November 2009 B U I L D I N G C O N N E C T I O N S T H A T L A S T 23 05 00 Basic Mechanical Methods and Materials 23 05 29 Hangers and Supports 21 11 00 Pipes, Valves and Fittings for Fire Protection Systems 22 30 00 Pipes, Valves and Fittings for Plumbing Systems 23 60 00 Pipes, Valves and Fittings for HVAC Heating and Cooling Systems 23 50 00 Piping Specialties Anvil CSI 3 Part MasterFormat Specifications:
40
Embed
Anvil CSI 3 Part MasterFormat Specifications€¦ · couplings; universal anvilets; forged steel fittings and unions; pipe hangers and supports; threaded rod; ... Wind-Dynamic Design,
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Anvil International WorldwideCustomer Service CenterTel: 708-885-3000 Fax: 708-534-5441
U.S. RegIOnAl SeRvICe CenteRS
Anvil International CanadaCustomer Service Center390 Second AvenueP.O. Box 40Simcoe, Ontario N3Y 4K9
Tel: 519-426-4551Fax: 519-426-5509
CAnAdA SeRvICe CenteR
www.anvilintl.com
b u i l d i n g c o n n e c t i o n s t h a t l a s t
northern RegionRegional Distribution & Customer Service CenterSeRviCing: Illinois, Indiana, Iowa, Kentucky, Michigan, Minnesota, Nebraska, North and South Dakota, Ohio,West Pennsylvania, West Virginia, Wisconsin
eastern RegionRegional Distribution CenterSeRviCing: Connecticut, Delaware, Florida, Georgia, Maine, Maryland, Massachusetts, New Hampshire, New Jersey,New York, North and South Carolina, East Pennsylvania,Rhode Island, Vermont, Virginia
800 Malleable Road Columbia, PA 17512
Western RegionRegional Distribution CenterSeRviCing: Alaska, Arizona, California, Colorado, Hawaii, Idaho, Montana, Nevada, New Mexico, Oregon, Utah, Washington, Wyoming
1385 Greg Street Sparks, NV 89431
InteRnAtIOnAl SAleS
Mexico, Puerto Rico andlatin AmericaAbraham Quijada, Sales [email protected]
Tel: +1-281-590-4600
U.S. Customer Service Tel: +1-708-885-3000 Fax: +1-708-534-5441
europe and Middle east RegionRick van Meesen, Sales DirectorThe [email protected]
Tel: +31-53-5725570 Fax: +31-53-5725579
U.S. Customer Service Tel: +1-708-885-3000 Fax: +1-708-534-5441
b u i l d i n g c o n n e c t i o n s t h a t l a s t
23 05 00 Basic Mechanical Methods and Materials
23 05 29 Hangers and Supports
21 11 00 Pipes, Valves and Fittings for Fire Protection Systems
22 30 00 Pipes, Valves and Fittings for Plumbing Systems
23 60 00 Pipes, Valves and Fittings for HVAC Heating and Cooling Systems
23 50 00 Piping Specialties
Anvil CSI 3 Part MasterFormat Specifications:
B U I l d I n g C O n n e C t I O n S t h At l A S t
For over 150 years, Anvil has worked diligently to build a strong, vibrant tradition of making connections — from pipe to pipe and people to people.
We pride ourselves in providing the finest-quality pipe products and
services with integrity and dedication to superior customer service at all levels.
We provide expertise and product solutions for a wide range of applications,
from plumbing, mechanical, HVAC, industrial and fire protection to mining,
oil and gas. Our comprehensive line of products includes: grooved pipe
couplings, grooved and plain-end fittings, valves, cast and malleable iron fittings,
forged steel fittings, steel pipe nipples and couplings, pipe hangers and supports,
channel and strut fittings, mining and oil field fittings, along with much more.
As an additional benefit to our customers, Anvil offers a complete and
comprehensive Design Services Analysis for mechanical equipment rooms, to
help you determine the most effective and cost-efficient piping solutions.
Anvil is a proud member of the United States Green Building Council (USGBC).
Go to the Anvil website to obtain manufacturer recycled certificates and other
Green information.
At Anvil, we believe that responsive and accessible customer support is
what makes the difference between simply delivering products —
and delivering solutions.
B R A n d S O f A n v I l I n t e R n At I O n A l
Anvil® product lines include malleable and cast iron fittings, unions and flanges; seamless steel pipe nipples; steel pipe couplings; universal anvilets; forged steel fittings and unions; pipe hangers and supports; threaded rod; and engineered hangers.
The Gruvlok® product line consists of couplings for grooved and plain-end fittings, butterfly valves and check valves; flanges; pump protection components; pipe grooving tools; as well as copper and stainless steel system components.
Anvil-Strut™ products include a complete line of channel in stock lengths of 10 and 20 feet, with custom lengths available upon request. A variety of fittings and accessories are also offered. All products can be ordered in an assortment of finishes and material choices including SupR-Green™, Zinc Trivalent Chromium, pre-galvanized, hot-dipped galvanized, electro-galvanized, aluminum, plain, and stainless steel.
JB Smith™ is the leading manufacturer of oil country tubular fittings, swages and bull plugs – all meeting API specifications. Offering tubing nipples, casing nipples as well as a full line of traditional line pipe and oil country threads in every schedule, JB Smith is the resource for all your oilfield needs.
Catawissa™ NACE and API approved wing unions for Standard Service are offered in non-pressure seal ends as well as threaded and butt weld, and are interchangeable with most leading union manufacturers. Fully traceable and available with complete mill certifications, Catawissa’s oilfield wing union product line includes the standard ball-and-cone design plus our unique Figure 300 Flat Face design, where space and pipe line separation are a consideration.
AnvilStar™ offers a complete line of products for the fire protection industry, including Gruvlok® couplings, fittings, flanges; valves, and roll groovers; steel pipe nipples and couplings; cast and malleable iron threaded and flanged fittings; pipe hangers and supports; Merit® tee-lets, drop nipples; steel welding flanges; SPF grooved couplings, fittings, and flanges; SPF cast iron and ductile iron threaded fittings, o’lets, steel pipe nipples; and Mueller valves and indicator posts.
The SPF/Anvil™ product line includes a variety of internationally sourced products such as grooved couplings, fittings and flanges, cast iron, malleable iron and ductile iron threaded fittings, steel pipe nipples, as well as o’lets.
The Merit® product line includes a variety of tee-lets, drop nipples, and steel welding flanges for fire protection applications. Most Merit products are UL/ULC Listed, FM Approved, and rated from 175 to 300 psi.
Beck steel pipe nipples and steel pipe couplings are manufactured in accordance with the ASTM A733 Standard Specification for Welded and Seamless Carbon Steel and Stainless Steel Pipe Nipples. Steel pipe couplings are manufactured in accordance with the ASTM A865 Standard Specification for Threaded Couplings, Steel, Black or Zinc-Coated (Galvanized) Welded or Seamless, for Use in Steel Pipe Joints. Beck API couplings are manufactured in accordance with the API Specification for line pipe.
Canvil® manufactures low pressure hexagon reducer bushings, as well as plugs and hex caps up to 1” in diameter in various finishes including Oil Treat, Phosphate and Electro Galvanized. In addition, Canvil manufactures A105 hex or round material in class 3000 and 6000 pound, forged steel couplings and bar stock products offered as either as normalized (A105N) or non-normalized (A105) that are fully traceable for mechanicals and chemistry through our MTR program.
Anvil also offers downloadable CSI 3 Part MasterFormat Specifications at www.anvilintl.com.
15050-4
SECTION 23 05 00 BASIC MECHANICAL METHODS AND MATERIALS
4 ANvIL® INTERNATIONAL
PART 1 GENERAL 1.1 SECTIONINCLUDES A. Piping,couplings,fittingsandvalvesforpipedbuildingsystems.
1.2 RELATEDSECTIONS A. Section230529-HangersandSupportsforHVACPipingandEquipment.
B. Section211100-FacilityFire-SuppressionWater-ServicePiping.
C. Section223000-PlumbingEquipment.
D. Section235000-CentralHeatingEquipment.
E. Section236000-CentralCoolingEquipment.
1.3 REFERENCES A. AmericanSocietyofMechanicalEngineers(ASME)B31.1-PowerPiping(SIEdition).
B. AmericanSocietyofMechanicalEngineers(ASME)B31.3-ChemicalPlantandPetroleumRefineryPiping.
C. AmericanSocietyofMechanicalEngineers(ASME)B31.9-BuildingServicesPiping.
D. ASTMInternational(ASTM)A36-StandardSpecificationforCarbonStructuralSteel.
E. ASTMInternational(ASTM)A47-StandardSpecificationforFerriticMalleableIronCastings.
F. ASTMInternational(ASTM)A48-StandardSpecificationforGrayIronCastings.
G. ASTMInternational(ASTM)A53-StandardSpecificationforPipe,Steel,BlackandHot-Dipped,Zinc-Coated,WeldedandSeamless.
H. ASTMInternational(ASTM)A123-StandardSpecificationforZinc(Hot-DipGalvanized)CoatingsonIronandSteelProducts.
I. ASTMInternational(ASTM)A153-SpecificationforZincCoating(HotDip)onIron&SteelHardware.
J. ASTMInternational(ASTM)A240-StandardSpecificationforChromiumandChromium-NickelStainlessSteelPlate, Sheet,andStripforPressureVesselsandforGeneralApplications.
K. ASTMInternational(ASTM)A387-StandardSpecificationforPressureVesselPlates,AlloySteel,Chromium-Molybdenum.
L. ASTMInternational(ASTM)A515-StandardSpecificationforPressureVesselPlates,CarbonSteel,forIntermediate-and Higher-TemperatureService.
N. ASTMInternational(ASTM)A575-StandardSpecificationforSteelBars,Carbon,MerchantQuality,M-Grades.
O. ASTMInternational(ASTM)A668-StandardSpecificationforSteelForgings,CarbonandAlloy,forGeneralIndustrialUse.
P. ASTMInternational(ASTM)A1011-StandardSpecificationforSteel,SheetandStrip,Hot-Rolled,Carbon,Structural, High-StrengthLow-AlloyandHigh-StrengthLow-AlloywithImprovedFormability.
BASIC MECHANICAL METHODS AND MATERIALS SECTION 23 05 00
5ANvIL® INTERNATIONAL
Pipe
s, V
alve
s an
d Fi
tting
sfo
r H
VAC
Hea
ting
and
Cool
ing
Syst
ems
Pipe
s, V
alve
s an
d Fi
tting
sfo
r Pl
umbi
ng S
yste
ms
Pipe
s, V
alve
s an
d Fi
tting
sfo
r F
ire
Prot
ectio
n Sy
stem
sPi
ping
Spec
ialti
esBa
sic
Mec
hani
cal
Met
hods
and
Mat
eria
ls H
ange
rs a
ndSu
ppor
ts
1.5 SUBMITTALS A. SubmitunderprovisionsofSection013000.
B. [ProductData]:Manufacturer’sdatasheetsoneachproducttobeused,including: 1. Preparationinstructionsandrecommendations. 2. Installationmethods.
C. Certifications: 1. Productcertificatessignedbymanufacturercertifyingmaterialscomplywithspecifiedperformancecharacteristicsand criteriaandphysicalrequirements.Certificatesshallbefurnishedonlyasrequiredbyspecificcodes,uponrequest.
D. SelectionSamples:Foreachfinishproductspecified,twocompletesetsofcolorchipsrepresentingmanufacturer’sfull rangeofavailablecolorsandpatterns.
E. VerificationSamples:Foreachfinishproductspecified,twosamples,minimumsize6inches(150mm)square,representing actualproduct,color,andpatterns.
F. CloseoutSubmittals: 1. Warranty:Warrantydocuments. 2. OperationandMaintenanceData:OperationandmaintenancedataforinstalledproductsinaccordancewithDivision1 CloseoutSubmittals(MaintenanceDataandOperationData)Section.Includemethodsformaintaininginstalled products,andprecautionsagainstcleaningmaterialsandmethodsdetrimentaltofinishesandperformance.
1.6 QUALITYASSURANCE A. ManufacturerQualifications: 1. ManufacturingfacilitiesshallberegisteredtoISO9001:2000andassessedtoISO9000:2000standard.Acopyofthe currentcertificateshallbeavailableuponrequest.
B. Conductpre-installationmeetingtoverifyprojectrequirements,coordinatewithothertrades,andestablishconditionand completenessofsubstrate.Reviewmanufacturer’sinstallationinstructionsandmanufacturer’swarrantyrequirements.
1.7 DELIVERY,STORAGE,ANDHANDLING A. Storeproductsinmanufacturer’sunopenedpackaginguntilreadyforinstallation.
B. Storeanddisposeofsolvent-basedmaterials,andmaterialsusedwithsolvent-basedmaterials,inaccordancewith requirementsoflocalauthoritieshavingjurisdiction.
1.8 PROJECTCONDITIONS A. Maintainenvironmentalconditions(temperature,humidity,andventilation)withinlimitsrecommendedbymanufacturer foroptimumresults.Donotinstallproductsunderenvironmentalconditionsoutsidemanufacturer’sabsolutelimits.
1.9 WARRANTY A. Manufacturer’sWarranty:Submit,forOwner’sacceptance,manufacturer’sstandardwarrantydocumentexecutedby authorizedcompanyofficial.Manufacturer’swarrantyisinadditionto,andnotalimitationof,otherrights.Ownermay haveunderContractDocuments.
PART 2 PRODUCTS 2.1 MANUFACTURERS A. AcceptableManufacturer:AnvilInternational,whichislocatedat:110CorporateDr.Suite10;Portsmouth,NH03801; Tel:603-422-8000;Fax:603-422-8033;Email:[email protected];Web:www.anvilintl.com
B. Substitutions:Notpermitted.
C. RequestsforsubstitutionswillbeconsideredinaccordancewithprovisionsofSection016000.
2.2 PIPING A. SteelPiping:BlackSteeland/orgalvanizedpipeconformingtoASTMA-53,GradeAorB.Groovingshallconformto Gruvlokpublishedgroovingspecifications.
B. SteelPiping:BlackSteeland/orgalvanizedpipeconformingtoASTMA-135orA-795.GroovingshallconformtoGruvlok publishedgroovingspecifications.
C. SteelPiping:BlackSteeland/orgalvanizedpipeconformingtoASTMA-53,GradeAorB.Standardschedule40pipe shallberollorcutgrooved.GroovingshallconformtoGruvlokpublishedgroovingspecifications.
D. SteelPiping:BlackSteeland/orgalvanizedpipeconformingtoASTMA-53,GradeAorB.Schedule10pipeandbelow shallberollgrooved.GroovingshallconformtoGruvlokpublishedgroovingspecifications.
E. CopperTubing:CoppertubetocomplywithASTMB-88. 1. TypesK,L,M,andDWVshallbeusedinconjunctionwiththeGruvlokCopperrollgroovedmethod.
2.3 FITTINGS A. Material: 1. CouplingsandGroovedFlangeAdaptersshallconformtoASTMA-536DuctileGrade65-45-12ortoASTMA-47 MalleableGrade32510. 2. CouplingTrackHeadBoltsshallconformtoASTMA-183Grade2.
15050-6
SECTION 23 05 00 BASIC MECHANICAL METHODS AND MATERIALS
D. GroovedCouplingsforCopperTubeSystems:Couplingworkingpressurenottoexceed300psig(2.0MPa). 1. Gruvlokstyle7400Rigidliteandstyle7012couplingflangeadapters. 2. Grade“E”EPDMgasket. 3. GruvlokXtremeLubricant.
E. GroovedFlangeAdapters:FlangeadapterstotransitionfromflangetogroovewithnonippleshallbeGruvlokFig7012orFigure7013: 1. FlangesinFigures7012and7013aredesignedwithinternalanti-rotationtinesandaredesignatedasarigidconnection. 2. Figures7012and7013flangeadaptersrequiresealingringswhenusedwithcertainflangedproducts. 3. Figure7012:ConformstoANSIclass125or150lb(57or68kg). a. Sizes2inchesthrough20inches(51mmthrough508mm)areratedat300psig(2.0MPa). b. Size24inches(610mm)isratedat250psig(1.72MPa). 4. Figure7013:2inchesthrough12inches(51mmthrough305mm)availableforANSIclass250or300lb(113kgor 136kg)boltpatternandisratedat750psig(5MPa).
F. GroovedFittingsforSteelPipingSystems-ShallbeGruvlokcastductile,malleable,forgedsteel,and/orsegmentalwelded steelfittings. 1. Sizes1inchesto30inches(25mmto762mm)diameter: a. CastductileconformstoASTMA-536orASTMA-47. b. ForgedsteelconformstoASTMA-234. c. SegmentalweldedconformstoASTMA-53. 2. FittingsshallbecoatedwithanAlkyd-enamelnon-toxicpaint. 3. ZincelectroplatedfittingsconformtoASTMB-633. 4. HotDipGalvanizedfittingsconformtoASTMA-153. 5. StandardFittingsshallbeschedule40orstandardwall.Otherfittingsareschedule80orlightwallasscheduled.
G. GroovedCopperFittings:GruvlokWrotCopperfittingsperASTMB-75andANSIB-16.22,alloyC12200. 1. WroughtCopperfittingssize2inchesto8inches(51mmto203mm)diametershallbeschedule10orstandardwall 304or316stainlesssteel.Copperfittingsshallbe99.9percentleadfree. 2. CouplingsandWroughtCopperFittingsshallbeNSF,PlumbingCodeapprovedandUL/ULClisted.
I. BranchOutlets:ShallbeGruvlokClamp-TStyles7045and7046,andClamp-TCrossFigure7047,7048and7049with groovedorthreadedoutlets. 1. Designatedasabolted-onpositivepipeengagementbranchoutlet.Workingpressureto500psi(3.5KPa).
15050-7
BASIC MECHANICAL METHODS AND MATERIALS SECTION 23 05 00
2.5 EQUIPMENTANCHORBOLTSANDTEMPLATES A. Providetemplatestoensureaccuratelocationofanchorbolts.
15050-8
SECTION 23 05 00 BASIC MECHANICAL METHODS AND MATERIALS
8 ANvIL® INTERNATIONAL
PART 3 EXECUTION 3.1 EXAMINATION A. Donotbegininstallationuntilsubstrateshavebeenproperlyprepared.
B. Ifsubstratepreparationistheresponsibilityofanotherinstaller,notifyArchitectofunsatisfactorypreparationbeforeproceeding.
3.2 PREPARATION A. Cleansurfacesthoroughlypriortoinstallation.
B. Preparesurfacesusingthemethodsrecommendedbythemanufacturerforachievingthebestresultforthesubstrateunder theprojectconditions.
3.3 INSTALLATION A. General:GroovedpipinginstallationshallmeetANSIB-31.1-ANSIB-31.9CodesforPressurePiping.
B. Installinaccordancewithmanufacturer’sinstructions.
C. Pipeendsshallbecleanandfreefromindentations,burrs,rustordamage.
D. Fieldgroovingorpipecuttingofgalvanizedpipemayrequirerepairofpossibledamagedgalvanizedpipeends.Twocoats ofspray-on“liquid-galvanize”arerecommended.
E. Installrigidcouplingswithtongue-and-groovehousingforprecisecouplingalignmentandengagement.Installtinesinthe housingkeysectiontoprovidearigid-likepipeconnection.
F. Companionormatingflangesshallhaveaflathardsurfaceandshallbefreefromgouges,undulationsordeformities.Use flangegasketsealingringsifmatingsurfacesarenotuniform.
G. Plain-endcouplingandfittinginstallationshallcomplywithspecifictorqueandinstallationrequirements.Consultcurrent manufacturer’sproductinstallationdata.
H. Gasketlubricantshallbeusedtoassurepropercouplinggasketseating,andconformancewithgasketserviceusage.
Notes: (1) For spacing supports incorporating type 40 shields, see table 5. (2) Does not apply where span calculations are made or where there are concentrated loads between supports such as flanges, valves, specialties, etc. or changes in direction requiring additional supports. (3) Unbalanced forces of hydrostatic or hydrodynamic origin (thrust forces) unless restrained externally can result in pipe movement and separation of joints if the joints of the system are not of a restrained joint design. See Section 13.3.
4.5 SUBMITTALS A. SubmitunderprovisionsofSection013000.
B. ProductData:Manufacturer’sdatasheetsoneachproducttobeused,including: 1. Preparationinstructionsandrecommendations. 2. LoadcapacityandsizingschedulesspecifictoProject. 3. Installationmethods.
C. Certifications: 1. Productcertificatessignedbymanufacturercertifyingmaterialscomplywithspecifiedperformancecharacteristicsand criteriaandphysicalrequirements.Certificatesshallbefurnishedonlyasrequiredbyspecificcodes,uponrequest.
D. ShopDrawings:
E. RecommendedMinimumRodDiametersforSingleRigidRodHangers:(ExtractedfromANSI/MSS-SP69,2003,Page9, Table4,withpermissionofthepublisher,theManufacturersStandardizationSociety.)
TABLE 4 – Recommended Min. Rod Diameter for Single Rigid Rod Hangers(1)(2)
Columns(3)
1, 2, 6, 7Columns(3)
3, 4, 8, 9, 10Nominal Pipe
orTubing Size
Nominal Rod Diameter Nominal Rod Diameter
in. mm ft. m ft. m1⁄4 (6) – – 3⁄8 M103⁄8 (10) 3⁄8 M10 3⁄8 M101⁄2 (15) 3⁄8 M10 3⁄8 M103⁄4 (20) 3⁄8 M10 3⁄8 M101 (25) 3⁄8 M10 3⁄8 M10
E. SelectionSamples:Foreachfinishproductspecified,twocompletesetsofcolorchipsrepresentingmanufacturer’sfull rangeofavailablecolorsandpatterns.
F. VerificationSamples:Foreachfinishproductspecified,twosamples,minimumsize6inches(150mm)square,representing actualproduct,color,andpatterns.
G. CloseoutSubmittals: 1. Warranty:Warrantydocuments. 2. OperationandMaintenanceData:OperationandmaintenancedataforinstalledproductsinaccordancewithDivision1 CloseoutSubmittals(MaintenanceDataandOperationData)Section.Includemethodsformaintaininginstalledproducts, andprecautionsagainstcleaningmaterialsandmethodsdetrimentaltofinishesandperformance.
4.6 QUALITYASSURANCE A. ManufacturerQualifications: 1. ManufacturingfacilitiesshallberegisteredtoISO9001.2000andassessedtoISO9000.2000standard.Acopyofthe currentcertificateshallbeavailableuponrequest.
B. InstallerQualifications: 1. Utilizeaninstallerexperiencedinperformingworkofthissectionwhoisexperiencedininstallationofworksimilar tothatrequiredforthisprojectandpertheminimumrequirementsofMSSSP-89.
C. Conductpre-installationmeetingtoverifyprojectrequirements,coordinatewithothertrades,andestablishconditionand completenessofsubstrate.Reviewmanufacturer’sinstallationinstructionsandmanufacturer’swarrantyrequirements.
4.7 DELIVERY,STORAGE,ANDHANDLING A. Storeproductsinmanufacturer’sunopenedpackaginguntilreadyforinstallation.
B. Storeanddisposeofsolvent-basedmaterials,andmaterialsusedwithsolvent-basedmaterials,inaccordancewith requirementsoflocalauthoritieshavingjurisdiction.
4.8 PROJECTCONDITIONS A. Maintainenvironmentalconditions(temperature,humidity,andventilation)withinlimitsrecommendedbymanufacturer foroptimumresults.Donotinstallproductsunderenvironmentalconditionsoutsidemanufacturer’sabsolutelimits.
4.9 WARRANTY A. Manufacturer’sWarranty:Submit,forOwner’sacceptance,manufacturer’sstandardwarrantydocumentexecutedby authorizedcompanyofficial.Manufacturer’swarrantyisinadditionto,andnotalimitationof,otherrights,Ownermay haveunderContractDocuments.
PART 5 PRODUCTS 5.1 MANUFACTURERS A. AcceptableManufacturer:AnvilIntl.,Inc.;110CorporateDr.Suite10,Portsmouth,NH03802.ASD.Tel:(603)422-8000. Fax:(603)422-8033.Email:[email protected]:http://www.anvilintl.com.
B. Substitutions:Notpermitted.
C. RequestsforsubstitutionswillbeconsideredinaccordancewithprovisionsofSection016000.
5.2 MANUFACTUREDUNITS-APPLICATIONREQUIREMENTS A. Fabricatehangers,supportsandswaybracestocomplywithbuildingcodes.
B. Donotuseinstalledhangersforriggingorerectionpurposes.
5.5 EQUIPMENTSUPPORTS A. Fabricateequipmentsupportsnotprovidedbyequipmentmanufacturerfromstructuralgradesteelmeetingrequirements ofSection051216-FabricatedFireproofedSteelColumns.
5.6 EQUIPMENTANCHORBOLTSANDTEMPLATES A. Providetemplatestoensureaccuratelocationofanchorbolts.
PART 6 EXECUTION 6.1 EXAMINATION A. Donotbegininstallationuntilsubstrateshavebeenproperlyprepared.
B. Ifsubstratepreparationistheresponsibilityofanotherinstaller,notifyArchitectofunsatisfactorypreparationbeforeproceeding.
6.2 PREPARATION A. Cleansurfacesthoroughlypriortoinstallation.
B. Preparesurfacesusingthemethodsrecommendedbythemanufacturerforachievingthebestresultforthesubstrateunder theprojectconditions.
6.3 HANGERSPACING A. PlumbingPiping:MoststringentrequirementsofPlumbingCode,orauthorityhavingjurisdiction. B. FireProtection:Complywithapplicablefirecode.
C. GasandFuelOilPiping:Complywithpipemanufacturer’srecommendationsandapplicablecodes.
D. CopperPiping:Complywithpipemanufacturer’srecommendationsandapplicablecodes.
E. FlexibleSystemGroovedPipe:Minimumofonehangerrequiredpertheminimumrecommendedpipelength.Comply withgroovemanufacturer’srecommendedaveragehangersperpipelength.
F. Whenpracticallocatedimmediatelyadjacenttoanychangeofdirectionofpipe.Totallengthofpipebetweensupports lessthanthree-fourthsthefullhangerspan.
G. Incaseofconcentratedloads(suchasvalves)thesupportsshallbeplacedascloseaspossible.
6.4 HANGERINSTALLATION A. Installinaccordancewithmanufacturer’sinstructions.
B. ClampsonRiserPiping: 1. Supportindependentofconnectedhorizontalpipeworkusingriserclampsandriserclamplugsweldedtoriser. 2. Bolttighteningtorquesshallbetoindustrystandards. 3. CastIronPipes:Installclampbelowjoint. 4. SteelPipes:Clampisfittedpreferablybelowcouplingorweldedpipelug.
15050-17
HANGERS AND SUPPORTS SECTION 23 05 29
17ANvIL® INTERNATIONAL
Pipe
s, V
alve
s an
d Fi
tting
sfo
r H
VAC
Hea
ting
and
Cool
ing
Syst
ems
Pipe
s, V
alve
s an
d Fi
tting
sfo
r Pl
umbi
ng S
yste
ms
Pipe
s, V
alve
s an
d Fi
tting
sfo
r F
ire
Prot
ectio
n Sy
stem
sPi
ping
Spec
ialti
esBa
sic
Mec
hani
cal
Met
hods
and
Mat
eria
ls H
ange
rs a
ndSu
ppor
ts
C. Useapprovedconstantsupporttypehangerswhere: 1. Forcriticalhightemperaturewhereverticalmovementofpipeworkis1/2inch(12.7mm)ormore. 2. Transferofloadtoadjacenthangersorconnectedequipmentisnotpermitted.
D. Usevariablesupportspringhangerswhere: 1. Transferofloadtoadjacentpipingortoconnectedequipmentisnotcritical. 2. Variationinsupportingeffectdoesnotexceed25percentoftotalload.
E. Adjusthangerstoequalizeload.
F. SupportfromStructuralMembers:Wherestructuralbearingdoesnotexistorinsertsarenotinsuitablelocations,provide supplementarystructuralsteelmembers.
G. Fieldweldingofsupportsshouldbedonebyqualifiedweldersusingqualifiedweldingprocedures.
H. Propercareandventilationshouldbegivenwhenweldinggalvanizedcomponents.
6.5 HORIZONTALMOVEMENT A. Angularityofrodhangerresultingfromhorizontalmovementofpipeworkfromcoldtohotpositionnottoexceed4degrees fromvertical.
B. Wherehorizontalpipemovementisgreaterthan1/2inch(12.7mm),offsetpipehangerandsupportsothatrodhangeris verticalinhotposition.
6.6 FINALADJUSTMENT A. AdjustHangersandSupports: 1. Ensurethatrodisverticalunderoperatingconditions. 2. Equalizeloads.
B. AdjustableClevis: 1. Tightenhangerloadnutsecurelytoensureproperhangerperformance. 2. Tightenuppernutafteradjustment.
C. C-Clamps: 1. Followmanufacturer’srecommendedwritteninstructionsandtorquevalueswhentighteningC-clampstobottom flangeofbeam.
D. BeamClamps: 1. Tightenallsetscrewsandlocknuts. 2. HammerjawfirmlyagainstundersideofbeamforFigure127only.
6.7 PROTECTION A. Protectinstalledproductsuntilcompletionofproject.
B. Touch-up,repairorreplacedamagedproductsbeforeSubstantialCompletion.
ENDOFSECTION
15050-18
SECTION 21 11 00 PIPES, vALvES AND FITTINGS FOR FIRE PROTECTION SYSTEMS
18 ANvIL® INTERNATIONAL
PART 7 GENERAL 7.1 SECTIONINCLUDES A. Scopeofwork: 1. Allareasasindicatedonthedrawingsaretobeprotectedbyanautomaticsuppressionsystem,oftypeasindicated. 2. Wetpipe. 3. Dry-pipe. 4. Wetstandpipe. 5. Dry-standpipe.
B. Contractorshallberesponsiblefordesigningthedistributionsystemsandsizingofthesystemsbyhydrauliccalculation; andshallprovidethenecessaryengineeringdrawingsandcalculationstoobtainacceptanceofallauthoritieshavingjurisdiction.
7.2 RELATEDSECTIONS A. Section078413-PenetrationFirestoppingMortars.
B. Section083116-AccessPanelsandFrames.
C. Section230500-CommonWorkResultsforHVAC.
D. Section230529-HangersandSupportsforHVACPipingandEquipment.
E. Section235000-CentralHeatingEquipment.
7.3 REFERENCES A. ASTMInternational(ASTM)A536-StandardSpecificationforDuctileIronCastings.
B. ManufacturersStandardizationSocietyoftheValveandFittingsIndustry(MSS)SP-127BracingforPipingSystemsSeismic- Wind-DynamicDesign,Selection,Application.
C. NFPA13-Installationofsprinklersystems.
D. NFPA72-Installation,maintenanceanduseofprotectivesignalingdevices.
7.4 SYSTEMDESCRIPTION A. SystemcomponentstobeULlisted/FMapprovedandlabeled.
B. Systemcomponentstobetoberatedforminimumoperatingpressureof175psig.
C. Pipe,Valves,andFittings-Groovedproductsforsteelandcopperfireprotectionsystemsshallbeused.RefertoSection 230500-CommonWorkResultsforHVAC.
D. ProductsshallbeUL/ULClistedandFMapproved.MaterialsshallbeinstalledinaccordancewithcurrentNFPAStandards, localRatingBureauand/orlocalFireMarshallrequirements.
E. Incorporateinconstructionpipehangersandsupportstomanufacturer’srecommendationsutilizingmanufacturer’sregular productioncomponents,partsandassemblies.RefertoSection230529-HangersandSupportsforHVACPipingand Equipment.
7.5 SUBMITTALS A. SubmitunderprovisionsofSection013000.
B. [ProductData]:Manufacturer’sdatasheetsoneachproducttobeused,including: 1. Preparationinstructionsandrecommendations. 2. Installationmethods.
C. Certifications: 1. Productcertificatessignedbymanufacturercertifyingmaterialscomplywithspecifiedperformancecharacteristics andcriteriaandphysicalrequirements.Certificatesshallbefurnishedonlyasrequiredbyspecificcodes,uponrequest.
D. ShopDrawings: 1. Submitshopdrawingsand[ProductData]groupedtoincludecompletesubmittalsofrelatedsystems,products,and accessoriesinasinglesubmittal.
E. CloseoutSubmittals: 1. Warranty:Warrantydocuments. 2. OperationandMaintenanceData:OperationandmaintenancedataforinstalledproductsinaccordancewithDivision1 CloseoutSubmittals(MaintenanceDataandOperationData)Section.Includemethodsformaintaininginstalled products,andprecautionsagainstcleaningmaterialsandmethodsdetrimentaltofinishesandperformance.
7.7 DEFINITION A. “Piping”includesallpipe,fittings,valves,hangers,andothersupportsandaccessoriesrelatedtosuchpiping.
B. “Concealed”meanshiddenfromsightinchases,furredspaces,shafts,hungceilings,embeddedinconstruction,incrawl spacesorburied.
C. “Exposed”meansnotinstalledundergroundor“concealed”asdefinedabove.
D. “FireProtectionWork”isalloftheworkIndicatedorrequiredbytheContractDocuments.
E. “Orequivalent”meanstopossessthesameperformancequalitiesandcharacteristicsandfulfilltheutilitarianfunction withoutanydecreaseinquality,durabilityorlongevity.
F. “Provide”meanstheContractorshall“furnishandinstall”workand/orequipment.
G. “FPC”meanstheFireProtectionContractor.
7.8 DELIVERY,STORAGE,ANDHANDLING A. Storeproductsinmanufacturer’sunopenedpackaginguntilreadyforinstallation.
B. Storeanddisposeofsolvent-basedmaterials,andmaterialsusedwithsolvent-basedmaterials,inaccordancewith requirementsoflocalauthoritieshavingjurisdiction.
7.9 PROJECTCONDITIONS A. Maintainenvironmentalconditions(temperature,humidity,andventilation)withinlimitsrecommendedbymanufacturer foroptimumresults.Donotinstallproductsunderenvironmentalconditionsoutsidemanufacturer’sabsolutelimits.
7.10WARRANTY A. Contractorshallguarantee,inwriting,thatallworkinstalledshallbefreefromanyandalldefectsinworkmanshipand materials;thatallapparatusshalldevelopcapacitiesandcharacteristicsspecified;andthatif,duringtheperiodofone year,orasotherwisespecified,fromthedateofsubstantialcompletion,anydefectsinworkmanship,materialorperformance appear,theContractorshall,withoutcosttotheOwner,remedysuchdefectswithinareasonabletimeasspecifiedin noticefromtheOwner’sRepresentative.Indefaultthereof,theOwner’sRepresentativeshallhavetheworkdoneand chargethecostoftheworktotheContractor.
B. Furnishmanufacturerswrittenwarrantiesforallequipment,statingeffectivedateofWarranty,totheOwner’sRepresentative.
PART 8 PRODUCTS 8.1 MANUFACTURERS A. AcceptableManufacturer:AnvilInternational,whichislocatedat:110CorporateDr.Suite10;Portsmouth,NH03801; Tel:603-422-8000;Fax:603-422-8033;Email:[email protected];Web:www.anvilintl.com
B. Substitutions:Notpermitted.
C. RequestsforsubstitutionswillbeconsideredinaccordancewithprovisionsofSection016000.
8.2 MANUFACTUREDUNITS A. GroovedButterflyValve:GruvlokFigureAE-7722-3A,2to10inches(51mmto254mm).300PSI(2.1MPa)ratedUL/FM approvedgrooved-endwithtwo(2)switches;oneisasupervisoryswitchandtheotherisanauxiliaryswitch.Tamper resistantscrewsshallbeprovidedtoattachthecoveroftheactuator.
B. CheckValves:GruvlokFigure78FP,2to12inches(51to305mm):300PSI(2.1MPa)rated,UL/ULClistedandFM approvedgrooved-end.
C. CouplingsforFireProtectionsSystems-GruvlokUL/ULClistedand/orFMapproved.Figure7000(Flexible)and7400 (Rigidlok)Grade“E”EPDMTypeA,“C”StyleGaskets(DRI-SEAL),TypeEEPDM,orFlushGapGasket.
D. GroovedFittingsforFireProtectionPipingSystems:GruvlokFire-Riteshortpatternfittings,90degreeelbowsandteesin2 to8inches(51mmto203mm)orGruvlokstandardpatternfittings,2to12inches(51to305mm).Castductileconforms toASTMA-536DuctileIrontoGrade65-45-12.Fittingsarepaintedtoindustryspecificationandareavailablegalvanized. Fire-RiteSYMBOL212fittingsareUL/ULClistedandFMapproved.
8.3 SPRINKLERHEADS A. Manufacturer: 1. Viking,Central,Reliableorequal. 2. Type:Refertoscheduleondrawingsforheadtyperequiredfordifferentbuildingareas.
8.4 PIPING A. SteelPiping: 1. RefertoSection230500-CommonWorkResultsforHVAC.
B. CopperPiping: 1. RefertoSection230500-CommonWorkResultsforHVAC.
8.5 ACCESSPANELS A. ProvideaccesspanelsasrequiredbySection083116-AccessPanelsandFrames.
8.6 FIRESTOPPINGMATERIALS A. ProvidefirestoppingassembliesasrequiredbySection078413-PenetrationFirestoppingMortars.
8.7 EQUIPMENTSUPPORTS A. Fabricateequipmentsupportsnotprovidedbyequipmentmanufacturerfromstructuralgradesteelmeetingrequirements ofSection051216-FabricatedFireproofedSteelColumns.
8.8 EQUIPMENTANCHORBOLTSANDTEMPLATES A. Providetemplatestoensureaccuratelocationofanchorbolts.
PART 9 EXECUTION 9.1 EXAMINATION A. Donotbegininstallationuntilsubstrateshavebeenproperlyprepared.
B. Ifsubstratepreparationistheresponsibilityofanotherinstaller,notifyArchitectofunsatisfactorypreparationbeforeproceeding.
C. Contractorshallverifyandobtainfireflowtestdatarequiredfordesign.
9.2 PREPARATION A. Cleansurfacesthoroughlypriortoinstallation.
B. Preparesurfacesusingthemethodsrecommendedbythemanufacturerforachievingthebestresultforthesubstrateunder theprojectconditions.
C. ProvideopeningsasnecessarytopermitinstallationofpipingoranyotherpartofworkunderthisSection.
D. Providesleevesforpipingpenetratingfloorandmasonrywalls.
E. ThisContractorshallberesponsibleforestablishingsizesandlocationsofallopeningsandlintelsinnewworkandto transmitthisinformationtotheContractorwhoseworkisinvolvedatsuchtimeastoavoidcuttingandpatching.
F. Allpatchingshallmatchadjacentsurfaces.
G. ContractorshallinspectandtakenoteofexistingconditionsalongwiththeOwner’sRepresentativetoavoiddisputes regardingtheconditionofexistingsurfacebeforeworkbegan.
H. Openingsthroughexistingconcreteshallbecore-drilledorsawcut.
9.3 INSTALLATION A. Installinaccordancewithmanufacturer’sinstructions.
B. Provideaccesspanelsforaccesstoequipment,valves,orotherspecialtiesinstalledbehindwalloraboveceilingsurfaces.
C. Lay-inacousticalteebarceilingsandsnap-inremovablemetalpanceilingsshallbeconsideredadequateforaccess.
D. FireProtectionContractorshallsubletinstallationworktosubcontractorsspecificallyskilledintheconstructionofthe surfacesinvolved.
E. ContractorshallconferwiththeotherProjectContractorswithrespecttoaccesspanellocationsandshall,wherever practicable,groupdevicesinsuchamannersoastoeliminateasmanypanelsaspossible.
F. Contractorshallremoveallmarkingsandlabelsfromaccesspanels.
G. Cuttingordrillingthrustructuralbeamsorjoistsisnotpermitted.
15050-21
PIPES, vALvES AND FITTINGS FOR FIRE PROTECTION SYSTEMS SECTION 21 11 00
21ANvIL® INTERNATIONAL
Pipe
s, V
alve
s an
d Fi
tting
sfo
r H
VAC
Hea
ting
and
Cool
ing
Syst
ems
Pipe
s, V
alve
s an
d Fi
tting
sfo
r Pl
umbi
ng S
yste
ms
Pipe
s, V
alve
s an
d Fi
tting
sfo
r F
ire
Prot
ectio
n Sy
stem
sPi
ping
Spec
ialti
esBa
sic
Mec
hani
cal
Met
hods
and
Mat
eria
ls H
ange
rs a
ndSu
ppor
ts
H. ProvideallopeningsandsetallsleevesincooperationwithContractorswhoseworkisaffectedthereby.
I. Caulkopeningbetweenpipeandsleevewithfirebarriersealant.
J. Ineventholesmustbeprovidedthroughreinforcedconcrete,theyshallbecarefullydrilledsoastoavoidspallingand unnecessarydamageofweakeningofanystructuralmember;choppingorbreakingoutwillnotbepermitted.
K. ObtainArchitect’sapprovalbeforeprovidingopeningsthroughconcreteormasonryinplaceandthenproceedasdirected.
L. Contractorshallberesponsiblefordamagetofinishedworkresultingfromcuttingordrillingrequiredbecauseofneglect ofContractortoprovideaccurateandsufficientinformation.
N. Complywiththemanufacturer’srequirementsforproperinstallationoffirestopmaterialstoobtaintherequiredfireand/or smokerating.
9.4 COMPENSATIONLOOPS A. Compensationloopsshallbepreparedforshipmentusingacut-to-lengthmetalshippingbar,tackedsecurelybetweenthe elbowsofthetwoparallellegs,tomaintainthemanufacturedlengthduringshipping.Shippingbarmustberemovedprior tosystemstart-up.
B. Compensationloophangerassemblykitshallbeusedtosupportandhangtheloop.TheFMApprovedandULListed SeismicWire/CableassembliesconformtotherequirementsoftheASCE(AmericanSocietyofCivilEngineers)guidelines forstructuralapplicationsofwirerope,inthatthecableispre-stretchedandthepermanentendfittingsmaintainthe breakstrengthofthecablewithasafetyfactoroftwo.
9.5 SPRINKLERHEADS A. Locatesprinklerheads,mainpipingandvalvesasindicatedonthedrawings.
B. Installsprinklerheadstocoordinatewithalllights,grillesandanyotherobstructionsinceiling.
C. Centersprinklerheadsinceilingtileandprovidepipingoffsetsasrequired.
D. Whereceilingistobepaintedorsprayed,applypapercoveroversprinklerheadstoensuretheheadandescutcheonsdo notgetcoated.Removeprotectivepapercoverafterpaintingorsprayingiscompleted.
E. Providemountablemetalboxofspareheadswithproperwrenchforheadreplacement.
9.6 TESTSANDINSPECTIONS A. Contractorshallberesponsiblefortestingandcertificationofsystemsandorderinginspectionsasrequiredbyauthorities havingjurisdiction.
B. AlltestsshallbeconductedinthepresenceofandtothesatisfactionoftheOwneroranauthorizedrepresentative.
C. InspectionsshallbemadebytheOwner’sauthorizedrepresentativeandinspectorshavingjurisdiction.
9.7 PROTECTION A. Afteralltestshavebeenmadeandthesystemspronouncedtobesatisfactory,theContractorshallgooverallwork andcleanequipment,fixtures,andrelatedappurtenancesandpiping,andleavethemcleanandincompleteworking orderatfinalcompletionoftheproject.
B. Protectinstalledproductsuntilcompletionofproject.
C. Touch-up,repairorreplacedamagedproductsbeforeSubstantialCompletion.
ENDOFSECTION
15050-22
SECTION 22 30 00 PIPES, vALvES AND FITTINGS FOR PLUMBING SYSTEMS
22 ANvIL® INTERNATIONAL
PART 10 GENERAL 10.1SECTIONINCLUDES A. Plumbingrequirements.
10.2RELATEDSECTIONS A. Section078413-PenetrationFirestoppingMortars.
B. Section083116-AccessPanelsandFrames.
C. Section230500-CommonWorkResultsforHVAC.
D. Section230529-HangersandSupportsforHVACPipingandEquipment.
E. Section235000-CentralHeatingEquipment.
10.3REFERENCES A. ManufacturersStandardizationSocietyoftheValveandFittingsIndustry(MSS)SP-127BracingforPipingSystemsSeismic- Wind-DynamicDesign,Selection,Application.
B. ContractorDesignRequirements: 1. Incorporateinconstructionpipehangersandsupportstomanufacturer’srecommendationsutilizingmanufacturer’s regularproductioncomponents,partsandassemblies.
10.5SUBMITTALS A. SubmitunderprovisionsofSection013000.
B. [ProductData]:Manufacturer’sdatasheetsoneachproducttobeused,including: 1. Preparationinstructionsandrecommendations. 2. Installationmethods.
C. Certifications: 1. Productcertificatessignedbymanufacturercertifyingmaterialscomplywithspecifiedperformancecharacteristics andcriteriaandphysicalrequirements.Certificatesshallbefurnishedonlyasrequiredbyspecificcodes,uponrequest.
D. ShopDrawings: 1. Submitshopdrawingsand[ProductData]groupedtoincludecompletesubmittalsofrelatedsystems,products,and accessoriesinasinglesubmittal.
E. SelectionSamples:Foreachfinishproductspecified,twocompletesetsofcolorchipsrepresentingmanufacturer’sfull rangeofavailablecolorsandpatterns.
F. VerificationSamples:Foreachfinishproductspecified,twosamples,minimumsize6inches(150mm)square,representing actualproduct,color,andpatterns.
G. CloseoutSubmittals: 1. Warranty:Warrantydocuments. 2. OperationandMaintenanceData:OperationandmaintenancedataforinstalledproductsinaccordancewithDivision1 CloseoutSubmittals(MaintenanceDataandOperationData)Section.Includemethodsformaintaininginstalled products,andprecautionsagainstcleaningmaterialsandmethodsdetrimentaltofinishesandperformance.
10.6QUALITYASSURANCE A. ManufacturerQualifications: 1. ManufacturingfacilitiesshallberegisteredtoISO9001:2000andassessedISO9000.2000standard.Acopyofthecurrent certificateshallbeavailableuponrequest.
B. InstallerQualifications: 1. ContractorshallobtainallnecessarypermitsandlicensespertainingtothisDivision(expensebornebytheContractor) andcomplywithMunicipalandStateCodes,Laws,OrdinancesandRegulations,andtherequirementsofthe NationalFireprotectionAssociation,andpayallfeesandsalestaxesasrequired,andpostallbondsincidentthereto.
C. Conductpre-installationmeetingtoverifyprojectrequirements,coordinatewithothertrades,andestablishconditionand completenessofsubstrate.Reviewmanufacturer’sinstallationinstructionsandmanufacturer’swarrantyrequirements.
10.7DEFINITION A. “Piping”includesallpipe,fittings,valves,hangers,andothersupportsandaccessoriesrelatedtosuchpiping.
B. “Concealed”meanshiddenfromsightinchases,furredspaces,shafts,hungceilings,embeddedinconstruction,incrawl
15050-23
PIPES, vALvES AND FITTINGS FOR PLUMBING SYSTEMS SECTION 22 30 00
23ANvIL® INTERNATIONAL
Pipe
s, V
alve
s an
d Fi
tting
sfo
r H
VAC
Hea
ting
and
Cool
ing
Syst
ems
Pipe
s, V
alve
s an
d Fi
tting
sfo
r Pl
umbi
ng S
yste
ms
Pipe
s, V
alve
s an
d Fi
tting
sfo
r F
ire
Prot
ectio
n Sy
stem
sPi
ping
Spec
ialti
esBa
sic
Mec
hani
cal
Met
hods
and
Mat
eria
ls H
ange
rs a
ndSu
ppor
ts
spacesorburied.
C. “Exposed”meansnotinstalledundergroundor“concealed”asdefinedabove.
D. “FireProtectionWork”isalloftheworkIndicatedorrequiredbytheContractDocuments.
E. “Orequivalent”meanstopossessthesameperformancequalitiesandcharacteristicsandfulfilltheutilitarianfunction withoutanydecreaseinquality,durabilityorlongevity.
F. “Provide”meanstheContractorshall“furnishandinstall”workand/orequipment.
G. “FPC”meanstheFireProtectionContractor.
10.8DELIVERY,STORAGE,ANDHANDLING A. Storeproductsinmanufacturer’sunopenedpackaginguntilreadyforinstallation.
B. Storeanddisposeofsolvent-basedmaterials,andmaterialsusedwithsolvent-basedmaterials,inaccordancewith requirementsoflocalauthoritieshavingjurisdiction.
10.9PROJECTCONDITIONS A. Maintainenvironmentalconditions(temperature,humidity,andventilation)withinlimitsrecommendedbymanufacturer foroptimumresults.Donotinstallproductsunderenvironmentalconditionsoutsidemanufacturer’sabsolutelimits.
10.10 WARRANTY A. Contractorshallguarantee,inwriting,thatallworkinstalledshallbefreefromanyandalldefectsinworkmanshipand materials;thatallapparatusshalldevelopcapacitiesandcharacteristicsspecified;andthatif,duringtheperiodofone year,orasotherwisespecified,fromthedateofsubstantialcompletion,anydefectsinworkmanship,materialorperformance appear,theContractorshall,withoutcosttotheOwner,remedysuchdefectswithinareasonabletimeasspecifiedin noticefromtheOwner’sRepresentative.Indefaultthereof,theOwner’sRepresentativeshallhavetheworkdoneand chargethecostoftheworktotheContractor.
B. Furnishmanufacturerswrittenwarrantiesforallequipment,statingeffectivedateofWarranty,totheOwner’sRepresentative.
PART 11 PRODUCTS 11.1MANUFACTURERS A. AcceptableManufacturer:AnvilInternational,whichislocatedat:110CorporateDr.Suite10;Portsmouth,NH03801; Tel:603-422-8000;Fax:603-422-8033;Email:[email protected];Web:www.anvilintl.com
B. Substitutions:Notpermitted.
C. RequestsforsubstitutionswillbeconsideredinaccordancewithprovisionsofSection016000.
N. TrackHeadBoltsandHexNuts:Couplingsshallbefurnishedwithheattreated,ovalnecktrackheadboltsconformingto ASTMA-183Grade2.Boltsshallmeetminimumtensilestrengthof110,000psi(758KPa).Hexnutsshallbecarbon steelconformingtoASTMA-563GradeA.Boltsandnutsshallbezincelectroplated.
11.3GROOVEDCONNECTIONFLOWCONTROLVALVES A. GruvlokTri-ServiceValves-ModelFTV-S.
15050-25
PIPES, vALvES AND FITTINGS FOR PLUMBING SYSTEMS SECTION 22 30 00
11.4PIPING A. SteelPiping: 1. RefertoSection230500-CommonWorkResultsforHVAC.
B. CopperPiping: 1. RefertoSection230500-CommonWorkResultsforHVAC.
C. StainlessSteelPiping: 1. RefertoSection230500-CommonWorkResultsforHVAC.
D. AluminumPiping: 1. RefertoSection230500-CommonWorkResultsforHVAC.
E. SteelPiping: 1. RefertoSection230500-CommonWorkResultsforHVAC.
F. PlasticPiping: 1. RefertoSection230500-CommonWorkResultsforHVAC.
11.5ACCESSPANELS A. ProvideaccesspanelsasrequiredbySection083116-AccessPanelsandFrames.
11.6FIRESTOPPINGMATERIALS A. ProvidefirestoppingassembliesasrequiredbySection078413-PenetrationFirestoppingMortars.
11.7EQUIPMENTSUPPORTS A. Fabricateequipmentsupportsnotprovidedbyequipmentmanufacturerfromstructuralgradesteelmeetingrequirements ofSection051216-FabricatedFireproofedSteelColumns.
11.8EQUIPMENTANCHORBOLTSANDTEMPLATES A. Providetemplatestoensureaccuratelocationofanchorbolts.
15050-26
SECTION 22 30 00 PIPES, vALvES AND FITTINGS FOR PLUMBING SYSTEMS
26 ANvIL® INTERNATIONAL
PART 12 EXECUTION 12.1EXAMINATION A. Donotbegininstallationuntilsubstrateshavebeenproperlyprepared.
B. Ifsubstratepreparationistheresponsibilityofanotherinstaller,notifyArchitectofunsatisfactorypreparationbeforeproceeding.
12.2PREPARATION A. Cleansurfacesthoroughlypriortoinstallation.
B. Preparesurfacesusingthemethodsrecommendedbythemanufacturerforachievingthebestresultforthesubstrateunder theprojectconditions.
C. ProvideopeningsasnecessarytopermitinstallationofpipingoranyotherpartofworkunderthisSection.
D. Providesleevesforpipingpenetratingfloorandmasonrywalls.
E. ThisContractorshallberesponsibleforestablishingsizesandlocationsofallopeningsandlintelsinnewworkandto transmitthisinformationtotheContractorwhoseworkisinvolvedatsuchtimeastoavoidcuttingandpatching.
F. Allpatchingshallmatchadjacentsurfaces.
G. ContractorshallinspectandtakenoteofexistingconditionsalongwiththeOwner’sRepresentativetoavoiddisputes regardingtheconditionofexistingsurfacebeforeworkbegan.
H. Openingsthroughexistingconcreteshallbecore-drilledorsawcut.
12.3INSTALLATION A. Installinaccordancewithmanufacturer’sinstructions.
12.5PROTECTION A. Protectinstalledproductsuntilcompletionofproject.
B. Touch-up,repairorreplacedamagedproductsbeforeSubstantialCompletion.
ENDOFSECTION
15050-27
PIPES, vALvES AND FITTINGS FOR HvAC HEATING AND COOLING SYSTEMS SECTION 23 60 00
27ANvIL® INTERNATIONAL
Pipe
s, V
alve
s an
d Fi
tting
sfo
r H
VAC
Hea
ting
and
Cool
ing
Syst
ems
Pipe
s, V
alve
s an
d Fi
tting
sfo
r Pl
umbi
ng S
yste
ms
Pipe
s, V
alve
s an
d Fi
tting
sfo
r F
ire
Prot
ectio
n Sy
stem
sPi
ping
Spec
ialti
esBa
sic
Mec
hani
cal
Met
hods
and
Mat
eria
ls H
ange
rs a
ndSu
ppor
ts
PART 13 GENERAL 13.1SECTIONINCLUDES A. HVACrequirements.
13.2RELATEDSECTIONS A. Section078413-PenetrationFirestoppingMortars.
B. Section083116-AccessPanelsandFrames.
C. Section230500-CommonWorkResultsforHVAC.
D. Section230529-HangersandSupportsforHVACPipingandEquipment.
E. Section235000-CentralHeatingEquipment.
13.3REFERENCES A. ManufacturersStandardizationSocietyoftheValveandFittingsIndustry(MSS)SP-127BracingforPipingSystemsSeismic- Wind-DynamicDesign,Selection,Application.
B. ContractorDesignRequirements: 1. Incorporateinconstructionpipehangersandsupportstomanufacturer’srecommendationsutilizingmanufacturer’s regularproductioncomponents,partsandassemblies.
13.5SUBMITTALS A. SubmitunderprovisionsofSection013000.
B. [ProductData]:Manufacturer’sdatasheetsoneachproducttobeused,including: 1. Preparationinstructionsandrecommendations. 2. Installationmethods.
C. Certifications: 1. Productcertificatessignedbymanufacturercertifyingmaterialscomplywithspecifiedperformancecharacteristics andcriteriaandphysicalrequirements.Certificatesshallbefurnishedonlyasrequiredbyspecificcodes,uponrequest.
D. ShopDrawings: 1. Submitshopdrawingsand[ProductData]groupedtoincludecompletesubmittalsofrelatedsystems,products,and accessoriesinasinglesubmittal.
E. CloseoutSubmittals: 1. Warranty:Warrantydocuments. 2. OperationandMaintenanceData:OperationandmaintenancedataforinstalledproductsinaccordancewithDivision1 CloseoutSubmittals(MaintenanceDataandOperationData)Section.Includemethodsformaintaininginstalled products,andprecautionsagainstcleaningmaterialsandmethodsdetrimentaltofinishesandperformance.
13.6QUALITYASSURANCE A. ManufacturerQualifications: 1. ManufacturingfacilitiesshallberegisteredtoISO9001:2000andassessedtoISO9000.2000standard.Acopyofthe currentcertificateshallbeavailableuponrequest.
B. InstallerQualifications: 1. ContractorshallobtainallnecessarypermitsandlicensespertainingtothisDivision(expensebornebytheContractor) andcomplywithMunicipalandStateCodes,Laws,OrdinancesandRegulations,andtherequirementsoftheNational FireprotectionAssociation,andpayallfeesandsalestaxesasrequired,andpostallbondsincidentthereto.
C. Conductpre-installationmeetingtoverifyprojectrequirements,coordinatewithothertrades,andestablishconditionsand completenessofsubstrate.Reviewmanufacturer’sinstallationinstructionsandmanufacturer’swarrantyrequirements.
13.7DEFINITION A. “Piping”includesallpipe,fittings,valves,hangers,andothersupportsandaccessoriesrelatedtosuchpiping.
B. “Concealed”meanshiddenfromsightinchases,furredspaces,shafts,hungceilings,embeddedinconstruction,incrawl spacesorburied.
C. “Exposed”meansnotinstalledundergroundor“concealed”asdefinedabove.
D. “FireProtectionWork”isalloftheworkIndicatedorrequiredbytheContractDocuments.
E. “Orequivalent”meanstopossessthesameperformancequalitiesandcharacteristicsandfulfilltheutilitarianfunction
15050-28
SECTION 23 60 00 PIPES, vALvES AND FITTINGS FOR HvAC HEATING AND COOLING SYSTEMS
F. “Provide”meanstheContractorshall“furnishandinstall”workand/orequipment.
G. “FPC”meanstheFireProtectionContractor.
13.8DELIVERY,STORAGE,ANDHANDLING A. Storeproductsinmanufacturer’sunopenedpackaginguntilreadyforinstallation.
B. Storeanddisposeofsolvent-basedmaterials,andmaterialsusedwithsolvent-basedmaterials,inaccordancewith requirementsoflocalauthoritieshavingjurisdiction.
13.9PROJECTCONDITIONS A. Maintainenvironmentalconditions(temperature,humidity,andventilation)withinlimitsrecommendedbymanufacturer foroptimumresults.Donotinstallproductsunderenvironmentalconditionsoutsidemanufacturer’sabsolutelimits.
13.10WARRANTY A. Contractorshallguarantee,inwriting,thatallworkinstalledshallbefreefromanyandalldefectsinworkmanshipand materials;thatallapparatusshalldevelopcapacitiesandcharacteristicsspecified;andthatif,duringtheperiodofone year,orasotherwisespecified,fromthedateofsubstantialcompletion,anydefectsinworkmanship,materialorperformance appear,theContractorshall,withoutcosttotheOwner,remedysuchdefectswithinareasonabletimeasspecifiedin noticefromtheOwner’sRepresentative.Indefaultthereof,theOwner’sRepresentativeshallhavetheworkdoneand chargethecostoftheworktotheContractor. B. Furnishmanufacturerswrittenwarrantiesforallequipment,statingeffectivedateofWarranty,totheOwner’sRepresentative.
PART 14 PRODUCTS 14.1MANUFACTURERS A. AcceptableManufacturer:AnvilInternational,whichislocatedat:110CorporateDr.Suite10;Portsmouth,NH03801; Tel:603-422-8000;Fax:603-422-8033;Email:[email protected];Web:www.anvilintl.com
B. Substitutions:Notpermitted.
C. RequestsforsubstitutionswillbeconsideredinaccordancewithprovisionsofSection016000.
N. TrackHeadBoltsandHexNuts:Couplingsshallbefurnishedwithheat-treated;ovalnecktrackheadboltsconformingto ASTMA-183Grade2.Boltsshallmeetminimumtensilestrengthof110,000psi(758KPa).Hexnutsshallbecarbon steelconformingtoASTMA-563GradeA.Boltsandnutsshallbezincelectroplated.
14.3GROOVEDCONNECTIONFLOWCONTROLVALVES A. GroovedButterflyValve:GruvlokSeries7700andSeries8000GRgroovedbutterflyvalves.ServiceusageforBalancing andOn/Offservice. 1. Series7700:ButterflyValve-Sizes2inchesto12inches(51mmto305mm).ListedinaccordancewithMSS SP-67.Bubbletightat300psig(2.1MPa).Body-DuctileIron,availablewithstandardnylonbodycoatingorepoxy bodycoated.Disc-DuctileIronwithEPDMencapsulation.Operatingtemperature-40degreesFto+230degreesF(-40 degreesCto110degreesC).(Optional-NitrileDiscencapsulation)Operatingtemperatureupto+180degreesF(82
15050-30
SECTION 23 60 00 PIPES, vALvES AND FITTINGS FOR HvAC HEATING AND COOLING SYSTEMS
D. GroovedSuctionDiffusers:ShallbeGruvlokSeries7250.Sizes2-1/2inchesto16inches(64mmto406mm).Body- DuctileorMalleableIronbodyforsizes2-1/2inchesby2-1/2inchesthrough10inchesby8inches(64mmby64mm through254mmby203mm).Body-CarbonsteeltoASTMA-53bodyforsizes10inchesby10inchesthrough16 inchesby14inches(254mmby254mmthrough406mmby356mm).300psig(1.9KPa).StrainerBasket-Stainless steel(3/16inchperf.)(4.76mmperf.)Withstart-up#16meshpre-filterremovablescreen.Blow-downandgageplug standard.
E. FlexibleConnectors:Sizes2inchesto12inches(51mmto305mm).Stainlesssteeltubeandbraiddesign.Carbonsteel grooved,threaded&flangedend.Ratedworkingpressure150to300psi(1.0to2.0KPa).
F. TripleDutyCombinationValves:ShallbeGruvlok“Tri-Service”(FTV-A/FTV-S)servicevalves.Sizes2-1/2inchesto12 inches(64mmto305mm).Services-Combinationshut-off,non-slamsilentcheckandfullthrottling.Throttlingflow indicatorisstandard.Horizontalorverticalserviceusage.Flowmeasurementportsoneithersideofvalvebody.Fixed orportablemetersavailablefordifferentialpressuremeasurement.
G. CalibratedCircuit(Setter)BalancingValves:ShallbeGBV-Gruvlok“CircuitBalancing”Valve.Sizes1/2inchto12inches (13mmto305mm).Multi-turnadjustment.Positiveshut-off.Tamper-proofmemorystop.Pressuredifferentialread-out ports.DifferentialPressureMeter-ProvideCBVdifferentialpressuremeter/transducerasrequired.DirectFlowreadout. Proportionalbalancing.
H. AutomaticAirVents-GruvlokModelsGAV-15rated150psigandGAV-30rated300psig.
14.5PIPING A. SteelPiping: 1. RefertoSection230500-CommonWorkResultsforHVAC.
B. CopperPiping: 1. RefertoSection230500-CommonWorkResultsforHVAC.
C. StainlessSteelPiping: 1. RefertoSection230500-CommonWorkResultsforHVAC.
D. AluminumPiping: 1. RefertoSection230500-CommonWorkResultsforHVAC.
E. SteelPiping: 1. RefertoSection230500-CommonWorkResultsforHVAC.
F. PlasticPiping: 1. RefertoSection230500-CommonWorkResultsforHVAC.
14.6ACCESSPANELS A. ProvideaccesspanelsasrequiredbySection083116-AccessPanelsandFrames.
14.7FIRESTOPPINGMATERIALS A. ProvidefirestoppingassembliesasrequiredbySection078413-PenetrationFirestoppingMortars.
14.8EQUIPMENTSUPPORTS A. Fabricateequipmentsupportsnotprovidedbyequipmentmanufacturerfromstructuralgradesteelmeetingrequirements ofSection051216-FabricatedFireproofedSteelColumns.
14.9EQUIPMENTANCHORBOLTSANDTEMPLATES A. Providetemplatestoensureaccuratelocationofanchorbolts.
15050-32
SECTION 23 60 00 PIPES, vALvES AND FITTINGS FOR HvAC HEATING AND COOLING SYSTEMS
32 ANvIL® INTERNATIONAL
PART 15 EXECUTION 15.1EXAMINATION A. Donotbegininstallationuntilsubstrateshavebeenproperlyprepared.
B. Ifsubstratepreparationistheresponsibilityofanotherinstaller,notifyArchitectofunsatisfactorypreparationbeforeproceeding.
15.2PREPARATION A. Cleansurfacesthoroughlypriortoinstallation.
B. Preparesurfacesusingthemethodsrecommendedbythemanufacturerforachievingthebestresultforthesubstrateunder theprojectconditions.
C. ProvideopeningsasnecessarytopermitinstallationofpipingoranyotherpartofworkunderthisSection.
D. Providesleevesforpipingpenetratingfloorandmasonrywalls.
E. ThisContractorshallberesponsibleforestablishingsizesandlocationsofallopeningsandlintelsinnewworkandto transmitthisinformationtotheContractorwhoseworkisinvolvedatsuchtimeastoavoidcuttingandpatching.
F. Allpatchingshallmatchadjacentsurfaces.
G. ContractorshallinspectandtakenoteofexistingconditionsalongwiththeOwner’sRepresentativetoavoiddisputes regardingtheconditionofexistingsurfacebeforeworkbegan.
H. Openingsthroughexistingconcreteshallbecore-drilledorsawcut.
15.3INSTALLATION A. Installinaccordancewithmanufacturer’sinstructions.
15.5PROTECTION A. Protectinstalledproductsuntilcompletionofproject.
B. Touch-up,repairorreplacedamagedproductsbeforeSubstantialCompletion.
ENDOFSECTION
15050-33
PIPING SPECIALTIES SECTION 23 50 00
33ANvIL® INTERNATIONAL
Pipe
s, V
alve
s an
d Fi
tting
sfo
r H
VAC
Hea
ting
and
Cool
ing
Syst
ems
Pipe
s, V
alve
s an
d Fi
tting
sfo
r Pl
umbi
ng S
yste
ms
Pipe
s, V
alve
s an
d Fi
tting
sfo
r F
ire
Prot
ectio
n Sy
stem
sPi
ping
Spec
ialti
esBa
sic
Mec
hani
cal
Met
hods
and
Mat
eria
ls H
ange
rs a
ndSu
ppor
ts
PART 16 GENERAL 16.1SECTIONINCLUDES A. Specialtypipedsystems.
16.2RELATEDSECTIONS A. Section078413-PenetrationFirestoppingMortars.
B. Section083116-AccessPanelsandFrames.
C. Section230500-CommonWorkResultsforHVAC.
D. Section230529-HangersandSupportsforHVACPipingandEquipment.
16.3REFERENCES A. AmericanSocietyofMechanicalEngineers(ASME)B31.1-PowerPiping(SIEdition).
B. AmericanSocietyofMechanicalEngineers(ASME)B31.3-ChemicalPlantandPetroleumRefineryPiping.
C. ManufacturersStandardizationSocietyoftheValveandFittingsIndustry(MSS)SP-127BracingforPipingSystemsSeismic- Wind-DynamicDesign,Selection,Application.
B. ContractorDesignRequirements: 1. Incorporateinconstructionpipehangersandsupportstomanufacturer’srecommendationsutilizingmanufacturer’s regularproductioncomponents,partsandassemblies.
16.5SUBMITTALS A. SubmitunderprovisionsofSection013000.
B. [ProductData]:Manufacturer’sdatasheetsoneachproducttobeused,including: 1. Preparationinstructionsandrecommendations. 2. Installationmethods.
C. Certifications: 1. Productcertificatessignedbymanufacturercertifyingmaterialscomplywithspecifiedperformancecharacteristics andcriteriaandphysicalrequirements.Certificatesshallbefurnishedonlyasrequiredbyspecificcodes,uponrequest.
E. SelectionSamples:Foreachfinishproductspecified,twocompletesetsofcolorchipsrepresentingmanufacturer’sfull rangeofavailablecolorsandpatterns.
F. VerificationSamples:Foreachfinishproductspecified,twosamples,minimumsize6inches(150mm)square,representing actualproduct,color,andpatterns.
G. CloseoutSubmittals: 1. Warranty:Warrantydocuments. 2. OperationandMaintenanceData:OperationandmaintenancedataforinstalledproductsinaccordancewithDivision1 CloseoutSubmittals(MaintenanceDataandOperationData)Section.Includemethodsformaintaininginstalled products,andprecautionsagainstcleaningmaterialsandmethodsdetrimentaltofinishesandperformance.
16.6QUALITYASSURANCE A. ManufacturerQualifications: 1. ManufacturingfacilitiesshallberegisteredtoISO9001:2000andassessedtoISO9000.2000standard.Acopyofthe currentcertificateshallbeavailableuponrequest.
B. InstallerQualifications: 1. ContractorshallobtainallnecessarypermitsandlicensespertainingtothisDivision(expensebornebytheContractor) andcomplywithMunicipalandStateCodes,Laws,OrdinancesandRegulations,andtherequirementsoftheNational FireprotectionAssociation,andpayallfeesandsalestaxesasrequired,andpostallbondsincidentthereto.
C. Conductpre-installationmeetingtoverifyprojectrequirements,coordinatewithothertrades,establishconditionand completenessofsubstrate.Reviewmanufacturer’sinstallationinstructionsandmanufacturer’swarrantyrequirements.
16.7DEFINITION A. “Piping”includesallpipe,fittings,valves,hangers,andothersupportsandaccessoriesrelatedtosuchpiping.
15050-34
SECTION 23 50 00 PIPING SPECIALTIES
34 ANvIL® INTERNATIONAL
B. “Concealed”meanshiddenfromsightinchases,furredspaces,shafts,hungceilings,embeddedinconstruction,incrawl spacesorburied.
C. “Exposed”meansnotinstalledundergroundor“concealed”asdefinedabove.
D. “FireProtectionWork”isalloftheworkIndicatedorrequiredbytheContractDocuments.
E. “Orequivalent”meanstopossessthesameperformancequalitiesandcharacteristicsandfulfilltheutilitarianfunction withoutanydecreaseinquality,durabilityorlongevity.
F. “Provide”meanstheContractorshall“furnishandinstall”workand/orequipment.
G. “FPC”meanstheFireProtectionContractor.
16.8DELIVERY,STORAGE,ANDHANDLING A. Storeproductsinmanufacturer’sunopenedpackaginguntilreadyforinstallation.
B. Storeanddisposeofsolvent-basedmaterials,andmaterialsusedwithsolvent-basedmaterials,inaccordancewithrequirements oflocalauthoritieshavingjurisdiction.
16.9PROJECTCONDITIONS A. Maintainenvironmentalconditions(temperature,humidity,andventilation)withinlimitsrecommendedbymanufacturer foroptimumresults.Donotinstallproductsunderenvironmentalconditionsoutsidemanufacturer’sabsolutelimits.
16.10WARRANTY A. Contractorshallguarantee,inwriting,thatallworkinstalledshallbefreefromanyandalldefectsinworkmanshipand materials;thatallapparatusshalldevelopcapacitiesandcharacteristicsspecified;andthatif,duringtheperiodofone year,orasotherwisespecified,fromthedateofsubstantialcompletion,anydefectsinworkmanship,materialorperformance appear,theContractorshall,withoutcosttotheOwner,remedysuchdefectswithinareasonabletimeasspecifiedin noticefromtheOwner’sRepresentative.Indefaultthereof,theOwner’sRepresentativeshallhavetheworkdoneand chargethecostoftheworktotheContractor.
B. Furnishmanufacturerswrittenwarrantiesforallequipment,statingeffectivedateofWarranty,totheOwner’sRepresentative.
PART 17 PRODUCTS 17.1MANUFACTURERS A. AcceptableManufacturer:AnvilInternational,whichislocatedat:110CorporateDr.Suite10;Portsmouth,NH03801; Tel:603-422-8000;Fax:603-422-8033;Email:[email protected];Web:www.anvilintl.com
B. Substitutions:Notpermitted.
C. RequestsforsubstitutionswillbeconsideredinaccordancewithprovisionsofSection016000.
F. GroovedSuctionDiffusers:ShallbeGruvlokSeries7250.Sizes2-1/2inchesto16inches(64mmto406mm).Body- DuctileorMalleableIronbodyforsizes2-1/2inchesby2-1/2inchesthrough10inchesby8inches(64mmby64mm through254mmby203mm).Body-CarbonsteeltoASTMA-53bodyforsizes10inchesby10inchesthrough16inches by14inches(254mmby254mmthrough406mmby356mm).300psig(1.9KPa).StrainerBasket-Stainlesssteel (3/16inchperf.)(4.76mmperf.)Withstart-up#16meshpre-filterremovablescreen.Blow-downandgageplugstandard.
G. FlexibleConnectors:Sizes2inchesto12inches(51mmto305mm).Stainlesssteeltubeandbraiddesign.Carbonsteel grooved,threaded&flangedend.Ratedworkingpressure150to300psi(1.0to2.0KPa).
H. TripleDutyCombinationValves:ShallbeGruvlok“Tri-Service”(FTV-A/FTV-S)servicevalves.Sizes2-1/2inchesto12 inches(64mmto305mm).Services-Combinationshut-off,non-slamsilentcheckandfullthrottling.Throttlingflow indicatorisstandard.Horizontalorverticalserviceusage.Flowmeasurementportsoneithersideofvalvebody.Fixed orportablemetersavailablefordifferentialpressuremeasurement.
I. CalibratedCircuit(Setter)BalancingValves:ShallbeGBV-Gruvlok“CircuitBalancing”Valve.Sizes1/2inchto12inches (13mmto305mm).Multi-turnadjustment.Positiveshut-off.Tamper-proofmemorystop.Pressuredifferentialread-out ports.DifferentialPressureMeter-ProvideCBVdifferentialpressuremeter/transducerasrequired.DirectFlowreadout. Proportionalbalancing.
J. AutomaticAirVents-GruvlokModelsGAV-15rated150psigandGAV-30rated300psig.
17.3PIPING A. SteelPiping: 1. RefertoSection230500-CommonWorkResultsforHVAC.
B. CopperPiping: 1. RefertoSection230500-CommonWorkResultsforHVAC.
C. StainlessSteelPiping: 1. RefertoSection230500-CommonWorkResultsforHVAC.
D. AluminumPiping: 1. RefertoSection230500-CommonWorkResultsforHVAC.
E. SteelPiping: 1. RefertoSection230500-CommonWorkResultsforHVAC.
F. PlasticPiping: 1. RefertoSection230500-CommonWorkResultsforHVAC.
17.4ACCESSPANELS A. ProvideaccesspanelsasrequiredbySection083116-AccessPanelsandFrames.
15050-36
SECTION 23 50 00 PIPING SPECIALTIES
36 ANvIL® INTERNATIONAL
17.5FIRESTOPPINGMATERIALS A. ProvidefirestoppingassembliesasrequiredbySection078413-PenetrationFirestoppingMortars.
17.6EQUIPMENTSUPPORTS A. Fabricateequipmentsupportsnotprovidedbyequipmentmanufacturerfromstructuralgradesteelmeetingrequirements ofSection051216-FabricatedFireproofedSteelColumns.
17.7EQUIPMENTANCHORBOLTSANDTEMPLATES A. Providetemplatestoensureaccuratelocationofanchorbolts.
PART 18 EXECUTION 18.1EXAMINATION A. Donotbegininstallationuntilsubstrateshavebeenproperlyprepared.
B. Ifsubstratepreparationistheresponsibilityofanotherinstaller,notifyArchitectofunsatisfactorypreparationbeforeproceeding.
18.2PREPARATION A. Cleansurfacesthoroughlypriortoinstallation.
B. Preparesurfacesusingthemethodsrecommendedbythemanufacturerforachievingthebestresultforthesubstrateunder theprojectconditions.
C. ProvideopeningsasnecessarytopermitinstallationofpipingoranyotherpartofworkunderthisSection.
D. Providesleevesforpipingpenetratingfloorandmasonrywalls.
E. ThisContractorshallberesponsibleforestablishingsizesandlocationsofallopeningsandlintelsinnewworkandto transmitthisinformationtotheContractorwhoseworkisinvolvedatsuchtimeastoavoidcuttingandpatching.
F. Allpatchingshallmatchadjacentsurfaces.
G. ContractorshallinspectandtakenoteofexistingconditionsalongwiththeOwner’sRepresentativetoavoiddisputes regardingtheconditionofexistingsurfacebeforeworkbegan.
H. Openingsthroughexistingconcreteshallbecore-drilledorsawcut.
18.3INSTALLATION A. Installinaccordancewithmanufacturer’sinstructions.
18.4PROTECTION A. Protectinstalledproductsuntilcompletionofproject.
B. Touch-up,repairorreplacedamagedproductsbeforeSubstantialCompletion.
ENDOFSECTION
NOTES
37ANvIL® INTERNATIONAL
NOTES
38 ANvIL® INTERNATIONAL
B U I l d I n g C O n n e C t I O n S t h At l A S t
For over 150 years, Anvil has worked diligently to build a strong, vibrant tradition of making connections — from pipe to pipe and people to people.
We pride ourselves in providing the finest-quality pipe products and
services with integrity and dedication to superior customer service at all levels.
We provide expertise and product solutions for a wide range of applications,
from plumbing, mechanical, HVAC, industrial and fire protection to mining,
oil and gas. Our comprehensive line of products includes: grooved pipe
couplings, grooved and plain-end fittings, valves, cast and malleable iron fittings,
forged steel fittings, steel pipe nipples and couplings, pipe hangers and supports,
channel and strut fittings, mining and oil field fittings, along with much more.
As an additional benefit to our customers, Anvil offers a complete and
comprehensive Design Services Analysis for mechanical equipment rooms, to
help you determine the most effective and cost-efficient piping solutions.
Anvil is a proud member of the United States Green Building Council (USGBC).
Go to the Anvil website to obtain manufacturer recycled certificates and other
Green information.
At Anvil, we believe that responsive and accessible customer support is
what makes the difference between simply delivering products —
and delivering solutions.
B R A n d S O f A n v I l I n t e R n At I O n A l
Anvil® product lines include malleable and cast iron fittings, unions and flanges; seamless steel pipe nipples; steel pipe couplings; universal anvilets; forged steel fittings and unions; pipe hangers and supports; threaded rod; and engineered hangers.
The Gruvlok® product line consists of couplings for grooved and plain-end fittings, butterfly valves and check valves; flanges; pump protection components; pipe grooving tools; as well as copper and stainless steel system components.
Anvil-Strut™ products include a complete line of channel in stock lengths of 10 and 20 feet, with custom lengths available upon request. A variety of fittings and accessories are also offered. All products can be ordered in an assortment of finishes and material choices including SupR-Green™, Zinc Trivalent Chromium, pre-galvanized, hot-dipped galvanized, electro-galvanized, aluminum, plain, and stainless steel.
JB Smith™ is the leading manufacturer of oil country tubular fittings, swages and bull plugs – all meeting API specifications. Offering tubing nipples, casing nipples as well as a full line of traditional line pipe and oil country threads in every schedule, JB Smith is the resource for all your oilfield needs.
Catawissa™ NACE and API approved wing unions for Standard Service are offered in non-pressure seal ends as well as threaded and butt weld, and are interchangeable with most leading union manufacturers. Fully traceable and available with complete mill certifications, Catawissa’s oilfield wing union product line includes the standard ball-and-cone design plus our unique Figure 300 Flat Face design, where space and pipe line separation are a consideration.
AnvilStar™ offers a complete line of products for the fire protection industry, including Gruvlok® couplings, fittings, flanges; valves, and roll groovers; steel pipe nipples and couplings; cast and malleable iron threaded and flanged fittings; pipe hangers and supports; Merit® tee-lets, drop nipples; steel welding flanges; SPF grooved couplings, fittings, and flanges; SPF cast iron and ductile iron threaded fittings, o’lets, steel pipe nipples; and Mueller valves and indicator posts.
The SPF/Anvil™ product line includes a variety of internationally sourced products such as grooved couplings, fittings and flanges, cast iron, malleable iron and ductile iron threaded fittings, steel pipe nipples, as well as o’lets.
The Merit® product line includes a variety of tee-lets, drop nipples, and steel welding flanges for fire protection applications. Most Merit products are UL/ULC Listed, FM Approved, and rated from 175 to 300 psi.
Beck steel pipe nipples and steel pipe couplings are manufactured in accordance with the ASTM A733 Standard Specification for Welded and Seamless Carbon Steel and Stainless Steel Pipe Nipples. Steel pipe couplings are manufactured in accordance with the ASTM A865 Standard Specification for Threaded Couplings, Steel, Black or Zinc-Coated (Galvanized) Welded or Seamless, for Use in Steel Pipe Joints. Beck API couplings are manufactured in accordance with the API Specification for line pipe.
Canvil® manufactures low pressure hexagon reducer bushings, as well as plugs and hex caps up to 1” in diameter in various finishes including Oil Treat, Phosphate and Electro Galvanized. In addition, Canvil manufactures A105 hex or round material in class 3000 and 6000 pound, forged steel couplings and bar stock products offered as either as normalized (A105N) or non-normalized (A105) that are fully traceable for mechanicals and chemistry through our MTR program.
Anvil International WorldwideCustomer Service CenterTel: 708-885-3000 Fax: 708-534-5441
U.S. RegIOnAl SeRvICe CenteRS
Anvil International CanadaCustomer Service Center390 Second AvenueP.O. Box 40Simcoe, Ontario N3Y 4K9
Tel: 519-426-4551Fax: 519-426-5509
CAnAdA SeRvICe CenteR
www.anvilintl.com
b u i l d i n g c o n n e c t i o n s t h a t l a s t
northern RegionRegional Distribution & Customer Service CenterSeRviCing: Illinois, Indiana, Iowa, Kentucky, Michigan, Minnesota, Nebraska, North and South Dakota, Ohio,West Pennsylvania, West Virginia, Wisconsin
eastern RegionRegional Distribution CenterSeRviCing: Connecticut, Delaware, Florida, Georgia, Maine, Maryland, Massachusetts, New Hampshire, New Jersey,New York, North and South Carolina, East Pennsylvania,Rhode Island, Vermont, Virginia
800 Malleable Road Columbia, PA 17512
Western RegionRegional Distribution CenterSeRviCing: Alaska, Arizona, California, Colorado, Hawaii, Idaho, Montana, Nevada, New Mexico, Oregon, Utah, Washington, Wyoming
1385 Greg Street Sparks, NV 89431
InteRnAtIOnAl SAleS
Mexico, Puerto Rico andlatin AmericaAbraham Quijada, Sales [email protected]
Tel: +1-281-590-4600
U.S. Customer Service Tel: +1-708-885-3000 Fax: +1-708-534-5441
europe and Middle east RegionRick van Meesen, Sales DirectorThe [email protected]
Tel: +31-53-5725570 Fax: +31-53-5725579
U.S. Customer Service Tel: +1-708-885-3000 Fax: +1-708-534-5441