1 V1.1.08.2012•Subject to modification BF24-C132 Spring-return actuator, combined with thermo-electric tripping device (72°C), for fire and smoke dampers 90° in ventilation and air-conditioning systems. T orque 20 Nm / 20 Nm Nominal voltage AC/DC 24 V Control: Open / Close • • • Technical data Electrical data Functional data Dimensions / Weight Nominal voltage Nominal voltage range Power consumption motor holding for wire sizing Auxiliary switch Contact rating (contacts gold plate on silver) Switching points Thermal trips Connecting cable motor auxiliary switch T orque motor spring-return Direction of rotation Angle of rotation Running time motor spring-return Sound power level motor spring-return Position indication Service life Protection class Degree of protection EMC Low Voltage Directive Mode of operation Rated impulse voltage Control pollution degree Ambient temperature rage normal duty safety duty Non-operation temperature Ambient humidity range Maintenance Dimensions Shaft diameter Weight AC 24V , 50/60 Hz / DC 24V AC 19.2...28.8V / DC 21.6...28.8V 10W @ norminal torque 2W 12.5VA / Imax. 8.3 A @ 5ms 2X1 SPDT 6 A (3 A), AC 250 V 5° , 80° Tf1: duct outside temperature 72°C Tf2 + Tf3: duct inside temperature 72°C 1 m, 2 x 0.75mm 2 (halogen-free) 1 m, 6 x 0.75mm 2 (halogen-free) Min. 20Nm Min. 20Nm Selected by mounting L/R Max. 95° < 60s < 30s (tamb = 20°C) Max. 55dB(A) ~60dB(A) Mechanical with pointer Min. 10’000 safe positions @ 15Nm followed by 50 safe positions @ 20Nm III Safety extra-low voltage IP54 CE according to 2004/108/EEC CE according to 2006/95/EEC Type 1.AA.B 0.8 kV 3 -30...+55°C The safe position will be attained up to max. 75 °C -40...+55°C 95% RH, non condensing Maintenance-free See <Dimensions> on page 3 Form-fit 12mm Approximately 3100g Working conditions
3
Embed
BF24-C132 - Belimo Actuators Ltd17.08.2012].pdf · BF24-C132 Spring-return ... Non-operation temperature Ambient humidity range Maintenance Dimensions ... Blanking cover (without
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
1V1.
1.08
.201
2•S
ubje
ct to
mod
ifica
tion
BF24-C132
Spring-return actuator, combined with thermo-electric tripping device (72°C), for fire and smoke dampers 90°
in ventilation and air-conditioning systems.
Torque 20 Nm / 20 NmNominal voltage AC/DC 24 V Control: Open / Close
•••
Technical data
Electrical data
Functional data
Dimensions / Weight
Nominal voltageNominal voltage rangePower consumption motor holding for wire sizingAuxiliary switchContact rating (contacts gold plate on silver)Switching pointsThermal trips
Connecting cable motor auxiliary switchTorque motor spring-returnDirection of rotationAngle of rotationRunning time motor spring-returnSound power level motor spring-returnPosition indicationService life
Protection classDegree of protectionEMCLow Voltage DirectiveMode of operationRated impulse voltageControl pollution degreeAmbient temperature rage normal duty safety dutyNon-operation temperatureAmbient humidity rangeMaintenanceDimensionsShaft diameterWeight
AC 24V, 50/60 Hz / DC 24VAC 19.2...28.8V / DC 21.6...28.8V10W @ norminal torque2W12.5VA / Imax. 8.3 A @ 5ms2X1 SPDT6 A (3 A), AC 250 V 5° , 80°Tf1: duct outside temperature 72°CTf2 + Tf3: duct inside temperature 72°C1 m, 2 x 0.75mm2 (halogen-free) 1 m, 6 x 0.75mm2 (halogen-free) Min. 20NmMin. 20NmSelected by mounting L/RMax. 95°< 60s< 30s (tamb = 20°C)Max. 55dB(A)~60dB(A)Mechanical with pointerMin. 10’000 safe positions @ 15Nmfollowed by 50 safe positions @ 20NmIII Safety extra-low voltageIP54CE according to 2004/108/EECCE according to 2006/95/EECType 1.AA.B0.8 kV3-30...+55°CThe safe position will be attained up to max. 75 °C -40...+55°C95% RH, non condensingMaintenance-freeSee <Dimensions> on page 3Form-fit 12mmApproximately 3100g
Working conditions
V1.
1.08
.201
2•S
ubje
ct to
mod
ifica
tion
2
BF24-C132
Safety notes
The actuator is not allowed to be used outside the specified field of application, especially in aircraft or in any other airborne means of transport.
The actuator is adapted and mounted to the fire and smoke damper by the damper manu-facturer. For this reason, the actuator is only supplied directly to safety damper manu-facturers. The manufacturer then bears full responsibility for the proper functioning of the damper.
The device may only be opened at the manufacturer‘s site. It does not contain any parts that can be replaced or repaired by the user.
The device contains electronic and electrical components and may not be disposed with the normal rubbish. Observe local regulations and valid laws.
•
•
•
•
!
Safety notes
Manual operation
Thermo-electric tripping deviceBAE72B-S
Signalling
Manual operation
The actuator moves the damper to its normal working position while tensioning the return spring at the same time. If the power supply is interrupted, the energy stored in the spring moves the damper back to its safe position.
Thermal trip Tf1 operates if the ambient temperature exceeds 72°C. Replaceable thermal trip Tf2/Tf3 operates if the temperature inside the duct exceeds 72°C. Tf1, Tf2 or Tf3 trips cause the power supply to be interrupted permanently and irrepealable.The LED is lit when– there is a supply voltage,– the temperature fuses are OK and– the test switch is not pressed.
Two microswitches with fixed settings are installed in the actuator for indicating the damper end positions.The position of the damper blade can be read off on a mechanical position indicator.
Without power supply, the damper can be operated manually and fixed in any required position. Release of the locking mechanism can be achieved manually or automatically by applying the supply voltage.
Accessories
NoteThe function of the thermal trip and the test switch is only warranted if the actuator is connected to the power supply and has reached its operating position.