Eliwell IO Extender Integration in Building Expert SmartStruxure Lite Application Tested in SBS Solutions Lab Validated in Field Installations *** We are always looking forward to your feedback about the experi- ence of using this application in a real life situation. For more informa- tion about feedback and references, please see the last page of this document. Developer Integrator Intended for:
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Eliwell IO Extender Integration in Building ExpertSmartStruxure Lite Application
Tested in SBS Solutions LabValidated in Field Installations
*** We are always looking forward to your feedback about the experi-ence of using this application in a real life situation. For more informa-tion about feedback and references, please see the last page of this document.
Schneider Electric Boston ONE Campus 800 Federal Street, Andover, MA 01810-1067 Tel: +1 978 794 0800 AN-MPM-IO-EXTENDER-US.EN.02.2015.v2 www.schneider-electric.com/buildings February 2015
INTRODUCTIONSchneider’s TM171OBM22R, or the Eliwell Free Smart SMC5500050400 units, are cost-effective I/O extenders and connect to a Multi-Purpose Manager (MPM) via Modbus RTU. The TM171OBM22R or the SMC5500050400 adds 6 digital In/out, 5 analog In/out I/O.
HARDWARE REQUIREMENTSRequired hardware for North America
Qty Part Number Description
1 MPM-UN-XX4-5045, MPM-VA-XX4-5045or MPM-VS-XX4-5045 SmartStruxure Lite Multi-Purpose Manager
Schneider Electric Boston ONE Campus 800 Federal Street, Andover, MA 01810-1067 Tel: +1 978 794 0800 AN-MPM-IO-EXTENDER-US.EN.02.2015.v2 www.schneider-electric.com/buildings February 2015
Custom Application I/O Extender
OVERVIEW OF TM171 PRODUCT FAMILY
*Refer to the below for more information on the Schneider TM171OBM22R product Family:
http://shoppingkiosk.schneider-electric.com/doc_info.aspx?DocRef=EIO0000002032&isdvd=False&df=3&gid=281018For more information about the Eliwell SMC5500:
http://www.eliwell.it/product.aspx?id=23134
TM171ACB4OLANSpare partCable provided with Expansion, Display and Keyboard
TM171ACB4OAO_MNeeded for 0-10 V AOLength: 1 or 2 meters
Schneider Electric Boston ONE Campus 800 Federal Street, Andover, MA 01810-1067 Tel: +1 978 794 0800 AN-MPM-IO-EXTENDER-US.EN.02.2015.v2 www.schneider-electric.com/buildings February 2015
INSTALLATION PROCEDURE *if not using the provided database
1. Connect MPM to TM171 via Modbus RS485 and connect terminal A to + and terminal B to -.2. Log in to Building Expert and navigate to Explorer menu.3. Create a Lua PG Object. 4. Copy and paste SSL_TECH_TM171O.lua file in to PG Object.5. Ensure Device configuration in PG Object is set-up for Modbus Device you are using.
NOTE: the script contains additional information regarding configuration. You can edit ID, tag, description and object values. Do not modify register, read only and dependency entries. NOTE: All of the Modbus registers representing the I/O of the TM171 are mapped to object variables in the MPM Building Expert interface. See the examples following.
6. In Explorer tab, add all AV objects referenced in the script.7. Save and run the script.
NOTE: as long as this script is running, you can communicate with any Device. Also, you must click the Save to Database button to ensure all changes are stored to Flash memory.
8. Validate script is running according to the following:• Open output of PG Object to confirm there are no error messages. The PG output prints a message with a time stamp every
time a telegram is received from one of the Devices.• Validate you are receiving correct information and ensure it is sent to the correct Object.
SEQUENCE OF OPERATION
Reading InputsThe delay between each reading is user configurable to reflect desired system performance and intended application. This is useful when requiring a fast response to an input change, or if using many Devices. By default, the delay is set to 30 seconds between readings. Analog and digital inputs on each Device are read by the MPM. This operation takes 2 seconds to perform.
Writing Configuration and OutputsConfiguration and Output values are modified on change of value. The MPM checks for a change of value every 5 seconds and applies the change to the Device.
Reading ConfigurationEvery minute, the MPM reads the entire configuration from the IO Extenders. The reading reflects changes if using an internal application script. It takes 5 seconds every minute to perform this operation.
LIMITATIONSWhile it is possible to control multiple Devices using this script, it is not possible to use the Modbus script and Building Expert built-in Modbus Fevices at the same time as they interfere and prevent Devices from functioning. To communicate with multiple Devices using the script, you must use the same communication parameters on each Device.
Schneider Electric Boston ONE Campus 800 Federal Street, Andover, MA 01810-1067 Tel: +1 978 794 0800 AN-MPM-IO-EXTENDER-US.EN.02.2015.v2 www.schneider-electric.com/buildings February 2015
Custom Application I/O Extender
MPM DEFAULT CONFIGURATIONThe provided database and script uses the following configuration. At any time, the below Objects number can be changed to suit the intended application, or when implementing to an existing system.
Name Object DescriptionAnalog Input 1 AV1 NTC input or Digital InputAnalog Input 2 AV2 NTC input or Digital InputAnalog Input 3 AV3 NTC input, Digital Input or Voltage/CurrentAnalog Input 4 AV4 NTC input, Digital Input or Voltage/CurrentAnalog Input 5 AV5 NTC input or Digital InputAnalog Input Config 1 AV6 1= DI, 2 = NTCAnalog Input Config 2 AV7 1= DI, 2 = NTCAnalog Input Config 3 AV8 1= DI, 2 = NTC, 3=4..20mA, 4=0-10V, 5=0-5V, 6=0-1VAnalog Input Config 4 AV9 1= DI, 2 = NTC, 3=4..20mA, 4=0-10V, 5=0-5V, 6=0-1VAnalog Input Config 5 AV10 1= DI, 2 = NTCAnalog Output 1 AV11 PWM output voltageAnalog Output 2 AV12 PWM output voltageAnalog Output 3 AV13 Voltage output 0-10VAnalog Output 4 AV14 Voltage output 0-10VAnalog Output 5 AV15 Voltage output 0-10VAnalog Output Config 1 AV16 Pulse width configurationAnalog Output Config 2 AV17 Pulse width configurationAnalog Output 1 Enable AV18 0 = Digital output, 2 = PWMAnalog Output 2 Enable AV19 0 = Digital output, 2 = PWMDigital Input 1 BV1 Digital InputDigital Input 2 BV2 Digital InputDigital Input 3 BV3 Digital InputDigital Input 4 BV4 Digital InputDigital Input 5 BV5 Digital InputDigital Input 6 BV6 Digital InputDigital Output 1 BV7 Digital OutputDigital Output 2 BV8 Digital OutputDigital Output 3 BV9 Digital OutputDigital Output 4 BV10 Digital OutputDigital Output 5 BV11 Digital OutputDigital Output 6 BV12 Digital Output
Schneider Electric Boston ONE Campus 800 Federal Street, Andover, MA 01810-1067 Tel: +1 978 794 0800 AN-MPM-IO-EXTENDER-US.EN.02.2015.v2 www.schneider-electric.com/buildings February 2015
WIRING DIAGRAM (MPM-UN)
MPM-UNModbus ConnectorsB Serial -A Serial +GND Serial Ground Reference
Schneider Electric Boston ONE Campus 800 Federal Street, Andover, MA 01810-1067 Tel: +1 978 794 0800 AN-MPM-IO-EXTENDER-US.EN.02.2015.v2 www.schneider-electric.com/buildings February 2015
Custom Application I/O Extender
WIRING DIAGRAM (TM171O)
TM1710Top Green ConnectorsDO4 High voltage relay outputDO4 High voltage relay outputNDO3 High voltage relay outputDO2 High voltage relay outputDO1 High voltage relay outputDO6 High voltage relay outputDO6 High voltage relay outputTop RS485 Connector- Connect to MPM terminal B+ Connect to MPM terminal AG Connect to MPM terminal GNDBottom Black ConnectorDI1 Clean contact digital inputDI2 Clean contact digital inputDI3 Clean contact digital inputDI4 Clean contact digital inputDI5 Clean contact digital inputDI6 Clean contact digital inputAI1 NTC input or Digital InputAI2 NTC input or Digital InputAI3 NTC input, Digital Input or Voltage/CurrentAI4 NTC input, Digital Input or Voltage/CurrentAI5 NTC input or Digital InputGND Ground terminalAO2 Low voltage PWM outputAO1 Low voltage PWM outputDO5 Low voltage open collector output5Vdc Auxiliary supply, 20mA max12Vdc Auxiliary supplySupply 12-24 Vac, 24Vdc NOT ISOLATED
Schneider Electric Boston ONE Campus 800 Federal Street, Andover, MA 01810-1067 Tel: +1 978 794 0800 AN-MPM-IO-EXTENDER-US.EN.02.2015.v2 www.schneider-electric.com/buildings February 2015
Feedback and ReferencesWe value your feedback about your experience using this application in a real world environment, and invite you to send us your feedback and comments about your implementation to [email protected].
Disclaimer
Feedback. RESELLER may, but is not obligated to, provide suggestions, comments, or other feedback (“Feedback”) to SCHNEIDER ELECTRIC with respect to the Products. Both parties agree that all Feedback is and shall be given entirely voluntarily and, even if designated as confidential, shall not create any confidentiality obligation for SCHNEIDER ELECTRIC. RESELLER agrees, however, not to provide SCHNEIDER ELECTRIC with any Feedback that is subject to license terms that seek to require any Product, technology, service or documentation incorporating or derived from such Feedback, or any SCHNEIDER ELECTRIC intellectual property, to be licensed or otherwise shared with any third party. Furthermore, SCHNEIDER ELECTRIC and its Affiliates shall be free to use, disclose, reproduce, license or otherwise distribute, and exploit the Feedback provided to SCHNEIDER ELECTRIC as it and they see fit, entirely without obligation or restriction of any kind on account of any intellectual property rights or otherwise.
NOTES
There may be objects within the MPM-UN database that are NOT used in this application
This application has only been tested in a Lab condition; therefore we cannot accept any responsibility for its accuracy.