BBC BETA BURNER COMBINATION SERIES NATURAL GAS OPERATION Model Number Specifications - HIGH FIRE _04 _06 _08 _10 _12 _14 _18 _24 Max Input @ 10% Excess Air (MMBtu/hr) 3.3 6.7 9.0 13.6 20.0 27.5 44.4 85.4 Max Excess Air (%) 320 320 400 500 560 600 700 600 Flame Length @ Max Input (ft) 7 8 9 13 14 15 18 25 LOW FIRE Input @ 10% Excess Air (MMBtu/hr) 0.3 0.9 1.6 2.1 3.2 4.7 6.8 11.6 Max Excess Air (%) 150 210 350 260 250 80 270 100 LOW PRESSURE OIL OPERATION Model Number Specifications - HIGH FIRE _04 _06 _08 _10 _12 _14 _18 _24 Max Input @ 20% Excess Air (MMBtu/hr) 2.9 5.3 8.3 12.3 18.0 25.1 39.6 75.6 Max Excess Air (%) 270 690 400 1000 500 550 350 1000 Flame Length @ Max Input (ft) 8 7 10 10 11 16 20 18 LOW FIRE Input @ 20% Excess Air (MMBtu/hr) 0.5 1.2 2.1 2.6 4.0 6.1 8.2 13.5 Max Excess Air (%) 70 20 500 700 400 160 80 200 HIGH PRESSURE OIL OPERATION Model Number Specifications - HIGH FIRE _04 _06 _08 _10 _12 _14 _18 _24 Max Input @ 20% Excess Air (MMBtu/hr) 3.0 5.2 10.1 16.5 20.8 27.0 40.0 72.7 Max Excess Air (%) 70 160 120 400 400 600 350 750 Flame Length @ Max Input (ft) 5 6 10 11 11 12 14 16 LOW FIRE Input @ 20% Excess Air (MMBtu/hr) 0.5 1.7 3.0 4.9 6.1 6.5 7.3 14.1 Max Excess Air (%) 90 55 100 100 100 150 220 500 Notes: 1. All burners equipped with converging tile and refractory baffle plate. 2. Btu input based on HHV’s of natural gas with 1034 Btu/ft 3 and 9.74:1 air/fuel ratio No. 2 oil with 138,000 Btu/gallon and 1380:1 air/fuel ratio and No. 6 oil with 151,000 Btu/gallon, 1510:1 air/fuel ratio. 3. Flame lengths measured from the end of converging tile; for a diverging tile (available from size _ _06 to _ _18), add 18% to the converging tile flame length. CAPACITIES HAUCK MANUFACTURING CO., P.O. Box 90 Lebanon, PA 17042-0090 717-272-3051 10/09 www.hauckburner.com Fax: 717-273-9882 BBC-2 (OVER)
30
Embed
BBC BETA BURNER COMBINATION SERIES · BBC BETA BURNER COMBINATION SERIES NATURAL GAS OPERATION Model Number Specifications - HIGH FIRE _04 _06 _08 _10 _12 _14 _18 _24 Max Input @
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
BBC BETA BURNER COMBINATION SERIES
NATURAL GAS OPERATION Model Number
Specifications - HIGH FIRE _04 _06 _08 _10 _12 _14 _18 _24
Max Input @ 10% Excess Air (MMBtu/hr) 3.3 6.7 9.0 13.6 20.0 27.5 44.4 85.4
Max Excess Air (%) 320 320 400 500 560 600 700 600
Flame Length @ Max Input (ft) 7 8 9 13 14 15 18 25 LOW FIRE
Max Excess Air (%) 90 55 100 100 100 150 220 500 Notes:
1. All burners equipped with converging tile and refractory baffle plate. 2. Btu input based on HHV’s of natural gas with 1034 Btu/ft3 and 9.74:1 air/fuel ratio No. 2 oil with 138,000 Btu/gallon
and 1380:1 air/fuel ratio and No. 6 oil with 151,000 Btu/gallon, 1510:1 air/fuel ratio. 3. Flame lengths measured from the end of converging tile; for a diverging tile (available from size _ _06 to _ _18),
add 18% to the converging tile flame length. ����������������������������������������� ������������������������������������������������������������ ���� ������ ����� ����������������������������� ����������������
Notes: 1. All burners equipped with converging tile and refractory baffle plate. 2. Btu input based on LHV’s of natural gas with 36.74MJ/nm3, No. 2 oil with 37MJ/L, and No. 6 oil flow with 41.3 MJ/L. 3. Flame lengths measured from the end of converging tile; for a diverging tile (available from size _ _06 to _ _18),
add 18% to the converging tile flame length. ��������������� ������������������������������������������������������������ ���� ������ ����� ����������������������������� ����������������
Notes: 1. Air Flows are at 100°F and sea level. 2. All pressures are static measurement at their respective pressure tap. 3. All burners equipped with converging tile and refractory baffle plate. 4. Btu input based on HHV’s of natural gas with 1034 Btu/ft3, and 9.74:1 air/fuel ratio No. 2 oil with 138,000 Btu/gallon, and
1380:1 air/fuel ratio and No. 6 oil with 151,000 Btu/gallon, 1510:1 air/fuel ratio. 5. Flame lengths measured from the end of converging tile; for a diverging tile (available from size _ _06 to _ _18),
add 18% to the flame length. ������������������������������������������������������������������� ������������������������������������������������������������ ���� ������ ����� ����������������������������� ����������������
Notes: 1. Air Flows are at 38°C and sea level. 2. All pressures are static measurement at their respective pressure tap. 3. All burners equipped with converging tile and refractory baffle plate. 4. Btu input based on LHV’s of natural gas with 36.74MJ/nm3, and 9.74:1 air/fuel ratio No. 2 oil with 37MJ/L, and
1380:1 air/fuel ratio and No. 6 oil with 41.3 MJ/L, 1510:1 air/fuel ratio. 5. Flame lengths measured from the end of converging tile; for a diverging tile (available from size _ _06 to _ _18),
add 18% to the flame length. ��������������� ������������������������������������������������������������ ���� ������ ����� ����������������������������� ����������������
Notes: 1. Air Flows are at 100°F and sea level. 2. All pressures are static measurement at their respective pressure tap. 3. All burners equipped with converging tile and refractory baffle plate. 4. Btu input based on HHV’s of natural gas with 1034 Btu/ft3, and 9.74:1 air/fuel ratio No. 2 oil with 138,000 Btu/gallon, and
1380:1 air/fuel ratio and No. 6 oil with 151,000 Btu/gallon, 1510:1 air/fuel ratio. 5. Flame lengths measured from the end of converging tile; for a diverging tile (available from size _ _06 to _ _18),
add 18% to the flame length. ����������������������������������������� ������������������������������������������������������������ ���� ������ ����� ����������������������������� ����������������
Notes: 1. Air Flows are at 38°C and sea level. 2. All pressures are static measurement at their respective pressure tap. 3. All burners equipped with converging tile and refractory baffle plate. 4. Btu input based on LHV’s of natural gas with 36.74MJ/nm3, and 9.74:1 air/fuel ratio No. 2 oil with 37MJ/L, and
1380:1 air/fuel ratio and No. 6 oil with 41.3 MJ/L, 1510:1 air/fuel ratio. 5. Flame lengths measured from the end of converging tile; for a diverging tile (available from size _ _06 to _ _18),
Notes: 1. Air Flows are at 100°F and sea level. 2. All pressures are static measurement at their respective pressure tap. 3. All burners equipped with converging tile and refractory baffle plate. 4. Btu input based on HHV’s of natural gas with 1034 Btu/ft3, and 9.74:1 air/fuel ratio No. 2 oil with 138,000 Btu/gallon, and
1380:1 air/fuel ratio and No. 6 oil with 151,000 Btu/gallon, 1510:1 air/fuel ratio. 5. Flame lengths measured from the end of converging tile; for a diverging tile (available from size _ _06 to _ _18),
add 18% to the flame length. ��������������� ������������������������������������������������������������ ���� ������ ����� ����������������������������� ����������������
Notes: 1. Air Flows are at 38°C and sea level. 2. All pressures are static measurement at their respective pressure tap. 3. All burners equipped with converging tile and refractory baffle plate. 4. Btu input based on LHV’s of natural gas with 36.74MJ/nm3, and 9.74:1 air/fuel ratio No. 2 oil with 37MJ/L, and
1380:1 air/fuel ratio and No. 6 oil with 41.3 MJ/L, 1510:1 air/fuel ratio. 5. Flame lengths measured from the end of converging tile; for a diverging tile (available from size _ _06 to _ _18),
Notes: 1. Air Flows are at 100°F and sea level. 2. All pressures are static measurement at their respective pressure tap. 3. All burners equipped with converging tile and refractory baffle plate. 4. Btu input based on HHV’s of natural gas with 1034 Btu/ft3, and 9.74:1 air/fuel ratio No. 2 oil with 138,000 Btu/gallon, and
1380:1 air/fuel ratio and No. 6 oil with 151,000 Btu/gallon, 1510:1 air/fuel ratio. 5. Flame lengths measured from the end of converging tile; for a diverging tile (available from size _ _06 to _ _18),
add 18% to the flame length. ��������������� ������������������������������������������������������������ ���� ������ ����� ����������������������������� ����������������
Notes: 1. Air Flows are at 38°C and sea level. 2. All pressures are static measurement at their respective pressure tap. 3. All burners equipped with converging tile and refractory baffle plate. 4. Btu input based on LHV’s of natural gas with 36.74MJ/nm3, and 9.74:1 air/fuel ratio No. 2 oil with 37MJ/L, and
1380:1 air/fuel ratio and No. 6 oil with 41.3 MJ/L, 1510:1 air/fuel ratio. 5. Flame lengths measured from the end of converging tile; for a diverging tile (available from size _ _06 to _ _18),
Notes: 1. Air Flows are at 100°F and sea level. 2. All pressures are static measurement at their respective pressure tap. 3. All burners equipped with converging tile and refractory baffle plate. 4. Btu input based on HHV’s of natural gas with 1034 Btu/ft3, and 9.74:1 air/fuel ratio No. 2 oil with 138,000 Btu/gallon, and
1380:1 air/fuel ratio and No. 6 oil with 151,000 Btu/gallon, 1510:1 air/fuel ratio. 5. Flame lengths measured from the end of converging tile; for a diverging tile (available from size _ _06 to _ _18),
add 18% to the flame length. ��������������� ������������������������������������������������������������ ���� ������ ����� ����������������������������� ����������������
Notes: 1. Air Flows are at 38°C and sea level. 2. All pressures are static measurement at their respective pressure tap. 3. All burners equipped with converging tile and refractory baffle plate. 4. Btu input based on LHV’s of natural gas with 36.74MJ/nm3, and 9.74:1 air/fuel ratio No. 2 oil with 37MJ/L, and
1380:1 air/fuel ratio and No. 6 oil with 41.3 MJ/L, 1510:1 air/fuel ratio. 5. Flame lengths measured from the end of converging tile; for a diverging tile (available from size _ _06 to _ _18),
Notes: 1. Air Flows are at 100°F and sea level. 2. All pressures are static measurement at their respective pressure tap. 3. All burners equipped with converging tile and refractory baffle plate. 4. Btu input based on HHV’s of natural gas with 1034 Btu/ft3, and 9.74:1 air/fuel ratio No. 2 oil with 138,000 Btu/gallon, and
1380:1 air/fuel ratio and No. 6 oil with 151,000 Btu/gallon, 1510:1 air/fuel ratio. 5. Flame lengths measured from the end of converging tile; for a diverging tile (available from size _ _06 to _ _18),
add 18% to the flame length. ��������������� ������������������������������������������������������������ ���� ������ ����� ����������������������������� ����������������
Notes: 1. Air Flows are at 38°C and sea level. 2. All pressures are static measurement at their respective pressure tap. 3. All burners equipped with converging tile and refractory baffle plate. 4. Btu input based on LHV’s of natural gas with 36.74MJ/nm3, and 9.74:1 air/fuel ratio No. 2 oil with 37MJ/L, and
1380:1 air/fuel ratio and No. 6 oil with 41.3 MJ/L, 1510:1 air/fuel ratio. 5. Flame lengths measured from the end of converging tile; for a diverging tile (available from size _ _06 to _ _18),
Notes: 1. Air Flows are at 100°F and sea level. 2. All pressures are static measurement at their respective pressure tap. 3. All burners equipped with converging tile and refractory baffle plate. 4. Btu input based on HHV’s of natural gas with 1034 Btu/ft3, and 9.74:1 air/fuel ratio No. 2 oil with 138,000 Btu/gallon, and
1380:1 air/fuel ratio and No. 6 oil with 151,000 Btu/gallon, 1510:1 air/fuel ratio. 5. Flame lengths measured from the end of converging tile; for a diverging tile (available from size _ _06 to _ _18),
add 18% to the flame length. ��������������� ������������������������������������������������������������ ���� ������ ����� ����������������������������� ����������������
Notes: 1. Air Flows are at 38°C and sea level. 2. All pressures are static measurement at their respective pressure tap. 3. All burners equipped with converging tile and refractory baffle plate. 4. Btu input based on LHV’s of natural gas with 36.74MJ/nm3, and 9.74:1 air/fuel ratio No. 2 oil with 37MJ/L, and
1380:1 air/fuel ratio and No. 6 oil with 41.3 MJ/L, 1510:1 air/fuel ratio. 5. Flame lengths measured from the end of converging tile; for a diverging tile (available from size _ _06 to _ _18),
Notes: 1. Air Flows are at 100°F and sea level. 2. All pressures are static measurement at their respective pressure tap. 3. All burners equipped with converging tile and refractory baffle plate. 4. Btu input based on HHV’s of natural gas with 1034 Btu/ft3, and 9.74:1 air/fuel ratio No. 2 oil with 138,000 Btu/gallon, and
1380:1 air/fuel ratio and No. 6 oil with 151,000 Btu/gallon, 1510:1 air/fuel ratio. 5. Flame lengths measured from the end of converging tile; for a diverging tile (available from size _ _06 to _ _18),
add 18% to the flame length. ��������������� ������������������������������������������������������������ ���� ������ ����� ����������������������������� ����������������
Notes: 1. Air Flows are at 38°C and sea level. 2. All pressures are static measurement at their respective pressure tap. 3. All burners equipped with converging tile and refractory baffle plate. 4. Btu input based on LHV’s of natural gas with 36.74MJ/nm3, and 9.74:1 air/fuel ratio No. 2 oil with 37MJ/L, and
1380:1 air/fuel ratio and No. 6 oil with 41.3 MJ/L, 1510:1 air/fuel ratio. 5. Flame lengths measured from the end of converging tile; for a diverging tile (available from size _ _06 to _ _18),