AUTOMATIC VOLTAGE REGULATOR(AVR) Automatic voltage regulator (AVR) maintains the Generator terminal voltage at a given value automatically by changing the excitation current to the Generator field. The AVR supplies the required D.C. to the Generator field depending on the load, power factor etc. to maintain a constant terminal voltage. 1
18

AUTOMATIC VOLTAGE REGULATOR(AVR) Automatic voltage regulator (AVR) maintains the Generator terminal voltage at a given value automatically by changing.

Dec 28, 2015

Download

Documents

Marcia McCoy
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: AUTOMATIC VOLTAGE REGULATOR(AVR) Automatic voltage regulator (AVR) maintains the Generator terminal voltage at a given value automatically by changing.

AUTOMATIC VOLTAGE REGULATOR(AVR)

Automatic voltage regulator (AVR) maintains the Generator terminal voltage at a given value automatically by changing the excitation current to the Generator field.

The AVR supplies the required D.C. to the Generator field depending on the load, power factor etc. to maintain a constant terminal voltage.

1

Page 2: AUTOMATIC VOLTAGE REGULATOR(AVR) Automatic voltage regulator (AVR) maintains the Generator terminal voltage at a given value automatically by changing.

CONTROL SYSTEMS OF AVR

1. Auto control

2. Manual control

2

Page 3: AUTOMATIC VOLTAGE REGULATOR(AVR) Automatic voltage regulator (AVR) maintains the Generator terminal voltage at a given value automatically by changing.

TYPES OF AVR

1.Single channel AVR

Two controllers one is automatic and the other is manual

Both the controllers are fed from the same supply

3

Page 4: AUTOMATIC VOLTAGE REGULATOR(AVR) Automatic voltage regulator (AVR) maintains the Generator terminal voltage at a given value automatically by changing.

2. Dual channel AVR system One automatic voltage controller

and one manual controller Different power supply, gate

control and pulse amplifier units for each of the controllers

4

Page 5: AUTOMATIC VOLTAGE REGULATOR(AVR) Automatic voltage regulator (AVR) maintains the Generator terminal voltage at a given value automatically by changing.

3.Twin channel AVR system

Two automatic voltage regulators

5

Page 6: AUTOMATIC VOLTAGE REGULATOR(AVR) Automatic voltage regulator (AVR) maintains the Generator terminal voltage at a given value automatically by changing.

Function of AVR compares the Generator terminal

voltage with a preset reference voltage.

If the Generator terminal voltage is less than the reference voltage, the AVR increases D.C. voltage across the Generator field.

Maintaining the constant voltage as per the setting.

6

Page 7: AUTOMATIC VOLTAGE REGULATOR(AVR) Automatic voltage regulator (AVR) maintains the Generator terminal voltage at a given value automatically by changing.

The automatic voltage control system

EXCITATION AS A CLOSED LOOP CONTROL SYSTEM

Grid

If Vg Synchronous

Generator

Excitation

System

Page 8: AUTOMATIC VOLTAGE REGULATOR(AVR) Automatic voltage regulator (AVR) maintains the Generator terminal voltage at a given value automatically by changing.

2

3

4

7

6

GAIN

INPUT OUTPUT

OP AMP

REF

FEED BACK

OPERATIONAL AMPLIFIER

Page 9: AUTOMATIC VOLTAGE REGULATOR(AVR) Automatic voltage regulator (AVR) maintains the Generator terminal voltage at a given value automatically by changing.

Block diagram of AVR

9

Page 10: AUTOMATIC VOLTAGE REGULATOR(AVR) Automatic voltage regulator (AVR) maintains the Generator terminal voltage at a given value automatically by changing.

AVR inputs Generator voltage feedback signal Generator voltage reference AVR provides the following

functions and signals Summing and amplification of signals to

provide the exciter rectifier firing angle control signal.

A signal for manual follow up.

10

Page 11: AUTOMATIC VOLTAGE REGULATOR(AVR) Automatic voltage regulator (AVR) maintains the Generator terminal voltage at a given value automatically by changing.

AVR Action Two inputs are of opposite polarity. When the magnitudes are equal,

the net input is zero. When unequal-the error is

amplified and reversed to obtain a correction signal which goes to the

GPG(gate pulse generator)

11

Page 12: AUTOMATIC VOLTAGE REGULATOR(AVR) Automatic voltage regulator (AVR) maintains the Generator terminal voltage at a given value automatically by changing.

AVR CIRCUIT

12

Page 13: AUTOMATIC VOLTAGE REGULATOR(AVR) Automatic voltage regulator (AVR) maintains the Generator terminal voltage at a given value automatically by changing.

+-50 V SUPPLY To power the regulator amplifier as

well as the optional accessories such as manual follow up and power integral stabilizer

13

Page 14: AUTOMATIC VOLTAGE REGULATOR(AVR) Automatic voltage regulator (AVR) maintains the Generator terminal voltage at a given value automatically by changing.

Regulator auxiliary card 3 phase voltage from the generator

PT’s are stepped down and applied to the regulator auxiliary card which converts it to ripple free dc voltage suitable for the input of regulator amplifier.

Page 15: AUTOMATIC VOLTAGE REGULATOR(AVR) Automatic voltage regulator (AVR) maintains the Generator terminal voltage at a given value automatically by changing.

Balance Voltmeter

A 30-0-30 V dc voltmeter is connected across the output of regulator amplifier to read the magnitude and polarity of the output voltage of OP-AMP at any instant.

Page 16: AUTOMATIC VOLTAGE REGULATOR(AVR) Automatic voltage regulator (AVR) maintains the Generator terminal voltage at a given value automatically by changing.

AVR Voltage Setting

From the +-50 V source ,-50 V is applied and taken across a motorized potentiometer which can be operated from the control bench board. The variable output from the pot. is applied to the input of the regulator OP-AMP.

Page 17: AUTOMATIC VOLTAGE REGULATOR(AVR) Automatic voltage regulator (AVR) maintains the Generator terminal voltage at a given value automatically by changing.

Manual Voltage Control In the absence of AVR the voltage

can be manually controlled. The stabilized 15 V from the MPS is

applied across a second potentiometer. The variable output goes to the GPG together with output of the regulator

OP-AMP.

Page 18: AUTOMATIC VOLTAGE REGULATOR(AVR) Automatic voltage regulator (AVR) maintains the Generator terminal voltage at a given value automatically by changing.

MANUAL FOLLOW UP

When there is a noticeable output from the regulator OP-AMP, depending on its polarity, either of a pair of relays is automatically closed to drive the manual potentiometer motor in the required direction.