Top Banner
ATI Aerosol Photometer & Aerosol Generator Basics NAFA Meeting April 18, 2012 Scottsdale, AZ
41

ATI Aerosol Photometer & Aerosol Generator Basics

Jan 14, 2016

Download

Documents

marci

ATI Aerosol Photometer & Aerosol Generator Basics. NAFA Meeting April 18, 2012 Scottsdale, AZ. ATI Aerosol Photometer Basics website: www.ATItest.com email: [email protected] phone: 410-363-9696. Dave Crosby [email protected] Tony Hawkins [email protected] - PowerPoint PPT Presentation
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: ATI Aerosol Photometer & Aerosol Generator Basics

ATI Aerosol Photometer & Aerosol Generator Basics

NAFA MeetingApril 18, 2012Scottsdale, AZ

Page 2: ATI Aerosol Photometer & Aerosol Generator Basics

ATI Aerosol Photometer Basics

website: website: www.ATItest.comwww.ATItest.comemail: email: [email protected]@ATItest.com

phone: 410-363-9696phone: 410-363-9696

Dave Crosby [email protected] Hawkins [email protected] Largent [email protected]

Page 3: ATI Aerosol Photometer & Aerosol Generator Basics

Topics

• Basic HEPA Filtration System• Aerosol Generator Basics• Photometer Basics• HEPA Filter Testing • Summary• Standards and help resources

Page 4: ATI Aerosol Photometer & Aerosol Generator Basics

Objectives of Session

• Explain basic HEPA filtration components• Describe “in-situ” test techniques• Detail aerosol generator design and operation• Describe components and functions of the

photometer• Differentiate between efficiency and leak

testing of HEPA filters

Page 5: ATI Aerosol Photometer & Aerosol Generator Basics

Basic HEPA Filtration System

Page 6: ATI Aerosol Photometer & Aerosol Generator Basics

HEPA System Examples

Page 7: ATI Aerosol Photometer & Aerosol Generator Basics

Aerosol Generators

• Types of Aerosols• Aerosol Size• Laskin Nozzle Type• Thermal Inert Gas Type• Generator Capacities & Concentration

Page 8: ATI Aerosol Photometer & Aerosol Generator Basics

Two Types of Aerosol Types of Aerosol

• Monodisperse or Near- Monodisperse• Polydisperse

Page 9: ATI Aerosol Photometer & Aerosol Generator Basics

Near-Monodisperse Aerosol

Page 10: ATI Aerosol Photometer & Aerosol Generator Basics

Polydisperse Aerosol

Page 11: ATI Aerosol Photometer & Aerosol Generator Basics

Aerosol Size 0.3 Micrometer

Page 12: ATI Aerosol Photometer & Aerosol Generator Basics

Monodisperse Aerosol Penetrometer (i.e. Filter Tester)

Page 13: ATI Aerosol Photometer & Aerosol Generator Basics

Polydisperse Laskin Nozzle Aerosol Generators

Page 14: ATI Aerosol Photometer & Aerosol Generator Basics

Polydisperse Laskin Nozzle

Page 15: ATI Aerosol Photometer & Aerosol Generator Basics

DOP Output of Laskin Nozzle

• NRL Report 5929, Echols & Young, pg. 16, Appendix A, Model III-A (4 jets)

• 20 psig @ 75 lpm @ 5.1 mg/l • 75 lpm X 5.1 mg/l = 382.5 mg/min DOP

• Output mixed with 135 cfm of air produces a concentration of 100ug/l

Page 16: ATI Aerosol Photometer & Aerosol Generator Basics

Calculate Aerosol Challenge Concentration (µg/l)

Laskin Nozzle

Number Nozzles X 13,500Total Flow (cfm)

Page 17: ATI Aerosol Photometer & Aerosol Generator Basics

Polydisperse Thermal (vapor condensation) Aerosol Generator (inert gas)

Page 18: ATI Aerosol Photometer & Aerosol Generator Basics

Thermal Generator Operation

Page 19: ATI Aerosol Photometer & Aerosol Generator Basics

Generator CapacitiesDescription TDA-4Blite TDA-4B 6D 5C

Aerosol Output Range 50-4,050 cfm 50-8,100 cfm 50-2,000 cfm 1,500-65,000 cfm

Aerosol Concentration 100µg/l @ 405 cfm* 810 cfm* 200 cfm* 6,500 cfm

Aerosol Concentration 10µg/l @ 4,050 cfm* 8,100 cfm* 2,000 cfm* 65,000 cfm

Generator Type 1 to 3 Laskin Nozzles

1 to 6 Laskin Nozzles

2 or 6 Laskin Nozzle Jets

Thermal (Vapor Condensation)

Compressed Gas 3 to 9 cfm @ 20 psi

3 to 18 cfm @ 20 psi

(Not Required) Inert Gas

Aerosol Type Polydispersed (cold)

Polydispersed (cold)

Polydispersed (cold)

Polydispersed (hot)

Size L x H x W L x H x W L x H x W L x H x W

Inches (in) 10in x 8in x 9in 11in x 10in x 11in 14.5in x 9in x 10in 14in x 10in x 10in

Weight-Pounds (lbs) 12 lbs 16 lbs 34 lbs 23 lbs

Electrical (Not Required) (Not Required) 110 or 220VAC 110 or 220VAC

*When operated at 20 psi

Page 20: ATI Aerosol Photometer & Aerosol Generator Basics

Generator Applications• Monodisperse Penetrometer -

used at the factory and DOE Filter Test Facility (ATI Filter Test Laboratory):EFFICIENCY Testing

• Polydisperse Aerosol Generators and Photometers:In-Place Filter Leak Testing

Page 21: ATI Aerosol Photometer & Aerosol Generator Basics

Photometers• Forward Light Scattering • Photometer Flow Diagram• Photometer Components Digital Type• Internal Reference (INT REF)

Page 22: ATI Aerosol Photometer & Aerosol Generator Basics

Light Scattering

Page 23: ATI Aerosol Photometer & Aerosol Generator Basics

Forward Light Scattering

Page 24: ATI Aerosol Photometer & Aerosol Generator Basics

Forward Light Scattering Chamber

Page 25: ATI Aerosol Photometer & Aerosol Generator Basics

Photometers View Particles En Masse

Page 26: ATI Aerosol Photometer & Aerosol Generator Basics

Particle Counter Operation(One Particle at a time)

Page 27: ATI Aerosol Photometer & Aerosol Generator Basics

Photometer Flow Diagram

Page 28: ATI Aerosol Photometer & Aerosol Generator Basics

Analog Photometer

Page 29: ATI Aerosol Photometer & Aerosol Generator Basics

TDA-2G Digital Photometer

Page 30: ATI Aerosol Photometer & Aerosol Generator Basics

2H Digital Photometer

Page 31: ATI Aerosol Photometer & Aerosol Generator Basics

2i Digital Photometer

Page 32: ATI Aerosol Photometer & Aerosol Generator Basics

Digital Photometer Components

• Selector Valve• % Penetration Display & Bar Graph• Program/Control Key (ENTER)• Scroll UP () & Scroll Down () keys• Function keys (0) (100) (REF) (ALARM)• Upstream & Downstream Connections• Power switch (Ctrl-Alt-DEL)• Fuses & various signal connectors

Page 33: ATI Aerosol Photometer & Aerosol Generator Basics

2i Digital Photometer Features

• Selector Valve – Electronically controlled• Full digital display % Penetration & Flow• Controlled via Probe and Base • Easily navigable menu structure• Power switch and button

Page 34: ATI Aerosol Photometer & Aerosol Generator Basics

Digital Photometer Operation

• Use INT REF to establish 100 ug/l sensitivity level

• Measure & record upstream challenge concentration

• Set for 100% with upstream challenge concentration (100% baseline)

• Set for .000% (0% baseline)• Test downstream for aerosol leakage

Page 35: ATI Aerosol Photometer & Aerosol Generator Basics

Purpose of INT REF Feature

• To measure upstream challenge concentration levels directly in ug/l

• To set a photometer to the correct sensitivity level when an upstream aerosol challenge sample is unavailable and the concentration has to be calculated

Page 36: ATI Aerosol Photometer & Aerosol Generator Basics

INT REF on Digital Photometer Using Calculated Concentration

• Simply scroll to the calculated concentration

Page 37: ATI Aerosol Photometer & Aerosol Generator Basics

In-Situ Filter Leak Testing

• Performed with Polydisperse Aerosol• Tests the entire filtration system for

defects

• Checks the following system componentsFramesGasketsFilters

Page 38: ATI Aerosol Photometer & Aerosol Generator Basics

SUMMARY

• Efficiency testing done at factory with Monodisperse aerosol

• Efficiency testing measures penetration through HEPA filter only

• In-place testing done with Polydisperse aerosol

• In-place tests complete filtration system for defects (leaks)

Page 39: ATI Aerosol Photometer & Aerosol Generator Basics

Standards• IEST RP-001 Filters• IEST RP-002 Laminar Flow Devices• IEST RP-006 Cleanrooms• IEST RP-034 Scanning HEPA Filters• ISO 14644• ASME AG-1 Code• ASME N-511• NSF 49

Page 40: ATI Aerosol Photometer & Aerosol Generator Basics

Where to Get More Information

• Nuclear Air Cleaning Handbook• NEBB Cleanroom Guide• IEST Standards• Various Manufacturers Literature and

websites• International Air Cleaning Conference

Proceedings

Page 41: ATI Aerosol Photometer & Aerosol Generator Basics