G6-76 (Monitor III Software) 6/11b Page 1 Decision-Makerr 3+ M340+ ATS Controller and PM340 Power Monitor are not illustrated. Standard Software Features and Functions D Monitor and control the power system generator sets and transfer switches from a personal computer using a single software package D Monitor and control systems through a Windowsr-based graphical user interface D View the status of all devices on one site overview screen D Password-protected data access: Guest, User, and Supervisor D Monitor and control systems over a local area network, remotely via a modem connection, or through an Ethernet connection D Connect up to 247 controller devices on a local area network D Monitor data from multiple devices on the same local area network simultaneously D Start or stop the generator set from a PC D Read and adjust trip points, time delays, and system parameter settings D Assign inputs and outputs D View ECM data for ECM-equipped engines D View system run time history D View up to 100 recent events including engine starts, faults, shutdowns, and warnings D Device data windows automatically update D Software kits include hardware for either local or remote communications Monitor III Software Monitoring and Control Software Monitor III software provides monitoring and control of Kohlerr generator sets and transfer switches equipped with the following controllers: Decision-Makerr 6000 generator set controller Decision-Makerr 3000 generator set controller Decision-Makerr 550 generator set controller Decision-Makerr 340 generator set controller Decision-Makerr 3+ generator set controller MPACt 1500 automatic transfer switch controller MPACt 1000 automatic transfer switch controller M340 and M340+ automatic transfer switch controllers PM340 Power Monitor Decision-Makerr 340 Decision-Makerr 550 Power System Accessories Applicable Controllers MPACt 1000 Windowsr is a registered trademark of Microsoft Corporation. MPACt 1500 Decision-Makerr 6000 Decision-Makerr 3000
18
Embed
Applicable Controllers Monitoring ... - · PDF fileMonitor III software provides monitoring and control of Kohler generator ... Overspeed Overvoltage Undervoltage Remote Operation
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
G6-76 (Monitor III Software) 6/11b Page 1
Decision-Maker� 3+
M340+ ATS Controller and PM340 Power Monitor are not illustrated.
Standard Software Features and Functions
� Monitor and control the power system generator sets and transfer
switches from a personal computer using a single software package
� Monitor and control systems through a Windows�-based graphical
user interface
� View the status of all devices on one site overview screen
� Password-protected data access: Guest, User, and Supervisor
� Monitor and control systems over a local area network, remotely via
a modem connection, or through an Ethernet connection
� Connect up to 247 controller devices on a local area network
� Monitor data from multiple devices on the same local area network
simultaneously
� Start or stop the generator set from a PC
� Read and adjust trip points, time delays, and system parameter
settings
� Assign inputs and outputs
� View ECM data for ECM-equipped engines
� View system run time history
� View up to 100 recent events including engine starts, faults,shutdowns, and warnings
� Device data windows automatically update
� Software kits include hardware for either local or remote
communications
Monitor III Software
Monitoring and Control Software
Monitor III software provides monitoring and control of Kohler� generator
sets and transfer switches equipped with the following controllers:
Decision-Maker� 6000 generator set controller
Decision-Maker� 3000 generator set controller
Decision-Maker� 550 generator set controller
Decision-Maker� 340 generator set controller
Decision-Maker� 3+ generator set controller
MPAC� 1500 automatic transfer switch controller
MPAC� 1000 automatic transfer switch controller
M340 and M340+ automatic transfer switch controllers
PM340 Power Monitor
Decision-Maker� 340
Decision-Maker� 550
Power System Accessories
Applicable Controllers
MPAC� 1000
Windows� is a registered trademark of Microsoft Corporation.
MPAC� 1500
Decision-Maker� 6000
Decision-Maker� 3000
G6-76 (Monitor III Software) 6/11b Page 2
Monitoring and Control Software
Use Monitor III software to create screens containing datawindows that display system information, controller settings, and
operating status for connected generator sets, transfer switches,and power monitors. For more information, see TP-6347,Monitor III Software Operation and Installation Manual.
� Easily select, create, arrange, or delete data windows.
� Create data windows for multiple devices in a network.
� Create and save multiple screen configurations.
� Display screens show system status and settings.
� Password-protected setup windows allow remote operation
and adjustment.
Kohler publishes Modbus� data register maps for its products.Modbus protocol manual TP-6113 is available through Kohlerdistributors.
Modbus� is registered trademark of Schneider Electric.
Minimum System Requirements
� 133 MHz or higher Intel� Pentium�-compatible CPU
� 32 MB RAM
� CD-ROM drive and 75 MB hard drive space available for
installation
� 800 x 600 or better color monitor (1024 x 768 recommended)
� Microsoft�Windows� 2000, Windows� XP, Windows Vista�, or
Windows� 7 operating system
� COM port numbered between 1 and 255, capable of baud rate
9600 or 19200 (for direct local connection)
� PC network interface card (NIC) (for applications using
ethernet connections only)
� Adobe� Acrobat� or Adobe�Reader� (to display the Help file)
Intel� and Pentium� are registered trademarks of Intel Corporation.Microsoft�, Windows�, and Windows Vista� are registered trademarks of MicrosoftCorporation.Adobe� Acrobat� and Adobe� Reader� are registered trademarks of Adobe SystemsIncorporated.
G6-76 (Monitor III Software) 6/11b Page 3
Decision-Maker� 550 and Decision-Maker� 6000 Generator Set Controllers
All of the following information is available through Decision-Maker� 550 and Decision-Maker� 6000 controller communications.
Adjustments and manual operations are password-protected.
Parameter View Adjust
Date and Time
Date � �
Time � �
Synchronize with computer �
Electrical Information
% of rated kW �
Current, L1, L2, L3 �
Frequency �
Voltage, line-line �
Voltage, line-neutral �
Total kVA, L1, L2, and L3 �
Total kVAR, L1, L2, and L3 �
Total kW, L1, L2, and L3 �
Total power factor, L1, L2, and L3 �
Engine Info
Battery voltage (ECM) �
Coolant Level �
Coolant Pressure �
Coolant Temperature �
Engine speed (RPM) �
Fuel last run consumption �
Fuel pressure �
Fuel burn rate, liters/hr. or gal./hr. �
Fuel temperature �
Intake air filter diff. pressure �
Intake air temperature �
Oil pressure �
Oil level �
Oil temperature �
Oil crankcase pressure �
Event History (100 most recent events)
Faults �
Warnings �
Shutdowns �
Input activation �
Output activiation �
Save history button � �
Time and date of each event �
Generator Info � �
Battery voltage, nominal � �
Connection, wye or delta � �
Rating, kW � �
NFPA 110 defaults, enabled or disabled � �
Phases, single or three � �
Frequency, nominal � �
Voltage, nominal � �
Operating mode, standby or prime power � �
Parameter View Adjust
Maintenance
kW hours * �
Last maintenance date �
Last run start date �
Last run start time �
Loaded/unloaded run time * �
Number of starts * �
Operating days �
Run time * �
Last run time, loaded and unloaded �
* Total and since last maintenance
Maintenance Operations
Reset maintenance records button �
Reset faults button �
System Info
Alternator part number �
Controller serial number �
Engine part number �
Final assembler’s clock number �
Final assembly date �
Generator set serial number �
Generator set model number �
Genset name (optional, user-defined) � �
Load description (optional, user-defined) � �
Location (optional, user-defined) � �
Device ID �
Specification number �
Application code version (controller) �
Time Delays
Crank on � �
Crank pause � �
Engine cooldown � �
Engine start � �
Load shed � �
Maximum crank cycles � �
Overvoltage � �
Starting aid � �
Undervoltage � �
Trip Points
High battery voltage � �
load shed output � �
Low battery voltage � �
Overfrequency � �
Overspeed � �
Overvoltage � �
Underfrequency � �
Undervoltage � �
G6-76 (Monitor III Software) 6/11b Page 4
Decision-Maker� 550 and Decision-Maker� 6000 Controllers, continued
Relay Driver Outputs (RDOs), System Events, and Common Alarms
Assign up to 31 relay driver outputs (RDOs). Define any event as a common fault, except as noted.
Parameter View Adjust
Relay Driver Outputs (RDOs), System Events, andCommon Alarms
High shutdown enable/disable � �
High warning enable/disable � �
Low shutdown enable/disable � �
Low warning enable/disable � �
Assign/remove functions: � �
AC sensing loss � �
Air damper control � �
Air damper indicator � �
Air/fuel module (AFM) remote start � �
Air temperature signal loss � �
Alternator protection shutdown � �
Analog inputs 1--7 � �
Battery charger fault � �
Breaker trip � �
Critical overvoltage � �
Defined common fault (not selectable ascommon fault)
� �
Delay engine cooldown � �
Delay engine start � �
Digital inputs 1--21 � �
EEPROM write failure � �
Emergency power system (EPS)supplying load
� �
Emergency stop � �
Fuel valve relay � �
Generator running � �
Ground fault � �
High air temperature shutdown � �
High air temperature warning � �
High battery voltage � �
High coolant temperature shutdown � �
High coolant temperature warning � �
High oil temperature shutdown � �
High oil temperature warning � �
In synch � �
Internal fault � �
Load shed kW over � �
Load shed overtemperature � �
Load shed underfrequency � �
Locked rotor � �
Parameter View Adjust
Loss of ECM communications � �
Loss of field shutdown � �
Low battery voltage � �
Low coolant level � �
Low coolant temperature shutdown � �
Low coolant temperature warning � �
Low fuel � �
Master switch error � �
Master switch not in AUTO � �
Master switch off � �
Master switch open � �
Block heater control (for future MDECapplications)
Availability is subject to change without notice. Kohler Co. reserves theright to change the designor specificationswithout noticeandwithoutanyobligation or liability whatsoever. Contact your local Kohler� generatordistributor for availability.
KOHLER CO., Kohler, Wisconsin 53044 USAPhone 920-457-4441, Fax 920-459-1646For the nearest sales and service outlet in theUS and Canada, phone 1-800-544-2444KohlerPower.com
Network Communication Products and Accessories
� Monitor III software kit with hardware key. Includes:
� Software CD-ROM
� Null modem cable
� Network termination resistor
� Operation manual and connection instructions
� Monitor III software kit with hardware key and device
modem for remote connections. Includes:
� Software CD-ROM
� AT modem cable
� Device modem, 120VAC/60Hz, 19.2k baud
� Optical isolator
� Converter, RS-232/RS-485
� Connector, 9-pin/25-pin
� Null modem, 25-pin
� Network termination resistor
� Operation manual and connection instructions
� Device modem kit, 50Hz, 19.2k baud
� Modbus�/Ethernet converter kit. Includes DC adapter
with universal AC plug. (RS-485/RJ-45 connectors;
required for TCP/IP connections. Not required for the
MPAC� 1500 ATS controller).
� Modbus�/KBUS converter kit for the following devices
(required for Monitor III or other Modbus�
communication):
� Decision-Maker� 340 generator set controller
� M340 and M340+ transfer switch controller
� PM340 power monitor
� Modbus� communication board for Decision-Maker� 3+
generator set controllers (required for Monitor III or other