Nov 03, 2015
Technical Papers31st Annual Meeting
International Institute of Ammonia Refrigeration
March 2225, 2009
2009 Industrial Refrigeration Conference & ExhibitionThe Hyatt Regency
Dallas, Texas
ACKNOWLEDGEMENT
The success of the 31st Annual Meeting of the International Institute of Ammonia
Refrigeration is due to the quality of the technical papers in this volume and the labor of its
authors. IIAR expresses its deep appreciation to the authors, reviewers and editors for their
contributions to the ammonia refrigeration industry.
Board of Directors, International Institute of Ammonia Refrigeration
ABOUT THIS VOLUME
IIAR Technical Papers are subjected to rigorous technical peer review.
The views expressed in the papers in this volume are those of the authors, not the
International Institute of Ammonia Refrigeration. They are not official positions of the
Institute and are not officially endorsed
International Institute of Ammonia Refrigeration
1110 North Glebe Road
Suite 250
Arlington, VA 22201
+ 1-703-312-4200 (voice)
+ 1-703-312-0065 (fax)
www.iiar.org
2009 Industrial Refrigeration Conference & Exhibition
The Hyatt Regency
Dallas, Texas
IIAR 2009 1
Technical Paper #7
Extended Surface Air Coolers for Industrial Plants the Contractors Perspective
Stefan S. Jensen, B.Sc.Eng. MIEAustScantec Refrigeration Technologies Pty. Ltd.
Brisbane, Queensland, Australia
Abstract
In view of the very large range of evaporator coil geometries, coil material combinations, coil defrost methods and circuiting options available on the market, the industrial refrigeration contractor often faces difficulties deciding which evaporator design to use for a certain application.
Often selections are based on rules of thumb, e.g., an allowance of a certain number of square feet of coil surface area per pound of product. Considering the fact that coil material selections, choice of refrigerant, coil circuiting and coil geometry can influence heat transmission coefficients (u-values) by up to a factor of three or more, such an approach can lead to very poor results in practice.
Other issues are relative humidity and dehydration of the refrigerated space. There are thousands of practical applications where the quality and shelf life of the products stored or chilled are directly influenced by the equilibrium relative humidity inside the room in question. Yet often extended surface air coolers are selected with geometries to suit the manufacturer and not the application. Frequently, the result is a squat coil when the coil should have been shallow and with large face area.
The performance impact of fouling both on the inside, but also on the outside surfaces of cooling coils is often not highlighted sufficiently by manufacturers. Extended surface air cooling coils featuring comparatively high-heat transmission coefficients (u-values) in clean condition generally display a more rapid performance deterioration as a function of increasing fouling than an equivalent coil with lower heat transmission coefficient in clean condition. It is often not in the commercial interest of coil manufacturers to disclose this information, yet it can be of crucial importance to the refrigeration plant designer.
It is commonly known that cooling coil performance increases as a function of increasing face velocity. What is not normally available from manufacturers is optimization of face velocities for maximum plant energy efficiency. This is the contractors problem and the tools that the contractor needs to perform this task are often not readily available.
This paper will show a range of practical performance comparisons between various coil geometries, coil materials, circuiting options, refrigerant choices, flow patterns and refrigerant feed options. These performance comparisons will have one thing in common namely the software used to perform them. The comparisons therefore represent relative information valuable to the contractor because it is information not readily available from extended surface cooling coil manufacturers under normal circumstances.
2009 IIAR Ammonia Refrigeration Conference & Exhibition, Dallas Texas
Technical Paper #7 IIAR 2009 3
Extended Surface Air Coolers for Industrial Plants the Contractors Perspective
Introduction
In modern industrial refrigeration applications, the extended surface air cooler is
one of the most common components. In terms of importance for the success of an
installation, it ranks at the level of compressors, condensers and control systems.
Although many software packages exist for the selection and rating of air coolers,
these are all designed for certain proprietary geometries and manufacturing ranges.
They are therefore not readily suitable for relative performance comparisons between
one manufacturer and the other.
The expertise of industrial refrigeration contractors relates to the ability to
successfully combine key plant components to form a functional refrigeration system
to suit a certain technical application. The selection of extended surface air coolers
can be a complex matter particularly if the outcome specified goes beyond simple
coil performance issues and extends into factors such as product quality, weight loss,
defrost frequency, overall energy efficiency, noise pollution, hygiene, temperature
and air flow uniformity within a facility, freezing times, part load behavior and other
similar performance outcomes for the system as a whole.
Not all extended surface air cooler geometries and layouts are suited optimally to
all applications. To some this may be a statement of the obvious and to some extent
it is. The statement does not refer to basics like selecting the correct fin spacing for
a freezing application. The statement makes the point that within one particular
plant it may be necessary to employ a wide range of cooler geometries and layouts
to achieve the optimal combination of components suitable for the application. This
may mean mixing coil manufacturers within the same system.
The marketing emphasis of cooler manufacturers is generally that their particular
product offered covers the widest range of applications. This is true for those
manufacturers who offer a wide range of geometries and construction materials.
Those manufacturers who for one reason or another limit the offering to one or
4 IIAR 2009 Technical Paper #7
2009 IIAR Industrial Refrigeration Conference & Exhibition, Dallas, Texas
very few coil geometries cannot cover as wide a set of applications. This paper will
examine the contractors perspective when it comes to selecting optimal extended
surface air coolers for a range of applications.
The Extended Surface Air Cooler
The typical air cooler type which is the topic of this paper is shown in principle
(Figure 1). It consists of a tube bundle fitted with plate fins; air is forced through the
fin side, refrigerant flows through the tubes. The tube pattern can be either square
or triangular; the tube diameters, fin thickness, fin design, tube centre distances,
circuiting, face velocity, refrigerant, refrigerant feed and material selections are
variables. This paper will not cover the issues of turbulators in tubes or wavy fins
nor will it describe any other fluid on the fin side than humid air at atmospheric
pressure. Finally, the paper will generally be limited to the presentation of results
to maximize clarity.
The air cooler performance modeling methodology used for the various comparisons
in this paper is described in earlier papers by the author [Reference 1], [Reference 2].
Impact of Coil Geometry on Overall Heat Transmission (U-Value)
The term, coil geometry, refers in this context to the tube pattern and the centre
distances between the tubes. Cooling coil layout refers to the way a particular cooler
of a particular geometry is laid out, i.e., rows high, rows deep, circuiting, finned
length, fin spacing, etc.
In Figure 2 is shown a range of hot dipped galvanized steel coils of different
geometries. By using the same material throughout the range, the variation in heat
transmission coefficients from 34.6 to 18.9 W/m2K (6.09 to 3.33 Btu/h ft2 F) is the
Technical Paper #7 IIAR 2009 5
Extended Surface Air Coolers for Industrial Plants the Contractors Perspective
result of variations in coil geometry only. All coils shown use 0.3 mm (0.0118") thick
fin material with a 0.112 mm (0.00441") thick layer of zinc.
Impact of Materials of Construction and Fin Thickness
Cooling coil performances are influenced by materials of construction and fin
thickness. This is demonstrated in Figure 3 where the coil geometry has been kept
constant, but materials and fin thicknesses have been varied to isolate the impact of
these variables. The variation in heat transmission coefficients from 13.2 to 37.5 W/
m2K (2.32 to 6.60 Btu/h ft2 F) is a direct result of the changes to thermal conductivity
of materials and fin efficiencies.
Circuiting
Circuiting is how the refrigerant is piped through the cooling coil. A coil can be
piped for physical parallel flow, physical counter flow, thermodynamic counter flow,
a mixture of physical parallel flow and counter flow and cross flow between air and
refrigerant. In addition, the circuits can be made long or short as dictated by the
tube diameter, refrigerant temperature, heat flux and refrigerant properties. If the
application requires relatively short circuits and the coil in question is large, then it is
often necessary to provide the coil with multiple headers or manifolds because there
is a manufacturing limitation with respect to the number of circuits which can enter/
leave a header. This makes the valve station more complicated and costly and is
generally not in the interest of the contractor.
The way the circuits run in relation to the force of gravity is dictated by a number
of factors. These include oil drainage, the type of refrigerant feed, orientation of the
coil, heat flux, type of defrost, thermostatic expansion valve sensor location and
general refrigerant side thermodynamics. Circuiting errors are most forgiving in liquid
6 IIAR 2009 Technical Paper #7
2009 IIAR Industrial Refrigeration Conference & Exhibition, Dallas, Texas
overfeed applications and potentially most disastrous in dry expansion feed cooling
coils.
The greater the turbulence on the refrigerant side, the greater the surface heat
transfer and the greater the pressure drop. The greater the refrigerant side pressure
drop for a volatile refrigerant, the greater the refrigerant temperature drop as the fluid
passes through the coil. The greater the refrigerant temperature drop, the lower the
logarithmic mean temperature difference (LMTD) all other things being equal. Lower
LMTD translates into reduced coil capacity. This scenario presents an optimization
problem between achieving good heat transfer on the tube side of the heat exchanger
without jeopardizing LMTD. A relatively high refrigerant side temperature drop has
the capacity to reduce LMTD to such an extent that any gain achieved by improved
heat transfer is more than eroded by a reduction in temperature difference hence
reducing overall coil capacity.
It is generally not possible to circuit any cooling coil in an optimal manner for the
entire operating range that the coil will encounter during its operating life. All choices
of circuiting therefore represent a compromise. If the manufacturer is provided with
the range of design operating conditions applicable to the coil in question then it
is possible to determine the most reasonable circuiting for the operating envelope
nominated. In many cases, however, the manufacturer is only provided with one
operating point namely the maximum coil performance required. Particularly in
dry expansion applications this can in practice lead to poor results at part load (low
temperature difference) and/or at reduced face velocity [Reference 2].
By far the most common circuiting method for industrial applications is shown in
Figure 4. This shows a liquid overfeed coil with horizontal headers; liquid inlet at the
bottom, wet return at the top; horizontal air flow and four tube passes. In effect, this
represents a cross flow arrangement between air and refrigerant.
Technical Paper #7 IIAR 2009 7
Extended Surface Air Coolers for Industrial Plants the Contractors Perspective
If a coil such as the one shown in Figure 4 is for a low temperature application and
is both long between the end plates and comparatively tall to meet the capacity
requirement, then the number of tube passes needs to reduce. This is to ensure that
the refrigerant side temperature (pressure) drop does not jeopardize LMTD to such
an extent that overall capacity reduces. It is generally less expensive for the coil
manufacturer to then supply a coil with multiple horizontal liquid and wet return
headers as opposed to having one inlet and one outlet header that accommodate all
the circuits. A typical multiple header coil is shown in Figure 5. The consequence to
the contractor of this header arrangement is that each evaporator segment needs to
be treated like an individual evaporator in terms of valve station design. Essentially,
the capital cost of the air cooler has therefore been minimized at the expense of
increased valve station costs. Often the result is an overall project cost increase
because the additional cost of the valve station more exceeds the saving in coil costs.
An alternative to multiple horizontal headers to achieve the correct circuit length
is vertical headers (Figure 6). In the great majority of cases, coil depth is less
than the coil height so the need for multiple headers can be eliminated by using
vertical headers. However, to ensure uniform distribution of refrigerant in a liquid
overfeed situation, each circuit inlet must have an orifice. If there are no orifices, the
refrigerant will take the path of least resistance and the upper circuits of the coil will
not perform. This may be illustrated with a simple example. If the refrigerant side
pressure drop for the coil illustrated in Figure 6 is 1K (1.8F) then this translates into a
pressure drop of 3839 Pa (0.56 psi) or 0.57 m (1.86 feet) of ammonia liquid column.
If the vertical liquid inlet header is 1.2 m (3.94 feet) tall, then gravity will force
the liquid refrigerant through the bottom half of the evaporator circuits leaving the
top circuits dry. The result will be more or less a halving of the anticipated cooling
capacity. The design driving force across the circuit orifices should be greater than
the height of the vertical inlet header. It follows therefore that the top orifices in the
header need to be larger than the bottom orifices to account for gravity. The mass
flows through circular orifices may be calculated as shown:
8 IIAR 2009 Technical Paper #7
2009 IIAR Industrial Refrigeration Conference & Exhibition, Dallas, Texas
m = * A * SQR(2 * p * ) (1)
For the orifice contraction coefficient , a value of 0.7 may be used. For the top
orifices in the header a design pressure drop (p) of around 0.45 to 0.6 m (1.5 to
2 feet) of liquid column is practical and will generally not yield orifices which are
too small and hence susceptible to blockage. The design pressure drops measured
in liquid column for the bottom orifices are the same as for the top plus the height
of the header. Using larger design pressure drops will reduce the size of the orifices
to such an extent that they become susceptible to impurities. For the purposes of
streamlining manufacturing operations, some coil manufacturers only provide a
choice between either 3 or 4 mm (0.12" or 0.16") orifices. In most cases these
are far too large (unless the liquid overfeed ratio is very high) and do not provide
the appropriate graduation in size between top and bottom of the inlet header. More
appropriate orifice sizes are around 1.7 to 2.8 mm (0.067" to 0.11"). Even with
these orifice sizes, it is often found in practice that the liquid overfeed ratio needs to
be elevated to around 6 to 1 to ensure adequate refrigerant distribution to all circuits
during all operating conditions.
The orifices in a vertical inlet header not only restrict the flow of liquidthey also
restrict the flow of hot gas. This needs to be carefully considered when an evaporator
is to be defrosted with hot gas. It is often found in practice that coils with vertical
headers require longer time to defrost with hot gas than coils with horizontal headers
where the hot gas is entered in the top wet return header hence pushing the cold
liquid out of the bottom header relatively rapidly at commencement of defrost.
The circuit orifices in the coil shown in Figure 6 may be eliminated by turning the
coil 90 such that the air flows vertically up through the coil. In liquid overfeed
applications this then enables liquid entry through the bottom header and wet return
from the top thus creating physical parallel flow or thermodynamic counter flow.
Simply turning the coil 90 is naturally not always physically possible, but if it is,
then a circuiting problem can be converted to a circuiting advantage. This circuiting
Technical Paper #7 IIAR 2009 9
Extended Surface Air Coolers for Industrial Plants the Contractors Perspective
method has been used successfully in a large number of automatic tunnel freezers in
Australia and New Zealand for about 50 years.
There are cases where circuit orifices may be required also in coils with horizontal
headers and horizontal air flow. In a situation where the coil is exposed to high ETD
for example a fresh air inlet cooling coil in a food processing plantthe circuits at
the air inlet to the coil may boil dry. This is due to the fact that high heat flux also
creates high refrigerant side pressure drop. At the air leaving side of the coil where
the heat flux is less, the refrigerant side pressure drop is relatively low. Without
circuit orifices the circuits at the air leaving side are then in equilibrium supplied
with excess refrigerant at the expense of the circuits at air entry, which are left
starved of refrigerant. The result is a significant reduction in overall coil performance
(Figure 7).
The impact of circuiting on coil performance is visualized in Figure 8. The number
of rows high, deep, fin spacing and finned length have all been kept constant.
The number of times that the refrigerant passes through the tube bundle has been
variedthis is referred to as the number of tube passes. The vertical axis shows
heat transmission coefficients and gross coil capacity; the horizontal axis shows
evaporating temperature and entering temperature difference (ETD) between air
and refrigerant. The ETD is calculated by subtracting the evaporating temperature
from the air on temperature of 18C (0.4F) shown. The graphs show the coil
performance as a function of the number of tube passes. It is clear that there is no
such thing as optimal circuiting for a wide range of operating envelopes. At 25C
(13F) evaporating temperature (7K or 12.6F ETD), 28 passes deliver maximum
coil performance. At 28C (18.4F) evaporating temperature, 14 passes yield
maximum performance. In a dry expansion application such as the one shown,
circuiting for a comparatively low refrigerant pressure drop at full load may deliver
optimal coil performance at that point. However, practical experience has also shown
that a coil circuited this way is likely to become difficult to control at low ETDs and
10 IIAR 2009 Technical Paper #7
2009 IIAR Industrial Refrigeration Conference & Exhibition, Dallas, Texas
the result will be increasing liquid entrainment in the suction vapor leaving the coil.
This is also known as liquid flood-back.
It is possible to circuit both dry expansion coils and liquid overfeed coils such that
the reduction in LMTD by a relatively high refrigerant side temperature (pressure)
drop is minimized (Figure 9). Physical parallel flow translates into thermodynamic
counter flow. Using this circuiting method will, in dry expansion applications, give
rise to problems obtaining a suitable superheat signal for the expansion valve. These
problems may be overcome by circuiting the last tube pass through the air inlet side
(Figure 10). This circuiting method is termed reversed suction return. The difference
in coil performance between reversed suction return and physical counter flow for a
typical dry expansion coil is illustrated in Figure 11.
Fouling
Fouling is a layer of material with relatively poor thermal conductivity that has
settled on the heat transfer surface of a heat exchanger. This layer has the capacity to
create a thermal resistance and hence inhibit heat transfer. The result is a reduction
of the overall heat transmission coefficient. In industrial extended surface air coolers,
fouling can occur both on the refrigerant side and on the air side. On the refrigerant
side of air coolers in ammonia plants, the most common form of fouling is oil; on the
air side it is frost. There are other forms of fouling, but these are outside the scope of
this paper.
Not all air cooler geometries are affected the same way by a given fouling resistance.
The percentage coil performance reduction as a function of the internal and external
fouling resistances is shown in Figure 12 for two different coil geometries. It is
evident that the performance of geometry (a) deteriorates more rapidly than that of
geometry (b) as fouling increases. Due to the fact that fouling is almost unavoidable
in industrial ammonia refrigeration plants, this observation can be of crucial
Technical Paper #7 IIAR 2009 11
Extended Surface Air Coolers for Industrial Plants the Contractors Perspective
importance to the contractor. A thin layer of oil of 0.05 mm (0.002") thickness on
the refrigerant side of an ammonia air cooler is not uncommon [Reference 3]. This
results in a fouling resistance of 0.0004 m2K/W (0.0023 ft2hrF/Btu). The impact of
this fouling resistance is a reduction in heat transmission coefficient of 13.5% in the
case of geometry (a). A frost layer of ~1 mm (0.04") throughout the coil represents
a fouling resistance of around 0.008 m2K/W (0.046 ft2hrF/Btu) [Reference 4]. The
impact of this is a capacity reduction of 27.8% and 21.4% for geometries (a) and (b)
respectively.
Refrigerant and Refrigerant Feed
A very common refrigerant feed method in industrial ammonia applications is liquid
overfeed. Figure 13 shows the performance of a typical ammonia liquid overfeed
coil as a function of liquid overfeed rate. Although the liquid overfeed rate has little
impact on the coil performance when viewed in isolation, excess liquid overfeed rates
can have a significant impact on the pressure drop in the wet return line downstream
of the evaporator. An increase in wet return line pressure drop increases the ammonia
pressure that the coil is exposed to at the suction connection and the result is a
reduction in coil capacity.
Common alternatives to liquid overfeed are gravity flooded and dry expansion feeds.
The principle of gravity flooded feed is shown in Figure 14. In equilibrium, the sum
of pressure gains and pressure drops in the refrigerant circuit must be zero. In Table 1
are shown the key data for a flooded evaporator with NH3 and CO2 refrigerants.
The air flow is vertically up (Figure 14).
12 IIAR 2009 Technical Paper #7
2009 IIAR Industrial Refrigeration Conference & Exhibition, Dallas, Texas
Table 1. Key data for NH3 and CO2 flooded evaporators
Refrigerant NH3 CO2tE, C (F) 41.5 (42.7) 41.5 (42.7)tS, C (F) 42.4 (44.3) 41.8 (44.3)tE +PR, C (F) 39.7 (39.5) 41.46 (42.63)
Air on/off, C (F)35.0/37.8
(31.0/36.0)
35.0/38.2
(31.0/36.8)Relative humidity on/off, % 80/93 80/93Liquid overfeed rate 5.2 to 1 5.6 to 1Total cooling capacity, kW (TR) 124.8 (35.6) 143.2 (40.8)Overall heat transmission coefficient,
service, W/m2K (Btu/h ft2 F)31.6 (5.56) 32.1 (5.65)
d1, m (inches) 0.10226 (4.03) 0.0779 (3.07)d2, m (inches) 0.0779 (3.07) 0.0627 (2.47)d3, m (inches) 0.1282 (5.05) 0.0779 (3.07)
For both refrigerants the evaporator coils and surge drum heights HL are identical.
The interconnecting refrigerant pipe line diameters have been selected in accordance
with good design practice. The impact of the difference between pressure/
temperature gradients for the two refrigerants is evident in Table 1. The practical
consequence of the greater temperature change of NH3 is reduced LMTD across the
NH3 evaporator and hence lower performance.
Dry expansion refrigerant feed is very common in commercial and small to medium
size industrial applications. Some characteristics of dry expansion feed are less
favorable than those of liquid overfeed. This becomes evident at evaporator part-load
i.e., at reduced face velocity, reduced ETD and when frost accumulates on the coil.
A comparison between dry expansion and liquid overfeed evaporators is provided
(Figure 15). The leveling or declining capacity at high ETDs for dry expansion feed
coils is evidence that the refrigerant side pressure (temperature) drop becomes so
Technical Paper #7 IIAR 2009 13
Extended Surface Air Coolers for Industrial Plants the Contractors Perspective
high that it starts to jeopardize LMTD and hence overall capacity. The liquid overfeed
coil capacity continues to climb when exposed to the same operating condition.
Air Pressure Drop
The air pressure drop through a finned air cooler is a function of air cooler geometry
and face velocity. Figure 16 provides some typical air pressure drop comparisons for
a number of geometries at identical face velocities. The geometries, coil layouts and
operating conditions are identical to those shown in Figure 2. The air pressure drop
increases with increasing face velocity. The rate of increase may be approximated as
the square of the face velocity increase.
Energy Optimization
The gross air cooler capacity increases with increasing face velocity. Gross and net
air cooler capacities are in this context defined as cooler capacities without and with
correction for fan power respectively. To force a certain quantity of air through a
cooling coil with a certain air pressure drop requires a certain amount of fan power.
In the majority of refrigeration, chilling and freezing applications, the fan power
is converted to heat, which enters the refrigerated space and in turn needs to be
removed again by the air cooler. In most cases it is therefore only the net cooler
capacity (gross capacity minus fan heat) that is available for refrigerating the space
in question.
Plotting net cooler capacity as a function of face velocity using the ETD as the
parameter reveals that the most energy efficient face velocity is not constant, but
varies depending on ETD, (Figure 17). For relatively high ETDs, it is more energy
efficient to operate with relatively high face velocities and vice versa. These data sets
may be generated for any combination of air cooler and fans. The data set is useful
14 IIAR 2009 Technical Paper #7
2009 IIAR Industrial Refrigeration Conference & Exhibition, Dallas, Texas
for producing a look-up table used in the electronic control system for an evaporator
where the fans are controlled by means of a variable frequency drive (VFD). The line
shown through the optimum operating points is of significance for the establishment
of this look-up table. Measurement of refrigerant and air entering temperature defines
ETD and this in turn enables the control system to automatically set the most energy
efficient fan speed.
Humidity
The minimization of chilling weight loss is of vital importance during the cooling of
most perishable goods where the cooling process uses air as the secondary refrigerant
surrounding the goods (Figure 18). In addition, the maintenance of high relative air
humidity in spaces where perishable goods such as leafy vegetables, flowers and
fruits are stored is equally important to maximize shelf life. The importance of cooler
geometry and cooler layout is often overlooked in this context.
A typical average refrigeration load in a batch type beef carcass chiller with a holding
capacity of 24,000 kg (52,911 lbs) and a design chilling cycle time of 18 hours may
calculate as shown in Table 2 with an assumed chilling weight loss of 1%.
Table 2. Average heat load in a typical beef carcass chiller
Sensible Heat
[kW]/[Btu/h]
Latent Heat
[kW]/[Btu/h]Conduction 5.4 (18,442) 0Infiltration 0 0Product 35.6 (121,580) 9.3 (31,761)Fans 6.6 (22,540) 0Total 47.6 (162,563) 9.3 (31,761)
Technical Paper #7 IIAR 2009 15
Extended Surface Air Coolers for Industrial Plants the Contractors Perspective
In Table 3 is shown a comparison of estimated chilling weight loss between two air
cooler types which have identical overall surface areas. Both coolers are shown in
end view (Figure 19) and both service the carcass chiller which is the subject of the
load calculation (Table 2). One cooler is squat; the other has a relatively large face
area and is shallow in the direction of air flow.
Table 3. Estimated theoretical chilling weight loss for two different air cooler
geometries and identical total heat exchanger surface areas.
Number of coils per chiller 2 3Estimated chilling weight loss, kg (lbs) 480 (1058) 270 (595)Chilling weight loss, % 2.0 1.1Value of loss, $/p.a. (1999 values) 240,000 135,000Approximate energy costs, $/p.a. (1999 values) 10,300 12,200
The higher energy cost for the low weight loss design is due to the greater circulated
air quantity. The difference in equipment costs is around $30,000 in 1999 values with
the low weight loss solution being the most expensive. Provided the operator gets
paid for the achieved weight gain, this differential investment may be returned in
a few months.
Discussion
Correct technical selection of an extended surface air cooler for an industrial
refrigeration application is a complex matter for the refrigeration contractor. It
requires careful evaluation of a large number of issues ranging from cooling capacity,
total/sensible heat ratios, relative humidity, water droplet carry-over, defrost
frequency, sound levels and air throw to oil drainage, defrost methods, operating
weight, material suitability, hygiene, corrosion resistance, delivery time and capital
costs. If the technical selection process being undertaken by the refrigeration
16 IIAR 2009 Technical Paper #7
2009 IIAR Industrial Refrigeration Conference & Exhibition, Dallas, Texas
contractor is being complicated further by equipment manufacturers attempting
to influence purchasing decisions by way of technical marketing material displaying
varying degrees of relevance and indeed integrity, then it is not a surprise that the
whole process can become confusing, at times overwhelming and prone to an easy
way out approach.
This paper has shown variations in heat transmission coefficients of around a
factor of two as a direct result of changes to coil geometry only (i.e., variations in
tube diameters, tube centers and tube patterns). In addition, a variation in heat
transmission coefficients by a factor of almost three was shown as a direct result of
changes in materials of construction and fin thickness for constant coil geometry.
These two statements highlight the inherent danger of rules of thumb selecting air
coolers on the basis of simple surface area allocation.
An area of great significance in practice is refrigerant circuiting. The refrigerant
circuiting of an air cooler is dictated by heat transfer fundamentals. Yet there are
thousands of examples of air cooling coils performing poorly due to incorrect
circuiting. This is particularly the case in dry expansion applications where optimal
circuiting is only possible inside a relatively limited envelope of operating conditions.
The key question for the refrigeration contractor is how is it possible to evaluate
whether or not the potential supplier of a particular cooling coil is proposing the
correct circuiting? The first step is to request information. There are many examples
of the circuiting details not being disclosed by manufacturers at design stage. Once
the equipment is on site or installed it is usually too late.
Although the issue of fouling has been discussed, the issue of frost accumulation
has not. Frost accumulation on the external surfaces of the cooling coil will inhibit
air flow. A reduction in air flow will reduce cooling capacity and this has not been
accounted for in Figure 12, which focuses on the thermal resistance only. This
raises an important issue to consider for the refrigeration contractor. The issue is the
Technical Paper #7 IIAR 2009 17
Extended Surface Air Coolers for Industrial Plants the Contractors Perspective
allowance of sufficient frost volume on the external surfaces of the cooling coil
particularly at coil inletto enable continued operation without inhibiting air flow.
It is commonly known that increasing the face velocity through a cooling coil
improves heat transfer and coil capacity. What may not be readily identifiable is that
a reduction in coil face velocity from 3.5 m/s (689 fpm) to 2.5 m/s (492 fpm) may
only reduce gross coil capacity by 18% yet reduce fan power by 60% and in many
cases leave net coil capacity (gross capacity minus fan power) almost unchanged.
This represents two potential traps for the refrigeration contractor. Firstly, there is
the likelihood of making a misdirected purchasing decision on the basis of gross coil
capacity. Secondly, excess fan heat may be detrimental to some perishable products
because the consequence will be a reduction in relative room humidity.
The message for refrigeration contractors generally and particularly with respect to
the selection of extended surface air coolers is to devote the topic the engineering
attention it deserves. A well known slogan from the oil industry is oil aint oils. This
slogan is equally applicable to the refrigeration industry in the slightly modified form
coils aint coils.
18 IIAR 2009 Technical Paper #7
2009 IIAR Industrial Refrigeration Conference & Exhibition, Dallas, Texas
Nomenclature
LMTD [K] Logarithmic Mean Temperature Difference
ETD [K] Entering temperature difference
m [kg/s] mass flow
[-] Orifice contraction coefficient
A [m2] Orifice area
p [Pa] Pressure drop
[kg/m3] Density
p [-] Number of tube passes
tE [C] Evaporating temperature
tS [C] Saturated suction temperature
pR [K] Refrigerant pressure (temperature) drop
d [m] Diameter
H [m] Height
FeZn [-] Mild steel, hot dipped galvanized
SS [-] Stainless steel
Al [-] Aluminum
FIN [m] Fin thickness
kO [W/m2K] Heat transmission coefficient
u [Btu/h ft2F] Heat transmission coefficient
QE [kW] Total evaporator capacity
Technical Paper #7 IIAR 2009 19
Extended Surface Air Coolers for Industrial Plants the Contractors Perspective
QE,SENS [kW] Gross sensible evaporator capacity
Q0 [kW] Net sensible evaporator capacity
QFAN [kW] Fan heat rejection
i [W/m2K] Inside film coefficient
WFACE [m/s] Face velocity
nFAN [-] Rotational fan speed
20 IIAR 2009 Technical Paper #7
2009 IIAR Industrial Refrigeration Conference & Exhibition, Dallas, Texas
References
[1] Jensen, S.S. 1989. Extended Surface Steel Air Coolers for Industrial
Refrigeration, AIRAH Journal August 1989: 4151.
[2] Jensen S.S. 2006. Dry Expansion Feed in Dual Stage Ammonia Plants: Operating
Experiences in a Large Refrigerated Distribution Centre. Proc. 2006 IIAR
Ammonia Refrigeration Conference and Exhibition, Reno, Nevada.
[3] Koster, G.J. 1985. Grenco, sHertogenbosch, Netherlands. Energy Savings
in Ammonia Refrigeration Plant by Using Oil Scrubbers. Proc. Institute of
Refrigeration 198485. 4.1
[4] Mlhammar, . 1986. Frost Growth in Evaporators. Scandinavian Refrigeration
6/86: 314323.
[5] Jensen, S.S. 2004. Design and Selection of Industrial Finned Air Coolers for
Natural RefrigerantsA Comparison between NH3 and CO2, Proc. The Natural
Refrigerants Transition Board Design Seminar, Sydney, Australia.
[6] Jensen S.S. 2000. Carcass Chilling After Slaughter, Innovative Air Cooling and
Air Distribution Techniques. Proc. Australian Meat Council CEO Conference.
Technical Paper #7 IIAR 2009 21
Extended Surface Air Coolers for Industrial Plants the Contractors Perspective
Figure 1. Typical extended surface stainless steel/aluminum air cooler
22 IIAR 2009 Technical Paper #7
2009 IIAR Industrial Refrigeration Conference & Exhibition, Dallas, Texas
Figure 2. Impact of cooler geometry on heat transmission coefficient (u-value)
Figure 3. Impact of materials of construction and fin thickness on heat transmission coefficient
Technical Paper #7 IIAR 2009 23
Extended Surface Air Coolers for Industrial Plants the Contractors Perspective
Figure 4. Common circuiting method with horizontal headers and bottom refrigerant inlet for industrial liquid overfeed applications
Figure 5. Multiple header arrangement
24 IIAR 2009 Technical Paper #7
2009 IIAR Industrial Refrigeration Conference & Exhibition, Dallas, Texas
Figure 6. Circuit length reduction by employing vertical headers, coil shown in plan view
Figure 7. Equilibrium refrigerant flows through the circuits of a cross flow finned air cooler, high heat flux, ammonia refrigerant, liquid overfeed
Technical Paper #7 IIAR 2009 25
Extended Surface Air Coolers for Industrial Plants the Contractors Perspective
Figure 8. Impact of refrigerant circuiting on coil performance
Figure 9. Physical parallel flow circuiting for thermodynamic counter flow
26 IIAR 2009 Technical Paper #7
2009 IIAR Industrial Refrigeration Conference & Exhibition, Dallas, Texas
Figure 10. Coil circuiting with parallel flow and reversed suction return
Figure 11. Performance comparison for large low temperature finned air cooler with physical parallel flow and physical counter flow air/refrigerant flow patterns
Technical Paper #7 IIAR 2009 27
Extended Surface Air Coolers for Industrial Plants the Contractors Perspective
Figure 12. Relative impact of fouling on coil performance; fi represents inside fouling, fo outside fouling
28 IIAR 2009 Technical Paper #7
2009 IIAR Industrial Refrigeration Conference & Exhibition, Dallas, Texas
Figure 13. Coil performance as a function of liquid overfeed rate
Technical Paper #7 IIAR 2009 29
Extended Surface Air Coolers for Industrial Plants the Contractors Perspective
Figure 14. Evaporator with gravity flooded refrigerant feed
Figure 15. Capacity of an NH3 evaporator as a function of entering temperature difference and face velocity. Dry expansion (DX) and liquid overfeed (LR), air on constant at 35C (31F)
30 IIAR 2009 Technical Paper #7
2009 IIAR Industrial Refrigeration Conference & Exhibition, Dallas, Texas
Figure 16. Air pressure drops for different coil geometries; coil layouts and operating conditions as per appendix 1
Figure 17. Energy optimization at varying face velocities and entering temperature differences
Technical Paper #7 IIAR 2009 31
Extended Surface Air Coolers for Industrial Plants the Contractors Perspective
Figure 18. Commonly used batch carcass chiller layout in side elevation.
Figure 19. End view of the two different evaporator geometries and layouts used for the weight loss estimate provided in Table 3
Notes:
32 IIAR 2009 Technical Paper #7
2009 IIAR Industrial Refrigeration Conference & Exhibition, Dallas, Texas