Top Banner
Member Due to constant improvement in our products, we reserved the right to modify or withdraw any product or service without prior notice. Distributed By :- Version : 16-09-2013 CERT NO.: 2001.1.0321 ISO 9001 : 2008 R DESCRIPTION ALARM BELL MBA-624 BACK BOX BBX-4 Optional (To be ordered separately) Weight 680g 300g Material Gong : Steel (Red) Housing : ABS Plastic Light Alloy (Painted Red) Rated Voltage 24 VDC - Rated Current 20 mA - Voltage Range 19.2 to 28.8 VDC - Sound Level 95 dB at 3m (10 ft.) - The MBA series Alarm Bells are low-current, audible signaling devices for use in Fire Alarm Systems and other signaling applications to provide warning during emergencies. ALARM BELL Model MBA-624 Typical Bell Installation with optional Back Box Gong Hex Bolt Striker Housing Back Box (Optional) Gasket (Optional) The Bells are polarized for usage with supervision circuitry, with low current, high efficiency DC motor to drive the striker. The Bell Gong is made of steel, finished in red enamel paint with the mechanism enclosed in an ABS plastic housing. Back Box BBX-4 (To be ordered separately), could be used in conjunction with the Bell as an option for outdoor installation, or when weatherproof installation is required. Back Box BBX-4 For Outdoor Installation (To be ordered separately) 85.5mm Back Box BBX-4 Dimension 42mm 96mm Sq. 127mm 112mm 85.5mm 112mm Ø20mm (ؾ”) Cable Entry 146.5mm Ø7mm M4 TAP Hole Ø150mm 75mm 68mm 26mm 85.5mm Alarm Bell MBA-624 Dimension 119mm Sq. Base) Ø5mm
14

ALARM BELL Model MBA-624 - GiaXD

Apr 29, 2023

Download

Documents

Khang Minh
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: ALARM BELL Model MBA-624 - GiaXD

Member

Due to constant improvement in our products, we reserved the right to modify or withdraw any product or service without prior notice.

Distributed By :-

Version : 16-09-2013

1. MEMBER

CERT NO.: 2001.1.0321

ISO 9001 : 2008

R

DESCRIPTION ALARM BELL

MBA-624

BACK BOX BBX-4 Optional

(To be ordered separately)

Weight 680g 300g

Material Gong : Steel (Red) Housing : ABS Plastic

Light Alloy (Painted Red)

Rated Voltage 24 VDC -

Rated Current ≤ 20 mA -

Voltage Range 19.2 to 28.8 VDC -

Sound Level 95 dB at 3m (10 ft.) -

The MBA series Alarm Bells are low-current, audible signaling devices for use in Fire Alarm Systems and other signaling applications to provide warning during emergencies.

ALARM BELL Model MBA-624

Typical Bell Installation with optional Back Box

Gong Hex Bolt

Striker

Housing

Back Box (Optional)

Gasket (Optional)

The Bells are polarized for usage with supervision circuitry, with low current, high efficiency DC motor to drive the striker. The Bell Gong is made of steel, finished in red enamel

paint with the mechanism enclosed in an ABS plastic housing.

Back Box BBX-4 (To be ordered separately), could be used in

conjunction with the Bell as an option for outdoor installation,

or when weatherproof installation is required.

Back Box BBX-4 For Outdoor Installation

(To be ordered separately)

85.5

mm

Back Box BBX-4 Dimension

42mm

96m

m S

q.

127mm

112mm

85.5mm

112m

m

Ø20mm (ؾ”) Cable Entry

146.5mm

Ø7mm

M4 TAP Hole

Ø150mm

75mm

68mm

26mm

85.5

mm

Alarm Bell MBA-624 Dimension

119m

m S

q. B

ase)

Ø5mm

Page 2: ALARM BELL Model MBA-624 - GiaXD

Technical Specifications

Operating Voltage 24VDC (Range 20VDC to 28VDC)

Operating Current Standby Current : 18mA

Alarm Current : 33mA

Detection Range Distance from 8m to 100m

Monitoring Area Maximum Area : 14 x 100 = 1400m2

Maximum Width : 14m

Wiring Non-Polarized Two-Core 24VDC

Non-Polarized Two-Core Detection Loop

Operating Environment

Temperature Range : -10C ~ +55C

Relative Humidity : 95% Non-condensation

Weight 650 Gram (with Mounting Bracket)

Material ABS Plastic

IP Rating IP30

Colour White with Black Screen

MULTRON Reflective Beam Detector is a reflective infrared beam smoke detector, which

must be used together with reflectors. The number of reflector(s) to be used (1 to 4) depends on the distance of coverage from the detector.

With built-in microprocessor, the detector has capabilities of analysis and judgment. The detector can automatically carry out system adjustment & compensation due to variations in ambience data through fixed algorithm.

The detectors can be used with all major brands of Conventional Fire Alarm Panels.

Hassle free alignment, using built-in digital guide display with Laser Beam

Auto-compensation for weaken receiving signals

Fire & Fault Interfacing Relay Output

Users’ programmable sensitivity

Self-diagnostic for internal faults

Designed in compliance to EN 54-12: 2002 Standards

Standard Accessories :-

1 pc. Mounting Bracket

1 pc. IR Light Filter (for site testing simulations)

4 pcs. Reflector

Reflective Beam Detector Model: DET-640RB

Due to constant improvement in our products, we reserved the right to modify or withdraw any product or service without prior notice.

Multron Systems Pte Ltd 217 Kallang Bahru, Multron Building, Singapore 339 347

info @ multron.com

www. multron. com 6395 6868

6395 6869

Version : 12-12-2015

CERT NO; 2001.1.0321

ISO 9001 : 2008 MEMBER

Front View Side View

191m

m

96.5mm

136.5mm

127mm

Mounting Bracket

Page 3: ALARM BELL Model MBA-624 - GiaXD

The C600 Series Detector Range

The range of Heat and Smoke Detectors are designed to comply with EN54 Part 5 & Part 7 respectively. With low profile attractive appearance, the detectors have stable and reliable performance against false alarm.

Optical Smoke Detector, Model DET-C631

It is suitable for general smoke detection, particularly effective in detecting large visible smoke particles such as those produced by smouldering wood, paper, PVC or polyurethane foam.

The smoke detector detects fire by the scattering of infrared beam, which circuits are consisted of a infrared beam emitter and receiver. The emitting and receiving lens are in the optical sensing chamber, screening any interference from outside lights, without preventing the entrance of smoke particles. In a smokeless condition, it only receives very weak infrared light. When smoke particles enter the chamber, the received light signal will increased due to scattering. When the smoke reaches a predetermined density, it will trigger an alarm signal.

To reduce interference and power consumption, pulsed emitting circuits are used to increase the life of the emitting lens.

Heat Detector, Model DET-C632 Combination Rate of Rise & Fixed Temperature

With a combination of detecting Rate-of-Rise and Fixed Temperature for higher safety, this detector is ideal for general fire detection purposes.

Rate-of-Rise Heat Detectors are particularly suited in areas where the temperature is normally fairly stable – useful for low ambient temperature areas where the response of fixed temperature may be slower. It activates upon rapid rise in temperature.

Fixed Temperature Heat Detectors are particularly suited to areas where temperature can fluctuate for natural reason – e.g. where there are large windows or industrial heat producing processes. It is preset to trigger an alarm

when the temperature reaches approximately 57C – therefore an excellent way of avoiding continual false alarms in areas where the temperature fluctuates rapidly.

Electronic thermistor type detector element provides high accuracy with no moving parts, which results in excellence reliability.

Standard Base, Model DB-6

This common base can be used for all the Point Detectors in the C600 Series.

With no electronics, this mounting base provides durable trouble-free operation and ease of use when replacement of the detector head is required.

Features :-

Wide operating voltage for both Fire & Security Systems

Error free non- polarized zone input termination

Optional Detector Head locking mechanism incorporated

Twin colour LED Indicator, with `Green’ (blinking) for Normal Operation, and `Red’ for Alarm Status

LPCB Approved

Optical Smoke Detector

Model : DET-C631

Heat Detector R.O.R & Fixed Temp.

Model : DET-C632

Standard Base

Model : DB-6

0832-CPD-2118 1148a / 01

0832-CPD-2119 1148b / 01

Smoke & Heat Detector Model : DET-C631 and DET-C632

Due to constant improvement in our products, we reserved the right to modify or withdraw any product or service without prior notice.

Multron Systems Pte Ltd 217 Kallang Bahru, Multron Building, Singapore 339 347

info @ multron.com

www. multron. com 6395 6868

6395 6869

Version : 17-08-2015

CERT NO; 2001.1.0321

ISO 9001 : 2008 MEMBER

Page 4: ALARM BELL Model MBA-624 - GiaXD

Technical Specifications Smoke Detector

Model : DET-C631 Heat Detector

Model : DET-C632

Normal Rated Voltage 24VDC 24VDC

Operating Voltage 9.6 VDC to 30 VDC 9.6 VDC to 30 VDC

Quiescent Current ≤ 65uA ≤ 35uA

Alarm Current 18 to 22mA (Typical 20mA) 18 to 22mA (Typical 20mA)

Remote LED Drive Current Output Max. 20mA Max. 20mA

Maximum Air Velocity 7.6 m/s -

Weight 102g (160g with Base DB-6 ) 85g (143g with Base DB-6 )

Operating Temp. Range -10°C to +50°C

Relative Humidity 95%RH, Non Condensing @ 40°C

Alarm LED Indication Red ( Continuous )

Normal LED Indication Green ( Blinking )

Ingress Protection IP42 IP42

Material of Body ABS Plastic ( To UL94V-0 Flammability Test Standards )

Colour of Body White

Standards EN54-7 EN54-5

Typical Detector Dimension

Heat Detector Model : DET-C632

Smoke Detector

Model : DET-C631

Ø100 mm

56

mm

48

mm

8

mm

Ø100 mm

52

mm

44

mm

8

mm

Optional – Remote LED

Typical Detector Termination Diagram

End-of-Line Resistor

1 2

5

3

8 6 7

4 1 2

5

3

8 6 7

4

+

-

Detection Zone Termination

FIRE ALARM PANEL

Page 5: ALARM BELL Model MBA-624 - GiaXD

Manual Call Point Model : MCP-C652

The Manual Call Point MCP-C652 is provided to manually trigger the Fire Alarm System. They are constructed in red ABS plastic housing, and are usually installed in areas like corridors and exit staircases.

They are alarm latching, with LED alarm indication provided as standard. Every unit is provided with a special `Key’ to facilitate the resetting of the unit during testing or routine inspection.

Features :-

Complies to the latest EN 54-11 Standards

Non-breaking resettable `Glass’ via special key

LED light provided to indicate activation

Plug-in type of Termination for ease of Installation

Optional Transparent Flip Cover available

(To be ordered separately)

Technical Specifications :-

Operation Voltage 24VDC

Monitoring Currently 0mA

Alarm Current 46.3mA @ 24VDC

Operating Temperature -10 °C to +55°C

Relative Humidity 95%, Non-Condensing

Ingress Protection IP 43

Dimension in mm. (Ht. x Width x Depth)

89.5 x 87 x 26 (without Back Box) 89.5 x 87 x 58 (with Back Box)

Weight 137g (with Back Box) 84g (without Back Box)

Alarm Contact (Terminal 1,2 and 3,4)

470 Ω with LED

Alarm Contact (Terminal 5,6 and 7,8)

N/O without Resistor & LED

Manual Call Point , Model : MCP-C652

Convenient Plug-in Terminals for ease of wiring installation

TYPICAL TERMINATION DIAGRAM (Using Terminal 1,2 and 3,4)

FIRE ALARM PANEL

Zone Termination End-of-Line

Resistor -

+

Transparent Flip Cover may be added for extra protection

against accidental activation (Optional - To Be Ordered Separately)

LED N/O Contact 470 Ω

1 2 - -

3 4 + +

5 6 - -

7 8 + +

Typical Circuitry

Page 6: ALARM BELL Model MBA-624 - GiaXD

Manual Call Point Model : MCP-C652

TO ACTIVATE ALARM :-

TO `RESET’ MANUAL CALL POINT :-

Innovative Resettable `Break-glass’…..

….with the look and feel of a real Break-glass, but without the trouble of replacement after activation....

1) Manual Call Point in its normal condition. 2) Position your finger onto the centre of the Break-glass’.

Position Finger onto `Break-glass’

6) To reset, insert the special Key at the bottom reset keyhole of the Manual Call Point.

7) Slid down the casing of the Manual Call Point downwards to reset the position of the `Break-glass’.

8) Press and slid back the casing to its original position. 9) Once the casing is snapped back, the Manual Call Point is properly `Reset’ to its normal condition.

3) To activate, press the `Break-glass’ and it will snap backwards. 4) Yellow marking will be shown at the top to indicate activation. 5) The Alarm Contact Signal shall be activated.

Press Hard to Activate.

The Yellow Marking will be shown once the Call Point is activated.

Due to constant improvement in our products, we reserved the right to modify or withdraw any product or service without prior notice. Version : 1-08-2016

MEMBER CERT NO; 2001.1.0321

ISO 9001 : 2008

Multron Systems Pte Ltd

217 Kallang Bahru, Multron Building, Singapore 339 347

6395 6868

6395 6869

info @ multron.com

www. multron. com

Page 7: ALARM BELL Model MBA-624 - GiaXD

CCOONNVVEENNTTIIOONNAALL FFIIRREE AALLAARRMM PPAANNEELL

CCFFPP--660000 SSEERRIIEESS

FFEEAATTUURREESS ::--

Designed to EN54 Parts 2 & 4 Standards

Standard Outputs Provided :-

2 Sounder Outputs

1 Alarm Output

1 Fault Output

1 Auxiliary 24VDC Output

1 Auxiliary 24VDC Output (with Reset)

Key Switch Controlled Access Level

Convenient Slot-in Zone Self-Labeling

Modular in Construction

Customisation is available to meet any special requirement

Colour Symbols & Indicators for ease of identification & usage

The CFP-600 Series of Fire Alarm Panel uses the latest in

microprocessor technology to meet today’s stringent needs for a

comprehensive and versatile range of Fire Detection & Alarm Systems.

Design for ease in installation and operation, the control functions and

programming are enables through a key switch to prevent unauthorized

access. Operation of the Panel is made simple with frontal indications

and switches.

Design in compliance to EN54 Parts 2 & 4, each detection zone can

cater up to 20 conventional devices.

Attractively styled and compact in size to blend into any modern

architecture, the slim profile of the panel is unobtrusive even when

surface mounted.

MULTRON®

Page 8: ALARM BELL Model MBA-624 - GiaXD

Model No. Zoning

CFP-600- 4 4- Zone

CFP-600- 8 8-Zone

CFP-600-12 12-Zone

CFP-600-16 16-Zone

CFP-600-20 20-Zone

CFP-600-24 24-Zone

The standard Fire Alarm Panel lowest capacity is 4-Zone, with increment in steps of 4-zone up to a capacity of 24- Zone. Panels requirement above 24-Zone may be customised and made to order based on clients’ requirement. Panels in Weatherproof Cabinets are also available upon request.

TYPICAL FIRE ALARM PANEL PHYSICAL DIMENSION

Zone Module (4 zone per Module)

Door Lock

Mains Module

Ø20mm Knock-Out Holes For Cable Entry

20 to 24-Zone

12 to 16-Zone

350mm 135mm

46

0m

m (

12

to

16

-zo

ne)

38

0m

m (

4 t

o 8

-zo

ne

)

54

0m

m (

20

to

24

-zo

ne)

Technical Specifications :-

Mains Voltage 230VAC ± 15% @ 50 Hz

System Operating Voltage 24VDC ± 15%

Detection Circuit Static Current 2.4mA (Based on 20 conventional detectors)

Resistance for Alarm Activation 100Ω to 1.4KΩ

End-of-Line Resistor 4.7KΩ

Sounder Output Circuit 1 amp (Total Current Output)

`Alarm’ Output Contact NO or NC Voltage-Free Contact (Selectable)

`Fault’ Output Contact NO or NC Voltage-Free Contact (Selectable)

Aux. Power Output 0.5amp @ 24VDC

Operating Temperature -10°C to 45°C

Relative Humidity 95%, Non-Condensing

IP Rating IP30

Estimated Weight (Excluding Standby Batteries)

4 and 8 zone : 6.3 kg 12 and 16 zone : 7.5 kg 20 and 24 zone : 8.7 kg

Page 9: ALARM BELL Model MBA-624 - GiaXD

The electronics components are mounted onto the PCBs by the latest surface mount technologies.

PCBs within the panel are easily accessible and connected by ribbon cables, with knockout holes for cable entry provided for ease of wiring installation and termination.

The modular construction of the Panels enables easy replacement of any faulty parts or modules, with the flexibility for any re-configuration.

THE PANELS ARE MANUFACTURED UNDER STRICT ISO 9001 QUALITY MANAGEMENT SYSTEM CERTIFIED BY ACCREDITED CERTIFICATION BODY

ZONE MODULE, CFP-600-ZM

Each Zone Module incorporates 4 Detection Zones, with each zone having an independent `FIRE’ (Red), and `FAULT’ (Yellow) LED Indicators

`DISABLE’ Pushbutton with corresponding LED Indicator is provided for each zone.

`DISABLE’ Pushbutton With LED Indicator

Zone Label (Slide-in from Behind)

`Fire’ & `Fault’ LED Status Indicator

Agent Release Countdown Timer

AGENT RELEASE MODULE, CFP-600-GM

The Agent Release Module may be incorporated into the Fire Alarm Panel for Extinguishing Agent Release Functions.

Typical examples are for usage in CO2, FM200, Foam or Pre-Action Sprinkler Systems. This Module can be factory programmed to work in conjunction with any 2 Alarm Detection Zones for Cross-Zone Detection prior to Agent release.

Zone Label (Slide-in from Behind)

Abort Pushbutton

Manual Release Pushbutton

Fault LED Indicators

MAINS MODULE, CFP-600-MM

The Mains Module provides all the Status Indicators, Control Pushbuttons, and Control Access Key Switch for Fire Alarm System.

Control Access Key-switch

LED Indicators Pushbuttons & LED Indicators

Page 10: ALARM BELL Model MBA-624 - GiaXD

DDuuee ttoo ccoonnssttaanntt iimmpprroovveemmeenntt iinn oouurr pprroodduuccttss,, wwee rreesseerrvveedd tthhee rriigghhtt ttoo mmooddiiffyy oorr wwiitthhddrraaww aannyy pprroodduucctt oorr sseerrvviiccee wwiitthhoouutt pprriioorr

nnoottiiccee.. Version : 1-08-2016

AAnnootthheerr QQuuaalliittyy PPrroodduucctt bbyy ::--

MMuullttrroonn SSyysstteemmss PPttee LLttdd 221177 KKaallllaanngg BBaahhrruu,, ++6655 66339955 66886688

MMuullttrroonn BBuuiillddiinngg ++6655 66339955 66886699

SSiinnggaappoorree 333399 334477 iinnffoo@@mmuullttrroonn..ccoomm

VViissiitt uuss aatt ::-- wwwwww..mmuullttrroonn..ccoomm

TYPICAL TERMINATION DIAGRAM

4.7kΩ EOL

Alarm Output (N/C or N/O)

Fault Output (N/C or N/O)

Sounder Output

FPE Alarm Output (24VDC)

24VDC Output (Max. 0.5A)

24VDC Output (with Reset)

Network Communication

Zone Termination Card

Main Termination Card

Power Supply On/Off Switch

230VAC Mains Incoming

L E N

Fuse

Mains Fuse

Fuse

12 VDC Battery

12 VDC Battery

+

-

-

+

Zone 1 Alarm Devices

Zone 2 Alarm Devices

4.7kΩ EOL

4.7kΩ EOL

Page 11: ALARM BELL Model MBA-624 - GiaXD

The Series CFP 601 Fire Alarm Control Panel are developed from single-chip microprocessor, to meet the needs for a comprehensive and versatile range of Fire Detection & Alarm Systems. Design for ease in installation and operation, the Panel is made simple with frontal indications and switches, and a lockable front door as protection against unauthorized access. The Panel is design in compliance to NFPA requirement, with each Detection Zone catering up to 20 conventional devices. Attractively styled and compact in size to blend into any modern architecture, the slim profile of the panel is unobtrusive even when surface mounted.

Features :-

Alarm, Trouble & Supervisory, Relay Output

3 amp Power Supply c/w Resettable & Non-Resettable 24VDC Output

Short Circuit at Zone Input can be set as `Alarm’ or `Fault’ status

Programmable to Disable / Enable each Zone

Programmable to Disable / Enable Sound Output

Two Supervisory Input with 12VDC Output

FIRE ALARM PANEL (Conventional Type)

Series CFP 601

Model No. Number of

Detection Zone Number of

Sounder Output Dimension (mm) Weight

CFP 601- 4 4 zone 1

400H x 350W x 115D 6.0kg

(without Battery) CFP 601- 8 8 zone 2

CFP 601-16 16 zone 4

Technical Specifications :-

AC Power : 220VAC, 50Hz

Battery Maximum Charging :- 27.6VDC @ 0.8 Amp

Maximum Battery Charger Capacity :- 18AH Battery (Sealed Lead Acid Type)

Total System Power : 24VD , 3.0Amp

Output Relay rated at 2.0 Amps @ 30VDC

End-of-Line Resistor : 4.7 KΩ, ½W

Member

Due to constant improvement in our products, we reserved the right to modify or withdraw any product or service without prior notice.

Distributed By :-

Version : 12-05-2013

1. MEMBER

CERT NO.: 2001.1.0321

ISO 9001 : 2008

Page 12: ALARM BELL Model MBA-624 - GiaXD

Typical 16 zone Panel Facial and Termination Board Layout

(Optional)

Page 13: ALARM BELL Model MBA-624 - GiaXD

The CFP 602 series Fire Alarm Control Panels are developed from single-chip microprocessor, to meet the needs for a comprehensive and versatile range of Fire Detection & Alarm Systems. Design for ease in installation and operation, the Panel is made simple with frontal indications and switches, and a lockable front door with Key Switch as protection against unauthorized access. The Panel is design in compliance to EN54 Part 2 & 4 requirement, with each Detection Zone catering up to 20 conventional devices. Attractively styled and compact in size to blend into any modern architecture, the slim profile of the panel is unobtrusive even when surface mounted.

Features :-

2 x Alarm, & 1 x Fault Relay Output

2 x Sounder Output

Zone Short Circuit `Fault’ status provided

Programmable to Disable / Enable each Zone

Programmable to Disable / Enable Sound Output

In compliance to EN54 Part 2 & 4 requirement

FIRE ALARM PANEL (Conventional Type)

Series CFP 602

Model No. Number of

Detection Zone Dimension (mm)

Approximate Weight

CFP 602 - 4 4 zone

265H x 335W x 87D 2.7 kg (without Battery)

6.7 kg (with 7AH Battery)

CFP 602 - 8 8 zone

CFP 602 - 12 12 zone

CFP 602 - 16 16 zone

Technical Specifications :-

AC Power : 230VAC, 50Hz

Battery Maximum Charging :- 28VDC @ 0.3 Amp

Maximum Battery Charger Capacity :- 7AH Battery (Sealed Lead Acid Type)

Output Relay rated at 1.0 Amps @ 30VDC

Zoning End-of-Line Resistor : 3.3 KΩ, ½W

Member

Due to constant improvement in our products, we reserved the right to modify or withdraw any product or service without prior notice.

Distributed By :-

Version : 12-05-2013

1. MEMBER

CERT NO.: 2001.1.0321

ISO 9001 : 2008

Page 14: ALARM BELL Model MBA-624 - GiaXD

Typical 4-Zone Panel Facial Layout

Typical Main PCB Board Termination Details