Arctic IEC-104 Gateway

Jari Lahti, CTO

Page 2: Arctic IEC-104 Gateway Jari Lahti, CTO. Arctic IEC-104 Gateway IEC 60870-5-104 to IEC 60870-5-101 communication gateway –Conversion between IEC-104 and.

Arctic IEC-104 Gateway• IEC 60870-5-104 to IEC 60870-5-101 communication gateway

– Conversion between IEC-104 and IEC-101

• Local IEC-101 polling of Class 1 and Class 2 events

• One RS-232 and one RS-232/422/485 port up to 460800 bps

• Internal Ethernet and GSM/GPRS wireless network interface

• Secure communication with internal VPN and firewall

• GPRS operator independent static IP addressing with Viola M2M Gateway

• Packet compression for slow-speed links

• I/O extension option (=Arctic RTU)

• DIN rail mounting option

IEC-104 OVER GPRS

IEC-101 OVER RS-232

Page 3: Arctic IEC-104 Gateway Jari Lahti, CTO. Arctic IEC-104 Gateway IEC 60870-5-104 to IEC 60870-5-101 communication gateway –Conversion between IEC-104 and.

Wireless Feeder Automation

IEC-101 OVER RS-232

Viola M2M Gateway

IEC-104 OVER SECURE VPN TUNNELGPRS

SCADA

Arctic IEC-104 Gateway

IEC-101 Devices (Feeder Controllers)

IEC-104

Page 4: Arctic IEC-104 Gateway Jari Lahti, CTO. Arctic IEC-104 Gateway IEC 60870-5-104 to IEC 60870-5-101 communication gateway –Conversion between IEC-104 and.

Physical Connections

RS 1 (RS-232)-Console or plain data

Console switch-Defines the mode of RS 1 (console or data)

RS 2 (RS-232/422/485)-IEC-101 data

RS 2 DIP switches-RS-232 / RS-422 / RS-485-Full (485) / Half (422) duplex-Bias on/off-Termination on/off

GPRS Antenna-FME connector

Power input-6-26 VDC

Ethernet-10/100 Base-T

Page 5: Arctic IEC-104 Gateway Jari Lahti, CTO. Arctic IEC-104 Gateway IEC 60870-5-104 to IEC 60870-5-101 communication gateway –Conversion between IEC-104 and.

DIP Switches and RS2 pinout• DIP switches control the operation of RS2

• RS2 pinout (standard male DB-9)

• RS2 operation in RS-232 mode (standard DTE) and in RS-422/485 mode

RS-485 termination0=off, 1=onTERMINATION4

RS-485 biasing0=off, 1=onBIAS3

Selects between full-duplex (4-wire) and half-duplex (2-wire) RS-485 operation

0=full, 1=halfFULL/HALF2

Selects RS-port operation0=RS-232, 1=RS-485RS-232/RS-4851

ExplanationStateFunctionNumber

RS-485 termination0=off, 1=onTERMINATION4

RS-485 biasing0=off, 1=onBIAS3

Selects between full-duplex (4-wire) and half-duplex (2-wire) RS-485 operation

0=full, 1=halfFULL/HALF2

Selects RS-port operation0=RS-232, 1=RS-485RS-232/RS-4851

ExplanationStateFunctionNumber

Pin RS-485 FD (4-wire) RS-485 HD (2-wire)12 RXD+ (in)3 TXD- (out) TXD/RXD- (out/in)45 GND GND67 TXD+ (out) TXD/RDX+ (out/in)8 RXD- (in)9

Page 6: Arctic IEC-104 Gateway Jari Lahti, CTO. Arctic IEC-104 Gateway IEC 60870-5-104 to IEC 60870-5-101 communication gateway –Conversion between IEC-104 and.

IEC-101 Serial settings

• Serial speed– 1200

– 2400

– 4800

– 9600

– 19200

– 38400

– 57600

•Data bits–5,6,7,8

•Parity–None, Even, Odd

•HW (CTS/RTS) Flow control–Yes/No

Page 7: Arctic IEC-104 Gateway Jari Lahti, CTO. Arctic IEC-104 Gateway IEC 60870-5-104 to IEC 60870-5-101 communication gateway –Conversion between IEC-104 and.

Network settings

• Network protocol– TCP (standard IEC-104)– UDP

• Network port to listen– The TCP or UDP port the Arctic IEC-104 Gateway listens for

incoming IEC-104 connections– 2404 is the standard port

• Network idle timeout– If there is no communication on open connection during defined

interval the Arctic IEC-104 Gateway closes the connection• New connection priority

– Defines are new connections accepted if there is a connection already

– Setting Yes enables new connection to have higher priority and the existing connection is closed

Page 8: Arctic IEC-104 Gateway Jari Lahti, CTO. Arctic IEC-104 Gateway IEC 60870-5-104 to IEC 60870-5-101 communication gateway –Conversion between IEC-104 and.

IEC-104 Settings• TX window size (k)

– how many IEC-104 packets Arctic sends to IEC-104 master before waiting acknowledgement

• RX window size (w)– how many IEC-104 packets Arctic receives from IEC-104 master

before sending acknowledgement• I frames TX timeout (t1)

– how many seconds to wait acknowledgement from IEC-104 master

• I frames RX timeout (t2)– how many seconds to wait from last received IEC-104 packet

before sending acknowledgement• Link test interval (t3)

– interval for sending IEC-104 link test packets• Suspended timeout

– if the IEC-104 link is on suspendet state over defined timeout Arctic will close the link

• Max sequence number– defines the maximum sequence number used on IEC-104

communication• Cause of transmission length

– size of IEC-104 Cause of transmission field length in bytes• Common address length

– size of IEC-104 Common address field length in bytes• Info object address length

– size of IEC-104 Information object address field length in bytes

• NOTE• (w) must be smaller than (k) (2/3 of k) • (t1) must be longer than (t2)• w, k, t1 and t2 should be same on both ends

(SCADA, Arctic) of IEC-104 connection

• (t3) should be smaller on Arctic than on SCADA

Page 9: Arctic IEC-104 Gateway Jari Lahti, CTO. Arctic IEC-104 Gateway IEC 60870-5-104 to IEC 60870-5-101 communication gateway –Conversion between IEC-104 and.

Local polling of events• The Arctic IEC-104 gateway polls locally the IEC-101

device for Class 1 and Class 2 events– events are sent when they occur

– no need to perform fast polling over GPRS

– slow periodic link test frames can be used

Local IEC-101 polls

Send when events

Page 10: Arctic IEC-104 Gateway Jari Lahti, CTO. Arctic IEC-104 Gateway IEC 60870-5-104 to IEC 60870-5-101 communication gateway –Conversion between IEC-104 and.

IEC-101 Settings• Slave link address

– the link address of IEC-101 slave• Link address field length

– the size of IEC-101 link address field in bytes– 1 or 2

• Event poll interval– the interval of polling Class 1 or Class 2 events from IEC-

101 slave in multiple of 100 ms• Link test interval

– the interval of testing IEC-101 link status in multiple of 100 ms

• Keep link open– defines is the IEC-101 link kept open by Arctic even when

there is no active IEC-104 connection– the events are still not polled untill the IEC-104 connection is

active• Reply header timeout

– timeout of waiting reply to start from IEC-101 slave• Reply end timeout

– timeout of waiting reply to end from IEC-101 slave• Retry limit

– how many times to retry a command to IEC-101 slave• Cause of transmission length

– size of IEC-101 Cause of transmission field length in bytes• Common address length

– size of IEC-101 Common address field length in bytes• Info object address length

– size of IEC-101 Information object address field length in bytes

Page 11: Arctic IEC-104 Gateway Jari Lahti, CTO. Arctic IEC-104 Gateway IEC 60870-5-104 to IEC 60870-5-101 communication gateway –Conversion between IEC-104 and.

ASDU Conversion• The Arctic IEC-104 Gateway supports ASDU level

header length conversion– Cause of transmission length

– Common address length

– Information object address length

• This is usually required because the header lengths typically differs between IEC-101 and IEC-104

• It is possible to convert also ASDU types if the implementation differs between IEC-104 master and slave

Page 12: Arctic IEC-104 Gateway Jari Lahti, CTO. Arctic IEC-104 Gateway IEC 60870-5-104 to IEC 60870-5-101 communication gateway –Conversion between IEC-104 and.

ASDU Converter settings• Use ASDU converter

– set Yes to allow conversion between IEC-101 and IEC-104 header field lengths

• Use ASDU type replacer– set Yes to allow conversion between ASDU

Original type and Applied type• Original type

– original ASDU type to be searched if ASDU type replacer is enabled

• Applied type– the ASDU defines is the type used to replace

the original type if ASDU type replacer is enabled

Page 13: Arctic IEC-104 Gateway Jari Lahti, CTO. Arctic IEC-104 Gateway IEC 60870-5-104 to IEC 60870-5-101 communication gateway –Conversion between IEC-104 and.

Packet collector• The packet collector can be used to "collect" multiple

IEC-104 packets to Arctic before sending them to IEC-104 master

• This decreases the amount of used GPRS data because data is sent in single packet rather than in multiple packets– single TCP/IP header instead of multiple headers

Page 14: Arctic IEC-104 Gateway Jari Lahti, CTO. Arctic IEC-104 Gateway IEC 60870-5-104 to IEC 60870-5-101 communication gateway –Conversion between IEC-104 and.

Packet collector settings• Use packet collector

– set yes to allow packet collector operation

• Max bytes– Maximum bytes to collect

before sending the packet

• Max time– Maximum time to collect before

sending the packet

• Max packets– Maximum number of IEC-104

frames to collect before sending the packet

• NOTE• If any of the triggers (Max bytes, Max

time, Max packets) is reached the packet is sent

Page 15: Arctic IEC-104 Gateway Jari Lahti, CTO. Arctic IEC-104 Gateway IEC 60870-5-104 to IEC 60870-5-101 communication gateway –Conversion between IEC-104 and.

IO Extension• It is possible to equip Arctic IEC-104 Gateway with I/O

extension board– 8 DI– 2 DO

• These I/O pins can be used as an extension of IEC-101 slave address space– single IEC-104 connection is required to control the IEC-101

slave and Arctic IO extension

• Arctic sends the I/O status as spontaneous events in case of General interrogation

• All IO extension information is Single-point information without time tag

• It is possible to send the Input status periodically as spontaneous events

• The output pins can be controlled with Single command• I/O extension board is a manufacturing option

Page 16: Arctic IEC-104 Gateway Jari Lahti, CTO. Arctic IEC-104 Gateway IEC 60870-5-104 to IEC 60870-5-101 communication gateway –Conversion between IEC-104 and.

IO PinoutPIN SYMBOL DESCRIPTION

1 V+ Vcc out, 50 mA

2 DI_1 Digital input, 0...60V

3 DI_2 Digital input, 0...60V

4 DI_3 Digital input, 0...60V

5 DI_4 Digital input, 0...60V

6 DI_5 Digital input, 0...60V

7 DI_6 Digital input, 0...60V

8 DI_7 Digital input, 0...60V

9 DI_8 Digital input, 0...60V

10 DI_COM Digital inputs referense input

11 DO_1A Digital output pole 1, 0...60V, 50 mA

12 DO_1B Digital output pole 2

13 DO_2A Digital output pole 2, 0...60V, 50 mA

14 DO_2B Digital output pole 2

15 GND GND output

Front View

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

Input circuit

Output circuit

• NOTE• Input voltages below 2 V are detected as

logic "0"• Input voltages between 5-60 V are detected

as logic "1"

Page 17: Arctic IEC-104 Gateway Jari Lahti, CTO. Arctic IEC-104 Gateway IEC 60870-5-104 to IEC 60870-5-101 communication gateway –Conversion between IEC-104 and.

IO Extension settings• Use IO extension board

– set Yes to enable IO extension• Common address

– the IEC-104 common address of IO extension board • Number of inputs

– number of digital inputs used– 0-8

• Inputs start address– The information object address of first digital input on IO

extension board • Number of outputs

– number of digital outputs used– 0-2

• Outputs start address– The information object address of first digital output on IO

extension board • Reply end timeout

– timeout of waiting reply to end from IEC-101 slave• Output short pulse duration

– Defines the duration in 0.1 secs of output short pulse. • Output long pulse duration

– Defines the duration in 0.1 secs of output long pulse • Paired outputs

– Defines are the outputs controlled individually or are they controlled as paired outputs.

• Forced output function– Defines the forced operation of outputs

executed regardless the actual command data.

• Send input status cyclic– Defines are the input pin status information

sent cyclically when the IEC-104 connection is active

• Cyclic interval– Defines the time interval in 0.1 secs of

sending input status cyclical message – Inputs status are sent as spontaneous

events• Send input state change event

– Defines does the state change of input cause sending of spontaneous event.

Page 18: Arctic IEC-104 Gateway Jari Lahti, CTO. Arctic IEC-104 Gateway IEC 60870-5-104 to IEC 60870-5-101 communication gateway –Conversion between IEC-104 and.

Serial port RS1 • The serial port RS1 can be used in two modes

– Console mode - access Arctic command line with serial console

– Data mode - transfer plain RS-232 data over network

• The RS1 mode is controlled by Console Switch on Arctic front panel– Switch position in Console mode

– Switch position in Data mode

• When operating the console switch always turn Arctic OFF

Page 19: Arctic IEC-104 Gateway Jari Lahti, CTO. Arctic IEC-104 Gateway IEC 60870-5-104 to IEC 60870-5-101 communication gateway –Conversion between IEC-104 and.

RS 1 Serial Gateway

Page 20: Arctic IEC-104 Gateway Jari Lahti, CTO. Arctic IEC-104 Gateway IEC 60870-5-104 to IEC 60870-5-101 communication gateway –Conversion between IEC-104 and.