  • 8/10/2019 Ampacimon Presentation Sth Am

    1/34

    Ampacimon SALiege Science Park,Rue des Chasseurs Ardennais, 34031 Angleurwww.ampacimon.com [email protected]

    http://www.ampacimon.com/mailto:[email protected]:[email protected]://www.ampacimon.com/
  • 8/10/2019 Ampacimon Presentation Sth Am

    2/34

    DLR Principles Ampacimons ADR system overview

    ADR product family Business cases

    Content

  • 8/10/2019 Ampacimon Presentation Sth Am

    3/34

    Connect more capacity to your existing grid in amatter of months rather than years Minimize curtailment of power due to network

    congestion

    Improve security of supply Quickly, economically & safely solve congestion

    issues

    Monitor overhead line clearances & guaranteecompliance

    Reduce impact of lines outages during scheduledmaintenance

    3

    Problems we can solve

  • 8/10/2019 Ampacimon Presentation Sth Am

    4/34

    DLRPrinciple

  • 8/10/2019 Ampacimon Presentation Sth Am

    5/34

    5

    Sea

    Seasonal

    ratingLine Capacity Dynamic Line Rating (DLR)

    DLR allows: To uncover the fullavailable line capacity (aka ampacity ) To get closer to the limit, with the same level of security

    From darkness to light.

  • 8/10/2019 Ampacimon Presentation Sth Am

    6/34

    Sag (Clearance) is the most critical limit to the operation of anoverhead-line

    Typically maximum sag will be reached at temperatures belowmaximum conductor temperature Direct sag measurement is the safest monitoring method REAL-TIME measurement of Sag: the only DLR system closing the

    loop with a direct measurement of Sag

    6

    Principle

  • 8/10/2019 Ampacimon Presentation Sth Am

    7/34

    0 500 1000 1500 2000 2500

    0

    20

    40

    60

    80

    100

    Current per subconductor [A ]

    A v e r a g e c o n

    d u c

    t o r

    t e m p e r a

    t u r e

    [ C ]

    Temperature vs. Current simulation [570.22 AMS] alpha=0.9 epsilon=0.7

    v = 0.5 m/s (angle= 90,T a =20C,P sun =800W/m 2)

    v = 2 m/s (angle=90,T a=20C,P sun =800W/m2)

    v = 5 m/s (angle=90,T a=20C,P sun =800W/m2)

    75 C

    2000A1500A

    7

    x 1.5

    x 2

    Actualline capacity

    Max. sag

    Design (reference)v=0.5 m/s

    Load [A]

    Conductor temperature [

    C] vs. Line load [Amps] (570mm 2 Aluminium-alloy conductor)

    Max.Temperature

    Seasonalrating

    but line capacity is very sensitive to low

    windspeed

    1000 A

    Line capacity is designed for theworst case.

  • 8/10/2019 Ampacimon Presentation Sth Am

    8/34

    FundamentalFrequency [Hz]

    Sag [m]

    0.1367 4 10 -4 16.40 0.1

    21

    2 328

    2 f

    gs

    T L gms

    mT

    Lk f k

    ==

    =

    Patented vibration method

  • 8/10/2019 Ampacimon Presentation Sth Am

    9/34

    9

    Validated

  • 8/10/2019 Ampacimon Presentation Sth Am

    10/34

    Principle Weatherstations

    Temperature Inclination ortension

    Ampacimon

    Ease ofinstallation

    Calibration/set-up

    Accuracy

    Intregration indata-flow andbusinessprocesses

    Portability

    Ampacimon vs other methods

  • 8/10/2019 Ampacimon Presentation Sth Am

    11/34

    Reliable measurement method combining direct sag andambient condition measurement Safe/Secure grid operation Reliable 1h and 4h forecast Integration with active network management software (TS2

    link), FACTS and PMUs

    Operations

    Reliable intra-day forecast Reliable day-ahead forecastMarkets

    Reliable DLR planning assumptions Reliable Correlation with weather dependent

    production & consumption loadsPlanning

    11

    DLR: integrated into T/ISOtoolbox

  • 8/10/2019 Ampacimon Presentation Sth Am

    12/34

    Typical Results

  • 8/10/2019 Ampacimon Presentation Sth Am

    13/34

    Products/service offering:The Ampacimon Dynamic Line Rating suite

    DLR planning software, performing rating estimations based on prevailingweather parameters. Typically identifies 5-15% ratings gains, no direct on-line measurements

    The OHL vibrations sensor (patented)

    Real-time data acquisition, sag and ampacity computation software

    Short term (1-4h) ampacity forecast software

    24-48h ampacity forecast software, using predicitive algorithms based onweather modeling combined with historical ampacity real-time acquisition

    A full suite of products enabling T/DSO to maximize the useof their grid, fully integrated within their SCADA/EMS

    13

  • 8/10/2019 Ampacimon Presentation Sth Am

    14/34

  • 8/10/2019 Ampacimon Presentation Sth Am

    15/34

    Sag sensorMeasures lines vibrationsTransmits data through GSM or Xbee network

    On-board wind measurement (patented)In average, one every 3- 5km (more if more complex terrain.less if flat !) Certified up to 400kV (500kV possible)

  • 8/10/2019 Ampacimon Presentation Sth Am

    16/34

    Captures Sag data in Real TimeComputes Real-time Ampacity for each monitored spanComputes line real-time ampacityDashboard of key line parameters for each monitored span

  • 8/10/2019 Ampacimon Presentation Sth Am

    17/34

    Computes a time- series based forecast ampacity over a 1 -4h horizonEliminates very short-term RT ampacity fluctuationsProvides dispatch center operators with a more practical information which can be fed directly into N-1 flow

    simulators

  • 8/10/2019 Ampacimon Presentation Sth Am

    18/34

    Up to 60h-ahead ampacity forecastUses weather-based models, correlated with historical Real-Time ampacity measurementsStatistically reliable, Percentiles can be setUsed for inter-market operations and day-ahead dispatching plans

  • 8/10/2019 Ampacimon Presentation Sth Am

    19/34

    DLR Applications

    19

    REN integration

    Accelerates wind farms integration (no need for new lines)Less curtailment => higher revenue for wind farms

    Infrastructure deployment and optimizationQuick, significant, easy to deploy extra capacity until newinfrastructure is in place or while maintenance is performed

    Market liquidity and security of supply

    Increases X-border capacityGives visibility and transparency on available capacity oncritical linesIncreases security of supplyIncreases markets liquidity and price convergence

  • 8/10/2019 Ampacimon Presentation Sth Am

    20/34

    Maximize usage of existing OVH lines Particularly interesting for wind farms Example:

    A TSO needs to connect 9MW extra wind farm capacity ona 63kV line (static rating 430Amp)New OHL would require new 24m investment, 5 yearsplan and deploymentdone in 3 months, costing 400k

    Gains up to 50% in RT sufficient to debottleneck the line

    REN integration

  • 8/10/2019 Ampacimon Presentation Sth Am

    21/34

    Increase security of supply with existing assets

    Improve interconnections Example:

    Belgium, faced with potential generation shortage needsto maximize interconnections with F and NL

    Equip all 8 interconnections with and

    D-2 forecast allows to increase total (3000MW) importcapacity by 10-15%

    Up to 30% in Real TimeDeployed in 2 months, increase security of supply by300MW !

    Infrastructure optimization

  • 8/10/2019 Ampacimon Presentation Sth Am

    22/34

    Monitors true available capacity, data can be shared withoperators/market participants Reliably forecast bottleneck interconnectors Increases price convergence at a fraction of the cost and time

    of new OHL projects Can be combined with other flexibility devices

    Example: Twenties project

    Market Liquidity

  • 8/10/2019 Ampacimon Presentation Sth Am

    23/34

    www.twenties-project.eu

    Safely, but more aggressively, use an existing regional grid

  • 8/10/2019 Ampacimon Presentation Sth Am

    24/34

    www.twenties-project.eu

    -

    50

    100

    150

    200

    250

    300

    case 1 case 2 case 3 case 4

    M / y e a r

    Cost-Benefits AnalysisCompared to the Business-as-usual case (REF)

    Benefits (M /year)

    Costs (M /year)

    Benefits minus Costs

    Twenties: Benefits at Regional (CWE) level

  • 8/10/2019 Ampacimon Presentation Sth Am

    25/34

    Simple & quick to install(typically 30mn)

    Self powered No maintenance

    25

    Simple and Robust

  • 8/10/2019 Ampacimon Presentation Sth Am

    26/34

  • 8/10/2019 Ampacimon Presentation Sth Am

    27/34

    Data processing chain-Scada integration

  • 8/10/2019 Ampacimon Presentation Sth Am

    28/34

  • 8/10/2019 Ampacimon Presentation Sth Am

    29/34

    Positive, strong correlation with windpower production New probabilistic network planning approaches are well suited to

    include DLR

    New, Day-ahead DLR forecast product facilitates integration of windfarms into existing grids

    Can increase X-border interconnections on day-ahead markets

    29

    Correlation Wind generation/DLR

  • 8/10/2019 Ampacimon Presentation Sth Am

    30/34

    Commissioned/decomissioned in 30mn Installation on live lines Self-powered, no maintenance

    Standard modules No calibration, can easily be used,stored, re-

    used

    Ampacimon service for initial set-up

    Flexible licence structures (per line, up to Xsensors, unlimited etc )

    Hosted or enbedded applications solutions

    Portability

  • 8/10/2019 Ampacimon Presentation Sth Am

    31/34

    Certified for 400 kV Lightning

    (1475 KV peak with cutted wave)

    Short circuit (63 kA rms, 150 kA peak)

    Corona free Corona Test under heavy rain

    shower, following IEC 600060-1 in420 kV hall at Renardires (RTE,France), January 2009

    31

    Certifications

  • 8/10/2019 Ampacimon Presentation Sth Am

    32/34

    Currently uses Ampacimons 1-4h forecast instead of static ratings in their 1/4h EMS Has been using Ampacilmon for 5 years Day-ahead forecasting on all interconnection lines being deployed

    Looking for a economical solution to reduce expensive re-dispatch events on congested network links Has been using Ampacimon in real operations for 1 year, with a 4 months pay -back

    Quick and economical solution to deal with significant congestion issues due to the integration of renewable energysources and the moratorium on nuclear energy

    Smartzone project Considering use of Day-ahead forecast modules

    Looking for a better alternative to the already installed Power Donuts

    Twenties project, in combination with Distributed Temperature Sensing

    32

    Proven

  • 8/10/2019 Ampacimon Presentation Sth Am

    33/34

    Ampacimon helps grid operators:

    Increase the capacity of your network quickly

    Manage your network 100% safely

    Integrate distributed renewable energy

    Increase X-border interconnections

    33

  • 8/10/2019 Ampacimon Presentation Sth Am

    34/34