NUE046 L/O 3 6/05 jh 1

Learning outcome 3

Motor starting.

Page 2: Alternating Current Machines 3

NUE046 L/O 3 6/05 jh 2

Until the motor gets up to speed, there is insufficient back EMF being generated to limit the current to its normal FLC.

In the locked rotor condition, at the initial point where it starts to turn, the only limiting factor to current draw is the motors impedance (Z).

This starting current can be very high, 6 – 8 times FLC.

Page 3: Alternating Current Machines 3

NUE046 L/O 3 6/05 jh 3

These are for 1Ø.

Page 4: Alternating Current Machines 3

NUE046 L/O 3 6/05 jh 4

These are 3Ø.

Page 5: Alternating Current Machines 3

NUE046 L/O 3 6/05 jh 5

Most starters reduce the starting current by limiting the voltage.

D.O.L.Star/deltaAuto-transformerPrimary resistanceSecondary resistance. (WRMs)

Jenneson p 304

L/O 3.1, 3.2 & 3.3

Page 6: Alternating Current Machines 3

NUE046 L/O 3 6/05 jh 6P 298 & P 305

Follow this circuit in your text book and identify the stop & start buttons.

Page 7: Alternating Current Machines 3

NUE046 L/O 3 6/05 jh 7

Auto start star/delta starter.

Star contactorLine contactor Run contactor Timer

Starting timer

TOL

NHP starter

Page 8: Alternating Current Machines 3

NUE046 L/O 3 6/05 jh 8

Liquid resistance starters and primary resistance starters.

P 299

These can be used on star or delta connected motors.

L/O 3.1 3.2 & 3.3

Page 9: Alternating Current Machines 3

NUE046 L/O 3 6/05 jh 9

Primary Resistance StartingStarting resistances

Star connected motor

Lift motor

Page 10: Alternating Current Machines 3

NUE046 L/O 3 6/05 jh 10

Do not get eye strain with this.Circuit diagramme of primary resistance starting for lift motor.

Resistors with parallel contacts Motor windings

Emerald TAFE campus lift.

Page 11: Alternating Current Machines 3

NUE046 L/O 3 6/05 jh 11

Variable speed drives.

Page 12: Alternating Current Machines 3

NUE046 L/O 3 6/05 jh 12

Secondary resistance starting.

On large machines this is often used with transformer starting.

P 303

Page 13: Alternating Current Machines 3

NUE046 L/O 3 6/05 jh 13

Motor Braking

MechanicalEddy-currentDynamic - (Regenerative)

- (injection)Plug braking

P 308

Page 14: Alternating Current Machines 3

NUE046 L/O 3 6/05 jh 14

Mechanical brake for parking.

Electric methods will not HOLD the motor and load still. Some form of mechanical brake is needed.

Page 15: Alternating Current Machines 3

NUE046 L/O 3 6/05 jh 15

www.railway-technology

Examples of eddy-current braking

www.fitnessscape

Page 16: Alternating Current Machines 3

NUE046 L/O 3 6/05 jh 16

www.-ph.postech.ac

This principle is commonly used with lifts and hoists to regulate the rate of decent.

Induction disc. Aluminium or stainless steel.Electro magnetics

The retarding force is altered by the supply current.

Eddy-current braking

Page 17: Alternating Current Machines 3

NUE046 L/O 3 6/05 jh 17

www.nesea.,org

www.uptenergy

http//aevcenter

www.forkliftsireland

Uses for regenerative braking.

Page 18: Alternating Current Machines 3

NUE046 L/O 3 6/05 jh 18

For a motor to accelerate a load from standstill the motor must be able to overcome the inertia, load resistance and losses within the system.

Student exercise..Make a list of ALL the losses in a system.

A motor in a crane raises a load from the ground to the back of a truck.What energy is used and where is it used.

L/O 3.4

Page 19: Alternating Current Machines 3

NUE046 L/O 3 6/05 jh 19

Applied voltage as reference

No load current

The no-load current is the magnetising current and the current to overcome the no-load losses. In simple terms this current remains constant.

The load current from the supply required to accommodate the load. This current is almost in phase with the applied voltage.

Total load current. Phasor sum of no-load and on-load currents at the running pf.

Page 20: Alternating Current Machines 3

NUE046 L/O 3 6/05 jh 20

When a load is placed on a motor eg; a conveyor is loaded, the motor slows, less back EMF is produced which allows more supply current to flow.

BUT this is only a small part of the story. What happens in the magnetic circuits?

Page 21: Alternating Current Machines 3

NUE046 L/O 3 6/05 jh 21

Prac work.

• Connect a star/delta starter• Observe injection brake• WRM with resistance in rotor circuit• Connect VF drive• Measure starting currents

Demo pracs.