Top Banner

of 34

Air Coolers for Meat Chilling

Nov 03, 2015

Download

Documents

Descripcion de enfriadores de aire para enfriamiento de carne
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
  • Technical Papers31st Annual Meeting

    International Institute of Ammonia Refrigeration

    March 2225, 2009

    2009 Industrial Refrigeration Conference & ExhibitionThe Hyatt Regency

    Dallas, Texas

  • ACKNOWLEDGEMENT

    The success of the 31st Annual Meeting of the International Institute of Ammonia

    Refrigeration is due to the quality of the technical papers in this volume and the labor of its

    authors. IIAR expresses its deep appreciation to the authors, reviewers and editors for their

    contributions to the ammonia refrigeration industry.

    Board of Directors, International Institute of Ammonia Refrigeration

    ABOUT THIS VOLUME

    IIAR Technical Papers are subjected to rigorous technical peer review.

    The views expressed in the papers in this volume are those of the authors, not the

    International Institute of Ammonia Refrigeration. They are not official positions of the

    Institute and are not officially endorsed

    International Institute of Ammonia Refrigeration

    1110 North Glebe Road

    Suite 250

    Arlington, VA 22201

    + 1-703-312-4200 (voice)

    + 1-703-312-0065 (fax)

    www.iiar.org

    2009 Industrial Refrigeration Conference & Exhibition

    The Hyatt Regency

    Dallas, Texas

  • IIAR 2009 1

    Technical Paper #7

    Extended Surface Air Coolers for Industrial Plants the Contractors Perspective

    Stefan S. Jensen, B.Sc.Eng. MIEAustScantec Refrigeration Technologies Pty. Ltd.

    Brisbane, Queensland, Australia

    Abstract

    In view of the very large range of evaporator coil geometries, coil material combinations, coil defrost methods and circuiting options available on the market, the industrial refrigeration contractor often faces difficulties deciding which evaporator design to use for a certain application.

    Often selections are based on rules of thumb, e.g., an allowance of a certain number of square feet of coil surface area per pound of product. Considering the fact that coil material selections, choice of refrigerant, coil circuiting and coil geometry can influence heat transmission coefficients (u-values) by up to a factor of three or more, such an approach can lead to very poor results in practice.

    Other issues are relative humidity and dehydration of the refrigerated space. There are thousands of practical applications where the quality and shelf life of the products stored or chilled are directly influenced by the equilibrium relative humidity inside the room in question. Yet often extended surface air coolers are selected with geometries to suit the manufacturer and not the application. Frequently, the result is a squat coil when the coil should have been shallow and with large face area.

    The performance impact of fouling both on the inside, but also on the outside surfaces of cooling coils is often not highlighted sufficiently by manufacturers. Extended surface air cooling coils featuring comparatively high-heat transmission coefficients (u-values) in clean condition generally display a more rapid performance deterioration as a function of increasing fouling than an equivalent coil with lower heat transmission coefficient in clean condition. It is often not in the commercial interest of coil manufacturers to disclose this information, yet it can be of crucial importance to the refrigeration plant designer.

    It is commonly known that cooling coil performance increases as a function of increasing face velocity. What is not normally available from manufacturers is optimization of face velocities for maximum plant energy efficiency. This is the contractors problem and the tools that the contractor needs to perform this task are often not readily available.

    This paper will show a range of practical performance comparisons between various coil geometries, coil materials, circuiting options, refrigerant choices, flow patterns and refrigerant feed options. These performance comparisons will have one thing in common namely the software used to perform them. The comparisons therefore represent relative information valuable to the contractor because it is information not readily available from extended surface cooling coil manufacturers under normal circumstances.

    2009 IIAR Ammonia Refrigeration Conference & Exhibition, Dallas Texas

  • Technical Paper #7 IIAR 2009 3

    Extended Surface Air Coolers for Industrial Plants the Contractors Perspective

    Introduction

    In modern industrial refrigeration applications, the extended surface air cooler is

    one of the most common components. In terms of importance for the success of an

    installation, it ranks at the level of compressors, condensers and control systems.

    Although many software packages exist for the selection and rating of air coolers,

    these are all designed for certain proprietary geometries and manufacturing ranges.

    They are therefore not readily suitable for relative performance comparisons between

    one manufacturer and the other.

    The expertise of industrial refrigeration contractors relates to the ability to

    successfully combine key plant components to form a functional refrigeration system

    to suit a certain technical application. The selection of extended surface air coolers

    can be a complex matter particularly if the outcome specified goes beyond simple

    coil performance issues and extends into factors such as product quality, weight loss,

    defrost frequency, overall energy efficiency, noise pollution, hygiene, temperature

    and air flow uniformity within a facility, freezing times, part load behavior and other

    similar performance outcomes for the system as a whole.

    Not all extended surface air cooler geometries and layouts are suited optimally to

    all applications. To some this may be a statement of the obvious and to some extent

    it is. The statement does not refer to basics like selecting the correct fin spacing for

    a freezing application. The statement makes the point that within one particular

    plant it may be necessary to employ a wide range of cooler geometries and layouts

    to achieve the optimal combination of components suitable for the application. This

    may mean mixing coil manufacturers within the same system.

    The marketing emphasis of cooler manufacturers is generally that their particular

    product offered covers the widest range of applications. This is true for those

    manufacturers who offer a wide range of geometries and construction materials.

    Those manufacturers who for one reason or another limit the offering to one or

  • 4 IIAR 2009 Technical Paper #7

    2009 IIAR Industrial Refrigeration Conference & Exhibition, Dallas, Texas

    very few coil geometries cannot cover as wide a set of applications. This paper will

    examine the contractors perspective when it comes to selecting optimal extended

    surface air coolers for a range of applications.

    The Extended Surface Air Cooler

    The typical air cooler type which is the topic of this paper is shown in principle

    (Figure 1). It consists of a tube bundle fitted with plate fins; air is forced through the

    fin side, refrigerant flows through the tubes. The tube pattern can be either square

    or triangular; the tube diameters, fin thickness, fin design, tube centre distances,

    circuiting, face velocity, refrigerant, refrigerant feed and material selections are

    variables. This paper will not cover the issues of turbulators in tubes or wavy fins

    nor will it describe any other fluid on the fin side than humid air at atmospheric

    pressure. Finally, the paper will generally be limited to the presentation of results

    to maximize clarity.

    The air cooler performance modeling methodology used for the various comparisons

    in this paper is described in earlier papers by the author [Reference 1], [Reference 2].

    Impact of Coil Geometry on Overall Heat Transmission (U-Value)

    The term, coil geometry, refers in this context to the tube pattern and the centre

    distances between the tubes. Cooling coil layout refers to the way a particular cooler

    of a particular geometry is laid out, i.e., rows high, rows deep, circuiting, finned

    length, fin spacing, etc.

    In Figure 2 is shown a range of hot dipped galvanized steel coils of different

    geometries. By using the same material throughout the range, the variation in heat

    transmission coefficients from 34.6 to 18.9 W/m2K (6.09 to 3.33 Btu/h ft2 F) is the

  • Technical Paper #7 IIAR 2009 5

    Extended Surface Air Coolers for Industrial Plants the Contractors Perspective

    result of variations in coil geometry only. All coils shown use 0.3 mm (0.0118") thick

    fin material with a 0.112 mm (0.00441") thick layer of zinc.

    Impact of Materials of Construction and Fin Thickness

    Cooling coil performances are influenced by materials of construction and fin

    thickness. This is demonstrated in Figure 3 where the coil geometry has been kept

    constant, but materials and fin thicknesses have been varied to isolate the impact of

    these variables. The variation in heat transmission coefficients from 13.2 to 37.5 W/

    m2K (2.32 to 6.60 Btu/h ft2 F) is a direct result of the changes to thermal conductivity

    of materials and fin efficiencies.

    Circuiting

    Circuiting is how the refrigerant is piped through the cooling coil. A coil can be

    piped for physical parallel flow, physical counter flow, thermodynamic counter flow,

    a mixture of physical parallel flow and counter flow and cross flow between air and

    refrigerant. In addition, the circuits can be made long or short as dictated by the

    tube diameter, refrigerant temperature, heat flux and refrigerant properties. If the

    application requires relatively short circuits and the coil in question is large, then it is

    often necessary to provide the coil with multiple headers or manifolds because there

    is a manufacturing limitation with respect to the number of circuits which can enter/

    leave a header. This makes the valve station more complicated and costly and is

    generally not in the interest of the contractor.

    The way the circuits run in relation to the force of gravity is dictated by a number

    of factors. These include oil drainage, the type of refrigerant feed, orientation of the

    coil, heat flux, type of defrost, thermostatic expansion valve sensor location and

    general refrigerant side thermodynamics. Circuiting errors are most forgiving in liquid

  • 6 IIAR 2009 Technical Paper #7

    2009 IIAR Industrial Refrigeration Conference & Exhibition, Dallas, Texas

    overfeed applications and potentially most disastrous in dry expansion feed cooling

    coils.

    The greater the turbulence on the refrigerant side, the greater the surface heat

    transfer and the greater the pressure drop. The greater the refrigerant side pressure

    drop for a volatile refrigerant, the greater the refrigerant temperature drop as the fluid

    passes through the coil. The greater the refrigerant temperature drop, the lower the

    logarithmic mean temperature difference (LMTD) all other things being equal. Lower

    LMTD translates into reduced coil capacity. This scenario presents an optimization

    problem between achieving good heat transfer on the tube side of the heat exchanger

    without jeopardizing LMTD. A relatively high refrigerant side temperature drop has

    the capacity to reduce LMTD to such an extent that any gain achieved by improved

    heat transfer is more than eroded by a reduction in temperature difference hence

    reducing overall coil capacity.

    It is generally not possible to circuit any cooling coil in an optimal manner for the

    entire operating range that the coil will encounter during its operating life. All choices

    of circuiting therefore represent a compromise. If the manufacturer is provided with

    the range of design operating conditions applicable to the coil in question then it

    is possible to determine the most reasonable circuiting for the operating envelope

    nominated. In many cases, however, the manufacturer is only provided with one

    operating point namely the maximum coil performance required. Particularly in

    dry expansion applications this can in practice lead to poor results at part load (low

    temperature difference) and/or at reduced face velocity [Reference 2].

    By far the most common circuiting method for industrial applications is shown in

    Figure 4. This shows a liquid overfeed coil with horizontal headers; liquid inlet at the

    bottom, wet return at the top; horizontal air flow and four tube passes. In effect, this

    represents a cross flow arrangement between air and refrigerant.

  • Technical Paper #7 IIAR 2009 7

    Extended Surface Air Coolers for Industrial Plants the Contractors Perspective

    If a coil such as the one shown in Figure 4 is for a low temperature application and

    is both long between the end plates and comparatively tall to meet the capacity

    requirement, then the number of tube passes needs to reduce. This is to ensure that

    the refrigerant side temperature (pressure) drop does not jeopardize LMTD to such

    an extent that overall capacity reduces. It is generally less expensive for the coil

    manufacturer to then supply a coil with multiple horizontal liquid and wet return

    headers as opposed to having one inlet and one outlet header that accommodate all

    the circuits. A typical multiple header coil is shown in Figure 5. The consequence to

    the contractor of this header arrangement is that each evaporator segment needs to

    be treated like an individual evaporator in terms of valve station design. Essentially,

    the capital cost of the air cooler has therefore been minimized at the expense of

    increased valve station costs. Often the result is an overall project cost increase

    because the additional cost of the valve station more exceeds the saving in coil costs.

    An alternative to multiple horizontal headers to achieve the correct circuit length

    is vertical headers (Figure 6). In the great majority of cases, coil depth is less

    than the coil height so the need for multiple headers can be eliminated by using

    vertical headers. However, to ensure uniform distribution of refrigerant in a liquid

    overfeed situation, each circuit inlet must have an orifice. If there are no orifices, the

    refrigerant will take the path of least resistance and the upper circuits of the coil will

    not perform. This may be illustrated with a simple example. If the refrigerant side

    pressure drop for the coil illustrated in Figure 6 is 1K (1.8F) then this translates into a

    pressure drop of 3839 Pa (0.56 psi) or 0.57 m (1.86 feet) of ammonia liquid column.

    If the vertical liquid inlet header is 1.2 m (3.94 feet) tall, then gravity will force

    the liquid refrigerant through the bottom half of the evaporator circuits leaving the

    top circuits dry. The result will be more or less a halving of the anticipated cooling

    capacity. The design driving force across the circuit orifices should be greater than

    the height of the vertical inlet header. It follows therefore that the top orifices in the

    header need to be larger than the bottom orifices to account for gravity. The mass

    flows through circular orifices may be calculated as shown:

  • 8 IIAR 2009 Technical Paper #7

    2009 IIAR Industrial Refrigeration Conference & Exhibition, Dallas, Texas

    m = * A * SQR(2 * p * ) (1)

    For the orifice contraction coefficient , a value of 0.7 may be used. For the top

    orifices in the header a design pressure drop (p) of around 0.45 to 0.6 m (1.5 to

    2 feet) of liquid column is practical and will generally not yield orifices which are

    too small and hence susceptible to blockage. The design pressure drops measured

    in liquid column for the bottom orifices are the same as for the top plus the height

    of the header. Using larger design pressure drops will reduce the size of the orifices

    to such an extent that they become susceptible to impurities. For the purposes of

    streamlining manufacturing operations, some coil manufacturers only provide a

    choice between either 3 or 4 mm (0.12" or 0.16") orifices. In most cases these

    are far too large (unless the liquid overfeed ratio is very high) and do not provide

    the appropriate graduation in size between top and bottom of the inlet header. More

    appropriate orifice sizes are around 1.7 to 2.8 mm (0.067" to 0.11"). Even with

    these orifice sizes, it is often found in practice that the liquid overfeed ratio needs to

    be elevated to around 6 to 1 to ensure adequate refrigerant distribution to all circuits

    during all operating conditions.

    The orifices in a vertical inlet header not only restrict the flow of liquidthey also

    restrict the flow of hot gas. This needs to be carefully considered when an evaporator

    is to be defrosted with hot gas. It is often found in practice that coils with vertical

    headers require longer time to defrost with hot gas than coils with horizontal headers

    where the hot gas is entered in the top wet return header hence pushing the cold

    liquid out of the bottom header relatively rapidly at commencement of defrost.

    The circuit orifices in the coil shown in Figure 6 may be eliminated by turning the

    coil 90 such that the air flows vertically up through the coil. In liquid overfeed

    applications this then enables liquid entry through the bottom header and wet return

    from the top thus creating physical parallel flow or thermodynamic counter flow.

    Simply turning the coil 90 is naturally not always physically possible, but if it is,

    then a circuiting problem can be converted to a circuiting advantage. This circuiting

  • Technical Paper #7 IIAR 2009 9

    Extended Surface Air Coolers for Industrial Plants the Contractors Perspective

    method has been used successfully in a large number of automatic tunnel freezers in

    Australia and New Zealand for about 50 years.

    There are cases where circuit orifices may be required also in coils with horizontal

    headers and horizontal air flow. In a situation where the coil is exposed to high ETD

    for example a fresh air inlet cooling coil in a food processing plantthe circuits at

    the air inlet to the coil may boil dry. This is due to the fact that high heat flux also

    creates high refrigerant side pressure drop. At the air leaving side of the coil where

    the heat flux is less, the refrigerant side pressure drop is relatively low. Without

    circuit orifices the circuits at the air leaving side are then in equilibrium supplied

    with excess refrigerant at the expense of the circuits at air entry, which are left

    starved of refrigerant. The result is a significant reduction in overall coil performance

    (Figure 7).

    The impact of circuiting on coil performance is visualized in Figure 8. The number

    of rows high, deep, fin spacing and finned length have all been kept constant.

    The number of times that the refrigerant passes through the tube bundle has been

    variedthis is referred to as the number of tube passes. The vertical axis shows

    heat transmission coefficients and gross coil capacity; the horizontal axis shows

    evaporating temperature and entering temperature difference (ETD) between air

    and refrigerant. The ETD is calculated by subtracting the evaporating temperature

    from the air on temperature of 18C (0.4F) shown. The graphs show the coil

    performance as a function of the number of tube passes. It is clear that there is no

    such thing as optimal circuiting for a wide range of operating envelopes. At 25C

    (13F) evaporating temperature (7K or 12.6F ETD), 28 passes deliver maximum

    coil performance. At 28C (18.4F) evaporating temperature, 14 passes yield

    maximum performance. In a dry expansion application such as the one shown,

    circuiting for a comparatively low refrigerant pressure drop at full load may deliver

    optimal coil performance at that point. However, practical experience has also shown

    that a coil circuited this way is likely to become difficult to control at low ETDs and

  • 10 IIAR 2009 Technical Paper #7

    2009 IIAR Industrial Refrigeration Conference & Exhibition, Dallas, Texas

    the result will be increasing liquid entrainment in the suction vapor leaving the coil.

    This is also known as liquid flood-back.

    It is possible to circuit both dry expansion coils and liquid overfeed coils such that

    the reduction in LMTD by a relatively high refrigerant side temperature (pressure)

    drop is minimized (Figure 9). Physical parallel flow translates into thermodynamic

    counter flow. Using this circuiting method will, in dry expansion applications, give

    rise to problems obtaining a suitable superheat signal for the expansion valve. These

    problems may be overcome by circuiting the last tube pass through the air inlet side

    (Figure 10). This circuiting method is termed reversed suction return. The difference

    in coil performance between reversed suction return and physical counter flow for a

    typical dry expansion coil is illustrated in Figure 11.

    Fouling

    Fouling is a layer of material with relatively poor thermal conductivity that has

    settled on the heat transfer surface of a heat exchanger. This layer has the capacity to

    create a thermal resistance and hence inhibit heat transfer. The result is a reduction

    of the overall heat transmission coefficient. In industrial extended surface air coolers,

    fouling can occur both on the refrigerant side and on the air side. On the refrigerant

    side of air coolers in ammonia plants, the most common form of fouling is oil; on the

    air side it is frost. There are other forms of fouling, but these are outside the scope of

    this paper.

    Not all air cooler geometries are affected the same way by a given fouling resistance.

    The percentage coil performance reduction as a function of the internal and external

    fouling resistances is shown in Figure 12 for two different coil geometries. It is

    evident that the performance of geometry (a) deteriorates more rapidly than that of

    geometry (b) as fouling increases. Due to the fact that fouling is almost unavoidable

    in industrial ammonia refrigeration plants, this observation can be of crucial

  • Technical Paper #7 IIAR 2009 11

    Extended Surface Air Coolers for Industrial Plants the Contractors Perspective

    importance to the contractor. A thin layer of oil of 0.05 mm (0.002") thickness on

    the refrigerant side of an ammonia air cooler is not uncommon [Reference 3]. This

    results in a fouling resistance of 0.0004 m2K/W (0.0023 ft2hrF/Btu). The impact of

    this fouling resistance is a reduction in heat transmission coefficient of 13.5% in the

    case of geometry (a). A frost layer of ~1 mm (0.04") throughout the coil represents

    a fouling resistance of around 0.008 m2K/W (0.046 ft2hrF/Btu) [Reference 4]. The

    impact of this is a capacity reduction of 27.8% and 21.4% for geometries (a) and (b)

    respectively.

    Refrigerant and Refrigerant Feed

    A very common refrigerant feed method in industrial ammonia applications is liquid

    overfeed. Figure 13 shows the performance of a typical ammonia liquid overfeed

    coil as a function of liquid overfeed rate. Although the liquid overfeed rate has little

    impact on the coil performance when viewed in isolation, excess liquid overfeed rates

    can have a significant impact on the pressure drop in the wet return line downstream

    of the evaporator. An increase in wet return line pressure drop increases the ammonia

    pressure that the coil is exposed to at the suction connection and the result is a

    reduction in coil capacity.

    Common alternatives to liquid overfeed are gravity flooded and dry expansion feeds.

    The principle of gravity flooded feed is shown in Figure 14. In equilibrium, the sum

    of pressure gains and pressure drops in the refrigerant circuit must be zero. In Table 1

    are shown the key data for a flooded evaporator with NH3 and CO2 refrigerants.

    The air flow is vertically up (Figure 14).

  • 12 IIAR 2009 Technical Paper #7

    2009 IIAR Industrial Refrigeration Conference & Exhibition, Dallas, Texas

    Table 1. Key data for NH3 and CO2 flooded evaporators

    Refrigerant NH3 CO2tE, C (F) 41.5 (42.7) 41.5 (42.7)tS, C (F) 42.4 (44.3) 41.8 (44.3)tE +PR, C (F) 39.7 (39.5) 41.46 (42.63)

    Air on/off, C (F)35.0/37.8

    (31.0/36.0)

    35.0/38.2

    (31.0/36.8)Relative humidity on/off, % 80/93 80/93Liquid overfeed rate 5.2 to 1 5.6 to 1Total cooling capacity, kW (TR) 124.8 (35.6) 143.2 (40.8)Overall heat transmission coefficient,

    service, W/m2K (Btu/h ft2 F)31.6 (5.56) 32.1 (5.65)

    d1, m (inches) 0.10226 (4.03) 0.0779 (3.07)d2, m (inches) 0.0779 (3.07) 0.0627 (2.47)d3, m (inches) 0.1282 (5.05) 0.0779 (3.07)

    For both refrigerants the evaporator coils and surge drum heights HL are identical.

    The interconnecting refrigerant pipe line diameters have been selected in accordance

    with good design practice. The impact of the difference between pressure/

    temperature gradients for the two refrigerants is evident in Table 1. The practical

    consequence of the greater temperature change of NH3 is reduced LMTD across the

    NH3 evaporator and hence lower performance.

    Dry expansion refrigerant feed is very common in commercial and small to medium

    size industrial applications. Some characteristics of dry expansion feed are less

    favorable than those of liquid overfeed. This becomes evident at evaporator part-load

    i.e., at reduced face velocity, reduced ETD and when frost accumulates on the coil.

    A comparison between dry expansion and liquid overfeed evaporators is provided

    (Figure 15). The leveling or declining capacity at high ETDs for dry expansion feed

    coils is evidence that the refrigerant side pressure (temperature) drop becomes so

  • Technical Paper #7 IIAR 2009 13

    Extended Surface Air Coolers for Industrial Plants the Contractors Perspective

    high that it starts to jeopardize LMTD and hence overall capacity. The liquid overfeed

    coil capacity continues to climb when exposed to the same operating condition.

    Air Pressure Drop

    The air pressure drop through a finned air cooler is a function of air cooler geometry

    and face velocity. Figure 16 provides some typical air pressure drop comparisons for

    a number of geometries at identical face velocities. The geometries, coil layouts and

    operating conditions are identical to those shown in Figure 2. The air pressure drop

    increases with increasing face velocity. The rate of increase may be approximated as

    the square of the face velocity increase.

    Energy Optimization

    The gross air cooler capacity increases with increasing face velocity. Gross and net

    air cooler capacities are in this context defined as cooler capacities without and with

    correction for fan power respectively. To force a certain quantity of air through a

    cooling coil with a certain air pressure drop requires a certain amount of fan power.

    In the majority of refrigeration, chilling and freezing applications, the fan power

    is converted to heat, which enters the refrigerated space and in turn needs to be

    removed again by the air cooler. In most cases it is therefore only the net cooler

    capacity (gross capacity minus fan heat) that is available for refrigerating the space

    in question.

    Plotting net cooler capacity as a function of face velocity using the ETD as the

    parameter reveals that the most energy efficient face velocity is not constant, but

    varies depending on ETD, (Figure 17). For relatively high ETDs, it is more energy

    efficient to operate with relatively high face velocities and vice versa. These data sets

    may be generated for any combination of air cooler and fans. The data set is useful

  • 14 IIAR 2009 Technical Paper #7

    2009 IIAR Industrial Refrigeration Conference & Exhibition, Dallas, Texas

    for producing a look-up table used in the electronic control system for an evaporator

    where the fans are controlled by means of a variable frequency drive (VFD). The line

    shown through the optimum operating points is of significance for the establishment

    of this look-up table. Measurement of refrigerant and air entering temperature defines

    ETD and this in turn enables the control system to automatically set the most energy

    efficient fan speed.

    Humidity

    The minimization of chilling weight loss is of vital importance during the cooling of

    most perishable goods where the cooling process uses air as the secondary refrigerant

    surrounding the goods (Figure 18). In addition, the maintenance of high relative air

    humidity in spaces where perishable goods such as leafy vegetables, flowers and

    fruits are stored is equally important to maximize shelf life. The importance of cooler

    geometry and cooler layout is often overlooked in this context.

    A typical average refrigeration load in a batch type beef carcass chiller with a holding

    capacity of 24,000 kg (52,911 lbs) and a design chilling cycle time of 18 hours may

    calculate as shown in Table 2 with an assumed chilling weight loss of 1%.

    Table 2. Average heat load in a typical beef carcass chiller

    Sensible Heat

    [kW]/[Btu/h]

    Latent Heat

    [kW]/[Btu/h]Conduction 5.4 (18,442) 0Infiltration 0 0Product 35.6 (121,580) 9.3 (31,761)Fans 6.6 (22,540) 0Total 47.6 (162,563) 9.3 (31,761)

  • Technical Paper #7 IIAR 2009 15

    Extended Surface Air Coolers for Industrial Plants the Contractors Perspective

    In Table 3 is shown a comparison of estimated chilling weight loss between two air

    cooler types which have identical overall surface areas. Both coolers are shown in

    end view (Figure 19) and both service the carcass chiller which is the subject of the

    load calculation (Table 2). One cooler is squat; the other has a relatively large face

    area and is shallow in the direction of air flow.

    Table 3. Estimated theoretical chilling weight loss for two different air cooler

    geometries and identical total heat exchanger surface areas.

    Number of coils per chiller 2 3Estimated chilling weight loss, kg (lbs) 480 (1058) 270 (595)Chilling weight loss, % 2.0 1.1Value of loss, $/p.a. (1999 values) 240,000 135,000Approximate energy costs, $/p.a. (1999 values) 10,300 12,200

    The higher energy cost for the low weight loss design is due to the greater circulated

    air quantity. The difference in equipment costs is around $30,000 in 1999 values with

    the low weight loss solution being the most expensive. Provided the operator gets

    paid for the achieved weight gain, this differential investment may be returned in

    a few months.

    Discussion

    Correct technical selection of an extended surface air cooler for an industrial

    refrigeration application is a complex matter for the refrigeration contractor. It

    requires careful evaluation of a large number of issues ranging from cooling capacity,

    total/sensible heat ratios, relative humidity, water droplet carry-over, defrost

    frequency, sound levels and air throw to oil drainage, defrost methods, operating

    weight, material suitability, hygiene, corrosion resistance, delivery time and capital

    costs. If the technical selection process being undertaken by the refrigeration

  • 16 IIAR 2009 Technical Paper #7

    2009 IIAR Industrial Refrigeration Conference & Exhibition, Dallas, Texas

    contractor is being complicated further by equipment manufacturers attempting

    to influence purchasing decisions by way of technical marketing material displaying

    varying degrees of relevance and indeed integrity, then it is not a surprise that the

    whole process can become confusing, at times overwhelming and prone to an easy

    way out approach.

    This paper has shown variations in heat transmission coefficients of around a

    factor of two as a direct result of changes to coil geometry only (i.e., variations in

    tube diameters, tube centers and tube patterns). In addition, a variation in heat

    transmission coefficients by a factor of almost three was shown as a direct result of

    changes in materials of construction and fin thickness for constant coil geometry.

    These two statements highlight the inherent danger of rules of thumb selecting air

    coolers on the basis of simple surface area allocation.

    An area of great significance in practice is refrigerant circuiting. The refrigerant

    circuiting of an air cooler is dictated by heat transfer fundamentals. Yet there are

    thousands of examples of air cooling coils performing poorly due to incorrect

    circuiting. This is particularly the case in dry expansion applications where optimal

    circuiting is only possible inside a relatively limited envelope of operating conditions.

    The key question for the refrigeration contractor is how is it possible to evaluate

    whether or not the potential supplier of a particular cooling coil is proposing the

    correct circuiting? The first step is to request information. There are many examples

    of the circuiting details not being disclosed by manufacturers at design stage. Once

    the equipment is on site or installed it is usually too late.

    Although the issue of fouling has been discussed, the issue of frost accumulation

    has not. Frost accumulation on the external surfaces of the cooling coil will inhibit

    air flow. A reduction in air flow will reduce cooling capacity and this has not been

    accounted for in Figure 12, which focuses on the thermal resistance only. This

    raises an important issue to consider for the refrigeration contractor. The issue is the

  • Technical Paper #7 IIAR 2009 17

    Extended Surface Air Coolers for Industrial Plants the Contractors Perspective

    allowance of sufficient frost volume on the external surfaces of the cooling coil

    particularly at coil inletto enable continued operation without inhibiting air flow.

    It is commonly known that increasing the face velocity through a cooling coil

    improves heat transfer and coil capacity. What may not be readily identifiable is that

    a reduction in coil face velocity from 3.5 m/s (689 fpm) to 2.5 m/s (492 fpm) may

    only reduce gross coil capacity by 18% yet reduce fan power by 60% and in many

    cases leave net coil capacity (gross capacity minus fan power) almost unchanged.

    This represents two potential traps for the refrigeration contractor. Firstly, there is

    the likelihood of making a misdirected purchasing decision on the basis of gross coil

    capacity. Secondly, excess fan heat may be detrimental to some perishable products

    because the consequence will be a reduction in relative room humidity.

    The message for refrigeration contractors generally and particularly with respect to

    the selection of extended surface air coolers is to devote the topic the engineering

    attention it deserves. A well known slogan from the oil industry is oil aint oils. This

    slogan is equally applicable to the refrigeration industry in the slightly modified form

    coils aint coils.

  • 18 IIAR 2009 Technical Paper #7

    2009 IIAR Industrial Refrigeration Conference & Exhibition, Dallas, Texas

    Nomenclature

    LMTD [K] Logarithmic Mean Temperature Difference

    ETD [K] Entering temperature difference

    m [kg/s] mass flow

    [-] Orifice contraction coefficient

    A [m2] Orifice area

    p [Pa] Pressure drop

    [kg/m3] Density

    p [-] Number of tube passes

    tE [C] Evaporating temperature

    tS [C] Saturated suction temperature

    pR [K] Refrigerant pressure (temperature) drop

    d [m] Diameter

    H [m] Height

    FeZn [-] Mild steel, hot dipped galvanized

    SS [-] Stainless steel

    Al [-] Aluminum

    FIN [m] Fin thickness

    kO [W/m2K] Heat transmission coefficient

    u [Btu/h ft2F] Heat transmission coefficient

    QE [kW] Total evaporator capacity

  • Technical Paper #7 IIAR 2009 19

    Extended Surface Air Coolers for Industrial Plants the Contractors Perspective

    QE,SENS [kW] Gross sensible evaporator capacity

    Q0 [kW] Net sensible evaporator capacity

    QFAN [kW] Fan heat rejection

    i [W/m2K] Inside film coefficient

    WFACE [m/s] Face velocity

    nFAN [-] Rotational fan speed

  • 20 IIAR 2009 Technical Paper #7

    2009 IIAR Industrial Refrigeration Conference & Exhibition, Dallas, Texas

    References

    [1] Jensen, S.S. 1989. Extended Surface Steel Air Coolers for Industrial

    Refrigeration, AIRAH Journal August 1989: 4151.

    [2] Jensen S.S. 2006. Dry Expansion Feed in Dual Stage Ammonia Plants: Operating

    Experiences in a Large Refrigerated Distribution Centre. Proc. 2006 IIAR

    Ammonia Refrigeration Conference and Exhibition, Reno, Nevada.

    [3] Koster, G.J. 1985. Grenco, sHertogenbosch, Netherlands. Energy Savings

    in Ammonia Refrigeration Plant by Using Oil Scrubbers. Proc. Institute of

    Refrigeration 198485. 4.1

    [4] Mlhammar, . 1986. Frost Growth in Evaporators. Scandinavian Refrigeration

    6/86: 314323.

    [5] Jensen, S.S. 2004. Design and Selection of Industrial Finned Air Coolers for

    Natural RefrigerantsA Comparison between NH3 and CO2, Proc. The Natural

    Refrigerants Transition Board Design Seminar, Sydney, Australia.

    [6] Jensen S.S. 2000. Carcass Chilling After Slaughter, Innovative Air Cooling and

    Air Distribution Techniques. Proc. Australian Meat Council CEO Conference.

  • Technical Paper #7 IIAR 2009 21

    Extended Surface Air Coolers for Industrial Plants the Contractors Perspective

    Figure 1. Typical extended surface stainless steel/aluminum air cooler

  • 22 IIAR 2009 Technical Paper #7

    2009 IIAR Industrial Refrigeration Conference & Exhibition, Dallas, Texas

    Figure 2. Impact of cooler geometry on heat transmission coefficient (u-value)

    Figure 3. Impact of materials of construction and fin thickness on heat transmission coefficient

  • Technical Paper #7 IIAR 2009 23

    Extended Surface Air Coolers for Industrial Plants the Contractors Perspective

    Figure 4. Common circuiting method with horizontal headers and bottom refrigerant inlet for industrial liquid overfeed applications

    Figure 5. Multiple header arrangement

  • 24 IIAR 2009 Technical Paper #7

    2009 IIAR Industrial Refrigeration Conference & Exhibition, Dallas, Texas

    Figure 6. Circuit length reduction by employing vertical headers, coil shown in plan view

    Figure 7. Equilibrium refrigerant flows through the circuits of a cross flow finned air cooler, high heat flux, ammonia refrigerant, liquid overfeed

  • Technical Paper #7 IIAR 2009 25

    Extended Surface Air Coolers for Industrial Plants the Contractors Perspective

    Figure 8. Impact of refrigerant circuiting on coil performance

    Figure 9. Physical parallel flow circuiting for thermodynamic counter flow

  • 26 IIAR 2009 Technical Paper #7

    2009 IIAR Industrial Refrigeration Conference & Exhibition, Dallas, Texas

    Figure 10. Coil circuiting with parallel flow and reversed suction return

    Figure 11. Performance comparison for large low temperature finned air cooler with physical parallel flow and physical counter flow air/refrigerant flow patterns

  • Technical Paper #7 IIAR 2009 27

    Extended Surface Air Coolers for Industrial Plants the Contractors Perspective

    Figure 12. Relative impact of fouling on coil performance; fi represents inside fouling, fo outside fouling

  • 28 IIAR 2009 Technical Paper #7

    2009 IIAR Industrial Refrigeration Conference & Exhibition, Dallas, Texas

    Figure 13. Coil performance as a function of liquid overfeed rate

  • Technical Paper #7 IIAR 2009 29

    Extended Surface Air Coolers for Industrial Plants the Contractors Perspective

    Figure 14. Evaporator with gravity flooded refrigerant feed

    Figure 15. Capacity of an NH3 evaporator as a function of entering temperature difference and face velocity. Dry expansion (DX) and liquid overfeed (LR), air on constant at 35C (31F)

  • 30 IIAR 2009 Technical Paper #7

    2009 IIAR Industrial Refrigeration Conference & Exhibition, Dallas, Texas

    Figure 16. Air pressure drops for different coil geometries; coil layouts and operating conditions as per appendix 1

    Figure 17. Energy optimization at varying face velocities and entering temperature differences

  • Technical Paper #7 IIAR 2009 31

    Extended Surface Air Coolers for Industrial Plants the Contractors Perspective

    Figure 18. Commonly used batch carcass chiller layout in side elevation.

    Figure 19. End view of the two different evaporator geometries and layouts used for the weight loss estimate provided in Table 3

  • Notes:

    32 IIAR 2009 Technical Paper #7

    2009 IIAR Industrial Refrigeration Conference & Exhibition, Dallas, Texas