Top Banner
APPLICATION OF SMART MODULAR SAMPLE SYSTEMS AT AN OLEFINS PLANT John B. Cumbus ExxonMobil Chemicals Baytown Olefins Plant
21

APPLICATION OF SMART MODULAR SAMPLE SYSTEMS AT AN OLEFINS PLANT John B. Cumbus ExxonMobil Chemicals Baytown Olefins Plant.

Dec 20, 2015

Download

Documents

Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: APPLICATION OF SMART MODULAR SAMPLE SYSTEMS AT AN OLEFINS PLANT John B. Cumbus ExxonMobil Chemicals Baytown Olefins Plant.

APPLICATION OF SMART MODULAR SAMPLE SYSTEMS AT

AN OLEFINS PLANT

John B. Cumbus

ExxonMobil Chemicals

Baytown Olefins Plant

Page 2: APPLICATION OF SMART MODULAR SAMPLE SYSTEMS AT AN OLEFINS PLANT John B. Cumbus ExxonMobil Chemicals Baytown Olefins Plant.

History

• Concept first described at 1998 WAN Meeting

• Dan Podkulski active on IP 76 “footprint” Committee

• Industrial Experience has shown benefit of monitoring

• Semi-conductor industry experience • CPAC NeSSI effort

Page 3: APPLICATION OF SMART MODULAR SAMPLE SYSTEMS AT AN OLEFINS PLANT John B. Cumbus ExxonMobil Chemicals Baytown Olefins Plant.

Expected Advantages

• Minimum Engineering /Drafting Effort

• Simplicity of Construction

• Ease of Maintenance

• Leverage Technicians for Higher Priority Activity

• Higher Service Factors

Page 4: APPLICATION OF SMART MODULAR SAMPLE SYSTEMS AT AN OLEFINS PLANT John B. Cumbus ExxonMobil Chemicals Baytown Olefins Plant.

Installation Considerations

• Designed for relatively clean, dry process streams (light hydrocarbons)

• Sensors connected to gas chromatograph (analog inputs and analog outputs)

• Power for sensors originates in the analyzer

Page 5: APPLICATION OF SMART MODULAR SAMPLE SYSTEMS AT AN OLEFINS PLANT John B. Cumbus ExxonMobil Chemicals Baytown Olefins Plant.

SupplyFilter

Bypass FlowController

SampleSupply

SampleBypass

SupplyPressure

ToAnalyzer

CalibrationSupply Stream

Valve(config-1)

GuardFilter

StreamValve

(config-2)

FromAnalyzerAnalyzer

Return

F

SupplyShut-Off

NC

NO

NC

NC

NC

Atmos.Vent

Calib.Shut-Off

FE

PI

F

Analyzer FlowController

FE

PE

PressureTransmitter

Page 6: APPLICATION OF SMART MODULAR SAMPLE SYSTEMS AT AN OLEFINS PLANT John B. Cumbus ExxonMobil Chemicals Baytown Olefins Plant.

Engineering Package

• Provided by Configurator

• Pressure Indicator left for Technicians

• Eight Single Stream and One Dual Stream

• Three Analog Outputs, Two Inputs

Page 7: APPLICATION OF SMART MODULAR SAMPLE SYSTEMS AT AN OLEFINS PLANT John B. Cumbus ExxonMobil Chemicals Baytown Olefins Plant.

Modular Sample System (minus MFMs)

Page 8: APPLICATION OF SMART MODULAR SAMPLE SYSTEMS AT AN OLEFINS PLANT John B. Cumbus ExxonMobil Chemicals Baytown Olefins Plant.

Modular System Connections Inside Enclosure

Page 9: APPLICATION OF SMART MODULAR SAMPLE SYSTEMS AT AN OLEFINS PLANT John B. Cumbus ExxonMobil Chemicals Baytown Olefins Plant.

New System in an Old Box

Page 10: APPLICATION OF SMART MODULAR SAMPLE SYSTEMS AT AN OLEFINS PLANT John B. Cumbus ExxonMobil Chemicals Baytown Olefins Plant.

Assembly Test of Smaller System (76 Pieces)

Page 11: APPLICATION OF SMART MODULAR SAMPLE SYSTEMS AT AN OLEFINS PLANT John B. Cumbus ExxonMobil Chemicals Baytown Olefins Plant.

Assembly Test Configuration

Page 12: APPLICATION OF SMART MODULAR SAMPLE SYSTEMS AT AN OLEFINS PLANT John B. Cumbus ExxonMobil Chemicals Baytown Olefins Plant.

Assembly Drawings Provided

Page 13: APPLICATION OF SMART MODULAR SAMPLE SYSTEMS AT AN OLEFINS PLANT John B. Cumbus ExxonMobil Chemicals Baytown Olefins Plant.

Completed Assembly

Page 14: APPLICATION OF SMART MODULAR SAMPLE SYSTEMS AT AN OLEFINS PLANT John B. Cumbus ExxonMobil Chemicals Baytown Olefins Plant.

Example of Mechanic’s Previous Work

Page 15: APPLICATION OF SMART MODULAR SAMPLE SYSTEMS AT AN OLEFINS PLANT John B. Cumbus ExxonMobil Chemicals Baytown Olefins Plant.

The “Mechanic”, Age 9

Page 16: APPLICATION OF SMART MODULAR SAMPLE SYSTEMS AT AN OLEFINS PLANT John B. Cumbus ExxonMobil Chemicals Baytown Olefins Plant.

Comparison of “Old” and “New” Sample Systems

Page 17: APPLICATION OF SMART MODULAR SAMPLE SYSTEMS AT AN OLEFINS PLANT John B. Cumbus ExxonMobil Chemicals Baytown Olefins Plant.

Sample System (Exterior) and Gas Chromatograph (Interior)

Page 18: APPLICATION OF SMART MODULAR SAMPLE SYSTEMS AT AN OLEFINS PLANT John B. Cumbus ExxonMobil Chemicals Baytown Olefins Plant.

Gas Chromatograph Display Panel

Page 19: APPLICATION OF SMART MODULAR SAMPLE SYSTEMS AT AN OLEFINS PLANT John B. Cumbus ExxonMobil Chemicals Baytown Olefins Plant.

Experience So Far

• Six of Nine Systems have been in Service since early to mid December

• Minor Start -Up Problems Encountered with Wiring Inside Sample System

• One MFM Operated Briefly, then Ceased to Control Flow

• No other Problems Encountered

Page 20: APPLICATION OF SMART MODULAR SAMPLE SYSTEMS AT AN OLEFINS PLANT John B. Cumbus ExxonMobil Chemicals Baytown Olefins Plant.

Conclusions

• Smart Modular System has performed as expected in limited evaluation time

• Expected benefits appear to be realistic• Thought should be given to GC/Controller

programming and what to do with system data

• Need to expand parts availability,meet electrical classification of at least Div 2

Page 21: APPLICATION OF SMART MODULAR SAMPLE SYSTEMS AT AN OLEFINS PLANT John B. Cumbus ExxonMobil Chemicals Baytown Olefins Plant.

John B. Cumbus

• Master’s in Analytical Chemistry from Auburn University in 1979 (After Pat Sullivan, but before Bo Jackson)

• Analyzer Engineer at Celanese in Bishop, Texas 1979-1981

• Analyzer Engineer at Exxon Baytown Olefins Plant 1981-Present

• Chairman Exxon Chemicals NA Analyzer Network 1987-1990

• Chairman ExxonMobil Worldwide Analyzer Network 1998 to Present

• Proudest of: Two Daughters and One Son

• Favorite Activities: Traveling to Florida’s Beaches, Enjoying Fine Rum, and Shooting Handguns (Not at the Same Time)