www.solerpalau.com AXIAL FLOW CABINET FANS CHGT Series Cylindrical cased axial flow fans CHGT Range of adjustable pitch aerofoil blade, axial flow cabinet fans designed for smoke extraction in fire conditions and certified F400-120 and F300-120 (CE marked). Fan casing manufactured from heavy gauge galvanised sheet steel internally lined with 25mm thickness fireproof fibreglass acoustic insulation (M0). All models incorporate separate high grade diecast aluminium blades locked within a pressed sheet steel hub. Motors Available, depending upon the model: - with three phase motors in 4 or 6 poles. - with three phase two speed motors 4/8 or 6/12 poles. F400-120 and F300-120 motors are IP55 class H insulation. Electrical supplies: Three phase 230/400V-50Hz up to 3 kW. Three phase 400V-50Hz, for higher power motors and two speed motors. (See characteristics chart). Additional information Standard air direction: form (A) configuration (motor over impeller). On request Air direction: form (B) configuration (impeller over motor). Constructive configuration models from 400 to 800 Constructive configuration models from 900 to 1250 F400-120 F300-120 Specific applications F300-120 Car Parks Industrial kitchens Officially approved to EN12101-3 standard (certificate number 0370-CPD-0420) Officially approved to EN12101-3 standard (certificate number 0370-CPD-0955) Highly versatile range due to different number of available blades and adjustable pitch angles Impellers with 3, 5, 6, 7 or 9 blades with adjustable pitch angles, allowing the most optimum selection to achieve with every kind of installation requirements.
47
Embed
AxIAl flOW CABINET fANS CHGT SeriesS(ozgfktex303uyt451mtgcymy... · AIAL FLOW CABINET FANS CHGT Series Cylindrical cased axial fiow fans CHGT Motor approved S1 and S2 F400-120 or
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
www.solerpalau.com
AXIAL FLOW CABINET FANSCHGT Series
Cylindrical cased axial flow fans CHGT
Range of adjustable pitch aerofoil blade, axial flow cabinet fans designed for smoke extraction in fire conditions and certified F400-120 and F300-120 (CE marked).Fan casing manufactured from heavy gauge galvanised sheet steel internally lined with 25mm thickness fireproof fibreglass acoustic insulation (M0).All models incorporate separate high grade diecast aluminium blades locked within a pressed sheet steel hub.
MotorsAvailable, depending upon the model:- with three phase motors in 4 or 6 poles.- with three phase two speed motors 4/8 or 6/12 poles.F400-120 and F300-120 motors are IP55 class H insulation.Electrical supplies:
Three phase 230/400V-50Hz up to 3 kW.Three phase 400V-50Hz, for higher power motors and two speed motors.(See characteristics chart).
Additional informationStandard air direction: form (A) configuration (motor over impeller).
On requestAir direction: form (B) configuration (impeller over motor).
Constructive configurationmodels from 400 to 800
Constructive configuration models from 900 to 1250
Highly versatile range due to different number of available blades and adjustable pitch angles
Impellers with 3, 5, 6, 7 or 9 blades with adjustable pitch angles, allowing the most optimum selection to achieve with everykind of installation requirements.
www.solerpalau.com
AXIAL FLOW CABINET FANSCHGT Series
Cylindrical cased axial flow fans CHGT
Motor approved S1 and S2F400-120 or F300-120certified motors approved forrunning continuously (S1) or for emergency operation (S2).
Corrosion resistanceCasings manufactured fromgalvanised sheet steel. Design enables the casing side panels to be removed and the motorimpeller assembly accessed.
Easy to installRobust base supports facilitate the installation.(Models from 900 to 1250)
Impeller dynamicallybalancedImpeller dynamicallybalanced, according to ISO1940 standard, providingvibration free operation.
Wide blade design: higher pressureWide blade design to ensure the highest efficient airflowperformances.Configuration 1: models from 400 to 630.Configuration 2: models from 710 to 1250.
Before installation check that the product electrical characteristics listed on the data plate label (Voltage, power, frequency, etc.) match those of the intended electrical supply.
Before installation check that the product electrical characteristics listed on the data plate label (Voltage, power, frequency, etc.) match those of the intended electrical supply.
CHGT/6-900-6/-1,5 1,5 6,75 3,90 161CHGT/6-900-6/-2,2 2,2 9,28 5,36 169CHGT/6-900-6/-3 3 11,81 6,82 186CHGT/6-900-6/-4 4 – 9,20 192We reserve right to supply different motors and hence data may change.
Before installation check that the product electrical characteristics listed on the data plate label (Voltage, power, frequency, etc.) match those of the intended electrical supply.
Before installation check that the product electrical characteristics listed on the data plate label (Voltage, power, frequency, etc.) match those of the intended electrical supply.
Before installation check that the product electrical characteristics listed on the data plate label (Voltage, power, frequency, etc.) match those of the intended electrical supply.
Before installation check that the product electrical characteristics listed on the data plate label (Voltage, power, frequency, etc.) match those of the intended electrical supply.
www.solerpalau.com
AXIAL FLOW CABINET FANSCHGT Series
Cylindrical cased axial flow fans CHGT
Model Motor power(kW)
full load current(A)
Weight(Kg)
V. 1 V. 2 V. 1 V. 2CHGT/4/8-800-6/-1,5/0,25 1,5 0,25 3,65 1,6 101CHGT/4/8-800-6/-2,2/0,37 2,2 0,37 4,7 1,66 109CHGT/4/8-800-6/-3/0,55 3 0,55 6,29 2,35 110CHGT/4/8-800-6/-4/0,75 4 0,75 8,44 2,25 117CHGT/4/8-800-6/-5,5/1,1 5,5 1,1 11,7 3,7 139CHGT/4/8-800-6/-7,5/1,5 7,5 1,5 15,9 4,72 152
Before installation check that the product electrical characteristics listed on the data plate label (Voltage, power, frequency, etc.) match those of the intended electrical supply.
Before installation check that the product electrical characteristics listed on the data plate label (Voltage, power, frequency, etc.) match those of the intended electrical supply.
Model Motor power(kW)
full load current(A)
Weight(Kg)
V. 1 V. 2 V. 1 V. 2CHGT/6/12-500-6/-0,55/0,09 0,55 0,09 2,07 0,94 51
CVD CGT/CHGTProtection guards.Wire protection guards for mountingon the inlet or discharge sides of the cabinets.
PER-CN CHGTAluminium and sheet steel louvre back draft shutter (without bird guard) for CHGT and CGT series.
70
A
B
Model cabinet Inlet and discharge
Protection guard model A B
CHGT-400 CVD/400 CGT/CHGT 424 313,5
CHGT-450 CVD/450 CGT/CHGT 474 341,5
CHGT-500 CVD/500 CGT/CHGT 524 369,5
CHGT-560 CVD/560 CGT/CHGT 584 403,5
CHGT-630 CVD/630 CGT/CHGT 654 422,5
CHGT-710 CVD/710 CGT/CHGT 751 503,8
CHGT-800 CVD/800 CGT/CHGT 851,5 560,2
CHGT-900 CVD/900 CGT/CHGT 951,5 616,2
CHGT-1000 CVD/1000 CGT/CHGT 1056,5 675
CHGT-1250 CVD/1250 CGT/CHGT 1276,5 798,3
A (Interior measurement)
E
e70
NV = NUM. TAL Ø 4.1
NH = NUM. TAL Ø 4.1
Ø 4.1
Ø 4.1
E
e
10
10
Model A
400 428
450 478
500 528
560 585
630 655
710 752
800 852
900 952
1000 1057
1250 1277
A
B
130 Model cabinet A B
ACOP RECT CHGT/CGT 400 F400 428 428
ACOP RECT CHGT/CGT 450 F400 478 478
ACOP RECT CHGT/CGT 500 F400 528 528
ACOP RECT CHGT/CGT 560 F400 585 585
ACOP RECT CHGT/CGT 630 F400 655 655
ACOP RECT CHGT/CGT 710 F400 752 752
ACOP RECT CHGT/CGT 800 F400 852 852
ACOP RECT CHGT/CGT 900 F400 952 952
ACOP RECT CHGT/CGT 1000 F400 1057 1057
ACOP RECT CHGT/CGT 1250 F400 1277 1277
Dimensions in mm.
Dimensions in mm.
ACOP RECT CHGT/CGT f400Rectangular flexible connector.
www.solerpalau.com
AXIAL FLOW CABINET FANSCHGT Series
Cylindrical cased axial flow fans CHGT
ExAMPlE Of SElECTING CHGT/ CGT fANS
- qv: Air volume in m3/h and m3/s.- psf: Static pressure in mmWG and Pa.– Dry air at 20ºC and 760 mmHg.– Performance data in accordance with ISO 5801 and AMCA
210-99 Standards.
CGT
Number of poles 4
Nominal diameter (mm) 1000
Number of blades 3
CGT/4-1000-3/_°-_ kW
Hz A B C
63 22 20 18
125 19 19 17
250 13 11 12
500 6 5 6
1000 4 5 5
2000 6 7 6
4000 11 13 12
8000 18 20 20
Table of correction factors for the calculation of the sound power level spectrum.
Spectrum sound power level
Hz dB(A) B lw dB(A)
63 95 20 75
125 95 19 76
250 95 11 84
500 95 5 90
1000 95 5 90
2000 95 7 88
4000 95 13 82
8000 95 20 75
Sound pressure spectrum
Hz dB(A) Atten. lw dB(A)
63 75 20 55
125 76 20 56
250 84 20 64
500 90 20 70
1000 90 20 70
2000 88 20 68
4000 82 20 62
8000 75 20 55
Working point:Airflow..................: 40,000 m3/hr = 11,1 m3/sPressure..: 23.4 mm c.a.
Taking as an example the following point: airflow axis (horizontal axis) at 40.000m3/h. (Airflow=11.1 m3/s) and at a static pressure of 23.4 mmWG (vertical axis at theleft side of the intersection).On those conditions the intersection point lies on the fan performance curve with 18º blade pitch angle (green line) with a dynamic pressure of 12.4 mmWG (red line)tracing at 40.000 m3/h point and clearly visible at upper vertical axis in the left side of the intersection).From this point, in the lower intersection that at 18º the absorbed power on the power scale on the left is 4768 W and that the upper red line corresponds, accordingto what can be read at the right lower side scale, to a motor power of 5,5 kW (S&P always recommends to work with a minimum security margin of 10% on theabsorbed power at the axis).Its total sound power level is 99 dB(A), (the sound level average value).The sound spectrum can be calculated from the noise area (the three areas delimited by grey lines): A, B, or C.In this case the working point is at the B area. To obtain the value of the spectrum for every octave band.For every eighth, the coefficient should be subtracted from the total sound power level.
At 3 meters of distance, the sound pressure level is 79 dB(A).
THE SOUND LEVEL VALUES IN THE PERFORMANCE CURVES CORRESPOND TO SOUND POWER LEVELS LwA.
TO CONVERT THIS DATA INTO SOUND PRESSURE LEVEL VALUES LpA, SUBTRACT REDUCTION DUE TO DISTANCE.
The resulting model would be CHGT/4-1000/3-16-5,5 kW.
BC
A
psf psf(Pa)
Pabs(W)15000
14000
13000
12000
10000
9000
8000
7000
6000
4000
3000
2000
10005000 15000 25000 35000 45000 55000
8º 10º12º
14º16º
18º20º 22º
24º 26º
28º
30º
32º
65000 75000
11000
(mmWG)
350
300
250
200
150
100
50
400
450
500
35
30
25
23,495
12,4
99
95 96 94 95 97
8º10º12º14º16º
18º
20º 22º 24º26º28º 30º32º
96 94 96 98 Lw dB(A)
989697101 100
40000
40000
4768
20
15
10
55000
2 4 6 8 10 12 14 16 18 20
15000 25000 35000 45000 55000
15
Absorbed power (W)
Recommended motorpower (kW)
11
5.5
7.5
43
65000 75000
40
45
50
qv [m3/h]
qv [m3/s]
qv [m3/h]
www.solerpalau.com
AXIAL FLOW CABINET FANSCHGT Series
Cylindrical cased axial flow fans CHGT
PERfORMANCE CuRVES - 2 POlE MOTORS
- qv: Air volume in m3/h and m3/s.- psf: Static pressure in mmWG and Pa.– Dry air at 20ºC and 760 mmHg.– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.
CGT
Number of poles 2
Nominal diameter (mm) 400
Number of blades 6
CGT/2-400-6/_°-_ kW
Hz A B C
63 42 43 36
125 29 30 23
250 17 17 14
500 8 6 8
1000 4 4 5
2000 5 6 5
4000 9 10 8
8000 17 19 14
Table of correction factors for the calculation of the sound power level spectrum.
THE SOUND LEVEL VALUES IN THE PERFORMANCE CURVES CORRESPOND TO SOUND POWER LEVELS LwA.
TO CONVERT THIS DATA INTO SOUND PRESSURE LEVEL VALUES LpA, SUBTRACT REDUCTION DUE TO DISTANCE.
Table of correction factors for the calculation of the sound power level spectrum.
THE SOUND LEVEL VALUES IN THE PERFORMANCE CURVES CORRESPOND TO SOUND POWER LEVELS LwA.
TO CONVERT THIS DATA INTO SOUND PRESSURE LEVEL VALUES LpA, SUBTRACT REDUCTION DUE TO DISTANCE.
90
80
70
60
50
40
30
20
10
0
900
800
700
600
500
400
300
200
100
0
3000
2500
2000
1500
1000
5001000 3000 5000 7000 9000 11000 13000
psf psf(Pa) (mmWG)
1000
0.4 0.8 1.2 1.6 2 2.4 2.8 3.2 3.6
qv [m3/h]
qv [m3/s]
3000 5000 7000 9000 11000 13000
8°10°12°14°
16°
18°
20°22°24°26° 28°
94
97
96 99 95 95
100 96 95 Lw dB(A)
102 98 97
Absorbed power (W) motorRecommended
power (kW)
2.2
1.5
3
28°
26°
24°22°
20°18°
16°14°12°
10°8°
qv [m3/h]
Pabs (W )
- qv: Air volume in m3/h and m3/s.- psf: Static pressure in mmWG and Pa.– Dry air at 20ºC and 760 mmHg.– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.
www.solerpalau.com
AXIAL FLOW CABINET FANSCHGT Series
Cylindrical cased axial flow fans CHGT
PERfORMANCE CuRVES - 4 POlE MOTORS - CHGT / CGT
CHGT / CGT
Number of poles 4
Nominal diameter (mm) 400
Number of blades 6
CHGT/4-400-6/_°-_ kWCGT/4-400-6/_°-_ kW
Hz A B C
63 38 38 31
125 22 21 19
250 12 9 12
500 5 5 6
1000 4 5 5
2000 7 8 6
4000 13 14 11
8000 21 23 19
Table of correction factors for the calculation of the sound power level spectrum.
THE SOUND LEVEL VALUES IN THE PERFORMANCE CURVES CORRESPOND TO SOUND POWER LEVELS LwA.
TO CONVERT THIS DATA INTO SOUND PRESSURE LEVEL VALUES LpA, SUBTRACT REDUCTION DUE TO DISTANCE.
16
18
20
14
12
10
8
6
4
2
0
160
180
200
140
120
100
80
60
40
20
0
psf psf(Pa) (mmWG)
8º10º12º14º
16º
18º
20º22º
24º26º 28º30º32º34º36º38º
65 75 72 69 69 70
70 74 71 70 71
72 75 73 72 72 73
71 Lw dB(A)
0
0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6
1000 2000 3000 4000 5000 6000 qv [m3/h]
qv [m3/s]
0.25
Pabs(W)300
250
200
150
100
50
00 1000 2000 3000 4000 5000 6000 qv [m3/h]
8º10º 12º 14º
16º 18º 20º22º
24º26º
28º
30º
32º
34º
36º
38º
motorRecommended
power (kW)Absorbed power (W)
(*) CGT Series only.CHGT Series motor 0,55.
- qv: Air volume in m3/h and m3/s.- psf: Static pressure in mmWG and Pa.– Dry air at 20ºC and 760 mmHg.– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.
www.solerpalau.com
AXIAL FLOW CABINET FANSCHGT Series
Cylindrical cased axial flow fans CHGT
PERfORMANCE CuRVES - 4 POlE MOTORS - CHGT / CGT
CHGT / CGT
Number of poles 4
Nominal diameter (mm) 450
Number of blades 6
CHGT/4-450-6/_°-_ kWCGT/4-450-6/_°-_ kW
Hz A B C
63 38 38 31
125 22 21 19
250 12 9 12
500 5 5 6
1000 4 5 5
2000 7 8 6
4000 13 14 11
8000 21 23 19
Table of correction factors for the calculation of the sound power level spectrum.
THE SOUND LEVEL VALUES IN THE PERFORMANCE CURVES CORRESPOND TO SOUND POWER LEVELS LwA.
TO CONVERT THIS DATA INTO SOUND PRESSURE LEVEL VALUES LpA, SUBTRACT REDUCTION DUE TO DISTANCE.
- qv: Air volume in m3/h and m3/s.- psf: Static pressure in mmWG and Pa.– Dry air at 20ºC and 760 mmHg.– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.
www.solerpalau.com
AXIAL FLOW CABINET FANSCHGT Series
Cylindrical cased axial flow fans CHGT
PERfORMANCE CuRVES - 4 POlE MOTORS - CHGT / CGT
CHGT / CGT
Number of poles 4
Nominal diameter (mm) 500
Number of blades 6
CHGT/4-500-6/_°-_ kWCGT/4-500-6/_°-_ kW
Hz A B C
63 38 38 31
125 22 21 19
250 12 9 12
500 5 5 6
1000 4 5 5
2000 7 8 6
4000 13 14 11
8000 21 23 19
Table of correction factors for the calculation of the sound power level spectrum.
THE SOUND LEVEL VALUES IN THE PERFORMANCE CURVES CORRESPOND TO SOUND POWER LEVELS LwA.
TO CONVERT THIS DATA INTO SOUND PRESSURE LEVEL VALUES LpA, SUBTRACT REDUCTION DUE TO DISTANCE.
- qv: Air volume in m3/h and m3/s.- psf: Static pressure in mmWG and Pa.– Dry air at 20ºC and 760 mmHg.– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.
www.solerpalau.com
AXIAL FLOW CABINET FANSCHGT Series
Cylindrical cased axial flow fans CHGT
PERfORMANCE CuRVES - 4 POlE MOTORS - CHGT / CGT
CHGT / CGT
Number of poles 4
Nominal diameter (mm) 560
Number of blades 6
CHGT/4-560-6/_°-_ kWCGT/4-560-6/_°-_ kW
Hz A B C
63 38 38 31
125 22 21 19
250 12 9 12
500 5 5 6
1000 4 5 5
2000 7 8 6
4000 13 14 11
8000 21 23 19
Table of correction factors for the calculation of the sound power level spectrum.
THE SOUND LEVEL VALUES IN THE PERFORMANCE CURVES CORRESPOND TO SOUND POWER LEVELS LwA.
TO CONVERT THIS DATA INTO SOUND PRESSURE LEVEL VALUES LpA, SUBTRACT REDUCTION DUE TO DISTANCE.
- qv: Air volume in m3/h and m3/s.- psf: Static pressure in mmWG and Pa.– Dry air at 20ºC and 760 mmHg.– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.
www.solerpalau.com
AXIAL FLOW CABINET FANSCHGT Series
Cylindrical cased axial flow fans CHGT
PERfORMANCE CuRVES - 4 POlE MOTORS - CHGT / CGT
CHGT / CGT
Number of poles 4
Nominal diameter (mm) 630
Number of blades 6
CHGT/4-630-6/_°-_ kWCGT/4-630-6/_°-_ kW
Hz A B C
63 38 38 31
125 22 21 19
250 12 9 12
500 5 5 6
1000 4 5 5
2000 7 8 6
4000 13 14 11
8000 21 23 19
Table of correction factors for the calculation of the sound power level spectrum.
THE SOUND LEVEL VALUES IN THE PERFORMANCE CURVES CORRESPOND TO SOUND POWER LEVELS LwA.
TO CONVERT THIS DATA INTO SOUND PRESSURE LEVEL VALUES LpA, SUBTRACT REDUCTION DUE TO DISTANCE.
- qv: Air volume in m3/h and m3/s.- psf: Static pressure in mmWG and Pa.– Dry air at 20ºC and 760 mmHg.– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.
Table of correction factors for the calculation of the sound power level spectrum.
THE SOUND LEVEL VALUES IN THE PERFORMANCE CURVES CORRESPOND TO SOUND POWER LEVELS LwA.
TO CONVERT THIS DATA INTO SOUND PRESSURE LEVEL VALUES LpA, SUBTRACT REDUCTION DUE TO DISTANCE.
A
B C
0 5000 10000 15000 20000 25000 30000
1 2 3 4 5 6 7 8
0
5
10
15
20
25
30
35
40
0
50
100
150
200
250
300
350
400
8°
14°
16°
18°
20°24°22°
26° 28° 30°32°
0 5000 10000 15000 20000 25000 300000
400
800
1200
1600
2000
2400
2800
3200
Pabs (W)
0.75
1.1
1.5
2.2
3
32°30°
28°26°
24°22°
20°18°16°
14°12°10°
8°
9189889092
91 LwdB(A)89889192
90919389
12°
10°
92
qv [m3/h]
psf psf(Pa)
qv [m3/h]
qv [m3/s]
Recommendedmotorpower (KW)Absorbed power (W)
(mmWG)
- qv: Air volume in m3/h and m3/s.- psf: Static pressure in mmWG and Pa.– Dry air at 20ºC and 760 mmHg.– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.
Table of correction factors for the calculation of the sound power level spectrum.
THE SOUND LEVEL VALUES IN THE PERFORMANCE CURVES CORRESPOND TO SOUND POWER LEVELS LwA.
TO CONVERT THIS DATA INTO SOUND PRESSURE LEVEL VALUES LpA, SUBTRACT REDUCTION DUE TO DISTANCE.
A
B C
0 5000 10000 15000 20000 25000 30000
1 2 3 4 5 6 7 8
0
5
10
15
20
25
30
35
40
45
50
55
60
0
50
100
150
200
250
300
350
400
450
500
550
6008°
14°16°
18°
20°
24°
22°
26°28°30°32°
0 5000 10000 15000 20000 25000 300000
500
1000
1500
2000
2500
3000
3500
4000
Pabs (W)
1.1
1.5
2.2
3
4
32°30°
28°26°
24°22°
20°
18°16°14°12°
10°8°
9291919393
93 LwdB(A)91919493
92939691
12°10°
93
psf psf(Pa)
qv [m3/h]
qv [m3/h]
qv [m3/s]
Recommendedmotorpower (KW)Absorbed power (W)
(mmWG)
- qv: Air volume in m3/h and m3/s.- psf: Static pressure in mmWG and Pa.– Dry air at 20ºC and 760 mmHg.– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.
www.solerpalau.com
AXIAL FLOW CABINET FANSCHGT Series
Cylindrical cased axial flow fans CHGT
PERfORMANCE CuRVES - 4 POlE MOTORS - CHGT f400
CHGT f400
Number of poles 4
Nominal diameter (mm) 710
Number of blades 5 or 7
CHGT/4-710-_/_°-_ kW
Hz A B C
63 38 38 31
125 22 21 19
250 12 9 12
500 5 5 6
1000 4 5 5
2000 7 8 6
4000 12 14 11
8000 18 23 19
Table of correction factors for the calculation of the sound power level spectrum.
THE SOUND LEVEL VALUES IN THE PERFORMANCE CURVES CORRESPOND TO SOUND POWER LEVELS LwA.
TO CONVERT THIS DATA INTO SOUND PRESSURE LEVEL VALUES LpA, SUBTRACT REDUCTION DUE TO DISTANCE.
- qv: Air volume in m3/h and m3/s.- psf: Static pressure in mmWG and Pa.– Dry air at 20ºC and 760 mmHg.– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.
www.solerpalau.com
AXIAL FLOW CABINET FANSCHGT Series
Cylindrical cased axial flow fans CHGT
PERfORMANCE CuRVES - 4 POlE MOTORS - CHGT / CGT
CHGT / CGT
Number of poles 4
Nominal diameter (mm) 800
Number of blades 3
CHGT/4-800-3/_°-_ kWCGT/4-800-3/_°-_ kW
Hz A B C
63 38 38 31
125 22 21 19
250 12 9 12
500 5 5 6
1000 4 5 5
2000 7 8 6
4000 12 14 11
8000 18 23 19
Table of correction factors for the calculation of the sound power level spectrum.
THE SOUND LEVEL VALUES IN THE PERFORMANCE CURVES CORRESPOND TO SOUND POWER LEVELS LwA.
TO CONVERT THIS DATA INTO SOUND PRESSURE LEVEL VALUES LpA, SUBTRACT REDUCTION DUE TO DISTANCE.
- qv: Air volume in m3/h and m3/s.- psf: Static pressure in mmWG and Pa.– Dry air at 20ºC and 760 mmHg.– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.
www.solerpalau.com
AXIAL FLOW CABINET FANSCHGT Series
Cylindrical cased axial flow fans CHGT
PERfORMANCE CuRVES - 4 POlE MOTORS - CHGT / CGT
CHGT / CGT
Number of poles 4
Nominal diameter (mm) 800
Number of blades 6
CHGT/4-800-6/_°-_ kWCGT/4-800-6/_°-_ kW
Hz A B C
63 38 38 31
125 22 21 19
250 12 9 12
500 5 5 6
1000 4 5 5
2000 7 8 6
4000 12 14 11
8000 18 23 19
Table of correction factors for the calculation of the sound power level spectrum.
THE SOUND LEVEL VALUES IN THE PERFORMANCE CURVES CORRESPOND TO SOUND POWER LEVELS LwA.
TO CONVERT THIS DATA INTO SOUND PRESSURE LEVEL VALUES LpA, SUBTRACT REDUCTION DUE TO DISTANCE.
- qv: Air volume in m3/h and m3/s.- psf: Static pressure in mmWG and Pa.– Dry air at 20ºC and 760 mmHg.– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.
www.solerpalau.com
AXIAL FLOW CABINET FANSCHGT Series
Cylindrical cased axial flow fans CHGT
PERfORMANCE CuRVES - 4 POlE MOTORS - CHGT / CGT
CHGT / CGT
Number of poles 4
Nominal diameter (mm) 800
Number of blades 9
CHGT/4-800-9/_°-_ kWCGT/4-800-9/_°-_ kW
Hz A B C
63 40 38 32
125 26 19 19
250 14 9 11
500 6 5 7
1000 4 5 5
2000 7 7 6
4000 12 13 10
8000 20 21 17
Table of correction factors for the calculation of the sound power level spectrum.
THE SOUND LEVEL VALUES IN THE PERFORMANCE CURVES CORRESPOND TO SOUND POWER LEVELS LwA.
TO CONVERT THIS DATA INTO SOUND PRESSURE LEVEL VALUES LpA, SUBTRACT REDUCTION DUE TO DISTANCE.
- qv: Air volume in m3/h and m3/s.- psf: Static pressure in mmWG and Pa.– Dry air at 20ºC and 760 mmHg.– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.
www.solerpalau.com
AXIAL FLOW CABINET FANSCHGT Series
Cylindrical cased axial flow fans CHGT
PERfORMANCE CuRVES - 4 POlE MOTORS - CHGT / CGT
CHGT / CGT
Number of poles 4
Nominal diameter (mm) 900
Number of blades 6
CHGT/4-900-6/_°-_ kWCGT/4-900-6/_°-_ kW
Hz A B C
63 38 38 31
125 22 21 19
250 12 9 12
500 5 5 6
1000 4 5 5
2000 7 8 6
4000 13 14 11
8000 21 23 19
Table of correction factors for the calculation of the sound power level spectrum.
THE SOUND LEVEL VALUES IN THE PERFORMANCE CURVES CORRESPOND TO SOUND POWER LEVELS LwA.
TO CONVERT THIS DATA INTO SOUND PRESSURE LEVEL VALUES LpA, SUBTRACT REDUCTION DUE TO DISTANCE.
- qv: Air volume in m3/h and m3/s.- psf: Static pressure in mmWG and Pa.– Dry air at 20ºC and 760 mmHg.– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.
www.solerpalau.com
AXIAL FLOW CABINET FANSCHGT Series
Cylindrical cased axial flow fans CHGT
PERfORMANCE CuRVES - 4 POlE MOTORS - CHGT / CGT
CHGT / CGT
Number of poles 4
Nominal diameter (mm) 900
Number of blades 9
CHGT/4-900-9/_°-_ kWCGT/4-900-9/_°-_ kW
Hz A B C
63 40 38 32
125 26 19 19
250 14 9 11
500 6 5 7
1000 4 5 5
2000 7 7 6
4000 12 13 10
8000 20 21 17
Table of correction factors for the calculation of the sound power level spectrum.
THE SOUND LEVEL VALUES IN THE PERFORMANCE CURVES CORRESPOND TO SOUND POWER LEVELS LwA.
TO CONVERT THIS DATA INTO SOUND PRESSURE LEVEL VALUES LpA, SUBTRACT REDUCTION DUE TO DISTANCE.
CB
A
psf psf(Pa)
70070
65
60
55
50
45
40
35
30
25
20
15
10
5
0
650
600
550
500
450
400
350
300
250
200
150
100
50
0
8°10°12°14°16°
18°
20°22°
24°26°
28°30°32°
94
98
100 99 96 97 99
98 94 95 97 Lw dB (A)
98 95 94 96
5000
2 4 6 8 10 12 14 16 18
15000 25000 35000 45000 55000 65000 qv [m3/h]
qv [m3/s]
16000
14000
12000
10000
8000
6000
4000
20005000 15000 25000 35000 45000 55000 65000
Pabs (W )
qv [m3/h]
32°
30°
28°26°
24°22°
20°18°
16°
14°12°10°8°
15
11
7.5
5.5
4
(mmWG)
motorRecommended
power (kW)Absorbed power (W)
- qv: Air volume in m3/h and m3/s.- psf: Static pressure in mmWG and Pa.– Dry air at 20ºC and 760 mmHg.– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.
- qv: Air volume in m3/h and m3/s.- psf: Static pressure in mmWG and Pa.– Dry air at 20ºC and 760 mmHg.– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.
www.solerpalau.com
AXIAL FLOW CABINET FANSCHGT Series
Cylindrical cased axial flow fans CHGT
PERfORMANCE CuRVES - 4 POlE MOTORS - CHGT / CGT
CHGT / CGT
Number of poles 4
Nominal diameter (mm) 1000
Number of blades 9
CHGT/4-1000-9/_°-_ kWCGT/4-1000-9/_°-_ kW
Hz A B C
63 40 38 32
125 26 19 19
250 14 9 11
500 6 5 7
1000 4 5 5
2000 7 7 6
4000 12 13 10
8000 20 21 17
Table of correction factors for the calculation of the sound power level spectrum.
THE SOUND LEVEL VALUES IN THE PERFORMANCE CURVES CORRESPOND TO SOUND POWER LEVELS LwA.
TO CONVERT THIS DATA INTO SOUND PRESSURE LEVEL VALUES LpA, SUBTRACT REDUCTION DUE TO DISTANCE.
- qv: Air volume in m3/h and m3/s.- psf: Static pressure in mmWG and Pa.– Dry air at 20ºC and 760 mmHg.– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.
www.solerpalau.com
AXIAL FLOW CABINET FANSCHGT Series
Cylindrical cased axial flow fans CHGT
PERfORMANCE CuRVES - 4 POlE MOTORS - CHGT / CGT
CHGT / CGT
Number of poles 4
Nominal diameter (mm) 1250
Number of blades 6
CHGT/4-1250-6/_°-_ kWCGT/4-1250-6/_°-_ kW
Hz A B C
63 38 38 31
125 22 21 19
250 12 9 12
500 5 5 6
1000 4 5 5
2000 7 8 6
4000 13 14 11
8000 21 23 19
Table of correction factors for the calculation of the sound power level spectrum.
THE SOUND LEVEL VALUES IN THE PERFORMANCE CURVES CORRESPOND TO SOUND POWER LEVELS LwA.
TO CONVERT THIS DATA INTO SOUND PRESSURE LEVEL VALUES LpA, SUBTRACT REDUCTION DUE TO DISTANCE.
- qv: Air volume in m3/h and m3/s.- psf: Static pressure in mmWG and Pa.– Dry air at 20ºC and 760 mmHg.– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.
www.solerpalau.com
AXIAL FLOW CABINET FANSCHGT Series
Cylindrical cased axial flow fans CHGT
PERfORMANCE CuRVES - 4 POlE MOTORS - CHGT / CGT
CHGT / CGT
Number of poles 4
Nominal diameter (mm) 1250
Number of blades 9
CHGT/4-1250-9/_°-_ kWCGT/4-1250-9/_°-_ kW
Hz A B C
63 40 38 32
125 26 19 19
250 14 9 11
500 6 5 7
1000 4 5 5
2000 7 7 6
4000 12 13 10
8000 20 21 17
Table of correction factors for the calculation of the sound power level spectrum.
THE SOUND LEVEL VALUES IN THE PERFORMANCE CURVES CORRESPOND TO SOUND POWER LEVELS LwA.
TO CONVERT THIS DATA INTO SOUND PRESSURE LEVEL VALUES LpA, SUBTRACT REDUCTION DUE TO DISTANCE.
- qv: Air volume in m3/h and m3/s.- psf: Static pressure in mmWG and Pa.– Dry air at 20ºC and 760 mmHg.– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.
www.solerpalau.com
AXIAL FLOW CABINET FANSCHGT Series
Cylindrical cased axial flow fans CHGT
PERfORMANCE CuRVES - 6 POlE MOTORS - CHGT / CGT
CHGT / CGT
Number of poles 6
Nominal diameter (mm) 500
Number of blades 6
CHGT/6-500-6/_°-_ kWCGT/6-500-6/_°-_ kW
Hz A B C
63 33 33 28
125 18 15 18
250 9 8 10
500 5 5 5
1000 5 5 5
2000 8 10 7
4000 15 16 13
8000 23 25 21
Table of correction factors for the calculation of the sound power level spectrum.
THE SOUND LEVEL VALUES IN THE PERFORMANCE CURVES CORRESPOND TO SOUND POWER LEVELS LwA.
TO CONVERT THIS DATA INTO SOUND PRESSURE LEVEL VALUES LpA, SUBTRACT REDUCTION DUE TO DISTANCE.
CB
A
9
10
11
12
8
7
6
5
4
3
2
1
0
90
100
110
120
80
70
60
50
40
30
20
10
0
psf psf(Pa) (mmWG)
qv [m3/h]
qv [m3/s]
8°10°12°14°
16°
18°
20°24° 28° 32°34°
36°38°
62 70 68 66
66 69 69 Lw dB(A)67 67 67
716969697068
66 67
0
0 0.3 0.6 0.9 1.2 1.5 1.8 2.1 2.4
1000 2000 3000 4000 5000 6000 7000 90008000
Pabs (W )350
300
250
200
150
100
00 1000 2000 3000 4000 5000 6000 7000 8000 9000
50
qv [m3/h]
0.37
38°
36°
34°32°
30°28°
26°24°
22°20°18°16°14°12°10°8°
motorRecommended
power (kW)Absorbed power (W)
- qv: Air volume in m3/h and m3/s.- psf: Static pressure in mmWG and Pa.– Dry air at 20ºC and 760 mmHg.– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.
www.solerpalau.com
AXIAL FLOW CABINET FANSCHGT Series
Cylindrical cased axial flow fans CHGT
PERfORMANCE CuRVES - 6 POlE MOTORS - CHGT / CGT
CHGT / CGT
Number of poles 6
Nominal diameter (mm) 560
Number of blades 6
CHGT/6-560-6/_°-_ kWCGT/6-560-6/_°-_ kW
Hz A B C
63 33 33 28
125 18 15 18
250 9 8 10
500 5 5 5
1000 5 5 5
2000 8 10 7
4000 15 16 13
8000 23 25 21
Table of correction factors for the calculation of the sound power level spectrum.
THE SOUND LEVEL VALUES IN THE PERFORMANCE CURVES CORRESPOND TO SOUND POWER LEVELS LwA.
TO CONVERT THIS DATA INTO SOUND PRESSURE LEVEL VALUES LpA, SUBTRACT REDUCTION DUE TO DISTANCE.
- qv: Air volume in m3/h and m3/s.- psf: Static pressure in mmWG and Pa.– Dry air at 20ºC and 760 mmHg.– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.
www.solerpalau.com
AXIAL FLOW CABINET FANSCHGT Series
Cylindrical cased axial flow fans CHGT
PERfORMANCE CuRVES - 6 POlE MOTORS - CHGT / CGT
CHGT / CGT
Number of poles 6
Nominal diameter (mm) 630
Number of blades 5
CHGT/6-630-6/_°-_ kWCGT/6-630-6/_°-_ kW
Hz A B C
63 33 33 28
125 18 15 18
250 9 8 10
500 5 5 5
1000 5 5 5
2000 8 10 7
4000 15 16 13
8000 23 25 21
Table of correction factors for the calculation of the sound power level spectrum.
THE SOUND LEVEL VALUES IN THE PERFORMANCE CURVES CORRESPOND TO SOUND POWER LEVELS LwA.
TO CONVERT THIS DATA INTO SOUND PRESSURE LEVEL VALUES LpA, SUBTRACT REDUCTION DUE TO DISTANCE.
- qv: Air volume in m3/h and m3/s.- psf: Static pressure in mmWG and Pa.– Dry air at 20ºC and 760 mmHg.– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.
Table of correction factors for the calculation of the sound power level spectrum.
THE SOUND LEVEL VALUES IN THE PERFORMANCE CURVES CORRESPOND TO SOUND POWER LEVELS LwA.
TO CONVERT THIS DATA INTO SOUND PRESSURE LEVEL VALUES LpA, SUBTRACT REDUCTION DUE TO DISTANCE.
CBA
0 4000 8000 12000 16000 20000
1 2 3 4 5
0
2
4
6
8
10
12
14
16
18
0
20
40
60
80
100
120
140
160
180
8°
14°
16°
18°
20°24°
22°26° 28° 30° 32°
0 4000 8000 12000 16000 200000
200
400
600
800
1000
Pabs (W )
0.55
0.7532°
30°
28°26°
24°22°
20°18°
16°14°12°
10°8°
8180787981
81 LwdB(A)80788081
81818278
12°
10°
82
psf psf(Pa)
qv [m3/h]
qv [m3/h]
qv [m3/s]
Recommendedmotorpower (KW)Absorbed power (W)
(mmWG)
- qv: Air volume in m3/h and m3/s.- psf: Static pressure in mmWG and Pa.– Dry air at 20ºC and 760 mmHg.– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.
Table of correction factors for the calculation of the sound power level spectrum.
THE SOUND LEVEL VALUES IN THE PERFORMANCE CURVES CORRESPOND TO SOUND POWER LEVELS LwA.
TO CONVERT THIS DATA INTO SOUND PRESSURE LEVEL VALUES LpA, SUBTRACT REDUCTION DUE TO DISTANCE.
CBA
0 4000 8000 12000 16000 20000
1 2 3 4 5
0
5
10
15
20
25
0
50
100
150
200
2508° 14°16°
18°
20°
24°
22°
26°28°30° 32°
0 4000 8000 12000 16000 200000
200
400
600
800
1000
1200
Pabs (W )
0.55
0.75
1.1
Recommendedmotorpower (KW)Absorbed power (W)
32°
30°
28°26°
24°
22°20°
18°16°
14°12°
10°8°
8281818282
83 LwdB(A)81818382
82838580
12°10°
83
psf psf(Pa) (mmWG)
qv [m3/h]
qv [m3/h]
qv [m3/s]
- qv: Air volume in m3/h and m3/s.- psf: Static pressure in mmWG and Pa.– Dry air at 20ºC and 760 mmHg.– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.
www.solerpalau.com
AXIAL FLOW CABINET FANSCHGT Series
Cylindrical cased axial flow fans CHGT
CBA
0 4000 8000 12000 16000 20000
1 2 3 4 5
0
5
10
15
20
25
0
50
100
150
200
2508° 14°16°
18°
20°
24°
22°
26°28°30° 32°
0 4000 8000 12000 16000 200000
200
400
600
800
1000
1200
Pabs (W )
0.55
0.75
1.1
Recommendedmotorpower (KW)Absorbed power (W)
32°
30°
28°26°
24°
22°20°
18°16°
14°12°
10°8°
8281818282
83 LwdB(A)81818382
82838580
12°10°
83
psf psf(Pa) (mmWG)
qv [m3/h]
qv [m3/h]
qv [m3/s]
PERfORMANCE CuRVES - 6 POlE MOTORS - CHGT
CHGT
Number of poles 6
Nominal diameter (mm) 710
Number of blades 5 or 7
CHGT/6-710-_/_°-_ kW
Hz A B C
63 33 33 28
125 18 15 18
250 9 8 10
500 5 5 5
1000 5 5 5
2000 8 10 7
4000 13 16 13
8000 19 25 21
Table of correction factors for the calculation of the sound power level spectrum.
THE SOUND LEVEL VALUES IN THE PERFORMANCE CURVES CORRESPOND TO SOUND POWER LEVELS LwA.
TO CONVERT THIS DATA INTO SOUND PRESSURE LEVEL VALUES LpA, SUBTRACT REDUCTION DUE TO DISTANCE.
- qv: Air volume in m3/h and m3/s.- psf: Static pressure in mmWG and Pa.– Dry air at 20ºC and 760 mmHg.– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.
www.solerpalau.com
AXIAL FLOW CABINET FANSCHGT Series
Cylindrical cased axial flow fans CHGT
PERfORMANCE CuRVES - 6 POlE MOTORS - CHGT / CGT
CHGT / CGT
Number of poles 6
Nominal diameter (mm) 800
Number of blades 3
CHGT/6-800-3/_°-_ kWCGT/6-800-3/_°-_ kW
Hz A B C
63 25 25 22
125 19 17 18
250 11 9 10
500 6 5 6
1000 4 5 4
2000 8 9 8
4000 13 14 14
8000 20 22 23
Table of correction factors for the calculation of the sound power level spectrum.
THE SOUND LEVEL VALUES IN THE PERFORMANCE CURVES CORRESPOND TO SOUND POWER LEVELS LwA.
TO CONVERT THIS DATA INTO SOUND PRESSURE LEVEL VALUES LpA, SUBTRACT REDUCTION DUE TO DISTANCE.
- qv: Air volume in m3/h and m3/s.- psf: Static pressure in mmWG and Pa.– Dry air at 20ºC and 760 mmHg.– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.
www.solerpalau.com
AXIAL FLOW CABINET FANSCHGT Series
Cylindrical cased axial flow fans CHGT
PERfORMANCE CuRVES - 6 POlE MOTORS - CHGT / CGT
CHGT / CGT
Number of poles 6
Nominal diameter (mm) 800
Number of blades 6
CHGT/6-800-6/_°-_ kWCGT/6-800-6/_°-_ kW
Hz A B C
63 33 33 28
125 18 15 18
250 9 8 10
500 5 5 5
1000 5 5 5
2000 8 10 7
4000 15 16 13
8000 23 25 21
Table of correction factors for the calculation of the sound power level spectrum.
THE SOUND LEVEL VALUES IN THE PERFORMANCE CURVES CORRESPOND TO SOUND POWER LEVELS LwA.
TO CONVERT THIS DATA INTO SOUND PRESSURE LEVEL VALUES LpA, SUBTRACT REDUCTION DUE TO DISTANCE.
CB
A
psf psf(Pa)
300
250
200
150
100
50
0
30
25
20
15
10
5
00
0 1 2 3 4 5 6 7
4000 8000 12000 16000 20000 24000 28000 qv [m3/h]
qv [m3/s]
8°
10°12° 14°
16°
18°
20°22°24° 26°28°30°32°
78 80 80 81
81 82 Lw dB(A)82
84 83 82 83 84
82 80
82
Pabs (W )
2.2
1.5
1.1
0.75
0.55
32°
30°
28°
26°
22°
24°
20°18°
16°14°12°10°
8°
0 4000 8000 12000 16000 20000 24000 28000
2200
2000
1800
1600
1400
1200
1000
800
600
400
200qv [m3/h]
(mmWG)
motorRecommended
power (kW)Absorbed power (W)
- qv: Air volume in m3/h and m3/s.- psf: Static pressure in mmWG and Pa.– Dry air at 20ºC and 760 mmHg.– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.
www.solerpalau.com
AXIAL FLOW CABINET FANSCHGT Series
Cylindrical cased axial flow fans CHGT
PERfORMANCE CuRVES - 6 POlE MOTORS - CHGT / CGT
CHGT / CGT
Number of poles 6
Nominal diameter (mm) 800
Number of blades 9
CHGT/6-800-9/_°-_ kWCGT/6-800-9/_°-_ kW
Hz A B C
63 37 31 29
125 22 15 16
250 11 8 10
500 5 5 6
1000 4 5 5
2000 9 9 7
4000 14 15 11
8000 22 23 19
Table of correction factors for the calculation of the sound power level spectrum.
THE SOUND LEVEL VALUES IN THE PERFORMANCE CURVES CORRESPOND TO SOUND POWER LEVELS LwA.
TO CONVERT THIS DATA INTO SOUND PRESSURE LEVEL VALUES LpA, SUBTRACT REDUCTION DUE TO DISTANCE.
- qv: Air volume in m3/h and m3/s.- psf: Static pressure in mmWG and Pa.– Dry air at 20ºC and 760 mmHg.– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.
www.solerpalau.com
AXIAL FLOW CABINET FANSCHGT Series
Cylindrical cased axial flow fans CHGT
PERfORMANCE CuRVES - 6 POlE MOTORS - CHGT / CGT
CHGT / CGT
Number of poles 6
Nominal diameter (mm) 900
Number of blades 6
CHGT/6-900-6/_°-_ kWCGT/6-900-6/_°-_ kW
Hz A B C
63 33 33 28
125 18 15 18
250 9 8 10
500 5 5 5
1000 5 5 5
2000 8 10 7
4000 15 16 13
8000 23 25 21
Table of correction factors for the calculation of the sound power level spectrum.
THE SOUND LEVEL VALUES IN THE PERFORMANCE CURVES CORRESPOND TO SOUND POWER LEVELS LwA.
TO CONVERT THIS DATA INTO SOUND PRESSURE LEVEL VALUES LpA, SUBTRACT REDUCTION DUE TO DISTANCE.
- qv: Air volume in m3/h and m3/s.- psf: Static pressure in mmWG and Pa.– Dry air at 20ºC and 760 mmHg.– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.
www.solerpalau.com
AXIAL FLOW CABINET FANSCHGT Series
Cylindrical cased axial flow fans CHGT
PERfORMANCE CuRVES - 6 POlE MOTORS - CHGT / CGT
CHGT / CGT
Number of poles 6
Nominal diameter (mm) 900
Number of blades 9
CHGT/6-900-9/_°-_ kWCGT/6-900-9/_°-_ kW
Hz A B C
63 37 31 29
125 22 15 16
250 11 8 10
500 5 5 6
1000 4 5 5
2000 9 9 7
4000 14 15 11
8000 22 23 19
Table of correction factors for the calculation of the sound power level spectrum.
THE SOUND LEVEL VALUES IN THE PERFORMANCE CURVES CORRESPOND TO SOUND POWER LEVELS LwA.
TO CONVERT THIS DATA INTO SOUND PRESSURE LEVEL VALUES LpA, SUBTRACT REDUCTION DUE TO DISTANCE.
- qv: Air volume in m3/h and m3/s.- psf: Static pressure in mmWG and Pa.– Dry air at 20ºC and 760 mmHg.– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.
www.solerpalau.com
AXIAL FLOW CABINET FANSCHGT Series
Cylindrical cased axial flow fans CHGT
PERfORMANCE CuRVES - 6 POlE MOTORS - CHGT / CGT
CHGT / CGT
Number of poles 6
Nominal diameter (mm) 1000
Number of blades 6
CHGT/6-1000-6/_°-_ kWCGT/6-1000-6/_°-_ kW
Hz A B C
63 22 20 18
125 19 19 17
250 13 11 12
500 6 5 6
1000 4 5 5
2000 6 7 6
4000 11 13 12
8000 18 20 12
Table of correction factors for the calculation of the sound power level spectrum.
THE SOUND LEVEL VALUES IN THE PERFORMANCE CURVES CORRESPOND TO SOUND POWER LEVELS LwA.
TO CONVERT THIS DATA INTO SOUND PRESSURE LEVEL VALUES LpA, SUBTRACT REDUCTION DUE TO DISTANCE.
- qv: Air volume in m3/h and m3/s.- psf: Static pressure in mmWG and Pa.– Dry air at 20ºC and 760 mmHg.– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.
www.solerpalau.com
AXIAL FLOW CABINET FANSCHGT Series
Cylindrical cased axial flow fans CHGT
PERfORMANCE CuRVES - 6 POlE MOTORS - CHGT / CGT
CHGT / CGT
Number of poles 6
Nominal diameter (mm) 1000
Number of blades 9
CHGT/6-1000-9/_°-_ kWCGT/6-1000-9/_°-_ kW
Hz A B C
63 37 31 29
125 22 15 16
250 11 8 10
500 4 5 6
1000 4 5 5
2000 9 9 7
4000 14 15 11
8000 22 23 19
Table of correction factors for the calculation of the sound power level spectrum.
THE SOUND LEVEL VALUES IN THE PERFORMANCE CURVES CORRESPOND TO SOUND POWER LEVELS LwA.
TO CONVERT THIS DATA INTO SOUND PRESSURE LEVEL VALUES LpA, SUBTRACT REDUCTION DUE TO DISTANCE.
- qv: Air volume in m3/h and m3/s.- psf: Static pressure in mmWG and Pa.– Dry air at 20ºC and 760 mmHg.– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.
www.solerpalau.com
AXIAL FLOW CABINET FANSCHGT Series
Cylindrical cased axial flow fans CHGT
PERfORMANCE CuRVES - 6 POlE MOTORS - CHGT / CGT
CHGT / CGT
Number of poles 6
Nominal diameter (mm) 1250
Number of blades 6
CHGT/6-1250-6/_°-_ kWCGT/6-1250-6/_°-_ kW
Hz A B C
63 33 33 28
125 18 15 18
250 9 8 10
500 5 5 5
1000 5 5 5
2000 8 10 7
4000 15 16 13
8000 23 25 21
Table of correction factors for the calculation of the sound power level spectrum.
THE SOUND LEVEL VALUES IN THE PERFORMANCE CURVES CORRESPOND TO SOUND POWER LEVELS LwA.
TO CONVERT THIS DATA INTO SOUND PRESSURE LEVEL VALUES LpA, SUBTRACT REDUCTION DUE TO DISTANCE.
- qv: Air volume in m3/h and m3/s.- psf: Static pressure in mmWG and Pa.– Dry air at 20ºC and 760 mmHg.– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.
www.solerpalau.com
AXIAL FLOW CABINET FANSCHGT Series
Cylindrical cased axial flow fans CHGT
PERfORMANCE CuRVES - 6 POlE MOTORS - CHGT / CGT
CHGT / CGT
Number of poles 6
Nominal diameter (mm) 1250
Number of blades 9
CHGT/6-1250-9/_°-_ kWCGT/6-1250-9/_°-_ kW
Hz A B C
63 37 31 29
125 22 15 16
250 11 8 10
500 5 5 6
1000 4 5 5
2000 9 9 7
4000 14 15 11
8000 22 23 19
Table of correction factors for the calculation of the sound power level spectrum.
THE SOUND LEVEL VALUES IN THE PERFORMANCE CURVES CORRESPOND TO SOUND POWER LEVELS LwA.
TO CONVERT THIS DATA INTO SOUND PRESSURE LEVEL VALUES LpA, SUBTRACT REDUCTION DUE TO DISTANCE.
- qv: Air volume in m3/h and m3/s.- psf: Static pressure in mmWG and Pa.– Dry air at 20ºC and 760 mmHg.– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.