ATD Unit Heater – AEROTEMPER ®
56

ATD Unit Heater – AEROTEMPER...The ATDI can be equipped with an explosion-proof motor, steel coil, etc. Contact Fläkt Woods for further details. ATD Unit Heater. Fläkt Woods 10014

Mar 03, 2021

Download

Documents

dariahiddleston
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: ATD Unit Heater – AEROTEMPER...The ATDI can be equipped with an explosion-proof motor, steel coil, etc. Contact Fläkt Woods for further details. ATD Unit Heater. Fläkt Woods 10014

ATD Unit Heater – AEROTEMPER®

Fläkt Woods is providing solutions for ventilation and air climate for buildings as well as fan solutions for Industry and Infrastructure.

Page 2: ATD Unit Heater – AEROTEMPER...The ATDI can be equipped with an explosion-proof motor, steel coil, etc. Contact Fläkt Woods for further details. ATD Unit Heater. Fläkt Woods 10014

Fläkt Woods 10014 GB 04.03 2 We reserve the right to alter specifications.

ATD Unit Heater CATALOGUE

Contents

Product Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3

Product Survey . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-5

Installation Packages . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6-10

Installation Examples . . . . . . . . . . . . . . . . . . . . . . . . . . .11-16

Accessories

Unit Heater . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17-19

Control Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20-28

Sizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29

Installation Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

Water

General Survey Chart . . . . . . . . . . . . . . . . . . . . . . . . . .31

Capacity Tables, Water ATDA . . . . . . . . . . . . . . .32-33

Airflows, Pressure Drop . . . . . . . . . . . . . . . . . . . . . . .34

Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35-36

Steam

Capacity Tables, Steam ATDG . . . . . . . . . . . . . . .37-38

Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39-40

Measurements and Weights . . . . . . . . . . . . . . . . . . . . .41-42

Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .43-48

Product Code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49-51

Packaging – Installation Package . . . . . . . . . . . . . . . . . . .52

Page 3: ATD Unit Heater – AEROTEMPER...The ATDI can be equipped with an explosion-proof motor, steel coil, etc. Contact Fläkt Woods for further details. ATD Unit Heater. Fläkt Woods 10014

Fläkt Woods 10014 GB 04.03 3 We reserve the right to alter specifications.

ATD Unit Heater CATALOGUE

The ATDAand ATDG fan-assistedunit heaters are designed for heat-ing and ventilating workshops,industrial and warehouse premis-es, shops, garages, supermarketsand the like.

The unit is available in twoversions: for hot water (ATDA)and for steam (ATDG).

Both types of unit heater incorpo-rate a corrosion-resistant watercoil consisting of aluminium finsand copper tubes.

The ATDAand ATDG are avail-able in four different sizes (theATDAin five different capacityvariants) for varying airflow andcapacity needs that meet most ofthe conditions under which theunit operates.General specifications:• Casing made of corrosion-

protected sheet steel, paintedwhite or 304 stainless steel

• Modern design with roundedand smooth sheet metal surfaces

• Can be opened to simplify clean-ing inside the unit

• One air deflector is included asstandard

• Airflows up to 2.2 m3/s• Motor for a single-phase, 230 V

or 3-phase, 400 V power supply• All units comply to EU

Requirements on the Safety ofMachinery 91/368/EEC

• Broad range of accessories for avariety of applications

• Avariety of control options

Product DescriptionThe unit heaters are available infour sizes; 33, 44, 55 and 66 for hotwater (ATDA) or in three sizes;33, 44 and 55 for steam (ATDG).The smallest size of ATDA(30) isalso available in a version for lowheating capacity. The unit heaters have a casingmade of sheet steel, painted white,or stainless sheet steel (304). Thecasing can be opened to enablecleaning inside. The top andbottom panels are easy to remove

afterremoving twoscrews.The pipe connections for water orsteam are situated on the side ofthe unit.The coil has high efficiency andconsists of copper tubes withaluminium fins. The motor, fanimpeller and protective grille aredesigned as one compact andcombined unit.The motor is of external rotor typeand is available as standard in thefollowing versions:

Sizes30, 33, 44: 1 x 230 V. Två Two-

speed: medium + highspeed.

Size 55: 1 x 230 V. Single-speed:high speed.

Size 66: 1 x 230 V. Single-speed:high speed.

Size 44: 3 x 400 V. Single-speed:high speed.

Size 55: 3 x 400 V. Two-speed,star/delta-coupled

Size 66: 3 x 400 V. Two-speed, star/delta -coupled.

All motors have built-in thermo-static contacts in the motor wind-ings except for the 3-phase, 400 Vmotor in the size 44 units.The size 30, 33 and 44 units havedegree of protection IP 44 whereasthe size 55 and 66 units havedegree of protection IP 54.

The maximum permissible ambi-ent temperature around themotors is 50°C.Other types of motors are availableas other versions.Alarge selection of accessories isavailable.See under Accessories in this cata-logue.

InstallationThe ATDAcan be installed for bothhorizontal and vertical airflow.The ATDG may be installed forhorizontal airflow only.

Materials and FinishUnit casing: Made of hot-galva-nized sheet steel and paintedwhite (RAL 9010) or made of 304stainless sheet steel.Fan impeller and protective grille:Sheet steel/wire, painted black.Coil: Copper tubes with alumini-um fins or material for corrosiveenvironments. The ATDAhasheaders with smooth 22 mm dia.connections for brazed joints orcompression rings.The ATDG has threaded connec-tions for steam and condensate.

PackagingThe unit heater with accessories issupplied corrugated cardboardcartons. CE labellingTransparent plastic foil packagingalso protects the unit.

Other VersionsThe ATD is also available withcorrosion-protected coils and astainless steel casing. Other motorssuch as spark-proof motors(EEXE) for 500-Volt operation andmotors having higher IP-class arealso available. The ATD is alsoavailable in an industry version(ATDI).The ATDI can be equipped with anexplosion-proof motor, steel coil,etc.Contact Fläkt Woods for furtherdetails.

ATD Unit Heater

Page 4: ATD Unit Heater – AEROTEMPER...The ATDI can be equipped with an explosion-proof motor, steel coil, etc. Contact Fläkt Woods for further details. ATD Unit Heater. Fläkt Woods 10014

Fläkt Woods 10014 GB 04.03 4 We reserve the right to alter specifications.

ATD Unit Heater CATALOGUE

Unit heater with accessories

Ceiling mounting bracket,ATDZ-10-bb

Unit heater, ATD(A,G)

Wall mounting bracket,ATDZ-03-bb

Spacer mountingbracket for mixingsection, set,ATDZ-05-bb

Lever actuator for mix-ing section, ATDZ-12

Recirculated air sectionwith filter, ATDZ-02-bb

Mixing section with filter,ATDZ-01-bb

Extra air deflector,ATDZ-09-bb

Page 5: ATD Unit Heater – AEROTEMPER...The ATDI can be equipped with an explosion-proof motor, steel coil, etc. Contact Fläkt Woods for further details. ATD Unit Heater. Fläkt Woods 10014

ATD Unit Heater CATALOGUE

Fläkt Woods 10014 GB 04.03 5 We reserve the right to alter specifications.

Automatic fan control,simple, FHC,ATDZ-15-4 1 x 230 V

Valve with thermalactuator, ATDZ-17-3

Room thermostat forfan operation, IP 54,

ATDZ-19-3

Temperature sensorRG Humidity, ATDZ-35-1

ATDZ-35-2

Remote control for ATC,ATDZ-21-3ATDZ-21-4

Timer for ATC,ATDZ-22-3

Speed selector,ATDZ-13

Speed selector, 2A,ATDZ-24-3

Speed switch, 9 A,ATDZ-28

Transformer, 2AATDZ-25-3

Connection device,ATDZ-30

Anti-frost protection thermostatATDZ-26

Damper motor, Belimo,ATDZ-27

Accessories - Control Equipment

Room thermostat forfan operation, IP 30,

ATDZ-18-3

Automatic unit heater control,advanced, ATC,ATDZ-29 1 x 230 V, 9A

Auxiliary module,network connection

ATDZ-37

Remote control, infrared,ATDZ-36

Valve with actuator,quick-action,ATDZ-17-4

Automatic unit heater control,advanced, ATC,ATDZ-33 1 x 230 V, 2A

Automatic fan control,simple, FHC,ATDZ-34 3 x 400 V

Page 6: ATD Unit Heater – AEROTEMPER...The ATDI can be equipped with an explosion-proof motor, steel coil, etc. Contact Fläkt Woods for further details. ATD Unit Heater. Fläkt Woods 10014

To make the task of selecting control equipment easier,we have produced ready-to use package solutions forthe most common control options. You can of coursecombine whichever installation package you choosewith other accessories. See the Installation ExamplesSection in this catalogue.The components that make up the various installationpackages are also sold as separate accessories.

ApplicationsA-Box – entrances, gateways, warehouses, garages.B-Box – entrances, workshops, shopping centres,

sport centresC-Box – same as B-Box but where higher demands

are made, such as outdoor air section, night-time temperature reduction, alarms,network connection or microprocessorsubstation (0-10 V) control.

.F-Box –most suitable for use in combination with the

C-Box which has ready-to-use connector sock-ets for anti-frost protection thermostat and actu-ator motor.- the F-Box can also be combined with the A-Box. To facilitate wiring, the ATDZ-30Connection device should then be used, seesection: Accessories, Control Equipment.

Installation Packages

Fläkt Woods 10014 GB 04.03 6 We reserve the right to alter specifications.

ATD Unit Heater CATALOGUE

Unit – control accessories A-Box B-Box C-Box F-Box

Unit heater x x x -

Mounting brackets x x x -

Mixing section - - - x

Room thermostat x - - -

Automatic fan control, - x - -FHC, simple

Automatic unit heater control, - - x -ATC, advanced

Temperature Sensor - x x -

Liquid valve x x x -

Anti-frost protection sensor - - - x

Damper motor - - - x

Documentation x x x x

x = included

Survey - Components of the boxes

A-Box Temperature-controlled airflow control, on/off, with liquidvalve, on/off.

B-Box Temperature-controlled airflow control in 3 steps orswitched-off position with liquid valve, on/off.

C-Box Temperature-controlled airflow control in 3 steps orswitched-off position with liquid valve, on/off. Preset fortimer control. 0-10 V control, remote control, networkconnection, alarm output, anti-frost protection and damperactuator.Control, 2A, the ATDZ-33. For control of max.:Three ATDA-30, -33 unitsTwo ATDA-44 unitsOne ATDA-55, -66 unit

F-Box For use in combination with the C-Box.Temperature-controlled airflow control with outdoor airmixture in 3 steps or closed position with anti-frost protec-tion and actuator and liquid valve, on/off.

Survey - Functions

Page 7: ATD Unit Heater – AEROTEMPER...The ATDI can be equipped with an explosion-proof motor, steel coil, etc. Contact Fläkt Woods for further details. ATD Unit Heater. Fläkt Woods 10014

Fläkt Woods 10014 GB 04.03 7 We reserve the right to alter specifications.

ATD Unit Heater CATALOGUE

How it operates:When heating is required, the room thermostat startsthe unit heater and opens the liquid valve. When thepreset temperature is reached, the liquid valve closesand the fan is switched off.

Ordering ExampleInstallation package, A-Box ATDA-aa-1-A

Size (aa)30, 33, 44, 55, 66

Motor1= 1x 230 V, IP44

Installation package

The A-Box, contains:

Unit heaterATDA-aa-b

The complete supply consists of unit heater, appropri-ate accessories and instructions.

1 Unit heater ATDA-aa-1aa = size of heater required, 30, 33, 44, 55, 66

1 Wall mounting brackets (set) ADTZ-03-bbbb = unit heater size 30, 33, 44, 55, 66

1 Room thermostat ATDZ-18-3IP 30, single-phase 230 V, 16 A

1 Valve with actuator, open/closed ATDZ-17-4IP 54, single-phase, 230 V, temperature range: 2-110 °C,kvs 4.0, on/off, time 10 seconds

1 Instruction manualInstallation, operation and maintenance instructions.

Room thermostatATDZ-18-3

Valve with actuator,open/closedATDZ-17-4

Wall mounting brackets, setATDZ-03

Page 8: ATD Unit Heater – AEROTEMPER...The ATDI can be equipped with an explosion-proof motor, steel coil, etc. Contact Fläkt Woods for further details. ATD Unit Heater. Fläkt Woods 10014

The B-Box, contains:

How it operates:When heating is needed, the liquid valve opens and theautomatic fan controller, in response to signals from thetemperature sensor, controls the fan to accelerate ordecelerate in three fixed steps to maintain the presettemperature. When heating is no longer necessary, theliquid valve closes and the fan is switched off.The fan speed can also be manually set at three differ-ent speed settings or be switched off.An LED indicates when the valve is open and whichfunctions have been selected. For particulars of other speeds, see pages 36 and 39.

Ordering ExampleInstallation package, B-Box ATDA-aa-1-B

Size (aa)30, 33, 44, 55, 66

Motor1= 1x 230 V, IP44

Installation Package

Fläkt Woods 10014 GB 04.03 8 We reserve the right to alter specifications.

ATD Unit Heater CATALOGUE

The complete supply consists of unit heater, appropri-ate accessories and instructions.

1 Unit heater ATDA-aa-1aa = size of heater required, 30, 33, 44, 55, 66

1 Wall mounting brackets (set) ATDZ-03-bbbb = unit heater size 30, 33, 44, 55, 66

1 Automatic fan control, FHC, simple ATDZ-15-4IP 54, 1 x 230 V, 2A1 temperature sensor

1 Valve with actuator, open/closed ATDZ-17-4 IP 54, 1 x 230 V, temperature area 2-110 °C, kvs 4.0, on/off, time 10 seconds.

1 Instruction manualInstallation, operation and maintenance instructions.

Automatic fan control,FHC, simpleATDZ-15-4 1 x 230 V

Temperature sensor

Wall mounting bracket, setATDZ-03

Unit heaterATDA-aa-b

Valve with actuator, open/closedATDZ-17-4

Page 9: ATD Unit Heater – AEROTEMPER...The ATDI can be equipped with an explosion-proof motor, steel coil, etc. Contact Fläkt Woods for further details. ATD Unit Heater. Fläkt Woods 10014

Fläkt Woods 10014 GB 04.03 9 We reserve the right to alter specifications.

ATD Unit Heater CATALOGUE

How it operates:When heating is needed, the liquid valve opens and theautomatic fan controller, in response to signals from thetemperature sensor, controls the fan to accelerate ordecelerate in three fixed steps to maintain the presettemperature. When heating is no longer necessary, theliquid valve closes and the fan is switched off. The presettemperature is shown in the display.

The control unit has provision for the following acces-sories:Alarm indicator for external alarms, time switch forday/night operation, remote control via wire or infraredlight, damper motor, anti-frost thermostat and networkconnection.The software for establishing a connection to a computeris included, LAN, 0-10 V signal (microprocessor substa-tion).For particulars of other speeds, see pages 36 and 39.

Ordering ExampleInstallation package, C-Box ATDA-aa-1-C

Size (aa)30, 33, 44, 55, 66

Motor1= 1x 230 V, IP44

Installation Package

The C-Box, contains:

Unit heaterATDA-aa-b

The complete supply consists of unit heater, appropri-ate accessories and instructions.

1 Unit heater ATDA-aa-1aa = size of heater required, 30, 33, 44, 55, 66

1 Wall mounting brackets (set) ATDZ-03-bbbb = unit heater size 30, 33, 44, 55, 66

1 Automatic unit heater control, ATC,advanced ATDZ-33IP 54, 1 x 230 V, 2 A1 temperature sensor

1 Valve with actuator, open/closed ATDZ-17-4 IP 54, 1 x 230 V, temperature area 2-110 °C, kvs 4.0, on/off, time 10 seconds.

1 Instruction manualInstallation, operation and maintenance instructions.

Valve with actuator, open/closedATDZ-17-4

Wall Bracket, setATDZ-03

Automatic Aerotemper Control, ATC, advancedATDZ-33 1 x 230 V

Page 10: ATD Unit Heater – AEROTEMPER...The ATDI can be equipped with an explosion-proof motor, steel coil, etc. Contact Fläkt Woods for further details. ATD Unit Heater. Fläkt Woods 10014

The F-Box, contains:

ates an alarm signal.The anti-frost protection thermostat is mounted on thereturn pipe of the unit heater.

-The F-Box is most suitable for use in combination withthe C-Box which has ready-to-use connector sockets forthe anti-frost protection thermostat and actuator motor.

-The F-Box can also be combined with the A-Box. To facil-itate wiring, the ATDZ-30 connection device should thenbe used. See Accessories, Control and ControlEquipment.How it operates: When the anti-frost protection thermo-stat trips, the damper closes and the motor stops. At thesame time the liquid valve opens.

Ordering ExamplesInstallation package, F-Box ATDA-aa-1-F

Size (aa)30, 33, 44, 55

Motor1= 1x 230 V, IP44

Installation Package

Fläkt Woods 10014 GB 04.03 10 We reserve the right to alter specifications.

ATD Unit Heater CATALOGUE

The supply consists of the appropriate accessories andinstructions. The possible combinations are given below.

1 Mixing section for outdoor air ATDZ-01-bbbb= size of heater required 30, 33, 44, 55 (not available for size 66)

1 Anti-frost protection thermostat ATDZ-26

1 Damper motor ATDZ-27

1 Instruction manualInstallation, operation and maintenance instructions

How it operates:When the unit heater starts, the liquid valve opens beforethe damper motor and the fan starts.When the temperature is too low, the control unit, inresponse to a signal from the anti-frost protection ther-mostat, first closes the outdoor air damper. If the temper-ature doesn’t rise, the control unit switches out the fanmotor, opens the liquid valve and at the same time initi-

Mixing section foroutdoor air ATDZ-01-bb

Damper motorATDZ-27

Anti-frost protection thermostatATDZ-26

Page 11: ATD Unit Heater – AEROTEMPER...The ATDI can be equipped with an explosion-proof motor, steel coil, etc. Contact Fläkt Woods for further details. ATD Unit Heater. Fläkt Woods 10014

Fläkt Woods 10014 GB 04.03 11 We reserve the right to alter specifications.

ATD Unit Heater CATALOGUE

Installation Example

Recirculated air section with filter ATDZ-02-bb

Mixing section with filter ATDZ-01-bb

Wall mounting bracket ATDZ-03-bbExtra air deflector ATDZ-09-bbManual speed selector ATDZ-24-3

Wall mounting bracket ATDZ-03-bbAutomatic fan control, FHC, simple ATDZ-15-4Extra air deflector ATDZ-09-bb

Page 12: ATD Unit Heater – AEROTEMPER...The ATDI can be equipped with an explosion-proof motor, steel coil, etc. Contact Fläkt Woods for further details. ATD Unit Heater. Fläkt Woods 10014

Fläkt Woods 10014 GB 04.03 12 We reserve the right to alter specifications.

ATD Unit Heater CATALOGUE

OperationThe speed switch is designed for use in applicationswhere manually setting the output (speed) is desirable.Switching is carried out between three preset speeds:low – medium – high, as well as switched out. AnATDZ-17-3 valve, ATDZ-18-3 or ATDZ-19-3 room ther-mostat and ATDZ-22-3 timer can be wired to theswitch. Simple and cost-effective control equipment

for the unit heater can be obtained using the switch andone or several accessories shown above. Several unitheaters can be wired to one and the same speed selec-tor, however the total capacity must not exceed 2 Aand9Arespectively. See motor data for the relevant sizes.Voltage: 1 x 230 V.Optional speeds, see pages 36 and 39.

Connection Options for the ATDZ-24-3/ATDZ-28 Speed Switch

RoomThermostat forfan operation,ATDZ-18-3

Speed switch, ATDZ-28, 9 A, for max.:9 type ATDA-30, 33-1 unit heaters

9 type ATDA-44-1 unit heaters5 type ATDA-55-1 unit heaters5 type ATDA-66-1 unit heaters

As an alternative, thefollowing can be used

orSpeed switch,ATDZ-28For obtaining a lowerfixed speed than thedesign speed.

Speed selector,ATDZ-24-3, 2AThree service positionsor switched out

Valve with actuator,ATDZ-17-3

Timer,ATDZ-22-3

Installation Example

Temperature-controlled airflow control, on/off, fixed speeds with nighttime temperature reduction and on/off valve

Page 13: ATD Unit Heater – AEROTEMPER...The ATDI can be equipped with an explosion-proof motor, steel coil, etc. Contact Fläkt Woods for further details. ATD Unit Heater. Fläkt Woods 10014

Fläkt Woods 10014 GB 04.03 13 We reserve the right to alter specifications.

ATD Unit Heater CATALOGUE

Installation Example

OperationThe automatic unit heater control, ATC, advanced, ATDZ-29regulates the speed of the unit heater motor in three presetsteps in response to ambient temperature readings from thetemperature sensor supplied. The desired temperature (setpoint) is set with the potentiometer set to Automatic unitheater control. If the ambient temperature is warmer than thepreset temperature, the controller reduces the speed step bystep and when no heating is needed, it shuts off the fanmotor. If the ambient temperature is lower than the presettemperature, the controller increases the speed step by stepand the capacity as well.

ATimer (ATDZ-22-3) can be wired to the ATC for loweringthe air temperature at night. Desired “night temperature”can then be set by means of another potentiometer in theAutomatic temperature regulation system.

Automatic temperature regulation can also be controlledin response to a 0-10 V signal. Remote control is available asan accessory (ATDZ-21-3).

Aseparate water valve with thermal actuator (ATDZ-17-3)can be connected to the Automatic temperature regulationsystem. When the desired air temperature has been reachedand the fan has stopped, the valve closes and shuts off waterflow. When the air temperature drops and the fan starts, the valve

opens again. Whenever a power failure occurs, the valve willopen.

Caution! External solenoid valves must not be connectedto the Automatic temperature regulation system because asurge of current is likely to occur when they are switched on.

The Automatic temperature regulation system is tested toestablish its electromagnetic compatibility (EMC) in accor-dance with SS-EN 50081-1 and EMC-immunity in accor-dance with SS-EN 50082-2.For particulars of alternative speeds, see pages 36 and 39.

Remote controlunitATDZ-21-3

Unit heater, ATDZ-29, 9 A, for controlling max.:9 type ATDA-30, 33-1 unit heaters

9 type ATDA-44-1 unit heaters5 type ATDA-55-1 unit heaters5 type ATDA-66-1 unit heaters

Valve withActuator,ATDZ-17-3

Timer,ATDZ-22-3

Temperature sensor,suppliedwith thecontroller

Automatic unitheater control,advanced, ATC,ATDZ-29

Automatic unit heater control ATC, advanced, ATDZ-29, for several unit heaters

Temperature-controlled airflow control of up to nine heaters with nighttime temperature reduction and liquid valve, on/off

Page 14: ATD Unit Heater – AEROTEMPER...The ATDI can be equipped with an explosion-proof motor, steel coil, etc. Contact Fläkt Woods for further details. ATD Unit Heater. Fläkt Woods 10014

Fläkt Woods 10014 GB 04.03 14 We reserve the right to alter specifications.

ATD Unit Heater CATALOGUE

Speed control

Installation Example

Unit heaterATDA-aa-b

Operation:For the ATDA-30, 33 and 44 only.The manual speed selector (ATDZ-13) is used forswitching between high and medium speed or theshut-off position.

Speed selectorATDZ-13

Voltage: 1 x 230 V.Max. current: 10 A.

Page 15: ATD Unit Heater – AEROTEMPER...The ATDI can be equipped with an explosion-proof motor, steel coil, etc. Contact Fläkt Woods for further details. ATD Unit Heater. Fläkt Woods 10014

Installation Example

Fläkt Woods 10014 GB 04.03 15 We reserve the right to alter specifications.

ATD Unit Heater CATALOGUE

Operation:When heating is needed, the fan is started in responseto signals from the room thermostat (ATDZ-18-3,ATDZ-19). Meanwhile the damper motor (ATDZ-27)actuates the damper to open and the liquid valve(ATDZ-17-4) opens. When heating is no longer neces-sary, the fan stops, the valve and the damper closes.

If the anti-frost protection thermostat (ATDZ-26) regis-ters a recirculated air temperature that is too low, thefan is switched out and the damper motor closes thedamper. The liquid valve opens at the same time. Theconnection device (ATDZ-30) is used for obtaining thecorrect function and makes wiring simpler.Voltage: single-phase, 230 VCurrent: Max. 2 A.

Valve with Actuator,ATDZ-17-4

RoomThermostatfor fan opera-tion,ATDZ-18-3

Anti-frost protection thermostat,ATDZ-26

Damper Motor, Belimo,ATDZ-27

Connectiondevice, ATDZ-30

Mixing Section with filter,ATDZ-01-bb

Unit heater,ATDA-aa-b

Temperature-controlled airflow regulation, on/off, with outdoor air mixed into the supply air and anti-frost protection.

Page 16: ATD Unit Heater – AEROTEMPER...The ATDI can be equipped with an explosion-proof motor, steel coil, etc. Contact Fläkt Woods for further details. ATD Unit Heater. Fläkt Woods 10014

Fläkt Woods 10014 GB 04.03 16 We reserve the right to alter specifications.

ATD Unit Heater CATALOGUE

Speed control, advanced

The temperature can be preset behind the cover bymeans of potentiometer A. If the ventilation system isequipped with a timer for an optional temperature, thissetting can be preset by means of potentiometer B. Thecontrol system can be supplemented with remote controlacross a cable (ATDZ-21-3 or a remote infrared unit(ATDZ-36). Then the fan can control the speed in theautomatic setting or three fixed speeds 1,2,3 or stop thefan in the 0 setting.

The control system has provision for control by meansof a 0-10 V signal from a microprocessor substation, or aLAN network control.

An external fault alarm signal input can be wired to thecontrol system.For particulars of alternative speeds, see pages 36 and 39.

Installation Example

Valve with Actuator,ATDZ-17-4

Operation:When heating is needed, the liquid valve (ATDZ-17-4)opens and the automatic fan controller, in response tosignals from the temperature sensor, controls the fan toaccelerate or decelerate in three fixed steps to maintainthe preset temperature. When heating is no longer neces-sary, the liquid valve closes and the fan stops.

Whenever the automatic unit heater controller, ATC,registers an abnormally low return water temperature inresponse to signals from the anti-frost protection thermo-stat (ATDZ-26), the damper motor (ADTZ-27) is firstclosed. If the liquid temperature doesn’t rise, thecontroller switches out the fan, opens the liquid valveand at the same time initiates an alarm signal.

Anti-frost protection thermostat,ATDZ-26

Damper Motor, Belimo,ATDZ-27

Automatic unitheater control,advancedATDZ-33, ATC 1 x 230 V

Time Clock forAutomaticTemperaturecontrol,ATDZ-22-3

Mixing Section with filter,ATDZ-01-bb

Unit heater,ATDA-aa-b

Remote controlunit for Auto-matic tempera-ture control, ATDZ-21-3

Temperature sensor,suppliedwith thecontroller

Temperature-controlled airflow regulation in three steps, with nighttime temperature reduction, remote control, anti-frost protection and liquid valve, on/off.

Page 17: ATD Unit Heater – AEROTEMPER...The ATDI can be equipped with an explosion-proof motor, steel coil, etc. Contact Fläkt Woods for further details. ATD Unit Heater. Fläkt Woods 10014

Fläkt Woods 10014 GB 04.03 17 We reserve the right to alter specifications.

ATD Unit Heater CATALOGUE

Size Dimensions (mm) Wgt.,ATDA A B C D E kg

-30/33 428 428 790 456 456 23-44 608 608 980 636 636 40-55 708 708 1080 736 736 50-66 - - - - - -

Mixing Section with Filter,ATDZ-01-bbConsists of a casing painted white,of the same type as for the unitheater, internally insulated withthermal and fire-resistant insula-tion. The damper is uninsulated.The mixing section has a shortpleated filter of disposable type,which can easily be replaced afteropening the top or bottom inspec-tion panel. The filter material isnon-inflammable polyester to FilterClass G85 in conformity withSwedish VVS AMA98 Standard(EU3 to EUROVENT 4/5).

Asector damper regulates theairflow through the intakes foroutdoor and recirculated air respec-tively. The damper isn’t completelytight fitting. The damper shaftprotrudes out on both sides of themixing section, enabling actuator tobe fitted on either side. Max.permissible torque for dampercontrol is 0.5 Nm for all sizes.

The mixing section is normallymounted with horizontal dampershaft. If there is no risk of thedamper freezing fast, the mixingsection can be mounted with verti-cal damper shaft.

The mixing section has to besecured to the unit by means of thebolts provided. Free fit holes areprovided in the mounting bracketson the inlet side of the unit forsecuring the mixing section to awall. Suspension devices made ofhot-galvanized sheet steel andscrews are provided to be fastenedto the front of the mixing section.

Important! When the mixingsection is combined with automaticfan control in a cold climate, anATDZ-26 anti-frost thermostat andan ATDZ-27 actuator must be used.

Accessories for the Unit Heater

EC

A

B

D

Two ceiling mountingbrackets are included inthe supply

4 x ø 14

– = the size is not available

The mixingsection is shownviewed from theunderside

Page 18: ATD Unit Heater – AEROTEMPER...The ATDI can be equipped with an explosion-proof motor, steel coil, etc. Contact Fläkt Woods for further details. ATD Unit Heater. Fläkt Woods 10014

Fläkt Woods 10014 GB 04.03 18 We reserve the right to alter specifications.

ATD Unit Heater CATALOGUE

Recirculated air sectionwith filter, ATDZ-02-bbConsists of an uninsulated casingpainted white, of the same type asfor the unit heater. Supplied fittedto the unit heater. The recirculatedair section has a short pleated filterof disposable type, which can easilybe replaced after opening theinspection panel on the front. Thefilter material is non-inflammablepolyester to Filter Class G85 inconformity with Swedish VVSAMA98 Standard (EU3 toEUROVENT 4/5).

For connection on the air side,the section is equipped with abranch conforming to circular ductstandard SIS 82 72 06. Fitted withboth filter and connected duct forincreased air circulation, the recir-culated air section utilizes thetemperature gradient in the prem-ises for maximal heating..

Wall mounting brackets,set, ATDZ-03-bbFor securing the unit heater with-out mixing section or recirculatedair section on a wall. The bracket issupplied in 2 pairs, to be securedto the inlet side of the unit bymeans of screws.The screw fasteners are includedin the supply.The mounting brackets are madeof tubular steel painted light grey.

Spacer mounting brack-ets for mixing section,set, ATDZ-05-bbFor suspending a unit heaterequipped with mixing section foradmission of recirculated air fromthe rear. The mounting bracketsare supplied in 2 pairs. Themounting screws and nuts aresupplied.The bracket is made of flat steelbar and painted light grey.

Accessories for the Unit Heater

Size Dimensions (mm) Wgt.,ATDA A B C D E kg

-30/33 550 370 390 315 350 12-44 710 550 570 500 520 21-55 810 550 670 500 610 26-66 - - - - - -

Ø10A

C

B

Size Dimensions (mm) Wgt., kgATDA A B C per pair

-30/33 180 340 200 1-44 340 500 250 2-55 440 600 300 3-66 540 700 300 4

100

A

50

B

Ø15

Size (mm) Wgt., kgATDA A B per pair

-30/33 516 456 3,5-44 696 636 4-55 796 736 4,5-66 - - -

4 x

CB

øD

A

– = the size is not available

Dimensions

Page 19: ATD Unit Heater – AEROTEMPER...The ATDI can be equipped with an explosion-proof motor, steel coil, etc. Contact Fläkt Woods for further details. ATD Unit Heater. Fläkt Woods 10014

Fläkt Woods 10014 GB 04.03 19 We reserve the right to alter specifications.

ATD Unit Heater CATALOGUE

Size Dimension (mm) Wgt., kgATDA A B C per pair

-30/33 590 360 200 3-44 750 450 290 4-55 850 500 340 5-66 - - - -

Extra air deflector,ATDZ-09-bbConsists of a frame and a numberof pivotal louvres. The frame andair deflector louvres are made ofanodised aluminium. The airdeflector is fitted to the unit heaterusing the self-tapping screwssupplied.

NOTE! The horizontal airdeflector is included in the ATDunit heater.

Ceiling mounting brack-ets, set,ATDZ-10-bbFor suspending the unit heaterwithout mixing section or recircu-lated air section from the ceiling.The mounting brackets are deliv-ered in 2 pairs, designed to bescrewed tight against the inlet sideof the unit. The fastening screws are includedin the supply.The bracket is made of tubularsteel and painted light grey.

Lever Actuator for mixingsection,ATDZ-12For ATDZ-01-bb mixing section.For manually regulating the airflow through the inlet openingsfor outdoor and recirculated airrespectively.Made of hot-galvanized sheetsteel with clamping knob for lock-ing in the appropriate position.

Accessories for the Unit Heater

55B

A

Size (mm) Wgt.,ATDA A B kg

-30/33 404 436 1-44 554 586 2-55 654 686 366 742 686 3

C

A

B

29090

120

Dimensions

Page 20: ATD Unit Heater – AEROTEMPER...The ATDI can be equipped with an explosion-proof motor, steel coil, etc. Contact Fläkt Woods for further details. ATD Unit Heater. Fläkt Woods 10014

Fläkt Woods 10014 GB 04.03 20 We reserve the right to alter specifications.

ATD Unit Heater CATALOGUE

Automatic fan control, simple, FHC-3,ATDZ-34The speed controller (ATDZ-15-4, ATDZ-34) automati-cally regulates the fan speed in three steps dependingon the heating load and switches out the fan when heat-ing is no longer required.Automatic fan controller also controls the liquid valve(ATDZ-17-4) between the open and closed positions.The desired temperature can be set on the externalpotentiometer. The temperature sensor (supplied sepa-rately) is included.The fan speed can be manually set to three positions, orstopped by pressing the touch pads on the cover panel.An LED indicates when the valve is open.

The automatic fan controller is delivered as a sepa-rate accessory.The automatic fan controller has degree of protectionIP54.The temperature sensor has IP30.Voltage: 3 x 400V.Max. current: 2 A.

Automatic fan control, simple, FHC-1,ATDZ-15-4Included in the B-Box installation package.The speed controller (ATDZ-15-4, ATDZ-34) automati-cally regulates the fan speed in three steps dependingon the heating load and switches off the fan when heat-ing is no longer required.The automatic fan controller also controls the liquidvalve (ATDZ-17-4) between the open and closed posi-tions.The desired temperature can be set on the externalpotentiometer. The temperature sensor (supplied sepa-rately) is included.The fan speed can be manually set to three positions, orstopped by pressing the touch pads on the cover panel.An LED indicates when the valve is open.Detailed technical description of the control system:When the ambient air temperature is 0.4°C below theset point setting, the fan starts at the lowest presetspeed. At 0.5°C below the set point, the connectedwater valve opens. At 1.5° below the preset set point,the fan switches over to the maximum speed setting.

The automatic fan controller is delivered as a sepa-rate accessory.The automatic fan controller has degree of protectionIP54.The temperature sensor has IP30.Voltage: 1 x 230 V.Max. current: 2A.

Accessories, Control Equipment

78

78

35

78

78

35

180

102

180

180

61255

Page 21: ATD Unit Heater – AEROTEMPER...The ATDI can be equipped with an explosion-proof motor, steel coil, etc. Contact Fläkt Woods for further details. ATD Unit Heater. Fläkt Woods 10014

Fläkt Woods 10014 GB 04.03 21 We reserve the right to alter specifications.

ATD Unit Heater CATALOGUE

Accessories, Control Equipment

Automatic Unit heater Control, advanced,ATC, ATDZ-29Is used for controlling max. nine unit heaters within onezone.

The automatic unit heater controller regulates thevoltage supplied to the motor to regulate the fan speed inthree preset steps in response to ambient temperaturereadings from the temperature sensor supplied. Whenheating is no longer required, the fan motor is switchedoff. Atimer (ATDZ-22-3) can be connected to automaticunit heater control for lowering the air temperature atnight. The automatic unit heater controller can also becontrolled in response to a 0-10 V signal. Remote control(ATDZ-21-3) is available as an accessory. Aseparatewater valve (ATDZ-17-3) with thermal actuator motor,open/closed, can be connected to Automatic unit heatercontroller.

NB! An external solenoid valve must not be connect-ed to the automatic temperature control system.

The Automatic temperature regulation system is test-ed to establish its electromagnetic compatibility (EMC) inaccordance with SS-EN 50081-1 and EMC-immunity inaccordance with SS-EN 50082-2.

The automatic unit heater controller, ATC, IP54, issupplied separately and with separate temperaturesensor.

For particulars of connection options, see the relevantinstallation example.

The temperature sensor is supplied loose, IP30.Voltage: 1 x 230 V.Max. current: 9 A

360

260

185

78

78

35

Page 22: ATD Unit Heater – AEROTEMPER...The ATDI can be equipped with an explosion-proof motor, steel coil, etc. Contact Fläkt Woods for further details. ATD Unit Heater. Fläkt Woods 10014

Accessories, Control Equipment

Fläkt Woods 10014 GB 04.03 22 We reserve the right to alter specifications.

ATD Unit Heater CATALOGUE

Automatic Aerotemper Control advanced, ATC,ATDZ-33Is included in the C-Box installation packageThe unit heater controller (ATDZ-33) automaticallycontrols the fan speed in three steps depending on theheating load and switches out the fan when heating isno longer necessary. The controller also controls the liq-uid valve (ATDZ-17-3 or ATDZ-17-4) between the openand closed positions. The desired temperature can beset by pressing buttons on the top panel, if the con-troller is to control to an alternative temperature acrossa timer (ATDZ-22) that temperature should also be pre-set.

The control system has provision for an anti-frostfunction, i.e. it has an input for an anti-frost thermostat(ATDZ-26). It also controls the damper motor (ATDZ-27) from open to closed position, adjustable for 0 –100% fresh air.

Detailed technical description of the control system:When the ambient air temperature is 0.4° C below theset point setting, the fan starts at the lowest presetspeed. At 0.5° C below the set point, the connectedwater valve opens. At 1.5° C below the preset set point,the fan switches over to the medium speed. At 2.5°Cbelow preset set point the fan changes over to the high-est preset speed. The corresponding 1-10V signalstrengths are: 1.5V-2V-5V-8V.

Remote control via cable (ATDZ-21-3) and remotecontrol via infrared communication (ATDZ-36) areavailable as accessories.

The speed control system can be controlled inresponse to a 0-10 V signal (from a microprocessor sub-station) or via a network connection LAN (AuxiliaryModule ATDZ-37), further communication options areavailable on request. An unlimited number of speedcontrollers can be connected in series via cables withmodular jack. The control system has an output for oneexternal fault alarm signal. An LED indicates when theliquid valve is open.

The preset temperature is shown in a display.The automatic unit heater control, ATC, is suppliedmounted on the unit heater and has degree of protec-tion IP54.

The temperature sensor is supplied separately, IP30.Voltage: 1 x 230 V.Max. current: 2 A.

130

76179

78

78

35

Page 23: ATD Unit Heater – AEROTEMPER...The ATDI can be equipped with an explosion-proof motor, steel coil, etc. Contact Fläkt Woods for further details. ATD Unit Heater. Fläkt Woods 10014

Fläkt Woods 10014 GB 04.03 23 We reserve the right to alter specifications.

ATD Unit Heater CATALOGUE

Valve with actuator,open/closed, ATDZ-17-4For use together with the following:ATDZ-15-4, ATDZ-18-3, ATDZ-19-3, ATDZ-33, or ATDZ-34.The valve opens/closes the circuit.Valve housing is made of red brass.Temperature range: 2 – 110 °C, kvs4.0. Motorized valve with built-inanti-frost function. Opening time: 10 seconds.Dead (non-energized) valve isopen. Max. permissible ambient tempera-ture: 50°C. Adapters for fitting torelevant water connection aresupplied. Threaded pipe connec-tion for further pipe routing.

Length of cable: 1.5 m.Degree of protection: IP 54.Voltage: 1x230 V.

Valve with thermal actua-tor, open/closed,ATDZ-17-3For use together with the following:ATDZ-15-4, ATDZ-24-3,ATDZ-18-3, ATDZ-19-3,ATDZ-25-3, ATDZ-29, ATDZ-33,or ATDZ-34. The valve opens/clos-es the circuit. The valve housing ismade of red brass. Temperaturerange: 2 – 110 °C, kvs 4.0. Thermalactuator. Dead (non-energized)valve is open. Max. permissible ambient tempera-ture: 50°C. Adapters for fitting torelevant water connection aresupplied. Threaded pipe connec-tion for further pipe routing. Length of cable: 1.5 m.

Degree of protection: IP 40.Voltage: 1 x 230 V.

Accessories, Control Equipment

66DN 20

120

DN 20

66

125

Speed selectorATDZ-13For manual switching to mediumspeed and switching off theATDA, sizes 30, 33 and 44Plastic casing for wall-mounting.

Degree of protection: IP 54Voltage: 1 x 230 V.Max: 10 A.

64

64

57

Page 24: ATD Unit Heater – AEROTEMPER...The ATDI can be equipped with an explosion-proof motor, steel coil, etc. Contact Fläkt Woods for further details. ATD Unit Heater. Fläkt Woods 10014

Fläkt Woods 10014 GB 04.03 24 We reserve the right to alter specifications.

ATD Unit Heater CATALOGUE

Accessories, Control Equipment

Room thermostat for fanoperation, ATDZ-19-3 For switching in and switchingout the unit heater.The thermostat can also beconnected to theATDZ-28, ATDZ-24-3 andATDZ-25-3. An ATDZ-17-3 orATDZ-17-4 valve with motorizedactuator can be connected to thethermostat. Make sure that thecorrect function is obtained,depending on the type of actuator.

Degree of protection: IP 54.Voltage: 1 x 230 V.Max. current: 16 A.

Remote control forAutomatic temperaturecontrol, ATDZ-21-3 forATDZ-29

Remote control forAutomatic temperaturecontrol, ATDZ-21-4 forATDZ-33For remote control of the ATDZ-29or ATDZ-33 Automatic unit heatercontrol system. The desired setpoint temperature can be set on thecontroller. Automatic or manualoperation as well as switched-offposition can be selected by pressingthe appropriate button. For manu-al operation, fixed low, medium orhigh fan speeds can be selected. The set point, fan speed andtemperature settings can be read inthe display.A5 m long connection cord withconnector for connection to the unitheater control system is supplied. The connection cord can be fittedwith an extension cord to 100 m.

Degree of protection: IP 30..57

130

65

49

Room thermostat for fanoperation, ATDZ-18-3 For switching in and switchingout the unit heater.The thermostat can also beconnected to the ATDZ-28, ATDZ-24-3 andATDZ-25-3. An ATDZ-17-3 orATDZ-17-4 valve with motorizedactuator can be connected to thethermostat. Make sure that thecorrect function is obtained,depending on the type of actuator.

Degree of protection: IP 30.Voltage: 1 x 230 V.Max. current: 16 A

3578

78

78

78 35

Page 25: ATD Unit Heater – AEROTEMPER...The ATDI can be equipped with an explosion-proof motor, steel coil, etc. Contact Fläkt Woods for further details. ATD Unit Heater. Fläkt Woods 10014

Fläkt Woods 10014 GB 04.03 25 We reserve the right to alter specifications.

ATD Unit Heater CATALOGUE

Transformer,ATDZ-25-3For obtaining a lower fixed speedthan the design speed.

The ATDZ-25-3 transformercan serve at the most:

• 3 type ATDA30, 33 unitheaters

• 2 type ATDA44 unit heaters• 1 type ATDA55, 66 unit

heatersIf more units are to be suppliedwith current, select the ATDZ-28.The transformer has a plasticcasing. The transformer has provi-sion for connecting an ATDZ-17-3or ATDZ-17-4 valve, ATDZ-18-3 orATDZ-19-3 room thermostat andan ATDZ-22-3 timer.

For particulars of the connec-tion options, see the appropriateinstallation example.

Degree of protection: IP 54.Voltage: 1 x 230 V.Max. current: 2 A.

125100

175

Speed selector,ATDZ-24-3For manual switching betweenthree preset speeds, low – medium– high, as well as switched-off. Theselector switch has a plastic casingand can be fitted e.g. to a wall. Theswitch has provision for connect-ing an ATDZ-17-3 valve, ATDZ-18-3 or ATDZ-19-3 room thermostatand an ATDZ-22-3 timer.For particulars of the connectionoptions, see the appropriate instal-lation example.

Degree of protection: IP 54.Voltage: 1 x 230 V.Max. current: 2 A.

Accessories, Control Equipment

125100

175

Timer for Automatic temperature control,ATDZ-22-3 For switching between presetdaytime and nighttime tempera-tures in the ATDZ-29/-33(Automatic unit heater control).The timer enables connection to asecond preset temperature in theAutomatic unit heater controlsystem. This makes it possible toobtain a lower temperature in thepremises e.g. at night and duringweekends to save on electric power. The timer can also be connected tothe ATDZ-24-3 and ATDZ-25-3.

Max. current: 10 A.

3546

66

2520

65 6085

Page 26: ATD Unit Heater – AEROTEMPER...The ATDI can be equipped with an explosion-proof motor, steel coil, etc. Contact Fläkt Woods for further details. ATD Unit Heater. Fläkt Woods 10014

Fläkt Woods 10014 GB 04.03 26 We reserve the right to alter specifications.

ATD Unit Heater CATALOGUE

Anti-frost protection ther-mostat, ATDZ-26Designed for use together with theATDZ-01-bb mixing section.The thermostat cuts off the powersupplied to the connected unitheater when frosting is likely. The limit temperature can bepreset, setting is made under thecasing. The thermostat is designed formounting directly against thereturn water pipe. The springclamp provided is used for fixingthe thermostat against the waterpipe. Temperature range: +10/ +90°C.

Degree of protection: IP 20.Voltage: 1 x 230 V.Max. current: 15 A.

Damper actuator, Belimo,ATDZ-27Designed for use together with theATDZ-01-bb mixing section.Spring return actuator used foractuating the damper to the openor closed position, 0-100%.When electric power is connectedto the actuator, the actuator setsitself to the service position andtensions the return spring. If thepower supply is opened, this tripsthe stored spring energy thatreturns the damper actuator to itssafety position. The actuator isdesigned for mounting on thedamper shaft by means of theuniversal locking clamp.The actuator is supplied withpivotal circuit breaker.The actuator is overload-resistantand stops automatically at presetstops.

Degree of protection: IP 54.Voltage: 1 x 230 V.

Accessories, Control Equipment

100

39

41

Speed switch,ATDZ-28For obtaining a lower fixed speedthan the design speed, for max. 9unit heaters. The transformer hasa plastic casing. The switch hasprovision for connecting anATDZ-17-3 valve, ATDZ-18-3 orATDZ-19-3 room thermostat andan ATDZ-22-3 timer.

For particulars of the connec-tion options, see the appropriateinstallation example.

Degree of protection: IP 54.Voltage: 1 x 230 V.Max. current: 9 A.

360

260

185

150

98

58

Page 27: ATD Unit Heater – AEROTEMPER...The ATDI can be equipped with an explosion-proof motor, steel coil, etc. Contact Fläkt Woods for further details. ATD Unit Heater. Fläkt Woods 10014

Fläkt Woods 10014 GB 04.03 27 We reserve the right to alter specifications.

ATD Unit Heater CATALOGUE

Temperature sensor, RGHumidity, ATDZ-35-1, ATDZ-35-2Temperature sensor for a humidenvironment. Suitable for use, ifrequired, instead of the temperature sensor suppliedfor the following control condi-tions:

The ATDZ-35-1 should be usedfor the ATDZ-29 Automatic unitheater control, ATC.

ATDZ-35-2 should be used forother Automatic fan/unit heatercontrol.

Degree of protection: IP54.

Connection device,ATDZ-30Connection device for connectingthe unit heater together with anATDZ-18-3 or ATDZ-19-3 roomthermostat, ATDZ-17-3 or ATDZ-17-4 valve with actuator,ATDZ-01-bb mixing section,ATDZ-27 damper actuator and anATDZ-26 anti-frost protection ther-mostat.

Degree of protection: IP 44.Voltage: 1 x 230 V.Max. current: 2 A.

.

Remote control, infrared,ATDZ-36Battery-powered control unitincluding wall mounting bracketfor remote control of the ATDZ-33Automatic unit heater control. Thedesired set point is preset on thecontrol unit. Automatic or manual operationand switched-off position can beselected by pressing the appropri-ate button. If the unit heater is to be operatedmanually, fixed low, medium orhigh fan speed can be selected.The preset temperature set point,fan speed and present tempera-ture can be read in the display.

Degree of protection: IP 30.

Accessories, Control Equipment

33

140

63

40

51

50

80

83

40

Page 28: ATD Unit Heater – AEROTEMPER...The ATDI can be equipped with an explosion-proof motor, steel coil, etc. Contact Fläkt Woods for further details. ATD Unit Heater. Fläkt Woods 10014

Fläkt Woods 10014 GB 04.03 28 We reserve the right to alter specifications.

ATD Unit Heater CATALOGUE

Accessories, Control Equipment

Auxiliary module fornetwork connection,ATDZ-37Automatic unit heater control,ATC, can be individually remote-controlled or controlled in group. All the settings can be read andaltered.If several Automatic unit heaterATC control units are to becontrolled from a master system,the module has a universal inter-face for other communicationprograms, such as Modbus,Profibus and RS 485.Operating voltage 10-30 V.

Aquotation will be submittedon request.

80

83

40

Page 29: ATD Unit Heater – AEROTEMPER...The ATDI can be equipped with an explosion-proof motor, steel coil, etc. Contact Fläkt Woods for further details. ATD Unit Heater. Fläkt Woods 10014

Fläkt Woods 10014 GB 04.03 29 We reserve the right to alter specifications.

ATD Unit Heater CATALOGUE

1 Measure the floor surface ofthe premises.The floor surface in the buildingshown above is 8 m x 20 m = 160m2.

2 Estimate the height of the ceil-ing.An average ceiling height of 3 mis estimated.

3 Then estimate the nature of thebuilding and the type of heat-ing used. Select the capacity requiredW/m2 from the chart. Thisbuilding has moderate insula-tion and basic heating in theform of a system with radiatorsthat generate 60 W/m2.

4 Estimate the capacity required.In this case, the capacityrequired will be 160 x 60 = 9,6kW.

5 Estimate the number of unitheaters needed.As a rule of thumb, each unitheater can heat 80 m2 (8 m x 10m), see adjacent illustration. For this case, select two unitheaters and locate them oppo-site one another.

6 Then plot the relevant temper-ature and inlet air temperaturein the table on page 32/33.We intend to use the existingboiler which provides 60–30°Cwater, and will want to quicklyincrease the heat in the workshop after weekends, duringwhich the temperature islowered to about 15°C.

7 The size of unit and the fanspeed can be obtained from the

table on page 33.If two unit heaters are used,each will have to provide acapacity of 4.8 kW.The ATDA-33-1 unit heater bythese temperatures will gener-ate 6.0 kW at 1035 r/min, andthis capacity will be more thanefficient. The motor outputrequired can be read from theMotor Data Table on page 36.

8 Motor.We are selecting a single-phase,230 V motor with manual speedselector. Should boosted orreduced capacity be required,the motor can easily bereswitched.

9 Control equipmentIn this case, we will be control-ling the unit heater by means ofa room thermostat. Should theneed arise to use the unit heatersfor automatically controllingthe temperature in the premises,we can purchase the Automaticunit heater control unit.

10 Select appropriate accessoriesfrom the range of accessories. We intend to mount the unitheater on the wall and thereforerequire a set of mounting brack-ets.

Our purchase list will thus be asfollows:2 type ATDA-33-1 units2 type ATDZ-03-33 bracket sets2 type ATDZ-24-3 1) manual speedselectors2 type ATDZ-18-3 1) room thermo-stats

Capacity Required W/m2

(for max. 5 metre highceiling)

Chart

Maximum HeatingSurface per Unit Heater.

1) For this application, it may beenough with 1 of each forcontrolling both units.

Sizing

3 m

8 m

20 m

None

Basicheating

Exists

Good Insulationbuildning

Poor

100

80

40

60

None

Exists

Insulation inbuilding

Poor

Basicheating

Good

8 m

10 m

Page 30: ATD Unit Heater – AEROTEMPER...The ATDI can be equipped with an explosion-proof motor, steel coil, etc. Contact Fläkt Woods for further details. ATD Unit Heater. Fläkt Woods 10014

Fläkt Woods 10014 GB 04.03 30 We reserve the right to alter specifications.

ATD Unit Heater CATALOGUE

Installation Instructions

10-20 m

The unit is nor-mally installed2.5 – 3 mabove the floor.

Min

. 0,5

mM

in. 2 m

NOTE! Not suitable for steam

Min. 0,5 m

The size of the unit heaters deter-mines their distance from oneanother.

Recirculated air section

Spacer mounting bracket, ATDZ-05

NOTE! Not suitable for steam

Wall mountingbracket

Mixing section

Arrange the unit heaters in theroom to obtain good circulation.

Ceiling mount-ing bracket

Page 31: ATD Unit Heater – AEROTEMPER...The ATDI can be equipped with an explosion-proof motor, steel coil, etc. Contact Fläkt Woods for further details. ATD Unit Heater. Fläkt Woods 10014

Fläkt Woods 10014 GB 04.03 31 We reserve the right to alter specifications.

ATD Unit Heater CATALOGUE

Capacity Chart - Hot Water

The general survey chart above is applicable to waterat a temperature of 80–60°C and an inlet air tempera-ture of +15°C using a single-phase, 230 V motor(highest speed is standard; a lower speed can beobtained by fitting an accessory).

Accurate sizingMore accurate selection and other operating condi-tions can be carried out in our data calculation com-puter program, COILS for Windows. Get in touchwith your nearest Fläkt Woods sales representativefor further information.

General Survey Chart for Quick Selection

1,3 m3/s

0,94 m3/s

0,68 m3/s

1,59 m3/s

1,11m3/s

0,9 m3/s

0,85 m3/s

0,54 m3/s

0,40 m3/s

42 kW

LjudnivådB(A)

Varvtalrpm

Effekt

34 kWStorlek-55-1

27 kW

65 kW

51 kWStorlek-66-1

44 kW

58

50

43

935

670

485

60

52

45

908

630

515

29 kW

21 kWStorlek-44-1

17 kW

58

48

41

1430

900

660

0,26 m3/s

0,39 m3/s

0,51 m3/s17 kW

14 kWStorlek-33-1

11 kW

0,26 m3/s

0,39 m3/s

0,51 m3/s11 kW

9 kWStorlek-30-1

7 kW

54

48

39

1420

1035

685

54

48

39

1420

1035

685

0 1 2 3 4 5 6 7 8 9 10 Horisontell kastlängd, m

CapacitySound level Speed

Size

Size

Size

Size

Size

Horizontal throw, m

Page 32: ATD Unit Heater – AEROTEMPER...The ATDI can be equipped with an explosion-proof motor, steel coil, etc. Contact Fläkt Woods for further details. ATD Unit Heater. Fläkt Woods 10014

Fläkt Woods 10014 GB 04.03 32 We reserve the right to alter specifications.

ATD Unit Heater CATALOGUE

Hot water

80–60 °C 70–40 °C 60–30 °C 55–35 °C

Size Speed Air- Inlet Outlet Outlet Outlet OutletATDA flow air air Water air Water air Water air Water

temp. Capacity temp. flow Capacity temp. flow Capacity temp. flow Capacity temp. flowrpm m3/s °C kW °C l/s kW °C l/s kW °C l/s kW °C l/s

30-1 1420 0,51 14,3 21,6 0,17 10,0 15,1 0,08 7,5 11,3 0,06 8,4 12,7 0,101035 0,39 12,3 24,2 0,15 8,6 17,0 0,07 6,4 12,7 0,05 7,2 14,2 0,09685 0,26 9,7 28,7 0,12 6,8 20,2 0,05 5,1 15,0 0,04 5,7 16,9 0,07

33-1 1420 0,51 21,2 32,0 0,20 16,5 24,8 0,13 12,8 19,3 0,10 13,7 20,6 0,161035 0,39 18,3 36,2 0,20 13,7 27,1 0,11 10,7 21,0 0,09 11,4 22,4 0,14685 0,26 14,3 42,2 0,17 10,5 31,1 0,08 8,1 24,1 0,07 8,7 25,7 0,10

44-1 1430 0,85 37,1 33,6 0,40 27,7 25,1 0,22 21,4 19,3 0,17 23,0 20,8 0,28900 0,54 ±0 28,1 40,0 0,34 20,5 29,2 0,16 15,8 22,6 0,13 17,0 24,2 0,20660 0,40 23,1 44,4 0,28 16,9 32,5 0,14 13,0 25,1 0,10 14,0 26,9 0,17

44-3 1430 0,85 37,1 33,6 0,40 27,7 25,1 0,22 21,4 19,3 0,17 23,0 20,8 0,28

55-1 935 1,30 55,9 33,1 0,67 40,0 23,7 0,32 30,4 18,0 0,24 33,3 19,7 0,40670 0,94 44,9 36,8 0,54 32,2 26,3 0,26 24,4 20,0 0,20 26,8 21,9 0,32485 0,68 36,2 41,0 0,43 26,0 29,5 0,21 19,8 22,4 0,16 21,6 24,5 0,26

55-3 1330 1,84 68,1 28,5 0,70 50,6 21,2 0,41 38,5 16,1 0,31 42,3 17,7 0,511035 1,44 59,9 32,0 0,72 42,8 22,9 0,34 32,6 17,4 0,26 35,7 19,1 0,43

66-1 908 1,59 85,8 41,5 1,06 63,4 30,7 0,51 49,3 23,9 0,40 52,5 25,4 0,63630 1,11 67,2 46,6 0,80 49,7 34,4 0,40 38,6 26,8 0,31 41,0 28,4 0,49515 0,90 57,9 49,3 0,69 43,0 36,6 0,34 33,4 28,4 0,27 35,5 30,2 0,42

66-3 1394 2,15 100,6 36,0 1,00 77,1 27,6 0,62 59,8 21,4 0,48 63,8 22,9 0,761153 1,77 90,9 39,5 1,00 68,0 29,6 0,54 52,8 23,0 0,42 56,3 24,5 0,67

Capacity Table - Unit Heaters for Hot Water

Inlet air temperature ±0°C

1)

1)

1)

1)

The speeds specified in bold type are for the deliveryversion without the use of an accessory. Other speeds are obtainable with an accessory. Thetable is applicable to an open discharge unit withoutany accessory on the air side.The calculated capacities take into account the airdensity at the inlet air temperature, which at ±0°C is 1,29 kg/m3.

1) The speed can be obtained by rewiring the powersupply leads to the motor, see the wiring diagram.

Page 33: ATD Unit Heater – AEROTEMPER...The ATDI can be equipped with an explosion-proof motor, steel coil, etc. Contact Fläkt Woods for further details. ATD Unit Heater. Fläkt Woods 10014

Fläkt Woods 10014 GB 04.03 33 We reserve the right to alter specifications.

ATD Unit Heater CATALOGUE

Capacity Table - Unit Heaters for Hot Water

The speeds specified in bold type are for the deliveryversion without the use of an accessory. Other speeds are obtainable with an accessory. Thetable is applicable to an open discharge unit withoutany accessory on the air side.The calculated capacities take into account the airdensity at the inlet air temperature, which at ±0°C is 1,23 kg/m3.

1) The speed can be obtained by rewiring the powersupply leads to the motor, see the wiring diagram.

Inlet air temperature ±15°C

1)

1)

1)

1)

Hot water

80–60 °C 70–40 °C 60–30 °C 55–35 °C

Size Speed Air- Inlet Outlet Outlet Outlet OutletATDA flow air air Water air Water air Water air Water

temp. Capacity temp. flow Capacity temp. flow Capacity temp. flöde Capacity temp. flowrpm m3/s °C kW °C l/s kW °C l/s kW °C l/s kW °C l/s

30-1 1420 0,51 10,8 32,0 0,13 6,5 25,2 0,05 3,7 20,9 0,03 4,9 22,8 0,061035 0,39 9,3 34,1 0,11 5,6 26,5 0,04 3,3 21,7 0,03 4,2 23,7 0,05685 0,26 7,3 37,7 0,09 4,4 28,6 0,04 2,6 23,0 0,02 3,3 25,3 0,04

33-1 1420 0,51 17,0 41,8 0,20 11,0 32,3 0,09 7,2 26,4 0,06 8,3 28,1 0,101035 0,39 14,2 44,2 0,17 9,2 34,0 0,07 6,0 27,4 0,05 6,9 29,3 0,08685 0,26 10,8 48,5 0,13 7,1 36,9 0,06 4,6 29,3 0,04 5,3 31,5 0,06

44-1 1430 0,85 28,7 42,1 0,34 18,4 32,4 0,15 11,9 26,2 0,10 13,9 28,2 0,17900 0,54 +15 21,3 46,7 0,25 13,7 35,4 0,11 8,8 28,1 0,07 10,3 30,4 0,12660 0,40 17,5 50,2 0,21 11,3 37,7 0,09 7,2 29,4 0,06 8,5 32,1 0,10

44-3 1430 0,85 28,7 42,1 0,34 18,4 32,4 0,15 11,9 26,2 0,10 13,9 28,2 0,17

55-1 935 1,30 42,0 41,0 0,50 26,1 31,2 0,21 16,0 24,9 0,13 19,8 27,2 0,24670 0,94 33,8 43,9 0,41 21,1 33,0 0,17 12,7 25,9 0,10 15,9 28,6 0,19485 0,68 27,4 47,4 0,33 17,1 35,2 0,14 10,4 27,3 0,08 12,9 30,3 0,15

55-3 1330 1,84 53,2 38,3 0,64 33,0 29,4 0,26 20,5 24,0 0,16 25,0 25,9 0,301035 1,44 45,0 40,2 0,54 28,0 30,6 0,22 17,2 24,6 0,14 21,2 26,8 0,25

66-1 908 1,59 65,1 48,2 0,78 42,2 36,6 0,34 27,8 29,2 0,22 32,0 31,3 0,38630 1,11 50,7 52,0 0,61 33,2 39,3 0,27 21,7 30,9 0,17 25,0 33,3 0,30515 0,90 43,6 54,2 0,52 28,7 40,7 0,23 18,6 31,7 0,15 21,6 34,4 0,26

66-3 1394 2,15 79,4 45,0 0,95 51,5 34,5 0,41 33,9 27,8 0,27 39,0 29,7 0,471153 1,77 69,9 47,1 0,84 45,5 35,9 0,36 29,9 28,7 0,24 34,4 30,8 0,41

Page 34: ATD Unit Heater – AEROTEMPER...The ATDI can be equipped with an explosion-proof motor, steel coil, etc. Contact Fläkt Woods for further details. ATD Unit Heater. Fläkt Woods 10014

Fläkt Woods 10014 GB 04.03 34 We reserve the right to alter specifications.

ATD Unit Heater CATALOGUE

Pressure drop on water side Airflow, ATDA-30, 33

Heating, water

Air- Airflow withSize Speed, flow, accessory 1),

ATDA rpm m3/s m3/s

30-1 1420 0,51 0,381035 0,39 0,29685 0,26 0,20

33-1 1420 0,51 0,381035 0,39 0,29685 0,26 0,20

44-1 1430 0,85 0,64900 0,54 0,41660 0,40 0,30

A44-3 1430 0,85 0,64

55-1 935 1,30 0,98670 0,94 0,71485 0,68 0,51

55-3 1330 1,84 1,381035 1,44 1,08

66-1 908 1,59 -630 1,11 - 515 0,90 -

66-3 1394 2,15 -1153 1,77 -

1) Accessory denotes a ATDZ-01mixing section or ATDZ-02recirculated air section, bothwith filter.

2) No mixing section is availablefor this size.

ATD-3

3AT

D-3

0

ATD-4

4AT

D-1

7-3

(ven

til)

ATD-5

5

ATD-

66

(With mounted valve ∆prtot =∆prtemper + ∆prvalve)

Airflow

Airflow, ATDA-44

Airflow, ATDA-55

Airflow, ATDA-66

2)

2)

Airflow m3/h

Water flow, l/s

Pre

ssur

e dr

op, k

Pa

20

10

54

3

2

1,51,00,50,10,05 0,2

200 300 500 1000 3000

Airflow m3/s

0 0,5

50

0

0 1000 2000

Sta

tic p

ress

ure,

Pa

With mixingsectionor recirculatedair section

1420 r/m

1035

685

Airflow m3/h

Airflow m3/s

Sta

tic p

ress

ure,

Pa

0 0,5

50

0

0 1000 2000

With mixingsectionor recirculatedair section

1430 r/m

900

660

2000

Airflow m3/h

Airflow m3/s

Sta

tic p

ress

ure,

Pa

2000 4000 6000

0,50 1,0 1,5 2,0

200

150

100

50

0

1300 r/m

1035

935

670

485

With mixingsectionor recircu-lated airsection

Airflow m3/h

Airflow m3/s

Sta

tic p

ress

ure,

Pa

2000 4000 6000

0,50 1,0 1,5 2,0

300

250

200

100

50

8000

2,5

0

150

0

1394 r/m

0

1153

908

630

515

ATD-1

7-3

(val

ve)

Page 35: ATD Unit Heater – AEROTEMPER...The ATDI can be equipped with an explosion-proof motor, steel coil, etc. Contact Fläkt Woods for further details. ATD Unit Heater. Fläkt Woods 10014

Fläkt Woods 10014 GB 04.03 35 We reserve the right to alter specifications.

ATD Unit Heater CATALOGUE

Single air deflectorSize Speed, Throw, m

rpm L0,2

ATDA-30-1 1420 5,81035 4,5685 3,0

ATDA-33-1 1420 5,81035 4,5685 3,0

ATDA-44-1 1430 6,0900 4,0660 3,5

ATDA-44-3 1430 6,0

ATDA-55-1 935 7,3670 5,3485 3,7

ATDA-55-3 1330 10,11035 8,1

ATDA-66-1 908 12630 7515 5

ATDA-66-3 1394 181153 15

Sound level, sound power levelHot water – ATDA

Throw, horizontalHot water – ATDA

Technical data, water

Tolerance: ± 2 dB1) Sound level at a distance of 5 meters, Q = 2, absorp-

tion area = 200 m2 Sabine.2) Sound power in accordance with ISO 3744.

The specified throw is applicable to a supply air tem-perature of +40°C and an indoor temperature of+18°C.The air deflector is fitted horizontally.The premises are completely free of disturbance fromair draughts and nearby furnishings. L0,2= the perpendicular distance from the unit heater

to air velocity v = 0.2 m/s..

Size Speed Sound Sound Linear sound power, dB,level power Octave band, Centre frequency, Hz1) 2)

ATDA rpm dB(A) dB(A) 125 250 500 1000 2000 4000 8000

30-1 1420 54 70 66 68 65 63 61 57 481035 48 65 60 62 59 57 55 51 42685 39 55 51 53 50 48 46 42 33

33-1 1420 54 70 66 68 65 63 61 57 481035 48 65 60 62 59 57 55 51 42685 39 55 51 53 50 48 46 42 33

44-1 1430 58 74 68 73 70 66 64 61 53900 48 64 58 63 60 56 54 51 43660 41 57 51 56 53 49 47 44 36

44-3 1430 58 74 68 73 70 66 64 61 53

55-1 935 58 74 74 76 65 66 63 58 50670 50 66 68 66 58 59 57 49 38485 43 59 61 59 51 52 50 42 31

55-3 1330 66 82 82 84 73 74 71 66 581035 60 76 76 78 67 68 65 60 52

66-1 908 60 76 78 76 71 70 68 68 59630 52 67 74 65 63 61 61 54 45515 45 61 68 60 57 56 54 44 34

66-3 1394 67 83 80 82 78 77 75 74 691153 53 79 79 78 75 73 71 71 65

Page 36: ATD Unit Heater – AEROTEMPER...The ATDI can be equipped with an explosion-proof motor, steel coil, etc. Contact Fläkt Woods for further details. ATD Unit Heater. Fläkt Woods 10014

Fläkt Woods 10014 GB 04.03 36 We reserve the right to alter specifications.

ATD Unit Heater CATALOGUE

Size Speed Rated Rated current (A), 50 Hz Termo- Degreeoutput 1-phase 3-phase 3-phase static of

ATDA rpm kW 230 V 400 V 400 V contact protection∆ Y

30-1 1420 0,11 0,54 – – Yes IP441035 0,45 – –685 0,40 – –

33-1 1420 0,11 0,54 – – Yes IP441035 0,45 – –685 0,40 – –

44-1 1430 0,16 0,73 – – Yes IP44900 0,60 – –660 0,55 – –

44-3 1430 0,15 – 0,55 – No IP44

55-1 935 0,29 1,65 – – Yes IP54670 1,30 – –485 1,15 – –

55-3 1330 0,65 – 1,15 – Yes IP541035 0,46 – – 0,79

66-1 900 0,37 1,7 – – Yes IP54640505

66-3 1360 0,84 – 1,65 – Ja IP541090 0,64 1,05

Motor dataHot water – ATDA

Design data, ATDAMax. permissible ambient air temperature at motor:+50°C.

Leakage testedMax operating pressure: 1.6 MPa at max operatingtemperature: 100 °C.Max operating pressure: 1.0 MPa at max operatingtemperature: 150 °C.

All coils are pressure-tested and leakage-tested withdry air under water.

Designed and manufactured in accordance withPressure Equipment Directive. 9723 EG (PED).

Technical Data, Water

The speeds specified in bold type are for the deliveryversion without the use of an accessory. Other speeds are obtainable with an accessory.

1) The speed can be obtained by rewiring the powersupply leads to the motor, see the wiring diagram.

1)

1)

1)

1)

The accessories ATDZ-15-4 (Automatic fan, unit heatercontrol), ATDZ-24-3 and ATDZ-25-3, ATDZ-28, ATDZ-29and ATDZ-33 include a transformer which, besides 230 Voutput current, has five lower voltages for lower speed.The ATDZ-15-4 (Automatic fan control) and ATDZ-24-3,ATDZ-28, ATDZ-29 and ATDZ-33 (3-step manualswitch) operate with 3 different voltages. These acces-sories are factory-wired making it possible to obtain theappropriate speed for each step.

The table above shows the factory-wired voltages andcorresponding speed. If for some reason it is desirable toalter the speeds, this can be done by reconnecting theflexible connections on the transformer. Detailed wiring diagrams for motors and accessories areprovided in the installation, operation and maintenanceinstructions for the ATD

Speed with Automatic fan control, Automatic unit heater control or three-step switch – voltage control

= rated speed of unit supplied

ATDA-30-1 ATDA-33-1 ATDA-44-1 ATDA-55-1 ATDA-66-1

230 V 1420 1420 1430 935 900

150 V 1190 1190 1210 670 640

130 V 1035 1035 900 485 505

115 V 850 850 660 390 430

100 V 685 685 550 310 355

80 V 500 500 410 240 270

Page 37: ATD Unit Heater – AEROTEMPER...The ATDI can be equipped with an explosion-proof motor, steel coil, etc. Contact Fläkt Woods for further details. ATD Unit Heater. Fläkt Woods 10014

Fläkt Woods 10014 GB 04.03 37 We reserve the right to alter specifications.

ATD Unit Heater CATALOGUE

Steam

110°C/1,4 bar(a) 130°C/2,7 bar(a) 150°C/4,7 bar(a) 170°C/7,9 bar(a)

Size Speed Air- Inlet Outlet Outlet Outlet Outletflow air air air air air

temp. Capacity temp. Capacity temp. Capacity temp. Capacity temp.rpm m3/s °C kW °C kW °C kW °C kW °C

ATDG-33-1 1420 0,51 13,6 20,6 16,1 24,4 18,7 28,2 21,2 32,01035 0,39 12,3 24,3 14,6 28,8 16,9 33,3 19,1 37,8685 0,26 10,5 31,0 12,4 36,7 14,4 42,5 16,3 48,3

ATDG-44-1 1430 0,85 27,9 25,3 33,1 30,0 38,3 34,7 43,5 39,4900 0,54 ±0 23,3 33,2 27,6 39,3 31,9 45,5 36,3 51,8660 0,40 20,5 39,5 24,4 46,9 28,2 54,4 32,1 61,9

ATDG-44-3 1430 0,85 27,9 25,3 33,1 30,0 38,3 34,7 43,5 39,4

ATDG-55-1 935 1,30 41,7 24,7 49,4 29,3 57,1 33,8 64,9 38,4670 0,94 36,6 30,0 43,4 35,6 50,2 41,2 57,1 46,8485 0,68 32,1 36,4 38,2 43,2 44,0 49,8 50,0 56,7

ATDG-55-3 1330 1,84 47,6 19,9 56,4 23,6 65,2 27,3 74,0 31,01035 1,44 43,4 23,2 51,4 27,5 59,4 31,8 67,5 36,1

Inlet air temperature ±0°C

Capacity Table – Steam

The speeds specified in bold type are for the deliveryversion without the use of an accessory. Other speeds are obtainable with an accessory. Thetable is applicable to an open discharge unit withoutany accessory on the air side.The calculated capacities take into account the airdensity at the inlet air temperature, which at ±0°C is 1,29 kg/m3.

More accurate selection and other operating condi-tions can be carried out in our data calculation com-puter program, COILS for Windows. Get in touchwith your nearest Fläkt Woods sales representative forfurther information.

Page 38: ATD Unit Heater – AEROTEMPER...The ATDI can be equipped with an explosion-proof motor, steel coil, etc. Contact Fläkt Woods for further details. ATD Unit Heater. Fläkt Woods 10014

Fläkt Woods 10014 GB 04.03 38 We reserve the right to alter specifications.

ATD Unit Heater CATALOGUE

Inlet air temperature ±15°C

Capacity Table - Steam

The speeds specified in bold type are for the deliveryversion without the use of an accessory. Other speeds are obtainable with an accessory. Thetable is applicable to an open discharge unit withoutany accessory on the air side.The calculated capacities take into account the airdensity at the inlet air temperature, which at ±0°C is 1,23 kg/m3

More accurate selection and other operating condi-tions can be carried out in our data calculation com-puter program, COILS for Windows. Get in touchwith your nearest Fläkt Woods sales representative forfurther information.

Steam

110°C/1,4 bar(a) 130°C/2,7 bar(a) 150°C/4,7 bar(a) 170°C/7,9 bar(a)

Size Speed Air- Inlet Outlet Outlet Outlet Outletflow air air air air air

temp. Capacity temp. Capacity temp. Capacity temp. Capacity temp.rpm m3/s °C kW °C kW °C kW °C kW °C

ATDG-33-1 1420 0,51 11,7 33,5 14,2 37,4 16,7 41,3 19,2 45,31035 0,39 10,6 36,8 12,8 41,4 15,1 46,1 17,3 50,8685 0,26 9,0 42,8 10,9 48,7 12,8 54,7 14,8 60,7

ATDG-44-1 1430 0,85 24,0 37,7 29,1 42,5 34,2 47,4 39,4 52,3900 0,54 +15 20,0 44,8 24,2 51,1 28,5 57,5 32,9 64,0660 0,40 17,6 50,3 21,4 58,0 25,2 65,6 29,0 73,4

ATDG-44-3 1430 0,85 24,0 37,7 29,1 42,5 34,2 47,4 39,4 52,3

ATDG-55-1 935 1,30 35,8 37,1 43,4 41,9 51,1 46,6 58,8 51,4670 0,94 31,4 41,9 38,1 47,7 44,9 53,5 51,7 59,3485 0,68 27,5 47,6 33,5 54,6 39,4 61,7 45,5 68,8

ATDG-55-3 1330 1,84 40,9 32,9 49,6 36,7 58,3 40,5 67,1 44,31035 1,44 37,2 35,8 45,2 40,2 53,1 44,7 61,2 49,2

Page 39: ATD Unit Heater – AEROTEMPER...The ATDI can be equipped with an explosion-proof motor, steel coil, etc. Contact Fläkt Woods for further details. ATD Unit Heater. Fläkt Woods 10014

Fläkt Woods 10014 GB 04.03 39 We reserve the right to alter specifications.

ATD Unit Heater CATALOGUE

Sound level, sound power levelSteam – ATDG

Technical data, steam

Single air deflectorSize Speed, Throw, m

rpm L0,2

ATDG-33-1 1420 5,81035 4,5685 3,0

ATDG-44-1 1430 6,0900 4,0660 3,0

ATDG-44-3 1430 6,0

ATDG-55-1 935 7,3670 5,3485 3,7

ATDG-55-3 1330 10,11035 8,1

Throw, horizontalSteam – ATDG

Tolerance: ± 2 dB1) Sound level at a distance of 5 meters, Q = 2, absorp-

tion area = 200 m2 Sabine.2) Sound power in accordance with ISO 3744.

The specified throw is applicable to a supply air tem-perature of +40°C and an indoor temperature of+18°C.The air deflector is fitted horizontally.The premises is completely free of disturbance fromair draughtcs and nearby furnishings. L0,2 = the perpendicular distance from the unit heaterto air velocity v = 0.2 m/s.

Size Speed Sound Sound Linear sound power, dBlevel power Octave band, Centre frequency, Hz1) 2)

ATDA rpm dB(A) dB(A) 125 250 500 1000 2000 4000 8000

33-1 1420 54 70 66 68 65 63 61 57 481035 48 65 60 62 59 57 55 51 42685 39 55 51 53 50 48 46 42 33

44-1 1430 58 74 68 73 70 66 64 61 53900 48 64 58 63 60 56 54 51 43660 41 57 51 56 53 49 47 44 36

44-3 1430 58 74 68 73 70 66 64 61 53

55-1 935 58 74 74 76 65 66 63 58 50670 50 66 68 66 58 59 57 49 38485 43 59 61 59 51 52 50 42 31

55-3 1330 66 82 82 84 73 74 71 66 581035 60 76 76 78 67 68 65 60 52

The accessories ATDZ-15-4 (Automatic fan, unit heatercontrol), ATDZ-24-3 and ATDZ-25-3, ATDZ-28, ATDZ-29and ATDZ-33 include a transformer which, besides 230 Voutput current, has five lower voltages for lower speed.The ATDZ-15-4 (Automatic fan control) and ATDZ-24-3,ATDZ-28, ATDZ-29 and ATDZ-33 (3-step manualswitch) operate with 3 different voltages. These acces-sories are factory-wired making it possible to obtain theappropriate speed for each step.

The table above shows the factory-wired voltages andcorresponding speed. If for some reason it is desirable toalter the speeds, this can be done by reconnecting theflexible connections on the transformer. Detailed wiring diagrams for motors and accessories areprovided in the installation, operation and maintenanceinstructions for the ATD.

Speed with Automatic fan control, Automatic unit heater control or three-step switch – voltage control

= rated speed of unit supplied

ATDA-30-1 ATDA-33-1 ATDA-44-1 ATDA-55-1 ATDA-66-1

230 V 1420 1420 1430 935 900

150 V 1190 1190 1210 670 640

130 V 1035 1035 900 485 505

115 V 850 850 660 390 430

100 V 685 685 550 310 355

80 V 500 500 410 240 270

Page 40: ATD Unit Heater – AEROTEMPER...The ATDI can be equipped with an explosion-proof motor, steel coil, etc. Contact Fläkt Woods for further details. ATD Unit Heater. Fläkt Woods 10014

Fläkt Woods 10014 GB 04.03 40 We reserve the right to alter specifications.

ATD Unit Heater CATALOGUE

Technical data, steam

Size Speed Rated Rated current (A), 50 Hz Thermo- Degreeoutput 1 phase 3 phase 3 phase static of

ATDA rpm kW 230 V 400 V 400 V contact protection∆ Y

33-1 1420 0,11 0,54 – – Ja IP441035 0,45 – –685 0,40 – –

44-1 1430 0,16 0,73 – – Ja IP44900 0,60 – –660 0,55 – –

44-3 1430 0,15 – 0,55 – Nej IP44

55-1 935 0,29 1,65 – – Ja IP54670 1,30 – –485 1,15 – –

55-3 1330 0,65 – 1,15 – Ja IP541035 0,46 – – 0,79

Motor dataStream – ATDG

Operating Data ATDGMax operating pressure: 1.0 MPaMax operating temperature: 185 °C.Test pressure = 1.3 MPaThe pH-value of the steam may not be below 8.5 andshould normally be at pH 9,5.The oxygen content - O2 - must not exceed 0.01 mg/l.

All coils are pressure-tested and leakage-tested withdry air under water.

Designed and manufactured in accordance withPressure Equipment Directive. 9723 EG (PED).

The speeds specified in bold type are for the deliveryversion without the use of an accessory. Other speeds are obtainable with an accessory.

1) Star coupling be obtained by reswitching the motor.The speeds specified in bold type are for the deliveryversion without the use of an accessory. Other speedsare obtainable with an accessory.

1)

Page 41: ATD Unit Heater – AEROTEMPER...The ATDI can be equipped with an explosion-proof motor, steel coil, etc. Contact Fläkt Woods for further details. ATD Unit Heater. Fläkt Woods 10014

Fläkt Woods 10014 GB 04.03 41 We reserve the right to alter specifications.

ATD Unit Heater CATALOGUE

ATDA Unit heater for hot waterAll dimensions in mm

Dimensions and Weights, ATDA

E

F

B

A

ø 22 x 1

ø 22 x 1

Ut

InG

J

C D

G

H

Dimensions, (mm) Nom. pipe Size conn. Number Wgt.,

ATDA A B C D E F G H J kg

-33 480 465 270 82 290 350 50 76 81 15

-44 670 615 310 82 355 510 58 89 67 23

-55 770 715 340 100 440 610 58 89 67 39

-66 990 815 370 136 495 740 58 115 70 52

Out

In

Page 42: ATD Unit Heater – AEROTEMPER...The ATDI can be equipped with an explosion-proof motor, steel coil, etc. Contact Fläkt Woods for further details. ATD Unit Heater. Fläkt Woods 10014

Fläkt Woods 10014 GB 04.03 42 We reserve the right to alter specifications.

Luftvärmare ATD KATALOG

ATDG Unit heater for steamAll dimensions in mm

Dimensions and Weights, ATDG

Dimensions, mm Nom. pipe Size conn. Number Wgt.,

ATDG A B C D E F G H J kg

-33 480 465 270 82 290 350 58 25 25 15

-44 670 615 310 82 355 510 61 32 25 23

-55 770 715 340 100 440 610 61 32 32 39

E

F 45

B B

A

H

J

Ut

In

G

CD

G

127

Out

In

Page 43: ATD Unit Heater – AEROTEMPER...The ATDI can be equipped with an explosion-proof motor, steel coil, etc. Contact Fläkt Woods for further details. ATD Unit Heater. Fläkt Woods 10014

Fläkt Woods 10014 GB 04.03 43 We reserve the right to alter specifications.

ATD Unit Heater CATALOGUE

Installation package

ATDZ-15-4 (B-Box)

Wiring Diagram

A-Box, principschema

PE N L

N PE L

RumstermostatATDZ-18-3, ATDZ-19-3

Ventil medställdonATDZ-17-4

Fan Transformer

TemperatureB-Box

L1 N

5 35

230V10A

Fläkt

Brown = Low speedRed = Medium speedWhite = High speed

ATDZ-17-4Ventil med

ställdon

Temperatur-givare

Lm Nm Nv Lv 1 2

1 2

°C

230V~

230V Fan Valve Control inputs

115V

100V

80V

230V

130V

150V

SV

Fan Transformer

C-Box

D

Remote

Moduljackför seriekoppling av flera ATDZ-33

Temp - 0-10V

L1 N

230V10A

Fläkt 0-10V

Brown = Low speedRed = Medium speedWhite = High speed

ATDZ-17-4Ventil med

ställdon

Temperatur-givare

ATDZ-22-3Tidsur

ATDZ-21-4Fjärrstyrning

för ATC

Lm Nm Nv Lv 1 2

1 2

°C

3 4 5 6

230V~

230V Fan Valve Control inputs

150V

130V

115V

100V

80V

230V

A = ÖppenB = Stängd

7 8 9 10 11

ATDZ-26 ATDZ-27

Larm

Lan

Frys-skydd

Ställ-don

Sv

ATDZ-33 (C-Box) (F-Box)

A-BoxBasic circuitdiagram

Room thermostat

Valve withactuator,ATDZ-17-4

Fan

ATDZ-17-4valve withactuator

Temperaturesensor

Fan

ATDZ-17-4valve withactuator

Temperaturesensor

ATDZ-21-4Remote

control forATC

ATDZ-27Actuator

ATDZ-22-3Timer

ATDZ-26Anti-frostprotection

Alarm

A = OpenB = Closed

Module jack forserial connection ofseveral ATDZ-33unit heaters

Page 44: ATD Unit Heater – AEROTEMPER...The ATDI can be equipped with an explosion-proof motor, steel coil, etc. Contact Fläkt Woods for further details. ATD Unit Heater. Fläkt Woods 10014

Fläkt Woods 10014 GB 04.03 44 We reserve the right to alter specifications.

ATD Unit Heater CATALOGUE

Wiring Diagram

Reglering med rumstermostatoch ventilATDZ-17-3

PE N L

N PE L

RumstermostatATDZ-18-3, ATDZ-19-3

Ventil medställdonATDZ-17-3

Control with room thermostat and valvewith actuator, ATDZ-17-3,Basic circuit diagram

ATDZ-24-3 3-step switch

ATDZ-25-3 Transformer

Brown = Low speedRed = Medium speedWhite = High speed

Fan Transformer ATDZ-24-3

Fan speed

1

1

2

2

3

3

4

230V10A MotorATDZ-17-3

Ventil medställdonATDZ-18-3

5 6 7 8 9 10 11 12230 V Valve Fan

150V

130V

115V

100V

80V

230V

0 31 2

Rumstermostat

Fan Transformer ATDZ-25-3

1 2 3 4

230V10A MotorATDZ-17-3

Ventil medställdon

5 6 7 8 9 10 11 12230 V Valve Fan

150V

130V

115V

100V

80V

230V

1

2 3

ATDZ-18-3Rumstermostat

ATDZ-18-3, ATDZ-19-3Room thermostat

ATDZ-17-3Valve withactuator

ATDZ-17-3Valve withactuatorATDZ-18-3 Room

thermostat

ATDZ-17-3Valve withactuatorATDZ-18-3 Room

thermostat

Page 45: ATD Unit Heater – AEROTEMPER...The ATDI can be equipped with an explosion-proof motor, steel coil, etc. Contact Fläkt Woods for further details. ATD Unit Heater. Fläkt Woods 10014

Fläkt Woods 10014 GB 04.03 45 We reserve the right to alter specifications.

ATD Unit Heater CATALOGUE

ATDZ--13 Speed switch

Wiring Diagram

L

N

BlåBrunSvart

2

1354

4

1

35

2

11911

753

1012

864

2 1

10

2

1

2

3 ATDZ-31-1ATDZ-32-1

Fläktmotor EBM

Läge 0 1 21-23-4

5-67-89-1011-12

Läge 1= LågfartLäge 2= Högfart

Fler motorer kan parallellkopplas viakopplingsdosor, under förutsättning att standarder för elsäkerhet uppfylls.

*)

*) Uttagen 1-3-7och 5-11byglas vid installationen

VarvtalsomkATDZ-13

N07VASEV-U 3G1,5eller likvärdigIngen längdbegränsning

A05VV-R 7G1,5eller likvärdigIngen längdbegränsning

230 VAC *)

*)

N07VASEV-U 3G1,5or the likeNo length limitation

A05VV-R 7G1,5or the likeNo length limitation

ATDZ 13Speed switch EBM Fan motor

Several motors can be connected inparallel across junction boxes,provided that standards for electri-cal safety are met.

*) A jumpermust beconnectedbetweenoutputs1-3-9 and7-11 whenthe unit isinstalled.

BlueBrown

Black

Position 1= Low speedPosition 2= High speed

Pos

Page 46: ATD Unit Heater – AEROTEMPER...The ATDI can be equipped with an explosion-proof motor, steel coil, etc. Contact Fläkt Woods for further details. ATD Unit Heater. Fläkt Woods 10014

Fläkt Woods 10014 GB 04.03 46 We reserve the right to alter specifications.

ATD Unit Heater CATALOGUE

Wiring Diagram

ATDZ-22-3 Timer

3

L

1 2

M

ATDZ-22-3

L1

N

Last

L1

N

N

C1

Ω

ATDZ-18-3 Roomthermostat

1

2 3

ATDZ-18-3

ATDZ-19-3 Roomthermostat

4 2 1

c

ATDZ-26 Anti-frost protection thermostat

1

23

L N

BRC

Inkommande matningefter säkerhetsbrytare1x230V, 10A

The power supply mustbe wired across a safetyisolating switch.1x230V, 10A

Page 47: ATD Unit Heater – AEROTEMPER...The ATDI can be equipped with an explosion-proof motor, steel coil, etc. Contact Fläkt Woods for further details. ATD Unit Heater. Fläkt Woods 10014

Fläkt Woods 10014 GB 04.03 47 We reserve the right to alter specifications.

ATD Unit Heater CATALOGUE

ATDZ-29 Automatic unit heater control ATC

Wiring Diagram

A

B

C

1234

56

Inkomm-ande styr

12 C

Enhe

t 9

Enhe

t 1

LF

NF

SV

Fläktmotor 2

GTK

Ventil medställdonATDZ-17-3

Fläktmotor 9

Koppl.dosa alt.KopplingsenhetATDZ-30

ATDZ 29

FS3FS2FS1N230

150V130V115V100V

80VN

230V

FjärrstyrningATDZ-21-3

TidurATDZ-22-3A=ÖppenB=Stängd

RumstermostatATDZ-18-3, 19-3

N

L1

Option

Inkommandematning230 V, 10 A

Installeras via säkerhetsbrytare

GTK

Ventil med ställdonATDZ-17-3

Fläktmotor 1

Fläktmotor 3

Fläktmotor 4

Fläktmotor 5

Fläktmotor 6

Temperatur

Temperatur

Fjärrstyrning

Fläktmotor 7

Fläktmotor 8Fläkttrans-formator

LF

NF

SV

ATDZ-17-3Valve withactuator

Connection box or.ATDZ-30Connection device

Fan trans-former

Uni

t 9U

nit 1

Fan Motor 8

Fan Motor 7

Fan Motor 6

Fan Motor 5

Fan Motor 4

Fan Motor 3

Fan Motor 2

Temperature

Temperature

Remote control

Controlinput

Fan motor 9

ATDZ-17-3 Valvewith actuator

ATDZ-21-3Remote control

Fan motor 1

ATDZ-22-3 TimerA=OpenB=Closed

ATDZ-18-3, 19-3Room thermostat

230 V, 10 Apower supplywiring across asafety isolatingswitch

Page 48: ATD Unit Heater – AEROTEMPER...The ATDI can be equipped with an explosion-proof motor, steel coil, etc. Contact Fläkt Woods for further details. ATD Unit Heater. Fläkt Woods 10014

Fläkt Woods 10014 GB 04.03 48 We reserve the right to alter specifications.

ATD Unit Heater CATALOGUE

Connection device ATDZ-30

Wiring Diagram

M

Ventil med ställdonATDZ-17-3

1

2

1

2

1

2

123

1

2

3

1

2

1

2

1

2

1

2

3

1

2

3

1

2

3

2

1

3

RumstermostatATDZ-18-3

LF

NF

SV

PE

Lx

Nx

PE

SV

N

L

PE

PE

PE

Nm

Lm

PE

Fläktmotor

FrysskyddATDZ-26

SpjällställdonATDZ-27

~

Matning 1x230 AC 18A

Fan motor

1x230 AC 18Asupply

ATDZ-18-3 Room thermostat

ATDZ-26 Anti-frost protection

ATDZ-27 Damper actuator

ATDZ-17-3Valve withactuator

Page 49: ATD Unit Heater – AEROTEMPER...The ATDI can be equipped with an explosion-proof motor, steel coil, etc. Contact Fläkt Woods for further details. ATD Unit Heater. Fläkt Woods 10014

Fläkt Woods 10014 GB 04.03 49 We reserve the right to alter specifications.

ATD Unit Heater CATALOGUE

Other versionsAir heater ATDA-aa-bb-c-d

ATDG-aa-bb-c-dATDI-aa-bb-c-d

A= for hot waterG = for steamI = industry version

(contact Fläkt Woods)

Size (aa)30, applicable to ATDAonly33, 44, 55

Motor (bb)04 = 1 x 230 V, IP55 (size 44)05 = 3 x 400 V, IP55, 1340/960 rpm, (size 44)06 = 3 x 500 V, 1400 rpm, (size 44) 07 = 3 x 500 V, 1000 rpm, (size 44)08 = 3 x 400 V, 1400 rpm, increased safety

(size 44)09 = 3 x 400 V, 1000 rpm, increased safety

(size 44, 55)10 = 1 x 230 V, IP55 (size 55)11 = 3 x 400 V, IP55, 1370/1000 rpm, (size 55)12 = 3 x 400 V, IP55, 920/700 rpm, (size 55)13 = 3 x 500 V, 940 rpm, (size 55)

Casing, material (c)1 = Sheet steel painted white (standard)2 = Stainless (304)

Coil body, material (d)1 = Cu/Al (standard)2 = Cu/Cu3 = Cu/Al + Blygold (not suitable for steam)

AccessoriesMixing section with filter ATDZ-01-bb *)Recirculated air section with filter ATDZ-02-bb *)Wall mounting bracket, set ATDZ-03-bb Spacer mounting bracket for mixing section, set ATDZ-05-bb *)Extra air deflector ATDZ-09-bb Ceiling mounting bracket, set ATDZ-10-bb *)

Size (bb)33, 44, 55, 66

*) Not in size 66

Lever actuator for mixing section ATDZ-12

Product code

Installation packageA-box, size 30 ATDA-30-1-AA-box, size 33 33-1-AA-box, size 44 44-1-AA-box, size 55 55-1-AA-box, size 66 66-1-A

B-box, size 30 ATDA-30-1-BB-box, size 33 33-1-BB-box, size 44 44-1-BB-box, size 55 55-1-BB-box, size 66 66-1-B

C-box, size 30 ATDA-30-1-CC-box, size 33 33-1-CC-box, size 44 44-1-CC-box, size 55 55-1-CC-box, size 66 66-1-C

Accessories for installation packageF-box, size 30 ATDZ-30-1-FF-box, size 33 33-1-FF-box, size 44 44-1-FF-box, size 55 55-1-F

Standard designUnit heater ATDA-aa-b

ATDG-aa-b

A= for hot waterG = for steam

Size (aa)30, applicable to ATDAonly33, 44, 55, 66

Motor (b)1 = 1 x 230 V, IP443 = 3 x 400 V, IP54 (applicable to size 44, 55 and 66 only)

Page 50: ATD Unit Heater – AEROTEMPER...The ATDI can be equipped with an explosion-proof motor, steel coil, etc. Contact Fläkt Woods for further details. ATD Unit Heater. Fläkt Woods 10014

Fläkt Woods 10014 GB 04.03 50 We reserve the right to alter specifications.

ATD Unit Heater CATALOGUE

Product code

Control EquipmentAutomatic fan control, ATDZ-15-4FHC-1, simpleIncluding sensor to IP30 for wall mounting.Supplied as separate item. 1 x 230 V. Max 2 A.

Automatic fan control, ATDZ-34FHC-3, simpleIncluding sensor to IP30 for wall mounting.Supplied as separate item. 3 x 400 V. Max 2 A.

Automatic unit heater control, ATDZ-29ATC, advancedIncluding sensor to IP30 for wall mounting.Fitted to unit. 1 x 230 V. Max 9 A.

Automatic unit heater control, ATDZ-33ATC, advancedIncluding sensor to IP30 for wall mounting.Fitted to unit. 1 x 230 V. Max 2 A.

Accessories for the control equipmentSpeed selector ATDZ-13

Speed selector ATDZ-24-3Manual 3-step. Motor 1 x 230 V. 2 A.

Speed selector ATDZ-28Manual 3-step. Motor 1 x 230 V. 9 A.

Valve with thermal actuator ATDZ-17-3Open/closed.1 x 230 V.

Valve with actuator ATDZ-17-4Open/closed. Quick-action1 x 230 V.

Room thermostat ATDZ-18-3On/off, 1 x 230 V. IP30.

Room thermostat ATDZ-19-3On/off, 1 x 230 V. IP54.

Remote control for the Automatic ATDZ-21-3Unit heater control ATDZ-29

Remote control for the Automatic ATDZ-21-4Air heater control ATDZ-33

Remote control, infrared ATDZ-36

Timer ATDZ-22-3Temperature control, day/night, forAutomatic air heater control.

Transformer ATDZ-25-3Lower speed. Motor 1 x 230 V.

Anti-freezing thermostat ATDZ-26Cuts off the power when frosting is likely.

Damper actuator, Belimo ATDZ-27With spring return, actuates damper toOpen/closed position.

Connection device ATDZ-30

Temperature sensor for the Automatic ATDZ-35-1Air heater control ATDZ-29IP54.

Temperature sensor for the Automatic ATDZ-35-2fan, air heater controlATDZ-15-4,-33, -34IP54.

Extra module, network ATDZ-37

Page 51: ATD Unit Heater – AEROTEMPER...The ATDI can be equipped with an explosion-proof motor, steel coil, etc. Contact Fläkt Woods for further details. ATD Unit Heater. Fläkt Woods 10014

Fläkt Woods 10014 GB 04.03 51 We reserve the right to alter specifications.

ATD Unit Heater CATALOGUE

Spare PartsCoil package ATDA-99-1-cc

ATDG-99-1-cc

A= for waterG = for stream

Size (cc)30 (applicable to ATDAonly), 33, 44, 55, 66.

Fan and motor unit,with protective grill ATDA-99-2-cc-d

Size (cc)33, 44, 55, 66.

Motor (d)1 = 1 x 230 V.3 = 3 x 400 V,(applicable to cc = 44, 55 and 66 only.)

Temperature sensor for the ATDA-99-16-3Automatic Air heater control ATDZ-29

Temperature sensor for the ATDA-99-16-4Automatic Fan, air heater controlATDZ-15, -33, -44

Replacement filter forMixing/Recirculated air section ATDZ-99-01-33

ATDZ-99-01-44ATDZ-99-01-55

Product code

Page 52: ATD Unit Heater – AEROTEMPER...The ATDI can be equipped with an explosion-proof motor, steel coil, etc. Contact Fläkt Woods for further details. ATD Unit Heater. Fläkt Woods 10014

Fläkt Woods 10014 GB 04.03 52 We reserve the right to alter specifications.

ATD Unit Heater CATALOGUE

The Installation Packages are supplied incardboard cartons.

Packaging – Installation Package

Size L B H Weight, kg

ATDA-30, 33 65 48 40 1844 84 64 44 3055 94 74 46 3566 115 83 57 57

Size L B H Weight, kg

ATDA-01-30, 33 65 48 40 1801-44 84 64 44 3001-55 94 74 46 3501-66 115 83 57 57

Dimensions in cm for the A, B, C box

Dimensions in cm for the F-box

L

B

H

Page 53: ATD Unit Heater – AEROTEMPER...The ATDI can be equipped with an explosion-proof motor, steel coil, etc. Contact Fläkt Woods for further details. ATD Unit Heater. Fläkt Woods 10014

Fläkt Woods 10014 GB 04.03 53 We reserve the right to alter specifications.

ATD Unit Heater CATALOGUE

Page 54: ATD Unit Heater – AEROTEMPER...The ATDI can be equipped with an explosion-proof motor, steel coil, etc. Contact Fläkt Woods for further details. ATD Unit Heater. Fläkt Woods 10014

Fläkt Woods 10014 GB 04.03 54 We reserve the right to alter specifications.

ATD Unit Heater CATALOGUE

Page 55: ATD Unit Heater – AEROTEMPER...The ATDI can be equipped with an explosion-proof motor, steel coil, etc. Contact Fläkt Woods for further details. ATD Unit Heater. Fläkt Woods 10014

Fläkt Woods 10014 GB 04.03 55 We reserve the right to alter specifications.

ATD Unit Heater CATALOGUE

Page 56: ATD Unit Heater – AEROTEMPER...The ATDI can be equipped with an explosion-proof motor, steel coil, etc. Contact Fläkt Woods for further details. ATD Unit Heater. Fläkt Woods 10014

We Bring Air to Life

Fläkt Woods is a globalleader in air management.We specialise in the designand manufacture of a widerange of air climate and airmovement solutions. Andour collective experienceis unrivalled.

Our constant aim is toprovide systems thatprecisely deliver requiredfunction and performance,as well as maximise energy efficiency.

Fläkt Woods is providing solutions for ventilation and air climate for buildings as well as fan solutions for Industry and Infrastructure.

Solutions for all your air climate and air movement needs

Air Handling Units (AHUs)Modular, compact and smallAHU units. Designed to ensureoptimisation of indoor air quality,operational performance andservice life.

Air Terminal Devices and DuctsSupply and exhaust diffusers andvalves for installation on walls, ceiling or floor are all included in our large range and fit all types of applications.

Chilled BeamsActive induction beams forventilation, cooling and heating,and passive convection beamsfor cooling. For suspended orflush-mounted ceiling installation –and multi-service configuration.With unique Comfort Control andFlow Pattern Control features.

Residential ventilationA complete range of products forresidential ventilation. Consists ofventilation units, exhaust air fans and cooker hoods designed to optimise indoor comfort and save energy. Energy recoveryDessicant-based product and sys-tems that recover energy, increase ventilation and control humidity.

FansAdvanced axial, centrifugal andboxed fans for general and specialist applications. Comprehensive range including high temperature and ATEX compliant options. Engineered for energy efficiency andminimised life cycle cost.

ChillersAir-cooled and water-cooled chillers with cooling capacity up to 1800 kW. Designed tominimise annual energy consumption in all types of buildings.

Controls and drivesVariable speed drives and controlsystems, all tested to ensure totalcompatibility with our products.Specialist team can advise on energy saving and overall systemintegration.

Acoustical productsA complete line of sound attenuating products, including rectangular and round silencers. Media Free silenc-ers, custom silencers and acoustic enclosure panels.

10014 G

B 2

01204 c

onde

sign

tel

esko

p AB

03

6-3

0 8

3 8

0

Fläkt Woods Group SA18, avenue Louis Casaï, CH-1209 Geneva, SwitzerlandTel. +41 22 309 3800email [email protected] www.flaktwoods.com