Hong Kong Convention and Exhibition Centre, Hong Kong 22 June 2009 Atrium Hot Smoke Test Atrium Hot Smoke Test at HKCEC at HKCEC at HKCEC at HKCEC (Ir Professor W.K. Chow) (Ir Professor W.K. Chow) (Ir Professor W.K. Chow) (Ir Professor W.K. Chow) Presented by Professor W.K. Chow Chair Professor of Architectural Science and Fire Engineering Director , Research Centre for Fire Engineering Head of Department, Department of Building Services Engineering Leader, Area of Strength: Fire Safety Engineering AHSTHKCEC2A1.ppt
48

Atrium Hot Smoke Test atat HKCECHKCECat HKCEC (Ir ...Fire Services Department (FSD), hot smoke tests (HST) are required as higgghlighted to evaluate the smoke extraction system for

Sep 30, 2020

Download

Documents

dariahiddleston
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Atrium Hot Smoke Test atat HKCECHKCECat HKCEC (Ir ...Fire Services Department (FSD), hot smoke tests (HST) are required as higgghlighted to evaluate the smoke extraction system for

Hong Kong Convention and Exhibition Centre, Hong Kong22 June 2009

Atrium Hot Smoke TestAtrium Hot Smoke Testat HKCECat HKCECat HKCECat HKCEC(Ir Professor W.K. Chow)(Ir Professor W.K. Chow)(Ir Professor W.K. Chow)(Ir Professor W.K. Chow)

Presented by Professor W.K. ChowChair Professor of Architectural Science and Fire EngineeringDirector, Research Centre for Fire Engineering, g gHead of Department, Department of Building Services EngineeringLeader, Area of Strength: Fire Safety Engineering

AHSTHKCEC2A1.ppt

Page 2: Atrium Hot Smoke Test atat HKCECHKCECat HKCEC (Ir ...Fire Services Department (FSD), hot smoke tests (HST) are required as higgghlighted to evaluate the smoke extraction system for

1 Introduction1. Introduction

2

Page 3: Atrium Hot Smoke Test atat HKCECHKCECat HKCEC (Ir ...Fire Services Department (FSD), hot smoke tests (HST) are required as higgghlighted to evaluate the smoke extraction system for

Foyer AH K C ti d E hibitiHong Kong Convention and Exhibition Centre – Expansion Project (HKCEC Expansion Project)

To evaluate the performance of dynamic smokeexhaust systems in the HKCEC ExpansionProject through the application of a hot smoketest

3

Page 4: Atrium Hot Smoke Test atat HKCECHKCECat HKCEC (Ir ...Fire Services Department (FSD), hot smoke tests (HST) are required as higgghlighted to evaluate the smoke extraction system for

Hong Kong Convention and

4Exhibition Centre

Page 5: Atrium Hot Smoke Test atat HKCECHKCECat HKCEC (Ir ...Fire Services Department (FSD), hot smoke tests (HST) are required as higgghlighted to evaluate the smoke extraction system for

The siteThe site

5

Page 6: Atrium Hot Smoke Test atat HKCECHKCECat HKCEC (Ir ...Fire Services Department (FSD), hot smoke tests (HST) are required as higgghlighted to evaluate the smoke extraction system for

Foyer Ay

6

Page 7: Atrium Hot Smoke Test atat HKCECHKCECat HKCEC (Ir ...Fire Services Department (FSD), hot smoke tests (HST) are required as higgghlighted to evaluate the smoke extraction system for

Testing procedure followed those in AS 4391-1999 as specified inthe Fire Service Installations (FSI) Code. Test fire with a heat

l f 2 MW ill b d Thi l i fi d hrelease rate of 2 MW will be used. This value satisfied thespecification in FSI with heat release rate higher than 1 MW.

The main testing criterion is to demonstrate the acceptableThe main testing criterion is to demonstrate the acceptableperformance of the proposed fire safety systems.

Evaluate the smoke hazard management performance in Foyer Ag p ywith reference to the smoke layer height being maintained at a levelabove 2.8 m (see Appendix K for details). Other testing criteria listedin the FSI Code will be followedin the FSI Code will be followed.

The air temperature criterion will be watched as roof sprinkler wasinstalled for suppressing fire. Sprinkler heads at some positions willbe thermally lagged. The smoke temperature is estimated to be in theorder of 55°C (see Appendix K for details).

7

Page 8: Atrium Hot Smoke Test atat HKCECHKCECat HKCEC (Ir ...Fire Services Department (FSD), hot smoke tests (HST) are required as higgghlighted to evaluate the smoke extraction system for

The test is conducted together with a team fromThe test is conducted together with a team fromthe Harbin Engineering University

L d P f G YLeaders: Professor Gao Ye

Professor Dong HuiProfessor Dong Hui

8

Page 9: Atrium Hot Smoke Test atat HKCECHKCECat HKCEC (Ir ...Fire Services Department (FSD), hot smoke tests (HST) are required as higgghlighted to evaluate the smoke extraction system for

Th t9

The team

Page 10: Atrium Hot Smoke Test atat HKCECHKCECat HKCEC (Ir ...Fire Services Department (FSD), hot smoke tests (HST) are required as higgghlighted to evaluate the smoke extraction system for

2 Objectives of the Test2. Objectives of the Test

10

Page 11: Atrium Hot Smoke Test atat HKCECHKCECat HKCEC (Ir ...Fire Services Department (FSD), hot smoke tests (HST) are required as higgghlighted to evaluate the smoke extraction system for

As specified in section 2.23 of the Fire ServiceInstallations (FSI) Code 2005 as in Appendix A by theInstallations (FSI) Code 2005 as in Appendix A by theFire Services Department (FSD), hot smoke tests (HST)are required as highlighted to evaluate the smokeq g gextraction system for a wide range of premise classes andareas of special risks for compartments with

– Headroom of 12 m or more; or

– Irregular geometrical dimensions or extraordinary largeIrregular geometrical dimensions or extraordinary largesize.

Reference of HST is made to the Australian Standard ASReference of HST is made to the Australian Standard AS4391.

11

Page 12: Atrium Hot Smoke Test atat HKCECHKCECat HKCEC (Ir ...Fire Services Department (FSD), hot smoke tests (HST) are required as higgghlighted to evaluate the smoke extraction system for

Foyer A has a floor area 2,565 m2y ,The hall void volume is approximately 51,355 m3.The smoke clear height for Foyer A is 2 8 m with a 7The smoke clear height for Foyer A is 2.8 m with a 7MW design fire in FE Report.Agreed to be 4.5 m with a 2 MW fire in hot smoke test.g

12

Page 13: Atrium Hot Smoke Test atat HKCECHKCECat HKCEC (Ir ...Fire Services Department (FSD), hot smoke tests (HST) are required as higgghlighted to evaluate the smoke extraction system for

To Phase 2 L7

15

L5 30 m

95 m 27 m

15 m

L2

Make-up air louversTo Phase 1

Make-up air flow

p

Remark: Extraction louvers uniformly distributed at the edge or under the slab of each level.

Zone A of Foyer

13

Page 14: Atrium Hot Smoke Test atat HKCECHKCECat HKCEC (Ir ...Fire Services Department (FSD), hot smoke tests (HST) are required as higgghlighted to evaluate the smoke extraction system for

3 The Fire Source3. The Fire Source

14

Page 15: Atrium Hot Smoke Test atat HKCECHKCECat HKCEC (Ir ...Fire Services Department (FSD), hot smoke tests (HST) are required as higgghlighted to evaluate the smoke extraction system for

As listed in section 2.2 on pool fire of the HST procedure,a 2 MW fire is proposed for the test.Th t f th fi ld f ll AS 4391 ith iThe apparatus for the fire would follow AS 4391 with sixA1-size fuel trays to give a 2 MW heat output.In accordance with AS 4391 the test fire fuel shall beIn accordance with AS 4391, the test fire fuel shall be‘Denatured Industrial Grade Methylated Spirit (Grade95)’.The fuel trays will sit in individual water baths with floorprotection as detailed in AS 4391.

15

Page 16: Atrium Hot Smoke Test atat HKCECHKCECat HKCEC (Ir ...Fire Services Department (FSD), hot smoke tests (HST) are required as higgghlighted to evaluate the smoke extraction system for

The quantities of fuel to be used shall follow thoseThe quantities of fuel to be used shall follow thoserecommended in Table 2.7 of AS 4391. It should besufficient for a steady burning time of about 10 minutesas stated in section 2.2.2 of the HST procedure.

Based on the mock-up tests at the PolyU/USTC Atriump yand the first preliminary field test, approximately 96 litresof methylated spirit will be required for a 2 MW fire with

b i f i i h b i6 trays burning for over 10 minutes, with about 8 minutesof steady burning. Each tray will require about 10 litresof methylated spiritof methylated spirit.

16

Page 17: Atrium Hot Smoke Test atat HKCECHKCECat HKCEC (Ir ...Fire Services Department (FSD), hot smoke tests (HST) are required as higgghlighted to evaluate the smoke extraction system for

2 MW Fire Source

17

Source

Page 18: Atrium Hot Smoke Test atat HKCECHKCECat HKCEC (Ir ...Fire Services Department (FSD), hot smoke tests (HST) are required as higgghlighted to evaluate the smoke extraction system for

4 Hot Smoke Generation4. Hot Smoke Generation

18

Page 19: Atrium Hot Smoke Test atat HKCECHKCECat HKCEC (Ir ...Fire Services Department (FSD), hot smoke tests (HST) are required as higgghlighted to evaluate the smoke extraction system for

As the test fire fuel selected will give clean combustionproducts, the smoke generated is not visible. Tracer

k h ld b i d d b ksmoke should be introduced by a smoke generator.

The Pepper Fog Smoke Generator Mark-XII-Dpreviously used for Hot Smoke Tests at Langham Placeand Mega Box.

The equipment is rented from the Fire ServicesDepartment, Hong Kong as in the first preliminary fieldtest.

19

Page 20: Atrium Hot Smoke Test atat HKCECHKCECat HKCEC (Ir ...Fire Services Department (FSD), hot smoke tests (HST) are required as higgghlighted to evaluate the smoke extraction system for

FSD S k G20

FSD Smoke Gun

Page 21: Atrium Hot Smoke Test atat HKCECHKCECat HKCEC (Ir ...Fire Services Department (FSD), hot smoke tests (HST) are required as higgghlighted to evaluate the smoke extraction system for

5 The Fire Chamber5. The Fire Chamber

21

Page 22: Atrium Hot Smoke Test atat HKCECHKCECat HKCEC (Ir ...Fire Services Department (FSD), hot smoke tests (HST) are required as higgghlighted to evaluate the smoke extraction system for

A chamber is used to reduce thermal radiative effect toA chamber is used to reduce thermal radiative effect toadjacent object.

Th t b fl t tiThere must be floor protection.

Sufficient hot air will be generated by this arrangementand more thoroughly-mixed hot smoke will be dischargedout of the chamber.

This 2 MW test fire is demonstrated by the mock-up testsand the first preliminary field test to generate sufficienth t d b t t t th t kheat and buoyancy to transport the tracer smoke up.

22

Page 23: Atrium Hot Smoke Test atat HKCECHKCECat HKCEC (Ir ...Fire Services Department (FSD), hot smoke tests (HST) are required as higgghlighted to evaluate the smoke extraction system for

42 m

4 m

2.7 m

23

Positions of the smoke generators in the FSD inspection test

Page 24: Atrium Hot Smoke Test atat HKCECHKCECat HKCEC (Ir ...Fire Services Department (FSD), hot smoke tests (HST) are required as higgghlighted to evaluate the smoke extraction system for

24Floor Protection of the Fire Source

Page 25: Atrium Hot Smoke Test atat HKCECHKCECat HKCEC (Ir ...Fire Services Department (FSD), hot smoke tests (HST) are required as higgghlighted to evaluate the smoke extraction system for

25

Page 26: Atrium Hot Smoke Test atat HKCECHKCECat HKCEC (Ir ...Fire Services Department (FSD), hot smoke tests (HST) are required as higgghlighted to evaluate the smoke extraction system for

Ignition of the pool fire

26

Page 27: Atrium Hot Smoke Test atat HKCECHKCECat HKCEC (Ir ...Fire Services Department (FSD), hot smoke tests (HST) are required as higgghlighted to evaluate the smoke extraction system for

27

Page 28: Atrium Hot Smoke Test atat HKCECHKCECat HKCEC (Ir ...Fire Services Department (FSD), hot smoke tests (HST) are required as higgghlighted to evaluate the smoke extraction system for

Smoke gun at back

28Old trial

Page 29: Atrium Hot Smoke Test atat HKCECHKCECat HKCEC (Ir ...Fire Services Department (FSD), hot smoke tests (HST) are required as higgghlighted to evaluate the smoke extraction system for

S k t tSmoke gun at top

New trial

29

New t a

Page 30: Atrium Hot Smoke Test atat HKCECHKCECat HKCEC (Ir ...Fire Services Department (FSD), hot smoke tests (HST) are required as higgghlighted to evaluate the smoke extraction system for

6 Location of6. Location of Temperature SensorsTemperature Sensors

30

Page 31: Atrium Hot Smoke Test atat HKCECHKCECat HKCEC (Ir ...Fire Services Department (FSD), hot smoke tests (HST) are required as higgghlighted to evaluate the smoke extraction system for

Temperature sensors were placed as a thermocoupletree T1 above the cabin.

There should be 14 measuring points of thermocouples(or thermoresistors) at 0 m, 2 m, 4 m, 6 m, 8 m, 10 m,( ) , , , , , ,12 m, 14 m, 16 m, 18 m, 20 m, 22 m, 24 m and 26 mabove the floor and at the ceiling level.

Temperatures to be measured at 5 s intervals, withmeasurement started from 5 minutes before ignition and5 minutes after burning.

Another tree T2 of temperature sensors is suggested top ggbe placed.

(Added to check smoke layer temperature)

31

(Added to check smoke layer temperature)

Page 32: Atrium Hot Smoke Test atat HKCECHKCECat HKCEC (Ir ...Fire Services Department (FSD), hot smoke tests (HST) are required as higgghlighted to evaluate the smoke extraction system for

1 m T1 T2

L7 slab

15 m1 mL7 slab

4 m

L5 slab

L3 slab 4 m

14 m (b) A pictorial view

T1 T2 (a) Thermocouple trees

L2 slab

2 MW test fire Thermocouples on thermocouple trees

Make-up air flow Make-up air louvers 2 m

Location of thermocouples in zone A of Foyer

(c) Thermocouples

Remark: Extraction louvers uniformly distributed at the edge or under the slab of each level.

32

Location of thermocouples in zone A of Foyer

Page 33: Atrium Hot Smoke Test atat HKCECHKCECat HKCEC (Ir ...Fire Services Department (FSD), hot smoke tests (HST) are required as higgghlighted to evaluate the smoke extraction system for

13 m 1 m 1 m

1 m

13

Boundary of L2 for Zone A

1 m 3 m

2 MW fire on floor

Boundary of roof for Zone A at L7

Boundary of L3 for Zone A Boundary of roof for Zone A at L5

Thermocouple trees hanging 2.8 m height line scale attached to wall

p g gat high level down to floor

Camera on floor Test control centre on floor

Pl i f A f F ith t t t

33

Plan view of zone A for Foyer with test setup

Page 34: Atrium Hot Smoke Test atat HKCECHKCECat HKCEC (Ir ...Fire Services Department (FSD), hot smoke tests (HST) are required as higgghlighted to evaluate the smoke extraction system for

T2 T1

30 m

1 m 13 m 1 m

95 m

Sectional view of zone A for Foyer with test setup

34

Page 35: Atrium Hot Smoke Test atat HKCECHKCECat HKCEC (Ir ...Fire Services Department (FSD), hot smoke tests (HST) are required as higgghlighted to evaluate the smoke extraction system for

7 Testing Procedure7. Testing Procedure

35

Page 36: Atrium Hot Smoke Test atat HKCECHKCECat HKCEC (Ir ...Fire Services Department (FSD), hot smoke tests (HST) are required as higgghlighted to evaluate the smoke extraction system for

Set up the instrument as required.

Set up the chamber with smoke generators in positionsSet up the chamber with smoke generators in positions.

Apply protective coatings to nearby glass and expensiveequipment such as the escalators where appropriate Noteequipment such as the escalators where appropriate. Notethat the radiative heat flux at 1 m away from a 2 MW firecan be up to 6.62 kWm-2 (8.86 kWm-2 for a 5 MW fire!).

Cover sprinkler heads next to the thermocouple tree T1 byappropriate thermal lagging.

Safety aspects of the test will be observed with portableextinguishers for Class B fires at the ready.

Start the data acquisition system and let it run for 5 minutes.

36

Page 37: Atrium Hot Smoke Test atat HKCECHKCECat HKCEC (Ir ...Fire Services Department (FSD), hot smoke tests (HST) are required as higgghlighted to evaluate the smoke extraction system for

T th id dTurn on the video recorder.

Set up the pool fires in the chamber by an ignition source.

Turn on the smoke generator.

Smoke generated would give a buoyancy-induced plumeg g y y pthat would move up, divert horizontally as a ceiling jet, andthen a smoke layer would be formed.

The whole operating sequence on detecting the fire,sounding the alarm, operating the smoke curtain, andturning on the fan will be testedturning on the fan will be tested.

The smoke layer should not descend to lower than thespecified height of 2 8 m above the floor levelspecified height of 2.8 m above the floor level.

Photographs on the transient positions of the smoke layerwill be taken at different angles

37

will be taken at different angles.

Page 38: Atrium Hot Smoke Test atat HKCECHKCECat HKCEC (Ir ...Fire Services Department (FSD), hot smoke tests (HST) are required as higgghlighted to evaluate the smoke extraction system for

Observe whether the smoke layer can be kept above theObserve whether the smoke layer can be kept above thespecified smoke interface height of 5.0 m in foyer.

Turn off the smoke generator before methylated spiritTurn off the smoke generator before methylated spiritin the pool fires is used up.

T t l t d k th d t i iti it iTest completed, keep the data acquisition unit runningfor another 5 minutes.

ff h id dTurn off the video recorder.

Run the system for another 15 minutes to clear up thespace.

38

Page 39: Atrium Hot Smoke Test atat HKCECHKCECat HKCEC (Ir ...Fire Services Department (FSD), hot smoke tests (HST) are required as higgghlighted to evaluate the smoke extraction system for

8. Mock-up Tests2 June 2009

3 June 20093 June 2009

39

Page 40: Atrium Hot Smoke Test atat HKCECHKCECat HKCEC (Ir ...Fire Services Department (FSD), hot smoke tests (HST) are required as higgghlighted to evaluate the smoke extraction system for

Zone A

40

o e

Page 41: Atrium Hot Smoke Test atat HKCECHKCECat HKCEC (Ir ...Fire Services Department (FSD), hot smoke tests (HST) are required as higgghlighted to evaluate the smoke extraction system for

Spread to zone C

41

Page 42: Atrium Hot Smoke Test atat HKCECHKCECat HKCEC (Ir ...Fire Services Department (FSD), hot smoke tests (HST) are required as higgghlighted to evaluate the smoke extraction system for

Another Test: Hall 3 Zone BAnother Test: Hall 3 Zone B12 February 2009

42

Page 43: Atrium Hot Smoke Test atat HKCECHKCECat HKCEC (Ir ...Fire Services Department (FSD), hot smoke tests (HST) are required as higgghlighted to evaluate the smoke extraction system for

43

Page 44: Atrium Hot Smoke Test atat HKCECHKCECat HKCEC (Ir ...Fire Services Department (FSD), hot smoke tests (HST) are required as higgghlighted to evaluate the smoke extraction system for

D t di44

Data recording

Page 45: Atrium Hot Smoke Test atat HKCECHKCECat HKCEC (Ir ...Fire Services Department (FSD), hot smoke tests (HST) are required as higgghlighted to evaluate the smoke extraction system for

Fire ChamberFire Chamber

45

Page 46: Atrium Hot Smoke Test atat HKCECHKCECat HKCEC (Ir ...Fire Services Department (FSD), hot smoke tests (HST) are required as higgghlighted to evaluate the smoke extraction system for

S k L46

Smoke Layer

Page 47: Atrium Hot Smoke Test atat HKCECHKCECat HKCEC (Ir ...Fire Services Department (FSD), hot smoke tests (HST) are required as higgghlighted to evaluate the smoke extraction system for

Smoke curtains drop to 3 m To phase 1above floor level To phase 1

15 mZone B

3 m

78 m

54.7 m

Zone A

To phase 2

M k i l

38.7 m93.4 m

Make-up air louvers

Make-up air flow Hall 3: Zone B

47

Extraction louvers

Page 48: Atrium Hot Smoke Test atat HKCECHKCECat HKCEC (Ir ...Fire Services Department (FSD), hot smoke tests (HST) are required as higgghlighted to evaluate the smoke extraction system for

Hall 3 Zone BT t 12 F b 2009

10

12

m

Test on 12 February 2009

6

8

10

CFD predictionayer

hei

ght /

m

5.0 m

Average

Accepted value under 2 MW fire

0

2

4FE Report

p3.5 m

Sm

oke

la Accepted value under 2 MW fire

FE Report: under 7 MW fire

0 200 400 600 800 1000 1200

Time / s

Smoke layer interface height by vertical air temperature profile

48