Relion ® 670 series Busbar protection REB670  Application manual
458

Best Application

Aug 08, 2018

Download

Documents

insanaziz
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 1/457

Relion® 670 series

Busbar protection REB670 Application manual

Page 2: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 2/457

Page 3: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 3/457

Document ID: 1MRK 505 211-UENIssued: December 2012

Revision: CProduct version: 1.2

© Copyright 2012 ABB. All rights reserved

Page 4: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 4/457

Copyright

This document and parts thereof must not be reproduced or copied without written

 permission from ABB, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose.

The software and hardware described in this document is furnished under a licenseand may be used or disclosed only in accordance with the terms of such license.

Trademarks

ABB and Relion are registered trademarks of the ABB Group. All other brand or  product names mentioned in this document may be trademarks or registeredtrademarks of their respective holders.

Warranty

Please inquire about the terms of warranty from your nearest ABB representative.

 ABB AB

Substation Automation Products

SE-721 59 Västerås

Sweden

Telephone: +46 (0) 21 32 50 00

Facsimile: +46 (0) 21 14 69 18

http://www.abb.com/substationautomation

Page 5: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 5/457

Disclaimer

The data, examples and diagrams in this manual are included solely for the concept

or product description and are not to be deemed as a statement of guaranteed properties. All persons responsible for applying the equipment addressed in thismanual must satisfy themselves that each intended application is suitable andacceptable, including that any applicable safety or other operational requirementsare complied with. In particular, any risks in applications where a system failure and/or product failure would create a risk for harm to property or persons (including butnot limited to personal injuries or death) shall be the sole responsibility of the

 person or entity applying the equipment, and those so responsible are herebyrequested to ensure that all measures are taken to exclude or mitigate such risks.

This document has been carefully checked by ABB but deviations cannot becompletely ruled out. In case any errors are detected, the reader is kindly requestedto notify the manufacturer. Other than under explicit contractual commitments, inno event shall ABB be responsible or liable for any loss or damage resulting fromthe use of this manual or the application of the equipment.

Page 6: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 6/457

Conformity

This product complies with the directive of the Council of the European

Communities on the approximation of the laws of the Member States relating toelectromagnetic compatibility (EMC Directive 2004/108/EC) and concerningelectrical equipment for use within specified voltage limits (Low-voltage directive2006/95/EC). This conformity is the result of tests conducted by ABB inaccordance with the product standards EN 50263 and EN 60255-26 for the EMCdirective, and with the product standards EN 60255-1 and EN 60255-27 for the lowvoltage directive. The product is designed in accordance with the internationalstandards of the IEC 60255 series.

Page 7: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 7/457

Table of contents

Section 1 Introduction.....................................................................11Introduction to the application manual..............................................11

 About the complete set of manuals for an IED............................11

 About the application manual......................................................12

Intended audience.......................................................................12

Revision notes.............................................................................13

Section 2 Requirements.................................................................15Current transformer requirements....................................................15

Current tr ansformer classification................................................15Conditions....................................................................................16

Fault current................................................................................17

Secondary wire resistance and additional load...........................17

General current transformer requirements..................................18

Rated equivalent secondary e.m.f. requirements........................18

Busbar protection...................................................................18

Breaker failure protection.......................................................19

Non-directional instantaneous and definitive time, phase

and residual overcurrent protection........................................20

Non-directional inverse time delayed phase and residualovercurrent protection............................................................21

Current transfor mer requirements for CTs according to

other standards............................................................................22

Current transformers according to IEC 60044-1,

class P, PR.............................................................................22

Current transformers according to IEC 60044-1, class

PX, IEC 60044-6, class TPS

(and old British Standard, class X).........................................22

Current transformers according to ANSI/IEEE.......................22

Voltage transformer requirements....................................................23

SNTP server requirements...............................................................24

Section 3 IED application...............................................................25General IED application....................................................................25

 Analog inputs....................................................................................28

Introduction..................................................................................28

Setting guidelines........................................................................28

Setting of the phase reference channel..................................28

Setting parameters......................................................................53

Local human-machine interface.......................................................59

Table of contents

1

 Application manual

Page 8: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 8/457

Page 9: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 9/457

Setting parameters.................................................................77

Signal matrix for analog inputs SMAI..........................................77

 Application..............................................................................77

Frequency values...................................................................77Setting guidelines...................................................................78

Setting parameters.................................................................83

Summation block 3 phase 3PHSUM...........................................84

 Application..............................................................................84

Setting guidelines...................................................................84

Setting parameters............................................................ .....85

 Authority status ATHSTAT..........................................................85

 Application..............................................................................85

Setting parameters.................................................................85

Denial of ser vice DOS.................................................................85Setting guidelines...................................................................86

Differential protection........................................................................86

Busbar differential protection ......................................................86

Basic applications...................................................................87

Busbar protection applications...............................................88

Different busbar arrangements.............................................111

Summation principle.............................................................130

Setting parameters...............................................................140

Current protection..................................................................... ......148

Four step phase overcurrent protection OC4PTOC .................148 Application............................................................................148

Setting guidelines.................................................................149

Setting parameters...............................................................154

Four step single phase overcurrent protection

PH4SPTOC ..............................................................................159

 Application............................................................................159

Setting guidelines.................................................................161

Setting parameters...............................................................168

Thermal overload protection, two time constants TRPTTR ......172

 Application............................................................................172Setting guideline...................................................................173

Setting parameters...............................................................176

Breaker failure protection CCRBRF .........................................177

 Application............................................................................177

Setting guidelines.................................................................177

Setting parameters...............................................................181

Breaker failure protection, single phase version

CCSRBRF ................................................................................181

 Application............................................................................182

Setting guidelines.................................................................182

Table of contents

3

 Application manual

Page 10: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 10/457

Setting parameters...............................................................184

Directional underpower protection GUPPDUP..........................185

 Application............................................................................185

Setting guidelines.................................................................187Setting parameters...............................................................191

Directional overpower protection GOPPDOP ...........................192

 Application............................................................................192

Setting guidelines.................................................................194

Setting parameters...............................................................198

Capacitor bank protection CBPGAPC.......................................199

 Application............................................................................199

Setting guidelines.................................................................203

Setting parameters...............................................................206

Voltage protection...........................................................................206Two step undervoltage protection UV2PTUV ...........................206

Setting guidelines.................................................................207

Setting parameters...............................................................210

Two step overvoltage protection OV2PTOV .............................212

 Application............................................................................212

Setting guidelines.................................................................213

Setting parameters...............................................................216

Two step residual overvoltage protection ROV2PTOV ............218

 Application............................................................................218

Setting guidelines.................................................................218Setting parameters...............................................................223

Voltage differential protection VDCPTOV .................................224

 Application............................................................................225

Setting guidelines.................................................................226

Setting parameters...............................................................227

Loss of voltage check LOVPTUV .............................................228

 Application............................................................................228

Setting guidelines.................................................................228

Setting parameters...............................................................228

Frequency protection......................................................................229Underfrequency protection SAPTUF ........................................229

Setting guidelines.................................................................229

Setting parameters...............................................................230

Rate-of-change frequency protection SAPFRC ........................231

 Application............................................................................231

Setting guidelines.................................................................231

Setting parameters...............................................................232

Multipurpose pr otection..................................................................233

General curr ent and voltage protection CVGAPC.....................233

Table of contents

4

 Application manual

Page 11: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 11/457

 Application............................................................................233

Setting guidelines.................................................................239

Setting parameters...............................................................248

Secondary system supervision.......................................................255Fuse failure supervision SDDRFUF..........................................255

Setting parameters...............................................................255

Control............................................................................................256

 Autorecloser SMBRREC ..........................................................256

 Application............................................................................256

Setting guidelines.................................................................268

Setting parameters...............................................................278

 Apparatus contr ol APC..............................................................279

 Application............................................................................279

Interaction between modules...............................................286Setting guidelines.................................................................288

Setting parameters...............................................................289

Interlocking ...............................................................................291

Configuration guidelines.......................................................293

Interlocking f or line bay ABC_LINE .....................................293

Interlocking f or bus-coupler bay ABC_BC ...........................298

Interlocking for transformer bay AB_TRAFO .......................304

Interlocking for bus-section breaker A1A2_BS.....................305

Interlocking f or bus-section disconnector A1A2_DC ...........308

Interlocking f or busbar earthing switch BB_ES ...................316Interlocking f or double CB bay DB ......................................322

Interlocking f or 1 1/2 CB BH ................................................324

Horizontal communication via GOOSE for interlocking

GOOSEINTLKRCV..............................................................325

Logic rotating switch for function selection and LHMI

presentation SLGGIO................................................................325

 Application............................................................................325

Setting guidelines.................................................................326

Setting parameters...............................................................327

Selector mini switch VSGGIO....................................................327 Application............................................................................327

Setting guidelines.................................................................328

Setting parameters...............................................................328

IEC61850 generic communication I/O functions DPGGIO........328

 Application............................................................................329

Setting guidelines.................................................................329

Single point generic control 8 signals SPC8GGIO....................329

 Application............................................................................329

Setting guidelines.................................................................329

Setting parameters...............................................................330

Table of contents

5

 Application manual

Page 12: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 12/457

 AutomationBits, command function for DNP3.0 AUTOBITS.... .330

 Application............................................................................330

Setting guidelines.................................................................331

Setting parameters...............................................................331Single command, 16 signals SINGLECMD...............................345

 Application............................................................................345

Setting guidelines.................................................................347

Setting parameters...............................................................347

Logic...............................................................................................348

Configurable logic blocks...........................................................348

 Application............................................................................348

Setting parameters...............................................................349

Fixed signal function block FXDSIGN.......................................350

 Application............................................................................350Setting parameters...............................................................351

Boolean 16 to Integer conversion B16I.....................................351

 Application............................................................................351

Setting guidelines.................................................................351

Boolean 16 to Integer conversion with logic node

representation B16IFCVI...........................................................351

 Application............................................................................352

Setting guidelines.................................................................352

Integer to Boolean 16 conversion IB16.....................................352

 Application............................................................................352Setting parameters...............................................................352

Integer to Boolean 16 conversion with logic node

representation IB16FCVB..........................................................352

 Application............................................................................352

Setting parameters...............................................................353

Monitoring.......................................................................................353

Measurement.............................................................................353

 Application...................................................................... ......354

Zero clamping.......................................................................355

Setting guidelines.................................................................356Setting parameters...............................................................366

Event counter CNTGGIO...........................................................379

Identification.........................................................................379

 Application............................................................................379

Setting parameters...............................................................379

Event function EVENT...............................................................379

Introduction...........................................................................379

Setting guidelines.................................................................379

Setting parameters...............................................................380

Logical signal status report BINSTATREP................................382

Table of contents

6

 Application manual

Page 13: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 13/457

 Application............................................................................382

Setting guidelines.................................................................383

Setting parameters...............................................................383

Measured value expander block RANGE_XP...........................383 Application............................................................................383

Setting guidelines.................................................................384

Disturbance report DRPRDRE..................................................384

 Application............................................................................384

Setting guidelines.................................................................385

Setting parameters...............................................................390

Event list....................................................................................399

 Application............................................................................399

Setting guidelines.................................................................399

Indications.................................................................................400 Application............................................................................400

Setting guidelines.................................................................400

Event recorder ..........................................................................401

 Application............................................................................401

Setting guidelines.................................................................401

Trip value recorder....................................................................401

 Application............................................................................401

Setting guidelines.................................................................402

Disturbance recorder.................................................................402

 Application............................................................................402Setting guidelines.................................................................403

Metering..........................................................................................403

Pulse-counter logic PCGGIO.....................................................403

 Application............................................................................404

Setting guidelines.................................................................404

Setting parameters...............................................................405

Function for energy calculation and demand handling

ETPMMTR.................................................................................405

 Application............................................................................405

Setting guidelines.................................................................406Setting parameters...............................................................407

Section 4 Station communication.................................................409Overview.........................................................................................409

IEC 61850-8-1 communication protocol.........................................409

 Application IEC 61850-8-1.........................................................409

Setting guidelines......................................................................411

Setting parameters....................................................................411

IEC 61850 generic communication I/O functions SPGGIO,

SP16GGIO................................................................................411

Table of contents

7

 Application manual

Page 14: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 14/457

 Application............................................................................411

Setting guidelines.................................................................411

Setting parameters...............................................................411

IEC 61850 generic communication I/O functions MVGGIO.......411 Application............................................................................412

Setting guidelines.................................................................412

Setting parameters...............................................................412

IEC 61850-8-1 redundant station bus communication..............412

 Application............................................................................413

Setting guidelines.................................................................414

Setting parameters...............................................................416

LON communication protocol.........................................................416

 Application.................................................................................416

Setting parameters....................................................................418SPA communication protocol.........................................................418

 Application.................................................................................418

Setting guidelines......................................................................420

Setting parameters....................................................................421

IEC 60870-5-103 communication protocol.....................................421

 Application.................................................................................421

Setting parameters....................................................................426

Multiple command and transmit MULTICMDRCV,

MULTICMDSND.............................................................................429

 Application.................................................................................430Setting guidelines......................................................................430

Settings................................................................................430

Setting parameters....................................................................430

Section 5 Remote communication................................................431Binary signal transfer......................................................................431

 Application.................................................................................431

Communication hardware solutions.....................................431

 Application possibility with one-phase REB670...................432

Setting guidelines......................................................................434

Setting parameters....................................................................436

Section 6 Configuration................................................................439Description of configuration REB670..............................................439

Description of 3 ph package A20...............................................439

Description of 3 ph package A31...............................................439

Description of 1 ph packages B20 and B21..............................439

Description of 1 ph package B31...............................................440

 Available configurations for pre-configured REB670.................440

Configuration X01......................................................................440

Table of contents

8

 Application manual

Page 15: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 15/457

Configuration X02......................................................................441

Configuration X03......................................................................441

Section 7 Glossary.......................................................................443

Table of contents

9

 Application manual

Page 16: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 16/457

10

Page 17: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 17/457

Section 1 Introduction

About this chapter

This chapter introduces the user to the manual as such.

1.1 Introduction to the application manual

1.1.1 About the complete set of manuals for an IED

The user’s manual (UM) is a complete set of five different manuals:

IEC09000744-1-en.vsd

   P   l  a  n  n   i  n  g   &  p  u  r  c   h  a  s  e

   d   i  s  p  o  s  a   l

   E  n  g   i  n  e  e  r   i  n  g

   I  n  s   t  a   l   l   i  n  g

   C  o  m  m   i  s  s   i  o  n   i  n  g

   O  p  e  r  a   t   i  o  n

   M  a   i  n   t  e  n  a  n  c  e

   D  e  c  o  m  m   i  s  s   i  o  n   i  n  g

   d  e   i  n  s   t  a   l   l   i  n  g   &

 Application manual

Operator’s manual

Installation and

Engineeringmanual

Commissioning manual

manual

Technical reference

IEC09000744 V1 EN

The Application Manual (AM) contains application descriptions, settingguidelines and setting parameters sorted per function. The application manualshould be used to find out when and for what purpose a typical protection functioncould be used. The manual should also be used when calculating settings.

The Technical Reference Manual (TRM) contains application and functionalitydescriptions and it lists function blocks, logic diagrams, input and output signals,setting parameters and technical data sorted per function. The technical reference

1MRK 505 211-UEN C Section 1Introduction

11

 Application manual

Page 18: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 18/457

manual should be used as a technical reference during the engineering phase,installation and commissioning phase, and during normal service.

The Installation and Commissioning Manual (ICM) contains instructions on

how to install and commission the protection IED. The manual can also be used asa reference during periodic testing. The manual covers procedures for mechanicaland electrical installation, energizing and checking of external circuitry, setting andconfiguration as well as verifying settings and performing directional tests. Thechapters are organized in the chronological order (indicated by chapter/sectionnumbers) in which the protection IED should be installed and commissioned.

The Operator’s Manual (OM) contains instructions on how to operate the protection IED during normal service once it has been commissioned. Theoperator’s manual can be used to find out how to handle disturbances or how toview calculated and measured network data in order to determine the cause of a fault.

The Engineering Manual (EM) contains instructions on how to engineer the IEDsusing the different tools in PCM600. The manual provides instructions on how toset up a PCM600 project and insert IEDs to the project structure. The manual alsorecommends a sequence for engineering of protection and control functions, LHMIfunctions as well as communication engineering for IEC 61850 and DNP3.

1.1.2 About the application manual

The application manual contains the following chapters:

• The chapter  “Requirements” describes current and voltage transformer 

requirements.• The chapter  “IED application” describes the use of the included software

functions in the IED. The chapter discusses application possibilities and givesguidelines for calculating settings for a particular application.

• The chapter  “Station communication“ describes the communication possibilities in a SA-system.

• The chapter  “Remote communication“ describes the remote end datacommunication possibilities through binary signal transferring.

• The chapter  “Configuration” describes the preconfiguration of the IED andits complements.

• The chapter  “Glossary” is a list of terms, acronyms and abbreviations used in

ABB technical documentation.

1.1.3 Intended audience

General

The application manual is addressing the system engineer/technical responsiblethat is responsible for specifying the application of the IED.

Section 1 1MRK 505 211-UEN C

Introduction

12

 Application manual

Page 19: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 19/457

Requirements

The system engineer/technical responsible must have a good knowledge about protection systems, protection equipment, protection functions and the configured

functional logics in the protection.

1.1.4 Revision notes

Revision Description

 A Minor corrections made

B Updates made for REB670 1.2.4

C Maintenance updates, PR corrections

1MRK 505 211-UEN C Section 1Introduction

13

 Application manual

Page 20: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 20/457

14

Page 21: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 21/457

Section 2 Requirements

About this chapter

This chapter describes current and voltage transformer requirements.

2.1 Current transformer requirements

The performance of a protection function will depend on the quality of the

measured current signal. Saturation of the current transformer (CT) will causedistortion of the current signal and can result in a failure to operate or causeunwanted operations of some functions. Consequently CT saturation can have aninfluence on both the dependability and the security of the protection. This

 protection IED has been designed to permit heavy CT saturation with maintainedcorrect operation.

2.1.1 Current transformer classification

To guarantee correct operation, the current transformers (CTs) must be able tocorrectly reproduce the current for a minimum time before the CT will begin to

saturate. To fulfill the requirement on a specified time to saturation the CTs mustfulfill the requirements of a minimum secondary e.m.f. that is specified below.

There are several different ways to specify CTs. Conventional magnetic core CTsare usually specified and manufactured according to some international or nationalstandards, which specify different protection classes as well. There are manydifferent standards and a lot of classes but fundamentally there are three differenttypes of CTs:

• High remanence type CT• Low remanence type CT• Non remanence type CT

The high remanence type has no limit for the remanent flux. This CT has amagnetic core without any airgap and a remanent flux might remain almost infinitetime. In this type of transformers the remanence can be up to around 80% of thesaturation flux. Typical examples of high remanence type CT are class P, PX, TPS,TPX according to IEC, class P, X according to BS (old British Standard) and nongapped class C, K according to ANSI/IEEE.

The low remanence type has a specified limit for the remanent flux. This CT ismade with a small air gap to reduce the remanence to a level that does not exceed10% of the saturation flux. The small air gap has only very limited influences on

1MRK 505 211-UEN C Section 2Requirements

15

 Application manual

Page 22: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 22/457

the other properties of the CT. Class PR, TPY according to IEC are low remanencetype CTs.

The non remanence type CT has practically negligible level of remanent flux.

This type of CT has relatively big air gaps in order to reduce the remanence to practically zero level. In the same time, these air gaps reduce the influence of the DC-component from the primary fault current. The air gaps will also decrease themeasuring accuracy in the non-saturated region of operation. Class TPZ accordingto IEC is a non remanence type CT.

Different standards and classes specify the saturation e.m.f. in different ways but itis possible to approximately compare values from different classes. The ratedequivalent limiting secondary e.m.f. Eal according to the IEC 60044 – 6 standard isused to specify the CT requirements for the IED. The requirements are alsospecified according to other standards.

2.1.2 Conditions

The requirements are a result of investigations performed in our network simulator.The current transformer models are representative for current transformers of highremanence and low remanence type. The results may not always be valid for nonremanence type CTs (TPZ).

The performances of the protection functions have been checked in the range fromsymmetrical to fully asymmetrical fault currents. Primary time constants of at least120 ms have been considered at the tests. The current requirements below are thus

applicable both for symmetrical and asymmetrical fault currents.Depending on the protection function phase-to-earth, phase-to-phase and three-

 phase faults have been tested for different relevant fault positions for example,close in forward and reverse faults, zone 1 reach faults, internal and external faults.The dependability and security of the protection was verified by checking for example, time delays, unwanted operations, directionality, overreach and stability.

The remanence in the current transformer core can cause unwanted operations or minor additional time delays for some protection functions. As unwantedoperations are not acceptable at all maximum remanence has been considered for fault cases critical for the security, for example, faults in reverse direction and

external faults. Because of the almost negligible risk of additional time delays andthe non-existent risk of failure to operate the remanence have not been consideredfor the dependability cases. The requirements below are therefore fully valid for allnormal applications.

It is difficult to give general recommendations for additional margins for remanence to avoid the minor risk of an additional time delay. They depend on the

 performance and economy requirements. When current transformers of lowremanence type (for example, TPY, PR) are used, normally no additional margin isneeded. For current transformers of high remanence type (for example, P, PX, TPS,TPX) the small probability of fully asymmetrical faults, together with high

Section 2 1MRK 505 211-UEN C

Requirements

16

 Application manual

Page 23: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 23/457

remanence in the same direction as the flux generated by the fault, has to be kept inmind at the decision of an additional margin. Fully asymmetrical fault current will

 be achieved when the fault occurs at approximately zero voltage (0°).Investigations have shown that 95% of the faults in the network will occur whenthe voltage is between 40° and 90°. In addition fully asymmetrical fault currentwill not exist in all phases at the same time.

2.1.3 Fault current

The current transformer requirements are based on the maximum fault current for faults in different positions. Maximum fault current will occur for three-phasefaults or single phase-to-earth faults. The current for a single phase-to-earth faultwill exceed the current for a three-phase fault when the zero sequence impedancein the total fault loop is less than the positive sequence impedance.

When calculating the current transformer requirements, maximum fault current for the relevant fault position should be used and therefore both fault types have to beconsidered.

2.1.4 Secondary wire resistance and additional load

The voltage at the current transformer secondary terminals directly affects thecurrent transformer saturation. This voltage is developed in a loop containing thesecondary wires and the burden of all relays in the circuit. For earth faults the loopincludes the phase and neutral wire, normally twice the resistance of the singlesecondary wire. For three-phase faults the neutral current is zero and it is justnecessary to consider the resistance up to the point where the phase wires areconnected to the common neutral wire. The most common practice is to use four wires secondary cables so it normally is sufficient to consider just a singlesecondary wire for the three-phase case.

The conclusion is that the loop resistance, twice the resistance of the singlesecondary wire, must be used in the calculation for phase-to-earth faults and the

 phase resistance, the resistance of a single secondary wire, may normally be usedin the calculation for three-phase faults.

As the burden can be considerable different for three-phase faults and phase-to-

earth faults it is important to consider both cases. Even in a case where the phase-to-earth fault current is smaller than the three-phase fault current the phase-to-earthfault can be dimensioning for the CT depending on the higher burden.

In isolated or high impedance earthed systems the phase-to-earth fault is not thedimensioning case and therefore the resistance of the single secondary wire alwayscan be used in the calculation, for this case.

1MRK 505 211-UEN C Section 2Requirements

17

 Application manual

Page 24: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 24/457

2.1.5 General current transformer requirements

The current transformer ratio is mainly selected based on power system data for example, maximum load. However, it should be verified that the current to the

 protection is higher than the minimum operating value for all faults that are to bedetected with the selected CT ratio. The minimum operating current is different for different functions and normally settable so each function should be checked.

The current error of the current transformer can limit the possibility to use a verysensitive setting of a sensitive residual overcurrent protection. If a very sensitivesetting of this function will be used it is recommended that the current transformer should have an accuracy class which have an current error at rated primary currentthat is less than ±1% (for example, 5P). If current transformers with less accuracyare used it is advisable to check the actual unwanted residual current during thecommissioning.

2.1.6 Rated equivalent secondary e.m.f. requirements

With regard to saturation of the current transformer all current transformers of highremanence and low remanence type that fulfill the requirements on the ratedequivalent secondary e.m.f. Eal below can be used. The characteristic of the nonremanence type CT (TPZ) is not well defined as far as the phase angle error isconcerned. If no explicit recommendation is given for a specific function wetherefore recommend contacting ABB to confirm that the non remanence type can

 be used.

The CT requirements for the different functions below are specified as a ratedequivalent limiting secondary e.m.f. Eal according to the IEC 60044-6 standard.Requirements for CTs specified in different ways are given at the end of this section.

2.1.6.1 Busbar protection

The main CT requirement for REB670 is that the CT do not saturate within 2 msafter fault current zero crossing.

The CT can be of high remanence or low remanence type and they can be usedtogether within the same zone of protection. Each of them must have a rated

equivalent secondary e.m.f. Eal that is larger than or equal to the requiredsecondary e.m.f. Ealreq below:

The high remanence type CT must fulfill

sn R al alreq f max CT L 2

 pn r 

I SE E 0.5 I R R  

I I³ = × × × + +

æ öç ÷è ø

EQUATION1534 V1 EN (Equation 1)

Section 2 1MRK 505 211-UEN C

Requirements

18

 Application manual

Page 25: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 25/457

The low remanence type CT must fulfill

sn R al alreq f max CT L 2

 pn r 

I SE E 0.2 I R R  

I I

³ = × × × + +æ öç ÷

è øEQUATION1535 V1 EN (Equation 2)

where

Ifmax Maximum primary fundamental frequency fault current on the busbar (A)

Ipn The rated primary CT current (A)

Isn The rated secondary CT current (A)

Ir  The rated current of the protection IED (A)

RCT The secondary resistance of the CT (W)

RL The resistance of the secondary wire and additional load (W). The loopresistance containing the phase and neutral wires, must be used for faults insolidly earthed systems. The resistance of a single secondary wire should beused for faults in high impedance earthed systems.

SR The burden of an IED current input channel (VA). SR=0.020 VA/channel for Ir =1

 A and SR=0.150 VA/channel for Ir =5 A.

The non remanence type CT

CTs of non remanence type (for example, TPZ) can be used but in this case theCTs within the differential zone must be of non remanence type. They must fulfill

the same requirements as for the low remanence type CTs and have a ratedequivalent secondary e.m.f. Eal that is larger than or equal to required secondarye.m.f. Ealreq below:

sn R al alreq f max CT L 2

 pn r 

I SE E 0.2 I R R  

I I³ = × × × + +

æ öç ÷è ø

EQUATION1536 V1 EN (Equation 3)

2.1.6.2 Breaker failure protection

The CTs must have a rated equivalent secondary e.m.f. Eal that is larger than or equal to the required secondary e.m.f. Ealreq below:

1MRK 505 211-UEN C Section 2Requirements

19

 Application manual

Page 26: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 26/457

sn R al alreq op CT L 2

 pn r 

I SE E 5 I R R  

I I

æ ö³ = × × × + +ç ÷

è øEQUATION1380 V1 EN (Equation 4)

where:

Iop The primary operate value (A)

Ipn The rated primary CT current (A)

Isn The rated secondary CT current (A)

Ir  The rated current of the protection IED (A)

RCT The secondary resistance of the CT (W)

RL The resistance of the secondary cable and additional load (W). The loop resistancecontaining the phase and neutral wires, must be used for faults in solidly earthed systems.The resistance of a single secondary wire should be used for faults in high impedanceearthed systems.

SR The burden of an IED current input channel (VA). SR=0.020 VA/channel for Ir =1 A and

SR=0.150 VA/channel for Ir =5 A

2.1.6.3 Non-directional instantaneous and definitive time, phase and residual

overcurrent protection

The CTs must have a rated equivalent secondary e.m.f. Eal that is larger than or equal to the required secondary e.m.f. Ealreq below:

sn R al alreq op CT L 2

 pn r 

I SE E 1,5 I R R  

I I

æ ö³ = × × × + +ç ÷

è øEQUATION1381 V1 EN (Equation 5)

where:

Iop The primary operate value (A)

Ipn The rated primary CT current (A)

Isn The rated secondary CT current (A)

Ir  The rated current of the protection IED (A)

RCT The secondary resistance of the CT (W)

RL The resistance of the secondary cable and additional load (W). The loop resistancecontaining the phase and neutral wires, must be used for faults in solidly earthed systems.The resistance of a single secondary wire should be used for faults in high impedanceearthed systems.

SR The burden of an IED current input channel (VA). SR=0.020 VA/channel for Ir =1 A and

SR=0.150 VA/channel for Ir =5 A

Section 2 1MRK 505 211-UEN C

Requirements

20

 Application manual

Page 27: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 27/457

2.1.6.4 Non-directional inverse time delayed phase and residual overcurrent

protection

The requirement according to Equation 6 and Equation 7 does not need to befulfilled if the high set instantaneous or definitive time stage is used. In this caseEquation 5 is the only necessary requirement.

If the inverse time delayed function is the only used overcurrent protection functionthe CTs must have a rated equivalent secondary e.m.f. Eal that is larger than or equal to the required secondary e.m.f. Ealreq below:

sn R al alreq op CT L 2

 pn r 

I SE E 20 I R R  

I I

æ ö³ = × × × + +ç ÷

è øEQUATION1076 V1 EN (Equation 6)

where

Iop The primary current set value of the inverse time function (A)

Ipn The rated primary CT current (A)

Isn The rated secondary CT current (A)

Ir  The rated current of the protection IED (A)

RCT The secondary resistance of the CT (W)

RL The resistance of the secondary cable and additional load (W). The loopresistance containing the phase and neutral wires, must be used for faults insolidly earthed systems. The resistance of a single secondary wire should beused for faults in high impedance earthed systems.

SR The burden of an IED current input channel (VA). SR=0.020 VA/channel for Ir =1

 A and SR=0.150 VA/channel for Ir =5 A

Independent of the value of Iop the maximum required Eal is specified according tothe following:

sn R al alreq max k max CT L 2

 pn r 

I SE E I R R  

I I

æ ö³ = × × + +ç ÷

è øEQUATION1077 V1 EN (Equation 7)

where

Ikmax Maximum primary fundamental frequency current for close-in faults (A)

1MRK 505 211-UEN C Section 2Requirements

21

 Application manual

Page 28: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 28/457

2.1.7 Current transformer requirements for CTs according to

other standards

All kinds of conventional magnetic core CTs are possible to use with the IEDs if they fulfill the requirements corresponding to the above specified expressed as therated equivalent secondary e.m.f. Eal according to the IEC 60044-6 standard. Fromdifferent standards and available data for relaying applications it is possible toapproximately calculate a secondary e.m.f. of the CT comparable with Eal. Bycomparing this with the required secondary e.m.f. Ealreq it is possible to judge if theCT fulfills the requirements. The requirements according to some other standardsare specified below.

2.1.7.1 Current transformers according to IEC 60044-1, class P, PR

A CT according to IEC 60044-1 is specified by the secondary limiting e.m.f. E2max.The value of the E2max is approximately equal to the corresponding Eal accordingto IEC 60044-6. Therefore, the CTs according to class P and PR must have asecondary limiting e.m.f. E2max that fulfills the following:

2maxmax

alreq E E >

 EQUATION1383 V2 EN (Equation 8)

2.1.7.2 Current transformers according to IEC 60044-1, class PX, IEC

60044-6, class TPS (and old British Standard, class X)

CTs according to these classes are specified approximately in the same way by arated knee-point e.m.f. Eknee (Ek for class PX, EkneeBS for class X and the limitingsecondary voltage Ual for TPS). The value of the Eknee is lower than thecorresponding Eal according to IEC 60044-6. It is not possible to give a generalrelation between the Eknee and the Eal but normally the Eknee is approximately 80 %

of the Eal. Therefore, the CTs according to class PX, X and TPS must have a ratedknee-point e.m.f. Eknee that fulfills the following:

Eknee » Ek  » EkneeBS » Ual > 0.8 · (maximum of Ealreq)

EQUATION2100 V1 EN (Equation 9)

2.1.7.3 Current transformers according to ANSI/IEEE

Current transformers according to ANSI/IEEE are partly specified in differentways. A rated secondary terminal voltage UANSI is specified for a CT of class C.

Section 2 1MRK 505 211-UEN C

Requirements

22

 Application manual

Page 29: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 29/457

UANSI is the secondary terminal voltage the CT will deliver to a standard burden at20 times rated secondary current without exceeding 10 % ratio correction. Thereare a number of standardized UANSI values for example, UANSI is 400 V for a C400

CT. A corresponding rated equivalent limiting secondary e.m.f. EalANSI can beestimated as follows:

EalANSI

20 Isn

RCT

U A NSI

+× × 20 Isn

RC T

× × 20 Isn

ZbANSI

× ×+= =

EQUATION971 V1 EN (Equation 10)

where:

ZbANSI The impedance (that is, complex quantity) of the standard ANSI burden for the specific Cclass (W)

U ANSI The secondary terminal voltage for the specific C class (V)

The CTs according to class C must have a calculated rated equivalent limitingsecondary e.m.f. EalANSI that fulfills the following:

alANSI alreqE max imum of E>

EQUATION1384 V1 EN (Equation 11)

A CT according to ANSI/IEEE is also specified by the knee-point voltageUkneeANSI that is graphically defined from an excitation curve. The knee-point

voltage UkneeANSI normally has a lower value than the knee-point e.m.f. accordingto IEC and BS. UkneeANSI can approximately be estimated to 75 % of thecorresponding Eal according to IEC 60044 6. Therefore, the CTs according to ANSI/IEEE must have a knee-point voltage UkneeANSI that fulfills the following:

EkneeANSI > 0.75 · (maximum of Ealreq)

EQUATION2101 V1 EN (Equation 12)

2.2 Voltage transformer requirements

The performance of a protection function will depend on the quality of themeasured input signal. Transients caused by capacitive voltage transformers(CVTs) can affect some protection functions.

Magnetic or capacitive voltage transformers can be used.

The capacitive voltage transformers (CVTs) should fulfill the requirementsaccording to the IEC 60044–5 standard regarding ferro-resonance and transients.The ferro-resonance requirements of the CVTs are specified in chapter 7.4 of thestandard.

1MRK 505 211-UEN C Section 2Requirements

23

 Application manual

Page 30: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 30/457

The transient responses for three different standard transient response classes, T1,T2 and T3 are specified in chapter 15.5 of the standard. CVTs according to allclasses can be used.

The protection IED has effective filters for these transients, which gives secure andcorrect operation with CVTs.

2.3 SNTP server requirements

The SNTP server to be used is connected to the local network, that is not more than4-5 switches or routers away from the IED. The SNTP server is dedicated for itstask, or at least equipped with a real-time operating system, that is not a PC withSNTP server software. The SNTP server should be stable, that is, either 

synchronized from a stable source like GPS, or local without synchronization.Using a local SNTP server without synchronization as primary or secondary server in a redundant configuration is not recommended.

Section 2 1MRK 505 211-UEN C

Requirements

24

 Application manual

Page 31: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 31/457

Section 3 IED application

About this chapter

This chapter describes the use of the included software functions in the IED. Thechapter discusses application possibilities and gives guidelines for calculatingsettings for a particular application.

3.1 General IED application

REB670 is designed for the selective, reliable and fast differential protection of  busbars, T-connections and meshed corners. REB670 can be used for protection of single and double busbar with or without transfer bus, double circuit breaker or one-and-half circuit breaker stations. The IED is applicable for the protection of medium voltage (MV), high voltage (HV) and extra high voltage (EHV)installations at a power system frequency of 50Hz or 60Hz. The IED can detect alltypes of internal phase-to-phase and phase-to-earth faults in solidly earthed or lowimpedance earthed power systems, as well as all internal multi-phase faults inisolated or high-impedance earthed power systems.

Ordering of VT inputs inside of the busbar protection IED will allow integration of 

voltage related functionality like under-voltage release, residual over-voltage, power functions, metering and voltage recording during the faults. However attention shall be given to the fact that inclusion of VT inputs will reduce number of available CT inputs (in total 24 analogue inputs are the product limit).Consequently when VT inputs are ordered the busbar protection IED will beapplicable for buses with a fewer number of bays. Practically the number of available CT inputs will limit the size of the station which can be protected.

REB670 has very low requirements on the main current transformers (that is, CTs)and no interposing current transformers are necessary. For all applications, it is

 possible to include and mix main CTs with 1A and 5A rated secondary current

within the same protection zone. Typically, CTs with up to 10:1 ratio differencecan be used within the same differential protection zone. Adjustment for differentmain CT ratios is achieved numerically by a parameter setting.

The numerical, low-impedance differential protection function is designed for fastand selective protection for faults within protected zone. All connected CT inputsare provided with a restraint feature. The minimum pick-up value for thedifferential current is set to give a suitable sensitivity for all internal faults. For 

 busbar protection applications typical setting value for the minimum differentialoperating current is from 50% to 150% of the biggest CT. This setting is madedirectly in primary amperes. The operating slope for the differential operatingcharacteristic is fixed to 53% in the algorithm.

1MRK 505 211-UEN C Section 3IED application

25

 Application manual

Page 32: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 32/457

The fast tripping time of the low-impedance differential protection function isespecially advantageous for power system networks with high fault levels or wherefast fault clearance is required for power system stability.

The advanced open CT detection algorithm detects instantly the open CTsecondary circuits and prevents differential protection operation without any needfor additional check zone.

Differential protection zones in REB670 include a sensitive operational level. Thissensitive operational level is designed to be able to detect internal busbar earthfaults in low impedance earthed power systems (that is, power systems where theearth-fault current is limited to a certain level, typically between 300A and 2000A

 primary by a neutral point reactor or resistor). Alternatively this sensitive level can be used when high sensitivity is required from busbar differential protection (thatis, energizing of the bus via long line).

Overall operating characteristic of the differential function in REB670 is shown infigure 1.

Differential protectionoperation characteristic

Operate

region

Diff Oper Level

   I   d   [   P  r   i  m  a  r  y   A  m  p  s   ]

Iin

[Primary Amps]

s=0.53

   I d

  =   I i  n

Sensitivedifferentialprotection

en06000142.vsd

Sensitive Oper LevelSens Iin

 Block

IEC06000142 V1 EN

Figure 1: REB670 operating characteristic 

Integrated overall check zone feature, independent from any disconnector position,is available. It can be used in double busbar stations to secure stability of the

 busbar differential protection in case of entirely wrong status indication of busbar disconnector in any of the feeder bays.

Flexible, software based dynamic Zone Selection enables easy and fast adaptationto the most common substation arrangements such as single busbar with or withouttransfer bus, double busbar with or without transfer bus, one-and-a-half breaker stations, double busbar-double breaker stations, ring busbars, and so on. Thesoftware based dynamic Zone Selections ensures:

Section 3 1MRK 505 211-UEN C

IED application

26

 Application manual

Page 33: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 33/457

• Dynamic linking of measured CT currents to the appropriate differential protection zone as required by substation topology

• Efficient merging of the two differential zones when required by substationtopology (that is load-transfer)

• Selective operation of busbar differential protection ensures tripping only of circuit breakers connected to the faulty zone

• Correct marshaling of backup-trip commands from internally integrated or external circuit breaker failure protections to all surrounding circuit breakers

• Easy incorporation of bus-section and/or bus-coupler bays (that is, tie- breakers) with one or two sets of CTs into the protection scheme

• Disconnector and/or circuit breaker status supervision

Advanced Zone Selection logic accompanied by optionally available end-fault and/or circuit breaker failure protections ensure minimum possible tripping time andselectivity for faults within the blind spot or the end zone between bay CT and baycircuit breaker. Therefore REB670 offers best possible coverage for such faults infeeder and bus-section/bus-coupler bays.

Optionally available circuit breaker failure protection, one for every CT input intoREB670, offers secure local back-up protection for the circuit breakers in the station.

Optionally available four-stage, non-directional overcurrent protections, one for every CT input into REB670, provide remote backup functionality for connectedfeeders and remote-end stations.

Optionally available voltage and frequency protection functions open possibility toinclude voltage release criterion for busbar protection or to integrate independentover-, under-voltage protection for the bus in the busbar protection IED.

Optionally available over-current, thermal overload and capacitor bank protectionfunctions open possibilities to integrate protection of shunt reactors and shuntcapacitor banks into the busbar protection IED.

It is normal practice to have just one busbar protection IED per busbar. Nevertheless some utilities do apply two independent busbar protection IEDs per zone of protection. REB670 IED fits both solutions.

A simplified bus differential protection for multi-phase faults and earth faults can be obtained by using a single, one-phase REB670 IED with external auxiliarysummation current transformers.

The wide application flexibility makes this product an excellent choice for bothnew installations and the refurbishment of existing installations.

Optional apparatus control for up to 30 objects can provide a facility to drawsimplified single line diagram (SLD) of the station on the local HMI. Note that insuch case medium-size, graphic display shall be ordered.

 Note that customized REB670 is delivered without anyconfiguration. Thus the complete IED engineering shall be done by

the customer or its system integrator. In order to secure proper 

1MRK 505 211-UEN C Section 3IED application

27

 Application manual

Page 34: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 34/457

operation of the busbar protection it is strictly recommended toalways start engineering work from the PCM600 project for the pre-configured REB670 which is the closest to the actual application.Then, necessary modifications shall be applied in order to adopt thecustomized IED configuration to suite the actual station layout. ThePCM600 project for the pre-configured REB670 IEDs is availablein the Connectivity Package DVD.

3.2 Analog inputs

3.2.1 Introduction

Analog input channels must be configured and set properly to get correctmeasurement results and correct protection operations. For power measuring andall directional and differential functions the directions of the input currents must bedefined properly. Measuring and protection algorithms in the IED use primarysystem quantities. Setting values are in primary quantities as well and it isimportant to set the data about the connected current and voltage transformers

 properly.

A reference PhaseAngleRef can be defined to facilitate service values reading. Thisanalog channels phase angle will always be fixed to zero degrees and all other angle information will be shown in relation to this analog input. During testing and

commissioning of the IED the reference channel can be changed to facilitate testingand service values reading.

The availability of VT inputs depends on the ordered transformer input module (TRM) type.

3.2.2 Setting guidelines

The available setting parameters related to analog inputs are

depending on the actual hardware (TRM) and the logicconfiguration made in PCM600.

3.2.2.1 Setting of the phase reference channel

All phase angles are calculated in relation to a defined reference. An appropriateanalog input channel is selected and used as phase reference. The parameter 

 PhaseAngleRef defines the analog channel that is used as phase angle reference.

Section 3 1MRK 505 211-UEN C

IED application

28

 Application manual

Page 35: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 35/457

ExampleThe setting PhaseAngleRef=10 shall be used if a phase-to-earth voltage (usuallythe L1 phase-to-earth voltage connected to VT channel number 10 of the analogcard) is selected to be the phase reference.

Setting of current channelsThe direction of a current to the IED is depending on the connection of the CT.Unless indicated otherwise, the main CTs are supposed to be star connected andcan be connected with the earthing point to the object or from the object. Thisinformation must be set in the IED. The convention of the directionality is definedas follows: A positive value of current, power, and so on means that the quantityhas the direction into the object and a negative value means direction out from theobject. For directional functions the direction into the object is defined as Forwardand the direction out from the object is defined as Reverse. See figure 2

A positive value of current, power, and so on (forward) means that the quantity hasa direction towards the object. - A negative value of current, power, and so on(reverse) means a direction away from the object. See figure 2.

Protected Object

Line, transformer, etc

ForwardReverse

Definition of direction

for directional functions

Measured quantity is

positive when flowing

towards the object

e.g. P, Q, I

ReverseForward

Definition of direction

for directional functions

e.g. P, Q, I

Measured quantity is

positive when flowing

towards the object

Set parameter 

CTStarPoint

Correct Setting is

"ToObject"

Set parameter 

CTStarPoint

Correct Setting is

"FromObject"  

en05000456.vsd

IEC05000456 V1 EN

Figure 2: Internal convention of the directionality in the IED 

With correct setting of the primary CT direction, CTStarPoint set to FromObject or ToObject , a positive quantities always flowing towards the object and a direction

defined as Forward always is looking towards the object. The following examplesshow the principle.

Example 1Two IEDs used for protection of two objects.

1MRK 505 211-UEN C Section 3IED application

29

 Application manual

Page 36: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 36/457

Transformer 

protection

Transformer 

Line

Line

Setting of current input:

Set parameter CTStarPoint with

Transformer as

reference object.

Correct setting is

"ToObject"

ForwardReverse

Definition of direction

for directional functions

Line protection

Setting of current input:

Set parameter CTStarPoint with

Transformer as

reference object.

Correct setting is

"ToObject"

Setting of current input:

Set parameter CTStarPoint with

Line as

reference object.

Correct setting is

"FromObject"

en05000753.vsd

Is

Is

Ip

Ip I

p

IEC05000753 V1 EN

Figure 3: Example how to set CTStarPoint parameters in the IED 

The figure 3 shows the normal case where the objects have their own CTs. Thesettings for CT direction shall be done according to the figure. To protect the line

the direction of the directional functions of the line protection shall be set to Forward . This means that the protection is looking towards the line.

Example 2Two IEDs used for protection of two objects and sharing a CT.

Section 3 1MRK 505 211-UEN C

IED application

30

 Application manual

Page 37: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 37/457

Transformer 

protection

Transformer 

Line

Setting of current input:

Set parameter 

CTStarPoint with

Transformer as

reference object.

Correct setting is

"ToObject"

ForwardReverse

Definition of direction

for directional functions

Line protection

Setting of current input:

Set parameter 

CTStarPoint with

Transformer as

reference object.

Correct setting is

"ToObject"

Setting of current input:

Set parameter 

CTStarPoint with

Line as

reference object.

Correct setting is

"FromObject"

en05000460.vsd

IEC05000460 V1 EN

Figure 4: Example how to set CTStarPoint parameters in the IED 

This example is similar to example 1, but here the transformer is feeding just oneline and the line protection uses the same CT as the transformer protection does.The CT direction is set with different reference objects for the two IEDs though itis the same current from the same CT that is feeding the two IEDs. With thesesettings the directional functions of the line protection shall be set to Forward tolook towards the line.

Example 3One IED used to protect two objects.

1MRK 505 211-UEN C Section 3IED application

31

 Application manual

Page 38: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 38/457

Transformer and

Line protection

Transformer 

Line

Setting of current input:

Set parameter 

CTStarPoint with

Transformer as

reference object.

Correct setting is

"ToObject"

ReverseForward

Definition of direction

for directional

line functions

Setting of current input:

Set parameter 

CTStarPoint with

Transformer as

reference object.

Correct setting is

"ToObject"

en05000461.vsd

IEC05000461 V1 EN

Figure 5: Example how to set CTStarPoint parameters in the IED 

In this example one IED includes both transformer and line protection and the line protection uses the same CT as the transformer protection does. For both currentinput channels the CT direction is set with the transformer as reference object. Thismeans that the direction Forward for the line protection is towards the transformer.To look towards the line the direction of the directional functions of the line

 protection must be set to Reverse. The direction Forward / Reverse is related to thereference object that is the transformer in this case.

When a function is set to Reverse and shall protect an object in reverse direction it

shall be noted that some directional functions are not symmetrical regarding thereach in forward and reverse direction. It is in first hand the reach of the directionalcriteria that can differ. Normally it is not any limitation but it is advisable to have itin mind and check if it is acceptable for the application in question.

If the IED has a sufficient number of analog current inputs an alternative solution isshown in figure 6. The same currents are fed to two separate groups of inputs andthe line and transformer protection functions are configured to the different inputs.The CT direction for the current channels to the line protection is set with the lineas reference object and the directional functions of the line protection shall be set to

 Forward to protect the line.

Section 3 1MRK 505 211-UEN C

IED application

32

 Application manual

Page 39: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 39/457

Transformer and

Line protection

Transformer 

Line

Setting of current input

for transformer functions:

Set parameter 

CTStarPoint with

Transformer as

reference object.

Correct setting is

"ToObject"

ForwardReverse

Definition of direction

for directional

line functions

Setting of current input

for transformer functions:

Set parameter 

CTStarPoint with

Transformer as

reference object.

Correct setting is

"ToObject"

Setting of current input

for line functions:

Set parameter 

CTStarPoint withLine as

reference object.

Correct setting is

"FromObject"

en05000462.vsd

IEC05000462 V1 EN

Figure 6: Example how to set CTStarPoint parameters in the IED 

1MRK 505 211-UEN C Section 3IED application

33

 Application manual

Page 40: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 40/457

Busbar 

Protection

Busbar 

1

2

2

1

en06000196.vsd

IEC06000196 V1 EN

Figure 7: Example how to set CTStarPoint parameters in the IED 

For busbar protection it is possible to set the CTStarPoint parameters in two ways.

The first solution will be to use busbar as a reference object. In that case for all CT

inputs marked with 1 in figure 7, set CTStarPoint = ToObject , and for all CT inputsmarked with 2 in figure 7, set CTStarPoint = FromObject .

The second solution will be to use all connected bays as reference objects. In thatcase for all CT inputs marked with 1 in figure 7, set CTStarPoint = FromObject ,and for all CT inputs marked with 2 in figure 7, set CTStarPoint = ToObject .

Regardless which one of the above two options is selected busbar differential protection will behave correctly.

Section 3 1MRK 505 211-UEN C

IED application

34

 Application manual

Page 41: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 41/457

The main CT ratios must also be set. This is done by setting the two parametersCTsec and CTprim for each current channel. For a 1000/1 A CT the followingsetting shall be used:

• CTprim = 1000 (value in A)• CTsec =1 (value in A).

Examples on how to connect, configure and set CT inputs for most

commonly used CT connectionsFigure 8 defines the marking of current transformer terminals commonly usedaround the world:

In the SMAI function block, you have to set if the SMAI block ismeasuring current or voltage. This is done with the parameter:

 AnalogInputType: Current/voltage. The ConnectionType: phase - phase/phase-earth and GlobalBaseSel .

ISec    I   P

  r   i

S1 (X1)

P1

(H1)

P2(H2)

S2 (X2)

P2

(H2)

P1(H1)

x  x 

a) b) c)

en06000641.vsd

S2 (X2) S1 (X1)

IEC06000641 V1 EN

Figure 8: Commonly used markings of CT terminals 

Where:

a) is symbol and terminal marking used in this document. Terminals marked with a dot indicatesthe primary and secondary winding terminals with the same (that is, positive) polarity

b) and c) are equivalent symbols and terminal marking used by IEC (ANSI) standard for CTs. Note thatfor these two cases the CT polarity marking is correct!

It shall be noted that depending on national standard and utility practices, the ratedsecondary current of a CT has typically one of the following values:

• 1A• 5A

However in some cases the following rated secondary currents are used as well:

1MRK 505 211-UEN C Section 3IED application

35

 Application manual

Page 42: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 42/457

• 2A• 10A

The IED fully supports all of these rated secondary values.

It is recommended to:

• use 1A rated CT input into the IED in order to connect CTswith 1A and 2A secondary rating

• use 5A rated CT input into the IED in order to connect CTswith 5A and 10A secondary rating

Example on how to connect a star connected three-phase CT set to

the IEDFigure 9 gives an example on how to connect a star connected three-phase CT setto the IED. It gives an overview of required actions by the user in order to makethis measurement available to the built-in protection and control functions withinthe IED as well.

L1

   I   L   1

   I   L   2

   I   L   3

L2 L3

Protected Object

CT 600/5

Star Connected

IL1

IL2

IL3

IED

1

2

3

4

SMAI_20

IEC11000025-2-en.vsd

IEC11000025 V2 EN

Figure 9: Star connected three-phase CT set with star point towards the protected object 

Section 3 1MRK 505 211-UEN C

IED application

36

 Application manual

Page 43: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 43/457

Where:

1) The drawing shows how to connect three individual phase currents from a star connectedthree-phase CT set to the three CT inputs of the IED.

2) shows how to connect residual/neutral current from the three-phase CT set to the fourth

inputs in the IED. It shall be noted that if this connection is not made, the IED will stillcalculate this current internally by vectorial summation of the three individual phase currents.

3) is the TRM where these current inputs are located. It shall be noted that for all thesecurrent inputs the following setting values shall be entered.

• CTprim=600A• CTsec=5A• CTStarPoint=ToObject

Inside the IED only the ratio of the first two parameters is used. The third parameter as setin this example will have no influence on the measured currents (that is, currents arealready measured towards the protected object).

4) are three connections made in the Signal Matrix tool (SMT), which connects these three

current inputs to the first three input channels on the preprocessing function block 6).Depending on the type of functions, which need this current information, more than onepreprocessing block might be connected in parallel to these three CT inputs.

5) is a connection made in the Signal Matrix tool (SMT), which connects the residual/neutralcurrent input to the fourth input channel of the preprocessing function block 6). Note thatthis connection in SMT shall not be done if the residual/neutral current is not connected tothe IED. In that case the pre-processing block will calculate it by vectorial summation of the three individual phase currents.

6) is a Preprocessing block that has the task to digitally filter the connected analog inputs andcalculate:

• fundamental frequency phasors for all four input channels• harmonic content for all four input channels• positive, negative and zero sequence quantities by using the fundamental frequency

phasors for the first three input channels (channel one taken as reference for 

sequence quantities)

These calculated values are then available for all built-in protection and control functionswithin the IED, which are connected to this preprocessing function block in theconfiguration tool. For this application most of the preprocessing settings can be left to thedefault values.If frequency tracking and compensation is required (this feature is typically required onlyfor IEDs installed in the generating stations), then the setting parameters DFTReferenceshall be set accordingly.

 

Another alternative is to have the star point of the three-phase CT set as shown infigure :

1MRK 505 211-UEN C Section 3IED application

37

 Application manual

Page 44: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 44/457

7

8

9

10

11

12

1

2

3

4

5

6

L1

   I   L   1

   I   L   2

   I   L   3

L2 L3

Protected Object

CT 800/1

Star ConnectedIL1

IL2

IL3

 AI 01 (I)

 AI 02 (I)

 AI 03 (I)

 AI 04 (I)

 AI 05 (I)

 AI 06 (I)

IR

IED

1

3

4

2

5

IEC06000644-3-en.vsd

 6

SMAI2

BLOCK AI3P

 AI1

 AI2

 AI3

 AI4

 AIN

^GRP2L2

^GRP2L1

^GRP2L3

^GRP2N

IEC06000644 V3 EN

Figure 10: Star connected three-phase CT set with its star point away from the protected object 

In this case everything is done in a similar way as in the above described example,except that for all used current inputs on the TRM the following setting parametersshall be entered as shown in the example figure 10:

• CTprim=600A• CTsec=5A• CTStarPoint =FromObject

Inside the IED only the ratio of the first two parameters is used. The third parameter as set in this example will invert the measured currents (that is, turn thecurrents by 180°) in order to ensure that the currents within the IED are measuredtowards the protected object.

Example how to connect delta connected three-phase CT set to the

IEDFigure 11 gives an example how to connect a delta connected three-phase CT set tothe IED. It gives an overview of the required actions by the user in order to makethis measurement available to the built-in protection and control functions in theIED as well.

Section 3 1MRK 505 211-UEN C

IED application

38

 Application manual

Page 45: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 45/457

7

8

9

10

11

12

1

2

3

4

5

6

L1

   I

   L   1

   I

   L   2

   I

   L   3

L2 L3

Protected Object

 AI 01 (I)

 AI 02 (I)

 AI 03 (I)

 AI 04 (I)

 AI 05 (I)

 AI 06 (I)

IED

IL1-IL2

IL2-IL3

IL3-IL1

1

2

3

.

# Not used

5

IEC06000645-3-en.vsd

SMAI2

BLOCK

^GRP2L1

 AI3P

 AI1

 AI2

 AI3

 AI4

 AIN

^GRP2L2

^GRP2L3

^GRP2N

4

   C   T   6   0   0   /   5

   i  n   D  e   l   t  a

   D   A   B   C  o  n  n  e  c   t  e   d

IEC06000645 V3 EN

Figure 11: Delta DAB connected three-phase CT set 

Where:

1) shows how to connect three individual phase currents from a delta connected three-phaseCT set to three CT inputs of the IED.

2) is the TRM where these current inputs are located. It shall be noted that for all thesecurrent inputs the following setting values shall be entered.

600346

3sec 5

 primCT A

CT A

= =

=

IECEQUATION2413 V1 EN (Equation 13)

• CTStarPoint =ToObject 

Inside the IED only the ratio of the first two parameters is used. The third parameter as setin this example will have no influence on the measured currents (that is, currents arealready measured towards the protected object).

Table continues on next page

1MRK 505 211-UEN C Section 3IED application

39

 Application manual

Page 46: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 46/457

3) are three connections made in Signal Matrix Tool (SMT), which connect these threecurrent inputs to first three input channels of the preprocessing function block 6).Depending on the type of functions which need this current information, more then onepreprocessing block might be connected in parallel to these three CT inputs.

4) shows that the fourth input channel of the preprocessing function block shall not beconnected in SMT.

5) is a Preprocessing block that has the task to digitally filter the connected analog inputs andcalculate:

• fundamental frequency phasors for all four input channels• harmonic content for all four input channels• positive, negative and zero sequence quantities by using the fundamental frequency

phasors for the first three input channels (channel one taken as reference for sequence quantities)

These calculated values are then available for all built-in protection and control functionswithin the IED, which are connected to this preprocessing function block in theconfiguration tool. For this application most of the preprocessing settings can be left to thedefault values.If frequency tracking and compensation is required (this feature is typically required onlyfor IEDs installed in the generating stations) then the setting parameters DFTReference 

shall be set accordingly.

Another alternative is to have the delta connected CT set as shown in figure 12:

7

8

9

10

1112

1

2

3

4

5

6

L1

   I   L   1

   I   L   2

   I   L   3

L2 L3

Protected Object

 AI 01 (I)

 AI 02 (I)

 AI 03 (I)

 AI 04 (I)

 AI 05 (I)

 AI 06 (I)

IED

IL3-IL2

IL2-IL1

IL1-IL3

2

3

#Not used

5

IEC06000646-3-en.vsd

4

SMAI2

BLOCK

^GRP2L1

 AI3P

 AI1

 AI2

 AI3

 AI4

 AIN

^GRP2L2

^GRP2L3

^GRP2N   C   T   8   0   0   /   1

    i  n   d  e   l   t  a

   D   C   A   C  o  n  n  e  c   t  e   d

IEC06000646 V3 EN

Figure 12: Delta DAC connected three-phase CT set 

Section 3 1MRK 505 211-UEN C

IED application

40

 Application manual

Page 47: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 47/457

In this case, everything is done in a similar way as in the above described example,except that for all used current inputs on the TRM the following setting parametersshall be entered:

sec

800 4623

1

 primCT A

CT A

= =

=IECEQUATION2414 V1 EN (Equation 14)

• CTStarPoint =ToObject

Inside the IED only the ratio of the first two parameters is used. The third parameter as set in this example will have no influence on the measured currents(that is, currents are already measured towards the protected object).

Example how to connect single-phase CT to the IEDFigure 13 gives an example how to connect the single-phase CT to the IED. Itgives an overview of the required actions by the user in order to make thismeasurement available to the built-in protection and control functions within theIED as well.

Protected Object

7

8

9

10

11

12

1

2

3

4

5

6

L1 L2 L3

 AI01 (I)

 AI02 (I)

 AI03 (I)

 AI04 (I)

 AI05 (I)

 AI06 (I)

IED

   I   N   P

INP

INP

2

1

3

# Not used

# Not used

# Not used

IEC06000647-3-en.vsd

5

SMAI2

BLOCK

^GRP2L1

 AI3P

 AI1

 AI2

 AI3

 AI4

 AIN

^GRP2L2

^GRP2L3

^GRP2N

4

   C   T   1   0   0   0   /   1

a)

b)

IEC06000647 V3 EN

Figure 13: Connections for single-phase CT input 

1MRK 505 211-UEN C Section 3IED application

41

 Application manual

Page 48: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 48/457

Where:

1) shows how to connect single-phase CT input in the IED.

2) is TRM where these current inputs are located. It shall be noted that for all thesecurrent inputs the following setting values shall be entered.

For connection (a) shown in figure 13:

sec

600

5

 primCT A

CT A

=

=IECEQUATION2415 V1 EN (Equation 15)

CTStarPoint =ToObject 

Inside the IED only the ratio of the first two parameters is used. The third parameter asset in this example will have no influence on the measured currents (that is, currentsare already measured towards the protected object). For connection (b) shown in figure 13:

sec

600

5

 primCT A

CT A

=

=IECEQUATION2415 V1 EN (Equation 16)

CTStarPoint =FromObject 

Inside the IED only the ratio of the first two parameters is used. The third parameter asset in this example will invert the measured currents (that is, turn the currents by 180°)in order to ensure that the currents within the IED are measured towards the protectedobject.

3) shows that in this example the first three input channel of the preprocessing block isnot connected in Signal Matrix Tool (SMT).

4) shows the connection made in SMT tool, which connect this CT input to the fourth inputchannel of the preprocessing function block 5).

5) is a Preprocessing block that has the task to digitally filter the connected analog inputs

and calculate:

• fundamental frequency phasors for all four input channels• harmonic content for all four input channels• positive, negative and zero sequence quantities by using the fundamental

frequency phasors for the first three input channels (channel one taken asreference for sequence quantities)

These calculated values are then available for all built-in protection and controlfunctions within the IED, which are connected to this preprocessing function block. inthe configuration tool. For this application most of the preprocessing settings can be leftto the default valuesIf frequency tracking and compensation is required (this feature is typically requiredonly for IEDs installed in the generating stations) then the setting parametersDFTReference shall be set accordingly.

Setting of voltage channelsAs the IED uses primary system quantities the main VT ratios must be known tothe IED. This is done by setting the two parameters VTsec and VTprim for eachvoltage channel. The phase-to-phase value can be used even if each channel isconnected to a phase-to-earth voltage from the VT.

ExampleConsider a VT with the following data:

Section 3 1MRK 505 211-UEN C

IED application

42

 Application manual

Page 49: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 49/457

132 110

3 3

kV V 

EQUATION2016 V1 EN (Equation 17)

The following setting should be used: VTprim=132 (value in kV) VTsec=110

(value in V)

Examples how to connect, configure and set VT inputs for most

commonly used VT connectionsFigure 14 defines the marking of voltage transformer terminals commonly usedaround the world.

 A

(H1)

B

(H2)

b

(X2)

a

(X1) A

(H1)

N

(H2)

n

(X2)

a

(X1)

b) c)

 A

(H1)

N

(H2)

dn

(X2)

da

(X1)

d)

UPri

+ +

USec

a)

en06000591.vsd

IEC06000591 V1 EN

Figure 14: Commonly used markings of VT terminals 

Where:

a) is the symbol and terminal marking used in this document. Terminals marked with a dot

indicate the primary and secondary winding terminals with the same (positive) polarity

b) is the equivalent symbol and terminal marking used by IEC (ANSI) standard for phase-to-earth connected VTs

c) is the equivalent symbol and terminal marking used by IEC (ANSI) standard for open deltaconnected VTs

d) is the equivalent symbol and terminal marking used by IEC (ANSI) standard for phase-to-phase connected VTs

It shall be noted that depending on national standard and utility practices the ratedsecondary voltage of a VT has typically one of the following values:

• 100 V• 110 V• 115 V• 120 V• 230 V

The IED fully supports all of these values and most of them will be shown in thefollowing examples.

1MRK 505 211-UEN C Section 3IED application

43

 Application manual

Page 50: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 50/457

Examples on how to connect a three phase-to-earth connected VT to

the IEDFigure 15 gives an example on how to connect a three phase-to-earth connected VTto the IED. It as well gives overview of required actions by the user in order tomake this measurement available to the built-in protection and control functionswithin the IED.

19

20

21

22

23

24

13

14

15

16

17

18

L1

 AI 07 (I)

 AI 08 (U)

 AI 09 (U)

 AI 10 (U)

 AI 11 (U)

 AI 12 (U)

IEDL2

L3

66

3110

3

kV 

1

3

2

66

3

1103

kV 

66

3110

3

kV 

.

#Not used

5

IEC06000599-3-en.vsd

SMAI2

BLOCK

^GRP2L1

 AI3P

 AI1

 AI2

 AI3

 AI4

 AIN

^GRP2L2

^GRP2L3

^GRP2N

4

IEC06000599 V3 EN

Figure 15: A Three phase-to-earth connected VT 

Section 3 1MRK 505 211-UEN C

IED application

44

 Application manual

Page 51: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 51/457

Where:

1) shows how to connect three secondary phase-to-earth voltages to three VT inputs onthe IED

2) is the TRM where these three voltage inputs are located. For these three voltage

inputs, the following setting values shall be entered:VTprim =66 kV 

VTsec = 110 V 

Inside the IED, only the ratio of these two parameters is used. It shall be noted that theratio of the entered values exactly corresponds to ratio of one individual VT.

6666 3

1101103

=

EQUATION1903 V1 EN (Equation 18)

3) are three connections made in Signal Matrix Tool (SMT), which connect these three

voltage inputs to first three input channels of the preprocessing function block 5).Depending on the type of functions which need this voltage information, more then onepreprocessing block might be connected in parallel to these three VT inputs.

4) shows that in this example the fourth (that is, residual) input channel of thepreprocessing block is not connected in SMT tool. Thus the preprocessing block willautomatically calculate 3Uo inside by vectorial sum from the three phase to earthvoltages connected to the first three input channels of the same preprocessing block.

 Alternatively, the fourth input channel can be connected to open delta VT input, asshown in figure 17.

5) is a Preprocessing block that has the task to digitally filter the connected analog inputsand calculate:

• fundamental frequency phasors for all four input channels• harmonic content for all four input channels

• positive, negative and zero sequence quantities by using the fundamentalfrequency phasors for the first three input channels (channel one taken asreference for sequence quantities)

These calculated values are then available for all built-in protection and controlfunctions within the IED, which are connected to this preprocessing function block in theconfiguration tool. For this application most of the preprocessing settings can be left tothe default values. However the following settings shall be set as shown here:UBase=66 kV (that is, rated Ph-Ph voltage)If frequency tracking and compensation is required (this feature is typically requiredonly for IEDs installed in the generating stations) then the setting parametersDFTReference shall be set accordingly.

Example on how to connect a phase-to-phase connected VT to the IEDFigure 16 gives an example how to connect a phase-to-phase connected VT to theIED. It gives an overview of the required actions by the user in order to make thismeasurement available to the built-in protection and control functions within theIED as well. It shall be noted that this VT connection is only used on lower voltagelevels (that is, rated primary voltage below 40 kV).

1MRK 505 211-UEN C Section 3IED application

45

 Application manual

Page 52: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 52/457

1920

21

22

23

24

13

14

15

16

17

18

L1

 AI 07(I)

 AI08(U)

 AI09(U)

 AI 10(U)

 AI11(U)

 AI12(U)

IED

L2

L3

13.8120

kV V 

1

2

3

#Not Used

13.8120

kV V 

.

5

IEC06000600-3-en.vsd

4

SMAI2

BLOCK

^GRP2L1

 AI3P

 AI1

 AI2

 AI3

 AI4

 AIN

^GRP2L2

^GRP2L3

^GRP2N

IEC06000600 V3 EN

Figure 16: A Two phase-to-phase connected VT 

Where:

1) shows how to connect the secondary side of a phase-to-phase VT to the VT inputs on theIED

2) is the TRM where these three voltage inputs are located. It shall be noted that for thesethree voltage inputs the following setting values shall be entered:VTprim =13.8 kVVTsec =120 VPlease note that inside the IED only ratio of these two parameters is used.

Table continues on next page

Section 3 1MRK 505 211-UEN C

IED application

46

 Application manual

Page 53: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 53/457

3) are three connections made in the Signal Matrix tool (SMT), which connects these threevoltage inputs to first three input channels of the preprocessing function block 5).Depending on the type of functions, which need this voltage information, more than onepreprocessing block might be connected in parallel to these three VT inputs

4) shows that in this example the fourth (that is, residual) input channel of the preprocessingblock is not connected in SMT.

5) Preprocessing block has a task to digitally filter the connected analog inputs and calculate:

• fundamental frequency phasors for all four input channels• harmonic content for all four input channels• positive, negative and zero sequence quantities by using the fundamental frequency

phasors for the first three input channels (channel one taken as reference for sequence quantities)

These calculated values are then available for all built-in protection and control functionswithin the IED, which are connected to this preprocessing function block in theconfiguration tool. For this application most of the preprocessing settings can be left to thedefault values. However the following settings shall be set as shown here:ConnectionType =Ph-Ph 

UBase=13.8 kVIf frequency tracking and compensation is required (this feature is typically required onlyfor IEDs installed in the generating stations) then the setting parameters DFTReference 

shall be set accordingly.

Example on how to connect an open delta VT to the IED for high

impedance earthed or unearthedFigure 17 gives an example about the wiring of an open delta VT to the IED for high impedance earthed or unearthed power systems. It shall be noted that this typeof VT connection presents a secondary voltage proportional to 3U0 to the IED.

In case of a solid earth fault close to the VT location the primary value of 3Uo will be equal to:

3 0 3. 3. Ph Ph Ph E U U U - -= =EQUATION1921 V2 EN (Equation 19)

The primary rated voltage of an open Delta VT is always equal to UPh-E. Threeseries connected VT secondary windings gives a secondary voltage equal to threetimes the individual VT secondary winding rating. Thus the secondary windings of open delta VTs quite often have a secondary rated voltage equal to one third of therated phase-to-phase VT secondary voltage (110/3V in this particular example).

Figure gives overview of required actions by the user in order to make thismeasurement available to the built-in protection and control functions within theIED as well.

1MRK 505 211-UEN C Section 3IED application

47

 Application manual

Page 54: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 54/457

19

20

21

22

23

24

13

14

15

16

17

18

L1

 AI 07 (I)

 AI 08 (U)

 AI 09 (U)

 AI 10 (U)

 AI 11 (U)

 AI 12 (U)

IEDL2

L3

6.6

3110

3

kV 

+3Uo

6.6

3110

3

kV 

6.6

3110

3

kV 

1

2

4

 3# Not Used

5

IEC06000601-3-en.vsd

# Not Used

# Not Used

SMAI2

BLOCK

^GRP2L1

^GRP2L2

^GRP2L3

^GRP2N

 AI3P

 AI1

 AI2

 AI3

 AI4

 AIN

IEC06000601 V3 EN

Figure 17: Open delta connected VT in high impedance earthed power system 

Section 3 1MRK 505 211-UEN C

IED application

48

 Application manual

Page 55: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 55/457

Where:

 

1) shows how to connect the secondary side of the open delta VT to one VT input on the IED.

+3U0 shall be connected to the IED

2) is the TRM where this voltage input is located. It shall be noted that for this voltage inputthe following setting values shall be entered:

3 6.6 11.43VTprim kV  = × =

EQUATION1923 V1 EN (Equation 20)

110sec 3 110

3VT V = × =

EQUATION1924 V1 EN (Equation 21)

Inside the IED, only the ratio of these two parameters is used. It shall be noted that theratio of the entered values exactly corresponds to ratio of one individual open delta VT.

6.63 6.6 3

1101103

×=

EQUATION1925 V1 EN (Equation 22)

3) shows that in this example the first three input channel of the preprocessing block is notconnected in SMT tool.

4) shows the connection made in Signal Matrix Tool (SMT), which connect this voltage inputto the fourth input channel of the preprocessing function block 5).

5) is a Preprocessing block that has the task to digitally filter the connected analog input andcalculate:

• fundamental frequency phasors for all four input channels• harmonic content for all four input channels• positive, negative and zero sequence quantities by using the fundamental frequency

phasors for the first three input channels (channel one taken as reference for sequence quantities)

These calculated values are then available for all built-in protection and control functionswithin the IED, which are connected to this preprocessing function block in the

configuration tool. For this application most of the preprocessing settings can be left to thedefault values.If frequency tracking and compensation is required (this feature is typically required only for IEDs installed in the generating stations ) then the setting parameters DFTReference shallbe set accordingly.

 

1MRK 505 211-UEN C Section 3IED application

49

 Application manual

Page 56: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 56/457

Example how to connect the open delta VT to the IED for low

impedance earthed or solidly earthed power systemsFigure 18 gives an example about the connection of an open delta VT to the IEDfor low impedance earthed or solidly earthed power systems. It shall be noted thatthis type of VT connection presents secondary voltage proportional to 3U0 to the IED.

In case of a solid earth fault close to the VT location the primary value of 3Uo will be equal to:

33

 Ph Ph

 Ph E 

U Uo U -

-= =

EQUATION1926 V1 EN (Equation 23)

The primary rated voltage of such VT is always equal to UPh-E Therefore, three

series connected VT secondary windings will give the secondary voltage equalonly to one individual VT secondary winding rating. Thus the secondary windingsof such open delta VTs quite often has a secondary rated voltage close to rated phase-to-phase VT secondary voltage, that is, 115V or 115/√3V as in this particular example. Figure 18 gives an overview of the actions which are needed to make thismeasurement available to the built-in protection and control functions within the IED.

19

20

21

22

23

24

13

14

15

16

17

18

L1

 AI07 (I)

 AI08 (U)

 AI09 (U)

 AI10 (U)

 AI11 (U)

 AI12 (U)

IEDL2

L3

1383115

3

kV 

+3Uo

138

3115

3

kV 

1383115

3

kV 

 1

2

4

3

IEC06000602-3-en.vsd

SMAI2

BLOCK

^GRP2L1

^GRP2L2

^GRP2L3

^GRP2N

 AI3P

 AI1

 AI2

 AI3

 AI4

 AIN

5

# Not Used

# Not Used

# Not Used

IEC06000602 V3 EN

Figure 18: Open delta connected VT in low impedance or solidly earthed power system 

Section 3 1MRK 505 211-UEN C

IED application

50

 Application manual

Page 57: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 57/457

Where:

1) shows how to connect the secondary side of open delta VT to one VT input in the IED.

+3Uo shall be connected to the IED.

2) is TRM where this voltage input is located. It shall be noted that for this voltage inputthe following setting values shall be entered:

1383 138

3VTprim kV  = × =

EQUATION1928 V1 EN (Equation 24)

115sec 3 115

3

VT V = × =

EQUATION1929 V1 EN (Equation 25)

Inside the IED, only the ratio of these two parameters is used. It shall be noted thatthe ratio of the entered values exactly corresponds to ratio of one individual opendelta VT.

138138 3

1151153

=

EQUATION1930 V1 EN (Equation 26)

3) shows that in this example the first three input channel of the preprocessing block isnot connected in SMT tool.

4) shows the connection made in Signal Matrix Tool (SMT), which connect this voltageinput to the fourth input channel of the preprocessing function block 4).

5) preprocessing block has a task to digitally filter the connected analog inputs andcalculate:

• fundamental frequency phasors for all four input channels• harmonic content for all four input channels• positive, negative and zero sequence quantities by using the fundamental

frequency phasors for the first three input channels (channel one taken asreference for sequence quantities)

These calculated values are then available for all built-in protection and controlfunctions within the IED, which are connected to this preprocessing function block inthe configuration tool. For this application most of the preprocessing settings can beleft to the default values.If frequency tracking and compensation is required (this feature is typically requiredonly for IEDs installed in the generating stations) then the setting parametersDFTReference shall be set accordingly.

Example on how to connect a neutral point VT to the IEDFigure 19 gives an example on how to connect a neutral point VT to the IED. Thistype of VT connection presents secondary voltage proportional to U0 to the IED.

1MRK 505 211-UEN C Section 3IED application

51

 Application manual

Page 58: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 58/457

In case of a solid earth fault in high impedance earthed or unearthed systems the primary value of Uo voltage will be equal to:

03

 Ph Ph Ph E 

U U U 

--= =

EQUATION1931 V2 EN (Equation 27)

Figure 19 gives an overview of required actions by the user in order to make thismeasurement available to the built-in protection and control functions within theIED as well.

19

20

21

22

23

24

13

14

15

16

17

18

L1 L2 L3

 AI07 (I)

 AI08 (I)

 AI09 (I)

 AI10 (U)

 AI11 (U)

 AI12 (U)

IED

6.6

3100

kV 

RUo

1

2

 3

IEC06000603-3-en.vsd

5

SMAI2

BLOCK

^GRP2L1

^GRP2L2

^GRP2L3

^GRP2N

 AI3P

 AI1

 AI2

 AI3

 AI4

 AIN

# Not Used

# Not Used

# Not Used

4

Protected Object

IEC06000603 V3 EN

Figure 19: Neutral point connected VT 

Section 3 1MRK 505 211-UEN C

IED application

52

 Application manual

Page 59: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 59/457

Where:

1) shows how to connect the secondary side of neutral point VT to one VT input in the IED.

U0 shall be connected to the IED.

2) is the TRM where this voltage input is located. It shall be noted that for this voltage inputthe following setting values shall be entered:is the TRM or AIM where this voltage input is located. For this voltage input the followingsetting values shall be entered:

6.63.81

3VTprim kV  = =

EQUATION1933 V1 EN (Equation 28)

sec 100VT V =EQUATION1934 V1 EN (Equation 29)

Inside the IED, only the ratio of these two parameters is used. It shall be noted that theratio of the entered values exactly corresponds to ratio of the neutral point VT.

3) shows that in this example the first three input channel of the preprocessing block is notconnected in SMT tool.

4) shows the connection made in Signal Matrix Tool (SMT), which connects this voltage inputto the fourth input channel of the preprocessing function block 5).

5) is a preprocessing block that has the task to digitally filter the connected analog inputs andcalculate:

• fundamental frequency phasors for all four input channels• harmonic content for all four input channels• positive, negative and zero sequence quantities by using the fundamental frequency

phasors for the first three input channels (channel one taken as reference for sequence quantities)

These calculated values are then available for all built-in protection and control functionswithin the IED, which are connected to this preprocessing function block in theconfiguration tool. For this application most of the preprocessing settings can be left to thedefault values.If frequency tracking and compensation is required (this feature is typically required onlyfor IEDs installed in the generating stations) then the setting parameters DFTReference 

shall be set accordingly.

3.2.3 Setting parameters

The available setting parameters related to analog inputs aredepending on the actual hardware (TRM) and the logicconfiguration made in PCM600.

1MRK 505 211-UEN C Section 3IED application

53

 Application manual

Page 60: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 60/457

Table 1: AISVBAS Non group settings (basic)

Name Values (Range) Unit Step Default Description

PhaseAngleRef TRM40-Ch1TRM40-Ch2

TRM40-Ch3TRM40-Ch4TRM40-Ch5TRM40-Ch6TRM40-Ch7TRM40-Ch8TRM40-Ch9TRM40-Ch10TRM40-Ch11TRM40-Ch12TRM41-Ch1TRM41-Ch2TRM41-Ch3TRM41-Ch4TRM41-Ch5TRM41-Ch6TRM41-Ch7TRM41-Ch8TRM41-Ch9TRM41-Ch10TRM41-Ch11TRM41-Ch12MU1-L1IMU1-L2IMU1-L3IMU1-L4IMU1-L1UMU1-L2UMU1-L3UMU1-L4UMU2-L1I

MU2-L2IMU2-L3IMU2-L4IMU2-L1UMU2-L2UMU2-L3UMU2-L4UMU3-L1IMU3-L2IMU3-L3IMU3-L4IMU3-L1UMU3-L2UMU3-L3UMU3-L4U

- - TRM40-Ch1 Reference channel for phase anglepresentation

Table 2: TRM_12I Non group settings (basic)

Name Values (Range) Unit Step Default Description

CTStarPoint1 FromObjectToObject

- - ToObject ToObject= towards protected object,FromObject= the opposite

CTsec1 1 - 10 A 1 1 Rated CT secondary current

CTprim1 1 - 99999 A 1 3000 Rated CT primary current

CTStarPoint2 FromObjectToObject

- - ToObject ToObject= towards protected object,FromObject= the opposite

Table continues on next page

Section 3 1MRK 505 211-UEN C

IED application

54

 Application manual

Page 61: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 61/457

Name Values (Range) Unit Step Default Description

CTsec2 1 - 10 A 1 1 Rated CT secondary current

CTprim2 1 - 99999 A 1 3000 Rated CT primary current

CTStarPoint3 FromObjectToObject

- - ToObject ToObject= towards protected object,FromObject= the opposite

CTsec3 1 - 10 A 1 1 Rated CT secondary current

CTprim3 1 - 99999 A 1 3000 Rated CT primary current

CTStarPoint4 FromObjectToObject

- - ToObject ToObject= towards protected object,FromObject= the opposite

CTsec4 1 - 10 A 1 1 Rated CT secondary current

CTprim4 1 - 99999 A 1 3000 Rated CT primary current

CTStarPoint5 FromObjectToObject

- - ToObject ToObject= towards protected object,FromObject= the opposite

CTsec5 1 - 10 A 1 1 Rated CT secondary current

CTprim5 1 - 99999 A 1 3000 Rated CT primary current

CTStarPoint6 FromObjectToObject

- - ToObject ToObject= towards protected object,FromObject= the opposite

CTsec6 1 - 10 A 1 1 Rated CT secondary current

CTprim6 1 - 99999 A 1 3000 Rated CT primary current

CTStarPoint7 FromObjectToObject

- - ToObject ToObject= towards protected object,FromObject= the opposite

CTsec7 1 - 10 A 1 1 Rated CT secondary current

CTprim7 1 - 99999 A 1 3000 Rated CT primary current

CTStarPoint8 FromObjectToObject

- - ToObject ToObject= towards protected object,FromObject= the opposite

CTsec8 1 - 10 A 1 1 Rated CT secondary current

CTprim8 1 - 99999 A 1 3000 Rated CT primary current

CTStarPoint9 FromObjectToObject

- - ToObject ToObject= towards protected object,FromObject= the opposite

CTsec9 1 - 10 A 1 1 Rated CT secondary current

CTprim9 1 - 99999 A 1 3000 Rated CT primary current

CTStarPoint10 FromObjectToObject

- - ToObject ToObject= towards protected object,FromObject= the opposite

CTsec10 1 - 10 A 1 1 Rated CT secondary current

CTprim10 1 - 99999 A 1 3000 Rated CT primary current

CTStarPoint11 FromObjectToObject

- - ToObject ToObject= towards protected object,FromObject= the opposite

CTsec11 1 - 10 A 1 1 Rated CT secondary current

CTprim11 1 - 99999 A 1 3000 Rated CT primary current

CTStarPoint12 FromObjectToObject

- - ToObject ToObject= towards protected object,FromObject= the opposite

CTsec12 1 - 10 A 1 1 Rated CT secondary current

CTprim12 1 - 99999 A 1 3000 Rated CT primary current

1MRK 505 211-UEN C Section 3IED application

55

 Application manual

Page 62: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 62/457

Table 3: TRM_6I_6U Non group settings (basic)

Name Values (Range) Unit Step Default Description

CTStarPoint1 FromObjectToObject

- - ToObject ToObject= towards protected object,FromObject= the opposite

CTsec1 1 - 10 A 1 1 Rated CT secondary current

CTprim1 1 - 99999 A 1 3000 Rated CT primary current

CTStarPoint2 FromObjectToObject

- - ToObject ToObject= towards protected object,FromObject= the opposite

CTsec2 1 - 10 A 1 1 Rated CT secondary current

CTprim2 1 - 99999 A 1 3000 Rated CT primary current

CTStarPoint3 FromObjectToObject

- - ToObject ToObject= towards protected object,FromObject= the opposite

CTsec3 1 - 10 A 1 1 Rated CT secondary current

CTprim3 1 - 99999 A 1 3000 Rated CT primary current

CTStarPoint4 FromObjectToObject

- - ToObject ToObject= towards protected object,FromObject= the opposite

CTsec4 1 - 10 A 1 1 Rated CT secondary current

CTprim4 1 - 99999 A 1 3000 Rated CT primary current

CTStarPoint5 FromObjectToObject

- - ToObject ToObject= towards protected object,FromObject= the opposite

CTsec5 1 - 10 A 1 1 Rated CT secondary current

CTprim5 1 - 99999 A 1 3000 Rated CT primary current

CTStarPoint6 FromObjectToObject

- - ToObject ToObject= towards protected object,FromObject= the opposite

CTsec6 1 - 10 A 1 1 Rated CT secondary current

CTprim6 1 - 99999 A 1 3000 Rated CT primary current

VTsec7 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage

VTprim7 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage

VTsec8 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage

VTprim8 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage

VTsec9 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage

VTprim9 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage

VTsec10 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage

VTprim10 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage

VTsec11 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage

VTprim11 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage

VTsec12 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage

VTprim12 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage

Section 3 1MRK 505 211-UEN C

IED application

56

 Application manual

Page 63: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 63/457

Table 4: TRM_7I_5U Non group settings (basic)

Name Values (Range) Unit Step Default Description

CTStarPoint1 FromObjectToObject

- - ToObject ToObject= towards protected object,FromObject= the opposite

CTsec1 1 - 10 A 1 1 Rated CT secondary current

CTprim1 1 - 99999 A 1 3000 Rated CT primary current

CTStarPoint2 FromObjectToObject

- - ToObject ToObject= towards protected object,FromObject= the opposite

CTsec2 1 - 10 A 1 1 Rated CT secondary current

CTprim2 1 - 99999 A 1 3000 Rated CT primary current

CTStarPoint3 FromObjectToObject

- - ToObject ToObject= towards protected object,FromObject= the opposite

CTsec3 1 - 10 A 1 1 Rated CT secondary current

CTprim3 1 - 99999 A 1 3000 Rated CT primary current

CTStarPoint4 FromObjectToObject

- - ToObject ToObject= towards protected object,FromObject= the opposite

CTsec4 1 - 10 A 1 1 Rated CT secondary current

CTprim4 1 - 99999 A 1 3000 Rated CT primary current

CTStarPoint5 FromObjectToObject

- - ToObject ToObject= towards protected object,FromObject= the opposite

CTsec5 1 - 10 A 1 1 Rated CT secondary current

CTprim5 1 - 99999 A 1 3000 Rated CT primary current

CTStarPoint6 FromObjectToObject

- - ToObject ToObject= towards protected object,FromObject= the opposite

CTsec6 1 - 10 A 1 1 Rated CT secondary current

CTprim6 1 - 99999 A 1 3000 Rated CT primary current

CTStarPoint7 FromObjectToObject

- - ToObject ToObject= towards protected object,FromObject= the opposite

CTsec7 1 - 10 A 1 1 Rated CT secondary current

CTprim7 1 - 99999 A 1 3000 Rated CT primary current

VTsec8 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage

VTprim8 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage

VTsec9 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage

VTprim9 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage

VTsec10 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltageVTprim10 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage

VTsec11 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage

VTprim11 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage

VTsec12 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage

VTprim12 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage

1MRK 505 211-UEN C Section 3IED application

57

 Application manual

Page 64: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 64/457

Table 5: TRM_9I_3U Non group settings (basic)

Name Values (Range) Unit Step Default Description

CTStarPoint1 FromObjectToObject

- - ToObject ToObject= towards protected object,FromObject= the opposite

CTsec1 1 - 10 A 1 1 Rated CT secondary current

CTprim1 1 - 99999 A 1 3000 Rated CT primary current

CTStarPoint2 FromObjectToObject

- - ToObject ToObject= towards protected object,FromObject= the opposite

CTsec2 1 - 10 A 1 1 Rated CT secondary current

CTprim2 1 - 99999 A 1 3000 Rated CT primary current

CTStarPoint3 FromObjectToObject

- - ToObject ToObject= towards protected object,FromObject= the opposite

CTsec3 1 - 10 A 1 1 Rated CT secondary current

CTprim3 1 - 99999 A 1 3000 Rated CT primary current

CTStarPoint4 FromObjectToObject

- - ToObject ToObject= towards protected object,FromObject= the opposite

CTsec4 1 - 10 A 1 1 Rated CT secondary current

CTprim4 1 - 99999 A 1 3000 Rated CT primary current

CTStarPoint5 FromObjectToObject

- - ToObject ToObject= towards protected object,FromObject= the opposite

CTsec5 1 - 10 A 1 1 Rated CT secondary current

CTprim5 1 - 99999 A 1 3000 Rated CT primary current

CTStarPoint6 FromObjectToObject

- - ToObject ToObject= towards protected object,FromObject= the opposite

CTsec6 1 - 10 A 1 1 Rated CT secondary current

CTprim6 1 - 99999 A 1 3000 Rated CT primary current

CTStarPoint7 FromObjectToObject

- - ToObject ToObject= towards protected object,FromObject= the opposite

CTsec7 1 - 10 A 1 1 Rated CT secondary current

CTprim7 1 - 99999 A 1 3000 Rated CT primary current

CTStarPoint8 FromObjectToObject

- - ToObject ToObject= towards protected object,FromObject= the opposite

CTsec8 1 - 10 A 1 1 Rated CT secondary current

CTprim8 1 - 99999 A 1 3000 Rated CT primary current

CTStarPoint9 FromObject

ToObject

- - ToObject ToObject= towards protected object,

FromObject= the opposite

CTsec9 1 - 10 A 1 1 Rated CT secondary current

CTprim9 1 - 99999 A 1 3000 Rated CT primary current

VTsec10 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage

VTprim10 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage

VTsec11 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage

VTprim11 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage

VTsec12 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage

VTprim12 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage

Section 3 1MRK 505 211-UEN C

IED application

58

 Application manual

Page 65: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 65/457

3.3 Local human-machine interface

3.3.1 Human machine interfaceThe local HMI is equipped with a LCD that is used among other things to locallydisplay the following crucial information:

• Connection of each bay, respecting the two differential protection zones andthe check zone. In the Parameter Setting Tool the user sets individual baynames to facilitate the identification of each primary bay for station personnel.

• Status of each individual primary switchgear device, for example, open,closed, 00 as intermediate state and 11 as bad state. In PCM600 the user setsthe individual primary switchgear object names to facilitate the identificationof each switchgear device for the station personnel.

The local HMI is divided into zones with different functionality.

• Status indication LEDs.• Alarm indication LEDs, which consist of 15 LEDs (6 red and 9 yellow) with

user printable label. All LEDs are configurable from PCM600.• Liquid crystal display (LCD).• Keypad with push buttons for control and navigation purposes, switch for 

selection between local and remote control and reset.• Isolated RJ45 communication port.

1MRK 505 211-UEN C Section 3IED application

59

 Application manual

Page 66: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 66/457

IEC06000143 V1 EN

Figure 20: Example of medium graphic HMI 

Section 3 1MRK 505 211-UEN C

IED application

60

 Application manual

Page 67: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 67/457

IEC06000191 V1 EN

Figure 21: Bay to zone connection example 

1 User settable bay name

2 Internally used bay FB

3 Connections to internal zones

 

1MRK 505 211-UEN C Section 3IED application

61

 Application manual

Page 68: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 68/457

IEC06000192 V1 EN

Figure 22: Example of status of primary switchgear objects 

1 User settable switchgear names

2 Switchgear object status

 

3.3.2 Local HMI related functions

3.3.2.1 Introduction

The local HMI can be adapted to the application configuration and to user preferences.

• Function block LocalHMI• Function block LEDGEN• Setting parameters

Section 3 1MRK 505 211-UEN C

IED application

62

 Application manual

Page 69: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 69/457

3.3.2.2 General setting parameters

Table 6: SCREEN Non group settings (basic)

Name Values (Range) Unit Step Default Description

Language EnglishOptionalLanguage

- - English Local HMI language

DisplayTimeout 10 - 120 Min 10 60 Local HMI display timeout

 AutoRepeat Off On

- - On Activation of auto-repeat (On) or not (Off)

ContrastLevel -10 - 20 % 1 0 Contrast level for display

DefaultScreen 0 - 0 - 1 0 Default screen

EvListSrtOrder Latest on topOldest on top

- - Latest on top Sort order of event list

SymbolFont IEC ANSI

- - IEC Symbol font for Single Line Diagram

3.3.3 Indication LEDs

3.3.3.1 Introduction

The function block LEDGEN controls and supplies information about the status of the indication LEDs. The input and output signals of LEDGEN are configured withPCM600. The input signal for each LED is selected individually with the SignalMatrix Tool in PCM600.

• LEDs (number 1–6) for trip indications are red.• LEDs (number 7–15) for start indications are yellow.

Each indication LED on the local HMI can be set individually to operate in sixdifferent sequences

• Two sequences operate as follow type.• Four sequences operate as latch type.

• Two of the latching sequence types are intended to be used as a protection indication system, either in collecting or restarting mode, with

reset functionality.• Two of the latching sequence types are intended to be used as signalingsystem in collecting (coll) mode with an acknowledgment functionality.

The light from the LEDs can be steady (-S) or flashing (-F). See the technicalreference manual for more information.

1MRK 505 211-UEN C Section 3IED application

63

 Application manual

Page 70: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 70/457

3.3.3.2 Setting parameters

Table 7: LEDGEN Non group settings (basic)

Name Values (Range) Unit Step Default Description

Operation Off  On

- - Off Operation mode for the LED function

tRestart 0.0 - 100.0 s 0.1 0.0 Defines the disturbance length

tMax 0.0 - 100.0 s 0.1 0.0 Maximum time for the definition of adisturbance

SeqTypeLED1 Follow-SFollow-FLatchedAck-F-SLatchedAck-S-FLatchedColl-SLatchedReset-S

- - Follow-S Sequence type for LED 1

SeqTypeLED2 Follow-S

Follow-FLatchedAck-F-SLatchedAck-S-FLatchedColl-SLatchedReset-S

- - Follow-S Sequence type for LED 2

SeqTypeLED3 Follow-SFollow-FLatchedAck-F-SLatchedAck-S-FLatchedColl-SLatchedReset-S

- - Follow-S Sequence type for LED 3

SeqTypeLED4 Follow-SFollow-FLatchedAck-F-S

LatchedAck-S-FLatchedColl-SLatchedReset-S

- - Follow-S Sequence type for LED 4

SeqTypeLED5 Follow-SFollow-FLatchedAck-F-SLatchedAck-S-FLatchedColl-SLatchedReset-S

- - Follow-S Sequence type for LED 5

SeqTypeLED6 Follow-SFollow-FLatchedAck-F-SLatchedAck-S-FLatchedColl-SLatchedReset-S

- - Follow-S Sequence type for LED 6

SeqTypeLED7 Follow-SFollow-FLatchedAck-F-SLatchedAck-S-FLatchedColl-SLatchedReset-S

- - Follow-S Sequence type for LED 7

SeqTypeLED8 Follow-SFollow-FLatchedAck-F-SLatchedAck-S-FLatchedColl-SLatchedReset-S

- - Follow-S sequence type for LED 8

Table continues on next page

Section 3 1MRK 505 211-UEN C

IED application

64

 Application manual

Page 71: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 71/457

Name Values (Range) Unit Step Default Description

SeqTypeLED9 Follow-SFollow-FLatchedAck-F-SLatchedAck-S-F

LatchedColl-SLatchedReset-S

- - Follow-S Sequence type for LED 9

SeqTypeLED10 Follow-SFollow-FLatchedAck-F-SLatchedAck-S-FLatchedColl-SLatchedReset-S

- - Follow-S Sequence type for LED 10

SeqTypeLED11 Follow-SFollow-FLatchedAck-F-SLatchedAck-S-FLatchedColl-SLatchedReset-S

- - Follow-S Sequence type for LED 11

SeqTypeLED12 Follow-SFollow-FLatchedAck-F-SLatchedAck-S-FLatchedColl-SLatchedReset-S

- - Follow-S Sequence type for LED 12

SeqTypeLED13 Follow-SFollow-FLatchedAck-F-SLatchedAck-S-FLatchedColl-SLatchedReset-S

- - Follow-S Sequence type for LED 13

SeqTypeLED14 Follow-SFollow-FLatchedAck-F-SLatchedAck-S-FLatchedColl-SLatchedReset-S

- - Follow-S Sequence type for LED 14

SeqTypeLED15 Follow-SFollow-FLatchedAck-F-SLatchedAck-S-FLatchedColl-SLatchedReset-S

- - Follow-S Sequence type for LED 15

3.4 Basic IED functions

3.4.1 Self supervision with internal event list

3.4.1.1 Application

The protection and control IEDs have many functions included . The included self-supervision with internal event list function block provides good supervision of theIED. The fault signals make it easier to analyze and locate a fault.

1MRK 505 211-UEN C Section 3IED application

65

 Application manual

Page 72: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 72/457

Both hardware and software supervision is included and it is also possible toindicate possible faults through a hardware contact on the power supply module and/or through the software communication.

Internal events are generated by the built-in supervisory functions. The supervisoryfunctions supervise the status of the various modules in the IED and, in case of failure, a corresponding event is generated. Similarly, when the failure is corrected,a corresponding event is generated.

Apart from the built-in supervision of the various modules, events are alsogenerated when the status changes for the:

• built-in real time clock (in operation/out of order).• external time synchronization (in operation/out of order).

Events are also generated:• whenever any setting in the IED is changed.

The internal events are time tagged with a resolution of 1 ms and stored in a list.The list can store up to 40 events. The list is based on the FIFO principle, that is,when it is full, the oldest event is overwritten. The list cannot be cleared and itscontent cannot be modified.

The list of internal events provides valuable information, which can be used duringcommissioning and fault tracing.

The information can only be retrieved with the aid of PCM600 Event MonitoringTool. The PC can either be connected to the front port, or to the port at the back of the IED.

3.4.1.2 Setting parameters

The function does not have any parameters available in the local HMI or PCM600.

3.4.2 Time synchronization

3.4.2.1 Application

Use time synchronization to achieve a common time base for the IEDs in a protection and control system. This makes it possible to compare events anddisturbance data between all IEDs in the system.

Time-tagging of internal events and disturbances are an excellent help whenevaluating faults. Without time synchronization, only the events within the IED can

 be compared to one another. With time synchronization, events and disturbanceswithin the entire station, and even between line ends, can be compared at evaluation.

In the IED, the internal time can be synchronized from a number of sources:

Section 3 1MRK 505 211-UEN C

IED application

66

 Application manual

Page 73: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 73/457

• BIN (Binary Minute Pulse)• GPS• SNTP• IRIG-B• SPA• LON• PPS

Odut of these, LON and SPA contains two types of synchronization messages:

• Coarse time messages are sent every minute and contain complete date andtime, that is year, month, day, hour, minute, second and millisecond.

• Fine time messages are sent every second and comprise only seconds andmilliseconds.

The setting tells the IED which of these that shall be used to synchronize the IED.

It is possible to set a backup time-source for GPS signal, for instance SNTP. In thiscase, when the GPS signal quality is bad, the IED will automatically choose SNTPas the time-source. At a given point in time, only one time-source will be used.

3.4.2.2 Setting guidelines

System timeThe time is set with years, month, day, hour, minute, second and millisecond.

SynchronizationThe setting parameters for the real-time clock with external time synchronization(TIME) are set via local HMI or PCM600.

TimeSynchWhen the source of the time synchronization is selected on the local HMI, the

 parameter is called TimeSynch. The time synchronization source can also be setfrom PCM600. The setting alternatives are:

 FineSyncSource which can have the following values:

• Off • SPA

• LON 

• BIN (Binary Minute Pulse)• GPS 

• GPS+SPA

• GPS+LON 

• GPS+BIN 

• SNTP 

• GPS+SNTP 

1MRK 505 211-UEN C Section 3IED application

67

 Application manual

Page 74: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 74/457

• GPS+IRIG-B

• IRIG-B

• PPS 

CoarseSyncSrc which can have the following values:

• Off 

• SPA

• LON 

• SNTP 

• DNP 

CoarseSyncSrc which can have the following values:

• Off 

• SNTP • DNP 

• IEC60870-5-103

The function input to be used for minute-pulse synchronization is called TIME-MINSYNC.

The system time can be set manually, either via the local HMI or via any of thecommunication ports. The time synchronization fine tunes the clock (seconds andmilliseconds).

The parameter SyncMaster defines if the IED is a master, or not a master for timesynchronization in a system of IEDs connected in a communication network (IEC61850-8-1). The SyncMaster can have the following values:

• Off 

• SNTP -Server 

Set the course time synchronizing source (CoarseSyncSrc) to Off 

when GPS time synchronization of line differential function is used.Set the fine time synchronization source ( FineSyncSource) to GPS .The GPS will thus provide the complete time synchronization. GPS

alone shall synchronize the analogue values in such systems.

3.4.2.3 Setting parameters

Path in the local HMI is located under Main menu/Setting/Time

Path in PCM600 is located under Main menu/Settings/Time/Synchronization

Section 3 1MRK 505 211-UEN C

IED application

68

 Application manual

Page 75: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 75/457

Table 8: SYNCHBIN Non group settings (basic)

Name Values (Range) Unit Step Default Description

ModulePosition 3 - 16 - 1 3 Hardware position of IO module for timesynchronization

BinaryInput 1 - 16 - 1 1 Binary input number for timesynchronization

BinDetection PositiveEdgeNegativeEdge

- - PositiveEdge Positive or negative edge detection

Table 9: SYNCHSNTP Non group settings (basic)

Name Values (Range) Unit Step Default Description

ServerIP-Add 0 - 18 IP Address

1 0.0.0.0 Server IP-address

RedServIP-Add 0 - 18 IP

 Address

1 0.0.0.0 Redundant server IP-address

Table 10: DSTBEGIN Non group settings (basic)

Name Values (Range) Unit Step Default Description

MonthInYear JanuaryFebruaryMarch

 AprilMayJuneJuly

 August

September October November December 

- - March Month in year when daylight time starts

DayInWeek SundayMondayTuesdayWednesdayThursdayFridaySaturday

- - Sunday Day in week when daylight time starts

WeekInMonth LastFirstSecond

ThirdFourth

- - Last Week in month when daylight time starts

UTCTimeOfDay 0 - 172800 s 1 3600 UTC Time of day in seconds whendaylight time starts

1MRK 505 211-UEN C Section 3IED application

69

 Application manual

Page 76: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 76/457

Table 11: DSTEND Non group settings (basic)

Name Values (Range) Unit Step Default Description

MonthInYear JanuaryFebruary

March AprilMayJuneJuly

 AugustSeptember October November December 

- - October Month in year when daylight time ends

DayInWeek SundayMondayTuesdayWednesdayThursday

FridaySaturday

- - Sunday Day in week when daylight time ends

WeekInMonth LastFirstSecondThirdFourth

- - Last Week in month when daylight time ends

UTCTimeOfDay 0 - 172800 s 1 3600 UTC Time of day in seconds whendaylight time ends

Table 12: TIM EZO NE Non group settings (basic)

Name Values (Range) Unit Step Default Description

NoHalfHourUTC -24 - 24 - 1 0 Number of half-hours from UTC

Table 13: SYNCHIRIG-B Non group settings (basic)

Name Values (Range) Unit Step Default Description

SynchType BNCOpto

- - Opto Type of synchronization

TimeDomain LocalTimeUTC

- - LocalTime Time domain

Encoding IRIG-B

13441344TZ

- - IRIG-B Type of encoding

TimeZoneAs1344 MinusTZPlusTZ

- - PlusTZ Time zone as in 1344 standard

Section 3 1MRK 505 211-UEN C

IED application

70

 Application manual

Page 77: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 77/457

3.4.3 Parameter setting groups

3.4.3.1 Application

Six sets of settings are available to optimize IED operation for different power system conditions. By creating and switching between fine tuned setting sets, either from the local HMI or configurable binary inputs, results in a highly adaptable IEDthat can cope with a variety of power system scenarios.

Different conditions in networks with different voltage levels require highlyadaptable protection and control units to best provide for dependability, securityand selectivity requirements. Protection units operate with a higher degree of availability, especially, if the setting values of their parameters are continuouslyoptimized according to the conditions in the power system.

Operational departments can plan for different operating conditions in the primaryequipment. The protection engineer can prepare the necessary optimized and pre-tested settings in advance for different protection functions. Six

A function block, SETGRPS, defines how many setting groups are used. Setting isdone with parameter  MAXSETGR and shall be set to the required value for eachIED. Only the number of setting groups set will be available in the Parameter Setting tool for activation with the ActiveGroup function block.

3.4.3.2 Setting guidelines

The setting ActiveSetGrp, is used to select which parameter group to be active. Theactive group can also be selected with configured input to the function block SETGRPS.

The length of the pulse, sent out by the output signal SETCHGD when an activegroup has changed, is set with the parameter t .

The parameter  MAXSETGR defines the maximum number of setting groups in useto switch between. Only the selected number of setting groups will be available inthe Parameter Setting tool (PST) for activation with the ActiveGroup function block.

3.4.3.3 Setting parameters

Table 14: ActiveG roup N on group settings (basic)

Name Values (Range) Unit Step Default Description

t 0.0 - 10.0 s 0.1 1.0 Pulse length of pulse when settingchanged

1MRK 505 211-UEN C Section 3IED application

71

 Application manual

Page 78: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 78/457

Table 15: SETG RPS Non group settings (basic)

Name Values (Range) Unit Step Default Description

 ActiveSetGrp SettingGroup1SettingGroup2

SettingGroup3SettingGroup4SettingGroup5SettingGroup6

- - SettingGroup1 ActiveSettingGroup

MAXSETGR 1 - 6 No 1 1 Max number of setting groups 1-6

3.4.4 Test mode functionality TEST

3.4.4.1 Application

The protection and control IEDs may have a complex configuration with manyincluded functions. To make the testing procedure easier, the IEDs include thefeature that allows individual blocking of a single-, several-, or all functions.

This means that it is possible to see when a function is activated or trips. It alsoenables the user to follow the operation of several related functions to check correct functionality and to check parts of the configuration, and so on.

3.4.4.2 Setting guidelines

Remember always that there are two possible ways to place the IED in theTestMode= On” state. If, the IED is set to normal operation (TestMode = Off ), butthe functions are still shown being in the test mode, the input signal INPUT on theTESTMODE function block might be activated in the configuration.

3.4.4.3 Setting parameters

Table 16: TESTM ODE Non group settings (basic)

Name Values (Range) Unit Step Default Description

TestMode Off  On

- - Off Test mode in operation (On) or not (Off)

EventDisable Off  

On

- - Off Event disable during testmode

CmdTestBit Off  On

- - Off Command bit for test required or notduring testmode

3.4.5 Change lock CHNGLCK

Section 3 1MRK 505 211-UEN C

IED application

72

 Application manual

Page 79: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 79/457

3.4.5.1 Application

Change lock function CHNGLCK is used to block further changes to the IEDconfiguration once the commissioning is complete. The purpose is to make it

impossible to perform inadvertent IED configuration and setting changes.

However, when activated, CHNGLCK will still allow the following actions thatdoes not involve reconfiguring of the IED:

• Monitoring• Reading events• Resetting events• Reading disturbance data• Clear disturbances• Reset LEDs

• Reset counters and other runtime component states• Control operations• Set system time• Enter and exit from test mode• Change of active setting group

The binary input controlling the function is defined in ACT or SMT. TheCHNGLCK function is configured using ACT.

LOCK Binary input signal that will activate/deactivate the function, defined in ACT or SMT.

When CHNGLCK has a logical one on its input, then all attempts to modify theIED configuration and setting will be denied and the message "Error: Changes

 blocked" will be displayed on the local HMI; in PCM600 the message will be"Operation denied by active ChangeLock". The CHNGLCK function should beconfigured so that it is controlled by a signal from a binary input card. Thisguarantees that by setting that signal to a logical zero, CHNGLCK is deactivated. If any logic is included in the signal path to the CHNGLCK input, that logic must bedesigned so that it cannot permanently issue a logical one to the CHNGLCK input.

If such a situation would occur in spite of these precautions, then please contact thelocal ABB representative for remedial action.

3.4.5.2 Setting parameters

Table 17: CHNGLCK Non group settings (basic)

Name Values (Range) Unit Step Default Description

Operation LockHMI and ComLockHMI,EnableComEnableHMI,LockCom

- - LockHMI and Com Operation mode of change lock

1MRK 505 211-UEN C Section 3IED application

73

 Application manual

Page 80: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 80/457

3.4.6 IED identifiers

3.4.6.1 Application

IED identifiers (TERMINALID) function allows the user to identify the individualIED in the system, not only in the substation, but in a whole region or a country.

Use only characters A-Z, a-z and 0-9 in station, object and unit names.

3.4.6.2 Setting parameters

Table 18: TERMINALID Non group settings (basic)

Name Values (Range) Unit Step Default Description

StationName 0 - 18 - 1 Station name Station name

StationNumber 0 - 99999 - 1 0 Station number  

ObjectName 0 - 18 - 1 Object name Object name

ObjectNumber 0 - 99999 - 1 0 Object number  

UnitName 0 - 18 - 1 Unit name Unit name

UnitNumber 0 - 99999 - 1 0 Unit number  

3.4.7 Product information

3.4.7.1 Application

The Product identifiers function identifies the IED. The function has seven pre-set,settings that are unchangeable but nevertheless very important:

• IEDProdType• ProductDef  • FirmwareVer  • SerialNo

• OrderingNo• ProductionDate

The settings are visible on the local HMI , under Main menu/Diagnostics/IED

status/Product identifiers

They are very helpful in case of support process (such as repair or maintenance).

3.4.7.2 Setting parameters

The function does not have any parameters available in the local HMI or PCM600.

Section 3 1MRK 505 211-UEN C

IED application

74

 Application manual

Page 81: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 81/457

Factory defined settingsThe factory defined settings are very useful for identifying a specific version andvery helpful in the case of maintenance, repair, interchanging IEDs betweendifferent Substation Automation Systems and upgrading. The factory made settingscan not be changed by the customer. They can only be viewed. The settings arefound in the local HMI under Main menu/Diagnostics/IED status/Product

identifiers

The following identifiers are available:

• IEDProdType

• Describes the type of the IED (like REL, REC or RET). Example: REL670

• FirmwareVer  

• Describes the firmware version. Example: 1.4.51

• Firmware versions numbers are “running” independently from therelease production numbers. For every release numbers (like 1.5.0.17 )there can be one or more firmware versions, depending on the smallissues corrected in between releases.

• IEDMainFunType

• Main function type code according to IEC 60870-5-103. Example: 128(meaning line protection).

• SerialNo• OrderingNo• ProductionDate

3.4.8 Rated system frequency PRIMVAL

3.4.8.1 Application

The rated system frequency is set under Main menu/General settings/ Power

system/ Primary Values in the local HMI and PCM600 parameter setting tree.

3.4.8.2 Setting guidelines

Set the system rated frequency. Refer to section "Signal matrix for analog inputsSMAI" for description on frequency tracking.

3.4.8.3 Setting parameters

Table 19: PRIMVAL Non group settings (basic)

Name Values (Range) Unit Step Default Description

Frequency 50.0 - 60.0 Hz 10.0 50.0 Rated system frequency

1MRK 505 211-UEN C Section 3IED application

75

 Application manual

Page 82: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 82/457

3.4.9 Signal matrix for binary inputs SMBI

3.4.9.1 Application

The Signal matrix for binary inputs function SMBI is used within the ApplicationConfiguration tool in direct relation with the Signal Matrix tool. SMBI representsthe way binary inputs are brought in for one IED configuration.

3.4.9.2 Setting guidelines

There are no setting parameters for the Signal matrix for binary inputs SMBIavailable to the user in Parameter Setting tool. However, the user shall give a nameto SMBI instance and the SMBI inputs, directly in the Application Configuration

tool. These names will define SMBI function in the Signal Matrix tool. The user defined name for the input or output signal will also appear on the respectiveoutput or input signal.

3.4.9.3 Setting parameters

The function does not have any parameters available in local HMI or PCM600.

3.4.10 Signal matrix for binary outputs SMBO

3.4.10.1 Application

The Signal matrix for binary outputs function SMBO is used within theApplication Configuration tool in direct relation with the Signal Matrix tool.SMBO represents the way binary outputs are sent from one IED configuration.

It is important that SMBO inputs are connected when SMBOs

are connected to physical outputs through the Signal Matrix

Tool. If SMBOs are connected (in SMT) but their inputs not, all

the physical outputs will be set by default. This might cause

malfunction of primary equipment and/or injury to personnel.

3.4.10.2 Setting guidelines

There are no setting parameters for the Signal matrix for binary outputs SMBOavailable to the user in Parameter Setting tool. However, the user must give a nameto SMBO instance and SMBO outputs, directly in the Application Configurationtool. These names will define SMBO function in the Signal Matrix tool.

Section 3 1MRK 505 211-UEN C

IED application

76

 Application manual

Page 83: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 83/457

3.4.10.3 Setting parameters

The function does not have any parameters available in local HMI or PCM600.

3.4.11 Signal matrix for analog inputs SMAI

3.4.11.1 Application

Signal matrix for analog inputs function (SMAI), also known as the preprocessor function, processes the analog signals connected to it and gives information aboutall aspects of the analog signals connected, like the RMS value, phase angle,frequency, harmonic content, sequence components and so on. This information isthen used by the respective functions in ACT (for example protection,

measurement or monitoring).The SMAI function is used within PCM600 in direct relation with the SignalMatrix tool or the Application Configuration tool.

3.4.11.2 Frequency values

The frequency functions includes a functionality based on level of positivesequence voltage, IntBlockLevel , to validate if the frequency measurement is validor not. If positive sequence voltage is lower than IntBlockLevel the function is

 blocked. IntBlockLevel , is set in % of UBase/√3

If SMAI setting ConnectionType is Ph-Ph at least two of the inputs GRPxL1,GRPxL2 and GRPxL3 must be connected in order to calculate positive sequencevoltage. If SMAI setting ConnectionType is Ph-N , all three inputs GRPxL1,GRPxL2 and GRPxL3 must be connected in order to calculate positive sequencevoltage.

If only one phase-phase voltage is available and SMAI setting ConnectionType is Ph-Ph the user is advised to connect two (not three) of the inputs GRPxL1,GRPxL2 and GRPxL3 to the same voltage input as shown in figure 23 to makeSMAI calculating a positive sequence voltage (that is input voltage/√3).

IEC10000060-1-en.vsd

IEC10000060 V1 EN

Figure 23: Connection example 

1MRK 505 211-UEN C Section 3IED application

77

 Application manual

Page 84: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 84/457

The above described scenario does not work if SMAI settingConnectionType is Ph-N . If only one phase-earth voltage isavailable, the same type of connection can be used but the SMAIConnectionType setting must still be Ph-Ph and this has to beaccounted for when setting IntBlockLevel . If SMAI settingConnectionType is Ph-N and the same voltage is connected to allthree SMAI inputs, the positive sequence voltage will be zero andthe frequency functions will not work properly.

The outputs from the above configured SMAI block shall only beused for Overfrequency protection (SAPTOF), Underfrequency

 protection (SAPTUF) and Rate-of-change frequency protection(SAPFRC) due to that all other information except frequency and

 positive sequence voltage might be wrongly calculated.

3.4.11.3 Setting guidelines

The parameters for the signal matrix for analog inputs (SMAI) functions are set viathe local HMI or PCM600.

Every SMAI function block can receive four analog signals (three phases and oneneutral value), either voltage or current. SMAI outputs give information aboutevery aspect of the 3ph analog signals acquired (phase angle, RMS value,

frequency and frequency derivates, and so on – 244 values in total). Besides the block “group name”, the analog inputs type (voltage or current) and the analoginput names that can be set directly in ACT.

Instantaneous protection function with a 3 ms cycle time, needs to be connected tothe processing SMAI function block, which is also running at 3 ms task cycle. Inaddition, logic function blocks used with these fast cycle protection functions needto have 3 ms task cycle. Same procedure needs to be followed for each cycle time.

 DFTRefExtOut : Parameter valid only for function block SMAI1 .

Reference block for external output (SPFCOUT function output).

 DFTReference: Reference DFT for the block.

These DFT reference block settings decide DFT reference for DFT calculations.The settings InternalDFTRef will use fixed DFT reference based on set systemfrequency. AdDFTRefChn will use DFT reference from the selected group block,when own group selected adaptive DFT reference will be used based on calculatedsignal frequency from own group. The setting  ExternalDFTRef will use reference

 based on what is connected to input DFTSPFC.

Section 3 1MRK 505 211-UEN C

IED application

78

 Application manual

Page 85: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 85/457

ConnectionType: Connection type for that specific instance (n) of the SMAI (if it is Ph-N or Ph-Ph). Depending on connection type setting the not connected Ph-N or  Ph-Ph outputs will be calculated.

 Negation: If the user wants to negate the 3ph signal, it is possible to choose tonegate only the phase signals Negate3Ph, only the neutral signal NegateN or both

 Negate3Ph+N . negation means rotation with 180° of the vectors.

UBase: Base voltage setting (for each instance x).

 MinValFreqMeas: The minimum value of the voltage for which the frequency iscalculated, expressed as percent of UBase (for each instance n).

Settings DFTRefExtOut and DFTReference shall be set to defaultvalue InternalDFTRef if no VT inputs are available.

Even if the user sets the AnalogInputType of a SMAI block to“Current ”, the MinValFreqMeas is still visible. However, using thecurrent channel values as base for frequency measurement is not

recommendable for a number of reasons, not last among them being the low level of currents that one can have in normaloperating conditions.

Examples of adaptive frequency tracking

1MRK 505 211-UEN C Section 3IED application

79

 Application manual

Page 86: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 86/457

IEC07000197.vsd

SMAI instance 3 phase group

SMAI1:1 1

SMAI2:2 2

SMAI3:3 3

SMAI4:4 4

SMAI5:5 5

SMAI6:6 6

SMAI7:7 7

SMAI8:8 8

SMAI9:9 9

SMAI10:10 10

SMAI11:11 11

SMAI12:12 12

Task time group 1

SMAI instance 3 phase group

SMAI1:13 1

SMAI2:14 2

SMAI3:15 3

SMAI4:16 4

SMAI5:17 5

SMAI6:18 6

SMAI7:19 7

SMAI8:20 8

SMAI9:21 9

SMAI10:22 10

SMAI11:23 11

SMAI12:24 12

Task time group 2

SMAI instance 3 phase group

SMAI1:25 1

SMAI2:26 2

SMAI3:27 3

SMAI4:28 4

SMAI5:29 5

SMAI6:30 6

SMAI7:31 7

SMAI8:32 8

SMAI9:33 9

SMAI10:34 10

SMAI11:35 11

SMAI12:36 12

Task time group 3

 AdDFTRefCh7

 AdDFTRefCh4

IEC07000197 V2 EN

Figure 24: Twelve SMAI instances are grouped within one task time. SMAI 

blocks are available in three different task times in the IED. Two 

pointed instances are used in the following examples.

The examples shows a situation with adaptive frequency tracking with onereference selected for all instances. In practice each instance can be adapted to theneeds of the actual application.

Example 1

Section 3 1MRK 505 211-UEN C

IED application

80

 Application manual

Page 87: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 87/457

IEC07000198-2-en.vsd

SMAI1:1

BLOCK

DFTSPFC

^GRP1L1

^GRP1L2

^GRP1L3

^GRP1N

SPFCOUT

 AI3P

 AI1

 AI2

 AI3

 AI4

 AIN

SMAI1:13

BLOCK

DFTSPFC

^GRP1L1

^GRP1L2

^GRP1L3^GRP1N

SPFCOUT

 AI3P

 AI1

 AI2

 AI3 AI4

 AIN

SMAI1:25

BLOCK

DFTSPFC

^GRP1L1

^GRP1L2

^GRP1L3

^GRP1N

SPFCOUT

 AI3P

 AI1

 AI2

 AI3

 AI4

 AIN

IEC07000198 V3 EN

Figure 25: Configuration for using an instance in task time group 1 as DFT 

reference 

Assume instance SMAI7:7 in task time group 1 has been selected in theconfiguration to control the frequency tracking . Observe that the selected referenceinstance (i.e. frequency tracking master) must be a voltage type. Observe that

 positive sequence voltage is used for the frequency tracking feature.

For task time group 1 this gives the following settings (see Figure 24 for numbering):

SMAI1:1: DFTRefExtOut = AdDFTRefCh7 to route SMAI7:7 reference to theSPFCOUT output, DFTReference = AdDFTRefCh7 for SMAI1:1 to use SMAI7:7as reference (see Figure 25) SMAI2:2 – SMAI12:12: DFTReference =

 AdDFTRefCh7 for SMAI2:2 – SMAI12:12 to use SMAI7:7 as reference.

For task time group 2 this gives the following settings:

SMAI1:13 – SMAI12:24: DFTReference = ExternalDFTRef to use DFTSPFCinput as reference (SMAI7:7)

For task time group 3 this gives the following settings:

SMAI1:25 – SMAI12:36: DFTReference = ExternalDFTRef to use DFTSPFCinput as reference (SMAI7:7)

Example 2

1MRK 505 211-UEN C Section 3IED application

81

 Application manual

Page 88: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 88/457

IEC07000199-2-en.vsd

SMAI1:13

BLOCK

DFTSPFC

^GRP1L1

^GRP1L2

^GRP1L3

^GRP1N

SPFCOUT

 AI3P

 AI1

 AI2

 AI3

 AI4

 AIN

SMAI1:1

BLOCK

DFTSPFC

^GRP1L1

^GRP1L2

^GRP1L3^GRP1N

SPFCOUT

 AI3P

 AI1

 AI2

 AI3 AI4

 AIN

SMAI1:25

BLOCK

DFTSPFC

^GRP1L1

^GRP1L2

^GRP1L3

^GRP1N

SPFCOUT

 AI3P

 AI1

 AI2

 AI3

 AI4

 AIN

IEC07000199 V3 EN

Figure 26: Configuration for using an instance in task time group 2 as DFT 

reference.

Assume instance SMAI4:16 in task time group 2 has been selected in theconfiguration to control the frequency tracking for all instances. Observe that theselected reference instance (i.e. frequency tracking master) must be a voltage type.Observe that positive sequence voltage is used for the frequency tracking feature.

For task time group 1 this gives the following settings (see Figure 24 for numbering):

SMAI1:1 – SMAI12:12: DFTReference = ExternalDFTRef to use DFTSPFC inputas reference (SMAI4:16)

For task time group 2 this gives the following settings:

SMAI1:13: DFTRefExtOut = AdDFTRefCh4 to route SMAI4:16 reference to theSPFCOUT output, DFTReference = AdDFTRefCh4 for SMAI1:13 to useSMAI4:16 as reference (see Figure 26) SMAI2:14 – SMAI12:24: DFTReference =

 AdDFTRefCh4 to use SMAI4:16 as reference.

For task time group 3 this gives the following settings:

SMAI1:25 – SMAI12:36: DFTReference = ExternalDFTRef to use DFTSPFCinput as reference (SMAI4:16)

Section 3 1MRK 505 211-UEN C

IED application

82

 Application manual

Page 89: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 89/457

3.4.11.4 Setting parameters

Table 20: SMAI1 Non group settings (basic)

Name Values (Range) Unit Step Default Description

DFTRefExtOut InternalDFTRef   AdDFTRefCh1 AdDFTRefCh2 AdDFTRefCh3 AdDFTRefCh4 AdDFTRefCh5 AdDFTRefCh6 AdDFTRefCh7 AdDFTRefCh8 AdDFTRefCh9 AdDFTRefCh10 AdDFTRefCh11 AdDFTRefCh12External DFT ref 

- - InternalDFTRef DFT reference for external output

DFTReference InternalDFTRef   AdDFTRefCh1 AdDFTRefCh2 AdDFTRefCh3 AdDFTRefCh4 AdDFTRefCh5 AdDFTRefCh6 AdDFTRefCh7 AdDFTRefCh8 AdDFTRefCh9 AdDFTRefCh10 AdDFTRefCh11 AdDFTRefCh12External DFT ref 

- - InternalDFTRef DFT reference

ConnectionType Ph-N

Ph-Ph

- - Ph-N Input connection type

TYPE 1 - 2 Ch 1 1 1=Voltage, 2=Current

Table 21: SM AI1 Non group settings (advanced)

Name Values (Range) Unit Step Default Description

Negation Off  NegateNNegate3PhNegate3Ph+N

- - Off Negation

MinValFreqMeas 5 - 200 % 1 10 Limit for frequency calculation in % of  UBase

UBase 0.05 - 2000.00 kV 0.05 400.00 Base voltage

1MRK 505 211-UEN C Section 3IED application

83

 Application manual

Page 90: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 90/457

Table 22: SMAI2 Non group settings (basic)

Name Values (Range) Unit Step Default Description

DFTReference InternalDFTRef   AdDFTRefCh1

 AdDFTRefCh2 AdDFTRefCh3 AdDFTRefCh4 AdDFTRefCh5 AdDFTRefCh6 AdDFTRefCh7 AdDFTRefCh8 AdDFTRefCh9 AdDFTRefCh10 AdDFTRefCh11 AdDFTRefCh12External DFT ref 

- - InternalDFTRef DFT reference

ConnectionType Ph-NPh-Ph

- - Ph-N Input connection type

TYPE 1 - 2 Ch 1 1 1=Voltage, 2=Current

Table 23: SMAI2 Non group settings (advanced)

Name Values (Range) Unit Step Default Description

Negation Off  NegateNNegate3PhNegate3Ph+N

- - Off Negation

MinValFreqMeas 5 - 200 % 1 10 Limit for frequency calculation in % of  UBase

UBase 0.05 - 2000.00 kV 0.05 400.00 Base voltage

3.4.12 Summation block 3 phase 3PHSUM

3.4.12.1 Application

The analog summation block 3PHSUM function block is used in order to get thesum of two sets of 3 phase analog signals (of the same type) for those IEDfunctions that might need it.

3.4.12.2 Setting guidelines

The summation block receives the three-phase signals from SMAI blocks. Thesummation block has several settings.

SummationType: Summation type (Group 1 + Group 2, Group 1 - Group 2, Group

2 - Group 1 or  –(Group 1 + Group 2)).

 DFTReference: The reference DFT block ( InternalDFT Ref , DFTRefGrp1 or  External DFT ref ) .

Section 3 1MRK 505 211-UEN C

IED application

84

 Application manual

Page 91: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 91/457

 FreqMeasMinVal : The minimum value of the voltage for which the frequency iscalculated, expressed as percent of UBase base voltage setting (for each instance x).

UBase: Base voltage setting.

3.4.12.3 Setting parameters

Table 24: 3PHSUM Non group settings (basic)

Name Values (Range) Unit Step Default Description

SummationType Group1+Group2Group1-Group2Group2-Group1-(Group1+Group2)

- - Group1+Group2 Summation type

DFTReference InternalDFTRef   AdDFTRefCh1External DFT ref 

- - InternalDFTRef DFT reference

Table 25: 3PHSUM Non group settings (advanced)

Name Values (Range) Unit Step Default Description

FreqMeasMinVal 5 - 200 % 1 10 Amplitude limit for frequency calculationin % of Ubase

UBase 0.05 - 2000.00 kV 0.05 400.00 Base voltage

3.4.13 Authority status ATHSTAT

3.4.13.1 Application

Authority status (ATHSTAT) function is an indication function block, whichinforms about two events related to the IED and the user authorization:

• the fact that at least one user has tried to log on wrongly into the IED and itwas blocked (the output USRBLKED)

• the fact that at least one user is logged on (the output LOGGEDON)

The two outputs of ATHSTAT function can be used in the configuration for different indication and alarming reasons, or can be sent to the station control for the same purpose.

3.4.13.2 Setting parameters

The function does not have any parameters available in the local HMI or PCM600.

3.4.14 Denial of service DOS

1MRK 505 211-UEN C Section 3IED application

85

 Application manual

Page 92: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 92/457

3.4.14.1 Setting guidelines

The function does not have any parameters available in the local HMI or PCM600.

3.5 Differential protection

3.5.1 Busbar differential protection

Busbar differential protection, 3-phase version

Function descriptionIEC 61850

identification

IEC 60617

identification

ANSI/IEEE C37.2

device number

Busbar differential protection, 2 zones,three phase/4 bays

BUTPTRC 3Id/I 

SYMBOL-JJ V1 EN

87B

Busbar differential protection, 2 zones,three phase/4 or 8 bays

BTCZPDIF 3Id/I 

SYMBOL-JJ V1 EN

87B

Busbar differential protection, 2 zones,three phase/4 or 8 bays

BTZNPDIF 3Id/I 

SYMBOL-JJ V1 EN

87B

Busbar differential protection, 2 zones,three phase/4 or 8 bays

BTZNPDIF 3Id/I 

SYMBOL-JJ V1 EN

87B

Busbar differential protection, 2 zones,three phase/4 or 8 bays

BZITGGIO 3Id/I 

SYMBOL-JJ V1 EN

87B

Section 3 1MRK 505 211-UEN C

IED application

86

 Application manual

Page 93: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 93/457

Busbar differential protection, 1-phase version

Function description IEC 61850

identification

IEC 60617

identification

ANSI/IEEE C37.2

device number

Busbar differential protection, 2 zones,single phase/12 or 24 bays

BUSPTRC 3Id/I 

SYMBOL-JJ V1 EN

87B

Busbar differential protection, 2 zones,single phase/12 or 24 bays

BCZSPDIF 3Id/I 

SYMBOL-JJ V1 EN

87B

Busbar differential protection, 2 zones,single phase/12 or 24 bays

BZNSPDIF 3Id/I 

SYMBOL-JJ V1 EN

87B

Busbar differential protection, 2 zones,single phase/12 or 24 bays

BZNSPDIF 3Id/I 

SYMBOL-JJ V1 EN

87B

Busbar differential protection, 2 zones,single phase/12 or 24 bays

BZISGGIO 3Id/I 

SYMBOL-JJ V1 EN

87B

Status of primary switching object for Busbar protection zone selection

Function description IEC 61850

identification

IEC 60617

identification

ANSI/IEEE C37.2

device number

Status of primary switching object for 

Busbar protection zone selection

SWSGGIO - -

3.5.1.1 Basic applications

GeneralBasic types of applications for REB670 IED are shown and described in thischapter. For these applications usually three phase version of the IED, with twodifferential zone and four (or even eight) 3-phase CT inputs, is used.

1MRK 505 211-UEN C Section 3IED application

87

 Application manual

Page 94: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 94/457

Meshed corner application and T-connection applicationThe REB670 general differential function is suitable for application on mesh-corner arrangements. Mesh corners might have four or even up to six CT inputsand are basically simple single busbar arrangements. A similar application willoccur when a T-protection is required for one-and-half breaker or ring busbar arrangements.

IEC11000237-1-en.vsd

IEC11000237 V1 EN

Figure 27: Example of REB670 application on T-connection 

3.5.1.2 Busbar protection applications

GeneralA busbar protection is a device which protects busbars against short-circuits andearth-faults. In the early development of electricity systems, no separate protectiondevice was used for busbar protection. Remote end line protections were used asmain protection for busbar faults. With the increased short-circuit power in thenetwork separate differential IEDs for busbar protection have to be installed inorder to limit the damage caused by the primary fault currents. In the same time, itis also a must to secure the network stability, as a delayed tripping for busbar faultscan also lead to network instability, pole slip of near-by generators and even totalsystem collapse.

For bus zone protection applications, it is extremely important to have goodsecurity since an unwanted operation might have severe consequences. Theunwanted operation of the bus differential IED will have the similar effect from theoperational point of view as simultaneous faults on all power system elementsconnected to the bus. On the other hand, the IED has to be dependable as well.

Failure to operate or even slow operation of the differential IED, in case of anactual internal fault, can have serious consequences. Human injuries, power system blackout, transient instability or considerable damage to the surrounding substationequipment and the close-by generators are some of the possible outcomes.

Therefore, Busbar differential protection must fulfill the following requirements:

1. Must be absolutely stable during all external faults. External faults are muchmore common than internal faults. The magnitude of external faults can beequal to the stations maximum short circuit capacity. Heavy CT-saturation dueto high DC components and/or remanence at external faults must not lead tomaloperation of the busbar differential protection. The security against

Section 3 1MRK 505 211-UEN C

IED application

88

 Application manual

Page 95: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 95/457

misoperation must be extremely high due to the heavy impact on the overallnetwork service.

2. Must have as short tripping time as possible in order to minimize the damage,minimize the danger and possible injury to the people who might be workingin the station at the moment of internal fault, and secure the network stability.

3. Must be able to detect and securely operate for internal faults even with heavyCT saturation. The protection must also be sensitive enough to operate for minimum fault currents, which sometimes can be lower than the maximumload currents.

4. Must be able to selectively detect faults and trip only the faulty part of the busbar system.

5. Must be secure against maloperation due to auxiliary contact failure, possiblehuman mistakes and faults in the secondary circuits and so on.

Distinctive features of busbar protection schemesA busbar protection scheme design, depends very much on the substationarrangement. Complexity of the scheme can drastically vary from station to station.Typical applications problems, for the most common busbar protection schemes,are described in this chapter.

Differential protectionThe basic concept for any differential IED is that the sum of all currents, whichflow to and from the protection zone, must be equal to zero. If this is not the case,an internal fault has occurred. This is practically a direct use of well knownKirchhoffss first law. However, busbar differential IEDs do not measure directlythe primary currents in the high voltage conductors, but the secondary currents of magnetic core current transformers (that is, CTs), which are installed in all high-voltage bays connected to the busbar.

Therefore, the busbar differential IED is unique in this respect, that usually quite afew CTs, often with very different ratios and classes, are connected to the samedifferential protection zone. Because the magnetic core current transformers are non-linear measuring devices, under high current conditions in the primary CT circuitsthe individual secondary CT currents can be drastically different from the original

 primary currents. This is caused by CT saturation, a phenomenon that is wellknown to protection engineers. During the time when any of the currenttransformer connected to the differential IED is saturated, the sum of all CT

secondary currents will not be equal to zero and the IED will measure falsedifferential current. This phenomenon is especially predominant for busbar differential protection applications, because it has the strong tendency to causeunwanted operation of the differential IED.

Remanence in the magnetic core of a current transformer is an additional factor,which can influence the secondary CT current. It can improve or reduce thecapability of the current transformer to properly transfer the primary current to thesecondary side. However, the CT remanence is a random parameter and it is not

 possible in practice to precisely predict it.

1MRK 505 211-UEN C Section 3IED application

89

 Application manual

Page 96: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 96/457

Another, and maybe less known, transient phenomenon appears in the CTsecondary circuit at the instant when a high primary current is interrupted. It is

 particularly dominant if the HV circuit breaker chops the primary current before itsnatural zero crossing. This phenomenon is manifested as an exponentially decayingdc current component in the CT secondary circuit. This secondary dc current hasno corresponding primary current in the power system. The phenomenon can besimply explained as a discharge of the magnetic energy stored in the magnetic coreof the current transformer during the high primary current condition. Depending onthe type and design of the current transformer this discharging current can have atime constant in the order of a hundred milliseconds.

Consequently, all these phenomena have to be considered during the design stageof a busbar differential IED in order to prevent the unwanted operation of the IEDduring external fault conditions.

The analog generation of the busbar differential IEDs (that is,RADHA, RADSS,REB 103) generally solves all these problems caused by the CT non-linear characteristics by using the galvanic connection between the secondary circuits of all CTs connected to the protected zone. These IEDs are designed in such a waythat the current distribution through the IED differential branch during all transientconditions caused by non-linearity of the CTs will not cause the unwantedoperation of the differential IED. In order to obtain the required secondary CTcurrent distribution, the resistive burden in the individual CT secondary circuitsmust be kept below the pre-calculated value in order to guaranty the stability of theIED.

In new numerical protection IEDs, all CT and VT inputs are galvanically separated

from each other. All analog input quantities are sampled with a constant samplingrate and these discreet values are then transferred to corresponding numericalvalues (that is, AD conversion). After these conversions, only the numbers are usedin the protection algorithms. Therefore, for the modern numerical differential IEDsthe secondary CT circuit resistance might not be a decisive factor any more.

The important factor for the numerical differential IED is the time available to theIED to make the measurements before the CT saturation, which will enable theIED to take the necessary corrective actions. This practically means that the IEDhas to be able to make the measurement and the decision during the short period of time, within each power system cycle, when the CTs are not saturated. From the

 practical experience, obtained from heavy current testing, this time, even under extremely heavy CT saturation, is for practical CTs around two milliseconds.Because of this, it was decided to take this time as the design criterion in REB 670IED, for the minimum acceptable time before saturation of a practical magneticcore CT. Thus, the CT requirements for REB 670 IED are kept to an absoluteminimum. Refer to section "Rated equivalent secondary e.m.f. requirements" for more details.

However, if the necessary preventive action has to be taken for every single CTinput connected to the differential IED, the IED algorithm would be quite complex.Thus, it was decided to re-use the ABB excellent experience from the analog

Section 3 1MRK 505 211-UEN C

IED application

90

 Application manual

Page 97: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 97/457

 percentage restrained differential protection IED (that is, RADSS and REB 103),and use only the following three quantities:

1. incoming current (that is, sum of all currents which are entering the protection

zone)2. outgoing current (that is, sum of all currents which are leaving the protection

zone)3. differential current (that is, sum of all currents connected to the protection zone)

as inputs into the differential algorithm in the numerical IED design.

These three quantities can be easily calculated numerically from the raw samplevalues (that is, twenty times within each power system cycle in the IED) from allanalog CT inputs connected to the differential zone. At the same time, they haveextremely valuable physical meaning, which clearly describes the condition of the

 protected zone during all operating conditions.By using the properties of only these three quantities, a new patented differentialalgorithm has been formed in the IED. This differential algorithm is completelystable for all external faults. All problems caused by the non-linearity of the CTsare solved in an innovative numerical way. In the same time, very fast trippingtime, down to 10 ms, can be commonly obtained for heavy internal faults.

Please refer to the technical reference manual for more details about the working principles of the Differential Function algorithm.

Zone selection (CT switching)

The so-called CT switching (that is, zone selection) is r equired in situation whenone particular circuit (that is, bay) can be connected to different busbars byindividual disconnectors. Typical example is a station with double busbars with or without transfer bus as shown in figure 56 and figure 49, where any feeder bay can

 be connected to any of the two buses. In such cases the status of all busbar disconnectors and all transfer disconnectors shall be given to the busbar protection.

Traditionally, the CT switching has been done in CT secondary circuits. However,with REB670 this is not the case. All necessary zone selection (that is, CTswitching) is done in software. Therefore, the CT secondary circuits are alwaysintact and without any auxiliary relay contacts.

To provide proper zone selection (that is, busbar replica) the position informationfrom all relevant primary switches (that is, disconnectors and/or circuit breakers)must be given to the IED. This is typically done by connecting two auxiliarycontacts (that is, normaly open and normaly closed aux contacts) from each

 primary switch to the IED binary inputs (that is, optocouplers). In REB670configuration one SwitchStatus function block shall be associated with each

 primary switching device. This block is then used internally to derive the primaryobject status and then pass this information to the busbar protection internal ZoneSelection logic.

1MRK 505 211-UEN C Section 3IED application

91

 Application manual

Page 98: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 98/457

Auxiliary contact requirement and evaluation

Auxiliary contact requirements for disconnectors and circuit breakers

The position of the primary switching object is typically obtained via two auxiliarycontacts of the primary apparatus. The first auxiliary contact indicates that primarydevice is closed. In protection literature it is called by different names as stated below:

• Normally open auxiliary contact• “a” contact (that is, 52a)• “closed”

The second auxiliary contact indicates that primary device is open. In protectionliterature it is called by different names as stated below:

• Normally closed auxiliary contact

• “b” contact (that is, 52b)• “open”

Typically both contacts are used to provide position indication and supervision for  busbar protection.

Minimum contact requirementsThe minimum requirement for the busbar replica is the record of the disconnector 

 position by using just one auxiliary contact, either NO or NC type. However recording a pair of auxiliary contacts, representing the OPEN and CLOSE position,offer additional features which can improve the reliability of the bus replica

including supervision possibilities.

Auxiliary contact evaluation logicTwo logic schemes can be found.

Scheme1_RADSS "If not OPEN then CLOSED"As the name of the scheme suggests, only when the auxiliary contacts signal cleanopen position ("normally open auxiliary (NO) contact input" = inactive and"normally closed auxiliary (NC) contact input" = active), the disconnector is takento be open. For all other signal combinations the disconnector is considered to beclosed. This scheme does not pose any special requirements to the auxiliary contact

timing. Only the disconnector NC contact must open before the disconnector maincontact is within arcing distance. The time during which the OPEN and CLOSEDsignal inputs disagree (that is, both binary inputs are active or both are inactive) ismonitored by the isolator supervision function. The maximum time allowed beforean alarm is given can be set according to the disconnector timing.

Scheme2_INX "Closed or open if clear indication available otherwise lastposition saved"As the name of the scheme suggests, only when the auxiliary contacts signal cleanOPEN or clean CLOSED position disconnector is considered to be openrespectively closed. However this poses the stringent requirements on the auxiliary

Section 3 1MRK 505 211-UEN C

IED application

92

 Application manual

Page 99: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 99/457

contacts that the CLOSED signal must become active a certain time (>150 ms) before current starts flowing for example, through arcing. Otherwise this currentwill not be taken into account in the busbar protection and this can result in amaloperation. Therefore, good timing of two auxiliary contacts is definitely required.

The time during which the OPEN and CLOSED signals disagree (that is, both binary inputs are active or both are inactive) is monitored by the isolator supervision function for both of the above two schemes. The maximum timeallowed before an alarm is given can be set according to the disconnector timing.

Table 26 and the following two figures summarize the properties of these twoschemes.

Tab le 26: T reatment of pr imary objec t aux il ia ry contac t s ta tus w ithin BBP in REB670

Primary equipment Status in busbar protection Alarm facility

Normally

Openauxiliary

contact status

(“closed” or

“a” contact)

Normally

Closedauxiliary

contact status

(“open” or “b”

contact)

when

“Scheme 1RADSS”

is selected

when

“Scheme 2INX”

is selected

Alarm after

settable timedelay

Information

visible onlocal HMI

open open closed Lastpositionsaved

yes intermediate_00

open 

closed open open no open

closed 

open closed closed no closed

closed closed closed closed yes badState_1

1

BBP

input „closed“

input „open“

N.O.

N.C.

1

0

1

0

1

0

closed

open

arcing possible

current

assignment

1) 1)

1) disconnector supervision running

en06000084.vsd

IEC06000084 V1 EN

Figure 28: Scheme_1 RADSS 

1MRK 505 211-UEN C Section 3IED application

93

 Application manual

Page 100: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 100/457

BBP

input „closed“

input „open“

N.O.

N.C.

1

0

1

0

1

0

closed

open

arcing possible

current

assignment

2)

1) 1)

1) disconnector supervision running

2) BI „closed“ should change before arcing distance

en06000085.vsd

IEC06000085 V1 EN

Figure 29: Scheme2_INX 

Circuit breaker replicaThe circuit breaker position from a bay shall be given to the busbar protectionwhen the position of this particular breaker can influence the busbar protectionoperation. Typical examples are Blind Spot protection in Bus-section and Bus-coupler bays or End Fault Protection in feeder bays. In both cases the measuringrange of a busbar protection is limited by the CT location. By additionallyrecording the CB position of a feeder or a coupler the zone between the CT and the

CB can be better protected while CB is open. However in such cases it is of utmostimportance to connect the CB closing command to the busbar protection in order toinclude again the CT current to the busbar protection zones in time. It is as stronglyrecommended to always use Scheme1_RADSS for all CBs positions connected tothe IED in order to minimize any risk of possible problems due to late inclusion of CT current to the relevant differential zones.

Line disconnector replicaThe line disconnector position from a feeder bay might be required for busbar 

 protection under certain circumstances. Typical example is when the linedisconnector QB9 and associated earthing switch are located between CT and

 protected busbar as indicated in figure 30.

Section 3 1MRK 505 211-UEN C

IED application

94

 Application manual

Page 101: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 101/457

BI1

QA1

QB1

ZA

ZB

QB2

QB9QC1

en06000086.vsd

IEC06000086 V1 EN

Figure 30: Feeder bay layout when line disconnector position might be 

required for busbar protection 

Such feeder set-up can be often found in GIS stations where cable CTs are used for  busbar protection. If in such feeder the line disconnector QB9 is open and thenimmediately the earthing switch QC1 is closed before the busbar disconnectorsQB1 & QB2 are open there is a danger to get current unbalance into the zonedifferential measurement under following circumstances:

• In case of parallel lines zero sequence mutual coupling can induce zerosequence current into the grounded line especially during external earth-faults.

• In case of cable feeder the stored energy in the cable will be dischargedthrough the earthing switch at the moment of its closing.

In order to avoid such problems for busbar protection the status of linedisconnector can be monitored by busbar protection and CT measurement can bedisconnected from both differential zones as soon line disconnector is open.Similar functionality can be obtained by instead monitoring the position of feeder 

 breaker QA1. In such case the breaker closing signal shall be connected to busbar  protection as well.

Zone selection featuresThe IED offers an extremely effective solution for stations where zone selection(that is, CT switching) is required. This is possible due to the software facility,which gives full and easy control over all CT inputs connected to the IED. The

 philosophy is to allow every CT input to be individually controlled by a setting parameter. This parameter called ZoneSel can be individually configured for everyCT input. This parameter, for every bay, can be set to only one of the followingfive alternatives:

1. FIXEDtoZA

2. FIXEDtoZB

3. FIXEDtoZA&-ZB

4. CtrlIncludes

5. CtrlExcludes

1MRK 505 211-UEN C Section 3IED application

95

 Application manual

Page 102: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 102/457

If for a particular CT input setting parameter  ZoneSel is set to FIXEDtoZA, thenthis CT input will be only included to the differential zone A. This setting istypically used for simple single zone application such as: single busbar staions, one-and-a-half breaker stations or double breaker stations.

If for a particular CT input setting parameter  ZoneSel is set to FIXEDtoZB, thenthis CT input will be only included to the differential zone B. This setting istypically used for applications such as: one-and-a-half breaker stations or double

 breaker stations.

If for a particular CT input setting parameter  ZoneSel is set to FIXEDtoZA&-ZB,then this CT input will be included to the differential zone A, but its invertedcurrent value will be as well included to the differential zone B. This setting istypically used for bus coupler or bus section bays when only one currenttransformer is available see figure 32.

If for a particular CT input setting parameter  ZoneSel is set to Ctrl_Includes, thenthis CT input will be:

• included to the differential zone A when input signal CTRLZA oncorresponding bay block is given logical value one and it will be excludedfrom the differential zone A when input signal CTRLZA on corresponding bay

 block is given logical value zero.• included to the differential zone B when input signal CTRLZB on

corresponding bay block is given logical value one and it will be excludedfrom the differential zone B when input signal CTRLZB on corresponding bay

 block is given logical value zero.

This setting is typically used for feeder bays in double busbar stations in order toform proper busbar disconnector replica. It is especially suitable when normallyopen and normally closed (that is, a and b) auxiliary contacts from the busbar disconnectors are available to the IED.

If for a particular CT input setting parameter  ZoneSel is set to Ctrl_Excludes, thenthis CT input will be:

• excluded from the differential zone A when input signal CTRLZA oncorresponding bay block is given logical value one and it will be included tothe differential zone A when input signal CTRLZA on corresponding bay

 block is given logical value zero• excluded from the differential zone B when input signal CTRLZB on

corresponding bay block is given logical value one and it will be included tothe differential zone B when input signal CTRLZB on corresponding bay

 block is given logical value zero

This setting is typically used for feeder bays in double busbar single breaker stations in order to form proper busbar disconnector replica. It is especially suitablewhen only normally closed (that is, b) auxiliary contact from the busbar 

Section 3 1MRK 505 211-UEN C

IED application

96

 Application manual

Page 103: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 103/457

disconnector(s) is available to the IED. For more information please refer tofigure 51.

In applications where zone selection (that is, CT switching) is required (for 

example double or multiple busbar stations) all CTs will be permanently connectedto the analogue input module(s), as shown in figure 50. Therefore, all necessaryswitching of currents will be performed in internal software logic.

CT disconnection for bus section and bus coupler current transformer

coresIn practice there are three different solutions for bus section or bus coupler baylayout. First solution is with two sets of main CTs, which are located on both sidesof the circuit breaker, as shown in figure 31.

ZA

21 8

ZB

21 8

BS

en01000013.vsd

IEC01000013 V1 EN

Figure 31: Example of station with two sets of main CTs in the bus-section bay 

This is the most expensive, but good solution for busbar protection. Twodifferential zones overlapping across the bus-section or bus-coupler circuit breaker.All faults in the overlapping zone will be instantly tripped by both zonesirrespective of the section/coupler circuit breaker status. However with modern

 busbar protection it is possible to disconnect both CTs from the relevant zones

when the bus-section or bus-coupler circuit breaker is open. This will insure that if internal fault happen, in the overlapping zone, while breaker is open, only thefaulty zone will be tripped while other busbar section will remain in service.However, due to low probability of such fault happening, while the breaker is open,such special considerations are typically not included in the busbar protectionscheme for this type of stations. In such application the bus section or bus coupler current transformers shall be wired just to two separate current input of the IED.Then in the parameter setting tool (PST) for the corresponding bays the parameter 

 ZoneSel shall be set to FIXEDtoZA in one bay and FIXEDtoZB in another bay. Thiswill insure that these currents are given to both differential zones.

1MRK 505 211-UEN C Section 3IED application

97

 Application manual

Page 104: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 104/457

When live tank circuit breakers are used, owing to the high cost of the HV currenttransformer often only one current transformer is available in bus-section or bus-coupler bay. The suggested solution in such applications is shown in figure 32.

en01000014.vsd

ZA

21 8

ZB

21 8

BS

Blind Zone

IEC01000014 V1 EN

Figure 32: Example of station with just one main CT in the bus-section bay 

For this type of solution just one main CT is located on only one side of the circuit breaker. Thus, there is no zone overlapping across the section/coupler circuit breaker as shown in figure 31. A blind spot exists between the current transformer and the circuit breaker in the bus section or bus-coupler bay as shown in figure 32.

For an internal fault in the blind spot, the differential zone ZA will unnecessarilyoperate and open the bus section breaker and all other feeder breakers associatedwith it. Nevertheless the fault will still exists on other busbar section, but it isoutside the current transformer in the bus section bay and hence outside the zoneZB ( that is, it is external fault for zone ZB). Similar problem will also exist if section/coupler circuit breaker was open before the internal fault in the blind zone.Therefore, the busbar protection scheme does not protect the complete busbar.

In order to improve the busbar protection scheme with this type of station layout, itis often required to disconnect the bus-section or bus-coupler CT from the two

differential zones as soon as the bus-section or bus-coupler circuit breaker isopened. This arrangement can be easily achieved within the IED. In suchapplication the bus section or bus coupler current transformer shall be wired just toone current input of the IED. Then in the Parameter Setting tool for thecorresponding bay parameter  ZoneSel shall be set to FIXEDtoZA&-ZB. This willinsure that this current is given to both differential zones. In order to disconnectthis current from both zones, when the coupler/section breaker is open additionallogic as shown in figure 33 have to be done in the configuration. The following two

 binary inputs are at least necessary in order to guaranty proper operation of such logic:

• Normally closed contact of the bus section or bus coupler circuit breaker 

Section 3 1MRK 505 211-UEN C

IED application

98

 Application manual

Page 105: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 105/457

• Signal from the bus section or bus coupler circuit breaker closing circuit thatsomebody wants to close the breaker 

This solution does not depend on contact timing between the main contacts andauxiliary contact of the circuit breaker. It directly follows the philosophy used for RADSS/REB 103 schemes used for similar applications before. Principleconnection between the bus-coupler CB normally closed auxiliary contact (b-contact), REB670 and internal configuration logic, as shown in figure 33

en06000155.vsd

Zone A

Zone B

Bus-Coupler 

Bay

REB 670

CTRLZA

CTRLZB

TRIP

CONNZA

CONNZB

Bxxx

I3PB1

BLKTR

TRZONE

TRBAY

BBP & BFP trip command to Bus-Coupler breaker 

BOM

 A/D

Parameter ZoneSel must

be set to "FixedToZA&-ZB"tZeroCurrent=150ms

Other 

Equipment

CT InputTRM

External or Internal

Bus-Coupler BFP

Backup Trip Command

Bus-Coupler Backup

OC Trip

QB1

QB2

b

BI1

2400/1

QA1

ZEROCUR

BIMCB Closing

Signal

³1tt=1s

&

IEC06000155 V1 EN

Figure 33: Bus coupler bay with one CT and b aux. contact only from CB 

This scheme will disconnect the section/coupler CTs after about 80 ms (pre-settime under parameter setting tZeroCurrent in the relevant bay function block) fromthe moment of opening of the section/coupler CB ( that is, from the moment when

auxiliary b contact makes). Nevertheless this time delay is absolutely necessary inorder to prevent racing between the opening of the main breaker contact anddisconnection of the CT from the differential zones. This scheme will as welldisconnect the CT in case of the operation of any of the two internal differentialzones used in the scheme. This will secure the delayed (about 150 ms) clearing andtripping of the internal fault within the blind zone even in case of section/coupler circuit breaker failure during such fault. This facility will improve the performanceof the busbar protection scheme when one CT is located on only one side of the bus-section / bus-coupler circuit breaker.

1MRK 505 211-UEN C Section 3IED application

99

 Application manual

Page 106: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 106/457

With GIS or live tank circuit breakers, owing to high cost of HV CT installations,sometimes no current transformers are available in bus-section or bus-coupler bay.This is the third solution shown in figure 34

en04000283.vsd

ZA

21 10

ZB

21 10

BS

IEC04000283 V1 EN

Figure 34: Example of station without main CTs in the bus-section bay 

In such case two separate zones can be maintained only while bus coupler breaker is open. As soon as bus coupler breaker is going to be closed the zoneinterconnection feature must be activated and complete busbars will beautomatically protected with just one overall differential zone.

Since there are no current transformer in the bus coupler bay, there is no need toallocate internal bay function block for the bus coupler bay. However someadditional configuration logic is required to obtain automatic zone interconnectionactivation when bus coupler breaker shall be closed. Example of such logic, asshown in figure 35.

Section 3 1MRK 505 211-UEN C

IED application

100

 Application manual

Page 107: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 107/457

en06000137.vsd

QA1

Zone A

Zone B

ZI

 ACTIVE

BOMBIM

REB 670

Bus coupler 

EXTSTART

 ALARM

Indication that

Zone interconnection

is active

&

   B   C

   C   B

  c   l  o

  s   i  n  g

  s  w

   i   t  c   h

QB1 QB2

t

tOFF=1.0s

1

IEC06000137 V1 EN

Figure 35: Configuration logic for bus coupler without main CTs 

End fault protectionWhen Live tank CBs or GIS are involved, there is a physical separation betweenthe CT and the CB. End Fault Protection is related to primary faults between mainCT and CB in a feeder bay. Therefore, it is directly related to the position of themain CT in feeder bay. Three CT positions in feeder bays are typically used in

 power systems around the world, as shown in figure 36.

en06000138.vsd

BI1

QA1

BI1Busbar 

Protection

Feeder 

Protection BI1

QA1

Busbar 

Protection

Feeder 

Protection

QA1

BI1

Busbar 

Protection

Feeder 

Protection

 A B

1

C

1

IEC06000138 V1 EN

Figure 36: Typical CT locations in a feeder bay 

where:

 A = two CTs are available one on each side of the feeder circuit breaker 

B = one CT is available on the line side of the feeder circuit breaker 

C = one CT is available on the bus side of the feeder circuit breaker 

1 = End fault region

1MRK 505 211-UEN C Section 3IED application

101

 Application manual

Page 108: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 108/457

In figure 36, /A where two CTs are available in a feeder bay the end fault protection is not an issue. The busbar and feeder protection zones overlap acrossfeeder circuit breaker and all faults between these two CTs will be instantlydetected and tripped by both protection schemes. As a consequence of such fault

 both busbar and feeder will be disconnected from the power system.

In figure 36/B where one CT is available on the line side of the feeder circuit breaker the primary fault between CT and CB will cause certain problems.Typically such fault will be detected and tripped by busbar protection. However tocompletely clear such fault the remote feeder end CB must be tripped as well. Itshall be noted that for the feeder protection such fault will be either a reverse fault(that is, distance protection used for feeder protection) or external fault (that is, line/transformer differential protection used for feeder protection).

In figure 36/C where one CT is available on the bus side of the feeder circuit

 breaker the primary fault between CT and CB will cause pr oblem as well.Typically such fault will be detected and tripped by feeder protection. However, tocompletely clear such fault the associated busbar section must be tripped as well. Itshall be noted that the busbar differential protection will classify such fault asexternal and without any additional measures the busbar protection will remain stable.

For better understanding end fault protection applications within busbar protection,the figure 37 is used.

BI1 BI1

QA1 QA1

ZA

QA1 QA1

BI1 BI1

xx06000139.vsd

4

3

1

2

IEC06000139 V1 EN

Figure 37: Busbar protection measuring and fault clearing boundaries 

where:1 is Busbar Protection measuring boundary determined by feeder CT locations

2 is Busbar Protection internal fault clearing boundary determined by feeder CB locations

3 is End fault region for feeders as shown in f igure 36/B

4 is End fault region for feeders as shown in f igure 36/C

In figure 37 single busbar station is shown. Two feeders on the left-hand side haveCTs on the line side of the breaker. The two feeders on the right-hand side of the

Section 3 1MRK 505 211-UEN C

IED application

102

 Application manual

Page 109: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 109/457

 busbar have CTs on the busbar side of the breaker. It is assumed that busbar  protection is connected to all four set of CTs in this station.

Due to CT location in feeder bays, busbar protection will detect all primary faults

located within measuring boundary determined by CT locations, see figure 37.However its operation will only completely clear faults within clearing boundarydetermined by CB locations as shown in figure 37. Obviously, the primary faults in-

 between these two boundaries do pose certain practical problems.

First of all it shall be noted that there is no ideal solution for faults within end zoneregion in a feeder bay when the feeder breaker is closed. Such faults, within endfault region, will be then cleared with additional time delay either by operation of local backup protection (that is, feeder circuit breaker failure protection) or byoperation of remote backup protection (that is, remote ends zone 2 distance

 protection).

However, the overall busbar protection behavior can be improved for primaryfaults within end fault regions, when feeder breaker is open. Under suchcircumstances the following actions can be taken:

• For feeders with CT on the line side of the circuit breaker (that is, two feederson the left-hand side in figure 37), the current measurement can bedisconnected from the busbar protection zone some time after feeder CBopening (for example, 400 ms for transformer and cable feeders or longestautoreclosing dead time +300 ms for overhead line feeders). At the same time,appropriately set and fast (that is, typically 40 ms time delayed) overcurrent

 protection shall be enabled to detect fault within end fault region. Any

operation of this overcurrent protection shall only issue inter-trip command tothe remote feeder end CB. Such overcurrent protection is often called end fault protection in relay literature. It shall be noted that at the same time busbar  protection will remain stable (that is, selective) for such fault.

• For feeders with CT on the bus side of the circuit breaker (that is, two feederson the right-hand side in figure 37), the current measurement can bedisconnected from the busbar protection zone some time after feeder CBopening (that is, after 400 ms). This measure will insure fast busbar protectiontripping for faults within end fault region in that feeder bay, while feeder CB isopen.

However, it shall be noted that in order to utilize end fault protection feeder circuit breaker status and its closing command must be connected to the binary inputs of  busbar protection scheme in order to be available for Zone Selection logic. Pleaserefer to Zone Selection section for more info.

End fault protection logic can be easily done with help of graphical configurationtool. One stage (that is, 4th stage) from optionally available overcurrent protectioncan be used as dedicated end fault protection for feeders with CT on the line side of the CB.

1MRK 505 211-UEN C Section 3IED application

103

 Application manual

Page 110: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 110/457

End fault protection is here explained for simple single busbar station. However thesame principles are applicable to almost all other station layouts. However, under certain circumstances, for stations with a transfer bus more extensive logic for endfault protection implementation might be required.

Zone interconnection (Load transfer)In double busbar stations or double busbar with transfer bus stations it is commonrequirement to use the possibility of zone interconnection of load current in anyfeeder bay from one busbar to the other. The sequence of operation during zoneinterconnection is normally as the following:

• bus coupler bay is closed (that is, CB and both disconnectors).• feeder bay busbar disconnector to the busbar not already in service is then

closed. The switchgear interlocking system shall allow this only when the buscoupler breaker is already closed. Depending on the thermal capacity of the

feeder busbar disconnectors (QB1 and QB2) the opening of the bus coupler circuit breaker is sometimes interlocked while both busbar disconnectorswithin one of the feeder bays are closed.

• opening of the feeder bay busbar disconnector originally closed. The load isnow transferred from one to other bus.

• opening of bus coupler CB.

The zone interconnection has to be taken into consideration for the busbar differential protection scheme, as the two busbar zones are interconnected together via two disconnectors. The primary current split between the two busbars is notknown and the two separate measuring zones cannot be maintained.

In conventional, analog busbar protection systems the solutions have been to, byextensive zone switching IEDs, disconnect one zone (normally zone B) and toconnect all feeders to other zone (normally zone A). At the same time the currentfrom the bus-coupler bay, which just circulates between two zones, must bedisconnected from the measuring differential zone.

Similar situation regarding busbar protection can occur between two single busbar sections interconnected via sectionalizing disconnector, as shown in figure 42.When sectionalizer is closed then two separate protection zones becomes one and

 busbar protection must be able to dynamically handle this.

Due to the numerical design the IED can manage this situation in an elegant andsimple way. Internal feature called ZoneInterconnection will be used to handle bothsituations. This feature can be activated either externally via binary input or derived internally by built-in logic. Internally, this “zone switching” feature will beactivated if the following conditions are met:

• bays have parameter  ZoneSel set to either CtrlInclude or CtrlExcludes

• internal zone selection logic concludes that this particular bay shall besimultaneously connected to both internal differential zones

Section 3 1MRK 505 211-UEN C

IED application

104

 Application manual

Page 111: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 111/457

This situation only means that for this particular bay both busbar disconnectors areclosed and therefore zone interconnection switching is happening in the station.

When zone switching feature is activated inside the IED, each individual bay

current will behave in the predetermined way as dictated by a parameter setting ZoneSwitching . This parameter, for every bay, can be set to only one of thefollowing three alternatives

• ForceOut 

• ForceIn

• Conditionally

If for a particular CT input setting parameter  ZoneSwitching is set to ForceOut ,then this CT input will be disconnected from both the differential zones, regardlessof any other set value or active binary input, while zone switching feature is active

within the IED. This setting is typically used for bus coupler bay in double busbar stations.

If for a particular CT input setting parameter  ZoneSwitching is set to ForceIn, thenthis CT input will be connected to both the differential zones, regardless of anyother set value or active binary input, while zone switching feature is active withinthe IED. This setting is typically used for all feeders bay in a station with twosingle zone interconnected by a sectionalizing disconnector.

If for a particular CT input setting parameter  ZoneSwitching is set to Conditionally,then this CT input will be connected to both the differential zones only if it wasincluded to any of the two zones for 2ms before the zone switching feature was

activated. This setting is typically used for all feeders bay in double busbar stations. With this setting all feeder bays, which were not connected to any of thetwo zones before the zone interconnection activation (that is, out for scheduledmaintenance), will not either be included during zone interconnection.

This practically means that for double busbar station, when zone switching featureis active, all feeder bays will be connected to both differential zones, while buscoupler CT will be disconnected from both zones. In this way simple but effectivesolution is formed. It is as well important to notice that all necessary changes in theindividual bay tripping arrangements will be automatically performed within theinternal logic.

A dedicated binary signal will be immediately activated in the internal logic whenzone interconnection feature is activated. If this feature is active longer than the pre-set time separate alarm binary signal is activated, in order to alarm the station

 personnel about such operating conditions. ZoneInterconnection feature can bedisabled by a parameter setting for substation arrangements where it is not requiredthat is, single busbar stations, one-and-half breakerbreaker-and-a-half stations andso on.

Discriminating zones (that is, Zone A and Zone B) in the IED includes a sensitiveoperational level. This sensitive operational level is designed to be able to detect

 busbar earth faults in low impedance earth power systems (that is, power systems

1MRK 505 211-UEN C Section 3IED application

105

 Application manual

Page 112: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 112/457

where the earth-fault current is limited to a certain level, typically between 300 Aand 2000 A by neutral point reactor or resistor) or for some other specialapplications where increased sensitivity is required. Operation and operatingcharacteristic of the sensitive differential protection can be set independently fromthe operating characteristic of the main differential protection. The sensitivedifferential level is blocked as soon as the total incoming current exceeds the pre-set level. By appropriate setting then it can be insured that this sensitive level is

 blocked for external phase-to-phase or three-phase faults, which can cause CTsaturation. Comparison between these two characteristics is shown in figure 38.

Differential protectionoperation characteristic

Operate

region

Diff Oper Level

   I   d   [   P  r   i  m  a  r  y   A  m  p  s   ]

Iin

[Primary Amps]

s=0.53

   I d  =   I i  n

Sensitivedifferentialprotection

en06000142.vsd

Sensitive Oper LevelSens Iin

 Block

IEC06000142 V1 EN

Figure 38: Differential protection operation characteristic 

Additionally the sensitive differential protection can be time delayed and it must beexternally enabled by a binary signal (that is, from external open delta VTovervoltage relay or power transformer neutral point overcurrent relay).

The setting parameters for the check zone are set via the local HMI or PCM600.

Such check zone is included in the IED. By a parameter setting CheckZoneSel = NotConnected /Connected can be decided, individually for every bay, if it shall be

connected to the check zone or not. This setting is available in bay function block.

For every zone there is a setting parameter CheckZoneSup, which can be set to On

or Off . This setting parameter determines if the individual zone shall be supervisedor not by a check zone. This setting is available in both Zone functions. Finally thecheck zone shall be enabled (that is, setting parameter Operation shall be set to On)in order to fully enable the check zone. Operating characteristics for the check zonecan be set independently from the two discriminating zones.

However, it is to be observed that the check zone has slightly different operatingcharacteristic from the usual discriminating zones. For the check zone the resultant

Section 3 1MRK 505 211-UEN C

IED application

106

 Application manual

Page 113: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 113/457

outgoing current is used as stabilizing current instead of total incoming current inorder to guarantee the check zone operation for all possible operating conditions inthe station. The check zone operating characteristic is shown in figure 39:

en06000062.vsd

Oper Levels=0.0-0.90 (settable)

Iout [Primary Amps]

   I   d   [   P  r   i  m  a  r  y   A  m  p  s   ]

Operate

region

IEC06000062 V1 EN

Figure 39: Check zone operation characteristic 

 Note that the check zone minimum differential operational level OperLevel shall beset equal to or less than the corresponding operating level of the usualdiscriminating zones.

For substations where traditional “CT switching” is not required (that is, single busbar station or one-and-half breaker station) the check zone must not be used.

For such applications the check zone shall be disabled by setting check zone setting parameter Operation to Off .

When CT-circuits are switched depending on the position of the busbar disconnectors there is a possibility that some of the CT secondary circuits can beopen circuited by a mistake. At the same time this can cause unwanted operation of the differential protection scheme.

For this reason, a so-called check zone is often required for a traditional high-impedance busbar protection scheme when switching in CT-circuit is done. Thecheck zone is fixed and has no switching of CTs in any of the outgoing circuits andis not connected to busbar section and busbar coupler bays. The check zone, will

detect faults anywhere in the substation but can not distinguish in which part of thestation the fault is located. When the check zone detects a fault it gives a releasesignal to the busbar protection relays in all individual, discriminating zones. The

 busbar protection discriminating zones will than trip the part of the substation thatis faulty. However, this principle creates not only a high cost as separate CT coresare required, but also a need for extra cabling and a separate check zone differentialrelay.

There is no need for an external check zone due to the following facts:

1MRK 505 211-UEN C Section 3IED application

107

 Application manual

Page 114: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 114/457

• the CT switching is made only in software, and CT secondary current circuitsdo not include any auxiliary contacts, as shown in figure 50.

• the IED is always supplied with a special zone and phase selective “Open CTDetection” algorithm, which can instantly block the differential function incase of an open CT secondary circuits caused by accidents or mistakes.

• internal check zone feature is available

This means that a very cost effective solution can be achieved using REB670, producing extra savings during scheme engineering, installation, commissioning,service and maintenance.

The pre-configured binary output contacts, are provided in the IED in order toalarm the open CT circuit condition. At the same time, one of the LEDs on thelocal HMI can be programmed to light up. It shall be noted that the Open CTCircuit alarm can only be manually reset by one of the three following ways:

1. By using the reset menu on the local HMI2. By energizing the dedicated binary input called “Reset OCT” via

communication links3. By energizing the dedicated binary input called “Reset OCT” via logic done in

the internal configuration

For more details about the working principles of the Open CT Detection algorithm,refer to Technical reference manual.

Tripping circuit arrangement

The contact outputs are of medium duty type. It is possible to use them to directlytrip the individual bay circuit breakers. This solution is suitable for all types of station arrangements. The internal zone selection logic provides individual bay tripsignals in the internal software and no external relay for this purpose are required.This arrangement insures correct trip signal distribution to all circuit breakers incase of busbar protection operation or individual bay breaker failure protectionoperation. Breaker failure protection can be internal or external to the IED.

By a parameter setting it is possible to provide self-rest or latched trip outputcontacts from the IED. However it shall be noted that the latching is electrical (thatis, if dc supply to the IED is lost the output contacts will reset).

However, sometimes due to a large number of required trip output contacts (that is,single pole operated circuit breakers and/or main and backup trip coils), a separatetrip repeat relay unit is applied for the tripping of the circuit breakers in the station.In that case the tripping arrangement can be done in different ways.

Trip arrangement with one-phase versionWhen one-phase version of the IED is used it is typically required to have threeIEDs (that is, one per phase). Thus, when busbar protection in one IED operates thetrip commands will be given to all bays but internal circuit breaker failure functionwill be started in the same phase only. In order to secure internal breaker failurestarting in all three phases it is advisable to do the following. Connect Zone A trip

Section 3 1MRK 505 211-UEN C

IED application

108

 Application manual

Page 115: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 115/457

signal from one IED to the external trip input of the Zone A in the other two IEDs.Thus all three IEDs will then issue trip in Zone A and start internally circuit

 breaker failure protection in all three phases.

 Note that:

• similar arrangements shall be done for Zone B• this have to be done between all three IEDs (that is, three times)

Such a scheme can be arranged in one of the following ways:

• by wiring between three IEDs• by using GOOSE messages when IEC 61850-8-1 is used• by using LDCM communication module.

 Note that in this case the external trip signal from other two IEDs shall be arrangedvia pulse timer in configuration in order to avoid locking of the trip signal betweenthree IED. Such arrangement via GOOSE is given in figure 40:

IED 670

IED 670

IED 670

Switch

ZoneA Trip

ZoneB Trip

Ext ZoneA Trip

Ext ZoneB Trip

Ext ZoneA Trip

Ext ZoneB Trip

50 ms

50 ms

50 ms

t

50 ms

   I   E   C

   6   1   8   5   0

   P  o  r   t

   (   O   E   M   )

   I   E   C

   6   1   8   5   0

   P  o  r   t

   (   O   E   M   )

en06000227.vsd

   S  a  m  e

   G   O   O   S   E   f  r  o  m

    I   E   D

   #   3

   t  o  w  a  r   d  s

   I   E   D

   #   1  a  n

   d   I   E   D

   #   2    S

  a  m  e

   G   O   O   S   E   f  r  o  m

    I   E   D

   #   2

   t  o  w  a  r   d  s

   I   E   D

   #   1

  a  n

   d   I   E   D

   #   3

   I   E   C

   6   1   8   5   0

   P  o  r   t

   (   O   E   M   ) GOOSE for ZoneA

GOOSE for ZoneB

IEC06000227 V1 EN

Figure 40: Principal trip arrangement via GOOSE between three one-phase 

IEDs 

Centralized trip unitTripping is performed directly from the IED contacts, which then activate anauxiliary trip unit, which multiplies the number of required trip contacts. Separate

1MRK 505 211-UEN C Section 3IED application

109

 Application manual

Page 116: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 116/457

 potential free contacts are provided for each bay and are supplied by the bayauxiliary voltage and will activate the trip coil of each bay circuit breaker atoperation. This tripping setup is suitable when no individual circuit breaker failureIEDs or lock-out of individual bay CB closing coils is required. A suitable externaltrip unit consists of a combination of RXMS1/RXMH 2 when heavy duty contactsare required and only RXMS 1 relays when medium duty contacts are sufficient.

Decentralized trip arrangementTripping is performed directly from the IED contacts, which then activatededicated auxiliary trip unit per bay. This individual auxiliary trip unit can bemounted either in the busbar protection cubicle or in the individual bay cubicles.This tripping setup is suitable when individual circuit breaker failure relays exist inall bays. A suitable external trip unit consists of a combination of RXMS1/RXMH2 when heavy duty contacts are required and only RXMS 1 relays when mediumduty contacts are sufficient.

This solution is especially suitable for the station arrangements, which require thedynamic zone selection logic (that is, so called CT switching).

Mechanical lock-out functionIt is sometimes required to use lock-out relays for busbar protection operation.

The IED has built-in feature to provide either self-reset or latched tripping in caseof busbar protection operation. Which type of trip signal each zone will issue isdetermined by a parameter setting DiffTripOut which can be set either to SelfReset 

or  Latched . When Latched is selected the trip output from the IED will only reset if:

1. Manual reset command is given to the IED2. DC power auxiliary supply to the IED is interrupted (that is, switched-off)

However, if it is required to have mechanically latched tripping and lock-out in thecircuit breaker closing circuit, then it is recommended to use one dedicated lockoutIED for each bay. Such mechanical lock-out trip IEDs are available in theCOMBIFLEX range (for example RXMVB2 or RXMVB4 bistable IEDs).

From the application point of view lock-out trip IEDs might have the followingdrawbacks:

• The trip contacts will remain closed. If the breaker would fail to open thetripping coil will be burnt and the DC supply short-circuited.

• The trip circuit supervision (TCS) IEDs will reset and give alarm for a failurein the trip circuit if the alarm is not opened by the lock-out IED or a doubletrip circuit supervision is recommended where the trip circuit is supervisedwith two alternatively, TCS IEDs.

Contact reinforcement with heavy duty relaysThere is sometimes a request for heavy duty trip relays. Normally the circuit

 breaker trip coils, with a power consumption of 200 to 300 W, are provided with anauxiliary contact opening the trip circuit immediately at breaker tripping.

Section 3 1MRK 505 211-UEN C

IED application

110

 Application manual

Page 117: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 117/457

Therefore, no heavy duty breaking capacity is required for the tripping relays. Nevertheless heavy duty trip relays are still often specified to ensure trip circuitopening also if the circuit breaker fails due to a mechanical failure or a lack of energy for operation. This can particularly occur during site testing. In this case itis recommended to use COMBIFLEX RXMH 2 or RXMVB 2 heavy duty relays.

Trip circuit supervision for busbar protectionTrip circuit supervision is mostly required to supervise the trip circuit from theindividual bay IED panel to the circuit breaker. It can be arranged also for thetripping circuits from the busbar protection.

However, it can be stated that the circuit from a busbar protection trip relay locatedin the busbar protection panel is not so essential to supervise as busbar faults arevery rare compared to faults in bays, especially on overhead power lines. Also it isnormally a small risk for faults in the tripping circuit and if there is a fault it affects

only one bay and all other bays are thus correctly tripped meaning that the faultcurrent disappears or is limited to a low value.

3.5.1.3 Different busbar arrangements

GeneralBusbar differential protection application principles for typical busbar arrangements are shown and described in this chapter.

Single busbar arrangementsThe simplest form of busbar protection is a one-zone protection for single busbar 

configuration, as shown in figure 41. When different CT ratios exist in the bayscompensation is done by setting the CT ratio individually for each bay.

The only requirement for busbar protection is that the protection scheme must haveone differential zone. For any internal fault all cir cuit breakers must be tripped,which will cause loss of supply to all loads connected to the station.

BI1 BI1 BI1 BI1

QA1 QA1 QA1 QA1

ZA

xx06000087.vsd

IEC06000087 V1 EN

Figure 41: Example of single busbar section with six feeder bays 

This type of busbar arrangement can be very easily protected. The most commonsetups for this type of station are described in the following table.

1MRK 505 211-UEN C Section 3IED application

111

 Application manual

Page 118: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 118/457

T ab le 27 : T yp ic al so lu tio ns for s in gle bu sb ar ar ran ge me nt

Version of REB670 IED Numbers of feeders per

busbar

Number of REB670

IEDs required for the

scheme

3PH; 2-zones, 4-bays BBP (A20) 4 1

3PH; 2-zones, 8-bays BBP (A31) 8 1

1Ph; 2-zones, 12-bays BBP (B20) 12 3

1Ph; 2-zones, 12-bays BBP (B21) 12 3

1Ph; 2-zones, 24-bays BBP (B31) 24 3

Please note that the above table 27 is given for the preconfigured versions of REB670 which do not contain any VT inputs.

Single busbar arrangements with sectionalizerThis arrangement is very similar to the single busbar arrangement. Thesectionalizer allows the operator to split the station into two separate buses.However, switching of the sectionalizing disconnector has to be done without anyload. This means that one of the two busbars has to be de-energized before anyopening or closing of the sectionalizer.

For this case the protection scheme must have two differential zones, which can beeither split to work independently from each other or switched to one overalldifferential zone when sectionalizing disconnector is closed. Nevertheless, whensectionalizer is closed, for internal fault on any of the two buses all feeder circuit

 breakers have to be tripped, which causes loss of supply to all loads connected to

this station.

BI1 BI1 BI1 BI1 BI1 BI1 BI1

QA1 QA1 QA1 QA1 QA1 QA1 QA1

QB1

ZA ZB

IEC11000238-1-en.vsdIEC11000238 V1 EN

Figure 42: Example of two single busbar sections with bus-sectionalizing 

disconnector and eight feeder bays per each busbar section 

The most common setups for this type of station are described in the following table.

Section 3 1MRK 505 211-UEN C

IED application

112

 Application manual

Page 119: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 119/457

Table 28: Typical so lu tions for stat ions with two s ingle busbar sect ions with bus-sectional iz ing

disconnector

Version of REB670 IED Total Number of feeders

in both busbar sections

Number of REB670

IEDs required for the

scheme3PH; 2-zones, 4-bays BBP (A20) 4 1

3PH; 2-zones, 8-bays BBP (A31) 8 1

1Ph; 2-zones, 12-bays BBP (B20) 12 3

1Ph; 2-zones, 12-bays BBP (B21) 12 3

1Ph; 2-zones, 24-bays BBP (B31) 24 3

Please note that table 28 is given for the preconfigured versions of REB670 whichdo not contain any VT inputs.

Two differential zones are available in the IED and the connecting of the two zonesis simply controlled via zone interconnection logic, as described in section "Zoneinterconnection (Load transfer)". In practice, the closed position of thesectionalizer shall start the zone interconnection logic inside the IED. All other thinks (that is, tripping) will automatically be arranged.

Single busbar arrangements with bus-section breakerThis arrangement is very similar to the single busbar arrangement. The bus-section

 breaker allows the operator to split the station into two separate buses under fullload. The requirement for busbar protection scheme is that the scheme must havetwo independent differential zones, one for each busbar section. If there is an

internal fault on one of the two sections, bus-section circuit breaker and all feeder circuit breakers associated with this section have to be tripped, leaving the other 

 busbar section in normal operation.

xx06000088.vsd

ZA ZB

BI1

QA1

BI1

QA1

BI1

QA1

BI1

QA1

BI1

QA1

BI1

QA1

QA1

BI1

IEC06000088 V1 EN

Figure 43: Example of two single busbar sections with bus-section circuit 

breaker and eight feeder bays per each busbar section 

This type of busbar arrangement can be quite easily protected. The most commonsetups for this type of station are described in the following table.

1MRK 505 211-UEN C Section 3IED application

113

 Application manual

Page 120: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 120/457

Table 29: Typical solut ions for s ingle busbar arrangements with bus-section breaker

Version of REB670 IED Total number of feeders

in both busbar sections

Number of REB670 IEDs

required for the scheme

3PH; 2-zones, 4-bays BBP (A20) 3*)/6 1/2

3PH; 2-zones, 8-bays BBP (A31) 7*)/14 1/2

1Ph; 2-zones, 12-bays BBP (B20) 11*)/22 3/6

1Ph; 2-zones, 12-bays BBP (B21) 11*)/22 3/6

1Ph; 2-zones, 24-bays BBP (B31) 23*)/46 3/6

*) with just one CT input from bus-section bay

Please note that table 29 is given for the preconfigured versions of REB670 whichdo not contain any VT inputs.

For station with just one CT in the bus-section bay, it might be required, dependingon the client requirements, to provide the special scheme for disconnection of bus-section CT when the bus-section CB is open. For more information, refer tofigure 33.

H-type busbar arrangementsThe H-type stations are often used in transmission and sub-transmission networksas load-centre substations, as shown in figure 44. These arrangements are verysimilar to the single busbar station with sectionalizer or bus-section breaker, but arecharacterized by very limited number of feeder bays connected to the station(normally only two OHL and two transformers).

Section 3 1MRK 505 211-UEN C

IED application

114

 Application manual

Page 121: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 121/457

01 02

04

BS

03

ZA ZB

xx06000121.vsd

IEC06000121 V1 EN

Figure 44: Example of H-type station 

The requirement for the busbar protection scheme for this type of station may

differ from utility to utility. It is possible to apply just one overall differential zone,which protects both busbar sections. However, at an internal fault on any of the two buses all feeder circuit breakers have to be tripped, which will cause loss of supplyto all loads connected to this station. Some utilities prefer to have two differentialzones, one for each bus section.

The most common setups for this type of station are given in the following table.

Table 30: Typical solutions for H -type stations

Version of REB670 IED Number of differential

zones/number of feeders

per zone

Number of REB670

IEDs required for the

scheme

3PH; 2-zones, 4-bays BBP (A20) 1/4 1

3PH; 2-zones, 8-bays BBP (A31) 2/3 1

1Ph; 2-zones, 12-bays BBP (B20) NA NA

1Ph; 2-zones, 12-bays BBP (B21) NA NA

1Ph; 2-zones, 24-bays BBP (B31) NA NA

Please note that table 30 is given for the preconfigured versions of REB670 whichdo not contain any VT inputs.

1MRK 505 211-UEN C Section 3IED application

115

 Application manual

Page 122: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 122/457

For station with double zone protection and just one set of CTs in the bus-section bay, it might be required, depending on the client requirements, to provide thespecial scheme for disconnection of bus-section CT when the bus-section CB isopen. For more information, refer to figure 33.

Double circuit breaker busbar arrangementThe circuit breaker, disconnectors and instrument transformers are duplicated for every feeder, as shown in figure 45.

QA1

BI1 BI2

QA2 QA1

BI1 BI2

QA2 QA1

BI1 BI2

QA2 QA1

BI1 BI2

QA2 QA1

BI1 BI2

QA2

ZA

ZB

xx06000018.vsd

IEC06000018 V1 EN

Figure 45: Example of double breaker station 

This is an extremely flexible solution. In normal service all breakers are closed.The requirement for busbar protection scheme is that the scheme must have twoindependent differential zones, one for each busbar. If there is an internal fault onone of the two buses all circuit breakers associated with the faulty busbar have to

 be tripped, but supply to any load will not be interrupted. The tripping logic for thecircuit breaker failure protection must be carefully arranged.

The most common setups for this type of busbar arrangement are described in thefollowing table.

Tab le 31 : Typ ical so lu tions fo r double c ircu it breaker busbar a rrangement

Version of REB670 IED Numbers of feeders per

station

Number of REB670

IEDs required for the

scheme

3PH; 2-zones, 4-bays BBP (A20) 4 2

3PH; 2-zones, 8-bays BBP (A31) 4/8 1/2

1Ph; 2-zones, 12-bays BBP (B20) 6/12 3/6

1Ph; 2-zones, 12-bays BBP (B21) 6/12 3/6

1Ph; 2-zones, 24-bays BBP (B31) 12/24 3/6

Please note that table 31 is given for the preconfigured versions of REB670 whichdo not contain any VT inputs.

A principle overall drawing of how to use REB670 for this type of station is givenin figure 46.

Section 3 1MRK 505 211-UEN C

IED application

116

 Application manual

Page 123: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 123/457

en06000148.vsd

Double

breaker 

REB 670

CTRLZA

CTRLZB

TRIP

CONNZA

CONNZB

Bxxx

I3PB1

BLKTR

TRZONE

TRBAY

BOM

CTRLZA

CTRLZB

TRIP

CONNZA

CONNZB

Bxxx

I3PB1

BLKTR

TRZONE

TRBAY

CT Input

TRM

QA1 Internal BFP

Backup Trip Command

BI1

1500/1

QA1

QA2

BI2

1500/1

Zone B

Other 

Equipment

Other 

Equipment

CT Input

Zone A

 A/D

 A/D

QA2 Internal BFP

Backup Trip Command

BBP &

BFP

TRIP

QA1

BBP &

BFP

TRIPQA2

OR

BFP

Remote

Feeder 

End

Inter-

Trip

   F  e  e

   d  e  r

Parameter ZoneSel must

be set to "FixedToZB"

Parameter ZoneSel must

be set to "FixedToZA"

IEC06000148 V1 EN

Figure 46: Feeder bay in double bus – double breaker station 

One-and-half circuit breakerA fewer number of circuit breakers are needed for the same flexibility as for doublecircuit breaker busbar arrangement, as shown in figure 47.

1MRK 505 211-UEN C Section 3IED application

117

 Application manual

Page 124: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 124/457

BI3

BI1

QA1

BI2

QA2

QA3

BI3

BI1

QA1

BI2

QA2

QA3

BI3

BI1

QA1

BI2

QA2

QA3

BI3

BI1

QA1

BI2

QA2

QA3

BI3

BI1

QA1

BI2

QA2

QA3

ZA

ZB

IEC11000240-1-en.vsd

IEC11000240 V1 EN

Figure 47: Example of one-and-half circuit breaker station 

All breakers are normally closed. The requirement for the busbar protectionscheme is that the scheme must have two independent differential zones, one for each busbar. In case of an internal fault on one of the two buses, all circuit breakersassociated with the faulty busbar have to be tripped, but the supply to any load willnot be interrupted. The breaker failure protection tripping logic also needs carefuldesign.

This type of busbar arrangement can be very easily protected. The most common

setups for this type of station are described in the following table.Table 32: Typical so lu tions for one-and-half ci rcui t breaker stat ions when CBF for middle

breaker is not required

Version of REB670 IED Number of diameters in

the station

Number of REB670

IEDs required for the

scheme

3PH; 2-zones, 4-bays BBP (A20) 2/4 1/2

3PH; 2-zones, 8-bays BBP (A31) 4/8 1/2

1Ph; 2-zones, 12-bays BBP (B20) 6/12 3/6

1Ph; 2-zones, 12-bays BBP (B21) 6/12 3/6

1Ph; 2-zones, 24-bays BBP (B31) 12/24 3/6

Please note that table 32 is given for the preconfigured versions of REB670 whichdo not contain any VT inputs.

A principle overall drawing of how to use REB670 for one-and-half circuit breaker station including internal CBF protection for middle breaker is given in figure 48.

Section 3 1MRK 505 211-UEN C

IED application

118

 Application manual

Page 125: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 125/457

en06000149.vsd

REB 670

OR

BFP

Remote

End

Inter-

Trip

Feeder 1

CTRLZA

CTRLZB

TRIP

CONNZA

CONNZB

Bxxx

I3PB1

BLKTR

TRZONE

TRBAY

Zone A

BBP &

BFP

TRIP

QA1

BFP

TRIP

QA2

BBP &

BFP

TRIP

QA3

BFP

Remote

End

Inter-

Trip

Feeder 2

1½ breaker 

Diameter 

CTRLZA

CTRLZB

TRIP

CONNZA

CONNZB

Bxxx

I3PB1

BLKTR

TRZONE

TRBAY

BOM

Parameter ZoneSel must

be set to "FixedToZB"

Parameter ZoneSel must

be set to "FixedToZA"

CT Input

TRM

QA1 Internal BFPBackup Trip Command

BI1

2000/1

QA1

BI2

2000/1

QA2

QA3

BI3

2000/1

Zone B

Other 

Equipment

Other 

Equipment

Other 

Equipment

CT Input

CT Input

CTRLZA

CTRLZB

TRIP

CONNZA

CONNZB

Bxxx

I3PB1

BLKTR

TRZONE

TRBAY

 A/D

 A/D

 A/D

Parameter ZoneSel must

be set to "CtrlIncludes"

and CTConnection="Off"

ZERO-

ZERO-

QA2 Internal BFP

Backup Trip Command

OR

OR

   F  e  e

   d  e  r

   1

   F  e  e

   d  e  r

   2

QA3 Internal BFP

Backup Trip Command

IEC06000149 V1 EN

Figure 48: Diameter in one-and-half breaker station with breaker failure 

protection for all three breakers inside REB670 

Double busbar single breaker arrangementThis type of arrangement is shown in figure 49.

BI1

QA1

QB1 QB2

BI1

QA1

QB1 QB2

BI1

QA1

QB1 QB2

BI1

QA1

QB1 QB2

BI1

QA1

QB1 QB2

BI1

QA1

BI1

QB1 QB2

QA1

ZA

ZB

IEC11000239-1-en.vsd

IEC11000239 V1 EN

Figure 49: Example of double busbar station 

1MRK 505 211-UEN C Section 3IED application

119

 Application manual

Page 126: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 126/457

This type of busbar arrangement is very common. It is often preferred for larger installations. It provides good balance between maintenance work requirementsand security of supply. If needed, two busbars can be split during normal service.The requirement for busbar protection scheme is that the scheme must have twoindependent differential zones, one for each busbar. In case of an internal fault onone of the two buses, bus-coupler circuit breaker and all feeder circuit breakersassociated with the faulty bus have to be tripped, leaving other busbar still innormal operation. Provision for zone selection, disconnector replica and zoneinterconnection have to be included into the scheme design.

This type of busbar arrangement can be protected as described in the following table:

Table 33: Typical solutions for double busbar stations

Version of REB670 IED Number of feeders in the

station (excluding bus-

coupler bay)

Number of

REB670 IED

required for the

scheme

3PH; 2-zones, 4-bays BBP (A20) 3*) 1

3PH; 2-zones, 8-bays BBP (A31) 7*) 1

1Ph; 2-zones, 12-bays BBP (B20) NA NA

1Ph; 2-zones, 12-bays BBP (B21) 11*) 3

1Ph; 2-zones, 24-bays BBP (B31) 23*) 3

*) with just one CT input from bus-coupler bay

Please note that table 33 is given for the preconfigured versions of REB670 which

do not contain any VT inputs.

For station with just one CT in the bus-coupler bay, it might be required, dependingon the client requirements, to provide the special scheme for disconnection of bus-coupler CT when the bus-coupler CB is open. For more info please refer to figure33.

Some principle overall drawings of how to use REB670 in this type of station aregiven in figure 50 to figure 54.

Section 3 1MRK 505 211-UEN C

IED application

120

 Application manual

Page 127: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 127/457

en06000151.vsd

Zone A

Zone B

BI1

1200/1

Feeder Bay

Other 

Equipment

REB 670

b a

 A/D

CT Input

Main

contact Aux. a

contact

 Aux. bcontact

Open

Open

Closed Open

Closed

Closed

b a

CTRLZA

CTRLZB

TRIP

CONNZA

CONNZB

Bxxx

I3PB1

BLKTR

TRZONE

TRBAY

NO

NC

CLOSED

OPEN

 ALARM

FORCED

SSxx

DISABLE

NO

NC

CLOSED

OPEN

 ALARM

FORCED

SSxx

DISABLE

BBP & BFP trip command to feeder breaker 

BIM

BOM

Set Parameter 

ZoneSel="CtrlIncludes"

TRM

External or Internal

Feeder BFP Backup TripCommand

Feeder Backup

OC Trip

Disconnector aux. contact timing

(Aux. contact a timing is only crucial when Scheme2_INX is used)

QB2

QB1

QB9

QA1

IEC06000151 V1 EN

Figure 50: Feeder bay where a&b aux. contacts are used 

1MRK 505 211-UEN C Section 3IED application

121

 Application manual

Page 128: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 128/457

en06000152.vsd

Zone A

Zone B

BI1

1200/1

REB 670

b

CT Input

 Aux. b

contactClosed Open

b

CTRLZACTRLZB

TRIP

CONNZA

CONNZB

Bxxx

I3PB1

BLKTR

TRZONE

TRBAY

BBP & BFP trip command to feeder breaker 

BIM

BOM

Main

contactOpen Closed

Set Parameter 

ZoneSel="CtrlExcludes"

Feeder Bay

Other 

Equipment

 A/D

TRM

Feeder Backup

OC Trip

Disconnector aux. contact timing

QB9

QB1

QB2

QA1

External or Internal

Feeder BFP Backup

Trip Command

IEC06000152 V1 EN

Figure 51: Feeder bay where b aux. contacts are used 

Section 3 1MRK 505 211-UEN C

IED application

122

 Application manual

Page 129: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 129/457

en06000153.vsd

BOM

QB1

Zone A

Zone B

Bus-Coupler 

Bay

REB 670

CTRLZA

CTRLZB

TRIP

CONNZA

CONNZB

Bxxx

I3PB1

BLKTR

TRZONE

TRBAY

BBP & BFP trip command to Bus-Coupler breaker 

BI1

2400/1

BI2

2400/1

CT Input

 A/D

 A/D

CTRLZA

CTRLZB

TRIP

CONNZA

CONNZB

Bxxx

I3PB1

BLKTR

TRZONE

TRBAY

Parameter ZoneSel must

be set to "FixedToZA"

OR

Other 

Equipment

Other 

Equipment

CT Input

TRM

Bus-Coupler Backup

OC Trip

QB2

QA1

External or Internal

Bus-Coupler BFP

Backup Trip Command

Parameter ZoneSel must

be set to "FixedToZB"

IEC06000153 V1 EN

Figure 52: Bus coupler bay with two sets of CTs 

1MRK 505 211-UEN C Section 3IED application

123

 Application manual

Page 130: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 130/457

en06000154.vsd

Zone A

Zone B

Bus-Coupler 

Bay

REB 670

CTRLZA

CTRLZB

TRIP

CONNZA

CONNZB

Bxxx

I3PB1

BLKTR

TRZONE

TRBAY

BBP & BFP trip command to Bus-Coupler breaker 

BOM

 A/D

Parameter ZoneSel must be

set to "FixedToZA&-ZB"

tZeroCurrent=150ms

Other 

Equipment

CT InputTRM

External or Internal

Bus-Coupler BFP

Backup Trip Command

Bus-Coupler Backup

OC Trip

QB1

QB2

b a

BI1

2400/1

QA1

NO

NC

CLOSED

OPEN

 ALARM

FORCED

SSxx

DISABLE

ZEROCUR

BIM

CB Closing

Signal

³1tt=1s

IEC06000154 V1 EN

Figure 53: Bus coupler bay with one CT and a&b aux. contact from CB 

Section 3 1MRK 505 211-UEN C

IED application

124

 Application manual

Page 131: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 131/457

en06000155.vsd

Zone A

Zone B

Bus-Coupler 

Bay

REB 670

CTRLZA

CTRLZB

TRIP

CONNZA

CONNZB

Bxxx

I3PB1

BLKTR

TRZONE

TRBAY

BBP & BFP trip command to Bus-Coupler breaker 

BOM

 A/D

Parameter ZoneSel must

be set to "FixedToZA&-ZB"

tZeroCurrent=150ms

Other 

Equipment

CT InputTRM

External or Internal

Bus-Coupler BFP

Backup Trip Command

Bus-Coupler Backup

OC Trip

QB1

QB2

b

BI1

2400/1

QA1

ZEROCUR

BIMCB Closing

Signal

³1tt=1s

&

IEC06000155 V1 EN

Figure 54: Bus coupler bay with one CT and b aux. contact only from CB 

Double busbar arrangements with two bus-section breakers and two

bus-coupler breakersThis type of station is commonly used for GIS installations. It offers highoperational flexibility. For this type of stations, two schemes similar to the double

 busbar station scheme can be used.

BI1

QA1

QB1 QB2

BI1

QA1

QB1 QB2

BI1

QA1

QB1 QB2

BI1

QA1

QB1 QB2

BI1

QA1

QB1 QB2

BI1

QA1

QB1 QB2

BI1

QA1

QB1 QB2

BI1

QA1

QB1 QB2

BI1

QA1

BI1QA1

BI1 QA1

BI1

QB1 QB2

QA1

BI1

QA1

ZA1

ZB1

ZA2

ZB2

xx06000016.vsd

IEC06000016 V1 EN

Figure 55: Example of typical GIS station layout 

With REB670 this type of arrangement can be protected as described in thefollowing table.

1MRK 505 211-UEN C Section 3IED application

125

 Application manual

Page 132: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 132/457

Table 34: Possible solutions for a typical GIS station

Version of REB670 IED Number of feeders on

each side of the station

(excluding bus-coupler &

bus-section bays)

Number of REB670

IEDs required for the

scheme

3PH; 2-zones, 4-bays BBP (A20) NA NA

3PH; 2-zones, 8-bays BBP (A31) 5*) 2

1Ph; 2-zones, 12-bays BBP (B20) NA NA

1Ph; 2-zones, 12-bays BBP (B21) 9*) 6

1Ph; 2-zones, 24-bays BBP (B31) 21*) 6

*) with just one CT input from bus-coupler bay

Please note that table 34 is given for the preconfigured versions of REB670 which

do not contain any VT inputs.

Provision for zone selection, disconnector replica and zone interconnection have to be included into the scheme design.

For station with just one CT in the bus-coupler or bus-section bays, it might berequired, depending on the client requirements, to provide the special scheme for disconnection of bus-coupler or bus-section CT when the bus-coupler or bus-section CB is open. For more info please refer to figure 33

Double busbar-single breaker with transfer bus arrangementsThis type of arrangement is shown in figure 56.

BI1

QB1 QB2 QB7

BI1

QB1 QB2 QB7

BI1

QB1 QB2 QB7

BI1

QB1 QB2 QB7

BI1

QB20QB2 QB7QB1

QA1 QA1 QA1 QA1 QA1

ZAZB

xx06000015.vsd

IEC06000015 V1 EN

Figure 56: Example of double busbar-single breaker with transfer bus 

arrangement 

This type of busbar arrangement is very common in some countries. It providesgood balance between maintenance work requirements and security of supply. If needed, two busbars can be split during normal service. Additionally any feeder CB can be taken out for maintenance without interruption of supply to the endcustomers connected to this feeder.

The requirement for busbar protection scheme is that the scheme must have twoindependent differential zones, one for each busbar. In case of an internal fault onone of the two buses, bus-coupler circuit breaker and all feeder circuit breakersassociated with the faulty bus have to be tripped, leaving other busbar still in

Section 3 1MRK 505 211-UEN C

IED application

126

 Application manual

Page 133: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 133/457

normal operation. When transfer bus is in operation it will be protected as anintegral part of one of the two internally available zones. Special attention shall begiven that appropriate logic for zone selection is done with help of graphicalconfiguration tool. At the same time, load transfer and possible transfer of tripsignals from the feeder under transfer to the transfer circuit breaker shall bearranged in appropriate way as well. This type of busbar arrangement can be

 protected as described in the following table:

Table 35: Possible solut ions for double busbar-sing le breaker with t ransfer bus arrangements

Version of REB670 IED Total number of feeder

bays in the station

(excluding buscoupler &

bus-section bays)

Number of REB670

IEDs required for the

scheme

3PH; 2-zones, 4-bays BBP (A20) NA NA

3PH; 2-zones, 8-bays BBP (A31) 7*) 1

1Ph; 2-zones, 12-bays BBP (B20) NA NA1Ph; 2-zones, 12-bays BBP (B21) 11*) 3

1Ph; 2-zones, 24-bays BBP (B31) 23*) 3

*) with one set of CTs in bus-coupler bay and separate transfer and bus-coupler breaker 

Please note that table 35 is given for the preconfigured versions of REB670 whichdo not contain any VT inputs.

 Note that for station layouts where combined transfer and bus-coupler bay is used,as for example is shown in figure 56, two internal bay function blocks must be

allocated to such primary bay, reducing number of available feeder bays. In suchstation maximum available number of feeder bays is less for one from the valuesshown in table 35, on condition that just one main CT is available from Bus-Coupler/Transfer bay. For station with just one CT in the bus-coupler bay, it might berequired, depending on the client requirements, to provide the logic scheme for disconnection of bus-coupler CT when the bus-coupler CB is open. For moreinformation, refer to figure 33.

Combined busbar arrangementsThere are stations which are practically a combination between two normal typesof station arrangements, which are already previously described. Some typical

examples will be shown here:

1MRK 505 211-UEN C Section 3IED application

127

 Application manual

Page 134: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 134/457

BI3

BI1

QA1

BI2

QA2

QA3

BI3

BI1

QA1

BI2

QA2

QA3

BI3

BI1

QA1

BI2

QA2

QA3

BI3

BI1

QA1

BI2

QA2

QA3

BI3

BI1

QA1

BI2

QA2

QA3

ZA

ZB

xx06000123.vsd

QA1

BI1 BI2

QA2

IEC06000123 V1 EN

Figure 57: Combination between one-and-half and double breaker station 

layouts 

This type of stations can be encountered very often in practice. Usually the stationis arranged in such a way that double breaker bays can be, at a later stage,transformed into one-and-half breaker setup. For busbar protection this type of station can be protected in exactly the same way as one-and-half breaker stationsdescribed above. The same type of IEDs can be used, and same limitationsregarding the number of diameters apply.

xx06000124.vsd

QA1

BI1 BI2

QA2

BI1

QA1

QB1 QB2

BI1

QA1

QB1 QB2

ZA

ZB

QA1

BI1 BI2

QA2

IEC06000124 V1 EN

Figure 58: Combination between double breaker and double busbar station 

layouts 

In this type of arrangement the double breaker bay has in the same time the role of the bus-coupler bay for normal double busbar single breaker stations. Therefore,zone interconnection, zone selection and disconnector replica facilities have to be

 provided for all double busbar bays. Because of the very specific requirements onzone interconnection feature, the following should be considered for this type of application:

Section 3 1MRK 505 211-UEN C

IED application

128

 Application manual

Page 135: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 135/457

• current inputs CT1 and CT2 shall be used for the first double breaker bay.• current inputs CT3 and CT4 shall be used for the second double breaker bay.• current inputs CT5 and CT6 shall be used for the third double breaker bay

(only available in 1ph version).

Accordingly the following solutions are possible:

Table 36: Typical solut ions for combinat ion between double breaker and double busbar

station layouts

Version of REB670 IED Number of double

breaker feeders /

Number of double

busbar feeders in the

station

Number of REB670

IEDs required for the

scheme

3PH; 2-zones, 4-bays BBP (A20) NA NA

3PH; 2-zones, 8-bays BBP (A31) 2/4 1

1Ph; 2-zones, 12-bays BBP (B20) NA NA

1Ph; 2-zones, 12-bays BBP (B21) 3/6 3

1Ph; 2-zones, 24-bays BBP (B31) 3/18 3

Please note that table 36 is given for the preconfigured versions of REB670 whichdo not contain any VT inputs.

xx06000125.vsd

BI3

BI1

QA1

BI2

QA2

QA3

BI3

BI1

QA1

BI2

QA2

QA3

BI3

BI1

QA1

BI2

QA2

QA3

BI3

BI1

QA1

BI2

QA2

QA3

BI3

BI1

QA1

BI2

QA2

QA3

ZA

ZB

BI1

QA1

QB1 QB2

BI1

QA1

QB1 QB2

IEC06000125 V1 EN

Figure 59: Combination between one-and-half breaker and double busbar 

station layouts 

For this type of busbar arrangement the double busbar bay is usually connected tothe reactive power compensation equipment (that is, shunt reactor or shuntcapacitor). The diameters in the one-and-half breaker part of the station have at the

1MRK 505 211-UEN C Section 3IED application

129

 Application manual

Page 136: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 136/457

same time the role of the bus-coupler bay. Therefore, zone interconnection, zoneselection and disconnector replica facilities have to be provided for all double

 busbar bays.

3.5.1.4 Summation principle

IntroductionA simplified bus differential protection for phase and earth faults can be obtained

 by using a single, one-phase IED with external auxiliary summation currenttransformers. By using this approach, more cost effective bus differential

 protection can be obtained. Such a solution makes it feasible to apply busdifferential protection even to medium voltage substations. The principaldifferences between full, phase-segregated bus differential protection scheme andsummation type bus differential protection scheme are shown in figure 60.

 Auxiliary Summation CT *)

type SLCE 8; 1/1A, 2/1A or 5/1A

+

Three one-phase

REB670Single one-phase

REB670

Up to 18 pcs

auxiliary CTs

*) One SLCE 8 per main CT

REB670with 1A

CT inputs

REB670

REB670

REB670

@

IEC06000126_2_en.vsd

IEC06000126 V2 EN

Figure 60: Difference between phase segregated & summation type 

differential protection 

In the full, phase-segregated design three, one-phase REB670 IEDs (that is, one per  phase) are used. However for the summation type only single, one-phase REB670IED plus one auxiliary summation CT per each main CT is required. Theseauxiliary summation CTs convert each main CT three-phase currents to a single-

 phase output current, which are all measured by one REB670 IED. The differentialcalculation is then made on a single-phase basis. By doing so, this more costeffective bus differential protection can be applied. Due to this characteristic, this

summation type of bus differential protection can be applied for all types of stations arrangements as shown section "Different busbar arrangements", for three,one-phase IEDs.

As an example, the necessary equipment for the summation type, busbar differential protection for a single busbar station with up to 24 bays, is shown infigure 61.

Section 3 1MRK 505 211-UEN C

IED application

130

 Application manual

Page 137: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 137/457

IED

with 1A

CT inputs

IB2 IX2IA2

L1 L2 L3 N

IA1 IB1 IX1

LA LB LX

 A-bus

Summation CTs

Main CTs

CT1 CT2 . . . CT24

IEC06000127_2_en.vsd

L1 L2 L3 N L1 L2 L3 N

IEC06000127 V2 EN

Figure 61: Principle CT connections for the complete station 

This summation type bus differential protection still has the same main CTrequirements as outlined in section "Rated equivalent secondary e.m.f.requirements". Some of these are:

• main CT ratio differences can be tolerated up to 10:1 (for example, 3000/5ACT can be balanced against CT"s as low as 300/5)

• different main CT ratios are compensated numerically by a parameter setting• main CT shall not saturate quicker than 2 ms ( refer to section "Ratedequivalent secondary e.m.f. requirements" for detailed CT requirementsregarding main CT knee-point voltage)

However, due to the summation principle this type of busbar protection scheme hasthe following limitations:

1MRK 505 211-UEN C Section 3IED application

131

 Application manual

Page 138: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 138/457

• Only one measuring circuit is utilized for all fault types (that is, no redundancyfor multi-phase faults)

• Primary fault sensitivity varies depending on the type of fault and involved phase(s), see table 38

• The load currents in the healthy phases might produce the stabilizing currentwhen an internal, single phase to ground fault occurs. However, there is no

 problem for solidly earthed systems with high earth-fault currents• No indication of faulty phase(s) in case of an internal fault• Not possible to fully utilize Open CT detection feature

Auxiliary summation CTsAuxiliary Summation Current Transformer (that is, ASCT in further text) of thetype SLCE 8 is used with the summation principle of the IED. The principledrawing of one such ASCT is shown in figure 62.

 Auxiliary Summation CT

type SLCE 8; X/1A

N4

S1

S2

en03000118.vsd

P1

N1

P2

P3

N2

P4

P5

N3

P6

IEC03000118 V1 EN

Figure 62: Principle ASCT drawing 

The ASCT has three primary windings and one secondary winding. In further text,turn numbers of these windings will be marked with N1, N2, N3 & N4,

respectively (see figure 62 for more information).

There are three types of ASCT for REB670:

1. ASCT type with ratio 1/1A, for balanced 3-Ph current input, shall be used withall main current transformers with 1A rated secondary current (that is, 2000/1A)

2. ASCT type with ratio 5/1A, for balanced 3-Ph current input, shall be used withall main current transformers with 5A rated secondary current (that is, 3000/5A)

3. ASCT type with ratio 2/1A, for balanced 3-Ph current input, shall be used withall main current transformers with 2A rated secondary current (that is, 1000/2A)

Section 3 1MRK 505 211-UEN C

IED application

132

 Application manual

Page 139: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 139/457

 Note the following:

• main CT rated primary current is not important for ASCT selection• possible main CT ratio differences will be compensated by a parameter setting

in the IED• rated secondary current of ASCT is 1A for all types. That means that

secondary ASCT winding should be always connected to the IED with 1A CTinputs, irrespective of the rated secondary current of the main CT

All of these features simplify the ordering of the ASCTs. Practically, in order to purchase ASCTs, the only required information is the main CT rated secondarycurrent that is, (1A, 2A or 5A).

Table 37 summarizes the ASCT data:

Table 37: Auxiliary summation CT data

Type of fault N1 N2 N3 N4 Ukp [V] Burden

[VA]

 ASCT SLCE 8;1/1A

52 52 104 90 33 1.0

 ASCT SLCE 8;5/1A

12 12 24 104 38 1.0

 ASCT SLCE 8;2/1A

26 26 52 90 33 1.0

where:

• N1, N2, N3 & N4 are ASCT windings turn numbers (see figure 62)• Ukp is knee point voltage, at 1.6T, of the secondary winding with N4 turns• Burden is the total 3Ph load of ASCT imposed to the main CT

Due to ASCT design, the ASCTs for summated bus differential protection, must always be mounted as close as possible to the IED(that is, in the same protection cubicle).

Possible ASCT connections for REB670It is possible to connect the ASCTs for summated bus differential protection withREB670:

• at the end of the main CT circuit (for example, beyond the other protectiverelays, as shown in figure 63

• in series with other secondary equipment when some other relay must belocated at the end of the main CT circuit , as shown in figure 64

1MRK 505 211-UEN C Section 3IED application

133

 Application manual

Page 140: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 140/457

End connection is the preferred arrangement as it gives greater sensitivity for summation type bus differential protection (as shown in table 38 for moreinformation).

However, it should be noted that these two connection types must not be mixed.This means that within one busbar installation all auxiliary summation CTs have to

 be either end-connected or series-connected.

Typical end-connection with ASCT is shown in figure 63.

L1

L2

L3

N

IL1

IL2

IL3

IN

Other relays

 Auxiliary Summation CT

type SLCE 8;

1/1A or 5/1A or 2/1A

N4

S1

S2

en06000128.vsd

Main CT

2000/1A or 2000/5A

or 2000/2A

 AI03

X401

5

6

REB 670 with 1A CTsP1

N1

P2

P3

N2

P4

P5

N3

P6

ISUMM

IEC06000128 V1 EN

Figure 63: End-connection with ASCT connected to CT3 inpu t 

It is important to notice that even in the case of 5A or 2A main CTs, secondarycurrent of the summation CTs shall be connected to the IED with 1A CT inputs (asshown in figure 63). The reason for this is that the rated secondary current of ASCT is always 1A irrespective of the rated secondary current of the main CT.

Refer to section "SLCE 8/ASCT characteristics for end-connection" for detailedASCT current calculations for end-connection.

Typical series-connection with ASCT is shown in figure 64.

Section 3 1MRK 505 211-UEN C

IED application

134

 Application manual

Page 141: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 141/457

Other 

relays

IL1 IL2 IL3

en06000129.vsd

IL3

 Auxiliary Summation CT

type SLCE 8; 1/1 or 5/1A or 2/1A

N4

S1

S2

 A103

X401

5

6

REB 670 with 1A CTs

L3L2L1 N

IL1

IN

IN

Main CT

2000/1A

or 2000/5A

or 2000/2A

ISUMM

Other 

relays

P1N1

P2

P3N2

P4

P5N3

P6

IEC06000129 V1 EN

Figure 64: Series-connection with ASCT connected to CT3 input 

Refer to section "SLCE 8/ASCT characteristics for series-connection"for detailedASCT current calculation for series-connection.

Main CT ratio mismatch correctionAs stated before, three types of ASCTs for REB670 are available. The first typeshall be used for main CTs with 1A rated secondary current. The second type shall

 be used for main CTs with 5A rated secondary current. The third type shall be usedwith 2A main CTs. However REB670 with 1A CT inputs is always used. Thereforemain CT ratio shall always be set in such a way that the primary current is enteredas for the main CT, but secondary current is always entered as 1A (that is, 3000/5main CT will be entered as 3000/1 CT in REB670).

Primary pick-up levels for summation type differential protection

The minimal differential operating current level is entered directly in primaryamperes. However, as stated previously, in case of the summated differential protection the primary fault sensitivity varies depending on the type of fault andinvolved phase(s). The entered value, for the minimal differential operating currentlevel, will exactly correspond to the REB670 start value in the event of a 3-phaseinternal fault. For all other fault types this value must be multiplied by a coefficientshown in the table 38 in order to calculate the actual primary start value.

1MRK 505 211-UEN C Section 3IED application

135

 Application manual

Page 142: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 142/457

Tab le 38: S ta rt coe ff ic ients for Summated D ifferen tial P ro tect ion

Type of fault L1-Gnd L2-Gnd L3-Gnd L1-L2 L2-L3 L3-L1 L1L2L3

 ASCT endconnected

0.434 0.578 0.867 1.732 1.732 0.867 1.0

 ASCT seriesconnected

1.732 0.867 0.578 1.732 1.732 0.867 1.0

The coefficients in table 38 are only relevant for ideal internalfaults (that is, load currents do not exist in the healthy phases).

Example 1:

The minimal differential operating current level in the IED is set to 1250A. All

ASCTs are series connected. What is the theoretical primary start value in case of L3-Gnd fault?

Answer 1:

According to table 38, pickup coefficient for this type of ASCT connection and thistype of fault is 0.578. Therefore:

IPickup L3 Gnd – ( ) 0.578 1250× 722.5A= =

EQUATION1106 V1 EN (Equation 30)

( ) 0.578 1250 722.5 Pickup

 I C Gnd A- = × =

EQUATION1784 V1 EN (Equation 30)

This means that if 722.5 primary amperes is injected only in phase L3 of any of theconnected main CTs, the IED shall display the differential current of 1250A(primary) and should be on the point of the start (that is, trip).

In addition to busbar protection differential zones, the IED can incorporate other additional functions and features. If and how they can be used together withsummation busbar protection design is shown in table 39:

Section 3 1MRK 505 211-UEN C

IED application

136

 Application manual

Page 143: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 143/457

Table 39: Functions

Functions Comment

Busbar Differential Protection Differential Protection, Sensitive differential protection,OCT algorithm, Check Zone and Differential Supervision

features will be connected to the summated baycurrents. Therefore, they will have different start leveldepending on the type of fault and involved phase(s).For more information, refer to table 38. However, if allthese limitations are acceptable it is still possible to useall these internal busbar protection features. Note thatOCT operating logic will not work properly in case of opening or shorting the main CT secondary leads (thatis, in-between main CT and ASCT). In case of openingor shorting the ASCT secondary leads (that is, in-between ASCT and the IED) the OCT logic will operatecorrectly.

Dynamic Zone Selection feature Zone Selection feature in the IED can be used in theexactly same way as with phase segregated design. Allbuilt-in features, even including breaker failure

protection, protection back-up trip command routing,EnFP logic can be used in the exactly same way as for phase segregated design.

CCRBRF/CCSRBRF function Breaker Fail Protection function will be connected to thesummated bay current. Therefore it will have differentstart level depending on the type of fault and involvedphase(s). See table 38 for more info. It will not bepossible to have individual starting per phase, but onlythree-phase starting can be effectively used. However, if all these limitations are acceptable it is still possible touse internal CCRBRF/CCSRBRF functions.

OC4PTOC/PHS4PTOCfunction Overcurrent Protection function will be connected to thesummated bay current. Therefore, it will have differentstart level depending on the type of fault and involved

phase(s). See table 38 for more info. Thus it will be verydifficult to insure proper start and time grading withdownstream overcurrent protection relays. Hence it willbe quite difficult to use OC4PTOC/PHS4PTOC asbackup feeder protection with summation design.

OC4PTOC/PHS4PTOC function End Fault Protection feature will be connected to thesummated bay current. Therefore it will have differentstart level depending on the type of fault and involvedphase(s). See table 38 for more info. However,OC4PTOC/PHS4PTOC do not need any start or timecoordination with any other overcurrent protection. Thusif above limitations are acceptable OC4PTOC/PHS4PTOC can be used with summation design.

DRPRDRE function Disturbance Recording feature will be connected to the

individual summated bay current. Therefore recordedcurrents will not correspond to any actual primarycurrents. However such DRPRDRE records can still beused to evaluate internal busbar protection, CCRBRF/CCSRBRF and OC4PTOC/PHS4PTOC protectionsoperation.

DRPRDRE function Event List feature in the IED can be used in the exactlythe same way as with phase segregated design.

Table continues on next page

1MRK 505 211-UEN C Section 3IED application

137

 Application manual

Page 144: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 144/457

Functions Comment

DRPRDRE function Trip Value Recording feature will be connected to theindividual summated bay current. Therefore recorded tripcurrent values will not correspond to any actual primarycurrents. However such records can still be used to

evaluate internal busbar protection, CCRBRF/CCSRBRFand OC4PTOC/PHS4PTOC protections operation.

Communication All communication features in the IED can be used in theexactly the same way as with phase segregated design

SMBRREC function Autoreclosing function in the IED can be used in theexactly same way as with phase segregated design.

SLCE 8/ASCT characteristics for end-connectionTypical ASCT end-connection is shown in figure 63. For this ASCT connectiontype, the ampere-turn balance equation has the form according to equation 31:

N4 ISUMM× N1 IL1× N2 IL1 IL2+( )× N3 IL1 IL2 IL3+ +( )×+ +=

EQUATION1107 V1 EN (Equation 31)

The relationships between number of turns for this SLCE 8, ASCT for REB670, isshown in equation 32, equation 33 and equation 34:

N1 N2 N;= =

EQUATION1108 V1 EN (Equation 32)

N3 2 N×=

EQUATION1109 V1 EN (Equation 33)

N4 k 3 N× ×=

EQUATION1110 V1 EN (Equation 34)

where:

k is a constant, which depends on the type of ASCT

(that is, k=1, for 1/1A ASCT or k=5 for 5/1A ASCT or k=2 for 2/1A ASCT)

The well-known relationship, between positive, negative and zero sequence currentcomponents and individual phase current quantities is shown in equation 35:

IL1

IL2

IL3

1 1 1

a2

a 1

a a2

1

I1

I2

I0

×=

EQUATION1111 V1 EN (Equation 35)

where:

a is complex constant (that is, a=-0.5+j0.866).

Section 3 1MRK 505 211-UEN C

IED application

138

 Application manual

Page 145: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 145/457

By including equation 32, equation 33, equation 34 and equation 35 into theequation 31 the equation for the end-connected, ASCT secondary current (that is,summated current) can be derived according to equation 36:

ISUMM1

k--- I1 e

-j30°× I2 e

 j30°× 3 3 I0× ×+ +( )×=

EQUATION1112 V1 EN (Equation 36)

From equation 36 it is obvious that the ASCT rated ratio is declared for balancedthree phase current system, when only positive sequence current component exist.For any unbalanced condition (that is, external or internal fault), both negative andzero sequence current components will give their own contribution to thesummated current.

SLCE 8/ASCT characteristics for series-connection

Typical ASCT series-connection is shown in figure 64. For this ASCT connectiontype, the ampere-turn balance equation has the form according to equation 37:

N4 ISUMM× N1 IL1 N2 –  IL3 N3 –  IL1 IL2 IL3+ +( )× × ×=

EQUATION1113 V1 EN (Equation 37)

The relationships between the number of turns for this SLCE 8 ASCT for REB670,is shown in equation 38, equation 39, equation 40:

N1 N2 N;= =

EQUATION1108 V1 EN (Equation 38)

N3 2 N×=

EQUATION1109 V1 EN (Equation 39)

N4 k 3 N× ×=

EQUATION1110 V1 EN (Equation 40)

where:

k is a constant, which depends on the type of ASCT

(that is, k=1, for 1/1A ASCT or k=5 for 5/1A ASCT or k=2 for 2/1A ASCT).

The well-known relationship, between positive, negative and zer o sequence currentcomponents and individual phase current quantities is shown in equation 41:

1MRK 505 211-UEN C Section 3IED application

139

 Application manual

Page 146: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 146/457

IL1

IL2

IL3

1 1 1

a2

a 1

a a2

1

I1

I2

I0

×=

EQUATION1111 V1 EN (Equation 41)

where:

a is complex constant (that is, a=-0.5+j0.866).

By including equation 38, equation 39, equation 40 and equation 41 into theequation 37 the equation for the series-connected, ASCT secondary current (that is,summated current) can be derived according to equation 42:

ISUMM1k--- I1 e-j30°× I2 e j30°× 2 3 I0× ×+ +( )×=

EQUATION1114 V1 EN (Equation 42)

From equation 42 it is obvious that the ASCT rated ratio is declared for balancedthree phase current system, when only positive sequence current component exist.For any unbalanced condition (that is, external or internal fault), both negative andzero sequence current components will give their own contribution to thesummated current.

3.5.1.5 Setting parameters

All general settings for Busbar differential protection are only relevant for proper event reporting via IEC 61850-8-1. They are not important for proper operation of Busbar differential protection.

 Note that all settings for busbar protection under relevant parameter setting groupare directly related to proper operation of the Busbar differential protection.

Table 40: BZNTPDIF_A G roup settings (basic)

Name Values (Range) Unit Step Default Description

Operation Off  On

- - Off Differential protection operation

DiffOperLev 1 - 99999 A 1 1000 Differential protection operation level inprimary amperes

DiffTripOut SelfResetLatched

- - SelfReset Differential protection trip output mode

tTripHold 0.000 - 60.000 s 0.001 0.200 Differential trip drop-off delay inSelfReset mode

CheckZoneSup Off  On

- - Off Check zone supervises differentialprotection operation

SlowOCTOper Off  BlockSupervise

- - Block Operation of slow open CT alarm

Table continues on next page

Section 3 1MRK 505 211-UEN C

IED application

140

 Application manual

Page 147: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 147/457

Page 148: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 148/457

Name Values (Range) Unit Step Default Description

IINL2 zeroDb 0 - 100000 - 1 500 Values less than this are forced to zeroin 0,001% of range

IINL2 L2hhLim 0.000 -

10000000000.000

- 0.001 5000.000 High High limit

IINL2 hLim 0.000 -10000000000.000

- 0.001 3000.000 High limit

IINL2 lLim 0.000 -10000000000.000

- 0.001 100.000 Low limit

IINL2 llLim 0.000 -10000000000.000

- 0.001 50.000 Low Low limit

IINL2 min 0.000 -10000000000.000

- 0.001 25.000 Minimum value

IINL2 max 0.000 -10000000000.000

- 0.001 6000.000 Maximum value

IINL2 dbType Cyclic

Dead bandInt deadband

- - Dead band Reporting type (0=cyclic, 1=db,

2=integral db)

IINL2 limHys 0.000 - 100.000 - 0.001 5.000 Hysteresis value in % of range and iscommon for all limits

IINL3 db 0 - 300 s,%,%s 1 10 Deadband value in % of range (in %s if  integral is used)

IINL3 zeroDb 0 - 100000 - 1 500 Values less than this are forced to zeroin 0,001% of range

IINL3 hhLim 0.000 -10000000000.000

- 0.001 5000.000 High High limit

IINL3 hLim 0.000 -10000000000.000

- 0.001 3000.000 High limit

IINL3 lLim 0.000 -10000000000.000

- 0.001 100.00 Low limit

IINL3 llLim 0.000 -10000000000.000

- 0.001 50.000 Low Low limit

IINL3 min 0.000 -10000000000.000

- 0.001 25.000 Minimum value

IINL3 max 0.000 -10000000000.000

- 0.001 6000.000 Maximum value

IINL3 dbType CyclicDead bandInt deadband

- - Dead band Reporting type (0=cyclic, 1=db,2=integral db)

IINL3 limHys 0.000 - 100.000 - 0.001 5.000 Hysteresis value in % of range and is

common for all limits

IDL1 db 0 - 300 s,%,%s 1 10 Deadband value in % of range (in %s if  integral is used)

IDL1 zeroDb 0 - 100000 - 1 500 Values less than this are forced to zeroin 0,001% of range

IDL1 hhLim 0.000 -10000000000.000

- 0.001 5000.000 High High limit

IDL1 hLim 0.000 -10000000000.000

- 0.001 3000.000 High limit

IDL1 lLim 0.000 -10000000000.000

- 0.001 100.000 Low limit

Table continues on next page

Section 3 1MRK 505 211-UEN C

IED application

142

 Application manual

Page 149: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 149/457

Name Values (Range) Unit Step Default Description

IDL1 llLim 0.000 -10000000000.000

- 0.001 50.000 Low Low limit

IDL1 min 0.000 -

10000000000.000

- 0.001 25.000 Minimum value

IDL1 max 0.000 -10000000000.000

- 0.001 6000.000 Maximum value

IDL1 dbType CyclicDead bandInt deadband

- - Dead band Reporting type (0=cyclic, 1=db,2=integral db)

IDL1 limHys 0.000 - 100.000 - 0.001 5.000 Hysteresis value in % of range and iscommon for all limits

IDL2 db 0 - 300 s,%,%s 1 10 Deadband value in % of range (in %s if  integral is used)

IDL2 zeroDb 0 - 100000 - 1 500 Values less than this are forced to zeroin 0,001% of range

IDL2 hhLim 0.000 -10000000000.000

- 0.001 5000.000 High High limit

IDL2 hLim 0.000 -10000000000.000

- 0.001 3000.000 High limit

IDL2 lLim 0.000 -10000000000.000

- 0.001 100.000 Low limit

IDL2 llLim 0.000 -10000000000.000

- 0.001 50.000 Low Low limit

IDL2 min 0.000 -10000000000.000

- 0.001 25.000 Minimum value

IDL2 max 0.000 -10000000000.000

- 0.001 6000.000 Maximum value

IDL2 dbType CyclicDead bandInt deadband

- - Dead band Reporting type (0=cyclic, 1=db,2=integral db)

IDL2 limHys 0.000 - 100.000 - 0.001 5.000 Hysteresis value in % of range and iscommon for all limits

IDL3 db 0 - 300 s,%,%s 1 10 Deadband value in % of range (in %s if  integral is used)

IDL3 zeroDb 0 - 100000 - 1 500 Values less than this are forced to zeroin 0,001% of range

IDL3 hhLim 0.000 -10000000000.000

- 0.001 5000.000 High High limit

IDL3 hLim 0.000 -

10000000000.000

- 0.001 3000.000 High limit

IDL3 lLim 0.000 -10000000000.000

- 0.001 100.000 Low limit

IDL3 llLim 0.000 -10000000000.000

- 0.001 50.000 Low Low limit

IDL3 min 0.000 -10000000000.000

- 0.001 25.000 Minimum value

Table continues on next page

1MRK 505 211-UEN C Section 3IED application

143

 Application manual

Page 150: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 150/457

Name Values (Range) Unit Step Default Description

IDL3 max 0.000 -10000000000.000

- 0.001 6000.000 Maximum value

IDL3 dbType Cyclic

Dead bandInt deadband

- - Dead band Reporting type (0=cyclic, 1=db,

2=integral db)

IDL3 limHys 0.000 - 100.000 - 0.001 5.000 Hysteresis value in % of range and iscommon for all limits

Table 42: BZNSPDIF_A Group settings (basic)

Name Values (Range) Unit Step Default Description

Operation Off  On

- - Off Differential protection operation

DiffOperLev 1 - 99999 A 1 1000 Differential protection operation level inprimary amperes

DiffTripOut SelfResetLatched

- - SelfReset Differential protection trip output mode

tTripHold 0.000 - 60.000 s 0.001 0.200 Differential trip drop-off delay inSelfReset mode

CheckZoneSup Off  On

- - Off Check zone supervises differentialprotection operation

SlowOCTOper Off  BlockSupervise

- - Block Operation of slow open CT alarm

FastOCTOper Off  BlockSupervise

- - Block Operation of fast open CT alarm

OCTOperLev 1 - 99999 A 1 200 Open CT operation level in primaryamperes

tSlowOCT 0.00 - 6000.00 s 0.01 20.000 Time delay for slow open CT alarm

OCTReleaseLev 1 - 99999 A 1 2500 Id level above which OCT alarmreleases in supervision mode

IdAlarmLev 1 - 99999 A 1 200 Differential current alarm level in primaryamperes

tIdAlarm 0.00 - 6000.00 s 0.01 30.000 Time delay for Differential Current AlarmLevel in sec.

IinAlarmLev 1 - 99999 A 1 3000 Incoming current alarm level in primaryamperes

SensDiffOper Off  On

- - Off Sensitive differential protection operation

SensOperLev 1 - 99999 A 1 200 Sensitive differential operation level inprimary amperes

SensIinBlock 1 - 99999 A 1 1000 Iin level above which sensitive diff.protection is blocked

tSensDiff 0.000 - 60.000 s 0.001 0.400 Time delay for sensitive differentialfunction operation

Section 3 1MRK 505 211-UEN C

IED application

144

 Application manual

Page 151: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 151/457

Table 43: BZNSPDIF_A Non group settings (basic)

Name Values (Range) Unit Step Default Description

IIN db 0 - 300 s,%,%s 1 10 Deadband value in % of range (in %s if  integral is used)

IIN zeroDb 0 - 100000 - 1 500 Values less than this are forced to zeroin 0,001% of range

IIN hhLim 0.000 -10000000000.000

- 0.001 5000.000 High High limit

IIN hLim 0.000 -10000000000.000

- 0.001 3000.000 High limit

IIN lLim 0.000 -10000000000.000

- 0.001 100.000 Low limit

IIN llLim 0.000 -10000000000.000

- 0.001 50.000 Low Low limit

IIN min 0.000 -10000000000.000

- 0.001 25.000 Minimum value

IIN max 0.000 -10000000000.000

- 0.001 6000.000 Maximum value

IIN dbType CyclicDead bandInt deadband

- - Dead band Reporting type (0=cyclic, 1=db,2=integral db)

IIN limHys 0.000 - 100.000 - 0.001 5.000 Hysteresis value in % of range and iscommon for all limits

ID db 0 - 300 s,%,%s 1 10 Deadband value in % of range (in %s if  integral is used)

ID zeroDb 0 - 100000 - 1 500 Values less than this are forced to zeroin 0,001% of range

ID hhLim 0.000 -10000000000.000

- 0.001 5000.000 High High limit

ID hLim 0.000 -10000000000.000

- 0.001 3000.000 High limit

ID lLim 0.000 -10000000000.000

- 0.001 100.000 Low limit

ID llLim 0.000 -10000000000.000

- 0.001 50.000 Low Low limit

ID min 0.000 -10000000000.000

- 0.001 25.000 Minimum value

ID max 0.000 -10000000000.000

- 0.001 6000.000 Maximum value

ID dbType CyclicDead bandInt deadband

- - Dead band Reporting type (0=cyclic, 1=db,2=integral db)

ID limHys 0.000 - 100.000 - 0.001 5.000 Hysteresis value in % of range and iscommon for all limits

1MRK 505 211-UEN C Section 3IED application

145

 Application manual

Page 152: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 152/457

Table 44: BCZTPDIF Group settings (basic)

Name Values (Range) Unit Step Default Description

Operation Off  On

- - Off Check zone operation

OperLevel 1 - 99999 A 1 1000 Check zone operation level in primaryamperes

Slope 0.00 - 0.90 - 0.01 0.15 Check zone slope

Table 45: BCZSPDIF Group settings (basic)

Name Values (Range) Unit Step Default Description

Operation Off  On

- - Off Check zone operation

OperLevel 0 - 99999 A 1 1000 Check zone operation level in primaryamperes

Slope 0.00 - 0.90 - 0.01 0.15 Check zone slope

Table 46: SWSGGIO Group settings (basic)

Name Values (Range) Unit Step Default Description

OperMode Off  Scheme1_RADSSScheme2_INXForceOpenForceClosed

- - Off Switch operating mode (Scheme 1,Scheme 2 or forced)

tAlarm 0.00 - 6000.00 s 0.01 15.00 Alarm time delay for abnormal aux.contact status

Table 47: SW SGGIO Non group settings (basic)

Name Values (Range) Unit Step Default Description

SwitchName 0 - 13 - 1 Switch# User defined name for switch

Table 48: BUTPTRC_B1 Group settings (basic)

Name Values (Range) Unit Step Default Description

CTConnection Conn Inverted

NotConnectedConnected

- - Connected Hardware CT input connection to the bay

function block

ZoneSel FixedToZAFixedToZBFixedToZA&-ZBCtrlIncludesCtrlExcludes

- - CtrlIncludes How bay/CT is controlled toward thezones

ZoneSwitching ForceOutForceInConditionally

- - ForceIn Bay/CT status during zone switching

CheckZoneSel NotConnectedConnected

- - NotConnected Bay/CT status for the check zone

Table continues on next page

Section 3 1MRK 505 211-UEN C

IED application

146

 Application manual

Page 153: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 153/457

Name Values (Range) Unit Step Default Description

tTripPulse 0.000 - 60.000 s 0.001 0.200 Bay trip pulse duration if zone trips inSelfReset mode

tZeroCurrent 0.000 - 60.000 s 0.001 0.200 Time delay to force current to zero via

binary signal

tInvertCurrent 0.000 - 60.000 s 0.001 0.200 Time delay to invert current via binarysignal

Table 49: BUTPTRC_B1 Non group settings (basic)

Name Values (Range) Unit Step Default Description

BAY01 0 - 13 - 1 BayName01 User defined name for bay

Table 50: BUSPTRC_B1 Group settings (basic)

Name Values (Range) Unit Step Default Description

CTConnection Conn InvertedNotConnectedConnected

- - Connected Hardware CT input connection to the bayfunction block

ZoneSel FixedToZAFixedToZBFixedToZA&-ZBCtrlIncludesCtrlExcludes

- - CtrlIncludes How bay/CT is controlled toward thezones

ZoneSwitching ForceOutForceInConditionally

- - ForceIn Bay/CT status during zone switching

CheckZoneSel NotConnectedConnected

- - NotConnected Bay/CT status for the check zone

tTripPulse 0.000 - 60.000 s 0.001 0.200 Bay trip pulse duration if zone trips inSelfReset mode

tZeroCurrent 0.000 - 60.000 s 0.001 0.200 Time delay to force current to zero viabinary signal

tInvertCurrent 0.000 - 60.000 s 0.001 0.200 Time delay to invert current via binarysignal

Table 51: BUSPTRC_B1 Non group settings (basic)

Name Values (Range) Unit Step Default Description

BAY01 0 - 13 - 1 BayName01 User defined name for bay

Table 52: BZITGGIO Group settings (basic)

Name Values (Range) Unit Step Default Description

Operation Off  On

- - Off Load Transfer/Zone Interconnectionoperation

tAlarm 0.00 - 6000.00 s 0.01 300.00 Time delayed alarm for too long LoadTransfer/Zone Intercon

1MRK 505 211-UEN C Section 3IED application

147

 Application manual

Page 154: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 154/457

Table 53: BZISGGIO Group settings (basic)

Name Values (Range) Unit Step Default Description

Operation Off  On

- - Off Load Transfer/Zone Interconnectionoperation

tAlarm 0.00 - 6000.00 s 0.01 300.00 Time delayed alarm for too long LoadTransfer/Zone Intercon.

3.6 Current protection

3.6.1 Four step phase overcurrent protection OC4PTOC

Function description IEC 61850

identification

IEC 60617

identification

ANSI/IEEE C37.2

device numberFour step phase overcurrent protection OC4PTOC

4

4alt

3I>

TOC-REVA V1 EN

51/67

3.6.1.1 Application

The Four step phase overcurrent protection 3-phase output OC4PTOC is used inseveral applications in the power system. Some applications are:

• Short circuit protection of feeders in distribution and subtransmission systems. Normally these feeders have radial structure.

• Back-up short circuit protection of transmission lines.• Back-up short circuit protection of power transformers.• Short circuit protection of different kinds of equipment connected to the power 

system such as; shunt capacitor banks, shunt reactors, motors and others.• Back-up short circuit protection of power generators.

If VT inputs are not available or not connected, setting parameter  DirModex ( x = step 1, 2, 3 or 4) shall be left to default value Non-

directional .

In many applications several steps with different current pick up levels and timedelays are needed. OC4PTOC can have up to four different, individual settable,steps. The flexibility of each step of OC4PTOC is great. The following options are

 possible:

 Non-directional / Directional function: In most applications the non-directionalfunctionality is used. This is mostly the case when no fault current can be fed fromthe protected object itself. In order to achieve both selectivity and fast faultclearance, the directional function can be necessary.

Section 3 1MRK 505 211-UEN C

IED application

148

 Application manual

Page 155: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 155/457

Choice of delay time characteristics: There are several types of delay timecharacteristics available such as definite time delay and different types of inversetime delay characteristics. The selectivity between different overcurrent protectionsis normally enabled by co-ordination between the function time delays of thedifferent protections. To enable optimal co-ordination between all overcurrent

 protections, they should have the same time delay characteristic. Therefore a widerange of standardized inverse time characteristics are available: IEC and ANSI. Itis also possible to tailor make the inverse time characteristic.

 Normally it is required that the phase overcurrent protection shall reset as fast as possible when the current level gets lower than the operation level. In some casessome sort of delayed reset is required. Therefore different kinds of resetcharacteristics can be used.

For some protection applications there can be a need to change the current pick-up

level for some time. A typical case is when the protection will measure the currentto a large motor. At the start up sequence of a motor the start current can besignificantly larger than the rated current of the motor. Therefore there is a

 possibility to give a setting of a multiplication factor to the current pick-up level.This multiplication factor is activated from a binary input signal to the function.

Power transformers can have a large inrush current, when being energized. This phenomenon is due to saturation of the transformer magnetic core during parts of the period. There is a risk that inrush current will reach levels above the pick-upcurrent of the phase overcurrent protection. The inrush current has a large 2ndharmonic content. This can be used to avoid unwanted operation of the protection.Therefore, OC4PTOC have a possibility of 2nd harmonic restrain if the level of 

this harmonic current reaches a value above a set percentage of the fundamentalcurrent.

The phase overcurrent protection is often used as protection for two and three phase short circuits. In some cases it is not wanted to detect single-phase earthfaults by the phase overcurrent protection. This fault type is detected and clearedafter operation of earth fault protection. Therefore it is possible to make a choicehow many phases, at minimum, that have to have current above the pick-up level,to enable operation. If set 1 of 3 it is sufficient to have high current in one phaseonly. If set 2 of 3 or 3 of 3 single-phase earth faults are not detected.

3.6.1.2 Setting guidelines

When inverse time overcurrent characteristic is selected, theoperate time of the stage will be the sum of the inverse time delayand the set definite time delay. Thus, if only the inverse time delayis required, it is of utmost importance to set the definite time delayfor that stage to zero.

The parameters for Four step phase overcurrent protection 3-phase outputOC4PTOC are set via the local HMI or PCM600.

1MRK 505 211-UEN C Section 3IED application

149

 Application manual

Page 156: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 156/457

The following settings can be done for OC4PTOC.

 MeasType: Selection of discrete Fourier filtered ( DFT ) or true RMS filtered ( RMS )signals. RMS is used when the harmonic contents are to be considered, for example

in applications with shunt capacitors.

Operation: The protection can be set to Off or On

 IBase: Base current in primary A. This current is used as reference for currentsetting. It can be suitable to set this parameter to the rated primary current of thecurrent of the protected object.

UBase: Base voltage level in kV. This voltage is give as a phase-to-phase voltageand this is the reference for voltage related settings of the function. Normally thesetting should be chosen to the rated phase-to-phase voltage of the voltagetransformer feeding the protection IED.

 AngleRCA: Protection characteristic angle set in degrees. If the angle of the faultloop current has the angle RCA the direction to fault is forward.

 AngleROA: Angle value, given in degrees, to define the angle sector of thedirectional function, see figure 65.

 IminOpPhSel : Minimum current for phase selection set in % of  IBase. This settingshould be less than the lowest step setting. Default setting is 7%.

StartPhSel : Number of phases, with high current, required for operation. Thesetting possibilities are: Not used ,1 out of 3, 2 out of 3 and 3 out of 3. Default

setting is 1 out of 3.2ndHarmStab: Operate level of 2nd harmonic current restrain set in % of thefundamental current. The setting range is 5 - 100% in steps of 1%. Default settingis 20%.

Section 3 1MRK 505 211-UEN C

IED application

150

 Application manual

Page 157: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 157/457

Uref 

Idir 

IEC09000636_1_vsd

1

2

2

3

4

IEC09000636 V1 EN

Figure 65: Directional function characteristic 

1. RCA = Relay characteristic angle2. ROA = Relay operating angle3. Reverse4. Forward

Settings for each step

 x means step 1, 2, 3 and 4.

 DirModex: The directional mode of step x. Possible settings are Off / Non-

directional / Forward / Reverse.

Characteristx: Selection of time characteristic for step x. Definite time delay anddifferent types of inverse time characteristics are available according to table 54.

1MRK 505 211-UEN C Section 3IED application

151

 Application manual

Page 158: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 158/457

Table 54: Inverse time characteristics

Curve name

 ANSI Extremely Inverse

 ANSI Very Inverse ANSI Normal Inverse

 ANSI Moderately Inverse

 ANSI/IEEE Definite time

 ANSI Long Time Extremely Inverse

 ANSI Long Time Very Inverse

 ANSI Long Time Inverse

IEC Normal Inverse

IEC Very Inverse

IEC Inverse

IEC Extremely Inverse

IEC Short Time Inverse

IEC Long Time Inverse

IEC Definite Time

User Programmable

 ASEA RI

RXIDG (logarithmic)

The different characteristics are described in Technical reference manual. Ix>: Operate phase current level for step x given in % of  IBase.

tx: Definite time delay for step x. Used if definite time characteristic is chosen.

kx: Time multiplier for inverse time delay for step x.

 IMinx: Minimum operate current for step x in % of  IBase. Set IMinx below Ix> for every step to achieve ANSI reset characteristic according to standard. If  IMinx isset above Ix> for any step the ANSI reset works as if current is zero when currentdrops below IMinx.

 IxMult : Multiplier for scaling of the current setting value. If a binary input signal(enableMultiplier) is activated the current operation level is increase by this settingconstant. Setting range: 1.0-10.0

txMin: Minimum operate time for all inverse time characteristics. At high currentsthe inverse time characteristic might give a very short operation time. By settingthis parameter the operation time of the step can never be shorter than the setting.Setting range: 0.000 - 60.000s in steps of 0.001s.

Section 3 1MRK 505 211-UEN C

IED application

152

 Application manual

Page 159: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 159/457

Current

Operatetime

IMinx 

txMin

IEC10000058-1-en.vsd

IEC10000058 V1 EN

Figure 66: Minimum operate current and operation time for inverse time 

characteristics 

In order to fully comply with curves definition setting parameter txMin shall be setto the value, which is equal to the operating time of the selected inverse curve for measured current of twenty times the set current pickup value. Note that theoperating time value is dependent on the selected setting value for time multiplier kx.

 ResetTypeCrvx: The reset of the delay timer can be made in different ways. Bychoosing setting the possibilities are according to table 55.

Table 55: Reset possibilities

Curve name Curve index no.Instantaneous 1

IEC Reset (constant time) 2

 ANSI Reset (inverse time) 3

The delay characteristics are described in the technical reference manual. There aresome restrictions regarding the choice of reset delay.

For the definite time delay characteristics the possible delay time settings areinstantaneous (1) and IEC (2 = set constant time reset).

1MRK 505 211-UEN C Section 3IED application

153

 Application manual

Page 160: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 160/457

For ANSI inverse time characteristics all three types of reset time characteristicsare available; instantaneous (1), IEC (2 = set constant time reset) and ANSI (3 =current dependent reset time).

For IEC inverse time characteristics the possible delay time settings areinstantaneous (1) and IEC (2 = set constant time reset).

For the customer tailor made inverse time delay characteristics (type 17) all threetypes of reset time characteristics are available; instantaneous (1), IEC (2 = setconstant time reset) and ANSI (3 = current dependent reset time). If the currentdependent type is used settings pr, tr and cr must be given.

 HarmRestrainx: Enable block of step x from the harmonic restrain function (2ndharmonic). This function should be used when there is a risk if power transformer inrush currents might cause unwanted trip. Can be set Off /On.

tPCrvx, tACrvx, tBCrvx, tCCrvx: Parameters for customer creation of inverse timecharacteristic curve (Curve type = 17). See equation 43 for the time characteristicequation.

[ ]

>

 p

 At s B IxMult  

iC 

in

= + ×

-

æ öç ÷ç ÷ç ÷æ öç ÷ç ÷è øè ø

EQUATION1261 V2 EN (Equation 43)

For more information, refer to the technical reference manual.

tPRCrvx, tTRCrvx, tCRCrvx: Parameters for customer creation of inverse reset timecharacteristic curve (Reset Curve type = 3). Further description can be found in thetechnical reference manual.

3.6.1.3 Setting parameters

Table 56: OC4PTOC Group settings (basic)

Name Values (Range) Unit Step Default Description

Operation Off  

On

- - Off Operation Off / On

IBase 1 - 99999 A 1 3000 Base current

UBase 0.05 - 2000.00 kV 0.05 400.00 Base voltage

 AngleRCA 40 - 65 Deg 1 55 Relay characteristic angle (RCA)

 AngleROA 40 - 89 Deg 1 80 Relay operation angle (ROA)

StartPhSel 1 out of 32 out of 33 out of 3

- - 1 out of 3 Number of phases required for op (1 of  3, 2 of 3, 3 of 3)

Table continues on next page

Section 3 1MRK 505 211-UEN C

IED application

154

 Application manual

Page 161: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 161/457

Name Values (Range) Unit Step Default Description

DirMode1 Off  Non-directionalForwardReverse

- - Non-directional Directional mode of step 1 (off, nodir,forward, reverse)

Characterist1 ANSI Ext. inv. ANSI Very inv. ANSI Norm. inv. ANSI Mod. inv. ANSI Def. TimeL.T.E. inv.L.T.V. inv.L.T. inv.IEC Norm. inv.IEC Very inv.IEC inv.IEC Ext. inv.IEC S.T. inv.IEC L.T. inv.IEC Def. TimeReservedProgrammableRI typeRD type

- - ANSI Def. Time Selection of time delay curve type for  step 1

I1> 1 - 2500 %IB 1 1000 Phase current operate level for step1 in% of IBase

t1 0.000 - 60.000 s 0.001 0.000 Definitive time delay of step 1

k1 0.05 - 999.00 - 0.01 0.05 Time multiplier for the inverse time delayfor step 1

IMin1 1 - 10000 %IB 1 100 Minimum operate current for step1 in %of IBase

t1Min 0.000 - 60.000 s 0.001 0.000 Minimum operate time for inverse curves

for step 1

I1Mult 1.0 - 10.0 - 0.1 2.0 Multiplier for current operate level for  step 1

DirMode2 Off  Non-directionalForwardReverse

- - Non-directional Directional mode of step 2 (off, nodir,forward, reverse)

Characterist2 ANSI Ext. inv. ANSI Very inv. ANSI Norm. inv. ANSI Mod. inv. ANSI Def. TimeL.T.E. inv.L.T.V. inv.L.T. inv.IEC Norm. inv.IEC Very inv.IEC inv.IEC Ext. inv.IEC S.T. inv.IEC L.T. inv.IEC Def. TimeReservedProgrammableRI typeRD type

- - ANSI Def. Time Selection of time delay curve type for  step 2

Table continues on next page

1MRK 505 211-UEN C Section 3IED application

155

 Application manual

Page 162: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 162/457

Name Values (Range) Unit Step Default Description

I2> 1 - 2500 %IB 1 500 Phase current operate level for step2 in% of IBase

t2 0.000 - 60.000 s 0.001 0.400 Definitive time delay of step 2

k2 0.05 - 999.00 - 0.01 0.05 Time multiplier for the inverse time delayfor step 2

IMin2 1 - 10000 %IB 1 50 Minimum operate current for step2 in %of IBase

t2Min 0.000 - 60.000 s 0.001 0.000 Minimum operate time for inverse curvesfor step 2

I2Mult 1.0 - 10.0 - 0.1 2.0 Multiplier for current operate level for  step 2

DirMode3 Off  Non-directionalForwardReverse

- - Non-directional Directional mode of step 3 (off, nodir,forward, reverse)

Characterist3 ANSI Ext. inv. ANSI Very inv. ANSI Norm. inv. ANSI Mod. inv. ANSI Def. TimeL.T.E. inv.L.T.V. inv.L.T. inv.IEC Norm. inv.IEC Very inv.IEC inv.IEC Ext. inv.IEC S.T. inv.IEC L.T. inv.IEC Def. Time

ReservedProgrammableRI typeRD type

- - ANSI Def. Time Selection of time delay curve type for  step 3

I3> 1 - 2500 %IB 1 250 Phase current operate level for step3 in% of IBase

t3 0.000 - 60.000 s 0.001 0.800 Definitive time delay of step 3

k3 0.05 - 999.00 - 0.01 0.05 Time multiplier for the inverse time delayfor step 3

IMin3 1 - 10000 %IB 1 33 Minimum operate current for step3 in %of IBase

t3Min 0.000 - 60.000 s 0.001 0.000 Minimum operate time for inverse curvesfor step 3

I3Mult 1.0 - 10.0 - 0.1 2.0 Multiplier for current operate level for  step 3

DirMode4 Off  Non-directionalForwardReverse

- - Non-directional Directional mode of step 4 (off, nodir,forward, reverse)

Table continues on next page

Section 3 1MRK 505 211-UEN C

IED application

156

 Application manual

Page 163: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 163/457

Name Values (Range) Unit Step Default Description

Characterist4 ANSI Ext. inv. ANSI Very inv. ANSI Norm. inv. ANSI Def. Time

L.T.E. inv.L.T.V. inv.L.T. inv.IEC Norm. inv.IEC Very inv.IEC inv.IEC Ext. inv.IEC S.T. inv.IEC L.T. inv.IEC Def. TimeReservedProgrammableRI typeRD type

- - ANSI Def. Time Selection of time delay curve type for  step 4

I4> 1 - 2500 %IB 1 175 Phase current operate level for step4 in% of IBase

t4 0.000 - 60.000 s 0.001 2.000 Definitive time delay of step 4

k4 0.05 - 999.00 - 0.01 0.05 Time multiplier for the inverse time delayfor step 4

IMin4 1 - 10000 %IB 1 17 Minimum operate current for step4 in %of IBase

t4Min 0.000 - 60.000 s 0.001 0.000 Minimum operate time for inverse curvesfor step 4

I4Mult 1.0 - 10.0 - 0.1 2.0 Multiplier for current operate level for  step 4

Table 57: OC4PTOC Group settings (advanced)

Name Values (Range) Unit Step Default Description

IMinOpPhSel 1 - 100 %IB 1 7 Minimum current for phase selection in% of IBase

2ndHarmStab 5 - 100 %IB 1 20 Operate level of 2nd harm restrain op in% of Fundamental

ResetTypeCrv1 InstantaneousIEC Reset

 ANSI reset

- - Instantaneous Selection of reset curve type for step 1

tReset1 0.000 - 60.000 s 0.001 0.020 Reset time delay used in IEC DefiniteTime curve step 1

tPCrv1 0.005 - 3.000 - 0.001 1.000 Parameter P for customer programmablecurve for step 1

tACrv1 0.005 - 200.000 - 0.001 13.500 Parameter A for customer programmablecurve for step 1

tBCrv1 0.00 - 20.00 - 0.01 0.00 Parameter B for customer programmablecurve for step 1

tCCrv1 0.1 - 10.0 - 0.1 1.0 Parameter C for customer  programmable curve for step 1

tPRCrv1 0.005 - 3.000 - 0.001 0.500 Parameter PR for customer  programmable curve for step 1

Table continues on next page

1MRK 505 211-UEN C Section 3IED application

157

 Application manual

Page 164: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 164/457

Name Values (Range) Unit Step Default Description

tTRCrv1 0.005 - 100.000 - 0.001 13.500 Parameter TR for customer  programmable curve for step 1

tCRCrv1 0.1 - 10.0 - 0.1 1.0 Parameter CR for customer  

programmable curve for step 1

HarmRestrain1 Off  On

- - Off Enable block of step 1 from harmonicrestrain

ResetTypeCrv2 InstantaneousIEC Reset

 ANSI reset

- - Instantaneous Selection of reset curve type for step 2

tReset2 0.000 - 60.000 s 0.001 0.020 Reset time delay used in IEC DefiniteTime curve step 2

tPCrv2 0.005 - 3.000 - 0.001 1.000 Parameter P for customer programmablecurve for step 2

tACrv2 0.005 - 200.000 - 0.001 13.500 Parameter A for customer programmablecurve for step 2

tBCrv2 0.00 - 20.00 - 0.01 0.00 Parameter B for customer programmablecurve for step 2

tCCrv2 0.1 - 10.0 - 0.1 1.0 Parameter C for customer  programmable curve for step 2

tPRCrv2 0.005 - 3.000 - 0.001 0.500 Parameter PR for customer  programmable curve for step 2

tTRCrv2 0.005 - 100.000 - 0.001 13.500 Parameter TR for customer  programmable curve for step 2

tCRCrv2 0.1 - 10.0 - 0.1 1.0 Parameter CR for customer  programmable curve for step 2

HarmRestrain2 Off  On

- - Off Enable block of step 2 from harmonicrestrain

ResetTypeCrv3 InstantaneousIEC Reset

 ANSI reset

- - Instantaneous Selection of reset curve type for step 3

tReset3 0.000 - 60.000 s 0.001 0.020 Reset time delay used in IEC DefiniteTime curve step 3

tPCrv3 0.005 - 3.000 - 0.001 1.000 Parameter P for customer programmablecurve for step 3

tACrv3 0.005 - 200.000 - 0.001 13.500 Parameter A for customer programmablecurve for step 3

tBCrv3 0.00 - 20.00 - 0.01 0.00 Parameter B for customer programmablecurve for step 3

tCCrv3 0.1 - 10.0 - 0.1 1.0 Parameter C for customer  

programmable curve for step 3

tPRCrv3 0.005 - 3.000 - 0.001 0.500 Parameter PR for customer  programmable curve for step 3

tTRCrv3 0.005 - 100.000 - 0.001 13.500 Parameter TR for customer  programmable curve for step 3

tCRCrv3 0.1 - 10.0 - 0.1 1.0 Parameter CR for customer  programmable curve for step 3

HarmRestrain3 Off  On

- - Off Enable block of step3 from harmonicrestrain

Table continues on next page

Section 3 1MRK 505 211-UEN C

IED application

158

 Application manual

Page 165: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 165/457

Name Values (Range) Unit Step Default Description

ResetTypeCrv4 InstantaneousIEC Reset

 ANSI reset

- - Instantaneous Selection of reset curve type for step 4

tReset4 0.000 - 60.000 s 0.001 0.020 Reset time delay used in IEC DefiniteTime curve step 4

tPCrv4 0.005 - 3.000 - 0.001 1.000 Parameter P for customer programmablecurve for step 4

tACrv4 0.005 - 200.000 - 0.001 13.500 Parameter A for customer programmablecurve for step 4

tBCrv4 0.00 - 20.00 - 0.01 0.00 Parameter B for customer programmablecurve for step 4

tCCrv4 0.1 - 10.0 - 0.1 1.0 Parameter C for customer  programmable curve for step 4

tPRCrv4 0.005 - 3.000 - 0.001 0.500 Parameter PR for customer  programmable curve for step 4

tTRCrv4 0.005 - 100.000 - 0.001 13.500 Parameter TR for customer  programmable curve for step 4

tCRCrv4 0.1 - 10.0 - 0.1 1.0 Parameter CR for customer  programmable curve for step 4

HarmRestrain4 Off  On

- - Off Enable block of step 4 from harmonicrestrain

Table 58: OC4PTOC Non group settings (basic)

Name Values (Range) Unit Step Default Description

MeasType DFTRMS

- - DFT Selection between DFT and RMSmeasurement

3.6.2 Four step single phase overcurrent protection PH4SPTOC

Function description IEC 61850

identification

IEC 60617

identification

ANSI/IEEE C37.2

device number

Four step single phase overcurrentprotection

PH4SPTOC

4

4alt

I>

OC V1 EN

51

3.6.2.1 Application

The Four step single phase overcurrent protection(PH4SPTOC) function is used inseveral applications in the power system. Some applications are:

1MRK 505 211-UEN C Section 3IED application

159

 Application manual

Page 166: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 166/457

• Short circuit protection of feeders in distribution and subtransmission systems. Normally these feeders have radial structure.

• Back-up short circuit protection of transmission lines.• Back-up short circuit protection of power transformers• Short circuit protection of different kinds of equipment connected to the power 

system such as; shunt capacitor banks, shunt reactors, motors and others.• Back-up short circuit protection of power generators.

The single phase overcurrent protection is used in IEDs having only input from one phase, for example busbar protection for large busbars (with many bays).

In many applications several steps with different current pick up levels and timedelays are needed. PH4SPTOCcan have up to four different, individual settable,steps. The flexibility of each step of PH4SPTOC function is great. The followingoptions are possible:

Choice of delay time characteristics: There are several types of time delaycharacteristics available such as definite time delay and different types of inversetime delay characteristics. The selectivity between different overcurrent protectionsis normally enabled by co-ordination between the function time delays of thedifferent protections. To enable optimal co-ordination all overcurrent IEDs, to be co-ordinated against each other, should have the same time delay characteristic.Therefore a wide range of standardised inverse time characteristics are available:IEC and ANSI. It is also possible to programme a user defined inverse timecharacteristic.

 Normally it is required that the phase overcurrent function shall reset as fast as possible when the current level gets lower than the operation level. In some casessome sort of time delayed reset is required. Therefore three different kinds of resettime characteristics can be used.

For some protection applications there can be a need to change the current pick-uplevel for some time. A typical case is when the protection will measure the currentto a large motor. At the start up sequence of a motor the start current can besignificantly larger then the rated current of the motor. Therefore there is a

 possibility to give a setting of a multiplication factor to the current pick-up level.This multiplication factor is activated from a binary input signal to the function.

Power transformers can have a large inrush current, when being energized. This phenomenon is due to saturation of the transformer magnetic core during parts of the period. There is a risk that inrush current will reach levels above the pick-upcurrent of the phase overcurrent protection. The inrush current has a large secondharmonic content. This can be used to avoid unwanted operation of the protection.Therefore the Four step phase overcurrent protection (OC4PTOC) function have a

 possibility of second harmonic restrain if the level of this harmonic current reachesa value above a set percentage of the fundamental current.

Section 3 1MRK 505 211-UEN C

IED application

160

 Application manual

Page 167: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 167/457

3.6.2.2 Setting guidelines

The parameters for the four step phase overcurrent protection function (OC) are setvia the local HMI or Protection and Control IED Manager (PCM 600).

The following settings can be done for the four step phase overcurrent protection.

Operation: Off/On

 IBase: Base current in primary A. This current is used as reference for currentsetting. It can be suitable to set this parameter to the rated primary current of the

 protected object.

2ndHarmStab: Operate level of 2nd harmonic current restrain set in % of thefundamental current. The setting range is 5-100% I steps of 1%. Default setting is20%.

 HarmRestrainx: Disabled/Enabled , enables blocking from harmonic restrain.

Settings for each step (x = 1-4)Characteristx: Selection of time delay characteristic for step x. Definite time delayand different types of inverse time delay characteristics are available according totable 59.

Table 59: Inverse tim e delay characteristics

Curve name

 ANSI Extremely Inverse

 ANSI Very Inverse ANSI Normal Inverse

 ANSI Moderately Inverse

 ANSI/IEEE Definite time

 ANSI Long Time Extremely Inverse

 ANSI Long Time Very Inverse

 ANSI Long Time Inverse

IEC Normal Inverse

IEC Very Inverse

IEC Inverse

IEC Extremely Inverse

IEC Short Time Inverse

IEC Long Time Inverse

IEC Definite Time

User Programmable

 ASEA RI

RXIDG (logarithmic)

1MRK 505 211-UEN C Section 3IED application

161

 Application manual

Page 168: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 168/457

The different characteristics are described in the “Technical reference manual ”.

 Ix>: Operation phase current level for step x given in % of  IBase.

tx: Definite time delay for step x. Used if definite time characteristic is chosen.Setting range: 0.000-60.000 s in step of 0.001 s

kx: Time multiplier for the dependent (inverse) characteristic.

 InxMult : Multiplier for scaling of the current setting value. If a binary input signal(enableMultiplier) is activated the current operation level is increase by this settingconstant. Setting range: 1.0-10.0

txMin: Minimum operation time for IEC inverse time characteristics. At highcurrents the inverse time characteristic might give a very short operation time. Bysetting this parameter the operation time of the step can never be shorter than the

setting. Setting range: 0.000-60.000 s in step of 0.001 s. ResetTypeCrvx: The reset of the delay timer can be made in different ways. Bychoosing setting the possibilities are according to table 60.

Table 60: Reset possibilities

Curve name Curve index no.

Instantaneous 1

IEC Reset (constant time) 2

 ANSI Reset (inverse time) 3

The delay characteristics are described in the “Technical reference manual ”. Thereare some restrictions regarding the choice of reset delay.

For the independent time delay characteristics the possible delay time settings areinstantaneous (1) and IEC (2 = set constant time reset).

For ANSI inverse time delay characteristics all three types of reset timecharacteristics are available; instantaneous (1), IEC (2 = set constant time reset)and ANSI (3 = current dependent reset time).

For IEC inverse time delay characteristics the possible delay time settings are

instantaneous (1) and IEC (2 = set constant time reset).

For the customer tailor made inverse time delay characteristics (type 17) all threetypes of reset time characteristics are available; instantaneous (1), IEC (2 = setconstant time reset) and ANSI (3 = current dependent reset time). If the currentdependent type is used settings pr, tr and cr must be given.

 HarmRestrainx: Enable block of step x from the harmonic restrain function (2ndharmonic). This function should be used when there is a risk if power transformer inrush currents might cause unwanted trip. Can be set Off/On.

Section 3 1MRK 505 211-UEN C

IED application

162

 Application manual

Page 169: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 169/457

tPCrvx, tACrvx, tBCrvx, tCCrvx: Parameters for customer creation of inverse timecharacteristic curve (Curve type = 17). See equation 44 for the time characteristicequation.

[ ]

>

 p

 At s B IxMult  

iC 

in

= + ×

-

æ öç ÷ç ÷ç ÷æ öç ÷ç ÷è øè ø

EQUATION1261 V2 EN (Equation 44)

For more information, please refer to the “Technical ref erence manual ”.

tPRCrvx, tTRCrvx, tCRCrvx: Parameters for customer creation of inverse reset timecharacteristic curve (Reset Curve type = 3). Further description can be found in the

“Technical reference manual ”.

Second harmonic restrainIf a power transformer is energized there is a risk that the transformer core willsaturate during part of the period, resulting in an inrush transformer current. Thiswill give a declining residual current in the network, as the inrush current isdeviating between the phases. There is a risk that the phase overcurrent functionwill give an unwanted trip. The inrush current has a relatively large ratio of 2nd

harmonic component. This component can be used to create a restrain signal to prevent this unwanted function.

The settings for the 2nd harmonic restrain are described below.2ndHarmStab: The rate of second harmonic current content for activation of the2nd harmonic restrain signal, to block chosen steps. The setting is given in % of thefundamental frequency residual current. The setting range is 5-100% in step of 1%.The default setting is 20%.

 HarmRestrainx: This parameter can be set Off/On, disable or enable the 2nd

harmonic restrain.

The four-step phase overcurrent protection can be used in different ways,depending on the application where the protection is used. A general description is

given below.

The pick up current setting inverse time protection or the lowest current stepconstant inverse time protection must be given a current setting so that the highest

 possible load current does not cause protection operation. Here consideration alsohas to be taken to the protection reset current, so that a short peak of overcurrentdoes not cause operation of the protection even when the overcurrent has ceased.This phenomenon is described in figure 67.

1MRK 505 211-UEN C Section 3IED application

163

 Application manual

Page 170: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 170/457

Operate current

Current I

The IED does not reset

Line phase current

Time t

Reset current

IEC05000203-en-2.vsd

IEC05000203 V3 EN

Figure 67: Pick up and reset current for an overcurrent protection 

The lowest setting value can be written according to equation 45.

ImaxIpu 1.2

k ³ ×

EQUATION1262 V2 EN (Equation 45)

where:

1.2 is a safety factor,

k is the resetting ratio of the protection, and

Imax is the maximum load current.

The maximum load current on the line has to be estimated. From operationstatistics the load current up to the present situation can be found. The currentsetting must be valid also for some years ahead. It is, in most cases, realistic thatthe setting values are updated not more often than once every five years. In manycases this time interval is still longer. Investigate the maximum load current thatdifferent equipment on the line can withstand. Study components such as lineconductors, current transformers, circuit breakers, and disconnectors. Themanufacturer of the equipment normally gives the maximum thermal load currentof the equipment.

Section 3 1MRK 505 211-UEN C

IED application

164

 Application manual

Page 171: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 171/457

There is also a demand that all faults, within the zone that the protection shallcover, must be detected by the phase overcurrent protection. The minimum faultcurrent Iscmin, to be detected by the protection, must be calculated. Taking thisvalue as a base, the highest pick up current setting can be written according toequation 46.

Ipu 0.7 Isc min£ ×

EQUATION1263 V2 EN (Equation 46)

where:

0.7 is a safety factor and

Iscmin is the smallest fault current to be detected by the overcurrent protection.

As a summary the pick up current shall be chosen within the interval stated inequation 47.

Imax1.2 Ipu 0.7 Iscmin

k × £ £ ×

EQUATION1264 V2 EN (Equation 47)

The high current function of the overcurrent protection, which only has a shortdelay of the operation, must be given a current setting so that the protection isselective to other protection in the power system. It is desirable to have a rapidtripping of faults within as large portion as possible of the part of the power system

to be protected by the protection (primary protected zone). A fault currentcalculation gives the largest current of faults, Iscmax, at the most remote part of the

 primary protected zone. Considerations have to be made to the risk of transientoverreach, due to a possible DC component of the short circuit current. The lowestcurrent setting of the most rapid stage, of the phase overcurrent protection, can bewritten according to

max1.2 t schigh I k I ³ × ×

EQUATION1265 V1 EN (Equation 48)

where:

1.2 is a safety factor,

kt is a factor that takes care of the transient overreach due to the DC component of the faultcurrent and can be considered to be less than 1.1

Iscmax is the largest fault current at a fault at the most remote point of the primary protection zone.

The operate times of the phase overcurrent protection has to be chosen so that thefault time is so short so that equipment will not be destroyed due to thermaloverload, at the same time as selectivity is assured. For overcurrent protection, in a

1MRK 505 211-UEN C Section 3IED application

165

 Application manual

Page 172: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 172/457

radial fed network, the time setting can be chosen in a graphical way. This ismostly used in the case of inverse time overcurrent protection. In the figure belowis shown how the time-versus-current curves are plotted in a diagram. The timesetting is chosen to get the shortest fault time with maintained selectivity.Selectivity is assured if the time difference between the curves is larger than acritical time difference.

en05000204.wmf 

IEC05000204 V1 EN

Figure 68: Fault time with maintained selectivity 

The operation time can be set individually for each overcurrent protection. Toassure selectivity between different protective protections, in the radial network,there have to be a minimum time difference Dt between the time delays of two

 protections. The minimum time difference can be determined for different cases.

To determine the shortest possible time difference between we must haveknowledge about operation time of protections, breaker opening time and

 protection resetting time. These time delays can vary significantly betweendifferent pieces of equipment. The following time delays can be estimated:

protection operation time: 15-60 ms

protection resetting time: 15-60 ms

Breaker opening time: 20-120 ms

Section 3 1MRK 505 211-UEN C

IED application

166

 Application manual

Page 173: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 173/457

Example

Assume two substations A and B directly connected to each other via one line, asshown in the figure below. We study a fault located at another line from the station

B. The fault current to the overcurrent protection of IED B1 has a magnitude sothat the protection will have instantaneous function. The overcurrent protection of IED A1 must have a delayed function. The sequence of events during the fault can

 be described using a time axis, see figure 69.

I> I>

 A1 B1Feeder 

Time axis

t=0 t=t1

t=t2

t=t3

The fault

occurs

Protection

B1 trips

Breaker at

B1 opens

Protection

 A1 resets

en05000205.vsd

IEC05000205 V1 EN

Figure 69: Sequence of events during fault 

where:

t=0 is the fault occurs,

t=t1 is the trip signal from the overcurrent protection at IED B1 is sent. Operation time of thisprotection is t1,

t=t2 is the circuit breaker at IED B1 opens. The circuit breaker opening time is t2 - t1 and

t=t3 is the overcurrent protection at IED A1 resets. The protection resetting time is t3 - t2.

To ensure that the overcurrent protection at IED A1, is selective to the overcurrent

 protection at IED B1, the minimum time difference must be larger that the time t3.There are uncertainties in the values of protection operation time, breaker openingtime and protection resetting time. Therefor a safety margin has to be included.With normal values the needed time difference can be calculated according toequation 49.

1MRK 505 211-UEN C Section 3IED application

167

 Application manual

Page 174: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 174/457

40 100 40 40 220t ms ms ms ms msD ³ + + + =EQUATION1266 V1 EN (Equation 49)

where it is considered that:

the operation time of overcurrent protection B1 is 40 ms

the breaker open time is 100 ms

the resetting time of protection A1 is 40 ms and

the additional margin is 40 ms

3.6.2.3 Setting parameters

Table 61: PH4SPTOC Group settings (basic)

Name Values (Range) Unit Step Default Description

Operation Off  On

- - Off Operation Off / On

IBase 1 - 99999 A 1 3000 Base setting for current values in A

OpStep1 Off  On

- - On Operation over current step 1 Off / On

Characterist1 ANSI Ext. inv. ANSI Very inv. ANSI Norm. inv. ANSI Mod. inv. ANSI Def. TimeL.T.E. inv.L.T.V. inv.

IEC Norm. inv.IEC Very inv.IEC inv.IEC Ext. inv.IEC L.T. inv.IEC Def. TimeReservedProgrammableRI typeRD type

- - ANSI Def. Time Selection of time delay curve type for  step 1

I1> 1 - 2500 %IB 1 1000 Operate phase current level for step1 in% of IBase

t1 0.000 - 60.000 s 0.001 0.000 Independent (defenitive) time delay of  step 1

k1 0.05 - 999.00 - 0.01 0.05 Time multiplier for the dependent timedelay for step 1

I1Mult 1.0 - 10.0 - 0.1 2.0 Multiplier for operate current level for  step 1

t1Min 0.000 - 60.000 s 0.001 0.000 Minimum operate time for IEC IDMTcurves for step 1

OpStep2 Off  On

- - On Operation over current step 2 Off / On

Table continues on next page

Section 3 1MRK 505 211-UEN C

IED application

168

 Application manual

Page 175: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 175/457

Name Values (Range) Unit Step Default Description

Characterist2 ANSI Ext. inv. ANSI Very inv.IEC Reset

 ANSI Norm. inv.

 ANSI Mod. inv. ANSI Def. TimeL.T.E. inv.L.T.V. inv.L.T. inv.IEC Norm. inv.IEC Very inv.IEC inv.IEC Ext. inv.IEC L.T. inv.IEC Def. TimeReservedProgrammableRI typeRD type

- - ANSI Def. Time Selection of time delay curve type for  step 2

I2> 1 - 2500 %IB 1 500 Operate phase current level for step2 in%of IBase

t2 0.000 - 60.000 s 0.001 0.400 Independent (defenitive) time delay of  step 2

k2 0.05 - 999.00 - 0.01 0.05 Time multiplier for the dependent timedelay for step 2

I2Mult 1.0 - 10.0 - 0.1 2.0 Multiplier for scaling the current settingvalue for step 2

t2Min 0.000 - 60.000 s 0.001 0.000 Minimum operate time for IEC IDMTcurves for step 2

OpStep3 Off  On

- - On Operation over current step 3 Off / On

Characterist3 ANSI Ext. inv.ReportEvents

 ANSI Very inv. ANSI Norm. inv. ANSI Mod. inv. ANSI Def. TimeL.T.E. inv.L.T.V. inv.L.T. inv.IEC Norm. inv.IEC Very inv.IEC inv.IEC Ext. inv.IEC S.T. inv.IEC L.T. inv.

IEC Def. TimeProgrammableRI typeRD type

- - ANSI Def. Time Selection of time delay curve type for  step 3

I3> 1 - 2500 %IB 1 250 Operate phase current level for step3 in%of Ibase

t3 0.000 - 60.000 s 0.001 0.800 Independent (definitive) time delay for  step 3

k3 0.05 - 999.00 - 0.01 0.05 Time multiplier for the dependent timedelay for step 3

Table continues on next page

1MRK 505 211-UEN C Section 3IED application

169

 Application manual

Page 176: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 176/457

Name Values (Range) Unit Step Default Description

I3Mult 1.0 - 10.0 - 0.1 2.0 Multiplier for scaling the current settingvalue for step 3

t3Min 0.000 - 60.000 s 0.001 0.000 Minimum operate time for IEC IDMT

curves for step 3

OpStep4 Off  On

- - On Operation over current step 4 Off / On

Characterist4 ANSI Ext. inv. ANSI Very inv. ANSI Norm. inv. ANSI Mod. inv. ANSI Def. TimeL.T.E. inv.L.T.V. inv.L.T. inv.IEC Norm. inv.IEC Very inv.IEC inv.

IEC Ext. inv.IEC S.T. inv.IEC L.T. inv.IEC Def. TimeReservedProgrammableRI typeRD type

- - ANSI Def. Time Selection of time delay curve type for  step 4

I4> 1 - 2500 %IB 1 175 Operate phase current level for step4 in% of IBase

t4 0.000 - 60.000 s 0.001 2.000 Independent (definitive) time delay of  step4

k4 0.05 - 999.00 - 0.01 0.05 Time multiplier for the dependent timedelay for step 4

I4Mult 1.0 - 10.0 - 0.1 2.0 Multiplier for scaling the current settingvalue for step 4

t4Min 0.000 - 60.000 s 0.001 0.000 Minimum operate time for IEC IDMTcurves for step 4

Table 62: PH4SPTOC Group settings (advanced)

Name Values (Range) Unit Step Default Description

2ndHarmStab 5 - 100 %IB 1 20 Operate level of 2nd harm restrain op in% of Fundamental

ResetTypeCrv1 Instantaneous

IEC Reset ANSI reset

- - Instantaneous Selection of reset curve type for step

tReset1 0.000 - 60.000 s 0.001 0.020 Reset time delay used in IEC DefiniteTime curve step 1

tPCrv1 0.005 - 3.000 - 0.001 1.000 Parameter P for customer programmablecurve for step 1

tACrv1 0.005 - 200.000 - 0.001 13.500 Parameter A for customer programmablecurve for step 1

tBCrv1 0.00 - 20.00 - 0.01 0.00 Parameter B for customer programmablecurve for step 1

Table continues on next page

Section 3 1MRK 505 211-UEN C

IED application

170

 Application manual

Page 177: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 177/457

Name Values (Range) Unit Step Default Description

tCCrv1 0.1 - 10.0 - 0.1 1.0 Parameter C for customer  programmable curve for step 1

tPRCrv1 0.005 - 3.000 - 0.001 0.500 Parameter PR for customer  

programmable curve for step 1

tTRCrv1 0.005 - 100.000 - 0.001 13.500 Parameter TR for customer  programmable curve for step 1

tCRCrv1 0.1 - 10.0 - 0.1 1.0 Parameter CR for customer  programmable curve for step 1

HarmRestrain1 DisabledEnabled

- - Enabled Enable block of step 1 from harmonicrestrain

ResetTypeCrv2 InstantaneousIEC Reset

 ANSI reset

- - Instantaneous Selection of reset curve type for step 2

tReset2 0.000 - 60.000 s 0.001 0.020 Reset time delay used in IEC DefiniteTime curve step 2

tPCrv2 0.005 - 3.000 - 0.001 1.000 Parameter P for customer programmablecurve for step 2

tACrv2 0.005 - 200.000 - 0.001 13.500 Parameter A for customer programmablecurve for step 2

tBCrv2 0.00 - 20.00 - 0.01 0.00 Parameter B for customer programmablecurve for step 2

tCCrv2 0.1 - 10.0 - 0.1 1.0 Parameter C for customer  programmable curve for step 2

tPRCrv2 0.005 - 3.000 - 0.001 0.500 Parameter PR for customer  programmable curve for step 2

tTRCrv2 0.005 - 100.000 - 0.001 13.500 Parameter TR for customer  programmable curve for step 2

tCRCrv2 0.1 - 10.0 - 0.1 1.0 Parameter CR for customer  programmable curve for step 2

HarmRestrain2 DisabledEnabled

- - Enabled Enable block of step 2 from harmonicrestrain

ResetTypeCrv3 InstantaneousIEC Reset

 ANSI reset

- - Instantaneous Selection of reset curve type for step 3

tReset3 0.000 - 60.000 s 0.001 0.020 Reset time delay used in IEC DefiniteTime curve step 3

tPCrv3 0.005 - 3.000 - 0.001 1.000 Parameter P for customer programmablecurve for step 3

tACrv3 0.005 - 200.000 - 0.001 13.500 Parameter A for customer programmable

curve for step 3

tBCrv3 0.00 - 20.00 - 0.01 0.00 Parameter B for customer programmablecurve for step 3

tCCrv3 0.1 - 10.0 - 0.1 1.0 Parameter C for customer  programmable curve for step 3

tPRCrv3 0.005 - 3.000 - 0.001 0.500 Parameter PR for customer  programmable curve for step 3

tTRCrv3 0.005 - 100.000 - 0.001 13.500 Parameter TR for customer  programmable curve for step 3

tCRCrv3 0.1 - 10.0 - 0.1 1.0 Parameter CR for customer  programmable curve for step 3

Table continues on next page

1MRK 505 211-UEN C Section 3IED application

171

 Application manual

Page 178: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 178/457

Name Values (Range) Unit Step Default Description

HarmRestrain3 DisabledEnabled

- - Enabled Enable block of step3 from harmonicrestrain

ResetTypeCrv4 Instantaneous

IEC Reset ANSI reset

- - Instantaneous Selection of reset curve type for step 4

tReset4 0.000 - 60.000 s 0.001 0.020 Reset time delay used in IEC DefiniteTime curve step 4

tPCrv4 0.005 - 3.000 - 0.001 1.000 Parameter P for customer programmablecurve for step 4

tACrv4 0.005 - 200.000 - 0.001 13.500 Parameter A for customer programmablecurve for step 4

tBCrv4 0.00 - 20.00 - 0.01 0.00 Parameter B for customer programmablecurve for step 4

tCCrv4 0.1 - 10.0 - 0.1 1.0 Parameter C for customer  programmable curve for step 4

tPRCrv4 0.005 - 3.000 - 0.001 0.500 Parameter PR for customer  programmable curve for step 4

tTRCrv4 0.005 - 100.000 - 0.001 13.500 Parameter TR for customer  programmable curve for step 4

tCRCrv4 0.1 - 10.0 - 0.1 1.0 Parameter CR for customer  programmable curve for step 4

HarmRestrain4 DisabledEnabled

- - Enabled Enable block of Step 4 from harmonicrestrain

3.6.3 Thermal overload protection, two time constants TRPTTR

Function description IEC 61850

identification

IEC 60617

identification

ANSI/IEEE C37.2

device number

Thermal overload protection, two timeconstants

TRPTTR

SYMBOL-A V1 EN

49

3.6.3.1 Application

Transformers in the power system are designed for a certain maximum load current(power) level. If the current exceeds this level the losses will be higher thanexpected. As a consequence the temperature of the transformer will increase. If thetemperature of the transformer reaches too high values the equipment might bedamaged:

• The insulation within the transformer will have forced ageing. As aconsequence of this, the risk of internal phase-to-phase or phase-to-earth faultswill increase.

• There might be hot spots within the transformer, which will degrade the paper insulation. It might also cause bubbling in the transformer oil.

Section 3 1MRK 505 211-UEN C

IED application

172

 Application manual

Page 179: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 179/457

In stressed situations in the power system it can be required to overloadtransformers for a limited time. This should be done without the above mentionedrisks. The thermal overload protection provides information and makes temporaryoverloading of transformers possible.

The permissible load level of a power transformer is highly dependent on thecooling system of the transformer. There are two main principles:

• OA: The air is naturally circulated to the coolers without fans and the oil isnaturally circulated without pumps.

• FOA: The coolers have fans to force air for cooling and pumps to force thecirculation of the transformer oil.

The protection can have two sets of parameters, one for non-forced cooling and onefor forced cooling. Both the permissive steady state loading level as well as the

thermal time constant is influenced by the cooling system of the transformer. Thetwo parameters sets can be activated by the binary input signal COOLING. Thiscan be used for transformers where forced cooling can be taken out of operation,for example at fan or pump faults.

The thermal overload protection estimates the internal heat content of thetransformer (temperature) continuously. This estimation is made by using a thermalmodel of the transformer, which is based on current measurement.

If the heat content of the protected transformer reaches a set alarm level a signalcan be given to the operator. Two alarm levels are available. This enables

 preventive actions in the power system to be taken before dangerous temperatures

are reached. If the temperature continues to increase to the trip value, the protectioninitiates a trip of the protected transformer.

After tripping by the thermal overload protection, the transformer will cool downover time. There will be a time gap before the heat content (temperature) reachessuch a level so that the transformer can be taken into service again. Therefore, thefunction will continue to estimate the heat content using a set cooling timeconstant. Energizing of the transformer can be blocked until the heat content hasreached a set level.

3.6.3.2 Setting guideline

The parameters for the thermal overload protection, two time constants (TRPTTR)are set via the local HMI or Protection and Control IED Manager (PCM600).

The following settings can be done for the thermal overload protection:

Operation: Off /On

Operation: Sets the mode of operation. Off switches off the complete function.

1MRK 505 211-UEN C Section 3IED application

173

 Application manual

Page 180: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 180/457

 IBase: Base current in primary A. This current is used as reference for currentsetting. It can be suitable to set this parameter to the rated primary current of thetransformer winding where the current measurement is made.

 IRef : Reference level of the current given in % of  IBase. When the current is equalto IRef the final (steady state) heat content is equal to 1. It is suggested to give asetting corresponding to the rated current of the transformer winding.

 IRefMult : If a binary input ENMULT is activated the reference current value can be multiplied by the factor  IRefMult . The activation could be used in case of deviating ambient temperature from the reference value. In the standard for loadingof a transformer an ambient temperature of 20°C is used. For lower ambienttemperatures the load ability is increased and vice versa. IRefMult can be set withina range: 0.01 - 10.00.

 IBase1: Base current for setting given as percentage of  IBase. This setting shall berelated to the status with no COOLING input. It is suggested to give a settingcorresponding to the rated current of the transformer with natural cooling (OA).

 IBase2: Base current for setting given as percentage of  IBase. This setting shall berelated to the status with activated COOLING input. It is suggested to give asetting corresponding to the rated current of the transformer with forced cooling(FOA). If the transformer has no forced cooling IBase2 can be set equal to IBase1.

Tau1: The thermal time constant of the protected transformer, related to IBase1 (nocooling) given in minutes.

Tau2: The thermal time constant of the protected transformer, related to IBase2

(with cooling) given in minutes.

The thermal time constant should be obtained from the transformer manufacturersmanuals. The thermal time constant is dependent on the cooling and the amount of oil. Normal time constants for medium and large transformers (according to IEC60076-7) are about 2.5 hours for naturally cooled transformers and 1.5 hours for forced cooled transformers.

The time constant can be estimated from measurements of the oil temperatureduring a cooling sequence (described in IEC 60076-7). It is assumed that thetransformer is operated at a certain load level with a constant oil temperature

(steady state operation). The oil temperature above the ambient temperature isDQo0. Then the transformer is disconnected from the grid (no load). After a time tof at least 30 minutes the temperature of the oil is measured again. Now the oiltemperature above the ambient temperature is DQot. The thermal time constant cannow be estimated as:

0ln lno ot 

t t  =

DQ - DQEQUATION1180 V1 EN (Equation 50)

Section 3 1MRK 505 211-UEN C

IED application

174

 Application manual

Page 181: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 181/457

If the transformer has forced cooling (FOA) the measurement should be made bothwith and without the forced cooling in operation, giving Tau2 and Tau1.

The time constants can be changed if the current is higher than a set value or lower 

than a set value. If the current is high it is assumed that the forced cooling isactivated while it is deactivated at low current. The setting of the parameters belowenables automatic adjustment of the time constant.

Tau1High: Multiplication factor to adjust the time constant Tau1 if the current ishigher than the set value IHighTau1. IHighTau1 is set in % of  IBase1.

Tau1Low: Multiplication factor to adjust the time constant Tau1 if the current islower than the set value ILowTau1. ILowTau1 is set in % of  IBase1.

Tau2High: Multiplication factor to adjust the time constant Tau2 if the current ishigher than the set value IHighTau2. IHighTau2 is set in % of  IBase2.

Tau2Low: Multiplication factor to adjust the time constant Tau2 if the current islower than the set value ILowTau2. ILowTau2 is set in % of  IBase2.

The possibility to change time constant with the current value as the base can beuseful in different applications. Below some examples are given:

• In case a total interruption (low current) of the protected transformer allcooling possibilities will be inactive. This can result in a changed value of thetime constant.

• If other components (motors) are included in the thermal protection, there is arisk of overheating of that equipment in case of very high current. The thermal

time constant is often smaller for a motor than for the transformer.

 ITrip: The steady state current that the transformer can withstand. The setting isgiven in % of  IBase1 or  IBase2.

 Alarm1: Heat content level for activation of the signal ALARM1. ALARM1 is setin % of the trip heat content level.

 Alarm2: Heat content level for activation of the output signal ALARM2. ALARM2is set in % of the trip heat content level.

 ResLo: Lockout release level of heat content to release the lockout signal. Whenthe thermal overload protection trips a lock-out signal is activated. This signal isintended to block switching on of the protected circuit transformer as long as thetransformer temperature is high. The signal is released when the estimated heatcontent is below the set value. This temperature value should be chosen below thealarm temperature. ResLo is set in % of the trip heat content level.

ThetaInit : Heat content before activation of the function. This setting can be set alittle below the alarm level. If the transformer is loaded before the activation of the

 protection function, its temperature can be higher than the ambient temperature.The start point given in the setting will prevent risk of no trip at overtemperature

1MRK 505 211-UEN C Section 3IED application

175

 Application manual

Page 182: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 182/457

during the first moments after activation. ThetaInit: is set in % of the trip heatcontent level.

Warning : If the calculated time to trip factor is below the setting Warning a

warning signal is activated. The setting is given in minutes.

3.6.3.3 Setting parameters

Table 63: TRPTTR Group settings (basic)

Name Values (Range) Unit Step Default Description

Operation Off  On

- - Off Operation Off / On

IBase 1 - 99999 A 1 3000 Base current in A

IRef 10.0 - 1000.0 %IB 1.0 100.0 Reference current in % of IBASE

IRefMult 0.01 - 10.00 - 0.01 1.00 Multiplication Factor for reference current

IBase1 30.0 - 250.0 %IB 1.0 100.0 Base current,IBase1 without Coolinginpout in % of IBASE

IBase2 30.0 - 250.0 %IB 1.0 100.0 Base Current,IBase2, with Cooling inputON in % of IBASE

Tau1 1.0 - 500.0 Min 1.0 60.0 Time constant without cooling input inmin, with IBase1

Tau2 1.0 - 500.0 Min 1.0 60.0 Time constant with cooling input in min,with IBase2

IHighTau1 30.0 - 250.0 %IB1 1.0 100.0 Current Sett, in % of IBase1 for rescalingTC1 by TC1-IHIGH

Tau1High 5 - 2000 %tC1 1 100 Multiplier in % to TC1 when current is >

IHIGH-TC1

ILowTau1 30.0 - 250.0 %IB1 1.0 100.0 Current Set, in % of IBase1 for rescalingTC1 by TC1-ILOW

Tau1Low 5 - 2000 %tC1 1 100 Multiplier in % to TC1 when current is <ILOW-TC1

IHighTau2 30.0 - 250.0 %IB2 1.0 100.0 Current Set, in % of IBase2 for rescalingTC2 by TC2-IHIGH

Tau2High 5 - 2000 %tC2 1 100 Multiplier in % to TC2 when current is>IHIGH-TC2

ILowTau2 30.0 - 250.0 %IB2 1.0 100.0 Current Set, in % of IBase2 for rescalingTC2 by TC2-ILOW

Tau2Low 5 - 2000 %tC2 1 100 Multiplier in % to TC2 when current is <

ILOW-TC2

ITrip 50.0 - 250.0 %IBx 1.0 110.0 Steady state operate current level in %of IBasex

 Alarm1 50.0 - 99.0 %Itr 1.0 80.0 First alarm level in % of heat content tripvalue

 Alarm2 50.0 - 99.0 %Itr 1.0 90.0 Second alarm level in % of heat contenttrip value

ResLo 10.0 - 95.0 %Itr 1.0 60.0 Lockout reset level in % of heat contenttrip value

Table continues on next page

Section 3 1MRK 505 211-UEN C

IED application

176

 Application manual

Page 183: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 183/457

Name Values (Range) Unit Step Default Description

ThetaInit 0.0 - 95.0 % 1.0 50.0 Initial Heat content, in % of heat contenttrip value

Warning 1.0 - 500.0 Min 0.1 30.0 Time setting, below which warning would

be set (in min)

tPulse 0.01 - 0.30 s 0.01 0.10 Length of the pulse for trip signal (inmsec).

3.6.4 Breaker failure protection CCRBRF

Function description IEC 61850

identification

IEC 60617

identification

ANSI/IEEE C37.2

device number

Breaker failure protection CCRBRF

3I>BF 

SYMBOL-U V1 EN

50BF

3.6.4.1 Application

In the design of the fault clearance system the N-1 criterion is often used. Thismeans that a fault needs to be cleared even if any component in the fault clearancesystem is faulty. One necessary component in the fault clearance system is thecircuit breaker. It is from practical and economical reason not feasible to duplicatethe circuit breaker for the protected component. Instead a breaker failure protectionis used.

Breaker failure protection, 3-phase activation and output (CCRBRF) will issue a back-up trip command to adjacent circuit breakers in case of failure to trip of the“normal” circuit breaker for the protected component. The detection of failure to

 break the current through the breaker is made by means of current measurement or as detection of remaining trip signal (unconditional).

CCRBRF can also give a re-trip. This means that a second trip signal is sent to the protected circuit breaker. The re-trip function can be used to increase the probability of operation of the breaker, or it can be used to avoid back-up trip of 

many breakers in case of mistakes during relay maintenance and test.

3.6.4.2 Setting guidelines

The parameters for Breaker failure protection 3-phase activation and outputCCRBRF are set via the local HMI or PCM600.

The following settings can be done for the breaker failure protection.

Operation: Off /On

1MRK 505 211-UEN C Section 3IED application

177

 Application manual

Page 184: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 184/457

 IBase: Base current in primary A. This current is used as reference for currentsetting. It can be suitable to set this parameter to the rated primary current of thecurrent transformer where the current measurement is made.

 FunctionMode This parameter can be set Current or Contact . This states the waythe detection of failure of the breaker is performed. In the mode current the currentmeasurement is used for the detection. In the mode Contact the long duration of 

 breaker position signal is used as indicator of failure of the breaker. The modeCurrent&Contact means that both ways of detections are activated. Contact modecan be usable in applications where the fault current through the circuit breaker issmall. This can be the case for some generator protection application (for examplereverse power protection) or in case of line ends with weak end infeed.

 RetripMode: This setting states how the re-trip function shall operate. Retrip Off 

means that the re-trip function is not activated. CB Pos Check (circuit breaker 

 position check) and Current means that a phase current must be larger than theoperate level to allow re-trip. CB Pos Check (circuit breaker position check) andContact means re-trip is done when circuit breaker is closed (breaker position isused). No CBPos Check means re-trip is done without check of breaker position.

Tab le 64: Dependenc ies between parameters Ret ripMode and FunctionMode

RetripMode FunctionMode Description

Retrip Off  N/A the re-trip function is notactivated

CB Pos Check Current   a phase current must be larger than the operate level to allowre-trip

Contact  re-trip is done when breaker position indicates that breaker is still closed after re-trip timehas elapsed

Current&Contact  both methods are used

No CBPos Check Current   re-trip is done without check of breaker position

Contact  re-trip is done without check of breaker position

Current&Contact  both methods are used

 BuTripMode: Back-up trip mode is given to state sufficient current criteria to detectfailure to break. For Current operation 2 out of 4 means that at least two currents,of the three-phase currents and the residual current, shall be high to indicate

 breaker failure. 1 out of 3 means that at least one current of the three-phase currentsshall be high to indicate breaker failure. 1 out of 4 means that at least one current of the three-phase currents or the residual current shall be high to indicate breaker failure. In most applications 1 out of 3 is sufficient. For Contact operation means

 back-up trip is done when circuit breaker is closed (breaker position is used).

 IP>: Current level for detection of breaker failure, set in % of  IBase. This parameter should be set so that faults with small fault current can be detected. The

Section 3 1MRK 505 211-UEN C

IED application

178

 Application manual

Page 185: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 185/457

setting can be chosen in accordance with the most sensitive protection function tostart the breaker failure protection. Typical setting is 10% of  IBase.

 I>BlkCont : If any contact based detection of breaker failure is used this function

can be blocked if any phase current is larger than this setting level. If the FunctionMode is set Current&Contact breaker failure for high current faults aresafely detected by the current measurement function. To increase security thecontact based function should be disabled for high currents. The setting can begiven within the range 5 – 200% of  IBase.

 IN>: Residual current level for detection of breaker failure set in % of  IBase. Inhigh impedance earthed systems the residual current at phase- to-earth faults arenormally much smaller than the short circuit currents. In order to detect breaker failure at single-phase-earth faults in these systems it is necessary to measure theresidual current separately. Also in effectively earthed systems the setting of the

earth-fault current protection can be chosen to relatively low current level. The BuTripMode is set 1 out of 4. The current setting should be chosen in accordance tothe setting of the sensitive earth-fault protection. The setting can be given withinthe range 2 – 200 % of  IBase.

t1: Time delay of the re-trip. The setting can be given within the range 0 – 60s insteps of 0.001 s. Typical setting is 0 – 50ms.

t2: Time delay of the back-up trip. The choice of this setting is made as short as possible at the same time as unwanted operation must be avoided. Typical setting is90 – 200ms (also dependent of re-trip timer).

The minimum time delay for the re-trip can be estimated as:

 _ 2 1³ + + +cbo pen BFP reset margin

t t t t t  

EQUATION1430 V1 EN (Equation 51)

where:

tcbopen is the maximum opening time for the circuit breaker 

tBFP_reset is the maximum time for breaker failure protection to detect correct breaker function (thecurrent criteria reset)

tmargin is a safety margin

It is often required that the total fault clearance time shall be less than a givencritical time. This time is often dependent of the ability to maintain transientstability in case of a fault close to a power plant.

1MRK 505 211-UEN C Section 3IED application

179

 Application manual

Page 186: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 186/457

Time

The fault

occurs

Protectionoperate time

Trip and StartCCRBRF

Normal tcbopen

Margin

Retrip delay t1 tcbopen after re-trip

tBFPreset

Minimum back-up trip delay t2

Critical fault clearance time for stability

IEC05000479_2_en.vsd

IEC05000479 V2 EN

Figure 70: Time sequence 

t2MPh: Time delay of the back-up trip at multi-phase start. The critical faultclearance time is often shorter in case of multi-phase faults, compared to single phase-to-earth faults. Therefore there is a possibility to reduce the back-up trip delay for multi-phase faults. Typical setting is 90 – 150 ms.

t3: Additional time delay to t2 for a second back-up trip TRBU2. In someapplications there might be a requirement to have separated back-up trip functions,tripping different back-up circuit breakers.

tCBAlarm: Time delay for alarm in case of indication of faulty circuit breaker.There is a binary input CBFLT from the circuit breaker. This signal is activatedwhen internal supervision in the circuit breaker detect that the circuit breaker isunable to clear fault. This could be the case when gas pressure is low in a SF6circuit breaker, of others. After the set time an alarm is given, so that actions can bedone to repair the circuit breaker. The time delay for back-up trip is bypassed whenthe CBFLT is active. Typical setting is 2.0 seconds.

tPulse: Trip pulse duration. This setting must be larger than the critical impulsetime of circuit breakers to be tripped from the breaker failure protection. Typicalsetting is 200 ms.

Section 3 1MRK 505 211-UEN C

IED application

180

 Application manual

Page 187: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 187/457

3.6.4.3 Setting parameters

Table 65: CCRBRF Group settings (basic)

Name Values (Range) Unit Step Default Description

Operation Off  On

- - Off Operation Off / On

IBase 1 - 99999 A 1 3000 Base current

FunctionMode CurrentContactCurrent&Contact

- - Current Detection principle for back-up trip

BuTripMode 2 out of 41 out of 31 out of 4

- - 1 out of 3 Back-up trip mode

RetripMode Retrip Off  CB Pos CheckNo CBPos Check

- - Retrip Off Operation mode of re-trip logic

IP> 5 - 200 %IB 1 10 Operate phase current level in % of IBase

IN> 2 - 200 %IB 1 10 Operate residual current level in % of  IBase

t1 0.000 - 60.000 s 0.001 0.000 Time delay of re-trip

t2 0.000 - 60.000 s 0.001 0.150 Time delay of back-up trip

t2MPh 0.000 - 60.000 s 0.001 0.150 Time delay of back-up trip at multi-phasestart

tPulse 0.000 - 60.000 s 0.001 0.200 Trip pulse duration

Table 66: CCRBRF Group settings (advanced)

Name Values (Range) Unit Step Default Description

I>BlkCont 5 - 200 %IB 1 20 Current for blocking of CB contactoperation in % of IBase

t3 0.000 - 60.000 s 0.001 0.030 Additional time delay to t2 for a secondback-up trip

tCBAlarm 0.000 - 60.000 s 0.001 5.000 Time delay for CB faulty signal

3.6.5 Breaker failure protection, single phase version CCSRBRF

Function description IEC 61850identification IEC 60617identification ANSI/IEEE C37.2device number

Breaker failure protection, single phaseversion

CCSRBRF

I>BF 

SYMBOL-II V1 EN

50BF

1MRK 505 211-UEN C Section 3IED application

181

 Application manual

Page 188: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 188/457

3.6.5.1 Application

In the design of the fault clearance system the N-1 criterion is often used. Thismeans that a fault shall be cleared even if any component in the fault clearance

system is faulty. One necessary component in the fault clearance system is thecircuit breaker. It is from practical and economical reason not feasible to duplicatethe circuit breaker for the protected component. Instead a breaker failure protectionis used.

Breaker failure protection, single phase version (CCSRBRF) function will issue a back-up trip command to adjacent circuit breakers in case of failure to trip of the“normal” circuit breaker for the protected component. The detection of failure to

 break the current through the breaker is made by means of current measurement or as detection of remaining trip signal (unconditional).

CCSRBRF function can also give a re-trip. This means that a second trip signal issent to the protected circuit breaker. The re-trip function can be used to increase the

 probability of operation of the breaker, or it can be used to avoid back-up trip of many breakers in case of mistakes during relay maintenance and test.

3.6.5.2 Setting guidelines

The parameters for Breaker failure protection, single phase version (CCSRBRF)are set via the local HMI or PCM600.

The following settings can be done for the breaker failure protection.

Operation: Off or On

 IBase: Base current in primary A. This current is used as reference for currentsetting. It can be suitable to set this parameter to the rated primary current of thecurrent transformer where the current measurement is made.

 FunctionMode: This parameter can be set to Current or Contact . This states theway the detection of failure of the breaker is performed. In the mode Current thecurrent measurement is used for the detection. In the mode Contact the longduration of start signal (trip) is used as indicator of failure of the breaker. The modeCurrent&Contact means that both ways of detections are activated. Contact modecan be usable in applications where the fault current through the circuit breaker is

small. This can be the case for some generator protection application (for example,reverse power protection) or in case of line ends with weak end infeed.

 RetripMode: This setting states how the re-trip function shall operate. Retrip Off 

means that the re-trip function is not activated. CB Pos Check (circuit breaker  position check) and Current means that a phase current must be larger than theoperate level to allow re-trip. CB Pos Check (circuit breaker position check) andConntact means retrip is done when circuit breaker is closed (breaker position isused). No CB Pos Check means re-trip is done without check of breaker position.

Section 3 1MRK 505 211-UEN C

IED application

182

 Application manual

Page 189: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 189/457

 IP>: Current level for detection of breaker failure, set in % of  IBase. This parameter must be set so that faults with small fault current can be detected. Thesetting can be chosen in accordance with the most sensitive protection function tostart the breaker failure protection. Typical setting is 10% of  IBase.

 I>BlkCont : If any contact based detection of breaker failure is used this functioncan be blocked if the current is larger than this setting level. If the FunctionMode isset to Current&Contact breaker failure for high current faults are safely detected

 by the current measurement function. To increase security the contact basedfunction must be disabled for high currents. The setting can be given within therange 5 – 200% of  IBase.

t1: Time delay of the re-trip. The setting can be given within the range 0 – 60 s insteps of 0.001 s. Typical setting is 0 – 50 ms.

t2: Time delay of the back-up trip. The choice of this setting is made as short as possible at the same time as unwanted operation must be avoided. Typical setting is90 – 150 ms (also dependent of re-trip timer).

The minimum time delay for the re-trip can be estimated as:

 _ 2 1³ + + +cbo pen BFP reset margin

t t t t t  

EQUATION1430 V1 EN (Equation 52)

where:

tcbopen is the maximum opening time for the circuit breaker 

tBFP_reset is the maximum time for breaker failure protection to detect correct breaker function (thecurrent criteria reset)

tmargin is a safety margin

It is often required that the total fault clearance time shall be less than a givencritical time. This time is often dependent of the ability to maintain transientstability in case of a fault close to a power plant.

1MRK 505 211-UEN C Section 3IED application

183

 Application manual

Page 190: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 190/457

Time

The fault

occurs

Protectionoperate time

Trip and StartCCRBRF

Normal tcbopen

Margin

Retrip delay t1 tcbopen after re-trip

tBFPreset

Minimum back-up trip delay t2

Critical fault clearance time for stability

IEC05000479_2_en.vsd

IEC05000479 V2 EN

Figure 71: Time sequence 

t3: Additional time delay to t2 for a second back-up trip TRBU2. In someapplications there might be a requirement to have separated back-up trip functions,tripping different back-up circuit breakers.

tCBAlarm: Time delay for alarm in case of indication of faulty circuit breaker.There is a binary input CBFLT from the circuit breaker. This signal is activatedwhen internal supervision in the circuit breaker detect that the circuit breaker isunable to clear fault. This could be the case when gas pressure is low in a SF6circuit breaker, of others. After the set time an alarm is given, so that actions can bedone to repair the circuit breaker. The time delay for back-up trip is bypassed whenthe CBFLT is active. Typical setting is 2.0 seconds.

tPulse: Trip pulse duration. This setting must be larger than the critical impulsetime of circuit breakers to be tripped from the breaker failure protection. Typicalsetting is 200 ms.

3.6.5.3 Setting parameters

Table 67: CCSRBRF Group settings (basic)

Name Values (Range) Unit Step Default Description

Operation Off  On

- - Off Operation Off / On

IBase 1 - 99999 A 1 3000 Base setting for current level settings

FunctionMode CurrentContactCurrent&Contact

- - Current Detection for trip Current/Contact/Current&Contact

Table continues on next page

Section 3 1MRK 505 211-UEN C

IED application

184

 Application manual

Page 191: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 191/457

Name Values (Range) Unit Step Default Description

RetripMode Retrip Off  I> CheckNo I> Check

- - Retrip Off Operation mode of re-trip logic: OFF /I>check/ No I> check

IP> 5 - 200 %IB 1 10 Operate level in % of IBase

I>BlkCont 5 - 200 %IB 1 20 Current for blocking of CB contactoperation in % of IBase

t1 0.000 - 60.000 s 0.001 0.000 Delay for re-trip

t2 0.000 - 60.000 s 0.001 0.150 Delay of back-up trip

t3 0.000 - 60.000 s 0.001 0.030 Additional delay to t2 for a second back-up trip

tCBAlarm 0.000 - 60.000 s 0.001 5.000 Delay for CB faulty signal

tPulse 0.000 - 60.000 s 0.001 0.200 Trip pulse duration

3.6.6 Directional underpower protection GUPPDUP

Function description IEC 61850

identification

IEC 60617

identification

ANSI/IEEE C37.2

device number

Directional underpower protection GUPPDUPP <

SYMBOL-LL V1 EN

37

3.6.6.1 Application

The task of a generator in a power plant is to convert mechanical energy availableas a torque on a rotating shaft to electric energy.

Sometimes, the mechanical power from a prime mover may decrease so much thatit does not cover bearing losses and ventilation losses. Then, the synchronousgenerator becomes a synchronous motor and starts to take electric power from therest of the power system. This operating state, where individual synchronousmachines operate as motors, implies no risk for the machine itself. If the generator under consideration is very large and if it consumes lots of electric power, it may

 be desirable to disconnect it to ease the task for the rest of the power system.

Often, the motoring condition may imply that the turbine is in a very dangerousstate. The task of the reverse power protection is to protect the turbine and not to

 protect the generator itself.

Steam turbines easily become overheated if the steam flow becomes too low or if the steam ceases to flow through the turbine. Therefore, turbo-generators shouldhave reverse power protection. There are several contingencies that may causereverse power: break of a main steam pipe, damage to one or more blades in thesteam turbine or inadvertent closing of the main stop valves. In the last case, it is

1MRK 505 211-UEN C Section 3IED application

185

 Application manual

Page 192: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 192/457

highly desirable to have a reliable reverse power protection. It may prevent damageto an otherwise undamaged plant.

During the routine shutdown of many thermal power units, the reverse power 

 protection gives the tripping impulse to the generator breaker (the unit breaker). Bydoing so, one prevents the disconnection of the unit before the mechanical power has become zero. Earlier disconnection would cause an acceleration of the turbinegenerator at all routine shutdowns. This should have caused overspeed and highcentrifugal stresses.

When the steam ceases to flow through a turbine, the cooling of the turbine bladeswill disappear. Now, it is not possible to remove all heat generated by the windagelosses. Instead, the heat will increase the temperature in the steam turbine andespecially of the blades. When a steam turbine rotates without steam supply, theelectric power consumption will be about 2% of rated power. Even if the turbine

rotates in vacuum, it will soon become overheated and damaged. The turbineoverheats within minutes if the turbine loses the vacuum.

The critical time to overheating a steam turbine varies from about 0.5 to 30 minutesdepending on the type of turbine. A high-pressure turbine with small and thin

 blades will become overheated more easily than a low-pressure turbine with longand heavy blades. The conditions vary from turbine to turbine and it is necessary toask the turbine manufacturer in each case.

Power to the power plant auxiliaries may come from a station service transformer connected to the secondary side of the step-up transformer. Power may also comefrom a start-up service transformer connected to the external network. One has to

design the reverse power protection so that it can detect reverse power independentof the flow of power to the power plant auxiliaries.

Hydro turbines tolerate reverse power much better than steam turbines do. OnlyKaplan turbine and bulb turbines may suffer from reverse power. There is a risk that the turbine runner moves axially and touches stationary parts. They are notalways strong enough to withstand the associated stresses.

Ice and snow may block the intake when the outdoor temperature falls far belowzero. Branches and leaves may also block the trash gates. A complete blockage of the intake may cause cavitations. The risk for damages to hydro turbines can justifyreverse power protection in unattended plants.

A hydro turbine that rotates in water with closed wicket gates will draw electric power from the rest of the power system. This power will be about 10% of therated power. If there is only air in the hydro turbine, the power demand will fall toabout 3%.

Diesel engines should have reverse power protection. The generator will take about15% of its rated power or more from the system. A stiff engine may require

 perhaps 25% of the rated power to motor it. An engine that is good run in mightneed no more than 5%. It is necessary to obtain information from the enginemanufacturer and to measure the reverse power during commissioning.

Section 3 1MRK 505 211-UEN C

IED application

186

 Application manual

Page 193: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 193/457

Gas turbines usually do not require reverse power protection.

Figure 72 illustrates the reverse power protection with underpower protection andwith overpower protection. The underpower protection gives a higher margin and

should provide better dependability. On the other hand, the risk for unwantedoperation immediately after synchronization may be higher. One should set theunderpower protection (reference angle set to 0) to trip if the active power from thegenerator is less than about 2%. One should set the overpower protection(reference angle set to 180) to trip if the power flow from the network to thegenerator is higher than 1%.

Underpower protection Overpower protection

Q Q

P P

Operating point

withoutturbine torque

Margin Margin

Operate

LineOperate

Line

Operating point

without

turbine torque

IEC09000019-2-en.vsd

IEC09000019 V2 EN

Figure 72: Reverse power protection with underpower or overpower protection 

3.6.6.2 Setting guidelines

Operation: With the parameter Operation the function can be set On/Off .

 IBase: The parameter  IBase is set to the generator rated current in A, seeequation 53.

3 N 

 N 

S  IBase

U =

×

EQUATION1707 V1 EN (Equation 53)

UBase: The parameter UBase is set to the generator rated voltage (phase-phase) inkV.

 Mode: The voltage and current used for the power measurement. The setting possibilities are shown in table 68.

1MRK 505 211-UEN C Section 3IED application

187

 Application manual

Page 194: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 194/457

Table 68: Complex power calculation

Set value Mode Formula used for complex power calculation

L1, L2, L3 * * *1 1 2 2 3 3 L L L L L LS U I U I U I  = × + × + ×

EQUATION1697 V1 EN (Equation 54)

 Arone * *1 2 1 2 3 3 L L L L L LS U I U I  = × - ×

EQUATION1698 V1 EN (Equation 55)

PosSeq *3 PosSeq PosSeqS U I = × ×

EQUATION1699 V1 EN (Equation 56)

L1L2 * *1 2 1 2( ) L L L LS U I I  = × -

EQUATION1700 V1 EN (Equation 57)

L2L3 * *2 3 2 3( ) L L L LS U I I  = × -

EQUATION1701 V1 EN (Equation 58)

L3L1 * *3 1 3 1( ) L L L LS U I I  = × -

EQUATION1702 V1 EN (Equation 59)

L1 *1 13 L LS U I = × ×

EQUATION1703 V1 EN (Equation 60)

L2 *2 23 L LS U I = × ×

EQUATION1704 V1 EN (Equation 61)

L3 *3 33 L LS U I = × ×

EQUATION1705 V1 EN (Equation 62)

The function has two stages that can be set independently.

With the parameter OpMode1(2) the function can be set On/Off .

The function gives trip if the power component in the direction defined by thesetting Angle1(2) is smaller than the set pick up power value Power1(2)

Section 3 1MRK 505 211-UEN C

IED application

188

 Application manual

Page 195: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 195/457

Operate

 Angle1(2)

Power1(2)

P

Q

en06000441.vsd

IEC06000441 V1 EN

Figure 73: Underpower mode 

The setting Power1(2) gives the power component pick up value in the Angle1(2)

direction. The setting is given in p.u. of the generator rated power, see equation 63.

Minimum recommended setting is 0.2% of S N when metering class CT inputs intothe IED are used.

3 N S UBase IBase= × ×

EQUATION1708 V1 EN (Equation 63)

The setting Angle1(2) gives the characteristic angle giving maximum sensitivity of the power protection function. The setting is given in degrees. For active power theset angle should be 0° or 180°. 0° should be used for generator low forward active

 power protection.

1MRK 505 211-UEN C Section 3IED application

189

 Application manual

Page 196: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 196/457

Operate

 Angle1(2) = 0 °  

Power1(2)

P

Q

en06000556.vsd

IEC06000556 V1 EN

Figure 74: For low forward power the set angle should be 0° in the 

underpower function 

TripDelay1(2) is set in seconds to give the time delay for trip of the stage after pick up.

 Hysteresis1(2) is given in p.u. of generator rated power according to equation 64.

3 N S UBase IBase= × ×

EQUATION1708 V1 EN (Equation 64)

The drop out power will be Power1(2) + Hysteresis1(2).

The possibility to have low pass filtering of the measured power can be made asshown in the formula:

( )1Old Calculated  S k S k S  = × + - ×

EQUATION1893 V1 EN (Equation 65)

Where

S is a new measured value to be used for the protection function

Sold is the measured value given from the function in previous execution cycle

SCalculated is the new calculated value in the present execution cycle

k  is settable parameter 

Section 3 1MRK 505 211-UEN C

IED application

190

 Application manual

Page 197: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 197/457

The value of k =0.92 is recommended in generator applications as the trip delay isnormally quite long.

The calibration factors for current and voltage measurement errors are set % of 

rated current/voltage:

 IAmpComp5, IAmpComp30, IAmpComp100

UAmpComp5, UAmpComp30, UAmpComp100

 IAngComp5, IAngComp30, IAngComp100

The angle compensation is given as difference between current and voltage angleerrors.

The values are given for operating points 5, 30 and 100% of rated current/voltage.

The values should be available from instrument transformer test protocols.

3.6.6.3 Setting parameters

Table 69: GUPPDUP Group settings (basic)

Name Values (Range) Unit Step Default Description

Operation Off  On

- - Off Operation Off / On

OpMode1 Off  UnderPower 

- - UnderPower Operation mode 1

Power1 0.0 - 500.0 %SB 0.1 1.0 Power setting for stage 1 in % of Sbase

 Angle1 -180.0 - 180.0 Deg 0.1 0.0 Angle for stage 1

TripDelay1 0.010 - 6000.000 s 0.001 1.000 Trip delay for stage 1

DropDelay1 0.010 - 6000.000 s 0.001 0.060 Drop delay for stage 1

OpMode2 Off  UnderPower 

- - UnderPower Operation mode 2

Power2 0.0 - 500.0 %SB 0.1 1.0 Power setting for stage 2 in % of Sbase

 Angle2 -180.0 - 180.0 Deg 0.1 0.0 Angle for stage 2

TripDelay2 0.010 - 6000.000 s 0.001 1.000 Trip delay for stage 2

DropDelay2 0.010 - 6000.000 s 0.001 0.060 Drop delay for stage 2

Table 70: GUPPDUP G roup settings (advanced)

Name Values (Range) Unit Step Default Description

k 0.000 - 0.999 - 0.001 0.000 Low pass filter coefficient for power  measurement, P and Q

Hysteresis1 0.2 - 5.0 pu 0.1 0.5 Absolute hysteresis of stage 1 in % Sbase

Hysteresis2 0.2 - 5.0 pu 0.1 0.5 Absolute hysteresis of stage 2 in % Sbase

IAmpComp5 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate current at5% of Ir 

Table continues on next page

1MRK 505 211-UEN C Section 3IED application

191

 Application manual

Page 198: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 198/457

Name Values (Range) Unit Step Default Description

IAmpComp30 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate current at30% of Ir 

IAmpComp100 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate current at

100% of Ir 

UAmpComp5 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate voltage at5% of Ur 

UAmpComp30 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate voltage at30% of Ur 

UAmpComp100 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate voltage at100% of Ur 

IAngComp5 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 5% of Ir  

IAngComp30 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 30% of Ir  

IAngComp100 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 100% of Ir  

Table 71: GUPPDUP Non group settings (basic)

Name Values (Range) Unit Step Default Description

IBase 1 - 99999 A 1 3000 Base setting for current level

UBase 0.05 - 2000.00 kV 0.05 400.00 Base setting for voltage level

Mode L1, L2, L3 AronePos SeqL1L2L2L3L3L1L1L2L3

- - Pos Seq Selection of measured current andvoltage

3.6.7 Directional overpower protection GOPPDOP

Function description IEC 61850

identification

IEC 60617

identification

ANSI/IEEE C37.2

device number

Directional overpower protection GOPPDOPP >

DOCUMENT172362-IMG158942

V1 EN

32

3.6.7.1 Application

The task of a generator in a power plant is to convert mechanical energy availableas a torque on a rotating shaft to electric energy.

Sometimes, the mechanical power from a prime mover may decrease so much thatit does not cover bearing losses and ventilation losses. Then, the synchronousgenerator becomes a synchronous motor and starts to take electric power from the

Section 3 1MRK 505 211-UEN C

IED application

192

 Application manual

Page 199: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 199/457

rest of the power system. This operating state, where individual synchronousmachines operate as motors, implies no risk for the machine itself. If the generator under consideration is very large and if it consumes lots of electric power, it may

 be desirable to disconnect it to ease the task for the rest of the power system.

Often, the motoring condition may imply that the turbine is in a very dangerousstate. The task of the reverse power protection is to protect the turbine and not to

 protect the generator itself.

Steam turbines easily become overheated if the steam flow becomes too low or if the steam ceases to flow through the turbine. Therefore, turbo-generators shouldhave reverse power protection. There are several contingencies that may causereverse power: break of a main steam pipe, damage to one or more blades in thesteam turbine or inadvertent closing of the main stop valves. In the last case, it ishighly desirable to have a reliable reverse power protection. It may prevent damage

to an otherwise undamaged plant.During the routine shutdown of many thermal power units, the reverse power 

 protection gives the tripping impulse to the generator breaker (the unit breaker). Bydoing so, one prevents the disconnection of the unit before the mechanical power has become zero. Earlier disconnection would cause an acceleration of the turbinegenerator at all routine shutdowns. This should have caused overspeed and highcentrifugal stresses.

When the steam ceases to flow through a turbine, the cooling of the turbine bladeswill disappear. Now, it is not possible to remove all heat generated by the windagelosses. Instead, the heat will increase the temperature in the steam turbine and

especially of the blades. When a steam turbine rotates without steam supply, theelectric power consumption will be about 2% of rated power. Even if the turbinerotates in vacuum, it will soon become overheated and damaged. The turbineoverheats within minutes if the turbine loses the vacuum.

The critical time to overheating of a steam turbine varies from about 0.5 to 30minutes depending on the type of turbine. A high-pressure turbine with small andthin blades will become overheated more easily than a low-pressure turbine withlong and heavy blades. The conditions vary from turbine to turbine and it isnecessary to ask the turbine manufacturer in each case.

Power to the power plant auxiliaries may come from a station service transformer 

connected to the primary side of the step-up transformer. Power may also comefrom a start-up service transformer connected to the external network. One has todesign the reverse power protection so that it can detect reverse power independentof the flow of power to the power plant auxiliaries.

Hydro turbines tolerate reverse power much better than steam turbines do. OnlyKaplan turbine and bulb turbines may suffer from reverse power. There is a risk that the turbine runner moves axially and touches stationary parts. They are notalways strong enough to withstand the associated stresses.

1MRK 505 211-UEN C Section 3IED application

193

 Application manual

Page 200: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 200/457

Ice and snow may block the intake when the outdoor temperature falls far belowzero. Branches and leaves may also block the trash gates. A complete blockage of the intake may cause cavitations. The risk for damages to hydro turbines can justifyreverse power protection in unattended plants.

A hydro turbine that rotates in water with closed wicket gates will draw electric power from the rest of the power system. This power will be about 10% of therated power. If there is only air in the hydro turbine, the power demand will fall toabout 3%.

Diesel engines should have reverse power protection. The generator will take about15% of its rated power or more from the system. A stiff engine may require

 perhaps 25% of the rated power to motor it. An engine that is well run in mightneed no more than 5%. It is necessary to obtain information from the enginemanufacturer and to measure the reverse power during commissioning.

Gas turbines usually do not require reverse power protection.

Figure 75 illustrates the reverse power protection with underpower IED and withoverpower IED. The underpower IED gives a higher margin and should provide

 better dependability. On the other hand, the risk for unwanted operationimmediately after synchronization may be higher. One should set the underpower IED to trip if the active power from the generator is less than about 2%. Oneshould set the overpower IED to trip if the power flow from the network to thegenerator is higher than 1%.

Underpower IED Overpower IED

Q Q

P P

Operating pointwithoutturbine torque

Margin Margin

OperateLine

OperateLine

Operating pointwithoutturbine torque

IEC06000315-2-en.vsd

IEC06000315 V2 EN

Figure 75:  Re verse power protection with underpower IED and overpower IED 

3.6.7.2 Setting guidelines

Operation: With the parameter Operation the function can be set On/Off .

 IBase: The parameter  IBase is set to the generator rated current in A, seeequation 66.

Section 3 1MRK 505 211-UEN C

IED application

194

 Application manual

Page 201: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 201/457

3 N 

 N 

S  IBase

U =

×

EQUATION1707 V1 EN (Equation 66)

UBase: The parameter UBase is set to the generator rated voltage (phase-phase) inkV.

 Mode: The voltage and current used for the power measurement. The setting possibilities are shown in table 72.

Table 72: Complex power calculation

Set value Mode Formula used for complex power calculation

L1, L2, L3 * * *

1 1 2 2 3 3 L L L L L LS U I U I U I  = × + × + ×

EQUATION1697 V1 EN (Equation 67)

 Arone * *1 2 1 2 3 3 L L L L L LS U I U I  = × - ×

EQUATION1698 V1 EN (Equation 68)

PosSeq *3 PosSeq PosSeqS U I = × ×

EQUATION1699 V1 EN (Equation 69)

L1L2 * *1 2 1 2( ) L L L LS U I I  = × -

EQUATION1700 V1 EN (Equation 70)

L2L3 * *2 3 2 3( ) L L L LS U I I  = × -

EQUATION1701 V1 EN (Equation 71)

L3L1 * *3 1 3 1( ) L L L LS U I I  = × -

EQUATION1702 V1 EN (Equation 72)

L1 *1 13 L LS U I = × ×

EQUATION1703 V1 EN (Equation 73)

L2 *2 23 L LS U I = × ×

EQUATION1704 V1 EN (Equation 74)

L3 *3 33 L LS U I = × ×

EQUATION1705 V1 EN (Equation 75)

The function has two stages that can be set independently.

With the parameter OpMode1(2) the function can be set On/Off .

The function gives trip if the power component in the direction defined by thesetting Angle1(2) is larger than the set pick up power value Power1(2)

1MRK 505 211-UEN C Section 3IED application

195

 Application manual

Page 202: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 202/457

Operate

 Angle1(2)

Power1(2)

P

Q

en06000440.vsd

IEC06000440 V1 EN

Figure 76: Overpower mode 

The setting Power1(2) gives the power component pick up value in the Angle1(2)

direction. The setting is given in p.u. of the generator rated power, see equation 76.

Minimum recommended setting is 0.2% of S N when metering class CT inputs intothe IED are used.

3 N S UBase IBase= × ×

EQUATION1708 V1 EN (Equation 76)

The setting Angle1(2) gives the characteristic angle giving maximum sensitivity of 

the power protection function. The setting is given in degrees. For active power theset angle should be 0° or 180°. 180° should be used for generator reverse power  protection.

Section 3 1MRK 505 211-UEN C

IED application

196

 Application manual

Page 203: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 203/457

Operate  Angle1(2 ) = 180 o

Power1(2)

P

Q

IEC06000557-2-en.vsd

IEC06000557 V2 EN

Figure 77: For reverse power the set angle should be 180° in the overpower 

function 

TripDelay1(2) is set in seconds to give the time delay for trip of the stage after pick up.

 Hysteresis1(2) is given in p.u. of generator rated power according to equation 77.

3 N S UBase IBase= × ×

EQUATION1708 V1 EN (Equation 77)

The drop out power will be Power1(2) - Hysteresis1(2).

The possibility to have low pass filtering of the measured power can be made asshown in the formula:

( )1Old Calculated  S k S k S  = × + - ×

EQUATION1893 V1 EN (Equation 78)

Where

S is a new measured value to be used for the protection function

Sold is the measured value given from the function in previous execution cycle

SCalculated is the new calculated value in the present execution cycle

k is settable parameter  

1MRK 505 211-UEN C Section 3IED application

197

 Application manual

Page 204: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 204/457

The value of k =0.92 is recommended in generator applications as the trip delay isnormally quite long.

The calibration factors for current and voltage measurement errors are set % of 

rated current/voltage:

 IAmpComp5, IAmpComp30, IAmpComp100

UAmpComp5, UAmpComp30, UAmpComp100

 IAngComp5, IAngComp30, IAngComp100

The angle compensation is given as difference between current and voltage angleerrors.

The values are given for operating points 5, 30 and 100% of rated current/voltage.

The values should be available from instrument transformer test protocols.

3.6.7.3 Setting parameters

Table 73: GOPPDOP Group settings (basic)

Name Values (Range) Unit Step Default Description

Operation Off  On

- - Off Operation Off / On

OpMode1 Off  OverPower 

- - OverPower Operation mode 1

Power1 0.0 - 500.0 %SB 0.1 120.0 Power setting for stage 1 in % of Sbase

 Angle1 -180.0 - 180.0 Deg 0.1 0.0 Angle for stage 1

TripDelay1 0.010 - 6000.000 s 0.001 1.000 Trip delay for stage 1

DropDelay1 0.010 - 6000.000 s 0.001 0.060 Drop delay for stage 1

OpMode2 Off  OverPower 

- - OverPower Operation mode 2

Power2 0.0 - 500.0 %SB 0.1 120.0 Power setting for stage 2 in % of Sbase

 Angle2 -180.0 - 180.0 Deg 0.1 0.0 Angle for stage 2

TripDelay2 0.010 - 6000.000 s 0.001 1.000 Trip delay for stage 2

DropDelay2 0.010 - 6000.000 s 0.001 0.060 Drop delay for stage 2

Table 74: GOPPDO P Group settings (advanced)

Name Values (Range) Unit Step Default Description

k 0.000 - 0.999 - 0.001 0.000 Low pass filter coefficient for power  measurement, P and Q

Hysteresis1 0.2 - 5.0 pu 0.1 0.5 Absolute hysteresis of stage 1 in % of  Sbase

Hysteresis2 0.2 - 5.0 pu 0.1 0.5 Absolute hysteresis of stage 2 in % of  Sbase

IAmpComp5 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate current at5% of Ir 

Table continues on next page

Section 3 1MRK 505 211-UEN C

IED application

198

 Application manual

Page 205: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 205/457

Name Values (Range) Unit Step Default Description

IAmpComp30 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate current at30% of Ir 

IAmpComp100 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate current at

100% of Ir 

UAmpComp5 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate voltage at5% of Ur 

UAmpComp30 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate voltage at30% of Ur 

UAmpComp100 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate voltage at100% of Ur 

IAngComp5 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 5% of Ir  

IAngComp30 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 30% of Ir  

IAngComp100 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 100% of Ir  

Table 75: GOPPDOP Non group settings (basic)

Name Values (Range) Unit Step Default Description

IBase 1 - 99999 A 1 3000 Base setting for current level

UBase 0.05 - 2000.00 kV 0.05 400.00 Base setting for voltage level

Mode L1, L2, L3 AronePos SeqL1L2L2L3L3L1L1L2L3

- - Pos Seq Selection of measured current andvoltage

3.6.8 Capacitor bank protection CBPGAPC

Function description IEC 61850

identification

IEC 60617

identification

ANSI/IEEE C37.2

device number

Capacitor bank protection CBPGAPC - -

3.6.8.1 Application

Shunt capacitor banks (SCBs) are somewhat specific and different from other  power system elements. These specific features of SCB are briefly summarized inthis section.

A capacitor unit is the building block used for SCB construction. The capacitor unitis made up of individual capacitor elements, arranged in parallel or seriesconnections. Capacitor elements normally consist of aluminum foil, paper, or film-insulated cells immersed in a biodegradable insulating fluid and are sealed in ametallic container. The internal discharge resistor is also integrated within the

1MRK 505 211-UEN C Section 3IED application

199

 Application manual

Page 206: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 206/457

capacitor unit in order to reduce trapped residual voltage after disconnection of theSCB from the power system. Units are available in a variety of voltage ratings(240V to 25kV) and sizes (2.5kVAr to about 1000kVAr). Capacitor unit can bedesigned with one or two bushings.

The high-voltage SCB is normally constructed using individual capacitor unitsconnected in series and/or parallel to obtain the required voltage and MVAr rating.Typically the neighboring capacitor units are mounted in racks. Each rack must beinsulated from the other by insulators because the can casing within each rack areat a certain potential. Refer figure 78 for an example:

  Capacitor Unit(Can)

Rack 

IEC09000753_1_en.vsd

IEC09000753 V1 EN

Figure 78: Replacement of a faulty capacitor unit within SCB 

There are four types of the capacitor unit fusing designs which are used for construction of SCBs:

Section 3 1MRK 505 211-UEN C

IED application

200

 Application manual

Page 207: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 207/457

Externallyfused

where an individual fuse, externally mounted, protects each capacitor unit.

Internallyfused

where each capacitor element is fused inside the capacitor unit

Fuseless where SCB is built from series connections of the individual capacitor units (that is,strings) and without any fuses

Unfused where, in contrary to the fuseless configuration, a series or parallel connection of the capacitor units is used to form SCB, still without any fuses

Which type of fusing is used may depend on can manufacturer or utility preferenceand previous experience.

Because the SCBs are built from the individual capacitor units the overallconnections may vary. Typically used SCB configurations are:

1. Delta-connected banks (generally used only at distribution voltages)2. Single wye-connected banks3. Double wye-connected banks4. H-configuration, where each phase is connected in a bridge

Additionally, the SCB star point, when available, can be either directly earthed ,earthed via impedance or isolated from earth. Which type of SCB earthing is useddepends on voltage level, used circuit breaker, utility preference and previousexperience. Many utilities have standard system earthing principle to earth neutralsof SCB above 100 kV.

Switching of SCB will produce transients in power system. The transient inrushcurrent during SCB energizing typically has high frequency components and canreach peak current values, which are multiples of SCB rating. Opening of capacitor 

 bank circuit breaker may produce step recovery voltages across open CB contact,which can consequently cause restrikes upon the first interruption of capacitivecurrent. In modern power system the synchronized CB closing/opening may beutilized in such a manner that transients caused by SCB switching are avoided.

SCB protectionIED protection of shunt capacitor banks requires an understanding of thecapabilities and limitations of the individual capacitor units and associated

electrical equipment. Different types of shunt capacitor bank fusing, configurationor earthing may affect the IED selection for the protection scheme. Availability and placement of CTs and VTs can be additional limiting factor during protectionscheme design.

SCB protection schemes are provided in order to detect and clear faults within thecapacitor bank itself or in the connected leads to the substation busbar. Bank 

 protection may include items such as a means to disconnect a faulted capacitor unitor capacitor element(s), a means to initiate a shutdown of the bank in case of faultsthat may lead to a catastrophic failure and alarms to indicate unbalance within the

 bank.

1MRK 505 211-UEN C Section 3IED application

201

 Application manual

Page 208: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 208/457

Capacitor bank outages and failures are often caused by accidental contact byanimals. Vermin, monkeys, birds, may use the SCB as a resting place or a landingsite. When the animal touches the HV live parts this can result in a flash-over, canrapture or a cascading failures that might cause extensive damages, fire or eventotal destruction of the whole SCB, unless the bank is sufficiently fitted with

 protection IEDs.

In addition, to fault conditions SCB can be exposed to different types of abnormaloperating conditions. In accordance with IEC and ANSI standards capacitors shall

 be capable of continuous operation under contingency system and bank conditions, provided the following limitations are not exceeded:

1. Capacitor units should be capable of continuous operation includingharmonics, but excluding transients, to 110% of rated IED root-mean-square(RMS) voltage and a crest voltage not exceeding of rated RMS voltage. The

capacitor should also be able to carry 135% of nominal current. The voltagecapability of any series element of a capacitor unit shall be considered to be itsshare of the total capacitor unit voltage capability.

2. Capacitor units should not give less than 100% nor more than 110% of ratedreactive power at rated sinusoidal voltage and frequency, measured at auniform case and internal temperature of 25°C.

3. Capacitor units mounted in multiple rows and tiers should be designed for continuous operation for a 24h average temperature of 40 °C during the hottestday, or −40 °C during the coldest day expected at the location.

4. Capacitor units should be suitable for continuous operation at up to 135% of rated reactive power caused by the combined effects of:

• Voltage in excess of the nameplate rating at fundamental frequency, butnot over 110% of rated RMS voltage• Harmonic voltages superimposed on the fundamental frequency• Reactive power manufacturing tolerance of up to 115% of rated reactive

 power 

5. Capacitor units rated above 600 V shall have an internal discharge device toreduce the residual voltage to 50 V or less in 5 or 10 minutes (depending onnational standard).

 Note that capacitor units designed for special applications can exceed these ratings.

Thus, as a general rule, the minimum number of capacitor units connected in parallel within a SCB is such that isolation of one capacitor unit in a group shouldnot cause a voltage unbalance sufficient to place more than 110% of rated voltageon the remaining capacitors of that parallel group. Equally, the minimum number of series connected groups within a SCB is such that complete bypass of one groupshould not pause voltage higher than 110% of the rated voltage on the remainingcapacitors of that serial group. The value of 110% is the maximum continuousovervoltage capability of capacitor units as per IEEE Std 18-1992.

The SCB typically requires the following types of IED protection:

Section 3 1MRK 505 211-UEN C

IED application

202

 Application manual

Page 209: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 209/457

1. Short circuit protection for SCB and connecting leads (can be provided byusing PHPIOC, OC4PTOC, CVGAPC, T2WPDIF/T3WPDIF or HZPDIFfunctions)

2. Earth-fault protection for SCB and connecting leads (can be provided by usingEFPIOC, EF4PTOC, CVGAPC, T2WPDIF/T3WPDIF or HZPDIF functions)

3. Current or Voltage based unbalance protection for SCB (can be provided byusing EF4PTOC, OC4PTOC, CVGAPC or VDCPTOV functions)

4. Overload protection for SCB5. Undercurrent protection for SCB6. Reconnection inhibit protection for SCB7. Restrike condition detection

CBPGAPC function can be used to provide the last four types of protectionmentioned in the above list.

3.6.8.2 Setting guidelines

This setting example will be done for application as shown in figure 79:

Preprocessing

Function Block

Capacitor bank

protection function

400kV

CBPGAPCSMAI

200MVAr 

400kV

500/1

IED

IEC09000754-1-en.vsd

IEC09000754 V1 EN

Figure 79: Single line diagram for the application example 

From figure 79 it is possible to calculate the following rated fundamental frequencycurrent for this SCB:

1000 200[ ]289

3 400[ ]r 

 MVAr  I A

kV 

×= =

×IEC09000755 V1 EN (Equation 79)

1MRK 505 211-UEN C Section 3IED application

203

 Application manual

Page 210: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 210/457

or on the secondary CT side:

 _ ec

2890.578

500 1r S 

 A I A= =

IEC09000756 V1 EN (Equation 80)

 Note that the SCB rated current on the secondary CT side is important for secondary injection of the function.

The parameters for the Capacitor bank protection function CBPGAPC are set viathe local HMI or PCM600. The following settings are done for this function:

General Settings:

Operation =On; to enable the function

 IBase =289A; Fundamental frequency SCB rated current in primary amperes. Thisvalue is used as a base value for pickup settings of all other features integrated inthis function.

Reconnection inhibit feature:

OperationRecIn =On; to enable this feature

 IRecnInhibit< =10% (of  IBase); Current level under which function will detect thatSCB is disconnected from the power system

tReconnInhibit =300s; Time period under which SCB shall discharge remaining

residual voltage to less than 5%.

Overcurrent feature:

OperationOC =On; to enable this feature

 IOC> =135% (of  IBase); Current level for overcurrent pickup. Selected valuegives pickup recommended by international standards.

tOC =30s; Time delay for overcurrent trip

Undercurrent feature:

OperationUC  =On; to enable this feature

 IUC< =70% (of  IBase); Current level for undercurrent pickup

tUC =5s; Time delay for undercurrent trip

Undercurrent feature is blocked by operation of Reconnectioninhibit feature.

Reactive power overload feature:

Section 3 1MRK 505 211-UEN C

IED application

204

 Application manual

Page 211: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 211/457

OperationQOL =On; to enable this feature

QOL> =130% (of SCB MVAr rating); Reactive power level required for pickup.Selected value gives pickup recommended by international standards.

tQOL =60s; Time delay for reactive power overload trip

Harmonic voltage overload feature:

OperationHOL =On; to enable this feature

Settings for definite time delay step

 HOLDTU> =200% (of SCB voltage rating); Voltage level required for pickup

tHOLDT  =10s; Definite time delay for harmonic overload trip

Settings for IDMT delay step

 HOLIDMTU> =110% (of SCB voltage rating); Voltage level required for pickupof IDMT stage. Selected value gives pickup recommended by international standards.

kHOLIDMT =1.0; Time multiplier for IDMT stage. Selected value gives operatetime in accordance with international standards

tMaxHOLIDMT =2000s; Maximum time delay for IDMT stage for very low levelof harmonic overload

tMinHOLIDMT =0.1s; Minimum time delay for IDMT stage. Selected value gives

operate time in accordance with international standards

Restrike detectionOpening of SCBs can be quite problematic for certain types of circuit breakers(CBs). Typically such problems are manifested as CB restrikes.

In simple words this means that the CB is not breaking the current at the first zerocrossing after separation of the CB contacts. Instead current is re-ignited and only

 braked at consecutive current zero crossings. This condition is manifested as highcurrent pulses at the moment of current re-ignition.

To detect this CB condition, the built in overcurrent feature can be used. Simply,

any start of the overcurrent feature during breaker normal opening means arestrike. Therefore simple logic can be created in the Application Configurationtool to detect such CB behavior. Such CB condition can be just alarmed, and if required, the built in disturbance recorder can also be triggered.

To create this logic, a binary signal that the CB is going to be opened (but not tripcommand) shall be made available to the IED.

1MRK 505 211-UEN C Section 3IED application

205

 Application manual

Page 212: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 212/457

3.6.8.3 Setting parameters

Table 76: CBPGAPC Group settings (basic)

Name Values (Range) Unit Step Default Description

Operation Off  On

- - Off Operation Off/On

IBase 1 - 99999 A 1 3000 Rated capacitor bank current

OperationRecIn Off  On

- - On Operation reconnection inhibit Off/On

IRecnInhibit< 4 - 1000 %IB 1 10 Cap bank cut off current level for inhibitin % of IBase

tReconnInhibit 1.00 - 6000.00 s 0.01 300.00 Time delay for reconnected inhibit signal

OperationOC Off  On

- - On Operation over current Off/On

IOC> 0 - 900 %IB 1 135 Start level for over current operation, %

of IBase

tOC 0.00 - 6000.00 s 0.01 30.00 Time delay for over current operation

OperationUC Off  On

- - Off Operation under current Off/On

IUC< 5 - 100 %IB 1 70 Start level for under current operation, %of IBase

tUC 0.00 - 6000.00 s 0.01 5.00 Time delay for under current operation

OperationQOL Off  On

- - On Operation reactive power over load Off/On

QOL> 5 - 900 % 1 130 Start level for reactive power over load in%

tQOL 1.00 - 6000.00 s 0.01 60.00 Time delay for reactive power overloadoperation

OperationHOL Off  On

- - On Operation harmonic over load Off/On

HOLDTU> 5 - 500 % 1 200 Start value of voltage for harmOvLoadfor DT stage in %

tHOLDT 0.00 - 6000.00 s 0.01 10.00 Time delay for minimum operation for  harmonic overload

HOLIDMTU> 80 - 200 % 1 110 Start value of voltage for harmOvLoad inIDMT stage in %

kHOLIDMT 0.50 - 1.50 - 0.01 1.00 Time multiplier for harmonic overloadIDMT curve

tMaxHOLIDMT 0.05 - 6000.00 s 0.01 2000.00 Maximum trip delay for harmonic overload

tMinHOLIDMT 0.05 - 60.00 s 0.01 0.10 Minimum trip delay for harmonic overload

3.7 Voltage protection

3.7.1 Two step undervoltage protection UV2PTUV

Section 3 1MRK 505 211-UEN C

IED application

206

 Application manual

Page 213: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 213/457

Function description IEC 61850

identification

IEC 60617

identification

ANSI/IEEE C37.2

device number

Two step undervoltage protection UV2PTUV

3U<

SYMBOL-R-2U-GREATER-THANV2 EN

27

3.7.1.1 Setting guidelines

All the voltage conditions in the system where UV2PTUV performs its functionsshould be considered. The same also applies to the associated equipment, itsvoltage and time characteristic.

There is a very wide application area where general undervoltage functions are

used. All voltage related settings are made as a percentage of the settings basevoltage UBase and base current IBase, which normally is set to the primary ratedvoltage level (phase-to-phase) of the power system or the high voltage equipmentunder consideration.

The setting for UV2PTUV is normally not critical, since there must be enough timeavailable for the main protection to clear short circuits and earth faults.

Some applications and related setting guidelines for the voltage level are describedin the following sections.

Equipment protection, such as for motors and generators

The setting must be below the lowest occurring "normal" voltage and above thelowest acceptable voltage for the equipment.

Disconnected equipment detectionThe setting must be below the lowest occurring "normal" voltage and above thehighest occurring voltage, caused by inductive or capacitive coupling, when theequipment is disconnected.

Power supply qualityThe setting must be below the lowest occurring "normal" voltage and above thelowest acceptable voltage, due to regulation, good practice or other agreements.

Voltage instability mitigationThis setting is very much dependent on the power system characteristics, andthorough studies have to be made to find the suitable levels.

Backup protection for power system faultsThe setting must be below the lowest occurring "normal" voltage and above thehighest occurring voltage during the fault conditions under consideration.

Settings for Two step undervoltage protectionThe following settings can be done for Two step undervoltage protection UV2PTUV:

1MRK 505 211-UEN C Section 3IED application

207

 Application manual

Page 214: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 214/457

ConnType: Sets whether the measurement shall be phase-to-earth fundamentalvalue, phase-to-phase fundamental value, phase-to-earth RMS value or phase-to-

 phase RMS value.

Operation: Off or On.

UBase: Base voltage phase-to-phase in primary kV. This voltage is used asreference for voltage setting. UV2PTUV measures selectively phase-to-earthvoltages, or phase-to-phase voltage chosen by the setting ConnType. The functionwill operate if the voltage gets lower than the set percentage of UBase. WhenConnType is set to PhN DFT or  PhN RMS then the IED automatically divides setvalue for UBase by √3. UBase is used when ConnType is set to PhPh DFT or  PhPh

 RMS . Therefore, always set UBase as rated primary phase-to-phase voltage of the protected object. This means operation for phase-to-earth voltage under:

(%) ( ) 3U UBase kV  < ×EQUATION1447 V1 EN (Equation 81)

and operation for phase-to-phase voltage under:

U (%) UBase(kV)< ×

EQUATION1990 V1 EN (Equation 82)

The below described setting parameters are identical for the two steps (n = 1 or 2).Therefore, the setting parameters are described only once.

Characteristicn: This parameter gives the type of time delay to be used. The settingcan be Definite time, Inverse Curve A, Inverse Curve B, Prog. inv. curve. Theselection is dependent on the protection application.

OpModen: This parameter describes how many of the three measured voltages thatshould be below the set level to give operation for step n. The setting can be 1 out 

of 3, 2 out of 3 or 3 out of 3. In most applications, it is sufficient that one phasevoltage is low to give operation. If UV2PTUV shall be insensitive for single phase-to-earth faults, 2 out of 3 can be chosen. In subtransmission and transmissionnetworks the undervoltage function is mainly a system supervision function and 3out of 3 is selected.

Un<: Set operate undervoltage operation value for step n, given as % of the parameter UBase. The setting is highly dependent of the protection application. Itis essential to consider the minimum voltage at non-faulted situations. Normallythis voltage is larger than 90% of nominal voltage.

tn: time delay of step n, given in s. This setting is dependent of the protectionapplication. In many applications the protection function shall not directly tripwhen there is a short circuit or earth faults in the system. The time delay must becoordinated to the short circuit protections.

Section 3 1MRK 505 211-UEN C

IED application

208

 Application manual

Page 215: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 215/457

tResetn: Reset time for step n if definite time delay is used, given in s. The defaultvalue is 25 ms.

tnMin: Minimum operation time for inverse time characteristic for step n, given in

s. When using inverse time characteristic for the undervoltage function during verylow voltages can give a short operation time. This might lead to unselective trip.By setting t1Min longer than the operation time for other protections suchunselective tripping can be avoided.

 ResetTypeCrvn: This parameter for inverse time characteristic can be set to Instantaneous, Frozen time, Linearly decreased . The default settingis Instantaneous.

tIResetn: Reset time for step n if inverse time delay is used, given in s. The defaultvalue is 25 ms.

kn: Time multiplier for inverse time characteristic. This parameter is used for coordination between different inverse time delayed undervoltage protections.

 ACrvn, BCrvn, CCrvn, DCrvn, PCrvn: Parameters to set to create programmableunder voltage inverse time characteristic. Description of this can be found in thetechnical reference manual.

CrvSatn: When the denominator in the expression of the programmable curve isequal to zero the time delay will be infinity. There will be an undesireddiscontinuity. Therefore, a tuning parameter CrvSatn is set to compensate for this

 phenomenon. In the voltage interval Un< down to Un< · (1.0 - CrvSatn/100) theused voltage will be: Un< · (1.0 - CrvSatn/100). If the programmable curve is usedthis parameter must be calculated so that:

0100

CrvSatn B C × - >

EQUATION1448 V1 EN (Equation 83)

 IntBlkSeln: This parameter can be set to Off , Block of trip, Block all . In case of alow voltage the undervoltage function can be blocked. This function can be used to

 prevent function when the protected object is switched off. If the parameter is set Block of trip or  Block all unwanted trip is prevented.

 IntBlkStValn: Voltage level under which the blocking is activated set in % of UBase. This setting must be lower than the setting Un<. As switch of shall bedetected the setting can be very low, that is, about 10%.

tBlkUVn: Time delay to block the undervoltage step n when the voltage level is below IntBlkStValn, given in s. It is important that this delay is shorter than theoperate time delay of the undervoltage protection step.

1MRK 505 211-UEN C Section 3IED application

209

 Application manual

Page 216: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 216/457

3.7.1.2 Setting parameters

Table 77: UV2PTUV Group settings (basic)

Name Values (Range) Unit Step Default Description

Operation Off  On

- - Off Operation Off / On

UBase 0.05 - 2000.00 kV 0.05 400.00 Base voltage

OperationStep1 Off  On

- - On Enable execution of step 1

Characterist1 Definite timeInverse curve AInverse curve BProg. inv. curve

- - Definite time Selection of time delay curve type for  step 1

OpMode1 1 out of 32 out of 33 out of 3

- - 1 out of 3 Number of phases required for op (1 of  3, 2 of 3, 3 of 3) from step 1

U1< 1 - 100 %UB 1 70 Voltage setting/start val (DT & IDMT) in% of UBase, step 1

t1 0.00 - 6000.00 s 0.01 5.00 Definitive time delay of step 1

t1Min 0.000 - 60.000 s 0.001 5.000 Minimum operate time for inverse curvesfor step 1

k1 0.05 - 1.10 - 0.01 0.05 Time multiplier for the inverse time delayfor step 1

IntBlkSel1 Off  Block of tripBlock all

- - Off Internal (low level) blocking mode, step 1

IntBlkStVal1 1 - 100 %UB 1 20 Voltage setting for internal blocking in %of UBase, step 1

tBlkUV1 0.000 - 60.000 s 0.001 0.000 Time delay of internal (low level)blocking for step 1

HystAbs1 0.0 - 100.0 %UB 0.1 0.5 Absolute hysteresis in % of UBase, step 1

OperationStep2 Off  On

- - On Enable execution of step 2

Characterist2 Definite timeInverse curve AInverse curve BProg. inv. curve

- - Definite time Selection of time delay curve type for  step 2

OpMode2 1 out of 32 out of 33 out of 3

- - 1 out of 3 Number of phases required for op (1 of  3, 2 of 3, 3 of 3) from step 2

U2< 1 - 100 %UB 1 50 Voltage setting/start val (DT & IDMT) in% of UBase, step 2

t2 0.000 - 60.000 s 0.001 5.000 Definitive time delay of step 2

t2Min 0.000 - 60.000 s 0.001 5.000 Minimum operate time for inverse curvesfor step 2

k2 0.05 - 1.10 - 0.01 0.05 Time multiplier for the inverse time delayfor step 2

IntBlkSel2 Off  Block of tripBlock all

- - Off Internal (low level) blocking mode, step 2

Table continues on next page

Section 3 1MRK 505 211-UEN C

IED application

210

 Application manual

Page 217: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 217/457

Name Values (Range) Unit Step Default Description

IntBlkStVal2 1 - 100 %UB 1 20 Voltage setting for internal blocking in %of UBase, step 2

tBlkUV2 0.000 - 60.000 s 0.001 0.000 Time delay of internal (low level)

blocking for step 2

HystAbs2 0.0 - 100.0 %UB 0.1 0.5 Absolute hysteresis in % of UBase, step 2

Table 78: UV2PTUV Group settings (advanced)

Name Values (Range) Unit Step Default Description

tReset1 0.000 - 60.000 s 0.001 0.025 Reset time delay used in IEC DefiniteTime curve step 1

ResetTypeCrv1 InstantaneousFrozen timer Linearly decreased

- - Instantaneous Selection of used IDMT reset curve typefor step 1

tIReset1 0.000 - 60.000 s 0.001 0.025 Time delay in IDMT reset (s), step 1

 ACrv1 0.005 - 200.000 - 0.001 1.000 Parameter A for customer programmablecurve for step 1

BCrv1 0.50 - 100.00 - 0.01 1.00 Parameter B for customer programmablecurve for step 1

CCrv1 0.0 - 1.0 - 0.1 0.0 Parameter C for customer  programmable curve for step 1

DCrv1 0.000 - 60.000 - 0.001 0.000 Parameter D for customer  programmable curve for step 1

PCrv1 0.000 - 3.000 - 0.001 1.000 Parameter P for customer programmablecurve for step 1

CrvSat1 0 - 100 % 1 0 Tuning param for prog. under voltage

IDMT curve, step 1

tReset2 0.000 - 60.000 s 0.001 0.025 Reset time delay used in IEC DefiniteTime curve step 2

ResetTypeCrv2 InstantaneousFrozen timer Linearly decreased

- - Instantaneous Selection of used IDMT reset curve typefor step 2

tIReset2 0.000 - 60.000 s 0.001 0.025 Time delay in IDMT reset (s), step 2

 ACrv2 0.005 - 200.000 - 0.001 1.000 Parameter A for customer programmablecurve for step 2

BCrv2 0.50 - 100.00 - 0.01 1.00 Parameter B for customer programmablecurve for step 2

CCrv2 0.0 - 1.0 - 0.1 0.0 Parameter C for customer  programmable curve for step 2

DCrv2 0.000 - 60.000 - 0.001 0.000 Parameter D for customer  programmable curve for step 2

PCrv2 0.000 - 3.000 - 0.001 1.000 Parameter P for customer programmablecurve for step 2

CrvSat2 0 - 100 % 1 0 Tuning param for prog. under voltageIDMT curve, step 2

1MRK 505 211-UEN C Section 3IED application

211

 Application manual

Page 218: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 218/457

Table 79: UV2PTUV Non group settings (basic)

Name Values (Range) Unit Step Default Description

ConnType PhN DFTPhPh RMS

PhN RMSPhPh DFT

- - PhN DFT Group selector for connection type

3.7.2 Two step overvoltage protection OV2PTOV

Function description IEC 61850

identification

IEC 60617

identification

ANSI/IEEE C37.2

device number

Two step overvoltage protection OV2PTOV

3U>

SYMBOL-C-2U-SMALLER-THANV2 EN

59

3.7.2.1 Application

Two step overvoltage protection OV2PTOV is applicable in all situations, wherereliable detection of high voltage is necessary. OV2PTOV is used for supervisionand detection of abnormal conditions, which, in combination with other protectionfunctions, increase the security of a complete protection system.

High overvoltage conditions are caused by abnormal situations in the power system. OV2PTOV is applied to power system elements, such as generators,transformers, motors and power lines in order to detect high voltage conditions.OV2PTOV is used in combination with low current signals, to identify atransmission line, open in the remote end. In addition to that, OV2PTOV is alsoused to initiate voltage correction measures, like insertion of shunt reactors, tocompensate for low load, and thereby decreasing the voltage. The function has ahigh measuring accuracy and hysteresis setting to allow applications to controlreactive load.

OV2PTOV is used to disconnect apparatuses, like electric motors, which will bedamaged when subject to service under high voltage conditions. It deals with high

voltage conditions at power system frequency, which can be caused by:1. Different kinds of faults, where a too high voltage appears in a certain power 

system, like metallic connection to a higher voltage level (broken conductor 

Section 3 1MRK 505 211-UEN C

IED application

212

 Application manual

Page 219: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 219/457

falling down to a crossing overhead line, transformer flash over fault from thehigh voltage winding to the low voltage winding and so on).

2. Malfunctioning of a voltage regulator or wrong settings under manual control(symmetrical voltage decrease).

3. Low load compared to the reactive power generation (symmetrical voltagedecrease).

4. Earth-faults in high impedance earthed systems causes, beside the high voltagein the neutral, high voltages in the two non-faulted phases, (unsymmetricalvoltage increase).

OV2PTOV prevents sensitive equipment from running under conditions that couldcause their overheating or stress of insulation material, and, thus, shorten their lifetime expectancy. In many cases, it is a useful function in circuits for local or remote automation processes in the power system.

3.7.2.2 Setting guidelines

The parameters for Two step overvoltage protection (OV2PTOV) are set via thelocal HMI or PCM600.

All the voltage conditions in the system where OV2PTOV performs its functionsshould be considered. The same also applies to the associated equipment, itsvoltage and time characteristic.

There is a very wide application area where general overvoltage functions are used.All voltage related settings are made as a percentage of a settable base primary

voltage, which normally is set to the nominal voltage level (phase-to-phase) of the power system or the high voltage equipment under consideration.

The time delay for the OV2PTOV can sometimes be critical and related to the sizeof the overvoltage - a power system or a high voltage component can withstandsmaller overvoltages for some time, but in case of large overvoltages the relatedequipment should be disconnected more rapidly.

Some applications and related setting guidelines for the voltage level are given below:

Equipment protection, such as for motors, generators, reactors and

transformers

High voltage will cause overexcitation of the core and deteriorate the windinginsulation. The setting has to be well above the highest occurring "normal" voltageand well below the highest acceptable voltage for the equipment.

Equipment protection, capacitorsHigh voltage will deteriorate the dielectricum and the insulation. The setting has to

 be well above the highest occurring "normal" voltage and well below the highestacceptable voltage for the capacitor.

1MRK 505 211-UEN C Section 3IED application

213

 Application manual

Page 220: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 220/457

Page 221: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 221/457

 phases at single phase-to-earth faults. In subtransmission and transmissionnetworks the UV function is mainly a system supervision function and 3 out of 3 isselected.

Un>: Set operate overvoltage operation value for step n, given as % of UBase. Thesetting is highly dependent of the protection application. Here it is essential toconsider the maximum voltage at non-faulted situations. Normally this voltage isless than 110% of nominal voltage.

tn: time delay of step n, given in s. The setting is highly dependent of the protectionapplication. In many applications the protection function is used to preventdamages to the protected object. The speed might be important for example in caseof protection of transformer that might be overexcited. The time delay must be co-ordinated with other automated actions in the system.

tResetn: Reset time for step n if definite time delay is used, given in s. The defaultvalue is 25 ms.

tnMin: Minimum operation time for inverse time characteristic for step n, given ins. For very high voltages the overvoltage function, using inverse timecharacteristic, can give very short operation time. This might lead to unselectivetrip. By setting t1Min longer than the operation time for other protections suchunselective tripping can be avoided.

 ResetTypeCrvn: This parameter for inverse time characteristic can be set: Instantaneous, Frozen time, Linearly decreased . The default setting is Instantaneous.

tIResetn: Reset time for step n if inverse time delay is used, given in s. The defaultvalue is 25 ms.

kn: Time multiplier for inverse time characteristic. This parameter is used for co-ordination between different inverse time delayed undervoltage protections.

 ACrvn, BCrvn, CCrvn, DCrvn, PCrvn: Parameters to set to create programmableunder voltage inverse time characteristic. Description of this can be found in thetechnical reference manual.

CrvSatn: When the denominator in the expression of the programmable curve isequal to zero the time delay will be infinity. There will be an undesireddiscontinuity. Therefore a tuning parameter CrvSatn is set to compensate for this

 phenomenon. In the voltage interval Un> up to Un> · (1.0 + CrvSatn/100) the usedvoltage will be: Un> · (1.0 + CrvSatn/100). If the programmable curve is used, this

 parameter must be calculated so that:

0100

CrvSatn B C × - >

EQUATION1448 V1 EN (Equation 86)

1MRK 505 211-UEN C Section 3IED application

215

 Application manual

Page 222: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 222/457

 HystAbsn: Absolute hysteresis set in % of UBase. The setting of this parameter ishighly dependent of the application. If the function is used as control for automaticswitching of reactive compensation devices the hysteresis must be set smaller thanthe voltage change after switching of the compensation device.

3.7.2.3 Setting parameters

Table 80: OV2PTOV Group settings (basic)

Name Values (Range) Unit Step Default Description

Operation Off  On

- - Off Operation Off / On

UBase 0.05 - 2000.00 kV 0.05 400.00 Base voltage

OperationStep1 Off  On

- - On Enable execution of step 1

Characterist1 Definite timeInverse curve AInverse curve BInverse curve CProg. inv. curve

- - Definite time Selection of time delay curve type for  step 1

OpMode1 1 out of 32 out of 33 out of 3

- - 1 out of 3 Number of phases required for op (1 of  3, 2 of 3, 3 of 3) from step 1

U1> 1 - 200 %UB 1 120 Voltage setting/start val (DT & IDMT) in% of UBase, step 1

t1 0.00 - 6000.00 s 0.01 5.00 Definitive time delay of step 1

t1Min 0.000 - 60.000 s 0.001 5.000 Minimum operate time for inverse curvesfor step 1

k1 0.05 - 1.10 - 0.01 0.05 Time multiplier for the inverse time delayfor step 1

HystAbs1 0.0 - 100.0 %UB 0.1 0.5 Absolute hysteresis in % of UBase, step 1

OperationStep2 Off  On

- - On Enable execution of step 2

Characterist2 Definite timeInverse curve AInverse curve BInverse curve CProg. inv. curve

- - Definite time Selection of time delay curve type for  step 2

OpMode2 1 out of 32 out of 33 out of 3

- - 1 out of 3 Number of phases required for op (1 of  3, 2 of 3, 3 of 3) from step 2

U2> 1 - 200 %UB 1 150 Voltage setting/start val (DT & IDMT) in% of UBase, step 2

t2 0.000 - 60.000 s 0.001 5.000 Definitive time delay of step 2

t2Min 0.000 - 60.000 s 0.001 5.000 Minimum operate time for inverse curvesfor step 2

k2 0.05 - 1.10 - 0.01 0.05 Time multiplier for the inverse time delayfor step 2

HystAbs2 0.0 - 100.0 %UB 0.1 0.5 Absolute hysteresis in % of UBase, step 2

Section 3 1MRK 505 211-UEN C

IED application

216

 Application manual

Page 223: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 223/457

Page 224: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 224/457

3.7.3 Two step residual overvoltage protection ROV2PTOV

Function description IEC 61850

identification

IEC 60617

identification

ANSI/IEEE C37.2

device number

Two step residual overvoltageprotection

ROV2PTOV

3U0

TRV V1 EN

59N

3.7.3.1 Application

Two step residual overvoltage protection ROV2PTOV is primarily used in highimpedance earthed distribution networks, mainly as a backup for the primary earth-fault protection of the feeders and the transformer. To increase the security for 

different earth-fault related functions, the residual overvoltage signal can be usedas a release signal. The residual voltage can be measured either at the transformer neutral or from a voltage transformer open delta connection. The residual voltagecan also be calculated internally, based on measurement of the three-phase voltages.

In high impedance earthed systems the residual voltage will increase in case of anyfault connected to earth. Depending on the type of fault and fault resistance theresidual voltage will reach different values. The highest residual voltage, equal tothree times the phase-to-earth voltage, is achieved for a single phase-to-earth fault.The residual voltage increases approximately to the same level in the whole systemand does not provide any guidance in finding the faulted component. Therefore,ROV2PTOV is often used as a backup protection or as a release signal for the

feeder earth-fault protection.

3.7.3.2 Setting guidelines

All the voltage conditions in the system where ROV2PTOV performs its functionsshould be considered. The same also applies to the associated equipment, itsvoltage and time characteristic.

There is a very wide application area where general single input or residualovervoltage functions are used. All voltage related settings are made as a

 percentage of a settable base voltage, which can be set to the primary nominal

voltage (phase-phase) level of the power system or the high voltage equipmentunder consideration.

The time delay for ROV2PTOV is seldom critical, since residual voltage is relatedto earth-faults in a high impedance earthed system, and enough time must normally

 be given for the primary protection to clear the fault. In some more specificsituations, where the single overvoltage protection is used to protect some specificequipment, the time delay is shorter.

Some applications and related setting guidelines for the residual voltage level aregiven below.

Section 3 1MRK 505 211-UEN C

IED application

218

 Application manual

Page 225: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 225/457

Equipment protection, such as for motors, generators, reactors and

transformersHigh residual voltage indicates earth-fault in the system, perhaps in the componentto which Two step residual overvoltage protection (ROV2PTOV) is connected. For selectivity reasons to the primary protection for the faulted device ROV2PTOVmust trip the component with some time delay. The setting must be above thehighest occurring "normal" residual voltage and below the highest acceptableresidual voltage for the equipment

Equipment protection, capacitorsHigh voltage will deteriorate the dielectric and the insulation. Two step residualovervoltage protection (ROV2PTOV) has to be connected to a neutral or open deltawinding. The setting must be above the highest occurring "normal" residual voltageand below the highest acceptable residual voltage for the capacitor.

Power supply qualityThe setting must be above the highest occurring "normal" residual voltage and

 below the highest acceptable residual voltage, due to regulation, good practice or other agreements.

High impedance earthed systemsIn high impedance earthed systems, earth faults cause a neutral voltage in thefeeding transformer neutral. Two step residual overvoltage protection ROV2PTOVis used to trip the transformer, as a backup protection for the feeder earth-fault

 protection, and as a backup for the transformer primary earth-fault protection. Thesetting must be above the highest occurring "normal" residual voltage, and below

the lowest occurring residual voltage during the faults under consideration. Ametallic single-phase earth fault causes a transformer neutral to reach a voltageequal to the nominal phase-to-earth voltage.

The voltage transformers measuring the phase-to-earth voltages measure zerovoltage in the faulty phase. The two healthy phases will measure full phase-to-

 phase voltage, as the faulty phase will be connected to earth. The residualovervoltage will be three times the phase-to-earth voltage. See figure 80.

1MRK 505 211-UEN C Section 3IED application

219

 Application manual

Page 226: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 226/457

IEC07000190 V1 EN

Figure 80: Earth fault in Non-effectively earthed systems 

Direct earthed systemIn direct earthed systems, an earth fault on one phase indicates a voltage collapse inthat phase. The two healthy phases will have normal phase-to-earth voltages. Theresidual sum will have the same value as the remaining phase-to-earth voltage. Seefigure 81.

Section 3 1MRK 505 211-UEN C

IED application

220

 Application manual

Page 227: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 227/457

IEC07000189 V1 EN

Figure 81: Earth fault in Direct earthed system 

Settings for Two step residual overvoltage protectionOperation: Off or On

UBase is used as voltage reference for the voltage. The voltage can be fed to theIED in different ways:

1. The IED is fed from a normal voltage transformer group where the residualvoltage is calculated internally from the phase-to-earth voltages within the

 protection. The setting of the analog input is given as UBase=Uph-ph.2. The IED is fed from a broken delta connection normal voltage transformer 

group. In an open delta connection the protection is fed by the voltage 3U0(single input). The Setting chapter in the application manual explains how theanalog input needs to be set.

3. The IED is fed from a single voltage transformer connected to the neutral point

of a power transformer in the power system. In this connection the protectionis fed by the voltage UN=U0 (single input). The Setting chapter in theapplication manual explains how the analog input needs to be set.ROV2PTOV will measure the residual voltage corresponding nominal phase-to-earth voltage for a high impedance earthed system. The measurement will be

 based on the neutral voltage displacement.

The below described setting parameters are identical for the two steps (n = step 1and 2). Therefore the setting parameters are described only once.

1MRK 505 211-UEN C Section 3IED application

221

 Application manual

Page 228: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 228/457

Characteristicn: Selected inverse time characteristic for step n. This parameter gives the type of time delay to be used. The setting can be, Definite time or  Inverse

curve A or  Inverse curve B or  Inverse curve C or  Prog. inv. curve. The choice ishighly dependent of the protection application.

Un>: Set operate overvoltage operation value for step n, given as % of residualvoltage corresponding to UBase:

( ) ( )% 3U UBase kV  > ×

IECEQUATION2290 V1 EN (Equation 87)

The setting is dependent of the required sensitivity of the protection and the systemearthing. In non-effectively earthed systems the residual voltage can be maximumthe rated phase-to-earth voltage, which should correspond to 100%.

In effectively earthed systems this value is dependent of the ratio Z0/Z1. Therequired setting to detect high resistive earth-faults must be based on network calculations.

tn: time delay of step n, given in s. The setting is highly dependent of the protectionapplication. In many applications, the protection function has the task to preventdamages to the protected object. The speed might be important for example in caseof protection of transformer that might be overexcited. The time delay must be co-ordinated with other automated actions in the system.

tResetn: Reset time for step n if definite time delay is used, given in s. The defaultvalue is 25 ms.

tnMin: Minimum operation time for inverse time characteristic for step n, given ins. For very high voltages the overvoltage function, using inverse timecharacteristic, can give very short operation time. This might lead to unselectivetrip. By setting t1Min longer than the operation time for other protections suchunselective tripping can be avoided.

 ResetTypeCrvn: Set reset type curve for step n. This parameter can be set: Instantaneous, Frozen time, Linearly decreased . The default setting is Instantaneous.

tIResetn: Reset time for step n if inverse time delay is used, given in s. The defaultvalue is 25 ms.

kn: Time multiplier for inverse time characteristic. This parameter is used for co-ordination between different inverse time delayed undervoltage protections.

 ACrvn, BCrvn, CCrvn, DCrvn, PCrvn: Parameters for step n, to set to create programmable undervoltage inverse time characteristic. Description of this can befound in the technical reference manual.

CrvSatn: Set tuning parameter for step n. When the denominator in the expressionof the programmable curve is equal to zero the time delay will be infinity. Therewill be an undesired discontinuity. Therefore, a tuning parameter CrvSatn is set tocompensate for this phenomenon. In the voltage interval U> up to U> · (1.0 +

Section 3 1MRK 505 211-UEN C

IED application

222

 Application manual

Page 229: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 229/457

CrvSatn/100) the used voltage will be: U> · (1.0 + CrvSatn/100). If the programmable curve is used this parameter must be calculated so that:

0100CrvSatn

 B C × - >EQUATION1448 V1 EN (Equation 88)

 HystAbsn: Absolute hysteresis for step n, set in % of UBase. The setting of this parameter is highly dependent of the application.

3.7.3.3 Setting parameters

Table 83: ROV2PTOV Group settings (basic)

Name Values (Range) Unit Step Default Description

Operation Off  On

- - Off Operation Off / On

UBase 0.05 - 2000.00 kV 0.05 400.00 Base voltage

OperationStep1 Off  On

- - On Enable execution of step 1

Characterist1 Definite timeInverse curve AInverse curve BInverse curve CProg. inv. curve

- - Definite time Selection of time delay curve type for  step 1

U1> 1 - 200 %UB 1 30 Voltage setting/start val (DT & IDMT),step 1 in % of UBase

t1 0.00 - 6000.00 s 0.01 5.00 Definitive time delay of step 1t1Min 0.000 - 60.000 s 0.001 5.000 Minimum operate time for inverse curves

for step 1

k1 0.05 - 1.10 - 0.01 0.05 Time multiplier for the inverse time delayfor step 1

HystAbs1 0.0 - 100.0 %UB 0.1 0.5 Absolute hysteresis in % of UBase, step 1

OperationStep2 Off  On

- - On Enable execution of step 2

Characterist2 Definite timeInverse curve AInverse curve BInverse curve CProg. inv. curve

- - Definite time Selection of time delay curve type for  step 2

U2> 1 - 100 %UB 1 45 Voltage setting/start val (DT & IDMT),step 2 in % of UBase

t2 0.000 - 60.000 s 0.001 5.000 Definitive time delay of step 2

t2Min 0.000 - 60.000 s 0.001 5.000 Minimum operate time for inverse curvesfor step 2

k2 0.05 - 1.10 - 0.01 0.05 Time multiplier for the inverse time delayfor step 2

HystAbs2 0.0 - 100.0 %UB 0.1 0.5 Absolute hysteresis in % of UBase, step 2

1MRK 505 211-UEN C Section 3IED application

223

 Application manual

Page 230: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 230/457

Table 84: ROV2PTOV G roup settings (advanced)

Name Values (Range) Unit Step Default Description

tReset1 0.000 - 60.000 s 0.001 0.025 Reset time delay used in IEC DefiniteTime curve step 1

ResetTypeCrv1 InstantaneousFrozen timer Linearly decreased

- - Instantaneous Selection of used IDMT reset curve typefor step 1

tIReset1 0.000 - 60.000 s 0.001 0.025 Time delay in IDMT reset (s), step 1

 ACrv1 0.005 - 200.000 - 0.001 1.000 Parameter A for customer programmablecurve for step 1

BCrv1 0.50 - 100.00 - 0.01 1.00 Parameter B for customer programmablecurve for step 1

CCrv1 0.0 - 1.0 - 0.1 0.0 Parameter C for customer  programmable curve for step 1

DCrv1 0.000 - 60.000 - 0.001 0.000 Parameter D for customer  programmable curve for step 1

PCrv1 0.000 - 3.000 - 0.001 1.000 Parameter P for customer programmablecurve for step 1

CrvSat1 0 - 100 % 1 0 Tuning param for prog. over voltageIDMT curve, step 1

tReset2 0.000 - 60.000 s 0.001 0.025 Time delay in DT reset (s), step 2

ResetTypeCrv2 InstantaneousFrozen timer Linearly decreased

- - Instantaneous Selection of used IDMT reset curve typefor step 2

tIReset2 0.000 - 60.000 s 0.001 0.025 Time delay in IDMT reset (s), step 2

 ACrv2 0.005 - 200.000 - 0.001 1.000 Parameter A for customer programmablecurve for step 2

BCrv2 0.50 - 100.00 - 0.01 1.00 Parameter B for customer programmablecurve for step 2

CCrv2 0.0 - 1.0 - 0.1 0.0 Parameter C for customer  programmable curve for step 2

DCrv2 0.000 - 60.000 - 0.001 0.000 Parameter D for customer  programmable curve for step 2

PCrv2 0.000 - 3.000 - 0.001 1.000 Parameter P for customer programmablecurve for step 2

CrvSat2 0 - 100 % 1 0 Tuning param for prog. over voltageIDMT curve, step 2

3.7.4 Voltage differential protection VDCPTOV

Function description IEC 61850

identification

IEC 60617

identification

ANSI/IEEE C37.2

device number

Voltage differential protection VDCPTOV - 60

Section 3 1MRK 505 211-UEN C

IED application

224

 Application manual

Page 231: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 231/457

3.7.4.1 Application

The Voltage differential protection VDCPTOV functions can be used in somedifferent applications.

• Voltage unbalance protection for capacitor banks. The voltage on the bus issupervised with the voltage in the capacitor bank, phase- by phase. Differenceindicates a fault, either short-circuited or open element in the capacitor bank. Itis mainly used on elements with external fuses but can also be used onelements with internal fuses instead of a current unbalance protectionmeasuring the current between the neutrals of two half’s of the capacitor bank.The function requires voltage transformers in all phases of the capacitor bank.Figure 82 shows some different alternative connections of this function.

Ud>L1

Ph L2Ph L3

U1

U2

Ud>L1

Ph L2Ph L3

U1 U2

Ph L3 Ph L2

Single earthed wye

Double wye

IEC06000390_1_en.vsd

IEC06000390 V3 EN

Figure 82: Connection of voltage differential protection VDCPTOV function to 

detect unbalance in capacitor banks (one phase only is shown) 

VDCPTOV function has a block input (BLOCK) where a fuse failure supervision(or MCB tripped) can be connected to prevent problems if one fuse in the capacitor 

 bank voltage transformer set has opened and not the other (capacitor voltage isconnected to input U2). It will also ensure that a fuse failure alarm is given insteadof a Undervoltage or Differential voltage alarm and/or tripping.

1MRK 505 211-UEN C Section 3IED application

225

 Application manual

Page 232: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 232/457

3.7.4.2 Setting guidelines

The parameters for the voltage differential function are set via the local HMI or PCM600.

The following settings are done for the voltage differential function.

Operation: Off /On

UBase: Base voltage level in kV. The base voltage is used as reference for thevoltage setting factors. Normally, it is set to the system voltage level.

 BlkDiffAtULow: The setting is to block the function when the voltages in the phases are low.

 RFLx: Is the setting of the voltage ratio compensation factor where possible

differences between the voltages is compensated for. The differences can be due todifferent voltage transformer ratios, different voltage levels e.g. the voltagemeasurement inside the capacitor bank can have a different voltage level but thedifference can also e.g. be used by voltage drop in the secondary circuits. Thesetting is normally done at site by evaluating the differential voltage achieved as aservice value for each phase. The factor is defined as U2 · RFLx and shall be equalto the U1 voltage. Each phase has its own ratio factor.

UDTrip: The voltage differential level required for tripping is set with this parameter. For application on capacitor banks the setting will depend of thecapacitor bank voltage and the number of elements per phase in series and parallel.Capacitor banks must be tripped before excessive voltage occurs on the healthycapacitor elements. The setting values required are normally given by the capacitor 

 bank supplier. For other applications it has to be decided case by case. For fusesupervision normally only the alarm level is used.

tTrip: The time delay for tripping is set by this parameter. Normally, the delay doesnot need to be so short in capacitor bank applications as there is no fault requiringurgent tripping.

tReset : The time delay for reset of tripping level element is set by this parameter. Normally, it can be set to a short delay as faults are permanent when they occur.

For the advanced users following parameters are also available for setting. Defaultvalues are here expected to be acceptable.

U1Low: The setting of the undervoltage level for the first voltage input is decided by this parameter. The proposed default setting is 70%.

U2Low: The setting of the undervoltage level for the second voltage input isdecided by this parameter. The proposed default setting is 70%.

tBlock : The time delay for blocking of the function at detected undervoltages is set by this parameter.

Section 3 1MRK 505 211-UEN C

IED application

226

 Application manual

Page 233: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 233/457

Page 234: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 234/457

3.7.5 Loss of voltage check LOVPTUV

Function description IEC 61850

identification

IEC 60617

identification

ANSI/IEEE C37.2

device number

Loss of voltage check LOVPTUV - 27

3.7.5.1 Application

The trip of the circuit breaker at a prolonged loss of voltage at all the three phasesis normally used in automatic restoration systems to facilitate the systemrestoration after a major blackout. Loss of voltage check (LOVPTUV) generates aTRIP signal only if the voltage in all the three phases is low for more than the settime. If the trip to the circuit breaker is not required, LOVPTUV is used for signallization only through an output contact or through the event recording function.

3.7.5.2 Setting guidelines

Loss of voltage check (LOVPTUV) is in principle independent of the protectionfunctions. It requires to be set to open the circuit breaker in order to allow a simplesystem restoration following a main voltage loss of a big part of the network andonly when the voltage is lost with breakers still closed.

All settings are in primary values or per unit. Set UBase to rated voltage of thesystem or the voltage transformer primary rated voltage. Set operating level per 

 phase UPE to typically 70% of rated UBase level. Set the time delay tTrip=5-20

seconds.

Advanced users settingsFor advanced users the following parameters need also to be set. Set the length of the trip pulse to typical tPulse=0.15 sec. Set the blocking time tBlock to block Loss of voltage check (LOVPTUV), if some but not all voltage are low, to typical5.0 seconds and set the time delay for enabling the function after restorationtRestore to 3 - 40 seconds.

3.7.5.3 Setting parameters

Table 87: LOVPTUV Group settings (basic)

Name Values (Range) Unit Step Default Description

Operation Off  On

- - Off Operation Off/On

UBase 0.1 - 9999.9 kV 0.1 400.0 Base voltage

UPE 1 - 100 %UB 1 70 Operate voltagein% of base voltageUbase

tTrip 0.000 - 60.000 s 0.001 7.000 Operate time delay

Section 3 1MRK 505 211-UEN C

IED application

228

 Application manual

Page 235: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 235/457

Table 88: LOVPTUV Group settings (advanced)

Name Values (Range) Unit Step Default Description

tPulse 0.050 - 60.000 s 0.001 0.150 Duration of TRIP pulse

tBlock 0.000 - 60.000 s 0.001 5.000 Time delay to block when all 3phvoltages are not low

tRestore 0.000 - 60.000 s 0.001 3.000 Time delay for enable the function after  restoration

3.8 Frequency protection

3.8.1 Underfrequency protection SAPTUF

3.8.1.1 Setting guidelines

All the frequency and voltage magnitude conditions in the system where SAPTUF performs its functions should be considered. The same also applies to theassociated equipment, its frequency and time characteristic.

There are especially two specific application areas for SAPTUF:

1. to protect equipment against damage due to low frequency, such as generators,transformers, and motors. Overexcitation is also related to low frequency

2. to protect a power system, or a part of a power system, against breakdown, by

shedding load, in generation deficit situations.

The underfrequency START value is set in Hz. All voltage magnitude relatedsettings are made as a percentage of a settable base voltage, which normally is setto the nominal primary voltage level (phase-phase) of the power system or the highvoltage equipment under consideration.

Some applications and related setting guidelines for the frequency level are given below:

Equipment protection, such as for motors and generators

The setting has to be well below the lowest occurring "normal" frequency and wellabove the lowest acceptable frequency for the equipment.

Power system protection, by load shedding

The setting has to be below the lowest occurring "normal" frequency and wellabove the lowest acceptable frequency for power stations, or sensitive loads. Thesetting level, the number of levels and the distance between two levels (in time and/or in frequency) depends very much on the characteristics of the power systemunder consideration. The size of the "largest loss of production" compared to "thesize of the power system" is a critical parameter. In large systems, the load

1MRK 505 211-UEN C Section 3IED application

229

 Application manual

Page 236: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 236/457

shedding can be set at a fairly high frequency level, and the time delay is normallynot critical. In smaller systems the frequency START level has to be set at a lower value, and the time delay must be rather short.

The voltage related time delay is used for load shedding. The settings of SAPTUFcould be the same all over the power system. The load shedding is then performedfirstly in areas with low voltage magnitude, which normally are the most

 problematic areas, where the load shedding also is most efficient.

Equipment protection, such as for motors and generatorsThe setting has to be well below the lowest occurring "normal" frequency and wellabove the lowest acceptable frequency for the equipment.

Power system protection, by load sheddingThe setting has to be well below the lowest occurring "normal" frequency and well

above the lowest acceptable frequency for power stations, or sensitive loads. Thesetting level, the number of levels and the distance between two levels (in time and/or in frequency) depends very much on the characteristics of the power systemunder consideration. The size of the "largest loss of production" compared to "thesize of the power system" is a critical parameter. In large systems, the loadshedding can be set at a fairly high frequency level, and the time delay is normallynot critical. In smaller systems the frequency start level has to be set at a lower value, and the time delay must be rather short.

The voltage related time delay is used for load shedding. The settings of theunderfrequency function could be the same all over the power system. The loadshedding is then performed firstly in areas with low voltage magnitude, which

normally are the most problematic areas, where the load shedding also is mostefficient.

3.8.1.2 Setting parameters

Table 89: SAPTUF Group settings (basic)

Name Values (Range) Unit Step Default Description

Operation Off  On

- - Off Operation Off / On

UBase 0.05 - 2000.00 kV 0.05 400.00 Base voltage

StartFrequency 35.00 - 75.00 Hz 0.01 48.80 Frequency setting/start value.

IntBlockLevel 0 - 100 %UB 1 50 Internal blocking level in % of UBase.

TimeDlyOperate 0.000 - 60.000 s 0.001 0.200 Operate time delay in over/under-frequency mode.

TimeDlyReset 0.000 - 60.000 s 0.001 0.000 Time delay for reset.

TimeDlyRestore 0.000 - 60.000 s 0.001 0.000 Restore time delay.

RestoreFreq 45.00 - 65.00 Hz 0.01 50.10 Restore frequency if frequency is abovefrequency value.

TimerOperation Definite timer  Volt based timer 

- - Definite timer Setting for choosing timer mode.

Table continues on next page

Section 3 1MRK 505 211-UEN C

IED application

230

 Application manual

Page 237: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 237/457

Name Values (Range) Unit Step Default Description

UNom 50 - 150 %UB 1 100 Nominal voltage in % of UBase for  voltage based timer.

UMin 50 - 150 %UB 1 90 Lower operation limit in % of UBase for  

voltage based timer.

Exponent 0.0 - 5.0 - 0.1 1.0 For calculation of the curve form for  voltage based timer.

tMax 0.010 - 60.000 s 0.001 1.000 Maximum time operation limit for voltagebased timer.

tMin 0.010 - 60.000 s 0.001 1.000 Minimum time operation limit for voltagebased timer.

3.8.2 Rate-of-change frequency protection SAPFRC

Function description IEC 61850

identification

IEC 60617

identification

ANSI/IEEE C37.2

device number

Rate-of-change frequency protection SAPFRC

df/dt ><

SYMBOL-N V1 EN

81

3.8.2.1 Application

Rate-of-change frequency protection (SAPFRC), is applicable in all situations,

where reliable detection of change of the fundamental power system voltagefrequency is needed. SAPFRC can be used both for increasing frequency and for decreasing frequency. SAPFRC provides an output signal, suitable for loadshedding or generator shedding, generator boosting, HVDC-set-point change, gasturbine start up and so on. Very often SAPFRC is used in combination with a lowfrequency signal, especially in smaller power systems, where loss of a fairly largegenerator will require quick remedial actions to secure the power system integrity.In such situations load shedding actions are required at a rather high frequencylevel, but in combination with a large negative rate-of-change of frequency theunderfrequency protection can be used at a rather high setting.

3.8.2.2 Setting guidelines

The parameters for Rate-of-change frequency protection SAPFRC are set via thelocal HMI or PCM600.

All the frequency and voltage magnitude conditions in the system where SAPFRC performs its functions should be considered. The same also applies to theassociated equipment, its frequency and time characteristic.

There are especially two application areas for SAPFRC:

1MRK 505 211-UEN C Section 3IED application

231

 Application manual

Page 238: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 238/457

Page 239: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 239/457

Page 240: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 240/457

• Definite time delay or Inverse Time Overcurrent TOC/IDMT delay for  both steps

• Second harmonic supervision is available in order to only allowoperation of the overcurrent stage(s) if the content of the secondharmonic in the measured current is lower than pre-set level

• Directional supervision is available in order to only allow operation of the overcurrent stage(s) if the fault location is in the pre-set direction( Forward or  Reverse). Its behavior during low-level polarizing voltage issettable ( Non-Directional , Block , Memory)

• Voltage restrained/controlled feature is available in order to modify the pick-up level of the overcurrent stage(s) in proportion to the magnitudeof the measured voltage

• Current restrained feature is available in or der to only allow operation of the overcurrent stage(s) if the measured current quantity is bigger thanthe set percentage of the current restrain quantity.

2. Two undercurrent steps with the following built-in features:

• Definite time delay for both steps

3. Two overvoltage steps with the following built-in features

• Definite time delay or Inverse Time Overcurrent TOC/IDMT delay for  both steps

4. Two undervoltage steps with the following built-in features

• Definite time delay or Inverse Time Overcurrent TOC/IDMT delay for  both steps

All these four protection elements within one general protection function worksindependently from each other and they can be individually enabled or disabled.However it shall be once more noted that all these four protection elementsmeasure one selected current quantity and one selected voltage quantity (seetable 91 and table 92). It is possible to simultaneously use all four-protectionelements and their individual stages. Sometimes in order to obtain desiredapplication functionality it is necessary to provide interaction between two or more

 protection elements/stages within one CVGAPC function by appropriate IEDconfiguration (for example, dead machine protection for generators).

Current and voltage selection for CVGAPC function

CVGAPC function is always connected to three-phase current and three-phasevoltage input in the configuration tool, but it will always measure only the singlecurrent and the single voltage quantity selected by the end user in the setting tool(selected current quantity and selected voltage quantity).

The user can select, by a setting parameter CurrentInput , to measure one of thefollowing current quantities shown in table 91.

Section 3 1MRK 505 211-UEN C

IED application

234

 Application manual

Page 241: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 241/457

Tab le 91 : Ava ilab le se lection fo r cur rent quan tity w ithin CVGAPC func tion

Set value for parameter

"CurrentInput”

Comment

1 phase1  CVGAPC function will measure the phase L1 current phasor 

2 phase2  CVGAPC function will measure the phase L2 current phasor 

3 phase3  CVGAPC function will measure the phase L3 current phasor 

4 PosSeq  CVGAPC function will measure internally calculated positivesequence current phasor 

5 NegSeq  CVGAPC function will measure internally calculated negativesequence current phasor 

6 3 · ZeroSeq  CVGAPC function will measure internally calculated zerosequence current phasor multiplied by factor 3

7 MaxPh  CVGAPC function will measure current phasor of the phasewith maximum magnitude

8 MinPh  CVGAPC function will measure current phasor of the phase

with minimum magnitude

9 UnbalancePh  CVGAPC function will measure magnitude of unbalancecurrent, which is internally calculated as the algebraicmagnitude difference between the current phasor of the phasewith maximum magnitude and current phasor of the phasewith minimum magnitude. Phase angle will be set to 0° all thetime

10 phase1 -phase2  CVGAPC function will measure the current phasor internallycalculated as the vector difference between the phase L1current phasor and phase L2 current phasor (IL1-IL2)

11 phase2 -phase3  CVGAPC function will measure the current phasor internallycalculated as the vector difference between the phase L2current phasor and phase L3 current phasor (IL2-IL3)

12 phase3 -phase1  CVGAPC function will measure the current phasor internallycalculated as the vector difference between the phase L3current phasor and phase L1 current phasor ( IL3-IL1)

13 MaxPh-Ph  CVGAPC function will measure ph-ph current phasor with themaximum magnitude

14 MinPh-Ph  CVGAPC function will measure ph-ph current phasor with theminimum magnitude

15 UnbalancePh-Ph  CVGAPC function will measure magnitude of unbalancecurrent, which is internally calculated as the algebraicmagnitude difference between the ph-ph current phasor withmaximum magnitude and ph-ph current phasor with minimummagnitude. Phase angle will be set to 0° all the time

The user can select, by a setting parameter VoltageInput , to measure one of thefollowing voltage quantities shown in table 92.

Tab le 92 : Ava ilab le se lection fo r voltage quant ity w ithin CVGAPC func tion

Set value for parameter

"VoltageInput"

Comment

1 phase1  CVGAPC function will measure the phase L1 voltage phasor 

2 phase2  CVGAPC function will measure the phase L2 voltage phasor 

3 phase3  CVGAPC function will measure the phase L3 voltage phasor 

Table continues on next page

1MRK 505 211-UEN C Section 3IED application

235

 Application manual

Page 242: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 242/457

Set value for parameter

"VoltageInput"

Comment

4 PosSeq  CVGAPC function will measure internally calculated positivesequence voltage phasor 

5 -NegSeq  CVGAPC function will measure internally calculated negativesequence voltage phasor. This voltage phasor will beintentionally rotated for 180° in order to enable easier settingsfor the directional feature when used.

6 -3*ZeroSeq  CVGAPC function will measure internally calculated zerosequence voltage phasor multiplied by factor 3. This voltagephasor will be intentionally rotated for 180° in order to enableeasier settings for the directional feature when used.

7 MaxPh  CVGAPC function will measure voltage phasor of the phasewith maximum magnitude

8 MinPh  CVGAPC function will measure voltage phasor of the phasewith minimum magnitude

9 UnbalancePh  CVGAPC function will measure magnitude of unbalance

voltage, which is internally calculated as the algebraicmagnitude difference between the voltage phasor of the phasewith maximum magnitude and voltage phasor of the phasewith minimum magnitude. Phase angle will be set to 0° all thetime

10 phase1 -phase2  CVGAPC function will measure the voltage phasor internallycalculated as the vector difference between the phase L1voltage phasor and phase L2 voltage phasor (UL1-UL2)

11 phase2 -phase3  CVGAPC function will measure the voltage phasor internallycalculated as the vector difference between the phase L2voltage phasor and phase L3 voltage phasor (UL2-UL3)

12 phase3 -phase1  CVGAPC function will measure the voltage phasor internallycalculated as the vector difference between the phase L3voltage phasor and phase L1 voltage phasor (UL3-UL1)

13 MaxPh-Ph  CVGAPC function will measure ph-ph voltage phasor with themaximum magnitude

14 MinPh-Ph  CVGAPC function will measure ph-ph voltage phasor with theminimum magnitude

15 UnbalancePh-Ph  CVGAPC function will measure magnitude of unbalancevoltage, which is internally calculated as the algebraicmagnitude difference between the ph-ph voltage phasor withmaximum magnitude and ph-ph voltage phasor with minimummagnitude. Phase angle will be set to 0° all the time

It is important to notice that the voltage selection from table 92 is alwaysapplicable regardless the actual external VT connections. The three-phase VTinputs can be connected to IED as either three phase-to-earth voltages UL1, UL2 &UL3 or three phase-to-phase voltages UL1L2, UL2L3 & UL3L1VAB, VBC and VCA.This information about actual VT connection is entered as a setting parameter for the pre-processing block, which will then take automatically care about it.

Base quantities for CVGAPC functionThe parameter settings for the base quantities, which represent the base (100%) for 

 pickup levels of all measuring stages shall be entered as setting parameters for every CVGAPC function.

Section 3 1MRK 505 211-UEN C

IED application

236

 Application manual

Page 243: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 243/457

Base current shall be entered as:

1. rated phase current of the protected object in primary amperes, when themeasured Current Quantity is selected from 1 to 9, as shown in table 91.

2. rated phase current of the protected object in primary amperes multiplied by√3 (1.732 x Iphase), when the measured Current Quantity is selected from 10to 15, as shown in table 91.

Base voltage shall be entered as:

1. rated phase-to-earth voltage of the protected object in primary kV, when themeasured Voltage Quantity is selected from 1 to 9, as shown in table 92.

2. rated phase-to-phase voltage of the protected object in primary kV, when themeasured Voltage Quantity is selected from 10 to 15, as shown in table 92.

Application possibilitiesDue to its flexibility the general current and voltage protection (CVGAPC)function can be used, with appropriate settings and configuration in many differentapplications. Some of possible examples are given below:

1. Transformer and line applications:

• Underimpedance protection (circular, non-directional characteristic)• Underimpedance protection (circular mho characteristic)• Voltage Controlled/Restrained Overcurrent protection• Phase or Negative/Positive/Zero Sequence (Non-Directional or 

Directional) Overcurrent protection

• Phase or phase-to-phase or Negative/Positive/Zero Sequence over/under voltage protection

• Special thermal overload protection• Open Phase protection• Unbalance protection

2. Generator protection

• 80-95% Stator earth fault protection (measured or calculated 3Uo)• Rotor earth fault protection (with external COMBIFLEX RXTTE4

injection unit)• Underimpedance protection

• Voltage Controlled/Restrained Overcurrent protection• Turn-to-Turn & Differential Backup protection (directional NegativeSequence. Overcurrent protection connected to generator HV terminalCTs looking into generator)

• Stator Overload protection• Rotor Overload protection• Loss of Excitation protection (directional pos. seq. OC protection)• Reverse power/Low forward power protection (directional pos. seq. OC

 protection, 2% sensitivity)• Dead-Machine/Inadvertent-Energizing protection• Breaker head flashover protection• Improper synchronizing detection

1MRK 505 211-UEN C Section 3IED application

237

 Application manual

Page 244: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 244/457

• Sensitive negative sequence generator over current protection and alarm• Phase or phase-to-phase or Negative/Positive/Zero Sequence over/under 

voltage protection• Generator out-of-step detection (based on directional pos. seq. OC)• Inadvertent generator energizing

Inadvertent generator energizationWhen the generator is taken out of service, and non-rotating, there is a risk that thegenerator circuit breaker is closed by mistake.

Three-phase energizing of a generator, which is at standstill or on turning gear,causes it to behave and accelerate similarly to an induction motor. The machine, atthis point, essentially represents the subtransient reactance to the system and it can

 be expected to draw from one to four per unit current, depending on the equivalent

system impedance. Machine terminal voltage can range from 20% to 70% of ratedvoltage, again, depending on the system equivalent impedance (including the block transformer). Higher quantities of machine current and voltage (3 to 4 per unitcurrent and 50% to 70% rated voltage) can be expected if the generator isconnected to a strong system. Lower current and voltage values (1 to 2 per unitcurrent and 20% to 40% rated voltage) are representative of weaker systems.

Since a generator behaves similarly to an induction motor, high currents willdevelop in the rotor during the period it is accelerating. Although the rotor may bethermally damaged from excessive high currents, the time to damage will be on theorder of a few seconds. Of more critical concern, however, is the bearing, whichcan be damaged in a fraction of a second due to low oil pressure. Therefore, it is

essential that high speed tripping is provided. This tripping should be almostinstantaneous (< 100 ms).

There is a risk that the current into the generator at inadvertent energization will belimited so that the “normal” overcurrent or underimpedance protection will notdetect the dangerous situation. The delay of these protection functions might be toolong. The reverse power protection might detect the situation but the operation timeof this protection is normally too long.

For big and important machines, fast protection against inadvertent energizingshould, therefore, be included in the protective scheme.

The protection against inadvertent energization can be made by a combination of undervoltage, overvoltage and overcurrent protection functions. The undervoltagefunction will, with a delay for example 10 s, detect the situation when the generator is not connected to the grid (standstill) and activate the overcurrent function. Theovervoltage function will detect the situation when the generator is taken intooperation and will disable the overcurrent function. The overcurrent function willhave a pick-up value about 50% of the rated current of the generator. The trip delaywill be about 50 ms.

Section 3 1MRK 505 211-UEN C

IED application

238

 Application manual

Page 245: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 245/457

3.9.1.2 Setting guidelines

When inverse time overcurrent characteristic is selected, theoperate time of the stage will be the sum of the inverse time delayand the set definite time delay. Thus, if only the inverse time delayis required, it is of utmost importance to set the definite time delayfor that stage to zero.

The parameters for the general current and voltage protection function (CVGAPC)are set via the local HMI or Protection and Control Manager (PCM600).

The overcurrent steps has a IMinx ( x=1 or 2 depending on step)setting to set the minimum operate current. Set IMinx below

StartCurr_OCx for every step to achieve ANSI reset characteristicaccording to standard. If  IMinx is set above StartCurr_OCx for anystep the ANSI reset works as if current is zero when current drops

 below IMinx.

Directional negative sequence overcurrent protectionDirectional negative sequence overcurrent protection is typically used as sensitiveearth-fault protection of power lines were incorrect zero sequence polarization mayresult from mutual induction between two or more parallel lines. Additionally, itcan be used in applications on underground cables where zero-sequence impedance

depends on the fault current return paths, but the cable negative-sequenceimpedance is practically constant. It shall be noted that directional negativesequence OC element offers protection against all unbalance faults (phase-to-phasefaults as well). Care shall be taken that the minimum pickup of such protectionfunction shall be set above natural system unbalance level.

An example will be given, how sensitive-earth-fault protection for power lines can be achieved by using negative-sequence directional overcurrent protectionelements within a CVGAPC function.

This functionality can be achieved by using one CVGAPC function. The followingshall be done to ensure proper operation of the function:

1. Connect three-phase power line currents and three-phase power line voltagesto one CVGAPC instance (for example, GF04)

2. Set CurrentInput to NegSeq (please note that CVGAPC function measures I2current and NOT 3I2 current; this is essential for proper OC pickup level setting)

3. Set VoltageInput to -NegSeq (please note that the negative sequence voltage phasor is intentionally inverted in order to simplify directionality

4. Set base current IBase value equal to the rated primary current of power line CTs5. Set base voltage UBase value equal to the rated power line phase-to-phase

voltage in kV6. Set RCADir to value +65 degrees ( NegSeq current typically lags the inverted

 NegSeq voltage for this angle during the fault)

1MRK 505 211-UEN C Section 3IED application

239

 Application manual

Page 246: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 246/457

7. Set ROADir to value 90 degree8. Set LowVolt_VM to value 2% ( NegSeq voltage level above which the

directional element will be enabled)9. Enable one overcurrent stage (for example, OC1)10. By parameter CurveType_OC1 select appropriate TOC/IDMT or definite time

delayed curve in accordance with your network protection philosophy11. Set StartCurr_OC1 to value between 3-10% (typical values)12. Set tDef_OC1 or parameter “k” when TOC/IDMT curves are used to insure

 proper time coordination with other earth-fault protections installed in thevicinity of this power line

13. Set DirMode_OC1 to Forward 

14. Set DirPrinc_OC1 to IcosPhi&U 

15. Set ActLowVolt1_VM to Block 

• In order to insure proper restraining of this element for CT saturationsduring three-phase faults it is possible to use current restraint feature andenable this element to operate only when NegSeq current is bigger than acertain percentage (10% is typical value) of measured PosSeq current inthe power line. To do this the following settings within the same functionshall be done:

16. Set EnRestrainCurr to On

17. Set RestrCurrInput to PosSeq

18. Set RestrCurrCoeff to value 0.10

If required, this CVGAPC function can be used in directional comparison protection scheme for the power line protection if communication channels to the

remote end of this power line are available. In that case typically two NegSeqovercurrent steps are required. One for forward and one for reverse direction. Asexplained before the OC1 stage can be used to detect faults in forward direction.The built-in OC2 stage can be used to detect faults in reverse direction.

However the following shall be noted for such application:

• the set values for   RCADir and ROADir settings will be as well applicable for OC2 stage

• setting DirMode_OC2 shall be set to Reverse

• setting parameter  StartCurr_OC2 shall be made more sensitive than pickupvalue of forward OC1 element (that is, typically 60% of OC1 set pickup level)

in order to insure proper operation of the directional comparison schemeduring current reversal situations

• start signals from OC1 and OC2 elements shall be used to send forward andreverse signals to the remote end of the power line

• the available scheme communications function block within IED shall be used between multipurpose protection function and the communication equipmentin order to insure proper conditioning of the above two start signals

Furthermore the other built-in UC, OV and UV protection elements can be used for other protection and alarming purposes.

Section 3 1MRK 505 211-UEN C

IED application

240

 Application manual

Page 247: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 247/457

Negative sequence overcurrent protectionExample will be given how to use one CVGAPC function to provide negativesequence inverse time overcurrent protection for a generator with capabilityconstant of 20s, and maximum continuous negative sequence rating of 7% of thegenerator rated current.

The capability curve for a generator negative sequence overcurrent protection,often used world-wide, is defined by the ANSI standard in accordance with thefollowing formula:

2op

 NS 

k t 

 I 

 I 

=æ öç ÷è ø

EQUATION1372 V1 EN (Equation 89)

where:

top is the operating time in seconds of the negative sequence overcurrent IED

k is the generator capabili ty constant in seconds

INS is the measured negative sequence current

Ir  is the generator rated current

By defining parameter x equal to maximum continuous negative sequence rating of the generator in accordance with the following formula

7% 0, 07 x pu= =EQUATION1373 V1 EN (Equation 90)

Equation 89 can be re-written in the following way without changing the value for the operate time of the negative sequence inverse overcurrent IED:

2

2

1

op

 NS 

k  xt 

 I 

 x I 

×=

æ öç ÷

×è øEQUATION1374 V1 EN (Equation 91)

In order to achieve such protection functionality with one CVGAPC functions thefollowing must be done:

1MRK 505 211-UEN C Section 3IED application

241

 Application manual

Page 248: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 248/457

1. Connect three-phase generator currents to one CVGAPC instance (for example, GF01)

2. Set parameter CurrentInput to value NegSeq

3. Set base current value to the rated generator current in primary amperes4. Enable one overcurrent step (for example, OC1)5. Select parameter CurveType_OC1 to value Programmable

op P 

 At k B

 M C 

æ ö= × +ç ÷-è øEQUATION1375 V1 EN (Equation 92)

where:

top  is the operating time in seconds of the Inverse Time Overcurrent TOC/IDMT algorithm

k is time multiplier (parameter setting)

M is ratio between measured current magnitude and set pickup current level

 A, B, C and P are user settable coefficients which determine the curve used for Inverse TimeOvercurrent TOC/IDMT calculation

When the equation 89 is compared with the equation 91 for the inverse timecharacteristic of the OC1 it is obvious that if the following rules are followed:

1. set k equal to the generator negative sequence capability value2. set A_OC1 equal to the value 1/x2

3. set B_OC1 = 0.0, C_OC1=0.0 and P_OC1=2.04. set StartCurr_OC1 equal to the value x

then the OC1 step of the CVGAPC function can be used for generator negativesequence inverse overcurrent protection.

For this particular example the following settings shall be entered to insure proper function operation:

1. select negative sequence current as measuring quantity for this CVGAPCfunction

2. make sure that the base current value for the CVGAPC function is equal to the

generator rated current3. set k_OC1 = 204. set A_OC1= 1/0.072 = 204.08165. set B_OC1 = 0.0, C_OC1 = 0.0 and P_OC1 = 2.06. set StartCurr_OC1 = 7%

Proper timing of the CVGAPC function made in this way can easily be verified bysecondary injection. All other settings can be left at the default values. If requireddelayed time reset for OC1 step can be set in order to ensure proper functionoperation in case of repetitive unbalance conditions.

Section 3 1MRK 505 211-UEN C

IED application

242

 Application manual

Page 249: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 249/457

Furthermore the other built-in protection elements can be used for other protectionand alarming purposes (for example, use OC2 for negative sequence overcurrentalarm and OV1 for negative sequence overvoltage alarm).

Generator stator overload protection in accordance with IEC or ANSIstandardsExample will be given how to use one CVGAPC function to provide generator stator overload protection in accordance with IEC or ANSI standard if minimum-operating current shall be set to 116% of generator rating.

The generator stator overload protection is defined by IEC or ANSI standard for turbo generators in accordance with the following formula:

2

1

op

m

k t 

 I 

 I 

=æ ö

-ç ÷è øEQUATION1376 V1 EN (Equation 93)

where:

top is the operating time of the generator stator overload IED

k is the generator capability constant in accordance with the relevant standard (k = 37.5 for theIEC standard or k = 41.4 for the ANSI standard)

Im is the magnitude of the measured current

Ir  is the generator rated current

This formula is applicable only when measured current (for example, positivesequence current) exceeds a pre-set value (typically in the range from 105 to 125%of the generator rated current).

By defining parameter x equal to the per unit value for the desired pickup for theoverload IED in accordance with the following formula:

x = 116% = 1.16 pu

EQUATION1377 V2 EN (Equation 94)

formula 3.5can be re-written in the following way without changing the value for the operate time of the generator stator overload IED:

2

2

2

1

1op

m

k  xt 

 I 

 x I x

×=

æ ö-ç ÷×è ø

EQUATION1378 V1 EN (Equation 95)

1MRK 505 211-UEN C Section 3IED application

243

 Application manual

Page 250: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 250/457

In order to achieve such protection functionality with one CVGAPC functions thefollowing must be done:

1. Connect three-phase generator currents to one CVGAPC instance (for 

example, GF01)2. Set parameter CurrentInput to value PosSeq

3. Set base current value to the rated generator current in primary amperes4. Enable one overcurrent step (for example OC1)5. Select parameter CurveType_OC1 to value Programmable

op P 

 At k B

 M C 

æ ö= × +ç ÷-è øEQUATION1375 V1 EN (Equation 96)

where:

top is the operating time in seconds of the Inverse Time Overcurrent TOC/IDMT algorithm

k is time multiplier (parameter setting)

M is ratio between measured current magnitude and set pickup current level

 A, B, C and P are user settable coefficients which determine the curve used for Inverse TimeOvercurrent TOC/IDMT calculation

When the equation 95 is compared with the equation 96 for the inverse timecharacteristic of the OC1 step in it is obvious that if the following rules are followed:

1. set k equal to the IEC or ANSI standard generator capability value2. set parameter  A_OC1 equal to the value 1/x23. set parameter C_OC1 equal to the value 1/x24. set parameters B_OC1 = 0.0 and P_OC1=2.05. set StartCurr_OC1 equal to the value x

then the OC1 step of the CVGAPC function can be used for generator negativesequence inverse overcurrent protection.

1. select positive sequence current as measuring quantity for this CVGAPCfunction

2. make sure that the base current value for CVGAPC function is equal to thegenerator rated current

3. set k = 37.5 for the IEC standard or k = 41.4 for the ANSI standard4. set A_OC1= 1/1.162 = 0.74325. set C_OC1= 1/1.162 = 0.74326. set B_OC1 = 0.0 and P_OC1 = 2.07. set StartCurr_OC1 = 116%

Proper timing of CVGAPC function made in this way can easily be verified bysecondary injection. All other settings can be left at the default values. If required

Section 3 1MRK 505 211-UEN C

IED application

244

 Application manual

Page 251: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 251/457

delayed time reset for OC1 step can be set in order to insure proper functionoperation in case of repetitive overload conditions.

Furthermore the other built-in protection elements can be used for other protection

and alarming purposes.

In the similar way rotor overload protection in accordance with ANSI standard can be achieved.

Open phase protection for transformer, lines or generators and circuit

breaker head flashover protection for generatorsExample will be given how to use one CVGAPC function to provide open phase

 protection. This can be achieved by using one CVGAPC function by comparing theunbalance current with a pre-set level. In order to make such a function moresecure it is possible to restrain it by requiring that at the same time the measured

unbalance current must be bigger than 97% of the maximum phase current. Bydoing this it will be insured that function can only pickup if one of the phases isopen circuited. Such an arrangement is easy to obtain in CVGAPC function byenabling the current restraint feature. The following shall be done in order to insure

 proper operation of the function:

1. Connect three-phase currents from the protected object to one CVGAPCinstance (for example, GF03)

2. Set CurrentInput to value UnbalancePh

3. Set EnRestrainCurr to On

4. Set RestrCurrInput to MaxPh

5. Set RestrCurrCoeff to value 0.97

6. Set base current value to the rated current of the protected object in primaryamperes

7. Enable one overcurrent step (for example, OC1)8. Select parameter CurveType_OC1 to value IEC Def. Time

9. Set parameter StartCurr_OC1 to value 5%10. Set parameter tDef_OC1 to desired time delay (for example, 2.0s)

Proper operation of CVGAPC function made in this way can easily be verified bysecondary injection. All other settings can be left at the default values. However itshall be noted that set values for restrain current and its coefficient will as well beapplicable for OC2 step as soon as it is enabled.

Furthermore the other built-in protection elements can be used for other protectionand alarming purposes. For example, in case of generator application by enablingOC2 step with set pickup to 200% and time delay to 0.1s simple but effective

 protection against circuit breaker head flashover protection is achieved.

Voltage restrained overcurrent protection for generator and step-up

transformerExample will be given how to use one CVGAPC function to provide voltagerestrained overcurrent protection for a generator. Let us assume that the timecoordination study gives the following required settings:

1MRK 505 211-UEN C Section 3IED application

245

 Application manual

Page 252: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 252/457

• Inverse Time Over Current TOC/IDMT curve: ANSI very inverse• Pickup current of 185% of generator rated current at rated generator voltage• Pickup current 25% of the original pickup current value for generator voltages

 below 25% of rated voltage

This functionality can be achieved by using one CVGAPC function. The followingshall be done in order to insure proper operation of the function:

1. Connect three-phase generator currents and voltages to one CVGAPC instance(for example, GF05)

2. Set CurrentInput to value MaxPh

3. Set VoltageInput to value MinPh-Ph (it is assumed that minimum phase-to- phase voltage shall be used for restraining. Alternatively, positive sequencevoltage can be used for restraining by selecting PosSeq for this setting parameter)

4. Set base current value to the rated generator current primary amperes

5. Set base voltage value to the rated generator phase-to-phase voltage in kV6. Enable one overcurrent step (for example, OC1)7. Select CurveType_OC1 to value ANSI Very inv

8. If required set minimum operating time for this curve by using parameter tMin_OC1 (default value 0.05s)

9. Set StartCurr_OC1 to value 185%10. Set VCntrlMode_OC1 to On

11. Set VDepMode_OC1 to Slope

12. Set VDepFact_OC1 to value 0.2513. Set UHighLimit_OC1 to value 100%14. Set ULowLimit_OC1 to value 25%

Proper operation of the CVGAPC function made in this way can easily be verified by secondary injection. All other settings can be left at the default values.Furthermore the other built-in protection elements can be used for other protectionand alarming purposes.

Loss of excitation protection for a generatorExample will be given how by using positive sequence directional overcurrent

 protection element within a CVGAPC function, loss of excitation protection for agenerator can be achieved. Let us assume that from rated generator data thefollowing values are calculated:

• Maximum generator capability to contentiously absorb reactive power at zeroactive loading 38% of the generator MVA rating

• Generator pull-out angle 84 degrees

This functionality can be achieved by using one CVGAPC function. The followingshall be done in order to insure proper operation of the function:

1. Connect three-phase generator currents and three-phase generator voltages toone CVGAPC instance (for example, GF02)

2. Set parameter CurrentInput to PosSeq

3. Set parameter VoltageInput to PosSeq

Section 3 1MRK 505 211-UEN C

IED application

246

 Application manual

Page 253: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 253/457

4. Set base current value to the rated generator current primary amperes5. Set base voltage value to the rated generator phase-to-phase voltage in kV6. Set parameter  RCADir to value -84 degree (that is, current lead voltage for this

angle)7. Set parameter  ROADir to value 90 degree8. Set parameter  LowVolt_VM to value 5%9. Enable one overcurrent step (for example, OC1)10. Select parameter CurveType_OC1 to value IEC Def. Time

11. Set parameter StartCurr_OC1 to value 38%12. Set parameter tDef_OC1 to value 2.0s (typical setting)13. Set parameter  DirMode_OC1 to Forward 

14. Set parameter  DirPrinc_OC1 to IcosPhi&U 

15. Set parameter  ActLowVolt1_VM to Block 

Proper operation of the CVGAPC function made in this way can easily be verified by secondary injection. All other settings can be left at the default values. However it shall be noted that set values for RCA & ROA angles will be applicable for OC2step if directional feature is enabled for this step as well. Figure 83 shows overall

 protection characteristic

Furthermore the other build-in protection elements can be used for other protectionand alarming purposes.

0.2 0.4 0.6

-0.2

0.6

0.8

0.8 1

DILowSet

B

 A

C

0.4

0.2

0

1.2 1.4

-0.4

-0.6

-0.8

-rca

Operating Region

Q [pu]

P

[pu]

rca

UPS

IPSILowSet

Operating region

en05000535.vsd

IEC05000535 V2 EN

Figure 83: Loss of excitation 

1MRK 505 211-UEN C Section 3IED application

247

 Application manual

Page 254: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 254/457

3.9.1.3 Setting parameters

Table 93: CVGAPC Group settings (basic)

Name Values (Range) Unit Step Default Description

Operation Off  On

- - Off Operation Off / On

CurrentInput phase1phase2phase3PosSeqNegSeq3*ZeroSeqMaxPhMinPhUnbalancePhphase1-phase2phase2-phase3phase3-phase1

MaxPh-PhMinPh-PhUnbalancePh-Ph

- - MaxPh Select current signal which will bemeasured inside function

IBase 1 - 99999 A 1 3000 Base Current

VoltageInput phase1phase2phase3PosSeq-NegSeq-3*ZeroSeqMaxPhMinPhUnbalancePhphase1-phase2

phase2-phase3phase3-phase1MaxPh-PhMinPh-PhUnbalancePh-Ph

- - MaxPh Select voltage signal which will bemeasured inside function

UBase 0.05 - 2000.00 kV 0.05 400.00 Base Voltage

OperHarmRestr Off  On

- - Off Operation of 2nd harmonic restrain Off /On

l_2nd/l_fund 10.0 - 50.0 % 1.0 20.0 Ratio of second to fundamental currentharmonic in %

EnRestrainCurr Off  On

- - Off Enable current restrain function On / Off  

RestrCurrInput PosSeqNegSeq3*ZeroSeqMax

- - PosSeq Select current signal which will be usedfor curr restrain

RestrCurrCoeff 0.00 - 5.00 - 0.01 0.00 Restraining current coefficient

RCADir -180 - 180 Deg 1 -75 Relay Characteristic Angle

ROADir 1 - 90 Deg 1 75 Relay Operate Angle

LowVolt_VM 0.0 - 5.0 %UB 0.1 0.5 Below this level in % of Ubase setting ActLowVolt takes over 

Operation_OC1 Off  On

- - Off Operation OC1 Off / On

Table continues on next page

Section 3 1MRK 505 211-UEN C

IED application

248

 Application manual

Page 255: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 255/457

Name Values (Range) Unit Step Default Description

StartCurr_OC1 2.0 - 5000.0 %IB 1.0 120.0 Operate current level for OC1 in % of  Ibase

CurveType_OC1 ANSI Ext. inv.

 ANSI Very inv. ANSI Norm. inv. ANSI Mod. inv. ANSI Def. TimeL.T.E. inv.L.T.V. inv.L.T. inv.IEC Norm. inv.IEC Very inv.IEC inv.IEC Ext. inv.IEC S.T. inv.IEC L.T. inv.IEC Def. TimeProgrammableRI typeRD type

- - ANSI Def. Time Selection of time delay curve type for OC1

tDef_OC1 0.00 - 6000.00 s 0.01 0.50 Independent (definitive) time delay of  OC1

k_OC1 0.05 - 999.00 - 0.01 0.30 Time multiplier for the dependent timedelay for OC1

IMin1 1 - 10000 %IB 1 100 Minimum operate current for step1 in %of IBase

tMin_OC1 0.00 - 6000.00 s 0.01 0.05 Minimum operate time for IEC IDMTcurves for OC1

VCntrlMode_OC1 Voltage controlInput controlVolt/Input control

Off 

- - Off Control mode for voltage controlled OC1function

VDepMode_OC1 StepSlope

- - Step Voltage dependent mode OC1 (step,slope)

VDepFact_OC1 0.02 - 5.00 - 0.01 1.00 Multiplying factor for I pickup when OC1is U dependent

ULowLimit_OC1 1.0 - 200.0 %UB 0.1 50.0 Voltage low limit setting OC1 in % of  Ubase

UHighLimit_OC1 1.0 - 200.0 %UB 0.1 100.0 Voltage high limit setting OC1 in % of  Ubase

HarmRestr_OC1 Off  On

- - Off Enable block of OC1 by 2nd harmonicrestrain

DirMode_OC1 Non-directionalForwardReverse

- - Non-directional Directional mode of OC1 (nondir,forward,reverse)

DirPrinc_OC1 I&UIcosPhi&U

- - I&U Measuring on IandU or IcosPhiandU for  OC1

 ActLowVolt1_VM Non-directionalBlockMemory

- - Non-directional Low voltage level action for Dir_OC1(Nodir, Blk, Mem)

Operation_OC2 Off  On

- - Off Operation OC2 Off / On

StartCurr_OC2 2.0 - 5000.0 %IB 1.0 120.0 Operate current level for OC2 in % of  Ibase

Table continues on next page

1MRK 505 211-UEN C Section 3IED application

249

 Application manual

Page 256: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 256/457

Name Values (Range) Unit Step Default Description

CurveType_OC2 ANSI Ext. inv. ANSI Very inv. ANSI Norm. inv. ANSI Mod. inv.

 ANSI Def. TimeL.T.E. inv.L.T.V. inv.L.T. inv.IEC Norm. inv.IEC Very inv.IEC inv.IEC Ext. inv.IEC S.T. inv.IEC L.T. inv.IEC Def. TimeProgrammableRI typeRD type

- - ANSI Def. Time Selection of time delay curve type for OC2

tDef_OC2 0.00 - 6000.00 s 0.01 0.50 Independent (definitive) time delay of  OC2

k_OC2 0.05 - 999.00 - 0.01 0.30 Time multiplier for the dependent timedelay for OC2

IMin2 1 - 10000 %IB 1 50 Minimum operate current for step2 in %of IBase

tMin_OC2 0.00 - 6000.00 s 0.01 0.05 Minimum operate time for IEC IDMTcurves for OC2

VCntrlMode_OC2 Voltage controlInput controlVolt/Input controlOff 

- - Off Control mode for voltage controlled OC2function

VDepMode_OC2 Step

Slope

- - Step Voltage dependent mode OC2 (step,

slope)

VDepFact_OC2 0.02 - 5.00 - 0.01 1.00 Multiplying factor for I pickup when OC2is U dependent

ULowLimit_OC2 1.0 - 200.0 %UB 0.1 50.0 Voltage low limit setting OC2 in % of  Ubase

UHighLimit_OC2 1.0 - 200.0 %UB 0.1 100.0 Voltage high limit setting OC2 in % of  Ubase

HarmRestr_OC2 Off  On

- - Off Enable block of OC2 by 2nd harmonicrestrain

DirMode_OC2 Non-directionalForwardReverse

- - Non-directional Directional mode of OC2 (nondir,forward,reverse)

DirPrinc_OC2 I&UIcosPhi&U

- - I&U Measuring on IandU or IcosPhiandU for  OC2

 ActLowVolt2_VM Non-directionalBlockMemory

- - Non-directional Low voltage level action for Dir_OC2(Nodir, Blk, Mem)

Operation_UC1 Off  On

- - Off Operation UC1 Off / On

EnBlkLowI_UC1 Off  On

- - Off Enable internal low current level blockingfor UC1

BlkLowCurr_UC1 0 - 150 %IB 1 20 Internal low current blocking level for  UC1 in % of Ibase

Table continues on next page

Section 3 1MRK 505 211-UEN C

IED application

250

 Application manual

Page 257: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 257/457

Name Values (Range) Unit Step Default Description

StartCurr_UC1 2.0 - 150.0 %IB 1.0 70.0 Operate undercurrent level for UC1 in %of Ibase

tDef_UC1 0.00 - 6000.00 s 0.01 0.50 Independent (definitive) time delay of UC1

tResetDef_UC1 0.00 - 6000.00 s 0.01 0.00 Reset time delay used in IEC DefiniteTime curve UC1

HarmRestr_UC1 Off  On

- - Off Enable block of UC1 by 2nd harmonicrestrain

Operation_UC2 Off  On

- - Off Operation UC2 Off / On

EnBlkLowI_UC2 Off  On

- - Off Enable internal low current level blockingfor UC2

BlkLowCurr_UC2 0 - 150 %IB 1 20 Internal low current blocking level for  UC2 in % of Ibase

StartCurr_UC2 2.0 - 150.0 %IB 1.0 70.0 Operate undercurrent level for UC2 in %of Ibase

tDef_UC2 0.00 - 6000.00 s 0.01 0.50 Independent (definitive) time delay of UC2

HarmRestr_UC2 Off  On

- - Off Enable block of UC2 by 2nd harmonicrestrain

Operation_OV1 Off  On

- - Off Operation OV1 Off / On

StartVolt_OV1 2.0 - 200.0 %UB 0.1 150.0 Operate voltage level for OV1 in % of  Ubase

CurveType_OV1 Definite timeInverse curve AInverse curve BInverse curve CProg. inv. curve

- - Definite time Selection of time delay curve type for OV1

tDef_OV1 0.00 - 6000.00 s 0.01 1.00 Operate time delay in sec for definitetime use of OV1

tMin_OV1 0.00 - 6000.00 s 0.01 0.05 Minimum operate time for IDMT curvesfor OV1

k_OV1 0.05 - 999.00 - 0.01 0.30 Time multiplier for the dependent timedelay for OV1

Operation_OV2 Off  On

- - Off Operation OV2 Off / On

StartVolt_OV2 2.0 - 200.0 %UB 0.1 150.0 Operate voltage level for OV2 in % of  Ubase

CurveType_OV2 Definite timeInverse curve A

Inverse curve BInverse curve CProg. inv. curve

- - Definite time Selection of time delay curve type for OV2

tDef_OV2 0.00 - 6000.00 s 0.01 1.00 Operate time delay in sec for definitetime use of OV2

tMin_OV2 0.00 - 6000.00 s 0.01 0.05 Minimum operate time for IDMT curvesfor OV2

k_OV2 0.05 - 999.00 - 0.01 0.30 Time multiplier for the dependent timedelay for OV2

Operation_UV1 Off  On

- - Off Operation UV1 Off / On

Table continues on next page

1MRK 505 211-UEN C Section 3IED application

251

 Application manual

Page 258: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 258/457

Page 259: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 259/457

Name Values (Range) Unit Step Default Description

B_OC1 0.000 - 99.000 - 0.001 0.000 Parameter B for customer programmablecurve for OC1

C_OC1 0.000 - 1.000 - 0.001 1.000 Parameter C for customer  

programmable curve for OC1

PR_OC1 0.005 - 3.000 - 0.001 0.500 Parameter PR for customer  programmable curve for OC1

TR_OC1 0.005 - 600.000 - 0.001 13.500 Parameter TR for customer  programmable curve for OC1

CR_OC1 0.1 - 10.0 - 0.1 1.0 Parameter CR for customer  programmable curve for OC1

CurrMult_OC2 1.0 - 10.0 - 0.1 2.0 Multiplier for scaling the current settingvalue for OC2

ResCrvType_OC2 InstantaneousIEC Reset

 ANSI reset

- - Instantaneous Selection of reset curve type for OC2

tResetDef_OC2 0.00 - 6000.00 s 0.01 0.00 Reset time delay used in IEC DefiniteTime curve OC2

P_OC2 0.001 - 10.000 - 0.001 0.020 Parameter P for customer programmablecurve for OC2

 A_OC2 0.000 - 999.000 - 0.001 0.140 Parameter A for customer programmablecurve for OC2

B_OC2 0.000 - 99.000 - 0.001 0.000 Parameter B for customer programmablecurve for OC2

C_OC2 0.000 - 1.000 - 0.001 1.000 Parameter C for customer  programmable curve for OC2

PR_OC2 0.005 - 3.000 - 0.001 0.500 Parameter PR for customer  programmable curve for OC2

TR_OC2 0.005 - 600.000 - 0.001 13.500 Parameter TR for customer  programmable curve for OC2

CR_OC2 0.1 - 10.0 - 0.1 1.0 Parameter CR for customer  programmable curve for OC2

tResetDef_UC2 0.00 - 6000.00 s 0.01 0.00 Reset time delay used in IEC DefiniteTime curve UC2

ResCrvType_OV1 InstantaneousFrozen timer Linearly decreased

- - Instantaneous Selection of reset curve type for OV1

tResetDef_OV1 0.00 - 6000.00 s 0.01 0.00 Reset time delay in sec for definite timeuse of OV1

tResetIDMT_OV1 0.00 - 6000.00 s 0.01 0.00 Reset time delay in sec for IDMT curves

for OV1

 A_OV1 0.005 - 999.000 - 0.001 0.140 Parameter A for customer programmablecurve for OV1

B_OV1 0.500 - 99.000 - 0.001 1.000 Parameter B for customer programmablecurve for OV1

C_OV1 0.000 - 1.000 - 0.001 1.000 Parameter C for customer  programmable curve for OV1

D_OV1 0.000 - 10.000 - 0.001 0.000 Parameter D for customer  programmable curve for OV1

P_OV1 0.001 - 10.000 - 0.001 0.020 Parameter P for customer programmablecurve for OV1

Table continues on next page

1MRK 505 211-UEN C Section 3IED application

253

 Application manual

Page 260: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 260/457

Name Values (Range) Unit Step Default Description

ResCrvType_OV2 InstantaneousFrozen timer Linearly decreased

- - Instantaneous Selection of reset curve type for OV2

tResetDef_OV2 0.00 - 6000.00 s 0.01 0.00 Reset time delay in sec for definite timeuse of OV2

tResetIDMT_OV2 0.00 - 6000.00 s 0.01 0.00 Reset time delay in sec for IDMT curvesfor OV2

 A_OV2 0.005 - 999.000 - 0.001 0.140 Parameter A for customer programmablecurve for OV2

B_OV2 0.500 - 99.000 - 0.001 1.000 Parameter B for customer programmablecurve for OV2

C_OV2 0.000 - 1.000 - 0.001 1.000 Parameter C for customer  programmable curve for OV2

D_OV2 0.000 - 10.000 - 0.001 0.000 Parameter D for customer  programmable curve for OV2

P_OV2 0.001 - 10.000 - 0.001 0.020 Parameter P for customer programmablecurve for OV2

ResCrvType_UV1 InstantaneousFrozen timer Linearly decreased

- - Instantaneous Selection of reset curve type for UV1

tResetDef_UV1 0.00 - 6000.00 s 0.01 0.00 Reset time delay in sec for definite timeuse of UV1

tResetIDMT_UV1 0.00 - 6000.00 s 0.01 0.00 Reset time delay in sec for IDMT curvesfor UV1

 A_UV1 0.005 - 999.000 - 0.001 0.140 Parameter A for customer programmablecurve for UV1

B_UV1 0.500 - 99.000 - 0.001 1.000 Parameter B for customer programmable

curve for UV1

C_UV1 0.000 - 1.000 - 0.001 1.000 Parameter C for customer  programmable curve for UV1

D_UV1 0.000 - 10.000 - 0.001 0.000 Parameter D for customer  programmable curve for UV1

P_UV1 0.001 - 10.000 - 0.001 0.020 Parameter P for customer programmablecurve for UV1

ResCrvType_UV2 InstantaneousFrozen timer Linearly decreased

- - Instantaneous Selection of reset curve type for UV2

tResetDef_UV2 0.00 - 6000.00 s 0.01 0.00 Reset time delay in sec for definite timeuse of UV2

tResetIDMT_UV2 0.00 - 6000.00 s 0.01 0.00 Reset time delay in sec for IDMT curvesfor UV2

 A_UV2 0.005 - 999.000 - 0.001 0.140 Parameter A for customer programmablecurve for UV2

B_UV2 0.500 - 99.000 - 0.001 1.000 Parameter B for customer programmablecurve for UV2

Table continues on next page

Section 3 1MRK 505 211-UEN C

IED application

254

 Application manual

Page 261: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 261/457

Name Values (Range) Unit Step Default Description

C_UV2 0.000 - 1.000 - 0.001 1.000 Parameter C for customer  programmable curve for UV2

D_UV2 0.000 - 10.000 - 0.001 0.000 Parameter D for customer  

programmable curve for UV2

P_UV2 0.001 - 10.000 - 0.001 0.020 Parameter P for customer programmablecurve for UV2

3.10 Secondary system supervision

3.10.1 Fuse failure supervision SDDRFUF

3.10.1.1 Setting parameters

Table 95: SDDRFUF Group settings (basic)

Name Values (Range) Unit Step Default Description

Operation Off  On

- - On Operation Off / On

IBase 1 - 99999 A 1 3000 Base current

UBase 0.05 - 2000.00 kV 0.05 400.00 Base voltage

OpMode Off  UNsINsUZsIZs

UZsIZs OR UNsINsUZsIZs ANDUNsINsOptimZsNs

- - UZsIZs Operating mode selection

3U0> 1 - 100 %UB 1 30 Operate level of residual overvoltageelement in % of UBase

3I0< 1 - 100 %IB 1 10 Operate level of residual undercurrentelement in % of IBase

3U2> 1 - 100 %UB 1 30 Operate level of neg seq overvoltageelement in % of UBase

3I2< 1 - 100 %IB 1 10 Operate level of neg seq undercurrentelement in % of IBase

OpDUDI Off  On

- - Off Operation of change based function Off/On

DU> 1 - 100 %UB 1 60 Operate level of change in phase voltagein % of UBase

DI< 1 - 100 %IB 1 15 Operate level of change in phase currentin % of IBase

UPh> 1 - 100 %UB 1 70 Operate level of phase voltage in % of  UBase

IPh> 1 - 100 %IB 1 10 Operate level of phase current in % of  IBase

Table continues on next page

1MRK 505 211-UEN C Section 3IED application

255

 Application manual

Page 262: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 262/457

Name Values (Range) Unit Step Default Description

SealIn Off  On

- - On Seal in functionality Off/On

USealln< 1 - 100 %UB 1 70 Operate level of seal-in phase voltage in

% of UBase

IDLD< 1 - 100 %IB 1 5 Operate level for open phase currentdetection in % of IBase

UDLD< 1 - 100 %UB 1 60 Operate level for open phase voltagedetection in % of UBase

3.11 Control

3.11.1 Autorecloser SMBRREC

Function Description IEC 61850

identification

IEC 60617

identification

ANSI/IEEE C37.2

device number

 Autorecloser SMBRREC

O->I 

SYMBOL-L V1 EN

79

3.11.1.1 Application

In certain countries it is standard practice to provide delayed restoration after  busbar protection operation for internal fault, reason being that many busbar faultsare of the transient natures that is, animals, birds, storm, flying objects, etc. In suchapplications, typically one pre-selected feeder is automatically closed with certaintime delay in order to try to re-energize the faulty bus. Typically, the longestoverhead line is selected in order to limit the fault current in case of permanent

 busbar fault. If the first feeder is successfully closed, all other feeder which have been connected to the same bus, are automatically put back into service.

Sensitive differential protection level available in REB670 can be used during such

operation, if increased sensitivity from busbar protection is required. Such busbar restoration logic can be implemented by using optionally available autoreclosingfunctions and built-in logical gates. Two autoreclosing functions are available, onefor each zone.

Automatic reclosing is a well-established method for the restoration of service in a power system after a transient line fault. The majority of line faults are flashover arcs, which are transient by nature. When the power line is switched off by theoperation of line protection and line breakers, the arc de-ionizes and recovers itsability to withstand voltage at a somewhat variable rate. Thus, a certain dead timewith a de-energized line is necessary. Line service can then be resumed by

Section 3 1MRK 505 211-UEN C

IED application

256

 Application manual

Page 263: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 263/457

automatic reclosing of the line breakers. The dead time selected should be longenough to ensure a high probability of arc de-ionization and successful reclosing.

For individual line breakers, auto-reclosing equipment or functions, the auto-

reclosing open time is used to determine line “dead time”. When simultaneoustripping and reclosing at the two line ends occurs, auto-reclosing open time isapproximately equal to the line “dead time”. If the open time and dead time differ then, the line will be energized until the breakers at both ends have opened.

Open

Closed

Operate time

Lineprotection

Circuitbreaker 

Break time

   T  r   i  p  c  o  m  m  a  n   d

   C  o  n   t  a  c   t  s  s  e  p  a  r  a   t  e   d

   A  r  e  e  x   t   i  n  g  u   i  s   h  e  r  s

Fault duration AR open time for breaker   Fault duration

   R  e  s  e   t  s

   I  n  s   t  a  n   t  o   f   f  a  u

   l   t

   O  p  e  r  a   t  e  s

Break timeClosing time

Operate time

   F  a  u   l   t

   O  p  e  r  a   t  e  s

   R  e  s  e   t  s

   C   l  o  s  e  c  o  m  m  a  n   d

   C  o  n   t  a  c   t  c   l  o  s  e

   d

Set AR open time Reclaim time Auto-reclosing

function

   S   t  a  r   t   A   R

   R  e  c   l  o  s   i  n  g

  c  o  m  m  a  n   d

   A   R

  r  e  s  e   t

en04000146.vsd

IEC04000146 V1 EN

Figure 84: Single-shot automatic reclosing at a permanent fault 

Single-phase tripping and single-phase automatic reclosing is a way of limiting theeffect of a single-phase line fault on power system operation. Especially at higher voltage levels, the majority of faults are of single-phase type (around 90%). Tomaintain system stability in power systems with limited meshing or parallel routingsingle phase auto reclosing is of particular value. During the single phase dead timethe system is still capable of transmitting load on the two healthy phases and thesystem is still synchronized. It requires that each phase breaker operatesindividually, which is usually the case for higher transmission voltages.

1MRK 505 211-UEN C Section 3IED application

257

 Application manual

Page 264: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 264/457

A somewhat longer dead time may be required for single-phase reclosingcompared to high-speed three-phase reclosing. This is due to the influence on thefault arc from the voltage and the current in the non-tripped phases.

To maximize the availability of the power system it is possible to choose single pole tripping and automatic reclosing during single-phase faults and three poletripping and automatic reclosing during multi-phase faults. Three-phase automaticreclosing can be performed with or without the use of a synchronicity check, andan energizing check, such as dead line or dead busbar check.

During the single-pole open time there is an equivalent "series"-fault in the systemresulting in a flow of zero sequence current. It is therefore necessary to coordinatethe residual current protections (earth fault protection) with the single pole trippingand the auto-reclosing function. Attention shall also be paid to "pole discordance"that arises when circuit breakers are provided with single pole operating devices.

These breakers need pole discordance protection. They must also be coordinatedwith the single pole auto-recloser and blocked during the dead time when a normaldiscordance occurs. Alternatively, they should use a trip time longer than the setsingle phase dead time.

For the individual line breakers and auto-reclosing equipment, the ”auto-reclosingopen time” expression is used. This is the dead time setting for the Auto-Recloser.During simultaneous tripping and reclosing at the two line ends, auto-reclosingopen time is approximately equal to the line dead time. Otherwise these two timesmay differ as one line end might have a slower trip than the other end which meansthat the line will not be dead until both ends have opened.

If the fault is permanent, the line protection will trip again when reclosing isattempted in order to clear the fault.

It is common to use one automatic reclosing function per line circuit-breaker (CB).When one CB per line end is used, then there is one auto-reclosing function per line end. If auto-reclosing functions are included in duplicated line protection,which means two auto-reclosing functions per CB, one should take measures toavoid uncoordinated reclosing commands. In 1 1/2 breaker, double-breaker andring bus arrangements, two CBs per line end are operated. One auto-reclosingfunction per CB is recommended. Arranged in such a way, sequential reclosing of the two CBs can be arranged with a priority circuit available in the auto-reclosefunction. In case of a permanent fault and unsuccessful reclosing of the first CB,reclosing of the second CB is cancelled and thus the stress on the power system islimited. Another advantage with the breaker connected auto-recloser is thatchecking that the breaker closed before the sequence, breaker prepared for an auto-reclose sequence and so on. is much simpler.

The auto-reclosing function can be selected to perform single-phase and/or three- phase automatic-reclosing from several single-shot to multiple-shot reclosing programs. The three-phase auto-reclosing open time can be set to give either High-Speed Automatic Reclosing (HSAR) or Delayed Automatic-Reclosing (DAR).These expressions, HSAR and DAR, are mostly used for three-phase Reclosing as

Section 3 1MRK 505 211-UEN C

IED application

258

 Application manual

Page 265: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 265/457

single phase is always high speed to avoid maintaining the unsymmetricalcondition. HSAR usually means a dead time of less than 1 second.

In power transmission systems it is common practise to apply single and/or three

 phase, single-shot Auto-Reclosing. In Sub-transmission and Distribution systemstripping and auto-reclosing are usually three-phase. The mode of automatic-reclosing varies however. Single-shot and multi-shot are in use. The first shot canhave a short delay, HSAR, or a longer delay, DAR. The second and followingreclosing shots have a rather long delay. When multiple shots are used the deadtime must harmonize with the breaker duty-cycle capacity.

Automatic-reclosing is usually started by the line protection and in particular byinstantaneous tripping of such protection. The auto-reclosing function can beinhibited (blocked) when certain protection functions detecting permanent faults,such as shunt reactor, cable or busbar protection are in operation. Back-up

 protection zones indicating faults outside the own line are also connected to inhibitthe Auto-Reclose.

Automatic-reclosing should not be attempted when closing a CB and energizing aline onto a fault (SOTF), except when multiple-shots are used where shots 2 etc.will be started at SOTF. Likewise a CB in a multi-breaker busbar arrangementwhich was not closed when a fault occurred should not be closed by operation of the Auto-Reclosing function. Auto-Reclosing is often combined with a releasecondition from synchrocheck and dead line or dead busbar check. In order to limitthe stress on turbo-generator sets from Auto-Reclosing onto a permanent fault, onecan arrange to combine Auto-Reclosing with a synchrocheck on line terminalsclose to such power stations and attempt energizing from the side furthest away

from the power station and perform the synchrocheck at the local end if theenergizing was successful.

Transmission protection systems are usually sub-divided and provided with tworedundant protection IEDs. In such systems it is common to provide auto-reclosingin only one of the sub-systems as the requirement is for fault clearance and afailure to reclose because of the auto-recloser being out of service is not considereda major disturbance. If two auto-reclosers are provided on the same breaker, theapplication must be carefully checked and normally one must be the master and beconnected to inhibit the other auto-recloser if it has started. This inhibit can for example be done from Autorecloser for 3-phase operation(SMBRREC) In progress.

When Single and/or three phase auto-reclosing is considered, there are a number of cases where the tripping shall be three phase anyway. For example:

• Evolving fault where the fault during the dead-time spreads to another phase.The other two phases must then be tripped and a three phase dead-time and auto-reclose initiated

• Permanent fault• Fault during three phase dead-time• Auto-reclose out of service or CB not ready for an auto-reclosing cycle

1MRK 505 211-UEN C Section 3IED application

259

 Application manual

Page 266: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 266/457

“Prepare three-phase tripping” is then used to switch the tripping to three-phase.This signal is generated by the auto-recloser and connected to the trip function

 block and also connected outside the IED through IO when a common auto-recloser is provided for two sub-systems. An alternative signal “Prepare 1 Phasetripping” is also provided and can be used as an alternative when the autorecloser isshared with another subsystem. This provides a fail safe connection so that even afailure in the IED with the auto-recloser will mean that the other sub-system willstart a three-phase trip.

A permanent fault will cause the line protection to trip again when it recloses in anattempt to clear the fault.

The auto-reclosing function allows a number of parameters to be adjusted.

Examples:

• number of auto-reclosing shots• auto-reclosing program• auto-reclosing open times (dead time) for each shot

Auto-reclosing operation OFF and ONOperation of the automatic reclosing can be set OFF and ON by a setting parameter and by external control. Parameter Operation= Off , or On sets the function OFFand ON. In setting Operation= ExternalCtrl , OFF and ON control is made by inputsignal pulses, for example, from the control system or from the binary input (andother systems).

When the function is set ON and operative (other conditions such as CB closed andCB Ready are also fulfilled), the output SETON is activated (high). When thefunction is ready to accept a reclosing start.

Start auto-reclosing and conditions for start of a reclosing cycleThe usual way to start a reclosing cycle, or sequence, is to start it at tripping by line

 protection by applying a signal to the input START. Starting signals can be either,General Trip signals or, only the conditions for Differential, Distance protectionZone 1 and Distance protection Aided trip. In some cases also Directional Earthfault function Aided trip can be connected to start an Auto-Reclose attempt.

In cases where one wants to differentiate three-phase “auto-reclosing open time”,(“dead time”) for different power system configuration or at tripping by different protection stages, one can also use the input STARTHS (Start High-SpeedReclosing). When initiating STARTHS, the auto-reclosing open time for three-

 phase shot 1, t1 3PhHS is used.

A number of conditions need to be fulfilled for the start to be accepted and a newauto-reclosing cycle to be started. They are linked to dedicated inputs. The inputs are:

Section 3 1MRK 505 211-UEN C

IED application

260

 Application manual

Page 267: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 267/457

• CBREADY, CB ready for a reclosing cycle, for example, charged operating gear.• CBPOS to ensure that the CB was closed when the line fault occurred and start

was applied.• No signal at input INHIBIT that is, no blocking or inhibit signal present. After 

the start has been accepted, it is latched in and an internal signal “Started” isset. It can be interrupted by certain events, like an “Inhibit” signal.

Start auto-reclosing from CB open informationIf a user wants to initiate auto-reclosing from the "CB open" position instead of from protection trip signals, the function offers such a possibility. This startingmode is selected with the setting parameter StartByCBOpen=On. It is thennecessary to block reclosing for all manual trip operations. TypicallyCBAuxContType= NormClosed is also set and a CB auxiliary contact of type NC(normally closed) is connected to inputs CBPOS and START. When the signal

changes from “CB closed” to “CB open” an auto-reclosing start pulse is generatedand latched in the function, subject to the usual checks. Then the reclosingsequence continues as usual. One needs to connect signals from manual trippingand other functions, which shall prevent reclosing, to the input INHIBIT.

Blocking of the autorecloserAuto-Reclose attempts are expected to take place only in the event of transientfaults on the own line. The Auto-Recloser must be blocked for the followingconditions:

• Tripping from Delayed Distance protection zones• Tripping from Back-up protection functions

• Tripping from Breaker failure function• Intertrip received from remote end Breaker failure function• Busbar protection tripping

Depending of the starting principle (General Trip or only Instantaneous trip)adopted above the delayed and back-up zones might not be required. Breaker failure local and remote must however always be connected.

Control of the auto-reclosing open time for shot 1Up to four different time settings can be used for the first shot, and one extensiontime. There are separate settings for single-, two- and three-phase auto-reclosing

open time, t1 1Ph, t1 2Ph, t1 3Ph. If no particular input signal is applied, and an auto-reclosing program with single-phase reclosing is selected, the auto-reclosing opentime t1 1Ph will be used. If one of the inputs TR2P or TR3P is activated inconnection with the start, the auto-reclosing open time for two-phase or three-phasereclosing is used. There is also a separate time setting facility for three-phase high-speed auto-reclosing without Synchrocheck, t1 3PhHS , available for use whenrequired. It is activated by the STARTHS input.

An auto-reclosing open time extension delay, tExtended t1, can be added to thenormal shot 1 delay. It is intended to come into use if the communication channelfor permissive line protection is lost. In such a case there can be a significant time

1MRK 505 211-UEN C Section 3IED application

261

 Application manual

Page 268: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 268/457

difference in fault clearance at the two ends of the line. A longer “auto-reclosingopen time” can then be useful. This extension time is controlled by setting

 parameter  Extended t1=On and the input PLCLOST.

Long trip signalIn normal circumstances the trip command resets quickly because of faultclearance. The user can set a maximum trip pulse duration tTrip. A longer tripsignal extends the auto-reclosing open time by tExtended t1. If  Extended t1=Off , along trip signal interrupts the reclosing sequence in the same way as a signal toinput INHIBIT.

Maximum number of reclosing shotsThe maximum number of reclosing shots in an auto-reclosing cycle is selected bythe setting parameter  NoOfShots. The type of reclosing used at the first reclosingshot is set by parameter  FirstShot . The first alternative is three-phase reclosing.

The other alternatives include some single-phase or two-phase reclosing. Usuallythere is no two-phase tripping arranged, and then there will be no two-phase reclosing.

The decision is also made in the tripping logic (SMPTTRC) function block wherethe setting 3Ph, 1/3Ph (or1/2/3Ph) is selected.

FirstShot=3ph (normal setting for a single 3 phase shot)3-phase reclosing, one to five shots according to setting NoOfShots. The outputPrepare three-phase trip PREP3P is always set (high). A trip operation is made as athree-phase trip at all types of fault. The reclosing is as a three-phase Reclosing asin mode 1/2/3ph described below. All signals, blockings, inhibits, timers,requirements and so on. are the same as in the example described below.

FirstShot=1/2/3ph1-phase, 2-phase or 3-phase reclosing first shot, followed by 3-phase reclosingshots, if selected. Here, the auto-reclosing function is assumed to be "On" and"Ready". The breaker is closed and the operation gear ready (operating energystored). Input START (or STARTHS) is received and sealed-in. The outputREADY is reset (set to false). Output ACTIVE is set.

• If TR2P is low and TR3P is low (1-phase trip): The timer for 1-phase reclosingopen time is started and the output 1PT1 (1-phase reclosing in progress) isactivated. It can be used to suppress pole disagreement trip and earth-fault

 protection during the 1-phase open interval.• If TR2P is high and TR3P is low (2-phase trip): The timer for 2-phasereclosing open time is started and the output 2PT1 (2-phase reclosing in

 progress) is activated.• If TR3P is high (3-phase trip): The timer for 3-phase auto-reclosing open time,

t1 3Ph or t1 3PhHS is started and output 3PT1 (3-phase auto-reclosing shot 1in progress) is set.

While any of the auto-reclosing open time timers are running, the outputINPROGR is activated. When the "open time" timer runs out, the respective

Section 3 1MRK 505 211-UEN C

IED application

262

 Application manual

Page 269: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 269/457

internal signal is transmitted to the output module for further checks and to issue aclosing command to the circuit breaker.

When a CB closing command is issued the output prepare 3-phase trip is set. When

issuing a CB closing command a “reclaim” timer tReclaim is started. If no trippingtakes place during that time the auto-reclosing function resets to the “Ready” stateand the signal ACTIVE resets. If the first reclosing shot fails, a 3-phase trip will beinitiated and 3-phase reclosing can follow, if selected.

FirstShot=1/2ph 1-phase or 2-phase reclosing in the first shot.In 1-phase or 2-phase tripping, the operation is as in the above described example,

 program mode 1/2/3ph. If the first reclosing shot fails, a 3-phase trip will be issuedand 3-phase reclosing can follow, if selected. In the event of a 3-phase trip, TR3Phigh, the auto-reclosing will be blocked and no reclosing takes place.

FirstShot=1ph + 1*2ph 1-phase or 2-phase reclosing in the first shotThe 1-phase reclosing attempt can be followed by 3-phase reclosing, if selected. Afailure of a 2-phase reclosing attempt will block the auto-reclosing. If the first tripis a 3-phase trip the auto-reclosing will be blocked. In the event of a 1-phase trip,(TR2P low and TR3P low), the operation is as in the example described above,

 program mode 1/2/3ph. If the first reclosing shot fails, a 3-phase trip will beinitiated and 3-phase reclosing can follow, if selected. A maximum of four additional shots can be done (according to the NoOfShots parameter). At 2-phasetrip (TR2P high and TR3P low), the operation is similar to the above. But, if thefirst reclosing shot fails, a 3-phase trip will be issued and the auto-reclosing will be

 blocked. No more shots are attempted! The expression 1*2ph should be understoodas “Just one shot at 2-phase reclosing” During 3-phase trip (TR2P low and TR3Phigh) the auto-reclosing will be blocked and no reclosing takes place.

FirstShot=1ph + 1*2/3ph 1-phase, 2-phase or 3-phase reclosing in

the first shotAt 1-phase trip, the operation is as described above. If the first reclosing shot fails,a 3-phase trip will be issued and 3-phase reclosing will follow, if selected. At 2-

 phase or 3-phase trip, the operation is similar to the above. But, if the first reclosingshot fails, a 3-phase trip command will be issued and the auto-reclosing will be

 blocked. No more shots take place 1*2/3ph should be understood as “Just one shotat 2-phase or 3-phase reclosing”.

FirstShot=1ph + 1*2/3ph 1-phase, 2-phase or 3-phase reclosing inthe first shotAt 1-phase trip, the operation is as described above. If the first reclosing shot fails,a 3-phase trip will be issued and 3-phase reclosing will follow, if selected. At 2-

 phase or 3-phase trip, the operation is similar as above. But, if the first reclosingshot fails, a 3-phase trip will be issued and the auto-reclosing will be blocked. Nomore shots take place! “1*2/3ph” should be understood as “Just one shot at 2-phaseor 3-phase reclosing”.

1MRK 505 211-UEN C Section 3IED application

263

 Application manual

Page 270: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 270/457

Tab le 96 : Type o f rec losing sho ts at d ifferen t set tings of “FirstSho t”

First Shot 1st shot 2nd-5th shot

3ph 3ph 3ph

1/2/3ph 1ph 3ph2ph 3ph --

3ph 3ph --

1/2ph 1ph 3ph

2ph 3ph --

-- --

1ph + 1*2ph 1ph 3ph

2ph -- --

-- --

1/2ph + 1*3ph 1ph 3ph

2ph 3ph

3ph --

1ph + 1*2/3ph 1ph 3ph

2ph --

3ph --

A start of a new reclosing cycle is blocked during the set “reclaim time” after theselected number of reclosing shots have been made.

External selection of auto-reclose modeThe auto-reclose mode can be selected by use of the available logic function

 blocks. Below is an example where the choice of mode is done from a symbol onthe local HMI through selector switch function block with only 3 phase or 1/3

 phase mode, but alternatively there can for example, be a physical selector switchon the front of the panel which is connected to a binary to integer function block (B16I).

If the PSTO input is used, connected to the Local-Remote switch on the local HMI,the choice can also be from the station HMI system, typically ABB Microscadathrough IEC 61850 communication.

The connection example for selection of the auto-reclose mode is shown in .Selected names are just examples but note that the symbol on local HMI can onlyshow three signs.

Section 3 1MRK 505 211-UEN C

IED application

264

 Application manual

Page 271: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 271/457

IEC07000119_en.vsd

SMBRREC

MODEINT

PSTO

SWPOSNNAME1NAME2

31/3

INTONE

SLGGIO

IEC07000119 V2 EN

Figure 85: Selection of the auto-reclose mode from a local HMI symbol 

through a selector switch function block 

Reclosing reclaim timerThe reclaim timer tReclaim defines the time it takes from issue of the reclosingcommand, until the reclosing function resets. Should a new trip occur during thistime, it is treated as a continuation of the first fault. The reclaim timer is startedwhen the CB closing command is given.

Pulsing of the CB closing command and CounterThe CB closing command, CLOSECB is given as a pulse with a duration set by

 parameter tPulse. For circuit-breakers without an anti-pumping function, close pulse cutting can be used. It is selected by parameter CutPulse=On. In case of anew trip pulse (start), the closing command pulse is then cut (interrupted). Theminimum closing pulse length is always 50 ms. At the issue of the Reclosingcommand, the appropriate Reclosing operation counter is incremented. There is acounter for each type of Reclosing and one for the total number of Reclosing

commands.

Transient faultAfter the Reclosing command the reclaim timer keeps running for the set time. If no tripping occurs within this time, tReclaim, the Auto-Reclosing will reset. TheCB remains closed and the operating gear recharges. The input signals CBPOS andCBREADY will be set

Permanent fault and reclosing unsuccessful signalIf a new trip occurs, and a new input signal START or TRSOTF appears, after theCB closing command, the output UNSUCCL (unsuccessful closing) is set high.

The timer for the first shot can no longer be started. Depending on the set number of Reclosing shots further shots may be made or the Reclosing sequence is ended.After reclaim timer time-out the Auto-Reclosing function resets, but the CBremains open. The “CB closed” information through the input CBPOS is missing.Thus, the reclosing function is not ready for a new reclosing cycle.

 Normally, the signal UNSUCCL appears when a new trip and start is received after the last reclosing shot has been made and the auto-reclosing function is blocked.The signal resets after reclaim time. The “unsuccessful” signal can also be made todepend on CB position input. The parameter UnsucClByCBChk should then be setto CBCheck , and a timer tUnsucCl should be set too. If the CB does not respond to

1MRK 505 211-UEN C Section 3IED application

265

 Application manual

Page 272: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 272/457

the closing command and does not close, but remains open, the output UNSUCCLis set high after time tUnsucCl . The Unsuccessful output can for example, be usedin Multi-Breaker arrangement to cancel the auto-reclosing function for the second

 breaker, if the first breaker closed onto a persistent fault. It can also be used togenerate a Lock-out of manual closing until the operator has reset the Lock-out, seeseparate section.

Lock-out initiationIn many cases there is a requirement that a Lock-out is generated when the auto-reclosing attempt fails. This is done with logic connected to the in- and outputs of the Autoreclose function and connected to Binary IO as required. Many alternativeways of performing the logic exist depending on whether manual closing isinterlocked in the IED, whether an external physical Lock-out relay exists andwhether the reset is hardwired, or carried out by means of communication. Thereare also different alternatives regarding what shall generate Lock-out. Examples of 

questions are:

• Shall back-up time delayed trip give Lock-out (normally yes)• Shall Lock-out be generated when closing onto a fault (mostly)• Shall Lock-out be generated when the Autorecloser was OFF at the fault or for 

example, in Single phase AR mode and the fault was multi-phase (normallynot as not closing attempt has been given)

• Shall Lock-out be generated if the Breaker did not have sufficient operating power for an auto-reclosing sequence (normally not as no closing attempt has been given)

In figures 86 and 87 the logic shows how a closing Lock-out logic can be designedwith the Lock-out relay as an external relay alternatively with the Lock-out createdinternally with the manual closing going through the Synchro-check function. Anexample of Lock-out logic.

Lock-out

RXMD1

11

12

21

MAIN ZAK CLOSE CLOSE COMMAND

SMBO

OR

SMBRRECOR

CCRBRF

BJ-TRIP

ZCVPSOF-TRIP INHIBIT

UNSUCCL

TRBU

IEC05000315_2_en.vsd

IEC05000315-WMF V2 EN

Figure 86: Lock-out arranged with an external Lock-out relay 

Section 3 1MRK 505 211-UEN C

IED application

266

 Application manual

Page 273: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 273/457

CLOSE COMMAND

OR

SMBRRECOR

CCRBRF

BU-TRIP

ZCVPSOF-TRIP INHIBIT

UNSUCCL

TRBU

SMPPTRC

 

 AND

RESET LOCK-OUT

OR

OR

SESRSYN

SOFTWARE

OR IO RESET

 AUTO STOP

MAN ENOK

MAN CLOSE

SMBRREC CLOSE

CLLKOUT

RSTLOUT

SETLKOUT

IEC05000316_2_en.vsd

SMBO

IEC05000316-WMF V2 EN

Figure 87: Lock-out arranged with internal logic with manual closing going 

through in IED 

Evolving faultAn evolving fault starts as a single-phase fault which leads to single-phase trippingand then the fault spreads to another phase. The second fault is then cleared by three-

 phase tripping.

The Auto-Reclosing function will first receive a trip and start signal (START)without any three-phase signal (TR3P). The Auto-Reclosing function will start a

single-phase reclosing, if programmed to do so. At the evolving fault clearancethere will be a new signal START and three-phase trip information, TR3P. The single- phase reclosing sequence will then be stopped, and instead the timer, t1 3Ph, for three- phase reclosing will be started from zero. The sequence will continue as a three- phase reclosing sequence, if it is a selected alternative reclosing mode.

The second fault which can be single phase is tripped three phase because tripmodule (TR) in the IED has an evolving fault timer which ensures that second faultis always tripped three phase. For other types of relays where the relays do notinclude this function the output PREP3PH (or the inverted PERMIT1PH) is used to

 prepare the other sub-system for three phase tripping. This signal will, for evolvingfault situations be activated a short time after the first trip has reset and will thus

ensure that new trips will be three phase.

Automatic continuation of the reclosing sequenceSMBRREC function can be programmed to proceed to the following reclosingshots (if multiple shots are selected) even if start signals are not received from the

 protection functions, but the breaker is still not closed. This is done by setting parameter  AutoCont = On and tAutoContWait to the required delay for the functionto proceed without a new start.

1MRK 505 211-UEN C Section 3IED application

267

 Application manual

Page 274: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 274/457

Thermal overload protection holding the auto-reclosing function backIf the input THOLHOLD (thermal overload protection holding reclosing back) isactivated, it will keep the reclosing function on a hold until it is reset. There maythus be a considerable delay between start of Auto-Reclosing and reclosingcommand to the circuit-breaker. An external logic limiting the time and sending aninhibit to the INHIBIT input can be used. The input can also be used to set the Auto-Reclosing on hold for a longer or shorter period.

3.11.1.2 Setting guidelines

ConfigurationUse the PCM600 configuration tool to configure signals.

Autorecloser function parameters are set via the local HMI or Parameter SettingTool (PST). Parameter Setting Tool is a part of PCM600.

Recommendations for input signalsPlease see examples in figure 88, figure 89 and figure 90 of default factoryconfigurations.

ON and OFF

These inputs can be connected to binary inputs or to a communication interface block for external control.

START

It should be connected to the trip output protection function, which starts theautorecloser for 3-phase operation (SMBRREC) function. It can also be connectedto a binary input for start from an external contact. A logical OR-gate can be usedto combine the number of start sources.

If StartByCBOpen is used, the CB Open condition shall also beconnected to the input START.

STARTHS, Start High-speed auto-reclosing

It is often not used and connected to FALSE. It may be used when one wants to use

two different dead times in different protection trip operations. This input starts thedead time t1 3PhHS . High-speed reclosing shot 1 started by this in put is without asynchronization check.

INHIBIT

To this input shall be connected signals that interrupt a reclosing cycle or prevent astart from being accepted. Such signals can come from protection for a lineconnected shunt reactor, from transfer trip receive, from back-up protectionfunctions, busbar protection trip or from breaker failure protection. When the CBopen position is set to start SMBRREC, then manual opening must also be

Section 3 1MRK 505 211-UEN C

IED application

268

 Application manual

Page 275: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 275/457

connected here. The inhibit is often a combination of signals from external IEDsvia the IO and internal functions. An OR gate is then used for the combination.

CBPOS and CBREADY

These should be connected to binary inputs to pick-up information from the CB.The CBPOS input is interpreted as CB Closed, if parameter CBAuxContType is set

 NormOpen, which is the default setting. At three operating gears in the breaker (single pole operated breakers) the connection should be “All poles closed” (seriesconnection of the NO contacts) or “At least one pole open” (parallel connection of 

 NC contacts) if the CBAuxContType is set to NormClosed . The “CB Ready” is asignal meaning that the CB is ready for a reclosing operation, either Close-Open(CO), or Open-Close-Open (OCO). If the available signal is of type “CB notcharged” or “not ready”, an inverter can be inserted in front of the CBREADY input.

SYNC

This is connected to the internal synchrocheck function when required. It can also be connected to a binary input for synchronization from an external device. If neither internal nor external synchronism or energizing check is required, it can beconnected to a permanently high source, TRUE. The signal is required for three

 phase shots 1-5 to proceed (Note! Not the HS step).

PLCLOST

This is intended for line protection permissive signal channel lost (fail) for example, PLC= Power Line Carrier fail. It can be connected, when required to

 prolong the AutoReclosing time when communication is not working, that is, one

line end might trip with a zone 2 delay. When the function is not used it is set toFALSE.

TRSOTF

This is the signal “Trip by Switch Onto Fault”. It is usually connected to the“switch onto fault” output of line protection if multi-shot Auto-Reclose attemptsare used. The input will start the shots 2-5. For single shot applications the input isset to FALSE.

THOLHOLD

Signal “Thermal overload protection holding back Auto-Reclosing”. It is normally

set to FALSE. It can be connected to a thermal overload protection trip signalwhich resets only when the thermal content has gone down to an acceptable level,for example, 70%. As long as the signal is high, indicating that the line is hot, theAuto-Reclosing is held back. When the signal resets, a reclosing cycle willcontinue. Please observe that this have a considerable delay. Input can also be usedfor other purposes if for some reason the Auto-Reclose shot is halted.

TR2P and TR3P

Signals for two-phase and three-phase trip. They are usually connected to thecorresponding output of the TRIP block. They control the choice of dead time and

1MRK 505 211-UEN C Section 3IED application

269

 Application manual

Page 276: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 276/457

the reclosing cycle according to the selected program. Signal TR2P needs to beconnected only if the trip has been selected to give 1/2/3 phase trip and an autoreclosing cycle with two phase reclosing is foreseen.

WAIT

Used to hold back reclosing of the “low priority unit” during sequential reclosing.See “Recommendation for multi-breaker arrangement” below. The signal isactivated from output WFMASTER on the second breaker Auto-Recloser in multi-

 breaker arrangements.

BLKON

Used to block the autorecloser for 3-phase operation (SMBRREC) function for example, when certain special service conditions arise. Input is normally set toFALSE. When used, blocking must be reset with BLOCKOFF.

BLOCKOFF

Used to Unblock SMBRREC function when it has gone to Block due to activatinginput BLKON or by an unsuccessful Auto-Reclose attempt if thesetting BlockByUnsucCl is set to On. Input is normally set to FALSE.

RESET

Used to Reset SMBRREC to start condition. Possible Thermal overload Hold will be reset. Positions, setting On-Off. will be started and checked with set times. Inputis normally set to FALSE.

Recommendations for output signalsPlease see figure 88, figure 89 and figure 90 and default factory configuration for examples.

SETON

Indicates that Autorecloser for 3-phase operation (SMBRREC) function isswitched on and operative.

BLOCKED

Indicates that SMRREC function is temporarily or permanently blocked.

ACTIVE

Indicates that SMBRREC is active, from start until end of Reclaim time.

INPROGR

Indicates that a sequence is in progress, from start until reclosing command.

UNSUCCL

Indicates unsuccessful reclosing.

Section 3 1MRK 505 211-UEN C

IED application

270

 Application manual

Page 277: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 277/457

CLOSECB

Connect to a binary output for circuit-breaker closing command.

READYIndicates that SMBRREC function is ready for a new and complete reclosingsequence. It can be connected to the zone extension of a line protection shouldextended zone reach before automatic reclosing be necessary.

1PT1 and 2PT1

Indicates that single-phase or two-phase automatic reclosing is in progress. It isused to temporarily block an earth-fault and/or pole disagreement function duringthe single-phase or two-phase open interval.

3PT1,-3PT2,-3PT3,-3PT4 and -3PT5

Indicates that three-phase automatic reclosing shots 1-5 are in progress. The signalscan be used as an indication of progress or for own logic.

PREP3P

Prepare three-phase trip is usually connected to the trip block to force a coming tripto be a three-phase one. If the function cannot make a single-phase or two-phasereclosing, the tripping should be three-phase.

PERMIT1P

Permit single-phase trip is the inverse of PREP1P. It can be connected to a binary

output relay for connection to external protection or trip relays. In case of a totalloss of auxiliary power, the output relay drops and does not allow single-phase trip.If needed, the signal can be inverted by a contact of the output relay breaking.

WFMASTER

Wait from master is used in high priority units to hold back reclosing of the low priority unit during sequential reclosing. Refer to the recommendation for multi- breaker arrangements in figure 90.

Other outputs

The other outputs can be connected for indication, disturbance recording, as required.

1MRK 505 211-UEN C Section 3IED application

271

 Application manual

Page 278: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 278/457

ON

OFFBLKON

BLOCKOFF

INHIBIT

BLOCKED

SETONINPROGR

 ACTIVE

UNSUCCL

SUCCL

CLOSECB

CBREADY

CBPOS

PLCLOST

1PT1

WFMASTER

RESET

START

THOLHOLD

READY

TRSOTF

SYNC

INPUT

xx

xxxx

xx

xx

xx

xx

xx

xx

xx

>1

>1

OUTPUT

xx

xxxx

xx

xx

xx

xx

xx

xx

xx

PROTECTION

xxxx-TRIP

ZCVPSOF-TRIPZMQPDIS-TRIP

SESRSYN-AUTOOK

IOM IOM

SMBRREC

IEC04000135_2_en.vsd

PERMIT1PPREP3P

F

F

T

STARTHS

SKIPHS

F

F

TR2P

TR3P

F

T

WAIT

RSTCOUNT

F

F

3PT12PT1

3PT2

3PT3

3PT4

3PT5

F

IEC04000135 V2 EN

Figure 88: Example of I/O-signal connections at a three-phase reclosing 

function 

Setting recommendations for multi-breaker arrangementsSequential reclosing in multi-breaker arrangements, like 1 1/2-breaker, double

 breaker and ring bus, is achieved by giving the two line breakers different priorities. Please refer to figure 90. In a single breaker arrangement the setting is Priority = None. In a multi-breaker arrangement the setting for the first CB, theMaster, is Priority = High and for the other CB Priority = Low.

While the reclosing of the master is in progress, it issues the signal WFMASTER.A reset delay of one second ensures that the WAIT signal is kept high for theduration of the breaker closing time. After an unsuccessful reclosing it is alsomaintained by the signal UNSUCCL. In the slave unit, the signal WAIT holds back a reclosing operation. When the WAIT signal is reset at the time of a successfulreclosing of the first CB, the slave unit is released to continue the reclosingsequence. A parameter tWait sets a maximum waiting time for the reset of theWAIT. At time-out it interrupts the reclosing cycle of the slave unit. If reclosing of the first breaker is unsuccessful, the output signal UNSUCCL connected to theinput INHIBIT of the slave unit interrupts the reclosing sequence of the latter.

Section 3 1MRK 505 211-UEN C

IED application

272

 Application manual

Page 279: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 279/457

The signals can be cross-connected to allow simple changing of the priority by just setting the High and the Low priorities withoutchanging the configuration. The inputs CBPOS for each breaker areimportant in multi breaker arrangements to ensure that the CB wasclosed at the beginning of the cycle. If the High priority breaker isnot closed the High priority moves to the low priority breaker.

ON

OFF

BLKON

BLOCKOFF

INHIBIT

BLOCKED

SETON

INPROGR

 ACTIVE

UNSUCCL

SUCCL

CLOSECB

PERMIT1P

CBREADYCBPOS

PLCLOST

3PT1

WFMASTER

RESET

START1PT1

2PT1

TRSOTF

TR2P

TR3P

SYNC

INPUT

xx

xx

xx

xxxx

xx

xx

xx

xx

xx

>1

>1

OUTPUT

xx

>1

PROTECTION

xxxx-TRIP

ZCVPSOF-TRIPZMQPDIS--TRIP

TRIP-TR2PTRIP-TR3P

SESRSYN-AUTOOK

EF4PTOC-BLOCK

IOM IOM

SMBRREC

IEC04000136_2_en.vsd

xxxx

xx

xxxx

xxxxxxxx

STARTHS

SKIPHSF

F

THOLHOLDF

WAIT

RSTCOUNTF

F

3PT2

3PT3

3PT4

3PT5

F

T

F

READYPREP3P TRIP-P3PTR

IEC04000136 V2 EN

Figure 89: Example of I/O-signal connections in a single-phase reclosing 

function 

1MRK 505 211-UEN C Section 3IED application

273

 Application manual

Page 280: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 280/457

IEC04000137_2_en.vsd

 ACTIVE

UNSUCCL

READY

CLOSECB

3PT23PT3

WAIT

CBPOSCBREADY

TRSOTF

START

RESET

BLOCKOFF

BLKON

OFF

ON BLOCKED

SETON

INPROGR

3PT4SYNC

INHIBIT

Terminal ‘‘ Master ”

Priority = High

SMBRREC

CLOSECB

WAIT

Terminal ‘‘ Slave ”

Priority = Low

CB1

CB2

WFMASTER

WFMASTER

*) Other input/output signals as in previous single

breaker arrangements

PLCLOST

SUCCL

SKIPHS

STARTHS

RSTCOUNT

THOLHOLD

PERMIT1P

PREP3P

3PT1

2PT11PT1

3PT5

RESET

BLOCKOFF

BLKONOFF

ON

INHIBIT

PLCLOST

START

SKIPHS

STARTHS

CBPOSCBREADY

SYNC

THOLHOLD

TRSOTF

3PT2

3PT33PT4

PERMIT1P

PREP3P

3PT12PT11PT1

3PT5

 ACTIVE

UNSUCCL

READY

BLOCKED

SETONINPROGR

x

x

SUCCL

SMBRREC

IEC04000137 V2 EN

Figure 90: Additional input and output signals at multi-breaker arrangement 

Auto-recloser parameter settings

Section 3 1MRK 505 211-UEN C

IED application

274

 Application manual

Page 281: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 281/457

Operation

The operation of the Autorecloser for 3-phase operation (SMBRREC) function can be switched On and Off . The setting External ctrl makes it possible to switch it On

or Off using an external switch via IO or communication ports.

NoOfShots, Number of reclosing shots

In power transmission 1 shot is mostly used. In most cases one reclosing shot issufficient as the majority of arcing faults will cease after the first reclosing shot. In

 power systems with many other types of faults caused by other phenomena, for example wind, a greater number of reclose attempts (shots) can be motivated.

First shot and reclosing program

There are six different possibilities in the selection of reclosing programs. The typeof reclosing used for different kinds of faults depends on the power system

configuration and the users practices and preferences. When the circuit-breakersonly have three-phase operation, then three-phase reclosing has to be chosen. Thisis usually the case in subtransmission and distribution lines. Three-phase trippingand reclosing for all types of faults is also widely accepted in completely meshed

 power systems. In transmission systems with few parallel circuits, single-phasereclosing for single-phase faults is an attractive alternative for maintaining serviceand system stability.

Auto-reclosing open times, dead times

Single-phase auto-reclosing time: A typical setting is t1 1Ph = 800ms. Due to theinfluence of energized phases the arc extinction may not be instantaneous. In long

lines with high voltage the use of shunt reactors in the form of a star with a neutralreactor improves the arc extinction.

Three-phase shot 1 delay: For three-phase High-Speed Auto-Reclosing (HSAR) atypical open time is 400ms. Different local phenomena, such as moisture, salt,

 pollution, can influence the required dead time. Some users apply Delayed Auto-Reclosing (DAR) with delays of 10s or more. The delay of reclosing shot 2 and

 possible later shots are usually set at 30s or more. A check that the CB duty cyclecan manage the selected setting must be done. The setting can in some cases berestricted by national regulations. For multiple shots the setting of shots 2-5 must

 be longer than the circuit breaker duty cycle time.

 Extended t1 and tExtended t1, Extended auto-reclosing open time for shot 1.

The communication link in a permissive (not strict) line protection scheme, for instance a power line carrier (PLC) link, may not always be available. If lost, it canresult in delayed tripping at one end of a line. There is a possibility to extend the auto-reclosing open time in such a case by use of an input to PLCLOST, and the setting

 parameters. Typical setting in such a case: Extended t1 = On and tExtended t1 =

0.8 s.

1MRK 505 211-UEN C Section 3IED application

275

 Application manual

Page 282: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 282/457

tSync, Maximum wait time for synchronizationcheck

The time window should be coordinated with the operate time and other settings of the synchronization check function. Attention should also be paid to the possibility

of a power swing when reclosing after a line fault. Too short a time may prevent a potentially successful reclosing.

tTrip, Long trip pulse

Usually the trip command and start auto-reclosing signal reset quickly as the faultis cleared. A prolonged trip command may depend on a CB failing to clear thefault. A trip signal present when the CB is reclosed will result in a new trip.Depending on the setting Extended t1 = Off or On a trip/start pulse longer than the

 set time tTrip will either block the reclosing or extend the auto-reclosing open time.A trip pulse longer than the set time tTrip will inhibit the reclosing. At a settingsomewhat longer than the auto-reclosing open time, this facility will not influence

the reclosing. A typical setting of tTrip could be close to the auto-reclosing open time.

tInhibit, Inhibit resetting delay

A typical setting is tInhibit = 5.0 s to ensure reliable interruption and temporary blocking of the function. Function will be blocked during this time after the tinhibit 

has been activated.

tReclaim, Reclaim time

The Reclaim time sets the time for resetting the function to its original state, after which a line fault and tripping will be treated as an independent new case with anew reclosing cycle. One may consider a nominal CB duty cycle of for instance,

O-0.3sec CO- 3 min. – CO. However the 3 minute (180 s) recovery time is usuallynot critical as fault levels are mostly lower than rated value and the risk of a newfault within a short time is negligible. A typical time may be tReclaim = 60 or 180

 s dependent of the fault level and breaker duty cycle.

StartByCBOpen

The normal setting is Off . It is used when the function is started by protection tripsignals.

FollowCB

The usual setting is Follow CB = Off . The setting On can be used for delayedreclosing with long delay, to cover the case when a CB is being manually closedduring the “auto-reclosing open time” before the auto-reclosing function has issuedits CB closing command.

tCBClosedMin

A typical setting is 5.0 s. If the CB has not been closed for at least this minimumtime, a reclosing start will not be accepted.

Section 3 1MRK 505 211-UEN C

IED application

276

 Application manual

Page 283: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 283/457

CBAuxContType, CB auxiliary contact type

It shall be set to correspond to the CB auxiliary contact used. A NormOpen contactis recommended in order to generate a positive signal when the CB is in the closed

 position.

CBReadyType, Type of CB ready signal connected

The selection depends on the type of performance available from the CB operatinggear. At setting OCO (CB ready for an Open – Close – Open cycle), the conditionis checked only at the start of the reclosing cycle. The signal will disappear after tripping, but the CB will still be able to perform the C-O sequence. For theselection CO (CB ready for a Close – Open cycle) the condition is also checkedafter the set auto-reclosing dead time. This selection has a value first of all at multi-shot reclosing to ensure that the CB is ready for a C-O sequence at shot 2 andfurther shots. During single-shot reclosing, the OCO selection can be used. A

 breaker shall according to its duty cycle always have storing energy for a COoperation after the first trip. (IEC 56 duty cycle is O-0.3sec CO-3minCO).

tPulse, Breaker closing command pulse duration

The pulse should be long enough to ensure reliable operation of the CB. A typicalsetting may be tPulse=200 ms. A longer pulse setting may facilitate dynamicindication at testing, for example, in “Debug” mode of Application Configurationtool (ACT). In CBs without anti-pumping relays, the setting CutPulse = On can beused to avoid repeated closing operation when reclosing onto a fault. A new startwill then cut the ongoing pulse.

BlockByUnsucCl

Setting of whether an unsuccessful auto-reclose attempt shall set the Auto-Reclosein block. If used the inputs BLOCKOFF must be configured to unblock thefunction after an unsuccessful Reclosing attempt. Normal setting is Off .

UnsucClByCBCheck, Unsuccessful closing by CB check

The normal setting is NoCBCheck . The “auto-reclosing unsuccessful” event is thendecided by a new trip within the reclaim time after the last reclosing shot. If onewants to get the UNSUCCL (Unsuccessful closing) signal in the case the CB doesnot respond to the closing command, CLOSECB, one can set UnsucClByCBCheck =CB Check and set tUnsucCl for instance to 1.0 s.

Priority and time tWaitForMaster

In single CB applications, one sets Priority = None. At sequential reclosing thefunction of the first CB, e.g. near the busbar, is set Priority = High and for thesecond CB Priority = Low. The maximum waiting time, tWaitForMaster of thesecond CB is set longer than the “auto-reclosing open time” and a margin for synchrocheck at the first CB. Typical setting is tWaitForMaster=2sec.

1MRK 505 211-UEN C Section 3IED application

277

 Application manual

Page 284: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 284/457

AutoCont and tAutoContWait , Automatic continuation to the next shotif the CB is not closed within the set time

The normal setting is AutoCont = Off . The tAutoContWait is the length of time

SMBRREC waits to see if the breaker is closed when AutoCont is set to On. Normally, the setting can be tAutoContWait = 2 sec.

3.11.1.3 Setting parameters

Table 97: SMBRREC Group settings (basic)

Name Values (Range) Unit Step Default Description

Operation Off  External ctrlOn

- - External ctrl Off, ExternalCtrl, On

 ARMode 3 phase1/2/3ph

1/2ph1ph+1*2ph1/2ph+1*3ph1ph+1*2/3ph

- - 1/2/3ph The AR mode selection e.g. 3ph, 1/3ph

t1 1Ph 0.000 - 60.000 s 0.001 1.000 Open time for shot 1, single-phase

t1 3Ph 0.000 - 60.000 s 0.001 6.000 Open time for shot 1, delayed reclosing3ph

t1 3PhHS 0.000 - 60.000 s 0.001 0.400 Open time for shot 1, high speedreclosing 3ph

tReclaim 0.00 - 6000.00 s 0.01 60.00 Duration of the reclaim time

tSync 0.00 - 6000.00 s 0.01 30.00 Maximum wait time for synchrocheck OK

tTrip 0.000 - 60.000 s 0.001 0.200 Maximum trip pulse duration

tPulse 0.000 - 60.000 s 0.001 0.200 Duration of the circuit breaker closingpulse

tCBClosedMin 0.00 - 6000.00 s 0.01 5.00 Min time that CB must be closed beforenew sequence allows

tUnsucCl 0.00 - 6000.00 s 0.01 30.00 Wait time for CB before indicatingUnsuccessful/Successful

Priority NoneLowHigh

- - None Priority selection between adjacentterminals None/Low/High

tWaitForMaster 0.00 - 6000.00 s 0.01 60.00 Maximum wait time for release fromMaster 

Section 3 1MRK 505 211-UEN C

IED application

278

 Application manual

Page 285: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 285/457

Table 98: SM BRREC Group settings (advanced)

Name Values (Range) Unit Step Default Description

NoOfShots 12

345

- - 1 Max number of reclosing shots 1-5

StartByCBOpen Off  On

- - Off To be set ON if AR is to be started byCB open position

CBAuxContType NormClosedNormOpen

- - NormOpen Select the CB aux contact type NC/NOfor CBPOS input

CBReadyType COOCO

- - CO Select type of circuit breaker readysignal CO/OCO

t1 2Ph 0.000 - 60.000 s 0.001 1.000 Open time for shot 1, two-phase

t2 3Ph 0.00 - 6000.00 s 0.01 30.00 Open time for shot 2, three-phase

t3 3Ph 0.00 - 6000.00 s 0.01 30.00 Open time for shot 3, three-phase

t4 3Ph 0.00 - 6000.00 s 0.01 30.00 Open time for shot 4, three-phase

t5 3Ph 0.00 - 6000.00 s 0.01 30.00 Open time for shot 5, three-phase

Extended t1 Off  On

- - Off Extended open time at loss of  permissive channel Off/On

tExtended t1 0.000 - 60.000 s 0.001 0.500 3Ph Dead time is extended with thisvalue at loss of perm ch

tInhibit 0.000 - 60.000 s 0.001 5.000 Inhibit reclosing reset time

CutPulse Off  On

- - Off Shorten closing pulse at a new trip Off/On

Follow CB Off  On

- - Off Advance to next shot if CB has beenclosed during dead time

 AutoCont Off On

- - Off Continue with next reclosing-shot if  breaker did not close

tAutoContWait 0.000 - 60.000 s 0.001 2.000 Wait time after close command beforeproceeding to next shot

UnsucClByCBChk NoCBCheckCB check

- - NoCBCheck Unsuccessful closing signal obtained bychecking CB position

BlockByUnsucCl Off  On

- - Off Block AR at unsuccessful reclosing

ZoneSeqCoord Off  On

- - Off Coordination of down stream devices tolocal prot unit’s AR

3.11.2 Apparatus control APC

3.11.2.1 Application

The apparatus control is a function for control and supervising of circuit breakers,disconnectors, and earthing switches within a bay. Permission to operate is givenafter evaluation of conditions from other functions such as interlocking,synchrocheck, operator place selection and external or internal blockings.

1MRK 505 211-UEN C Section 3IED application

279

 Application manual

Page 286: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 286/457

Figure 91 gives an overview from what places the apparatus control functionreceive commands. Commands to an apparatus can be initiated from the ControlCentre (CC), the station HMI or the local HMI on the IED front.

Station HMI

GW

cc

Station bus

breakers disconnectors earthing switches

IEC08000227.vsd

 Apparatus

Control

IED

I/O

Local

HMI

 Apparatus

Control

IED

I/O

 Apparatus

Control

IED

I/O

Local

HMI

Local

HMI

IEC08000227 V1 EN

Figure 91: Overview of the apparatus control functions 

Features in the apparatus control function:

• Operation of primary apparatuses• Select-Execute principle to give high security• Selection and reservation function to prevent simultaneous operation• Selection and supervision of operator place• Command supervision• Block/deblock of operation• Block/deblock of updating of position indications• Substitution of position indications• Overriding of interlocking functions• Overriding of synchrocheck • Pole discordance supervision• Operation counter  • Suppression of Mid position

The apparatus control function is realized by means of a number of function blocksdesignated:

Section 3 1MRK 505 211-UEN C

IED application

280

 Application manual

Page 287: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 287/457

• Switch controller SCSWI• Circuit breaker SXCBR • Circuit switch SXSWI• Bay control QCBAY• Position evaluation POS_EVAL• Bay reserve QCRSV• Reservation input RESIN• Local remote LOCREM• Local remote control LOCREMCTRL

SCSWI, SXCBR, SXSWI and CBAY are logical nodes according to IEC 61850.The signal flow between these function blocks appears in figure 92. To realize thereservation function, the function blocks Reservation input (RESIN) and Bayreserve (QCRSV) also are included in the apparatus control function. Theapplication description for all these functions can be found below. The functionSCILO in the figure below is the logical node for interlocking.

Control operation can be performed from the local IED HMI. If the administrator has defined users with the UMT tool, then the local/remote switch is under authority control. If not, the default (factory) user is the SuperUser that can

 perform control operations from the local IED HMI without LogOn. The default position of the local/remote switch is on remote.

1MRK 505 211-UEN C Section 3IED application

281

 Application manual

Page 288: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 288/457

en05000116.vsd

SXCBRSCSWI

SCILO

SXCBR

SXCBR

SCSWI

SCILO

SXSWI

-QA1

-QB1

-QB9

IEC 61850

QCBAY

IEC05000116 V1 EN

Figure 92: Signal flow between apparatus control function blocks 

The IEC 61850 communication has always priority over binaryinputs, e.g. a block command on binary inputs will not preventcommands over IEC 61850.

Bay control (QCBAY)

The Bay control (QCBAY) is used to handle the selection of the operator place per  bay. The function gives permission to operate from two types of locations either from Remote (for example, control centre or station HMI) or from Local (localHMI on the IED) or from all (Local and Remote). The Local/Remote switch

 position can also be set to Off, which means no operator place selected that is,operation is not possible neither from local nor from remote.

QCBAY also provides blocking functions that can be distributed to differentapparatuses within the bay. There are two different blocking alternatives:

• Blocking of update of positions• Blocking of commands

Section 3 1MRK 505 211-UEN C

IED application

282

 Application manual

Page 289: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 289/457

The function does not have a corresponding functionality defined in the IEC 61850standard, which means that this function is included as a vendor specific logical node.

Switch controller (SCSWI)

SCSWI may handle and operate on one three-phase device or three one-phaseswitching devices.

After the selection of an apparatus and before the execution, the switch controller  performs the following checks and actions:

• A request initiates to reserve other bays to prevent simultaneous operation.• Actual position inputs for interlocking information are read and evaluated if 

the operation is permitted.• The synchrocheck/synchronizing conditions are read and checked, and

 performs operation upon positive response.• The blocking conditions are evaluated• The position indications are evaluated according to given command and its

requested direction (open or closed).

The command sequence is supervised regarding the time between:

• Select and execute.• Select and until the reservation is granted.• Execute and the final end position of the apparatus.• Execute and valid close conditions from the synchrocheck.

At error the command sequence is cancelled.In the case when there are three one-phase switches (SXCBR) connected to theswitch controller function, the switch controller will "merge" the position of thethree switches to the resulting three-phase position. In case of a pole discordancesituation, that is, the positions of the one-phase switches are not equal for a timelonger than a settable time; an error signal will be given.

The switch controller is not dependent on the type of switching device SXCBR or SXSWI. The switch controller represents the content of the SCSWI logical node(according to IEC 61850) with mandatory functionality.

Switch (SXCBR/SXSWI)The Switch is a function used to close and interrupt an ac power circuit under normal conditions, or to interrupt the circuit under fault, or emergency conditions.The intention with this function is to represent the lowest level of a power-switching device with or without short circuit breaking capability, for example,circuit breakers, disconnectors, earthing switches etc.

The purpose of this function is to provide the actual status of positions and to perform the control operations, that is, pass all the commands to the primaryapparatus via output boards and to supervise the switching operation and position.

The Switch has this functionality:

1MRK 505 211-UEN C Section 3IED application

283

 Application manual

Page 290: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 290/457

• Local/Remote switch intended for the switchyard• Block/deblock for open/close command respectively• Update block/deblock of position indication• Substitution of position indication• Supervision timer that the primary device starts moving after a command• Supervision of allowed time for intermediate position• Definition of pulse duration for open/close command respectively

The realization of this function is performed with SXCBR representing a circuit breaker and with SXSWI representing a circuit switch that is, a disconnector or anearthing switch.

The Circuit breaker (SXCBR) can be realized either as three one-phase switches or as one three-phase switch.

The content of this function is represented by the IEC 61850 definitions for thelogical nodes Circuit breaker (SXCBR) and Circuit switch (SXSWI) withmandatory functionality.

Reservation function (QCRSV/RESIN)The purpose of the reservation function is primarily to transfer interlockinginformation between IEDs in a safe way and to prevent double operation in a bay,switchyard part, or complete substation.

For interlocking evaluation in a substation, the position information from switchingdevices, such as circuit breakers, disconnectors and earthing switches can berequired from the same bay or from several other bays. When information isneeded from other bays, it is exchanged over the serial station bus between thedistributed IEDs. The problem that arises, even at a high speed of communication,is a space of time during which the information about the position of the switchingdevices are uncertain. The interlocking function uses this information for evaluation, which means that also the interlocking conditions will be uncertain.

To ensure that the interlocking information is correct at the time of operation, aunique reservation method is available in the IEDs. With this reservation methodthe operation will temporarily be blocked for all switching devices in other bays,which switching states are used for evaluation of permission to operate. Actual

 position indications from these bays are then transferred over the serial bus for 

evaluation in the IED. After the evaluation the operation can be executed with highsecurity.

This functionality is realized over the station bus by means of the function blocksQCRSV and RESIN. The application principle appears from figure 93.

The function block QCRSV handles the reservation. It sends out either thereservation request to other bays or the acknowledgement if the bay has received arequest from another bay.

The other function block RESIN receives the reservation information from other  bays. The number of instances is the same as the number of involved bays (up to

Section 3 1MRK 505 211-UEN C

IED application

284

 Application manual

Page 291: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 291/457

60 instances are available). The received signals are either the request for reservation from another bay or the acknowledgment from each bay respectively,which have received a request from this bay. Also the information of validtransmission over the station bus must be received.

en05000117.vsd

IEDIED

From other 

SCSWI in

the bayTo other 

SCSWI

in thebay

3

Station bus

 .

  .

  .

. . .

. . .

3

RESIN

EXCH_OUTEXCH_IN

RESIN

EXCH_OUT

EXCH_IN

..

SCSWI

RES_RQ

RES_GRT

RES_DATA

QCRSV

RES_RQ1

RES_RQ8

RES_GRT1

RES_GRT8

..

2

IEC05000117 V2 EN

Figure 93: Application principles for reservation over the station bus 

The reservation can also be realized with external wiring according to theapplication example in figure 94. This solution is realized with external auxiliary

relays and extra binary inputs and outputs in each IED, but without use of function blocks QCRSV and RESIN.

SCSWI

SELECTED

RES_EXT

+

IED

BI BO

IED

BIBO

OROther SCSWI in the bay

en05000118.vsd

IEC05000118 V2 EN

Figure 94: Application principles for reservation with external wiring 

The solution in figure 94 can also be realized over the station bus according to theapplication example in figure 95. The solutions in figure 94 and figure 95 do not

1MRK 505 211-UEN C Section 3IED application

285

 Application manual

Page 292: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 292/457

have the same high security compared to the solution in figure 93, but have insteada higher availability. This because no acknowledgment is required.

SCSWI

SELECTED

RES_EXT

IEDIED

OROther SCWI in

the bay

Station bus

. . .

SPGGIOIN

RESGRANT

IntlReceive

.                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                 

.                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                 

.                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                 

.                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                 

.                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                 

.                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                 

RESGRANT

IntlReceive

en05000178.vsd

IEC05000178 V2 EN

Figure 95: Application principle for an alternative reservation solution 

3.11.2.2 Interaction between modules

A typical bay with apparatus control function consists of a combination of logicalnodes or functions that are described here:

• The Switch controller (SCSWI) initializes all operations for one apparatus and performs the actual switching and is more or less the interface to the drive of one apparatus. It includes the position handling as well as the control of the

 position.• The Circuit breaker (SXCBR) is the process interface to the circuit breaker for 

the apparatus control function.• The Circuit switch (SXSWI) is the process interface to the disconnector or the

earthing switch for the apparatus control function.• The Bay control (QCBAY) fulfils the bay-level functions for the apparatuses,

such as operator place selection and blockings for the complete bay.• The Reservation (QCRSV) deals with the reservation function.

• The Four step residual overcurrent protection (EF4PTOC) trips the breaker incase of Distance protection zones (ZMQPDIS).• The Protection trip logic (SMPPTRC) connects the "trip" outputs of one or 

more protection functions to a common "trip" to be transmitted to SXCBR.• The Autorecloser (SMBRREC) consists of the facilities to automatically close

a tripped breaker with respect to a number of configurable conditions.• The logical node Interlocking (SCILO) provides the information to SCSWI

whether it is permitted to operate due to the switchyard topology. Theinterlocking conditions are evaluated with separate logic and connected toSCILO .

• The Synchrocheck, energizing check, and synchronizing (SESRSYN)calculates and compares the voltage phasor difference from both sides of an

Section 3 1MRK 505 211-UEN C

IED application

286

 Application manual

Page 293: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 293/457

open breaker with predefined switching conditions (synchrocheck). Also thecase that one side is dead (energizing-check) is included.

• The logical node Generic Automatic Process Control, GAPC, is an automaticfunction that reduces the interaction between the operator and the system.With one command, the operator can start a sequence that will end with aconnection of a process object (for example a line) to one of the possible busbars.

The overview of the interaction between these functions is shown in figure 96 below.

en05000120.vsd

ZMQPDIS

(Distance)

SXCBR

(Circuit breaker)

Interlocking

functionblock

(Not a LN)

SCSWI

(Switching control)

QCBAY

(Bay control)

SMBRREC

(Auto-

reclosure)I/O

Trip

Close rel.

Res. req.   S   t  a  r   t   A   R

Close CB

Position

Res. granted

Operator placeselection

SCSWI

(Switching control)

SXSWI

(Disconnector)

Open cmd

Close cmd

Position

SECRSYN

(Synchrocheck)

SCILO

SCILO

Synchrocheck

OK

QCRSV

(Reservation) Res. req.

Res.

grantedGAPC

(Generic

 Automatic

Process

Control) Open/Close

Open/Close

Enable

close

Enable

open

Open rel.

Close rel.

Open rel.

SMPPTRC

(Trip logic)

Position

   E  n  a   b   l  e

  o  p  e  n

   E  n  a   b   l  e

  c   l  o  s  e

   P  o  s .

   f  r  o  m

  o   t   h  e  r   b  a  y  s

I/O

Open cmd

Close cmd

(Interlocking)

(Interlocking)

IEC05000120 V1 EN

Figure 96: Example overview of the interactions between functions in a typical 

bay 

1MRK 505 211-UEN C Section 3IED application

287

 Application manual

Page 294: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 294/457

3.11.2.3 Setting guidelines

The setting parameters for the apparatus control function are set via the local HMIor PCM600.

Bay control (QCBAY)If the parameter  AllPSTOValid is set to No priority, all originators from local andremote are accepted without any priority.

Switch controller (SCSWI)The parameter CtlModel specifies the type of control model according to IEC61850. For normal control of circuit breakers, disconnectors and earthing switchesthe control model is set to SBO Enh (Select-Before-Operate) with enhanced security.

When the operation shall be performed in one step, the model direct control with

normal security is used.At control with enhanced security there is an additional supervision of the statusvalue by the control object, which means that each command sequence must beterminated by a termination command.

The parameter  PosDependent gives permission to operate depending on the position indication, that is, at Always permitted it is always permitted to operateindependent of the value of the position. At Not perm at 00/11 it is not permitted tooperate if the position is in bad or intermediate state.

tSelect is the maximum time between the select and the execute command signal,

that is, the time the operator has to perform the command execution after theselection of the object to operate. When the time has expired, the selected outputsignal is set to false and a cause-code is given over IEC 61850.

The time parameter tResResponse is the allowed time from reservation request tothe feedback reservation granted from all bays involved in the reservation function.When the time has expired, the control function is reset.

tSynchrocheck is the allowed time for the synchrocheck function to fulfill the closeconditions. When the time has expired, the control function is reset.

The timer tSynchronizing supervises that the signal synchronizing in progress is

obtained in SCSWI after start of the synchronizing function. The start signal for thesynchronizing is obtained if the synchrocheck conditions are not fulfilled. Whenthe time has expired, the control function is reset. If no synchronizing function isincluded, the time is set to 0, which means no start of the synchronizing function.

tExecutionFB is the maximum time between the execute command signal and thecommand termination. When the time has expired, the control function is reset.

tPoleDiscord is the allowed time to have discrepancy between the poles at controlof three one-phase breakers. At discrepancy an output signal is activated to be usedfor trip or alarm.

Section 3 1MRK 505 211-UEN C

IED application

288

 Application manual

Page 295: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 295/457

Switch (SXCBR/SXSWI)tStartMove is the supervision time for the apparatus to start moving after acommand execution. When the time has expired, the switch function is reset.

During the tIntermediate time the position indication is allowed to be in anintermediate (00) state. When the time has expired, the switch function is reset. Theindication of the mid-position at SCSWI is suppressed during this time periodwhen the position changes from open to close or vice-versa.

If the parameter  AdaptivePulse is set to Adaptive the command output pulse resetswhen a new correct end position is reached. If the parameter is set to Not adaptive

the command output pulse remains active until the timer tOpenPulsetClosePulse

has elapsed.

tOpenPulse is the output pulse length for an open command. The default length isset to 200 ms for a circuit breaker (SXCBR) and 500 ms for a disconnector (SXSWI).

tClosePulse is the output pulse length for a close command. The default length isset to 200 ms for a circuit breaker (SXCBR) and 500 ms for a disconnector (SXSWI).

SuppressMidPos when On will suppress the mid-position during the timetIntermediate.

Bay Reserve (QCRSV)The timer tCancelRes defines the supervision time for canceling the reservation,when this cannot be done by requesting bay due to for example communicationfailure.

When the parameter  ParamRequestx ( x=1-8) is set to Only own bay res.

individually for each apparatus (x) in the bay, only the own bay is reserved, that is,the output for reservation request of other bays (RES_BAYS) will not be activatedat selection of apparatus x.

Reservation input (RESIN)With the FutureUse parameter set to Bay future use the function can handle baysnot yet installed in the SA system.

3.11.2.4 Setting parameters

Table 99: QCBAY Non group settings (basic)

Name Values (Range) Unit Step Default Description

 AllPSTOValid PriorityNo priority

- - Priority Priority of originators

Table 100: LO CRE M N on group settings (basic)

Name Values (Range) Unit Step Default Description

ControlMode Internal LR-switchExternal LR-switch

- - Internal LR-switch Control mode for internal/external LR-switch

1MRK 505 211-UEN C Section 3IED application

289

 Application manual

Page 296: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 296/457

Table 101: SCSW I Non group settings (basic)

Name Values (Range) Unit Step Default Description

CtlModel Dir NormSBO Enh

- - SBO Enh Specifies control model type

PosDependent Always permittedNot perm at 00/11

- - Always permitted Permission to operate depending on theposition

tSelect 0.00 - 600.00 s 0.01 30.00 Maximum time between select andexecute signals

tResResponse 0.000 - 60.000 s 0.001 5.000 Allowed time from reservation request toreservation granted

tSynchrocheck 0.00 - 600.00 s 0.01 10.00 Allowed time for synchrocheck to fulfilclose conditions

tSynchronizing 0.00 - 600.00 s 0.01 0.00 Supervision time to get the signalsynchronizing in progress

tExecutionFB 0.00 - 600.00 s 0.01 30.00 Maximum time from command executionto termination

tPoleDiscord 0.000 - 60.000 s 0.001 2.000 Allowed time to have discrepancybetween the poles

Table 102: SXCBR Non group settings (basic)

Name Values (Range) Unit Step Default Description

tStartMove 0.000 - 60.000 s 0.001 0.100 Supervision time for the apparatus tomove after a command

tIntermediate 0.000 - 60.000 s 0.001 0.150 Allowed time for intermediate position

 AdaptivePulse Not adaptive Adaptive

- - Not adaptive Output resets when a new correct endposition is reached

tOpenPulse 0.000 - 60.000 s 0.001 0.200 Output pulse length for open command

tClosePulse 0.000 - 60.000 s 0.001 0.200 Output pulse length for close command

SuppressMidPos Off  On

- - On Mid-position is suppressed during thetime tIntermediate

Table 103: SXSW I Non group settings (basic)

Name Values (Range) Unit Step Default Description

tStartMove 0.000 - 60.000 s 0.001 3.000 Supervision time for the apparatus tomove after a command

tIntermediate 0.000 - 60.000 s 0.001 15.000 Allowed time for intermediate position

 AdaptivePulse Not adaptive Adaptive

- - Not adaptive Output resets when a new correct endposition is reached

tOpenPulse 0.000 - 60.000 s 0.001 0.200 Output pulse length for open command

tClosePulse 0.000 - 60.000 s 0.001 0.200 Output pulse length for close command

SwitchType Load BreakDisconnector Earthing SwitchHS Earthing Switch

- - Disconnector 1=LoadBreak,2=Disconnector,3=EarthSw,4=HighSpeedEarthSw

SuppressMidPos Off  On

- - On Mid-position is suppressed during thetime tIntermediate

Section 3 1MRK 505 211-UEN C

IED application

290

 Application manual

Page 297: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 297/457

Table 104: QCRSV Non group settings (basic)

Name Values (Range) Unit Step Default Description

tCancelRes 0.000 - 60.000 s 0.001 10.000 Supervision time for canceling thereservation

ParamRequest1 Other bays res.Only own bay res.

- - Only own bay res. Reservation of the own bay only, atselection of apparatus 1

ParamRequest2 Other bays res.Only own bay res.

- - Only own bay res. Reservation of the own bay only, atselection of apparatus 2

ParamRequest3 Other bays res.Only own bay res.

- - Only own bay res. Reservation of the own bay only, atselection of apparatus 3

ParamRequest4 Other bays res.Only own bay res.

- - Only own bay res. Reservation of the own bay only, atselection of apparatus 4

ParamRequest5 Other bays res.Only own bay res.

- - Only own bay res. Reservation of the own bay only, atselection of apparatus 5

ParamRequest6 Other bays res.Only own bay res.

- - Only own bay res. Reservation of the own bay only, atselection of apparatus 6

ParamRequest7 Other bays res.Only own bay res.

- - Only own bay res. Reservation of the own bay only, atselection of apparatus 7

ParamRequest8 Other bays res.Only own bay res.

- - Only own bay res. Reservation of the own bay only, atselection of apparatus 8

Table 105: R ES IN 1 Non group settings (basic)

Name Values (Range) Unit Step Default Description

FutureUse Bay in useBay future use

- - Bay in use The bay for this ResIn block is for futureuse

Table 106: R ES IN 2 Non group settings (basic)

Name Values (Range) Unit Step Default Description

FutureUse Bay in useBay future use

- - Bay in use The bay for this ResIn block is for futureuse

3.11.3 Interlocking

The main purpose of switchgear interlocking is:

• To avoid the dangerous or damaging operation of switchgear • To enforce restrictions on the operation of the substation for other reasons for 

example, load configuration. Examples of the latter are to limit the number of  parallel transformers to a maximum of two or to ensure that energizing isalways from one side, for example, the high voltage side of a transformer.

This section only deals with the first point, and only with restrictions caused byswitching devices other than the one to be controlled. This means that switchinterlock, because of device alarms, is not included in this section.

1MRK 505 211-UEN C Section 3IED application

291

 Application manual

Page 298: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 298/457

Disconnectors and earthing switches have a limited switching capacity.Disconnectors may therefore only operate:

• With basically zero current. The circuit is open on one side and has a small

extension. The capacitive current is small (for example, < 5A) and power transformers with inrush current are not allowed.

• To connect or disconnect a parallel circuit carrying load current. The switchingvoltage across the open contacts is thus virtually zero, thanks to the parallelcircuit (for example, < 1% of rated voltage). Paralleling of power transformersis not allowed.

Earthing switches are allowed to connect and disconnect earthing of isolated points. Due to capacitive or inductive coupling there may be some voltage (for example < 40% of rated voltage) before earthing and some current (for example <100A) after earthing of a line.

Circuit breakers are usually not interlocked. Closing is only interlocked againstrunning disconnectors in the same bay, and the bus-coupler opening is interlockedduring a busbar transfer.

The positions of all switching devices in a bay and from some other bays determinethe conditions for operational interlocking. Conditions from other stations areusually not available. Therefore, a line earthing switch is usually not fullyinterlocked. The operator must be convinced that the line is not energized from theother side before closing the earthing switch. As an option, a voltage indication can

 be used for interlocking. Take care to avoid a dangerous enable condition at theloss of a VT secondary voltage, for example, because of a blown fuse.

The switch positions used by the operational interlocking logic are obtained fromauxiliary contacts or position sensors. For each end position (open or closed) a trueindication is needed - thus forming a double indication. The apparatus controlfunction continuously checks its consistency. If neither condition is high (1 or TRUE), the switch may be in an intermediate position, for example, moving. Thisdynamic state may continue for some time, which in the case of disconnectors may

 be up to 10 seconds. Should both indications stay low for a longer period, the position indication will be interpreted as unknown. If both indications stay high,something is wrong, and the state is again treated as unknown.

In both cases an alarm is sent to the operator. Indications from position sensorsshall be self-checked and system faults indicated by a fault signal. In theinterlocking logic, the signals are used to avoid dangerous enable or release

conditions. When the switching state of a switching device cannot be determinedoperation is not permitted.

For switches with an individual operation gear per phase, the evaluation mustconsider possible phase discrepancies. This is done with the aid of an AND-

 function for all three phases in each apparatus for both open and close indications.Phase discrepancies will result in an unknown double indication state.

Section 3 1MRK 505 211-UEN C

IED application

292

 Application manual

Page 299: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 299/457

3.11.3.1 Configuration guidelines

The following sections describe how the interlocking for a certain switchgear configuration can be realized in the IED by using standard interlocking modules

and their interconnections. They also describe the configuration settings. Theinputs for delivery specific conditions (Qx_EXy) are set to 1=TRUE if they are notused, except in the following cases:

• QB9_EX2 and QB9_EX4 in modules BH_LINE_A and BH_LINE_B• QA1_EX3 in module AB_TRAFO

when they are set to 0=FALSE.

3.11.3.2 Interlocking for line bay ABC_LINE

ApplicationThe interlocking for line bay (ABC_LINE) function is used for a line connected toa double busbar arrangement with a transfer busbar according to figure 97. Thefunction can also be used for a double busbar arrangement without transfer busbar or a single busbar arrangement with/without transfer busbar.

QB1 QB2

QC1

QA1

QC2

QB9

QC9

WA1 (A)

WA2 (B)

WA7 (C)

QB7

en04000478.vsd

IEC04000478 V1 EN

Figure 97: Switchyard layout ABC_LINE 

The signals from other bays connected to the module ABC_LINE are described below.

Signals from bypass busbarTo derive the signals:

1MRK 505 211-UEN C Section 3IED application

293

 Application manual

Page 300: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 300/457

Signal

BB7_D_OP All line disconnectors on bypass WA7 except in the own bay are open.

VP_BB7_D The switch status of disconnectors on bypass busbar WA7 are valid.

EXDU_BPB No transmission error from any bay containing disconnectors on bypass busbar WA7

These signals from each line bay (ABC_LINE) except that of the own bay are needed:

Signal

QB7OPTR Q7 is open

VPQB7TR The switch status for QB7 is valid.

EXDU_BPB No transmission error from the bay that contains the above information.

For bay n, these conditions are valid:

QB7OPTR (bay 1)QB7OPTR (bay 2)

. . .

. . .QB7OPTR (bay n-1)

& BB7_D_OP

VPQB7TR (bay 1)VPQB7TR (bay 2)

. . .

. . .VPQB7TR (bay n-1)

& VP_BB7_D

EXDU_BPB (bay 1)EXDU_BPB (bay 2)

. . .

. . .EXDU_BPB (bay n-1)

& EXDU_BPB

en04000477.vsd

IEC04000477 V1 EN

Figure 98: Signals from bypass busbar in line bay n 

Signals from bus-couplerIf the busbar is divided by bus-section disconnectors into bus sections, the busbar-

 busbar connection could exist via the bus-section disconnector and bus-coupler 

within the other bus section.

Section 3 1MRK 505 211-UEN C

IED application

294

 Application manual

Page 301: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 301/457

Section 1 Section 2

 A1A2_DC(BS)B1B2_DC(BS)

 ABC_LINE ABC_BC ABC_LINE ABC_BC

(WA1)A1

(WA2)B1

(WA7)C C

B2

 A2

en04000479.vsd

IEC04000479 V1 EN

Figure 99: Busbars divided by bus-section disconnectors (circuit breakers) 

To derive the signals:

Signal

BC_12_CL A bus-coupler connection exists between busbar WA1 and WA2.

BC_17_OP No bus-coupler connection between busbar WA1 and WA7.

BC_17_CL A bus-coupler connection exists between busbar WA1and WA7.

BC_27_OP No bus-coupler connection between busbar WA2 and WA7.

BC_27_CL A bus-coupler connection exists between busbar WA2 and WA7.

VP_BC_12 The switch status of BC_12 is valid.

VP_BC_17 The switch status of BC_17 is valid.

VP_BC_27 The switch status of BC_27 is valid.

EXDU_BC No transmission error from any bus-coupler bay (BC).

These signals from each bus-coupler bay (ABC_BC) are needed:

Signal

BC12CLTR A bus-coupler connection through the own bus-coupler exists between busbar WA1and WA2.

BC17OPTR No bus-coupler connection through the own bus-coupler between busbar WA1 andWA7.

BC17CLTR A bus-coupler connection through the own bus-coupler exists between busbar WA1and WA7.

BC27OPTR No bus-coupler connection through the own bus-coupler between busbar WA2 andWA7.

BC27CLTR A bus-coupler connection through the own bus-coupler exists between busbar WA2

and WA7.

VPBC12TR The switch status of BC_12 is valid.

VPBC17TR The switch status of BC_17 is valid.

VPBC27TR The switch status of BC_27 is valid.

EXDU_BC No transmission error from the bay that contains the above information.

These signals from each bus-section disconnector bay (A1A2_DC) are also needed.For B1B2_DC, corresponding signals from busbar B are used. The same type of 

1MRK 505 211-UEN C Section 3IED application

295

 Application manual

Page 302: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 302/457

module (A1A2_DC) is used for different busbars, that is, for both bus-sectiondisconnector A1A2_DC and B1B2_DC.

Signal

DCOPTR The bus-section disconnector is open.

DCCLTR The bus-section disconnector is closed.

VPDCTR The switch status of bus-section disconnector DC is valid.

EXDU_DC No transmission error from the bay that contains the above information.

If the busbar is divided by bus-section circuit breakers, the signals from the bus-section coupler bay (A1A2_BS), rather than the bus-section disconnector bay(A1A2_DC) must be used. For B1B2_BS, corresponding signals from busbar B areused. The same type of module (A1A2_BS) is used for different busbars, that is,for both bus-section circuit breakers A1A2_BS and B1B2_BS.

Signal

S1S2OPTR No bus-section coupler connection between bus-sections 1 and 2.

S1S2CLTR A bus-section coupler connection exists between bus-sections 1 and 2.

VPS1S2TR The switch status of bus-section coupler BS is valid.

EXDU_BS No transmission error from the bay that contains the above information.

For a line bay in section 1, these conditions are valid:

Section 3 1MRK 505 211-UEN C

IED application

296

 Application manual

Page 303: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 303/457

BC12CLTR (sect.1)

DCCLTR (A1A2)DCCLTR (B1B2)

>1&

BC12CLTR (sect.2)

&VPBC12TR (sect.1)

VPDCTR (A1A2)VPDCTR (B1B2)

VPBC12TR (sect.2)

>1&

BC17OPTR (sect.1)

DCOPTR (A1A2)BC17OPTR (sect.2)

>1&

BC17CLTR (sect.1)

DCCLTR (A1A2)

BC17CLTR (sect.2)

&VPBC17TR (sect.1)

VPDCTR (A1A2)VPBC17TR (sect.2)

>1&

>1

&

&

&

BC27OPTR (sect.1)

DCOPTR (B1B2)BC27OPTR (sect.2)

BC27CLTR (sect.1)

DCCLTR (B1B2)BC27CLTR (sect.2)

VPBC27TR (sect.1)VPDCTR (B1B2)

VPBC27TR (sect.2)

EXDU_BC (sect.1)EXDU_DC (A1A2)EXDU_DC (B1B2)EXDU_BC (sect.2)

BC_12_CL

VP_BC_12

BC_17_OP

BC_17_CL

VP_BC_17

BC_27_OP

BC_27_CL

VP_BC_27

EXDU_BC

en04000480.vsd

IEC04000480 V1 EN

Figure 100: Signals to a line bay in section 1 from the bus-coupler bays in each section 

For a line bay in section 2, the same conditions as above are valid by changingsection 1 to section 2 and vice versa.

Configuration settingIf there is no bypass busbar and therefore no QB7 disconnector, then theinterlocking for QB7 is not used. The states for QB7, QC71, BB7_D, BC_17,BC_27 are set to open by setting the appropriate module inputs as follows. In thefunctional block diagram, 0 and 1 are designated 0=FALSE and 1=TRUE:

1MRK 505 211-UEN C Section 3IED application

297

 Application manual

Page 304: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 304/457

• QB7_OP = 1• QB7_CL = 0

• QC71_OP = 1• QC71_CL = 0

• BB7_D_OP = 1

• BC_17_OP = 1• BC_17_CL = 0• BC_27_OP = 1• BC_27_CL = 0

• EXDU_BPB = 1

• VP_BB7_D = 1• VP_BC_17 = 1• VP_BC_27 = 1

If there is no second busbar WA2 and therefore no QB2 disconnector, then theinterlocking for QB2 is not used. The state for QB2, QC21, BC_12, BC_27 are setto open by setting the appropriate module inputs as follows. In the functional block diagram, 0 and 1 are designated 0=FALSE and 1=TRUE:

• QB2_OP = 1

• QB2_CL = 0

• QC21_OP = 1• QC21_CL = 0

• BC_12_CL = 0• BC_27_OP = 1• BC_27_CL = 0

• VP_BC_12 = 1

3.11.3.3 Interlocking for bus-coupler bay ABC_BC

ApplicationThe interlocking for bus-coupler bay (ABC_BC) function is used for a bus-coupler 

 bay connected to a double busbar arrangement according to figure 101. Thefunction can also be used for a single busbar arrangement with transfer busbar or double busbar arrangement without transfer busbar.

Section 3 1MRK 505 211-UEN C

IED application

298

 Application manual

Page 305: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 305/457

QB1 QB2

QC1

QA1

WA1 (A)

WA2 (B)

WA7 (C)

QB7QB20

QC2

en04000514.vsd

IEC04000514 V1 EN

Figure 101: Switchyard layout ABC_BC 

ConfigurationThe signals from the other bays connected to the bus-coupler module ABC_BC aredescribed below.

Signals from all feedersTo derive the signals:

Signal

BBTR_OP No busbar transfer is in progress concerning this bus-coupler.

VP_BBTR The switch status is valid for all apparatuses involved in the busbar transfer.

EXDU_12 No transmission error from any bay connected to the WA1/WA2 busbars.

These signals from each line bay (ABC_LINE), each transformer bay(AB_TRAFO), and bus-coupler bay (ABC_BC), except the own bus-coupler bayare needed:

Signal

QQB12OPTR QB1 or QB2 or both are open.

VPQB12TR The switch status of QB1 and QB2 are valid.

EXDU_12 No transmission error from the bay that contains the above information.

For bus-coupler bay n, these conditions are valid:

1MRK 505 211-UEN C Section 3IED application

299

 Application manual

Page 306: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 306/457

QB12OPTR (bay 1)QB12OPTR (bay 2)

. . .

. . .QB12OPTR (bay n-1)

& BBTR_OP

VPQB12TR (bay 1)VPQB12TR (bay 2)

. . .

. . .VPQB12TR (bay n-1)

& VP_BBTR

EXDU_12 (bay 1)EXDU_12 (bay 2)

. . .

. . .EXDU_12 (bay n-1)

& EXDU_12

en04000481.vsd

IEC04000481 V1 EN

Figure 102: Signals from any bays in bus-coupler bay n 

If the busbar is divided by bus-section disconnectors into bus-sections, the signalsBBTR are connected in parallel - if both bus-section disconnectors are closed. Sofor the basic project-specific logic for BBTR above, add this logic:

Section 1 Section 2

 A1A2_DC(BS)B1B2_DC(BS)

 ABC_LINE

 ABC_BC

 ABC_LINE ABC_BC

(WA1)A1

(WA2)B1

(WA7)C C

B2

 A2

en04000482.vsd

 AB_TRAFO

IEC04000482 V1 EN

Figure 103: Busbars divided by bus-section disconnectors (circuit breakers) 

The following signals from each bus-section disconnector bay (A1A2_DC) areneeded. For B1B2_DC, corresponding signals from busbar B are used. The sametype of module (A1A2_DC) is used for different busbars, that is, for both bus-section disconnector A1A2_DC and B1B2_DC.

Signal

DCOPTR The bus-section disconnector is open.

VPDCTR The switch status of bus-section disconnector DC is valid.

EXDU_DC No transmission error from the bay that contains the above information.

If the busbar is divided by bus-section circuit breakers, the signals from the bus-section coupler bay (A1A2_BS), rather than the bus-section disconnector bay(A1A2_DC), have to be used. For B1B2_BS, corresponding signals from busbar B

Section 3 1MRK 505 211-UEN C

IED application

300

 Application manual

Page 307: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 307/457

are used. The same type of module (A1A2_BS) is used for different busbars, thatis, for both bus-section circuit breakers A1A2_BS and B1B2_BS.

Signal

S1S2OPTR No bus-section coupler connection between bus-sections 1 and 2.

VPS1S2TR The switch status of bus-section coupler BS is valid.

EXDU_BS No transmission error from the bay that contains the above information.

For a bus-coupler bay in section 1, these conditions are valid:

BBTR_OP (sect.1)

DCOPTR (A1A2)DCOPTR (B1B2)

BBTR_OP (sect.2)

&VP_BBTR (sect.1)

VPDCTR (A1A2)VPDCTR (B1B2)

VP_BBTR (sect.2)

EXDU_12 (sect.1)

EXDU_DC (B1B2)EXDU_12 (sect.2)

VP_BBTR

EXDU_12

en04000483.vsd

&EXDU_DC (A1A2)

BBTR_OP

>1&

IEC04000483 V1 EN

Figure 104: Signals to a bus-coupler bay in section 1 from any bays in each 

section 

For a bus-coupler bay in section 2, the same conditions as above are valid bychanging section 1 to section 2 and vice versa.

Signals from bus-couplerIf the busbar is divided by bus-section disconnectors into bus-sections, the signalsBC_12 from the busbar coupler of the other busbar section must be transmitted tothe own busbar coupler if both disconnectors are closed.

Section 1 Section 2

 A1A2_DC(BS)B1B2_DC(BS)

 ABC_BC ABC_BC

(WA1)A1

(WA2)B1(WA7)C C

B2

 A2

en04000484.vsd

IEC04000484 V1 EN

Figure 105: Busbars divided by bus-section disconnectors (circuit breakers) 

To derive the signals:

1MRK 505 211-UEN C Section 3IED application

301

 Application manual

Page 308: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 308/457

Signal

BC_12_CL Another bus-coupler connection exists between busbar WA1 and WA2.

VP_BC_12 The switch status of BC_12 is valid.

EXDU_BC No transmission error from any bus-coupler bay (BC).

These signals from each bus-coupler bay (ABC_BC), except the own bay, are needed:

Signal

BC12CLTR A bus-coupler connection through the own bus-coupler exists between busbar WA1and WA2.

VPBC12TR The switch status of BC_12 is valid.

EXDU_BC No transmission error from the bay that contains the above information.

These signals from each bus-section disconnector bay (A1A2_DC) are also needed.For B1B2_DC, corresponding signals from busbar B are used. The same type of module (A1A2_DC) is used for different busbars, that is, for both bus-sectiondisconnector A1A2_DC and B1B2_DC.

Signal

DCCLTR The bus-section disconnector is closed.

VPDCTR The switch status of bus-section disconnector DC is valid.

EXDU_DC No transmission error from the bay that contains the above information.

If the busbar is divided by bus-section circuit breakers, the signals from the bus-section coupler bay (A1A2_BS), rather than the bus-section disconnector bay(A1A2_DC), must be used. For B1B2_BS, corresponding signals from busbar Bare used. The same type of module (A1A2_BS) is used for different busbars, thatis, for both bus-section circuit breakers A1A2_BS and B1B2_BS.

Signal

S1S2CLTR A bus-section coupler connection exists between bus sections 1 and 2.

VPS1S2TR The switch status of bus-section coupler BS is valid.

EXDU_BS No transmission error from the bay containing the above information.

For a bus-coupler bay in section 1, these conditions are valid:

Section 3 1MRK 505 211-UEN C

IED application

302

 Application manual

Page 309: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 309/457

DCCLTR (A1A2)DCCLTR (B1B2)

BC12CLTR (sect.2)

VPDCTR (A1A2)VPDCTR (B1B2)VPBC12TR (sect.2)

EXDU_DC (A1A2)

EXDU_DC (B1B2)EXDU_BC (sect.2)

& BC_12_CL

VP_BC_12

EXDU_BC

en04000485.vsd

&

&

IEC04000485 V1 EN

Figure 106: Signals to a bus-coupler bay in section 1 from a bus-coupler bay in 

another section 

For a bus-coupler bay in section 2, the same conditions as above are valid bychanging section 1 to section 2 and vice versa.

Configuration settingIf there is no bypass busbar and therefore no QB2 and QB7 disconnectors, then theinterlocking for QB2 and QB7 is not used. The states for QB2, QB7, QC71 are setto open by setting the appropriate module inputs as follows. In the functional block diagram, 0 and 1 are designated 0=FALSE and 1=TRUE:

• QB2_OP = 1• QB2_CL = 0

• QB7_OP = 1• QB7_CL = 0

• QC71_OP = 1• QC71_CL = 0

If there is no second busbar B and therefore no QB2 and QB20 disconnectors, thenthe interlocking for QB2 and QB20 are not used. The states for QB2, QB20, QC21,BC_12, BBTR are set to open by setting the appropriate module inputs as follows.In the functional block diagram, 0 and 1 are designated 0=FALSE and 1=TRUE:

• QB2_OP = 1• QB2_CL = 0

• QB20_OP = 1• QB20_CL = 0

• QC21_OP = 1• QC21_CL = 0

1MRK 505 211-UEN C Section 3IED application

303

 Application manual

Page 310: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 310/457

• BC_12_CL = 0• VP_BC_12 = 1

• BBTR_OP = 1• VP_BBTR = 1

3.11.3.4 Interlocking for transformer bay AB_TRAFO

ApplicationThe interlocking for transformer bay (AB_TRAFO) function is used for atransformer bay connected to a double busbar arrangement according to figure 107.The function is used when there is no disconnector between circuit breaker andtransformer. Otherwise, the interlocking for line bay (ABC_LINE) function can be

used. This function can also be used in single busbar arrangements.

QB1 QB2

QC1

QA1

QC2

WA1 (A)

WA2 (B)

QA2

QC3

T

QC4

QB4QB3

QA2 and QC4 are not

used in this interlocking

 AB_TRAFO

en04000515.vsdIEC04000515 V1 EN

Figure 107: Switchyard layout AB_TRAFO 

The signals from other bays connected to the module AB_TRAFO are described below.

Signals from bus-couplerIf the busbar is divided by bus-section disconnectors into bus-sections, the busbar-

 busbar connection could exist via the bus-section disconnector and bus-coupler within the other bus-section.

Section 3 1MRK 505 211-UEN C

IED application

304

 Application manual

Page 311: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 311/457

Section 1 Section 2

 A1A2_DC(BS)B1B2_DC(BS)

 AB_TRAFO ABC_BC AB_TRAFO ABC_BC

(WA1)A1

(WA2)B1

(WA7)C C

B2

 A2

en04000487.vsd

IEC04000487 V1 EN

Figure 108: Busbars divided by bus-section disconnectors (circuit breakers) 

The project-specific logic for input signals concerning bus-coupler are the same asthe specific logic for the line bay (ABC_LINE):

Signal

BC_12_CL A bus-coupler connection exists between busbar WA1 and WA2.

VP_BC_12 The switch status of BC_12 is valid.

EXDU_BC No transmission error from bus-coupler bay (BC).

The logic is identical to the double busbar configuration “Signals from bus-coupler“.

Configuration settingIf there are no second busbar B and therefore no QB2 disconnector, then theinterlocking for QB2 is not used. The state for QB2, QC21, BC_12 are set to open

 by setting the appropriate module inputs as follows. In the functional block diagram, 0 and 1 are designated 0=FALSE and 1=TRUE:

• QB2_OP = 1• QB2QB2_CL = 0

• QC21_OP = 1• QC21_CL = 0

• BC_12_CL = 0• VP_BC_12 = 1

If there is no second busbar B at the other side of the transformer and therefore noQB4 disconnector, then the state for QB4 is set to open by setting the appropriatemodule inputs as follows:

• QB4_OP = 1• QB4_CL = 0

3.11.3.5 Interlocking for bus-section breaker A1A2_BS

1MRK 505 211-UEN C Section 3IED application

305

 Application manual

Page 312: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 312/457

Signals from all feedersIf the busbar is divided by bus-section circuit breakers into bus-sections and bothcircuit breakers are closed, the opening of the circuit breaker must be blocked if a

 bus-coupler connection exists between busbars on one bus-section side and if onthe other bus-section side a busbar transfer is in progress:

Section 1 Section 2

 A1A2_BSB1B2_BS

 ABC_LINE

 ABC_BC

 ABC_LINE

 ABC_BC

(WA1)A1

(WA2)B1

(WA7)C C

B2

 A2

en04000489.vsd

 AB_TRAFO AB_TRAFO

IEC04000489 V1 EN

Figure 109: Busbars divided by bus-section circuit breakers 

To derive the signals:

Signal

BBTR_OP No busbar transfer is in progress concerning this bus-section.

VP_BBTR The switch status of BBTR is valid.

EXDU_12 No transmission error from any bay connected to busbar 1(A) and 2(B).

These signals from each line bay (ABC_LINE), each transformer bay

(AB_TRAFO), and bus-coupler bay (ABC_BC) are needed:

Signal

QB12OPTR QB1 or QB2 or both are open.

VPQB12TR The switch status of QB1 and QB2 are valid.

EXDU_12 No transmission error from the bay that contains the above information.

These signals from each bus-coupler bay (ABC_BC) are needed:

Signal

BC12OPTR No bus-coupler connection through the own bus-coupler between busbar WA1 andWA2.

VPBC12TR The switch status of BC_12 is valid.

EXDU_BC No transmission error from the bay that contains the above information.

These signals from the bus-section circuit breaker bay (A1A2_BS, B1B2_BS) areneeded.

Section 3 1MRK 505 211-UEN C

IED application

306

 Application manual

Page 313: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 313/457

Signal

S1S2OPTR No bus-section coupler connection between bus-sections 1 and 2.

VPS1S2TR The switch status of bus-section coupler BS is valid.

EXDU_BS No transmission error from the bay that contains the above information.

For a bus-section circuit breaker between A1 and A2 section busbars, theseconditions are valid:

S1S2OPTR (B1B2)BC12OPTR (sect.1)

QB12OPTR (bay 1/sect.2)

QB12OPTR (bay n/sect.2)

S1S2OPTR (B1B2)BC12OPTR (sect.2)

QB12OPTR (bay 1/sect.1)

QB12OPTR (bay n /sect.1)

BBTR_OP

VP_BBTR

EXDU_12

en04000490.vsd

>1

&

>1

&

. . .

. . .

. . .

. . .

&

&

VPS1S2TR (B1B2)VPBC12TR (sect.1)

VPQB12TR (bay 1/sect.2)

VPQB12TR (bay n/sect.1)

. . .

. . .

VPBC12TR (sect.2)VPQB12TR (bay 1/sect.1)

VPQB12TR (bay n/sect.1)

. . .

. . .

&

EXDU_12 (bay 1/sect.2)

EXDU_12 (bay n /sect.2)

EXDU_12(bay 1/sect.1)

EXDU_12 (bay n /sect.1)

EXDU_BS (B1B2)EXDU_BC (sect.1)

EXDU_BC (sect.2)

. . .

. . .

. . .

. . .

IEC04000490 V1 EN

Figure 110: Signals from any bays for a bus-section circuit breaker between 

sections A1 and A2 

For a bus-section circuit breaker between B1 and B2 section busbars, theseconditions are valid:

1MRK 505 211-UEN C Section 3IED application

307

 Application manual

Page 314: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 314/457

S1S2OPTR (A1A2)BC12OPTR (sect.1)

QB12OPTR (bay 1/sect.2)

QB12OPTR (bay n/sect.2)

S1S2OPTR (A1A2)BC12OPTR (sect.2)

QB12OPTR (bay 1/sect.1)

QB12OPTR (bay n /sect.1)

BBTR_OP

VP_BBTR

EXDU_12

en04000491.vsd

>1

&

>1

&

. . .

. . .

. . .

. . .

&

&

VPS1S2TR (A1A2)VPBC12TR (sect.1)

VPQB12TR (bay 1/sect.2)

VPQB12TR (bay n/sect.1)

. . .

. . .

VPBC12TR (sect.2)VPQB12TR (bay 1/sect.1)

VPQB12TR (bay n/sect.1)

. . .

. . .

&

EXDU_12(bay 1/sect.2)

EXDU_12 (bay n /sect.2)

EXDU_12 (bay 1/sect.1)

EXDU_12 (bay n /sect.1)

EXDU_BS (A1A2)EXDU_BC (sect.1)

EXDU_BC (sect.2)

. . .

. . .

. . .

. . .

IEC04000491 V1 EN

Figure 111: Signals from any bays for a bus-section circuit breaker between 

sections B1 and B2 

Configuration settingIf there is no other busbar via the busbar loops that are possible, then either theinterlocking for the QA1 open circuit breaker is not used or the state for BBTR isset to open. That is, no busbar transfer is in progress in this bus-section:

• BBTR_OP = 1• VP_BBTR = 1

3.11.3.6 Interlocking for bus-section disconnector A1A2_DC

Section 3 1MRK 505 211-UEN C

IED application

308

 Application manual

Page 315: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 315/457

ApplicationThe interlocking for bus-section disconnector (A1A2_DC) function is used for one

 bus-section disconnector between section 1 and 2 according to figure 112.A1A2_DC function can be used for different busbars, which includes a bus-sectiondisconnector.

WA1 (A1) WA2 (A2)

QB

QC1 QC2

 A1A2_DCen04000492.vsd

IEC04000492 V1 EN

Figure 112: Switchyard layout A1A2_DC 

The signals from other bays connected to the module A1A2_DC are described below.

Signals in single breaker arrangementIf the busbar is divided by bus-section disconnectors, the condition no other 

disconnector connected to the bus-section must be made by a project-specific logic.

The same type of module (A1A2_DC) is used for different busbars, that is, for both bus-section disconnector A1A2_DC and B1B2_DC. But for B1B2_DC,

corresponding signals from busbar B are used.

Section 1 Section 2

 A1A2_DC(BS)B1B2_DC(BS)

 ABC_LINE ABC_BC

 ABC_LINE

(WA1)A1

(WA2)B1

(WA7)C C

B3

 A3

en04000493.vsd

 AB_TRAFO AB_TRAFO

 A2

B2

IEC04000493 V1 EN

Figure 113: Busbars divided by bus-section disconnectors (circuit breakers) 

To derive the signals:

Signal

S1DC_OP All disconnectors on bus-section 1 are open.

S2DC_OP All disconnectors on bus-section 2 are open.

VPS1_DC The switch status of disconnectors on bus-section 1 is valid.

VPS2_DC The switch status of disconnectors on bus-section 2 is valid.

EXDU_BB No transmission error from any bay that contains the above information.

1MRK 505 211-UEN C Section 3IED application

309

 Application manual

Page 316: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 316/457

These signals from each line bay (ABC_LINE), each transformer bay(AB_TRAFO), and each bus-coupler bay (ABC_BC) are needed:

Signal

QB1OPTR QB1 is open.

QB2OPTR QB2 is open (AB_TRAFO, ABC_LINE).

QB220OTR QB2 and QB20 are open (ABC_BC).

VPQB1TR The switch status of QB1 is valid.

VPQB2TR The switch status of QB2 is valid.

VQB220TR The switch status of QB2 and QB20 are valid.

EXDU_BB No transmission error from the bay that contains the above information.

If there is an additional bus-section disconnector, the signal from the bus-section

disconnector bay (A1A2_DC) must be used:Signal

DCOPTR The bus-section disconnector is open.

VPDCTR The switch status of bus-section disconnector DC is valid.

EXDU_DC No transmission error from the bay that contains the above information.

If there is an additional bus-section circuit breaker rather than an additional bus-section disconnector the signals from the bus-section, circuit-breaker bay(A1A2_BS) rather than the bus-section disconnector bay (A1A2_DC) must be used:

Signal

QB1OPTR QB1 is open.

QB2OPTR QB2 is open.

VPQB1TR The switch status of QB1 is valid.

VPQB2TR The switch status of QB2 is valid.

EXDU_BS No transmission error from the bay BS (bus-section coupler bay) that contains theabove information.

For a bus-section disconnector, these conditions from the A1 busbar section are valid:

Section 3 1MRK 505 211-UEN C

IED application

310

 Application manual

Page 317: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 317/457

QB1OPTR (bay 1/sect.A1)S1DC_OP

VPS1_DC

EXDU_BB

en04000494.vsd

&

&

&

QB1OPTR (bay n/sect.A1)

. . .

. . .

. . .

VPQB1TR (bay 1/sect.A1)

VPQB1TR (bay n/sect.A1)

EXDU_BB (bay 1/sect.A1)

EXDU_BB (bay n/sect.A1)

. . .

. . .

. . .

. . .

. . .

. . .

IEC04000494 V1 EN

Figure 114: Signals from any bays in section A1 to a bus-section disconnector 

For a bus-section disconnector, these conditions from the A2 busbar section are valid:

QB1OPTR (bay 1/sect.A2)S2DC_OP

VPS2_DC

EXDU_BB

en04000495.vsd

QB1OPTR (bay n/sect.A2)

. . .

. . .

. . .

VPQB1TR (bay 1/sect.A2)

VPQB1TR (bay n/sect.A2)

VPDCTR (A2/A3)

EXDU_BB (bay n/sect.A2)

. . .

. . .

. . .

. . .

. . .

. . .

&

&

&

DCOPTR (A2/A3)

EXDU_BB (bay 1/sect.A2)

EXDU_DC (A2/A3)

IEC04000495 V1 EN

Figure 115: Signals from any bays in section A2 to a bus-section disconnector 

For a bus-section disconnector, these conditions from the B1 busbar section are valid:

1MRK 505 211-UEN C Section 3IED application

311

 Application manual

Page 318: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 318/457

QB2OPTR (QB220OTR)(bay 1/sect.B1)S1DC_OP

VPS1_DC

EXDU_BB

en04000496.vsd

QB2OPTR (QB220OTR)(bay n/sect.B1)

. . .

. . .

. . .

VPQB2TR (VQB220TR)(bay 1/sect.B1)

VPQB2TR (VQB220TR)(bay n/sect.B1)

EXDU_BB (bay 1/sect.B1)

EXDU_BB (bay n/sect.B1)

. . .

. . .

. . .

. . .

. . .

. . .

&

&

&

IEC04000496 V1 EN

Figure 116: Signals from any bays in section B1 to a bus-section disconnector 

For a bus-section disconnector, these conditions from the B2 busbar section are valid:

QB2OPTR (QB220OTR)(bay 1/sect.B2) S2DC_OP

VPS2_DC

EXDU_BB

en04000497.vsd

QB2OPTR (QB220OTR)(bay n/sect.B2)

. . .

. . .

. . .

VPQB2TR(VQB220TR) (bay 1/sect.B2)

VPQB2TR(VQB220TR) (bay n/sect.B2)VPDCTR (B2/B3)

EXDU_BB (bay n/sect.B2)

. . .

. . .

. . .

. . .

. . .

. . .

&

&

&

DCOPTR (B2/B3)

EXDU_BB (bay 1/sect.B2)

EXDU_DC (B2/B3)

IEC04000497 V1 EN

Figure 117: Signals from any bays in section B2 to a bus-section disconnector 

Signals in double-breaker arrangement

If the busbar is divided by bus-section disconnectors, the condition for the busbar disconnector bay no other disconnector connected to the bus-section must be made

 by a project-specific logic.

The same type of module (A1A2_DC) is used for different busbars, that is, for both bus-section disconnector A1A2_DC and B1B2_DC. But for B1B2_DC,corresponding signals from busbar B are used.

Section 3 1MRK 505 211-UEN C

IED application

312

 Application manual

Page 319: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 319/457

Section 1 Section 2

 A1A2_DC(BS)B1B2_DC(BS)

DB_BUS DB_BUSDB_BUS DB_BUS

(WA1)A1

(WA2)B1 B2

 A2

en04000498.vsd

IEC04000498 V1 EN

Figure 118: Busbars divided by bus-section disconnectors (circuit breakers) 

To derive the signals:

Signal

S1DC_OP All disconnectors on bus-section 1 are open.

S2DC_OP All disconnectors on bus-section 2 are open.

VPS1_DC The switch status of all disconnectors on bus-section 1 is valid.

VPS2_DC The switch status of all disconnectors on bus-section 2 is valid.

EXDU_BB No transmission error from double-breaker bay (DB) that contains the aboveinformation.

These signals from each double-breaker bay (DB_BUS) are needed:

Signal

QB1OPTR QB1 is open.

QB2OPTR QB2 is open.

VPQB1TR The switch status of QB1 is valid.

VPQB2TR The switch status of QB2 is valid.

EXDU_DB No transmission error from the bay that contains the above information.

The logic is identical to the double busbar configuration “Signals in single breaker arrangement”.

For a bus-section disconnector, these conditions from the A1 busbar section are valid:

1MRK 505 211-UEN C Section 3IED application

313

 Application manual

Page 320: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 320/457

QB1OPTR (bay 1/sect.A1)S1DC_OP

VPS1_DC

EXDU_BB

en04000499.vsd

&

&

&

QB1OPTR (bay n/sect.A1)

. . .

. . .

. . .

VPQB1TR (bay 1/sect.A1)

VPQB1TR (bay n/sect.A1)

EXDU_DB (bay 1/sect.A1)

EXDU_DB (bay n/sect.A1)

. . .

. . .

. . .

. . .

. . .

. . .

IEC04000499 V1 EN

Figure 119: Signals from double-breaker bays in section A1 to a bus-section 

disconnector 

For a bus-section disconnector, these conditions from the A2 busbar section are valid:

QB1OPTR (bay 1/sect.A2)S2DC_OP

VPS2_DC

EXDU_BB

en04000500.vsd

&

&

&

QB1OPTR (bay n/sect.A2)

. . .

. . .

. . .

VPQB1TR (bay 1/sect.A2)

VPQB1TR (bay n/sect.A2)

EXDU_DB (bay 1/sect.A2)

EXDU_DB (bay n/sect.A2)

. . .

. . .

. . .

. . .

. . .

. . .

IEC04000500 V1 EN

Figure 120: Signals from double-breaker bays in section A2 to a bus-section 

disconnector 

For a bus-section disconnector, these conditions from the B1 busbar section are valid:

Section 3 1MRK 505 211-UEN C

IED application

314

 Application manual

Page 321: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 321/457

QB2OPTR (bay 1/sect.B1)S1DC_OP

VPS1_DC

EXDU_BB

en04000501.vsd

&

&

&

QB2OPTR (bay n/sect.B1)

. . .

. . .

. . .

VPQB2TR (bay 1/sect.B1)

VPQB2TR (bay n/sect.B1)

EXDU_DB (bay 1/sect.B1)

EXDU_DB (bay n/sect.B1)

. . .

. . .

. . .

. . .

. . .

. . .

IEC04000501 V1 EN

Figure 121: Signals from double-breaker bays in section B1 to a bus-section 

disconnector 

For a bus-section disconnector, these conditions from the B2 busbar section are valid:

QB2OPTR (bay 1/sect.B2)S2DC_OP

VPS2_DC

EXDU_BB

en04000502.vsd

&

&

&

QB2OPTR (bay n/sect.B2)

. . .

. . .

. . .

VPQB2TR (bay 1/sect.B2)

VPQB2TR (bay n/sect.B2)

EXDU_DB (bay 1/sect.B2)

EXDU_DB (bay n/sect.B2)

. . .

. . .

. . .

. . .

. . .

. . .

IEC04000502 V1 EN

Figure 122: Signals from double-breaker bays in section B2 to a bus-section 

disconnector 

Signals in 1 1/2 breaker arrangementIf the busbar is divided by bus-section disconnectors, the condition for the busbar disconnector bay no other disconnector connected to the bus-section must be made

 by a project-specific logic.

The same type of module (A1A2_DC) is used for different busbars, that is, for both bus-section disconnector A1A2_DC and B1B2_DC. But for B1B2_DC,corresponding signals from busbar B are used.

1MRK 505 211-UEN C Section 3IED application

315

 Application manual

Page 322: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 322/457

Page 323: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 323/457

Section 1 Section 2

 A1A2_DC(BS)B1B2_DC(BS)

 AB_TRAFO ABC_LINEBB_ES

 ABC_LINE

(WA1)A1

(WA2)B1

(WA7)C C

B2

 A2

en04000505.vsd

BB_ES ABC_BC

IEC04000505 V1 EN

Figure 125: Busbars divided by bus-section disconnectors (circuit breakers) 

To derive the signals:

Signal

BB_DC_OP All disconnectors on this part of the busbar are open.

VP_BB_DC The switch status of all disconnector on this part of the busbar is valid.

EXDU_BB No transmission error from any bay containing the above information.

These signals from each line bay (ABC_LINE), each transformer bay(AB_TRAFO), and each bus-coupler bay (ABC_BC) are needed:

Signal

QB1OPTR QB1 is open.

QB2OPTR QB2 is open (AB_TRAFO, ABC_LINE)

QB220OTR QB2 and QB20 are open (ABC_BC)

QB7OPTR QB7 is open.

VPQB1TR The switch status of QB1 is valid.

VPQB2TR The switch status of QB2 is valid.

VQB220TR The switch status of QB2and QB20 is valid.

VPQB7TR The switch status of QB7 is valid.

EXDU_BB No transmission error from the bay that contains the above information.

These signals from each bus-section disconnector bay (A1A2_DC) are also needed.For B1B2_DC, corresponding signals from busbar B are used. The same type of 

module (A1A2_DC) is used for different busbars, that is, for both bus-sectiondisconnectors A1A2_DC and B1B2_DC.

Signal

DCOPTR The bus-section disconnector is open.

VPDCTR The switch status of bus-section disconnector DC is val id.

EXDU_DC No transmission error from the bay that contains the above information.

If no bus-section disconnector exists, the signal DCOPTR, VPDCTR andEXDU_DC are set to 1 (TRUE).

1MRK 505 211-UEN C Section 3IED application

317

 Application manual

Page 324: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 324/457

If the busbar is divided by bus-section circuit breakers, the signals from the bus-section coupler bay (A1A2_BS) rather than the bus-section disconnector bay(A1A2_DC) must be used. For B1B2_BS, corresponding signals from busbar B areused. The same type of module (A1A2_BS) is used for different busbars, that is,for both bus-section circuit breakers A1A2_BS and B1B2_BS.

Signal

QB1OPTR QB1 is open.

QB2OPTR QB2 is open.

VPQB1TR The switch status of QB1 is valid.

VPQB2TR The switch status of QB2 is valid.

EXDU_BS No transmission error from the bay BS (bus-section coupler bay) that contains theabove information.

For a busbar earthing switch, these conditions from the A1 busbar section are valid:

QB1OPTR (bay 1/sect.A1)BB_DC_OP

VP_BB_DC

EXDU_BB

en04000506.vsd

QB1OPTR (bay n/sect.A1)

. . .

. . .

. . .

VPQB1TR (bay 1/sect.A1)

VPQB1TR (bay n/sect.A1)VPDCTR (A1/A2)

EXDU_BB (bay n/sect.A1)

. . .

. . .

. . .

. . .

. . .

. . .

&

&

&

DCOPTR (A1/A2)

EXDU_BB (bay 1/sect.A1)

EXDU_DC (A1/A2)

IEC04000506 V1 EN

Figure 126: Signals from any bays in section A1 to a busbar earthing switch in 

the same section 

For a busbar earthing switch, these conditions from the A2 busbar section are valid:

Section 3 1MRK 505 211-UEN C

IED application

318

 Application manual

Page 325: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 325/457

QB1OPTR (bay 1/sect.A2)BB_DC_OP

VP_BB_DC

EXDU_BB

en04000507.vsd

QB1OPTR (bay n/sect.A2)

. . .

. . .

. . .

VPQB1TR (bay 1/sect.A2)

VPQB1TR (bay n/sect.A2)VPDCTR (A1/A2)

EXDU_BB (bay n/sect.A2)

. . .

. . .

. . .

. . .

. . .

. . .

&

&

&

DCOPTR (A1/A2)

EXDU_BB (bay 1/sect.A2)

EXDU_DC (A1/A2)

IEC04000507 V1 EN

Figure 127: Signals from any bays in section A2 to a busbar earthing switch in 

the same section 

For a busbar earthing switch, these conditions from the B1 busbar section are valid:

QB2OPTR(QB220OTR)(bay 1/sect.B1)BB_DC_OP

VP_BB_DC

EXDU_BB

en04000508.vsd

QB2OPTR (QB220OTR)(bay n/sect.B1)

. . .

. . .

. . .

VPQB2TR(VQB220TR) (bay 1/sect.B1)

VPQB2TR(VQB220TR) (bay n/sect.B1)VPDCTR (B1/B2)

EXDU_BB (bay n/sect.B1)

. . .

. . .

. . .

. . .

. . .

. . .

&

&

&

DCOPTR (B1/B2)

EXDU_BB (bay 1/sect.B1)

EXDU_DC (B1/B2)

IEC04000508 V1 EN

Figure 128: Signals from any bays in section B1 to a busbar earthing switch in 

the same section 

For a busbar earthing switch, these conditions from the B2 busbar section are valid:

1MRK 505 211-UEN C Section 3IED application

319

 Application manual

Page 326: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 326/457

QB2OPTR(QB220OTR) (bay 1/sect.B2)BB_DC_OP

VP_BB_DC

EXDU_BB

en04000509.vsd

QB2OPTR(QB220OTR) (bay n/sect.B2)

. . .

. . .

. . .

VPQB2TR(VQB220TR) (bay 1/sect.B2)

VPQB2TR(VQB220TR) (bay n/sect.B2)VPDCTR (B1/B2)

EXDU_BB (bay n/sect.B2)

. . .

. . .

. . .

. . .

. . .

. . .

&

&

&

DCOPTR (B1/B2)

EXDU_BB (bay 1/sect.B2)

EXDU_DC (B1/B2)

IEC04000509 V1 EN

Figure 129: Signals from any bays in section B2 to a busbar earthing switch in 

the same section 

For a busbar earthing switch on bypass busbar C, these conditions are valid:

QB7OPTR (bay 1)BB_DC_OP

VP_BB_DC

EXDU_BB

en04000510.vsd

&

&

&

QB7OPTR (bay n)

. . .

. . .

. . .

VPQB7TR (bay 1)

VPQB7TR (bay n)

EXDU_BB (bay 1)

EXDU_BB (bay n)

. . .

. . .

. . .

. . .

. . .

. . .

IEC04000510 V1 EN

Figure 130: Signals from bypass busbar to busbar earthing switch 

Signals in double-breaker arrangementThe busbar earthing switch is only allowed to operate if all disconnectors of the bussection are open.

Section 3 1MRK 505 211-UEN C

IED application

320

 Application manual

Page 327: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 327/457

Page 328: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 328/457

Section 1 Section 2

 A1A2_DC(BS)B1B2_DC(BS) BB_ESBB_ES

BH_LINE

(WA1)A1

(WA2)B1 B2

 A2

en04000512.vsdBH_LINE

IEC04000512 V1 EN

Figure 132: Busbars divided by bus-section disconnectors (circuit breakers) 

The project-specific logic are the same as for the logic for the double busbar configuration described in section “Signals in single breaker arrangement”.

Signal

BB_DC_OP All disconnectors on this part of the busbar are open.

VP_BB_DC The switch status of all disconnectors on this part of the busbar is valid.EXDU_BB No transmission error from any bay that contains the above information.

3.11.3.8 Interlocking for double CB bay DB

ApplicationThe interlocking for a double busbar double circuit breaker bay includingDB_BUS_A, DB_BUS_B and DB_LINE functions are used for a line connected toa double busbar arrangement according to figure 133.

Section 3 1MRK 505 211-UEN C

IED application

322

 Application manual

Page 329: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 329/457

WA1 (A)

WA2 (B)

QB1

QC1

QA1

QC2

QC9

QB61

QB9

QB2

QC4

QA2

QC5

QC3

QB62

DB_BUS_B

DB_LINE

DB_BUS_A

en04000518.vsd

IEC04000518 V1 EN

Figure 133: Switchyard layout double circuit breaker 

Three types of interlocking modules per double circuit breaker bay are defined.DB_LINE is the connection from the line to the circuit breaker parts that areconnected to the busbars. DB_BUS_A and DB_BUS_B are the connections from

the line to the busbars.

For a double circuit-breaker bay, the modules DB_BUS_A, DB_LINE andDB_BUS_B must be used.

Configuration settingFor application without QB9 and QC9, just set the appropriate inputs to open stateand disregard the outputs. In the functional block diagram, 0 and 1 are designated0=FALSE and 1=TRUE:

• QB9_OP = 1• QB9_CL = 0

• QC9_OP = 1• QC9_CL = 0

If, in this case, line voltage supervision is added, then rather than setting QB9 toopen state, specify the state of the voltage supervision:

• QB9_OP = VOLT_OFF• QB9_CL = VOLT_ON

1MRK 505 211-UEN C Section 3IED application

323

 Application manual

Page 330: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 330/457

If there is no voltage supervision, then set the corresponding inputs as follows:

• VOLT_OFF = 1• VOLT_ON = 0

3.11.3.9 Interlocking for 1 1/2 CB BH

ApplicationThe interlocking for 1 1/2 breaker diameter (BH_CONN, BH_LINE_A,BH_LINE_B) functions are used for lines connected to a 1 1/2 breaker diameter according to figure 134.

WA1 (A)

WA2 (B)

QB1

QC1

QA1

QC2

QC9

QB6

QB9

QB2

QC1

QA1

QC2

QC3

QB6

QC3

QB62QB61 QA1

QC1 QC2

QC9

QB9

BH_LINE_A BH_LINE_B

BH_CONNen04000513.vsd

IEC04000513 V1 EN

Figure 134: Switchyard layout 1 1/2 breaker 

Three types of interlocking modules per diameter are defined. BH_LINE_A andBH_LINE_B are the connections from a line to a busbar. BH_CONN is theconnection between the two lines of the diameter in the 1 1/2 breaker switchyardlayout.

For a 1 1/2 breaker arrangement, the modules BH_LINE_A, BH_CONN andBH_LINE_B must be used.

Section 3 1MRK 505 211-UEN C

IED application

324

 Application manual

Page 331: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 331/457

Configuration settingFor application without QB9 and QC9, just set the appropriate inputs to open stateand disregard the outputs. In the functional block diagram, 0 and 1 are designated0=FALSE and 1=TRUE:

• QB9_OP = 1• QB9_CL = 0

• QC9_OP = 1• QC9_CL = 0

If, in this case, line voltage supervision is added, then rather than setting QB9 toopen state, specify the state of the voltage supervision:

• QB9_OP = VOLT_OFF

• QB9_CL = VOLT_ON

If there is no voltage supervision, then set the corresponding inputs as follows:

• VOLT_OFF = 1• VOLT_ON = 0

3.11.3.10 Horizontal communication via GOOSE for interlocking

GOOSEINTLKRCV

T able 1 07 : G OO SE IN TL KR CV N on g rou p se ttin gs (ba sic)

Name Values (Range) Unit Step Default Description

Operation Off  On

- - Off Operation Off/On

3.11.4 Logic rotating switch for function selection and LHMI

presentation SLGGIO

Function description IEC 61850

identification

IEC 60617

identification

ANSI/IEEE C37.2

device numberLogic rotating switch for functionselection and LHMI presentation

SLGGIO - -

3.11.4.1 Application

The logic rotating switch for function selection and LHMI presentation function(SLGGIO) (or the selector switch function block, as it is also known) is used to geta selector switch functionality similar with the one provided by a hardware multi-

 position selector switch. Hardware selector switches are used extensively by

1MRK 505 211-UEN C Section 3IED application

325

 Application manual

Page 332: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 332/457

utilities, in order to have different functions operating on pre-set values. Hardwareswitches are however sources for maintenance issues, lower system reliability andextended purchase portfolio. The virtual selector switches eliminate all these

 problems.

SLGGIO function block has two operating inputs (UP and DOWN), one blockinginput (BLOCK) and one operator position input (PSTO).

SLGGIO can be activated both from the local HMI and from external sources(switches), via the IED binary inputs. It also allows the operation from remote (likethe station computer). SWPOSN is an integer value output, giving the actual outputnumber. Since the number of positions of the switch can be established by settings(see below), one must be careful in coordinating the settings with the configuration(if one sets the number of positions to x in settings – for example, there will beonly the first x outputs available from the block in the configuration). Also the

frequency of the (UP or DOWN) pulses should be lower than the setting tPulse.From the local HMI, there are two modes of operating the switch: from the menuand from the Single-line diagram (SLD).

3.11.4.2 Setting guidelines

The following settings are available for the Logic rotating switch for functionselection and LHMI presentation (SLGGIO) function:

Operation: Sets the operation of the function On or Off .

 NrPos: Sets the number of positions in the switch (max. 32). This setting influencethe behavior of the switch when changes from the last to the first position.

OutType: Steady or  Pulsed .

tPulse: In case of a pulsed output, it gives the length of the pulse (in seconds).

tDelay: The delay between the UP or DOWN activation signal positive front andthe output activation.

StopAtExtremes: Sets the behavior of the switch at the end positions – if set to Disabled , when pressing UP while on first position, the switch will jump to the last

 position; when pressing DOWN at the last position, the switch will jump to the first position; when set to Enabled , no jump will be allowed.

Section 3 1MRK 505 211-UEN C

IED application

326

 Application manual

Page 333: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 333/457

3.11.4.3 Setting parameters

Table 108: SLG GIO N on group settings (basic)

Name Values (Range) Unit Step Default Description

Operation Off  On

- - Off Operation Off/On

NrPos 2 - 32 - 1 32 Number of positions in the switch

OutType PulsedSteady

- - Steady Output type, steady or pulse

tPulse 0.000 - 60.000 s 0.001 0.200 Operate pulse duration, in [s]

tDelay 0.000 - 60000.000 s 0.010 0.000 Time delay on the output, in [s]

StopAtExtremes DisabledEnabled

- - Disabled Stop when min or max position is reached

3.11.5 Selector mini switch VSGGIO

Function description IEC 61850

identification

IEC 60617

identification

ANSI/IEEE C37.2

device number

Selector mini switch VSGGIO - -

3.11.5.1 Application

Selector mini switch (VSGGIO) function is a multipurpose function used in the

configuration tool in PCM600 for a variety of applications, as a general purposeswitch. VSGGIO can be used for both acquiring an external switch position(through the IPOS1 and the IPOS2 inputs) and represent it through the single linediagram symbols (or use it in the configuration through the outputs POS1 andPOS2) as well as, a command function (controlled by the PSTO input), givingswitching commands through the CMDPOS12 and CMDPOS21 outputs.

The output POSITION is an integer output, showing the actual position as aninteger number 0 – 3.

An example where VSGGIO is configured to switch Autorecloser on–off from a button symbol on the local HMI is shown in figure 135. The I and O buttons on the

local HMI are normally used for on–off operations of the circuit breaker.

1MRK 505 211-UEN C Section 3IED application

327

 Application manual

Page 334: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 334/457

IEC07000112-2-en.vsd

PSTO

CMDPOS12

IPOS1

NAM_POS1

NAM_POS2

IPOS2

CMDPOS21OFF

ON

VSGGIO

SMBRRECON

OFF

SETON

INTONE

INVERTER

INPUT OUT

IEC07000112 V2 EN

Figure 135: Control of Autorecloser from local HMI through Selector mini switch 

VSGGIO is also provided with IEC 61850 communication so it can be controlled

from SA system as well.

3.11.5.2 Setting guidelines

Selector mini switch (VSGGIO) function can generate pulsed or steady commands(by setting the Mode parameter). When pulsed commands are generated, the lengthof the pulse can be set using the tPulse parameter. Also, being accessible on thesingle line diagram (SLD), this function block has two control modes (settablethrough CtlModel ): Dir Norm and SBO Enh.

3.11.5.3 Setting parametersTable 109: VSG GIO Non group settings (basic)

Name Values (Range) Unit Step Default Description

Operation Off  On

- - Off Operation Off / On

CtlModel Dir NormSBO Enh

- - Dir Norm Specifies the type for control modelaccording to IEC 61850

Mode SteadyPulsed

- - Pulsed Operation mode

tSelect 0.000 - 60.000 s 0.001 30.000 Max time between select and executesignals

tPulse 0.000 - 60.000 s 0.001 0.200 Command pulse lenght

3.11.6 IEC61850 generic communication I/O functions DPGGIO

Function description IEC 61850

identification

IEC 60617

identification

ANSI/IEEE C37.2

device number

IEC 61850 generic communication I/Ofunctions

DPGGIO - -

Section 3 1MRK 505 211-UEN C

IED application

328

 Application manual

Page 335: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 335/457

3.11.6.1 Application

The IEC61850 generic communication I/O functions (DPGGIO) function block isused to send three logical outputs to other systems or equipment in the substation.

The three inputs are named OPEN, CLOSE and VALID, since this function block is intended to be used as a position indicator block in interlocking and reservationstation-wide logics.

3.11.6.2 Setting guidelines

The function does not have any parameters available in the local HMI or PCM600.

3.11.7 Single point generic control 8 signals SPC8GGIO

Function description IEC 61850

identification

IEC 60617

identification

ANSI/IEEE C37.2

device number

Single point generic control 8 signals SPC8GGIO - -

3.11.7.1 Application

The Single point generic control 8 signals (SPC8GGIO) function block is acollection of 8 single point commands, designed to bring in commands fromREMOTE (SCADA) to those parts of the logic configuration that do not needcomplicated function blocks that have the capability to receive commands (for 

example SCSWI). In this way, simple commands can be sent directly to the IEDoutputs, without confirmation. Confirmation (status) of the result of the commandsis supposed to be achieved by other means, such as binary inputs and SPGGIOfunction blocks.

PSTO is the universal operator place selector for all controlfunctions. Even if PSTO can be configured to allow LOCAL or ALL operator positions, the only functional position usable with theSPC8GGIO function block is REMOTE.

3.11.7.2 Setting guidelines

The parameters for the single point generic control 8 signals (SPC8GGIO) functionare set via the local HMI or PCM600.

Operation: turning the function operation On/Off .

There are two settings for every command output (totally 8):

 Latchedx: decides if the command signal for output x is Latched (steady) or  Pulsed .

1MRK 505 211-UEN C Section 3IED application

329

 Application manual

Page 336: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 336/457

tPulsex: if  Latchedx is set to Pulsed , then tPulsex will set the length of the pulse (inseconds).

3.11.7.3 Setting parameters

Table 110: SPC 8G GIO Non group settings (basic)

Name Values (Range) Unit Step Default Description

Operation Off  On

- - Off Operation Off/On

Latched1 PulsedLatched

- - Pulsed Setting for pulsed/latched mode for  output 1

tPulse1 0.01 - 6000.00 s 0.01 0.10 Output1 Pulse Time

Latched2 PulsedLatched

- - Pulsed Setting for pulsed/latched mode for  output 2

tPulse2 0.01 - 6000.00 s 0.01 0.10 Output2 Pulse Time

Latched3 PulsedLatched

- - Pulsed Setting for pulsed/latched mode for  output 3

tPulse3 0.01 - 6000.00 s 0.01 0.10 Output3 Pulse Time

Latched4 PulsedLatched

- - Pulsed Setting for pulsed/latched mode for  output 4

tPulse4 0.01 - 6000.00 s 0.01 0.10 Output4 Pulse Time

Latched5 PulsedLatched

- - Pulsed Setting for pulsed/latched mode for  output 5

tPulse5 0.01 - 6000.00 s 0.01 0.10 Output5 Pulse Time

Latched6 PulsedLatched

- - Pulsed Setting for pulsed/latched mode for  output 6

tPulse6 0.01 - 6000.00 s 0.01 0.10 Output6 Pulse Time

Latched7 PulsedLatched

- - Pulsed Setting for pulsed/latched mode for  output 7

tPulse7 0.01 - 6000.00 s 0.01 0.10 Output7 Pulse Time

Latched8 PulsedLatched

- - Pulsed Setting for pulsed/latched mode for  output 8

tPulse8 0.01 - 6000.00 s 0.01 0.10 Output8 pulse time

3.11.8 AutomationBits, command function for DNP3.0 AUTOBITS

Function description IEC 61850

identification

IEC 60617

identification

ANSI/IEEE C37.2

device number

 AutomationBits, command function for DNP3

 AUTOBITS - -

3.11.8.1 Application

Automation bits, command function for DNP3 (AUTOBITS) is used withinPCM600 in order to get into the configuration the commands coming through the

Section 3 1MRK 505 211-UEN C

IED application

330

 Application manual

Page 337: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 337/457

DNP3.0 protocol.The AUTOBITS function plays the same role as functionsGOOSEBINRCV (for IEC 61850) and MULTICMDRCV (for LON).AUTOBITSfunction block have 32 individual outputs which each can be mapped as a BinaryOutput point in DNP3. The output is operated by a "Object 12" in DNP3. Thisobject contains parameters for control-code, count, on-time and off-time. Tooperate an AUTOBITS output point, send a control-code of latch-On, latch-Off,

 pulse-On, pulse-Off, Trip or Close. The remaining parameters are regarded asappropriate. For example, pulse-On, on-time=100, off-time=300, count=5 wouldgive 5 positive 100 ms pulses, 300 ms apart.

For description of the DNP3 protocol implementation, refer to the Communicationmanual.

3.11.8.2 Setting guidelines

AUTOBITS function block has one setting, (Operation: On/Off ) enabling or disabling the function. These names will be seen in the DNP3 communicationmanagement tool in PCM600.

3.11.8.3 Setting parameters

Table 111: D NP GEN N on group settings (basic)

Name Values (Range) Unit Step Default Description

Operation Off  On

- - Off Operation mode Off / On

Table 112: C HS ER RS485 Non group settings (basic)

Name Values (Range) Unit Step Default Description

Operation Off  Serial-Mode

- - Off Operation mode

BaudRate 300 Bd600 Bd1200 Bd2400 Bd4800 Bd9600 Bd19200 Bd

- - 9600 Bd Baud-rate for serial port

WireMode Four-wireTwo-wire

- - Two-wire RS485 wire mode

T able 1 13 : C HS ER RS 48 5 N on g ro up se ttin gs (a dv an ce d)

Name Values (Range) Unit Step Default Description

DLinkConfirm Never  Sometimes

 Always

- - Never Data-link confirm

tDLinkTimeout 0.000 - 60.000 s 0.001 2.000 Data-link confirm timeout in s

DLinkRetries 0 - 255 - 1 3 Data-link maximum retries

Table continues on next page

1MRK 505 211-UEN C Section 3IED application

331

 Application manual

Page 338: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 338/457

Name Values (Range) Unit Step Default Description

tRxToTxMinDel 0.000 - 60.000 s 0.001 0.000 Rx to Tx minimum delay in s

 ApLayMaxRxSize 20 - 2048 - 1 2048 Application layer maximum Rx fragmentsize

 ApLayMaxTxSize 20 - 2048 - 1 2048 Application layer maximum Tx fragmentsize

StopBits 1 - 2 - 1 1 Stop bits

Parity NoEvenOdd

- - Even Parity

tRTSWarmUp 0.000 - 60.000 s 0.001 0.000 RTS warm-up in s

tRTSWarmDown 0.000 - 60.000 s 0.001 0.000 RTS warm-down in s

tBackOffDelay 0.000 - 60.000 s 0.001 0.050 RS485 back-off delay in s

tMaxRndDelBkOf 0.000 - 60.000 s 0.001 0.100 RS485 maximum back-off random delayin s

Table 114: CH 2TC P N on group settings (basic)

Name Values (Range) Unit Step Default Description

Operation Off  TCP/IPUDP-Only

- - Off Operation mode

TCPIPLisPort 1 - 65535 - 1 20000 TCP/IP listen port

UDPPortAccData 1 - 65535 - 1 20000 UDP port to accept UDP datagrams frommaster 

UDPPortInitNUL 1 - 65535 - 1 20000 UDP port for initial NULL response

UDPPortCliMast 0 - 65535 - 1 0 UDP port to remote client/master  

Table 115: CH 2TC P N on group settings (advanced)

Name Values (Range) Unit Step Default Description

 ApLayMaxRxSize 20 - 2048 - 1 2048 Application layer maximum Rx fragmentsize

 ApLayMaxTxSize 20 - 2048 - 1 2048 Application layer maximum Tx fragmentsize

Table 116: CH 3TC P N on group settings (basic)

Name Values (Range) Unit Step Default Description

Operation Off  TCP/IPUDP-Only

- - Off Operation mode

TCPIPLisPort 1 - 65535 - 1 20000 TCP/IP listen port

UDPPortAccData 1 - 65535 - 1 20000 UDP port to accept UDP datagrams frommaster 

UDPPortInitNUL 1 - 65535 - 1 20000 UDP port for initial NULL response

UDPPortCliMast 0 - 65535 - 1 0 UDP port to remote client/master  

Section 3 1MRK 505 211-UEN C

IED application

332

 Application manual

Page 339: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 339/457

Table 117: C H3TC P N on group settings (advanced)

Name Values (Range) Unit Step Default Description

 ApLayMaxRxSize 20 - 2048 - 1 2048 Application layer maximum Rx fragmentsize

 ApLayMaxTxSize 20 - 2048 - 1 2048 Application layer maximum Tx fragmentsize

Table 118: C H4TC P N on group settings (basic)

Name Values (Range) Unit Step Default Description

Operation Off  TCP/IPUDP-Only

- - Off Operation mode

TCPIPLisPort 1 - 65535 - 1 20000 TCP/IP listen port

UDPPortAccData 1 - 65535 - 1 20000 UDP port to accept UDP datagrams from

master 

UDPPortInitNUL 1 - 65535 - 1 20000 UDP port for initial NULL response

UDPPortCliMast 0 - 65535 - 1 0 UDP port to remote client/master  

Table 119: C H4TC P N on group settings (advanced)

Name Values (Range) Unit Step Default Description

 ApLayMaxRxSize 20 - 2048 - 1 2048 Application layer maximum Rx fragmentsize

 ApLayMaxTxSize 20 - 2048 - 1 2048 Application layer maximum Tx fragmentsize

Table 120: C H5TC P N on group settings (basic)

Name Values (Range) Unit Step Default Description

Operation Off  TCP/IPUDP-Only

- - Off Operation mode

TCPIPLisPort 1 - 65535 - 1 20000 TCP/IP listen port

UDPPortAccData 1 - 65535 - 1 20000 UDP port to accept UDP datagrams frommaster 

UDPPortInitNUL 1 - 65535 - 1 20000 UDP port for initial NULL response

UDPPortCliMast 0 - 65535 - 1 0 UDP port to remote client/master  

Table 121: C H5TC P N on group settings (advanced)

Name Values (Range) Unit Step Default Description

 ApLayMaxRxSize 20 - 2048 - 1 2048 Application layer maximum Rx fragmentsize

 ApLayMaxTxSize 20 - 2048 - 1 2048 Application layer maximum Tx fragmentsize

1MRK 505 211-UEN C Section 3IED application

333

 Application manual

Page 340: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 340/457

Table 122: M STR S485 Non group settings (basic)

Name Values (Range) Unit Step Default Description

Operation Off  On

- - Off Operation Off / On

SlaveAddress 0 - 65519 - 1 1 Slave address

MasterAddres 0 - 65519 - 1 1 Master address

Obj1DefVar 1:BISingleBit2:BIWithStatus

- - 1:BISingleBit Object 1, default variation

Obj2DefVar 1:BIChWithoutTime2:BIChWithTime3:BIChWithRelTime

- - 3:BIChWithRelTime

Object 2, default variation

Obj4DefVar 1:DIChWithoutTime2:DIChWithTime

3:DIChWithRelTime

- - 3:DIChWithRelTime

Object 4, default variation

Obj10DefVar 1:BO2:BOStatus

- - 2:BOStatus Object 10, default variation

Obj20DefVar 1:BinCnt322:BinCnt165:BinCnt32WoutF6:BinCnt16WoutF

- - 5:BinCnt32WoutF Object 20, default variation

Obj22DefVar 1:BinCnt32EvWoutT2:BinCnt16EvWoutT5:BinCnt32EvWithT

6:BinCnt16EvWithT

- - 1:BinCnt32EvWoutT

Object 22, default variation

Obj30DefVar 1:AI32Int2:AI16Int3:AI32IntWithoutF4:AI16IntWithoutF5:AI32FltWithF6:AI64FltWithF

- - 3:AI32IntWithoutF Object 30, default variation

Obj32DefVar 1:AI32IntEvWoutF2:AI16IntEvWoutF3:AI32IntEvWithFT4:AI16IntEvWithFT5:AI32FltEvWithF6:AI64FltEvWithF

7:AI32FltEvWithFT8:AI64FltEvWithFT

- - 1:AI32IntEvWoutF Object 32, default variation

Section 3 1MRK 505 211-UEN C

IED application

334

 Application manual

Page 341: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 341/457

Table 123: M STR S485 Non group settings (advanced)

Name Values (Range) Unit Step Default Description

ValMasterAddr NoYes

- - Yes Validate source (master) address

 AddrQueryEnbl NoYes

- - Yes Address query enable

tApplConfTout 0.00 - 300.00 s 0.01 10.00 Application layer confim timeout

 ApplMultFrgRes NoYes

- - Yes Enable application for multiple fragmentresponse

ConfMultFrag NoYes

- - Yes Confirm each multiple fragment

UREnable NoYes

- - Yes Unsolicited response enabled

URSendOnline NoYes

- - No Unsolicited response sends when on-line

UREvClassMask Off  Class 1Class 2Class 1 and 2Class 3Class 1 and 3Class 2 and 3Class 1, 2 and 3

- - Off Unsolicited response, event class mask

UROfflineRetry 0 - 10 - 1 5 Unsolicited response retries before off-line retry mode

tURRetryDelay 0.00 - 60.00 s 0.01 5.00 Unsolicited response retry delay in s

tUROfflRtryDel 0.00 - 60.00 s 0.01 30.00 Unsolicited response off-line retry delayin s

UREvCntThold1 1 - 100 - 1 5 Unsolicited response class 1 event countreport treshold

tUREvBufTout1 0.00 - 60.00 s 0.01 5.00 Unsolicited response class 1 eventbuffer timeout

UREvCntThold2 1 - 100 - 1 5 Unsolicited response class 2 event countreport treshold

tUREvBufTout2 0.00 - 60.00 s 0.01 5.00 Unsolicited response class 2 eventbuffer timeout

UREvCntThold3 1 - 100 - 1 5 Unsolicited response class 3 event countreport treshold

tUREvBufTout3 0.00 - 60.00 s 0.01 5.00 Unsolicited response class 3 eventbuffer timeout

DelOldBufFull NoYes

- - No Delete oldest event when buffer is full

tSynchTimeout 30 - 3600 s 1 1800 Time synch timeout before error status isgenerated

TSyncReqAfTout NoYes

- - No Time synchronization request after  timeout

DNPToSetTime NoYes

- - Yes Allow DNP to set time in IED

Table continues on next page

1MRK 505 211-UEN C Section 3IED application

335

 Application manual

Page 342: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 342/457

Name Values (Range) Unit Step Default Description

 Averag3TimeReq NoYes

- - No Use average of 3 time requests

PairedPoint No

Yes

- - Yes Enable paired point

tSelectTimeout 1.0 - 60.0 s 0.1 30.0 Select timeout

Table 124: M ST1TC P N on group settings (basic)

Name Values (Range) Unit Step Default Description

Operation Off  On

- - Off Operation Off / On

SlaveAddress 0 - 65519 - 1 1 Slave address

MasterAddres 0 - 65519 - 1 1 Master address

ValMasterAddr NoYes

- - Yes Validate source (master) address

MasterIP-Addr 0 - 18 IP Address

1 0.0.0.0 Master IP-address

MasterIPNetMsk 0 - 18 IP Address

1 255.255.255.255 Master IP net mask

Obj1DefVar 1:BISingleBit2:BIWithStatus

- - 1:BISingleBit Object 1, default variation

Obj2DefVar 1:BIChWithoutTime2:BIChWithTime3:BIChWithRelTime

- - 3:BIChWithRelTime

Object 2, default variation

Obj3DefVar 1:DIWithoutFlag2:DIWithFlag

- - 1:DIWithoutFlag Object 3, default variation

Obj4DefVar 1:DIChWithoutTime2:DIChWithTime3:DIChWithRelTime

- - 3:DIChWithRelTime

Object 4, default variation

Obj10DefVar 1:BO2:BOStatus

- - 2:BOStatus Object 10, default variation

Obj20DefVar 1:BinCnt322:BinCnt165:BinCnt32WoutF6:BinCnt16WoutF

- - 5:BinCnt32WoutF Object 20, default variation

Table continues on next page

Section 3 1MRK 505 211-UEN C

IED application

336

 Application manual

Page 343: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 343/457

Name Values (Range) Unit Step Default Description

Obj22DefVar 1:BinCnt32EvWoutT2:BinCnt16EvWoutT

5:BinCnt32EvWithT6:BinCnt16EvWithT

- - 1:BinCnt32EvWoutT

Object 22, default variation

Obj30DefVar 1:AI32Int2:AI16Int3:AI32IntWithoutF4:AI16IntWithoutF5:AI32FltWithF6:AI64FltWithF

- - 3:AI32IntWithoutF Object 30, default variation

Obj32DefVar 1:AI32IntEvWoutF2:AI16IntEvWoutF3:AI32IntEvWithFT4:AI16IntEvWithFT

5:AI32FltEvWithF6:AI64FltEvWithF7:AI32FltEvWithFT8:AI64FltEvWithFT

- - 1:AI32IntEvWoutF Object 32, default variation

Table 125: M ST1TCP Non group settings (advanced)

Name Values (Range) Unit Step Default Description

 AddrQueryEnbl NoYes

- - Yes Address query enable

tApplConfTout 0.00 - 300.00 s 0.01 10.00 Application layer confim timeout

 ApplMultFrgRes No

Yes

- - Yes Enable application for multiple fragment

response

ConfMultFrag NoYes

- - Yes Confirm each multiple fragment

UREnable NoYes

- - Yes Unsolicited response enabled

UREvClassMask Off  Class 1Class 2Class 1 and 2Class 3Class 1 and 3Class 2 and 3Class 1, 2 and 3

- - Off Unsolicited response, event class mask

UROfflineRetry 0 - 10 - 1 5 Unsolicited response retries before off-line retry mode

tURRetryDelay 0.00 - 60.00 s 0.01 5.00 Unsolicited response retry delay in s

tUROfflRtryDel 0.00 - 60.00 s 0.01 30.00 Unsolicited response off-line retry delayin s

UREvCntThold1 1 - 100 - 1 5 Unsolicited response class 1 event countreport treshold

tUREvBufTout1 0.00 - 60.00 s 0.01 5.00 Unsolicited response class 1 eventbuffer timeout

UREvCntThold2 1 - 100 - 1 5 Unsolicited response class 2 event countreport treshold

Table continues on next page

1MRK 505 211-UEN C Section 3IED application

337

 Application manual

Page 344: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 344/457

Name Values (Range) Unit Step Default Description

tUREvBufTout2 0.00 - 60.00 s 0.01 5.00 Unsolicited response class 2 eventbuffer timeout

UREvCntThold3 1 - 100 - 1 5 Unsolicited response class 3 event count

report treshold

tUREvBufTout3 0.00 - 60.00 s 0.01 5.00 Unsolicited response class 3 eventbuffer timeout

DelOldBufFull NoYes

- - No Delete oldest event when buffer is full

ExtTimeFormat LocalTimeUTC

- - UTC External time format

DNPToSetTime NoYes

- - No Allow DNP to set time in IED

tSynchTimeout 30 - 3600 s 1 1800 Time synch timeout before error status isgenerated

TSyncReqAfTout No

Yes

- - No Time synchronization request after  

timeout

 Averag3TimeReq NoYes

- - No Use average of 3 time requests

PairedPoint NoYes

- - Yes Enable paired point

tSelectTimeout 1.0 - 60.0 s 0.1 30.0 Select timeout

tBrokenConTout 0 - 3600 s 1 0 Broken connection timeout

tKeepAliveT 0 - 3600 s 1 10 Keep-Alive timer  

Table 126: M ST2TC P N on group settings (basic)

Name Values (Range) Unit Step Default Description

Operation Off  On

- - Off Operation Off / On

SlaveAddress 0 - 65519 - 1 1 Slave address

MasterAddres 0 - 65519 - 1 1 Master address

ValMasterAddr NoYes

- - Yes Validate source (master) address

MasterIP-Addr 0 - 18 IP Address

1 0.0.0.0 Master IP-address

MasterIPNetMsk 0 - 18 IP Address

1 255.255.255.255 Master IP net mask

Obj1DefVar 1:BISingleBit2:BIWithStatus

- - 1:BISingleBit Object 1, default variation

Obj2DefVar 1:BIChWithoutTime2:BIChWithTime3:BIChWithRelTime

- - 3:BIChWithRelTime

Object 2, default variation

Obj3DefVar 1:DIWithoutFlag2:DIWithFlag

- - 1:DIWithoutFlag Object 3, default variation

Table continues on next page

Section 3 1MRK 505 211-UEN C

IED application

338

 Application manual

Page 345: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 345/457

Name Values (Range) Unit Step Default Description

Obj4DefVar 1:DIChWithoutTime2:DIChWithTime3:DIChWithRelTim

e

- - 3:DIChWithRelTime

Object 4, default variation

Obj10DefVar 1:BO2:BOStatus

- - 2:BOStatus Object 10, default variation

Obj20DefVar 1:BinCnt322:BinCnt165:BinCnt32WoutF6:BinCnt16WoutF

- - 5:BinCnt32WoutF Object 20, default variation

Obj22DefVar 1:BinCnt32EvWoutT2:BinCnt16EvWoutT5:BinCnt32EvWithT

6:BinCnt16EvWithT

- - 1:BinCnt32EvWoutT

Object 22, default variation

Obj30DefVar 1:AI32Int2:AI16Int3:AI32IntWithoutF4:AI16IntWithoutF5:AI32FltWithF6:AI64FltWithF

- - 3:AI32IntWithoutF Object 30, default variation

Obj32DefVar 1:AI32IntEvWoutF2:AI16IntEvWoutF3:AI32IntEvWithFT4:AI16IntEvWithFT5:AI32FltEvWithF6:AI64FltEvWithF7:AI32FltEvWithFT8:AI64FltEvWithFT

- - 1:AI32IntEvWoutF Object 32, default variation

Table 127: M ST2TCP Non group settings (advanced)

Name Values (Range) Unit Step Default Description

 AddrQueryEnbl NoYes

- - Yes Address query enable

tApplConfTout 0.00 - 300.00 s 0.01 10.00 Application layer confim timeout

 ApplMultFrgRes NoYes

- - Yes Enable application for multiple fragmentresponse

ConfMultFrag NoYes

- - Yes Confirm each multiple fragment

UREnable NoYes

- - Yes Unsolicited response enabled

UREvClassMask Off  Class 1Class 2Class 1 and 2Class 3Class 1 and 3Class 2 and 3Class 1, 2 and 3

- - Off Unsolicited response, event class mask

Table continues on next page

1MRK 505 211-UEN C Section 3IED application

339

 Application manual

Page 346: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 346/457

Name Values (Range) Unit Step Default Description

UROfflineRetry 0 - 10 - 1 5 Unsolicited response retries before off-line retry mode

tURRetryDelay 0.00 - 60.00 s 0.01 5.00 Unsolicited response retry delay in s

tUROfflRtryDel 0.00 - 60.00 s 0.01 30.00 Unsolicited response off-line retry delayin s

UREvCntThold1 1 - 100 - 1 5 Unsolicited response class 1 event countreport treshold

tUREvBufTout1 0.00 - 60.00 s 0.01 5.00 Unsolicited response class 1 eventbuffer timeout

UREvCntThold2 1 - 100 - 1 5 Unsolicited response class 2 event countreport treshold

tUREvBufTout2 0.00 - 60.00 s 0.01 5.00 Unsolicited response class 2 eventbuffer timeout

UREvCntThold3 1 - 100 - 1 5 Unsolicited response class 3 event countreport treshold

tUREvBufTout3 0.00 - 60.00 s 0.01 5.00 Unsolicited response class 3 eventbuffer timeout

DelOldBufFull NoYes

- - No Delete oldest event when buffer is full

ExtTimeFormat LocalTimeUTC

- - UTC External time format

DNPToSetTime NoYes

- - No Allow DNP to set time in IED

tSynchTimeout 30 - 3600 s 1 1800 Time synch timeout before error status isgenerated

TSyncReqAfTout No

Yes

- - No Time synchronization request after  

timeout Averag3TimeReq No

Yes- - No Use average of 3 time requests

PairedPoint NoYes

- - Yes Enable paired point

tSelectTimeout 1.0 - 60.0 s 0.1 30.0 Select timeout

tBrokenConTout 0 - 3600 s 1 0 Broken connection timeout

tKeepAliveT 0 - 3600 s 1 10 Keep-Alive timer  

Table 128: M ST3TC P N on group settings (basic)

Name Values (Range) Unit Step Default Description

Operation Off  On

- - Off Operation Off / On

SlaveAddress 0 - 65519 - 1 1 Slave address

MasterAddres 0 - 65519 - 1 1 Master address

ValMasterAddr NoYes

- - Yes Validate source (master) address

MasterIP-Addr 0 - 18 IP Address

1 0.0.0.0 Master IP-address

Table continues on next page

Section 3 1MRK 505 211-UEN C

IED application

340

 Application manual

Page 347: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 347/457

Name Values (Range) Unit Step Default Description

MasterIPNetMsk 0 - 18 IP Address

1 255.255.255.255 Master IP net mask

Obj1DefVar 1:BISingleBit

2:BIWithStatus

- - 1:BISingleBit Object 1, default variation

Obj2DefVar 1:BIChWithoutTime2:BIChWithTime3:BIChWithRelTime

- - 3:BIChWithRelTime

Object 2, default variation

Obj3DefVar 1:DIWithoutFlag2:DIWithFlag

- - 1:DIWithoutFlag Object 3, default variation

Obj4DefVar 1:DIChWithoutTime2:DIChWithTime3:DIChWithRelTime

- - 3:DIChWithRelTime

Object 4, default variation

Obj10DefVar 1:BO2:BOStatus

- - 2:BOStatus Object 10, default variation

Obj20DefVar 1:BinCnt322:BinCnt165:BinCnt32WoutF6:BinCnt16WoutF

- - 5:BinCnt32WoutF Object 20, default variation

Obj22DefVar 1:BinCnt32EvWoutT2:BinCnt16EvWoutT5:BinCnt32EvWithT6:BinCnt16EvWithT

- - 1:BinCnt32EvWoutT

Object 22, default variation

Obj30DefVar 1:AI32Int2:AI16Int3:AI32IntWithoutF4:AI16IntWithoutF5:AI32FltWithF6:AI64FltWithF

- - 3:AI32IntWithoutF Object 30, default variation

Obj32DefVar 1:AI32IntEvWoutF2:AI16IntEvWoutF3:AI32IntEvWithFT4:AI16IntEvWithFT5:AI32FltEvWithF6:AI64FltEvWithF7:AI32FltEvWithFT8:AI64FltEvWithFT

- - 1:AI32IntEvWoutF Object 32, default variation

Table 129: M ST3TCP Non group settings (advanced)

Name Values (Range) Unit Step Default Description

 AddrQueryEnbl NoYes

- - Yes Address query enable

tApplConfTout 0.00 - 300.00 s 0.01 10.00 Application layer confim timeout

 ApplMultFrgRes NoYes

- - Yes Enable application for multiple fragmentresponse

Table continues on next page

1MRK 505 211-UEN C Section 3IED application

341

 Application manual

Page 348: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 348/457

Name Values (Range) Unit Step Default Description

ConfMultFrag NoYes

- - Yes Confirm each multiple fragment

UREnable No

Yes

- - Yes Unsolicited response enabled

UREvClassMask Off  Class 1Class 2Class 1 and 2Class 3Class 1 and 3Class 2 and 3Class 1, 2 and 3

- - Off Unsolicited response, event class mask

UROfflineRetry 0 - 10 - 1 5 Unsolicited response retries before off-line retry mode

tURRetryDelay 0.00 - 60.00 s 0.01 5.00 Unsolicited response retry delay in s

tUROfflRtryDel 0.00 - 60.00 s 0.01 30.00 Unsolicited response off-line retry delay

in s

UREvCntThold1 1 - 100 - 1 5 Unsolicited response class 1 event countreport treshold

tUREvBufTout1 0.00 - 60.00 s 0.01 5.00 Unsolicited response class 1 eventbuffer timeout

UREvCntThold2 1 - 100 - 1 5 Unsolicited response class 2 event countreport treshold

tUREvBufTout2 0.00 - 60.00 s 0.01 5.00 Unsolicited response class 2 eventbuffer timeout

UREvCntThold3 1 - 100 - 1 5 Unsolicited response class 3 event countreport treshold

tUREvBufTout3 0.00 - 60.00 s 0.01 5.00 Unsolicited response class 3 event

buffer timeout

DelOldBufFull NoYes

- - No Delete oldest event when buffer is full

ExtTimeFormat LocalTimeUTC

- - UTC External time format

DNPToSetTime NoYes

- - No Allow DNP to set time in IED

tSynchTimeout 30 - 3600 s 1 1800 Time synch timeout before error status isgenerated

TSyncReqAfTout NoYes

- - No Time synchronization request after  timeout

 Averag3TimeReq NoYes - - No Use average of 3 time requests

PairedPoint NoYes

- - Yes Enable paired point

tSelectTimeout 1.0 - 60.0 s 0.1 30.0 Select timeout

tBrokenConTout 0 - 3600 s 1 0 Broken connection timeout

tKeepAliveT 0 - 3600 s 1 10 Keep-Alive timer  

Section 3 1MRK 505 211-UEN C

IED application

342

 Application manual

Page 349: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 349/457

Table 130: M ST4TCP Non group settings (basic)

Name Values (Range) Unit Step Default Description

Operation Off  On

- - Off Operation Off / On

SlaveAddress 0 - 65519 - 1 1 Slave address

MasterAddres 0 - 65519 - 1 1 Master address

ValMasterAddr NoYes

- - Yes Validate source (master) address

MasterIP-Addr 0 - 18 IP Address

1 0.0.0.0 Master IP-address

MasterIPNetMsk 0 - 18 IP Address

1 255.255.255.255 Master IP net mask

Obj1DefVar 1:BISingleBit2:BIWithStatus

- - 1:BISingleBit Object 1, default variation

Obj2DefVar 1:BIChWithoutTim

e2:BIChWithTime3:BIChWithRelTime

- - 3:BIChWithRelTim

e

Object 2, default variation

Obj3DefVar 1:DIWithoutFlag2:DIWithFlag

- - 1:DIWithoutFlag Object 3, default variation

Obj4DefVar 1:DIChWithoutTime2:DIChWithTime3:DIChWithRelTime

- - 3:DIChWithRelTime

Object 4, default variation

Obj10DefVar 1:BO2:BOStatus

- - 2:BOStatus Object 10, default variation

Obj20DefVar 1:BinCnt322:BinCnt165:BinCnt32WoutF6:BinCnt16WoutF

- - 5:BinCnt32WoutF Object 20, default variation

Obj22DefVar 1:BinCnt32EvWoutT2:BinCnt16EvWoutT5:BinCnt32EvWithT6:BinCnt16EvWithT

- - 1:BinCnt32EvWoutT

Object 22, default variation

Obj30DefVar 1:AI32Int2:AI16Int

3:AI32IntWithoutF4:AI16IntWithoutF5:AI32FltWithF6:AI64FltWithF

- - 3:AI32IntWithoutF Object 30, default variation

Obj32DefVar 1:AI32IntEvWoutF2:AI16IntEvWoutF3:AI32IntEvWithFT4:AI16IntEvWithFT5:AI32FltEvWithF6:AI64FltEvWithF7:AI32FltEvWithFT8:AI64FltEvWithFT

- - 1:AI32IntEvWoutF Object 32, default variation

1MRK 505 211-UEN C Section 3IED application

343

 Application manual

Page 350: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 350/457

Table 131: M ST4TC P N on group settings (advanced)

Name Values (Range) Unit Step Default Description

 AddrQueryEnbl NoYes

- - Yes Address query enable

tApplConfTout 0.00 - 300.00 s 0.01 10.00 Application layer confim timeout

 ApplMultFrgRes NoYes

- - Yes Enable application for multiple fragmentresponse

ConfMultFrag NoYes

- - Yes Confirm each multiple fragment

UREnable NoYes

- - Yes Unsolicited response enabled

UREvClassMask Off  Class 1Class 2Class 1 and 2Class 3

Class 1 and 3Class 2 and 3Class 1, 2 and 3

- - Off Unsolicited response, event class mask

UROfflineRetry 0 - 10 - 1 5 Unsolicited response retries before off-line retry mode

tURRetryDelay 0.00 - 60.00 s 0.01 5.00 Unsolicited response retry delay in s

tUROfflRtryDel 0.00 - 60.00 s 0.01 30.00 Unsolicited response off-line retry delayin s

UREvCntThold1 1 - 100 - 1 5 Unsolicited response class 1 event countreport treshold

tUREvBufTout1 0.00 - 60.00 s 0.01 5.00 Unsolicited response class 1 eventbuffer timeout

UREvCntThold2 1 - 100 - 1 5 Unsolicited response class 2 event countreport treshold

tUREvBufTout2 0.00 - 60.00 s 0.01 5.00 Unsolicited response class 2 eventbuffer timeout

UREvCntThold3 1 - 100 - 1 5 Unsolicited response class 3 event countreport treshold

tUREvBufTout3 0.00 - 60.00 s 0.01 5.00 Unsolicited response class 3 eventbuffer timeout

DelOldBufFull NoYes

- - No Delete oldest event when buffer is full

ExtTimeFormat LocalTimeUTC

- - UTC External time format

DNPToSetTime NoYes

- - No Allow DNP to set time in IED

tSynchTimeout 30 - 3600 s 1 1800 Time synch timeout before error status isgenerated

TSyncReqAfTout NoYes

- - No Time synchronization request after  timeout

 Averag3TimeReq NoYes

- - No Use average of 3 time requests

PairedPoint NoYes

- - Yes Enable paired point

Table continues on next page

Section 3 1MRK 505 211-UEN C

IED application

344

 Application manual

Page 351: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 351/457

Name Values (Range) Unit Step Default Description

tSelectTimeout 1.0 - 60.0 s 0.1 30.0 Select timeout

tBrokenConTout 0 - 3600 s 1 0 Broken connection timeout

tKeepAliveT 0 - 3600 s 1 10 Keep-Alive timer  

3.11.9 Single command, 16 signals SINGLECMD

Function description IEC 61850

identification

IEC 60617

identification

ANSI/IEEE C37.2

device number

Single command, 16 signals SINGLECMD - -

3.11.9.1 Application

Single command, 16 signals (SINGLECMD) is a common function and alwaysincluded in the IED.

The IEDs may be provided with a function to receive commands either from asubstation automation system or from the local HMI. That receiving function block has outputs that can be used, for example, to control high voltage apparatuses inswitchyards. For local control functions, the local HMI can also be used. Together with the configuration logic circuits, the user can govern pulses or steady outputsignals for control purposes within the IED or via binary outputs.

Figure 136 shows an application example of how the user can connectSINGLECMD via configuration logic circuit to control a high-voltage apparatus.This type of command control is normally carried out by sending a pulse to the

 binary outputs of the IED. Figure 136 shows a close operation. An open breaker operation is performed in a similar way but without the synchro-check condition.

1MRK 505 211-UEN C Section 3IED application

345

 Application manual

Page 352: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 352/457

Single

command

function

SINGLECMD

CMDOUTy

OUTy

Close CB1

&User-

defined

conditions

Synchro-

check

Configuration logic circuits

en04000206.vsdIEC04000206 V2 EN

Figure 136: Application example showing a logic diagram for control of a circuit 

breaker via configuration logic circuits 

Figure 137 and figure 138 show other ways to control functions, which requiresteady On/Off signals. Here, the output is used to control built-in functions or external devices.

Singlecommand

functionSINGLECMD

CMDOUTy

OUTy

Function n

en04000207.vsd

Function n

IEC04000207 V2 EN

Figure 137: Application example showing a logic diagram for control of built-in 

functions 

Section 3 1MRK 505 211-UEN C

IED application

346

 Application manual

Page 353: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 353/457

Singlecommand

function

SINGLESMD

CMDOUTy

OUTy

Device 1

User-

defined

conditions

Configuration logic circuits

en04000208.vsd

&

IEC04000208 V2 EN

Figure 138: Application example showing a logic diagram for control of external 

devices via configuration logic circuits 

3.11.9.2 Setting guidelines

The parameters for Single command, 16 signals (SINGLECMD) are set via thelocal HMI or PCM600.

Parameters to be set are MODE, common for the whole block, and CMDOUTy

which includes the user defined name for each output signal. The MODE input setsthe outputs to be one of the types Off, Steady, or Pulse.

• Off, sets all outputs to 0, independent of the values sent from the station level,that is, the operator station or remote-control gateway.

• Steady, sets the outputs to a steady signal 0 or 1, depending on the values sentfrom the station level.

• Pulse, gives a pulse with 100 ms duration, if a value sent from the station levelis changed from 0 to 1. That means the configured logic connected to thecommand function block may not have a cycle time longer than the cycle timefor the command function block.

3.11.9.3 Setting parameters

Table 132: SIN GLEC MD Non group settings (basic)

Name Values (Range) Unit Step Default Description

Mode Off  SteadyPulsed

- - Off Operation mode

1MRK 505 211-UEN C Section 3IED application

347

 Application manual

Page 354: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 354/457

3.12 Logic

3.12.1 Configurable logic blocks

3.12.1.1 Application

A set of standard logic blocks, like AND, OR etc, and timers are available for adapting the IED configuration to the specific application needs.

There are no settings for AND gates, OR gates, inverters or XOR gates.

For normal On/Off delay and pulse timers the time delays and pulse lengths are setfrom the local HMI or via the PST tool.

Both timers in the same logic block (the one delayed on pick-up and the onedelayed on drop-out) always have a common setting value.

For controllable gates, settable timers and SR flip-flops with memory, the setting parameters are accessible via the local HMI or via the PST tool.

ConfigurationLogic is configured using the ACT configuration tool in PCM600.

Execution of functions as defined by the configurable logic blocks runs accordingto a fixed sequence with different cycle times.

For each cycle time, the function block is given an serial execution number. This isshown when using the ACT configuration tool with the designation of the function

 block and the cycle time, see example below.

IEC09000695_2_en.vsd

IEC09000695 V2 EN

Figure 139: Example designation, serial execution number and cycle time for 

logic function 

The execution of different function blocks within the same cycle is determined bythe order of their serial execution numbers. Always remember this whenconnecting two or more logical function blocks in series.

Section 3 1MRK 505 211-UEN C

IED application

348

 Application manual

Page 355: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 355/457

Always be careful when connecting function blocks with a fastcycle time to function blocks with a slow cycle time.Remember to design the logic circuits carefully and always check the execution sequence for different functions. In other cases,additional time delays must be introduced into the logic schemes to

 prevent errors, for example, race between functions.

3.12.1.2 Setting parameters

Table 133: TIMER Non group settings (basic)

Name Values (Range) Unit Step Default Description

T 0.000 - 90000.000 s 0.001 0.000 Time delay of function

Table 134: PU LSE TIM ER Non group settings (basic)

Name Values (Range) Unit Step Default Description

T 0.000 - 90000.000 s 0.001 0.010 Time delay of function

Table 135: SRM EM ORY Group settings (basic)

Name Values (Range) Unit Step Default Description

Memory Off  On

- - On Operating mode of the memory function

Table 136: RSM EM ORY Group settings (basic)

Name Values (Range) Unit Step Default Description

Memory Off  On

- - On Operating mode of the memory function

Table 137: GATE Group settings (basic)

Name Values (Range) Unit Step Default Description

Operation Off  On

- - Off Operation Off/On

Table 138: TIMERSET Group settings (basic)

Name Values (Range) Unit Step Default Description

Operation Off  On

- - Off Operation Off/On

t 0.000 - 90000.000 s 0.001 0.000 Delay for settable timer n

1MRK 505 211-UEN C Section 3IED application

349

 Application manual

Page 356: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 356/457

3.12.2 Fixed signal function block FXDSIGN

Function description IEC 61850

identification

IEC 60617

identification

ANSI/IEEE C37.2

device number

Fixed signals FXDSIGN - -

3.12.2.1 Application

The Fixed signals function (FXDSIGN) generates a number of pre-set (fixed)signals that can be used in the configuration of an IED, either for forcing theunused inputs in other function blocks to a certain level/value, or for creatingcertain logic.

Example for use of GRP_OFF signal in FXDSIGN

The Restricted earth fault function REFPDIF can be used both for auto-transformers and normal transformers.

When used for auto-transformers, information from both windings parts, together with the neutral point current, needs to be available to the function. This means thatthree inputs are needed.

I3PW1CT1

I3PW2CT1

I3P

REFPDIF

IEC09000619_3_en.vsd

IEC09000619 V3 EN

Figure 140: REFPDIF function inputs for autotransformer application 

For normal transformers only one winding and the neutral point is available. Thismeans that only two inputs are used. Since all group connections are mandatory to

 be connected, the third input needs to be connected to something, which is theGRP_OFF signal in FXDSIGN function block.

Section 3 1MRK 505 211-UEN C

IED application

350

 Application manual

Page 357: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 357/457

I3PW1CT1

I3PW2CT1

I3P

REFPDIF

GRP_OFF

FXDSIGN

IEC09000620_3_en.vsd

IEC09000620 V3 EN

Figure 141: REFPDIF function inputs for normal transformer application 

3.12.2.2 Setting parameters

The function does not have any parameters available in Local HMI or Protectionand Control IED Manager (PCM 600)

3.12.3 Boolean 16 to Integer conversion B16I

Function description IEC 61850

identification

IEC 60617

identification

ANSI/IEEE C37.2

device number

Boolean 16 to integer conversion B16I - -

3.12.3.1 Application

Boolean 16 to integer conversion function B16I is used to transform a set of 16 binary (logical) signals into an integer. It can be used – for example, to connectlogical output signals from a function (like distance protection) to integer inputsfrom another function (like line differential protection). B16I does not have alogical node mapping.

3.12.3.2 Setting guidelines

The function does not have any parameters available in Local HMI or Protectionand Control IED Manager (PCM600).

3.12.4 Boolean 16 to Integer conversion with logic node

representation B16IFCVI

Function description IEC 61850

identification

IEC 60617

identification

ANSI/IEEE C37.2

device number

Boolean 16 to integer conversion withlogic node representation

B16IFCVI - -

1MRK 505 211-UEN C Section 3IED application

351

 Application manual

Page 358: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 358/457

3.12.4.1 Application

Boolean 16 to integer conversion with logic node representation functionB16IFCVI is used to transform a set of 16 binary (logical) signals into an integer.

B16IFCVI can receive an integer from a station computer – for example, over IEC61850–8–1. These functions are very useful when you want to generate logicalcommands (for selector switches or voltage controllers) by inputting an integer number. B16IFCVI has a logical node mapping in IEC 61850.

3.12.4.2 Setting guidelines

The function does not have any parameters available in the local HMI or Protectionand Control IED Manager (PCM600).

3.12.5 Integer to Boolean 16 conversion IB16

Function description IEC 61850

identification

IEC 60617

identification

ANSI/IEEE C37.2

device number

Integer to boolean 16 conversion IB16 - -

3.12.5.1 Application

Integer to boolean 16 conversion function (IB16) is used to transform an integer into a set of 16 binary (logical) signals. It can be used – for example, to connect

integer output signals from one function to binary (logical) inputs to another function. IB16 function does not have a logical node mapping.

3.12.5.2 Setting parameters

The function does not have any parameters available in the local HMI or Protectionand Control IED Manager (PCM600).

3.12.6 Integer to Boolean 16 conversion with logic node

representation IB16FCVB

Function description IEC 61850

identification

IEC 60617

identification

ANSI/IEEE C37.2

device number

Integer to boolean 16 conversion withlogic node representation

IB16FCVB - -

3.12.6.1 Application

Integer to boolean 16 conversion with logic node representation function(IB16FCVB) is used to transform an integer into a set of 16 binary (logical)

Section 3 1MRK 505 211-UEN C

IED application

352

 Application manual

Page 359: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 359/457

signals. IB16FCVB function can receive an integer from a station computer – for example, over IEC 61850–8–1. These functions are very useful when the user wants to generate logical commands (for selector switches or voltage controllers)

 by inputting an integer number. IB16FCVB function has a logical node mapping inIEC 61850.

3.12.6.2 Setting parameters

The function does not have any parameters available in the local HMI or Protectionand Control IED Manager (PCM600)

3.13 Monitoring

3.13.1 Measurement

Function description IEC 61850

identification

IEC 60617

identification

ANSI/IEEE C37.2

device number

Measurements CVMMXN

P, Q, S, I, U, f 

SYMBOL-RR V1 EN

-

Phase current measurement CMMXU

SYMBOL-SS V1 EN

-

Phase-phase voltage measurement VMMXU

SYMBOL-UU V1 EN

-

Current sequence componentmeasurement

CMSQI

I1, I2, I0 

SYMBOL-VV V1 EN

-

Voltage sequence measurement VMSQI

U1, U2, U0 

SYMBOL-TT V1 EN

-

Phase-neutral voltage measurement VNMMXU

SYMBOL-UU V1 EN

-

1MRK 505 211-UEN C Section 3IED application

353

 Application manual

Page 360: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 360/457

3.13.1.1 Application

Measurement functions is used for power system measurement, supervision andreporting to the local HMI, monitoring tool within PCM600 or to station level for 

example, via IEC 61850. The possibility to continuously monitor measured valuesof active power, reactive power, currents, voltages, frequency, power factor etc. isvital for efficient production, transmission and distribution of electrical energy. It

 provides to the system operator fast and easy overview of the present status of the power system. Additionally, it can be used during testing and commissioning of  protection and control IEDs in order to verify proper operation and connection of instrument transformers (CTs and VTs). During normal service by periodiccomparison of the measured value from the IED with other independent meters the

 proper operation of the IED analog measurement chain can be verified. Finally, itcan be used to verify proper direction orientation for distance or directionalovercurrent protection function.

The available measured values of an IED are depending on theactual hardware (TRM) and the logic configuration made in PCM600.

All measured values can be supervised with four settable limits that is, low-lowlimit, low limit, high limit and high-high limit. A zero clamping reduction is alsosupported, that is, the measured value below a settable limit is forced to zero whichreduces the impact of noise in the inputs.

Dead-band supervision can be used to report measured signal value to station levelwhen change in measured value is above set threshold limit or time integral of all

changes since the last time value updating exceeds the threshold limit. Measurevalue can also be based on periodic reporting.

The measurement function, CVMMXN, provides the following power systemquantities:

• P, Q and S: three phase active, reactive and apparent power • PF: power factor  • U: phase-to-phase voltage amplitude• I: phase current amplitude• F: power system frequency

Main menu/Measurement/Monitoring/Service values/CVMMXN

The measuring functions CMMXU, VNMMXU and VMMXU provide physicalquantities:

• I: phase currents (amplitude and angle) (CMMXU)• U: voltages (phase-to-earth and phase-to-phase voltage, amplitude and angle)

(VMMXU, VNMMXU)

Section 3 1MRK 505 211-UEN C

IED application

354

 Application manual

Page 361: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 361/457

It is possible to calibrate the measuring function above to get better then class 0.5 presentation. This is accomplished by angle and amplitude compensation at 5, 30and 100% of rated current and at 100% of rated voltage.

The power system quantities provided, depends on the actualhardware, (TRM) and the logic configuration made in PCM600.

The measuring functions CMSQI and VMSQI provide sequence componentquantities:

• I: sequence currents (positive, zero, negative sequence, amplitude and angle)• U: sequence voltages (positive, zero and negative sequence, amplitude and

angle).

The CVMMXN function calculates three-phase power quantities by usingfundamental frequency phasors (DFT values) of the measured current respectivelyvoltage signals. The measured power quantities are available either, asinstantaneously calculated quantities or, averaged values over a period of time (low

 pass filtered) depending on the selected settings.

3.13.1.2 Zero clamping

The measuring functions, CMMXU, VMMXU, VNMMXU and CVMMXN haveno interconnections regarding any setting or parameter.

Zero clampings are also entirely handled by the ZeroDb for each and every signalseparately for each of the functions. For example, the zero clamping of U12 ishandled by UL12ZeroDb in VMMXU, zero clamping of I1 is handled by

 IL1ZeroDb in CMMXU ETC.

Example how CVMMXN is operating:

The following outputs can be observed on the local HMI under Monitoring/

Servicevalues/SRV1

S Apparent three-phase power  

P Active three-phase power  

Q Reactive three-phase power  

PF Power factor  

ILAG I lagging U

ILEAD I leading U

U System mean voltage, calculated according to selected mode

I System mean current, calculated according to selected mode

F Frequency

1MRK 505 211-UEN C Section 3IED application

355

 Application manual

Page 362: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 362/457

The settings for this function is found under Setting/General setting/Monitoring/

Service values/SRV1

It can be seen that:

• When system voltage falls below UGenZeroDB, the shown value for S, P, Q,PF, ILAG, ILEAD, U and F on the local HMI is forced to zero

• When system current falls below IGenZeroDB, the shown value for S, P, Q,PF, ILAG, ILEAD, U and F on the local HMI is forced to zero

• When the value of a single signal falls below the set dead band for that specificsignal, the value shown on the local HMI is forced to zero. For example, if apparent three-phase power falls below SZeroDb the value for S on the localHMI is forced to zero.

3.13.1.3 Setting guidelines

The available setting parameters of the measurement function CVMMXN,CMMXU, VMMXU, CMSQI, VMSQI, VNMMXU are depending on the actualhardware (TRM) and the logic configuration made in PCM600.

The parameters for the Measurement functions CVMMXN, CMMXU, VMMXU,CMSQI, VMSQI, VNMMXU are set via the local HMI or PCM600.

Operation: Off /On. Every function instance (CVMMXN, CMMXU, VMMXU,CMSQI, VMSQI, VNMMXU) can be taken in operation (On) or out of operation(Off ).

The following general settings can be set for the Measurement function

(CVMMXN).

 PowAmpFact : Amplitude factor to scale power calculations.

 PowAngComp: Angle compensation for phase shift between measured I & U.

 Mode: Selection of measured current and voltage. There are 9 different ways of calculating monitored three-phase values depending on the available VT inputsconnected to the IED. See parameter group setting table.

k : Low pass filter coefficient for power measurement, U and I.

UGenZeroDb: Minimum level of voltage in % of UBase used as indication of zerovoltage (zero point clamping). If measured value is below UGenZeroDb calculatedS, P, Q and PF will be zero.

 IGenZeroDb: Minimum level of current in % of  IBase used as indication of zerocurrent (zero point clamping). If measured value is below IGenZeroDb calculatedS, P, Q and PF will be zero.

Section 3 1MRK 505 211-UEN C

IED application

356

 Application manual

Page 363: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 363/457

UBase: Base voltage in primary kV. This voltage is used as reference for voltagesetting. It can be suitable to set this parameter to the rated primary voltagesupervised object.

 IBase: Base current in primary A. This current is used as reference for currentsetting. It can be suitable to set this parameter to the rated primary current of thesupervised object.

SBase: Base setting for power values in MVA.

UAmpCompY : Amplitude compensation to calibrate voltage measurements at Y%of Ur, where Y is equal to 5, 30 or 100.

 IAmpCompY : Amplitude compensation to calibrate current measurements at Y% of Ir, where Y is equal to 5, 30 or 100.

 IAngCompY : Angle compensation to calibrate angle measurements at Y% of Ir,where Y is equal to 5, 30 or 100.

Parameters IBase, Ubase and SBase have been implemented as asettings instead of a parameters, which means that if the values of the parameters are changed there will be no restart of theapplication. As restart is required to activate new parametersvalues, the IED must be restarted in some way. Either manually or 

 by changing some other parameter at the same time.

The following general settings can be set for the Phase-phase current

measurement (CMMXU).

 IAmpCompY : Amplitude compensation to calibrate current measurements at Y% of Ir, where Y is equal to 5, 30 or 100.

 IAngCompY : Angle compensation to calibrate angle measurements at Y% of Ir,where Y is equal to 5, 30 or 100.

The following general settings can be set for the Phase-phase voltage

measurement (VMMXU).

UAmpCompY : Amplitude compensation to calibrate voltage measurements at Y%

of Ur, where Y is equal to 5, 30 or 100.UAngCompY : Angle compensation to calibrate angle measurements at Y% of Ur,where Y is equal to 5, 30 or 100.

The following general settings can be set for all monitored quantities included inthe functions (CVMMXN, CMMXU, VMMXU, CMSQI, VMSQI, VNMMXU) Xin setting names below equals S, P, Q, PF, U, I, F, IL1-3, UL1-3UL12-31, I1, I2,3I0, U1, U2 or 3U0.

 Xmin: Minimum value for analog signal X set directly in applicable measuring unit.

1MRK 505 211-UEN C Section 3IED application

357

 Application manual

Page 364: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 364/457

 Xmax: Maximum value for analog signal X.

 XZeroDb: Zero point clamping. A signal value less than XZeroDb is forced to zero.

Observe the related zero point clamping settings in Setting group N for CVMMXN(UGenZeroDb and IGenZeroDb). If measured value is below UGenZeroDb and/or  IGenZeroDb calculated S, P, Q and PF will be zero and these settings will override XZeroDb.

 XRepTyp: Reporting type. Cyclic (Cyclic), amplitude deadband ( Dead band ) or integral deadband ( Int deadband ). The reporting interval is controlled by the

 parameter  XDbRepInt .

 XDbRepInt : Reporting deadband setting. Cyclic reporting is the setting value and isreporting interval in seconds. Amplitude deadband is the setting value in % of measuring range. Integral deadband setting is the integral area, that is, measured

value in % of measuring range multiplied by the time between two measured values.

 XHiHiLim: High-high limit. Set in applicable measuring unit.

 XHiLim: High limit.

 XLowLim: Low limit.

 XLowLowLim: Low-low limit.

 XLimHyst : Hysteresis value in % of range and is common for all limits.

All phase angles are presented in relation to defined reference channel. The parameter  PhaseAngleRef defines the reference.

Calibration curves

It is possible to calibrate the functions (CVMMXN, CMMXU, VNMMXU andVMMXU) to get class 0.5 presentations of currents, voltages and powers. This isaccomplished by amplitude and angle compensation at 5, 30 and 100% of ratedcurrent and voltage. The compensation curve will have the characteristic for amplitude and angle compensation of currents as shown in figure 142 (example).The first phase will be used as reference channel and compared with the curve for calculation of factors. The factors will then be used for all related channels.

Section 3 1MRK 505 211-UEN C

IED application

358

 Application manual

Page 365: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 365/457

IEC05000652 V2 EN

Figure 142: Calibration curves 

Setting examplesThree setting examples, in connection to Measurement function (CVMMXN), are

 provided:

• Measurement function (CVMMXN) application for a 400 kV OHL• Measurement function (CVMMXN) application on the secondary side of a

transformer • Measurement function (CVMMXN) application for a generator 

For each of them detail explanation and final list of selected setting parametersvalues will be provided.

The available measured values of an IED are depending on theactual hardware (TRM) and the logic configuration made in PCM600.

Measurement function application for a 400 kV OHLSingle line diagram for this application is given in figure 143:

1MRK 505 211-UEN C Section 3IED application

359

 Application manual

Page 366: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 366/457

400kV Busbar 

400kV OHL

P Q

800/1 A

400 0,1/

3 3kV 

IEC09000039-1-en.vsd

IED

IEC09000039-1-EN V1 EN

Figure 143: Single line diagram for 400 kV OHL application 

In order to monitor, supervise and calibrate the active and reactive power asindicated in figure 143 it is necessary to do the following:

1. Set correctly CT and VT data and phase angle reference channel

 PhaseAngleRef using PCM600 for analog input channels2. Connect, in PCM600, measurement function to three- phase CT and VT inputs3. Set under General settings parameters for the Measurement function:

• general settings as shown in table 139.• level supervision of active power as shown in table 140.• calibration parameters as shown in table 141.

Tab le 139: General se tt ings pa ramete rs fo r the Measurement func tion

Setting Short Description Selected

value

Comments

Operation Operation Off/On On Function must be On 

PowAmpFact Amplitude factor to scale power calculations

1.000 It can be used duringcommissioning to achieve higher measurement accuracy.Typically no scaling is required

PowAngComp Angle compensation for phaseshift between measured I & U

0.0 It can be used duringcommissioning to achieve higher measurement accuracy.Typically no angle compensationis required. As well here requireddirection of P & Q measurementis towards protected object (asper IED internal default direction)

Table continues on next page

Section 3 1MRK 505 211-UEN C

IED application

360

 Application manual

Page 367: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 367/457

Setting Short Description Selected

value

Comments

Mode Selection of measured currentand voltage

L1, L2, L3 All three phase-to-earth VTinputs are available

k Low pass filter coefficient for  power measurement, U and I

0.00 Typically no additional filtering isrequired

UGenZeroDb Zero point clamping in % of Ubase

25 Set minimum voltage level to25%. Voltage below 25% willforce S, P and Q to zero.

IGenZeroDb Zero point clamping in % of Ibase 3 Set minimum current level to 3%.Current below 3% will force S, Pand Q to zero.

UBase Base setting for voltage level inkV

400.00 Set rated OHL phase-to-phasevoltage

IBase Base setting for current level in A 800 Set rated primary CT currentused for OHL

T ab le 140 : S etting s p aram ete rs fo r lev el su pe rvision

Setting Short Description Selected

value

Comments

PMin  Minimum value -750 Minimum expected load

PMax  Minimum value 750 Maximum expected load

PZeroDb  Zero point clamping in 0.001% of range

3000 Set zero point clamping to 45MW that is, 3% of 1500 MW

PRepTyp  Reporting type db Select amplitude deadbandsupervision

PDbRepInt  Cycl: Report interval (s), Db: In% of range, Int Db: In %s

2 Set ±Δdb=30 MW that is, 2%(larger changes than 30 MW willbe reported)

PHiHiLim  High High limit (physical value) 600 High alarm limit that is, extremeoverload alarm

PHiLim  High limit (physical value) 500 High warning limit that is,overload warning

PLowLim  Low limit (physical value) -800 Low warning limit. Not active

PLowLowlLim  Low Low limit (physical value) -800 Low alarm limit. Not active

PLimHyst  Hysteresis value in % of range(common for all limits)

2 Set ±Δ Hysteresis MW that is, 2%

Table 141: S ettings for calibration param eters

Setting Short Description Selected

value

Comments

IAmpComp5   Amplitude factor to calibratecurrent at 5% of Ir 

0.00

IAmpComp30   Amplitude factor to calibratecurrent at 30% of Ir 

0.00

IAmpComp100   Amplitude factor to calibratecurrent at 100% of Ir 

0.00

Table continues on next page

1MRK 505 211-UEN C Section 3IED application

361

 Application manual

Page 368: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 368/457

Setting Short Description Selected

value

Comments

UAmpComp5   Amplitude factor to calibratevoltage at 5% of Ur 

0.00

UAmpComp30   Amplitude factor to calibratevoltage at 30% of Ur 

0.00

UAmpComp100   Amplitude factor to calibratevoltage at 100% of Ur 

0.00

IAngComp5   Angle calibration for current at5% of Ir 

0.00

IAngComp30   Angle pre-calibration for currentat 30% of Ir 

0.00

IAngComp100   Angle pre-calibration for currentat 100% of Ir 

0.00

Measurement function application for a power transformer Single line diagram for this application is given in figure 144.

Section 3 1MRK 505 211-UEN C

IED application

362

 Application manual

Page 369: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 369/457

110kV Busbar 

200/1

35/0,1kV 

35kV Busbar 

500/5

P Q

31,5 MVA110/36,75/(10,5) kV

Yy0(d5)

UL1L2

IEC09000040-1-en.vsd

IED

IEC09000040-1-EN V1 EN

Figure 144: Single line diagram for transformer application 

In order to measure the active and reactive power as indicated in figure 144, it isnecessary to do the following:

1. Set correctly all CT and VT and phase angle reference channel PhaseAngleRef 

data using PCM600 for analog input channels2. Connect, in PCM600, measurement function to LV side CT & VT inputs3. Set the setting parameters for relevant Measurement function as shown in the

following table 142:

1MRK 505 211-UEN C Section 3IED application

363

 Application manual

Page 370: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 370/457

Tab le 142: General se tt ings pa ramete rs fo r the Measurement func tion

Setting Short description Selected

value

Comment

Operation  Operation Off /On On   Function must be On 

PowAmpFact   Amplitude factor to scale power calculations

1.000 Typically no scaling is required

PowAngComp   Angle compensation for phaseshift between measured I & U

180.0 Typically no angle compensationis required. However here therequired direction of P & Qmeasurement is towards busbar (Not per IED internal defaultdirection). Therefore anglecompensation have to be used inorder to get measurements inaliment with the requireddirection.

Mode  Selection of measured currentand voltage

L1L2 Only UL1L2 phase-to-phasevoltage is available

k Low pass filter coefficient for  power measurement, U and I

0.00 Typically no additional filtering isrequired

UGenZeroDb Zero point clamping in % of Ubase

25 Set minimum voltage level to 25%

IGenZeroDb Zero point clamping in % of Ibase 3 Set minimum current level to 3%

UBase Base setting for voltage level inkV

35.00 Set LV side rated phase-to-phase voltage

IBase Base setting for current level in A 495 Set transformer LV winding ratedcurrent

Measurement function application for a generator Single line diagram for this application is given in figure 145.

Section 3 1MRK 505 211-UEN C

IED application

364

 Application manual

Page 371: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 371/457

220kV Busbar 

300/1

15/0,1kV 

4000/5

100 MVA

242/15,65 kV

Yd5

UL1L2 , UL2L3

G

P Q

100MVA15,65kV

IEC09000041-1-en.vsd

IED

IEC09000041-1-EN V1 EN

Figure 145: Single line diagram for generator application 

In order to measure the active and reactive power as indicated in figure 145, it is

necessary to do the following:

1. Set correctly all CT and VT data and phase angle reference channel PhaseAngleRef using PCM600 for analog input channels

2. Connect, in PCM600, measurement function to the generator CT & VT inputs3. Set the setting parameters for relevant Measurement function as shown in the

following table:

1MRK 505 211-UEN C Section 3IED application

365

 Application manual

Page 372: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 372/457

Tab le 143: General se tt ings pa ramete rs fo r the Measurement func tion

Setting Short description Selected

value

Comment

Operation Operation Off/On On Function must be On 

PowAmpFact Amplitude factor to scale power calculations

1.000 Typically no scaling is required

PowAngComp Angle compensation for phaseshift between measured I & U

0.0 Typically no angle compensationis required. As well here requireddirection of P & Q measurementis towards protected object (asper IED internal default direction)

Mode Selection of measured currentand voltage

 Arone Generator VTs are connectedbetween phases (V-connected)

k Low pass filter coefficient for  power measurement, U and I

0.00 Typically no additional filtering isrequired

UGenZeroDb Zero point clamping in % of 

Ubase

25% Set minimum voltage level to 25%

IGenZeroDb Zero point clamping in % of Ibase 3 Set minimum current level to 3%

UBase Base setting for voltage level inkV

15,65 Set generator rated phase-to-phase voltage

IBase Base setting for current level in A 3690 Set generator rated current

3.13.1.4 Setting parameters

The available setting parameters of the measurement function (MMXU, MSQI) aredepending on the actual hardware (TRM) and the logic configuration made in

PCM600.

Table 144: CV MM XN Non group settings (basic)

Name Values (Range) Unit Step Default Description

SLowLim 0.0 - 2000.0 %SB 0.1 80.0 Low limit in % of SBase

SLowLowLim 0.0 - 2000.0 %SB 0.1 60.0 Low Low limit in % of SBase

SMin 0.0 - 2000.0 %SB 0.1 50.0 Minimum value in % of SBase

SMax 0.0 - 2000.0 %SB 0.1 200.0 Maximum value in % of SBase

SRepTyp CyclicDead bandInt deadband

- - Cyclic Reporting type

PMin -2000.0 - 2000.0 %SB 0.1 -200.0 Minimum value in % of SBase

PMax -2000.0 - 2000.0 %SB 0.1 200.0 Maximum value in % of SBase

PRepTyp CyclicDead bandInt deadband

- - Cyclic Reporting type

QMin -2000.0 - 2000.0 %SB 0.1 -200.0 Minimum value in % of SBase

QMax -2000.0 - 2000.0 %SB 0.1 200.0 Maximum value in % of SBase

QRepTyp CyclicDead bandInt deadband

- - Cyclic Reporting type

Table continues on next page

Section 3 1MRK 505 211-UEN C

IED application

366

 Application manual

Page 373: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 373/457

Name Values (Range) Unit Step Default Description

PFMin -1.000 - 1.000 - 0.001 -1.000 Minimum value

PFMax -1.000 - 1.000 - 0.001 1.000 Maximum value

PFRepTyp CyclicDead bandInt deadband

- - Cyclic Reporting type

UMin 0.0 - 200.0 %UB 0.1 50.0 Minimum value in % of UBase

UMax 0.0 - 200.0 %UB 0.1 200.0 Maximum value in % of UBase

URepTyp CyclicDead bandInt deadband

- - Cyclic Reporting type

IMin 0.0 - 500.0 %IB 0.1 50.0 Minimum value in % of IBase

IMax 0.0 - 500.0 %IB 0.1 200.0 Maximum value in % of IBase

IRepTyp CyclicDead band

Int deadband

- - Cyclic Reporting type

FrMin 0.000 - 100.000 Hz 0.001 0.000 Minimum value

FrMax 0.000 - 100.000 Hz 0.001 70.000 Maximum value

FrRepTyp CyclicDead bandInt deadband

- - Cyclic Reporting type

Operation Off  On

- - Off Operation Off / On

IBase 1 - 99999 A 1 3000 Base setting for current values in A

UBase 0.05 - 2000.00 kV 0.05 400.00 Base setting for voltage value in kV

SBase 0.05 - 200000.00 MVA 0.05 2080.00 Base setting for power values in MVA

Mode L1, L2, L3 AronePos SeqL1L2L2L3L3L1L1L2L3

- - L1, L2, L3 Selection of measured current andvoltage

PowAmpFact 0.000 - 6.000 - 0.001 1.000 Amplitude factor to scale power  calculations

PowAngComp -180.0 - 180.0 Deg 0.1 0.0 Angle compensation for phase shiftbetween measured I & U

k 0.000 - 1.000 - 0.001 0.000 Low pass filter coefficient for power  measurement, U and I

Table 145: C VM MX N N on group settings (advanced)

Name Values (Range) Unit Step Default Description

SDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of  range, Int Db: In %s

SZeroDb 0 - 100000 m% 1 500 Zero point clamping in 0,001% of range

SHiHiLim 0.0 - 2000.0 %SB 0.1 150.0 High High limit in % of SBase

Table continues on next page

1MRK 505 211-UEN C Section 3IED application

367

 Application manual

Page 374: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 374/457

Name Values (Range) Unit Step Default Description

SHiLim 0.0 - 2000.0 %SB 0.1 120.0 High limit in % of SBase

SLimHyst 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range (commonfor all limits)

PDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of  range, Int Db: In %s

PZeroDb 0 - 100000 m% 1 500 Zero point clamping in 0,001% of range

PHiHiLim -2000.0 - 2000.0 %SB 0.1 150.0 High High limit in % of SBase

PHiLim -2000.0 - 2000.0 %SB 0.1 120.0 High limit in % of SBase

PLowLim -2000.0 - 2000.0 %SB 0.1 -120.0 Low limit in % of SBase

PLowLowLim -2000.0 - 2000.0 %SB 0.1 -150.0 Low Low limit in % of SBase

PLimHyst 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range (commonfor all limits)

QDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of  range, Int Db: In %s

QZeroDb 0 - 100000 m% 1 500 Zero point clamping in 0,001% of range

QHiHiLim -2000.0 - 2000.0 %SB 0.1 150.0 High High limit in % of SBase

QHiLim -2000.0 - 2000.0 %SB 0.1 120.0 High limit in % of SBase

QLowLim -2000.0 - 2000.0 %SB 0.1 -120.0 Low limit in % of SBase

QLowLowLim -2000.0 - 2000.0 %SB 0.1 -150.0 Low Low limit in % of SBase

QLimHyst 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range (commonfor all limits)

PFDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of  range, Int Db: In %s

PFZeroDb 0 - 100000 m% 1 500 Zero point clamping in 0,001% of range

PFHiHiLim -1.000 - 1.000 - 0.001 1.000 High High limit (physical value)

PFHiLim -1.000 - 1.000 - 0.001 0.800 High limit (physical value)

PFLowLim -1.000 - 1.000 - 0.001 -0.800 Low limit (physical value)

PFLowLowLim -1.000 - 1.000 - 0.001 -1.000 Low Low limit (physical value)

PFLimHyst 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range (commonfor all limits)

UDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of  range, Int Db: In %s

UZeroDb 0 - 100000 m% 1 500 Zero point clamping in 0,001% of range

UHiHiLim 0.0 - 200.0 %UB 0.1 150.0 High High limit in % of UBase

UHiLim 0.0 - 200.0 %UB 0.1 120.0 High limit in % of UBase

ULowLim 0.0 - 200.0 %UB 0.1 80.0 Low limit in % of UBase

ULowLowLim 0.0 - 200.0 %UB 0.1 60.0 Low Low limit in % of UBase

ULimHyst 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range (commonfor all limits)

IDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of  range, Int Db: In %s

IZeroDb 0 - 100000 m% 1 500 Zero point clamping in 0,001% of range

IHiHiLim 0.0 - 500.0 %IB 0.1 150.0 High High limit in % of IBase

Table continues on next page

Section 3 1MRK 505 211-UEN C

IED application

368

 Application manual

Page 375: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 375/457

Name Values (Range) Unit Step Default Description

IHiLim 0.0 - 500.0 %IB 0.1 120.0 High limit in % of IBase

ILowLim 0.0 - 500.0 %IB 0.1 80.0 Low limit in % of IBase

ILowLowLim 0.0 - 500.0 %IB 0.1 60.0 Low Low limit in % of IBase

ILimHyst 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range (commonfor all limits)

FrDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of  range, Int Db: In %s

FrZeroDb 0 - 100000 m% 1 500 Zero point clamping in 0,001% of range

FrHiHiLim 0.000 - 100.000 Hz 0.001 65.000 High High limit (physical value)

FrHiLim 0.000 - 100.000 Hz 0.001 63.000 High limit (physical value)

FrLowLim 0.000 - 100.000 Hz 0.001 47.000 Low limit (physical value)

FrLowLowLim 0.000 - 100.000 Hz 0.001 45.000 Low Low limit (physical value)

FrLimHyst 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range (common

for all limits)

UGenZeroDb 1 - 100 %UB 1 5 Zero point clamping in % of Ubase

IGenZeroDb 1 - 100 %IB 1 5 Zero point clamping in % of Ibase

UAmpComp5 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate voltage at5% of Ur 

UAmpComp30 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate voltage at30% of Ur 

UAmpComp100 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate voltage at100% of Ur 

IAmpComp5 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate current at5% of Ir 

IAmpComp30 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate current at30% of Ir 

IAmpComp100 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate current at100% of Ir 

IAngComp5 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 5% of Ir  

IAngComp30 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 30% of Ir  

IAngComp100 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 100% of Ir  

Table 146: CMM XU Non group settings (basic)

Name Values (Range) Unit Step Default Description

IL1DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of  range, Int Db: In %s

Operation Off  On

- - Off Operation Mode On / Off  

IBase 1 - 99999 A 1 3000 Base setting for current level in A

IL1Max 0.000 -10000000000.000

 A 0.001 1000.000 Maximum value

IL1RepTyp CyclicDead bandInt deadband

- - Cyclic Reporting type

Table continues on next page

1MRK 505 211-UEN C Section 3IED application

369

 Application manual

Page 376: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 376/457

Name Values (Range) Unit Step Default Description

IL1AngDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of  range, Int Db: In %s

IL2DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of  

range, Int Db: In %s

IL2Max 0.000 -10000000000.000

 A 0.001 1000.000 Maximum value

IL2RepTyp CyclicDead bandInt deadband

- - Cyclic Reporting type

IL2AngDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of  range, Int Db: In %s

IL3DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of  range, Int Db: In %s

IL3Max 0.000 -10000000000.000

 A 0.001 1000.000 Maximum value

IL3RepTyp CyclicDead bandInt deadband

- - Cyclic Reporting type

IL3AngDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of  range, Int Db: In %s

Table 147: CM MX U N on group settings (advanced)

Name Values (Range) Unit Step Default Description

IL1ZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range

IL1HiHiLim 0.000 -10000000000.000

 A 0.001 900.000 High High limit (physical value)

IL1HiLim 0.000 -10000000000.000

 A 0.001 800.000 High limit (physical value)

IAmpComp5 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate current at5% of Ir 

IAmpComp30 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate current at30% of Ir 

IL1LowLim 0.000 -10000000000.000

 A 0.001 0.000 Low limit (physical value)

IL1LowLowLim 0.000 -10000000000.000

 A 0.001 0.000 Low Low limit (physical value)

IAmpComp100 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate current at

100% of Ir 

IAngComp5 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 5% of Ir  

IL1Min 0.000 -10000000000.000

 A 0.001 0.000 Minimum value

IAngComp30 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 30% of Ir  

IAngComp100 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 100% of Ir  

IL1LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and iscommon for all limits

IL2ZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range

Table continues on next page

Section 3 1MRK 505 211-UEN C

IED application

370

 Application manual

Page 377: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 377/457

Name Values (Range) Unit Step Default Description

IL2HiHiLim 0.000 -10000000000.000

 A 0.001 900.000 High High limit (physical value)

IL2HiLim 0.000 -

10000000000.000

 A 0.001 800.000 High limit (physical value)

IL2LowLim 0.000 -10000000000.000

 A 0.001 0.000 Low limit (physical value)

IL2LowLowLim 0.000 -10000000000.000

 A 0.001 0.000 Low Low limit (physical value)

IL2Min 0.000 -10000000000.000

 A 0.001 0.000 Minimum value

IL2LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and iscommon for all limits

IL3ZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range

IL3HiHiLim 0.000 -10000000000.000

 A 0.001 900.000 High High limit (physical value)

IL3HiLim 0.000 -10000000000.000

 A 0.001 800.000 High limit (physical value)

IL3LowLim 0.000 -10000000000.000

 A 0.001 0.000 Low limit (physical value)

IL3LowLowLim 0.000 -10000000000.000

 A 0.001 0.000 Low Low limit (physical value)

IL3Min 0.000 -10000000000.000

 A 0.001 0.000 Minimum value

IL3LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and iscommon for all limits

Table 148: VN MM XU N on group settings (basic)

Name Values (Range) Unit Step Default Description

UL1DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of  range, Int Db: In %s

Operation Off  On

- - Off Operation Mode On / Off  

UBase 0.05 - 2000.00 kV 0.05 400.00 Base setting for voltage level in kV

UL1Max 0.000 -10000000000.000

V 0.001 300000.000 Maximum value

UL1RepTyp CyclicDead bandInt deadband

- - Cyclic Reporting type

UL1LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and iscommon for all limits

UL1AnDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of  range, Int Db: In %s

UL2DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of  range, Int Db: In %s

UL2Max 0.000 -10000000000.000

V 0.001 300000.000 Maximum value

Table continues on next page

1MRK 505 211-UEN C Section 3IED application

371

 Application manual

Page 378: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 378/457

Name Values (Range) Unit Step Default Description

UL2RepTyp CyclicDead bandInt deadband

- - Cyclic Reporting type

UL2LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and iscommon for all limits

UL2AnDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of  range, Int Db: In %s

UL3DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of  range, Int Db: In %s

UL3Max 0.000 -10000000000.000

V 0.001 300000.000 Maximum value

UL3RepTyp CyclicDead bandInt deadband

- - Cyclic Reporting type

UL3LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is

common for all limitsUL3AnDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of  

range, Int Db: In %s

Table 149: VN MM XU Non group settings (advanced)

Name Values (Range) Unit Step Default Description

UL1ZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range

UL1HiHiLim 0.000 -10000000000.000

V 0.001 260000.000 High High limit (physical value)

UL1HiLim 0.000 -10000000000.000

V 0.001 240000.000 High limit (physical value)

UL1LowLim 0.000 -10000000000.000

V 0.001 220000.000 Low limit (physical value)

UL1LowLowLim 0.000 -10000000000.000

V 0.001 200000.000 Low Low limit (physical value)

UAmpComp100 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate voltage at100% of Ur 

UL1Min 0.000 -10000000000.000

V 0.001 0.000 Minimum value

UL2ZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range

UL2HiHiLim 0.000 -10000000000.000

V 0.001 260000.000 High High limit (physical value)

UL2HiLim 0.000 -10000000000.000

V 0.001 240000.000 High limit (physical value)

UL2LowLim 0.000 -10000000000.000

V 0.001 220000.000 Low limit (physical value)

UL2LowLowLim 0.000 -10000000000.000

V 0.001 200000.000 Low Low limit (physical value)

UL2Min 0.000 -10000000000.000

V 0.001 0.000 Minimum value

UL3ZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range

Table continues on next page

Section 3 1MRK 505 211-UEN C

IED application

372

 Application manual

Page 379: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 379/457

Name Values (Range) Unit Step Default Description

UL3HiHiLim 0.000 -10000000000.000

V 0.001 260000.000 High High limit (physical value)

UL3HiLim 0.000 -

10000000000.000

V 0.001 240000.000 High limit (physical value)

UL3LowLim 0.000 -10000000000.000

V 0.001 220000.000 Low limit (physical value)

UL3LowLowLim 0.000 -10000000000.000

V 0.001 200000.000 Low Low limit (physical value)

UL3Min 0.000 -10000000000.000

V 0.001 0.000 Minimum value

Table 150: VM MXU Non group settings (basic)

Name Values (Range) Unit Step Default Description

UL12DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of  range, Int Db: In %s

Operation Off  On

- - Off Operation Mode On / Off  

UBase 0.05 - 2000.00 kV 0.05 400.00 Base setting for voltage level in kV

UL12Max 0.000 -10000000000.000

V 0.001 500000.000 Maximum value

UL12RepTyp CyclicDead bandInt deadband

- - Cyclic Reporting type

UL12AnDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of  range, Int Db: In %s

UL23DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of  range, Int Db: In %s

UL23Max 0.000 -10000000000.000

V 0.001 500000.000 Maximum value

UL23RepTyp CyclicDead bandInt deadband

- - Cyclic Reporting type

UL23AnDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of  range, Int Db: In %s

UL31DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of  range, Int Db: In %s

UL31Max 0.000 -

10000000000.000

V 0.001 500000.000 Maximum value

UL31RepTyp CyclicDead bandInt deadband

- - Cyclic Reporting type

UL31AnDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of  range, Int Db: In %s

1MRK 505 211-UEN C Section 3IED application

373

 Application manual

Page 380: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 380/457

Table 151: VM MXU Non group settings (advanced)

Name Values (Range) Unit Step Default Description

UL12ZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range

UL12HiHiLim 0.000 -10000000000.000 V 0.001 450000.000 High High limit (physical value)

UL12HiLim 0.000 -10000000000.000

V 0.001 420000.000 High limit (physical value)

UL12LowLim 0.000 -10000000000.000

V 0.001 380000.000 Low limit (physical value)

UL12LowLowLim 0.000 -10000000000.000

V 0.001 350000.000 Low Low limit (physical value)

UAmpComp100 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate voltage at100% of Ur 

UL12Min 0.000 -10000000000.000

V 0.001 0.000 Minimum value

UL12LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and iscommon for all limits

UL23ZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range

UL23HiHiLim 0.000 -10000000000.000

V 0.001 450000.000 High High limit (physical value)

UL23HiLim 0.000 -10000000000.000

V 0.001 420000.000 High limit (physical value)

UL23LowLim 0.000 -10000000000.000

V 0.001 380000.000 Low limit (physical value)

UL23LowLowLim 0.000 -10000000000.000

V 0.001 350000.000 Low Low limit (physical value)

UL23Min 0.000 -10000000000.000

V 0.001 0.000 Minimum value

UL23LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and iscommon for all limits

UL31ZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range

UL31HiHiLim 0.000 -10000000000.000

V 0.001 450000.000 High High limit (physical value)

UL31HiLim 0.000 -10000000000.000

V 0.001 420000.000 High limit (physical value)

UL31LowLim 0.000 -10000000000.000

V 0.001 380000.000 Low limit (physical value)

UL31LowLowLim 0.000 -

10000000000.000

V 0.001 350000.000 Low Low limit (physical value)

UL31Min 0.000 -10000000000.000

V 0.001 0.000 Minimum value

UL31LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and iscommon for all limits

Section 3 1MRK 505 211-UEN C

IED application

374

 Application manual

Page 381: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 381/457

Table 152: CMSQI Non group settings (basic)

Name Values (Range) Unit Step Default Description

3I0DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of  range, Int Db: In %s

3I0Min 0.000 -10000000000.000

 A 0.001 0.000 Minimum value

3I0Max 0.000 -10000000000.000

 A 0.001 1000.000 Maximum value

3I0RepTyp CyclicDead bandInt deadband

- - Cyclic Reporting type

3I0LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and iscommon for all limits

3I0AngDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of  range, Int Db: In %s

Operation Off  On

- - Off Operation Mode On / Off  

3I0AngMin -180.000 - 180.000 Deg 0.001 -180.000 Minimum value

3I0AngMax -180.000 - 180.000 Deg 0.001 180.000 Maximum value

3I0AngRepTyp CyclicDead bandInt deadband

- - Cyclic Reporting type

I1DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of  range, Int Db: In %s

I1Min 0.000 -10000000000.000

 A 0.001 0.000 Minimum value

I1Max 0.000 -

10000000000.000

 A 0.001 1000.000 Maximum value

I1RepTyp CyclicDead bandInt deadband

- - Cyclic Reporting type

I1AngDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of  range, Int Db: In %s

I1AngMax -180.000 - 180.000 Deg 0.001 180.000 Maximum value

I1AngRepTyp CyclicDead bandInt deadband

- - Cyclic Reporting type

I2DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of  range, Int Db: In %s

I2Min 0.000 -10000000000.000

 A 0.001 0.000 Minimum value

I2Max 0.000 -10000000000.000

 A 0.001 1000.000 Maximum value

I2RepTyp CyclicDead bandInt deadband

- - Cyclic Reporting type

I2LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and iscommon for all limits

Table continues on next page

1MRK 505 211-UEN C Section 3IED application

375

 Application manual

Page 382: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 382/457

Name Values (Range) Unit Step Default Description

I2AngDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of  range, Int Db: In %s

I2AngMin -180.000 - 180.000 Deg 0.001 -180.000 Minimum value

I2AngRepTyp CyclicDead bandInt deadband

- - Cyclic Reporting type

Table 153: CM SQ I N on group settings (advanced)

Name Values (Range) Unit Step Default Description

3I0ZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range

3I0HiHiLim 0.000 -10000000000.000

 A 0.001 900.000 High High limit (physical value)

3I0HiLim 0.000 -

10000000000.000

 A 0.001 800.000 High limit (physical value)

3I0LowLim 0.000 -10000000000.000

 A 0.001 0.000 Low limit (physical value)

3I0LowLowLim 0.000 -10000000000.000

 A 0.001 0.000 Low Low limit (physical value)

3I0AngZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range

I1ZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range

I1HiHiLim 0.000 -10000000000.000

 A 0.001 900.000 High High limit (physical value)

I1HiLim 0.000 -10000000000.000

 A 0.001 800.000 High limit (physical value)

I1LowLim 0.000 -10000000000.000

 A 0.001 0.000 Low limit (physical value)

I1LowLowLim 0.000 -10000000000.000

 A 0.001 0.000 Low Low limit (physical value)

I1LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and iscommon for all limits

I1AngZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range

I1AngMin -180.000 - 180.000 Deg 0.001 -180.000 Minimum value

I2ZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range

I2HiHiLim 0.000 -10000000000.000

 A 0.001 900.000 High High limit (physical value)

I2HiLim 0.000 -10000000000.000

 A 0.001 800.000 High limit (physical value)

I2LowLim 0.000 -10000000000.000

 A 0.001 0.000 Low limit (physical value)

I2LowLowLim 0.000 -10000000000.000

 A 0.001 0.000 Low Low limit (physical value)

I2AngZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range

I2AngMax -180.000 - 180.000 Deg 0.001 180.000 Maximum value

Section 3 1MRK 505 211-UEN C

IED application

376

 Application manual

Page 383: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 383/457

Table 154: VM SQI Non group settings (basic)

Name Values (Range) Unit Step Default Description

3U0DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of  range, Int Db: In %s

3U0Min 0.000 -10000000000.000

V 0.001 0.000 Minimum value

3U0Max 0.000 -10000000000.000

V 0.001 300000.000 Maximum value

3U0RepTyp CyclicDead bandInt deadband

- - Cyclic Reporting type

3U0LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and iscommon for all limits

3U0AngDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of  range, Int Db: In %s

Operation Off  On

- - Off Operation Mode On / Off  

3U0AngZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range

3U0AngMin -180.000 - 180.000 Deg 0.001 -180.000 Minimum value

3U0AngMax -180.000 - 180.000 Deg 0.001 180.000 Maximum value

3U0AngRepTyp CyclicDead bandInt deadband

- - Cyclic Reporting type

U1DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of  range, Int Db: In %s

U1Min 0.000 -10000000000.000

V 0.001 0.000 Minimum value

U1Max 0.000 -10000000000.000

V 0.001 300000.000 Maximum value

U1RepTyp CyclicDead bandInt deadband

- - Cyclic Reporting type

U1LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and iscommon for all limits

U1AngDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of  range, Int Db: In %s

U2DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of  range, Int Db: In %s

U2Min 0.000 -

10000000000.000

V 0.001 0.000 Minimum value

U2Max 0.000 -10000000000.000

V 0.001 300000.000 Maximum value

U2RepTyp CyclicDead bandInt deadband

- - Cyclic Reporting type

U2LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and iscommon for all limits

U2AngDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of  range, Int Db: In %s

U2AngMin -180.000 - 180.000 Deg 0.001 -180.000 Minimum value

Table continues on next page

1MRK 505 211-UEN C Section 3IED application

377

 Application manual

Page 384: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 384/457

Name Values (Range) Unit Step Default Description

U2AngMax -180.000 - 180.000 Deg 0.001 180.000 Maximum value

U2AngRepTyp CyclicDead band

Int deadband

- - Cyclic Reporting type

UAmpPreComp5 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to pre-calibrate voltageat 5% of Ir 

UAmpPreComp30 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to pre-calibrate voltageat 30% of Ir 

UAmpPreComp100 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to pre-calibrate voltageat 100% of Ir 

Table 155: VM SQ I Non group settings (advanced)

Name Values (Range) Unit Step Default Description

3U0ZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range

3U0HiHiLim 0.000 -10000000000.000

V 0.001 260000.000 High High limit (physical value)

3U0HiLim 0.000 -10000000000.000

V 0.001 240000.000 High limit (physical value)

3U0LowLim 0.000 -10000000000.000

V 0.001 220000.000 Low limit (physical value)

3U0LowLowLim 0.000 -10000000000.000

V 0.001 200000.000 Low Low limit (physical value)

U1ZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range

U1HiHiLim 0.000 -10000000000.000

V 0.001 260000.000 High High limit (physical value)

U1HiLim 0.000 -10000000000.000

V 0.001 240000.000 High limit (physical value)

U1LowLim 0.000 -10000000000.000

V 0.001 220000.000 Low limit (physical value)

U1LowLowLim 0.000 -10000000000.000

V 0.001 200000.000 Low Low limit (physical value)

U1AngZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range

U1AngMin -180.000 - 180.000 Deg 0.001 -180.000 Minimum value

U1AngMax -180.000 - 180.000 Deg 0.001 180.000 Maximum value

U1AngRepTyp CyclicDead band

Int deadband

- - Cyclic Reporting type

U2ZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range

U2HiHiLim 0.000 -10000000000.000

V 0.001 260000.000 High High limit (physical value)

U2HiLim 0.000 -10000000000.000

V 0.001 240000.000 High limit (physical value)

U2LowLim 0.000 -10000000000.000

V 0.001 220000.000 Low limit (physical value)

U2LowLowLim 0.000 -10000000000.000

V 0.001 200000.000 Low Low limit (physical value)

U2AngZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range

Section 3 1MRK 505 211-UEN C

IED application

378

 Application manual

Page 385: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 385/457

3.13.2 Event counter CNTGGIO

3.13.2.1 Identification

Function description IEC 61850

identification

IEC 60617

identification

ANSI/IEEE C37.2

device number

Event counter CNTGGIO

S00946 V1 EN

-

3.13.2.2 Application

Event counter (CNTGGIO) has six counters which are used for storing the number of times each counter has been activated. CNTGGIO can be used to count how

many times a specific function, for example the tripping logic, has issued a tripsignal. All six counters have a common blocking and resetting feature.

3.13.2.3 Setting parameters

The function does not have any parameters available in Local HMI or Protectionand Control IED Manager (PCM600)

3.13.3 Event function EVENT

Function description IEC 61850

identification

IEC 60617

identification

ANSI/IEEE C37.2

device number

Event function EVENT

S00946 V1 EN

-

3.13.3.1 Introduction

When using a Substation Automation system with LON or SPA communication,time-tagged events can be sent at change or cyclically from the IED to the stationlevel. These events are created from any available signal in the IED that is

connected to the Event function (EVENT). The event function block is used for LON and SPA communication.

Analog and double indication values are also transferred through EVENT function.

3.13.3.2 Setting guidelines

The parameters for the Event (EVENT) function are set via the local HMI or PCM600.

EventMask (Ch_1 - 16)The inputs can be set individually as:

1MRK 505 211-UEN C Section 3IED application

379

 Application manual

Page 386: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 386/457

• NoEvents

• OnSet , at pick-up of the signal• OnReset , at drop-out of the signal• OnChange, at both pick-up and drop-out of the signal• AutoDetect 

LONChannelMask or SPAChannelMask Definition of which part of the event function block that shall generate events:

• Off 

• Channel 1-8

• Channel 9-16 

• Channel 1-16 

MinRepIntVal (1 - 16)A time interval between cyclic events can be set individually for each inputchannel. This can be set between 0.0 s to 1000.0 s in steps of 0.1 s. It shouldnormally be set to 0, that is, no cyclic communication.

It is important to set the time interval for cyclic events in anoptimized way to minimize the load on the station bus.

3.13.3.3 Setting parameters

Table 156: EVENT Non group settings (basic)

Name Values (Range) Unit Step Default Description

SPAChannelMask Off  Channel 1-8Channel 9-16Channel 1-16

- - Off SPA channel mask

LONChannelMask Off  Channel 1-8Channel 9-16Channel 1-16

- - Off LON channel mask

EventMask1 NoEventsOnSetOnResetOnChange

 AutoDetect

- - AutoDetect Reporting criteria for input 1

EventMask2 NoEventsOnSetOnResetOnChange

 AutoDetect

- - AutoDetect Reporting criteria for input 2

EventMask3 NoEventsOnSetOnResetOnChange

 AutoDetect

- - AutoDetect Reporting criteria for input 3

Table continues on next page

Section 3 1MRK 505 211-UEN C

IED application

380

 Application manual

Page 387: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 387/457

Name Values (Range) Unit Step Default Description

EventMask4 NoEventsOnSetOnResetOnChange

 AutoDetect

- - AutoDetect Reporting criteria for input 4

EventMask5 NoEventsOnSetOnResetOnChange

 AutoDetect

- - AutoDetect Reporting criteria for input 5

EventMask6 NoEventsOnSetOnResetOnChange

 AutoDetect

- - AutoDetect Reporting criteria for input 6

EventMask7 NoEventsOnSet

OnResetOnChange AutoDetect

- - AutoDetect Reporting criteria for input 7

EventMask8 NoEventsOnSetOnResetOnChange

 AutoDetect

- - AutoDetect Reporting criteria for input 8

EventMask9 NoEventsOnSetOnResetOnChange

 AutoDetect

- - AutoDetect Reporting criteria for input 9

EventMask10 NoEvents

OnSetOnResetOnChange

 AutoDetect

- - AutoDetect Reporting criteria for input 10

EventMask11 NoEventsOnSetOnResetOnChange

 AutoDetect

- - AutoDetect Reporting criteria for input 11

EventMask12 NoEventsOnSetOnResetOnChange

 AutoDetect

- - AutoDetect Reporting criteria for input 12

EventMask13 NoEventsOnSetOnResetOnChange

 AutoDetect

- - AutoDetect Reporting criteria for input 13

EventMask14 NoEventsOnSetOnResetOnChange

 AutoDetect

- - AutoDetect Reporting criteria for input 14

Table continues on next page

1MRK 505 211-UEN C Section 3IED application

381

 Application manual

Page 388: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 388/457

Name Values (Range) Unit Step Default Description

EventMask15 NoEventsOnSetOnResetOnChange

 AutoDetect

- - AutoDetect Reporting criteria for input 15

EventMask16 NoEventsOnSetOnResetOnChange

 AutoDetect

- - AutoDetect Reporting criteria for input 16

MinRepIntVal1 0 - 3600 s 1 2 Minimum reporting interval input 1

MinRepIntVal2 0 - 3600 s 1 2 Minimum reporting interval input 2

MinRepIntVal3 0 - 3600 s 1 2 Minimum reporting interval input 3

MinRepIntVal4 0 - 3600 s 1 2 Minimum reporting interval input 4

MinRepIntVal5 0 - 3600 s 1 2 Minimum reporting interval input 5

MinRepIntVal6 0 - 3600 s 1 2 Minimum reporting interval input 6

MinRepIntVal7 0 - 3600 s 1 2 Minimum reporting interval input 7

MinRepIntVal8 0 - 3600 s 1 2 Minimum reporting interval input 8

MinRepIntVal9 0 - 3600 s 1 2 Minimum reporting interval input 9

MinRepIntVal10 0 - 3600 s 1 2 Minimum reporting interval input 10

MinRepIntVal11 0 - 3600 s 1 2 Minimum reporting interval input 11

MinRepIntVal12 0 - 3600 s 1 2 Minimum reporting interval input 12

MinRepIntVal13 0 - 3600 s 1 2 Minimum reporting interval input 13

MinRepIntVal14 0 - 3600 s 1 2 Minimum reporting interval input 14

MinRepIntVal15 0 - 3600 s 1 2 Minimum reporting interval input 15

MinRepIntVal16 0 - 3600 s 1 2 Minimum reporting interval input 16

3.13.4 Logical signal status report BINSTATREP

Function description IEC 61850

identification

IEC 60617

identification

ANSI/IEEE C37.2

device number

Logical signal status report BINSTATREP - -

3.13.4.1 Application

The Logical signal status report (BINSTATREP) function makes it possible for aSPA master to poll signals from various other function blocks.

BINSTATREP has 16 inputs and 16 outputs. The output status follows the inputsand can be read from the local HMI or via SPA communication.

When an input is set, the respective output is set for a user defined time. If theinput signal remains set for a longer period, the output will remain set until theinput signal resets.

Section 3 1MRK 505 211-UEN C

IED application

382

 Application manual

Page 389: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 389/457

t t

INPUTn

OUTPUTn

IEC09000732-1-en.vsd

IEC09000732 V1 EN

Figure 146: BINSTATREP logical diagram 

3.13.4.2 Setting guidelines

The pulse time t is the only setting for the Logical signal status report

(BINSTATREP). Each output can be set or reset individually, but the pulse timewill be the same for all outputs in the entire BINSTATREP function.

3.13.4.3 Setting parameters

Table 157: BIN STA TR EP Non group settings (basic)

Name Values (Range) Unit Step Default Description

t 0.000 - 60000.000 s 0.001 10.000 Time delay of function

3.13.5 Measured value expander block RANGE_XP

Function description IEC 61850

identification

IEC 60617

identification

ANSI/IEEE C37.2

device number

Measured value expander block RANGE_XP - -

3.13.5.1 Application

The current and voltage measurements functions (CVMMXN, CMMXU, VMMXUand VNMMXU), current and voltage sequence measurement functions (CMSQIand VMSQI) and IEC 61850 generic communication I/O functions (MVGGIO) are

 provided with measurement supervision functionality. All measured values can besupervised with four settable limits, that is low-low limit, low limit, high limit andhigh-high limit. The measure value expander block ( RANGE_XP) has beenintroduced to be able to translate the integer output signal from the measuringfunctions to 5 binary signals, that is below low-low limit, below low limit, normal,above high-high limit or above high limit. The output signals can be used asconditions in the configurable logic.

1MRK 505 211-UEN C Section 3IED application

383

 Application manual

Page 390: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 390/457

3.13.5.2 Setting guidelines

There are no settable parameters for the measured value expander block function.

3.13.6 Disturbance report DRPRDRE

Function description IEC 61850

identification

IEC 60617

identification

ANSI/IEEE C37.2

device number

 Analog input signals A41RADR - -

Disturbance report DRPRDRE - -

Disturbance report A1RADR - -

Disturbance report A4RADR - -

Disturbance report B1RBDR - -

3.13.6.1 Application

To get fast, complete and reliable information about disturbances in the primary and/or in the secondary system it is very important to gather information on faultcurrents, voltages and events. It is also important having a continuous event-logging to be able to monitor in an overview perspective. These tasks areaccomplished by the disturbance report function DRPRDRE and facilitate a better understanding of the power system behavior and related primary and secondaryequipment during and after a disturbance. An analysis of the recorded data

 provides valuable information that can be used to explain a disturbance, basis for change of IED setting plan, improve existing equipment, and so on. Thisinformation can also be used in a longer perspective when planning for anddesigning new installations, that is, a disturbance recording could be a part of Functional Analysis (FA).

Disturbance report DRPRDRE, always included in the IED, acquires sampled dataof all selected analog and binary signals connected to the function blocks that is,

• maximum 30 external analog signals,• 10 internal derived analog signals, and• 96 binary signals.

Disturbance report function is a common name for several functions that is,Indications (IND), Event recorder (ER), Event list (EL), Trip value recorder (TVR), Disturbance recorder (DR).

Disturbance report function is characterized by great flexibility as far asconfiguration, starting conditions, recording times, and large storage capacity areconcerned. Thus, disturbance report is not dependent on the operation of protectivefunctions, and it can record disturbances that were not discovered by protectivefunctions for one reason or another. Disturbance report can be used as an advancedstand-alone disturbance recorder.

Section 3 1MRK 505 211-UEN C

IED application

384

 Application manual

Page 391: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 391/457

Every disturbance report recording is saved in the IED. The same applies to allevents, which are continuously saved in a ring-buffer. Local HMI can be used toget information about the recordings, and the disturbance report files may beuploaded in the PCM600 using the Disturbance handling tool, for report reading or further analysis (using WaveWin, that can be found on the PCM600 installationCD). The user can also upload disturbance report files using FTP or MMS (over 61850–8–1) clients.

If the IED is connected to a station bus (IEC 61850-8-1), the disturbance recorder (record made and fault number) and the fault locator information are available asGOOSE or Report Control data. The same information is obtainable if IEC60870-5-103 is used.

3.13.6.2 Setting guidelines

The setting parameters for the Disturbance report function DRPRDRE are set viathe local HMI or PCM600.

It is possible to handle up to 40 analog and 96 binary signals, either internal signalsor signals coming from external inputs. The binary signals are identical in allfunctions that is, Disturbance recorder (DR), Event recorder (ER), Indication(IND), Trip value recorder (TVR) and Event list (EL) function.

User-defined names of binary and analog input signals is set using PCM600. Theanalog and binary signals appear with their user-defined names. The name is usedin all related functions (Disturbance recorder (DR), Event recorder (ER), Indication(IND), Trip value recorder (TVR) and Event list (EL)).

Figure 147 shows the relations between Disturbance report, included functions andfunction blocks. Event list (EL), Event recorder (ER) and Indication (IND) usesinformation from the binary input function blocks (BxRBDR). Trip value recorder (TVR) uses analog information from the analog input function blocks (AxRADR),.Disturbance report function acquires information from both AxRADR and BxRBDR.

Figure 147: Disturbance report functions and related function blocks 

For Disturbance report function there are a number of settings which alsoinfluences the sub-functions.

Three LED indications placed above the LCD screen makes it possible to get quick status information about the IED.

Green LED:

Steady light In Service

Flashing light Internal failure

Dark No power supply

 

Yellow LED:

Steady light A Disturbance Report is triggered

Table continues on next page

1MRK 505 211-UEN C Section 3IED application

385

 Application manual

Page 392: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 392/457

Flashing light The IED is in test mode

 

Red LED:

Steady light Triggered on binary signal N with SetLEDN = On 

OperationThe operation of Disturbance report function DRPRDRE has to be set On or Off . If Off is selected, note that no disturbance report is registered, and none sub-functionwill operate (the only general parameter that influences Event list (EL)).

Operation = Off :

• Disturbance reports are not stored.• LED information (yellow - start, red - trip) is not stored or changed.

Operation = On:

• Disturbance reports are stored, disturbance data can be read from the localHMI and from a PC using PCM600.

• LED information (yellow - start, red - trip) is stored.

Every recording will get a number (0 to 999) which is used as identifier (localHMI, disturbance handling tool and IEC 61850). An alternative recordingidentification is date, time and sequence number. The sequence number isautomatically increased by one for each new recording and is reset to zero atmidnight. The maximum number of recordings stored in the IED is 100. The oldestrecording will be overwritten when a new recording arrives (FIFO).

To be able to delete disturbance records, Operation parameter hasto be On.

The maximum number of recordings depend on each recordingstotal recording time. Long recording time will reduce the number of recordings to less than 100.

The IED flash disk should NOT be used to store any user files. Thismight cause disturbance recordings to be deleted due to lack of disk space.

Section 3 1MRK 505 211-UEN C

IED application

386

 Application manual

Page 393: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 393/457

Recording timesThe different recording times for Disturbance report are set (the pre-fault time, post-fault time, and limit time). These recording times affect all sub-functions more or less but not the Event list (EL) function.

Prefault recording time ( PreFaultRecT ) is the recording time before the starting point of the disturbance. The setting should be at least 0.1 s to ensure enoughsamples for the estimation of pre-fault values in the Trip value recorder (TVR)function.

Postfault recording time ( PostFaultRecT ) is the maximum recording time after thedisappearance of the trig-signal (does not influence the Trip value recorder (TVR)function).

Recording time limit (TimeLimit ) is the maximum recording time after trig. The parameter limits the recording time if some trigging condition (fault-time) is verylong or permanently set (does not influence the Trip value recorder (TVR) function).

Post retrigger ( PostRetrig ) can be set to On or Off . Makes it possible to choose performance of Disturbance report function if a new trig signal appears in the post-fault window.

 PostRetrig = Off 

The function is insensitive for new trig signals during post fault time.

 PostRetrig = On

The function completes current report and starts a new complete report that is, thelatter will include:

• new pre-fault- and fault-time (which will overlap previous report)• events and indications might be saved in the previous report too, due to overlap• new trip value calculations if installed, in operation and started

Operation in test modeIf the IED is in test mode and OpModeTest = Off . Disturbance report function doesnot save any recordings and no LED information is displayed.

If the IED is in test mode and OpModeTest = On. Disturbance report functionworks in normal mode and the status is indicated in the saved recording.

Binary input signalsUp to 96 binary signals can be selected among internal logical and binary inputsignals. The configuration tool is used to configure the signals.

For each of the 96 signals, it is also possible to select if the signal is to be used as atrigger for the start of the Disturbance report and if the trigger should be activatedon positive (1) or negative (0) slope.

OperationN : Disturbance report may trig for binary input N (On) or not (Off ).

1MRK 505 211-UEN C Section 3IED application

387

 Application manual

Page 394: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 394/457

TrigLevelN : Trig on positive (Trig on 1) or negative (Trig on 0) slope for binaryinput N.

 Func103N : Function type number (0-255) for binary input N according to

IEC-60870-5-103, that is, 128: Distance protection, 160: overcurrent protection,176: transformer differential protection and 192: line differential protection.

 Info103N : Information number (0-255) for binary input N according toIEC-60870-5-103, that is, 69-71: Trip L1-L3, 78-83: Zone 1-6.

See also description in the chapter IEC 60870-5-103.

Analog input signalsUp to 40 analog signals can be selected among internal analog and analog inputsignals. PCM600 is used to configure the signals.

For retrieving remote data from LDCM module, the Disturbancereport function should not be connected to a 3 ms SMAI function

 block if this is the only intended use for the remote data.

The analog trigger of Disturbance report is not affected if analog input M is to beincluded in the disturbance recording or not (OperationM = On/Off ).

If OperationM = Off , no waveform (samples) will be recorded and reported ingraph. However, Trip value, pre-fault and fault value will be recorded and reported.The input channel can still be used to trig the disturbance recorder.

If OperationM = On, waveform (samples) will also be recorded and reported in graph.

 NomValueM : Nominal value for input M.

OverTrigOpM , UnderTrigOpM : Over or Under trig operation, Disturbance reportmay trig for high/low level of analog input M (On) or not (Off ).

OverTrigLeM , UnderTrigLeM : Over or under trig level, Trig high/low levelrelative nominal value for analog input M in percent of nominal value.

Sub-function parametersAll functions are in operation as long as Disturbance report is in operation.

Indications IndicationMaN : Indication mask for binary input N. If set (Show), a status changeof that particular input, will be fetched and shown in the disturbance summary onlocal HMI. If not set ( Hide), status change will not be indicated.

SetLEDN : Set red LED on local HMI in front of the IED if binary input N changesstatus.

Section 3 1MRK 505 211-UEN C

IED application

388

 Application manual

Page 395: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 395/457

Disturbance recorder OperationM : Analog channel M is to be recorded by the disturbance recorder (On)or not (Off ).

If OperationM = Off , no waveform (samples) will be recorded and reported ingraph. However, Trip value, pre-fault and fault value will be recorded and reported.The input channel can still be used to trig the disturbance recorder.

If OperationM = On, waveform (samples) will also be recorded and reported in graph.

Event recorder Event recorder (ER) function has no dedicated parameters.

Trip value recorder  ZeroAngleRef : The parameter defines which analog signal that will be used as phase angle reference for all other analog input signals. This signal will also beused for frequency measurement and the measured frequency is used whencalculating trip values. It is suggested to point out a sampled voltage input signal,for example, a line or busbar phase voltage (channel 1-30).

Event listEvent list (EL) (SOE) function has no dedicated parameters.

ConsiderationThe density of recording equipment in power systems is increasing, since thenumber of modern IEDs, where recorders are included, is increasing. This leads toa vast number of recordings at every single disturbance and a lot of information has

to be handled if the recording functions do not have proper settings. The goal is tooptimize the settings in each IED to be able to capture just valuable disturbancesand to maximize the number that is possible to save in the IED.

The recording time should not be longer than necessary ( PostFaultrecT andTimeLimit ).

• Should the function record faults only for the protected object or cover more?• How long is the longest expected fault clearing time?• Is it necessary to include reclosure in the recording or should a persistent fault

generate a second recording ( PostRetrig )?

Minimize the number of recordings:

• Binary signals: Use only relevant signals to start the recording that is, protection trip, carrier receive and/or start signals.

• Analog signals: The level triggering should be used with great care, sinceunfortunate settings will cause enormously number of recordings. If nevertheless analog input triggering is used, chose settings by a sufficientmargin from normal operation values. Phase voltages are not recommended for trigging.

1MRK 505 211-UEN C Section 3IED application

389

 Application manual

Page 396: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 396/457

Remember that values of parameters set elsewhere are linked to the information ona report. Such parameters are, for example, station and object identifiers, CT andVT ratios.

3.13.6.3 Setting parameters

Table 158: DR PR DR E N on group settings (basic)

Name Values (Range) Unit Step Default Description

Operation Off  On

- - Off Operation Off/On

PreFaultRecT 0.05 - 9.90 s 0.01 0.10 Pre-fault recording time

PostFaultRecT 0.1 - 10.0 s 0.1 0.5 Post-fault recording time

TimeLimit 0.5 - 10.0 s 0.1 1.0 Fault recording time limit

PostRetrig Off  

On

- - Off Post-fault retrig enabled (On) or not (Off)

ZeroAngleRef 1 - 30 Ch 1 1 Reference channel (voltage), phasors,frequency measurement

OpModeTest Off  On

- - Off Operation mode during test mode

Table 159: A1RA DR N on group settings (basic)

Name Values (Range) Unit Step Default Description

Operation01 Off  On

- - Off Operation On/Off  

NomValue01 0.0 - 999999.9 - 0.1 0.0 Nominal value for analogue channel 1UnderTrigOp01 Off  

On- - Off Use under level trig for analogue cha 1

(on) or not (off)

UnderTrigLe01 0 - 200 % 1 50 Under trigger level for analogue cha 1 in% of signal

OverTrigOp01 Off  On

- - Off Use over level trig for analogue cha 1(on) or not (off)

OverTrigLe01 0 - 5000 % 1 200 Over trigger level for analogue cha 1 in% of signal

Operation02 Off  On

- - Off Operation On/Off  

NomValue02 0.0 - 999999.9 - 0.1 0.0 Nominal value for analogue channel 2

UnderTrigOp02 Off  On

- - Off Use under level trig for analogue cha 2(on) or not (off)

UnderTrigLe02 0 - 200 % 1 50 Under trigger level for analogue cha 2 in% of signal

OverTrigOp02 Off  On

- - Off Use over level trig for analogue cha 2(on) or not (off)

OverTrigLe02 0 - 5000 % 1 200 Over trigger level for analogue cha 2 in% of signal

Operation03 Off  On

- - Off Operation On/Off  

Table continues on next page

Section 3 1MRK 505 211-UEN C

IED application

390

 Application manual

Page 397: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 397/457

Name Values (Range) Unit Step Default Description

NomValue03 0.0 - 999999.9 - 0.1 0.0 Nominal value for analogue channel 3

UnderTrigOp03 Off  On

- - Off Use under level trig for analogue cha 3(on) or not (off)

UnderTrigLe03 0 - 200 % 1 50 Under trigger level for analogue cha 3 in% of signal

OverTrigOp03 Off  On

- - Off Use over level trig for analogue cha 3(on) or not (off)

OverTrigLe03 0 - 5000 % 1 200 Overtrigger level for analogue cha 3 in %of signal

Operation04 Off  On

- - Off Operation On/Off  

NomValue04 0.0 - 999999.9 - 0.1 0.0 Nominal value for analogue channel 4

UnderTrigOp04 Off  On

- - Off Use under level trig for analogue cha 4(on) or not (off)

UnderTrigLe04 0 - 200 % 1 50 Under trigger level for analogue cha 4 in% of signal

OverTrigOp04 Off  On

- - Off Use over level trig for analogue cha 4(on) or not (off)

OverTrigLe04 0 - 5000 % 1 200 Over trigger level for analogue cha 4 in% of signal

Operation05 Off  On

- - Off Operation On/Off  

NomValue05 0.0 - 999999.9 - 0.1 0.0 Nominal value for analogue channel 5

UnderTrigOp05 Off  On

- - Off Use under level trig for analogue cha 5(on) or not (off)

UnderTrigLe05 0 - 200 % 1 50 Under trigger level for analogue cha 5 in

% of signal

OverTrigOp05 Off  On

- - Off Use over level trig for analogue cha 5(on) or not (off)

OverTrigLe05 0 - 5000 % 1 200 Over trigger level for analogue cha 5 in% of signal

Operation06 Off  On

- - Off Operation On/Off  

NomValue06 0.0 - 999999.9 - 0.1 0.0 Nominal value for analogue channel 6

UnderTrigOp06 Off  On

- - Off Use under level trig for analogue cha 6(on) or not (off)

UnderTrigLe06 0 - 200 % 1 50 Under trigger level for analogue cha 6 in

% of signalOverTrigOp06 Off  

On- - Off Use over level trig for analogue cha 6

(on) or not (off)

OverTrigLe06 0 - 5000 % 1 200 Over trigger level for analogue cha 6 in% of signal

Operation07 Off  On

- - Off Operation On/Off  

NomValue07 0.0 - 999999.9 - 0.1 0.0 Nominal value for analogue channel 7

UnderTrigOp07 Off  On

- - Off Use under level trig for analogue cha 7(on) or not (off)

Table continues on next page

1MRK 505 211-UEN C Section 3IED application

391

 Application manual

Page 398: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 398/457

Name Values (Range) Unit Step Default Description

UnderTrigLe07 0 - 200 % 1 50 Under trigger level for analogue cha 7 in% of signal

OverTrigOp07 Off  

On

- - Off Use over level trig for analogue cha 7

(on) or not (off)

OverTrigLe07 0 - 5000 % 1 200 Over trigger level for analogue cha 7 in% of signal

Operation08 Off  On

- - Off Operation On/Off  

NomValue08 0.0 - 999999.9 - 0.1 0.0 Nominal value for analogue channel 8

UnderTrigOp08 Off  On

- - Off Use under level trig for analogue cha 8(on) or not (off)

UnderTrigLe08 0 - 200 % 1 50 Under trigger level for analogue cha 8 in% of signal

OverTrigOp08 Off  On

- - Off Use over level trig for analogue cha 8(on) or not (off)

OverTrigLe08 0 - 5000 % 1 200 Over trigger level for analogue cha 8 in% of signal

Operation09 Off  On

- - Off Operation On/Off  

NomValue09 0.0 - 999999.9 - 0.1 0.0 Nominal value for analogue channel 9

UnderTrigOp09 Off  On

- - Off Use under level trig for analogue cha 9(on) or not (off)

UnderTrigLe09 0 - 200 % 1 50 Under trigger level for analogue cha 9 in% of signal

OverTrigOp09 Off  On

- - Off Use over level trig for analogue cha 9(on) or not (off)

OverTrigLe09 0 - 5000 % 1 200 Over trigger level for analogue cha 9 in% of signal

Operation10 Off  On

- - Off Operation On/Off  

NomValue10 0.0 - 999999.9 - 0.1 0.0 Nominal value for analogue channel 10

UnderTrigOp10 Off  On

- - Off Use under level trig for analogue cha 10(on) or not (off)

UnderTrigLe10 0 - 200 % 1 50 Under trigger level for analogue cha 10in % of signal

OverTrigOp10 Off  On

- - Off Use over level trig for analogue cha 10(on) or not (off)

OverTrigLe10 0 - 5000 % 1 200 Over trigger level for analogue cha 10 in% of signal

Table 160: A4RA DR N on group settings (basic)

Name Values (Range) Unit Step Default Description

Operation31 Off  On

- - Off Operation On/off  

NomValue31 0.0 - 999999.9 - 0.1 0.0 Nominal value for analogue channel 31

UnderTrigOp31 Off  On

- - Off Use under level trig for analogue cha 31(on) or not (off)

Table continues on next page

Section 3 1MRK 505 211-UEN C

IED application

392

 Application manual

Page 399: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 399/457

Name Values (Range) Unit Step Default Description

UnderTrigLe31 0 - 200 % 1 50 Under trigger level for analogue cha 31in % of signal

OverTrigOp31 Off  

On

- - Off Use over level trig for analogue cha 31

(on) or not (off)

OverTrigLe31 0 - 5000 % 1 200 Over trigger level for analogue cha 31 in% of signal

Operation32 Off  On

- - Off Operation On/off  

NomValue32 0.0 - 999999.9 - 0.1 0.0 Nominal value for analogue channel 32

UnderTrigOp32 Off  On

- - Off Use under level trig for analogue cha 32(on) or not (off)

UnderTrigLe32 0 - 200 % 1 50 Under trigger level for analogue cha 32in % of signal

OverTrigOp32 Off  On

- - Off Use over level trig for analogue cha 32(on) or not (off)

OverTrigLe32 0 - 5000 % 1 200 Over trigger level for analogue cha 32 in% of signal

Operation33 Off  On

- - Off Operation On/off  

NomValue33 0.0 - 999999.9 - 0.1 0.0 Nominal value for analogue channel 33

UnderTrigOp33 Off  On

- - Off Use under level trig for analogue cha 33(on) or not (off)

UnderTrigLe33 0 - 200 % 1 50 Under trigger level for analogue cha 33in % of signal

OverTrigOp33 Off  On

- - Off Use over level trig for analogue cha 33(on) or not (off)

OverTrigLe33 0 - 5000 % 1 200 Overtrigger level for analogue cha 33 in% of signal

Operation34 Off  On

- - Off Operation On/off  

NomValue34 0.0 - 999999.9 - 0.1 0.0 Nominal value for analogue channel 34

UnderTrigOp34 Off  On

- - Off Use under level trig for analogue cha 34(on) or not (off)

UnderTrigLe34 0 - 200 % 1 50 Under trigger level for analogue cha 34in % of signal

OverTrigOp34 Off  On

- - Off Use over level trig for analogue cha 34(on) or not (off)

OverTrigLe34 0 - 5000 % 1 200 Over trigger level for analogue cha 34 in% of signal

Operation35 Off  On

- - Off Operation On/off  

NomValue35 0.0 - 999999.9 - 0.1 0.0 Nominal value for analogue channel 35

UnderTrigOp35 Off  On

- - Off Use under level trig for analogue cha 35(on) or not (off)

UnderTrigLe35 0 - 200 % 1 50 Under trigger level for analogue cha 35in % of signal

OverTrigOp35 Off  On

- - Off Use over level trig for analogue cha 35(on) or not (off)

Table continues on next page

1MRK 505 211-UEN C Section 3IED application

393

 Application manual

Page 400: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 400/457

Name Values (Range) Unit Step Default Description

OverTrigLe35 0 - 5000 % 1 200 Over trigger level for analogue cha 35 in% of signal

Operation36 Off  

On

- - Off Operation On/off  

NomValue36 0.0 - 999999.9 - 0.1 0.0 Nominal value for analogue channel 36

UnderTrigOp36 Off  On

- - Off Use under level trig for analogue cha 36(on) or not (off)

UnderTrigLe36 0 - 200 % 1 50 Under trigger level for analogue cha 36in % of signal

OverTrigOp36 Off  On

- - Off Use over level trig for analogue cha 36(on) or not (off)

OverTrigLe36 0 - 5000 % 1 200 Over trigger level for analogue cha 36 in% of signal

Operation37 Off  On

- - Off Operation On/off  

NomValue37 0.0 - 999999.9 - 0.1 0.0 Nominal value for analogue channel 37

UnderTrigOp37 Off  On

- - Off Use under level trig for analogue cha 37(on) or not (off)

UnderTrigLe37 0 - 200 % 1 50 Under trigger level for analogue cha 37in % of signal

OverTrigOp37 Off  On

- - Off Use over level trig for analogue cha 37(on) or not (off)

OverTrigLe37 0 - 5000 % 1 200 Over trigger level for analogue cha 37 in% of signal

Operation38 Off  On

- - Off Operation On/off  

NomValue38 0.0 - 999999.9 - 0.1 0.0 Nominal value for analogue channel 38

UnderTrigOp38 Off  On

- - Off Use under level trig for analogue cha 38(on) or not (off)

UnderTrigLe38 0 - 200 % 1 50 Under trigger level for analogue cha 38in % of signal

OverTrigOp38 Off  On

- - Off Use over level trig for analogue cha 38(on) or not (off)

OverTrigLe38 0 - 5000 % 1 200 Over trigger level for analogue cha 38 in% of signal

Operation39 Off  On

- - Off Operation On/off  

NomValue39 0.0 - 999999.9 - 0.1 0.0 Nominal value for analogue channel 39UnderTrigOp39 Off  

On- - Off Use under level trig for analogue cha 39

(on) or not (off)

UnderTrigLe39 0 - 200 % 1 50 Under trigger level for analogue cha 39in % of signal

OverTrigOp39 Off  On

- - Off Use over level trig for analogue cha 39(on) or not (off)

OverTrigLe39 0 - 5000 % 1 200 Over trigger level for analogue cha 39 in% of signal

Operation40 Off  On

- - Off Operation On/off  

Table continues on next page

Section 3 1MRK 505 211-UEN C

IED application

394

 Application manual

Page 401: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 401/457

Name Values (Range) Unit Step Default Description

NomValue40 0.0 - 999999.9 - 0.1 0.0 Nominal value for analogue channel 40

UnderTrigOp40 Off  On

- - Off Use under level trig for analogue cha 40(on) or not (off)

UnderTrigLe40 0 - 200 % 1 50 Under trigger level for analogue cha 40in % of signal

OverTrigOp40 Off  On

- - Off Use over level trig for analogue cha 40(on) or not (off)

OverTrigLe40 0 - 5000 % 1 200 Over trigger level for analogue cha 40 in% of signal

Table 161: B1R BD R Non group settings (basic)

Name Values (Range) Unit Step Default Description

Operation01 Off  

On

- - Off Trigger operation On/Off  

TrigLevel01 Trig on 0Trig on 1

- - Trig on 1 Trig on positiv (1) or negative (0) slopefor binary inp 1

IndicationMa01 HideShow

- - Hide Indication mask for binary channel 1

SetLED01 Off  On

- - Off Set red-LED on HMI for binary channel 1

Operation02 Off  On

- - Off Trigger operation On/Off  

TrigLevel02 Trig on 0Trig on 1

- - Trig on 1 Trig on positiv (1) or negative (0) slopefor binary inp 2

IndicationMa02 Hide

Show

- - Hide Indication mask for binary channel 2

SetLED02 Off  On

- - Off Set red-LED on HMI for binary channel 2

Operation03 Off  On

- - Off Trigger operation On/Off  

TrigLevel03 Trig on 0Trig on 1

- - Trig on 1 Trig on positiv (1) or negative (0) slopefor binary inp 3

IndicationMa03 HideShow

- - Hide Indication mask for binary channel 3

SetLED03 Off  On

- - Off Set red-LED on HMI for binary channel 3

Operation04 Off  On

- - Off Trigger operation On/Off  

TrigLevel04 Trig on 0Trig on 1

- - Trig on 1 Trig on positiv (1) or negative (0) slopefor binary inp 4

IndicationMa04 HideShow

- - Hide Indication mask for binary channel 4

SetLED04 Off  On

- - Off Set red-LED on HMI for binary channel 4

Operation05 Off  On

- - Off Trigger operation On/Off  

Table continues on next page

1MRK 505 211-UEN C Section 3IED application

395

 Application manual

Page 402: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 402/457

Name Values (Range) Unit Step Default Description

TrigLevel05 Trig on 0Trig on 1

- - Trig on 1 Trig on positiv (1) or negative (0) slopefor binary inp 5

IndicationMa05 Hide

Show

- - Hide Indication mask for binary channel 5

SetLED05 Off  On

- - Off Set red-LED on HMI for binary channel 5

Operation06 Off  On

- - Off Trigger operation On/Off  

TrigLevel06 Trig on 0Trig on 1

- - Trig on 1 Trig on positiv (1) or negative (0) slopefor binary inp 6

IndicationMa06 HideShow

- - Hide Indication mask for binary channel 6

SetLED06 Off  On

- - Off Set red-LED on HMI for binary channel 6

Operation07 Off  

On

- - Off Trigger operation On/Off  

TrigLevel07 Trig on 0Trig on 1

- - Trig on 1 Trig on positiv (1) or negative (0) slopefor binary inp 7

IndicationMa07 HideShow

- - Hide Indication mask for binary channel 7

SetLED07 Off  On

- - Off Set red-LED on HMI for binary channel 7

Operation08 Off  On

- - Off Trigger operation On/Off  

TrigLevel08 Trig on 0Trig on 1

- - Trig on 1 Trig on positiv (1) or negative (0) slopefor binary inp 8

IndicationMa08 HideShow - - Hide Indication mask for binary channel 8

SetLED08 Off  On

- - Off Set red-LED on HMI for binary channel 8

Operation09 Off  On

- - Off Trigger operation On/Off  

TrigLevel09 Trig on 0Trig on 1

- - Trig on 1 Trig on positiv (1) or negative (0) slopefor binary inp 9

IndicationMa09 HideShow

- - Hide Indication mask for binary channel 9

SetLED09 Off  On

- - Off Set red-LED on HMI for binary channel 9

Operation10 Off  On

- - Off Trigger operation On/Off  

TrigLevel10 Trig on 0Trig on 1

- - Trig on 1 Trig on positiv (1) or negative (0) slopefor binary inp 10

IndicationMa10 HideShow

- - Hide Indication mask for binary channel 10

SetLED10 Off  On

- - Off Set red-LED on HMI for binary channel 10

Operation11 Off  On

- - Off Trigger operation On/Off  

Table continues on next page

Section 3 1MRK 505 211-UEN C

IED application

396

 Application manual

Page 403: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 403/457

Name Values (Range) Unit Step Default Description

TrigLevel11 Trig on 0Trig on 1

- - Trig on 1 Trig on positiv (1) or negative (0) slopefor binary inp 11

IndicationMa11 Hide

Show

- - Hide Indication mask for binary channel 11

SetLED11 Off  On

- - Off Set red-LED on HMI for binary channel 11

Operation12 Off  On

- - Off Trigger operation On/Off  

TrigLevel12 Trig on 0Trig on 1

- - Trig on 1 Trig on positiv (1) or negative (0) slopefor binary inp 12

IndicationMa12 HideShow

- - Hide Indication mask for binary channel 12

SetLED12 Off  On

- - Off Set red-LED on HMI for binary input 12

Operation13 Off  

On

- - Off Trigger operation On/Off  

TrigLevel13 Trig on 0Trig on 1

- - Trig on 1 Trig on positiv (1) or negative (0) slopefor binary inp 13

IndicationMa13 HideShow

- - Hide Indication mask for binary channel 13

SetLED13 Off  On

- - Off Set red-LED on HMI for binary channel 13

Operation14 Off  On

- - Off Trigger operation On/Off  

TrigLevel14 Trig on 0Trig on 1

- - Trig on 1 Trig on positiv (1) or negative (0) slopefor binary inp 14

IndicationMa14 HideShow - - Hide Indication mask for binary channel 14

SetLED14 Off  On

- - Off Set red-LED on HMI for binary channel 14

Operation15 Off  On

- - Off Trigger operation On/Off  

TrigLevel15 Trig on 0Trig on 1

- - Trig on 1 Trig on positiv (1) or negative (0) slopefor binary inp 15

IndicationMa15 HideShow

- - Hide Indication mask for binary channel 15

SetLED15 Off  On

- - Off Set red-LED on HMI for binary channel 15

Operation16 Off  On

- - Off Trigger operation On/Off  

TrigLevel16 Trig on 0Trig on 1

- - Trig on 1 Trig on positiv (1) or negative (0) slopefor binary inp 16

IndicationMa16 HideShow

- - Hide Indication mask for binary channel 16

SetLED16 Off  On

- - Off Set red-LED on HMI for binary channel 16

FUNT1 0 - 255 FunT 1 0 Function type for binary channel 1 (IEC-60870-5-103)

Table continues on next page

1MRK 505 211-UEN C Section 3IED application

397

 Application manual

Page 404: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 404/457

Name Values (Range) Unit Step Default Description

FUNT2 0 - 255 FunT 1 0 Function type for binary channel 2 (IEC-60870-5-103)

FUNT3 0 - 255 FunT 1 0 Function type for binary channel 3 (IEC

-60870-5-103)

FUNT4 0 - 255 FunT 1 0 Function type for binary channel 4 (IEC-60870-5-103)

FUNT5 0 - 255 FunT 1 0 Function type for binary channel 5 (IEC-60870-5-103)

FUNT6 0 - 255 FunT 1 0 Function type for binary channel 6 (IEC-60870-5-103)

FUNT7 0 - 255 FunT 1 0 Function type for binary channel 7 (IEC-60870-5-103)

FUNT8 0 - 255 FunT 1 0 Function type for binary channel 8 (IEC-60870-5-103)

FUNT9 0 - 255 FunT 1 0 Function type for binary channel 9 (IEC

-60870-5-103)

FUNT10 0 - 255 FunT 1 0 Function type for binary channel 10 (IEC-60870-5-103)

FUNT11 0 - 255 FunT 1 0 Function type for binary channel 11 (IEC-60870-5-103)

FUNT12 0 - 255 FunT 1 0 Function type for binary channel 12 (IEC-60870-5-103)

FUNT13 0 - 255 FunT 1 0 Function type for binary channel 13 (IEC-60870-5-103)

FUNT14 0 - 255 FunT 1 0 Function type for binary channel 14 (IEC-60870-5-103)

FUNT15 0 - 255 FunT 1 0 Function type for binary channel 15 (IEC-60870-5-103)

FUNT16 0 - 255 FunT 1 0 Function type for binary channel 16 (IEC-60870-5-103)

INFNO1 0 - 255 InfNo 1 0 Information number for binary channel 1(IEC -60870-5-103)

INFNO2 0 - 255 InfNo 1 0 Information number for binary channel 2(IEC -60870-5-103)

INFNO3 0 - 255 InfNo 1 0 Information number for binary channel 3(IEC -60870-5-103)

INFNO4 0 - 255 InfNo 1 0 Information number for binary channel 4(IEC -60870-5-103)

INFNO5 0 - 255 InfNo 1 0 Information number for binary channel 5(IEC -60870-5-103)

INFNO6 0 - 255 InfNo 1 0 Information number for binary channel 6(IEC -60870-5-103)

INFNO7 0 - 255 InfNo 1 0 Information number for binary channel 7(IEC -60870-5-103)

INFNO8 0 - 255 InfNo 1 0 Information number for binary channel 8(IEC -60870-5-103)

INFNO9 0 - 255 InfNo 1 0 Information number for binary channel 9(IEC -60870-5-103)

Table continues on next page

Section 3 1MRK 505 211-UEN C

IED application

398

 Application manual

Page 405: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 405/457

Name Values (Range) Unit Step Default Description

INFNO10 0 - 255 InfNo 1 0 Information number for binary channel10 (IEC -60870-5-103)

INFNO11 0 - 255 InfNo 1 0 Information number for binary channel

11 (IEC -60870-5-103)

INFNO12 0 - 255 InfNo 1 0 Information number for binary channel12 (IEC -60870-5-103)

INFNO13 0 - 255 InfNo 1 0 Information number for binary channel13 (IEC -60870-5-103)

INFNO14 0 - 255 InfNo 1 0 Information number for binary channel14 (IEC -60870-5-103)

INFNO15 0 - 255 InfNo 1 0 Information number for binary channel15 (IEC -60870-5-103)

INFNO16 0 - 255 InfNo 1 0 Information number for binary channel16 (IEC -60870-5-103)

3.13.7 Event list

3.13.7.1 Application

From an overview perspective, continuous event-logging is a useful systemmonitoring instrument and is a complement to specific disturbance recorder functions.

The event list (EL), always included in the IED, logs all selected binary inputsignals connected to the Disturbance report function. The list may contain of up to1000 time-tagged events stored in a ring-buffer where, if the buffer is full, theoldest event is overwritten when a new event is logged.

The difference between the event list (EL) and the event recorder (ER) function isthat the list function continuously updates the log with time tagged events while therecorder function is an extract of events during the disturbance report time window.

The event list information is available in the IED via the local HMI or PCM600.

3.13.7.2 Setting guidelines

The setting parameters for the Event list function (EL) are a part of the Disturbancereport settings.

It is possible to event handle up to 96 binary signals, either internal signals or signals from binary input channels. These signals are identical with the binarysignals recorded by the disturbance recorder.

There is no dedicated setting for the EL function.

1MRK 505 211-UEN C Section 3IED application

399

 Application manual

Page 406: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 406/457

3.13.8 Indications

3.13.8.1 Application

Fast, condensed and reliable information about disturbances in the primary and/or in the secondary system is important. Binary signals that have changed statusduring a disturbance are an example of this. This information is used primarily inthe short term (for example, immediate disturbance analysis, corrective actions) toget information via the local HMI in a straightforward way without any knowledgeof how to handle the IED.

There are three LEDs on the local HMI (green, yellow and red), which will displaystatus information about the IED (in service, internal failure, and so on) and theDisturbance report function (trigged).

The Indication function (IND), always included in the IED, shows all selected binary input signals connected to the Disturbance Report function that have beenactivated during a disturbance. The status changes are logged during the entirerecording time, which depends on the set of recording times (pre-, post-fault andlimit time) and the actual fault time. The indications are not time-tagged.

The indication information is available for each of the recorded disturbances in theIED and the user may use the local HMI to view the information.

3.13.8.2 Setting guidelines

The setting parameters for LEDs and the Indication function (IND) are a part of thedisturbance report settings.

Available signals are identical with the binary signals recorded by the disturbancereport. It is possible to use all binary input signals for the Indication function on thelocal HMI, but it is not recommended since the general view will be lost. Theintention is to point out some important signals, not to many, to be shown. If amore thorough analysis is to be done information from the event recorder should beused.

To be able to control the red LED in the local HMI:

SetLEDn: Set red LED on LMHI in front of the IED if binary input N changes status.For the IND function there are a number dedicated settings:

 IndicationMaN : Indication mask for binary input N. If set (Show), a status changeof that particular input, will be fetched and shown on the local HMI. If not set( Hide), status change will not be indicated.

Section 3 1MRK 505 211-UEN C

IED application

400

 Application manual

Page 407: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 407/457

3.13.9 Event recorder

3.13.9.1 Application

Quick, complete and reliable information about disturbances in the primary and/or in the secondary system is vital, for example, time tagged events logged duringdisturbances. This information is used for different purposes in the short term, for example, disturbance analysis, corrective actions and in the long term, for example,disturbance analysis, statistics and maintenance, that is Functional Analysis).

The event recorder, always included in the IED, logs all selected binary inputsignals connected to the disturbance report function DRPRDRE. Each recordingcan contain up to 150 time-tagged events. The events are logged during the totalrecording time, which depends on the set of recording times (pre-, post-fault andlimit time) and the actual fault time. During this time, the first 150 events for all 96

 binary signals are logged and time-tagged.

The event recorder information is available for each of the recorded disturbances inthe IED and the user may use the local HMI to get the information. Theinformation is included in the disturbance recorder file, which may be uploaded toPCM600 and further analyzed using the Disturbance Handling tool.

The event recording information is an integrated part of the disturbance record(Comtrade file).

3.13.9.2 Setting guidelines

The setting parameters for the Event Recorder (ER) function are a part of theDisturbance Report settings.

It is possible to event handle up to 96 binary signals, either internal signals or signals from binary input channels. These signals are identical to the binary signalsrecorded by the disturbance report.

For the ER function there is no dedicated setting.

3.13.10 Trip value recorder

3.13.10.1 Application

Fast, complete and reliable information about disturbances such as fault currentsand voltage faults in the power system is vital. This information is used for different purposes in the short perspective (for example, fault location, disturbanceanalysis, corrective actions) and the long term (for example, disturbance analysis,statistics and maintenance, that is Functional Analysis).

The trip value recorder (TVR), always included in the IED, calculates the values of all selected external analog input signals (channel 1-30) connected to the

1MRK 505 211-UEN C Section 3IED application

401

 Application manual

Page 408: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 408/457

Disturbance Report function. The estimation is performed immediately after finalizing each recording and available in the disturbance report. The result ismagnitude and phase angle before and during the fault for each analog input signal.

The information is used as input to the fault location function (FL), if included inthe IED and in operation.

The trip value recorder (TVR) information is available for each of the recordeddisturbances in the IED and the user may use the local HMI to get the information.The information is included in the disturbance recorder file, which can be uploadedto PCM600 and further analyzed using the Disturbance Handling tool.

3.13.10.2 Setting guidelines

The trip value recorder (TVR) setting parameters are a part of the disturbance

report settings.For the trip value recorder (TVR) there is one dedicated setting:

 ZeroAngleRef : The parameter defines which analog signal to use as phase-anglereference for all other input signals. It is suggested to point out a sampled voltageinput signal, for example a line or busbar phase voltage (channel 1-30).

3.13.11 Disturbance recorder

3.13.11.1 Application

The maximum number of recordings depend on each recordingstotal recording time. Long recording time will reduce the number of recordings to less than 100.

The IED flash disk should NOT be used to store any user files. Thismight cause disturbance recordings to be deleted due to lack of disk space.

To get fast, complete and reliable information about fault current, voltage, binarysignal and other disturbances in the power system is very important. This isaccomplished by the Disturbance Recorder function and facilitates a better understanding of the behavior of the power system and related primary andsecondary equipment during and after a disturbance. An analysis of the recordeddata provides valuable information that can be used to explain a disturbance, basisfor change of IED setting plan, improvement of existing equipment, and so on.This information can also be used in a longer perspective when planning for anddesigning new installations, that is a disturbance recording could be a part of Functional Analysis (FA).

Section 3 1MRK 505 211-UEN C

IED application

402

 Application manual

Page 409: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 409/457

The Disturbance Recorder (DR), always included in the IED, acquires sampleddata from all selected analog input and binary signals connected to the function

 blocks, that is maximum 30 external analog, 10 internal (derived) analog and 96 binary signals.

The function is characterized by great flexibility as far as configuration, startingconditions, recording times, and large storage capacity are concerned. Thus, thedisturbance recorder is not dependent on the operation of protective functions, andit can record disturbances that were not discovered by protective functions.

The disturbance recorder information is saved for each of the recorded disturbancesin the IED and the user may use the local HMI to get some general informationabout the recordings. The disturbance recording information is included in thedisturbance recorder files, which may be uploaded to PCM600 for further analysisusing the Disturbance Handling tool. The information is also available on a station

 bus according to IEC 61850 and according to IEC 60870-5-103.

3.13.11.2 Setting guidelines

The setting parameters for the Disturbance Recorder function (DR) is a part of theDisturbance Report settings.

It is possible to handle up to 40 analog and 96 binary signals, either internal signalsor signals coming from external inputs. The binary signals are identical with thesignals recorded by the other functions in the Disturbance Report function, that isEvent recorder (ER), Indication (IND) and Trip value recorder (TVR) function.

For the DR function there is one dedicated setting:

OperationM : Analog channel M is to be recorded by the disturbance recorder (On)or not (Off ). Other disturbance report settings, such as Operation and TrigLevel for 

 binary signals, will also influence the disturbance recorder.

3.14 Metering

3.14.1 Pulse-counter logic PCGGIO

Function description IEC 61850

identification

IEC 60617

identification

ANSI/IEEE C37.2

device number

Pulse-counter logic PCGGIO

S00947 V1 EN

-

1MRK 505 211-UEN C Section 3IED application

403

 Application manual

Page 410: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 410/457

3.14.1.1 Application

Pulse counter logic function counts externally generated binary pulses, for instance pulses coming from an external energy meter, for calculation of energy

consumption values. The pulses are captured by the binary input module (BIM),and read by the pulse counter function. The number of pulses in the counter is thenreported via the station bus to the substation automation system or read via thestation monitoring system as a service value. When using IEC 61850–8–1, a scaledservice value is available over the station bus.

The normal use for this function is the counting of energy pulses from externalenergy meters. An optional number of inputs from an arbitrary input module inIED can be used for this purpose with a frequency of up to 40 Hz. The pulsecounter can also be used as a general purpose counter.

3.14.1.2 Setting guidelines

From PCM600, these parameters can be set individually for each pulse counter:

• Operation: Off /On

• tReporting : 0-3600s

• EventMask : NoEvents/ ReportEvents

The configuration of the inputs and outputs of the Pulse counter function block ismade with PCM600.

On the Binary Input Module, the debounce filter time is fixed set to 5 ms, that is,the counter suppresses pulses with a pulse length less than 5 ms. The inputoscillation blocking frequency is preset to 40 Hz. That means that the counter findsthe input oscillating if the input frequency is greater than 40 Hz. The oscillationsuppression is released at 30 Hz. The values for blocking/release of the oscillationcan be changed in the local HMI and PCM600 under Main menu/Settings/

General settings/I/O-modules

The setting is common for all input channels on a Binary InputModule, that is, if changes of the limits are made for inputs notconnected to the pulse counter, the setting also influences the inputson the same board used for pulse counting.

Section 3 1MRK 505 211-UEN C

IED application

404

 Application manual

Page 411: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 411/457

3.14.1.3 Setting parameters

Table 162: PC GG IO N on group settings (basic)

Name Values (Range) Unit Step Default Description

Operation Off  On

- - Off Operation Off/On

EventMask NoEventsReportEvents

- - NoEvents Report mask for analog events frompulse counter 

CountCriteria Off  RisingEdgeFalling edgeOnChange

- - RisingEdge Pulse counter criteria

Scale 1.000 - 90000.000 - 0.001 1.000 Scaling value for SCAL_VAL output tounit per counted value

Quantity Count ActivePower 

 ApparentPower ReactivePower 

 ActiveEnergy ApparentEnergyReactiveEnergy

- - Count Measured quantity for SCAL_VAL output

tReporting 0 - 3600 s 1 60 Cycle time for reporting of counter value

3.14.2 Function for energy calculation and demand handling

ETPMMTR

Function description IEC 61850identification

IEC 60617identification

ANSI/IEEE C37.2device number

Energy calculation and demandhandling

ETPMMTR -

3.14.2.1 Application

Energy calculation and demand handling function ETPMMTR is intended for statistics of the forward and reverse active and reactive energy. It has a highaccuracy basically given by the measurements function (CVMMXN). This functionhas a site calibration possibility to further increase the total accuracy.

The function is connected to the instantaneous outputs of (CVMMXN) as shown infigure 148.

1MRK 505 211-UEN C Section 3IED application

405

 Application manual

Page 412: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 412/457

P

Q

STACC

RSTACC

RSTDMD

TRUE

FALSEFALSE

CVMMXN

IEC09000106.vsd

ETPMMTRP_INST

Q_INST

IEC09000106 V1 EN

Figure 148: Connection of energy calculation and demand handling function 

ETPMMTR to the measurements function (CVMMXN) 

The energy values can be read through communication in MWh and MVarh inmonitoring tool of PCM600 and/or alternatively the values can be presented on thelocal HMI. The local HMI graphical display is configured with PCM600 Graphicaldisplay editor tool (GDE) with a measuring value which is selected to the active

and reactive component as preferred. All four values can also be presented.Maximum demand values are presented in MWh or MVarh in the same way.

Alternatively, the values can be presented with use of the pulse counters function(PCGGIO). The output values are scaled with the pulse output setting values

 EAFAccPlsQty, EARAccPlsQty, ERFAccPlsQty and ERVAccPlsQty of the energymetering function and then the pulse counter can be set-up to present the correctvalues by scaling in this function. Pulse counter values can then be presented onthe local HMI in the same way and/or sent to the SA system throughcommunication where the total energy then is calculated by summation of theenergy pulses. This principle is good for very high values of energy as the

saturation of numbers else will limit energy integration to about one year with 50kV and 3000 A. After that the accumulation will start on zero again.

3.14.2.2 Setting guidelines

The parameters are set via the local HMI or PCM600.

The following settings can be done for the energy calculation and demand handlingfunction ETPMMTR:

Operation: Off /On

tEnergy: Time interval when energy is measured.

StartAcc: Off /On is used to switch the accumulation of energy on and off.

The input signal STACC is used to start accumulation. Input signalSTACC cannot be used to halt accumulation. The energy content isreset every time STACC is activated. STACC can for example, beused when an external clock is used to switch two active energymeasuring function blocks on and off to have indication of two tariffs.

Section 3 1MRK 505 211-UEN C

IED application

406

 Application manual

Page 413: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 413/457

tEnergyOnPls: gives the pulse length ON time of the pulse. It should be at least100 ms when connected to the Pulse counter function block. Typical value can be100 ms.

tEnergyOffPls: gives the OFF time between pulses. Typical value can be 100 ms.

 EAFAccPlsQty and EARAccPlsQty: gives the MWh value in each pulse. It should be selected together with the setting of the Pulse counter (PCGGIO) settings togive the correct total pulse value.

 ERFAccPlsQty and ERVAccPlsQty : gives the MVarh value in each pulse. It should be selected together with the setting of the Pulse counter (PCGGIO) settings togive the correct total pulse value.

For the advanced user there are a number of settings for direction, zero clamping,max limit, and so on. Normally, the default values are suitable for these parameters.

3.14.2.3 Setting parameters

Table 163: ETP MM TR N on group settings (basic)

Name Values (Range) Unit Step Default Description

Operation Off  On

- - Off Operation Off/On

StartAcc Off  On

- - Off Activate the accumulation of energyvalues

tEnergy 1 Minute5 Minutes10 Minutes15 Minutes30 Minutes60 Minutes180 Minutes

- - 1 Minute Time interval for energy calculation

tEnergyOnPls 0.000 - 60.000 s 0.001 1.000 Energy accumulated pulse ON time insecs

tEnergyOffPls 0.000 - 60.000 s 0.001 0.500 Energy accumulated pulse OFF time insecs

EAFAccPlsQty 0.001 - 10000.000 MWh 0.001 100.000 Pulse quantity for active forwardaccumulated energy value

EARAccPlsQty 0.001 - 10000.000 MWh 0.001 100.000 Pulse quantity for active reverseaccumulated energy value

ERFAccPlsQty 0.001 - 10000.000 MVArh 0.001 100.000 Pulse quantity for reactive forwardaccumulated energy value

ERVAccPlsQty 0.001 - 10000.000 MVArh 0.001 100.000 Pulse quantity for reactive reverseaccumulated energy value

1MRK 505 211-UEN C Section 3IED application

407

 Application manual

Page 414: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 414/457

Table 164: ETPM MTR Non group settings (advanced)

Name Values (Range) Unit Step Default Description

EALim 0.001 -10000000000.000

MWh 0.001 1000000.000 Active energy limit

ERLim 0.001 -10000000000.000

MVArh 0.001 1000.000 Reactive energy limit

DirEnergyAct ForwardReverse

- - Forward Direction of active energy flow Forward/Reverse

DirEnergyReac ForwardReverse

- - Forward Direction of reactive energy flow Forward/Reverse

EnZeroClamp Off  On

- - On Enable of zero point clamping detectionfunction

LevZeroClampP 0.001 - 10000.000 MW 0.001 10.000 Zero point clamping level at active Power  

LevZeroClampQ 0.001 - 10000.000 MVAr 0.001 10.000 Zero point clamping level at reactivePower 

EAFPrestVal 0.000 - 10000.000 MWh 0.001 0.000 Preset Initial value for forward activeenergy

EARPrestVal 0.000 - 10000.000 MWh 0.001 0.000 Preset Initial value for reverse activeenergy

ERFPresetVal 0.000 - 10000.000 MVArh 0.001 0.000 Preset Initial value for forward reactiveenergy

ERVPresetVal 0.000 - 10000.000 MVArh 0.001 0.000 Preset Initial value for reverse reactiveenergy

Section 3 1MRK 505 211-UEN C

IED application

408

 Application manual

Page 415: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 415/457

Section 4 Station communication

About this chapter

This chapter describes the communication possibilities in a SA-system.

4.1 Overview

Each IED is provided with a communication interface, enabling it to connect to one

or many substation level systems or equipment, either on the SubstationAutomation (SA) bus or Substation Monitoring (SM) bus.

Following communication protocols are available:

• IEC 61850-8-1 communication protocol• LON communication protocol• SPA or IEC 60870-5-103 communication protocol• DNP3.0 communication protocol

Theoretically, several protocols can be combined in the same IED.

4.2 IEC 61850-8-1 communication protocol

4.2.1 Application IEC 61850-8-1

IEC 61850-8-1 communication protocol allows vertical communication to HSIclients and allows horizontal communication between two or more intelligentelectronic devices (IEDs) from one or several vendors to exchange information andto use it in the performance of their functions and for correct co-operation.

GOOSE (Generic Object Oriented Substation Event), which is a part of IEC 61850– 8–1 standard, allows the IEDs to communicate state and control informationamongst themselves, using a publish-subscribe mechanism. That is, upon detectingan event, the IED(s) use a multi-cast transmission to notify those devices that haveregistered to receive the data. An IED can, by publishing a GOOSE message,report its status. It can also request a control action to be directed at any device inthe network.

Figure 149 shows the topology of an IEC 61850–8–1 configuration. IEC 61850–8– 1 specifies only the interface to the substation LAN. The LAN itself is left to thesystem integrator.

1MRK 505 211-UEN C Section 4Station communication

409

 Application manual

Page 416: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 416/457

KIOSK 2 KIOSK 3

Station HSI

Base System

Engineering

Workstation

SMS

Gateway

Printer 

CC

IEC09000135_en.v

sd

KIOSK 1

IED

1

IED

2

IED

3

IED

1

IED

2

IED

3

IED

1

IED

2

IED

3

IEC09000135 V1 EN

Figure 149: SA system with IEC 61850–8–1 

Figure 150 shows the GOOSE peer-to-peer communication.

Control Protection Control ProtectionControl and protection

GOOSE

en05000734.vsd

Station HSI

MicroSCADAGateway

IED

A

IED

A

IED

A

IED

A

IED

A

IEC05000734 V1 EN

Figure 150: Example of a broadcasted GOOSE message 

Section 4 1MRK 505 211-UEN C

Station communication

410

 Application manual

Page 417: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 417/457

4.2.2 Setting guidelines

There are two settings related to the IEC 61850–8–1 protocol:

Operation User can set IEC 61850 communication to On or Off .

GOOSE has to be set to the Ethernet link where GOOSE traffic shall be send andreceived.

4.2.3 Setting parameters

T able 1 65 : IE C6 18 50-8-1 N on g ro up se ttin gs (b as ic)

Name Values (Range) Unit Step Default Description

Operation Off  On

- - Off Operation Off/On

GOOSE FrontOEM311_ABOEM311_CD

- - OEM311_AB Port for GOOSE communication

Table 166: G OO SEB INR CV Non group settings (basic)

Name Values (Range) Unit Step Default Description

Operation Off  On

- - Off Operation Off/On

4.2.4 IEC 61850 generic communication I/O functions SPGGIO,SP16GGIO

4.2.4.1 Application

IEC 61850–8–1 generic communication I/O functions (SPGGIO) function is usedto send one single logical output to other systems or equipment in the substation. Ithas one visible input, that should be connected in ACT tool.

4.2.4.2 Setting guidelinesThere are no settings available for the user for SPGGIO. However, PCM600 must

 be used to get the signals sent by SPGGIO.

4.2.4.3 Setting parameters

The function does not have any parameters available in the local HMI or PCM600.

4.2.5 IEC 61850 generic communication I/O functions MVGGIO

1MRK 505 211-UEN C Section 4Station communication

411

 Application manual

Page 418: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 418/457

4.2.5.1 Application

IEC61850 generic communication I/O functions (MVGGIO) function is used tosend the instantaneous value of an analog signal to other systems or equipment in

the substation. It can also be used inside the same IED, to attach a RANGE aspectto an analog value and to permit measurement supervision on that value.

4.2.5.2 Setting guidelines

The settings available for IEC61850 generic communication I/O functions(MVGGIO) function allows the user to choose a deadband and a zero deadband for the monitored signal. Values within the zero deadband are considered as zero.

The high and low limit settings provides limits for the high-high-, high, normal,low and low-low ranges of the measured value. The actual range of the measured

value is shown on the range output of MVGGIO function block. When a Measuredvalue expander block (RANGE_XP) is connected to the range output, the logicaloutputs of the RANGE_XP are changed accordingly.

4.2.5.3 Setting parameters

Table 167: M VG GIO Non group settings (basic)

Name Values (Range) Unit Step Default Description

MV db 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of  range, Int Db: In %s

MV zeroDb 0 - 100000 m% 1 500 Zero point clamping in 0,001% of range

MV hhLim -10000000000.000- 10000000000.000

- 0.001 90.000 High High limit

MV hLim -10000000000.000- 10000000000.000

- 0.001 80.000 High limit

MV lLim -10000000000.000- 10000000000.000

- 0.001 -80.000 Low limit

MV llLim -10000000000.000- 10000000000.000

- 0.001 -90.000 Low Low limit

MV min -10000000000.000- 10000000000.000

- 0.001 -100.000 Minimum value

MV max -10000000000.000- 10000000000.000

- 0.001 100.000 Maximum value

MV dbType CyclicDead bandInt deadband

- - Dead band Reporting type

MV limHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range (commonfor all limits)

4.2.6 IEC 61850-8-1 redundant station bus communication

Section 4 1MRK 505 211-UEN C

Station communication

412

 Application manual

Page 419: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 419/457

Function description IEC 61850

identification

IEC 60617

identification

ANSI/IEEE C37.2

device number

Parallel Redundancy Protocol Status PRPSTATUS - -

Duo driver configuration DUODRV - -

4.2.6.1 Application

Parallel redundancy protocol status (PRPSTATUS) together with Duo driver configuration (DUODRV) are used to supervise and assure redundant Ethernetcommunication over two channels. This will secure data transfer even though onecommunication channel might not be available for some reason. Together PRPSTATUS and DUODRV provide redundant communication over station busrunning IEC 61850-8-1 protocol. The redundant communication use both port ABand CD on OEM module.

1MRK 505 211-UEN C Section 4Station communication

413

 Application manual

Page 420: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 420/457

Page 421: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 421/457

The settings can then be viewed, but not set, in the Parameter Setting tool inPCM600 under Main menu/IED Configuration/Communication/Ethernet

configuration/DUODRV:

Operation: The redundant communication will be activated when this parameter isset to On.After confirmation the IED will restart and the setting alternatives Rear 

OEM - Port AB and CD will not be further displayed in the local HMI. The ETHLANAB and ETHLANCD in the Parameter Setting Tool are irrelevant when theredundant communication is activated, only DUODRV IPAdress and IPMask arevalid.

IEC10000057-1-en.vsd

IEC10000057 V1 EN

Figure 152: PST screen: DUODRV Operation is set to On, which affect Rear 

OEM - Port AB and CD which are both set to Duo 

1MRK 505 211-UEN C Section 4Station communication

415

 Application manual

Page 422: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 422/457

4.2.6.3 Setting parameters

Table 168: DU OD RV N on group settings (basic)

Name Values (Range) Unit Step Default Description

Operation Off  On

- - Off Operation Off / On

IPAddress 0 - 18 IP Address

1 192.168.7.10 IP-Address

IPMask 0 - 18 IP Address

1 255.255.255.0 IP-Mask

4.3 LON communication protocol

4.3.1 Application

Control Center 

IED IEDIED

Gateway

Star coupler RER 111

Station HSIMicroSCADA

IEC05000663-1-en.vsd

IEC05000663 V2 EN

Figure 153: Example of LON communication structure for a substation automation system 

An optical network can be used within the substation automation system. Thisenables communication with the IEDs in the 670 series through the LON bus fromthe operator’s workplace, from the control center and also from other IEDs via bay-to-bay horizontal communication.

The fibre optic LON bus is implemented using either glass core or plastic core fibreoptic cables.

Section 4 1MRK 505 211-UEN C

Station communication

416

 Application manual

Page 423: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 423/457

T ab le 169 : S pe cific ation of th e fibre optic co nne cto rs

Glass fibre Plastic fibre

Cable connector ST-connector snap-in connector  

Cable diameter 62.5/125 m 1 mmMax. cable length 1000 m 10 m

Wavelength 820-900 nm 660 nm

Transmitted power -13 dBm (HFBR-1414) -13 dBm (HFBR-1521)

Receiver sensitivity -24 dBm (HFBR-2412) -20 dBm (HFBR-2521)

The LON ProtocolThe LON protocol is specified in the LonTalkProtocol Specification Version 3from Echelon Corporation. This protocol is designed for communication in control

networks and is a peer-to-peer protocol where all the devices connected to thenetwork can communicate with each other directly. For more information of the bay-to-bay communication, refer to the section Multiple command function.

Hardware and software modulesThe hardware needed for applying LON communication depends on theapplication, but one very central unit needed is the LON Star Coupler and opticalfibres connecting the star coupler to the IEDs. To interface the IEDs fromMicroSCADA, the application library LIB670 is required.

The HV Control 670 software module is included in the LIB520 high-voltage process package, which is a part of the Application Software Library within

MicroSCADA applications.

The HV Control 670 software module is used for control functions in IEDs in the670 series. This module contains the process picture, dialogues and a tool togenerate the process database for the control application in MicroSCADA.

Use the LON Network Tool (LNT) to set the LON communication. This is asoftware tool applied as one node on the LON bus. To communicate via LON, theIEDs need to know

• The node addresses of the other connected IEDs.• The network variable selectors to be used.

This is organized by LNT.

The node address is transferred to LNT via the local HMI by setting the parameter ServicePinMsg = Yes. The node address is sent to LNT via the LON bus, or LNTcan scan the network for new nodes.

The communication speed of the LON bus is set to the default of 1.25 Mbit/s. Thiscan be changed by LNT.

1MRK 505 211-UEN C Section 4Station communication

417

 Application manual

Page 424: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 424/457

4.3.2 Setting parameters

Table 170: HO RZC OM M N on group settings (basic)

Name Values (Range) Unit Step Default DescriptionOperation Off  

On- - Off Operation

Table 171: ADE Non group settings (basic)

Name Values (Range) Unit Step Default Description

Operation Off  On

- - Off Operation

TimerClass SlowNormalFast

- - Slow Timer class

4.4 SPA communication protocol

4.4.1 Application

SPA communication protocol as an alternative to IEC 60870-5-103. The samecommunication port as for IEC 60870-5-103 is used.

SPA communication is applied using the front communication port. For this

 purpose, no serial communication module is required in the IED. Only PCM600software in the PC and a crossed-over Ethernet cable for front connection is required.

When communicating with a PC (as shown in figure 155), using the rear SPA porton the serial communication module (SLM), the only hardware required for a localmonitoring system is:

• Optical fibres for the SPA bus loop• Optical/electrical converter for the PC• PC

A remote monitoring system for communication over the public telephone network also requires telephone modems and a remote PC.

The software required for a local monitoring system is PCM600, and for a remotemonitoring system it is PCM600 in the remote PC only.

Section 4 1MRK 505 211-UEN C

Station communication

418

 Application manual

Page 425: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 425/457

Local monitoring

system with

PCM600

IED IEDIED

Optical to electrical

converter, e.g. SPA-ZC 22

or Fiberdata modem

Teleph

one

modem

Teleph

one

modem

Remote monitoring

system with

PCM600

en05000672.vsd

IEC05000672 V2 EN

Figure 154: SPA communication structure for a monitoring system. The 

monitoring system can either be local, remote or a combination of 

both 

When communicating with a PC connected to the utility substation LAN, via WANand the utility office LAN, as shown in figure 155, and using the rear Ethernet porton the optical Ethernet module (OEM), the only hardware required for a stationmonitoring system is:

• Optical fibres from the IED to the utility substation LAN.• PC connected to the utility office LAN.

The software required is PCM600.

IED IEDIED

Substation LAN

en05000715.vsd

Remote

monitoring

system with

PCM600

Utility LAN

WAN

IEC05000715 V2 EN

Figure 155: SPA communication structure for a remote monitoring system via a 

substation LAN, WAN and utility LAN 

The SPA communication is mainly used for the Station Monitoring System. It caninclude different IEDs with remote communication possibilities. Connection to acomputer (PC) can be made directly (if the PC is located in the substation) or bytelephone modem through a telephone network with ITU (former CCITT)characteristics or via a LAN/WAN connection.

1MRK 505 211-UEN C Section 4Station communication

419

 Application manual

Page 426: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 426/457

glass <1000 m according to optical budget

plastic <20 m (inside cubicle) according to optical budget

FunctionalityThe SPA protocol V2.5 is an ASCII-based protocol for serial communication. Thecommunication is based on a master-slave principle, where the IED is a slave andthe PC is the master. Only one master can be applied on each fibre optic loop. A

 program is required in the master computer for interpretation of the SPA-bus codesand for translation of the data that should be sent to the IED.

For the specification of the SPA protocol V2.5, refer to SPA-bus CommunicationProtocol V2.5.

4.4.2 Setting guidelines

The setting parameters for the SPA communication are set via the local HMI.

SPA, IEC 60870-5-103 and DNP3 uses the same rear communication port. Set the parameter Operation, under Main menu /Settings /General settings /

Communication /SLM configuration /Rear optical SPA-IEC-DNP port /

Protocol selection to the selected protocol.

When the communication protocols have been selected, the IED is automaticallyrestarted.

The most important settings in the IED for SPA communication are the slavenumber and baud rate (communication speed). These settings are absolutelyessential for all communication contact to the IED.

These settings can only be done on the local HMI for rear channel communicationand for front channel communication.

The slave number can be set to any value from 1 to 899, as long as the slavenumber is unique within the used SPA loop.

The baud rate, which is the communication speed, can be set to between 300 and38400 baud. Refer to technical data to determine the rated communication speed

for the selected communication interfaces. The baud rate should be the same for thewhole station, although different baud rates in a loop are possible. If different baudrates in the same fibre optical loop or RS485 network are used, consider this whenmaking the communication setup in the communication master, the PC.

For local fibre optic communication, 19200 or 38400 baud is the normal setting. If telephone communication is used, the communication speed depends on the qualityof the connection and on the type of modem used. But remember that the IED doesnot adapt its speed to the actual communication conditions, because the speed is seton the local HMI.

Section 4 1MRK 505 211-UEN C

Station communication

420

 Application manual

Page 427: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 427/457

4.4.3 Setting parameters

Table 172: SPA Non group settings (basic)

Name Values (Range) Unit Step Default DescriptionSlaveAddress 1 - 899 - 1 30 Slave address

BaudRate 300 Bd1200 Bd2400 Bd4800 Bd9600 Bd19200 Bd38400 Bd

- - 9600 Bd Baudrate on serial line

Table 173: LO NSPA Non group settings (basic)

Name Values (Range) Unit Step Default Description

Operation Off  On

- - Off Operation

SlaveAddress 1 - 899 - 1 30 Slave address

4.5 IEC 60870-5-103 communication protocol

4.5.1 Application

TCP/IP

Control Center 

IED IEDIED

Gateway

Star coupler RER 125

Station HSI

en05000660.vsd

IEC05000660 V3 EN

Figure 156: Example of IEC 60870-5-103 communication structure for a 

substation automation system 

1MRK 505 211-UEN C Section 4Station communication

421

 Application manual

Page 428: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 428/457

IEC 60870-5-103 communication protocol is mainly used when a protection IEDcommunicates with a third party control or monitoring system. This system musthave software that can interpret the IEC 60870-5-103 communication messages.

FunctionalityIEC 60870-5-103 is an unbalanced (master-slave) protocol for coded-bit serialcommunication exchanging information with a control system. In IEC terminologya primary station is a master and a secondary station is a slave. The communicationis based on a point-to-point principle. The master must have software that caninterpret the IEC 60870-5-103 communication messages. For detailed informationabout IEC 60870-5-103, refer to IEC60870 standard part 5: Transmission

 protocols, and to the section 103, Companion standard for the informative interfaceof protection equipment.

Design

GeneralThe protocol implementation consists of the following functions:

• Event handling• Report of analog service values (measurands)• Fault location• Command handling

• Autorecloser ON/OFF• Teleprotection ON/OFF• Protection ON/OFF

• LED reset• Characteristics 1 - 4 (Setting groups)

• File transfer (disturbance files)• Time synchronization

HardwareWhen communicating locally with a Personal Computer (PC) or a RemoteTerminal Unit (RTU) in the station, using the SPA/IEC port, the only hardwareneeded is:· Optical fibres, glass/plastic· Opto/electrical converter for the PC/RTU·PC/RTU

CommandsThe commands defined in the IEC 60870-5-103 protocol are represented in adedicated function blocks. These blocks have output signals for all availablecommands according to the protocol.

• IED commands in control direction

Function block with defined IED functions in control direction, I103IEDCMD.This block use PARAMETR as FUNCTION TYPE, and INFORMATION

 NUMBER parameter is defined for each output signal.

Section 4 1MRK 505 211-UEN C

Station communication

422

 Application manual

Page 429: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 429/457

• Function commands in control direction

Function block with pre defined functions in control direction, I103CMD. This

 block includes the FUNCTION TYPE parameter, and the INFORMATION NUMBER parameter is defined for each output signal.

• Function commands in control direction

Function block with user defined functions in control direction, I103UserCMD.These function blocks include the FUNCTION TYPE parameter for each block inthe private range, and the INFORMATION NUMBER parameter for each outputsignal.

StatusThe events created in the IED available for the IEC 60870-5-103 protocol are

 based on the:

• IED status indication in monitor direction

Function block with defined IED functions in monitor direction, I103IED. This block use PARAMETER as FUNCTION TYPE, and INFORMATION NUMBER  parameter is defined for each input signal.

• Function status indication in monitor direction, user-defined

Function blocks with user defined input signals in monitor direction, I103UserDef.

These function blocks include the FUNCTION TYPE parameter for each block inthe private range, and the INFORMATION NUMBER parameter for each inputsignal.

• Supervision indications in monitor direction

Function block with defined functions for supervision indications in monitor direction, I103Superv. This block includes the FUNCTION TYPE parameter, andthe INFORMATION NUMBER parameter is defined for each output signal.

• Earth fault indications in monitor direction

Function block with defined functions for earth fault indications in monitor direction, I103EF. This block includes the FUNCTION TYPE parameter, and theINFORMATION NUMBER parameter is defined for each output signal.

• Fault indications in monitor direction, type 1

Function block with defined functions for fault indications in monitor direction,I103FltDis. This block includes the FUNCTION TYPE parameter, and theINFORMATION NUMBER parameter is defined for each input signal. This block is suitable for distance protection function.

1MRK 505 211-UEN C Section 4Station communication

423

 Application manual

Page 430: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 430/457

Page 431: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 431/457

to the disturbance function blocks A1RADR to A4RADR. The eight first ones belong to the public range and the remaining ones to the private range.

Settings

Settings from the local HMISPA, IEC 60870-5-103 and DNP3 uses the same rear communication port. Set the

 parameter Operation, under Main menu/Settings /General settings /

Communication /SLM configuration /Rear optical SPA-IEC-DNP port /

Protocol selection to the selected protocol.

When the communication protocols have been selected, the IED is automaticallyrestarted.

The general settings for IEC 60870-5-103 communication are the following:

• SlaveAddress and BaudRate: Settings for slave number and communicationspeed (baud rate).The slave number can be set to any value between 1 and 31. Thecommunication speed, can be set either to 9600 bits/s or 19200 bits/s.

• RevPolarity: Setting for inverting the light (or not).• CycMeasRepTime: Setting for CycMeasRepTime must be coordinated with the

 xDbRepInt and xAngDbRepInt reporting setting on the MMXU measurementfunction blocks. See I103MEAS function block for more information.

• EventRepMode: Defines the mode for how events are reported.

Event reporting modeThe settings for communication parameters slave number and baud rate can befound on the local HMI under: Main menu/Settings /General settings /

Communication /SLM configuration /Rear optical SPA-IEC-DNP port /

Protocol selection to the selected protocol

Settings from PCM600EventFor each input of the Event (EVENT) function there is a setting for the informationnumber of the connected signal. The information number can be set to any value

 between 0 and 255. To get proper operation of the sequence of events the event

masks in the event function is to be set to ON_CHANGE. For single-commandsignals, the event mask is to be set to ON_SET.

In addition there is a setting on each event block for function type. Refer todescription of the Main Function type set on the local HMI.

CommandsAs for the commands defined in the protocol there is a dedicated function block with eight output signals. Use PCM600 to configure these signals. To realize theBlockOfInformation command, which is operated from the local HMI, the outputBLKINFO on the IEC command function block ICOM has to be connected to an

1MRK 505 211-UEN C Section 4Station communication

425

 Application manual

Page 432: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 432/457

input on an event function block. This input must have the information number 20(monitor direction blocked) according to the standard.

Disturbance Recordings

For each input of the Disturbance recorder function there is a setting for theinformation number of the connected signal. The information number can be set toany value between 0 and 255.

Furthermore, there is a setting on each input of the Disturbance recorder functionfor the function type. Refer to description of Main Function type set on the local HMI.

Function and information typesThe function type is defined as follows:

128 = distance protection

160 = overcurrent protection

176 = transformer differential protection

192 = line differential protection

Refer to the tables in the Technical reference manual /Station communication,specifying the information types supported by the communication protocol IEC60870-5-103.

To support the information, corresponding functions must be included in the protection IED.

There is no representation for the following parts:

• Generating events for test mode• Cause of transmission: Info no 11, Local operation

EIA RS-485 is not supported. Glass or plastic fibre should be used. BFOC/2.5 isthe recommended interface to use (BFOC/2.5 is the same as ST connectors). STconnectors are used with the optical power as specified in standard.

For more information, refer to IEC standard IEC 60870-5-103.

4.5.2 Setting parameters

T ab le 1 74 : IE C60 870 -5 -1 03 N on g ro up se ttin gs (b as ic)

Name Values (Range) Unit Step Default Description

SlaveAddress 0 - 255 - 1 30 Slave address

BaudRate 9600 Bd19200 Bd

- - 9600 Bd Baudrate on serial line

RevPolarity Off  On

- - On Invert polarity

CycMeasRepTime 1.0 - 3600.0 - 0.1 5.0 Cyclic reporting time of measurments

Section 4 1MRK 505 211-UEN C

Station communication

426

 Application manual

Page 433: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 433/457

Table 175: I103IED CM D N on group settings (basic)

Name Values (Range) Unit Step Default Description

FUNTYPE 1 - 255 FunT 1 255 Function type (1-255)

Table 176: I103C MD Non group settings (basic)

Name Values (Range) Unit Step Default Description

FUNTYPE 1 - 255 FunT 1 1 Function type (1-255)

Table 177: I103U SR CM D Non group settings (basic)

Name Values (Range) Unit Step Default Description

PULSEMOD 0 - 1 Mode 1 1 Pulse mode 0=Steady, 1=Pulsed

T 0.200 - 60.000 s 0.001 0.400 Pulse length

FUNTYPE 1 - 255 FunT 1 1 Function type (1-255)

INFNO_1 1 - 255 InfNo 1 1 Information number for output 1 (1-255)

INFNO_2 1 - 255 InfNo 1 2 Information number for output 2 (1-255)

INFNO_3 1 - 255 InfNo 1 3 Information number for output 3 (1-255)

INFNO_4 1 - 255 InfNo 1 4 Information number for output 4 (1-255)

INFNO_5 1 - 255 InfNo 1 5 Information number for output 5 (1-255)

INFNO_6 1 - 255 InfNo 1 6 Information number for output 6 (1-255)

INFNO_7 1 - 255 InfNo 1 7 Information number for output 7 (1-255)

INFNO_8 1 - 255 InfNo 1 8 Information number for output 8 (1-255)

Table 178: I103IED Non group settings (basic)

Name Values (Range) Unit Step Default Description

FUNTYPE 1 - 255 FunT 1 1 Function type (1-255)

Table 179: I103U SR DEF Non group settings (basic)

Name Values (Range) Unit Step Default Description

FUNTYPE 1 - 255 FunT 1 5 Function type (1-255)

INFNO_1 1 - 255 InfNo 1 1 Information number for binary input 1(1-255)

INFNO_2 1 - 255 InfNo 1 2 Information number for binary input 2(1-255)

INFNO_3 1 - 255 InfNo 1 3 Information number for binary input 3(1-255)

INFNO_4 1 - 255 InfNo 1 4 Information number for binary input 4(1-255)

INFNO_5 1 - 255 InfNo 1 5 Information number for binary input 5(1-255)

Table continues on next page

1MRK 505 211-UEN C Section 4Station communication

427

 Application manual

Page 434: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 434/457

Name Values (Range) Unit Step Default Description

INFNO_6 1 - 255 InfNo 1 6 Information number for binary input 6(1-255)

INFNO_7 1 - 255 InfNo 1 7 Information number for binary input 7

(1-255)

INFNO_8 1 - 255 InfNo 1 8 Information number for binary input 8(1-255)

Table 180: I103S UPE RV Non group settings (basic)

Name Values (Range) Unit Step Default Description

FUNTYPE 1 - 255 FunT 1 1 Function type (1-255)

Table 181: I103E F N on group settings (basic)

Name Values (Range) Unit Step Default Description

FUNTYPE 1 - 255 FunT 1 160 Function type (1-255)

Table 182: I103F LTD IS Non group settings (basic)

Name Values (Range) Unit Step Default Description

FUNTYPE 1 - 255 FunT 1 128 Function type (1-255)

Table 183: I103F LTS TD Non group settings (basic)

Name Values (Range) Unit Step Default Description

FUNTYPE 1 - 255 FunT 1 1 Function type (1-255)

Table 184: I103A R Non group settings (basic)

Name Values (Range) Unit Step Default Description

FUNTYPE 1 - 255 FunT 1 1 Function type (1-255)

Table 185: I103M EA S N on group settings (basic)

Name Values (Range) Unit Step Default Description

RatedIL1 1 - 99999 A 1 3000 Rated current phase L1

RatedIL2 1 - 99999 A 1 3000 Rated current phase L2

RatedIL3 1 - 99999 A 1 3000 Rated current phase L3

RatedIN 1 - 99999 A 1 3000 Rated residual current IN

RatedUL1 0.05 - 2000.00 kV 0.05 230.00 Rated voltage for phase L1

RatedUL2 0.05 - 2000.00 kV 0.05 230.00 Rated voltage for phase L2

RatedUL3 0.05 - 2000.00 kV 0.05 230.00 Rated voltage for phase L3

RatedUL1-UL2 0.05 - 2000.00 kV 0.05 400.00 Rated voltage for phase-phase L1-L2

Table continues on next page

Section 4 1MRK 505 211-UEN C

Station communication

428

 Application manual

Page 435: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 435/457

Name Values (Range) Unit Step Default Description

RatedUN 0.05 - 2000.00 kV 0.05 230.00 Rated residual voltage UN

RatedP 0.00 - 2000.00 MW 0.05 1200.00 Rated value for active power  

RatedQ 0.00 - 2000.00 MVA 0.05 1200.00 Rated value for reactive power  

RatedF 50.0 - 60.0 Hz 10.0 50.0 Rated system frequency

FUNTYPE 1 - 255 FunT 1 1 Function type (1-255)

Table 186: I103M EAS US R N on group settings (basic)

Name Values (Range) Unit Step Default Description

FUNTYPE 1 - 255 FunT 1 25 Function type (1-255)

INFNO 1 - 255 InfNo 1 1 Information number for measurands(1-255)

RatedMeasur1 0.05 -

10000000000.00

- 0.05 1000.00 Rated value for measurement on input 1

RatedMeasur2 0.05 -10000000000.00

- 0.05 1000.00 Rated value for measurement on input 2

RatedMeasur3 0.05 -10000000000.00

- 0.05 1000.00 Rated value for measurement on input 3

RatedMeasur4 0.05 -10000000000.00

- 0.05 1000.00 Rated value for measurement on input 4

RatedMeasur5 0.05 -10000000000.00

- 0.05 1000.00 Rated value for measurement on input 5

RatedMeasur6 0.05 -10000000000.00

- 0.05 1000.00 Rated value for measurement on input 6

RatedMeasur7 0.05 -10000000000.00

- 0.05 1000.00 Rated value for measurement on input 7

RatedMeasur8 0.05 -10000000000.00

- 0.05 1000.00 Rated value for measurement on input 8

RatedMeasur9 0.05 -10000000000.00

- 0.05 1000.00 Rated value for measurement on input 9

4.6 Multiple command and transmit MULTICMDRCV,

MULTICMDSND

Function description IEC 61850

identification

IEC 60617

identification

ANSI/IEEE C37.2

device number

Multiple command and transmit MULTICMDRCV - -

Multiple command and transmit MULTICMDSND - -

1MRK 505 211-UEN C Section 4Station communication

429

 Application manual

Page 436: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 436/457

Page 437: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 437/457

Section 5 Remote communication

About this chapter

This chapter describes the remote end data communication possibilities through binary signal transferring.

5.1 Binary signal transfer

Function description IEC 61850

identification

IEC 60617

identification

ANSI/IEEE C37.2

device number

Binary signal transfer BinSignReceive - -

Binary signal transfer BinSignTransm - -

5.1.1 Application

The IEDs can be equipped with communication devices for line differentialcommunication and/or communication of binary signals between IEDs. The samecommunication hardware is used for both purposes.

Communication between two IEDs geographically on different locations is afundamental part of the line differential function.

Sending of binary signals between two IEDs, one in each end of a power line isused in teleprotection schemes and for direct transfer trips. In addition to this, thereare application possibilities, for example, blocking/enabling functionality in theremote substation, changing setting group in the remote IED depending on theswitching situation in the local substation and so on.

When equipped with a LDCM, a 64 kbit/s communication channel can beconnected to the IED, which will then have the capacity of 192 binary signals to be

communicated with a remote IED.

5.1.1.1 Communication hardware solutions

The LDCM (Line Data Communication Module) has an optical connection suchthat two IEDs can be connected over a direct fibre (multimode), as shown in figure157. The protocol used is IEEE/ANSI C37.94. The distance with this solution istypical 110 km.

1MRK 505 211-UEN C Section 5Remote communication

431

 Application manual

Page 438: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 438/457

   L   D  C   M

   L   D  C   M

   L   D  C   M

   L   D  C   M

   L   D  C   M

   L   D  C   M

   L   D  C   M

   L   D  C   M

   L   D  C   M

   L   D  C   M

   L   D  C   M

   L   D  C   M

   L   D  C   M

   L   D  C   M

   L   D  C   M

   L   D  C   M

en06000519-2.vsd

IEC06000519 V2 EN

Figure 157: Direct fibre optical connection between two IEDs with LDCM 

The LDCM can also be used together with an external optical to galvanic G.703converter or with an alternative external optical to galvanic X.21 converter asshown in figure 158. These solutions are aimed for connections to a multiplexer,which in turn is connected to a telecommunications transmission network (for example, SDH or PDH).

   L   D  C   M

   L   D  C   M

   L   D  C   M

   L   D  C   M

Telecom. Network

*) *)

Multiplexer Multiplexer  

   L   D  C   M

   L   D  C   M

   L   D  C   M

   L   D  C   M

   L   D  C   M

   L   D  C   M

   L   D  C   M

   L   D  C   M

   L   D  C   M

   L   D  C   M

   L   D  C   M

   L   D  C   M

en05000527.vsd

*) Converting optical to galvanic G.703 or X.21 alternatively

IEC05000527 V1 EN

Figure 158: LDCM with an external optical to galvanic converter and a multiplexer 

When an external modem G.703 or X21 is used, the connection between LDCM

and the modem is made with a multimode fibre of max. 3 km length. The IEEE/ANSI C37.94 protocol is always used between LDCM and the modem.

Alternatively, a LDCM with X.21 built-in converter and micro D-sub 15-poleconnector output can be used.

5.1.1.2 Application possibility with one-phase REB670

For busbar protection applications in substations where dynamic zone selection isrequired, it is typically necessary to wire the normally open and normally closed

Section 5 1MRK 505 211-UEN C

Remote communication

432

 Application manual

Page 439: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 439/457

auxiliary contacts from every monitored disconnector and/or circuit breaker to theoptocoupler inputs of the busbar protection. When one phase version of REB670 isused, then six optocoupler inputs (that is, two in each phase/IED) are required for every primary switchgear object. For big stations (for example, with 24 bays) thiswill require quite a lot of binary inputs into every IED. To limit the number of required optocoupler inputs into every IED it is possible to use LDCMcommunication modules to effectively share the binary Ios between three units, asshown in figure 159159.

IEC06000198 V1 EN

Figure 159: Example how to share binary IO between one-phase REB670 IEDs 

by using LDCM modules 

As shown in figure 159, it is possible to wire only the status for bays 01-08 to L1-IED. After that the information about auxiliary contact status for switchgear objects

from these eight bays can be sent via LDCM modules to other two phases. In thesimilar way information from other bays can be only wired to L2, respectively L3

 phase IED and then shared to the other two phases via LDCM communication.

Typical LDCM communication delay between two IEDs is in order of 30-40 ms. Note that for disconnector status this delay will not pose any practical problems.However, time delay caused by LDCM communication can be crucial for circuit

 breakers status. In such cases it is strongly recommended that at least the circuit breaker closing command from every circuit breaker is directly wired to all three phases/IEDs to minimize any risk for unwanted operation of the busbar differential

1MRK 505 211-UEN C Section 5Remote communication

433

 Application manual

Page 440: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 440/457

 protection zones due to late inclusion of respective bay current into the differentialmeasuring circuit.

5.1.2 Setting guidelines

ChannelMode: This parameter can be set On or Off . Besides this, it can be setOutOfService which signifies that the local LDCM is out of service. Thus, with thissetting, the communication channel is active and a message is sent to the remoteIED that the local IED is out of service, but there is no COMFAIL signal and theanalog and binary values are sent as zero.

TerminalNo: This setting shall be used to assign an unique address to each LDCM,in all current differential IEDs. Up to 256 LDCMs can be assigned a uniquenumber. Consider a local IED with two LDCMs:

• LDCM for slot 302: Set TerminalNo to 1 and RemoteTermNo to 2• LDCM for slot 303: Set TerminalNo to 3 and RemoteTermNo to 4

In multiterminal current differential applications, with 4 LDCMs in each IED, up to20 unique addresses must be set.

The unique address is necessary to give high security againstincorrect addressing in the communication system. Using the samenumber for setting TerminalNo in some of the LDCMs, a loop-back test in the communication system can give incorrect trip.

 RemoteTermNo: This setting assigns a number to each related LDCM in the remoteIED. For each LDCM, the parameter  RemoteTermNo shall be set to a differentvalue than parameter TerminalNo, but equal to the TerminalNo of the remote endLDCM. In the remote IED the TerminalNo and RemoteTermNo settings arereversed as follows:

• LDCM for slot 302: Set TerminalNo to 2 and RemoteTermNo to 1• LDCM for slot 303: Set TerminalNo to 4 and RemoteTermNo to 3

The redundant channel is always configured in the lower position,for example

• Slot 302: Main channel• Slot 303: Redundant channel

The same is applicable for slot 312-313 and slot 322-323.

 DiffSync: Here the method of time synchronization, Echo or GPS , for the linedifferential function is selected.

Section 5 1MRK 505 211-UEN C

Remote communication

434

 Application manual

Page 441: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 441/457

GPSSyncErr : If GPS synchronization is lost, the synchronization of the linedifferential function will continue during 16 s. based on the stability in the localIED clocks. Thereafter the setting Block will block the line differential function or the setting Echo will make it continue by using the Echo synchronization method.It shall be noticed that using Echo in this situation is only safe as long as there is norisk of varying transmission asymmetry.

CommSync: This setting decides the Master or Slave relation in the communicationsystem and shall not be mistaken for the synchronization of line differential currentsamples. When direct fibre is used, one LDCM is set as Master and the other oneas Slave. When a modem and multiplexer is used, the IED is always set as Slave, asthe telecommunication system will provide the clock master.

OptoPower : The setting LowPower is used for fibres 0 – 1 km and HighPower for fibres >1 km.

TransmCurr : This setting decides which of 2 possible local currents that shall betransmitted, or if and how the sum of 2 local currents shall be transmitted, or finally if the channel shall be used as a redundant channel.

In a 1½ breaker arrangement, there will be 2 local currents, and the earthing on theCTs can be different for these. CT-SUM will transmit the sum of the 2 CT groups.CT-DIFF1 will transmit CT group 1 minus CT group 2 and CT-DIFF2 willtransmit CT group 2 minus CT group 1.

CT-GRP1 or CT-GRP2 will transmit the respective CT group, and the setting RedundantChannel makes the channel be used as a backup channel.

ComFailAlrmDel : Time delay of communication failure alarm. In communicationsystems, route switching can sometimes cause interruptions with a duration up to50 ms. Thus, a too short time delay setting might cause nuisance alarms in thesesituations.

ComFailResDel : Time delay of communication failure alarm reset.

 RedChSwTime: Time delay before switchover to a redundant channel in case of  primary channel failure.

 RedChRturnTime: Time delay before switchback to a the primary channel after channel failure.

 AsymDelay: The asymmetry is defined as transmission delay minus receive delay.If a fixed asymmetry is known, the Echo synchronization method can be used if the

 parameter  AsymDelay is properly set. From the definition follows that theasymmetry will always be positive in one end, and negative in the other end.

 AnalogLatency: Local analog latency; A parameter which specifies the time delay(number of samples) between actual sampling and the time the sample reaches thelocal communication module, LDCM. The parameter shall be set to 2 whentransmitting analog data from the local transformer module, TRM. .

1MRK 505 211-UEN C Section 5Remote communication

435

 Application manual

Page 442: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 442/457

 RemAinLatency: Remote analog latency; This parameter corresponds to the LocAinLatency set in the remote IED.

 MaxTransmDelay: Data for maximum 40 ms transmission delay can be buffered

up. Delay times in the range of some ms are common. It shall be noticed that if data arrive in the wrong order, the oldest data will just be disregarded.

CompRange: The set value is the current peak value over which truncation will bemade. To set this value, knowledge of the fault current levels should be known.The setting is not overly critical as it considers very high current values for whichcorrect operation normally still can be achieved.

 MaxtDiffLevel : Allowed maximum time difference between the internal clocks inrespective line end.

5.1.3 Setting parametersT ab le 1 89 : LD CM Re cB in Sta t1 Non gro up se ttin gs (ba sic)

Name Values (Range) Unit Step Default Description

ChannelMode Off  OnOutOfService

- - On Channel mode of LDCM, 0=OFF, 1=ON,2=OutOfService

TerminalNo 0 - 255 - 1 0 Terminal number used for line differentialcommunication

RemoteTermNo 0 - 255 - 1 0 Terminal number on remote terminal

CommSync SlaveMaster 

- - Slave Com Synchronization mode of LDCM,0=Slave, 1=Master 

OptoPower LowPower  HighPower 

- - LowPower Transmission power for LDCM, 0=Low,1=High

ComFailAlrmDel 5 - 500 ms 5 100 Time delay before communication error  signal is activated

ComFailResDel 5 - 500 ms 5 100 Reset delay before communication error  signal is reset

InvertPolX21 Off  On

- - Off Invert polarization for X21 communication

T ab le 1 90 : LD CM Re cB in Sta t2 Non gro up se ttin gs (ba sic)

Name Values (Range) Unit Step Default Description

ChannelMode Off  OnOutOfService

- - On Channel mode of LDCM, 0=OFF, 1=ON,2=OutOfService

NAMECH1 0 - 13 - 1 LDCM#-CH1 User define string for analogue input 1

TerminalNo 0 - 255 - 1 0 Terminal number used for line differentialcommunication

RemoteTermNo 0 - 255 - 1 0 Terminal number on remote terminal

NAMECH2 0 - 13 - 1 LDCM#-CH2 User define string for analogue input 2

Table continues on next page

Section 5 1MRK 505 211-UEN C

Remote communication

436

 Application manual

Page 443: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 443/457

Name Values (Range) Unit Step Default Description

DiffSync EchoGPS

- - Echo Diff Synchronization mode of LDCM,0=ECHO, 1=GPS

GPSSyncErr Block

Echo

- - Block Operation mode when GPS

synchroniation signal is lost

CommSync SlaveMaster 

- - Slave Com Synchronization mode of LDCM,0=Slave, 1=Master 

NAMECH3 0 - 13 - 1 LDCM#-CH3 User define string for analogue input 3

OptoPower LowPower  HighPower 

- - LowPower Transmission power for LDCM, 0=Low,1=High

NAMECH4 0 - 13 - 1 LDCM#-CH4 User define string for analogue input 4

TransmCurr CT-GRP1CT-GRP2CT-SUMCT-DIFF1CT-DIFF2

- - CT-GRP1 Summation mode for transmitted currentvalues

ComFailAlrmDel 5 - 500 ms 5 100 Time delay before communication error  signal is activated

ComFailResDel 5 - 500 ms 5 100 Reset delay before communication error  signal is reset

RedChSwTime 5 - 500 ms 5 5 Time delay before switching inredundant channel

RedChRturnTime 5 - 500 ms 5 100 Time delay before switching back fromredundant channel

 AsymDelay -20.00 - 20.00 ms 0.01 0.00 Asymmetric delay when communicationuse echo synch.

 AnalogLatency 2 - 20 - 1 2 Latency between local analogue dataand transmitted

remAinLatency 2 - 20 - 1 2 Analog latency of remote terminal

MaxTransmDelay 0 - 40 ms 1 20 Max allowed transmission delay

CompRange 0-10kA0-25kA0-50kA0-150kA

- - 0-25kA Compression range

MaxtDiffLevel 200 - 2000 us 1 600 Maximum time diff for ECHO back-up

DeadbandtDiff 200 - 1000 us 1 300 Deadband for t Diff  

InvertPolX21 Off  On

- - Off Invert polarization for X21 communication

T able 1 91 : L DC MR ecB in Sta t3 N on g ro up se ttin gs (b as ic )

Name Values (Range) Unit Step Default Description

ChannelMode Off  OnOutOfService

- - On Channel mode of LDCM, 0=OFF, 1=ON,2=OutOfService

NAMECH1 0 - 13 - 1 LDCM#-CH1 User define string for analogue input 1

TerminalNo 0 - 255 - 1 0 Terminal number used for line differentialcommunication

RemoteTermNo 0 - 255 - 1 0 Terminal number on remote terminal

Table continues on next page

1MRK 505 211-UEN C Section 5Remote communication

437

 Application manual

Page 444: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 444/457

Name Values (Range) Unit Step Default Description

NAMECH2 0 - 13 - 1 LDCM#-CH2 User define string for analogue input 2

DiffSync EchoGPS

- - Echo Diff Synchronization mode of LDCM,0=ECHO, 1=GPS

GPSSyncErr BlockEcho

- - Block Operation mode when GPSsynchroniation signal is lost

CommSync SlaveMaster 

- - Slave Com Synchronization mode of LDCM,0=Slave, 1=Master 

NAMECH3 0 - 13 - 1 LDCM#-CH3 User define string for analogue input 3

OptoPower LowPower  HighPower 

- - LowPower Transmission power for LDCM, 0=Low,1=High

NAMECH4 0 - 13 - 1 LDCM#-CH4 User define string for analogue input 4

TransmCurr CT-GRP1CT-GRP2CT-SUMCT-DIFF1

CT-DIFF2RedundantChannel

- - CT-GRP1 Summation mode for transmitted currentvalues

ComFailAlrmDel 5 - 500 ms 5 100 Time delay before communication error  signal is activated

ComFailResDel 5 - 500 ms 5 100 Reset delay before communication error  signal is reset

RedChSwTime 5 - 500 ms 5 5 Time delay before switching inredundant channel

RedChRturnTime 5 - 500 ms 5 100 Time delay before switching back fromredundant channel

 AsymDelay -20.00 - 20.00 ms 0.01 0.00 Asymmetric delay when communicationuse echo synch.

 AnalogLatency 2 - 20 - 1 2 Latency between local analogue dataand transmitted

remAinLatency 2 - 20 - 1 2 Analog latency of remote terminal

MaxTransmDelay 0 - 40 ms 1 20 Max allowed transmission delay

CompRange 0-10kA0-25kA0-50kA0-150kA

- - 0-25kA Compression range

MaxtDiffLevel 200 - 2000 us 1 600 Maximum time diff for ECHO back-up

DeadbandtDiff 200 - 1000 us 1 300 Deadband for t Diff  

InvertPolX21 Off  

On

- - Off Invert polarization for X21 communication

Section 5 1MRK 505 211-UEN C

Remote communication

438

 Application manual

Page 445: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 445/457

Section 6 Configuration

About this chapter

This chapter describes the IED configurations.

6.1 Description of configuration REB670

6.1.1 Description of 3 ph package A20

Three-phase version of the IED with two low-impedance differential protectionzones and four three-phase CT inputs A20. The version is intended for simpler applications such as T-connections, meshed corners, and so on.

6.1.2 Description of 3 ph package A31

Three-phase version of the IED with two low-impedance differential protectionzones and eight three-phase CT inputs A31. The version is intended for applications on smaller busbars, with up to two zones and eight CT inputs.

6.1.3 Description of 1 ph packages B20 and B21

One-phase version of the IED with two low-impedance differential protectionzones and twelve CT inputs B20, B21.

• Due to three available binary input modules, the B20 is intended for applications without need for dynamic Zone Selection such as substations withsingle busbar with or without bus-section breaker, one-and-half breaker or double breaker arrangements. Three such IEDs offer cost effective solutionsfor such simple substation arrangements with up to twelve CT inputs.

• The B21 is intended for applications in substations where dynamic Zone

Selection or bigger number of binary inputs and outputs is needed. Suchstations for example are double busbar station with or without transfer buswith up to 12 CT inputs. Note that binary inputs can be shared between phases

 by including the LDCM communication module. This simplifies panel wiringand saves IO boards.

• This version can be used with external auxiliary 3-phase to 1-phase summationcurrent transformers with different turns ratio for each phase.

1MRK 505 211-UEN C Section 6Configuration

439

 Application manual

Page 446: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 446/457

6.1.4 Description of 1 ph package B31

One-phase version of the IED with two low-impedance differential protectionzones and twenty-four CT inputs B31.

• The IED is intended for busbar protection applications in big substationswhere dynamic Zone Selection, quite large number of binary inputs andoutputs and many CT inputs are needed. The IED includes two differentialzones and twenty-four CT inputs. Note that binary inputs can be shared

 between phases by including the LDCM communication module. Thissimplifies panel wiring and saves IO boards.

• This version can be used with external auxiliary 3-phase to 1-phase summationcurrent transformers with different turns ratio for each phase.

6.1.5 Available configurations for pre-configured REB670

Three configurations have been made available for pre-configured REB670 IED. Itshall be noted that all three configurations include the following features:

• fully configured for the total available number of bays in each REB670 variant• facility to take any bay out of service via the local HMI or externally via

 binary input• facility to block any of the two zones via the local HMI or externally via

 binary input

• facility to block all bay trips via the local HMI or externally via binary input, but leaving all other function in service (that is BBP Zones, BFP and OCPwhere applicable)

• facility to externally initiate built-in disturbance recorder • facility to connect external breaker failure backup trip signal from every bay• facility to connect external bay trip signal

6.1.6 Configuration X01

• This configuration includes just busbar protection for simple stations layouts

(that is One-and-a-half breaker, Double Breaker or Single Breaker stations).Additionally it can be used for double busbar-single breaker stations wheredisconnector replica is done by using just b auxiliary contact from everydisconnector and/or circuit breakers. As a consequence no disconnector/

 breaker supervision will be available. It is as well possible to adapt thisconfiguration by the Signal Matrix tool to be used as direct replacement of RED521 · 1.0 terminals. This configuration is available for all five REB670variants (that is A20, A31, B20, B21 & B31). It shall be noted that optionalfunctions breaker failure protection CCRBRF, end fault protection andovercurrent protection PH4SPTOC can be ordered together with this

Section 6 1MRK 505 211-UEN C

Configuration

440

 Application manual

Page 447: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 447/457

configuration, but they will not be pre-configured. Thus these optionalfunctions shall be configured by the end user.

6.1.7 Configuration X02

• This configuration includes just busbar protection for double busbar-single breaker stations, where Zone Selection is done by using a and b auxiliarycontacts from every disconnector and/or circuit breaker. Thus full disconnector/

 breaker supervision is available. This configuration is available for only threeREB670 variants (that is A31, B21 and B31). It shall be noted that optionalfunctions breaker failure protection CCRBRF, end fault protection andovercurrent protection PH4SPTOC can be ordered together with thisconfiguration, but they will not be pre-configured. Thus these optionalfunctions shall be configured by the end user.

6.1.8 Configuration X03

• This configuration includes BBP with breaker failure protection CCRBRF, endfault protection and overcurrent protection PH4SPTOC for double busbar-single breaker stations, where Zone Selection is done by using a and bauxiliary contacts from every disconnectors and/or circuit breakers. Thus fulldisconnector/breaker supervision is available. This configuration is availablefor only three REB670 variants (that is A31, B21 and B31).

1MRK 505 211-UEN C Section 6Configuration

441

 Application manual

Page 448: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 448/457

442

Page 449: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 449/457

Section 7 Glossary

About this chapter

This chapter contains a glossary with terms, acronyms and abbreviations used inABB technical documentation.

AC Alternating current

ACT Application configuration tool within PCM600

A/D converter Analog-to-digital converter 

ADBS Amplitude deadband supervisionADM Analog digital conversion module, with time synchronization

AI Analog input

ANSI American National Standards Institute

AR  Autoreclosing

ArgNegRes Setting parameter/ZD/

ArgDir Setting parameter/ZD/

ASCT Auxiliary summation current transformer 

ASD Adaptive signal detectionAWG American Wire Gauge standard

BBP Busbar protection

BFP Breaker failure protection

BI Binary input

BIM Binary input module

BOM Binary output module

BOS Binary outputs status

BR  External bistable relay

BS British Standards

BSR  Binary signal transfer function, receiver blocks

BST Binary signal transfer function, transmit blocks

C37.94 IEEE/ANSI protocol used when sending binary signals between IEDs

CAN Controller Area Network. ISO standard (ISO 11898) for serial communication

CB Circuit breaker 

1MRK 505 211-UEN C Section 7Glossary

443

 Application manual

Page 450: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 450/457

CBM Combined backplane module

CCITT Consultative Committee for International Telegraph andTelephony. A United Nations-sponsored standards body

within the International Telecommunications Union.CCM CAN carrier module

CCVT Capacitive Coupled Voltage Transformer 

Class C Protection Current Transformer class as per IEEE/ ANSI

CMPPS Combined megapulses per second

CMT Communication Management tool in PCM600

CO cycle Close-open cycle

Codirectional Way of transmitting G.703 over a balanced line. Involves

two twisted pairs making it possible to transmit informationin both directions

COMTRADE Standard format according to IEC 60255-24

Contra-directional Way of transmitting G.703 over a balanced line. Involvesfour twisted pairs, two of which are used for transmittingdata in both directions and two for transmitting clock signals

CPU Central processor unit

CR  Carrier receive

CRC Cyclic redundancy check 

CROB Control relay output block CS Carrier send

CT Current transformer 

CVT Capacitive voltage transformer 

DAR  Delayed autoreclosing

DARPA Defense Advanced Research Projects Agency (The USdeveloper of the TCP/IP protocol etc.)

DBDL Dead bus dead line

DBLL Dead bus live lineDC Direct current

DFC Data flow control

DFT Discrete Fourier transform

DHCP Dynamic Host Configuration Protocol

DIP-switch Small switch mounted on a printed circuit board

DI Digital input

DLLB Dead line live bus

Section 7 1MRK 505 211-UEN C

Glossary

444

 Application manual

Page 451: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 451/457

DNP Distributed Network Protocol as per IEEE/ANSI Std.1379-2000

DR  Disturbance recorder 

DRAM Dynamic random access memory

DRH Disturbance report handler 

DSP Digital signal processor 

DTT Direct transfer trip scheme

EHV network  Extra high voltage network 

EIA Electronic Industries Association

EMC Electromagnetic compatibility

EMF (Electric Motive Force)

EMI Electromagnetic interference

EnFP End fault protection

EPA Enhanced performance architecture

ESD Electrostatic discharge

FCB Flow control bit; Frame count bit

FOX 20 Modular 20 channel telecommunication system for speech,data and protection signals

FOX 512/515 Access multiplexer 

FOX 6Plus Compact time-division multiplexer for the transmission of up to seven duplex channels of digital data over optical fibers

G.703 Electrical and functional description for digital lines used by local telephone companies. Can be transported over  balanced and unbalanced lines

GCM Communication interface module with carrier of GPSreceiver module

GDE Graphical display editor within PCM600

GI General interrogation command

GIS Gas-insulated switchgear GOOSE Generic object-oriented substation event

GPS Global positioning system

GSAL Generic security application

GTM GPS Time Module

HDLC protocol High-level data link control, protocol based on the HDLCstandard

HFBR connector

type

Plastic fiber connector 

1MRK 505 211-UEN C Section 7Glossary

445

 Application manual

Page 452: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 452/457

HMI Human-machine interface

HSAR  High speed autoreclosing

HV High-voltage

HVDC High-voltage direct current

IDBS Integrating deadband supervision

IEC International Electrical Committee

IEC 60044-6 IEC Standard, Instrument transformers – Part 6:Requirements for protective current transformers for transient performance

IEC 60870-5-103 Communication standard for protective equipment. A serialmaster/slave protocol for point-to-point communication

IEC 61850 Substation automation communication standardIEC 61850–8–1 Communication protocol standard

IEEE Institute of Electrical and Electronics Engineers

IEEE 802.12 A network technology standard that provides 100 Mbits/son twisted-pair or optical fiber cable

IEEE P1386.1 PCI Mezzanine Card (PMC) standard for local busmodules. References the CMC (IEEE P1386, also known asCommon Mezzanine Card) standard for the mechanics andthe PCI specifications from the PCI SIG (Special InterestGroup) for the electrical EMF (Electromotive force).

IEEE 1686 Standard for Substation Intelligent Electronic Devices(IEDs) Cyber Security Capabilities

IED Intelligent electronic device

I-GIS Intelligent gas-insulated switchgear 

IOM Binary input/output module

Instance When several occurrences of the same function areavailable in the IED, they are referred to as instances of thatfunction. One instance of a function is identical to another of the same kind but has a different number in the IED user 

interfaces. The word "instance" is sometimes defined as anitem of information that is representative of a type. In thesame way an instance of a function in the IED isrepresentative of a type of function.

IP 1. Internet protocol. The network layer for the TCP/IP protocol suite widely used on Ethernet networks. IP is aconnectionless, best-effort packet-switching protocol. It

 provides packet routing, fragmentation and reassemblythrough the data link layer.

2. Ingression protection, according to IEC standard

Section 7 1MRK 505 211-UEN C

Glossary

446

 Application manual

Page 453: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 453/457

IP 20 Ingression protection, according to IEC standard, level 20

IP 40 Ingression protection, according to IEC standard, level 40

IP 54 Ingression protection, according to IEC standard, level 54

IRF Internal failure signal

IRIG-B: InterRange Instrumentation Group Time code format B,standard 200

ITU International Telecommunications Union

LAN Local area network 

LIB 520 High-voltage software module

LCD Liquid crystal display

LDCM Line differential communication module

LDD Local detection device

LED Light-emitting diode

LNT LON network tool

LON Local operating network 

MCB Miniature circuit breaker 

MCM Mezzanine carrier module

MIM Milli-ampere module

MPM Main processing module

MVB Multifunction vehicle bus. Standardized serial busoriginally developed for use in trains.

NCC  National Control Centre

NUM  Numerical module

OCO cycle Open-close-open cycle

OCP Overcurrent protection

OEM Optical ethernet module

OLTC On-load tap changer 

OV Over-voltage

Overreach A term used to describe how the relay behaves during afault condition. For example, a distance relay isoverreaching when the impedance presented to it is smaller than the apparent impedance to the fault applied to the

 balance point, that is, the set reach. The relay “sees” thefault but perhaps it should not have seen it.

PCI Peripheral component interconnect, a local data bus

PCM Pulse code modulation

1MRK 505 211-UEN C Section 7Glossary

447

 Application manual

Page 454: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 454/457

PCM600 Protection and control IED manager 

PC-MIP Mezzanine card standard

PMC PCI Mezzanine card

POR  Permissive overreach

POTT Permissive overreach transfer trip

Process bus Bus or LAN used at the process level, that is, in near  proximity to the measured and/or controlled components

PSM Power supply module

PST Parameter setting tool within PCM600

PT ratio Potential transformer or voltage transformer ratio

PUTT Permissive underreach transfer trip

RASC Synchrocheck relay, COMBIFLEX

RCA Relay characteristic angle

RFPP Resistance for phase-to-phase faults

RFPE Resistance for phase-to-earth faults

RISC Reduced instruction set computer 

RMS value Root mean square value

RS422 A balanced serial interface for the transmission of digitaldata in point-to-point connections

RS485 Serial link according to EIA standard RS485

RTC Real-time clock 

RTU Remote terminal unit

SA Substation Automation

SBO Select-before-operate

SC Switch or push button to close

SCS Station control system

SCADA Supervision, control and data acquisition

SCT System configuration tool according to standard IEC 61850

SDU Service data unit

SLM Serial communication module. Used for SPA/LON/IEC/DNP3 communication.

SMA connector Subminiature version A, A threaded connector withconstant impedance.

SMT Signal matrix tool within PCM600

SMS Station monitoring system

Section 7 1MRK 505 211-UEN C

Glossary

448

 Application manual

Page 455: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 455/457

SNTP Simple network time protocol – is used to synchronizecomputer clocks on local area networks. This reduces therequirement to have accurate hardware clocks in every

embedded system in a network. Each embedded node caninstead synchronize with a remote clock, providing therequired accuracy.

SPA Strömberg protection acquisition, a serial master/slave protocol for point-to-point communication

SRY Switch for CB ready condition

ST Switch or push button to trip

Starpoint  Neutral point of transformer or generator 

SVC Static VAr compensation

TC Trip coilTCS Trip circuit supervision

TCP Transmission control protocol. The most common transportlayer protocol used on Ethernet and the Internet.

TCP/IP Transmission control protocol over Internet Protocol. Thede facto standard Ethernet protocols incorporated into4.2BSD Unix. TCP/IP was developed by DARPA for Internet working and encompasses both network layer andtransport layer protocols. While TCP and IP specify two

 protocols at specific protocol layers, TCP/IP is often used

to refer to the entire US Department of Defense protocolsuite based upon these, including Telnet, FTP, UDP andRDP.

TEF Time delayed earth-fault protection function

TNC connector Threaded Neill-Concelman, a threaded constant impedanceversion of a BNC connector 

TPZ, TPY, TPX,

TPS

Current transformer class according to IEC

UMT User management tool

Underreach A term used to describe how the relay behaves during afault condition. For example, a distance relay isunderreaching when the impedance presented to it isgreater than the apparent impedance to the fault applied tothe balance point, that is, the set reach. The relay does not“see” the fault but perhaps it should have seen it. See alsoOverreach.

UTC Coordinated Universal Time. A coordinated time scale,maintained by the Bureau International des Poids etMesures (BIPM), which forms the basis of a coordinateddissemination of standard frequencies and time signals.

1MRK 505 211-UEN C Section 7Glossary

449

 Application manual

Page 456: Best Application

8/22/2019 Best Application

http://slidepdf.com/reader/full/best-application 456/457

UTC is derived from International Atomic Time (TAI) bythe addition of a whole number of "leap seconds" tosynchronize it with Universal Time 1 (UT1), thus allowingfor the eccentricity of the Earth's orbit, the rotational axistilt (23.5 degrees), but still showing the Earth's irregular rotation, on which UT1 is based. The CoordinatedUniversal Time is expressed using a 24-hour clock, anduses the Gregorian calendar. It is used for aeroplane andship navigation, where it is also sometimes known by themilitary name, "Zulu time." "Zulu" in the phonetic alphabetstands for "Z", which stands for longitude zero.

UV Undervoltage

WEI Weak end infeed logic

VT Voltage transformer 

X.21 A digital signalling interface primarily used for telecomequipment

3IO Three times zero-sequence current. Often referred to as theresidual or the earth-fault current

3UO Three times the zero sequence voltage. Often referred to asthe residual voltage or the neutral point voltage

Section 7 1MRK 505 211-UEN C

Glossary

450