TO POSITIVE (+) A AND B TERMINALS OF FUSE PANEL E-1 SHEET NO. TYPICAL -48VDC DISTRIBUTION DETAIL STATE OF FLORIDA DEPARTMENT OF TRANSPORTATION SICN SITE NAME FINANCIAL PROJECT ID COUNTY \\dotscoteo1\Traffic_Ops_Data\Public\TSMO\Telcom\SICN\SICN Technology Replacement Plan\Phase 2 Contract Plans\Contract Plans\6-Equipment\E-Equipment Details 20180920.vsd 424401-2-93-03 FLORIDA DEPARTMENT OF TRANSPORTATION 605 SUWANNEE ST. MS 90 TALLAHASSEE, FL 32399-0450 PH.(850)-410-5600 FAX.(850)-410-5501 CONTRACT PLANS RECORD REV. DATE DESCRIPTION REV. DATE DESCRIPTION -48 VDC BREAKER PANEL 23 24 25 26 27 28 23 24 25 26 27 28 1 2 3 4 5 6 7 8 9 10 11 12 19 LOAD RETURNS LOAD RETURNS GROUND 13 14 15 16 17 18 TO NEGATIVE (-) A AND B TERMINALS OF FUSE PANEL APPROPRIATELY SIZED BREAKERS IN THE NEXT AVAILABLE POSITIONS. BREAKER TYPE SPECIFIED ON SITE-SPECIFIC INSTALLATION PLANS. ON | TRIPPED ALM 30A ON | TRIPPED ALM 30A ON | TRIPPED ALM 30A ON | TRIPPED ALM 30A ON | TRIPPED ALM 30A CABLE TRAY DROP TO FUSE PANEL WHITE JACKETED APPROPRIATELY SIZED LOAD CONDUCTOR TO BE INSTALLED BY THE VENDOR. MINIMUM WIRE SIZE #12 AWG ON | TRIPPED BLACK JACKETED APPROPRIATELY SIZED LOAD RETURN CONDUCTOR TO BE INSTALLED BY THE VENDOR. MINIMUM WIRE SIZE #12 AWG ON | TRIPPED FIGURE 1 – EXAMPLE 10A BOLT-IN BREAKER FIGURE 2 – EXAMPLE 30A PLUG-IN BREAKER Attachment 1 112
4
Embed
BLACK JACKETED APPROPRIATELY SIZED TO POSITIVE (+) A …...FINANCIAL PROJECT ID ... Minor BIT S1 BIT S2 Alarm Module External Alarms ACO Alarms. FUTURE NOKIA MPR-9500 RADIO SHELF NOKIA
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
NOTES:1. THE VENDOR SHALL FURNISH AND INSTALL THREE (3) NEW PUNCH BLOCKS ON THE TELCO BACKBOARD. THE VENDOR SHALL USE THE EXISTING DVA AND DVM6-45 PUNCH BLOCKS AND
CROSS-CONNECT TO THE NEW RTU PUNCH BLOCKS. THE VENDOR SHALL INSTALL A NEW EQUIPMENT PUNCHBLOCK TO WIRE THE ALARM POINTS FROM THE EQUIPMENT TO THE LEFT
SIDE OF THE PUNCHBLOCK, AND TO THE RTU PUNCH BLOCKS ON THE RIGHT SIDE. AN FDOT REPRESENTATIVE WILL ASSIST IN IDENTIFYING THE EXISTING ALARM WIRING.
2. THE VENDOR SHALL WIRE FROM THE LEFT SIDE OF EACH RTU PUNCHBLOCK TO THE FURNISHED AND INSTALLED DPS TELECOM ALARM POINT SPD. THEN, FROM THE SPD TO THE
PLUGGABLE PANEL ON THE BACK OF THE DPS TELECOM NETGUARDIAN 832A RTU.
3. THE VENDOR SHALL WIRE THE RTU CONTACT POINTS AS NORMALLY CLOSED (NC) WHEN POSSIBLE.