501Fax: 269.945.4495www.vikinggroupinc.com

*As.manufactured.by.Harel,.IPEX,.Nibco,.Tyco.and.viking

Lubrizol produces and sells CPVC compounds to licensed manufacturers of BlazeMaster pipe and fittings (see above for contact information).

Refer to individual installation instructions published by each pipe and/or fittings manufacturer for their corresponding agency Listing and approvals.

*

For.a.complete.listing.of.regional.sales.representaties.and.manufacturers,..

please.isit.our.website.at.www.blazemaster.com