Top Banner
Scientific Journal Impact Factor (SJIF): 1.711 International Journal of Modern Trends in Engineering and Research www.ijmter.com @IJMTER-2014, All rights Reserved 201 e-ISSN: 2349-9745 p-ISSN: 2393-8161 ARM based protection system for induction motor against faults Sandip J.Murchite 1 , Dr. S. A. Patil 2 1 Student, Department of Electronics 2 Professor, H.O.D. Department of Electronics & Telecommunication Dkte’sTextile& Engineering Institute of Technology, Ichalkaranji,India Abstract-This paper deal with protection of an induction motor against faults like over voltage, under voltage, single phasing ,voltage unbalance, over temperature. In this system 3 PT’s are connected to each phase of induction motor. The electrical signal is acquired by the ARM LPC2148 and 10 bit digital equivalent values of these electrical and temp signals are compared with the reference values by the means of software. The 10bit digital equivalent parameters are send to COM port of PC When any fault is detected, the system activated relay and thus cuts the power supply to the induction motor. The corresponding faults are displaced on LCD display of ARM processor as well as the graphs plotted on console of a PC with the help of LABVIEW 2014 software. LABVIEW 2014 also stores a database file of the electrical signals along with graphs. I. INTRODUCTION Three phase induction motors are very popular in industrial applications because of their simple and safe structures. Towards the end of the 20 th century, development in electronics and computer technology has started new progress in control technology. Electrical related faults are frequently occurring faults in three phase induction machine which will produce more heat on stator and rotor winding. To protect the machine from more heating due to these electrical faults, a reliable, low cost protection scheme for three phase induction motor is developed using ARM LPC 2148. The faults come under electrical related faults are over voltage, under voltage, voltage unbalance, single phasing. Voltage and temperature. data are measured in fault detection system and this measured data is transferred to LPC 2148 and through COM port to PC. Hence we can monitor motor operating parameters through designed LABVIEW 2014 software. If any fault is found in the system, it becomes necessary to detect and diagnose the fault. Soft computing techniques are more advanced in error detection and diagnosis problems than classical methods. II. Electrical faults in induction motor 1) Unbalance voltage: Voltage unbalance of a three phase induction motor is expressed as a percentage value and defined as the maximum deviation from the average of the three phase voltages divided by the average of the three phase voltages. (Max deviation from avg value) Unbalance (%)= x100 (Average voltage) 2) Single phasing: It occurs when one of the three phase supply is open. Single phasing is worst case of voltage unbalance.
8

ARM based protection system for induction motor against faults

Apr 15, 2017

Download

Engineering

Editor IJMTER
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: ARM based protection system for induction motor against faults

Scientific Journal Impact Factor (SJIF): 1.711

International Journal of Modern Trends in Engineering

and Research www.ijmter.com

@IJMTER-2014, All rights Reserved 201

e-ISSN: 2349-9745

p-ISSN: 2393-8161

ARM based protection system for induction

motor against faults

Sandip J.Murchite1, Dr. S. A. Patil2

1Student, Department of Electronics

2Professor, H.O.D. Department of Electronics & Telecommunication

Dkte’sTextile& Engineering Institute of Technology, Ichalkaranji,India

Abstract-This paper deal with protection of an induction motor against faults like over voltage, under voltage, single phasing ,voltage unbalance, over temperature. In this system 3 PT’s are connected to each phase of induction motor. The electrical signal is acquired by the ARM LPC2148 and 10 bit digital equivalent values of these electrical and temp signals are compared with the reference values by the means of software. The 10bit digital equivalent parameters are send to COM port of PC When any fault is detected, the system activated relay and thus cuts the power supply to the induction motor. The corresponding faults are displaced on LCD display of ARM processor as well as the graphs plotted on console of a PC with the help of LABVIEW 2014 software. LABVIEW 2014 also stores a database file of the electrical signals along with graphs.

I. INTRODUCTION Three phase induction motors are very popular in industrial applications because of their simple

and safe structures. Towards the end of the 20th century, development in electronics and computer technology has started new progress in control technology. Electrical related faults are frequently occurring faults in three phase induction machine which will produce more heat on stator and rotor winding. To protect the machine from more heating due to these electrical faults, a reliable, low cost protection scheme for three phase induction motor is developed using ARM LPC 2148. The faults come under electrical related faults are over voltage, under voltage, voltage unbalance, single phasing. Voltage and temperature. data are measured in fault detection system and this measured data is transferred to LPC 2148 and through COM port to PC. Hence we can monitor motor operating parameters through designed LABVIEW 2014 software. If any fault is found in the system, it becomes necessary to detect and diagnose the fault. Soft computing techniques are more advanced in error detection and diagnosis problems than classical methods.

II. Electrical faults in induction motor

1) Unbalance voltage: Voltage unbalance of a three phase induction motor is expressed as a percentage value and defined as the maximum deviation from the average of the three phase voltages divided by the average of the three phase voltages.

(Max deviation from avg value) Unbalance (%)= x100

(Average voltage)

2) Single phasing: It occurs when one of the three phase supply is open. Single phasing is worst case of voltage unbalance.

Page 2: ARM based protection system for induction motor against faults

International Journal of Modern Trends in Engineering and Research (IJMTER)

Volume 01, Issue 06, [December - 2014] e-ISSN: 2349-9745, p-ISSN: 2393-8161

@IJMTER-2014, All rights Reserved 202

3) Under voltage: it occurs when phase voltage is greater than 110% of rated value.

4) Over temperature: Temperature rise is the change in temperature of the critical electrical parts within a motor when it is being operated at full speed. %( Temp rise) = 2*(voltage unbalance) 2

III. HARDWARE DESIGN Fig 3. Shows the overall block diagram of the protection scheme. It consists of three parts

Part A: voltage and Temperature sensing module.

Part B: ARM LPC 2148 Module.

Part C: LABVIEW VISA 2014.

Figure 1-Block diagram of Motor protection scheme.

A. Voltage and temperature sensing module

In this module, three PTs are connected to each phase of IM. The low ac signal is taken from

transformer secondary windings and converted into DC using precision rectifier.

3phase supply

Page 3: ARM based protection system for induction motor against faults

International Journal of Modern Trends in Engineering and Research (IJMTER)

Volume 01, Issue 06, [December - 2014] e-ISSN: 2349-9745, p-ISSN: 2393-8161

@IJMTER-2014, All rights Reserved 203

Figure 2-Dual Precision rectifier.

Figure 2 shows the standard dual full wave version of the precision rectifier. The tolerance of R1,

2, 3, 4 and 5 are critical for good performance, and all five resistors should be 1% or better. Note that the

diodes are connected to obtain a positive rectified signal. The second stage inverts the signal polarity. To

obtain improved high frequency response, the resistor values should be reduced. This circuit is sensitive

to source impedance, so it is important to ensure that it is driven from low impedance

B.ARM LPC2148 Module.

The data gathered from voltage transformers and temperature sensor is transferred to the

LPC2148 digitally using ADC unit. The arm processor continuously monitors the inputs signals VR,

VY, VB and Temperature. The needed comparison is made in the ARM according to limit values which

are previously entered. When an unexpected situation is encountered, trip signal send by the ARM to the

relay and corresponding LED glow on relay circuit. The corresponding fault is displayed on LCD

display as well as alerts the operator by glowing LED on relay circuit.

Figure 3 -Schematic of ARM LPC 2148

Page 4: ARM based protection system for induction motor against faults

International Journal of Modern Trends in Engineering and Research (IJMTER)

Volume 01, Issue 06, [December - 2014] e-ISSN: 2349-9745, p-ISSN: 2393-8161

@IJMTER-2014, All rights Reserved 204

C.LABVIEW VISA 2014

In lab view , VISA is the standard API for instrument drivers throughout the instrumentation

industry. we can use NI-VISA to communicate with most instrumentation buses including GPIB, USB,

Serial, and Ethernet. It provides a consistent and easy to use command set to communicate with a variety

of instruments. Serial, GPIB, and many VXI devices recognize a variety of message-based command

strings. At the VISA level the actual protocol used to send a command string to an instrument is

transparent. A user only needs to know that they would like to write a message to or read a message

from a message-based device. The VIs that are used to perform these operations are VISA Write and

VISA Read.

Figure 4- VISA write Virtual instrument

Figure 5-VISA read virtual instrument

IV. RESULT

Figure 6-Terminal output showing phase voltages and temperature

Page 5: ARM based protection system for induction motor against faults

International Journal of Modern Trends in Engineering and Research (IJMTER)

Volume 01, Issue 06, [December - 2014] e-ISSN: 2349-9745, p-ISSN: 2393-8161

@IJMTER-2014, All rights Reserved 205

S

Figure 7-lab view output signals under single phasing fault.

Figure 8-labview output signals under voltage unbalance fault

Figure 9-labview output signals under over temperature fault

Page 6: ARM based protection system for induction motor against faults

International Journal of Modern Trends in Engineering and Research (IJMTER)

Volume 01, Issue 06, [December - 2014] e-ISSN: 2349-9745, p-ISSN: 2393-8161

@IJMTER-2014, All rights Reserved 206

Figure 10-Labview output signals under under voltage fault

V.CONCLUSION

In this paper ARM based fault protection system is designed . The protection system detects the

voltage unbalance, single phasing, over temperature, under /over voltage faults thus provide efficient

protective scheme.

REFERENCES

[1] M. SUIDHA,P. ANBALAGAN, ”A Novel Protecting Method for Induction Motor Against Faults Due to

Voltage Unbalance and Single Phasing”, 33rd Annual Conference of the IEEE Industrial Electronics Society (IECON), pp. 1144- 1148, November 2007.

[2] Mr. S. KALIAPPAN, K. RAJSHREE “Arm based efficiency monitoring with protection technique in

induction motor” International Journal of Scientific & Engineering Research, Volume 4, Issue 12,

December 2013.

[3] W.H.Kersting,”Causes and Effects of Single phasing induction motors”IEEETrans.on Industry

applications,Vol:41, no.6, Nov/Dec 2005.

[4] ABITHA, MEMALA.W “Induction motor fault diagnosis using labview .” Circuits, Power and Computing Technologies (ICCPCT), 2013 International Conference.

[5] PINJIA ZHANG “A survey of condition monitoring and protection methods for medium voltage induction

motors.” Energy Conversion Congress and Exposition, 2009. ECCE 2009. IEEE

Page 7: ARM based protection system for induction motor against faults
Page 8: ARM based protection system for induction motor against faults