The perfect match for: • Pumps • Fans • Compressors • Mixers • Conveyors • and many more Power range: 7.5–110 kW VL T® Compact Start er MCD 200 from Danfoss includes two families of soft starters in t he power range from 7.5–110 kW. The series offer easy DIN rail mount- ing for sizes up to 30 kW, 2-wire or 3-wire start/stop control and excellent starting duty (4 x I e for 6 seconds). Heavy starting ratings at 4x I e for 20 seconds. Compatible with grounded delta power systems. Features Benefits • S mall footprint and compact size • Saves panel space • Built-in bypass • Minimises installation cost and eliminates power loss • Advanced accessories • Allows enhanced function ality • I nternal delta wiring kit • The soft starter carries only phase current, and can therefore control a motor with greater full load current Reliable – Maximum up-time • Essential motor pr ot ec ti on s ( MC D 20 2) • Redu ce s over al l pr oj ec t i nv es tm en t • Pass word protection of parameters • Prevents unauthoriz ed changes • Max. ambient temperature 50 ˚C without derating • No external cooling or ov ersizing necessary User-friendly –Save commissioning and operating cost • Easy to install and use • • Eas y D IN rail moun ting f or siz es up to 30 kW • Saves time and spa ce MCD 201 MCD 202 MCD 202 provides enhanced soft start functionality and various motor protection features Ramp up Initial torque Ramp down U M 3~ M 3~ Ramp up Initial current Current limit Ramp down U I VLT® Compact Starter MCD 200
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.