F UH-2 6"Ø EF-3 UH-3 UH-4 250 9x9 S-1 50 6x6 S-1 400 12x12 S-1 200 9x9 S-1 250 9x9 S-1 UH-1 250 9x9 S-1 600 15x15 E-1 600 15x15 E-1 525 15x15 E-1 525 15x15 E-1 525 15x15 E-1 8x8 R-1 10x10 R-1 T T T L-1 AHU-1 6"Ø EF-4 14"Ø 14"Ø 10"Ø 10"Ø 6"Ø 6"Ø 16x16" SA 9"Ø 14x16 12"Ø 10"Ø 10"Ø 10"Ø 12x14" RA 12x12 R-1 9"Ø 12"Ø 525 15x15 E-1 14x14 16x20 14x18 14x14 12"Ø 12"Ø 12"Ø 12"Ø 12"Ø 12"Ø 12"Ø 26x20 12x16" RA 16x18" SA (ABOVE) (BELOW) (BELOW) (ABOVE) 12"Ø EF-1 EF-2 L-2 OHP-1 1 4 5 5 6 3 3 9"Ø 7 7 12"Ø 12"Ø 12"Ø 10x20 16x20 14"Ø Approved As Is Approved As Noted Resubmit As Noted Signature: Print: Date: Hellas Construction, Inc. 12720 Research Boulevard Suite 240 Austin, TX 78759 (P) (512) 250-2910 (F) (512) 250-1960 www.hellasconstruction.com OWNER: City of Portland 1900 Billy G. Webb Drive Portland, TX 78374 PROJECT: CITY OF PORTLAND SPORTS COMPLEX & 13-ACRE/MUNICIPAL PARK IMPROVEMENTS PROJECT LOCATION: PORTLAND, TEXAS DATE: REVISION: 1 SHEET NUMBER: SHEET TITLE: All drawings and written material appearing herein constitute original unpublished work, and may not be duplicated, used or disclosed without the written consent of Hellas Construction, Inc. Rhodes Architecture, Inc. 600 S. Tyler Suite 1501 Amarillo, Texas 79101 (P) (806) 468- 7641 www.raoffice.com COMMENTS: (P) (361) 777-4500 (F) (361) 777-4501 FEBRUARY 23, 2017 This document is released for the purpose of interim review under the authority of Kris Stepp, P.E. 93736 on Feb. 20, 2017. It is not to be used for construction, bidding, or permit purposes. WWW.FINCHERENG.COM FINCHER ENGINEERING, LLC FINCHER ENGINEERING, LLC TX FIRM #F-16408 12402 SLIDE ROAD, SUITE 403 LUBBOCK, TX 79424 PH: 806-701-5109 Architecture Rhodes INC. MUNICIPAL PARK CONCESSION MECHANICAL M1.01 M1.01.01 MUNICIPAL PARK CONCESSION FLOOR PLAN - MECHANICAL SCALE 1/4" = 1'-0" GENERAL NOTES KEYED NOTES 1. 4" THICK CONCRETE EQUIPMENT PAD. WITH 12" TURN DOWN AT ALL SIDES. PROVIDE WITH #3 REBAR @ 16" O.C. 2. INSTALL E.A. DUCT AND EXHAUST FANS SUCH THAT THE RECTANGULAR DUCT MAINS ARE INSTALLED BETWEEN TWO ROOF TRUSSES WITH ROUND RUNOUTS THROUGH TRUSSES AS SHOWN. VERIFY EXACT LOCATION AND DUCT ROUTING WITH TRUSSES AT JOBSITE PRIOR TO DUCT FABRICATION. 3. STACK S.A. AND R.A. DUCTS SUCH THAT THE RECTANGULAR DUCT MAINS ARE INSTALLED BETWEEN TWO ROOF TRUSSES WITH ROUND RUNOUTS THROUGH TRUSSES AS SHOWN. VERIFY EXACT LOCATION AND DUCT ROUTING WITH TRUSSES AT JOBSITE PRIOR TO DUCT FABRICATION. 4. 14" Ø O.A. DUCT FROM R.A. DUCT TO O.A. LOUVER. STUB INTO SIDE OF R.A. DUCT WITH MOTORIZED DAMPER AND MANUAL BALANCING DAMPER. 5. 6"Ø EXHAUST AIR DUCT UP THRU ROOF TO ROOF CAP. 6. ORIENT OUTDOOR HEAT PUMP UNIT SUCH THAT DISCHARGE OF CONDENSER FAN IS DIRECTED TOWARDS THE CHAIN LINK PORTION AND NOT TOWARDS SOLID MASONRY WALL. A. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN FOR LOCATION OF ALL CEILING MOUNTED AIR DISTRIBUTION DEVICES. B. LOCATE ALL THERMOSTATS A MINIMUM OF SIX INCHES FROM WALL CORNERS, DOOR FRAMES AND OTHER DEVICES. MOUNT THERMOSTATS AT 48" A.F.F. COORDINATE THE LOCATION OF ALL THERMOSTATS WITH ARCHITECT PRIOR TO INSTALLATION. PROVIDE LOCKING PLEXIGLASS COVER OVER ALL THERMOSTATS AND SENSORS. C. MECHANICAL CONTRACTOR TO PROVIDE AND INSTALL ALL THERMOSTATS AND INSTALL ALL THERMOSTAT WIRING. ELECTRICIAN TO PROVIDE BACK BOX WITH CONDUIT UP TO ACCESSIBLE CEILING AT ALL THERMOSTAT/SENSOR LOCATIONS. D. WHEREVER THE MANUAL BALANCING DAMPERS ARE RENDERED INACCESSIBLE BEHIND NON-REMOVABLE CEILINGS OR FURRINGS, OR OTHER CONSTRUCTION THAT IS NOT EASILY REMOVABLE TO PERMIT ACCESS TO THE DAMPERS, THE DAMPERS SHALL BE EQUAL TO YOUNG REGULATOR NO. 1200 RIGHT ANGLE WORM GEAR REGULATOR, FLEX SHAFT, AND 301-FS CONCEALED DAMPER REGULATOR WITH PRIMER COVER PLATE FOR FIELD PAINTING TO MATCH CEILING. N
5

Architecture - Barcombarcom.cc/wp-content/uploads/2017/03/City-of... · concession mechanical m1.01 m1.01.01 municipal park concession floor plan - mechanical scale 1/4" = 1'-0" general

Aug 21, 2020

Download

Documents

dariahiddleston
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Architecture - Barcombarcom.cc/wp-content/uploads/2017/03/City-of... · concession mechanical m1.01 m1.01.01 municipal park concession floor plan - mechanical scale 1/4" = 1'-0" general

F

UH-2

6"Ø

EF-3

UH-3

UH-4

250

9x9

S-1

50

6x6

S-1

400

12x12

S-1

200

9x9

S-1

250

9x9

S-1

UH-1

250

9x9

S-1

600

15x15

E-1

600

15x15

E-1

525

15x15

E-1

525

15x15

E-1

525

15x15

E-1

8x8

R-1

10x10

R-1

TT

T

L-1

AHU-1

6"Ø

EF-4

14"Ø

14"Ø 10"Ø

10"Ø

6"Ø

6"Ø

16x16" S

A

9"Ø

14x16

12"Ø

10"Ø

10"Ø

10"Ø

12x14" R

A

12x12

R-1

9"Ø

12"Ø

525

15x15

E-1

14x14

16x20

14x18

14x14

12"Ø

12"Ø

12"Ø

12"Ø

12"Ø

12"Ø

12"Ø

26x20

12x16" R

A

16x18" S

A

(A

BO

VE

)

(B

ELO

W)

(B

ELO

W)

(A

BO

VE

)

12"Ø

EF-1

EF-2

L-2

OHP-1

1

4

5

5

6

3

3

9"Ø

7

7

12"Ø

12"Ø

12"Ø

10x20

16x20

14"Ø

Approved As Is

Approved As Noted

Resubmit As Noted

Signature:

Print:

Date:

Hellas Construction, Inc.

12720 Research Boulevard

Suite 240 Austin, TX 78759

(P) (512) 250-2910

(F) (512) 250-1960

www.hellasconstruction.com

OWNER:

City of Portland

1900 Billy G. Webb Drive

Portland, TX 78374

PROJECT:

CITY OF PORTLAND SPORTS

COMPLEX & 13-ACRE/MUNICIPAL

PARK IMPROVEMENTS

PROJECT LOCATION:

PORTLAND, TEXAS

DATE:

REVISION:

1

SHEET NUMBER:

SHEET TITLE:

All drawings and written material appearing herein

constitute original unpublished work, and may not be

duplicated, used or disclosed without the written consent

of Hellas Construction, Inc.

Rhodes Architecture, Inc.

600 S. Tyler Suite 1501

Amarillo, Texas 79101

(P) (806) 468- 7641

www.raoffice.com

COMMENTS:

(P) (361) 777-4500

(F) (361) 777-4501

FEBRUARY 23, 2017

This document is released

for the purpose of interim

review under the authority

of Kris Stepp, P.E. 93736

on Feb. 20, 2017. It is not

to be used for construction,

bidding, or permit purposes.

WWW.FINCHERENG.COM

FINCHER

ENGINEERING, LLC

FINCHER ENGINEERING, LLC

TX FIRM #F-16408

12402 SLIDE ROAD, SUITE 403

LUBBOCK, TX 79424

PH: 806-701-5109

Architecture

Rhodes

INC.

MUNICIPAL PARK

CONCESSION

MECHANICAL

M1.01

M1.01.01

MUNICIPAL PARK CONCESSION FLOOR PLAN - MECHANICAL

SCALE 1/4" = 1'-0"

GENERAL NOTES

KEYED NOTES

1. 4" THICK CONCRETE EQUIPMENT PAD. WITH 12" TURN DOWN AT ALL SIDES. PROVIDE

WITH #3 REBAR @ 16" O.C.

2. INSTALL E.A. DUCT AND EXHAUST FANS SUCH THAT THE RECTANGULAR DUCT MAINS

ARE INSTALLED BETWEEN TWO ROOF TRUSSES WITH ROUND RUNOUTS THROUGH

TRUSSES AS SHOWN. VERIFY EXACT LOCATION AND DUCT ROUTING WITH TRUSSES AT

JOBSITE PRIOR TO DUCT FABRICATION.

3. STACK S.A. AND R.A. DUCTS SUCH THAT THE RECTANGULAR DUCT MAINS ARE

INSTALLED BETWEEN TWO ROOF TRUSSES WITH ROUND RUNOUTS THROUGH TRUSSES

AS SHOWN. VERIFY EXACT LOCATION AND DUCT ROUTING WITH TRUSSES AT JOBSITE

PRIOR TO DUCT FABRICATION.

4. 14" Ø O.A. DUCT FROM R.A. DUCT TO O.A. LOUVER. STUB INTO SIDE OF R.A. DUCT WITH

MOTORIZED DAMPER AND MANUAL BALANCING DAMPER.

5. 6"Ø EXHAUST AIR DUCT UP THRU ROOF TO ROOF CAP.

6. ORIENT OUTDOOR HEAT PUMP UNIT SUCH THAT DISCHARGE OF CONDENSER FAN IS

DIRECTED TOWARDS THE CHAIN LINK PORTION AND NOT TOWARDS SOLID MASONRY

WALL.

A. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN FOR LOCATION OF ALL CEILING

MOUNTED AIR DISTRIBUTION DEVICES.

B. LOCATE ALL THERMOSTATS A MINIMUM OF SIX INCHES FROM WALL CORNERS, DOOR

FRAMES AND OTHER DEVICES. MOUNT THERMOSTATS AT 48" A.F.F. COORDINATE THE

LOCATION OF ALL THERMOSTATS WITH ARCHITECT PRIOR TO INSTALLATION. PROVIDE

LOCKING PLEXIGLASS COVER OVER ALL THERMOSTATS AND SENSORS.

C. MECHANICAL CONTRACTOR TO PROVIDE AND INSTALL ALL THERMOSTATS AND INSTALL

ALL THERMOSTAT WIRING. ELECTRICIAN TO PROVIDE BACK BOX WITH CONDUIT UP TO

ACCESSIBLE CEILING AT ALL THERMOSTAT/SENSOR LOCATIONS.

D. WHEREVER THE MANUAL BALANCING DAMPERS ARE RENDERED INACCESSIBLE BEHIND

NON-REMOVABLE CEILINGS OR FURRINGS, OR OTHER CONSTRUCTION THAT IS NOT

EASILY REMOVABLE TO PERMIT ACCESS TO THE DAMPERS, THE DAMPERS SHALL BE

EQUAL TO YOUNG REGULATOR NO. 1200 RIGHT ANGLE WORM GEAR REGULATOR, FLEX

SHAFT, AND 301-FS CONCEALED DAMPER REGULATOR WITH PRIMER COVER PLATE FOR

FIELD PAINTING TO MATCH CEILING.

N

AutoCAD SHX Text
WOMENS RESTROOM
AutoCAD SHX Text
MENS RESTROOM
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
FAMILY
AutoCAD SHX Text
MECH/UTILITY
AutoCAD SHX Text
CONCESSION STAND
AutoCAD SHX Text
CITY STORAGE
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text
101
AutoCAD SHX Text
102
AutoCAD SHX Text
103
AutoCAD SHX Text
104
AutoCAD SHX Text
105
AutoCAD SHX Text
106
AutoCAD SHX Text
107
AutoCAD SHX Text
108
Page 2: Architecture - Barcombarcom.cc/wp-content/uploads/2017/03/City-of... · concession mechanical m1.01 m1.01.01 municipal park concession floor plan - mechanical scale 1/4" = 1'-0" general

AHU-1

OHP-1

1

2

2

2

3

4

1" D

S

L

Approved As Is

Approved As Noted

Resubmit As Noted

Signature:

Print:

Date:

Hellas Construction, Inc.

12720 Research Boulevard

Suite 240 Austin, TX 78759

(P) (512) 250-2910

(F) (512) 250-1960

www.hellasconstruction.com

OWNER:

City of Portland

1900 Billy G. Webb Drive

Portland, TX 78374

PROJECT:

CITY OF PORTLAND SPORTS

COMPLEX & 13-ACRE/MUNICIPAL

PARK IMPROVEMENTS

PROJECT LOCATION:

PORTLAND, TEXAS

DATE:

REVISION:

1

SHEET NUMBER:

SHEET TITLE:

All drawings and written material appearing herein

constitute original unpublished work, and may not be

duplicated, used or disclosed without the written consent

of Hellas Construction, Inc.

Rhodes Architecture, Inc.

600 S. Tyler Suite 1501

Amarillo, Texas 79101

(P) (806) 468- 7641

www.raoffice.com

COMMENTS:

(P) (361) 777-4500

(F) (361) 777-4501

FEBRUARY 23, 2017

This document is released

for the purpose of interim

review under the authority

of Kris Stepp, P.E. 93736

on Feb. 20, 2017. It is not

to be used for construction,

bidding, or permit purposes.

WWW.FINCHERENG.COM

FINCHER

ENGINEERING, LLC

FINCHER ENGINEERING, LLC

TX FIRM #F-16408

12402 SLIDE ROAD, SUITE 403

LUBBOCK, TX 79424

PH: 806-701-5109

Architecture

Rhodes

INC.

MUNICIPAL PARK

CONCESSION

MECHANICAL PIPING

M1.02

N

M1.02.01

MUNICIPAL PARK CONCESSION FLOOR PLAN - MECHANICAL PIPING

SCALE 1/4" = 1'-0"

GENERAL NOTES

A. PROVIDE P-TRAP ON ALL DRAIN LINES FROM EACH COOLING COIL; REFER TO DETAIL.

B. REFER TO CONDENSING UNIT SCHEDULE FOR REFRIGERANT LINE SIZES. SUSPEND

LINES FROM STRUCTURE AS DETAILED.

C. REFRIGERANT PIPING IS SHOWN FOR DIAGRAMMATIC PURPOSES ONLY. CONTRACTOR

SHALL COORDINATE EXACT ROUTING OF PIPING AT JOBSITE. PROVIDE ALL REQUIRED

OFFSETS AND ELBOWS AS REQUIRED FOR A COMPLETE OPERATIONAL SYSTEM.

KEYED NOTES

1. 4" THICK CONCRETE EQUIPMENT PAD. WITH 12" TURN DOWN AT ALL SIDES. PROVIDE

WITH #3 REBAR @ 16" O.C.

2. 8" PVC PIPE SLEEVE FOR UNDERGROUND REFRIGERANT PIPING. PROVIDE WITH LONG,

SWEEP RADIUS ELBOWS.

3. TURN REFRIGERANT LINES UP FROM 8" UNDERGROUND PIPE SLEEVE TO CONNECT TO

COOLING COIL. TURN 8" SLEEVE UP TO 180° ELL AND CAP AND SEAL PIPE

PENETRATIONS WATER TIGHT.

4. TURN 1" CONDENSATE DRAIN LINE DOWN FROM FURNACE AND COIL UNIT. PROVIDE

P-TRAP AT COOLING COIL CONNECTION, REFER TO DETAIL. EXTEND DRAIN LINE TO

FLOOR AND EXTEND ALONG FLOOR TO SPILL TO FLOOR DRAIN WITH 1" AIR GAP.

SECURE DRAIN LINE WITH UNISTRUT AND PIPE CLAMPS.

AutoCAD SHX Text
WOMENS RESTROOM
AutoCAD SHX Text
MENS RESTROOM
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
FAMILY
AutoCAD SHX Text
MECH/UTILITY
AutoCAD SHX Text
CONCESSION STAND
AutoCAD SHX Text
CITY STORAGE
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text
101
AutoCAD SHX Text
102
AutoCAD SHX Text
103
AutoCAD SHX Text
104
AutoCAD SHX Text
105
AutoCAD SHX Text
106
AutoCAD SHX Text
107
AutoCAD SHX Text
108
Page 3: Architecture - Barcombarcom.cc/wp-content/uploads/2017/03/City-of... · concession mechanical m1.01 m1.01.01 municipal park concession floor plan - mechanical scale 1/4" = 1'-0" general

F

UH-6

6"Ø

EF-8

UH-7

UH-8

250

9x9

S-1

50

6x6

S-1

200

9x9

S-1

250

9x9

S-1

UH-5

250

9x9

S-1

600

15x15

E-1

600

15x15

E-1

525

15x15

E-1

525

15x15

E-1

525

15x15

E-1

8x8

R-1

10x10

R-1

TT

T

L-3

AHU-2

6"Ø

EF-7

14"Ø

14"Ø

10"Ø

10"Ø

6"Ø

6"Ø

16x16" S

A

9"Ø

14x16

9"Ø

10"Ø

10"Ø

10"Ø

12x14" R

A

8x8

R-1

26x20

14x14

16x20

14"Ø

14x18

14x14

12"Ø

12"Ø

12"Ø

12"Ø

12x16" R

A16x18" S

A

(B

EL

OW

)(A

BO

VE

)

200

9x9

S-1

200

9x9

S-1

8x8

R-1

10x12" R

A

9"Ø

9"Ø

9"Ø

(A

BO

VE

)(B

ELO

W)

(B

EL

OW

)

14"Ø

EF-6

EF-5

L-4

OHP-2

1

5

5

6

14"Ø

14"Ø

14"Ø

14"Ø

14"Ø

525

15x15

E-1

9"Ø

9"Ø

14"Ø

4

3

3

Approved As Is

Approved As Noted

Resubmit As Noted

Signature:

Print:

Date:

Hellas Construction, Inc.

12720 Research Boulevard

Suite 240 Austin, TX 78759

(P) (512) 250-2910

(F) (512) 250-1960

www.hellasconstruction.com

OWNER:

City of Portland

1900 Billy G. Webb Drive

Portland, TX 78374

PROJECT:

CITY OF PORTLAND SPORTS

COMPLEX & 13-ACRE/MUNICIPAL

PARK IMPROVEMENTS

PROJECT LOCATION:

PORTLAND, TEXAS

DATE:

REVISION:

1

SHEET NUMBER:

SHEET TITLE:

All drawings and written material appearing herein

constitute original unpublished work, and may not be

duplicated, used or disclosed without the written consent

of Hellas Construction, Inc.

Rhodes Architecture, Inc.

600 S. Tyler Suite 1501

Amarillo, Texas 79101

(P) (806) 468- 7641

www.raoffice.com

COMMENTS:

(P) (361) 777-4500

(F) (361) 777-4501

FEBRUARY 23, 2017

This document is released

for the purpose of interim

review under the authority

of Kris Stepp, P.E. 93736

on Feb. 20, 2017. It is not

to be used for construction,

bidding, or permit purposes.

WWW.FINCHERENG.COM

FINCHER

ENGINEERING, LLC

FINCHER ENGINEERING, LLC

TX FIRM #F-16408

12402 SLIDE ROAD, SUITE 403

LUBBOCK, TX 79424

PH: 806-701-5109

Architecture

Rhodes

INC.

SPORTS COMPLEX

CONCESSION

MECHANICAL

M2.01

N

M2.01.01

SPORTS COMPLEX CONCESSION FLOOR PLAN - MECHANICAL

SCALE 1/4" = 1'-0"

GENERAL NOTES

KEYED NOTES

1. 4" THICK CONCRETE EQUIPMENT PAD. WITH 12" TURN DOWN AT ALL SIDES. PROVIDE

WITH #3 REBAR @ 16" O.C.

2. INSTALL E.A. DUCT AND EXHAUST FANS SUCH THAT THE RECTANGULAR DUCT MAINS

ARE INSTALLED BETWEEN TWO ROOF TRUSSES WITH ROUND RUNOUTS THROUGH

TRUSSES AS SHOWN. VERIFY EXACT LOCATION AND DUCT ROUTING WITH TRUSSES AT

JOBSITE PRIOR TO DUCT FABRICATION.

3. STACK S.A. AND R.A. DUCTS SUCH THAT THE RECTANGULAR DUCT MAINS ARE

INSTALLED BETWEEN TWO ROOF TRUSSES WITH ROUND RUNOUTS THROUGH TRUSSES

AS SHOWN. VERIFY EXACT LOCATION AND DUCT ROUTING WITH TRUSSES AT JOBSITE

PRIOR TO DUCT FABRICATION.

4. 14" Ø O.A. DUCT FROM R.A. DUCT TO O.A. LOUVER. STUB INTO SIDE OF R.A. DUCT WITH

MOTORIZED DAMPER AND MANUAL BALANCING DAMPER.

5. 6"Ø EXHAUST AIR DUCT UP THRU ROOF TO ROOF CAP.

6. ORIENT OUTDOOR HEAT PUMP UNIT SUCH THAT DISCHARGE OF CONDENSER FAN IS

DIRECTED TOWARDS THE CHAIN LINK PORTION AND NOT TOWARDS SOLID MASONRY

WALL.

A. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN FOR LOCATION OF ALL CEILING

MOUNTED AIR DISTRIBUTION DEVICES.

B. LOCATE ALL THERMOSTATS A MINIMUM OF SIX INCHES FROM WALL CORNERS, DOOR

FRAMES AND OTHER DEVICES. MOUNT THERMOSTATS AT 48" A.F.F. COORDINATE THE

LOCATION OF ALL THERMOSTATS WITH ARCHITECT PRIOR TO INSTALLATION. PROVIDE

LOCKING PLEXIGLASS COVER OVER ALL THERMOSTATS AND SENSORS.

C. MECHANICAL CONTRACTOR TO PROVIDE AND INSTALL ALL THERMOSTATS AND INSTALL

ALL THERMOSTAT WIRING. ELECTRICIAN TO PROVIDE BACK BOX WITH CONDUIT UP TO

ACCESSIBLE CEILING AT ALL THERMOSTAT/SENSOR LOCATIONS.

D. WHEREVER THE MANUAL BALANCING DAMPERS ARE RENDERED INACCESSIBLE BEHIND

NON-REMOVABLE CEILINGS OR FURRINGS, OR OTHER CONSTRUCTION THAT IS NOT

EASILY REMOVABLE TO PERMIT ACCESS TO THE DAMPERS, THE DAMPERS SHALL BE

EQUAL TO YOUNG REGULATOR NO. 1200 RIGHT ANGLE WORM GEAR REGULATOR, FLEX

SHAFT, AND 301-FS CONCEALED DAMPER REGULATOR WITH PRIMER COVER PLATE FOR

FIELD PAINTING TO MATCH CEILING.

AutoCAD SHX Text
WOMENS RESTROOM
AutoCAD SHX Text
MENS RESTROOM
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
FAMILY
AutoCAD SHX Text
MECH/UTILITY
AutoCAD SHX Text
CONCESSION STAND
AutoCAD SHX Text
CITY STG.
AutoCAD SHX Text
FOOTBALL
AutoCAD SHX Text
SOFTBALL
AutoCAD SHX Text
101
AutoCAD SHX Text
102
AutoCAD SHX Text
103
AutoCAD SHX Text
104
AutoCAD SHX Text
105
AutoCAD SHX Text
106
AutoCAD SHX Text
107
AutoCAD SHX Text
108
AutoCAD SHX Text
109
AutoCAD SHX Text
STG.
AutoCAD SHX Text
STG.
Page 4: Architecture - Barcombarcom.cc/wp-content/uploads/2017/03/City-of... · concession mechanical m1.01 m1.01.01 municipal park concession floor plan - mechanical scale 1/4" = 1'-0" general

AHU-2

L

L

OHP-2

1" D

1

2

3

4

S

S

2

2

Approved As Is

Approved As Noted

Resubmit As Noted

Signature:

Print:

Date:

Hellas Construction, Inc.

12720 Research Boulevard

Suite 240 Austin, TX 78759

(P) (512) 250-2910

(F) (512) 250-1960

www.hellasconstruction.com

OWNER:

City of Portland

1900 Billy G. Webb Drive

Portland, TX 78374

PROJECT:

CITY OF PORTLAND SPORTS

COMPLEX & 13-ACRE/MUNICIPAL

PARK IMPROVEMENTS

PROJECT LOCATION:

PORTLAND, TEXAS

DATE:

REVISION:

1

SHEET NUMBER:

SHEET TITLE:

All drawings and written material appearing herein

constitute original unpublished work, and may not be

duplicated, used or disclosed without the written consent

of Hellas Construction, Inc.

Rhodes Architecture, Inc.

600 S. Tyler Suite 1501

Amarillo, Texas 79101

(P) (806) 468- 7641

www.raoffice.com

COMMENTS:

(P) (361) 777-4500

(F) (361) 777-4501

FEBRUARY 23, 2017

This document is released

for the purpose of interim

review under the authority

of Kris Stepp, P.E. 93736

on Feb. 20, 2017. It is not

to be used for construction,

bidding, or permit purposes.

WWW.FINCHERENG.COM

FINCHER

ENGINEERING, LLC

FINCHER ENGINEERING, LLC

TX FIRM #F-16408

12402 SLIDE ROAD, SUITE 403

LUBBOCK, TX 79424

PH: 806-701-5109

Architecture

Rhodes

INC.

SPORTS COMPLEX

CONCESSION

MECHANICAL PIPING

M2.02

N

M2.02.01

SPORTS COMPLEX CONCESSION FLOOR PLAN - MECHANICAL PIPING

SCALE 1/4" = 1'-0"

GENERAL NOTES

A. PROVIDE P-TRAP ON ALL DRAIN LINES FROM EACH COOLING COIL; REFER TO DETAIL.

B. REFER TO CONDENSING UNIT SCHEDULE FOR REFRIGERANT LINE SIZES. SUSPEND

LINES FROM STRUCTURE AS DETAILED.

C. REFRIGERANT PIPING IS SHOWN FOR DIAGRAMMATIC PURPOSES ONLY. CONTRACTOR

SHALL COORDINATE EXACT ROUTING OF PIPING AT JOBSITE. PROVIDE ALL REQUIRED

OFFSETS AND ELBOWS AS REQUIRED FOR A COMPLETE OPERATIONAL SYSTEM.

KEYED NOTES

1. 4" THICK CONCRETE EQUIPMENT PAD. WITH 12" TURN DOWN AT ALL SIDES. PROVIDE

WITH #3 REBAR @ 16" O.C.

2. 8" PVC PIPE SLEEVE FOR UNDERGROUND REFRIGERANT PIPING. PROVIDE WITH LONG,

SWEEP RADIUS ELBOWS.

3. TURN REFRIGERANT LINES UP FROM 8" UNDERGROUND PIPE SLEEVE TO CONNECT TO

COOLING COIL. TURN 8" SLEEVE UP TO 180° ELL AND CAP AND SEAL PIPE

PENETRATIONS WATER TIGHT.

4. TURN 1" CONDENSATE DRAIN LINE DOWN FROM FURNACE AND COIL UNIT. PROVIDE

P-TRAP AT COOLING COIL CONNECTION, REFER TO DETAIL. EXTEND DRAIN LINE TO

FLOOR AND EXTEND ALONG FLOOR TO SPILL TO FLOOR DRAIN WITH 1" AIR GAP.

SECURE DRAIN LINE WITH UNISTRUT AND PIPE CLAMPS.

AutoCAD SHX Text
WOMENS RESTROOM
AutoCAD SHX Text
MENS RESTROOM
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
FAMILY
AutoCAD SHX Text
MECH/UTILITY
AutoCAD SHX Text
CONCESSION STAND
AutoCAD SHX Text
CITY STG.
AutoCAD SHX Text
FOOTBALL
AutoCAD SHX Text
SOFTBALL
AutoCAD SHX Text
101
AutoCAD SHX Text
102
AutoCAD SHX Text
103
AutoCAD SHX Text
104
AutoCAD SHX Text
105
AutoCAD SHX Text
106
AutoCAD SHX Text
107
AutoCAD SHX Text
108
AutoCAD SHX Text
109
AutoCAD SHX Text
STG.
AutoCAD SHX Text
STG.
Page 5: Architecture - Barcombarcom.cc/wp-content/uploads/2017/03/City-of... · concession mechanical m1.01 m1.01.01 municipal park concession floor plan - mechanical scale 1/4" = 1'-0" general

Approved As Is

Approved As Noted

Resubmit As Noted

Signature:

Print:

Date:

Hellas Construction, Inc.

12720 Research Boulevard

Suite 240 Austin, TX 78759

(P) (512) 250-2910

(F) (512) 250-1960

www.hellasconstruction.com

OWNER:

City of Portland

1900 Billy G. Webb Drive

Portland, TX 78374

PROJECT:

CITY OF PORTLAND SPORTS

COMPLEX & 13-ACRE/MUNICIPAL

PARK IMPROVEMENTS

PROJECT LOCATION:

PORTLAND, TEXAS

DATE:

REVISION:

1

SHEET NUMBER:

SHEET TITLE:

All drawings and written material appearing herein

constitute original unpublished work, and may not be

duplicated, used or disclosed without the written consent

of Hellas Construction, Inc.

Rhodes Architecture, Inc.

600 S. Tyler Suite 1501

Amarillo, Texas 79101

(P) (806) 468- 7641

www.raoffice.com

COMMENTS:

(P) (361) 777-4500

(F) (361) 777-4501

FEBRUARY 23, 2017

This document is released

for the purpose of interim

review under the authority

of Kris Stepp, P.E. 93736

on Feb. 20, 2017. It is not

to be used for construction,

bidding, or permit purposes.

WWW.FINCHERENG.COM

FINCHER

ENGINEERING, LLC

FINCHER ENGINEERING, LLC

TX FIRM #F-16408

12402 SLIDE ROAD, SUITE 403

LUBBOCK, TX 79424

PH: 806-701-5109

Architecture

Rhodes

INC.

CONCESSION

MECHANICAL DETAILS

M3.01

EXHAUST FAN SCHEDULE

MARK CFM SP RPM

MOTOR

SIZE

DRIVE

ELECTRICAL

DATA

TYPE EXAMPLE

EF-1 1200 0.5 843 1/4 HP BELT115 V, 1 Ø, 60 Hz

CABINET GREENHECK BDF-90-4

EF-2 2100 0.5 1088 1 HP BELT115 V, 1 Ø, 60 Hz

CABINET GREENHECK BDF-90-10

EF-3 100 0.3 1224 29.3 W DIRECT115 V, 1 Ø, 60 Hz

CEILING GREENHECK SP-A190

EF-4 100 0.3 1224 29.3 W DIRECT115 V, 1 Ø, 60 Hz

CEILING GREENHECK SP-A190

EF-5 1200 0.5 843 1/4 HP BELT115 V, 1 Ø, 60 Hz

CABINET GREENHECK BDF-90-4

EF-6 2100 0.5 1088 1 HP BELT115 V, 1 Ø, 60 Hz

CABINET GREENHECK BDF-90-10

EF-7 100 0.3 1224 29.3 W DIRECT115 V, 1 Ø, 60 Hz

CEILING GREENHECK SP-A190

EF-8 100 0.3 1224 29.3 W DIRECT115 V, 1 Ø, 60 Hz

CEILING GREENHECK SP-A190

NOTES:

1. ALL SELECTIONS BASED ON JOBSITE ELEVATION.

LOUVER SCHEDULE

MARK FREE AREA DIMENSION SERVES TYPE FRAME EXAMPLE

L-1 4.54 SQ. FT. 42" W X 30" H O.A. DRAINABLE CHANNEL RUSKIN ELF6375DX

L-2 4.54 SQ. FT. 42" W X 30" H E.A. DRAINABLE CHANNEL RUSKIN ELF6375DX

L-3 4.54 SQ. FT. 42" W X 30" H O.A. DRAINABLE CHANNEL RUSKIN ELF6375DX

L-4 4.54 SQ. FT. 42" W X 30" H E.A. DRAINABLE CHANNEL RUSKIN ELF6375DX

NOTES:

1. PROVIDE INSIDE BIRDSCREEN WITH ALL EXHAUST LOUVERS AND INSECT SCREEN ON ALL INTAKE LOUVERS.

2. LOUVER CONSTRUCTION SHALL BE ALUMINUM.

3. LOUVER SHALL BE FACTORY FINISHED WITH KYNAR. COLOR SHALL BE SELECTED FROM FACTORY

STANDARD COLORS BY ARCHITECT.

AIR DISTRIBUTION SCHEDULE

MARK TYPE LOCATION FRAME FINISH EXAMPLE

S-1 SUPPLY CEILING PF WHITE TITUS TDC-AA, ALUMINUM

R-1 RETURN CEILING PF WHITE TITUS PAR-AA, ALUMINUM

E-1 EXHAUST CEILING PF WHITE TITUS PAR-AA, ALUMINUM

NOTES:

1. OBD = OPPOSED BLADE DAMPER

2. EXT = EXTRACTOR

3. TB = LAY-IN T-BAR

4. PF = PLASTER FRAME (EQUAL TO TITUS ALUMINUM RAPID MOUNT)

5. VERIFY FRAME TYPE WITH CEILING INSTALLER'S LAYOUT.

ROOF

PURLIN

1/4" ALL THREAD

HANGAR ROD

UNIT HEATER

ELECTRIC UNIT HEATER

MOUNTING DETAIL

NO SCALE

SUSPENDED REFRIGERANT

PIPE SUPPORT AT CEILING

NO SCALE

SECURE REFRIGERANT

PIPING TO TRUSS

WITH "HYDRA-ZORB",

"CUSH-A-CLAMP", OR

EQUAL (TYPICAL)

TRUSS SECTION

TYPICAL REFRIGERANT PIPING

VA

RIE

S

1'-6

" M

IN

.3

"

3"

MIN.

NOTE: PAINT ANGLE

SUPPORTS TO

MATCH BLDG.

FACE BRICK

COLOR (TYP.)

EXTERIOR REFRIGERANT PIPE SUPPORT DETAIL

NO SCALE

BUTT INSULATION

OF SUCTION LINE

AGAINST CLAMP

ASSEMBLY

INSULATION ON

SUCTION LINE

WELD ALL

AROUND

2" X 2" X 3/16" ANGLE

SECURE REFRIGERANT

PIPING TO SUPPORTS

WITH "HYDRA-ZORB"

"CUSH-A-CLAMP"

OR EQUAL

EQUAL TO

1-5/8" P-1000

NOTE: CONNECTIONS OF FLEX DUCT INNER CORE

SHALL BE MADE WITH S.S. WORM DRIVE CLAMPS.

OUTER INSULATION SHALL BE FITTED OVER

CORE CONNECTION AND SECURED WITH S.S. CLAMP.

SPIN-IN DUCT TAP

FLEX. DUCT

SQUARE TO ROUND

TRANSITION

EXHAUST AIR GRILLE

S.S. SCREW CLAMP (TYP)

EXHAUST AIR DUCT SEE

PLAN FOR SIZE

TYPICAL CEILING GRILLE

CONNECTION DETAIL

NO SCALE

AIR HANDLING UNIT SCHEDULE

MARK

FAN DATA COOLING DATA HEATING DATA

ELECTRICAL

DATA

EXAMPLE:

S.A. CFM O.A. CFM ESP HP SENSIBLE TOTAL EAT KW STEPS REHEAT COIL CAPACITY

AHU-1 1400 700 1.0 2.3 38.24 67.88 84/72 21 3 21.0480 V, 3Ø, 60 Hz

AAON V3-BRB-3

AHU-2 1400 700 1.0 2.3 38.24 67.88 84/72 21 3 21.0480 V, 3Ø, 60 Hz

AAON V3-BRB-3

NOTES:

1. ALL SELECTIONS BASED ON JOBSITE ELEVATION.

2. COOLING COIL VELOCITY SHALL BE 500 FPM OR LESS.

3. SENSIBLE AND TOTAL CAPACITIES ARE EXPRESSED IN MBTUH.

4. AMBIENT TEMPERATURE IS 100°F.

5. COOLING EAT IS COIL ENTERING AIR DB/WB TEMPERATURE IN °F.

OUTDOOR HEAT PUMP UNIT SCHEDULE

MARK SERVES CAPACITY - MBH EER ELECTRICAL DATA HEATING CAPACITY-MBH REFRIGERANT LINE SIZES EXAMPLE:

OHP-1 AHU-1 67.88 11.6480 V, 3Ø, 60 Hz

66.51-1/8" S, 1/2" L

AAON CFA-007-A

OHP-2 AHU-2 67.88 11.6480 V, 3Ø, 60 Hz

66.51-1/8" S, 1/2" L

AAON CFA-007-A

NOTES:

1. ALL SELECTIONS BASED ON JOBSITE ELEVATION.

2. SELECT UNITS AT 100°F DB AMBIENT TEMPERATURE.

MECHANICAL LEGEND

SYMBOL DESCRIPTION

AHU AIR HANDLING UNIT

OHP OUTDOOR HEAT PUMP

EF EXHAUST FAN

CU CONDENSING UNIT

CFM CUBIC FEET PER MINUTE

RPM REVOLUTIONS PER MINUTE

BTUH BRITISH THERMAL UNITS PER HOUR

MBH BTUH X 1000

SP STATIC PRESSURE

ESP EXTERNAL STATIC PRESSURE

HP HORSEPOWER

EAT ENTERING AIR TEMPERATURE

LAT LEAVING AIR TEMPERATURE

DB DRY BULB TEMPERATURE

WB WET BULB TEMPERATURE

OA OUTSIDE AIR

RA RETURN AIR

SA SUPPLY AIR

EA EXHAUST AIR

DRAIN

REFRIGERANT SUCTION LINE

REFRIGERANT LIQUID LINE

MANUAL BALANCING DAMPER

THERMOSTAT

FAN SWITCH

REMOTE TEMPERATURE SENSOR

SUPPLY DIFFUSER WITH PATTERN

RETURN GRILLE

EXHAUST REGISTER

SUPPLY DUCT - CROSS SECTION

EXHAUST DUCT - CROSS SECTION

RETURN DUCT - CROSS SECTION

SLOP IN DIRECTION OF ARROW

ELBOW TURNED DOWN

ELBOW TURNED UP

D

S

L

T

F

S

X-# AIR DISTRIBUTION TYPE

X" NECK SIZE

### AIRFLOW (CFM)

DIFFUSER/GRILLE LABEL

ELECTRIC UNIT HEATER SCHEDULE

MARK KW ELECTRICAL DATA EXAMPLE

UH-1 5.0460 V, 3 Ø, 60 Hz

BERKO HUHAA548

UH-2 5.0460 V, 3 Ø, 60 Hz

BERKO HUHAA548

UH-3 5.0460 V, 3 Ø, 60 Hz

BERKO HUHAA548

UH-4 5.0460 V, 3 Ø, 60 Hz

BERKO HUHAA548

UH-5 5.0460 V, 3 Ø, 60 Hz

BERKO HUHAA548

UH-6 5.0460 V, 3 Ø, 60 Hz

BERKO HUHAA548

UH-7 5.0460 V, 3 Ø, 60 Hz

BERKO HUHAA548

UH-8 5.0460 V, 3 Ø, 60 Hz

BERKO HUHAA548

NOTES:

1. PROVIDE UNIT MOUNTED THERMOSTAT IN RESTROOMS AND WALL MOUNT THERMOSTAT IN CONCESSION AND STORAGE AS SHOWN ON PLANS.

NOTE: CONNECTIONS OF FLEX DUCT INNER CORE SHALL BE MADE WITH S.S.

WORM DRIVE CLAMPS. OUTER INSULATION SHALL BE FITTED OVER

CORE CONNECTION AND SECURED WITH S.S. CLAMP.

SUSPEND ELBOW

FROM STRUCTURE

ABOVE

S.S. SCREW

CLAMP (TYP.)

INSULATE SHEET

METAL DUCT

ROUND SPIN-IN WITH

LOCKING MANUAL

VOLUME DAMPER

INSULATED

TRUNK DUCT - SEE

PLAN FOR SIZE

SEAL TAP WITH DUCT

JOINT SEALANT

FLEXIBLE INSULATED

DUCT (MAX. 4'-0" LENGTH)

SEE PLAN FOR SIZE

ADJUSTABLE ELBOW -

SEAL JOINTS AFTER

ADJUSTMENT

TYPICAL CEILING MOUNTED

SUPPLY DIFFUSER - SEE

SCHEDULE FOR TYPE

CEILING

SUPPLY AIR DIFFUSER MOUNTING DETAIL

NO SCALE

1" IN 4" MAXIMUM SLOPE

1" IN 7" DESIRABLE SLOPE

MANUAL

BALANCING

DAMPER

ANGLE TAP DETAIL

NO SCALE

MANUAL BALANCING DAMPER

BALANCE TO SCHEDULED O.A. CFM

FLEX CONNECTION

COOLING COIL

AIR HANDLING UNIT

VERTICAL AIR HANDLING UNIT MOUNTING DETAIL

NO SCALE

R.A

. D

UC

T

S.A

. D

UC

T

JOIST

ROOF

PROVIDE BACKDRAFT

DAMPER ON EXHAUST FANS

FLEX

CONNECTION

INLINE FAN

CEILING

SEE PLAN FOR

DUCT SIZE

3/8" HANGER

ROD (TYP.)

INLINE EXHAUST FAN MOUNTING DETAIL

NO SCALE

NEOPRENE ISOLATORS (4 THUS)

CONDENSING UNIT CLEARANCE DETAIL

NO SCALE

2'-0" MIN.

2'-6" MIN.

2'-0" MIN.

IF INSTALLED

ADJACENT TO SOLID

WALL

CONCRETE

EQUIPMENT

PAD

6"

MIN.

BETWEEN UNITS

BETWEEN UNIT

AND BUILDING

O.A

. D

UC

T

M

SLIDE IN FILTER RACK ASSEMBLY

SUPPLY FAN

MOTORIZED O.A. DAMPER