Top Banner
Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units | Air Distribution Products | Air Conditioning | Fire Safety | Air Curtains and Heating Products | Tunnel Fans
268

Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Aug 11, 2020

Download

Documents

dariahiddleston
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Air ConditioningLight Commercial, Commercial and Industrial

Fans | Air Handling Units | Air Distribution Products | Air Conditioning | Fire Safety | Air Curtains and Heating Products | Tunnel Fans

Page 2: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Systemair Trust

We consider your trust in us as a supplier an important goal. It is always included in our work on all levels and in all areas whether it is a question of cooperation, quality, deliveries or documentation. This catalogue is of course a part of this work.

With this catalogue, which features products of air conditioning, we want to give you as a customer a general overview of what Systemair can offer within this field. More detailed information are available in our Online catalogue at www.systemair.com and as downloadable software. Systemair’s range of fans, air distribution products and accessories also appears in our printed main catalogue.

Our product development leads the field - latest technologies in unitdesign, fans, motors, heat recovery, chillers, fan coils,... interact to give high efficiency and with that low power consumption. Systemair has grown each year since the start and we aim to continue with this trend.

Systemair strives to be a reliable supplier of quality products. We help our customers to focus on their own business. Reliable deliveries give the customer greater possibilities to quickly complete a job, and move on to the next project.

At Systemair we call this Trust.

© Systemair 2015.Systemair reserves the right to make technical changes. For updated documentation, please refer to www.systemair.com

Page 3: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Content | 1

Content

Systemair 2

Product Range 6

Application 8

Air Cooled Chiller & Heat Pumps 10

Water Cooled Chiller, Heat Pumps and Condensing Unit 131

Free-Cooling 155

Condensing Unit 161

Residential Heat Pump 190

Water Terminals 200

Water Source Heat Pump 228

Roof Top 240

Close control 246

Direct Expansion 252

Hydrokit HPT 262

Page 4: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

2| Systemair

Skinnskatteberg, Sweden: Systemair AB, the Systemair group head office is in Skinnskatteberg, Sweden. The production is virtually fully automated with modern machinery featuring advanced computer support. Also located here is the company’s most advanced test installation for measuring technical data.

Klockgården, Sweden: Systemair’s small air handling units are manufactured at Klockgården in Skinnskatteberg. Frico’s central warehouse of approximately 8000 m2 is also located here.

Windischbuch, Germany: Production facility for fans and modular air handling units, specialized on engineered products (e.g. tunnel and jet fans). Distribution center.

Langenfeld, Germany: Production of air curtains.

Hässleholm, Sweden: VEAB is the leading European manufacturer of electric duct heaters. Production of heating and cooling coils, electric and water based.

Ukmerge, Lithuania:Production of smaller air handling units with energy recovery systems.

Maribor, Slovenia: Specialized in centrifugal smoke extract fans, EN certified.

Hasselager, Denmark: Production of modular air handling units.

Dal Eidsvoll, Norway: Production of air handling units.

Systemair worldwide

Page 5: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

3Systemair |

Bratislava, Slovakia: The factory in Bratislava manufactures air distribution products and EN certified fire and smoke dampers.

Kuala Lumpur, Malaysia:Production and marketing of products for Tunnel and garage ventilation.

Madrid, Spain: Production of air handling units for the southern European market.

Hyderabad, India: Production of air distribution products.

New Delhi, India: The factories in New Delhi and Noida manufacture grilles and diffusers.

Barlassina, Italy: Our factory in Italy, Systemair, develops and manufactures a wide range of chiller and heat pump in A class from 20 to 1.700kW.

Bouctouche, Canada: Our main North American production facility of air handling units and inline fans for commercial and residential applications is located in Bouctouche.

Kansas City, USA: Production of fans for the US market.

Istanbul, Turkey:Systemair-HSK is Turkey‘s leading manufacturer of air handling units.

Waalwijk, Netherlands:Holland Heating is Netherlands leading manufacturer of air handling units.

Tillières-sur-Avre, France: Our factory in France, Systemair, develops and manufactures: Roof top, water source heat pump, hight temperature heat pump, water terminals.

Save energy, lower running cost!Our label “Green Ventilation” features products with a high energy saving potential. All products labelled with “Green Ventilation” combine energy economy with energy efficiency.

Quality:Systemair is certified in accordance with ISO 9001; ISO 14001 and ATEX. Our research and development laboratories are one of the most modern in Europe; measurements are made in accordance with international standards like AMCA and ISO.

Kuala Lumpur, Malaysia

Skinnskatteberg, Sweden

Windischbuch, Germany

Madrid, Spain

Hasselager, Denmark

Kansas City, USA

Dal, Eidsvoll, Norway

Bouctouche, Canada

New Delhi, India

Hyderabad, India

Barlassina, Italy

Waalwijk, Netherlands Langenfeld, Germany

Tillières-sur-Avre, France

Hässleholm, Sweden Ukmerge, Lithuania

Bratislava, Slovakia Maribor, Slovenia

Istanbul, Turkey

Page 6: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

4

Systemair worldwide

The companySystemair AC, French factory of Systemair group, Founded in 1947 by Paul Vallet, is one of the globally leading manu-factures and distributors air conditioning systems.Over 60 years of experience in the design, development and production of residential, commercial and industrial applications make Systemair an indispensable actor on the european market. References are numerous in France and internationally and concern all sectors of activity including many hospitals (surgery rooms, white rooms...) industrial sites, energy-efficient office buildings, hotels, and also under naval board. Our sales department will be able to illustrate our references according to your requests.The factory benefit from ISO certifications 9001 freed deliv-ered by the most recognized certification bodies. Besides, Systemair AC participates in the certification programme Eurovent insuring by independent laboratories the check of the technical specifications according to the international standards.

The Factory of Tillières-sur-Avre

Production The Factory in France, Extends over a total area of 36.000 sqm with 150 employees. The number of employees, in-cluding the organization of sales is more than 200 people.

RangeThe factory develops and manufactures a wide range of air conditionning produts: Chillers & Heat Pumps Water Terminals Residential heat pump Water Source Heat Pump Close control Direct expansion.

Brand Products of French factory , are sold under SySTEMAIR brand.

Systemair (France)

Page 7: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

5Systemair |

Systemair |Save energy, lower running cost!Our label “Green Ventilation” features products with a high energy saving potential. All products labelled with “Green Ventilation” combine energy economy with energy efficiency.

Quality:Systemair is certified in accordance with ISO 9001; ISO 14001 and ATEX. Our research and development laboratories are one of the most modern in Europe; measurements are made in accordance with international standards like AMCA and ISO.

The factory of Barlassina

RangeThe factory, develops and manufactures a wide range of air conditioning produts: Chillers & Heat Pumps Condensing Unit Close control.

Brand Products of our Italian factory, are sold under SySTEMAIR brand.

The companySystemair, Italian factory of Systemair Group, is important in equipment for HVAC’s market from 20 to 1.700 kW suit-able for a wide range of applications of air conditioning and industrial processes.Systemair has 70 years experience in the industrial produc-tion, of which 50 years in HVAC business.Systemair Italy is equipped with high tech equipment and has one of the most modern research centers in Europe for the devlopment and testing the of chillers and heat pumps. The range of product, that is Eurovent certified, consist of Air and Water cooled chillers and heat pumps as well as condensing and conderseless unit.

Production The factory in Italy extend over a total area of 33.400 sqm and a manufacture area over of 19.400 sqm with around 200 employees.

Systemair (Italy)

Page 8: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

6 | Product range

Duct fansDuct fans for circular duct installation.

Roof fans Roof fans with circular or square con-nection.

Rectangular duct fansDuct fans with rectangular connec-tion.

Centrifugal fansCentrifugal supply single fans.

Axial fansAxial fans for duct or wall application.

Square duct fansFor different applications, there are models for ambient with high tem-perature.

Jet Axial FansJet Axial Fans for car park, tunnels and air overpression.

Fans

Systemair has the wider range of fans for use in different applications.Our range includes any type of fans, from circular ducts – hystorical product – boxed up to those of extraction, axial, and explosion-proof for the extraction of fumes. All products listed above are made in different dimensions from 100 mm in diameter to fans of large size for tunnel. All our fans are designed to meet the strict requirements, easy to use, high quality and durability.

Product range

Explosion proof fansExplosion proof fans in duct, roof or wall design.

High temperature fansSystemair provides high fire resis-tance fans till 600°C/2 hours.

Systemair has an extensive range of ventilation products: fans including smoke extractor, tunnel and car park fans, explosion proof fans, air handling units from large central units to small residential units with energy recovery, air distribution products and fire dampers. These products are installed in a variety of locations, including homes, offices, healthcare premises, shops, industrial buildings, tunnels, parking garages, training facilities, sports centres etc.

Page 9: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

7Product range |

Air distribution products

The range also includes a wideselection of air distribution productsand accessories.

Nozzle diffusersOptimum flexibility and comfort in airdistribution for rooms.

Supply, extract & transfer devicesFor mounting in ceilings or walls.

Residential ventilation

Complete energy-efficient air han-dling units with heat recovery and built in control systems. Designed to be mounted over the cooker, on walls or horizontally in attics.

Residential unitsFor homes with living areas of 60-320 m2.

Cooker hoodsIdeal for capturing odours even at low airflows.

Fire and smoke dampers Smoke extract fansHigh efficient fans to extract the combustion smoke.

Fire & smoke dampersDampers that reduce the spread ofsmoke and fire.

Air handling unitsSystemair produces a wide range of air handling units for several ap-plications, from small office to large industrial building. All range is been developped to satisfy strict needs of low energy consumption.

Page 10: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Applications

OfficesIn buildings for tertiary application, the air conditioning and the ventilation are ne-cessary during the day. The heat loads to be removed are generally generated by people present, from the lighting system, from solar radiation and by machines.Normally it is necessary the use of chillers, Heat Pump to produce cold and/or hot water to be sent to hydronic (fan coils, cassettes, ducted) to obtain an optimum air conditioning of offices.

SchoolsIn buildings for school, the load to be disposed is variable during the day due to the presence of people only for some periods, thus it is mandatory to control the users requirements during daily plant use. Systemair offers a wide range of equipment suitable for this purpose, the fan coils with EC motors allow to obtain the requiredflexibility.

Page 11: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Commercial buildingsNormally the number of people varies continuously; the optimal solution would be to use machinery for the conditioning with variable flow and with constant moni-toring of concentration of pollutants (VOC and CO2). Systemair ACʼs products can easily meet the plantʼs requirement.

IndustryIndustrial plants generate a large amount of heat that must be dissipated in the appropriate way.Systemair AC offers a wide range of products (chillers from 20 kW to 1.700 kW) that can be readily integrated industrial installation. The chiller can be used both for air conditioning and for the cooling equipment process (production of chilled water up to -10°C).

HotelsIn the hotel rooms, it is needed a high level of comfort with the minimum impact with respect to the noise level. Systemair ducted products equipped with EC motors fully comply with requirements efficiency, cooling capacity and sound impact , required by this type of installations.

Page 12: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Air Cooled Chiller & Heat Pump

SyScroll 240-660 Air CO-HP 238-654 kW 256-679 kW 410A Scroll Plate

SyScroll 140-360 Air EVO CO-HP 144-361 kW 145-361 kW 410A Scroll Plate

AQVL/AQVH 85-140 85-137 kW 87-144 kW 410A Scroll Plate

SyScroll 85-135 Air CO-HP 84-132 kW 85-133 kW 410A Scroll Plate

SyScroll 20-35 Air CO-HP 21-34 kW 21-35 kW 410A Scroll Plate

SyScroll 40-75 Air CO-HP 41-77 kW 39-76 kW 410A Scroll Plate

SysAqua 25-40L-H 25-37 kW 27-40 kW 410A Scroll Plate

SysAqua 45 to 125 L-H 46-122 kW 50-120 kW 410A Scroll Plate

Mini SysAqua DCI 5-16 5-14.5 kW 5.5-16 kW 410A Rotary Inverter Plate

INVERTER

SyScroll 20-30 Air EVO HP 20-36 kW 20-34 kW 410A Scroll Inverter Plate

INVERTER

Page 13: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

SLS HE 5204-8404 1.142-1.687 kW 134a Screw S&T evaporator

SyScrew 360-1300 Air CO 365-1.316 kW 134a Screw Shell & Tube

SyScrew 370-1100 Air EVO CO 364-1.118 kW 134a Screw Shell & Tube

AQWH 1404-2406 359-602 kW 420-702 kW 410A Scroll Plate

VLS/VLH604-1204 153-307 kW 170-337 kW 410A Scroll Plate

Page 14: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Air cooled Chiller & Heat Pump12

Selection guide Air Cooled Chiller

Product Range Capacity EER Flow rate Acoustic Power Size (LxHxP)

SySc

roll

20-3

5 Ai

r CO SyScroll 20

Air CO 20,8 kW 3,12 0,97 l/s 73 1.477 x

1.615 x 539

SyScroll 25 Air CO

24,4 kW 3,29 1,14 l/s 74 1.477 x 1.615 x 539

SyScroll 30 Air CO

28,2 kW 3,14 1,32 l/s 74 1.477 x 1.615 x 539

SyScroll 35 Air CO

33,7 kW 2,93 1,59 l/s 75 1.477 x 1.615 x 539

SysA

qua

L

SysAqua 25 L

26,6 kW 3,09 1,19 l/s 75 1.000 x 1.983 x 1.000

SysAqua 30 L

28,3 kW 3,03 1,27 l/s 75 1.000 x 1.983 x 1.000

SysAqua 35 L

37,6 kW 2,97 1,69 l/s 76 1.000 x 1.983 x 1.000

SysAqua 40 L

39,3 kW 2,88 1,75 l/s 76 1.000 x 1.983 x 1.000

SySc

roll

40-7

5 Ai

r CO

SyScroll 40 Air CO

40,8 kW 2,91 1,9 l/s 80 1.750 x 1.580 x 1.100

SyScroll 45 Air CO

44,8 kW 2,77 2,1 l/s 81 1.750 x 1.580 x 1.100

SyScroll 50 Air CO

51,9 kW 2,79 2,4 l/s 81 1.750 x 1.580 x 1.100

SyScroll 60 Air CO

60,9 kW 2,97 2,8 l/s 85 2.200 x 1.580 x 1.100

SyScroll 65 Air CO

68,9 kW 2,93 3,2 l/s 86 2.200 x 1.580 x 1.100

SyScroll 75 Air CO

76,7 kW 2,75 3,6 l/s 86 2.200 x 1.580 x 1.100

SysA

qua

L

SysAqua 45 L

49,1 kW 2,91 2,22 l/s 79 2.180 x 1.986 x 1.160

SysAqua55 L

56 kW 2,85 2,52 l/s 79 2.180 x 1.986 x 1.160

SysAqua65 L

69,1 kW 3,13 3,13 l/s 79 2.180 x 1.986 x 1.160

SysAqua75 L

75,1 kW 3,10 3,41 l/s 79 2.180 x 1.986 x 1.160

SysAqua90 L

96,0 kW 2,79 4,36 l/s 82 2.180 x 1.986 x 1.160

SysAqua 105 L

111,5 kW 2,93 5,05 l/s 82 2.180 x 1.986 x 1.160

SysAqua125 L 2,76 5,80 l/s 82 2.180 x

1.986 x 1.160

SySc

roll

85-1

35 A

ir CO

SyScroll 85 Air CO

84,2 kW 3,09 4,02 l/s 84 3.000 x 2.250 x 1.100

SyScroll 95 Air CO

93,2 kW 2,96 4,44 l/s 84 3.000 x 2.250 x 1.100

SyScroll 105 Air CO

104,6 kW 2,77 5 l/s 88 3.000 x 2.250 x 1.100

SyScroll 120 Air CO

118,6 kW 2,82 5,6 l/s 88 3.500 x 2.250 x 1.100

SyScroll 135 Air CO

2,78 6,3 l/s 88 3.500 x 2.250 x 1.100

AQVL

85-

140

AQVL 85 83,3 kW 3,08 3,9 l/s 85 2.555 x

2.185 x 1.095

AQVL 95 93,3 3,01 4,4 l/s 85 2.555 x

2.185 x 1.095

AQVL 105 102,6 kW 3,05 4,9 l/s 85 2.555 x

2.185 x 1.095

AQVL 115 110,5 kW 3,02 5,2 l/s 85 2.555 x

2.185 x 1.095

AQVL 125 121,6 kW 2,97 5,8 l/s 89 3.155 x

2.185 x 1.095

AQVL 140 2,96 6,5 l/s 89 3.155 x 2.185 x 1.095

132,1 kW

136,5 kW

128 kW

Page 15: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Air cooled Chiller & Heat Pump | 13

Air Cooled Chiller &

heAt PumP

Product Range Capacity EER Flow rate Acoustic Power Size (LxHxP)

SySc

roll

140-

360

Air E

vo C

O

SyScroll 140 Air Evo CO

144 kW 3,22 6,9 l/s 90 4.000 x 2.600 x 1.100

SyScroll 170 Air Evo CO

168,6 kW 3,11 8,0 l/s 90 4.000 x 2.600 x 1.100

SyScroll 200 Air Evo CO

196,4 kW 3,17 9,4 l/s 92 3.500 x 2.600 x 2.150

SyScroll 230 Air Evo CO

229,9 kW 3,11 11,0 l/s 92 3.500 x 2.600 x 2.150

SyScroll 260 Air Evo CO

262,6 kW 3,15 12,5 l/s 93 3.500 x 2.600 x 2.150

SyScroll 280 Air Evo CO

283,5 kW 3,14 13,5 l/s 93 3.500 x 2.600 x 2.150

SyScroll 300 Air Evo CO

309,3 kW 3,14 14,8 l/s 94 4.550 x 2.600 x 2.150

SyScroll 330 Air Evo CO

330,3 kW 3,18 15,8 l/s 95 4.550 x 2.600 x 2.150

SyScroll 360 Air Evo CO

360,7 kW 3,11 17,2 l/s 95 4.550 x 2.600 x 2.150

VLS

604-

1204

VLS 604 153,4 kW 2,75 7,3 l/s 93 3.300 x

2.300 x 1.100

VLS 704 176,2 kW 2,67 8,4 l/s 93 4.300 x

2.300 x 1.100

VLS 804 198,1 kW 2,74 9,4 l/s 93 4.300 x

2.300 x 1.100

VLS 904 228,4 kW 2,75 10,9 l/s 94 4.300 x

2.300 x 1.100

VLS 1004 250,3 kW 2,88 11,9 l/s 94 4.300 x

2.300 x 1.100

VLS 1104 279,1 kW 2,79 13,3 l/s 95 4.300 x

2.300 x 1.100

VLS1204 306,9 kW 2,67 14,7 l/s 95 4.300 x

2.300 x 1.100

SySc

roll

240-

660

Air C

O

SyScroll 240 Air CO

238,1 kW 2,84 11,4 l/s 93 3.500 x 2.600 x 2.150

SyScroll 270 Air CO

267,4 kW 2,7 12,8 l/s 93 3.500 x 2.600 x 2.150

SyScroll 290 Air CO

287,4 kW 2,78 13,8 l/s 94 3.500 x 2.600 x 2.150

SyScroll 320 Air CO

316,1 kW 2,83 15,13 l/s 94 3.500 x 2.600 x 2.150

SyScroll 360 Air CO

362 kW 2,82 17,3 l/s 94 4.550 x 2.600 x 2.150

SyScroll 420 Air CO

414,2 kW 2,78 19,8 l/s 95 4.550 x 2.600 x 2.150

SyScroll 470 Air CO

469,6 kW 2,92 22,5 l/s 95 5.600 x 2.600 x 2.150

SyScroll 540 Air CO

2,9 25,6 l/s 96 5.600 x 2.600 x 2.150

SyScroll 590 Air CO

2,97 28,2 l/s 96 6.650 x 2.600 x 2.150

SyScroll 660 Air CO

2,95 31,4 l/s 97 6.650 x 2.600 x 2.150

533,7 kW

588,9 kW

654,2 kW

Page 16: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Air cooled Chiller & Heat Pump14

Selection guide Air Cooled Chiller

Product Range Capacity EER Flow rate Acoustic Power Size (LxHxP)

SySc

rew

370

-110

0 Ai

r EVO

CO

SyScrew 370 Air EVO CO

364,1 kW 3,23 17,3 l/s 97 4.600 x 2.550 x 2.200

SyScrew 400 Air EVO CO

414,5 kW 3,18 19,8 l/s 98 5.700 x 2.550 x 2.200

SyScrew 450 Air EVO CO

445,5 kW 3,11 21,2 l/s 98 5.700 x 2.550 x 2.200

SyScrew 500 Air EVO CO

502,9 kW 3,15 24,0 l/s 98 5.700 x 2.550 x 2.200

SyScrew 570 Air EVO CO

562,1 kW 3,18 26,8 l/s 99 6.700 x 2.550 x 2.200

SyScrew 650 Air EVO CO

625,5 kW 3,16 29,8 l/s 99 6.700 x 2.550 x 2.200

SyScrew 700 Air EVO CO

712,9 kW 3,19 34,0 l/s 99 7.800 x 2.550 x 2.200

SyScrew 750 Air EVO CO

749,2 kW 3,16 35,7 l/s 100 7.800 x 2.550 x 2.200

SyScrew 850 Air EVO CO

839 kW 3,21 40,0 l/s 100 8.800 x 2.550 x 2.200

SyScrew 950 Air EVO CO

961,8 kW 3,33 45,9 l/s 101 9.900 x 2.550 x 2.200

SyScrew 1000 Air EVO CO

1.019 kW 3,26 48,6 l/s 101,00 10.900 x 2.550 x 2.200

SyScrew 1100 Air EVO CO

1.117,90 kW 3,29 53,4 l/s 102,00 12.000 x 2.550 x 2.200

SySc

rew

360

-130

0 Ai

r CO

SyScrew 360 Air CO

365 kW 2,71 17,4 l/s 96 4.600 x 2.550 x 2.200

SyScrew 410 Air CO

413 kW 2,73 19,7 l/s 97 4.600 x 2.550 x 2.200

SyScrew 450 Air CO

445 kW 2,65 21, l/s 97 4.600 x 2.550 x 2.200

SyScrew 480 Air CO

480 kW 2,72 22,9 l/s 97 4.600 x 2.550 x 2.200

SyScrew 500 Air CO

505 kW 2,74 24,1 l/s 97 4.600 x 2.550 x 2.200

SyScrew 540 Air CO

540 kW 2,72 25,8 l/s 98 5.700 x 2.550 x 2.200

SyScrew 580 Air CO

575 kW 2,7 27,4 l/s 98 6.700 x 2.550 x 2.200

SyScrew 650 Air CO

652 kW 2,75 31,1 l/s 99 6.700 x 2.550 x 2.200

SyScrew 720 Air CO

713 kW 2,81 34,1 l/s 99 6.700 x 2.550 x 2.200

SyScrew 800 Air CO

794 kW 2,88 37,9 l/s 99 6.700 x 2.550 x 2.200

SyScrew 850 Air CO

851 kW 2,85 40,6 l/s 100 8.800 x 2.550 x 2.200

SyScrew 910 Air CO

909 kW 2,84 43,4 l/s 100 8.800 x 2.550 x 2.200

SyScrew 970 Air CO

971 kW 2,85 46,3 l/s 100 8.800 x 2.550 x 2.200

SyScrew 1000 Air CO

1.008 kW 3 48,1 l/s 100 8.800 x 2.550 x 2.200

SyScrew 1070 Air CO

1.071 kW 2,88 51,1 l/s 100 9.900 x 2.550 x 2.200

SyScrew 1130 Air CO

1.132 kW 2,89 54,1 l/s 101 10.900 x 2.550 x 2.200

SyScrew 1170 Air CO

1.172 kW 2,85 55,9 l/s 101 10.900 x 2.550 x 2.200

SyScrew 1200 Air CO

1.218 kW 2,82 58,2 l/s 101 10.900 x 2.550 x 2.200

SyScrew1300 Air CO 2,82 62,8 l/s 102 12.000 x

2.550 x 2.2001.316 kW

Page 17: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Air cooled Chiller & Heat Pump | 15

Air Cooled Chiller &

heAt PumP

Product Range Capacity EER Flow rate Acoustic Power Size (LxHxP)

SLS

5204

-840

4 HE

SLS 5204 HE 1.142 kW 3,50 54,5 l/s 102 12.000 x

2.550 x 2.200

SLS 5604 HE 1.208 kW 3,50 57,7 l/s 102 12.000 x

2.550 x 2.200

SLS 6004 HE

3,40 61,7 l/s 103 12.000 x 2.550 x 2.200

SLS 6404 HE

3,40 67,2 l/s 103 12.000 x 2.550 x 2.200

SLS 6804 HE

3,20 70,8 l/s 103 12.000 x 2.550 x 2.200

SLS 7204 HE

3,00 74,4 l/s 103 12.000 x 2.550 x 2.200

SLS 7804 HE

3,00 78,2 l/s 103 12.000 x 2.550 x 2.200

SLS 8404 HE

2,90 80,6 l/s 103 12.000 x 2.550 x 2.200

1.292,80 kW

1.406,40 kW

1.482,20 kW

1.557,90 kW

1.637,20 kW

1.686,90 kW

Chiller Range Capacity COP Flow rate Acoustic Power Size (LxHxP)

Min

i Sys

Aqua

DCI

Mini SysAqua DCI 5

5 kW 3,24 0,24 l/s 58 990 x 966 x 354

Mini SysAqua DCI 7

7 kW 3,20 0,33 l/s 58 990 x 966 x 354

Mini SysAqua DCI 10

10 kW 3,39 0,48 l/s 59 990 x 1327 x 354

Mini SysAqua DCI 12

11.2 kW 3,31 0,53 l/s 59 990 x 1327 x 354

Mini SysAqua DCI 14

12.5 kW 3,25 0,60 l/s 60 990 x 1327 x 354

Mini SysAqua DCI 16

14.5 kW 3,30 0,69 l/S 60 990 x 1327 x 354

SySc

roll

20-3

0 Ai

r EVO

HP

SyScroll 20 Air EVO HP

20,4 kW 3,17 0,975 l/s 74 1.477 x 1.615 x 539

SyScroll 30 Air EVO HP

26,1 kW 3,1 1,247 l/s 75 1.477 x 1.615 x 539

SySc

roll

20-3

5 Ai

r HP SyScroll 20

Air HP 20,9 kW 3,12 0,99 l/s 73 1.477 x

1.615 x 539

SyScroll 25 Air HP

24,5 kW 3,19 1,17 l/s 74 1.477 x 1.615 x 539

SyScroll 30 Air HP

28,4 kW 3,26 1,35 l/s 74 1.477 x 1.615 x 539

SyScroll 35 Air HP

35 kW 3,24 1,67 l/S 75 1.477 x 1.615 x 539

SysA

qua

H

SysAqua 25 H

26,9 kW 2,91 1,28 l/s 75 1.000 x 1.983 x 1.000

SysAqua 30 H

29,7 kW 3,02 1,41 l/s 75 1.000 x 1.983 x 1.000

SysAqua 35 H

37,3 kW 2,82 1,78 l/s 76 1.000 x 1.983 x 1.000

SysAqua 40 H

41,6 kW 3,04 1,98 l/s 76 1.000 x 1.983 x 1.000

Selection guide Air Cooled Heat Pump

Page 18: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Air cooled Chiller & Heat Pump16

Selection guide Air Cooled Heat Pump

Product Range Capacity COP Flow rate Acoustic Power Size (LxHxP)

SySc

roll

40-7

5 Ai

r HP

SyScroll 40 Air HP

39,2 kW 2,95 1,74 l/s 80 1.750 x 1.580 x 1.100

SyScroll 45 Air HP

43,7 kW 3,01 1,95 l/s 81 1.750 x 1.580 x 1.100

SyScroll 50 Air HP

51,7 kW 3,17 2,27 l/s 81 1.750 x 1.580 x 1.100

SyScroll 60 Air HP

58 kW 2,72 2,67 l/s 85 2.200 x 1.580 x 1.100

SyScroll 65 Air HP

69,1 kW 3 3,02 l/s 86 2.200 x 1.580 x 1.100

SyScroll 75 Air HP

76,3 kW 2,84 3,37 l/s 86 2.200 x 1.580 x 1.100

SysA

qua

H

SysAqua 45 H

50 kW 2,80 2,38 l/s 79 2.180 x 1.986 x 1.160

SysAqua55 H

58,4 kW 2,86 2,79 l/s 79 2.180 x 1.986 x 1.160

SysAqua65 H

69,6 kW 3,06 3,32 l/s 79 2.180 x 1.986 x 1.160

SysAqua75 H

75,9 kW 3,12 3,62 l/s 79 2.180 x 1.986 x 1.160

SysAqua90 H

88 kW 2,62 4,20 l/s 82 2.180 x 2.286 x 1.160

SysAqua 105 H

101 kW 2,63 4,82 l/s 82 2.180 x 2.286 x 1.160

SysAqua125 H

119 kW 2,62 5,68 l/s 82 2.180 x 2.286 x 1.160

SySc

roll

85-1

35 A

ir HP

SyScroll 85 Air HP

85 kW 3,14 3,77 l/s 84 3.000 x 2.250 x 1.100

SyScroll 95 Air HP

96 kW 3,12 4,16 l/s 84 3.000 x 2.250 x 1.100

SyScroll 105 Air HP

107 kW 2,82 4,69 l/s 88 3.000 x 2.250 x 1.100

SyScroll 120 Air HP

120 kW 2,82 5,44 l/s 88 3.500 x 2.250 x 1.100

SyScroll 135 Air HP

132,6 kW 2,81 5,97 l/s 88 3.500 x 2.250 x 1.100

AQVH

85-

140

AQVH 85 87 kW 3,39 3,87 l/s 85 2.555 x

2.185 x 1.095

AQVH 95 100,4 kW 3,23 4,30 l/s 85 2.555 x

2.185 x 1.095

AQVH 105 108,3 kW 3,29 4,73 l/s 85 2.555 x

2.185 x 1.095

AQVH 115 116,4 kW 3,26 5,11 l/s 85 2.555 x

2.185 x 1.095

AQVH 125 131,5 kW 3,13 5,55 l/s 89 3.155 x

2.185 x 1.095

AQVH 140 143,6 kW 3,14 6,19 l/s 89 3.155 x

2.185 x 1.095

SySc

roll

140-

360

Air E

vo H

P

SyScroll 140 Air Evo HP

144,9 kW 3,23 6,8 l/s 90 4.000 x 2.600 x 1.100

SyScroll 170 Air Evo HP

165,7 kW 3,21 7,88 l/s 90 4.000 x 2.600 x 1.100

SyScroll 200 Air Evo HP

200,1 kW 3,22 9,52 l/s 92 3.500 x 2.600 x 2.150

SyScroll 230 Air Evo HP

229 kW 3,23 10,91 l/s 92 3.500 x 2.600 x 2.150

SyScroll 260 Air Evo HP

262,3 kW 3,21 12,50 l/s 93 3.500 x 2.600 x 2.150

SyScroll 280 Air Evo HP

279,6 kW 3,2 13,30 l/s 93 3.500 x 2.600 x 2.150

SyScroll 300 Air Evo HP

305,6 kW 3,22 14,55 l/s 94 4.550 x 2.600 x 2.150

SyScroll 330 Air Evo HP

327,2 kW 3,21 15,58 l/s 95 4.550 x 2.600 x 2.150

SyScroll 360 Air Evo HP

361,4 kW 3,21 17,22 l/s 95 4.550 x 2.600 x 2.150

132,1 kW

Page 19: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Air cooled Chiller & Heat Pump | 17

Air Cooled Chiller &

heAt PumP

Product Range Capacity COP Flow rate Acoustic Power Size (LxHxP)

VLH

604-

1204

VLH 604 169,8 kW 2,93 8,11 l/s 93 3.300 x

2.300 x 1.100

VLH 704 200,1 kW 2,97 9,56 l/s 93 4.300 x

2.300 x 1.100

VLH 804 223,2 kW 3,17 10,66 l/s 93 4.300 x

2.300 x 1.100

VLH 904 254,7 kW 3,2 12,17 l/s 94 4.300 x

2.300 x 1.100

VLH 1004 270,8 kW 3,09 12,94 l/s 94 4.300 x

2.300 x 1.100

VLH 1104 302,1 kW 3,02 14,43 l/s 95 4.300 x

2.300 x 1.100

VLH 1204 337,4 kW 3,00 16,12 l/s 95 4.300 x

2.300 x 1.100

SySc

roll

240-

660

Air H

P

SyScroll 240 Air HP

255,9 kW 2,76 12,16 l/s 93 3.500 x 2.600 x 2.150

SyScroll 270 Air HP

289,1 kW 2,71 13,72 l/s 93 3.500 x 2.600 x 2.150

SyScroll 290 Air HP

313,3 kW 2,68 14,86 l/s 94 3.500 x 2.600 x 2.150

SyScroll 320 Air HP

333 kW 2,84 15,86 l/s 94 3.500 x 2.600 x 2.150

SyScroll 360 Air HP

382,4 kW 2,81 18,19 l/s 94 4.550 x 2.600 x 2.150

SyScroll 420 Air HP

444 kW 2,78 21,11 l/s 95 4.550 x 2.600 x 2.150

SyScroll 470 Air HP

491,5 kW 2,88 23,38 l/s 95 5.600 x 2.600 x 2.150

SyScroll 540 Air HP

2,91 26,47 l/s 96 5.600 x 2.600 x 2.150

SyScroll 590 Air HP

2,89 28,77 l/s 96 6.650 x 2.600 x 2.150

SyScroll 660 Air HP

2,94 32,27 l/s 97 6.650 x 2.600 x 2.150

AQW

H 14

04-2

406

AQWH 1404 420 kW 3,17 20,06 l/s 97 4.000 x

2.550 x 2.200

AQWH 1604 470,1 kW 3,21 22,46 l/s 97 4.000 x

2.550 x 2.200

AQWH 1806

3,18 26,19 l/s 98 5.000 x 2.550 x 2.200

AQWH 2106

3,23 29,96 l/s 98 6.000 x 2.550 x 2.200

AQWH 2406

3,18 33,54 l/s 98 6.000 x 2.550 x 2.200

605 kW

679,1 kW

627,2 kW

702 kW

556,4 kW

548,3 kW

Page 20: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Air cooled Chiller & Heat Pump18

Technical feature 4 sizes Cooling capacity from 20,8 to 33,7 kW One refrigerant circuit One scroll compressor New control Operating low water content in the plant Pump as standard

Accessories and options Automatic circuit breaker (standard) Buffer tank placed under unit Coil grilles Coils treatment Desuperheater Electronic expansion valve Fan speed control (standard) Mechanical gauges Power factor corrector capacitors Sequence phases control (standard) Softstart Water differential pressure switch (standard) Water filter (standard) Water flow switch

Operating limit (to be confirmed following selection software issue)

SyScroll 20-35 Air CO20 25 30 35

Min - MaxLeaving water temperature* °C from -8 to +18∆ T water K 3 - 7Air temperature °C Refer to below graphich

* Below 5°C, glycol and electronic expansion valve is required.

Chillers suitable for operation without buffer tank for water content greater than 4 liters of water per kW of cooling capacity.

-20 -15 -10 -5 0 5

10 15 20 25 30 35 40 45 50 55 60

-8 -6 -4 -2 0 2 4 6 8 10 12 14 16 18

OAT

(°C)

LWT (°C)

Water+Glycol+EEV

Water

SyScroll 20-35 Air CO - Cooling Operation

Air Cooled ChillerSyScroll 20-35 Air CO

20-33 kW Plate

Air cooled Scroll

410A

Page 21: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Air cooled Chiller & Heat Pump | 19

Air Cooled Chiller &

heAt PumPCaratteristiche tecniche AQL 20–35Technical feature

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard.3 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.4 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.

SyScroll 20-35 Air CO 20 25 30 35Cooling capacity1 kW 20,8 24,4 28,2 33,7Power input1 kW 6,67 7,41 8,97 11,5EER 100%1 3,12 3,29 3,14 2,93Energy Efficiency Class A A A BESEER 3,56 3,77 3,70 3,44Part load steps % 0-100Power supply V/Ph/Hz 400/3+N/50Startup type DirectRefrigerantType HFC 410ANumber of refrigerant circuits 1CompressorQty 1Type ScrollCrankcase heater W 70 90 90 90Internal heat exchangerQty 1Type Plate exchanger AISI 316Water flow l/s 0,97 1,14 1,32 1,59Available Static Pressure kPa 169 152 144 114Antifreeze heater W 35 35 35 35Connection type Male gas threadedInlet/outlet diameter inch 1”1/4Water drain connection inch ⅜”FanQty 2Type AxialAir flow m3/h 10.957 10.425 10.425 9.919Power input kW 0,54 0,54 0,54 0,55PumpQty 1Power input kW 0,57 0,60 0,63 0,65WeightShipping kg 254 285 289 304Operating kg 248 279 283 298DimensionsLenght mm 1.477 1.477 1.477 1.477Width mm 539 539 539 539Height mm 1.615 1.615 1.615 1.615Acoustical dataSound power level3 dB(A) 73 74 74 75Sound pressure level at 10 m4 dB(A) 41 42 42 43

Page 22: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Air cooled Chiller & Heat Pump20

SysAqua 25-40 LLeaving water temperature (without glycol) +5°C / +18°CLeaving water temperature (with glycol max 40%) +2°CExternal air temperature (Maximum) +50°CExternal air temperature (Minimum) -10°C

Air Cooled ChillerSysAqua 25-40 L

Technical feature 4 sizes Cooling capacity from 26.6 to 39.3 kW Refrigerant R410A EER up to 3.09 ESSEER up to 4.07

Main function Available with one cooling circuit Tandem scroll per refrigerant circuit Extented operating limits STD operating up to +7°C external

Available versions Low sound level Standard High temperature operation up to 50°C (STD) Return or leaving water temperature control With Hydraulic kit 1 pump STD

Product Advantages

Tandem scroll compressors per circuit for a highest efficiency at partial load

High ESEER ILTC II Controller that allows to reduce the use of an external

water tank 3,5 lt/kW Low footprint Easy maintenance Low water pressure drop Set point compensation (standard) Night mode (extra low sound level) (standard) ON OFF Remote Water flow switch factory mounted (standard) Water filter (standard) (not mounted) Phase monitor (standard) Few options, maximum features as (standard) Closed cabinet with inside the thermodynamic and hydraulic

parts

Main accessories and options

HP/BP Manometers Kit interface modbus Low temperature kit (-10°C) Compressor softstarter Power supply without neutral Aluminium fins with epoxy coating Condenser coil guards Complete hydraulic kit 1 pump medium pressure Standard Rubber antivibration pad Water level pressure switch Water tank 100 l High pressure fan

25-37 kW Plate

Air cooled Scroll

410A

Operating limit (to be confirmed following selection software issue)

Page 23: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Air cooled Chiller & Heat Pump | 21

Air Cooled Chiller &

heAt PumP

SysAqua 25-40 L 25 30 35 40Cooling Capacity kW 26,6 28,3 37,6 39,3Power input kW 8,6 9,34 13,49 13,6 Total EER 100%** 3,09 3,03 2,97 2,88 ESEER** 3,97 3,96 4,07 3,90Energy Efficiency Class B B B CPower supply 400V/3~+N/50HzStart up type Direct Direct Direct Direct Nominal current A 15,1 16,3 24 24Maximum operating current A 18,2 21 29,6 30Inrush current A 61 75 115 118Refrigerant Type HFC 410ANumber refrigerant circuits 1 1 1 1CompressorQuantity 2 2 2 2Type Scroll Scroll Scroll Scroll N° capactity steps % 0/50/100 0/50/100 0/50/100 0/50/100Crankcase heater W 40 70 70 70EvaporatorQty 1 1 1 1 Type Plate Plate Plate Plate Water flow rate m³/h 4,3 4,6 6,1 6,3Water pressure drop kPa 37 22 37 37Water volume l 1,78 2,55 2,55 2,55Antifreeze heater W 30 30 30 30CoilQty 1 1 1 1Total coil face area per coil m2 2,4 2,4 2,8 2,8Fan motorsQty 1 1 1 1Air flow m³/h 13.000 13.000 16.000 16.000Speed tr/mn 900 900 650 650Power input (unitary) W 940 940 930 930PumpQty Option 1 or 2 PumpsPower input Option 1 or 2 PumpsAvailable static pressure Option 1 or 2 PumpsHydraulic connexionType Male Gas Threaded Inlet diameter inch 1”1/2 1”1/2 1”1/2 1”1/2Outlet diameter inch 1”1/2 1”1/2 1”1/2 1”1/2DimensionsLength mm 1.000 1.000 1.000 1.000Width mm 1.000 1.000 1.000 1.000Height mm 1.983 1.983 1.983 1.983WeightOperating kg 300 330 340 340Acoustical dataSound power level* dB(A) 75 75 76 76

* Following Eurovent standard.** Following Eurovent 14511.

Technical feature

Page 24: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Air cooled Chiller & Heat Pump22

Technical feature 6 sizes Cooling capacity from 40,8 to 76,7 kW

3 versions: STD (standard version) HT ( High Temperature) HPF (High Pressure Fans) 2 Low Noise versions: Standard version (STD) Super Low Noise version (S) One refrigerant circuit 2 scroll compressors (one tandem) Operating low water content in the plant “Brine” version for process application

Accessories and options Automatic circuit breaker Coils treatments Coils grilles (standard) Compressors jackets (standard S) Electronic expansion valves Overload protection for compressors Sequencer for up to 4 chillers installation Desuperheater Fan speed control ( down to -18°C) Hydrokit with 1 or 2 pumps with or without buffer tank Hydrometer (standard) Mechanical gauges Power factor corrector capacitors Sequence phases control (standard) Softstart Water filter (standard) Water differential switch (standard) Water flow switch (standard)

Air Cooled ChillerSyScroll 40-75 Air CO

41-77 kW Plate

Air cooled Scroll

410A

Page 25: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Air cooled Chiller & Heat Pump | 23

Air Cooled Chiller &

heAt PumPOperating limit (to be confirmed following selection software issue)

SyScroll 40-75 Air CO40 45 50 60 65 75

Min - MaxLeaving water temperature * °C from -8 to +18Water ∆ T K 3 - 7Air Temperature °C Refers to following graphics

* Below 5°C, glycol and electronic expansion valve are required.

Chillers suitable for operation without buffer tank for water content greater than 4 liters of water per kW of output.

-25-20-15-10

-505

1015202530354045

WaterWater+ Glycol + EEV

Water+ Glycol + EEV + FSC Water+ FSC

LWT (°C)

OAT

(°C)

01 9 8 7 6 5 4 3 2 1 0 1- 2- 3- 4- 5- 6- 7- 8-01- 9- 11 21 31 41 51 61 71 81 91 02

S Version

-25-20-15-10

-505

10152025303540455055

WaterWater+ Glycol + EEV

LWT (°C)

OAT

(°C)

9 8 7 6 5 4 3 2 1 0 1- 2- 3- 4- 5- 6- 7- 8-01- 9- 10 11 21 31 41 51 61 71 81 91 02

HT Version

-25-20-15-10

-505

101520253035404550

WaterWater + Glycol + EEV

Water+ Glycol + EEV + FSC Water+ FSC

LWT (°C)

OAT

(°C)

9 8 7 6 5 4 3 2 1 0 1- 2- 3- 4- 5- 6- 7- 8-01- 9- 10 2011 21 31 41 51 61 71 81 91

BLN Version

T

40-50

60-75

Page 26: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Air cooled Chiller & Heat Pump24

Technical feature

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard.2 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.3 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.* HPF / HT versions with EC fan motor.

SyScroll 40-75 Air CO (STD-HPF-HT) 40 45 50 60 65 75Cooling capacity1 kW 40,8 44,8 51,9 60,9 68,9 76,7Power input1 kW 14,0 16,2 18,6 20,5 23,5 27,9EER1 2,91 2,77 2,79 2,97 2,93 2,75Energy Efficiency Class B C C B B CESEER 4,08 3,87 3,89 4,01 4,07 3,73Part load steps % 0-50-100 0-50-100 0-50-100 0-44-56-100 0-50-100 0-50-100Power supply V/Ph/Hz 400/3+N/50Startup type DirettoRefrigerantType HFC 410ANumber of refrigerant circuits 1 1 1 1 1 1CompressorQty 2 2 2 2 2 2Type ScrollCranckcase heater W 90 90 90 90 90 90EvaporatorQty 1 1 1 1 1 1Type Plate exchanger AISI 316Water flow l/h 6.884 7.572 8.774 10.317 11.680 13.032Antifreeze heater W 35 35 35 35 35 35Connection type Male GAS threadedInlet/outlet diameter inch 2” 2” 2” 2” 2” 2”Water drain connection inch ⅜” ⅜” ⅜” ⅜” ⅜” ⅜”CondenserQty 1 1 1 1 1 1Total coil face area per coil mm 2,6 2,6 2,6 3,2 3,2 3,2FanQty 1 1 1 1 1 1Air flow m3/h 14.000 14.000 13.200 21.100 21.100 21.100Speed rpm/min 680 680 680 900 900 900Power input kW 0,98 0,98 0,98 2,00 2,00 2,00Power input* kW 2,67 2,67 2,67 2,67 2,67 2,67Available static pressure* Pa from 0 to 120WeightShipping kg 403 411 436 476 483 488Operating kg 413 421 446 489 496 502DimensionsLenght mm 1.750 1.750 1.750 2.200 2.200 2.200Width mm 1.100 1.100 1.100 1.100 1.100 1.100Height mm 1.580 1.580 1.580 1.580 1.580 1.580Acoustical dataSound power level2 dB(A) 78 79 79 83 84 84Sound pressure level at 10 m3 dB(A) 47 47 47 52 52 52

Page 27: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Air cooled Chiller & Heat Pump | 25

Air Cooled Chiller &

heAt PumPCaratteristiche tecniche AQL 20–35Technical feature

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard.2 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.3 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.

SyScroll 40-75 Air CO S 40 45 50 60 65 75Cooling capacity1 kW 39,4 43,1 49,6 59,0 64,0 73,7Power input1 kW 14,3 16,6 19,4 20,7 23,6 28,7EER1 2,76 2,60 2,56 2,85 2,71 2,57Energy Efficiency Class C D D C C DESEER 3,87 3,62 3,58 3,85 3,77 3,50Part load steps % 0-50-100 0-50-100 0-50-100 0-44-56-100 0-50-100 0-50-100Power supply V/Ph/Hz 400/3+N/50Startup type DirectRefrigerantType HFC 410ANumber of refrigerant circuits 1 1 1 1 1 1CompressorQty 2 2 2 2 2 2Type ScrollCrankcase heater W 90 90 90 90 90 90EvaporatorQty 1 1 1 1 1 1Type Plate exchanger AISI 316Water flow l/h 6.656 7.293 8.376 9.976 10.853 12.522Antifreeze heater W 35 35 35 35 35 35Connection type Male gas threadedInlet/outlet diameter inch 2” 2” 2” 2” 2” 2”Water drain connection inch ⅜” ⅜” ⅜” ⅜” ⅜” ⅜”CondenserQty 1 1 1 1 1 1Total coil face area per coil mm 2,6 2,6 2,6 3,2 3,2 3,2FanQty 1 1 1 1 1 1Air flow m3/h 11.000 11.000 10.300 16.000 16.000 16.000Speed rpm/min 530 530 530 720 720 720Power input kW 0,57 0,57 0,57 1,27 1,27 1,27WeightShipping kg 403 411 436 476 483 488Operating kg 413 421 446 489 496 502DimensionsLenght mm 1.750 1.750 1.750 2.200 2.200 2.200Width mm 1.100 1.100 1.100 1.100 1.100 1.100Height mm 1.580 1.580 1.580 1.580 1.580 1.580Acoustical dataSound power level2 dB(A) 74 75 75 78 79 79Sound pressure level at 10 m3 dB(A) 42 44 44 46 47 47

Page 28: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Air cooled Chiller & Heat Pump26

Air Cooled ChillerSysAqua 45-125 L

Technical feature Cooling capacity from 49.1 to 128 kW 7 sizes Refrigerant: R410A EER up to 3.13 ESSEER up to 4.14

Main functions Available with one cooling circuit Tandem scroll per refrigerant circuit Extented operating limits STD operating up to +7°C external T

Product Advantages

Tandem scroll compressors per circuit for a highest efficiency at partial load

High ESEER ILTC II Controller that allows to reduce the use of an external

water tank 3,5 lt/kW Low footprint Easy maintenance Low water pressure drop Set point compensation (standard) Night mode (extra low sound level) std ON OFF Remote Water flow switch factory mounted (standard) Water filter (standard) (not mounted) Phase monitor (standard) Few options, maximum features as (standard)

49.1-128 kW Plate

Air cooled Scroll

410A

SysAqua 45-125 LLeaving water temperature (without glycol) +5°C / +18°CLeaving water temperature (with glycol max 40%) +2°CExternal air temperature (Maximum) +50°CExternal air temperature (Minimum) -10°C

Accessories and options HP/BP Manometers Kit interface modbus Low temperature kit (-10° C) Compressor softstarter Power supply without neutral Aluminium fins with epoxy coating Condenser coil guards Complete Hydraulic kit 2 pumps medium pressure Rubber antivibration pad Water level pressure switch Water tank 300lt High pressure fan

Operating limit (to be confirmed following selection software issue)

Page 29: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Air cooled Chiller & Heat Pump | 27

Air Cooled Chiller &

heAt PumP

SysAqua 45-125 L 45 55 65 75 90 105 125Cooling Capacity kW 49,1 56 69,1 75,1 96 111,5 128Power input kW 16,9 19,67 22,1 24,3 34,36 38,06 46,4Total EER 100%** 2,91 2,85 3,13 3,1 2,79 2,93 2,76ESEER** 4,06 4,08 4,2 4,17 4,01 4,04 4,02Energy Efficiency Class B C A A C B CPower supply 400V/3~+N/50HzStart up type Direct Direct Direct Direct Direct Direct Direct Nominal current A 30 35 42 47 62 69 84Maximum operating current A 34 39 52 57 67 77 92Inrush current A 126 134 195 201 250 300 330Refrigerant Type HFC 410ANumber refrigerant circuits 1 1 1 1 1 1 1CompressorQuantity cooling cicuits 2 2 2 2 2 2 2Type Scroll Scroll Scroll Scroll Scroll Scroll Scroll

N° capactity steps % 0/50/100 0/45/ 55/100

0/40/ 60/100

0/45/ 55/100

0/45/ 55/100

0/40/ 60/100

0/33/ 67/100

Crankcrase heater W 2*90 2*90 2*90 2*90 140 90/140 90/140EvaporatorQty 1 1 1 1 1 1 1 Type Plate Plate Plate Plate Plate Plate Plate Water flow rate m3/h 8 9,1 11,3 12,3 15,7 18,2 20,9Water pressure drop kPa 27 35 28 33 26 34 45Water volume l 4,1 4,1 6,1 6,1 10,8 10,8 10,8Antifreeze heater W 30 30 2*30 2*30 2*30 2*30 2*30CoilQty 1 1 2 2 2 2 2Total coil face area per coil m2 4,2 4,2 5,55 5,55 6,4 6,4 6,4Fan motorsQuantity 1 1 2 2 2 2 2Air flow m3/h 22.500 22.500 30.000 30.000 42.000 42.000 42.000Power input (unitary) W 2.100 2.100 930 930 2.100 2.100 2.100PumpsQty Option 1 ou 2 pumpsPower input kW Option 1 ou 2 pumpsAvailable static pressure Kpa Option 1 ou 2 pumpsHydraulic ConnectionType Male GAS Threaded Inlet diameter inch 2” 2” 2” 2” 2”1/2 2”1/2 2”1/2Outlet diameter inch 2” 2” 2” 2” 2”1/2 2”1/2 2”1/2DimensionsLength mm 2.180 2.180 2.180 2.180 2.180 2.180 2.180Width mm 1.160 1.160 1.160 1.160 1.160 1.160 1.160Height mm 1.986 1.986 1.986 1.986 2.286 2.286 2.286WeightOperating kg 490 490 560 560 870 980 1.000Acoustical dataSound power level* dB(A) 79 79 79 79 82 82 82

* Following Eurovent standard.** Following Eurovent 14511.

Technical feature

Page 30: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Air cooled Chiller & Heat Pump28

Air Cooled ChillerSyScroll 85-135 Air CO

Technical feature 5 sizes Cooling capacity from 84,2 to 132,1 kW 3 Versions:

STD (Standard version) HT (High Temperature version) HPF (High Pressure Fans version)

2 acoustic versions: Standard version (STD)

Super Low Noise version (S) One refrigerant circuit 2 Scroll compressors (Tandem) Microchannel coils Microprocessor control Electronic expansion valve as standard E-Coating coil treatment as standard “Brine” version for process application

Accessories and options Hydrokit with 1 or 2 pumps with or without buffer tank Desuperheater Unit protection grilles Sofstart BMS interface Overload protection for compressors Automatic circuit breaker Water flow switch (standard) Mechanical gauges Fan speed control Water pressure switch Water filter Power factor corrector capacitors Compressors acoustic box (standard) Sequence phases control (standard) Compressors jackets

84-132 kW Plate

Air cooled Scroll

410A

Page 31: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Air cooled Chiller & Heat Pump | 29

Air Cooled Chiller &

heAt PumP

SyScroll 85-135 Air CO85-135

Min Max

Leaving water temperature

Water °С +6 +18Water with glycol +electonic expansion valve* °С -8 +5

∆ T Water К 3 7

Air temperatureBLN °С +10 +45S °С -14 +42HT °С -16 +47

External static pressureStandard fans Pa 0High pressure fans (HPF) Pa < 120

Operating Limit (to be confirmed following selection software issue)

* For operation below 0°C contact sales office.

-20 -15 -10 -5 0 5

10 15 20 25 30 35 40 45 50

-12 -10 -8 -6 -4 -2 0 2 4 6 8 10 12 14 16 18

OAT

(°C)

LWT (°C)

Brine Version* +Water + Glycol

Brine Version* +Water + Glycol + FSC

Water +Glycol

Water +Glycol + FSC

Water

Water + FSC

STD Version

-20 -15 -10

-5 0 5

10 15 20 25 30 35 40 45 50

-12 -10 -8 -6 -4 -2 0 2 4 6 8 10 12 14 16 18

OAT

(°C)

LWT (°C)

Brine Version* +Water + Glycol

Water +Glycol Water

S Version

-20 -15 -10

-5 0 5

10 15 20 25 30 35 40 45 50 55

-12 -10 -8 -6 -4 -2 0 2 4 6 8 10 12 14 16 18

OAT

(°C)

LWT (°C)

Brine Version* +Water + Glycol

Water +Glycol Water

HT Version

Page 32: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Air cooled Chiller & Heat Pump30

Technical feature

SyScroll 85-135 Air CO 85 95 105 120 135Cooling capacity1 kW 84,2 93,2 104,6 118,6 132,1Power input1 kW 27,2 31,5 37,7 42,0 47,6EER1 3,09 2,96 2,77 2,82 2,78Energy efficiency class B C C C CESEER 3,94 4,35 4,00 4,01 4,03Part load steps 0-50-100 0-43-100 0-50-100 0-44-100 0-50-100Startup type DirectRefrigerantType HFC 410ANumber of refrigerant circuits 1CompressorQty 2Type ScrollInternal heat exchangerQty 1Type PlateWater flow rate m3/h 14,5 16,0 18,0 20,4 22,7Water pressure drop kPa 26 32 28 22 19Antifreeze heater W 130External heat exchangerQty 2Total coil face area per coil m2 2,4 3,1FanQty 2Water connectionsType Male GAS ThreadedInlet diameter inch 2”1/2Outlet diameter inch 2”1/2DimensionsLenght mm 3.000 3.500Width mm 1.100 1.100Height mm 2.250 2.250Acoustic dataSound power level2 dB(A) 84 84 88 88 88Sound pressure level3 dB(A) 52 52 56 56 56

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard.2 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.3 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.

Page 33: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Air cooled Chiller & Heat Pump | 31

Air Cooled Chiller &

heAt PumPTechnical feature

SyScroll 85-135 Air CO S 85 95 105 120 135Cooling capacity1 kW 81,1 89,3 101,4 113,5 126,0Power input1 kW 28,0 32,8 38,6 43,0 49,6EER1 2,90 2,72 2,63 2,64 2,54Energy efficiency class C C D D DESEER 3,91 4,32 3,98 4,03 4,00Part load steps % 0-50-100 0-43-100 0-50-100 0-44-100 0-50-100Startup type DirectRefrigerantType HFC 410ANumber of refrigerant circuits 1CompressorQty 2Type ScrollInternal heat exchangerQty 1Type PlateWater flow rate m3/h 13,9 15,4 17,4 19,5 21,7Water pressure drop kPa 23 28 25 20 17Antifreeze heater W 130External heat exchangerQty 2Total coil face area per coil m2 2,4 3,1FansQty 2Air flow rate m3/h 25.000 34.000 36.000Water connectionsType Male GAS ThreadedInlet diameter inch 2”1/2Outlet diameter inch 2”1/2DimensionsLenght mm 3.000 3.500Width mm 1.100 1.100Height mm 2.250 2.250Acoustic dataSound power level2 dB(A) 82 82 85 85 85Sound pressure level3 dB(A) 50 50 53 53 53

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard.2 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.3 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.

Page 34: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Air cooled Chiller & Heat Pump32

Technical feature 6 sizes Cooling capacity from 83,3 to 136,5 kW 4 versions:

STD (Standard) HSE (High Seasonal Efficiency) HT (High Temperature) HPF (High Pressure Fans)

2 acoustic versions: Standard version (STD), Extra Low Noise version (ELN)

Two refrigerant circuits Scroll compressors Microprocessor control Low operating water content in the plant Electronic expansion valve as standard “Brine” version for process application E-Coating coil treatment as standard

Accessories and options Automatic circuit breaker BMS interface Coils treatments Compressors acoustic box (standard) Compressors jackets as standard on ELN Desuperheater & Totaly heat recovery Fan speed control Hydrokit with 1 or 2 pumps with or without buffer tank Mechanical gauges Overload protection for compressors Power factor corrector capacitors Pressure switch Sequence phases control (standard) Sofstart Unit protection grilles Water differential pressure & Water flow switch (standard) Water filter

Air Cooled ChillerAQVL 85-140

Operating limit (to be confirmed following selection software issue)

AQVL 85-140 Min Max

Leaving water temperatureWater °С +5 +18Water with glycol °С 0 +18Water with glycol (Brine version) °C -8 +18

Air temperature

BLN °С +5 +47ELN °С -18 +44

HSE/HT °С -18 +50 (85-115) +47 (125-140)

External static pressureStandard fans Pa 0High Pressure Fans (HPF) Pa < 120

83-137 kW Plate

Air cooled Scroll

410A

-25-20-15-10

-505

10152025303540455055

WaterWater+ Glycol + EEV

LWT (°C)

OAT

(°C)

9 8 7 6 5 4 3 2 1 0 1- 2- 3- 4- 5- 6- 7- 8-01- 9- 10 11 21 31 41 51 61 71 81 91 02

85-115 125-140

Page 35: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Air cooled Chiller & Heat Pump | 33

Air Cooled Chiller &

heAt PumPTechnical feature

AQVL 85-140 BLN 85 95 105 115 125 140Cooling capacity1 kW 83,3 93,3 102,6 110,5 121,6 136,5Power input1 kW 27,1 31,0 33,6 36,6 40,9 46,1EER1 3,08 3,01 3,05 3,02 2,97 2,96Energy Efficiency class B B B B B BESEER 4,16 4,15 4,07 4,12 3,95 4,01EER HSE1 3,19 3,09 3,13 3,10 3,05 3,03Energy Efficiency class A B A A B BESEER HSE 4,06 4,12 4,23 4,19 3,96 4,08

Part load steps % 0-25-50- 75-100

0-25-50- 75-100

0-24-47- 74-100

0-25-50- 75-100

0-22-43- 72-100

0-25-50- 75-100

Power supply V/Ph/Hz 400/3/50Startup type DirectRefrigerantType HFC 410ANumber of refrigerant circuits 2 2 2 2 2 2CompressorQty 4 4 4 4 4 4Type ScrollCrankcase heater W 90 90 90 90 90 90EvaporatorQty 1 1 1 1 1 1Type Plate exchanger AISI 316Water flow m3/h 14.377 16.116 17.681 19.023 21.033 23.588Antifreeze heater W 130 130 130 130 130 130Connection type Male GAS threadedInlet/outlet diameter inch 2½” 2½” 2½” 2½” 2½” 2½”CondenserQty 2 2 2 2 2 2Total coil face area per coil mm 2,4 2,4 2,4 2,4 3,1 3,1FanQty 2 2 2 2 2 2Air flow m3/h 34.000 34.000 33.200 32.400 44.000 42.800Speed rpm/min 690 690 690 690 900 900Power input kW 2,1 2,1 2,1 2,1 3,4 3,4Power input HSE kW 1,2 1,2 1,2 1,2 2,4 2,4Power input HPF kW 3,6 3,6 3,6 3,6 4,6 4,6WeightShipping kg 1.033 1.047 1.084 1.116 1.151 1.230Operating kg 1.058 1.072 1.111 1.143 1.183 1.262DimensionsLength mm 2.555 2.555 2.555 2.555 3.155 3.155Width mm 1.095 1.095 1.095 1.095 1.095 1.095Height mm 2.185 2.185 2.185 2.185 2.185 2.185Acoustical dataSound power level2 dB(A) 84 84 84 84 88 88Sound pressure level3 dB(A) 52 52 52 52 56 56Sound power level HPF2 dB(A) 92 92 92 92 95 95Sound pressure level HPF3 dB(A) 60 60 60 60 63 63

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard.2 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.3 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.

Page 36: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Air cooled Chiller & Heat Pump34

Technical feature

AQVL 85-140 ELN 85 95 105 115 125 140Cooling capacity1 kW 80,6 89,9 98,3 105,6 119,6 133,5Power input1 kW 26,1 30,2 32,8 35,7 39,9 45,1EER1 2,87 2,75 2,77 2,73 2,90 2,86Energy efficiency class C C C C B CESEER 3,91 3,78 3,81 3,67 3,92 3,93EER HSE1 3,00 2,87 2,87 2,81 2,96 2,91Energy efficiency class B C C C B BESEER HSE 3,91 3,87 3,87 3,79 3,99 3,94

Part load steps % 0-25-50- 75-10

0-25-50- 75-100

0-24-47- 74-100

0-25-50- 75-100

0-22-43- 72-100

0-25-50- 75-100

Power supply V/Ph/Hz 400/3/50Startup type DirectRefrigerantType HFC 410ANumber of refrigerant circuits 2 2 2 2 2 2CompressorQty 4 4 4 4 4 4Type ScrollCrankcase heater W 90 90 90 90 90 90EvaporatorQty 1 1 1 1 1 1Type Plate exchanger AISI 316Water flow l/h 13.906 15.532 16.971 18.204 20.550 22.988Antifreeze heater W 130 130 130 130 130 130Connection type Male GAS threadedInlet/outlet diameter inch 2½” 2½” 2½” 2½” 2½” 2½”CondenserQty 2 2 2 2 2 2Total coil face area per coil m2 2,4 2,4 2,4 2,4 3,1 3,1FanQty 2 2 2 2 2 2Air flow m3/h 25.200 25.200 24.600 24.000 36.500 35.000Speed rpm/min 500 500 500 500 690 690Power input kW 1,8 1,8 1,8 1,8 2,1 2,1Power input HSE kW 0,6 0,6 0,6 0,6 1,2 1,2WeightShipping kg 1.063 1.077 1.114 1.146 1.181 1.260Operating kg 1.088 1.102 1.141 1.173 1.213 1.292DimensionsLength mm 2.555 2.555 2.555 2.555 3.155 3.155Width mm 1.095 1.095 1.095 1.095 1.095 1.095Height mm 2.185 2.185 2.185 2.185 2.185 2.185Acoustical dataSound power level2 dB(A) 82 82 82 82 86 86Sound pressure level3 dB(A) 50 50 50 50 54 54

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard.2 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.3 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.

Page 37: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Air cooled Chiller & Heat Pump | 35

Air Cooled Chiller &

heAt PumPTechnical feature

AQVL 85-140 HT 85 95 105 115 125 140Cooling capacity1 kW 86,2 97,0 106,9 115,3 124,6 139,6Power input2 kW 23,2 26,6 28,9 31,4 36,1 40,9EER 3,10 3,10 3,19 3,21 3,06 3,07ESEER 4,34 4,34 4,46 4,49 4,29 4,30

Part load steps % 0-25-50- 75-100

0-25-50- 75-100

0-24-47- 74-100

0-25-50- 75-100

0-22-43- 72-100

0-25-50- 75-100

Power supply V/Ph/Hz 400/3/50Startup type DirectRefrigerantType HFC 410ANumber of refrigerant circuits 2 2 2 2 2 2CompressorQty 4 4 4 4 4 4Type ScrollCrankcase heater W 90 90 90 90 90 90EvaporatorQty 1 1 1 1 1 1Type Plate exchanger AISI 316Water flow l/h 14.835 16.680 18.381 19.838 21.427 24.014Antifreeze heater W 130 130 130 130 130 130Connection type Male GAS threadedInlet/outlet diameter inch 2½” 2½” 2½” 2½” 2½” 2½”CondenserQty 2 2 2 2 2 2Total coil face area per coil m2 2,4 2,4 2,4 2,4 3,1 3,1FansQty 2 2 2 2 2 2Air flow m3/h 49.700 49.700 48.950 48.200 52.200 50.700Speed rpm/min 1.130 1.130 1.130 1.130 1.130 1.130Power input kW 4,6 4,6 4,6 4,6 4,6 4,6WeightShipping kg 1.033 1.047 1.084 1.116 1.151 1.230Operating kg 1.058 1.072 1.111 1.143 1.183 1.262DimensionsLength mm 2.555 2.555 2.555 2.555 3.155 3.155Width mm 1.095 1.095 1.095 1.095 1.095 1.095Height mm 2.185 2.185 2.185 2.185 2.185 2.185Acoustical dataSound power level3 dB(A) 95 95 95 95 95 95Sound pressure level4 dB(A) 63 63 63 63 63 63

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature.2 Input power (only compressors).3 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.4 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.

Page 38: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Air cooled Chiller & Heat Pump36

Air Cooled ChillerSyScroll 140-360 Air EVO CO

Technical feature 9 sizes Cooling capacity from 144 to 360,7 kW Fans versions:

STD (Standard) EC (Inverter Fans) HT (High Temperature) HPF (High Pressure Fans)

Acoustic versions: - (Basic Low Noise) L (Low Noise) S (Super Low Noise)

“Brine” version: Cooling only for process application LWT -10°C Two refrigerant circuits 4 Scroll compressors Electronic expansion valve Microchannel coils E-Coating coil treatment as standard

Accessories and options Automatic circuit breaker BMS interface Coils treatments Compressors acoustic box (standard) Compressors jackets (standard as Super Low Noise) Desuperheater and totaly heat recovery (TR version) Fan speed control (-14 °C in cooling mode – standard as

Super Low Noise version) Hydrokit with 1 or 2 pumps with or without buffer tank Mechanical gauges Overload protection for compressors Power factor corrector capacitors Sequence phases control (standard) Softstarter Unit protection grilles Water differential pressure switch (standard) Water filter Water flow switch

ENERGY EFFICIENCY

Report to performance data

COOLING MODE

2014

144-360 kW Plate

Air cooled Scroll

410A

Page 39: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Air cooled Chiller & Heat Pump | 37

Air Cooled Chiller &

heAt PumP

SyScroll 140-360 Air EVO CO140 170 200 230

Min Max Min Max Min Max Min Max

Chilled liquid

Liquid outlettemperature

Water °C +5 to +18Water with glycol* °C -10 to +5Temperature spread K 3 to 7

Maximum operating pressure bar 6

Ambient air

Air enteringtemperature cooling

- °C +5 to +48L °C +0 to +46S °C -14 to +44EC-HT °C -18 to +50

Externalstatic pressure

Temperature spread Pa 0High pressure fans Pa <120

Recommended system chilled water volume1 l 420 510 600 690Minimum capacity step % 25 25 21 19Power supply voltage2 V 400 V / 3 Ø / 50 Hz (nominal)

Operating limit (to be confirmed following selection software issue)

* For Liquid outlet temperature <0 °C provide Brine Version (available for CO; on request for HP).1 Table shows minimum water / brine volume of system (about 3 lt/kW).2 Voltage 400V +/- 10%.

SyScroll 140-360 Air EVO CO260 280 300 330 360

Min Max Min Max Min Max Min Max Min Max

High pressure fans

Liquid outlettemperature

Water °C +5 to +18Water with glycol* °C -10 to +5Temperature spread K 3 to 7

Maximum operating pressure bar 6

Ambient air

Air enteringtemperature cooling

- °C +5 to +48L °C +0 to +46S °C -14 to +44EC-HT °C -18 to +50

Externalstatic pressure

Standard fans Pa 0High pressure fans Pa <120

Recommended system chilled water volume1 l 780 840 900 990 1080Minimum capacity step % 17 16 24 23 25Power supply voltage2 V 400 V / 3 Ø / 50 Hz (nominal)

-20 -15 -10

-5 0 5

10 15 20 25 30 35 40 45 50 55 60

-12 -10 -8 -6 -4 -2 0 2 4 6 8 10 12 14 16 18

OAT

(°C)

LWT (°C)

Water + FSC

Brine Version* +Water + Glycol

Brine Version*+ Water + Glycol +

FSC

Water +Glycol

Water +Glycol +

FSC

Water

- version

-20 -15 -10 -5 0 5

10 15 20 25 30 35 40 45 50 55 60

OAT

(°C)

Water

Water + FSC

Brine Version* +Water + Glycol

Brine Version* +Water + Glycol

Water +Glycol

Acqua +Glycol +

FSC

-12 -10 -8 -6 -4 -2 0 2 4 6 8 10 12 14 16 18LWT (°C)

L version

-20 -15 -10

-5 0 5

10 15 20 25 30 35 40 45 50 55 60

-12 -10 -8 -6 -4 -2 0 2 4 6 8 10 12 14 16 18

OAT

(°C)

LWT (°C)

Brine Version*+Water + Glycol

Water +Glycol Water

S version

-20 -15 -10

-5 0 5

10 15 20 25 30 35 40 45 50 55 60

-12 -10 -8 -6 -4 -2 0 2 4 6 8 10 12 14 16 18

OAT

(°C)

LWT (°C)

WaterBrine Version* +Water + Glycol

Water +Glycol

EC-HT version

Page 40: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Air cooled Chiller & Heat Pump38

Technical feature

SyScroll 140-360 Air Evo CO (STD-EC-HPF) 140 170 200 230 260 280 300 330 360Nominal cooling capacity1 kW 144,0 168,6 196,4 229,9 262,6 283,5 309,3 330,3 360,7Input power1 kW 44,7 54,2 62,0 73,9 83,4 90,3 98,5 103,9 116,0EER1 3,22 3,11 3,17 3,11 3,15 3,14 3,14 3,18 3,11Energy efficiency class A A A A A A A A AESEER 3,96 3,81 4,00 4,00 4,05 4,02 4,01 4,10 4,00EER* 3,26 3,14 3,22 3,16 3,19 3,18 3,19 3,23 3,16ESEER* 4,16 4,00 4,20 4,22 4,27 4,24 4,21 4,26 4,20EER** 3,03 2,96 2,95 2,93 2,96 2,96 2,95 2,98 2, 93ESEER** 3,81 3,63 3,84 3,84 3,93 3,86 3,85 4,02 3,84

Total capacity steps % 25-50-75-100

25-50-75-100

21-43-71-100

19-38-69-100

17-39-67-100

16-37-68-100

24-48-71-100

23-50-73-100

25-50-75-100

RefrigerantType HFC 410ANumber of refrigerant circuits 2 2 2 2 2 2 2 2 2CompressorQty 4 4 4 4 4 4 4 4 4Type Scroll EvaporatorQty 1 1 1 2 2 2 1 1 1Type PlateWater flow m3/h 24,9 29,1 33,9 39,7 45,3 48,9 53,4 57,0 62,2Pressure drop kPa 27 37 40 35 35 41 30 34 41Water volume l 11,4 11,4 13 21,1 23,4 23,4 32,4 32,4 32,4Antifreeze heater W 130 130 130 130+130 130+130 130+130 130 130 130Air cooled condenserQty 2 2 5 5 6 6 7 8 8Total coil face area per coil m2 4,6 4,6 2,4 2,4 2,4 2,4 2,4 2,4 2,4FansQty 3 3 5 5 6 6 7 8 8Nominal speed rpm 900 900 900 900 900 900 900 900 900Total airflow m3/h 68.400 68.400 112.500 112.500 135.000 135.000 157.500 180.000 180.000Total input power kW 5,1 5,1 8,5 8,5 10,2 10,2 11,9 13,6 13,6Total input power* kW 4,5 4,5 7,5 7,5 9,0 9,0 10,5 12,0 12,0Total input power** kW 7,8 7,8 13,0 13,0 15,6 15,6 18,2 20,8 20,8External static pressure Pa 0 or 120 Pa**

Water Connections (Evaporator)Type Male GAS ThreadedInlet Diameter inch 2”1/2 2”1/2 2”1/2 3” 3” 3” 3” 3” 3”Outlet Diameter inch 2”1/2 2”1/2 2”1/2 3” 3” 3” 3” 3” 3”Water Connections (Desuperheater)Type Male GAS ThreadedInlet Diameter / Outlet Diameter inch 1”/1”WeightShipping kg 1.139 1.183 1.477 1.592 1.738 1.738 2.237 2.264 2.274Operating kg 1.157 1.200 1.492 1.617 1.765 1.705 2.286 2.303 2.313Additional weightEC-HPF versions kg 30 30 50 50 60 60 70 80 80With desuperheater kg 8,5 8,5 17 17 19 19 23 23 23With one pump kg 45 45 45 55 55 55 65 65 65With two pumps kg 95 95 95 115 115 115 140 140 140DimensionsLength mm 4.000 4.000 3.500 3.500 3.500 3.500 4.550 4.550 4.550Width mm 1.100 1.100 2.150 2.150 2.150 2.150 2.150 2.150 2.150Height mm 2.600 2.600 2.600 2.600 2.600 2.600 2.600 2.600 2.600Acoustical dataSound power level2 dB(A) 90 90 92 92 93 93 94 95 95Sound pressure level 10 m3 dB(A) 58 58 60 60 61 61 62 63 63

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard.2 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.3 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.* High Efficiency Units (EC) with inverter fans.** HPF Units with high static pressure fans.

Page 41: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Air cooled Chiller & Heat Pump | 39

Air Cooled Chiller &

heAt PumPTechnical feature

SyScroll 140-360 Air Evo CO L (STD-EC) 140 170 200 230 260 280 300 330 360Nominal cooling capacity1 kW 139,9 162,9 191,5 222,9 255,1 275,0 300,1 321,3 349,5Input power1 kW 45,0 54,9 61,4 74,3 83,6 91,1 99,0 103,7 116,5EER1 3,11 2,97 3,12 3,00 3,05 3,02 3,03 3,10 3,00Energy efficiency class A B A B B B B A BESEER 4,04 3,91 4,08 4,08 4,11 4,10 4,09 4,14 4,08EER* 3,15 3,01 3,17 3,04 3,10 3,06 3,07 3,15 3,04ESEER* 4,24 4,10 4,28 4,30 4,34 4,33 4,29 4,31 4,28

Total capacity steps % 25-50-75-100

25-50-75-100

21-43-71-100

19-38-69-100

17-39-67-100

16-37-68-100

24-48-71-100

23-50-73-100

25-50-75-100

RefrigerantType HFC 410ANumber of refrigerant circuits 2 2 2 2 2 2 2 2 2CompressorNumber 4 4 4 4 4 4 4 4 4Type Scroll EvaporatorQty 1 1 1 2 2 2 1 1 1Type PlateWater flow m3/h 24,1 28,1 33,1 38,5 44,0 47,5 51,8 55,4 60,3Pressure drop kPa 26 35 38 33 33 38 28 32 38Water volume l 11,4 11,4 13 21,1 23,4 23,4 32,4 32,4 32,4Antifreeze heater W 130 130 130 130+130 130+130 130+130 130 130 130Air cooled condenserQty 2 2 5 5 6 6 7 8 8Total coil face area per coil m2 4,6 4,6 2,4 2,4 2,4 2,4 2,4 2,4 2,4FansQty 3 3 5 5 6 6 7 8 8Nominal speed rpm 700 700 700 700 700 700 700 700 700Total airflow m3/h 55.000 55.000 92.500 92.500 111.000 111.000 129.500 148.000 148.000Total input power kW 3,6 3,6 6,0 6,0 7,2 7,2 8,4 9,6 9,6Water Connections (Evaporator)Type Male GAS ThreadedInlet Diameter inch 2”1/2 2”1/2 2”1/2 3” 3” 3” 3” 3” 3”Outlet Diameter inch 2”1/2 2”1/2 2”1/2 3” 3” 3” 3” 3” 3”Water Connections (Desuperheater)Type Male GAS ThreadedInlet Diameter inch 1” 1” 1” 1” 1” 1” 1” 1” 1”Outlet Diameter inch 1” 1” 1” 1” 1” 1” 1” 1” 1”WeightShipping kg 1.139 1.183 1.477 1.592 1.738 1.738 2.237 2.264 2.274Operating kg 1.157 1.200 1.492 1.617 1.765 1.765 2.286 2.303 2.313Additional weightEC versions kg 30 30 50 50 60 60 70 80 80With desuperheater kg 8,5 8,5 17 17 19 19 23 23 23With one pump kg 45 45 45 55 55 55 65 65 65With two pumps kg 95 95 95 115 115 115 140 140 140DimensionsLength mm 4.000 4.000 3.500 3.500 3.500 3.500 4.550 4.550 4.550Width mm 1.100 1.100 2.150 2.150 2.150 2.150 2.150 2.150 2.150Height mm 2.600 2.600 2.600 2.600 2.600 2.600 2.600 2.600 2.600Acoustical dataSound power level2 dB(A) 85 85 87 87 88 88 89 90 90Sound pressure level 10 m3 dB(A) 53 53 55 55 56 56 57 58 58

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard.2 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.3 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.* High Efficiency Units (EC) with inverter fans.

Page 42: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Air cooled Chiller & Heat Pump40

Technical feature

SyScroll 140-360 Air Evo CO S (STD-EC) 140 170 200 230 260 280 300 330 360Nominal cooling capacity1 kW 132,5 152,9 182,3 209,4 241,0 258,7 282,5 304,3 328,5Input power1 kW 47,0 57,5 63,3 78,7 88,0 96,2 104,6 108,7 123,5EER1 2,82 2,66 2,88 2,66 2,74 2,69 2,70 2,80 2,66Energy efficiency class C D C C C D C C CESEER 4,12 4,00 4,16 4,16 4,17 4,18 4,17 4,18 4,16EER* 2,86 2,69 2,92 2,70 2,78 2,72 2,74 2,84 2,70ESEER* 4,33 4,20 4,37 4,39 4,40 4,41 4,38 4,35 4,37

Total capacity steps % 25-50-75-100

25-50-75-100

21-43-71-100

19-38-69-100

17-39-67-100

16-37-68-100

24-48-71-100

23-50-73-100

25-50-75-100

RefrigerantType HFC 410ANumber of refrigerant circuits 2 2 2 2 2 2 2 2 2CompressorQty 4 4 4 4 4 4 4 4 4Type ScrollEvaporatorQty 1 1 1 2 2 2 1 1 1Type PlateWater flow m3/h 22,9 26,4 31,5 36,1 41,6 44,6 48,7 52,5 56,7Pressure drop kPa 23 31 35 29 29 34 25 29 34Water volume l 11,4 11,4 13 21,1 23,4 23,4 32,4 32,4 32,4Antifreeze heater W 130 130 130 130+130 130+130 130+130 130 130 130Air cooled condenserQty 2 2 5 5 6 6 7 8 8Total coil face area per coil m2 4,6 4,6 2,4 2,4 2,4 2,4 2,4 2,4 2,4FansQty 3 3 5 5 6 6 7 8 8Nominal speed rpm 550 550 550 550 550 550 550 550 550Total airflow m3/h 44.000 44.000 72.500 72.500 87.000 87.000 101.500 116.000 116.000Total input power kW 2,7 2,7 4,5 4,5 5,4 5,4 6,3 7,2 7,2Water Connections (Evaporator)Type Male GAS ThreadedInlet diameter inch 2”1/2 2”1/2 2”1/2 3” 3” 3” 3” 3” 3”Outlet diameter inch 2”1/2 2”1/2 2”1/2 3” 3” 3” 3” 3” 3”Water Connections (Desuperheater)Type Male GAS ThreadedInlet diameter inch 1” 1” 1” 1” 1” 1” 1” 1” 1”Outlet diameter inch 1” 1” 1” 1” 1” 1” 1” 1” 1”WeightShipping kg 1.144 1.188 1.482 1.597 1.743 1.743 2.242 2.269 2.279Operating kg 1.162 1.205 1.497 1.622 1.770 1.770 2.291 2.308 2.318Additional weightEC version kg 30 30 50 50 60 60 70 80 80With desuperheater kg 8,5 8,5 17 17 19 19 23 23 23With one pump kg 45 45 45 55 55 55 65 65 65With two pumps kg 95 95 95 115 115 115 140 140 140DimensionsLength mm 4.000 4.000 3.500 3.500 3.500 3.500 4.550 4.550 4.550Width mm 1.100 1.100 2.150 2.150 2.150 2.150 2.150 2.150 2.150Height mm 2.600 2.600 2.600 2.600 2.600 2.600 2.600 2.600 2.600Acoustical dataSound power level2 dB(A) 79 79 82 82 83 83 85 86 86Sound pressure level 10 m3 dB(A) 47 47 50 50 51 51 53 54 54

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard.2 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.3 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.* High Efficiency Units (EC) with inverter fans.

Page 43: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Air cooled Chiller & Heat Pump | 41

Air Cooled Chiller &

heAt PumPTechnical feature

SyScroll 140-360 Air Evo CO HT 140 170 200 230 260 280 300 330 360Nominal cooling capacity1 kW 145,3 170,2 197,9 232,0 264,7 286,0 312,0 332,9 363,8Input power2 kW 38,7 47,9 52,2 63,7 71,4 78,2 84,5 88,1 99,7EER 3,09 3,02 3,00 2,99 3,01 3,02 3,01 3,03 2,99Energy efficiency class B B B B B B B B BESEER 3,88 3,72 3,92 3,92 3,99 3,94 3,93 4,06 3,92

Total capacity steps % 25-50-75-100

25-50-75-100

21-43-71-100

19-38-69-100

17-39-67-100

16-37-68-100

24-48-71-100

23-50-73-100

25-50-75-100

RefrigerantType HFC 410ANumber of refrigerant circuits 2 2 2 2 2 2 2 2 2CompressorQty 4 4 4 4 4 4 4 4 4Type Scroll EvaporatorQty 1 1 1 2 2 2 1 1 1Type PlateWater flow m3/h 25,1 29,4 34,2 40,0 45,7 49,4 53,8 57,4 62,8Pressure drop kPa 28 38 41 36 36 42 31 35 42Water volume l 11,4 11,4 13 21,1 23,4 23,4 32,4 32,4 32,4Antifreeze heater W 130 130 130 130+130 130+130 130+130 130 130 130Air cooled condenserQty 2 2 5 5 6 6 7 8 8Total coil face area per coil m2 4,6 4,6 2,4 2,4 2,4 2,4 2,4 2,4 2,4FansQty 3 3 5 5 6 6 7 8 8Nominal speed rpm 1.100 1.100 1.100 1.100 1.100 1.100 1.100 1.100 1.100Total airflow m3/h 80.500 80.500 132.500 132.500 159.000 159.000 185.500 212.000 212.000Total input power kW 7,8 7,8 13,0 13,0 15,6 15,6 18,2 20,8 20,8Water Connections (Evaporator)Type Male GAS ThreadedInlet diameter inch 2”1/2 2”1/2 2”1/2 3” 3” 3” 3” 3” 3”Outlet diameter inch 2”1/2 2”1/2 2”1/2 3” 3” 3” 3” 3” 3”Water Connections (Desuperheater)Type Male GAS ThreadedInlet diameter inch 1” 1” 1” 1” 1” 1” 1” 1” 1”Outlet diameter inch 1” 1” 1” 1” 1” 1” 1” 1” 1”WeightShipping kg 1.169 1.213 1.527 1.642 1.798 1.798 2.307 2.344 2.354Operating kg 1.187 1.230 1.542 1.667 1.825 1.825 2.356 2.383 2.393Additional weightWith desuperheater kg 8,5 8,5 17 17 19 19 23 23 23With one pump kg 45 45 45 55 55 55 65 65 65With two pumps kg 95 95 95 115 115 115 140 140 140DimensionsLength mm 4.000 4.000 3.500 3.500 3.500 3.500 4.550 4.550 4.550Width mm 1.100 1.100 2.150 2.150 2.150 2.150 2.150 2.150 2.150Height mm 2.600 2.600 2.600 2.600 2.600 2.600 2.600 2.600 2.600Acoustical dataSound power level3 dB(A) 92 92 94 94 96 96 97 98 98Sound pressure level 10 m4 dB(A) 60 60 62 62 64 64 65 66 66

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature.2 Input power (only compressors).3 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.4 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.

Page 44: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Air cooled Chiller & Heat Pump42

Technical feature

SyScroll 140-360 Air Evo TR 140 170 200 230 260 280 300 330 360Nominal cooling capacity1 kW 141,8 169,7 189,2 230,5 260,5 283,7 308,1 324,1 359,8Input power2 kW 39,9 47,9 55,3 64,0 73,2 78,9 86,0 91,6 101,1EER 3,43 3,40 3,29 3,47 3,44 3,46 3,48 3,43 3,43Heat recovery capacity1 183,2 219,7 246,7 296,9 336,2 365,7 396,7 418,6 464,7

Total capacity steps % 25-50-75-100

25-50-75-100

21-43-71-100

19-38-69-100

17-39-67-100

16-37-68-100

24-48-71-100

23-50-73-100

25-50-75-100

RefrigerantType HFC 410ANumber of refrigerant circuits 2 2 2 2 2 2 2 2 2CompressorQty 4 4 4 4 4 4 4 4 4Type Scroll EvaporatorQty 1 1 1 2 2 2 1 1 1Type PlateWater flow m3/h 24,5 29,3 32,7 39,8 45,0 49,0 53,2 55,9 62,1Pressure drop kPa 26 38 37 35 34 41 30 33 41Water volume 11,4 11,4 13 21,1 23,4 23,4 32,4 32,4 32,4Inlet/outlet water connection inch 2”1/2 2”1/2 2”1/2 3” 3” 3” 3” 3” 3”Recovery Condenser Qty 1 1 1 2 2 2 1 1 1Type PlateWater flow m3/h 31,3 37,6 42,2 50,8 57,5 62,5 67,9 71,7 79,5Pressure drop kPa 43 62 62 57 56 67 49 54 67Water volume 11,4 11,4 13 21,1 23,4 23,4 32,4 32,4 32,4Inlet/outlet water connection inch 2”1/2 2”1/2 2”1/2 3” 3” 3” 3” 3” 3”WeightShipping kg 1.331 1.375 1.875 2.008 2.227 2.227 2.844 2.937 2.937Operating kg 1.342 1.386 1.885 2.028 2.250 2.250 2.876 2.969 2.969Additional weightEC version kg 30 30 50 50 60 60 70 80 80DimensionsLength mm 4.000 4.000 3.500 3.500 3.500 3.500 4.550 4.550 4.550Width mm 1.100 1.100 2.150 2.150 2.150 2.150 2.150 2.150 2.150Height mm 2.600 2.600 2.600 2.600 2.600 2.600 2.600 2.600 2.600

1 Data refers to 7°C leaving chilled water temperature and 45°C leaving condenser water temperature.2 Input power (only compressors).

Page 45: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Air cooled Chiller & Heat Pump | 43

Keep it cool.With Systemair Air Conditioning system.

AIR COOLED CHILLER &

HEAT PuMP

Page 46: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Air cooled Chiller & Heat Pump44

Air Cooled ChillerSyScroll 240-660 Air CO

Technical feature 10 sizes Cooling capacity from 238,1 to 654,2 kW 3 versions:

STD (Standard) HT (High Temperature) HPF (High Pressure Fans)

3 acoustic versions - (Basic Low Noise) L (Low Noise) S (Super Low Noise)

“Brine” version: Cooling only for process application LWT -10°C

Two refrigerant circuits 3/4/5/6 Scroll compressors Electronic expansion valve Microchannel coils E-Coating coil treatment as standard

Accessories and options Automatic circuit breaker BMS interface Coils treatments Compressors acoustic box (standard) Compressors jackets (standard for S version) Desuperheater and totaly heat recovery (TR version) Hydrokit with 1 or 2 pumps with or without buffer tank Overload protection for compressors Mechanical gauges Pressostatic fan speed control (standard for S version) Power factor corrector capacitors Sequence phases control (standard) Softstart Unit protection grilles Water flow switch Water differential pressure switch (standard) Water filter

238-654 kW Plate

Air cooled Scroll

410A

Page 47: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Air cooled Chiller & Heat Pump | 45

Air Cooled Chiller &

heAt PumPOperating limit (to be confirmed following selection software issue)

* For Liquid outlet temperature <0 °C provide Brine Version (available for CO; on request for HP).1 Table shows minimum water / brine volume of system (about 3 lt/kW).2 Voltage 400V +/- 10%.

SyScroll 420-660 Air CO420 470 540 590 660

Min Max Min Max Min Max Min Max Min Max

Chilled liquid

Liquid outlettemperature

Water °C +6 to +18Water with glycol* °C -10 to +6Temperature spread K 3 to 7

Maximum operating pressure bar 6

Ambient air

Air enteringtemperature cooling

- °C +10 to +45 +10 to +45 +10 to +45 +10 to +45 +10 to +45L °C +7 to +43 +7 to +43 +7 to +43 +7 to +43 +7 to +43S °C -14 to +43 -14 to +43 -14 to +43 -14 to +43 -14 to +43HT-HPF °C -18 to +47 -18 to +47 -18 to +47 -18 to +47 -18 to +47

Externalstatic pressure

Standard fans Pa 0High pressure fans Pa < 120

Recommended system chilled water volume1 l 1.260 1.128 1.296 1.180 1.320Minimum capacity step % 25 24 20 14 17Power supply voltage2 V 400 V / 3 Ø / 50 Hz (nominal)

SyScroll 240-360 Air CO240 270 290 320 360

Min Max Min Max Min Max Min Max Min Max

Chilled liquid

Liquid outlettemperature

Water °C +6 to +18Water with glycol* °C -10 to +6Temperature spread K 3 to 7

Maximum operating pressure bar 6

Ambient air

Air enteringtemperature cooling

- °C +10 to +45 +10 to +45 +10 to +45 +10 to +45 +10 to +45L °C +7 to +43 +7 to +43 +7 to +43 +7 to +43 +7 to +43S °C -14 to +43 -14 to +43 -14 to +43 -14 to +43 -14 to +43HT-HPF °C -18 to +47 -18 to +47 -18 to +47 -18 to +47 -18 to +47

Externalstatic pressure

Standard fans Pa 0High pressure fans Pa < 120

Recommended system chilled water volume1 l 960 1.080 1.160 1.280 1.080Minimum capacity step % 31 33 30 27 23Power supply voltage2 V 400 V / 3 Ø / 50 Hz (nominal)

-12 -10 -8 -6 -4 -2 0 2 4 6 8 10 12 14 16 18

OAT

(°C)

LWT (°C)

Water

Water + FSC Brine Version* +

Water + Glycol + FSC

Water +Glycol

Water +Glycol + FSC

-20 -15 -10

-5 0 5

10 15 20 25 30 35 40 45 50

Brine Version* +Water + Glycol

- version

-20 -15 -10

-5 0 5

10 15 20 25 30 35 40 45 50

-12 -10 -8 -6 -4 -2 0 2 4 6 8 10 12 14 16 18

OAT

(°C)

LWT (°C)

Water + FSC

Brine Version* +Water + Glycol

Brine Version*+Water + Glycol

Water +Glycol

Water +Glycol + FSC

Water

L version

-20 -15 -10

-5 0 5

10 15 20 25 30 35 40 45 50

-12 -10 -8 -6 -4 -2 0 2 4 6 8 10 12 14 16 18

OAT

(°C)

LWT (°C)

WaterBrine Version* +Water + Glycol

Water +Glycol

S version

-20 -15 -10

-5 0 5

10 15 20 25 30 35 40 45 50 55

-12 -10 -8 -6 -4 -2 0 2 4 6 8 10 12 14 16 18

OAT

(°C)

LWT (°C)

WaterBrine Version* +Water + Glycol

Water +Glycol

HT-HPF version

Page 48: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Air cooled Chiller & Heat Pump46

SyScroll 240-660 Air CO (STD-EC-HPF) 240 270 290 320 360 420 470 540 590 660Nominal cooling capacity1 kW 238,1 267,4 287,4 316,1 362,0 414,2 469,6 533,7 588,9 654,2Input power1 kW 83,8 99,0 103,4 111,6 128,3 148,7 160,9 183,9 198,1 221,6EER1 2,84 2,70 2,78 2,83 2,82 2,78 2,92 2,90 2,97 2,95Energy efficiency class C C C C C C B B B BESEER 3,75 3,62 3,80 3,89 3,93 3,95 4,01 3,87 4,01 3,98EER* 2,87 2,73 2,81 2,86 2,85 2,82 2,95 2,93 3,01 2,99ESEER* 3,84 3,69 3,89 3,98 4,02 4,04 4,10 3,95 4,09 4,06EER** 2,70 2,58 2,64 2,70 2,69 2,66 2,78 2,77 2,83 2,82ESEER** 3,40 3,33 3,44 3,53 3,55 3,57 3,64 3,54 3,66 3,73

Total capacity steps % 31-62-100

33-67-100

30-60-100

27-64-100

23-46-69-100

25-50-75-100

24-47-65-82-

100

20-40-60-800-

100

14-29-43-62-81-100

17-33-50-67-83-100

RefrigerantType HFC 410ANumber of refrigerant circuits 2CompressorQty 3 3 3 3 4 4 5 5 6 6Type Scroll EvaporatorQty 1Type PlateWater flow m3/h 41,1 46,2 49,7 54,5 62,5 71,6 81,1 92,2 101,7 113,1Pressure drop kPa 50 62 72 35 45 58 44 57 54 66Water volume l 14 14 14 24 24 24 32 32 39 39Antifreeze Heater W 130 130 130 130 130 130 130 130 130 130Air cooled condenserQty of coils 5 5 6 6 7 8 9 10 11 12Total coil face area per coil m2 2,4 2,4 2,4 2,4 2,4 2,4 2,4 2,4 2,4 2,4FanQty of fans 5 5 6 6 7 8 9 10 11 12Nominal speed rpm 900 900 900 900 900 900 900 900 900 900Total airflow m3/h 112.500 112.500 135.000 135.000 157.500 180.000 202.500 225.000 247.500 270.000Total input power kW 8,5 8,5 10,2 10,2 11,9 13,6 15,3 17,0 18,7 20,4Total input power* kW 7,5 7,5 9,0 9,0 10,5 12,0 13,5 15,0 16,5 18,0Total input power** kW 13,0 13,0 15,6 15,6 18,2 20,8 23,4 26,0 28,6 31,2External static pressure Pa 0 or 120 Pa**

Water Connections (Evaporator)Type Male GAS Threaded VictaulicInlet diameter inch 3” 3” 3” 3” 4” 4” 4” 4” 5” 5”Outlet diameter inch 3” 3” 3” 3” 4” 4” 4” 4” 5” 5”Water Connections (Desuperheater)Type Male GAS ThreadedInlet diameter/Outlet diameter inch 1”/1”WeightShipping kg 1.772 1.773 1.865 1.921 2.306 2.417 2.897 3.009 3.412 3.509Operating kg 1.786 1.787 1.879 1.945 2.330 2.441 2.934 3.047 3.456 3.553Additional weightHT-HPF versions kg 50 50 60 60 70 80 90 100 110 120With desuperheater kg 49 49 49 49 62 62 73 73 83 83DimensionsLength mm 3.500 3.500 3.500 3.500 4.550 4.550 5.600 5.600 6.650 6.650Width mm 2.150 2.150 2.150 2.150 2.150 2.150 2.150 2.150 2.150 2.150Height mm 2.600 2.600 2.600 2.600 2.600 2.600 2.600 2.600 2.600 2.600Acoustical dataSound power level2 dB(A) 93 93 94 94 94 95 95 96 96 97Sound pressure level 10 m3 dB(A) 61 61 62 62 62 63 63 64 64 64

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard.2 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.3 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.* Unità alta temperatura (HT) con ventilatori inverter.** HPF Units with high static pressure fans.

Technical feature

Page 49: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Air cooled Chiller & Heat Pump | 47

Air Cooled Chiller &

heAt PumP

SyScroll 240-660 Air CO L 240 270 290 320 360 420 470 540 590 660Nominal cooling capacity1 kW 230,0 256,9 277,6 303,8 348,5 398,6 451,7 513,1 566,5 628,8Input power1 kW 85,1 101,5 104,9 113,9 131,1 151,6 164,2 187,5 202,2 225,9EER1 2,70 2,53 2,65 2,67 2,66 2,63 2,75 2,74 2,80 2,78Energy efficiency class C D D D D D C C C CESEER 3,83 3,60 3,73 3,82 3,99 4,03 4,07 3,89 4,01 3,99

Total capacity steps % 31-62-100

33-67-100

30-60-100

27-64-100

23-46-69-100

25-50-75-100

24-47-65-82-

100

20-40-60-800-

100

14-29-43-62-81-100

17-33-50-67-83-100

RefrigerantType HFC 410ANumber of refrigerant circuits 2CompressorQty 3 3 3 3 4 4 5 5 6 6Type Scroll EvaporatorQty 1Type PlateWater flow m3/h 39,7 44,4 48,0 52,4 60,2 68,9 78,0 88,6 97,8 108,6Water pressure drop kPa 47 58 67 32 42 54 41 52 50 61Water volume l 14 14 14 24 24 24 32 32 39 39Antifreeze heater W 130 130 130 130 130 130 130 130 130 130Air cooled condenserQty 5 5 6 6 7 8 9 10 11 12Total coil face area per coil m2 2,4 2,4 2,4 2,4 2,4 2,4 2,4 2,4 2,4 2,4FanQty 5 5 6 6 7 8 9 10 11 12Nominal speed rpm 700 700 700 700 700 700 700 700 700 700Total airflow m3/h 92.500 92.500 111.000 111.000 129.500 148.000 166.500 185.000 203.500 222.000Total input power kW 6,0 6,0 7,2 7,2 8,4 9,6 10,8 12,0 13,2 14,4Water Connections (Evaporator)Type Male GAS Threaded VictaulicInlet diameter inch 3” 3” 3” 3” 4” 4” 4” 4” 5” 5”Outlet diameter inch 3” 3” 3” 3” 4” 4” 4” 4” 5” 5”Water Connections (Desuperheater)Type Male GAS ThreadedInlet diameter/Outlet diameter inch 1”/1”WeightShipping kg 1.772 1.773 1.865 1.921 2.306 2.417 2.897 3.009 3.412 3.509Operating kg 1.786 1.787 1.879 1.945 2.330 2.441 2.934 3.047 3.456 3.553Additional weightWith desuperheater kg 49 49 49 49 62 62 73 73 83 83DimensionsLength mm 3.500 3.500 3.500 3.500 4.550 4.550 5.600 5.600 6.650 6.650Width mm 2.150 2.150 2.150 2.150 2.150 2.150 2.150 2.150 2.150 2.150Height mm 2.600 2.600 2.600 2.600 2.600 2.600 2.600 2.600 2.600 2.600Acoustical dataSound power level2 dB(A) 88 88 89 89 90 91 91 91 92 92Sound pressure level 10 m3 dB(A) 56 56 57 57 58 59 59 59 59 59

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard.2 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.3 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.

Technical feature

Page 50: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Air cooled Chiller & Heat Pump48

SyScroll 240-660 Air CO S 240 270 290 320 360 420 470 540 590 660Nominal cooling capacity1 kW 214,4 236,9 259,0 280,6 323,0 368,9 418,3 474,2 524,1 580,9Input power1 kW 91,0 109,9 112,0 122,6 141,3 162,9 176,6 201,5 217,3 242,5EER1 2,36 2,16 2,31 2,29 2,29 2,26 2,37 2,35 2,41 2,40Energy efficiency class E F E F F F E E E EESEER 3,61 3,42 3,57 3,59 3,82 3,88 3,90 3,68 3,99 3,99

Total capacity steps % 31-62-100

33-67-100

30-60-100

27-64-100

23-46-69-100

25-50-75-100

24-47-65-82-

100

20-40-60-800-

100

14-29-43-62-81-100

17-33-50-67-83-100

RefrigerantType HFC 410ANumber of refrigerant circuits 2CompressorQty 3 3 3 3 4 4 5 5 6 6Type Scroll EvaporatorQty 1Type PlateWater flow m3/h 37,0 40,9 44,8 48,4 55,7 63,7 72,2 81,9 90,5 100,3Water pressure drop kPa 41 49 59 28 36 47 35 45 43 53Water volume l 14 14 14 24 24 24 32 32 39 39Antifreeze heater W 130 130 130 130 130 130 130,0 130 130 130Air cooled condenserQty 5 5 6 6 7 8 9 10 11 12Total coil face area per coil m2 2,4 2,4 2,4 2,4 2,4 2,4 2,4 2,4 2,4 2,4FanQty 5 5 6 6 7 8 9 10 11 12Nominal speed rpm 550 550 550 550 550 550 550 550 550 550Total airflow m3/h 72.500 72.500 87.000 87.000 101.500 116.000 130.500 145.000 159.500 174.000Total input power kW 4,5 4,5 5,4 5,4 6,3 7,2 8,1 9,0 9,9 10,8Water Connections (Evaporator)Type Male GAS Threaded VictaulicInlet diameter inch 3” 3” 3” 3” 4” 4” 4” 4” 5” 5”Outlet diameter inch 3” 3” 3” 3” 4” 4” 4” 4” 5” 5”Water Connections (Desuperheater)Type Male GAS ThreadedInlet diameter/Outlet diameter inch 1”/1”WeightShipping kg 1.772 1.773 1.865 1.921 2.306 2.417 2.897 3.009 3.412 3.509Operating kg 1.786 1.787 1.879 1.945 2.330 2.441 2.934 3.047 3.456 3.553Additional weightWith desuperheater kg 49 49 49 49 62 62 73 73 83 83DimensionsLength mm 3.500 3.500 3.500 3.500 4.550 4.550 5.600 5.600 6.650 6.650Width mm 2.150 2.150 2.150 2.150 2.150 2.150 2.150 2.150 2.150 2.150Height mm 2.600 2.600 2.600 2.600 2.600 2.600 2.600 2.600 2.600 2.600Acoustical dataSound power level2 dB(A) 85 86 87 87 88 88 89 89 90 90Sound pressure level 10 m3 dB(A) 53 54 55 55 56 56 57 57 57 57

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard.2 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.3 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.

Technical feature

Page 51: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Air cooled Chiller & Heat Pump | 49

Air Cooled Chiller &

heAt PumP

SyScroll 240-660 Air TR 240 270 290 320 360 420 470 540 590 660Nominal cooling capacity1 kW 233,7 266,1 280,1 321,2 365,4 413,9 474,9 535,1 596,3 659,2Input power1 kW 85,5 100,5 105,2 113,9 131,3 151,7 169,1 189,9 207,3 228,3EER1 2,93 2,83 2,74 3,17 3,10 2,97 3,23 3,12 3,29 3,21Total heat rejection1 313,4 360,3 382,5 422,6 483,2 553,3 622,0 706,5 777,7 864,9

Total capacity steps % 31-62-100

33-67-100

30-60-100

27-64-100

23-46-69-100

25-50-75-100

24-47-65-82-

100

20-40-60-800-

100

14-29-43-62-81-100

17-33-50-67-83-100

RefrigerantType HFC 410ANumber of refrigerant circuits 2CompressorQty 3 3 3 3 4 4 5 5 6 6Type Scroll EvaporatorQty 1Type PlateWater flow m3/h 40,4 46,0 48,5 55,4 63,1 71,5 82,0 92,4 103,0 113,9Water pressure drop kPa 48 62 68 36 46 58 45 57 55 67Water volume l 14 14 14 24 24 24 32 32 39 39Inlet/outlet water connection inch 3” 3” 3” 3” 4” 4” 4” 4” 5” 5”Recovery condenserQty 1Type PlateWater flow m3/h 53,5 61,4 65,2 72,3 82,6 94,5 106,4 120,7 132,9 147,6Water pressure drop kPa 83 108 121 59 77 99 74 95 91 111Water volume 14 14 14 24 24 24 32 32 39 39Inlet/outlet water connection inch 3” 3” 3” 3” 4” 4” 4” 4” 5” 5”WeightShipping kg 1.918 1.919 2.011 2.111 2.506 2.616 3.143 3.256 3.705 9.801Operating kg 1.946 1.947 2.039 2.160 2.554 2.665 3.218 3.331 3.793 9.889DimensionsLength mm 3.500 3.500 3.500 3.500 4.550 4.550 5.600 5.600 6.650 6.650Width mm 2.150 2.150 2.150 2.150 2.150 2.150 2.150 2.150 2.150 2.150Height mm 2.600 2.600 2.600 2.600 2.600 2.600 2.600 2.600 2.600 2.600

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard.

Technical feature

Page 52: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Air cooled Chiller & Heat Pump50

Technical feature 7 sizes Cooling capacity from 153,4 to 306,9 kW 3 versions:

STD (Standard); HT (High Temperature); HPF (High Pressure Fans)

3 acoustic versions: BLN (Basic Low Noise), LN (Low Noise) and ELN (Extra Low Noise)

Two refrigerant circuits Scroll compressors Microprocessor control Microchannel coils (CO only version) Electronic expansion valve Inverter fans and HT “Brine” versione for process application (on request) E-Coating coil treatment as standard

Accessories and options Automatic circuit breaker BMS interface Coils treatments Compressors acoustic box (standard) Compressors jackets Desuperheater and totaly heat recovery VLR Fan speed control (-18°C) Hydrokit with 1 or 2 pumps with or without buffer tank (500 lt)

( +1mt of lenght)

Air Cooled ChillerVLS 604-1204

VLS 604-1204604 704 804 904 1004 1004 1204

Min Max Min Max Min Max Min Max Min Max Min Max Min Max

Leaving watertemperature

Water °C +6 to +15Water with glycol °C 0 to +15Water with Glycol (Brine version) °C -8 to +15

∆ T K 3 to 8

Air temperature BLN °C -5 to +472 -5 to +472 0 to +463 0 to +473 0 to +463 0 to +453 0 to +453

LN/ELN1 °C -5 to +452 -5 to +452 0 to +443 0 to +453 0 to +443 0 to +423 0 to +423

HT °C -18 to +492 -18 to +492 -18 to +483 -18 to +493 -18 to +483 -18 to +473 -18 to +473

Externalstatic pressure

Standard fans Pa 0Inverter fans HPF Pa <120

Operating limit (to be confirmed following selection software issue)

1 Minimum air temperature -18°C with Fan speed control (standard ELN). 2 High Pressure at 40.5 ba.

Chillers suitable for operation without buffer tank for water content greater than 3 liters of water per kW of output.

Mechanical gauges Overload protection for compressors Power factor corrector capacitors Sequence phases control (standard) Sofstart Unit protection grilles Water differential pressure switch (standard) Water filter Water flow switch

153-307 kW Plate

Air cooled Scroll

410A

Page 53: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Air cooled Chiller & Heat Pump | 51

Air Cooled Chiller &

heAt PumPTechnical feature

VLS STD/HPF 604-1204 BLN 604 704 804 904 1004 1104 1204Cooling capacity1 kW 153,4 176,2 198,1 228,4 250,3 279,1 306,9Power input1 kW 55,8 66,0 72,3 83,1 86,9 100,0 114,9EER1 2,75 2,67 2,74 2,75 2,88 2,79 2,67Energy efficiency class C D C C C C DESEER 3,50 3,47 3,44 3,43 3,59 3,52 3,45

Part load steps % 28-57- 78-100

20-50- 70-100

25-50- 75-100

28-50- 78-100

25-50- 75-100

23-50- 73-100

25-50- 75-100

RefrigerantType HFC 410ANumber of refrigerant circuits 2CompressorQty 4Type ScrollEvaporatorQty 1Type Plate exchanger AISI 316Water flow l/h 26.540 30.427 34.194 39.371 43.155 48.091 52.924Connection type Male GAS threadedInlet/outlet diameter inch 2½” 2½” 2½” 3” 3” 3” 3”CondenserQty 2Total coil face area per coil mm2 3,5 4,8 4,8 4,8 4,8 4,8 4,8FanQty 3 3 3 4 4 4 4Speed rpm/min 900 900 900 900 900 900 900Air flow m3/h 63.000 68.300 68.300 85.000 80.000 75.500 75.500Power input kW 5,7 5,7 5,7 7,6 7,6 7,6 7,6Power input* kW 4,0 4,0 4,0 5,3 5,3 5,3 5,3Static head pressure Pa from 0 to 120 Pa*

WeightShipping kg 1.303 1.478 1.611 1.745 1.795 1.810 1.815Operating kg 1.315 1.490 1.625 1.770 1.820 1.835 1.840Additional weightsVersions HPF kg 30 30 30 40 40 40 40With desuperheater kg 20 20 30 30 30 30 30With one pump kg 50 85 85 90 90 95 95With two pumps kg 140 200 200 205 205 215 215With copper/copper coils kg 380 520 520 520 700 880 880DimensionsLenght mm 3.300 4.300 4.300 4.300 4.300 4.300 4.300Width mm 1.100 1.100 1.100 1.100 1.100 1.100 1.100Height mm 2.300 2.300 2.300 2.300 2.300 2.300 2.300Acoustical dataSound power level2 dB(A) 91 91 91 92 92 93 93Sound pressure level3 dB(A) 59 59 59 60 60 61 61

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard. 2 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard. 3 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.* For version with High Pressure Fans (HPF).

Page 54: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Air cooled Chiller & Heat Pump52

Technical feature

VLS STD 604-1204 LN 604 704 804 904 1004 1104 1204Cooling capacity1 kW 149,4 171,2 192,1 222,4 241,3 266,2 292,0Power input1 kW 56,4 66,4 73,3 83,6 88,7 104,0 120,2EER1 2,65 2,58 2,62 2,66 2,72 2,56 2,43Energy efficiency class D D D D C D EESEER 3,72 3,63 3,65 3,58 3,75 3,66 3,57

Part load steps % 28-57- 78-100

20-50- 70-100

25-50- 75-100

28-50- 78-100

25-50- 75-100

23-50- 73-100

25-50- 75-100

RefrigerantType HFC 410ANumber of refrigerant circuits 2CompressorQty 4Type ScrollEvaporatorQty 1Type Plate exchanger AISI 316Water flow l/h 25.765 29.618 33.213 38.321 41.555 45.958 50.361Connection type Male GAS threadedInlet/outlet diameter inch 2½” 2½” 2½” 3” 3” 3” 3”CondenserQty 2 2 2 2 2 2 2Total coil face area per coil mm2 3,5 4,8 4,8 4,8 4,8 4,8 4,8FanQty 3 3 3 4 4 4 4Speed rpm/min 700 700 700 700 700 700 700Air flow m3/h 47.300 52.200 52.200 63.700 58.800 54.900 54.900Power input kW 3,6 3,6 3,6 4,8 4,8 4,8 4,8Static head pressure Pa 0WeightShipping kg 1.303 1.478 1.611 1.745 1.795 1.810 1.815Operating kg 1.315 1.490 1.625 1.770 1.820 1.835 1.840Additional weightsWith desuperheater kg 20 20 30 30 30 30 30With one pump kg 50 85 85 90 90 95 95With two pumps kg 140 200 200 205 205 215 215With copper/copper coils kg 380 520 520 520 700 880 880DimensionsLength mm 3.300 4.300 4.300 4.300 4.300 4.300 4.300Width mm 1.100 1.100 1.100 1.100 1.100 1.100 1.100Height mm 2.300 2.300 2.300 2.300 2.300 2.300 2.300Acoustical dataSound power level2 dB(A) 87 87 87 88 88 89 89Sound pressure level3 dB(A) 55 55 55 56 56 57 57

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard. 2 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard. 3 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.

Page 55: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Air cooled Chiller & Heat Pump | 53

Air Cooled Chiller &

heAt PumPTechnical feature

VLS STD 604-1204 ELN 604 704 804 904 1004 1104 1204Cooling capacity1 kW 145,4 166,3 186,2 216,5 234,4 258,2 282,1Power input1 kW 57,9 68,7 76,3 86,3 91,2 106,7 124,8EER1 2,51 2,42 2,44 2,51 2,57 2,42 2,26Energy efficiency class D E E D D E FESEER 3,62 3,52 3,53 3,59 3,68 3,58 3,47

Part load steps % 28-57- 78-100

20-50- 70-100

25-50- 75-100

28-50- 78-100

25-50- 75-100

23-50- 73-100

25-50- 75-100

RefrigerantType HFC 410ANumber of refrigerant circuits 2CompressorQty 4Type ScrollEvaporatorQty 1Type Plate exchanger AISI 316Water flow l/h 25.112 28.758 32.129 37.272 40.368 44.513 48.658Connection type Male GAS threadedInlet/outlet diameter inch 2½” 2½” 2½” 3” 3” 3” 3”CondenserQty 2 2 2 2 2 2 2Frontal surface mm2 3,5 4,8 4,8 4,8 4,8 4,8 4,8FanQty 3 3 3 4 4 4 4Speed gir/min 550 550 550 550 550 550 550Air flow m3/h 38.500 41.800 41.800 52.000 48.900 46.200 46.200Power input kW 3 3 3 4 4 4 4Static head pressure Pa 0WeightShipping kg 1.338 1.513 1.646 1.780 1.835 1.850 1.855Operating kg 1.350 1.525 1.660 1.805 1.860 1.875 1.880Additional weightsWith desuperheater kg 20 20 30 30 30 30 30With one pump kg 50 85 85 90 90 95 95With two pumps kg 140 200 200 205 205 215 215With copper/copper coils kg 380 520 520 520 700 880 880DimensionsLength mm 3.300 4.300 4.300 4.300 4.300 4.300 4.300Width mm 1.100 1.100 1.100 1.100 1.100 1.100 1.100Height mm 2.300 2.300 2.300 2.300 2.300 2.300 2.300Acoustical dataSound power level2 dB(A) 83 83 83 84 84 85 85Sound pressure level3 dB(A) 51 51 51 52 52 53 53

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard. 2 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard. 3 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.

Page 56: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Air cooled Chiller & Heat Pump54

Technical feature

VLS 604-1204 HT 604 704 804 904 1004 1104 1204Cooling capacity1 kW 156,1 178,6 200,9 231,7 254,2 282,4 313,3Power input2 kW 48,7 58,4 64,4 73,2 76,8 89,9 103,1EER 2,79 2,74 2,82 2,80 2,93 2,83 2,77

Part load steps % 28-57- 78-100

20-50- 70-100

25-50- 75-100

28-50- 78-100

25-50- 75-100

23-50- 73-100

25-50- 75-100

RefrigerantType HFC 410ANumber of refrigerant circuits 2 2 2 2 2 2 2CompressorQty 4Type ScrollEvaporatorQty 1Type Plate exchanger AISI 316Water flow l/h 26.849 30.719 34.554 39.852 43.722 48.572 53.887Connection type Male GAS threadedInlet/outlet diameter inch 2½” 2½” 2½” 3” 3” 3” 3”CondenserQty 2 2 2 2 2 2 2Total coil face area per coil mm2 3,5 4,8 4,8 4,8 4,8 4,8 4,8FanQty 3 3 3 4 4 4 4Speed rpm/min 1.110 1.110 1.110 1.110 1.110 1.110 1.110Air flow m3/h 71.800 76.200 76.200 95.800 91.200 87.600 87.600Power input kW 7,2 6,9 6,9 9,6 9,9 10 10Static head pressure Pa 0WeightShipping kg 1.333 1.508 1.641 1.785 1.835 1.850 1.855Operating kg 1.345 1.520 1.655 1.810 1.860 1.875 1.880Additional weightsWith desuperheater kg 20 20 30 30 30 30 30With one pump kg 50 85 85 90 90 95 95With two pumps kg 140 200 200 205 205 215 215With copper/copper coils kg 380 520 520 520 700 880 880DimensionsLength mm 3.300 4.300 4.300 4.300 4.300 4.300 4.300Width mm 1.100 1.100 1.100 1.100 1.100 1.100 1.100Height mm 2.300 2.300 2.300 2.300 2.300 2.300 2.300Acoustical dataSound power level3 dB(A) 99 99 99 100 100 100 100Sound pressure level4 dB(A) 67 67 67 68 68 68 68

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature. 2 Input power (only compressors).3 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard. 4 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.

Page 57: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Air cooled Chiller & Heat Pump | 55

Air Cooled Chiller &

heAt PumPTechnical feature

1 Data based on 7°C leaving chilled water temperature and 35°C ambient air temperature. 2 Input power (only compressors).3 Data based on 7°C leaving chilled water temperature and 45°C condenser warm water temperature.

VLR 604-1204 604 704 804 904 1004 1104 1204Cooling capacity1 kW 152,0 176,0 200,0 230,0 250,0 277,0 306,0Power input2 kW 49,0 58,5 64,5 73,5 77,0 90,0 103,0Total heat rejection3 kW 191,0 222,8 251,3 288,3 310,7 348,7 388,6EER 3,10 3,01 3,10 3,13 3,25 3,08 2,97

Part load steps % 28-57- 78-100

20-50- 70-100

25-50- 75-100

28-50- 78-100

25-50-75-100

23-50- 73-100

25-50- 75-100

RefrigerantType HFC 410ANumber of refrigerant circuits 2 2 2 2 2 2 2CompressorQty 4Type ScrollEvaporatorQty 1Type Plate exchanger AISI 316Water flow l/h 26.144 30.272 34.400 39.560 43.000 47.644 52.632Connection type Male GAS threadedInlet/outlet diameter inch 2½” 2½” 2½” 3” 3” 3” 3”CondenserQty 2Total coil face area per coil mm2 3,5 4,8 4,8 4,8 4,8 4,8 4,8Heat recoveryQty 1Type Plate exchanger AISI 316Water volume l 11,5 11,5 13,3 25,2 25,2 25,2 25,2Connection type Male GAS threadedInlet/outlet connection diameter inch 2½” 2½” 2½” 3” 3” 3” 3”WeightShipping kg 1.513 1.702 1.853 2.051 2.180 2.270 2.279Operating kg 1.536 1.725 1.880 2.101 2.230 2.320 2.329Additional weightsVersion ELN kg 35 35 35 35 40 40 40Versions HPF/HT kg 30 30 30 40 40 40 40DimensionsLength mm 3.300 4.300 4.300 4.300 4.300 4.300 4.300Width mm 1.100 1.100 1.100 1.100 1.100 1.100 1.100Height mm 2.300 2.300 2.300 2.300 2.300 2.300 2.300

Page 58: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Air cooled Chiller & Heat Pump56

Air Cooled ChillerSyScrew 370-1100 Air EVO CO

Technical features 12 sizes Cooling capacity from 364,1 to 1.117,9 kW 3 acoustic versions:

- (Basic Low Noise) L (Low Noise) S (Super Low Noise)

Two refrigerant circuits Screw compressors Electronic expansion valve “Brine” version for process application LWT -8°C “Polar” Version for air temperature -18°C E-Coating coil treatment as standard

Accessories and options Automatic circuit breaker BMS interface Coils treatments Compressors acoustic box (standard) Compressor stepless control Desuperheater and total heat recovery (TR) Hydrokit with 1 or 2 pumps Mechanical gauges Pressostatic fan speed control Power factor corrector capacitors Sequence phases control (standard) Softstart Unit protection grilles Water filter Water flow switch

ENERGY EFFICIENCY

Report to performance data

COOLING MODE

2014

364-1.118 kW Shell & Tube

Air cooled Screw

134a

Page 59: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Air cooled Chiller & Heat Pump | 57

Air Cooled Chiller &

heAt PumPOperating limit (to be confirmed following selection software issue)

SyScrew 370-1100 Air EVO COfrom 370 to 1100

Мin Max

Leaving water temperature

Water °С from +5 to +15

Water + glycol °С from 0 to +15

Water + glycol (Brine Version) °С from -8 to +15

∆ T K from 3 to 8

Air temperature

- °С da 0 a +49

L/S °С da 0 a +47

HT °С da -10 a +51

Minimum Air tempera-ture Polar Version °C -18

External static pressureStandard fans Pа 0

Inverter fans Pа < 120

STD version

1 Water.2 Water + Glycol.3 Water + FSC.4 Water + Glycol + FSC.

14 Brine Version.15 Polar Version.16 Polar + Glycol.1 + 2 Standard unit.

L/S version

1 Water.2 Water + Glycol.3 Water + FSC.4 Water + Glycol + FSC.

14 Brine Version.15 Polar Version.16 Polar + Glycol.1 + 2 Standard unit.

HT version

1 Water.2 Water + Glycol.14 Brine Version.

15 Polar Version.16 Polar + Glycol.1 + 2 Standard unit.

14 2 1

4 3

16 15

T Ai

r (°C

)

LWT (°C)

50

40

30

20

10

0

-10

-20-10 -5 0 5 10 15

14 2 1

4 3

16 15

T Ai

r (°C

)

LWT (°C)

50

40

30

20

10

0

-10

-20-10 -5 0 5 10 15

14 2 1

16 15

T Ai

r (°C

)

LWT (°C)

50

40

30

20

10

0

-10

-20-10 -5 0 5 10 15

Page 60: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Air cooled Chiller & Heat Pump58

Technical feature

SyScrew 370-700 Air EVO CO (STD) 370 400 450 500 570 650 700Cooling capacity1 kW 364,1 414,5 445,5 502,9 562,1 625,5 712,9Power input1 kW 112,7 130,4 143,5 159,9 176,5 197,7 223,5EER1 3,23 3,18 3,11 3,15 3,18 3,16 3,19Energy efficiency class A A A A A A AESEER 3,75 3,69 3,60 3,65 3,69 3,67 3,70RefrigerantType HFC 134aNumber of refrigerant circuits 2 2 2 2 2 2 2CompressorQty 2Type ScrewPart load steps % 25-50-62-75-87-100Power supply 400V/3/50HzStart-up type Part Winding Y/ΔEvaporatorQty 1Type Shell & TubeWater flow rate m3/h 62,7 71,4 76,8 86,7 96,9 107,8 123,0Water pressure drop kPa 17,0 21,1 24,4 18,7 23,3 29,3 37,6Inlet/outlet diameter inch 6 6 6 8 8 8 8CondenserQty 8 10 10 10 12 12 14Type MCHX - Al/AlloyFanQty 6 8 8 8 8 9 10Air flow m3/s 51,1 63,9 63,9 63,9 76,7 76,7 89,4Power input kW 16,8 21,0 21,0 21,0 25,2 25,2 29,4WeightShipping kg 3.500 3.840 3.870 4.720 5.050 5.100 5.550Operating kg 3.650 3.980 4.010 4.970 5.300 5.340 5.780DimensionsLength mm 4.600 5.700 5.700 5.700 6.700 6.700 7.800Width mm 2.200 2.200 2.200 2.200 2.200 2.200 2.200Height mm 2.550 2.550 2.550 2.550 2.550 2.550 2.550Acoustical dataSound power level2 dB(A) 97 98 98 98 99 99 99Sound pressure level at 10 m3 dB(A) 65 66 66 66 67 67 67

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard. 2 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.3 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.

Page 61: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Air cooled Chiller & Heat Pump | 59

Air Cooled Chiller &

heAt PumPTechnical feature

SyScrew 750-1100 Air EVO CO (STD) 750 850 950 1000 1100Cooling capacity1 kW 749,2 839,0 961,8 1.019,0 1.117,9Power input1 kW 237,4 261,2 288,6 312,8 340,0EER1 3,16 3,21 3,33 3,26 3,29Energy efficiency class A A A A AESEER 3,66 3,73 3,87 3,78 3,81RefrigerantType HFC 134aNumber of refrigerant circuits 2 2 2 2 2CompressorQty 2Type ScrewPart load steps % 25-50-62-75-87-100Power supply 400V/3/50HzStart-up type Y/ΔEvaporatorQty 1Type Shell & TubeWater flow rate m3/h 129,0 144,5 165,7 175,6 192,7Water pressure drop kPa 15,4 19,4 24,2 25,6 31,4Inlet/outlet diameter inch 8 8 8 10 10CondenserQty 14 16 18 20 22Type MCHX - Al/AlloyFanQty 14 16 18 20 22Air flow m3/s 89,4 102,2 115,0 127,8 140,6Power input kW 29,4 33,6 37,8 42,0 46,2WeightShipping kg 6.730 7.030 7.460 7.840 8.260Operating kg 7.120 7.420 7.840 8.210 8.660DimensionsLength mm 7.800 8.800 9.900 10.900 12.000Width mm 2.200 2.200 2.200 2.200 2.200Height mm 2.550 2.550 2.550 2.550 2.550Acoustical dataSound power level2 dB(A) 100 100 101 101 102Sound pressure level at 10 m3 dB(A) 67 67 68 68 69

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard. 2 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.3 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.

Page 62: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Air cooled Chiller & Heat Pump60

Technical feature

SyScrew 370-700 Air EVO CO L 370 400 450 500 570 650 700Cooling capacity1 kW 354,6 401,7 438,5 478,8 547,5 610,5 702,3Power input1 kW 111,8 126,4 142,5 159,0 176,4 199,6 224,3EER1 3,17 3,18 3,08 3,01 3,10 3,06 3,13Energy efficiency class A A B B A B AESEER 4,07 4,19 4,07 4,00 4,11 4,05 4,14RefrigerantType HFC 134aNumber of refrigerant circuits 2 2 2 2 2 2 2CompressorQty 2Type ScrewPart load steps % 25-50-62-75-87-100Power supply 400V/3/50HzStart-up type Part Winding Y/ΔEvaporatorQty 1Type Shell & TubeWater flow rate m3/h 61,1 69,2 75,6 82,5 94,3 105,3 121,1Water pressure drop kPa 16 20 24 17 22 28 37Inlet/outlet diameter inch 6 6 6 8 8 8 8CondenserQty 8 10 10 10 12 12 14Type MCHX - Al/AlloyFanQty 6 8 8 8 8 9 10Air flow m3/s 42,4 53,1 53,1 53,1 63,7 63,7 74,3Power input kW 9,2 11,5 11,5 11,5 13,8 13,8 16,1WeightShipping kg 3.500 3.840 3.870 4.720 5.050 5.100 5.550Operating kg 3.650 3.980 4.010 4.970 5.300 5.340 5.780DimensionsLength mm 4.600 5.700 5.700 5.700 6.700 6.700 7.800Width mm 2.200 2.200 2.200 2.200 2.200 2.200 2.200Height mm 2.550 2.550 2.550 2.550 2.550 2.550 2.550Acoustical dataSound power level2 dB(A) 91 92 92 92 93 93 94Sound pressure level at 10 m3 dB(A) 59 60 60 60 61 61 61

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard. 2 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.3 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.

Page 63: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Air cooled Chiller & Heat Pump | 61

Air Cooled Chiller &

heAt PumPTechnical feature

SyScrew 750-1100 Air EVO CO L 750 850 950 1000 1100Cooling capacity1 kW 722,2 814,4 922,4 981,4 1.086,0Power input1 kW 237,7 264,2 288,3 309,8 339,3EER1 3,04 3,08 3,20 3,17 3,20Energy efficiency class B B A A AESEER 4,04 4,08 4,23 4,21 4,24RefrigerantType HFC 134aNumber of refrigerant circuits 2 2 2 2 2CompressorQty 2Type ScrewPart load steps % 25-50-62-75-87-100Power supply 400V/3/50HzStart-up type Y/ΔEvaporatorQty 1Type Shell & TubeWater flow rate m3/h 124,5 140,5 158,9 169,1 187,2Water pressure drop kPa 31 39 22 24 30Inlet/outlet diameter inch 8 8 8 10 10CondenserQty 14 16 18 20 22Type MCHX - Al/AlloyFanQty 14 16 18 20 22Air flow m3/s 74,3 84,9 95,5 106,1 116,7Power input kW 16,1 18,4 20,7 23,0 25,3WeightShipping kg 6.730 7.030 7.460 7.840 8.260Operating kg 7.120 7.420 7.840 8.210 8.660DimensionsLength mm 7.800 8.800 9.900 10.900 12.000Width mm 2.200 2.200 2.200 2.200 2.200Height mm 2.550 2.550 2.550 2.550 2.550Acoustical dataSound power level2 dB(A) 94 94 95 95 96Sound pressure level at 10 m3 dB(A) 61 61 62 62 63

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard. 2 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.3 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.

Page 64: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Air cooled Chiller & Heat Pump62

Technical feature

SyScrew 370-700 Air EVO CO S 370 400 450 500 570 650 700Cooling capacity1 kW 354,6 401,7 438,5 478,8 547,5 610,5 702,3Power input1 kW 111,8 126,4 142,5 159,0 176,4 199,6 224,3EER1 3,17 3,18 3,08 3,01 3,10 3,06 3,13Energy efficiency class A A B B A B AESEER 4,07 4,19 4,07 4,00 4,11 4,05 4,14RefrigerantType HFC 134aNumber of refrigerant circuits 2 2 2 2 2 2 2CompressorQty 2Type ScrewPart load steps % 25-50-62-75-87-100Power supply 400V/3/50HzStart-up type Part Winding Y/ΔEvaporatorQty 1Type Shell & TubeWater flow rate m3/h 61,1 69,2 75,6 82,5 94,3 105,3 61,1Water pressure drop kPa 16 20 24 17 22 28 16Inlet/outlet diameter inch 6 6 6 8 8 8 8CondenserQty 8 10 10 10 12 12 14Type MCHX - Al/AlloyFanQty 8 10 10 10 12 12 14Air flow m3/s 42,4 53,1 53,1 53,1 63,7 63,7 74,3Power input kW 9,2 11,5 11,5 11,5 13,8 13,8 16,1WeightShipping kg 3.590 3.930 3.950 4.810 5.140 5.200 5.650Operating kg 3.740 4.070 4.100 5.060 5.390 5.430 5.880DimensionsLength mm 4.600 5.700 5.700 5.700 6.700 6.700 7.800Width mm 2.200 2.200 2.200 2.200 2.200 2.200 2.200Height mm 2.550 2.550 2.550 2.550 2.550 2.550 2.550Acoustical dataSound power level2 dB(A) 87 88 88 88 89 89 90Sound pressure level at 10 m3 dB(A) 55 56 56 56 57 57 58

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard. 2 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.3 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.

Page 65: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Air cooled Chiller & Heat Pump | 63

Air Cooled Chiller &

heAt PumPTechnical feature

SyScrew 750-1100 Air EVO CO S 750 850 950 1000 1100Cooling capacity1 kW 722,2 814,4 922,4 981,4 1086,0Power input1 kW 237,7 264,2 288,3 309,8 339,3EER1 3,04 3,08 3,20 3,17 3,20Energy efficiency class B B A A AESEER 4,04 4,08 4,23 4,21 4,24RefrigerantType HFC 134aNumber of refrigerant circuits 2 2 2 2 2CompressorQty 2Type ScrewPart load steps % 25-50-62-75-87-100Power supply 400V/3/50HzStart-up type Y/ΔEvaporatorQty 1Type Shell & TubeWater flow rate m3/h 69,2 75,6 82,5 94,3 105,3Water pressure drop kPa 20 24 17 22 28Inlet/outlet diameter inch 8 8 8 10 10CondenserQty 14 16 18 20 22Type MCHX - Al/AlloyFanQty 14 16 18 20 22Air flow m3/s 74,3 84,9 95,5 106,1 116,7Power input kW 16,1 18,4 20,7 23,0 25,3WeightShipping kg 6.830 7.130 7.570 7.940 8.360Operating kg 7.220 7.520 7.940 8.310 8.760DimensionsLength mm 7.800 8.800 9.900 10.900 12.000Width mm 2.200 2.200 2.200 2.200 2.200Height mm 2.550 2.550 2.550 2.550 2.550Acoustical dataSound power level2 dB(A) 90 90 91 91 92Sound pressure level at 10 m3 dB(A) 57 57 58 58 59

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard.2 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.3 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.

Page 66: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Air cooled Chiller & Heat Pump64

Air Cooled ChillerSyScrew 360-1300 Air CO

Technical features 19 sizes Cooling capacity from 366 to 1.320 kW 3 acoustic versions:

- (Basic Low Noise) L (Low Noise) S (Super Low Noise)

Two refrigerant circuits Screw compressors Valvola di espansione elettronica “Brine” version for process application LWT-8°C “Polar” Version for air temperature -18°C E-Coating coil treatment as standard

Accessories and options Automatic circuit breaker BMS interface Coils treatments Compressors acoustic box (standard) Compressors stepless control Desuperheater and totaly heat recovery Fan speed control Hydrokit with 1 or 2 pumps with ot without buffer tank Mechanical gauges Power factor corrector capacitors Sequence phases control (standard) Sofstart Unit protection grilles Water filter Water flow switch

366-1.320 kW Shell & Tube

Air cooled Screw

134a

Page 67: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Air cooled Chiller & Heat Pump | 65

Air Cooled Chiller &

heAt PumPOperating limit (to be confirmed following selection software issue)

SyScrew 360-1300 Air COfrom 360 to 1300

Мin Max

Leaving water temperature

Water °С from +5 to +15

Water + glycol °С from 0 to +15

Water + glycol (Brine Version) °С from -8 to +15

∆ T K from 3 to 8

Air temperature

- °С from 0 to +48

L °С from 0 to +46

S °С from -10 to +42

HT °С from -10 to +50

Minimum Air tempera-ture Polar Version °C -18

External static pressureStandard fans Pа 0

Inverter fans Pа < 120

STD version

14 2 1

4 3

16 15

T Ai

r (°C

)

LWT (°C)

50

40

30

20

10

0

-10

-20-10 -5 0 5 10 15

1 Water.2 Water + Glycol.3 Water + FSC.4 Water + Glycol + FSC.

14 Brine Version.15 Polar Version.16 Polar + Glycol.1 + 2 Standard unit.

L version

14 2 1

4 3

16 15

T Ai

r (°C

)

LWT (°C)

50

40

30

20

10

0

-10

-20-10 -5 0 5 10 15

1 Water.2 Water + Glycol.3 Water + FSC.4 Water + Glycol + FSC.

14 Brine Version.15 Polar Version.16 Polar + Glycol.1 + 2 Standard unit.

S version

14 2 1

16 15

T Ai

r (°C

)

LWT (°C)

50

40

30

20

10

0

-10

-20-10 -5 0 5 10 15

1 Water.2 Water + Glycol.14 Brine Version.

15 Polar Version.16 Polar + Glycol.1 + 2 Standard unit.

HT version

14 2 1

16 15

T Ai

r (°C

)

LWT (°C)

50

40

30

20

10

0

-10

-20-10 -5 0 5 10 15

1 Water.2 Water + Glycol.14 Brine Version.

15 Polar Version.16 Polar + Glycol.1 + 2 Standard unit.

Page 68: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Air cooled Chiller & Heat Pump66

Technical feature

SyScrew 360-580 Air CO (STD) 360 410 450 480 500 540 580Cooling capacity1 kW 365 413 445 480 505 540 575Power input1 kW 134,4 151,5 167,7 176,3 184,1 198,6 212,5EER1 2,71 2,73 2,65 2,72 2,74 2,72 2,70Energy efficiency class C C D C C C CESEER 3,15 3,16 3,18 3,27 3,18 3,26 3,14RefrigerantType HFC 134aNumber of refrigerant circuits 2 2 2 2 2 2 2CompressorQty 2Type ScrewPart load steps % 25-50-62-75-87-100Power supply 400V/3/50HzStart-up type Part Winding Y/Δ EvaporatorQty 1Type Shell & TubeWater flow rate m3/h 63,0 71,3 76,8 82,9 87,0 93,1 99,1Water pressure drop kPa 57,3 39,0 45,3 52,4 31,8 36,3 40,4Inlet/outlet diameter inch 5” 6” 6” 6” 6” 6” 6”CondenserQty 6 8 8 8 8 9 10Type MCHX - Al/AlloyFanQty 6 8 8 8 8 9 10Air flow m3/s 38,3 51,1 51,1 51,1 51,1 57,5 63,9Power input kW 12,6 16,8 16,8 16,8 16,8 18,9 21,0WeightShipping kg 3.200 3.520 3.830 4.140 4.170 4.400 4.660Operating kg 3.300 3.670 3.990 4.290 4.320 4.550 4.800DimensionsLength mm 4.600 4.600 4.600 4.600 4.600 5.700 6.700Width mm 2.200 2.200 2.200 2.200 2.200 2.200 2.200Height mm 2.550 2.550 2.550 2.550 2.550 2.550 2.550Acoustical dataSound power level2 dB(A) 96 97 97 97 97 98 98Sound pressure level at 10 m3 dB(A) 64 65 65 65 65 66 65

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard. 2 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.3 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.

Page 69: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Air cooled Chiller & Heat Pump | 67

Air Cooled Chiller &

heAt PumPTechnical feature

SyScrew 650-1000 Air CO (STD) 650 720 800 850 910 970 1000Cooling capacity1 kW 652 713 794 851 909 971 1.008Power input1 kW 236,8 253,4 275,7 298,9 320,2 340,5 350,7EER1 2,75 2,81 2,88 2,85 2,84 2,85 2,87Energy efficiency class C C C C C C CESEER 3,19 3,38 3,45 3,42 3,29 3,42 3,33RefrigerantType HFC 134aNumber of refrigerant circuits 2 2 2 2 2 2 2CompressorQty 2Type ScrewPart load steps % 25-50-62-75-87-100Power supply 400V/3/50HzStart-up type Y/ΔEvaporatorQty 1Type Shell & TubeWater flow rate m3/h 112,4 123,0 137,0 147,0 157,0 167,6 174,1Water pressure drop kPa 30,4 36,2 46,5 53,4 60,2 55,4 60,2Inlet/outlet diameter inch 6” 6” 8” 8” 8” 8” 8”CondenserQty 12 12 12 14 14 15 16Type MCHX - Al/AlloyFanQty 12 12 12 14 14 15 16Air flow m3/s 76,7 76,7 76,7 89,4 89,4 95,8 102,2Power input kW 25,2 25,2 25,2 29,4 29,4 31,5 33,6WeightShipping kg 5.080 5.500 5.990 6.510 6.600 6.810 6.900Operating kg 5.330 5.760 6.220 6.750 6.830 7.090 7.180DimensionsLength mm 6.700 6.700 6.700 8.800 8.800 8.800 8.800Width mm 2.200 2.200 2.200 2.200 2.200 2.200 2.200Height mm 2.550 2.550 2.550 2.550 2.550 2.550 2.550Acoustical dataSound power level2 dB(A) 99 99 99 100 100 100 100Sound pressure level at 10 m3 dB(A) 66 66 66 67 67 67 67

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard. 2 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.3 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.

Page 70: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Air cooled Chiller & Heat Pump68

Technical feature

SyScrew 1070-1300 Air CO (STD) 1070 1130 1170 1200 1300Cooling capacity1 kW 1.071 1.132 1.172 1.218 1.316Power input1 kW 371,8 391,8 410,5 431,2 465,9EER1 2,88 2,89 2,85 2,82 2,82Energy efficiency class C C C C CESEER 3,46 3,35 3,43 3,28 3,28RefrigerantType HFC 134aNumber of refrigerant circuits 2 2 2 2 2CompressorQty 2Type ScrewPart load steps % 25-50-62-75-87-100Power supply 400V/3/50HzStart-up type Y/ΔEvaporatorQty 1 1 1 1 1Type Shell & TubeWater flow rate m3/h 184,7 195,3 202,1 210,0 227,0Water pressure drop kPa 30,7 34,3 35,1 37,9 43,9Inlet/outlet diameter inch 8” 8” 8” 8” 10”CondenserQty 17 18 19 20 22Type MCHX - Al/AlloyFanQty 17 18 19 20 22Air flow m3/s 108,6 115,0 121,4 127,8 140,6Power input kW 35,7 37,8 39,9 42,0 46,2WeightShipping kg 7.490 7.760 7.970 8.180 8.570Operating kg 7.880 8.150 8.350 8.560 8.940DimensionsLength mm 9.900 10.900 10.900 10.900 12.000Width mm 2.200 2.200 2.200 2.200 2.200Height mm 2.550 2.550 2.550 2.550 2.550Acoustical dataSound power level2 dB(A) 100 101 101 101 102Sound pressure level at 10 m3 dB(A) 67 68 68 68 69

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard. 2 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.3 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.

Page 71: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Air cooled Chiller & Heat Pump | 69

Air Cooled Chiller &

heAt PumPTechnical feature

SyScrew 360-580 Air CO L 360 410 450 480 500 540 580Cooling capacity1 kW 357 405 436 470 495 529 563Power input1 kW 133,4 149,2 166,0 174,9 183,0 197,1 210,5EER1 2,68 2,72 2,63 2,69 2,70 2,68 2,68Energy efficiency class D C D D C D DESEER 3,32 3,37 3,37 3,45 3,35 3,45 3,32RefrigerantType HFC 134aNumber of refrigerant circuits 2 2 2 2 2 2 2CompressorQty 2Type ScrewPart load steps % 25-50-62-75-87-100Power supply 400V/3/50HzStart-up type Part Winding Y/ΔEvaporatorQty 1Type Shell & TubeWater flow rate m3/h 61,7 69,9 75,3 81,2 85,3 91,2 97,2Water pressure drop kPa 55,1 37,5 43,5 50,4 30,5 34,8 38,8Inlet/outlet diameter inch 5” 6” 6” 6” 6” 6” 6”CondenserQty 6 8 8 8 8 9 10Type MCHX - Al/AlloyFanQty 6 8 8 8 8 9 10Air flow m3/s 31,8 42,4 42,4 42,4 42,4 47,8 53,1Power input kW 6,9 9,2 9,2 9,2 9,2 10,4 11,5WeightShipping kg 3.200 3.520 3.830 4.140 4.170 4.400 4.660Operating kg 3.300 3.670 3.990 4.290 4.320 4.550 4.800DimensionsLength mm 4.600 4.600 4.600 4.600 4.600 5.700 6.700Width mm 2.200 2.200 2.200 2.200 2.200 2.200 2.200Height mm 2.550 2.550 2.550 2.550 2.550 2.550 2.550Acoustical dataSound power level2 dB(A) 90 91 91 91 91 92 92Sound pressure level at 10 m3 dB(A) 58 59 59 59 59 60 59

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard. 2 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.3 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.

Page 72: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Air cooled Chiller & Heat Pump70

Technical feature

SyScrew 650-1000 Air CO L 650 720 800 850 910 970 1000Cooling capacity1 kW 639 699 778 835 891 952 988Power input1 kW 233,7 250,9 272,0 296,0 318,2 338,2 347,8EER1 2,73 2,78 2,86 2,82 2,80 2,81 2,84Energy efficiency class C C C C C C CESEER 3,39 3,58 3,67 3,62 3,48 3,61 3,52RefrigerantType HFC 134aNumber of refrigerant circuits 2 2 2 2 2 2 2CompressorQty 2Tipo ScrewPart load steps % 25-50-62-75-87-100Power supply 400V/3/50HzStart-up type Y/ΔEvaporatorQty 1Type Shell & TubeWater flow rate m3/h 110,1 120,5 134,2 144,1 153,9 164,3 170,6Water pressure drop kPa 29,2 34,8 44,7 51,3 57,8 53,2 57,8Inlet/outlet diameter inch 6” 6” 8” 8” 8” 8” 8”CondenserQty 12 12 12 14 14 15 16Type MCHX - Al/AlloyFanQty 12 12 12 14 14 15 16Air flow m3/s 63,7 63,7 63,7 74,3 74,3 79,6 84,9Power input kW 13,8 13,8 13,8 16,1 16,1 17,3 18,4WeightShipping kg 5.080 5.500 5.990 6.510 6.600 6.810 6.900Operating kg 5.330 5.760 6.220 6.750 6.830 7.090 7.180DimensionsLength mm 6.700 6.700 6.700 8.800 8.800 8.800 8.800Width mm 2.200 2.200 2.200 2.200 2.200 2.200 2.200Height mm 2.550 2.550 2.550 2.550 2.550 2.550 2.550Acoustical dataSound power level2 dB(A) 93 93 93 94 94 94 94Sound pressure level at 10 m3 dB(A) 60 60 60 61 61 61 61

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard. 2 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.3 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.

Page 73: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Air cooled Chiller & Heat Pump | 71

Air Cooled Chiller &

heAt PumPTechnical feature

SyScrew 1070-1300 Air CO L 1070 1130 1170 1200 1300Cooling capacity1 kW 1.050 1.110 1.148 1.193 1.290Power input1 kW 368,8 388,6 407,0 427,4 461,4EER1 2,85 2,86 2,82 2,79 2,80Energy efficiency class C C C C CESEER 3,65 3,54 3,62 3,46 3,47RefrigerantType HFC 134aNumber of refrigerant circuits 2 2 2 2 2CompressorQty 2Type ScrewPart load steps % 25-50-62-75-87-100Power supply 400V/3/50HzStart-up type Y/ΔEvaporatorQty 1Type Shell & TubeWater flow rate m3/h 181,0 191,3 198,0 205,8 222,5Water pressure drop kPa 29,5 32,9 33,7 36,4 42,2Inlet/outlet diameter inch 8” 8” 8” 8” 10”Condenser Qty 17 18 19 20 22Type MCHX - Al/AlloyFanQty 17 18 19 20 22Air flow m3/s 90,2 95,5 100,8 106,1 116,7Power input kW 19,6 20,7 21,9 23,0 25,3WeightShipping kg 7.490 7.760 7.970 8.180 8.570Operating kg 7.880 8.150 8.350 8.560 8.940DimensionsLength mm 9.900 10.900 10.900 10.900 12.000Width mm 2.200 2.200 2.200 2.200 2.200Height mm 2.550 2.550 2.550 2.550 2.550Acoustical dataSound power level2 dB(A) 94 95 95 95 96Sound pressure level at 10 m3 dB(A) 61 62 62 62 63

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard. 2 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.3 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.

Page 74: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Air cooled Chiller & Heat Pump72

SyScrew 360-580 Air CO S 360 410 450 480 500 540 580Cooling capacity1 kW 339 385 414 446 469 502 535Power input1 kW 140,4 157,0 174,7 184,1 192,8 207,6 221,6EER1 2,42 2,45 2,37 2,43 2,43 2,42 2,41Energy efficiency class E E E E E E EESEER 3,14 3,18 3,18 3,26 3,16 3,25 3,13RefrigerantType HFC 134aNumber of refrigerant circuits 2 2 2 2 2 2 2CompressorQty 2Type ScrewPart load steps % 25-50-62-75-87-100Power supply 400V/3/50HzStart-up type Part Winding Y/ΔEvaporatorQty 1Type Shell & TubeWater flow rate m3/h 58,6 66,3 71,4 77,1 80,9 86,6 92,2Water pressure drop kPa 49,6 33,8 39,2 45,4 27,5 31,4 35,0Inlet/outlet diameter inch 5” 6” 6” 6” 6” 6” 6”CondenserQty 6 8 8 8 8 9 10Type MCHX - Al/AlloyFanQty 6 8 8 8 8 9 10Air flow m3/s 25,8 34,4 34,4 34,4 34,4 38,6 43,1Power input kW 6,9 9,2 9,2 9,2 9,2 10,4 11,5WeightShipping kg 3.280 3.600 3.920 4.230 4.260 4.490 4.760Operating kg 3.380 3.760 4.080 4.390 4.410 4.640 4.900DimensionsLength mm 4.600 4.600 4.600 4.600 4.600 5.700 6.700Width mm 2.200 2.200 2.200 2.200 2.200 2.200 2.200Height mm 2.550 2.550 2.550 2.550 2.550 2.550 2.550Acoustical dataSound power level2 dB(A) 86 87 87 87 87 88 88Sound pressure level at 10 m3 dB(A) 54 55 55 55 55 56 55

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard. 2 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.3 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.

Technical feature

Page 75: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Air cooled Chiller & Heat Pump | 73

Air Cooled Chiller &

heAt PumP

SyScrew 650-1000 Air CO S 650 720 800 850 910 970 1000Cooling capacity1 kW 606 663 738 792 846 903 938Power input1 kW 246,1 264,3 286,3 311,6 335,0 356,1 366,0EER1 2,46 2,51 2,58 2,54 2,53 2,54 2,56Energy efficiency class E D D D D D DESEER 3,20 3,37 3,47 3,42 3,28 3,41 3,33RefrigerantType HFC 134aNumber of refrigerant circuits 2 2 2 2 2 2 2CompressorQty 2Type ScrewPart load steps % 25-50-62-75-87-100Power supply 400V/3/50HzStart-up type Y/ΔEvaporatorQty 1Type Shell & TubeWater flow rate m3/h 104,5 114,4 127,4 136,7 146,0 155,9 161,9Water pressure drop kPa 26,3 31,3 40,2 46,2 52,0 47,9 52,0Inlet/outlet diameter inch 6” 6” 8” 8” 8” 8” 8”CondenserQty 12 12 12 14 14 15 16Type MCHX - Al/AlloyFanQty 12 12 12 14 14 15 16Air flow m3/s 51,7 51,7 51,7 60,3 60,3 64,6 68,9Power input kW 13,8 13,8 13,8 16,1 16,1 17,3 18,4WeightShipping kg 5.180 5.600 6.090 6.620 6.700 6.920 7.010Operating kg 5.430 5.860 6.320 6.850 6.930 7.190 7.280DimensionsLength mm 6.700 6.700 6.700 8.800 8.800 8.800 8.800Width mm 2.200 2.200 2.200 2.200 2.200 2.200 2.200Height mm 2.550 2.550 2.550 2.550 2.550 2.550 2.550Acoustical dataSound power level2 dB(A) 89 89 89 89 90 90 90Sound pressure level at 10 m3 dB(A) 56 56 56 56 57 57 57

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard. 2 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.3 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.

Technical feature

Page 76: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Air cooled Chiller & Heat Pump74

Technical feature

SyScrew Air 1070-1300 Air CO S 1070 1130 1170 1200 1300Cooling capacity1 kW 996 1.053 1.090 1.133 1.224Power input1 kW 388,5 409,3 428,7 450,2 485,8EER1 2,56 2,57 2,54 2,52 2,52Energy efficiency class D D D D DESEER 3,45 3,34 3,42 3,27 3,27RefrigerantType HFC 134aNumber of refrigerant circuits 2 2 2 2 2CompressorQty 2Type ScrewPart load steps % 25-50-62-75-87-100Power supply 400V/3/50HzStart-up type Y/ΔEvaporatorQty 1Type Shell & TubeWater flow rate m3/h 171,7 181,6 187,9 195,3 211,1Water pressure drop kPa 26,6 29,6 30,3 32,8 38,0Inlet/outlet diameter inch 8” 8” 8” 8” 10”Condenser Qty 17 18 19 20 22Type MCHX - Al/AlloyFanQty 17 18 19 20 22Air flow m3/s 73,2 77,5 81,8 86,1 94,7Power input kW 19,6 20,7 21,9 23,0 25,3WeightShipping kg 7.590 7.860 8.070 8.280 8.670Operating kg 7.980 8.250 8.450 8.660 9.040DimensionsLength mm 9.900 10.900 10.900 10.900 12.000Width mm 2.200 2.200 2.200 2.200 2.200Height mm 2.550 2.550 2.550 2.550 2.550Acoustical dataSound power level2 dB(A) 90 91 91 91 92Sound pressure level at 10 m3 dB(A) 57 58 58 58 59

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard. 2 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.3 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.

Page 77: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Air cooled Chiller & Heat Pump | 75

Air Cooled Chiller &

heAt PumPTechnical feature

SyScrew 360-580 Air CO HT 360 410 450 480 500 540 580Cooling capacity1 kW 372 422 454 489 515 550 586Power input1 kW 138,1 156,9 172,8 181,2 188,8 204,1 218,8EER1 2,69 2,69 2,63 2,70 2,73 2,70 2,68Energy efficiency class D D D C C D DESEER 3,12 3,12 3,15 3,24 3,16 3,24 3,11RefrigerantType HFC 134aNumber of refrigerant circuits 2 2 2 2 2 2 2CompressorQty 2Type ScrewPart load steps % 25-50-62-75-87-100Power supply 400V/3/50HzStart-up type Part Winding Y/ΔEvaporatorQty 1Type Shell & TubeWater flow rate m3/h 64,3 72,8 78,4 84,5 88,8 94,9 101,1Water pressure drop kPa 59,7 40,6 47,2 54,6 33,1 37,7 42,0Inlet/outlet diameter inch 5” 6” 6” 6” 6” 6” 6”CondenserQty 6 8 8 8 8 9 10Type MCHX - Al/AlloyFanQty 6 8 8 8 8 9 10Air flow m3/s 46,8 62,4 62,4 62,4 62,4 70,3 78,1Power input kW 18,6 24,8 24,8 24,8 24,8 27,9 31,0WeightShipping kg 3.200 3.520 3.830 4.140 4.170 4.400 4.660Operating kg 3.300 3.670 3.990 4.290 4.320 4.550 4.800DimensionsLength mm 4.600 4.600 4.600 4600 4.600 5.700 6700Width mm 2.200 2.200 2.200 2.200 2.200 2.200 2.200Height mm 2.550 2.550 2.550 2550 2.550 2.550 2.550Acoustical dataSound power level2 dB(A) 102 103 103 103 103 104 104Sound pressure level at 10 m3 dB(A) 70 71 71 71 71 72 71

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard. 2 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.3 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.

Page 78: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Air cooled Chiller & Heat Pump76

Technical feature

SyScrew 650-1000 Air CO HT 650 720 800 850 910 970 1000Cooling capacity1 kW 665 727 809 868 927 990 1.028Power input1 kW 244,7 261,0 285,0 307,7 328,7 349,6 360,6EER1 2,72 2,79 2,84 2,82 2,82 2,83 2,85Energy efficiency class C C C C C C CESEER 3,15 3,34 3,41 3,39 3,27 3,40 3,31RefrigerantType HFC 134aNumber of refrigerant circuits 2 2 2 2 2 2 2CompressorQty 2Type ScrewPart load steps % 25-50-62-75-87-100Power supply 400V/3/50HzStart-up type Y/ΔEvaporatorQty 1Type Shell & TubeWater flow rate m3/h 114,6 125,4 139,7 149,9 160,2 171,0 177,5Water pressure drop kPa 31,6 37,7 48,4 55,5 62,6 57,7 62,6Inlet/outlet diameter inch 6” 6” 8” 8” 8” 8” 8”CondenserQty 12 12 12 14 14 15 16Type MCHX - Al/AlloyFanQty 12 12 12 14 14 15 16Air flow m3/s 93,7 93,7 93,7 109,3 109,3 117,1 124,9Power input kW 37,2 37,2 37,2 43,4 43,4 46,5 49,6WeightShipping kg 5.080 5.500 5.990 6.510 6.600 6.810 6.900Operating kg 5.330 5.760 6.220 6.750 6.830 7.090 7.180DimensionsLength mm 6.700 6.700 6.700 8.800 8.800 8.800 8.800Width mm 2.200 2.200 2.200 2.200 2.200 2.200 2.200Height mm 2.550 2.550 2.550 2.550 2.550 2.550 2.550Acoustical dataSound power level2 dB(A) 105 105 105 106 106 106 106Sound pressure level at 10 m3 dB(A) 72 72 72 73 73 73 73

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard. 2 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.3 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.

Page 79: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Air cooled Chiller & Heat Pump | 77

Air Cooled Chiller &

heAt PumPTechnical feature

SyScrew 1070-1300 Air CO HT 1070 1130 1170 1200 1300Cooling capacity1 kW 1092 1155 1195 1242 1342Power input1 kW 382,2 402,9 422,3 443,6 479,8EER1 2,86 2,87 2,83 2,80 2,80Energy efficiency class C C C C CESEER1 3,43 3,33 3,40 3,25 3,25RefrigerantType HFC 134aNumber of refrigerant circuits 2 2 2 2 2CompressorQty 2Type ScrewPart load steps % 25-50-62-75-87-100Power supply 400V/3/50HzStart-up type Y/ΔEvaporatorQty 1Type Shell & TubeWater flow rate m3/h 188,4 199,2 206,1 214,2 231,6Water pressure drop kPa 32,0 35,6 36,5 39,5 45,7Inlet/outlet diameter inch 8” 8” 8” 8” 10”CondenserQty 17 18 19 20 22Type MCHX - Al/AlloyFanQty 17 18 19 20 22Air flow m3/s 132,7 140,5 148,3 156,1 171,7Power input kW 52,7 55,8 58,9 62,0 68,2WeightShipping kg 7.490 7.760 7.970 8.180 8.570Operating kg 7.880 8.150 8.350 8.560 8.940DimensionsLength mm 9.900 10.900 10.900 10.900 12.000Width mm 2.200 2.200 2.200 2.200 2.200Height mm 2.550 2.550 2.550 2.550 2.550Acoustical dataSound power level2 dB(A) 106 107 107 107 108Sound pressure level at 10 m3 dB(A) 73 74 74 74 75

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard. 2 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.3 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.

Page 80: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Air cooled Chiller & Heat Pump78

Air Cooled ChillerSLS HE 5204-8404

Technical feature 8 sizes Cooling capacity from 1142 to 1.687 kW 3 acoustic versions:

BLN (Basic Low Noise) LN (Low Noise) ELN (Extra Low Noise)

Four indipendent refrigerant circuit 4 Screw compressors Electronic expansion valve

Accessories and options BMS interface Coils treatments Compressors acoustic box (standard) Compressors stepless control Desuperheater and totaly heat recovery Fan speed control (-15°C) Hydrokit with 1 or 2 pumps with ot without buffer tank Mechanical gauges Power factor corrector capacitors Sequence phases control (standard) Sofstart Unit protection grilles Water filter Water flow switch

1.142-1.687 kW Shell & Tube

Air cooled Screw

134a

Page 81: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Air cooled Chiller & Heat Pump | 79

Air Cooled Chiller &

heAt PumPOperating limit (to be confirmed following selection software issue)

SLS HE 5204-64045204 5604 6004 6404

Min Max Min Max Min Max Min Max

Leaving water temperatureWater °C from +5 to +15

∆ T K from 3 to 8

Air temperature

BLN °C from -52 to 48 from -52 to 48 from -52 to 47 from -52 to 47

LN °C from -52 to 45 from -52 to 45 from -52 to 44 from -52 to 44

ELN °C from -15 to 45 from -15 to 45 from -15 to 44 from -15 to 44

External static pressureStandard fans Pа 0

High pressure fans (HPF) Pа 100

SLS HE 6804-84046804 7204 7804 8404

Min Max Min Max Min Max Min Max

Leaving water temperatureWater °C from +5 to +15

∆ T K from 3 to 8

Air temperature

BLN °C from -52 to 47 da -52 a 44 from -52 to 44 from -52 to 44

LN °C from -52 to 41 from -52 to 41 from -52 to 41 from -52 to 41

ELN °C from -15 to 41 from -15 to 41 from -15 to 41 from -15 to 41

External static pressureStandard fans Pа 0

High pressurefans (HPF) Pа 100

2 Minimum Air Temperature -15°C with fan speed control (option).

2 Minimum Air Temperature -15°C with fan speed control (option).

Page 82: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Air cooled Chiller & Heat Pump80

Technical feature

SLS 5204-8404 HE BLN 5204 5604 6004 6404 6804 7204 7804 8404Cooling capacity1 kW 1.142,0 1.208,0 1.292,8 1.406,4 1.482,2 1.557,9 1.637,2 1.686,9Power input1 kW 326,2 342,4 377,8 419,8 467 514,2 543,3 575,0EER1 3,50 3,50 3,40 3,40 3,20 3,00 3,00 2,90Part load steps % 9RefrigerantType HFC 134aNumber of refrigerant circuits 4CompressorQty 4Type ScrewEvaporatorQty 2Type Shell & TubeWater flow l/h 196.424 207.776 222.361 241.900 254.938 267.958 281.598 290.146Diametro ingresso/uscita inch 6˝ 6˝ 6˝ 8˝ 8˝ 8˝ 8˝ 8˝CondenserQty 8Total coil face area per coil mm2 12FanQty 20 20 24 24 24 24 24 24Air flow m3/h 420.000 408.000 440.000 440.000 440.000 440.000 440.000 440.000Speed rpm 900 900 900 900 900 900 900 900Power input kW 36 36 43,2 43,2 43,2 43,2 43,2 43,2WeightShipping kg 11.344 12.089 12.936 13.679 13.756 13.944 14.050 14.167Operating kg 11.580 12.561 13.388 14.085 14.135 14.421 14.542 14.659DimensionsLength mm 12.000 12.000 12.000 12.000 12.000 12.000 12.000 12.000Width mm 2.200 2.200 2.200 2.200 2.200 2.200 2.200 2.200Height mm 2.550 2.550 2.550 2.550 2.550 2.550 2.550 2.550Acoustical dataSound power level2 dB(A) 102 102 103 103 103 103 103 103Sound pressure level at 10 m3 dB(A) 69 69 70 70 70 70 70 70

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard. 2 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.3 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.

Page 83: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Air cooled Chiller & Heat Pump | 81

Air Cooled Chiller &

heAt PumPTechnical feature

SLS HE 5204-8404 LN 5204 5604 6004 6404 6804 7204 7804 8404Cooling capacity1 kW 1.096,3 1.159,7 1.241,1 1.350,1 1.422,9 1.495,6 1.571,7 1.619,4Power input1 kW 345,8 362,9 400,5 445,0 495,0 545,1 575,9 609,5EER1 3,20 3,20 3,10 3,00 2,90 2,70 2,70 2,70Part load steps % 9RefrigerantType HFC 134aNumber of refrigerant circuits 4CompressorQty 4Type Screw EvaporatorQty 2Type Shell & TubeWater flow l/h 188.563 199.468 213.469 232.217 244.738 257.243 270.332 278.536Inlet/outlet diameter inch 6˝ 6˝ 6˝ 8˝ 8˝ 8˝ 8˝ 8˝CondenserQty 8Total coil face area per coil mm2 12FanQty 20 20 24 24 24 24 24 24Air flow m3/h 285.600 277.440 299.200 299.200 299.200 299.200 299.200 299.200Speed rpm 700 700 700 700 700 700 700 700Power input kW 25 25 30 30 30 30 30 30WeightShipping kg 11.560 12.305 13.152 13.895 13.972 14.160 14.266 14.383Operating kg 11.796 12.777 13.604 14.301 14.351 14.637 14.758 14.875DimensionsLength mm 12.000 12.000 12.000 12.000 12.000 12.000 12.000 12.000Width mm 2.200 2.200 2.200 2.200 2.200 2.200 2.200 2.200Height mm 2.550 2.550 2.550 2.550 2.550 2.550 2.550 2.550Acoustical dataSound power level2 dB(A) 96 96 97 97 97 97 97 97Sound pressure level at 10 m3 dB(A) 63 63 64 64 64 64 64 64

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard. 2 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.3 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.

Page 84: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Air cooled Chiller & Heat Pump82

Technical feature

SLS HE 5204-8404 ELN 5204 5604 6004 6404 6804 7204 7804 8404Cooling capacity1 kW 1.096,3 1.159,7 1.241,1 1.350,1 1.422,9 1.495,6 1.571,7 1.619,4Power input1 kW 345,8 362,9 400,5 445,0 495,0 545,1 575,9 609,5EER1 3,20 3,20 3,10 3,00 2,90 2,70 2,70 2,70Part load steps % 9RefrigerantType HFC 134aNumber of refrigerant circuits 4CompressorsQty 4Type ScrewEvaporatorQty 2Type Shell & TubeWater flow l/h 188.563 199.468 213.469 232.217 244.738 257.243 270.332 278.536Inlet/outlet diameter inch 6˝ 6˝ 6˝ 8˝ 8˝ 8˝ 8˝ 8˝CondenserQty 8Total coil face area per coil mm2 12FanQty 20 20 24 24 24 24 24 24Air flow m3/h 285.600 277.440 299.200 299.200 299.200 299.200 299.200 299.200Speed rpm 700 700 700 700 700 700 700 700Power input kW 25 25 30 30 30 30 30 30WeightShipping kg 11.560 12.305 13.152 13.895 13.972 14.160 14.266 14.383Operating kg 11.796 12.777 13.604 14.301 14.351 14.637 14.758 14.875DimensionsLength mm 12.000 12.000 12.000 12.000 12.000 12.000 12.000 12.000Width mm 2.200 2.200 2.200 2.200 2.200 2.200 2.200 2.200Height mm 2.550 2.550 2.550 2.550 2.550 2.550 2.550 2.550Acoustical dataSound power level2 dB(A) 90 90 91 91 93 93 93 93Sound pressure level at 10 m3 dB(A) 57 57 58 58 60 60 60 60

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard. 2 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.3 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.

Page 85: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

AIR COOLED CHILLER &

HEAT PuMP

Page 86: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Air cooled Chiller & Heat Pump84

Operating limit (to be confirmed following selection software issue)

Cooling mode

Mini SysAqua DCI5-16

Min MaxLeaving water temperature* °C 4 20Air temperature °C -5 46

Heating mode

Mini SysAqua DCI5-16

Min MaxLeaving water temperature* °C 30 55Air temperature °C -15 27

Technical feature 6 sizes Cooling capacity from 5,0 to 14,5 kW Heating capacity from 5,5 to 16,0 kW Operating Range:

from -5 to 46 °C cooling and from -15 to 27 °C heating DC Inverter technology: Compressor and outdoor fan motor One refrigerant circuit with DC compressor Blue fin coil LWT up to +55 °C in heating mode, outdoor temperature down

to -15 °C. Bi-flow electronic expansion valve as standard Stainless steel plate heat exchanger with antifreeze protection Centrifugal pump as standard Operating low water content in the plant

Accessories and options Automatic circuit breaker (standard) Coil grilles (standard) Fan speed control (standard) Remote on/off Sequence phases control (standard) Softstart (standard) Water differential pressure switch (standard from 10 to 16) Water flow switch ( standard from 5 to 7 )

Inverter Air Cooled Heat PumpMini SysAqua DCI 5-16

5-14.5kW

Plate

Air cooled Scroll 410A

INVERTER Inverter5.5-16 kW

NEW Q1 2016

Page 87: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Air cooled Chiller & Heat Pump | 85

Air Cooled Chiller &

heAt PumPTechnical feature

Mini SysAqua DCI 5 7 10 12 14 16Cooling Capacity 4 kW 5.0 7.0 10.0 11.2 12.5 14.5Power input4 kW 1.55 2.25 2.95 3.38 3.9 4.53EER4 3.23 3.11 3.39 3.31 3.2 3.2Energy Efficiency Class A A A A A ACooling Capacity 2 kW 6.57 7.88 10.9 14.5 15.17 16.70Power input2 kW 1.27 1.84 2.95 2.8 3.13 3.73EER2 5.16 4.28 4.39 5.17 4.84 4.48Heating Capacity3 kW 5.5 8.0 11.0 12.3 13.8 16.0Power input3 kW 1.7 2.5 3.14 3.72 4.25 4.85COP3 3.24 3.2 3.50 3.31 3.25 3.3Energy Efficiency Class A A A A A AHeating Capacity 1 kW 6.32 8.29 10.96 13.75 15.30 16.97Power input1 kW 1.52 2.13 2.51 2.85 3.15 3.86Part load steps % SteplessPower supply V/ph/Hz 230/1/50 230/1/50 230/1/50 400/3/50 400/3/50 400/3/50Startup type Soft-start (inverter)RefrigerantType HFC 410ANumber of refrigerant circuits 1CompressorNumber / Type 1 / RotaryEvaporatorQty 1Type Plate exchangerWater flow rate l/h 860 1200 1720 1920 2150 2490Pressure drop kPa 15 15 18 18 18 19FanQty 1 1 1 2 2 2 Air flow m3/h 5.100 5.100 7.000 7.000 7.000 7.000Power input W 170 170 100 100 100 100PumpQty 1 1 1 1 1 1Power input (H/M/L) W 93/67/46 93/67/46 210/175/120 210/175/120 210/175/120 210/175/120Available static pressure m 5.5 5.5 8 8 8 8Water ConnectionsInlet/Outlet Diameter inch 1" 1" 1” 1/4 1” 1/4 1” 1/4 1” 1/4WeightShipping kg 91 91 121 121 122 122Operating kg 81 81 110 110 111 111DimensionsLenght mm 990 990 970 970 970 970Width mm 354 354 400 400 400 400Height mm 966 966 1327 1327 1327 1327Acoustical dataSound pressure level5 dB(A) 58 58 59 59 60 60

1 Data refers to chilled water inlet/outlet temperature: 12/7°C,outdoor ambient temperature 35°C DB..2 Data refers to chilled water inlet/outlet temperature: 23/18°C,outdoor ambient temperature 35°C DB. 3 Data refers to warm water inlet/outlet temperature: 40/45°C,outdoor ambient temperature 7°C DB/6°C WB.4 Data refers to warm water inlet/outlet temperature: 30/35°C,outdoor ambient temperature 7°C DB/6°C WB.5 Sound pressure levels is tested 1m away in front of the unit in a semi-anechoic room(sound pressure).

Page 88: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Air cooled Chiller & Heat Pump86

Operating limit (to be confirmed following selection software issue)

Cooling mode

SyScroll 20-30 Air EVO HP20 30

Min Max Min MaxLeaving water temperature* °C -8 18 -8 18∆ T water K 3 7 3 7Air temperature °C -10 45 -10 45

* Below 5°C, glycol is required. For operation below 0°C contact sales office.

Chillers suitable for operation without buffer tank for water content greater than 2,5 liters of water per kW of output.

Heating mode

SyScroll 20-30 Air EVO HP20 30

Min Max Min MaxLeaving water temperature* °C 25 55 25 55∆ T water K 3 7 3 7Air temperature °C -15 20 -15 20

Technical feature 2 sizes Cooling capacity from 20,0 to 35,9 kW Heating capacity from 20,4 to 34,0 kW Operating Range:

from -10 to 45 °C cooling and from -15 to 20 °C heating Inverter driven compressor A single inverter driven 3-phase scroll compressor equipped

with brushless motor with variable frequency (20-120 Hz) One refrigerant circuit Bi-flow electronic expansion valve Multistage centrifugal pump as standard Bluefin coil Operating low water content in the plant

Accessories and options Automatic circuit breaker (standard) Buffer tank placed under unit Coils treatments Coil grilles (standard) Fan speed control (standard) In/Out Valve kit Power factor corrector capacitors (standard) Remote on/off Sequence phases control (standard) Softstart (standard) Water differential pressure switch (standard) Water filter (standard) & Water flow switch

Inverter Air Cooled Heat PumpSyScroll 20-30 Air EVO HP

20-36 kW

Plate

Air cooled Scroll 410A

INVERTER Inverter20-34 kW

ENERGY EFFICIENCY

Report to performance data

COOLING MODE

2014

Page 89: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Air cooled Chiller & Heat Pump | 87

Air Cooled Chiller &

heAt PumPTechnical feature

SyScroll 20-30 Air EVO HP 20 30Heating Capacity (min/nom/max)1 kW 9,94 20,4 29,4 11,5 26,1 34,0Power input1 kW 2,98 5,02 8,37 3,01 6,45 9,80COP1 kW/kW 3,34 4,06 3,51 3,82 4,05 3,47Eurovent class A ACooling Capacity (min/nom/max)2 kW 9,33 20,0 28,0 13,9 29,0 35,9Power input2 kW 2,38 4,15 6,61 3,51 7,24 13,0EER2 kW/kW 3,92 4,82 4,24 3,96 4,01 2,76Energy Efficiency Class A AHeating Capacity (min/nom/max)3 kW 8,90 20,4 27,4 10,2 26,1 33,5Power input3 kW 3,34 6,44 9,64 3,97 8,42 11,6COP3 kW/kW 2,66 3,17 2,84 2,57 3,10 2,89Energy Efficiency Class B BCooling Capacity (min/nom/max)4 kW 6,60 20,0 25,2 9,43 29,0 31,1Power input4 kW 2,52 6,65 10,3 3,14 10,7 12,4EER4 kW/kW 2,62 3,01 2,45 3,00 2,71 2,51Energy Efficiency Class B CEER 75% kW/kW 3,83 3,65EER 50% kW/kW 4,53 4,48EER 25% kW/kW 3,80 4,79ESEER kW/kW 4,08 4,23Part load steps % SteplessPower supply V/ph/Hz 400/3+N/50Startup type Soft-start (inverter)RefrigerantType HFC 410ANumber of refrigerant circuits 1CompressorNumber / Type 1 / Scroll (BLDC Motor)Crankcase heater W 40EvaporatorQty 1Type Plate exchanger AISI 316Water flow rate / pressure drop l/h / kPa Refer to hydraulic circuit dataAntifreeze heater W 35FanQty 2 2Air flow m3/h 10.848 10.425Power input kW 0,54 0,54PumpQty 1 1Power input kW 0,56 0,63Water flow rate / available static pressure l/h/kPa Refer to hydraulic circuit dataWater ConnectionsType Male GAS ThreadedInlet/Outlet Diameter inch 1” 1/4WeightShipping kg 266 281Operating kg 260 275DimensionsLenght mm 1.477 1.477Width mm 539 539Height mm 1.615 1.615Acoustical dataSound power level5 dB(A) 74 75Sound pressure level6 dB(A) 43 44

1 Data refers to 35°C leaving warm water temperature and 7°C ambient coil air temperature with 87% R.H., according EN14511 standard.2 Data refers to 18°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard. 3 Data refers to 45°C leaving warm water temperature and 7°C ambient coil air temperature with 87% R.H., according EN14511 standard.4 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard.5 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.6 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.

Page 90: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Air cooled Chiller & Heat Pump88

Technical feature 4 sizes Cooling capacity from 20,2 to 33,4 kW Heating capacity from 20,9 to 35 kW One scroll compressor New control Operating low water content in the plant Pump as standard

Accessories and options Automatic circuit breaker (standard) Buffer tank placed under unit Coils treatments Coil grilles Desuperheater Fan speed control (standard) Mechanical gauges Power factor corrector capacitors Sequence phases control (standard) Softstart Water flow switch Water differential pressure switch (standard) Water filter (standard)

Operating limit (to be confirmed following selection software issue)

SyScroll Air HP20 25 30 35

Min - MaxLeaving water temperature (cooling)* °C from -8 to 18∆ T water (cooling mode) K 3 - 7Leaving water temperature (heating) °C +25 to +55∆ T water (heating mode) K 3 - 15Air temperature °C Refer to below graphichs

* Below 5°C, glycol and electronic expansion valve is required.

Chillers suitable for operation without buffer tank for water content greater than 4 liters of water per kW of output.

Air Cooled Chiller & Heat PumpSyScroll 20-35 Air HP

20-33 kW

Plate

Air cooled Scroll

410A21-35 kW

-20 -15 -10 -5 0 5

10 15 20 25 30 35 40 45 50 55 60

-8 -6 -4 -2 0 2 4 6 8 10 12 14 16 18

OAT

(°C)

LWT (°C)

Water +Glycol + EEV Water

-12 25 27 29 31 33 35 37 39 41 43 45 47 49 51 53 55 57

-10 -8 -6 -4 -2 0 2 4 6 8

10 12 14 16 18 20 22

OAT

(°C)

LWT (°C)

SyScroll 20-35 Air HP - Cooling operation SyScroll 20-35 Air HP - Heating operation

Page 91: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Air cooled Chiller & Heat Pump | 89

Air Cooled Chiller &

heAt PumP

SyScroll 20-35 Air HP 20 25 30 35Cooling capacity1 kW 20,2 23,9 27,4 33,4Power input1 kW 6,91 7,65 9,27 11,5EER 100%1 2,92 3,12 2,96 2,90Energy Efficiency Class B A B BESEER 3,34 3,61 3,50 3,40Heating capacity2 kW 20,9 24,5 28,4 35,0Power input2 kW 6,70 7,69 8,70 10,8COP2 3,12 3,19 3,26 3,24Energy Efficiency Class B B A APart load steps % 0-100Power supply V/Ph/Hz 400/3+N/50Startup type DirectRefrigerantType HFC 410ANumber of refrigerant circuits 1CompressorQty / Type 1 / ScrollCrankcase heater W 70 90 90 90Internal heat exchangerQty / Type 1 / Plate exchanger AISI 316

Summer operationWater flow l/s 0,95 1,12 1,29 1,57Available Static Pressure kPa 172 154 148 116

Winter operationWater flow l/s 1,02 1,19 1,38 1,70Available Static Pressure kPa 164 146 138 101

Antifreeze heater W 35 35 35 35Connection type Male gas threadedInlet/outlet diameter inch 1”1/4Water drain connection inch ⅜”FanQty / Type 2 / AxialAir flow m3/h 11.289 10.848 10.848 10.425Power input kW 0,53 0,54 0,54 0,54PumpQty 1 1 1 1Input Power (Summer / Winter) kW 0,57/0,58 0,60/0,61 0,62/0,63 0,65/0,66WeightShipping kg 256 287 291 305Operating kg 250 281 286 299DimensionsLenght mm 1.477 1.477 1.477 1.477Width mm 539 539 539 539Height mm 1.615 1.615 1.615 1.615Acoustical dataSound power level3 dB(A) 73 74 74 75Sound pressure level at 10 m4 dB(A) 41 42 42 43

Technical feature

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard.2 Data refers to 45°C leaving warm water temperature and 7°C ambient coil air temperature with 87% R.H., according EN14511 standard.3 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.4 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.

Page 92: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Air cooled Chiller & Heat Pump90

Cooling modeLeaving water temperature (without glycol) 5/18°CLeaving water temperature (with glycol max 40%) 2/18°CExternal Max air temperature 50°CExternal Min air temperature -10°CHeating modeLeaving water temperature max 55°CExternal Max air temperature +20°CExternal Min air temperature -15°C

Air cooled heat pump SysAqua 25-40 H

Technical feature 4 sizes Cooling capacity from 25 to 37 kW Heating capacity from 27 to 40 kW

EER up to 2,97 ESSEER up to 4 COP up to 3,04 SCOP up to 3,19 Refrigerant R410A

Main functions Available with one cooling circuit Tandem scroll per refrigerant circuit Extented working limit Heat Pump operating function Leaving hot water up to 55°C

Available versions Low sound level standard High temperature operation up to 50°C Return or leaving water temperature control With Hydraulic kit as STD

Product Advantages Operating heating mode up to -15°C Tandem scroll compressors per circuit for a highest

efficiency at partial load High ESEER ILTC II Controller that allows to reduce the use of an external

water tank 3,5 l/kW Low footprint

Easy maintenance Low water pressure drop Set point compensation as (standard) Night mode (extra low sound level) std

25-37 kW

Plate

Air cooled Scroll

27-40 kW 410A

ON OFF Remote Remote heat cool mode Water flow switch factory mounted (standard) Water filter (standard) (not mounted) Phase monitor (standard) Few options, maximum features as (standard)

Main accessories and options HP/BP Manometers Kit interface modbus Low temperature kit (-15°C) Compressor softstarter Power supply without neutral Aluminium fins with epoxy coating Condenser coil guards Complete Hydraulic kit 1 pump medium pressure as standard Rubber antivibration pad Water level pressure switch External water tank

Operating limit (to be confirmed following selection software issue)

Page 93: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Air cooled Chiller & Heat Pump | 91

Air Cooled Chiller &

heAt PumP

SysAqua 25-40 H 25 30 35 40Cooling Capacity kW 25,3 26,9 35,8 37,4Power input kW 8,6 9,3 13,5 13,6Total EER 100%** 2,94 2,88 2,71 2,70ESEER** 3,78 3,77 3,88 3,71Heating Capacity kW 26,9 29,7 37,3 41,6Power input kW 9,27 9,93 13,21 13,49SCOP 3.19 3.16 3.03 3.17SCOP Energy Efficiency Class A+ A+ A A+Power supply 400V/3~+N/50HzStart up type Direct Direct Direct Direct Nominal current A 15,1 16,3 24 24Maximum operating current A 22,5 24,5 32 34Inrush current A 64 77.5 118.5 119.5RefrigerantType HFC 410ANumber of refrigerant circuit 1 1 1 1CompressorQty 2 2 2 2Type Scroll Scroll Scroll Scroll N° capactity steps % 0/50/100 0/50/100 0/50/100 0/50/100Cranckcrease heater W 2 X 40 2 X 70 2 X 70 2 X 70EvaporatorQty 1 1 1 1 Type Plate Plate Plate PlateWater flow rate m³/h 4,3 4,6 6,1 6,3Water pressure drop kPa 37 22 37 37Water volume l 1,78 2,55 2,55 2,55Antifreeze heater W 30 30 30 30CoilQty 1 1 1 1Total coil face area per coil m2 2,4 2,4 2,4 2,4Fan motorsQty 1 1 1 1Air flow m³/h 13.000 13.000 16.000 16.000Rotation speed tr/mn 900 900 650 650Power input (unitary) W 940 940 930 930PumpsQty Option 2 pumps Power input kW Option 2 pumps Available static pressure Kpa Options 2 pumps Hydraulic ConnectionType Male gas threadedInlet diameter inch 1”1/2 1”1/2 1”1/2 1”1/2Outlet diameter inch 1”1/2 1”1/2 1”1/2 1”1/2DimensionsLength mm 1.000 1.000 1.000 1.000Width mm 1.000 1.000 1.000 1.000Height mm 1.983 1.983 1.983 1.983WeightOperating kg 300 330 340 340Acoustic dataSound power level* dB(A) 75 75 76 76

* Following Eurovent standard.** Following Eurovent 14511.

Technical feature

Page 94: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Air cooled Chiller & Heat Pump92

Technical feature 6 sizes

Cooling capacity from 36,8 to 71,6 kW Heating capacity from 39,2 to 76,3 kW

3 versions: STD (Standard version)

HT (High Temperature) HPF (High Pressure Fans) 2 Low Noise versions:

Standard version (STD) Super Low Noise (S) One refrigerant circuit 2 scroll compressors (one tandem) Low operating water content in the plant “Polar” version for extreme conditions

Accessories and options Automatic circuit breaker Coils treatments Coil grilles (standard) Compressors acoustic box (standard on S) Compressors jackets (standard S) Desuperheater Electric heater inside buffer tank for additional heating Fan speed control Hydrokit with 1 or 2 pumps with or without buffer tank Mechanical gauges Power factor corrector capacitors Sequence phases control (standard) Softstart Water filter (standard) Water pressure switch (standard) Water flow switch (standard)

Air Cooled Heat PumpSyScroll 40-75 Air HP

Operating limit (to be confirmed following selection software issue)

SyScroll 40-75 Air HP40 45 50 60 65 75

Min - MaxLeaving water temperature (cooling)* °C from -8 to +18Water ∆ T (cooling) K 3 - 7Leaving water temperature (heating) °C from +25 to +55Water ∆ T (heating) K 3 - 15Air temperature °C Refers to following graphics

* Below 5°C, glycol and electronic expansion valve are required.

Chillers suitable for operation without buffer tank for water content greater than 2,5 liters of water per kW of output.

37-72 kW

Plate

Air cooled Scroll

39-76 kW 410A

Page 95: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Air cooled Chiller & Heat Pump | 93

Air Cooled Chiller &

heAt PumP

-25-20-15-10

-505

1015202530354045

WaterWater + Glycol + EEV

Water + Glycol + EEV + FSC Water + FSC

LWT (°C)

OAT

(°C)

-9 -10 -8 -7 -6 -5 -4 -3 -2 -1 0 1 2 3 4 5 6 7 8 9 10 20191817161514131211

S Version

Cooling

-25-20-15-10

-505

101520253035404550

WaterWater + Glycol + EEV

Water + Glycol + EEV + FSC Water + FSC

LWT (°C)

OAT

(°C)

-9 -10 -8 -7 -6 -5 -4 -3 -2 -1 0 1 2 3 4 5 6 7 8 9 10 20191817161514131211

BLN Version

Cooling

-25-20-15-10

-505

10152025303540455055

WaterWater + Glycol + EEV

LWT (°C)

OAT

(°C)

-9 -10 -8 -7 -6 -5 -4 -3 -2 -1 0 1 2 3 4 5 6 7 8 9 10 20191817161514131211

40-50

60-75

HT Version

Cooling

-25-20-15-10

-505

10152025303540455055

WaterWater + Glycol + EEV

LWT (°C)

OAT

(°C)

-9 -10 -8 -7 -6 -5 -4 -3 -2 -1 0 1 2 3 4 5 6 7 8 9 10 20191817161514131211

40-50

60-75

-12-10

-8-6-4-202468

10121416182022

LWT (°C)

OAT

(°C)

18 20 22 24 26 28 30 32 34 36 38 40 42 44 565452504846

Heating

LWT (°C)

OAT

(°C)

18 20 22 24 26 28 30 32 34 36 38 40 42 44 565452504846-12-10

-8-6-4-202468

10121416182022

Heating

Heating

-12-10

-8-6-4-202468

10121416182022

LWT (°C)

OAT

(°C)

18 20 22 24 26 28 30 32 34 36 38 40 42 44 565452504846

Page 96: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Air cooled Chiller & Heat Pump94

Technical feature

SyScroll 40-75 Air HP (STD-HPF-HT) 40 45 50 60 65 75 Cooling capacity1 kW 36,8 41,7 48,4 56,8 64,3 71,6Power input1 kW 13,6 15,6 18,1 19,9 22,8 27,1EER1 2,71 2,67 2,67 2,85 2,82 2,64Energy Efficiency Class C D D C C DESEER 3,81 3,74 3,72 3,82 3,75 3,57Heating capacity2 kW 39,2 43,7 51,7 58,0 69,1 76,3Power input2 kW 13,3 14,5 16,3 21,3 23,0 26,9COP2 2,95 3,01 3,17 2,72 3,00 2,84Energy Efficiency Class C B B C B CPart load steps % 0-50-100 0-50-100 0-50-100 0-44-56-100 0-50-100 0-50-100Power supply V/Ph/Hz 400/3+N/50Startup type DirectRefrigerantType HFC 410ANumber of refrigerant circuits 1 1 1 1 1 1CompressorQty 2 2 2 2 2 2Type ScrollCrankcase heater W 90 90 90 90 90 90EvaporatorQty 1 1 1 1 1 1Type Plate exchanger AISI 316Water flow l/h 6.209 7.052 8.170 9.615 10.888 12.160Antifreeze heater W 35 35 35 35 35 35Connection type Male gas threadedInlet/outlet diameter inch 2” 2” 2” 2” 2” 2”Water drain connection inch ⅜” ⅜” ⅜” ⅜” ⅜” ⅜”CondenserQty 1 1 1 1 1 1Total coil face area per coil mm 2,6 2,6 2,6 3,2 3,2 3,2FanQty 1 1 1 1 1 1Air flow m3/h 14.800 14.800 14.800 22.250 22.250 22.250Speed rpm/min 680 680 680 900 900 900Power Input kW 0,98 0,98 0,98 2,00 2,00 2,00Power Input* kW 2,67 2,67 2,67 2,67 2,67 2,67Available static pressure* Pa from 0 to 120WeightShipping kg 422 430 457 504 511 517Operating kg 431 440 467 517 524 530DimensionsLength mm 1.750 1.750 1.750 2.200 2.200 2.200Width mm 1.100 1.100 1.100 1.100 1.100 1.100Height mm 1.580 1.580 1.580 1.580 1.580 1.580Acoustical dataSound power level3 dB(A) 78 79 79 83 84 84Sound pressure level4 dB(A) 47 47 47 52 52 52

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard.2 Data refers to 45°C leaving warm water temperature and 7°C ambient coil air temperature with 87% R.H., according EN14511 standard.3 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.4 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.* HPF / HT versions with EC fan motor.

Page 97: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Air cooled Chiller & Heat Pump | 95

Air Cooled Chiller &

heAt PumPTechnical feature

SyScroll 40-75 Air HP S 40 45 50 60 65 75 Cooling capacity1 kW 36,8 40,2 46,3 55,0 59,8 68,9Power input1 kW 13,9 16,1 18,9 20,1 22,9 28,0EER1 2,65 2,50 2,45 2,74 2,61 2,46Energy Efficiency Class D D E C D EESEER 3,61 3,50 3,42 3,67 3,47 3,35Heating capacity2 kW 38,2 42,5 50,4 56,6 67,3 74,4Power input2 kW 13,0 14,2 16,1 20,8 22,5 26,4COP2 2,94 2,99 3,13 2,72 2,99 2,82Energy Efficiency Class C C B C C CNumber of refrigerant circuits 1 1 1 1 1 1Part load steps % 0-50-100 0-50-100 0-50-100 0-44-56-100 0-50-100 0-50-100Power supply V/Ph/Hz 400/3+N/50Startup type DirectRefrigerantType HFC 410ACompressorQty 2 2 2 2 2 2Type ScrollCrankcase heater W 90 90 90 90 90 90EvaporatorQty 1 1 1 1 1 1Type Plate exchanger AISI 316Water flow l/h 6.209 6.794 7.809 9.305 10.114 11.679Antifreeze heater W 35 35 35 35 35 35Connection type Male gas threadedInlet/outlet Diameter inch 2” 2” 2” 2” 2” 2”Water drain connection inch ⅜” ⅜” ⅜” ⅜” ⅜” ⅜”CondenserQty 1 1 1 1 1 1Total coil face area per coil mm 2,6 2,6 2,6 3,2 3,2 3,2FanQty 1 1 1 1 1 1Air flow m3/h 11.500 11.500 10.800 17.000 17.000 17.000Speed rpm/min 530 530 530 720 720 720Power Input kW 0,57 0,57 0,57 1,27 1,27 1,27WeightShipping kg 422 430 457 504 511 517Operating kg 431 440 467 517 524 530DimensionsLength mm 1.750 1.750 1.750 2.200 2.200 2.200Width mm 1.100 1.100 1.100 1.100 1.100 1.100Height mm 1.580 1.580 1.580 1.580 1.580 1.580Acoustical dataSound power level3 dB(A) 74 75 75 78 79 79Sound pressure level4 dB(A) 42 44 44 46 47 47

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard.2 Data refers to 45°C leaving warm water temperature and 7°C ambient coil air temperature with 87% R.H., according EN14511 standard.3 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.4 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.

Page 98: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Air cooled Chiller & Heat Pump96

Cooling modeLeaving water temperature (without glycol) 5/18°CLeaving water temperature (with glycol max 40%) 2/18°CExternal Max air temperature 50°CExternal Min air temperature -10°CHeating modeLeaving water temperature max 55°CExternal Max air temperature +20°CExternal Min air temperature -15°C

Air Cooled Heat PumpSysAqua 45-125 Air H

Technical feature 7 sizes Cooling capacity from 46 to 12 kW Heating capacity from 50 to 120 kW Refrigerant R410A EER up to 3 ESSEER up to 4 COP up to 3.12 SCOP up to 3,31

Main functions Available with one cooling circuit Tandem scroll for refrigerant circuit Extented operating limits Heat Pump operating function

Leaving hot water up to 55°C

Available versions Low sound level standard High temperature operation up to 50°C Return or leaving water temperature control With or without Hydraulic kit

Product Advantages Operating heating mode up to -15°C Tandem scroll compressors per circuit for a highest efficiency

at partial load High ESEER

ILTC II Controller that allows to reduce the use of an external water tank 3,5 l/kW

Low footprint Easy maintenance Low water pressure drop Set point compensation as (standard) Night mode (extra low sound level) std

ON-OFF Remote Remote heat cool mode Water flow switch factory mounted (standard) Water filter (standard) (not mounted) Phase monitor (standard) Few options, maximum features as (standard)

Main accessories and options HP/BP Manometers Kit interface modbus Low temperature kit (-15°C) Compressor softstarter Power supply without neutral Aluminium fins with epoxy coating Condenser coil guards Complete Hydraulic kit 1 pump medium pressure Rubber antivibration pad Water level pressure switch Water tank 300lt Complete Hydraulik kit 2 pumps medium pressure High pressure Fan

46.8-121.9 kW

Plate

Air cooled Scroll

50-120 kW 410A

Operating limit (to be confirmed following selection software issue)

Page 99: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Air cooled Chiller & Heat Pump | 97

Air Cooled Chiller &

heAt PumP

SysAqua 45-125 Air H 45 55 65 75 90 105 125Cooling Capacity kW 46,8 53,3 65,8 71,6 91,4 106,0 122Power input kW 16,89 19,66 22,1 23,8 34,36 38,0 46,4Total EER 100%** 2,77 2,71 2,97 3 2,66 2,79 2,63ESEER** 3,87 3,89 4 3,97 3,82 3,85 3,83Heating Capacity kW 50 58,4 69,6 75,9 88 101,0 119Power input kW 17,85 20,42 22,7 24,3 33,72 38,4 45,4

SCOP 2.99 3.07 3.30 3.23 3.24 3.26 3.31SCOP Energy Efficiency Class A A A+ A+ A+ A+ A+Power supply 400V/3~+N/50HzStart up type Direct Direct Direct Direct Direct Direct Direct Nominal current A 30 35 42 47 62 69 84Maximum operating current A 41 45 59.5 64.5 79.5 87.5 103.5Inrush current A 134 141 205.5 206.5 266.5 313.5 351.5RefrigerantType R410A Number of refrigerant circuit 1 1 1 1 1 1 1CompressorsQty 2 2 2 2 2 2 2Type Scroll Scroll Scroll Scroll Scroll Scroll Scroll

N° capactity steps % 0/45/ 55/100

0/40/ 60/100

0/40/ 60/100

0/45/ 55/100

0/45/ 55/100

0/40/ 60/100

0/33/ 67/100

Cranckcrease heater W 2*90 2*90 2*90 2*90 90/120 90/140 90/140EvaporatorQty 1 1 1 1 1 1 1 Type Plates Plates Plates Plates Plates Plates Plates Water flow rate m³/h 8 9,1 11,3 12,3 15,7 18,2 20,9Water pressure drop kPa 27 35 28 33 26 34 45Water volume l 4,1 4,1 6,1 6,1 10,8 10,8 10,8Antifreeze heater W 30 30 2*30 2*30 2,30 2*30 2*30CoilQty 1 1 2 2 2 2 2Total coil face area per coil m2 4,2 4,2 5,55 5,55 6,4 6,4 6,4Fan motorsQty 1 1 2 2 2 2 2Air flow m³/h 23.500 23.500 30.000 30.000 42.000 42.000 42.000Power input (unitary) W 1.800 1.800 800 800 1.800 1.800 1.800PumpsQty Option 1 or 2 PumpsPower input kW Option 1 or 2 PumpsAvailable static pressure Kpa Option 1 or 2 PumpsHydraulic ConnectionType Male GAS Threaded Inlet Diameter inch 2” 2” 2” 2” 2”1/2 2”1/2 2”1/2Outlet diameter inch 2” 2” 2” 2” 2”1/2 2”1/2 2”1/2DimensionsLength mm 2.180 2.180 2.180 2.180 2.180 2.180 2.180Width mm 1.160 1.160 1.160 1.160 1.160 1.160 1.160Height mm 1.986 1.986 1.986 1.986 2.286 2.286 2.286WeightOperating kg 510 510 580 580 890 1.000 1.020Acoustical dataSound power level* dB(A) 79 79 79 79 82 82 82

* Following Eurovent standard.** Following Eurovent 14511.

Technical feature

Page 100: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Air cooled Chiller & Heat Pump98

Air Cooled Heat PumpSyScroll 85-135 Air HP

Technical feature 5 sizes

Cooling capacity from 79,0 to 125,0 kW Heating capacity from 85,0 to 132,6 kW 3 versions:

STD (Standard versions) HT (High Temperature version) HPF (High Pressure Fans version)

2 acoustic versions: Standard version (STD)

Extra Low Noise version (S) One refrigerant circuit 2 Scroll compressors ( tandem) Microprocessor control Electronic expansion valve as standard

Accessories and options Automatic circuit breaker BMS interface Compressors acoustic box (standard) Compressors jackets Coils treatments Desuperheater Fan speed control Hydrokit with 1 or 2 pumps with or without buffer tank Mechanical gauges Overload protection for compressors Power factor corrector capacitors Sequence phases control (standard) Sofstart Unit protection grilles Water flow switch (standard) Water pressure switch Water filter

79-152 kW

Plate

Air cooled Scroll

85-133 kW 410A

Page 101: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Air cooled Chiller & Heat Pump | 99

Air Cooled Chiller &

heAt PumPOperating limit (to be confirmed following selection software issue)

SyScroll 85-135 Air HP85-135

Min Max

Leaving water temperature(cooling)

Water °С +6 +18Water with glycol +electonic expansion valve* °С -8 +6

∆ T К 3 7

Leaving water temperature(heating)

Water °С +20 +52∆ T К 3 7

Air temperature(cooling)

BLN °С +5 +42S °С -14 +40HT °С -18 +44

Air temperature (heating)

BLN °С -10 +20S °С -10 +20HT °С -12 +20

External static pressureStandard Fans Pa 0High Pressure Fans (HPF) Pa < 120

-20 -15 -10

-5 0 5

10 15 20 25 30 35 40 45 50

-12 -10 -8 -6 -4 -2 0 2 4 6 8 10 12 14 16 18

OAT

(°C)

LWT (°C)

Brine Version* +Water + Glycol

Brine Version*+Water + Glycol + FSC

Water +Glycol

Water +Glycol + FSC

Water

Water + FSC

Std Version - Cooling

-20 -15 -10

-5 0 5

10 15 20 25 30 35 40 45 50

-12 -10 -8 -6 -4 -2 0 2 4 6 8 10 12 14 16 18

OAT

(°C)

LWT (°C)

Brine Version* +Water + Glycol

Water +Glycol Water

S Version - Cooling

-20 -15 -10 -5 0 5

10 15 20 25 30 35 40 45 50 55

-12 -10 -8 -6 -4 -2 0 2 4 6 8 10 12 14 16 18

OAT

(°C)

LWT (°C)

Brine Version* +Water + Glycol

Water +Glycol Water

HT Version - Cooling

-20

-15

-10

-5

0

5

10

15

20

25

15 20 25 30 35 40 45 50 55 60

OAT

(°C)

LWT (°C)

HT Version

Heating

Page 102: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Air cooled Chiller & Heat Pump100

Technical feature

SyScroll 85-135 Air HP 85 95 105 120 135Cooling capacity1 kW 79,0 87,0 98,0 113,8 125,0Power input1 kW 27,6 32,0 39,0 42,0 47,0EER1 2,86 2,72 2,51 2,71 2,66Energy efficiency class C C D C DESEER 3,84 4,22 3,75 3,98 4,00Heating capacity2 kW 85,0 96,0 107,0 120,0 132,6Power input2 kW 27,1 30,8 38,0 42,5 47,2COP2 3,14 3,12 2,82 2,82 2,81Energy efficiency class B B C C CPart load steps % 0-50-100 0-43-100 0-50-100 0-44-100 0-50-100Startup type DirectRefrigerantType HFC 410ANumber of refrigerant circuits 1CompressorQty 2Type ScrollInternal heat exchangerQty 1Type PlateWater flow rate m3/h 13,6 15,0 16,9 19,6 21,5Water pressure drop kPa 24 29 25 21 17Antifreeze heater W 130External heat exchangerQty 2Total coil face area per coil mm 2,4 3,1FanQty 2Air flow rate m3/h 34.700 42.000 43.200Water connectionsType Male GAS ThreadedInlet diameter inch 2”1/2Outlet diameter inch 2”1/2DimensionsLenght mm 3.000 3.500Width mm 1.100 1.100Height mm 2.250 2.250Acoustic dataSound power level3 dB(A) 84 84 88 88 88Sound pressure level4 dB(A) 52 52 56 56 56

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard.2 Data refers to 45°C leaving warm water temperature and 7°C ambient coil air temperature with 87% R.H., according EN14511 standard.3 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.4 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.

Page 103: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Air cooled Chiller & Heat Pump | 101

Air Cooled Chiller &

heAt PumPTechnical feature

SyScroll 85-135 Air HP S 85 95 105 120 135Cooling capacity1 kW 76,0 83,3 95,0 111,4 121,8Power input1 kW 28,3 33,3 40,0 42,6 48,0EER1 2,68 2,50 2,37 2,62 2,54Energy efficiency class D E E D DESEER 3,73 4,10 3,68 3,74 3,88Heating capacity2 kW 82,6 93,1 105,1 117,8 129,4Power input2 kW 26,4 30,1 37,0 41,5 46,2COP2 3,13 3,09 2,84 2,84 2,80Energy efficiency class B B C C CPart load steps % 0-50-100 0-43-100 0-50-100 0-44-100 0-50-100Startup type DirectRefrigerantType HFC 410ANumber of refrigerant circuits 1CompressorQty 2Type ScrollInternal heat exchangerQty 1Type PlateWater flow rate m3/h 13,1 14,3 16,3 19,2 20,9Water pressure drop kPa 22 26 24 20 17Antifreeze heater W 130External heat exchangerQty 2Total coil face area per coil mm 2,4 3,1FanQty 2Air flow rate m3/h 26.200 34.700 35.800Water connectionsType Male GAS ThreadedInlet diameter inch 2”1/2Outlet diameter inch 2”1/2DimensionsLenght mm 3.000 3.500Width mm 1.100 1.100Height mm 2.250 2.250Acoustic dataSound power level3 dB(A) 82 82 85 85 85Sound pressure level4 dB(A) 50 50 53 53 53

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard.2 Data refers to 45°C leaving warm water temperature and 7°C ambient coil air temperature with 87% R.H., according EN14511 standard.3 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.4 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.

Page 104: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Air cooled Chiller & Heat Pump102

Technical feature 6 sizes Cooling capacity from 81,0 to 129,6 kW Heating capacity from 87,0 to 143,6 kW 4 versions:

STD (Standard) HSE (High Seasonal Efficiency) HT (High Temperature) HPF (High Pressure Fans)

2 acoustic versions: BLN (Basic Low Noise)

ELN (Extra Low Noise) Two refrigerant circuit Scroll compressors Microprocessor control Low operating water content in the plant Electronic expansion valve as standard “Polar” version for extreme conditions

Accessories and options Automatic circuit breaker BMS interface Coils treatments Compressors acoustic box (standard) Compressors jackets Desuperheater Double set point Electric heater inside buffer tank for additional heating Fan speed control Hydrokit with 1 or 2 pumps with or without buffer tank Mechanical gauges

Air Cooled Heat PumpAQVH 85-140

Operating limit (to be confirmed following selection software issue)

AQVH 85-140 Min Max

Leaving water temperature (cooling)Water °С +5 +18Water with glycol °С -8 +18

Leaving water temperature (heating) °С +20 +55Air temperature (heating) °С -10 +20Air temperature (heating) Polar Version °C -15 +20

Air temperature (cooling)

BLN °С +5 +47ELN °С -18 +44

HT °С -18 +50 ( 85-115) +47 (125-140)

External static pressureStandard fans Pa 0High Pressure Fans (HPF) Pa < 120

Overload protection for compressors Power factor corrector capacitors Pressure switch Sequence phases control (standard) Sofstart Unit protection grilles Water filter Water flow switch (standard)

81-130 kW

Plate

Air cooled Scroll

87-144 kW 410A

Page 105: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Air cooled Chiller & Heat Pump | 103

Air Cooled Chiller &

heAt PumPTechnical feature

AQVH 85-140 BLN 85 95 105 115 125 140

Cooling capacity1 kW 81,0 89,9 98,9 106,7 115,6 129,6Power input1 kW 27,5 31,5 34,2 36,8 41,6 46,6EER1 2,95 2,85 2,89 2,90 2,78 2,78Energy efficiency class B C B C C CESEER 3,78 3,81 3,86 3,96 3,69 3,77EER HSE1 3,05 2,94 2,97 2,96 2,84 2,84Energy efficiency class B B B B C C

ESEER HSE1 4,21 4,14 4,27 4,28 3,96 4,03

Heating capacity2 kW 87,0 100,4 108,3 116,4 131,5 143,6Power input2 kW 25,7 31,1 32,9 35,7 42,0 45,7COP2 3,39 3,23 3,29 3,26 3,13 3,14Energy efficiency class A A A A B BCOP HSE2 3,54 3,47 3,52 3,47 3,36 3,36Energy efficiency class A A A A A A

Part load steps % 0-25-50- 75-100

0-25-50- 75-100

0-24-47- 74-100

0-25-50- 75-100

0-22-43- 72-100

0-25-50- 75-100

Power supply V/Ph/Hz 400/3/50Startup type DirectRefrigerantType HFC 410ANumber of refrigerant circuits 2 2 2 2 2 2CompressorQty 4 4 4 4 4 4Type ScrollCrankcase heater W 90 90 90 90 90 90EvaporatorQty 1 1 1 1 1 1Type Plate exchanger AISI 316Water flow l/h 13.967 15.508 17.060 18.431 19.987 22.288Antifreeze heater W 130 130 130 130 130 130Connection type Male GAS threadedInlet/outlet diameter inch 2½” 2½” 2½” 2½” 2½” 2½”CondenserQty 2 2 2 2 2 2Total coil face area per coil mm 2,4 2,4 2,4 2,4 3,1 3,1FanQty 2 2 2 2 2 2Air flow m3/h 34.700 34.700 34.050 33.400 44.500 43.200Speed rpm/min 690 690 690 690 900 900Power input kW 2,1 2,1 2,1 2,1 3,4 3,4WeightShipping kg 1.065 1.080 1.122 1.153 1.196 1.270Operating kg 1.090 1.105 1.149 1.180 1.227 1.301DimensionLength mm 2.555 2.555 2.555 2.555 3.155 3.155Width mm 1.095 1.095 1.095 1.095 1.095 1.095Height mm 2.185 2.185 2.185 2.185 2.185 2.185Acoustical dataSound power level3 dB(A) 84 84 84 84 88 88Sound pressure level4 dB(A) 52 52 52 52 56 56Sound power level HPF3 dB(A) 92 92 92 92 95 95Sound pressure level HPF4 dB(A) 60 60 60 60 63 63

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard.2 Data refers to 45°C leaving warm water temperature and 7°C ambient coil air temperature with 87% R.H., according EN14511 standard.3 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.4 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.

Page 106: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Air cooled Chiller & Heat Pump104

Technical feature

AQVH 85-140 ELN 85 95 105 115 125 140Cooling capacity1 kW 78,3 86,5 94,8 102,7 112,7 124,6Power input1 kW 28,7 33,3 36,2 39,4 43,5 47,6EER1 2,73 2,60 2,62 2,61 2,59 2,62Energy Efficiency class C D D D D DESEER 3,57 3,57 3,61 3,52 3,50 3,59EER HSE1 2,84 2,70 2,71 2,69 2,65 2,67Energy Efficiency class C C C D D DESEER HSE1 4,07 3,94 3,94 3,97 3,72 3,85Heating capacity2 kW 85,2 97,8 105,3 113,4 127,4 139,5Power input2 kW 25,3 30,6 32,5 35,4 40,1 44,0COP2 3,37 3,20 3,24 3,20 3,18 3,17Energy Efficiency class A A A A B BCOP HSE2 3,55 3,46 3,50 3,45 3,38 3,38Energy Efficiency class A A A A A A

Part load steps % 0-25-50- 75-100

0-25-50- 75-100

0-24-47- 74-100

0-25-50- 75-100

0-22-43- 72-100

0-25-50- 75-100

Power supply V/Ph/Hz 400/3/50Startup type DirectRefrigerantType HFC 410ANumber of refrigerant circuits 2 2 2 2 2 2CompressorQty 4 4 4 4 4 4Type ScrollCrankcase heater W 90 90 90 90 90 90EvaporatorQty 1 1 1 1 1 1Type Plate exchanger AISI 316Water flow l/h 13.496 14.924 16.355 17.632 19.349 21.508Antifreeze heater W 130 130 130 130 130 130Connection type Male GAS threadedInlet/outlet diameter inch 2½” 2½” 2½” 2½” 2½” 2½”CondenserQty 2 2 2 2 2 2FanQty 2 2 2 2 2 2Air flow m3/h 25.800 25.800 25.300 24.800 36.900 35.800Speed rpm/min 500 500 500 500 690 690Power input kW 1,8 1,8 1,8 1,8 2,1 2,1WeightShipping kg 1.095 1.110 1.152 1.183 1.226 1.300Operating kg 1.120 1.135 1.179 1.210 1.257 1.331DimensionsLength mm 2.555 2.555 2.555 2.555 3.155 3.155Width mm 1.095 1.095 1.095 1.095 1.095 1.095Height mm 2.185 2.185 2.185 2.185 2.185 2.185Acoustical dataSound power level3 dB(A) 82 82 82 82 86 86Sound pressure level4 dB(A) 50 50 50 50 54 54

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard.2 Data refers to 45°C leaving warm water temperature and 7°C ambient coil air temperature with 87% R.H., according EN14511 standard.3 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.4 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.

Page 107: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Air cooled Chiller & Heat Pump | 105

Air Cooled Chiller &

heAt PumPTechnical feature

AQVH 85-140 HT 85 95 105 115 125 140Cooling capacity1 kW 83,6 93,4 103,8 111,7 118,0 132,1Power input2 kW 23,6 27,2 29,5 32,0 37,0 41,2EER 2,96 2,94 3,04 3,05 2,83 2,88ESEER 4,14 4,12 4,25 4,27 3,97 4,03Heating capacity3 kW 93,5 104,9 113,7 121,9 135,6 148,3Power input2 kW 24,5 28,1 30,1 32,8 37,2 40,9COP 3,22 3,21 3,28 3,26 3,25 3,26

Part load steps % 0-25-50- 75-100

0-25-50- 75-100

0-24-47- 74-100

0-25-50- 75-100

0-22-43- 72-100

0-25-50- 75-100

Power supply V/Ph/Hz 400/3/50Startup type DirectRefrigerantType HFC 410ANumber of refrigerant circuits 2 2 2 2 2 2CompressorQty 4 4 4 4 4 4Type ScrollCrankcase heater W 90 90 90 90 90 90EvaporatorQty 1 1 1 1 1 1Type Plate exchanger AISI 316Water flow l/h 14.371 16.073 17.847 19.219 20.291 22.718Antifreeze heater W 130 130 130 130 130 130Connection type Male GAS threadedInlet/outlet diameter inch 2½” 2½” 2½” 2½” 2½” 2½”CondenserQty 2 2 2 2 2 2FanQty 2 2 2 2 2 2Air flow m3/h 50.700 50.700 49.700 48.700 52.700 51.700Speed rpm/min 1.130 1.130 1.130 1.130 1.130 1.130Power input kW 4,6 4,6 4,6 4,6 4,6 4,6WeightShipping kg 1.065 1.080 1.122 1.153 1.196 1.270Operating kg 1.090 1.105 1.149 1.180 1.227 1.301DimensionsLength mm 2.555 2.555 2.555 2.555 3.155 3.155Width mm 1.095 1.095 1.095 1.095 1.095 1.095Height mm 2.185 2.185 2.185 2.185 2.185 2.185Acoustical dataSound power level4 dB(A) 95 95 95 95 95 95Sound pressure level5 dB(A) 63 63 63 63 63 63

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature.2 Input power (only compressors).3 Data refers to 45°C leaving warm water temperature and 7°C ambient coil air temperature with 87% R.H., according EN14511 standard.4 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.5 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.

Page 108: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Air cooled Chiller & Heat Pump106

Air Cooled Heat PumpSyScroll 140-360 Air EVO HP

Technical feature 9 sizes Cooling capacity from 136,7 to 340,5 kW Heating capacity from 144,9 to 361,4 kW Fans versions:

STD (Standard) EC (Inverter Fans) HT (High Temperature) HPF (High Pressure Fans)

Acoustic versions: - (Basic Low Noise) L (Low Noise) S (Super Low Noise)

“Polar” version: Heat Pump for extreme conditions

Two refrigerant circuits 4 Scroll compressors Electronic expansion valve

Accessories and options Automatic circuit breaker BMS interface Coils treatments Compressors acoustic box (standard) Compressors jackets (standard as Super Low Noise) Desuperheater Fan speed control (standard as Super Low Noise version) Hydrokit with 1 or 2 pumps with or without buffer tank

(350lt 140-170, 500lt 200-360) Mechanical gauges Overload protection for compressors Power factor corrector capacitors Sequence phases control (standard) Softstarter Unit protection grilles Water differential pressure switch (standard) Water filter Water flow switch

137-340 kW

Plate

Air cooled Scroll

145-361 kW 410AENERGY EFFICIENCY

Report to performance data

COOLING MODE

2014

Page 109: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Air cooled Chiller & Heat Pump | 107

Air Cooled Chiller &

heAt PumP

SyScroll 140-360 Air EVO HP140 170 200 230

Min Max Min Max Min Max Min Max

Chilled liquid

Temperaturauscita liquido

Water °C +5 to +18Water with glycol* °C -10 to +5Temperature spread K 3 to 7

Maximum operating pressure bar 6

WarmedLiquid

Liquid outlettemperature

Acqua °C +20 to +55ΔT °K 3 to 7

Maximum operating pressure bar 6

Ambient air

Air enteringtemp. Heating

- / L / S / EC °C -10 to +20 Versione Polar °C -13 to +20HT °C -13 to +20

Ambient air

Air enteringtemp. Cooling

- / L / S °C +5 to +48 / +0 to +46 / -14 to +44EC-HT °C -18 to +50

Externalstatic pressure

Standard fans Pa 0High pressure fans Pa <120

Recommended system chilled water volume1 l 420 510 600 690Minimum capacity step % 25 25 21 19Power supply voltage2 V 400 V / 3 Ø / 50 Hz (nominal)

Operating limit (to be confirmed following selection software issue)

* For Liquid outlet temperature <0 °C provide Brine Version (on request for HP).1 Table shows minimum water / brine volume of system (about 3 lt/kW).2 Voltage 400V +/- 10%.

SyScroll 140-360 Air EVO HP260 280 300 330 360

Min Max Min Max Min Max Min Max Min Max

Chilled liquid

Temperaturauscita liquido

Water °C +5 to +18Water with glycol* °C -10 to +5Temperature spread K 3 to 7

Maximum operating pressure bar 6

WarmedLiquid

Liquid outlettemperature

Acqua °C +20 to +55ΔT °K 3 to 7

Maximum operating pressure bar 6

Ambient air

Air enteringtemp. Heating

- / L / S / EC °C -10 to +20 Versione Polar °C -13 to +20HT °C -13 to +20

Ambient air

Air enteringtemp. Cooling

- / L / S °C +5 to +48 / +0 to +46 / -14 to +44EC-HT °C -18 to +50

Externalstatic pressure

Standard fans Pa 0High pressure fans Pa <120

Recommended system chilled water volume1 l 780 840 900 990 1080Minimum capacity step % 17 16 24 23 25Power supply voltage2 V 400 V / 3 Ø / 50 Hz (nominal)

-20

-15

-10

-5

0

5

10

15

20

25

15 20 25 30 35 40 45 50 55 60

OAT

(°C)

LWT (°C)

HT-Polar Version

Heating mode (Cooling mode see page 35)

Page 110: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Air cooled Chiller & Heat Pump108

Technical feature

SyScroll 140-360 Air Evo HP (STD-EC-HPF) 140 170 200 230 260 280 300 330 360Nominal cooling capacity1 kW 136,7 154,5 181,3 213,6 243,7 261,1 287,8 307,4 340,5Input power1 kW 45,1 54,6 61,9 73,2 83,8 90,7 98,5 103,5 117,0EER1 3,03 2,83 2,93 2,92 2,91 2,88 2,92 2,97 2,91Energy efficiency class B C B B B C B B BESEER 3,52 3,47 3,60 3,71 3,71 3,65 3,60 3,64 3,65EER* 3,08 2,86 2,97 2,96 2,95 2,91 2,96 3,02 2,95ESEER* 3,62 3,57 3,71 3,83 3,83 3,78 3,71 3,71 3,76EER** 2,86 2,69 2,73 2,75 2,73 2,71 2,75 2,78 2,74ESEER** 3,38 3,30 3,46 3,56 3,60 3,51 3,46 3,57 3,51Nominal heating capacity2 kW 144,9 165,7 200,1 229,0 262,3 279,6 305,6 327,2 361,4Input power2 kW 44,9 51,6 62,1 70,9 81,7 87,4 94,9 101,9 112,6COP2 3,23 3,21 3,22 3,23 3,21 3,20 3,22 3,21 3,21Energy efficiency class A A A A A A A A ACOP* 3,28 3,25 3,28 3,27 3,26 3,25 3,27 3,26 3,26COP** 3,05 3,05 3,01 3,03 3,01 3,02 3,02 2,99 3,02Nominal heating capacity3 kW 148,6 170,0 207,0 233,8 268,4 285,6 311,0 333,9 367,9Input power3 kW 37,2 43,6 52,7 58,7 67,8 72,3 77,8 83,7 92,7COP3 4,00 3,90 3,93 3,98 3,96 3,95 4,00 3,99 3,97

Total capacity steps % 25-50-75-100

25-50-75-100

21-43-71-100

19-38-69-100

17-39-67-100

16-37-68-100

24-48-71-100

23-50-73-100

25-50-75-100

RefrigerantType HFC 410ANumber of refrigerant circuits 2 2 2 2 2 2 2 2 2CompressorQty 4 4 4 4 4 4 4 4 4Type Scroll EvaporatorQty 1 1 1 2 2 2 1 1 1Type PlateWater flow cooling m3/h 23,6 26,7 31,3 36,9 42,1 45,1 49,6 53,0 58,8Water pressure drop cooling kPa 25 31 34 30 30 35 26 30 37Water flow heating2 m3/h 24,8 28,4 34,3 39,3 45,0 47,9 52,4 56,1 62,0Water pressure drop heating2 kPa 27 36 41 34 34 39 29 33 41Water flow heating3 m3/h 25,5 29,1 35,5 40,1 46,0 48,9 53,3 57,3 63,1Water pressure drop heating3 kPa 29 37 44 36 36 41 30 35 42Water volume l 11,4 11,4 13 21,1 23,4 23,4 32,4 32,4 32,4Antifreeze Heater W 130 130 130 130+130 130+130 130+130 130 130 130Air cooled condenserQty 2 2 5 5 6 6 7 8 8Total coil face area per coil m2 4,6 4,6 2,4 2,4 2,4 2,4 2,4 2,4 2,4FanQty 3 3 5 5 6 6 7 8 8Nominal speed rpm 900 900 900 900 900 900 900 900 900Total airflow m3/h 68.400 68.400 112.500 112.500 135.000 135.000 157.500 180.000 180.000Total input power kW 5,1 5,1 8,5 8,5 10,2 10,2 11,9 13,6 13,6Total input power* kW 4,5 4,5 7,5 7,5 9,0 9,0 10,5 12,0 12,0Total input power** kW 7,8 7,8 13,0 13,0 15,6 15,6 18,2 20,8 20,8External static pressure Pa 0 or 120 Pa**

Water Connections (Evaporator)Type Male GAS ThreadedInlet diameter inch 2”1/2 2”1/2 2”1/2 3” 3” 3” 3” 3” 3”Outlet diameter inch 2”1/2 2”1/2 2”1/2 3” 3” 3” 3” 3” 3”Water Connections (Desuperheater)Type Male GAS ThreadedInlet diameter/Outlet diameter inch 1”/1”WeightShipping kg 1.294 1.337 1.843 1.967 2.188 2.198 2.767 2.860 2.870Operating kg 1.312 1.355 1.858 1.993 2.216 2.226 2.806 2.899 2.909Additional weightEC-HPF versions kg 30 30 50 50 60 60 70 80 80With desuperheater kg 8,5 8,5 17 17 19 19 23 23 23With one pump kg 45 45 45 55 55 55 65 65 65With two pumps kg 95 95 95 115 115 115 140 140 140DimensionsLength mm 4.000 4.000 3.500 3.500 3.500 3.500 4.550 4.550 4.550Width mm 1.100 1.100 2.150 2.150 2.150 2.150 2.150 2.150 2.150Height mm 2.600 2.600 2.600 2.600 2.600 2.600 2.600 2.600 2.600Acoustical dataSound power level4 dB(A) 90 90 92 92 93 93 94 95 95Sound pressure level 10 m5 dB(A) 47 47 50 50 51 51 53 54 54

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard. 2 Data refers to 45°C leaving warm water temperature and 7°C ambient coil air temperature with 87% R.H., according EN14511 standard. 3 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard.4 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard. 5 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape. * High Efficiency Units (EC) with inverter fans. ** HPF Units with high static pressure fans.

Page 111: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Air cooled Chiller & Heat Pump | 109

Air Cooled Chiller &

heAt PumPTechnical feature

SyScroll 140-360 Air Evo HP L (STD-EC) 140 170 200 230 260 280 300 330 360Nominal cooling capacity1 kW 132,9 149,3 176,9 207,2 236,9 253,3 279,4 299,1 330,1Input power1 kW 45,2 55,3 61,2 73,7 83,7 91,4 99,1 103,1 117,5EER1 2,94 2,70 2,89 2,81 2,83 2,77 2,82 2,90 2,81Energy efficiency class B C C C C C C C CESEER 3,59 3,55 3,67 3,78 3,76 3,72 3,67 3,67 3,72EER* 2,98 2,73 2,93 2,85 2,87 2,81 2,86 2,94 2,84Energy efficiency class* B C B C C C C B CESEER* 3,69 3,66 3,78 3,91 3,89 3,85 3,78 3,75 3,83Nominal heating capacity2 kW 141,0 162,1 193,7 223,7 255,6 272,3 299,4 320,8 353,9Input power2 kW 43,5 50,3 60,0 69,0 79,4 84,8 92,7 99,6 109,9COP2 3,24 3,22 3,23 3,24 3,22 3,21 3,23 3,22 3,22Energy efficiency class A A A A A A A A ANominal heating capacity3 kW 144,2 165,8 199,8 227,8 260,8 277,3 303,8 326,4 359,2Input power3 kW 35,8 42,2 50,5 56,5 65,2 69,8 75,2 81,0 89,8COP3 4,03 3,93 3,96 4,03 4,00 3,97 4,04 4,03 4,00COP* 3,32 3,30 3,32 3,32 3,31 3,29 3,31 3,31 3,30

Total capacity steps % 25-50-75-100

25-50-75-100

21-43-71-100

19-38-69-100

17-39-67-100

16-37-68-100

24-48-71-100

23-50-73-100

25-50-75-100

RefrigerantType HFC 410ANumber of refrigerant circuits 2 2 2 2 2 2 2 2 2CompressorQty 4 4 4 4 4 4 4 4 4Type Scroll EvaporatorQty 1 1 1 2 2 2 1 1 1Type PlateWater flow cooling m3/h 22,9 25,8 30,5 35,7 40,9 43,7 48,2 51,6 57,0Water pressure drop cooling kPa 23 29 33 28 28 33 25 28 34Water flow heating2 m3/h 24,2 27,8 33,2 38,4 43,8 46,7 51,4 55,0 60,7Water pressure drop heating2 kPa 26 34 39 33 33 37 28 32 39Water flow heating3 m3/h 24,7 28,4 34,2 39,0 44,7 47,5 52,1 56,0 61,6Water pressure drop heating3 kPa 27 36 41 34 34 39 29 33 40Water volume l 11,4 11,4 13 21,1 23,4 23,4 32,4 32,4 32,4Antifreeze heater W 130 130 130 130+130 130+130 130+130 130 130 130Air cooled condenserQty 2 2 5 5 6 6 7 8 8Total coil face area per coil m2 4,6 4,6 2,4 2,4 2,4 2,4 2,4 2,4 2,4FanQty 3 3 5 5 6 6 7 8 8Nominal speed rpm 700 700 700 700 700 700 700 700 700Total airflow m3/h 55.000 55.000 92.500 92.500 111.000 111.000 129.500 148.000 148.000Total input power kW 3,6 3,6 6,0 6,0 7,2 7,2 8,4 9,6 9,6Water Connections (Evaporator)Type Male GAS ThreadedInlet diameter inch 2”1/2 2”1/2 2”1/2 3” 3” 3” 3” 3” 3”Outlet diameter inch 2”1/2 2”1/2 2”1/2 3” 3” 3” 3” 3” 3”Water Connections (Desuperheater)Type Male GAS ThreadedInlet diameter inch 1” 1” 1” 1” 1” 1” 1” 1” 1”Outlet diameter inch 1” 1” 1” 1” 1” 1” 1” 1” 1”WeightShipping kg 1.294 1.337 1.843 1.967 2.188 2.198 2.767 2.860 2.870Operating kg 1.312 1.355 1.858 1.993 2.216 2.226 2.806 2.899 2.909Additional weightEC version kg 30 30 50 50 60 60 70 80 80With desuperheater kg 8,5 8,5 17 17 19 19 23 23 23With one pump kg 45 45 45 55 55 55 65 65 65With two pumps kg 95 95 95 115 115 115 140 140 140DimensionsLength mm 4.000 4.000 3.500 3.500 3.500 3.500 4.550 4.550 4.550Width mm 1.100 1.100 2.150 2.150 2.150 2.150 2.150 2.150 2.150Height mm 2.600 2.600 2.600 2.600 2.600 2.600 2.600 2.600 2.600Acoustical dataSound power level4 dB(A) 85 85 87 87 88 88 89 90 90Sound pressure level 10 m5 dB(A) 58 58 60 60 61 61 62 63 63

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard. 2 Data refers to 45°C leaving warm water temperature and 7°C ambient coil air temperature with 87% R.H., according EN14511 standard. 3 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard.4 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard. 5 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape. * High Efficiency Units (EC) with inverter fans.

Page 112: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Air cooled Chiller & Heat Pump110

Technical feature

SyScroll 140-360 Air Evo HP S (STD-EC) 140 170 200 230 260 280 300 330 360Nominal cooling capacity1 kW 125,9 140,3 168,5 194,7 224,0 238,5 263,3 283,5 310,5Input power1 kW 47,2 57,7 63,4 77,6 88,2 96,6 104,5 108,2 124,2EER1 2,67 2,43 2,66 2,51 2,54 2,47 2,52 2,62 2,50Energy efficiency class D D D D D D D D DESEER 3,66 3,64 3,75 3,85 3,82 3,80 3,75 3,71 3,80EER* 2,71 2,45 2,70 2,54 2,58 2,50 2,55 2,66 2,53Energy efficiency class* C D C D D D D D DESEER* 3,77 3,75 3,86 3,99 3,95 3,93 3,86 3,79 3,91Nominal heating capacity2 kW 138,5 159,5 189,8 219,8 250,8 267,1 294,7 315,0 348,9Input power2 kW 42,4 48,9 58,0 67,2 77,2 82,4 90,4 96,9 107,4COP2 3,27 3,26 3,27 3,27 3,25 3,24 3,26 3,25 3,25Energy efficiency class A A A A A A A A ANominal heating capacity3 kW 141,3 162,7 195,3 223,3 255,3 271,3 298,3 319,7 353,2Input power3 kW 34,9 41,1 49,1 55,1 63,5 67,8 73,5 78,9 87,6COP3 4,05 3,96 3,98 4,05 4,02 4,00 4,06 4,05 4,03

Total capacity steps % 25-50-75-100

25-50-75-100

21-43-71-100

19-38-69-100

17-39-67-100

16-37-68-100

24-48-71-100

23-50-73-100

25-50-75-100

RefrigerantType HFC 410ANumber of refrigerant circuits 2 2 2 2 2 2 2 2 2CompressorQty 4 4 4 4 4 4 4 4 4Type Scroll EvaporatorQty 1 1 1 2 2 2 1 1 1Type PlateWater flow cooling m3/h 21,7 24,2 29,1 33,6 38,6 41,1 45,4 48,9 53,6Water pressure drop cooling kPa 21 26 30 25 25 29 22 25 30,3Water flow heating2 m3/h 23,8 27,3 32,5 37,7 43,0 45,8 50,6 54,0 59,8Water pressure drop heating2 kPa 25 33 37 32 32 36 27 31 38Water flow heating3 m3/h 24,2 27,9 33,5 38,3 43,8 46,5 51,2 54,8 60,5Water pressure drop heating3 kPa 26 34 39 33 33 37 28 32 39Water volume l 11,4 11,4 13 21,1 23,4 23,4 32,4 32,4 32,4Antifreeze heater W 130 130 130 130+130 130+130 130+130 130 130 130Air cooled condenserQty 2 2 5 5 6 6 7 8 8Total coil face area per coil m2 4,6 4,6 2,4 2,4 2,4 2,4 2,4 2,4 2,4FanQty 3 3 5 5 6 6 7 8 8Nominal speed rpm 550 550 550 550 550 550 550 550 550Total airflow m3/h 44.000 44.000 72.500 72.500 87.000 87.000 101.500 116.000 116.000Total input power kW 2,7 2,7 4,5 4,5 5,4 5,4 6,3 7,2 7,2Water Connections (Evaporator)Type Male GAS ThreadedInlet diameter inch 2”1/2 2”1/2 2”1/2 3” 3” 3” 3” 3” 3”Outlet diameter inch 2”1/2 2”1/2 2”1/2 3” 3” 3” 3” 3” 3”Water Connections (Desuperheater)Type Male GAS ThreadedInlet diameter inch 1” 1” 1” 1” 1” 1” 1” 1” 1”Outlet diameter inch 1” 1” 1” 1” 1” 1” 1” 1” 1”WeightShipping kg 1.299 1.342 1.848 1.972 2.193 2.203 2.772 2.865 2.875Operating kg 1.317 1.360 1.863 1.998 2.221 2.231 2.811 2.904 2.914Additional weightEC version kg 30 30 50 50 60 60 70 80 80With desuperheater kg 8,5 8,5 17 17 19 19 23 23 23With one pump kg 45 45 45 55 55 55 65 65 65With two pumps kg 95 95 95 115 115 115 140 140 140DimensionsLength mm 4.000 4.000 3.500 3.500 3.500 3.500 4.550 4.550 4.550Width mm 1.100 1.100 2.150 2.150 2.150 2.150 2.150 2.150 2.150Height mm 2.600 2.600 2.600 2.600 2.600 2.600 2.600 2.600 2.600Acoustical dataSound power level4 dB(A) 79 79 82 82 83 83 85 86 86Sound pressure level 10 m5 dB(A) 53 53 55 55 56 56 57 58 58

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard. 2 Data refers to 45°C leaving warm water temperature and 7°C ambient coil air temperature with 87% R.H., according EN14511 standard. 3 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard.4 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard. 5 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape. * High Efficiency Units (EC) with inverter fans.

Page 113: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Air cooled Chiller & Heat Pump | 111

Air Cooled Chiller &

heAt PumPTechnical feature

SyScroll 140-360 Air Evo HP HT 140 170 200 230 260 280 300 330 360Nominal cooling capacity1 kW 137,9 156,0 182,5 215,5 245,8 263,4 290,3 309,8 343,4Input power3 kW 39,0 48,4 52,3 63,2 71,9 78,6 84,9 88,0 101,0EER 2,92 2,75 2,77 2,80 2,78 2,77 2,80 2,82 2,79Energy efficiency class B C C C C C C C CESEER 3,45 3,38 3,53 3,63 3,65 3,58 3,53 3,60 3,58Nominal heating capacity2 kW 147,0 168,5 202,8 232,3 266,0 283,7 309,8 331,5 366,5Input power3 kW 39,2 46,0 52,8 61,8 70,7 76,1 82,3 87,1 97,8COP 3,11 3,12 3,07 3,10 3,07 3,08 3,08 3,06 3,08Energy efficiency class B B B B B B B B B

Total capacity steps % 25-50-75-100

25-50-75-100

21-43-71-100

19-38-69-100

17-39-67-100

16-37-68-100

24-48-71-100

23-50-73-100

25-50-75-100

RefrigerantType HFC 410ANumber of refrigerant circuits 2 2 2 2 2 2 2 2 2CompressorQty 4 4 4 4 4 4 4 4 4Type Scroll EvaporatorQty 1 1 1 2 2 2 1 1 1Type PlateWater flow cooling m3/h 23,8 26,9 31,5 37,2 42,4 45,5 50,1 53,4 59,3Water pressure drop cooling kPa 25 32 35 31 31 35 26 30 37Water flow heating2 m3/h 25,2 28,9 34,7 39,8 45,6 48,6 53,1 56,8 62,8Water pressure drop heating2 kPa 28 37 42 35 35 40 30 34 42Water flow heating6 m3/h 25,9 29,7 36,0 40,8 46,8 49,8 54,2 58,1 64,1Water pressure drop heating6 kPa 30 39 45 37 37 42 31 36 43Water volume l 11,4 11,4 13 21,1 23,4 23,4 32,4 32,4 32,4Antifreeze Heater W 130 130 130 130+130 130+130 130+130 130 130 130Air cooled condenserQty 5 5 5 6 6 6 7 8 8Total coil face area per coil m2 12 12 12 14,4 14,4 14,4 16,8 19,2 19,2FanQty 3 3 5 5 6 6 7 8 8Nominal speed rpm 1.100 1.100 1.100 1.100 1.100 1.100 1.100 1.100 1.100Total airflow m3/h 80.500 80.500 132.500 132.500 159.000 159.000 185.500 212.000 212.000Total input power* kW 7,8 7,8 13,0 13,0 15,6 15,6 18,2 20,8 20,8Water Connections (Evaporator)Type Male GAS ThreadedInlet diameter inch 2”1/2 2”1/2 2”1/2 3” 3” 3” 3” 3” 3”Outlet diameter inch 2”1/2 2”1/2 2”1/2 3” 3” 3” 3” 3” 3”Water Connections (Desuperheater)Type Male GAS ThreadedInlet diameter inch 1” 1” 1” 1” 1” 1” 1” 1” 1”Outlet diameter inch 1” 1” 1” 1” 1” 1” 1” 1” 1”WeightShipping kg 1.324 1.367 1.893 2.017 2.248 2.258 2.837 2.940 2.950Operating kg 1.342 1.385 1.908 2.043 2.276 2.286 2.876 2.979 2.989Additional weightDesuperheater versions kg 8,5 8,5 17 17 19 19 23 23 23With one pump kg 45 45 45 55 55 55 65 65 65With two pumps kg 95 95 95 115 115 115 140 140 140DimensionsLength mm 4.000 4.000 3.500 3.500 3.500 3.500 4.550 4.550 4.550Width mm 1.100 1.100 2.150 2.150 2.150 2.150 2.150 2.150 2.150Height mm 2.600 2.600 2.600 2.600 2.600 2.600 2.600 2.600 2.600Acoustical dataSound power level4 dB(A) 92 92 94 94 96 96 97 98 98Sound pressure level 10 m5 dB(A) 60 60 62 62 64 64 65 66 66

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature.2 Data refers to 45°C leaving warm water temperature and 7°C ambient coil air temperature with 87% R.H., according EN14511 standard. 3 Input power (only compressors). 4 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard. 5 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape. * High Efficiency Units (EC) with inverter fans.

Page 114: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Air cooled Chiller & Heat Pump112

Air Cooled Heat PumpSyScroll 240-660 Air HP

Technical feature 10 sizes Cooling capacity from 216,5 to 580,6 kW Heating capacity from 255,9 to 679,1 kW Fans versions:

STD (Standard) HT (High Temperature) HPF (High Pressure Fans) Acoustic versions:

- (Basic Low Noise) L (Low Noise) S (Super Low Noise) Two refrigerant circuits 3/4/5/6 Scroll compressors Electronic expansion valve

Accessories and options Automatic circuit breaker BMS interface Coils treatments Compressors acoustic box (standard) Compressors jackets (standard as Super Low Noise) Desuperheater Fan speed control (standard as Super Low Noise version) Hydrokit with 1 or 2 pumps with or without buffer tank Mechanical gauges Overload protection for compressors Power factor corrector capacitors Sequence phases control (standard) Softstarter Unit protection grilles Water differential pressure switch (standard) Water filter Water flow switch

217-581 kW

Plate

Air cooled Scroll

256-679 kW 410A

Page 115: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Air cooled Chiller & Heat Pump | 113

Air Cooled Chiller &

heAt PumP

* For Liquid outlet temperature <0 °C provide Brine Version (available for CO; on request for HP).1 Table shows minimum water / brine volume of system (about 3 lt/kW).2 Voltage 400V +/- 10%.

SyScroll 420-660 Air HP420 470 540 590 660

Min Max Min Max Min Max Min Max Min Max

Chilled liquid

Liquid outlettemperature

Water °C +6 to +18Water with glycol* °C -10 to +6ΔT K 3 to 7

Maximum operating pressure bar 6

Ambient air

Air enteringtemperatureCooling

- °C +5 to +42 +5 to +42 +5 to +42 +5 to +42 +5 to +42L °C +5 to +40 +5 to +40 +5 to +40 +5 to +40 +5 to +40S °C -14 to +40 -14 to +40 -14 to +40 -14 to +40 -14 to +40HT-HPF °C -18 to +44 -18 to +44 -18 to +44 -18 to +44 -18 to +44

Externalstatic pressure

Standard fans Pa 0High pressure fans Pa < 120

Recommended system chilled water volume1 l 1.260 1.128 1.296 1.180 1.320Minimum capacity step % 25 24 20 14 17Power supply voltage2 V 400 V / 3 Ø / 50 Hz (nominal)

SyScroll 240-360 Air HP240 270 290 320 360

Min Max Min Max Min Max Min Max Min Max

Chilled liquid

Liquid outlettemperature

Water °C +6 to +18Water with glycol* °C -10 to +6ΔT K 3 to 7

Maximum operating pressure bar 6

Ambient air

Air enteringtemperatureCooling

- °C +5 to +42 +5 to +42 +5 to +42 +5 to +42 +5 to +42L °C +5 to +40 +5 to +40 +5 to +40 +5 to +40 +5 to +40S °C -14 to +40 -14 to +40 -14 to +40 -14 to +40 -14 to +40HT-HPF °C -18 to +44 -18 to +44 -18 to +44 -18 to +44 -18 to +44

Externalstatic pressure

Standard fans Pa 0High pressure fans Pa < 120

Recommended system chilled water volume1 l 960 1.080 1.160 1.280 1.080Minimum capacity step % 31 33 30 27 23Power supply voltage2 V 400 V / 3 Ø / 50 Hz (nominal)

Operating limit (to be confirmed following selection software issue)

-20 -15 -10

-5 0 5

10 15 20 25 30 35 40 45 50

-12 -10 -8 -6 -4 -2 0 2 4 6 8 10 12 14 16 18

OAT

(°C)

LWT (°C)

Water

Water + FSC

Brine Version* +Water + Glycol

Brine Version* +Water + Glycol +

FSC

Water +Glycol

Water +Glycol + FSC

- Version

-20 -15 -10

-5 0 5

10 15 20 25 30 35 40 45 50

-12 -10 -8 -6 -4 -2 0 2 4 6 8 10 12 14 16 18

OAT

(°C)

LWT (°C)

Water

Water + FSC

Brine Version* +Water + Glycol

Brine Version* +Water + Glycol

Water +Glycol

Water +Glycol + FSC

L Version

-20 -15 -10

-5 0 5

10 15 20 25 30 35 40 45 50

-12 -10 -8 -6 -4 -2 0 2 4 6 8 10 12 14 16 18

OAT

(°C)

LWT (°C)

WaterBrine Version* +Water + Glycol

Water +Glycol

S Version

-20 -15 -10

-5 0 5

10 15 20 25 30 35 40 45 50 55

-12 -10 -8 -6 -4 -2 0 2 4 6 8 10 12 14 16 18

OAT

(°C)

LWT (°C)

WaterBrine Version* +Water + Glycol

Water +Glycol

HT-HPF Version

Page 116: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Air cooled Chiller & Heat Pump114

Operating limit - Heating (to be confirmed following selection software issue)

1 Table shows minimum water / brine volume of system (about 3 lt/kW).2 Voltage 400V +/- 10%.

SyScroll 420-660 Air HP420 470 540 590 660

Min Max Min Max Min Max Min Max Min Max

Warmed liquid

Liquid outlettemperature

Water °C +20 to +52Temperature spread K 3 to 7

Maximum operating pressure bar 6

Ambient air

Air enteringtemperature heating

- / L / S °C 10 to +20 -10 to +20 -10 to +20 -10 to +20 -10 to +20

HT °C -12 to +20 -12 to +20 -12 to +20 -12 to +20 -12 to +20

Externalstatic pressure

Standard fans Pa 0High pressure fans Pa < 120

Recommended system chilled water volume1 l 1.260 1.410 1.620 1.770 1.980Minimum capacity step % 25 24 20 14 17Power supply voltage2 V 400 V / 3 Ø / 50 Hz (nominal)

SyScroll 240-360 Air HP240 270 290 320 360

Min Max Min Max Min Max Min Max Min Max

Warmed liquid

Liquid outlettemperature

Water °C +20 to +52Temperature spread K 3 to 7

Maximum operating pressure bar 6

Ambient air

Air enteringtemperature heating

- / L / S °C -10 to +20 -10 to +20 -10 to +20 -10 to +20 -10 to +20

HT °C -12 to +20 -12 to +20 -12 to +20 -12 to +20 -12 to +20

Externalstatic pressure

Standard fans Pa 0High pressure fans Pa < 120

Recommended system chilled water volume1 l 720 810 870 960 1.080Minimum capacity step % 31 33 30 27 23Power supply voltage2 V 400 V / 3 Ø / 50 Hz (nominal)

-20

-15

-10

-5

0

5

10

15

20

25

15 20 25 30 35 40 45 50 55 60

OAT

(°C)

LWT (°C)

HT Version

Heating mode (Cooling mode see page 43)

Page 117: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Air cooled Chiller & Heat Pump | 115

Air Cooled Chiller &

heAt PumP

SyScroll 240-660 Air HP (STD-EC-HPF) 240 270 290 320 360 420 470 540 590 660Nominal cooling capacity1 kW 216,5 251,6 263,8 287,1 330,0 380,7 435,1 481,9 530,7 580,6Input power1 kW 85,5 100,5 105,2 113,9 131,3 151,7 169,1 189,9 207,3 228,3EER1 2,53 2,50 2,51 2,52 2,51 2,51 2,57 2,54 2,56 2,54Energy efficiency class D D D D D D D D D DESEER 3,55 3,43 3,52 3,66 3,66 3,79 3,80 3,66 3,74 3,82EER* 2,56 2,53 2,54 2,55 2,54 2,54 2,60 2,56 2,59 2,57ESEER* 3,63 3,50 3,60 3,74 3,74 3,88 3,89 3,74 3,81 3,90EER** 2,41 2,40 2,38 2,41 2,40 2,40 2,46 2,42 2,44 2,43ESEER** 3,21 3,16 3,19 3,32 3,31 3,43 3,45 3,35 3,41 3,58Nominal heating capacity2 kW 255,9 289,1 313,3 333,0 382,4 444,0 491,5 556,4 605,0 679,1Input power2 kW 92,7 106,8 117 117,4 136,2 159,7 170,5 191,2 209,2 231,1COP2 2,76 2,71 2,68 2,84 2,81 2,78 2,88 2,91 2,89 2,94Energy efficiency class D D D C C D C C C CCOP* 2,79 2,73 2,71 2,87 2,84 2,81 2,91 2,94 2,92 2,97COP** 2,63 2,60 2,56 2,71 2,68 2,66 2,75 2,78 2,76 2,81

Total capacity steps % 31-62-100

33-67-100

30-60-100

27-64-100

23-46-69-100

25-50-75-100

24-47-65-82-

100

20-40-60-800-

100

14-29-43-62-81-100

17-33-50-67-83-100

RefrigerantType HFC 410ANumber of refrigerant circuits 2 2 2 2 2 2 2 2 2 2CompressorQty 3 3 3 3 4 4 5 5 6 6Type Scroll EvaporatorQty 1 1 1 2 2 2 1 1 1 1Type PlateWater flow cooling m3/h 37,4 43,5 45,6 49,5 57,0 65,8 75,1 83,2 91,6 100,3Water pressure drop cooling kPa 42 55 61 29 38 50 38 46 44 53Water flow heating2 m3/h 43,8 49,4 53,5 57,1 65,5 76,0 84,2 95,3 103,6 116,2Water pressure drop heating2 kPa 56 71 83 38 49 65 48 60 56 70Water volume l 14 14 14 24 24 24 32 32 39 39Antifreeze heater W 130 130 130 130 130 130 130,0 130 130 130Air cooled condenserQty 5 5 6 6 7 8 9 10 11 12Total coil face area per coil m2 2,4 2,4 2,4 2,4 2,4 2,4 2,4 2,4 2,4 2,4FanQty 5 5 6 6 7 8 9 10 11 12Nominal speed rpm 900 900 900 900 900 900 900 900 900 900Total airflow m3/h 107.500 107.500 129.000 129.000 150.500 172.000 193.500 215.000 236.500 258.000Total input power kW 8,5 8,5 10,2 10,2 11,9 13,6 15,3 17,0 18,7 20,4Total input power* kW 7,5 7,5 9,0 9,0 10,5 12,0 13,5 15,0 16,5 18,0Total input power** kW 13,0 13,0 15,6 15,6 18,2 20,8 23,4 26,0 28,6 31,2External static pressure Pa 0 or 120 Pa**

Water Connections (Evaporator)Type Male GAS Threaded VictaulicInlet diameter inch 3” 3” 3” 3” 4” 4” 4” 4” 5” 5”Outlet diameter inch 3” 3” 3” 3” 4” 4” 4” 4” 5” 5”Water Connections (Desuperheater)Type Male GAS ThreadedInlet diameter/Outlet diameter inch 1”/1”WeightShipping kg 1.934 1.935 2.041 2.098 2.509 2.634 3.151 3.278 3.718 3.829Operating kg 1.948 1.949 2.055 2.122 2.534 2.659 3.189 3.316 3.762 3.873Additional weightHT/HPF versions kg 50 50 60 60 70 80 90 100 110 120With desuperheater kg 49 49 49 49 62 62 73 73 83 83DimensionsLength mm 3.500 3.500 3.500 3.500 4.550 4.550 5.600 5.600 6.650 6.650Width mm 2.150 2.150 2.150 2.150 2.150 2.150 2.150 2.150 2.150 2.150Height mm 2.600 2.600 2.600 2.600 2.600 2.600 2.600 2.600 2.600 2.600Acoustical dataSound power level3 dB(A) 93 93 94 94 94 95 95 96 96 97Sound pressure level 10 m4 dB(A) 61 61 62 62 62 63 63 64 63 64

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard.2 Data refers to 45°C leaving warm water temperature and 7°C ambient coil air temperature with 87% R.H., according EN14511 standard.3 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.4 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.* Unità alta temperatura (HT) con ventilatori inverter.** HPF Units with high static pressure fans.

Technical feature

Page 118: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Air cooled Chiller & Heat Pump116

Technical feature

SyScroll 240-660 Air HP L 240 270 290 320 360 420 470 540 590 660Nominal cooling capacity1 kW 204,9 236,3 249,9 269,8 311,1 358,4 409,7 453,2 499,5 545,9Input power1 kW 88,6 105,2 109,0 118,7 137,0 158,0 176,3 197,8 216,1 237,8EER1 2,31 2,24 2,29 2,27 2,27 2,27 2,32 2,29 2,31 2,30Energy efficiency class E F F F F F E F E FESEER 3,50 3,29 3,51 3,56 3,66 3,80 3,77 3,60 3,82 3,79Nominal heating capacity2 kW 253,0 285,5 309,7 328,9 377,7 438,6 485,4 539,8 597,5 670,7Input power2 kW 90,1 104,1 113,6 114,1 132,3 155,1 165,7 188 202,7 224COP2 2,81 2,74 2,72 2,88 2,86 2,83 2,93 2,87 2,95 2,99Energy efficiency class C D D C C C C C C C

Total capacity steps % 31-62-100

33-67-100

30-60-100

27-64-100

23-46-69-100

25-50-75-100

24-47-65-82-

100

20-40-60-800-

100

14-29-43-62-81-100

17-33-50-67-83-100

RefrigerantType HFC 410ANumber of refrigerant circuits 2 2 2 2 2 2 2 2 2 2CompressorQty 3 3 3 3 4 4 5 5 6 6Type Scroll EvaporatorQty 1 1 1 2 2 2 1 1 1 1Type PlateWater flow cooling m3/h 35,4 40,8 43,2 46,5 53,7 61,9 70,7 78,2 86,2 94,2Water pressure drop cooling kPa 37 49 55 26 34 44 34 41 39 47Water flow heating m3/h 43,3 48,8 52,9 56,4 64,7 75,1 83,2 92,4 102,4 114,8Water pressure drop heating kPa 55 69 81 37 48 64 46 57 55 68Water volume l 14 14 14 24 24 24 32 32 39 39Antifreeze heater W 130 130 130 130 130 130 130 130 130 130Air cooled condenserQty 5 5 6 6 7 8 9 10 11 12Total coil face area per coil m2 2,4 2,4 2,4 2,4 2,4 2,4 2,4 2,4 2,4 2,4FanQty 5 5 6 6 7 8 9 10 11 12Nominal speed rpm 700 700 700 700 700 700 700 700 700 700Total airflow m3/h 85.000 85.000 102.000 102.000 119.000 136.000 153.000 170.000 187.000 204.000Total input power kW 6,0 6,0 7,2 7,2 8,4 9,6 10,8 12,0 13,2 14,4Water Connections (Evaporator)Type Male GAS Threaded VictaulicInlet diameter inch 3” 3” 3” 3” 4” 4” 4” 4” 5” 5”Outlet diameter inch 3” 3” 3” 3” 4” 4” 4” 4” 5” 5”Water Connections (Desuperheater)Type Male GAS ThreadedInlet diameter/Outlet diameter inch 1”/1”WeightShipping kg 1.934 1.935 2.041 2.098 2.509 2.634 3.151 3.278 3.718 3.829Operating kg 1.948 1.949 2.055 2.122 2.534 2.659 3.189 3.316 3.762 3.873Additional weightWith desuperheater kg 49 49 49 49 62 62 73 73 83 83DimensionsLength mm 3.500 3.500 3.500 3.500 4.550 4.550 5.600 5.600 6.650 6.650Width mm 2.150 2.150 2.150 2.150 2.150 2.150 2.150 2.150 2.150 2.150Height mm 2.600 2.600 2.600 2.600 2.600 2.600 2.600 2.600 2.600 2.600Acoustical dataSound power level3 dB(A) 88 88 89 89 90 91 91 91 92 92Sound pressure level 10 m4 dB(A) 56 56 57 57 58 59 59 59 59 59

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard.2 Data refers to 45°C leaving warm water temperature and 7°C ambient coil air temperature with 87% R.H., according EN14511 standard.3 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.4 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.

Page 119: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Air cooled Chiller & Heat Pump | 117

Air Cooled Chiller &

heAt PumPTechnical feature

SyScroll 240-660 Air HP S 240 270 290 320 360 420 470 540 590 660Nominal cooling capacity1 kW 186,8 212,3 228,4 243,4 281,5 324,0 370,5 409,0 451,5 492,5Input power1 kW 96,3 115,5 117,9 129,4 149,7 172,0 192,4 215,4 235,6 258,9EER1 1,94 1,84 1,94 1,88 1,88 1,88 1,93 1,90 1,92 1,90Energy efficiency class G G G G G G G G G GESEER 3,28 3,12 3,30 3,38 3,62 3,60 3,61 3,70 3,76 3,64Nominal heating capacity2 kW 249,0 280,7 304,8 323,3 371,4 431,3 477,3 540,4 587,5 659,5Input power2 kW 87,5 101 110 111,1 128,8 150,6 161,4 179,9 197,4 219,8COP2 2,85 2,78 2,77 2,91 2,88 2,86 2,96 3,00 2,98 3,00Classe energetica C D D C C C C B C B

Total capacity steps % 31-62-100

33-67-100

30-60-100

27-64-100

23-46-69-100

25-50-75-100

24-47-65-82-

100

20-40-60-800-

100

14-29-43-62-81-100

17-33-50-67-83-100

RefrigerantType HFC 410ANumber of refrigerant circuits 2 2 2 2 2 2 2 2 2 2CompressorQty 3 3 3 3 4 4 5 5 6 6Type Scroll EvaporatorQty 1 1 1 2 2 2 1 1 1 1Type PlateWater flow cooling m3/h 32,2 36,7 39,5 42,0 48,6 55,9 63,9 70,6 77,9 85,0Water pressure drop cooling kPa 31 40 46 21 28 36 28 34 32 38Water flow heating m3/h 42,6 48,0 52,1 55,4 63,6 73,8 81,8 92,6 100,6 112,9Water pressure drop heating kPa 53 67 79 36 47 62 45 57 53 66Water volume l 14 14 14 24 24 24 32 32 39 39Antifreeze heater W 130 130 130 130 130 130 130 130 130 130Air cooled condenserQty 5 5 6 6 7 8 9 10 11 12Total coil face area per coil m2 2,4 2,4 2,4 2,4 2,4 2,4 2,4 2,4 2,4 2,4FanQty 5 5 6 6 7 8 9 10 11 12Nominal speed rpm 550 550 550 550 550 550 550 550 550 550Total airflow m3/h 67.500 67.500 81.000 81.000 94.500 108.000 121.500 135.000 148.500 162.000Total input power kW 4,5 4,5 5,4 5,4 6,3 7,2 8,1 9,0 9,9 10,8Water Connections (Evaporator)Type Male GAS Threaded VictaulicInlet diameter inch 3” 3” 3” 3” 4” 4” 4” 4” 5” 5”Outlet diameter inch 3” 3” 3” 3” 4” 4” 4” 4” 5” 5”Water Connections (Desuperheater)Type Male GAS ThreadedInlet diameter/Outlet diameter inch 1”/1”WeightShipping kg 1.934 1.935 2.041 2.098 2.509 2.634 3.151 3.278 3.718 3.829Operating kg 1.948 1.949 2.055 2.122 2.534 2.659 3.189 3.316 3.762 3.873Additional weightWith desuperheater kg 49 49 49 49 62 62 73 73 83 83DimensionsLength mm 3.500 3.500 3.500 3.500 4.550 4.550 5.600 5.600 6.650 6.650Width mm 2.150 2.150 2.150 2.150 2.150 2.150 2.150 2.150 2.150 2.150Height mm 2.600 2.600 2.600 2.600 2.600 2.600 2.600 2.600 2.600 2.600Acoustical dataSound power level3 dB(A) 85 86 87 87 88 88 89 89 90 90Sound pressure level 10 m4 dB(A) 53 54 55 55 56 56 57 57 57 57

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard.2 Data refers to 45°C leaving warm water temperature and 7°C ambient coil air temperature with 87% R.H., according EN14511 standard.3 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.4 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.

Page 120: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Air cooled Chiller & Heat Pump118

Technical feature 7 sizes Cooling capacity from 149,4 to 299,9 kW Heating capacity from 169,8 to 337,4 kW 3 versions:

STD (Standard) HT (High Temperature) HPF (High Pressure Fans) 3 acoustic versions:

BLN (Base Low Noise) LN (Low Noise) ELN (Extra Low Noise) Two refrigerant circuits Scroll compressors Microprocessor control Electronic expansion valve Inverter fans (Standard on HT) “Polar” version for extreme conditions (on request)

Accessories and options

Automatic circuit breaker BMS interface Coils treatments Compressors acoustic box (standard) Compressors jackets Desuperheater Fan speed control (-18°C) Hydrokit with 1 or 2 pumps with ot without buffer tank (500 lt)

( +1mt of lenght) Mechanical gauges Overload protection for compressors Power factor corrector capacitors Sequence phases control (standard) Sofstart Unit protection grilles Water differential pressure switch (standard) Water filter Water flow switch

Air Cooled Heat PumpVLH 604-1204

149-300 kW

Plate

Air cooled Scroll

170-337 kW 410A

Page 121: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Air cooled Chiller & Heat Pump | 119

Air Cooled Chiller &

heAt PumP

VLH 604-804604 704 804

Min Max Min Max Min Max

Leaving water temperature

Water °C from +6 to +15

Water + glycol °C from 0 to +15

Water with Glycol (Brine version) °C from -8 to +15

∆ T K from 3 to 8

Air temperature

BLN °C from -5 to +47 from -5 to +47 from 0 to +46

Cooling LN °C from -5 to +45 from -5 to +45 from 0 to +44

Cooling ELN °C from -18 to +41 from -18 to +41 from -18 to +40

Cooling HT/HSE °C from -18 to +49 from -18 to +49 from -18 to +48

Heating °C from -10 (-4 LN/ELN) to + 20

High pressure fansStandard fans Pa 0

Invert fans HPF Pa <120

Operating limit (to be confirmed following selection software issue)

VLH 904-1204904 1004 1104 1204

Min Max Min Max Min Max Min Max

Leaving water temperature

Water °C from +6 to +15

Water + glycol °C from 0 to +15

Water + Glycol (Brine version) °C from -8 to +15

∆ T K from 3 to 8

Air temperature

BLN °C from 0 to +47 from 0 to +46 from 0 to +45 from 0 to +45

Cooling LN °C from 0 to +45 from 0 to +44 from 0 to +42 from 0 to +42

Cooling ELN °C from -18 to +41 from -18 to +40 from -18 to +38 from -18 to +38

Cooling HT/HSE °C from -18 to +49 from -18 to +48 from -18 a +47 from -18 to +47

Heating °C from -10 (-4 LN/ELN) to + 20

Externalstatic pressure

Standard fans Pa 0

Invert fans HPF Pa <120

Page 122: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Air cooled Chiller & Heat Pump120

Technical feature

VLH STD/HPF 604-1204 BLN 604 704 804 904 1004 1104 1204Cooling capacity1 kW 149,4 173,2 197,1 226,4 246,3 273,1 299,9Power input1 kW 56,4 66,1 72,2 82,6 86,7 99,7 114,0EER1 2,65 2,62 2,73 2,74 2,84 2,74 2,63Energy efficiency class D D C C C C DESEER 3,38 3,41 3,43 3,45 3,57 3,46 3,41Heating capacity2 kW 169,8 200,1 223,2 254,7 270,8 302,1 337,4Power input2 kW 58,0 67,4 70,4 79,6 87,6 100,0 112,5COP2 2,93 2,97 3,17 3,20 3,09 3,02 3,00Energy efficiency class B B B A B B B

Part load steps % 28-57-78-100

20-50-70-100

25-50-75-100

28-50-78-100

25-50-75-100

23-50-73-100

25-50-75-100

RefrigerantType HFC 410ANumber of refrigerant circuits 2CompressorQty 4Type ScrollEvaporatorQty 1Type Plate exchanger AISI 316Water flow l/h 25.817 29.928 33.987 38.992 42.449 47.110 51.686Connection type Male GAS threadedInlet/outlet diameter inch 2½” 2½” 2½” 3” 3” 3” 3”CondenserQty 2Total coil face area per coil mm2 3,5 4,8 4,8 4,8 4,8 4,8 4,8FanQty 3 3 3 4 4 4 4Speed rpm/min 900 900 900 900 900 900 900Air flow m3/h 63.000 68.300 68.300 85.000 80.000 75.500 75.500Power input kW 5,7 5,7 5,7 7,6 7,6 7,6 7,6Static head pressure Pa from 0 to120*

WeightShipping kg 1.473 1.663 1.806 1.955 2.100 2.190 2.200Operating kg 1.485 1.675 1.820 1.980 2.125 2.215 2.225Additional weightsVersions HPF kg 30 30 30 40 40 40 40With desuperheater kg 20 20 30 30 30 30 30With one pump kg 50 85 85 90 90 95 95With two pumps kg 140 200 200 205 205 215 215With copper/copper coils kg 380 520 520 520 700 880 880DimensionsLength mm 3.300 4.300 4.300 4.300 4.300 4.300 4.300Width mm 1.100 1.100 1.100 1.100 1.100 1.100 1.100Height mm 2.300 2.300 2.300 2.300 2.300 2.300 2.300Acoustical dataSound power level3 dB(A) 91 91 91 92 92 93 93Sound pressure level4 dB(A) 59 59 59 60 60 61 61

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard.2 Data refers to 45°C leaving warm water temperature and 7°C ambient coil air temperature with 87% R.H., according EN14511 standard.3 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.4 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.* For version with High Pressure Fans (HPF).

Page 123: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Air cooled Chiller & Heat Pump | 121

Air Cooled Chiller &

heAt PumPTechnical feature

VLH STD 604-1204 LN 604 704 804 904 1004 1104 1204Cooling capacity1 kW 145,4 168,2 191,2 220,4 237,3 261,2 285,1Power input1 kW 56,8 66,2 73,3 83,8 88,5 102,8 119,8EER1 2,56 2,54 2,61 2,63 2,68 2,54 2,38Energy efficiency class D D D D D D EESEER 3,60 3,58 3,64 3,59 3,70 3,63 3,49Heating capacity2 kW 165,7 195,0 217,1 247,7 261,8 288,9 322,2Power input2 kW 56,0 65,2 68,3 76,9 84,7 97,0 109,2COP2 2,96 2,99 3,18 3,22 3,09 2,98 2,95Energy efficiency class C C B A B C C

Part load steps % 28-57- 78-100

20-50- 70-100

25-50- 75-100

28-50- 78-100

25-50- 75-100

23-50- 73-100

25-50- 75-100

RefrigerantType HFC 410ANumber of refrigerant circuits 2 2 2 2 2 2 2CompressorQty 4Type ScrollEvaporatorQty 1Type Plate exchanger AISI 316Water flow l/h 25.094 29.102 32.955 38.046 40.901 45.081 49.226Connection type Male GAS threadedInlet/outlet diameter inch 2½” 2½” 2½” 3” 3” 3” 3”CondenserQty 2Total coil face area per coil mm2 3,5 4,8 4,8 4,8 4,8 4,8 4,8FanQty 3 3 3 4 4 4 4Speed gir/min 700 700 700 700 700 700 700Air flow m3/h 47.300 52.200 52.200 63.700 58.800 54.900 54.900Power input kW 3,6 3,6 3,6 4,8 4,8 4,8 4,8Static head pressure Pa 0 WeightShipping kg 1.473 1.663 1.806 1.955 2.100 2.190 2.200Operating kg 1.485 1.675 1.820 1.980 2.125 2.215 2.225Additional weightsWith desuperheater kg 20 20 30 30 30 30 30With one pump kg 50 85 85 90 90 95 95With two pumps kg 140 200 200 205 205 215 215With copper/copper coils kg 380 520 520 520 700 880 880DimensionsLength mm 3.300 4.300 4.300 4.300 4.300 4.300 4.300Width mm 1.100 1.100 1.100 1.100 1.100 1.100 1.100Height mm 2.300 2.300 2.300 2.300 2.300 2.300 2.300Acoustical dataSound power level3 dB(A) 87 87 87 88 88 89 89Sound pressure level4 dB(A) 55 55 55 56 56 57 57

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard.2 Data refers to 45°C leaving warm water temperature and 7°C ambient coil air temperature with 87% R.H., according EN14511 standard.3 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.4 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.

Page 124: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Air cooled Chiller & Heat Pump122

Technical feature

VLH STD 604-1204 ELN 604 704 804 904 1004 1104 1204Cooling capacity1 kW 141,5 164,3 185,2 214,5 230,4 253,3 276,1Power input1 kW 58,0 69,0 76,2 86,1 90,7 106,9 124,9EER1 2,44 2,38 2,43 2,49 2,54 2,37 2,21Energy efficiency class E E E E D E FESEER 3,49 3,46 3,51 3,60 3,67 3,51 3,40Heating capacity2 kW 156,6 184,9 202,9 232,6 245,7 266,8 297,0Power input2 kW 55,0 64,9 67,0 75,8 83,9 95,0 108,0COP2 2,85 2,85 3,03 3,07 2,93 2,81 2,75Energy efficiency class C C B B B C CCOP HSE 2,95 2,95 3,13 3,19 3,04 2,90 2,83

Part load steps % 28-57- 78-100

20-50- 70-100

25-50- 75-100

28-50- 78-100

25-50- 75-100

23-50- 73-100

25-50- 75-100

RefrigerantType HFC 410ANumber of refrigerant circuits 2CompressorQty 4Type ScrollEvaporatorQty 1Type Plate exchanger AISI 316Water flow l/h 24.458 28.311 31.940 36.945 39.732 43.705 47.592Connection type Male GAS threadedInlet/outlet diameter inch 2½” 2½” 2½” 3” 3” 3” 3”CondenserQty 2Total coil face area per coil mm2 3,5 4,8 4,8 4,8 4,8 4,8 4,8FanQty 3 3 3 4 4 4 4Speed rpm/min 550 550 550 550 550 550 550Air flow m3/h 38.500 41.800 41.800 52.000 48.900 46.200 46.200Power input kW 3 3 3 4 4 4 4Static head pressure Pa 0WeightShipping kg 1.508 1.698 1.841 1.990 2.140 2.230 2.240Operating kg 1.520 1.710 1.855 2.015 2.165 2.255 2.265Additional weightsWith desuperheater kg 20 20 30 30 30 30 30With one pump kg 50 85 85 90 90 95 95With two pumps kg 140 200 200 205 205 215 215With copper/copper coils kg 380 520 520 520 700 880 880DimensionsLength mm 3.300 4.300 4.300 4.300 4.300 4.300 4.300Width mm 1.100 1.100 1.100 1.100 1.100 1.100 1.100Height mm 2.300 2.300 2.300 2.300 2.300 2.300 2.300Acoustical dataSound power level3 dB(A) 83 83 83 84 84 85 85Sound pressure level4 dB(A) 51 51 51 52 52 53 53

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard.2 Data refers to 45°C leaving warm water temperature and 7°C ambient coil air temperature with 87% R.H., according EN14511 standard.3 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.4 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.

Page 125: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Air cooled Chiller & Heat Pump | 123

Air Cooled Chiller &

heAt PumPTechnical feature

VLH 604-1204 HT 604 704 804 904 1004 1104 1204Cooling capacity1 kW 151,7 175,6 199,7 229,5 250,1 276,5 305,6Power input3 kW 49,2 58,4 64,4 73,2 76,8 89,9 102,8EER 2,69 2,69 2,80 2,77 2,88 2,77 2,71Energy efficiency class D D D D D D EHeating capacity2 kW 170,5 200,7 224,0 256,6 273,7 305,5 341,5Power input3 kW 51,3 60,6 63,5 71,4 79,3 91,4 103,5COP 2,91 2,97 3,18 3,17 3,07 3,01 3,01Energy efficiency class C C B A B C C

Part load steps % 28-57- 78-100

20-50- 70-100

25-50- 75-100

28-50- 78-100

25-50- 75-100

23-50- 73-100

25-50- 75-100

RefrigerantType HFC 410ANumber of refrigerant circuits 2CompressorQty 4Type ScrollEvaporatorQty 1Type Plate exchanger AISI 316Water flow l/h 26.092 30.203 34.348 39.474 43.017 47.558 52.563Connection type Male GAS threadedInlet/outlet diameter inch 2½” 2½” 2½” 3” 3” 3” 3”CondenserQty 2Total coil face area per coil mm2 3,5 4,8 4,8 4,8 4,8 4,8 4,8FanQty 3 3 3 4 4 4 4Speed rpm/min 1.110 1.110 1.110 1.110 1.110 1.110 1.110Air flow m3/h 71.800 76.200 76.200 95.800 91.200 87.600 87.600Power input kW 7,2 6,9 6,9 9,6 9,9 10 10Static head pressure Pa 0WeightShipping kg 1.503 1.693 1.836 1.995 2.140 2.230 2.240Operating kg 1.515 1.705 1.850 2.020 2.165 2.255 2.265Additional weightsWith desuperheater kg 20 20 30 30 30 30 30With one pump kg 50 85 85 90 90 95 95With two pumps kg 140 200 200 205 205 215 215With copper/copper coils kg 380 520 520 520 700 880 880DimensionsLength mm 3.300 4.300 4.300 4.300 4.300 4.300 4.300Width mm 1.100 1.100 1.100 1.100 1.100 1.100 1.100Height mm 2.300 2.300 2.300 2.300 2.300 2.300 2.300Acoustical dataSound power level4 dB(A) 99 99 99 100 100 100 100Sound pressure level5 dB(A) 67 67 67 68 68 68 68

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard. 2 Data refers to 45°C leaving warm water temperature and 7°C ambient coil air temperature with 87% R.H., according EN14511 standard.3 Input power (only compressors).4 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard. 5 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.

Page 126: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Air cooled Chiller & Heat Pump124

Technical feature 5 sizes Cooling capacity from 358,8 to 601,9 kW Heating capacity 420,0 to702,0 kW 4 versions:

STD (Standard) HSE (High Seasonal Efficiency) HT (High Temperature) HPF (High Pressure Fans)

3 acoustic versions: BLN (Basic Low Noise) LN (Low Noise) ELN (Extra Low Noise)

Two refrigerant circuits Scroll compressors Electronic expansion valve Inverter fans (Standard HSE and HT) “Polar” version for extreme conditions (on request)

Accessories and options Automatic circuit breaker BMS interface Coils treatments Compressors acoustic box (standard) Compressors jackets (standard ELN) Desuperheater Fan speed control (-18°C) Hydrokit with 1 or 2 pumps with or without buffer tank (750 or

1.000 liters size 2106-2406) Mechanical gauges Overload protection for compressors Power factor corrector capacitors Sequence phases control (standard) Sofstart Unit protection grilles Water differential pressure switch (standard) Water filter Water flow switch

Air Cooled Heat PumpAQWH 1404-2406

359-602 kW

Plate

Air cooled Scroll

420-702 kW 410A

Page 127: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Air cooled Chiller & Heat Pump | 125

Air Cooled Chiller &

heAt PumP

AQWH 1404-24061404 1604 1806 2106 2406

Min Max Min Max Min Max Min Max Min Max

Leavingwater temperature

Acqua °C from +6 to +15

Water + glicol °C from -8 to +15

∆ T К from 3 to 8

Leaving water temperature (heating) °C from 30 to 50

Air temperature

BLN °C from -5 to +44 from 0 to +44 from 0 to +44 from 0 to +44 from 0 to +44

LN °C from -5 to +42 from 0 to +42 from 0 to +42 from 0 to +42 from 0 to +42

ELN °C from -18 to +40 from -18 to +40 from -18 to +40 from -18 to +40 from -18 to +40

HT °C from -18 to +45 from -18 to +45 from -18 to +45 from -18 to +45 from -18 to +45

Heating °C from -10 (-4 LN/ELN) to +20

Heating (Polar Version) °C from -15 to +20

Externalstatic pressure

Standard fans Pa 0

Inverter fans SIF Pa < 120

Opearting limit (to be confirmed following selection software issue)

Page 128: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Air cooled Chiller & Heat Pump126

Technical feature

AQWH STD/HSE/HPF 1404-2406 BLN 1404 1604 1806 2106 2406Cooling capacity1 kW 358,8 400,6 470,4 534,8 601,9Power input1 kW 134,9 150,0 175,5 199,6 224,6EER1 2,66 2,67 2,68 2,68 2,68Energy Efficiency class D D D D DESEER 3,47 3,54 3,55 3,59 3,59EER HSE1 2,69 2,70 2,71 2,71 2,71Energy Efficiency class D C C C CESEER HSE1 3,57 3,69 3,73 3,79 3.73Heating capacity2 kW 420,0 470,1 548,3 627,2 702,0Power input2 kW 132,5 146,5 172,4 194,2 220,8Energy Efficiency class B A B A BCOP2 3,17 3,21 3,18 3,23 3,18Energy Efficiency class A A A A ACOP HSE2 3,21 3,24 3,22 3,26 3,22

Part load steps % 21-50-71-100

25-50-75-100

17-33-50-67-83-100

15-29-43-62-81-100

17-33-50-67-83-100

RefrigerantType HFC 410ANumber of refrigerant circuits 2CompressorQty 4 4 6 6 6Type ScrollEvaporatorQty 1Type Plate exchanger AISI 316Water flow l/h 61.950 69.092 81.210 92.371 103.532Connection type VictaulicInlet/outlet diameter inch 4” 4” 4” 4” 4”CondenserQty 4 4 4 4 4Total coil face area per coil mm2 4,4 4,4 5,6 6,7 6,7FanQty 8 8 10 10 12Speed rpm/min 880 880 880 880 880Air flow m3/h 181.000 181.000 200.000 214.500 242.000Power input kW 14,4 14,4 18,0 18,0 21,6Power input HSE kW 13,0 13,0 16,3 16,3 19,6Static head pressure Pa from 0 to 120**

WeightShipping kg 2.896 3.018 3.967 4.083 4.465Operating kg 2.931 3.056 4.007 4.123 4.507DimensionsLength mm 4.000 4.000 5.000 6.000 6.000Width mm 2.200 2.200 2.200 2.200 2.200Height mm 2.550 2.550 2.550 2.550 2.550Acoustical dataSound power level3 dB(A) 97 97 98 98 99Sound pressure level4 dB(A) 65 65 66 66 67

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard.2 Data refers to 45°C leaving warm water temperature and 7°C ambient coil air temperature with 87% R.H., according EN14511 standard.3 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.4 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.** HPF Units with high static pressure fans.

Page 129: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Air cooled Chiller & Heat Pump | 127

Air Cooled Chiller &

heAt PumPTechnical feature

AQWH STD/HSE 1404-2406 LN 1404 1604 1806 2106 2406Cooling capacity1 kW 346,8 386,7 455,5 518,0 582,0Power input1 kW 134,9 149,9 176,6 200,0 223,0EER1 2,57 2,58 2,58 2,59 2,61Energy Efficiency class D D D D DESEER 3,57 3,63 3,68 3,70 3,73EER HSE1 2,63 2,63 2,64 2,64 2,56Energy Efficiency class D D D D DESEER HSE1 3,74 3,85 3,94 3,95 3,84Heating capacity2 kW 397,7 445,8 519,0 593,8 665,4Power input2 kW 126,3 141,5 165,8 187,9 212,6COP2 3,15 3,15 3,13 3,16 3,13Energy Efficiency class B B B B BCOP HSE2 3,22 3,22 3,20 3,23 3,22Energy Efficiency class A A A A A

Part load steps % 21-50-71-100

25-50-75-100

17-33-50-67-83-100

15-29-43-62-81-100

17-33-50-67-83-100

RefrigerantType HFC 410ANumber of refrigerant circuits 2CompressorQty 4 4 6 6 6Type ScrollEvaporatorQty 1Type Plate exchanger AISI 316Water flow l/h 59.821 66.787 78.655 89.474 100.104Connection type VictaulicInlet/outlet diameter inch 4” 4” 4” 4” 4”CondenserQty 4Total coil face area per coil mm2 4,4 4,4 5,6 6,7 6,7FanQty 8 8 10 10 12Speed rpm/min 700 700 700 700 700Air flow m3/h 142.000 142.000 153.000 165.000 183.000Power input kW 9,6 9,6 12,0 12,0 14,4Power input HSE kW 6,6 6,6 8,2 8,2 9,8Static head pressure Pa 0WeightShipping kg 2.896 3.018 3.967 4.083 4.465Operating kg 2.931 3.056 4.007 4.123 4.507DimensionsLength mm 4.000 4.000 5.000 6.000 6.000Width mm 2.200 2.200 2.200 2.200 2.200Height mm 2.550 2.550 2.550 2.550 2.550Acoustical dataSound power level4 dB(A) 91 91 92 92 93Sound pressure level5 dB(A) 59 59 60 60 61

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard.2 Data refers to 45°C leaving warm water temperature and 7°C ambient coil air temperature with 87% R.H., according EN14511 standard.3 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.4 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.

Page 130: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Air cooled Chiller & Heat Pump128

Technical feature

AQWH STD/HSE 1404-2406 ELN 1404 1604 1806 2106 2406Cooling capacity1 kW 328,9 366,9 432,7 490,2 551,1Power input1 kW 143,0 158,8 187,3 211,3 237,5EER1 2,30 2,31 2,31 2,32 2,32Energy Efficiency class E E E E EESEER 3,28 3,38 3,48 3,49 3,49EER HSE1 2,42 2,42 2,42 2,42 2,42Energy Efficiency class E E E E EESEER HSE1 3,51 3,61 3,69 3,67 3,67Heating capacity2 kW 381,6 427,6 498,4 570,5 639,0Power input2 kW 126,36 140,2 165,58 187,66 200,3COP2 3,02 3,05 3,01 3,04 3,19Energy Efficiency class B B B B BCOP HSE2 3,20 3,21 3,17 3,19 3,03Energy Efficiency class A A B B B

Part load steps % 21-50-71-100

25-50-75-100

17-33-50-67-83-100

15-29-43-62-81-100

17-33-50-67-83-100

RefrigerantType HFC 410ANumber of refrigerant circuits 2CompressorQty 4 4 6 6 6Type ScrollEvaporatorQty 1Type Plate exchanger AISI 316Water flow l/h 56.794 63.244 74.579 84.675 94.789Connection type VictaulicInlet/outlet diameter inch 4” 4” 4” 4” 4”CondenserQty 4Total coil face area per coil mm2 4,4 4,4 5,6 6,7 6,7FanQty 8 8 10 10 12Speed rpm/min 550 550 550 550 550Air flow m3/h 112.000 112.000 120.000 130.000 144.000Power input kW 9,6 9,6 12,0 12,0 14,4Power input HSE kW 2,6 2,6 3,2 3,2 3,8Static head pressure Pa 0WeightShipping kg 2.896 3.018 3.967 4.083 4.465Operating kg 2.931 3.056 4.007 4.123 4.507DimensionsLength mm 4.000 4.000 5.000 6.000 6.000Width mm 2.200 2.200 2.200 2.200 2.200Height mm 2.550 2.550 2.550 2.550 2.550Acoustical dataSound power level3 dB(A) 88 88 89 89 90Sound pressure level4 dB(A) 56 56 57 57 58

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard.2 Data refers to 45°C leaving warm water temperature and 7°C ambient coil air temperature with 87% R.H., according EN14511 standard.3 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.4 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.

Page 131: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Air cooled Chiller & Heat Pump | 129

Air Cooled Chiller &

heAt PumPTechnical feature

AQWH 1404-2406 HT 1404 1604 1806 2106 2406Cooling capacity1 kW 363,8 405,7 477,0 542,3 608,0Power input3 kW 117,8 132,7 154,4 176,7 199,0EER 2,73 2,64 2,72 2,64 2,64Heating capacity2 kW 422,0 473,0 551,0 630,0 709,0Power input3 kW 114,8 128,7 150,3 171,7 193,0COP 3,11 3,16 3,13 3,19 3,16

Part load steps % 21-50-71-100

25-50-75-100

17-33-50-67-83-100

15-29-43-62-81-100

17-33-50-67-83-100

RefrigerantType HFC 410ANumber of refrigerant circuits 2CompressorQty 4 4 6 6 6Type ScrollEvaporatorQty 1Type Plate exchanger AISI 316Water flow l/h 62.573 69.780 82.044 93.275 104576Connection type VictaulicInlet/outlet diameter inch 4” 4” 4” 4” 4”CondenserQty 4Total coil face area per coil mm2 4,4 4,4 5,6 6,7 6,7FanQty 8 8 10 10 12Speed rpm/min 1.100 1.100 1.100 1.100 1.100Air flow m3/h 220.000 220.000 244.000 278.000 295.000Power input kW 20,8 20,8 26,0 26,0 31,2Static head pressure HSE Pa 0WeightShipping kg 2.896 3.018 3.967 4.083 4.465Operating kg 2.931 3.056 4.007 4.123 4.507DimensionsLength mm 4.000 4.000 5.000 6.000 6.000Width mm 2.200 2.200 2.200 2.200 2.200Height mm 2.550 2.550 2.550 2.550 2.550Acoustical dataSound power level4 dB(A) 103 103 104 104 105Sound pressure level5 dB(A) 71 71 72 72 73

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature. 2 Input power (only compressors).3 Data refers to 45°C leaving warm water temperature and 7°C ambient coil air temperature with 87% R.H., according EN14511 standard..4 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard. 5 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.

Page 132: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and
Page 133: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Water Cooled Chiller

& heat PumP

Water Cooled Chiller,Heat Pump and Condensing unit

WQl/WQh/WQrC 20-190 21-193 kW 24-212 kW 410A Scroll Plate

WQl/WQh/WQrC 524-1204 154-379 kW 170-419 kW 410A Scroll Plate

SyScrew 440-1550 Water eVo Co/hP/rC 444-1.567 kW 134a Screw Shell & Tube

Page 134: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Water cooled Chiller & Heat Pump132

Selection guide Water Cooled Chiller

Product Range Cooling Capacity EER Flow rate Acoustic Power

Size (LxHxP) mm

WQL

20-

190

WQL 20 21,2 kW 4,58 1,02 l/s 65 dB(A) 821 x

1.350 x 455

WQL 25 26,2 kW 4,54 1,26 l/s 67 dB(A) 821 x

1.350 x 455

WQL 30 31,1 kW 4,46 1,5 l/s 67 dB(A) 821 x

1.350 x 455

WQL 35 34,8 kW 4,53 1,68 l/s 68 dB(A) 821 x

1.350 x 455

WQL 40 39,2 kW 4,48 1,89 l/s 68 dB(A) 821 x

1.350 x 455

WQL 45 46,6 kW 4,57 2,24 l/s 70 dB(A) 821 x

1.350 x 455

WQL 50 50,9 kW 4,29 2,44 l/s 70 dB(A) 1.210 x

1.500 x 850

WQL 60 61,1 kW 4,48 2,93 l/s 70 dB(A) 1.210 x

1.500 x 850

WQL 75 77,3 kW 4,48 3,71 l/s 72 dB(A) 1.210 x

1.500 x 850

WQL 90 91,1 kW 4,38 4,37 l/s 73 dB(A) 1.210 x

1.500 x 850

WQL 120 118,4 kW 4,46 5,68 l/s 78 dB(A) 1.210 x

1.500 x 850

WQL 150 147,1 kW 4,46 7,05 l/s 81 dB(A) 1.210 x

1.500 x 850

WQL 170 170 kW 4,5 8,15 l/s 81 dB(A) 1.210 x

1.500 x 850

WQL 190 192,7 kW 4,51 9,24 l/s 81 dB(A) 1.210 x

1.500 x 850

WQL

524

-120

4

WQL 524 154,3 kW 4,51 7,4 l/s 81 dB(A) 2.250 x

1.845 x 850

WQL 604 181,8 kW 4,37 8,71 l/s 82 dB(A) 2.250 x

1.845 x 850

WQL 704 208,9 kW 4,4 10,01 l/s 85 dB(A) 2.250 x

1.845 x 850

WQL 804 232,6 kW 4,36 11,2 l/s 87 dB(A) 2.250 x

1.845 x 850

WQL 904 265,8 kW 4,48 12,7 l/s 89 dB(A) 2.250 x

1.845 x 850

WQL 1004 295,6 kW 4,51 14,1 l/s 90 dB(A) 2.250 x

1.845 x 850

WQL 1104 338 kW 4,51 16,2 l/s 90 dB(A) 2.250 x

1.845 x 850

WQL 1204 379,2 kW 4,55 18,2 l/s 90 dB(A) 2.250 x

1.845 x 850

136,5 kW

Page 135: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Water cooled Chiller & Heat Pump |

Water Cooled Chiller

& heat PumP

133

Product Range Capacity EER Flow rate Acoustic Power

Size (LxHxP) mm

SySc

rew

440

-155

0Wat

er E

VO C

O

SyScrew 440 Water EVO CO

444,3 kW 5,06 21,3 l/s 95 dB(A) 3.620 x 1.750 x 1.350

SyScrew 490 Water EVO CO

494,4 kW 5,05 23,6 l/s 95 dB(A) 3.620 x 1.750 x 1.350

SyScrew 570 Water EVO CO

570,4 kW 5,07 27,3 l/s 95 dB(A) 4.210 x 1.750 x 1.350

SyScrew 630 Water EVO CO

636,2 kW 5,07 30,5 l/s 95 dB(A) 4.210 x 1.750 x 1.350

SyScrew 700 Water EVO CO

708,5 kW 5,05 33,9 l/s 95 dB(A) 4.180 x 1.750 x 1.350

SyScrew 770 Water EVO CO

787,1 kW 5,06 37,7 l/s 95 dB(A) 4.180 x 1.750 x 1.350

SyScrew 860 Water EVO CO

875,5 kW 5,06 41,94 l/s 98 dB(A) 4.400 x 1.710 x 1.520

SyScrew 920 Water EVO CO

936 kW 5,05 44,86 l/s 98 dB(A) 4.400 x 1.710 x 1.520

SyScrew 990 Water EVO CO

998,6 kW 5,05 47,86 l/s 98 dB(A) 4.600 x 1.710 x 1.520

SyScrew 1070 Water EVO CO

1.071,4 kW 5,06 51,36 l/s 98 dB(A) 4.650 x 1.710 x 1.520

SyScrew 1130 Water EVO CO

1.132,9 kW 5,06 54,33 l/s 98 dB(A) 4.650 x 1.710 x 1.520

SyScrew 1220 Water EVO CO

1.224,1 kW 5,08 58,61 l/s 98 dB(A) 4.650 x 1.710 x 1.520

SyScrew 1280 Water EVO CO

1.285,2 kW 5,06 61,56 l/s 98 dB(A) 4.650 x 1.710 x 1.520

SyScrew 1400 Water EVO CO 1.428,5 kW 5,06 68,53 l/s 98 dB(A) 5350 x

1.710 x 1.520

SyScrew 1550 Water EVO CO

5,06 75,22 l/s 98 dB(A) 5350 x 1.710 x 1.5201.567 kW

Page 136: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Water cooled Chiller & Heat Pump134

Selection guide Water Heat Pump

Product Range Heating Capacity COP Flow rate Acoustic Power

Size (LxHxP) mm

WQH

20-

190

WQH 20 23,7 kW 3,88 1,13 l/s 65 dB(A) 821 x

1.350 x 455

WQH 25 28,9 kW 3,85 1,38 l/s 67 dB(A) 821 x

1.350 x 455

WQH 30 33,6 kW 3,73 1,61 l/s 67 dB(A) 821 x

1.350 x 455

WQH 35 38,5 kW 3,79 1,84 l/s 68 dB(A) 821 x

1.350 x 455

WQH 40 42,9 kW 3,77 2,05 l/s 68 dB(A) 821 x

1.350 x 455

WQH 45 51,2 kW 3,85 2,45 l/s 70 dB(A) 821 x

1.350 x 455

WQH 50 57,7 kW 3,83 2,73 l/s 70 dB(A) 1.210 x

1.500 x 850

WQH 60 68,2 kW 3,81 3,23 l/s 70 dB(A) 1.210 x

1.500 x 850

WQH 75 86,3 kW 3,92 4,09 l/s 72 dB(A) 1.210 x

1.500 x 850

WQH 90 102,2 kW 3,89 4,84 l/s 73 dB(A) 1.210 x

1.500 x 850

WQH 120 132 kW 3,92 6,24 l/s 78 dB(A) 1.210 x

1.500 x 850

WQH 150 164,2 kW 3,95 7,78 l/s 81 dB(A) 1.210 x

1.500 x 850

WQH 170 190,1 kW 3,93 9 l/s 81 dB(A) 1.210 x

1.500 x 850

WQH 190 212,3 kW 3,93 10,05 l/s 81 dB(A) 1.210 x

1.500 x 850

WQH

524

-120

4

WQH 524 170,2 kW 3,85 8,1 l/s 81 dB(A) 2.250 x

1.845 x 850

WQH 604 201,1 kW 3,75 9,57 l/s 82 dB(A) 2.250 x

1.845 x 850

WQH 704 231,8 kW 3,85 11 l/s 85 dB(A) 2.250 x

1.845 x 850

WQH 804 256,5 kW 3,75 12,2 l/s 87 dB(A) 2.250 x

1.845 x 850

WQH 904 295,6 kW 3,82 14,1 l/s 89 dB(A) 2.250 x

1.845 x 850

WQH 1004 331 kW 3,94 15,8 l/s 90 dB(A) 2.250 x

1.845 x 850

WQH 1104 376,6 kW 3,94 18 l/s 90 dB(A) 2.250 x

1.845 x 850

WQH 1204 418,5 kW 3,94 20 l/s 90 dB(A) 2.250 x

1.845 x 850

Page 137: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Water cooled Chiller & Heat Pump |

Water Cooled Chiller

& heat PumP

135

Product Range Capacity COP Flow rate Acoustic Power

Size (LxHxP) mm

SySc

rew

440

-155

0Wat

er E

VO H

P

SyScrew 440 Water EVO HP

487,7 kW 4,68 27,08 l/s 95 dB(A) 3.620 x 1.750 x 1.350

SyScrew 490 Water EVO HP

549,1 kW 4,75 30,64 l/s 95 dB(A) 3.620 x 1.750 x 1.350

SyScrew 570 Water EVO HP

634,6 kW 4,65 35,22 l/s 95 dB(A) 4.210 x 1.750 x 1.350

SyScrew 630 Water EVO HP

707,9 kW 4,61 39,19 l/s 95 dB(A) 4.210 x 1.750 x 1.350

SyScrew 700 Water EVO HP

791,9 kW 4,58 43,72 l/s 95 dB(A) 4.180 x 1.750 x 1.350

SyScrew 770 Water EVO HP

862,1 kW 4,65 47,81 l/s 95 dB(A) 4.180 x 1.750 x 1.350

SyScrew 860 Water EVO HP

960,2 kW 4,7 53,39 l/s 98 dB(A) 4.400 x 1.710 x 1.520

SyScrew 920 Water EVO HP

1.033,2 kW 4,71 57,50 l/s 98 dB(A) 4.400 x 1.710 x 1.520

SyScrew 990 Water EVO HP

1.109,2 kW 4,73 61,78 l/s 98 dB(A) 4.600 x 1.710 x 1.520

SyScrew 1070 Water EVO HP

1.189,3 kW 4,67 66,03 l/s 98 dB(A) 4.650 x 1.710 x 1.520

SyScrew 1130 Water EVO HP

1.257 kW 4,63 69,61 l/s 98 dB(A) 4.650 x 1.710 x 1.520

SyScrew 1220 Water EVO HP

1.359,9 kW 4,68 75,50 l/s 98 dB(A) 4.650 x 1.710 x 1.520

SyScrew 1280 Water EVO HP 1.426,9 kW 4,68 79,22 l/s 98 dB(A) 4.650 x

1.710 x 1.520

SyScrew 1400 Water EVO HP

4,53 87,72 l/s 98 dB(A) 5350 x 1.710 x 1.520

SyScrew 1550 Water EVO HP

4,60 94,83 l/s 98 dB(A) 5350 x 1.710 x 1.520

1.593,1 kW

1.714,6 kW

Page 138: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Water cooled Chiller & Heat Pump136

Water Cooled Chiller, Heat Pump and Condensing WQl/WQh/WQrC 20-190

technical features 14 sizes Cooling capacity from 21,2 to 192,7 kW Heating capacity from 23,7 to 212,3 kW 3 versions:

WQL (Cooling only) WQH (Heat pump) WQRC (Condenserless)

2 acoustic versions: BLN (Basic Low Noise)

ELN (Extra Low Noise) 2 frames:

F1 (size from 20 to 45) F2 (size from 50 to 190)

One refrigerant circuit Scroll compressors

accessories and options BMS interface Compressors acoustic box (standard on ELN) Compressors jackets Desuperheater available for frame 2 Differential pressure switch (standard) Electronic expansion valve (standard WQRC 170-190) Hydrokit with 1 or 2 pumps for evaporator and condenser Mechanical gauges kit Power factor corrector capacitors Sequence phases control (standard) Sofstart Water filter Water flow switch

21-193 kW

Plate

Water cooled Scroll

24-212 kW 410a

Page 139: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Water cooled Chiller & Heat Pump |

Water Cooled Chiller

& heat PumP

137

operating limit (to be confirmed following selection software issue)

WQL-WQH 20-190

Leaving water temperature (cooling)

Water °C from +5 to +18

Water + glycol °C -8 / +5 (with glycol + electronic expansion valve);+5/+18 (standard)

∆ T K from 3 to 8

Leaving water temperature (heating)

Water °C from +25 to +55

∆ T °C from 3 to 15

Note: maximum % glycol (ethylenic or propilenic): 40%.

WQRC 20-190

Leaving water temperature (cooling)

Water °C from +5 to +18

Water + glycol °C -8 / +5 (with glycol + electronic expansion valve); +5/+18 (standard)

∆ T K from 3 to 8

Note: maximum % glycol (ethylenic or propilenic): 40%.

Page 140: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Water cooled Chiller & Heat Pump138

technical feature

WQL 20-45 20 25 30 35 40 45Cooling capacity1 kW 21,2 26,2 31,1 34,8 39,2 46,6Input power1 kW 4,63 5,77 6,97 7,68 8,75 10,2EER1 4,58 4,54 4,46 4,53 4,48 4,57Energy Efficiency class C C C C C CESEER 5,16 5,09 4,93 4,95 4,81 5,08Part load steps % 0-100 0-100 0-100 0-100 0-100 0-100Power supply V/Ph/Hz 400/3/50RefrigerantType HFC 410ANumber of refrigerant circuits 1 1 1 1 1 1CompressorQty 1Type ScrollCrankcase heater W 70 90 90 90 90 90EvaporatorQty 1Type Plate exchanger AISI 316Water flow l/s 1,02 1,26 1,5 1,68 1,89 2,24Water pressure drop kPa 17,7 26,2 35,6 43,9 40,5 39,7Connection type VictaulicInlet/outlet diameter inch 1½” 1½” 1½” 1½” 1½” 1½”Evaporator pumpPower input kW 1,06 1,06 1,06 1,32 1,32 1,32Available static pressure kPa 251 222 189 198 187 159CondenserQty 1Type Plate exchanger AISI 316Water flow l/s 1,23 1,52 1,80 2,02 2,28 2,70Water pressure drop kPa 14,5 21,4 57,4 35,8 44,8 26,5Connection type VictaulicInlet/outlet diameter inch 1½˝ 1½” 1½” 1½” 1½” 1½”Condenser pumpPower input kW 1,06 1,06 1,32 1,32 1,32 1,32Available static pressure kPa 236 199 161 183 155 132WeightShipping kg 156 176 174 179 185 203Operating kg 162 182 179 185 191 214DimensionsLength mm 821 821 821 821 821 821Width mm 455 455 455 455 455 455Height mm 1.350 1.350 1.350 1.350 1.350 1.350Acoustical dataSound power level2/3* dB(A) 65/62 67/64 67/64 68/65 68/66 70/67Sound pressure level at 10 m2/3** dB(A) 34/31 36/33 36/33 37/34 38/35 39/36

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard. 2 BLN version. 3 ELN version.* Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.** Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.

Page 141: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Water cooled Chiller & Heat Pump |

Water Cooled Chiller

& heat PumP

139

technical feature

WQH 20-45 20 25 30 35 40 45Cooling capacity1 kW 20,8 26,0 30,1 34,0 38,2 45,5Power input1 kW 4,67 5,82 7,03 7,82 8,80 10,4EER1 4,45 4,47 4,28 4,35 4,34 4,39Energy Efficiency class C C C C C CESEER 4,95 5,03 4,80 4,86 4,67 4,86Heating capacity2 23,7 28,9 33,6 38,5 42,9 51,2Power input2 6,11 7,51 9,01 10,2 11,4 13,3COP2 3,88 3,85 3,73 3,79 3,77 3,85Energy Efficiency class C C D D D CPart load steps % 0-100 0-100 0-100 0-100 0-100 0-100Power supply V/Ph/Hz 400/3/50RefrigerantType HFC 410ANumber of refrigerant circuits 1 1 1 1 1 1CompressorQty 1Type ScrollCrankcase heater W 70 90 90 90 90 90Internal heat exchangerQty 1Type Plate exchanger AISI 316Water flow rate - cooling l/s 1,00 1,25 1,45 1,63 1,83 2,19Pressure drop - cooling kPa 17,0 25,6 33,4 41,7 38,3 38,2Water flow rate - heating l/s 1,13 1,38 1,61 1,84 2,05 2,45Pressure drop - heating kPa 21,8 31,4 41,1 52,8 47,8 47,7Connection type VictaulicInlet/outlet diameter inch 1½” 1½” 1½” 1½” 1½” 1½”Internal heat exchanger pumpPower input kW 1,06 1,06 1,06 1,32 1,32 1,32Available static pressure - cooling kPa 253 224 196 203 193 165Available static pressure - heating kPa 239 208 172 181 171 139External heat exchangerQty 1Type Plate exchanger AISI 316Water flow l/s 1,21 1,51 1,76 1,98 2,23 2,66Water pressure drop kPa 13,6 20,5 54,8 33,8 42,2 25,5Connection type VictaulicInlet/outlet diameter inch 1½˝ 1½˝ 1½˝ 1½˝ 1½˝ 1½˝Internal heat exchanger pumpPower input kW 1,06 1,06 1,32 1,32 1,32 1,32Available static pressure - heating kPa 238 201 167 187 161 137WeightShipping kg 159 181 179 184 190 208Operating kg 165 187 184 190 195 219DimensionsLength mm 821 821 821 821 821 821Width mm 455 455 455 455 455 455Height mm 1.350 1.350 1.350 1.350 1.350 1.350Acoustical dataSound power level3/4* dB(A) 65/62 67/64 67/64 68/65 68/66 70/67Sound pressure level at 10 m3/4** dB(A) 34/31 36/33 36/33 37/34 38/35 39/36

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard.2 Data refers to 45°C leaving warm water temperature and 7°C ambient coil air temperature with 87% R.H., according EN14511 standard.3 BLN version.4 ELN version.* Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.** Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.

Page 142: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Water cooled Chiller & Heat Pump140

technical feature

WQRC 20-45 20 25 30 35 40 45Cooling capacity1 kW 20,9 26,0 31,3 34,8 39,3 46,2Power input2 kW 4,54 5,61 6,37 7,24 8,15 9,89Part load steps % 0-100 0-100 0-100 0-100 0-100 0-100Power supply V/Ph/Hz 400/3/50RefrigerantType HFC 410ANumber of refrigerant circuits 1 1 1 1 1 1CompressorQty 1Type ScrollCrankcase heater W 70 90 90 90 90 90EvaporatorQty 1Type Plate exchanger AISI 316Water flow l/s 1,00 1,24 1,50 1,66 1,88 2,21Water pressure drop kPa 17,1 25,4 35,6 43,7 34,3 38,9Connection type VictaulicInlet/outlet diameter inch 1½” 1½” 1½” 1½” 1½” 1½”Evaporator pumpQty 1 1 1 1 1 1Power input kW 1,06 1 ,06 1,06 1,32 1,32 1,32Available static pressure kPa 253 225 188 200 188 163Remore condenser refrigerant connectionsConnection type To be brazedInlet diameter inch ⅝” ⅝” ⅝” ⅝” ⅝” ⅝”Outlet diameter inch ⅝” ⅞” ⅞” ⅞” ⅞” ⅞”WeightShipping kg 142 161 163 163 169 168Operating kg 144 164 166 166 172 172DimensionsLength mm 821 821 821 821 821 821Width mm 455 455 455 455 455 455Height mm 1.350 1.350 1.350 1.350 1.350 1.350Acoustical dataSound power level3/4* dB(A) 65/62 67/64 67/64 68/65 68/66 70/67Sound pressure level at 10 m3/4** dB(A) 34/31 36/33 36/33 37/34 38/35 39/36

1 Data refered to evaporator water temperature 12/7°C and condenser water temperature 40°C. 2 Input power (only compressors).3 BLN version. 4 ELN version.* Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.** Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.

Page 143: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Water cooled Chiller & Heat Pump |

Water Cooled Chiller

& heat PumP

141

technical feature

WQL 50-190 50 60 75 90 120 150 170 190Cooling capacity1 kW 50,9 61,1 77,3 91,1 118,4 147,1 170,0 192,7Power input1 kW 11,9 13,6 17,3 20,8 26,6 33,0 37,8 42,7EER1 4,29 4,48 4,48 4,38 4,46 4,46 4,50 4,51Energy Efficiency class C C C C C C C CESEER 5,68 5,95 5,53 5,92 5,58 5,38 5,38 5,41Part load steps % 0-50-100 0-50-100 0-50-100 0-50-100 0-50-100 0-50-100 0-50-100 0-50-100Power supply V/Ph/Hz 400/3/50RefrigerantType HFC 410ANumber of refrigerant circuits 1 1 1 1 1 1 1 1CompressorQty 2Type ScrollCrankcase heater W 90+90 90+90 90+90 90+90 120+120 150+150 150+150 150+150EvaporatorQty 1Type Plate exchanger AISI 316Water flow l/s 2,44 2,93 3,71 4,37 5,68 7,05 8,15 9,24Water pressure drop kPa 25,1 20,2 21,4 20,7 21,2 22,6 24,4 25,0Connection type VictaulicInlet/outlet diameter inch 2½” 2½” 2½” 2½” 2½” 2½” 2½” 2½”Evaporator pumpPower input (SP version) kW 1,10 1,10 1,99 1,99 2,45 2,45 3,00 3,00Available static pressure (SP version) kPa 127 124 154 145 157 121 180 152Power input (HP version) kW 2,20 2,20 3,26 3,26 3,00 3,00 4,00 4,00Available static pressure (HP version) kPa 244 241 246 235 241 214 248 221CondenserQty 1Type Plate exchanger AISI 316Water flow l/s 2,98 3,55 4,50 5,33 6,90 8,57 9,89 11,21Water pressure drop kPa 35,0 27,0 29,0 28,0 29,0 32,0 34,0 35,0Connection type VictaulicInlet/outlet diameter pollici 2½” 2½” 2½” 2½” 2½” 2½” 2½” 2½”Condenser pumpPower input (SP version) kW 1,10 1,10 1,99 1,99 2,45 3,00 3,00 4,00Available static pressure (SP version) kPa 107 100 134 116 114 165 115 145Power input (HP version) kW 2,20 2,20 3,26 3,26 3,00 4,00 5,50 5,50Available static pressure (HP version) kPa 226 221 224 211 206 234 247 200DesuperheaterQty 1Type Plate exchanger AISI 316Heat recovery kW 11,0 14,2 18,1 21,0 25,2 34,1 39,1 41,0Water flow l/s 0,53 0,68 0,86 1,00 1,20 1,63 1,87 1,96Water pressure drop kPa 8,3 4,5 5,1 5,7 5,0 8,7 10,3 7,5WeightShipping kg 433 481 528 577 818 942 1.013 1.113Operating kg 440 491 540 591 837 966 1.041 1.145DimensionsLength mm 1.210 1.210 1.210 1.210 1.210 1.210 1.210 1.210Width mm 850 850 850 850 850 850 850 850Height mm 1.500 1.500 1.500 1.500 1.500 1.500 1.500 1.500Acoustical dataSound power level2/3* dB(A) 70/68 70/68 72/70 73/71 78/76 81/79 81/79 81/79Sound pressure level at 10 m2/3** dB(A) 39/37 39/37 40/39 42/40 47/45 50/48 50/48 50/48

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard.2 BLN version.3 ELN version.* Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.** Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.SP version: low pressure pump. HP version: high pressure pump.

Page 144: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Water cooled Chiller & Heat Pump142

technical feature

WQH 50-190 50 60 75 90 120 150 170 190Cooling capacity1 kW 49,9 58,9 76,1 88,6 114,9 144,3 165,7 185,4Power input1 kW 12,0 13,9 17,5 21,1 27,0 33,3 38,2 43,3EER1 4,15 4,24 4,36 4,20 4,26 4,34 4,34 4,28Energy Efficiency class D D C D C C C CESEER 5,48 5,62 5,43 5,60 5,25 5,22 5,31 5,09Heating capacity2 kW 57,7 68,2 86,3 102,2 132,0 164,2 190,1 212,3Power input2 kW 15,1 17,9 22,0 26,3 33,7 41,6 48,4 54,0COP2 3,83 3,81 3,92 3,89 3,92 3,95 3,93 3,93Energy Efficiency class D D C C C C C CPart load steps % 0-50-100 0-50-100 0-50-100 0-50-100 0-50-100 0-50-100 0-50-100 0-50-100Power supply V/Ph/Hz 400/3/50RefrigerantType HFC 410ANumber of refrigerant circuits 1 1 1 1 1 1 1 1CompressorQty 2Type ScrollCrankcase heater W 90+90 90+90 90+90 90+90 120+120 150+150 150+150 150+150Internal heat exchangerQty 1Type Plate exchanger AISI 316Water flow rate - cooling l/s 2,40 2,83 3,65 4,25 5,51 6,92 7,95 8,89Pressure drop - cooling kPa 24,1 18,8 20,7 19,7 20,0 21,8 23,2 23,3Water flow rate - heating l/s 2,73 3,23 4,09 4,84 6,24 7,78 9,00 10,05Pressure drop - heating kPa 31,3 24,4 26,0 25,5 25,7 27,6 29,8 29,7Connection type VictaulicInlet/outlet diameter pollici 2½” 2½” 2½” 2½” 2½” 2½” 2½” 2½”Internal heat pumpOperation CoolingAvailable static pressure (SP version) kPa 129 127 156 148 162 126 187 164Available static pressure (HP version) kPa 245 244 247 238 245 218 254 233Operating HeatingAvailable static pressure (SP version) kPa 115 113 144 132 139 93 150 121Available static pressure (HP version) kPa 233 231 236 223 225 192 219 192External heat exchangerQty 1Type Plate exchanger AISI 316Water flow l/s 2,94 3,46 4,45 5,22 6,75 8,45 9,7 10,9Water pressure drop kPa 37,3 28,7 31,2 29,2 29,5 32,1 34,8 34,1Connection type VictaulicInlet/outlet diameter inch 2½” 2½” 2½” 2½” 2½” 2½” 2½” 2½”Internal heat pumpAvailable static pressure (SP version) kPa 108 104 135 120 120 170 123 158Available static pressure (HP version) kPa 227 224 226 214 210 238 255 215WeightShipping kg 441 489 539 588 831 959 1.031 1.130Operating kg 448 499 551 602 850 983 1.058 1.162DimensionsLength mm 1.210 1.210 1.210 1.210 1.210 1.210 1.210 1.210Width mm 850 850 850 850 850 850 850 850Height mm 1.500 1.500 1.500 1.500 1.500 1.500 1.500 1.500Acoustical dataSound power level3/4* dB(A) 70/68 70/68 72/70 73/71 78/76 81/79 81/79 81/79Sound pressure level at 10 m3/4** dB(A) 39/37 39/37 40/39 42/40 47/45 50/48 50/48 50/48

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard.2 Data refers to 45°C leaving warm water temperature and 7°C ambient coil air temperature with 87% R.H., according EN14511 standard.3 BLN version.4 ELN version.* Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.** Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.SP version: low pressure pump. HP version: high pressure pump.

Page 145: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Water cooled Chiller & Heat Pump |

Water Cooled Chiller

& heat PumP

143

technical feature

WQRC 50-190 50 60 75 90 120 150 170 190Cooling capacity1 kW 51,2 61,7 77,8 91,4 118,7 147,6 169,4 193,2Power input1 kW 11,2 12,9 16,5 20,0 25,7 31,8 36,9 41,4Part load steps % 0-50-100 0-50-100 0-50-100 0-50-100 0-50-100 0-50-100 0-50-100 0-50-100Power supply V/Ph/Hz 400/3/50RefrigerantType HFC 410ANumber of refrigerant circuits 1 1 1 1 1 1 1 1CompressorQty 2Type ScrollCrankcase heater W 90+90 90+90 90+90 90+90 120+120 150+150 150+150 150+150EvaporatorQty 1Type Plate exchanger AISI 316Water flow l/s 2,45 2,95 3,72 4,37 5,67 7,05 8,09 9,23Water pressure drop kPa 25,2 20,5 21,5 20,7 21,2 22,6 24,1 24,9Connection type VictaulicInlet/outlet diameter inch 2½” 2½” 2½” 2½” 2½” 2½” 2½” 2½”Evaporator pumpQty 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2Power Input (SP version) kW 1,10 1,10 1,99 1,99 2,45 2,45 3,00 3,00Available static pressure (SP version) kPa 127 123 154 145 157 121 182 152Power Input (HP version) kW 2,20 2,20 3,26 3,26 3,00 3,00 4,00 4,00Available static pressure (HP version) kPa 244 240 245 235 241 214 250 221Remote condenser refrigerant connectionsConnection type To be brazedInlet diameter inch ⅝” ⅝” ⅞” ⅞” ⅞” ⅞” 1⅛” 1⅛”Outlet diameter inch ⅞” ⅞” 1⅛” 1⅛” 1⅜” 1⅝” 1⅝” 1⅝”WeightShipping kg 373 399 433 459 668 750 799 858Operating kg 376 404 439 466 678 762 813 874DimensionsLength mm 1.210 1.210 1.210 1.210 1.210 1.210 1.210 1.210Width mm 850 850 850 850 850 850 850 850Height mm 1.500 1.500 1.500 1.500 1.500 1.500 1.500 1.500Acoustical dataSound power level2/3* dB(A) 70/68 70/68 72/70 73/71 78/76 81/79 81/79 81/79Sound pressure level at 10 m2/3** dB(A) 39/37 39/37 41/39 42/40 47/45 50/48 50/48 50/48

1 Data refered to evaporator water temperature 12/7°C and condenser temperature 40°C.2 Input power (only compressors).3 BLN version.4 ELN version.* Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.** Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.SP version: low pressure pump.HP version: high pressure pump.

Page 146: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Water cooled Chiller & Heat Pump144

Water Cooled Chiller & Heat PumpWQl/WQh/WQrC 524-1204

technical features 8 sizes Cooling capacity from 154,3 to 379,2 kW Heating capacity from 170,2 to 418,5 kW 3 versions:

WQL (Cooling only) WQH (Heat pump) WQRC (Condenserless)

2 acoustic option: BLN (Basic Low Noise) ELN (Extra Low Noise)

Two refrigerant circuits Scroll compressors

accessories and options Desuperheater Differential pressure switch (standard) Electronic expansion valve (standard WQRC 1104-1204) Hydrokit with 1 or 2 pumps for evaporator and condenser Mechanical gauges Sequence phases control (standard) Softstart Water filter Water flow switch

operating limit (to be confirmed following selection software issue)

WQL-WQH 524-1204

Leaving water temperature(cooling)

Water °C from +5 to +18

Water + glycol °C -8 / +5 (with glycol and eletronic expansion valve);+5/+18 (standard)

∆ T K from 3 to 8

Leaving water temperature(heating)

Water °C from +25 to +55∆ T °C from 3 to 15

Note: maximum % glycol (ethylenic or propilenic): 40%.

WQRC 524-1204

Leaving water temperature(cooling)

Water °C from +5 to +18

Water + glycol °C -8 / +5 (with glycol and eletronic expansion valve);+5/+18 (standard)

∆ T K from 3 to 8

Note: maximum % glycol (ethylenic or propilenic): 40%.

154-379 kW

Plate

Water cooled Scroll

170-419 kW 410a

Page 147: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Water cooled Chiller & Heat Pump |

Water Cooled Chiller

& heat PumP

145

technical feature

WQL/WQH 524-1204 524 604 704 804 904 1004 1104 1204Cooling capacity1 kW 154,3 181,8 208,9 232,6 265,8 295,6 338,0 379,2Input power1 kW 34,2 41,6 47,5 53,3 59,3 65,5 74,9 83,3EER1 kW/kW 4,51 4,37 4,40 4,36 4,48 4,51 4,51 4,55Energy Efficiency class C C C C C C C CESEER kW/kW 5,40 5,68 5,81 5,29 5,74 5,52 5,70 5,67Power supply V/Ph/Hz 400/3/50RefrigerantType HFC 410ANumber of refrigerant circuits 2CompressorQty/Type5 4 / ScrollCrankcase heater5 W 90-90 90-90 90-120 140-140 140-140 140-140 140-140 140-140EvaporatorQty/Type 1 / PlateWater flow rate l/s 7,40 8,71 10,01 11,2 12,7 14,1 16,2 18,2Water pressure drop kPa 26,7 26,6 31,5 36,3 18,7 22,8 17,8 18,4Evaporator water connectionsQty VictaulicInlet/outlet diameter inch 2”1/2 2”1/2 2”1/2 2”1/2 4” 4” 4” 4”Evaporator pumpQty 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2Input power (SP version) kW 2,20 2,20 2,20 3,00 3,00 3,00 4,00 4,00Available static pressure (SP version) kPa Refer to EDM graphicsInput power (HP version) kW 3,00 3,00 4,00 4,00 5,50 5,50 5,50 7,50Available static pressure (HP version) kPa Refer to EDM graphicsCondenserQty/Type 1 / PlateWater flow rate l/s 8,97 10,6 12,2 13,6 15,5 17,2 19,7 22,0Water pressure drop kPa 38.1 38,6 45,8 53,0 23,6 18,6 21,5 21,5Condenser water connectionsQty VictaulicInlet/outlet diameter inch 2”1/2 2”1/2 2”1/2 2”1/2 4” 4” 4” 4”Condenser pumpQty 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2Input power (SP version) kW 2,20 3,00 3,00 4,00 4,00 5,50 5,50 5,50Available static pressure (SP version) kPa Refer to EDM graphicsInput power (HP version) kW 3,00 4,00 5,50 5,50 5,50 5,50 7,50 7,50Available static pressure (HP version) kPa Refer to EDM graphicsDesuperheaterQty/Type 2 / PlateHeat recovery kW 22,1 28,4 36,1 42,0 50,4 68,3 78,1 81,9Water flow rate l/s 1,05 1,35 1,73 2,01 2,41 3,26 3,73 3,91Water pressure drop kPa 8,3 4,5 5,1 5,7 5,0 8,7 10,3 7,5WeightShipping2/3 kg 858/961 929/1.032 1.110/1.213 1.279/1.382 1.266/1.369 1.363/1.466 1.449/1.552 1.541/1.644Operating2/3 kg 890/993 971/1.074 1.156/1.259 1.329/1.432 1.340/1.443 1.453/1.556 1.552/1.655 1.660/1.763DimensionsLength mm 2.250Width mm 8502/8543/ 8852/4 - 1.0053/4

Height mm 1.8452/ 18503

Acoustic dataSound power level2/3* dB(A) 81/75 82/76 85/79 87/81 89/83 90/84 90/84 90/84Sound pressure level2*/3** dB(A) 49/43 50/44 53/47 55/49 57/51 58/52 58/52 58/52

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard.2 BLN version. 3 ELN version.4 Only for movimentation.5 Data for each refrigerant circuit.* Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.** Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.

Page 148: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Water cooled Chiller & Heat Pump146

technical feature

WQH 524-1204 524 604 704 804 904 1004 1104 1204Cooling capacity1 kW 150,7 176,2 204,5 225,4 263,1 291,3 332,0 370,5Input power1 kW 34,9 42,7 48,3 54,3 59,8 66,4 76,2 85,2EER1 kW/kW 4,32 4,13 4,23 4,15 4,40 4,39 4,36 4,35Energy Efficiency class C D D D C C C CESEER kW/kW 5,35 5,59 5,71 5,25 5,66 5,46 5,63 5,59Heating capacity2 kW 170,2 201,1 231,8 256,5 295,6 331,0 376,6 418,5Input power2 kW 44,2 53,6 60,2 68,4 77,4 84,0 95,6 106,2COP2 kW/kW 3,85 3,75 3,85 3,75 3,82 3,94 3,94 3,94Energy Efficiency class C D C D C C C CPower supply V/Ph/Hz 400/3/50RefrigerantType HFC 410ANumber of refrigerant circuits 2 2 2 2 2 2 2 2CompressorQty / Type6 4 / ScrollCrankcase heater6 W 90-90 90-90 90-120 140-140 140-140 140-140 140-140 140-140Internal heat exchangerQty/ Type 1 / PlateWater flow rate - Cooling operation l/s 7,22 8,44 9,80 10,8 12,6 14,0 15,9 17,7Water pressure drop - Cooling operation kPa 25,5 25,0 30,3 34,2 18,3 22,2 17,2 17,7Water flow rate - Heating operation l/s 8,10 9,57 11,0 12,2 14,1 15,8 18,0 20,0Water pressure drop - Heating operation kPa 31,6 31,7 37,9 43,2 22,6 28,0 21,6 22,1Internal heat exchanger water connectionsType VictaulicInlet/outlet diameter inch 2”1/2 2”1/2 2”1/2 2”1/2 4” 4” 4” 4”Internal heat exchanger pumpQty 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2Input power (SP version) kW 2,20 2,20 2,20 3,00 3,00 3,00 4,00 4,00Available static pressure (SP version) kPa Refer to EDM graphicsInput power (HP version) kW 3,00 3,00 4,00 4,00 5,50 5,50 5,50 7,50Available static pressure (HP version) kPa Refer to EDM graphicsExternal heat exchangerQty / Type 1 / PlateWater Flow Rate - Cooling operation l/s 8,83 10,4 12,0 13,3 15,4 17,1 19,5 21,7Water Pressure Drop - Cooling operation kPa 37,1 37,2 44,6 50,9 23,3 18,3 21,0 20,9Water Flow Rate - Heating operation l/s 10,3 12,0 13,9 15,3 17,8 20,0 22,7 25,2Water Pressure Drop - Heating operation kPa 48,9 48,5 58,8 66,5 30,7 24,6 28,1 27,6DesuperheaterQty / Type 2 / PlateHeat recovery kW 22,1 28,4 36,1 42,0 50,4 68,3 78,1 81,9Water flow rate l/s 1,05 1,35 1,73 2,01 2,41 3,26 3,73 3,91Water pressure drop kPa 8,3 4,5 5,1 5,7 5,0 8,7 10,3 7,5WeightShipping3/4 kg 876/979 947/1.050 1.141/1.244 1.311/1.414 1.302/1.405 1.410/1.513 1.494/1.597 1.585/1.688Operating3/4 kg 909/1.012 989/1.092 1.187/1.290 1.360/1.463 1.376/1.479 1.500/1.603 1.598/1.701 1.704/1.807DimensionsLength mm 2.250Width mm 8503/8544/ 8853/5 - 1.0054/5

Height mm 1.8453/1.8504

Acoustic dataSound power level3/4* dB(A) 81/75 82/76 85/79 87/81 89/83 90/84 90/84 90/84Sound pressure level3*/4** dB(A) 49/43 50/44 53/47 55/49 57/51 58/52 58/52 58/52

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard.2 Data refers to 45°C leaving warm water temperature and 7°C ambient coil air temperature with 87% R.H., according EN14511 standard.3 BLN version. 4 ELN version.5 Only for movimentation.6 Data for each refrigerant circuit.* Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.** Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.

Page 149: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Water cooled Chiller & Heat Pump |

Water Cooled Chiller

& heat PumP

147

technical feature

WQRC 524-1204 524 604 704 804 904 1004 1104 1204Cooling capacity1 kW 130,0 155,3 177,6 196,5 224,2 247,2 285,9 316,1Input power1 kW 42,9 51,1 59,0 65,8 74,4 82,5 94,6 105,8

Part load steps % 0-25-50- 75-100

0-25-50- 75-100

0-21-50- 71-100

0-25-50- 75-100

0-22-50-72-100

0-25-50- 75-100

0-23-50- 73-100

0-25-50- 75-100

Power supply V/Ph/Hz 400/3/50RefrigerantType HFC 410ANumber of refrigerant circuits 2CompressoreQty / Type5 4 / ScrollCrankcase heater5 W 90-90 90-90 90-120 140-140 140-140 140-140 140-140 140-140Internal heat exchangerQty / Type 1 / PlateWater flow rate l/s 6,21 7,42 8,49 9,39 10,7 11,8 13,7 15,1Water pressure drop kPa 19,3 19,6 23,0 26,2 13,5 16,2 12,9 13,0Internal heat exchanger water connectionsType VictaulicInlet diameter inch 2”1/2 2”1/2 2”1/2 2”1/2 4” 4” 4” 4”Internal heat exchanger pumpQty 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2Input power (SP version) kW 2.20 2,20 2,20 3,00 3,00 3,00 4,00 4,00Available static pressure (SP version) kPa Refer to EDM graphicsInput power (HP version) kW 3.00Available static pressure (HP version) kPa Refer to EDM graphicsRemote condenser refrigerant connectionsType To be brazedInlet diameter inch 7/8” 7/8” 1 1/8” 1 1/8” 1 1/8” 1 1/8” 1 1/8” 1 1/8”Outlet diameter inch 1 1/8” 1 1/8” 1 3/8” 1 3/8” 1 5/8” 1 5/8” 1 5/8” 1 5/8”WeightShipping2/3 kg 754/857 791/894 965/1.068 1.138/1.241 1.153/1.256 1.203/1.306 1.279/1.382 1.333/1.436Operating2/3 kg 770/873 812/915 988/1.091 1.163/1.266 1.188/1.291 1.241/1.344 1.328/1.431 1.388/1.491DimensionsLength mm 2.250Width mm 8502/8543/8852/4- 1.0053/4

Height mm 1.8452/1.8503

Acoustic dataSound power level2* dB(A) 81 82 85 87 89 90 90 90Sound pressure level2** dB(A) 49 50 53 55 57 58 58 58Sound power level3* dB(A) 75 76 79 81 83 84 84 84Sound pressure level3** dB(A) 43 44 47 49 51 52 52 52

1 Evaporator EWT/LWT 12 °C/7 °C, condensing temperature 50 °C.2 BLN version. 3 ELN version.4 Only for movimentation.5 Data for each refrigerant circuit.* Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.** Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.

Page 150: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Water cooled Chiller & Heat Pump148

Water Cooled ChillerSyScrew 440-1550 Water eVo Co/hP/rC

technical features 15 sizes Cooling capacity from 444 to 1.567 kW 3 versions:

CO (chiller) HP (heat pump) water side RC (condenserless)

2 acoustic versions: STD (Standard) S (Super Low Noise)

1/2 refrigerant circuit Screw compressors Shell & Tube evaporator and condenser Electronic expansion valve

accessories and options Automatic circuit breaker BMS interface Compressors acoustic box (standard for S version) Compressor stepless control Mechanical gauges Power factor corrector capacitors Sequence phases control (standard) Softstart Water filter Water flow switch

operating limit (to be confirmed following selection software issue)

Models SyScrew Water EVO CO

SyScrew Water EVO HP

SyScrew Water EVO RC

Evaporator Leaving watertemperature

Water °C from 5 to 15

Water + glycol °C from -8 to 5

∆ T K from 3 to 7

Condenser

Leaving water temperature °C from 25 a 45 from 25 to 60 -

Condensing Temperature °C - - da 30 a 63

Leaving water + glycol temperature K from +3 to +8 with tower water15 with well water -

ENERGY EFFICIENCY

Report to performance data

COOLING MODE

2014

444-1.567 kW Shell & tube

Water cooled Screw

134a

Page 151: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Water cooled Chiller & Heat Pump |

Water Cooled Chiller

& heat PumP

149

technical feature

SyScrew 440-770 Water EVO CO 440 490 570 630 700 770Cooling capacity1 kW 444,3 494,4 570,4 636,2 708,5 787,1Power input1 kW 87,9 97,8 112,4 125,4 140,2 155,7EER1 5,06 5,05 5,07 5,07 5,05 5,06Energy efficiency class A A A A A AESEER 6,27 6,27 6,29 6,29 6,27 6,27Part load steps % 50-75-100RefrigerantType HFC 134aNumber of refrigerant circuits 1CompressorType ScrewQty 1Startup type S/ΔEvaporatorType Shell & Tube (Pure counterflow)Qty 1Water flow m3/h 76,7 85,3 98,5 109,9 122,2 135,8Water pressure drop kPa 42,9 30,2 52,0 64,7 30,2 37,2Connection type VictaulicInlet/outlet diameter inch 6 6 6 6 8 8CondenserType Shell & Tube (Pure counterflow)Qty 1Water flow m3/h 91,2 101,5 117,0 130,6 145,5 161,6Water pressure drop kPa 52,5 50,7 54,7 34,3 42,5 51,1Connection type Female gas threadedInlet/outlet diameter inch 4 4 5 5 5 5Weight / STD versionShipping kg 2.502 2.531 2.694 2.800 3.178 3.245Operating kg 2.683 2.718 2.911 3.033 3.516 3.590Dimensions / STD versionLength mm 3.620 4.210 4.180Width mm 1.350Height mm 1.650Acoustic data / STD versionSound power level2 dB(A) 95 95 95 95 95 95Sound pressure level3 dB(A) 76 76 76 76 76 76Weight / S versionShipping kg 2.682 2.711 2.874 2.980 3.358 3.425Operating kg 2.863 2.898 3.091 3.213 3.696 3.770Dimensions / S versionLength mm 3.620 4.210 4.180Width mm 1.350Height mm 1.750Acoustic data / S versionSound power level2 dB(A) 85 85 85 85 85 85Sound pressure level3 dB(A) 66 66 66 66 66 66

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard.2 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.3 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.

Page 152: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Water cooled Chiller & Heat Pump150

technical feature

SyScrew 860-1550 Water EVO CO 860 920 990 1070 1130 1220 1280 1400 1550Cooling capacity1 kW 875,5 936,0 998,6 1.071,4 1.132,9 1.224,1 1.285,2 1.428,5 1.567,0Power input1 kW 173,1 185,2 197,6 211,7 223,8 241,0 253,9 282,4 309,9EER1 5,06 5,05 5,05 5,06 5,06 5,08 5,06 5,06 5,06Energy efficiency class A C A A A A A A AESEER 6,37 6,37 6,39 6,42 6,42 6,43 6,37 6,38 6,38Part load steps % 25-50-62-75-87-100RefrigerantType HFC 134aNumber of refrigerant circuits 2CompressorType ScrewQty 2Startup type S/ΔEvaporatorType Shell & Tube (Pure counterflow)Qty 1Water flow m3/h 151,0 161,5 172,3 184,9 195,6 211,0 221,6 246,7 270,8Water pressure drop kPa 41,6 47,6 42,6 47,6 53,2 32,3 35,6 62,1 74,8Connection type VictaulicInlet/outlet diameter inch 8 8 8 8 8 8 8 10 10CondenserType Shell & TubeQty 2Water flow m3/h 179,7 192,2 205,0 219,9 232,5 251,1 263,8 293,4 321,8Water pressure drop 1 circuit kPa 51,0 51,8 51,8 52,9 54,0 56,0 54,6 42,2 50,7Water pressure drop 2 circuit 51,0 50,9 51,8 54,0 54,0 55,3 54,6 42,2 50,7Connection type Female gas threadedInlet/outlet diameter inch 4 4 4 4 / 5 5 5 5 5 5Weight / STD versionShipping kg 5.085 5.115 5.227 5.361 5.466 5.557 5.599 6.093 6.188Operating kg 5.540 5.576 5.787 5.909 6.016 6.087 6.136 6.754 6.849Dimensions / STD versionLength mm 4.400 4.600 4.650 5.350Width mm 1.520Height mm 1.710Acoustic data / STD versionSound power level2 dB(A) 98 98 98 98 98 98 98 98 98Sound pressure level3 dB(A) 79 79 79 79 79 79 79 79 79Weight / S versionShipping kg 5.445 5.475 5.587 5.721 5.826 5.917 5.959 6.453 6.548Operating kg 5.900 5.936 6.147 6.269 6.376 6.447 6.496 7.114 7.209Dimensions / S versionLength mm 4.400 4.600 4.650 5.350Width mm 1.520Height mm 1.710Acoustic data / S versionSound power level2 dB(A) 89 89 89 89 89 89 89 89 89Sound pressure level3 dB(A) 70 70 70 70 70 70 70 70 70

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard.2 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.3 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.

Page 153: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Water cooled Chiller & Heat Pump |

Water Cooled Chiller

& heat PumP

151

technical feature

SyScrew 440-770 Water EVO HP 440 490 570 630 700 770Cooling Capacity1 3 kW 383,4 433,6 498,1 554,5 619,1 676,8Power input1 3 kW 104,3 115,6 136,4 153,4 172,8 185,2Heating Capacity1 3 kW 487,7 549,1 634,6 707,9 791,9 862,1COP1 3 4,68 4,75 4,65 4,61 4,58 4,65Energy Efficiency Class A A A A A ACooling Capacity2 3 kW 339,5 383,8 441,3 491,4 548,0 599,1Total Input Power2 3 kW 117,1 130,3 152,2 172,0 195,5 208,9Heating Capacity2 3 kW 456,6 514,1 593,5 663,4 743,5 808,0COP2 3 3,90 3,95 3,90 3,86 3,80 3,87Part Load Steps % 50-75-100Start-up Type SD SD SD SD SD SDRefrigerantType HFC 134aNumber of Refrigerant Circuits 1 1 1 1 1 1CompressorQty / Type 1 / ScrewInternal heat exchanger (Evaporator)Qty / Type 1 / Shell & tube (Pure counterflow)Connection type VictaulicInlet/outlet diameter inch 6 6 6 6 8 8Water flow rate1 m3/h 110,4 124,8 143,5 159,4 178,1 194,8Water pressure drop1 kPa 89 65 110 136 64 77Water flow rate2 m3/h 97,5 110,3 126,8 141,1 157,4 172,1Water pressure drop2 kPa 69 50 86 107 50 60External heat exchanger (Condenser)Qty / Type 1 / Shell & tubeConnection type VictaulicInlet/outlet diameter inch 4 4 5 5 5 5Water flow rate (total)1 m3/h 83,4 94,0 108,4 120,7 135,6 147,5Water pressure drop cond 11 kPa 44 44 47 29 37 43Water pressure drop cond 21 kPa - - - - - -Water flow rate (total)2 m3/h 48,8 55,0 63,4 70,8 79,6 86,5Water pressure drop cond 12 kPa 15 15 16 10 13 15Water pressure drop cond 22 kPa - - - - - -Acoustic Data / STD versionSound power level4 dB(A) 95 95 95 95 95 95Sound pressure level5 dB(A) 76 76 76 76 76 76Acoustic Data / S versionSound Power Level4 dB(A) 85 85 85 85 85 85Sound Pressure Level5 dB(A) 66 66 66 66 66 66Dimensions / STD versionLenght mm 3.620 3.620 4.210 4.210 4.180 4.180Width mm 1.350 1.350 1.350 1.350 1.350 1.350Height mm 1.650 1.650 1.650 1.650 1.650 1.650Dimensions / S versionLenght mm 3.620 3.620 4.210 4.210 4.180 4.180Width mm 1.350 1.350 1.350 1.350 1.350 1.350Height mm 1.750 1.750 1.750 1.750 1.750 1.750Weight / STD versionShipping kg 2.509 2.538 2.701 2.807 3.185 3.252Operating kg 2.690 2.725 2.918 3.040 3.523 3.597Weight / S versionShipping kg 2.703 2.732 2.895 3.001 3.379 3.446Operating kg 2.884 2.919 3.112 3.234 3.717 3.791

1 Heating mode conditions: evaporator EWT/LWT 10°C/7°C, condenser EWT/LWT 40°C/45°C.2 Heating mode conditions: evaporator EWT/LWT 10°C/7°C, condenser EWT/LWT 47°C/55°C.3 NET value. According to standard EN 14511-3:2011.4 Sound power levels refers to standard ISO 3744 and Eurovent 8/1 for units certified. Units at fully loaded conditions.5 Sound pressure levels refers to unit in free field on refletive surface at 1m. Values derived from sound power levels (standard ISO 3744 with parallepiped shape).

Page 154: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Water cooled Chiller & Heat Pump152

technical feature

SyScrew 860-1550 Water EVO HP 860 920 990 1070 1130 1220 1280 1400 1550Cooling Capacity1 3 kW 755,9 813,8 874,6 934,6 985,3 1.069,6 1.122,1 1.241,5 1.341,5Power Input1 3 kW 204,3 219,4 234,6 254,7 271,7 290,3 304,8 351,6 373,1Heating Capacity1 3 kW 960,2 1.033,2 1.109,2 1.189,3 1.257,0 1.359,9 1.426,9 1.593,1 1.714,6COP1 3 4,70 4,71 4,73 4,67 4,63 4,68 4,68 4,53 4,60Energy Efficiency Class A A A A A A A A ACooling Capacity2 3 kW 669,3 720,7 774,4 827,8 872,7 946,6 993,3 1.100,0 1.189,1Total Input Power2 3 kW 230,2 246,6 264,0 286,2 305,1 327,7 343,8 395,2 417,5Heating Capacity2 3 kW 899,5 967,3 1.038,4 1.114,0 1.177,8 1.274,3 1.337,1 1.495,2 1.606,6COP2 3 3,91 3,92 3,93 3,89 3,86 3,89 3,89 3,78 3,85Part Load Steps % 25-50-62-75-87-100Start-up Type SD SD SD SD SD SD SD SD SDRefrigerantType HFC 134aNumber of Refrigerant Circuits 2 2 2 2 2 2 2 2 2CompressorQty / Type 2 / ScrewInternal heat exchanger (Evaporator)Qty / Type 1 / Shell & tube (Pure counterflow)Connection type VictaulicInlet/outlet diameter inch 8 8 8 8 8 8 8 10 10Water flow rate1 m3/h 217,6 234,2 251,7 269,0 283,6 307,9 323,0 357,0 386,0Water pressure drop1 kPa 86 100 91 101 112 69 76 130 152Water flow rate2 m3/h 192,2 207,0 222,4 237,7 250,6 271,8 285,2 315,8 341,4Water pressure drop2 kPa 67 78 71 79 87 54 59 102 119External heat exchanger (Condenser)Qty / Type 2 / Shell & tubeConnection type VictaulicInlet/outlet diameter inch 4 4 4 4 / 5 5 5 5 5 5Water flow rate (total)1 m3/h 164,2 176,6 189,7 203,3 214,7 232,9 244,3 271,9 292,3Water pressure drop cond 11 kPa 43 44 44 45 46 48 47 36 42Water pressure drop cond 21 kPa 43 43 44 46 46 48 47 36 42Water flow rate (total)2 m3/h 96,3 103,4 111,1 119,1 125,9 136,5 143,2 159,7 171,5Water pressure drop cond 12 kPa 15 15 15 15 16 16 16 12 14Water pressure drop cond 22 kPa 15 15 15 16 16 16 16 12 14Acoustic Data / STD versionSound power level4 dB(A) 98 98 98 98 98 98 98 98 98Sound pressure level5 dB(A) 79 79 79 79 79 79 79 79 79Acoustic Data / S versionSound power level4 dB(A) 89 89 89 89 89 89 89 89 89Sound pressure level5 dB(A) 70 70 70 70 70 70 70 70 70Dimensions / STD versionLenght mm 4.400 4.400 4.600 4.650 4.650 4.650 4.650 5.350 5.350Width mm 1.520 1.520 1.520 1.520 1.520 1.520 1.520 1.520 1.520Height mm 1.710 1.710 1.710 1.710 1.710 1.710 1.710 1.710 1.710Dimensions / S versionLenght mm 4.650 4.650 4.650 4.650 4.650 4.650 4.650 5.350 5.350Width mm 1.520 1.520 1.520 1.520 1.520 1.520 1.520 1.520 1.520Height mm 1.770 1.770 1.770 1.770 1.770 1.770 1.770 1.770 1.770Weight / STD versionShipping kg 5.124 5.154 5.266 5.400 5.505 5.596 5.638 6.132 6.227Operating kg 5.579 5.615 5.826 5.948 6.055 6.126 6.175 6.793 6.888Weight / S versionShipping kg 5.511 5.541 5.653 5.787 5.892 5.983 6.025 6.519 6.614Operating kg 5.966 6.002 6.213 6.335 6.442 6.513 6.562 7.180 7.275

1 Heating mode conditions: evaporator EWT/LWT 10°C/7°C, condenser EWT/LWT 40°C/45°C.2 Heating mode conditions: evaporator EWT/LWT 10°C/7°C, condenser EWT/LWT 47°C/55°C.3 NET value. According to standard EN 14511-3:2011.4 Sound power levels refers to standard ISO 3744 and Eurovent 8/1 for units certified. Units at fully loaded conditions.5 Sound pressure levels refers to unit in free field on refletive surface at 1m. Values derived from sound power levels (standard ISO 3744 with parallepiped shape).

Page 155: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Water cooled Chiller & Heat Pump |

Water Cooled Chiller

& heat PumP

153

technical feature

SyScrew 440-770 Water EVO RC 440 490 570 630 700 770Cooling capacity1 kW 386,3 435,7 502,8 561,0 621,9 680,6Power input1 kW 101,2 113,3 131,4 147,4 170,4 181,5EER1 3,82 3,85 3,83 3,81 3,65 3,75Part load steps % 50-75-100RefrigerantType HFC 134aNumber of refrigerant circuits 1CompressorType ScrewQty 1Startup type S/ΔEvaporatorType Shell & Tube (Pure counterflow)Qty 1Water flow m3/h 66,4 74,9 86,5 96,5 107,0 117,1Water pressure drop kPa 32,2 23,3 40,0 49,9 23,1 27,7Connection type VictaulicInlet/outlet diameter inch 6 6 6 6 8 8Weight / STD versionShipping kg 2.152 2.162 2.278 2.298 2.669 2.709Operating kg 2.295 2.305 2.449 2.469 2.945 2.985Dimensions / STD versionLength mm 3.620 4.210 4.180Width mm 1.350Height mm 1.620Acoustic data / STD versionSound power level2 dB(A) 95 95 95 95 95 95Sound pressure level3 dB(A) 76 76 76 76 76 76Weight / S versionShipping kg 2.332 2.342 2.458 2.478 2.849 2.889Operating kg 2.475 2.485 2.629 2.649 3.125 3.165Dimensions / S versionLength mm 3.620 4.210 4.180Width mm 1.350Height mm 1.620Acoustic data / S versionSound power level2 dB(A) 85 85 85 85 85 85Sound pressure level3 dB(A) 66 66 66 66 66 66

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard.2 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.3 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.

Page 156: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Water cooled Chiller & Heat Pump154

technical feature

SyScrew 860-1550 Water EVO RC 860 920 990 1070 1130 1220 1280 1400 1550Cooling capacity1 kW 760,8 820,0 880,4 941,7 993,6 1.074,2 1.127,6 1.253,8 1.357,3Power input1 kW 199,5 213,2 228,7 247,5 263,2 285,5 299,1 340,5 357,8EER1 3,81 3,85 3,85 3,80 3,77 3,76 3,77 3,68 3,79Part load steps % 25-50-62-75-87-100RefrigerantType HFC 134aNumber of refrigerant circuits 2CompressorType ScrewQty 2Startup type S/ΔEvaporatorType Shell & TubeQty 1Water flow m3/h 130,9 141,0 151,4 162,0 170,9 184,8 194,0 215,6 233,5Water pressure drop kPa 31,2 36,3 32,9 36,5 40,6 24,7 27,3 47,4 55,6Connection type VictaulicInlet/outlet diameter inch 8 8 8 8 8 8 8 10 10Weight STD versionShipping kg 4.386 4.396 4.487 4.574 4.634 4.700 4.720 5.034 5.114Operating kg 4.765 4.775 4.959 5.032 5.092 5.131 5.151 5.557 5.637Dimensions STD versionLength mm 4.400 4.600 4.650 5.350Width mm 1.520Height mm 1.710Acoustic data STD versionSound power level2 dB(A) 98 98 98 98 98 98 98 98 98Sound pressure level3 dB(A) 79 79 79 79 79 79 79 79 79Weight S versionShipping kg 4.746 4.756 4.847 4.934 4.994 5.060 5.080 5.394 5.474Operating kg 5.125 5.135 5.319 5.392 5.452 5.491 5.511 5.917 5.997Dimensions S versionLength mm 4.400 4.600 4.650 5.350Width mm 1.520Height mm 1.710Acoustic data S versionSound power level2 dB(A) 89 89 89 89 89 89 89 89 89Sound pressure level3 dB(A) 70 70 70 70 70 70 70 70 70

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard.2 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.3 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.

Page 157: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Free-Cooling

Free-cooling module

SysFreeCool 100-550 kW Free-cooling

Page 158: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Free-cooling156

technical feature 10 sizes Cooling capacity from 100 to 550 kW Freecooling option is developed in two versions:

Slave Stand-alone

2 acoustic versions: - (Basic Low Noise) L (Low Noise)

2 fans versions: EC Version (Inverter Fans) HPF Version (High Pressure Fans

accessories and options Set point timer/clock card as standard Fan speed control as standard Sequence phase control as standard Power supply without neutral Hour meter as standard Main switch ModBus protocol kit Automatic circuit breaker E-coating for AL/CU fins Coils with cooper fins Coil grilles Free-cooling grilles High static pressure fan motors (HPF Version) Brushless fan motors (EC Version) Remote ON/OFF control Remote keyboard panel Water filter

operating limit (to be confirmed following selection software issue)

Free-cooling moduleSysFreeCool

SysFreeCool 12 14 22 23 24 32 33 34 43 44

BrineMinimum temperature1 °C -10Maximum operating pressure bar 6

Min./Max.

AmbientOutdoor air temperature °C -20 to +50

External static pressure

Standard fans Pa 0High pressure fans Pa < 120

Power supply voltage2 V 400 V, 3 Ø, 50 Hz (nominal)

* Operating limits refer to free-cooling module. Concerning chiller to be matched to free-cooling module, operating limit can be found inside chiller correspondent chapter1 Liquid with appropriate % of glycol.2 Voltage 400V +/- 10%.

100-550 kW Free-cooling

Page 159: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Free-cooling |

Free-cooling

157

Configuration

Following modules are available in order to cover a wide capacity range: 1V: equipped with two coils and two fan motors 2V: equipped with four coils and four fan motors 3V: equipped with six coils and six fan motors 4V: equipped with eight coils and eight fan motors

Each module is be available in further versions, according coil row number, sound level emission

Following table is summarizing allowed combination be-tween free-cooling modules and SyScroll Air range.The table is valid for Slave version

SyScroll Air CO Free-cooling module SyScroll Air FC

Assembly view Size Assembly view Size Assembly view

240270290320

232432

360420

3334

470540

3334

590660

4344

+ =

SyScroll Air EVO CO Free-cooling module SyScroll Air EVO FC

Assembly view Size Assembly view Size Assembly view

200 22

230260280

232432

300330360

2324

+ =

V VV VVV VVVV

Stand-alone Slave / Stand-alone

85 200 300 400 550

Cooling Capacity (kW)

Following picture is showing cooling capacity field where it is possible to have stand-alone, slave or both configuration

Page 160: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Free-cooling158

technical feature

SySFREECOOL_ - (STD -HPF) 12 14 22 23 24Nominal capacity1 kW 101 156 206 245 275Nominal Water Flow m3/h 19,0 29,4 38,7 46,0 51,7Total pressure drop1 kPa 44 83 74 43 49FansNumber of fans 2 2 4 4 4Nominal speed rpm 900 900 900 900 900Total airflow m3/h 45.400 41.000 90.000 85.200 80.400Total input power kW 4,2 4,2 8,4 8,4 8,4Total input power* kW 6,2 6,2 12,4 12,4 12,4Water ConnectionsType Male GAS ThreadedInlet Diameter inch 2” 1/2 2” 1/2 2” 1/2 3” 3”Outlet Diameter inch 2” 1/2 2” 1/2 2” 1/2 3” 3”Water Flow RangeMin water flow m3/h 11,1 12,5 17,4 27,2 28,7Max water flow m3/h 30,0 33,8 47,2 73,6 77,8WeightShipping kg 624 664 912 965 1.005Operating kg 669 733 1.002 1.075 1.139DimensionsLength mm 2.146 2.124Width mm 1.097 2.146Height mm 2.519 2.519Acoustical dataSound power level2 dB(A) 88 88 91 91 91Sound pressure level at 10 m3 dB(A) 56 56 59 59 59

SySFREECOOL_ - (STD -HPF) 32 33 34 43 44Nominal capacity1 kW 309 367 413 490 550Nominal Water Flow m3/h 58,0 69,0 77,5 92,0 103,4Total pressure drop1 kPa 70 51 57 43 49FansNumber of fans 6 6 6 8 8Nominal speed rpm 900 900 900 900 900Total airflow m3/h 135.000 127.800 120.600 170.400 160.800Total input power kW 12,6 12,6 12,6 16,8 16,8Total input power* kW 18,6 18,6 18,6 24,8 24,8Water ConnectionsType Male GAS Threaded VictaulicInlet Diameter inch 3” 4” 4” 5” 5”Outlet Diameter inch 3” 4” 4” 5” 5”Water Flow RangeMin water flow m3/h 26,8 37,5 39,7 54,3 57,5Max water flow m3/h 72,6 101,6 107,4 147,2 155,6WeightShipping kg 1.336 1.404 1.464 1.800 1.880Operating kg 1.466 1.574 1.670 2.070 2.198DimensionsLength mm 3.176 4.228Width mm 2.146 2.146Height mm 2.519 2.519Acoustical dataSound power level2 dB(A) 93 93 93 94 94Sound pressure level at 10 m3 dB(A) 61 61 61 62 62

1 Data refers to 15 (°C) return brine temperature, 10 (°C) leaving brine temperature, 0 (°C) outdoor air temperature; 30% EG.2 Sound levels are at fully loaded conditions. Sound power level values refer to ISO standard 3744.3 Sound pressure levels refer to ISO Standard 3744, parallelepiped shape.

Page 161: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Free-cooling |

Free-cooling

159

technical feature

SySFREECOOL_ L- (STD -HPF) 12 14 22 23 24Nominal capacity1 kW 84,4 123,5 170,3 197,0 215,9Nominal Water Flow m3/h 15,9 23,2 32,0 37,0 40,6Total pressure drop1 kPa 31 52 50 28 30FansNumber of fans 2 2 4 4 4Nominal speed rpm 700 700 700 700 700Total airflow m3/h 34.000 30.000 66.400 62.000 58.000Total input power kW 2,3 2,3 4,6 4,6 4,6Water ConnectionsType Male GAS ThreadedInlet Diameter inch 2” 1/2 2” 1/2 2” 1/2 3” 3”Outlet Diameter inch 2” 1/2 2” 1/2 2” 1/2 3” 3”Water Flow RangeMin water flow m3/h 11,1 12,5 17,4 27,2 28,7Max water flow m3/h 30,0 33,8 47,2 73,6 77,8WeightShipping kg 624 664 912 965 1.005Operating kg 669 733 1.002 1.075 1.139DimensionsLength mm 2.146 2.124Width mm 1.097 2.146Height mm 2.519 2.519Acoustical dataSound power level2 dB(A) 79 79 82 82 82Sound pressure level at 10 m3 dB(A) 47 47 50 50 50

1 Data refers to 15 (°C) return brine temperature, 10 (°C) leaving brine temperature, 0 (°C) outdoor air temperature; 30% EG.2 Sound levels are at fully loaded conditions. Sound power level values refer to ISO standard 3744.3 Sound pressure levels refer to ISO Standard 3744, parallelepiped shape.

Page 162: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Free-cooling160

SySFREECOOL_ L- (STD -HPF) 32 33 34 43 44Nominal capacity1 kW 255,4 295,5 323,8 394,0 431,8Nominal Water Flow m3/h 48,0 55,5 60,8 74,0 81,1Total pressure drop1 kPa 48 33 35 28 30FansNumber of fans 6 6 6 8 8Nominal speed rpm 700 700 700 700 700Total airflow m3/h 99.600 93.000 87.000 124.000 116.000Total input power kW 6,9 6,9 6,9 9,2 9,2Water ConnectionsType Male GAS Threaded VictaulicInlet Diameter inch 3” 4” 4” 5” 5”Outlet Diameter inch 3” 4” 4” 5” 5”Water Flow RangeMin water flow m3/h 26,8 37,5 39,7 54,3 57,5Max water flow m3/h 72,6 101,6 107,4 147,2 155,6WeightShipping kg 1.336 1.404 1.464 1.800 1.880Operating kg 1.466 1.574 1.670 2.070 2.198DimensionsLength mm 3.176 4.228Width mm 2.146 2.146Height mm 2.519 2.519Acoustical dataSound power level2 dB(A) 84 84 84 85 85Sound pressure level at 10 m3 dB(A) 52 52 52 53 53

1 Data refers to 15 (°C) return brine temperature, 10 (°C) leaving brine temperature, 0 (°C) outdoor air temperature; 30% EG.2 Sound levels are at fully loaded conditions. Sound power level values refer to ISO standard 3744.3 Sound pressure levels refer to ISO Standard 3744, parallelepiped shape.

technical feature

Page 163: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

CondenSing unit

Condensing unit

VlC 604-1204 174-347 kW 410A Scroll

SyScroll 240-660 air re 266-727 kW 410A Scroll

SyScroll 40-75 air re 43-85 kW 410A Scroll

SyScroll 85-135 air re 94-142 kW 410A Scroll

aQVC 85-140 92-151 kW 410A Scroll

SyScroll 140-360 air re 165-395 kW 410A Scroll

Sysaqua 25-125 C

32-136 kW 410A Scroll

SyScroll 20-35 air re 22-36 kW 410A Scroll

Page 164: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Condensing unit162

SyScroll 20-35 Air RE

Evaporating temperature2 °C from -12 to +14Ambient Air temperature -1 °C refer to graphic

Condensing unitSyScroll 20-35 air re

operating limit (to be confirmed following selection software issue)

technical features 4 sizes Cooling capacity from 22,1 to 36,2 kW One scroll compressor New control Scroll compressors

accessories and options Automatic circuit breaker (standard) Coil grilles Coils treatment Desuperheater Fan speed control (standard) Power factor corrector capacitors Sequence phases control (standard) Softstart

22-36 kW

air cooled

Scroll 410a

-20 -15 -10 -5 0 5

10 15 20 25 30 35 40 45 50 55 60

-12 -10 -8 -6 -4 -2 0 2 4 6 8 10 12 14

Air T

empe

ratu

re (°

C)

Evaporating Temperature (°C)

SyScroll 20-35 air re - Cooling operation

Page 165: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Condensing unit |

Condensing unit

163

technical feature

SyScroll 20-35 Air RE 20 25 30 35Cooling Capacity (1) kW 22,1 26,4 29,9 36,2Input Power (1) kW 7,23 7,96 9,56 12,3Part load steps % 0-50-100 0-50-100 0-50-100 0-44-56-100Power supply V/Ph/Hz 400/3/50Startup type DirectRefrigerantType HFC 410ANumber of refrigerant circuits 1CompressorQty 2Type ScrollCrankcase heater W 70 90 90 90CondenserQty 1FanNumber 2Type AxialAir Flow Rate mc/h 10.957 10.425 10.425 9.919Total Input Power kW 0,54 0,54 0,54 0,55Refrigerant connectionType To be brazedLiquid diameter inch 1”1/2Gas diameter inch 7/8" 1" 1/8WeightShipping kg 228 259 263 278DimensionsLength mm 1.477 1.477 1.477 1.477Width mm 539 539 539 539Height mm 1.615 1.615 1.615 1.615Acoustical dataSound Power Level dB(A) 73 74 74 75Sound Pressure Level* dB(A) 41 42 42 43

(1) Data refers to 7°C evaporating temperature and 35°C condenser inlet air temperature(*) Sound pressure level at 10 m.- Values refers to ISO Standard 3744 with parallepiped shape.

Page 166: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Condensing unit164

SyScroll 40-75 Air RE

Evaporating limit1 °C from -13 to +14

Ambient Air temperature-2 °C from -18 to +44S2 °C from -18 to +40HPF °C refer to graphic

1 Till to air temperature -12, between -3°C to +40°C with fan speed control.2 Till to air temperature -18°C with fan speed control.

Condensing unitSyScroll 40-75 air re

operating limit (to be confirmed following selection software issue)

technical features 6 sizes Cooling capacity from 43,2 to 84,5 kW 2 versions:

STD (Standard) HPF (High Pressure Fans)

2 acoustic versions: - (Basic Low Noise) S (Extra Low Noise)

One refrigerant circuit Scroll compressors

accessories and options Automatic circuit breaker Coils treatments Compressors acoustic box as standard Compressors jackets (standard on S) Desuperheater Fan speed control (standard) Overload protection for compressors Power factor corrector capacitors Sequence phases control (standard) Sofstart Unit protection grilles (standard)

25-37 kW

air cooled

Scroll 410a

-25-20-15-10

-505

101520253035404550

Evaporating Temperature (°C)

Air T

empe

ratu

re (°

C)

-13 -14 -12 -11 -10 -9 -8 -7 -6 -5 -4 -3 -2 -1 0 1 2 3 4 5 6 16151413121110987

SyScroll 40-75 air re -

-25-20-15-10

-505

1015202530354045

Evaporating Temperature(°C)

Air T

empe

ratu

re (°

C)

-13 -14 -12 -11 -10 -9 -8 -7 -6 -5 -4 -3 -2 -1 0 1 2 3 4 5 6 16151413121110987

SyScroll 40-75 air re S version

-25-20-15-10

-505

1015

2025303540455055

Evaporating Temperature (°C)

Air T

empe

ratu

re (°

C)

-13 -14 -12 -11 -10 -9 -8 -7 -6 -5 -4 -3 -2 -1 0 1 2 3 4 5 6 16151413121110987

40-50

60-75

SyScroll 40-75 air re hPF version

Page 167: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Condensing unit |

Condensing unit

165

technical feature

SyScroll 40-75 Air RE 40 45 50 60 65 75Cooling capacity1 kW 43,2 48,8 56,9 67,4 73,8 84,5Power input1 kW 13,0 15,3 17,8 18,7 21,6 26,3Part load steps % 0-50-100 0-50-100 0-50-100 0-44-56-100 0-50-100 0-50-100Power supply V/Ph/Hz 400/3/50Startup type DirectRefrigerantType HFC 410ANumber of refrigerant circuits 1CompressorQty 2Type ScrollCrankcase heater W 90CondenserQty 1Frontal surface mm 2.160x1.200 2.160x1.200 2.160x1.200 2.650x1.200 2.650x1.200 2.650x1.200Number of rows 2 2 3 3 3 3FanQty 1Air flow m3/h 14.000 14.000 13.200 21.100 21.100 21.100Speed rpm/min 680 680 680 900 900 900Power input kW 0,98 0,98 0,98 2,00 2,00 2,00Refrigerant connectionType To be brazedInlet diameter inch ⅝” ⅝” ⅝” ⅞” ⅞” ⅞”Outlet diameter inch 1⅜” 1⅜” 1⅜” 1⅜” 1⅜” 1⅜”WeightShipping kg 391 399 422 456 466 469DimensionsLength mm 1.750 1.750 1.750 2.200 2.200 2.200Width mm 1.100 1.100 1.100 1.100 1.100 1.100Height mm 1.580 1.580 1.580 1.580 1.580 1.580Acoustical dataSound power level2 dB(A) 80,5 81,0 81,0 85,5 85,6 85,8Sound pressure level3 dB(A) 48,9 49,4 49,4 53,8 53,9 54,1

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard. 2 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.3 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.

SyScroll 40-75 air re hPF version

Page 168: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Condensing unit166

technical feature

SyScroll 40-75 Air RE S 40 45 50 60 65 75Cooling capacity1 kW 41,6 46,7 54,0 64,9 70,7 80,6Power input1 kW 13,7 16,3 19,1 19,7 22,8 28,1Part load steps % 0-50-100 0-50-100 0-50-100 0-44-56-100 0-50-100 0-50-100Power supply V/Ph/Hz 400/3/50Startup type DirectRefrigerantType HFC 410ANumber of refrigerant circuits 1CompressorQty 2Type ScrollCrankcase heater W 90CondenserQty 1Frontal surface mm 2.160x1.200 2.160x1.200 2.160x1.200 2.650x1.200 2.650x1.200 2.650x1.200Number of rows 2 2 3 3 3 3FanQty 1Air flow m3/h 11.000 11.000 10.300 16.000 16.000 16.000Speed rpm/min 530 530 530 720 720 720Power input kW 0.57 0.57 0.57 1.27 1.27 1.27Refrigerant connectionType To be brazedInlet diameter inch ⅝” ⅝” ⅝” ⅞” ⅞” ⅞”Outlet diameter inch 1⅜” 1⅜” 1⅜” 1⅜” 1⅜” 1⅜”WeightShipping kg 391 399 422 456 466 469DimensionsLength mm 1.750 1.750 1.750 2.200 2.200 2.200Width mm 1.100 1.100 1.100 1.100 1.100 1.100Height mm 1.580 1.580 1.580 1.580 1.580 1.580Acoustical dataSound power level2 dB(A) 74,0 75,3 75,3 78,0 78,5 79,0Sound pressure level3 dB(A) 42,4 43,7 43,7 46,3 46,8 47,3

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard. 2 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.3 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.

Page 169: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Condensing unit |

Condensing unit

167

technical feature

SyScroll 40-75 Air RE HPF 40 45 50 60 65 75Cooling capacity1 kW 45,8 52,1 61,3 68,4 75,2 85,9Power input1 kW 11,9 13,9 16,0 18,3 21,1 25,6Part load steps % 0-50-100 0-50-100 0-50-100 0-44-56-100 0-50-100 0-50-100Power supply V/Ph/Hz 400/3/50Startup type DirectRefrigerantType HFC 410ANumber of refrigerant circuits 1CompressorQty 2Type ScrollCrankcase heater W 90CondenserQty 1Frontal surface mm 2.160x1.200 2.160x1.200 2.160x1.200 2.650x1.200 2.650x1.200 2.650x1.200Number of rows 2 2 3 3 3 3FanQty 1Air flow m3/h 25.284 25.284 24.300 25.284 25.284 25.284Speed rpm/min 1.110 1.110 1.110 1.110 1.110 1.110Power input kW 2.67 2.67 2.67 2.67 2.67 2.67Refrigerant connectionType To be brazedInlet diameter inch ⅝” ⅝” ⅝” ⅞” ⅞” ⅞”Outlet diameter inch 1⅜” 1⅜” 1⅜” 1⅜” 1⅜” 1⅜”WeightShipping kg 391 399 422 456 466 469DimensionsLength mm 1.750 1.750 1.750 2.200 2.200 2.200Width mm 1.100 1.100 1.100 1.100 1.100 1.100Height mm 1.685 1.685 1.685 1.685 1.685 1.685

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard.

Page 170: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Condensing unit168

Condensing unitSysaqua 25-125 C

technical features Coolling only 32 to 136 kW R410A refrigerant Units are optimized for partial load operation High ESEER 2 compressors fitted in tandem for all the range with two

capacity steps Sizes 25 to 125, three capacity steps with an immediate return

on investment versus the inverter units Low noise version supplied as standard, extra low noise

version for the XLS units (AQUAC 45-125 only) Refrigerant circuit is completely closed in a separate

compartment in order to reduce noise level (sizes 25 to 40) Great accessibility to internal components for service

mantenance Wide operating limits Fan speed control for low ambient operation in cooling mode

down to -10 °C as STD Phase sequence monitor supplied as standard Small footprint, allowing shipping and handling costs to be

saved, units find easily a place to be installed Suction and liquid line shut-off valve as STD, Ideal to be

connected with air handling unit accessories and options Condenser protective grid Reinforced acoustic insulation (XLS version) Coil with epoxy treatment LP/HP gauges Power supply without neutral kit

operating limit (to be confirmed following selection software issue)

-15-10

-505

10152025303540455055

-14 -13 -12 -11 -10 -9 -8 -7 -6 -5 -4 -3 -2 -1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

Cond

ense

r inl

et te

mpe

ratu

re (°

C)

Evaporating temperature (°C)

Running with fan speed control STD

32-136 kW

air cooled

410aScroll

Soft starter Anti-vibration rubber pads

Page 171: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Condensing unit |

Condensing unit

169

SysAqua 25-125 C 25 30 35 40 45Cooling capacity kW 32,5 33,7 43,1 44,8 57,3Power input kW 9,1 9,8 13,9 14,1 17,4Total EER 100%1 3,57 3,44 3,10 3,18 3,29Power supply 400V/3~N/50HzStartup type Direct Maximum operating current A 22,5 24,5 32 34 41Startup current A 64 77,5 118,5 119,5 134Refrigerant (units are delivered with a neutral charge of Nitrogen)Type HFC 410ANumber of refrigerant circuits 1CompressorsQty 2 2 2 2 2Type Scroll Part load steps % 0/50/100 0/50/100 0/50/100 0/50/100 0/50/100Crankcase heater W 2 x 40 2 x 70 2 x 70 2 x 70 2 x 90Coil Qty 1 1 1 1 1Total coil face area per coil m2 2,4 2,4 2,8 2,8 4,2FanQty 1 1 1 1 1Air flow m³/h 13.000 13.000 16.000 16.000 22.500Speed rpm 930 930 650 650 900Power input each fan W 900 900 930 930 2.100Refrigerant ConnectionsLiquid line inch 5/8” 5/8” 5/8” 5/8” 5/8”Suction line inch 1”1/8 1”1/8 1”1/8 1”1/8 1”5/8DimensionsLength mm 1.000 1.000 1.000 1.000 2.180Width mm 1.000 1.000 1.000 1.000 1.160Height mm 1.983 1.983 1.983 1.983 1.986Weight Operating kg 260 270 280 280 490Acoustical dataSound power level dB(A) 75 75 76 76 80

technical feature

1 Air: 35 °C. Evaporating temperature: +7 °C.

Page 172: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Condensing unit170

SysAqua 25-125 C 55 65 75 90 105 125Cooling capacity kW 64,5 72,3 79,3 103,9 119,6 136,4Power input kW 20,2 22,5 25,3 35 38,8 47,1Total EER 100%1 3,19 3,21 3,13 2,97 3,08 2,89Power supply 400V/3~N/50HzStartup type DirectMaximum operating current A 45 59,5 64,5 79,5 87,5 103,5Startup current A 141 201,5 206,5 266,5 313,5 351,5Refrigerant (units are delivered with a neutral charge of Nitrogen)Type HFC 410ANumber of refrigerant circuits 1Compressors Qty 2 2 2 2 2 2Type ScrollPart load steps % 0/45/55/100 0/40/60/100 0/45/55/100 0/45/55/100 0/40/60/100 0/33/67/100Crankcase heater W 2 x 90 2 x 90 2 x 90 90/140 90/140 90/140Coil(s)Qty 1 2 2 2 2 2Total coil face area per coil 4,2 5,55 5,55 6,4 6,4 6,4Fan(s)Qty 1 2 2 2 2 2Air flow m³/h 22.500 30.000 30.000 42.000 42.000 42.000Speed rpm 900 650 650 860 860 860Power input each fan W 2.100 930 930 2.100 2.100 2.100Refrigerant connectionsLiquid line inch 5/8” 5/8” 5/8” 7/8” 7/8” 7/8”Suction line inch 1”5/8 1”5/8 1”5/8 1”5/8 1”5/8 1”5/8DimensionsLength mm 2.180 2.180 2.180 2.180 2.180 2.180Width mm 1.160 1.160 1.160 1.160 1.160 1.160Height mm 1.986 1.986 1.986 2.286 2.286 2.286Weight Operating kg 490 560 560 740 850 870Acoustical dataSound power level dB(A) 79 79 79 82 82 82

technical feature

1 Air: 35 °C. Evaporating temperature: +7 °C.

Page 173: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

CondenSing unit

Page 174: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Condensing unit172

technical feature 5 sizes Cooling capacity from 94,3 to 142,4 kW Fans version:

STD (standard) HT (high temperature) HPF (high pressure fans)

2 acoustic versions: - version (Basic Low Noise) S version (Super Low Noise)

One refrigerant circuit 2 scroll compressors (1 tandem) Microchannel coils E-Coating coil treatment as standard

accessories and options Coils treatments Unit protection grilles Softstart BMS interface Overload protection for compressors Automatic circuit breaker Fan speed control (standard) Power factor corrector capacitors Sequence phases control (standard) Compressors box (standard) Compressors jackets (standard on Super Low Noise)

Condensing unitSyScroll 85-135 air re

SyScroll 85-135 Air RE85 95 105 120 135

Min Max Min Max Min Max Min Max Min Max

Ambient Air

Air enteringtemperature(cooling)

- °C from +10 to +45S °C from -10 to +43HT-HPF °C from -12 to +47

Externalstatic pressure

Standard fans Pa 0

High pressure fans (HPF) Pa <120

Minimum capacity step % 50 43 50 44 50Power supply voltage1 V 400 V / 3 Ø / 50 Hz (nominal)

operating limit (to be confirmed following selection software issue)

1 Voltage 400V +/- 10%.

94-142 kW

air cooled

410aScroll

Page 175: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Condensing unit |

Condensing unit

173

Model 85 95 105 120 135

SyScroll 85-135 Air RE - (STD)Nominal cooling capacity 1 kW 94,3 105,0 116,4 130,5 142,4Power Input2 kW 24,8 29,2 34,6 39,8 45,1Refrigerant In connections inch 1 5/8” 1 5/8” 2 1/8” 2 1/8” 2 1/8”Refrigerant Out connections inch 7/8” 7/8” 1 1/8” 1 1/8” 1 1/8”SyScroll 85-135 Air RE_ - (S)Nominal cooling capacity 1 kW 90,2 99,8 112,4 125,2 135,7Power Input2 kW 26,3 31,3 36,7 42,5 48,4Refrigerant In connections inch 1 5/8” 1 5/8” 2 1/8” 2 1/8” 2 1/8”Refrigerant Out connections inch 7/8” 7/8” 1 1/8” 1 1/8” 1 1/8”WeightShipping kg 625 697 765 817 840Additional weightHT/HPF Versions kg 20 20 20 20 20DimensionsLength mm 3.000 3.500Width mm 1.100Height mm 2.250

technical feature

1 Data refers to 7°C evaporating temperature and 35°C condenser air temperature.2 Input power (only compressors).N.B. For additional technical data regarding compressors, fan motors and noise, please refer to correspondant CO unit.

-20 -17 -12 -7 -2 3 8 13

-15 -10

-5 0 5

10 15 20 25 30 35 40 45 50

OAT

(°C)

SST (°C)

FSC

- Version

-20 -17 -12 -7 -2 3 8 13

-15 -10

-5 0 5

10 15 20 25 30 35 40 45 50

OAT

(°C)

SST (°C)

S Version

-20 -17 -12 -7 -2 3 8 13

-15 -10

-5 0 5

10 15 20 25 30 35 40 45 50

OAT

(°C)

SST (°C)

ht-hPF Version

Page 176: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Condensing unit174

Condensing unitaQVC 85-140

operating limit (to be confirmed following selection software issue)

AQVC 85-14085 95 105 115 125 140

Min Max Min Max Min Max Min Max Min Max Min MaxEvaporating limit °C from +1 to +15

Air temperature

BLN °C from 0 to +48 from 0 to +48 from 0 to +48 from 0 to +48 from 0 to +48 from 0 to +48

ELN °C from -18 to +45

from -18 to +45

from -18 to +45

from -18 to +45

from -18 to +45

from -18 to +45

HT °C from 0 to +50 from 0 to +50 from 0 to +50 from 0 to +50 from 0 to +50 from 0 to +50

technical features 6 sizes Cooling capacity from 92,1 to 151 kW 2 versions:

STD (Standard) SIF (Special Inverter Fans)

2 acoustic versions: BLN (Basic Low Noise) ELN (Extra Low Noise)

Two refrigerant circuits 4 Scroll compressors (tandem) E-Coating coil treatment as standard

accessories and options Automatic circuit breaker BMS interface Coils treatments Compressors acoustic box as standard Compressors jackets Fan speed control Overload protection for compressors Power factor corrector capacitors Sequence phases control as standard Sofstart Unit protection grilles

94-151 kW

air cooled

410aScroll

Page 177: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Condensing unit |

Condensing unit

175

technical feature

AQVC STD/HSE/HPF 85-140 BLN 85 95 105 115 125 140Cooling capacity1 kW 92,1 103,2 113,2 121,8 134,7 151,0Power input1 kW 25,3 29,3 32,0 34,9 38,3 43,4

Part load steps % 0-25-5075-100

0-25-5075-100

0-24-47-74-100

0-25-5075-100

0-22-43-72-100

0-25-5075-100

Power supply V/Ph/Hz 400/3/50Startup type DirectRefrigerantType HFC 410ANumber of refrigerant circuits 2CompressorQuantità 4Type ScrollCrankcase heater W 90 90 90 90 90 90CondenserQty 2Frontal surface mm 2.000х1.200 2.000х1.200 2.000х1.200 2.000х1.200 2.600х1.200 2.600х1.200Connection type To be brazedInlet diameter inch ⅝” ⅝” ⅝” ⅝” ⅞” ⅞”Outlet diameter inch 1⅜” 1⅜” 1⅜” 1⅜” 1⅜” 1⅜”FanQty 2Air flow m3/h 34.000 34.000 33.200 32.400 44.000 42.800Speed rpm/min 690 690 690 690 900 900Power input kW 2,1 2,1 2,1 2,1 3,4 3,4WeightShipping kg 971 983 1.013 1.043 1.066 1.142DimensionsLength mm 2.555 2.555 2.555 2.555 3.155 3.155Width mm 1.095 1.095 1.095 1.095 1.095 1.095Height mm 2.185 2.185 2.185 2.185 2.185 2.185Acoustical dataSound power level2 dB(A) 85 85 85 85 89 89Sound pressure level at 10 m3 dB(A) 53 53 53 53 57 57

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard. 2 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.3 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.

Page 178: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Condensing unit176

technical feature

AQVC STD/HSE 85-140 ELN 85 95 105 115 125 140Cooling capacity1 kW 89 99,4 108,7 116,6 131,6 147,2Power input1 kW 26,8 31,3 34,3 37,5 39,8 45,2

Part load steps % 0-25-5075-100

0-25-5075-100

0-24-47-74-100

0-25-5075-100

0-22-43-72-100

0-25-5075-100

Power supply V/Ph/Hz 400/3+N/50Startup type DirectRefrigerantType HFC 410ANumber of refrigerant circuits 2CompressorQty 4Type ScrollCrankcase heater W 90 90 90 90 90 90CondenserQty 2Frontal surface mm 2.000х1.200 2.000х1.200 2.000х1.200 2.000х1.200 2.600х1.200 2.600х1.200Connection type To be brazedInlet diameter inch ⅝” ⅝” ⅝” ⅝” ⅞” ⅞”Outlet diameter inch 1⅜” 1⅜” 1⅜” 1⅜” 1⅜” 1⅜”FanQty 2Air flow m3/h 25.200 25.200 24.600 24.000 36.500 35.000Speed rpm/min 500 500 500 500 690 690Power input kW 1,8 1,8 1,8 1,8 2,1 2,1WeightShipping kg 1.001 1.013 1.043 1.073 1.096 1.172DimensionsLength mm 2.555 2.555 2.555 2.555 3.155 3.155Width mm 1.095 1.095 1.095 1.095 1.095 1.095Height mm 2.185 2.185 2.185 2.185 2.185 2.185Acoustical dataSound power level2 dB(A) 82 82 82 82 86 86Sound pressure level at 10 m3 dB(A) 50 50 50 50 54 54

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard. 2 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.3 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.

Page 179: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Condensing unit |

Condensing unit

177

technical feature

AQVC HT 85-140 85 95 105 115 125 140Cooling capacity1 kW 95 106,8 117,7 127 137,2 153,8Power input2 kW 23,9 27,4 29,8 32,3 37,1 42,1

Part load steps % 0-25-5075-100

0-25-5075-100

0-24-47-74-100

0-25-5075-100

0-22-43-72-100

0-25-5075-100

Power supply V/Ph/Hz 400/3+N/50Startup type DirectRefrigerantType HFC 410ANumber of refrigerant circuits 2CompressorQty 4Type ScrollCrankcase heater W 90 90 90 90 90 90CondenserQty 2Frontal surface mm 2.000х1.200 2.000х1.200 2.000х1.200 2.000х1.200 2.600х1.200 2.600х1.200Connection type To be brazedInlet diameter inch ⅝” ⅝” ⅝” ⅝” ⅞” ⅞”Outlet diameter inch 1⅜” 1⅜” 1⅜” 1⅜” 1⅜” 1⅜”FanQty 2Air flow m3/h 49.700 49.700 48.950 48.200 52.200 50.700Speed rpm/min 1.130 1.130 1.130 1.130 1.130 1.130Power input kW 4,6 4,6 4,6 4,6 4,6 4,6WeightShipping kg 971 983 1.013 1.043 1.066 1.142DimensionsLength mm 2.555 2.555 2.555 2.555 3.155 3.155Width mm 1.095 1.095 1.095 1.095 1.095 1.095Height mm 2.185 2.185 2.185 2.185 2.185 2.185Acoustical dataSound power level3 dB(A) 95 95 95 95 95 95Sound pressure level at 10 m4 dB(A) 63 63 63 63 63 63

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature. 2 Input power (only compressors).3 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard.4 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.

Page 180: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Condensing unit178

Condensing unitSyScroll 140-360 air eVo re

technical feature 9 sizes Cooling capacity from 165 to 394,5 kW Fans versions:

STD (Standard) EC (Inverter Fans) HT (High Temperature) HPF (High Pressure Fans)

Acoustic versions: - (Basic Low Noise) L (Low Noise) S (Super Low Noise)

Two refrigerant circuits 4 Scroll compressors E-Coating coil treatment as standard

accessories and options Automatic circuit breaker BMS interface Coils treatments Compressors acoustic box as standard Compressors jackets (standard as Super Low Noise) Fan speed control standard Overload protection for compressors Power factor corrector capacitors Sequence phases control as standard Softstarter Unit protection grilles

operating limit (to be confirmed following selection software issue)

SyScroll 140-360 Air EVO RE140-360

Min MaxEvaporating temperature °C from +3 to +15

Ambient

- °C from +5 to +48L °C from +0 to +46S °C from -14 to +44EC-HT °C from -18 to +50

165-395 kW

air cooled

410aScroll

Page 181: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Condensing unit |

Condensing unit

179

technical feature

Model 140 170 200 230 260 280 300 330 360

SyScroll 140-360 Air EVO RE (STD/EC)Nominal cooling capacity1 kW 165,0 193,4 216,3 250,3 288,4 312,7 337,2 361,2 394,5Input power2 kW 40,6 50,4 54,1 66,1 74,2 81,4 87,5 91,1 103,4

Refrigerant In connections inch 1 5/8” 1 5/8” 1 5/8” - 2 1/8”

1 5/8” - 2 1/8”

1 5/8” - 2 1/8”

1 5/8” - 2 1/8” 2 1/8” 2 1/8” 2 1/8”

Refrigerant Out connections inch 7/8” 7/8” 7/8” - 1 1/8”

7/8” - 1 1/8”

7/8” - 1 1/8”

7/8” - 1 1/8” 1 1/8” 1 1/8” 1 1/8”

SyScroll 140-360 Air EVO RE L (STD/EC)Nominal cooling capacity1 kW 165,0 193,4 216,3 250,3 288,4 312,7 337,2 361,2 394,5Input power2 kW 42,5 52,8 56,2 69,3 77,6 85,3 91,9 95,3 108,6

Refrigerant In connections inch 1 5/8” 1 5/8” 1 5/8” - 2 1/8”

1 5/8” - 2 1/8”

1 5/8” - 2 1/8”

1 5/8” - 2 1/8” 2 1/8” 2 1/8” 2 1/8”

Refrigerant Out connections inch 7/8” 7/8” 7/8” - 1 1/8”

7/8” - 1 1/8”

7/8” - 1 1/8”

7/8” - 1 1/8” 1 1/8” 1 1/8” 1 1/8”

SyScroll 140-360 Air EVO RE S (STD/EC)Nominal cooling capacity1 kW 149,2 172,1 198,5 225,0 261,4 281,2 305,2 329,9 355,8Input power2 kW 45,7 56,7 60,0 75,6 84,2 93,0 100,4 103,5 118,6

Refrigerant In connections inch 1 5/8” 1 5/8” 1 5/8” - 2 1/8”

1 5/8” - 2 1/8”

1 5/8” - 2 1/8”

1 5/8” - 2 1/8” 2 1/8” 2 1/8” 2 1/8”

Refrigerant Out connections inch 7/8” 7/8” 7/8” - 1 1/8”

7/8” - 1 1/8”

7/8” - 1 1/8”

7/8” - 1 1/8” 1 1/8” 1 1/8” 1 1/8”

SyScroll 140-360 Air EVO RE HTNominal cooling capacity1 kW 166,6 195,6 218,2 252,8 291,2 315,9 340,5 364,4 398,4Input power2 kW 40,1 49,8 53,6 65,2 73,3 80,2 86,3 89,9 101,9

Refrigerant In connections inch 1 5/8” 1 5/8” 1 5/8” - 2 1/8”

1 5/8” - 2 1/8”

1 5/8” - 2 1/8”

1 5/8” - 2 1/8” 2 1/8” 2 1/8” 2 1/8”

Refrigerant Out connections inch 7/8” 7/8” 7/8” - 1 1/8”

7/8” - 1 1/8”

7/8” - 1 1/8”

7/8” - 1 1/8” 1 1/8” 1 1/8” 1 1/8”

WeightShipping kg 1.107 1.150 1.598 1.695 1.875 1.875 2.364 2.433 2.445Additional weightEC/HT/HPF versions kg 30 30 50 50 60 60 70 80 80DimensionsLength mm 4.000 4.000 3.500 3.500 3.500 3.500 4.550 4.550 4.550Width mm 1.100 1.100 2.150 2.150 2.150 2.150 2.150 2.150 2.150Height mm 2.600 2.600 2.600 2.600 2.600 2.600 2.600 2.600 2.600

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature.2 Input power (only compressors).

Page 182: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Condensing unit180

Condensing unitVlC 604-1204

technical features 7 sizes Cooling capacity from 174 to 347 kW 4 versions:

STD (Standard) HT (High Temperature) HPF (High Pressure Fans)

3 acoustic versions: BLN (Basic Low Noise) LN (Low Noise) ELN (Extra Low Noise)

Two refrigerant circuits Scroll compressors E-Coating coil treatment as standard

accessories and options Automatic circuit breaker BMS interface Compressors acoustic box (standard) Compressors jackets (standard on ELN) Fan speed control (-18°C) Overload protection for compressors Power factor corrector capacitors Sequence phases control (standard) Sofstart Unit protection grilles

174-347 kW

air cooled

410aScroll

Page 183: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Condensing unit |

Condensing unit

181

operating limit (to be confirmed following selection software issue)

VLC 604-804604 704 804

Min Max Min Max Min Max

Temperatura di evaporazione °C from +3 to +15

Temperatura aria

BLN °C from -5 to +471 from -5 to +471 from 0 to +461

LN/ELN °C from -5 to +451 from -5 to +451 from 0 to +441

HT °C from -18 to +491 from -18 to +491 from -18 to +481

VLC 904-1204904 1004 1104 1204

Min Max Min Max Min Max Min Max

Evaporating temperature °C from +3 to +15

Air temperture

BLN °C from 0 to +461 from 0 to +461 from 0 to +451 from 0 to +451

LN/ELN °C from 0 to +451 from 0 to +441 from 0 to +421 from 0 to +421

HT °C from -18 to +491 from -18 to +481 from -18 to +471 from -18 to +471

1 At high pressure 40,5 bar.

1 At high pressure 40,5 bar.

Page 184: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Condensing unit182

technical feature

VLC STD/HPF 604-1204 BLN 604 704 804 904 1004 1104 1204Cooling capacity1 kW 174,0 199,0 224,0 258,0 283,0 315,0 347,0Power input1 kW 52,5 63,0 69,0 79,0 83,0 98,0 112,0

Part load steps % 28-57-78-100

20-50-70-100

25-50-75-100

28-50-78-100

25-50-75-100

23-50-73-100

25-50-75-100

RefrigerantType HFC 410ANumber of refrigerant circuits 2CompressorType ScrollQty 4CondenserQty 2Total coil face area per coil m3 3,5 4,8 4,8 4,8 4,8 4,8 4,8FanQty 3 3 3 4 4 4 4Speed rpm/min 900 900 900 900 900 900 900Air flow m3/h 63.000 68.300 68.300 85.000 80.000 75.500 75.500Power input kW 5,7 5,7 5,7 7,6 7,6 7,6 7,6Power input* kW 4,0 4,0 4,0 5,3 5,3 5,3 5,3Available static pressure Pa from 0 to 120 Pa*

Refrigerant connectionInlet diameter inch ⅞” ⅞” ⅞” 1⅛” 1⅛” 1⅛” 1⅛”Outlet diameter inch 1⅝” 1⅝” 1⅝” 2⅛” 2⅛” 2⅛” 2⅛”DimensionsLength mm 3.300 4.300 4.300 4.300 4.300 4.300 4.300Width mm 1.100 1.100 1.100 1.100 1.100 1.100 1.100Height mm 2.300 2.300 2.300 2.300 2.300 2.300 2.300WeightShipping kg 1.300 1.490 1.615 1.700 1.825 1.910 1.920Additional weightsVersion HPF kg 10 10 10 15 15 15 15Acoustical dataSound power level2 dB(A) 93 93 93 94 94 95 95Sound pressure level at 10 m3 dB(A) 61 61 61 62 62 63 63

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature.2 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard. 3 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.* For HPF version with Special Inverter Fans.

Page 185: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Condensing unit |

Condensing unit

183

technical feature

VLC STD 604-1204 LN 604 704 804 904 1004 1104 1204Cooling capacity1 kW 169,0 194,0 218,0 251,0 272,5 301,0 330,0Power input1 kW 55,0 66,0 73,0 83,0 88,0 104,0 121,0

Part load steps % 28-57-78-100

20-50-70-100

25-50-75-100

28-50-78-100

25-50-75-100

23-50-73-100

25-50-75-100

RefrigerantType HFC 410ANumber of refrigerant circuits 2CompressorType ScrollQty 4CondenserQty 2Total coil face per coil m3 3,5 4,8 4,8 4,8 4,8 4,8 4,8FanQty 3 3 3 4 4 4 4Speed rpm/min 700 700 700 700 700 700 700Air flow m3/h 47.300 52.200 52.200 63.700 58.800 54.900 54.900Power input kW 3,6 3,6 3,6 4,8 4,8 4,8 4,8Available static pressure Pa 0Refrigerant connectionLiquid diameter inch ⅞” ⅞” ⅞” 1⅛” 1⅛” 1⅛” 1⅛”Gas diameter inch 1⅝” 1⅝” 1⅝” 2⅛” 2⅛” 2⅛” 2⅛”DimensionsLength mm 3.300 4.300 4.300 4.300 4.300 4.300 4.300Width mm 1.100 1.100 1.100 1.100 1.100 1.100 1.100Height mm 2.300 2.300 2.300 2.300 2.300 2.300 2.300WeightShipping kg 1.300 1.490 1.615 1.700 1.825 1.910 1.920Acoustical dataSound power level2 dB(A) 87 87 87 88 88 89 89Sound pressure level at 10 m3 dB(A) 55 55 55 56 56 57 57

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature.2 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard. 3 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.

Page 186: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Condensing unit184

technical feature

VLC STD 604-1204 ELN 604 704 804 904 1004 1104 1204Cooling capacity1 kW 164,5 188,5 211,0 244,0 264,5 292,0 319,0Power input1 kW 57,0 69,0 76,5 86,5 91,5 108,0 127,0

Part load steps % 28-57-78-100

20-50-70-100

25-50-75-100

28-50-78-100

25-50-75-100

23-50-73-100

25-50-75-100

RefrigerantType HFC 410ANumber of refrigerant circuits 2CompressorType ScrollQty 4CondenserQty 2Total coil face per coil m3 3,5 4,8 4,8 4,8 4,8 4,8 4,8FanQty 3 3 3 4 4 4 4Speed rpm/min 550 550 550 550 550 550 550Air flow m3/h 38.500 41.800 41.800 52.000 48.900 46.200 46.200Power input kW 3 3 3 4 4 4 4Available static pressure Pa 0Refrigerant connectionLiquid diameter inch ⅞” ⅞” ⅞” 1⅛” 1⅛” 1⅛” 1⅛”Gas diameter inch 1⅝” 1⅝” 1⅝” 2⅛” 2⅛” 2⅛” 2⅛”DimensionsLength mm 3.300 4.300 4.300 4.300 4.300 4.300 4.300Width mm 1.100 1.100 1.100 1.100 1.100 1.100 1.100Height mm 2.300 2.300 2.300 2.300 2.300 2.300 2.300WeightShipping kg 1.335 1.525 1.650 1.735 1.865 1.950 1.960Acoustical dataSound power level2 dB(A) 83 83 83 84 84 85 85Sound pressure level at 10 m3 dB(A) 51 51 51 52 52 53 53

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature.2 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard. 3 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.

Page 187: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Condensing unit |

Condensing unit

185

technical feature

VLC HT 604-1204 604 704 804 904 1004 1104 1204Cooling capacity1 kW 176,0 201,0 226,5 261,0 286,5 318,0 353,0Power input1 kW 51,5 62,0 68,0 77,5 81,0 95,0 109,0

Part load steps % 28-57-78-100

20-50-70-100

25-50-75-100

28-50-78-100

25-50-75-100

23-50-73-100

25-50-75-100

RefrigerantType HFC 410ANumber of refrigerant circuits 2CompressorType ScrollQty 4CondenserQty 2Total coil face per coil m3 3,5 4,8 4,8 4,8 4,8 4,8 4,8FanQty 3 3 3 4 4 4 4Speed rpm/min 1.110 1.110 1.110 1.110 1.110 1.110 1.110Air flow m3/h 71.800 76.200 76.200 95.800 91.200 87.600 87.600Power input kW 7,2 6,9 6,9 9,6 9,9 10,0 10,0Available static pressure Pa 0Refrigerant connectionLiquid diameter inch ⅞” ⅞” ⅞” 1⅛” 1⅛” 1⅛” 1⅛”Gas diameter inch 1⅝” 1⅝” 1⅝” 2⅛” 2⅛” 2⅛” 2⅛”DimensionsLength mm 3.300 4.300 4.300 4.300 4.300 4.300 4.300Width mm 1.100 1.100 1.100 1.100 1.100 1.100 1.100Height mm 2.300 2.300 2.300 2.300 2.300 2.300 2.300WeightShipping kg 1.330 1.520 1.645 1.740 1.865 1.950 1960Acoustical dataSound power level2 dB(A) 99 99 99 100 100 100 100Sound pressure level at 10 m3 dB(A) 67 67 67 68 68 68 68

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature.2 Sound levels are at fully loaded conditions. Sound power level values refers to ISO 3744 standard. 3 Sound pressure levels refer to ISO 3744 standard, parallelepiped shape.

Page 188: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Condensing unit186

Condensing unitSyScroll 240-660 air re

technical features 10 sizes Cooling capacity from 267,5 to 726,7 kW 3 versions:

STD (Standard) HT (High Temperature) HPF (High Pressure Fans)

3 acoustic versions: - (Basic Low Noise) L (Low Noise) S (Super Low Noise)

Two refrigerant circuits 3/4/5/6 Scroll compressors Microchannel coils E-Coating coil treatment as standard

accessories and options Coils treatments Unit protection grilles Softstart BMS interface Overload protection for compressors Automatic circuit breaker Pressostatic fan speed control (standard) Power factor corrector capacitors Sequence phases control (standard) Compressors acoustic box (standard) Compressors jackets (standard )

267-727 kW

air cooled

410aScroll

Page 189: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Condensing unit |

Condensing unit

187

operating limit (to be confirmed following selection software issue)

SyScroll 240-360 Air RE240 270 290 320 360

Min Max Min Max Min Max Min Max Min Max

Ambient temp.

Air temp. cooling

- °C from +10 to +45 from +10 to +45 from +10 to +45 from +10 to +45 from +10 to +45L °C from +7 to +43 from +7 to +43 from +7 to +43 from +7 to +43 from +7 to +43S °C from -14 to +43 from -14 to +43 from -14 to +43 from -14 to +43 from -14 to +43HT-HPF °C from -18 to +47 from -18 to +47 from -18 to +47 from -18 to +47 from -18 to +47

External static pressure

Standard fans Pa 0High pressure fans Pa <120

Minimum capacity step % 31 33 30 27 23Power supply voltage1 V 400 V, 3 Ø, 50 Hz (nominal)

SyScroll 420-660 Air RE420 470 540 590 660

Min Max Min Max Min Max Min Max Min Max

Ambient temp.

Air temp. cooling

- °C from +10 to +45 from +10 to +45 from +10 to +45 from +10 to +45 from +10 to +45L °C from +7 to +43 from +7 to +43 from +7 to +43 from +7 to +43 from +7 to +43S °C from -14 to +43 from -14 to +43 from -14 to +43 from -14 to +43 from -14 to +43HT-HPF °C from -18 to +47 from -18 to +47 from -18 to +47 from -18 to +47 from -18 to +47

External static pressure

Standard fans Pa 0High pressure fans Pa <120

Minimum capacity step % 31 33 30 27 23Power supply voltage1 V 400 V, 3 Ø, 50 Hz (nominal)

1 Voltage 400V +/- 10%.

1 Voltage 400V +/- 10%.

- version

-20 -15 -10

-5 0 5

10 15 20 25 30 35 40 45 50

-17 -12 -7 -2 3 8 13

OAT

(°C)

LWT (°C)

SFC

l version

-20 -15 -10

-5 0 5

10 15 20 25 30 35 40 45 50

-17 -12 -7 -2 3 8 13

OAT

(°C)

LWT (°C)

SFC

S version

-20 -15 -10

-5 0 5

10 15 20 25 30 35 40 45 50

-17 -12 -7 -2 3 8 13

OAT

(°C)

LWT (°C)

ht-hPF version

-20 -15 -10

-5 0 5

10 15 20 25 30 35 40 45 50

-17 -12 -7 -2 3 8 13

OAT

(°C)

LWT (°C)

Page 190: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Condensing unit188

technical feature

Model 240 270 290 320 360

SyScroll 240-360 Air RE -Nominal cooling capacity1 kW 267,5 303,1 330,7 349,9 403,2Input power2 kW 76,8 92,8 95,4 103,8 119,0

Refrigerant In connections inch 1 5/8” - 2 1/8”

1 5/8” - 2 1/8”

1 5/8” - 2 1/8”

1 5/8” - 2 1/8” 2 1/8”

Refrigerant Out connections inch 7/8” - 1 1/8”

7/8” - 1 1/8”

7/8” - 1 3/8”

7/8” - 1 3/8”

1 1/8” - 1 3/8”

SyScroll 240-360 Air RE LNominal cooling capacity1 kW 256,7 288,7 316,7 333,9 385,4Input power2 kW 80,9 98,4 100,6 109,6 125,8

Refrigerant In connections inch 1 5/8” - 2 1/8”

1 5/8” - 2 1/8”

1 5/8” - 2 1/8”

1 5/8” - 2 1/8” 2 1/8”

Refrigerant Out connections inch 7/8” - 1 1/8”

7/8” - 1 1/8”

7/8” - 1 3/8”

7/8” - 1 3/8”

1 1/8” - 1 3/8”

SyScroll 240-360 Air RE SNominal cooling capacity1 kW 236,4 262,0 262,0 304,4 352,6Input power2 kW 89,2 109,2 109,2 120,7 139,2

Refrigerant In connections inch 1 5/8” - 2 1/8”

1 5/8” - 2 1/8”

1 5/8” - 2 1/8”

1 5/8” - 2 1/8” 2 1/8”

Refrigerant Out connections inch 7/8” - 1 1/8”

7/8” - 1 1/8”

7/8” - 1 1/8”

7/8” - 1 3/8”

1 1/8” - 1 3/8”

WeightShipping kg 1.670 1.671 1.790 1.802 2.185Additional weightHT/HPF versions kg 50 50 60 60 70DimensionsLength mm 3.500 3.500 3.500 3.500 4.550Width mm 2.150 2.150 2.150 2.150 2.150Height mm 2.600 2.600 2.600 2.600 2.600

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature.2 Input power (only compressors).

Page 191: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Condensing unit |

Condensing unit

189

technical feature

Model 420 470 540 590 660

SyScroll 420-660 Air RE -Nominal cooling capacity1 kW 466,2 518,8 594,9 650,4 726,7Input power2 kW 138,4 148,6 170,6 182,7 204,9

Refrigerant In connections inch 2 1/8” 2 1/8” - 2 5/8”

2 1/8” - 2 5/8” 2 5/8” 2 5/8”

Refrigerant Out connections inch 1 3/8” 1 3/8” 1 3/8” 1 3/8” 1 3/8”

SyScroll 420-660 Air RE LNominal cooling capacity1 kW 444,8 495,9 567,7 621,5 693,4Input power2 kW 146,1 157,0 180,1 193,1 216,4

Refrigerant In connections inch 2 1/8” 2 1/8” - 2 5/8”

2 1/8” - 2 5/8” 2 5/8” 2 5/8”

Refrigerant Out connections inch 1 3/8” 1 3/8” 1 3/8” 1 3/8” 1 3/8”

SyScroll 420-660 Air RE SNominal cooling capacity1 kW 405,5 453,6 517,5 568,1 632,2Input power2 kW 161,0 173,5 198,4 213,1 238,3

Refrigerant In connections inch 2 1/8” 2 1/8” - 2 5/8”

2 1/8” - 2 5/8” 2 5/8” 2 5/8”

Refrigerant Out connections inch 1 3/8” 1 3/8” 1 3/8” 1 3/8” 1 3/8”

WeightShipping kg 2.296 2.747 2.860 3.237 3.333Additional weightHT/HPF versions kg 80 90 100 110 120DimensionsLength mm 4.550 5.600 5.600 6.650 6.650Width mm 2.150 2.150 2.150 2.150 2.150Height mm 2.600 2.600 2.600 2.600 2.600

1 Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature.2 Input power (only compressors).

Page 192: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Residential Heat Pump

aquascop ht V2 6-18 kW 407C

aquascop ht split 6-18 kW 407C

Page 193: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Residential Heat Pump |

Residential Heat Pum

P

191

Product Range Capacity COP Flow Rate Acoustic Power Sound Size

(LxHxP) mm

Aqu@

scop

HT

V2

Aqu@scop HT V2 12.6

12.5 kW (A7°C/W35°C) 4.02 1.030 l/h 67dB(A) 1.458 x 516 x 1.308

8.2 kW (A-7°C/W35°C) 2.95 1.030 l/h 67dB(A) 1.458 x 516 x 1.308

Aqu@scop HT V2 14.7

15.4 kW (A7°C/W35°C) 4.18 1.370 l/h 1.458 x 516 x 1.308

10.9 kW (A-7°C/W35°C) 3.03 1.370 l/h 67dB(A) 1.458 x 516 x 1.308

Aqu@scopHT V2 18.9

18.4 kW (A7°C/W35°C) 4.02 1.580 l/h 67dB(A) 1.458 x 516 x 1.308

12.5 kW (A-7°C/W35°C) 3.08 1.580 l/h 67dB(A) 1.458 x 516 x 1.308

Aqu@

scop

HT

SPL

IT

Aqu@scop HT SPLIT 12.6

12.3 kW (A7°C/W35°C) 3.95 1.030 l/h outdoor unit

65 dB(A) 1.458 x 516 x 1.308

8.1 kW (A-7°C/W35°C) 2.90 1.030 l/h indoor unit

41 dB(A) 400 x 260 x 720

Aqu@scop HT SPLIT 14.7

15.15 kW (A7°C/W35°C) 3.84 1.230 l/h outdoor unit

65 dB(A) 1.458 x 516 x 1.308

10.7 kW (A-7°C/W35°C) 2.97 1.230 l/h indoor unit

41 dB(A) 400 x 260 x 720

Aqu@scop HT SPLIT 18.9

18.7 kW (A7°C/W35°C) 3.95 1.480 l/h outdoor unit

65 dB(A) 400 x 260 x 720

12.2 kW (A-7°C/W35°C) 3.02 1.480 l/h indoorunit

41 dB(A) 1.458 x 516 x 1.308

Selection guide High Temperature Residential Heat Pump

Page 194: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Residential Heat Pump 192

Split monobloc-unit high-temperature heat pumpaquascop ht V2

technical features Ideal for renovations as well as for new construction Water outlet temperature up to 65°C without external backup Ideal for boiler replacement Constant operation at +65°C with -20°C outdoors 6 to 18 kW of heating over 3 models Systemair patented “dual-stage” cascading compressors A single refrigerant fluid (preloaded up to 20 m) Electronic expansion valve and flow meter Low noise level Three-speed circulator pump Dual-zone management

Product advantages Very high performance, COP up to 4,5 SCOP class A++ Very low noise level No refrigerant links to be made Information screen with eight lines of text in French with

diagnosis assistance New “antifreeze” evaporator, 2 hours without defrosting

(no 4-mm fins) Inverter fans Easy maintenance Possibility of installing several heat pumps in cascade

(on request)

operating limit (to be confirmed following selection software issue)

systemair

Patented[ ]

6-18 kW 407C

10

15

20

25

30

35

40

45

50

55

60

65

70

-15- 10 -5 05 10 15 20-20-25 25

Double étage - mini retour d'eau

Double étage - maxi départ d'eau

Mono étage - maxi départ d'eau

MONO ÉTAGE

Outside temperature °C

Double stage – water return min.

DOUBLE STAGE

SINGLE STAGE

Double stage – water starting max.

Single stage – water starting max.

Wat

er fl

ow s

etpo

int (

°C)

Ce Standard

LO WTEMPERATURE

HEATER

HEATING/COOLIN GFLOOR

heating/Cooling Floor

loW-temPerature

radiator

boiler rePlaCement

boiler baCkuP

bi-zone domeStiC hot Water

Water Programme

Patented

reVerSible r407C Fluid outdoor oPerating

limitS in heating mode

high temPerature

uP to 65°C

ProduCt deVeloPed and manuFaCtured

in FranCe

°C-

Page 195: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Residential Heat Pump |

Residential Heat Pum

P

193

Accessories and options

7ACEL1592

Wired ambient thermostat- Adjustment of ambient temperature - Daily or weekly programming- Holiday programming, no-frost mode

7ACEL1593

Wireless thermostat with radio communicationSends the measured ambient temperature.

7ACFH0662

300-litre domestic hot water tank (and 2.5 kW of electrical resistance heaters) optimised with the operation of the Aqu@Scop HT- Three authorisation modes- Holiday mode- Programmable anti-legionella function- Management of the three-way valve / circulator pump couple- 3.1 m2 exchange surface 7ACFH0663

140-litre buffer tank / mixing tankNecessary when the volume of water in the installation is insufficient. It protects the heat pump against short cycles that can reduce the useful life of the compressors and improves operation during defrosting phases.

7ACFH0543

ON/OFF three-way valve Required for optional production of domestic hot water. Directs the produced hot water either towards the heating circuit or towards the domestic hot water tank. A second three-way valve is recommended for boiler-backup installation.

7ACFH0789 (top outlet)7ACEL1801

(bottom outlet)

Domestic hot water kitRequired when replacing existing installations. This kit, made up of a plate exchanger and a circulator pump, enables the production of domestic hot water using existing tanks (electric cumulus).

7ACFH0491 (alone)7ACFH0490 (kit)

Hydraulic kitFor connecting to the boiler, available alone or in a complete kit with the three-way valve.Made up of a set of assembled pipes and valves, a set of connectors with spherical-conical seat.

7ACFH0665

On-line electric heaterInstallation inside the building, offers two power stages (2 and 4 kW, or 6 kW in total).Provides extra heating when the heating demand is greater than the capacity of the heat pump. The Aqu@Scop HT is adjusted to manage the electric heater, or a boiler backup.

7ACFH0666

Decanting pot (sludge pot)Effectively separates the impurities from the heating circuit and collects them in a decanting chamber, where they can be bled off, even while the installation is operational.

7ACTL0472

Shock-absorbing support feetRaise the heat pump by 10cm, allow the evacuation of condensates and defrosting water.Their rubber design provides excellent shock absorption against the transmission of vibrations through solids.

Page 196: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Residential Heat Pump 194

AQuASCOP HT HT 12-6 HT 14-7 HT 18-9

OUTdOOr AIr REGIME 7°C

Dual compressor heating power / water regime 30/35°C kW 12,26 15,15 18,07COP* 3,95 3,84 3,95Single compressor heating power / water outlet 30/35°C kW 6,3 8,35 9,71COP* 4,12 4,35 4,52Single compressor heating power / water outlet 45°C kW 5,74 7,77 9,27COP* 3,09 3,31 3,47Dual compressor heating power / water outlet 55°C kW 5,25 7,08 8,58COP* 2,28 2,48 2,62

OUTdOOr AIr REGIME 2°C

Single compressor heating power / water outlet 35°C kW 10,31 13 15,32COP* 3,45 3,4 3,49

OUTdOOr AIr REGIME -7°C

Single compressor heating power / water outlet 35°C kW 8,05 10,68 12,21COP* 2,9 2,97 3,02Dual compressor heating power / water outlet 55°C kW 8,40 10,71 12,44COP* 2,25 2,31 2,35Dual compressor heating power / water outlet 65°C kW 8,33 10,69 12,01COP* 1,87 2,02 2,03

OUTdOOr AIr REGIME -15°C

Dual compressor heating power / water outlet 35°C kW 7,79 10,24 11,71COP* 2,80 2,86 2,9Dual compressor heating power / water outlet 65°C kW 8 10,27 11,5COP* 1,81 1,96 1,96

OUTdOOr UnIT

Sound power at 5 m in free field dB(A)Sound power dB(A) 65 65 65Compressor type (R407C) 2 scroll compressors in cascadeDimensions (WxDxH) mm 47 47 47Weight kg 184 209 213Refrigerant connections (gas/liquid) (0 to 25 metres) 5/8 - 3/8 Refrigerant connections (gas/liquid) (0 to 45 metres) 3/4 - 1/2Maximum length m 45 45 45Maximum height difference m 15 15 15Outdoor temperature operating limits** °C -20 -20 -20

POWEr SUPPLy1~230V-50Hz

Power cable mm2 3x6 3x6 N/DProtection rating A 32 32 N/D

POWEr SUPPLy3~400V-50Hz

Power cable mm2 5x2,5 5x2,5 5x2,5Protection rating A 16 16 20

IndOOr UnIT

Sound power at 5 m in free field dB(A)Sound power dB(A) 41 41 41Dimensions (WxDxH) mm 400x260x720Weight kg 28 28 30Finish Brushed aluminiumExchanger type PlatesWater intake/outlet connections inches 1” Femalenominal water flow m3/h 1,03 1,23 1,48Water outlet temperatures (mini/maxi) °C 25°C/65°CAvailable hydraulic pressure kPa 57 49 56

POWEr SUPPLy1~230V-50Hz

Power cable mm2 3x1,5 3x1,5 3x1,5Protection rating A 4 4 4

technical feature

* COP values with defrosting.** According to application conditions.

Page 197: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

reSidential heat Pum

P

Page 198: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Residential Heat Pump 196

Split high temperature heat pumpaquascop ht split

Ce Standard

LO WTEMPERATURE

HEATER

HEATING/COOLIN GFLOOR

heating/Cooling Floor

loW-temPerature

radiator

boiler rePlaCement

boiler baCkuP

bi-zone domeStiC hot Water

Water Programme

Patented

reVerSible r407C Fluid outdoor oPerating

limitS in heating mode

high temPerature

uP to 65°C

ProduCt deVeloPed and manuFaCtured

in FranCe

°C-

technical features Ideal for renovations as well as for new construction Water outlet temperature up to 65°C without external backup Ideal for boiler replacement Constant operation at +65°C with -20°C outdoors 6 to 18 kW of heating over 3 models Systemair patented “dual-stage” cascading compressors A single refrigerant fluid (preloaded up to 20 m) Electronic expansion valve and flow meter

Low noise level Three-speed circulator pump Dual-zone management

Product advantages Very high performance, COP up to 4.5 Aesthetics and aluminium finish Very low noise level

Compact wall unit (700x400x260) Weight of 30 kg only for the indoor unit, can be installed by

one person working alone Fluid connections on the bottom surface Cover removable by a quarter turn for immediate access

Information screen with eight lines of text in French with diagnosis assistance

New “antifreeze” evaporator, 2 hours without defrosting (no 4-mm fins) Inverter fans No risk of frost for the water, and no need to add glycol

to the installation Easy maintenance Possibility of installing several heat pumps in cascade

advantages of the Systemair high-temperature

SySTEMAIr

PATENTED[ ] Each compressor works with a low compression rate, ensuring longer service life and reduced electricity consumption. Heating power of the heat pump maintained even at low temperatures. Remarkable adaptability of power supplied / requirements thanks to the option of using the compressors separately. Optimised domestic hot water production, staging of the compressors adapted according to the exchange capacity of the tank, while

taking into account the outside temperature.

6-18 kW 407C

Page 199: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Residential Heat Pump |

Residential Heat Pum

P

197

Accessories and options

7ACEL1592

Wired ambient thermostat- Adjustment of ambient temperature - Daily or weekly programming- Holiday programming, no-frost mode

7ACEL1593

Wireless thermostat with radio communicationSends the measured ambient temperature.

7ACFH0662

300-litre domestic hot water tank (and 2.5 kW of electrical resistance heaters) optimised with the operation of the Aqu@Scop HT- Three authorisation modes- Holiday mode- Programmable anti-legionella function- Management of the three-way valve / circulator pump couple- 3.1 m2 exchange surface 7ACFH0663

140-litre buffer tank / mixing tankNecessary when the volume of water in the installation is insufficient. It protects the heat pump against short cycles that can reduce the useful life of the compressors and improves operation during defrosting phases.

7ACFH0543

ON/OFF three-way valve Required for optional production of domestic hot water. Directs the produced hot water either towards the heating circuit or towards the domestic hot water tank. A second three-way valve is recommended for boiler-backup installation.

7ACFH0789 (top outlet)7ACEL1801

(bottom outlet)

Domestic hot water kitRequired when replacing existing installations. This kit, made up of a plate exchanger and a circulator pump, enables the production of domestic hot water using existing tanks (electric cumulus).

7ACFH0491 (alone)7ACFH0490 (kit)

Hydraulic kitFor connecting to the boiler, available alone or in a complete kit with the three-way valve.Made up of a set of assembled pipes and valves, a set of connectors with spherical-conical seat.

7ACFH0665

On-line electric heaterInstallation inside the building, offers two power stages (2 and 4 kW, or 6 kW in total).Provides extra heating when the heating demand is greater than the capacity of the heat pump. The Aqu@Scop HT is adjusted to manage the electric heater, or a boiler backup.

7ACFH0666

Decanting pot (sludge pot)Effectively separates the impurities from the heating circuit and collects them in a decanting chamber, where they can be bled off, even while the installation is operational.

7ACTL0472

Shock-absorbing support feetRaise the heat pump by 10cm, allow the evacuation of condensates and defrosting water.Their rubber design provides excellent shock absorption against the transmission of vibrations through solids.

Page 200: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Residential Heat Pump 198

AQuASCOP HT SPLIT HT 12-6 HT 14-7 HT 18-9

OUTdOOr AIr REGIME 7°C

Dual compressor heating power / water regime 30/35°C kW 12,26 15,15 18,07COP* 3,95 3,84 3,95Single compressor heating power / water outlet 30/35°C kW 6,3 8,35 9,71COP* 4,12 4,35 4,52Single compressor heating power / water outlet 45°C kW 5,74 7,77 9,27COP* 3,09 3,31 3,47Dual compressor heating power / water outlet 55°C kW 5,25 7,08 8,58COP* 2,28 2,48 2,62

OUTdOOr AIr REGIME 2°C

Single compressor heating power / water outlet 35°C kW 10,31 13 15,32COP* 3,45 3,4 3,49

OUTdOOr AIr REGIME -7°C

Single compressor heating power / water outlet 35°C kW 8,05 10,68 12,21COP* 2,9 2,97 3,02Dual compressor heating power / water outlet 55°C kW 8,40 10,71 12,44COP* 2,25 2,31 2,35Dual compressor heating power / water outlet 65°C kW 8,33 10,69 12,01COP* 1,87 2,02 2,03

OUTdOOr AIr REGIME -15°C

Dual compressor heating power / water outlet 35°C kW 7,79 10,24 11,71COP* 2,80 2,86 2,9Dual compressor heating power / water outlet 65°C kW 8 10,27 11,5COP* 1,81 1,96 1,96

OUTdOOr UnIT

Sound power at 5 m in free field dB(A)Sound power dB(A) 65 65 65Compressor type (R407C) 2 scroll compressors in cascadeDimensions (WxDxH) mm 47 47 47Weight kg 184 209 213Refrigerant connections (gas/liquid) (0 to 25 metres) 5/8 - 3/8 Refrigerant connections (gas/liquid) (0 to 45 metres) 3/4 - 1/2Maximum length m 45 45 45Maximum height difference m 15 15 15Outdoor temperature operating limits** °C -20 -20 -20

POWEr SUPPLy1~230V-50Hz

Power cable mm2 3x6 3x6 N/DProtection rating A 32 32 N/D

POWEr SUPPLy3~400V-50Hz

Power cable mm2 5x2,5 5x2,5 5x2,5Protection rating A 16 16 20

IndOOr UnIT

Sound power at 5 m in free field dB(A)Sound power dB(A) 41 41 41Dimensions (WxDxH) mm 400x260x720Weight kg 28 28 30Finish Brushed aluminiumExchanger type PlatesWater intake/outlet connections inches 1” Femalenominal water flow m3/h 1,03 1,23 1,48Water outlet temperatures (mini/maxi) °C 25°C/65°CAvailable hydraulic pressure kPa 57 49 56

POWEr SUPPLy1~230V-50Hz

Power cable mm2 3x1,5 3x1,5 3x1,5Protection rating A 4 4 4

technical feature

* COP values with defrosting.** According to application conditions.

Page 201: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

reSidential heat Pum

P

Page 202: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Water Terminals

hawair 4-4 kW 5.2-33.9 kW

kog ln (Cassette) 1.6-9.3 kW 2.1-11.7 kW Motor EC

kog ln (cassette) 1.6-9.3 kW 2.1-11.7 kW Motor EC

kCo2 1-9 kW 1.2-11.3 kW Motor EC

ductys 0.6-6.8 kW 0.7-8.8 kW Motor EC

Vh 1-9 kW 1.2-11.3 kW

Selection guide water terminals units Fan Coil units

Product Range Capacity Acoustic Flow rate Pressure Fan Size (LxHxP)

SysC

oil 2

SC10 1.8 kW NR 24 at MS 108-417 m³/h 0-30 Pa EC 766 x 477 x 225

SC20 2.1 kW NR 26 at MS 98-413 m³/h 0-30 Pa EC 766 x 477 x 225

SC30 2.4 kW NR 28 at MS 185-570m³/h 0-30 Pa EC 951 x 477 x 225

SC40 3.7 kW NR 20 at MS 163-667 m³/h 0-30 Pa EC 1.136 x 477 x 225

SC50 4.4 kW NR 28 at MS 203-816 m³/h 0-40 Pa EC 1.321 x 477 x 225

SC60 5.4 kW NR 30 at MS 245-912 m³/h 0-40 Pa EC 1.506 x 477 x 225

SC70 6.5 kW NR 28 at MS 416-1.028 m³/h 0-40 Pa EC 1.321 x 577 x 225

SC80 9.1 kW NR 31 at MS 685-1.398 m³/h 0-40 Pa EC 1.508 x 578 x 225

AQuA

FAN

TTE 20 TTE

2.3 kW NR 29 at MS 137-358 m³/h 0 Pa 768 x 478 x 231

40 TTE 4.5 kW NR 30 at MS 312-672 m³/h 0 Pa 1.138 x 478 x 231

60 TTE 7.2 kW NR 42 at MS 492-1.018 m³/h 0 Pa 1.508 x 478 x 231

SysCoil 2 neW 0.48-10.0 kW 0.79-12.7 kW Motor EC

Page 203: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Water Terminals |

Water term

inals

201

Water cassetteProduct Range Capacity Acoustic Flow rate Pressure Fan Size (LxHxP)

KOG

LN

KOG 09 LN 2.3 kW NR 27 at MS 330-720 m³/h 0 Pa EC 625 x 625 x 287

KOG 12 LN 3.5 kW NR 27 at MS 330-720 m³/h 0 Pa EC 625 x 625 x 287

KOG 18 LN 4.6 kW NR 28 at MS 290-830 m³/h 0 Pa EC 625 x 625 x 287

KOG 30 LN 6.4 kW NR 37 at MS 1.100-1.550

m³/h 0 Pa EC 1.225 x 625 x 287

KOG 45 LN 10.2 kW NR 40 at MS 1.000-1.630

m³/h 0 Pa EC 1.225 x 625 x 287

KCO

2

KCO2 60 1.6 kW NR 28 at MS 140-305 m³/h 0 Pa EC 492 x 492 x 309

KCO2 90 3.2 kW NR 27 at MS 200-560 m³/h 0 Pa EC 970 x 492 x 309

KCO2 120 4.1 kW NR 30 at MS 290-680 m³/h 0 Pa EC 1.192 x 492 x 309

Selection guide water terminals units

irYS

highwallProduct Range Capacity Acoustic Flow rate Pressure Fan Size (LxHxP)

HAW

AIR

HAWAIR 07 2.2 kW NR 27 at MS 320-450 m³/h 0 Pa - 845 x 275 x 180

HAWAIR 09 2.9 kW NR 29 at MS 400-600 m³/h 0 Pa - 845 x 275 x 180

HAWAIR 18 3.6 kW NR 35 at MS 550-750 m³/h 0 Pa - 940 x 298 x 200

HAWAIR 22 4.7 kW NR 41 at MS 650-900 m³/h 0 Pa - 940 x 298 x 200

ducted

Product Range Capacity Acoustic Flow rate Pressure Fan Size (LxHxP)

DuCT

yS

DT 1000 1.4 kW NR 30 at MS 90-370 m³/h 0-80 Pa EC 581 x 540 x 223

DT 1500 2 kW NR 30 at MS 270-505 m³/h 0-80 Pa EC 581 x 640 x 223

DT 2000 2.5 kW NR 31 at MS 370-600 m³/h 0-80 Pa EC 581 x 740 x 223

DT 2500 3.3 kW NR 31 at MS 440-640 m³/h 0-80 Pa EC 581 x 840 x 223

DT 4000 6 kW NR 35 at MS 316-1190 m³/h 0-80 Pa EC 581 x 1.140 x 223

VH

VH07 6.2 kW NR 34 at MS 648-1251 m³/h 0-150 Pa EC 698 x 1.200 x 250

VH15 14.8 kW NR 40 at MS 671-3176 m³/h 0-150 Pa EC 798 x 1.380 x 375

VH18 18.9 kW NR 40 at MS 671-3176 m³/h 0-150 Pa EC 798 x 1.380 x 375

VH21 21.9 kW NR 40 at MS 671-3176 m³/h 0-150 Pa EC 798 x 1.380 x 375

VH24 23.9 kW NR 44 at MS 1938-3882 m³/h 0-150 Pa EC 798 x 1.500 x 450

VH27 28.4 kW NR 44 at MS 1938-3882 m³/h 0-150 Pa EC 798 x 1.500 x 450

Page 204: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Water Terminals202

Control ready-to-install.

Fin coils for efficient and hygienic solution.

Cost-optimized3-speed setting for EC fan.

A Large Range... with lowercaseInnovation and easy installation

Wide range of control.

Page 205: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Water Terminals |

Water term

inals

203

A large range of terminal units dedicated to energy saving and comfort:

low consumption solution with: High efficiency fan motor available on fan coil, ducted fan coil

and cassette range High level of energy performance with mainly Energy class A

or B Same thermal performance as with AC fan motor

Silence Optimized fan speed staging for new low noise versions Reinforced acoustical insulation Profiled air diffuser

Factory facilities dedicated to flexibility and quality

many factory-mounted options or accessories: Control Valve Air diffuser Condensate drain pump

Products fully customized to satisfy your requirements: Choice of service side for hydraulic and electric connection Version with or without cabinet On-board control

100% units are tested electrically and acoustically.

All Terminals Unitsare according to Eurovent standard.

Page 206: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Water Terminals204

Cooling modeMinimum water temperature +5°CMaximum water temperature +90°CMaximum operating pressure 5 barsHeating modeMinimum indoor air temperature (room/intake/around unit) 5°C/15% RHMaximum indoor air temperature (room/intake/around unit) 32°C/70% RH

Fan coils unitsCooling and heatingSysCoil 2 VC/hC

technical features Cooling Capacity from 0.49 to 9.14 kW Heating Capacity from 0.81 to 12.58 kW 8 sizes

Versions: 2-Pipes 2-Pipes/2-Wires 4-Pipes

Configuration VC Vertical console units with cabinet HC Ceiling exposed units with cabinet

Product advantages Ease of installation Harmonuous and aesthetic RAL 9003 painted cabinet

design Streamlined design and elaborate finish enabling

harmonious integration 5-speed AC fan motor Very low operating acoustical levels Airflow rate between 89 and 1.397 m³/h

Extended monobloc condensate drain pan

main accessories and options Selection of 3 speed Electrical heater On-board electronic control or terminal block for wall-

mounted control Modbus communication interface board 2-way or 3-way ON/OFF valve Condensate drain pump G3 filter Fuse holder

operating limit (to be confirmed following selection software issue)

0.49-9.14 kW 0.81-12.58 kW

Selection of service side Large choice of controls : Electro-mechanic, electro-

nic, on-board or wall-mounted Suspension kit

hotel oFFiCeS

Page 207: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Water Terminals |

Water term

inals

205

SysCoil 2 VC/HC SC10 SC20 SC30 SC40 SC50 SC60 SC70 SC80

Capacities - 2 PIPE V1 / V3 / V5 V1 / V3 / V5 V1 / V3 / V5 V1 / V3 / V5 V1 / V3 / V5 V1 / V3 / V5 V1 / V3 / V5 V1 / V3 / V5

Cooling1

Total cooling capacity W 590 /

930 / 1.290700 /

1.100 / 1.4901.210 /

1.950 / 2.400970 / 2.140

/2.8101.620 /3.070

/ 4.0902.630 /

4.180 / 5.4603.100 /

5.840 / 6.6204.710 /

6.650 / 9.140

Sensible capacity W 470/

750 / 1.050520 /

830 / 1.1701100 /

1.710 / 2.100670 /

1.620 / 2.0701.260 / 2.160

/ 3.0001.790 /

2.960 / 4.0302.170 /

4.280 / 5.0303.490 /

4.930 / 6.990

Water flow l/h 102 / 161 / 222

120 / 189 / 257

208 /335 / 413

167 /368 / 484

279 /528 / 705

452 /721 / 941

533 /1006 / 1140

811 /1146 / 1575

Water pressure drop kPa 2.9 / 6.6 /

11.9 1.7 / 3.3 / 5.3 4.4 / 9.9 / 14.3

3.9 / 14 / 22.5

4.1 / 13 / 22.4

10.4 / 25.2 / 42.2 4 / 13.9 / 17.9 12.3 / 22.6 /

40.3

Heating2 Heating capacity W 810 /

1.300 / 1.810860 /

1.380 / 1.9501.350 /

2.360 / 2.9701.370 /

2.710 / 3.6702.050 /

3.940 / 5.4002.360 /

3.970 / 5.2704.140 /

7.370 / 8.7206.520 /

9.250 / 12.580Capacities - 4 PIPE

Cooling1

Total cooling capacity W 490 /

800 / 1.110580 /

950 / 1.3101.080 /

1.760 / 2.130860 /

1.900 / 2.5201.470 /

2.790 / 3.6902.410 /

3.830 / 4.9802.840 /

5.260 / 5.9804.560 /

6.490 / 9.030

Sensible capacity W 390 /

640 / 900430 /

720 / 1.020990 /

1.550 / 1.840590 /

1.440 / 1.8801.150 /

1.970 / 2.6901.640 /

2.700 / 3.6601.980 /

3.840 / 4.4903.360 /

4.790 / 6.880

Water flow l/h 85 /137 / 192

99 /163 / 226

186 /303 / 368

148 /327 / 435

254 /480 / 635

414 /660 / 857

490 /906 / 1030

785 /1.117 / 1.555

Water pressure drop kPa 2.1 / 4.9 / 9.1 1.3 / 2.6 / 4.3 3.7 / 8.3 /

11.73.3 / 11.5 /

18.73.5 / 10.9 /

18.48.8 / 21.3 /

35.23.4 / 11.3 /

14.611.6 / 21.7 /

39.6

Heating3

Heating capacity W 830 /

1.240 / 1.650960 /

1.380 / 1.7301.560 /

2.220 / 2.5501.580 /

2.660 / 3.3402.370 /

3.760 / 4.8102.340 /

3.580 / 4.5304.240 /

5.900 / 7.0506.660 /

9.440 / 11.790

Water flow l/h 71 /107 / 142

82 /118 / 149

135 /192 / 220

136 /229 / 288

204 /324 / 414

201 /308 / 391

365 /508 / 607

573 /813 / 1.016

Water pressure drop kPa 1/ 1.9 / 3.3 1.1 / 2.1

/ 3.3 3.8/ 6.6 / 8.2 4.1 / 10.1 / 15.3

7.5 / 16.8 / 26.1

9.1 / 18.5 / 27.9

23.1 / 41.1 / 56.5

17 / 31.9 / 48.1

Sound Levels - 2 PipesSound power level dB(A) 33 / 41 / 47 32 / 44 / 51 40 / 53 / 59 29 / 46 / 53 36 / 48 / 57 40 / 52 / 58 46 / 59 / 63 52 / 57 / 66Sound pressure level4 dB(A) 19 / 24 / 31 16 / 28 / 35 24 / 37 / 43 14 / 30 / 37 20 / 33 / 41 24 / 36 / 42 30 / 43 / 47 34 / 41 / 49NR4 dB(A) 10 / 15 / 22 5 / 20 / 26 14 / 28 / 34 5 / 22 / 27 9 / 22 / 31 14 / 28 / 34 21 / 33 / 36 26 / 34 / 48Sound Levels - 4 PipesSound power level dB(A) 33 / 41 / 47 32 / 44 / 51 40 / 53 / 59 29 / 46 / 53 36 / 48 / 57 40 / 52 / 58 46 / 59 / 63 52 / 57 / 66Sound pressure level4 dB(A) 19 / 24 / 31 16 / 28 / 35 24 / 37 / 43 14 / 30 / 37 20 / 33 / 41 24 / 36 / 42 30 / 43 / 47 34 / 41 / 49NR4 dB(A) 10 / 15 / 22 5 / 20 / 26 14 / 28 / 34 5 / 22 / 27 9 / 22 / 31 14 / 28 / 34 21 / 33 / 36 26 / 34 / 48Fans Number 1 1 1 2 2 2 2 3

Airflow - 2 Pipes m³/h 111 /190 / 283

105 /179 / 265

229 /388 / 483

172 /356 / 493

253 /486 / 716

350 /640 / 933

480 /893 / 1064

660 /936 / 1397

Airflow - 4 Pipes m³/h 95 /168 / 253

89 /161 / 241

214 /366 / 450

162 /333 / 461

242 /466 / 671

334 /614 / 885

470 /859 / 1012

634 /905 / 1370

Electrical Data

Power supply V/Ph/Hz 230V / 1~ / 50Hz - 230V / 1~ / 60Hz

Fan consumption - 2 pipes W 14 / 24 / 36 14 / 23 / 35 24 / 50 / 81 18 / 39 / 59 33 / 57 / 80 39 / 76 / 111 60 / 114 / 161 90 / 112 / 188Fan consumption - 4 pipes W 14 / 24 / 36 14 / 23 / 34 24 / 50 / 80 18 / 39 / 58 33 / 56 / 78 39 / 75 / 110 60 / 113 / 159 90 / 112 / 188Electrical heater (max) W 500 500 5.00/1.000 1.250/2.500 1.250/2.500 1.250/2.500 1.000/2.000 1.500/3.000Water ConnectionsType Gas female threadedCooling coil inches 1/2” 1/2” 1/2” 1/2” 1/2” 1/2” 3/4” 1/2”Heating coil inches 1/2”Dimensions

LxWxH SVC mm 766 x 225 x 477

766 x 225 x 477

951 x225 x 477

1.136 x225 x 477

1.321 x225 x 477

1.506 x225 x 477

1.321 x225 x 577

1.508 x225 x 578

LxWxH SHC mm 766 x 477 x 225

766 x 477 x 225

951 x477 x 225

1.136 x 477 x 225

1.321 x477 x 225

1.506 x477 x 225

1.321 x577 x 225

1.508 x578 x 225

Weight Unit weight SVC kg 18 18 21.5 27 30 35 35 50Unit weight SHC kg 19 19 22.5 29 32 37 37 52

technical feature

1 According to Eurovent standard. Air: 27°C DB/19°C WB, Water in: 7°C/12°C.2 According to Eurovent standard. Air: 20°C, Water in: 50°C, same water flow as in cooling.3 According to Eurovent standard. Air: 20°C, Water in: 70°C/60°C.4 Informative data, considering a sound attenuation of the room and installation of 16dBA.

Page 208: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Water Terminals206

Cooling modeMinimum water temperature +5°CMaximum water temperature +90°CMaximum operating pressure 5 barsHeating modeMinimum indoor air temperature (room/intake/around unit) 5°C/15% RHMaximum indoor air temperature (room/intake/around unit) 32°C/70% RH

Fan coils units Cooling and heatingSysCoil 2 VC/hC eC

technical features Cooling Capacity from 0.48 to 10.0 kW Heating Capacity from 0.79 to 12.7 kW 8 sizes

Versions 2-Pipes 2-Pipes/2-Wires 4-Pipes

Configuration VC Vertical console units with cabinet HC Ceiling exposed units with cabinet

Product advantages Ease of installation Harmonuous and aesthetic RAL9003 painted cabinet

design Streamlined design and elaborate finish enabling harmonious

integration Very low operating acoustical levels Airflow rate between 84 and 1.548 m³/h

Extended monobloc condensate drain pan

main accessories and options EC motor Selection of 3 speed Electrical heater On-board electronic control or terminal block for wall-mounted

control Modbus communication interface board 2-way or 3-way ON/OFF valve Condensate drain pump G3 filter

operating limit (to be confirmed following selection software issue)

hotel oFFiCeS

0.48-10.0 kW eC motor

0.79-12.7 kW

Fuse holder Selection of service side Large choice of controls : Electro-mechanic, electronic, on-

board or wall-mounted Suspension kit

Page 209: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Water Terminals |

Water term

inals

207

SysCoil 2 VC/HC EC SC10 SC20 SC30 SC40 SC50 SC60 SC70 SC80

Capacities - 2 PIPE V1 / V3 / V5 V1 / V3 / V5 V1 / V3 / V5 V1 / V3 / V5 V1 / V3 / V5 V1 / V3 / V5 V1 / V3 / V5 V1 / V3 / V5

Cooling1

Total cooling capacity W 580 /

1.080 / 1.790660 /

1.350 / 2.160670 /

1.610 / 2.4301.270 /

2.660 / 3.7201.260 /

3.810 / 4.4002.060 /

4.610 / 5.3702.590 /

5.520 / 6.5104.880 /

6.590 / 9.150

Sensible capacity W 460 /

870 / 1.490490 /

1.050 / 1.770560 /

1.360 / 2.040940 /

1.760 / 2.6701.060 /

2.740 / 3.3501.370 /

3.320 / 3.9601.810 /

3.970 / 4.8703.620 /

4.890 / 6.990

Water flow l/h 100 /186 / 309

114 /232 / 373

115 /277 / 418

218 /457 / 642

217 /657 / 759

355 /794 / 925

446 /951 / 1.122

841 /1.135 / 1.575

Water pressure drop kPa 2.7 / 8.5 /

22.1 1.6 / 4.5 / 9.6 1.7 / 7.1 / 14.6

5.9 / 20.4 / 37.4

2.6 / 19.6 / 25.8

6.6 / 30.4 / 40.8

2.8 / 12.5 / 17.3

13.1 / 22.2 / 40.3

Heating2 Heating capacity W 790 /

1.510 / 2.570810 /

1.750 / 2.940980 /

2.150 / 3.3101.310 /

2.850 / 4.9001.580 /

4.910 / 5.8001.780 /

4.420 / 5.1703.640 /

6.870 / 8.4606.740 /

9.170 / 12.580Capacities - 4 PIPE

Cooling1

Total cooling capacity W 480 /

920 / 1.560550 /

1.130 / 1.930500 /

1.370 / 2.1301.090 /

2.320 / 3.3701.090 /

3.300 / 3.9701.750 /

4.080 / 4.8102.190 /

4.730 / 5.7104.740 /

6.340 / 10.000

Sensible capacity W 370 /

740 / 1.280410 /

870 / 1.550410 /

1.150 / 1.790830 /

1.560 / 2.390930 /

2.390 / 2.9701.150 /

2.990 / 3.5201.530 /

3.400 / 4.2203.500 /

4.680 / 7.690

Water flow l/h 82 /159 / 268

95 /195 / 333

87 /235 / 366

189 /400 / 580

188 /568 / 685

301 / 703 / 829

377 / 816 / 983

817 / 1092 / 1722

Water pressure drop kPa 1.9 / 6.4 / 17 1.2 / 3.4 / 8 1.1 / 5.4 /

11.54.7 / 16.1

/ 312.1 / 14.9 /

21.24.9 / 24.1

/ 33 2 / 9.2 / 13.3 12.5 / 20.8 / 47.8

Heating3

Heating capacity W 810 /

1.410 / 2.220930 /

1.560 / 2.2801.680 /

2.420 / 2.8902.030 /

3.440 / 4.4702.570 /

3.980 / 4.9801.770 /

3.790 / 4.4004.040 /

5.640 / 6.8306.920 /

9.220 / 12.700

Water flow l/h 69 /121 / 191

80 /135 / 197

145 /209 / 249

175 /296 / 385

221 /342 / 429

152 /326 / 379

348 /486 / 588

596 /794 / 1093

Water pressure drop kPa 1 / 2.4 / 6 1 / 2.7 / 5.7 4.2/ 7.6 /

10.16.3 / 16.1 /

28.58.6 / 18.5 /

27.95.8 / 20.3 /

26.421.3 / 38 /

53.318.2 / 30.5 /

55.2Sound levels - 2 PipesSound power level dB(A) 40 / 49 / 61 36 / 50 / 62 33 / 54 / 62 31 / 45 / 57 34 / 52 / 58 34 / 55 / 59 40 / 54 / 59 53 / 58 / 66Sound pressure level4 dB(A) 25 / 33 / 45 20 / 34 / 46 17 / 37 / 46 15 / 29 / 41 19 / 36 / 42 18 / 39 / 43 24 / 38 / 43 33 / 39 / 49NR4 dB(A) 16 / 24 / 35 10 / 26 / 35 10 / 28 / 37 5 / 20 / 32 8 / 28 / 33 6 / 30 / 33 14 / 28 / 33 23 / 31 / 42Sound levels - 4 PipesSound power level dB(A) 40 / 49 / 61 36 / 50 / 62 33 / 54 / 62 31 / 45 / 57 34 / 52 / 58 30 / 55 / 59 40 / 54 / 59 53 / 58 / 66Sound pressure level4 dB(A) 25 / 33 / 45 20 / 34 / 46 17 / 37 / 46 15 / 29 / 41 19 / 36 / 42 15 / 39 / 43 24 / 38 / 43 33 / 39 / 49NR4 dB(A) 16 / 24 / 35 10 / 26 / 35 10 / 28 / 37 5 / 20 / 32 8 / 28 / 33 6 / 30 / 33 14 / 28 / 33 23 / 31 / 42FansNumber 1 1 1 2 2 2 2 3

Airflow - 2Pipes m³/h 108 /228 / 417

98 /234 / 413

185 /384 / 570

163 /385 / 667

203 /645 / 816

245 /737 / 912

417 /827 / 1028

685 /927 / 1398

Airflow - 2Pipes m³/h 91 /199 / 379 84 /200 / 380 155 /

346 / 526144 /

349 / 615185 /

587 / 754205 /

668 / 845390 /

777 / 969660 /

884 / 1548Electrical Data

Power supply V/Ph/Hz 230V / 1~ / 50Hz - 230V / 1~ / 60Hz

Fan consumption-2Pipes W 8 / 14 / 41 8 / 15 / 41 6 / 19 / 46 2 / 13 / 43 2 / 24 / 46 2 / 30 / 54 12 / 45 / 77 23 / 42 / 108Fan consumption-4Pipes W 8 / 14 / 39 8 / 15 / 40 6 / 18 / 45 2 / 12 / 41 2 / 23 / 44 2 / 28 / 52 12 / 44 / 74 22 / 41 / 116Set voltage V 2 / 5 / 10 2 / 5 / 10 2 / 6 / 10 2 / 5 / 10 2 / 7 / 10 2 / 7 / 10 4 / 8 / 10 3 / 4.1 / 6Electrical heater (max) W 500 500 500/1.000 1.250/2.500 1.250/2.500 1.250/2.500 1.000/2.000 1.500/3.000Water Connections Type Gas female threadedCooling coil inches 1/2” 1/2” 1/2” 1/2” 1/2” 1/2” 3/4” 1/2”Heating coil inches 1/2”Dimensions

LxWxH SVC mm 766 x 225 x 477

766 x 225 x 477

951 x225 x 477

1.136 x225 x 477

1.321 x225 x 477

1.506 x225 x 477

1.321 x225 x 577

1.508 x225 x 578

LxWxH SHC mm 766 x 477 x 225

766 x 477 x 225

951 x477 x 225

1.136 x 477 x 225

1.321 x477 x 225

1.506 x477 x 225

1.321 x577 x 225

1.508 x578 x 225

WeightUnit weight SVC kg 18 18 21.5 27 30 35 35 50Unit weight SHC kg 19 19 22.5 29 32 37 37 52

technical feature

1 According to Eurovent standard. Air: 27°C DB/19°C WB, Water in: 7°C/12°C.2 According to Eurovent standard. Air: 20°C, Water in: 50°C, same water flow as in cooling.3 According to Eurovent standard. Air: 20°C, Water in: 70°C/60°C.4 Informative data, considering a sound attenuation of the room and installation of 16dBA.

Page 210: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Water Terminals208

Cooling modeMinimum water temperature +5°CMaximum water temperature +90°CMaximum operating pressure 5 barsHeating modeMinimum indoor air temperature (room/intake/around unit) 5°C/15% RHMaximum indoor air temperature (room/intake/around unit) 32°C/70% RH

Fan coils unitsCooling and heatingSysCoil 2 Vn/hn

technical features Cooling Capacity from 0.49 to 9.14 kW Heating Capacity from 0.81 to 12.58 kW 8 sizes

Versions 2-Pipes 2-Pipes/2-Wires 4-Pipes

Configuration VN Vertical concealed units without cabinet HN Ceiling concealed units without cabinet

Product advantages Ease of installation Streamlined design and elaborate finish enabling

harmonious integration 5-speed AC fan motor Very low operating acoustical levels Airflow rate between 89 and 1.397 m³/h

Extended monobloc condensate drain pan

main accessories and options EC motor Selection of 3 speed Electrical heater On-board electronic control or terminal block for wall-mounted

control Modbus communication interface board 2-way or 3-way ON/OFF valve Condensate drain pump G3 filter Fuse holder Selection of service side

operating limit (to be confirmed following selection software issue)

hotel oFFiCeS

0.49-9.14 kW 0.81-12.58 kW

Large choice of controls : Electro-mechanic, electronic, on-board or wall-mounted

Suspension kit

Page 211: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Water Terminals |

Water term

inals

209

SysCoil 2 VN/HN STD SC10 SC20 SC30 SC40 SC50 SC60 SC70 SC80

Capacities - 2 PIPE V1 / V3 / V5 V1 / V3 / V5 V1 / V3 / V5 V1 / V3 / V5 V1 / V3 / V5 V1 / V3 / V5 V1 / V3 / V5 V1 / V3 / V5

Cooling1

Total cooling capacity W 590 /

930 / 1.290700 /

1.100 / 1.4901.210 /

1.950 / 2.400970 /

2.140 / 2.8101.620 /

3.070 / 4.0902.630 /

4.180 / 5.4603.100 /

5.840 / 6.6204.710 /

6.650 / 9.140

Sensible capacity W 470 /

750 / 1.050520 /

830 / 1.1701.100 /

1.710 / 2.100670 /

1.620 / 2.0701.260 /

2.160 / 3.0001.790 /

2.960 / 4.0302.170 /

4.280 / 5.0303.480 /

4.930 / 6.990

Water flow l/h 102 /161 / 222

120 /189 / 257

208 /335 / 413

167 /368 / 484

279 /528 / 705

452 /721 / 941

533 /1006 / 1140

811 /1146 / 1.575

Water pressure drop kPa 2.9 / 6.6 /

11.9 1.7 / 3.3 / 5.3 4.4 / 9.9 / 14.3

3.9 / 14 / 22.5

4.1 / 13 / 22.4

10.4 / 25.2 / 42.2

4 / 13.9 / 17.9.8

12.3 / 22.6 / 40.3

Heating2 Heating capacity W 810 /

1.300 / 1.810860 /

1.390 / 1.9501.350 /

2.360 / 2.9701.370 /

2.710 / 3.6702.050 /

3.940 / 5.4002.360 /

3.970 / 5.2704.140 /

7.370 / 8.7206.520 /

9.250 / 12.580

Capacities - 4 PIPE

Cooling1

Total cooling capacity W 490 /

800 / 1.110580 /

950 / 1.3101.080 /

1.760 / 2.130860 /

1.900 / 2.5201.470 /

2.790 / 3.6902.410 /

3.830 / 4.9802.840 /

5.260 / 5.9804.560 /

6.490 / 9.030

Sensible capacity W 390 /

640 / 900430 /

720 / 1.020990 /

1.550 / 1.870590 /

1.440 / 1.8801.150 /

1.970 / 2.6901.640 /

2.700 / 3.6601.980 /

3.840 / 4.4903.360 /

4.790 / 6.880

Water flow l/h 85 /137 / 192

99 /163 / 226

186 /303 / 368

148 /327 / 435

254 /480 / 635

414 /660 / 857

490 /906 / 1030

785 /1117 / 1555

Water pressure drop kPa 2.1 / 4.9 / 9.1 1.3 / 2.6 / 4.3 3.7 / 8.3 /

11.73.3 / 11.5 /

18.73.5 / 10.9 /

18.48.8 / 21.3 /

35.23.4 / 11.3 /

14.611.6 / 21.7 /

39.6

Heating3

Heating capacity W 830 /

1.240 / 1.650960 /

1.380 / 1.7301.560 /

2.220 / 2.5501.580 /

2.660 / 3.3402.370 /

3.760 / 4.8102.340 /

3.580 / 4.5304.240 /

5.900 / 7.0506.660 /

9.440 / 11.790

Water flow l/h 71 /107 / 142

82 /118 / 149

135 /192 / 220

136 /229 / 288

204 /324 / 414

201 /308 / 391

365 /508 / 607

573 /813 / 1016

Water pressure drop kPa 1 / 1.9 / 3.3 1.1 / 2.1

/ 3.3 3.8/ 6.6 / 8.2 4.1 / 10.1 / 15.3

7.5 / 16.8 / 26.1

9.1 / 18.5 / 27.9

23.1 / 41.1 / 56.5

17 / 31.9 / 48.1

Sound Levels - 2 PipesSound power level dB(A) 33 / 41 / 47 32 / 44 / 51 40 / 53 / 59 29 / 46 / 53 36 / 48 / 57 40 / 52 / 58 46 / 59 / 63 52 / 57 / 66Sound pressure level4 dB(A) 19 / 24 / 31 16 / 28 / 35 24 / 37 / 43 14 / 30 / 37 20 / 33 / 41 24 / 36 / 42 30 / 43 / 47 34 / 41 / 49NR4 dB(A) 10 / 15 / 22 5 / 20 / 26 14 / 28 / 34 5 / 22/ 27 9 / 22 / 31 14 / 28 / 34 21 / 33 / 36 26 / 34 / 48Sound Levels - 4 PipesSound power level dB(A) 33 / 41 / 47 32 / 44 / 51 40 / 53 / 59 29 / 46 / 53 36 / 48 / 57 40 / 52 / 58 46 / 59 / 63 52 / 57 / 66Sound pressure level4 dB(A) 19 / 24 / 31 16 / 28 / 35 24 / 37 / 43 14 / 30 / 37 20 / 33 / 41 24 / 36 / 42 30 / 43 / 47 34 / 41 / 49NR4 dB(A) 10 / 15 / 22 5 / 20 / 26 14 / 28 / 34 5 / 22/ 27 9 / 22 / 31 14 / 28 / 34 21 / 33 / 36 26 / 34 / 48Fans Number 1 1 1 2 2 2 2 3

Airflow - 2 Pipes m³/h 111 /190 / 283

105 /179 / 265

229 /388 / 483

172 /356 / 493

253 /486 / 716

350 /640 / 933

480 /893 / 1064

660 /936 / 1397

Airflow - 4 Pipes m³/h 95 /168 / 253

89 /161 / 241

214 /366 / 450

162 /333 / 461

242 /466 / 671

334 /614 / 885

470 /859 / 1012

634 /905 / 1370

Electrical Data

Power supply V/Ph/Hz 230V / 1~ / 50Hz - 230V / 1~ / 60Hz

Fan consumption-2 Pipes W 14 / 24 / 36 14 / 23 / 35 24 / 50 / 81 18 / 39 / 59 33 / 57 / 80 39 / 76 / 111 60 / 114 / 161 90 / 112 / 188Fan consumption-4 Pipes W 14 / 24 / 36 14 / 23 / 34 24 / 50 / 80 18 / 39 / 58 33 / 56 / 78 39 / 75 / 110 60 / 113 / 159 90 / 112 / 188Electrical heater (max) W 500 500 500/1.000 1.250/2.500 1.250/2.500 1.250/2.500 1.000/2.000 1.500/3.000Water Connections Type Gas female threaded Cooling coil inches 1/2” 1/2” 1/2” 1/2” 1/2” 1/2” 3/4” 1/2”Heating coil inches 1/2”Dimensions

LxWxH SVN mm 677 x220 x 430

677 x220 x 430

862 x220 x 430

1.047 x220 x 430

1.232 x220 x 430

1.417 x220 x 430

1.232 x220 x 530

1.425 x220 x 530

LxWxH SHN mm 677 x430 x 220

677 x430 x 220

862 x430 x 220

1.047 x430 x 220

1.232 x430 x 220

1.417 x430 x 220

1.232 x530 x 220

1.425 x530 x 220

WeightUnit weight SVn kg 12 12 14.5 20 22 26 27 41

Unit weight SHn kg 13 13 15.5 22 24 28 29 43

technical feature

1 According to Eurovent standard. Air: 27°C DB/19°C WB, Water in: 7°C/12°C.2 According to Eurovent standard. Air: 20°C, Water in: 50°C, same water flow as in cooling.3 According to Eurovent standard. Air: 20°C, Water in: 70°C/60°C.4 Informative data, considering a sound attenuation of the room and installation of 16dBA.

ON STOCK!Configuration: 2 or 4-pipes, terminal block, without valve, left service side without brand.Accessories for customization on site also available on stock. Please consult us to get the last updated information on leadtime.

Page 212: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Water Terminals210

Cooling modeMinimum water temperature +5°CMaximum water temperature +90°CMaximum operating pressure 5 barsHeating modeMinimum indoor air temperature (room/intake/around unit) 5°C/15% RHMaximum indoor air temperature (room/intake/around unit) 32°C/70% RH

Fan coils units Cooling and heatingSysCoil 2 Vn/hn eC

technical features Cooling Capacity from 0.48 to 10.0 kW Heating Capacity from 0.79 to 12.7 kW 7 sizes

Versions 2-Pipes 2-Pipes/2-Wires 4-Pipes

Configuration VN Vertical concealed units without cabinet HN Ceiling concealed units without cabinet

Product advantages Ease of installation Streamlined design and elaborate finish enabling

harmonious integration 5-speed AC fan motor Very low operating acoustical levels Airflow rate between 84 and 1.548 m³/h

Extended monobloc condensate drain pan

main accessories and options EC motor Selection of 3 speed Electrical heater On-board electronic control or terminal block for wall-mounted

control Modbus communication interface board 2-way or 3-way ON/OFF valve Condensate drain pump G3 filter Fuse holder

operating limit (to be confirmed following selection software issue)

hotel oFFiCeS

0.48-10.0 kW eC motor

0.79-12.7 kW

Selection of service side Large choice of controls : Electro-mechanic, electronic, on-

board or wall-mounted Suspension kit

Page 213: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Water Terminals |

Water term

inals

211

Syscoil 2 VN/HN EC SC10 SC20 SC30 SC40 SC50 SC60 SC70 SC80

Capacities - 2 Pipes V1 / V3 / V5 V1 / V3 / V5 V1 / V3 / V5 V1 / V3 / V5 V1 / V3 / V5 V1 / V3 / V5 V1 / V3 / V5 V1 / V3 / V5

Cooling1

Total cooling capacity W 580 /

1.080/ 1.790660 /

1.350 / 2.160670 /

1.610 / 2.4301.270 /

2.660 / 3.7201.260 /

3.810 / 4.4002.060 /

4.610 / 5.370 2.590 /

5.520 / 6.510 4.880 /

6.590 / 9.150

Sensible capacity W 460 /

870 / 1.490490 /

1.050 / 1.770560 /

1.360 / 2.040940 /

1.760 / 2.6701.060 /

2.740 / 3.3501.370 /

3.320 / 3.9601.810 /

3.970 / 4.8703.620 /

4.890 / 6.990

Water flow l/h 100 /186 / 309

114 /232 / 373

115 /277 / 418

218 /457 / 642

217 /657 / 759

355 /794 / 925

446 /951 / 1122

841 /1135 / 1575

Water pressure drop kPa 2.7 /

8.5 / 22.11.6 /

4.5 / 9.61.7 /

7.1 / 14.65.9 /

20.4 / 37.42.6 /

19.6 / 25.86.6 /

30.4 / 40.82.8 /

12.5 / 17.3 13.1 /

22.2 / 40.3

Heating2 Heating capacity W 790 /

1.510 / 2.570810 /

1.750 / 2.940980 /

2.150 / 3.3101.310 /

2.850 / 4.9001.580 /

4.910 / 5.8001.780 /

4.420 / 5.1703.640 /

6.870 / 8.4606.740 /

9.170 / 12.580Capacities - 4 Pipes

Cooling1

Total cooling capacity W 480 /

920 / 1.560550 /

1.130 / 1.930500 /

1.370 / 2.1301.090 /

2.320 / 3.3701.090 /

3.300 / 3.9701.750 /

4.080 / 4.8102.190 /

4.730 / 5.7104.740 /

6.340 / 10.000

Sensible capacity W 370 /

740 / 1280410 /

870 / 1.550410 /

1.150 / 1.790830 /

1.560 / 2.390930 /

2.390 / 2.9701.150 /

2.990 / 3.5201.530 /

3.400 / 4.2203.500 /

4.680 / 7.690

Water flow l/h 82/159 / 268

95 /195 / 333

87 /235 / 366

189 /400 / 580

188 /568 / 685

301 / 703 / 829

377 /816 / 983

817 / 1092 / 1722

Water pressure drop kPa 1.9 /

6.4 / 171.2 /

3.4 / 81.1 /

5.4 / 11.54.7 /

16.1 / 312.1 /

14.9 / 21.24.9/

24.1/ 332/

9.2 / 13.312.5 /

20.8 / 47.8

Heating2

Heating capacity W 810 /

1.410 / 2.220930 /

1.560 / 2.2801.680 /

2.420 / 2.8902.030 /

3.440 / 4.4702.570 /

3.980 / 4.9801.770 /

3.790 / 4.4004.040 /

5.640 / 6.8306.920 /

9.220 / 12.700

Water flow l/h 69 /121 / 191

80 /135 / 197

145 /209 / 249

175 /296 / 385

221 /342 / 429

152 /326 / 379

348 /486 / 588

596 /794 / 1093

Water pressure drop kPa 1 /

2.4 / 61 /

2.7 / 5.74.2/

7.6 / 10.16.3 /

16.1 / 26.38.6 /

18.5 / 27.9 5.8 /

20.3 / 26.421.3 / 38 /

53.318.2 / 30.5 /

55.2Sound Levels - 2 PipesSound power level dB(A) 40 / 49 / 61 36 / 50 / 62 33 / 54 / 62 31 / 45 / 57 34 / 52 / 58 34/ 55 / 59 40 / 54 / 59 53 / 58 / 66Sound pressure level4 dB(A) 25 / 33 / 45 20 / 34 / 46 17 / 37 / 46 15 / 29 / 41 19 / 36 / 42 18 / 39 / 43 24 / 38 / 43 33 / 39 / 49NR4 dB(A) 16 / 24 / 35 10 / 26 / 35 10 / 28 / 37 5 / 20 / 32 5 / 28 / 33 6 / 30 / 33 14 / 28 /33 23 / 31 /42Sound Levels - 4 PipesSound power level dB(A) 40 / 49 / 61 36 / 50 / 62 33 / 54 / 62 30 / 45 / 57 34 / 52 / 58 34 / 55 / 59 40 / 54 / 59 53 / 58 / 66Sound pressure level4 dB(A) 25 / 33 / 45 20 / 34 / 46 17 / 37 / 46 15 / 29 / 41 19 / 36 / 42 18 / 39 / 43 24 / 38 / 43 33 / 39 / 49NR4 dB(A) 16 / 24 / 35 10 / 26 / 35 10 / 28 / 37 5 / 20 / 32 5 / 28 / 33 6 / 30 / 33 14 / 28 /33 23 / 31 /42Fans (LS/MS/HS)Number 1 1 1 2 2 2 2 3

Airflow - 2 Pipes m³/h 108 /228 / 417

98 /234 / 413

185 /384 / 570

163 /385 / 667

203 /645 / 816

245 /737 / 912

417 /827 / 1028

685 /927 / 1398

Airflow - 4 Pipes m³/h 91 /199 / 379

84 / 200 / 380

155 /346 / 526

144 /349 / 615

185 /587 / 755

205 /668 / 845

390 /777 / 969

660 /884 / 1548

Electrical Data (LS/MS/HS)

Power supply V/Ph/Hz 230V / 1~ / 50Hz - 230V / 1~ / 60Hz

Fan consumption-2Pipes W 8 / 14 / 41 8 / 15 / 41 6 / 19 / 46 2 / 12 / 43 2 / 24 / 46 2 / 30 / 54 12 / 45 / 77 23 / 42 / 108Fan consumption-4Pipes W 8 / 14 / 39 8 / 15 / 40 6 / 18 / 45 2 / 12 / 41 2 / 23 / 44 2 / 28 / 52 12 / 44 / 74 22 / 41 / 116Set voltage V 2 / 5 / 10 2 / 5 / 10 2 / 6 / 10 2 / 5 / 10 2 / 7 / 10 2 / 7 / 10 4 / 8 / 10 3 / 4.1 / 6Electrical heater (max) W 500 500 500/1.000 1.250/2.500 1.250/2.500 1.250/2.500 1.000/2.000 1.500/3.000Water Connections Type Gas female threaded Cooling coil inches 1/2” 1/2” 1/2” 1/2” 1/2” 1/2” 3/4” 1/2”Heating coil inches 1/2”Dimensions

LxWxH SVN mm 677 x220 x 430

677 x220 x 430

862 x220 x 430

1.047 x220 x 430

1.232 x220 x 430

1.417 x220 x 430

1.232 x220 x 530

1.425 x220 x 530

LxWxH SHN mm 677 x430 x 220

677 x430 x 220

862 x430 x 220

1.047 x430 x 220

1.232 x430 x 220

1.417 x430 x 220

1.232 x530 x 220

1.425 x530 x 220

WeightUnit weight SVn kg 12 12 14.5 20 22 26 27 41Unit weight SHn kg 13 13 15.5 22 24 28 29 43

technical feature

1 According to Eurovent standard. Air: 27°C DB/19°C WB, Water in: 7°C/12°C.2 According to Eurovent standard. Air: 20°C, Water in: 50°C, same water flow as in cooling.3 According to Eurovent standard. Air: 20°C, Water in: 70°C/60°C.4 Informative data, considering a sound attenuation of the room and installation of 16dBA.

Page 214: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Water Terminals212

Cooling modeMinimum water temperature +5°CMaximum water temperature +70°C (size 09-12-18) +60°C (size 30/45)Maximum operating pressure 15 barsHeating modeMinimum indoor air temperature (room/intake/around unit) 13°C/15% RHMaximum indoor air temperature (room/intake/around unit) 32°C/70% RH

4-way chilled water cassette Cooling and heating kog ln

technical features Cooling Capacity from 3.3 to 9.9 kW Heating Capacity from 2.2 to 11.6 kW

5 sizes

Versions 2-Pipes 2-Pipes/2-Wires 4-Pipes

Configuration Cassette

Product advantages Design for suspended celing integration 600x600 (9, 12 and

18 models) and 600x1.200 formats, (30 and 45 models) Low built-in height: 287 mm Direct access to electrical connection on sliding chassis Integrated valve and electrical connections 3-speed AC fan motor Very low operating acoustical levels with new low noise LN

versions Fresh air intake Air distribution in adjacent room

Integrated condensate drain lift pump up to 600 mm, (3-top for 9, 12 and 18 models)

Infra-red remote control version with valve and change-over Galvanized steel sheet with thermal and acoustical insulation,

avoiding condensation on the casing and providing good sound attenuation

Possibility to close one or two discharge flaps Cleanable synthetic-type air filter

main accessories and options 3-row coil for optimized cooling performances Electrical heater with inserted heating rod

operating limit (to be confirmed following selection software issue)

2-stage heater available with Aquanet control AC motor Large choice of control: Aquanet control or wall-mounted

thermostat 2-way or 3-way ON/OFF valve Relay

Fuse holder ModBus Communication interface board

Design metallic panel with 192 colours and Coanda air diffusion (9-12-18 models) Valve Aquanet control Solid ceiling frame

Condensate drain pump Auxiliary condensate drain pan Master and slaves control, up to 4 units max Selection software

hotel oFFiCeS

3.3-9.9 kW 2.2-11.6 kW

Page 215: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Water Terminals |

Water term

inals

213

KOG LN Size 09 LN 12 LN 18 LN 30 LN 45 LN

Capacities - 2 PIPE NOMINAL V5 / V3 / V1 V5 / V3 / V1 V5 / V3 / V1 V5 / V3 / V1 V5 / V3 / V1

Cooling1

Total cooling capacity W 1.600 /1.900 / 2.300

2.300 /2.600 / 3.500

2.800 /3.700 / 4.600

4.150 /5.611 / 6.840

5.414 /7.039 / 9.298

Sensible capacity W 1.250 /1.500 / 1.800

1.700 /2.050 / 2.900

2.150 /2.950 / 3.850

3.350 /4.591 / 5.660

4.329 /5.728 / 7.650

Water flow l/h 280 /330 / 400

400 /450 / 600

480 /640 / 790

715 /966 / 1.178

933 /1.212 / 1.602

Water pressure drop kPa 6 / 9 / 12 8 / 11 / 18 8 / 11 / 16 8 /14 / 21 4/ 12,5 / 20

Heating2 Heating capacity W 2.100 /2.500 / 3.100

2.700 /3.200 / 4.500

3.300 /4.600 / 5.700

5.300 /7.500 / 9.400

4.600 /7.400 / 10.000

CAPACITIES - 4 PIPE NOMINAL

Cooling1

Total cooling capacity W 1.600 /1.900 / 2.300

2.300 /2.600 / 3.500

2.800 /3.700 / 4.600 - 5.716 /

7.925 / 9.887

Sensible capacity W 1.250 /1.500 / 1.800

1.700 /2.050 / 2.900

2.150 /2.950 / 3.850 - 4.324 /

6.185 / 7.655

Water flow l/h 280 /330 / 400

400 /450 / 600

480 /640 / 790 - 985 /

1.365 / 1.703

Water pressure drop kPa 6 / 9 / 12 8 / 11 / 18 8 / 11 / 16 - 10,5 /18,5 / 28

Heating3

Heating capacity W 1.700 /1.900 / 2.200

2.200 /2.500 / 3.335

3.300 /3.950 / 4.470 - 6.586 /

7.506 / 8.980

Water flow l/h 160 /180 / 210

200 /220 / 290

290 /340 / 380 - 577 /

658 / 788

Water pressure drop kPa 5 13 28 - 5 /6/ 8

Sound Levels (LS/MS/HS)Sound power level dB(A) 34 / 40 / 50 34 / 40 / 50 41 / 49 / 57 44 / 52 / 58 39 / 50 / 57Sound pressure level4 dB(A) 26 / 32 / 42 26 / 32 / 42 33 / 41 / 49 31,9 / 40,6 / 49,3 46 / 54 / 62NR4 dB(A) 20 / 27 / 37 20 / 27 / 37 28 / 35 / 43 29 / 36 / 44 35 / 42 / 50Fans (LS/MS/HS)Number 1 1 1 2 2

Airflow m³/h 330 /450 / 720

330 /450 / 720

410 /580 / 830

469 /668 / 902

547 /707 / 907

Electrical Data (LS/MS/HS)Power supply V/Ph/Hz 230V / 1~ / 50Hz

Fan consumption - STD W 20 / 30 / 50 20 / 30 / 50 21 / 30 / 46 / 71 38 / 66 / 100 58/90/136 (2pipes)63/91/140 (4pipes)

Electrical heater W 1.500 1.800 2.400 2.800 2.800Water Connections Type Gas male threadedCooling coil (2 tubes cooling or heating/ 4 tubes cooling) inches 1/2” 2 1/2” 3/4” 1” 1”

Heating coil (4 tubes heating) inches 1/2” 1/2” 1/2” - 1/2”Dimensions Casing (LxWxH) mm 571 x 571 x 287 1.171 x 571 x 287Plastic Grille (LxWxH) mm 625 x 625 x 40 1.225 x 625 x 40WeightUnit weight kg 26 28 29 49 55

technical feature

1 According to Eurovent standard. Air: 27°C DB/19°C WB, Water in: 7°C/12°C.2 According to Eurovent standard. Air: 20°C, Water in: 50°C, same water flow as in cooling.3 Air: 20°C, Water in: 70°C/60°C.4 Sound pressure considering a local of 100 m3, a reverberation time of 0,5 sec and a distance of 1 m.

Page 216: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Water Terminals214

Cooling modeMinimum water temperature +5°CMaximum water temperature +70°C (size 09-12-18) +60°C (size 30/45)Maximum operating pressure 15 barsHeating modeMinimum indoor air temperature (room/intake/around unit) 13°C/15% RHMaximum indoor air temperature (room/intake/around unit) 32°C/70% RH

4-way chilled water cassette Cooling and heating kog ln eC

technical features Cooling Capacity from 2.2 to 8.6 kW Heating Capacity from 2.0 to 8.3 kW 5 sizes

Versions 2-Pipes 2-Pipes/2-Wires 4-Pipes

Configuration Cassette

Product advantages Designed for suspended ceiling integration

Design for suspended celing integration 600x600 (9, 12 and 18 models) and 600x1.200 formats, (30 and 45 models)

Low built-in height: 287 mm Direct access to electrical connection on sliding chassis Integrated valve and electrical connections Low consumption EC fan motor Very low operating acoustical levels with new low noise LN

versions Fresh air intake Air distribution in adjacent room Integrated condensate drain lift pump up to 600 mm, (3-top

for 9, 12 and 18 models) Infra-red remote control version with valve and change-over Galvanized steel sheet with thermal and acoustical insulation,

avoiding condensation on the casing and providing good sound attenuation

Possibility to close one or two discharge flaps Cleanable synthetic-type air filter

main accessories and options 3-row coil for optimized cooling performances

operating limit (to be confirmed following selection software issue)

Electrical heater with inserted heating rod 2-stage heater available with Aquanet control EC motor Selection of 3 speed with ECoSpeed3 board Large choice of control: Aquanet control or wall-mounted

thermostat 2-way or 3-way ON/OFF valve G1 filter Condensate drain pump Relay Fuse holder ModBus Communication interface board Design metallic panel with 192 colours and Coanda air

diffusion (9-12-18 models) Valve Aquanet control Solid ceiling frame Condensate drain pump Auxiliary condensate drain pan Select’it

hotel oFFiCeS

2.2-8.6 kW motor eC

2.0-8.3 kW

Page 217: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Water Terminals |

Water term

inals

215

KOG LN EC 09 LN 12 LN 18 LN 30 LN 45 LN

Capacities - 2 PIPE NOMINAL

Cooling1

Total cooling capacity W 1.600 /1.900 / 2.300

2.300 /2.600 / 3.500

2.800 /3.700 / 4.600

4.215 / 5.700 / 6.800

3.730 / 5.900 / 7.980

Sensible capacity W 1.250 /1.500 / 1.800

1.700 /2.050 / 2.900

2.150 /2.950 / 3.850

3.400 / 4.600 / 5.700

2.920 / 4.700 / 6.500

Air flow l/h 280 /330 / 400

400 /450 / 600

480 /640 / 790

725 / 982 / 1.171

642 / 1.016 / 1.375

Water pressure drop kPa 6 / 9 / 12 8 / 11 / 18 8 / 11 / 16 8 / 13 / 18 4 / 9 / 15

Heating2 Heating capacity W 2.100 /2.500 / 3.100

2.700 /3.200 / 4.500

3.300 /4.600 / 5.700

5.300 / 7.500 / 9.400

4.600 / 7.400 / 10.000

Capacities - 4 PIPE NOMINAL

Cooling1

Total cooling capacity W 1.600 /1.900 / 2.300

2.300 /2.600 / 3.500

2.800 /3.700 / 4.600 - 4.000 /

6.490 / 8.600

Sensible capacity W 1.250 /1.500 / 1.800

1.700 /2.050 / 2.900

2.150 /2.950 / 3.850 - 3.050 /

5.000 / 6.700

Air flow l/h 280 /330 / 400

400 /450 / 600

480 /640 / 790 - 689 /

1.118 / 1.481

Water pressure drop kPa 6 / 9 / 12 8 / 11 / 18 8 / 11 / 16 - 6 / 13 / 22

Heating3

Heating capacity W 1.700 /1.900 / 2.200

2.200 /2.500 / 3.335

3.300 /3.950 / 4.470 - 4.700 /

6.790 / 8.300

Air flow l/h 160 /180 / 210

200 /220 / 290

290 /340 / 380 - 405 /

585 / 715

Water pressure drop kPa 3 / 4 / 5 7 / 9 / 13 17 / 24 / 28 - 3 / 5 / 7

Sound Levels (LS/MS/HS)Sound power level dB(A) 34 / 40 / 50 34 / 40 / 50 41 / 49 / 57 44 / 52 / 58 39 / 50 / 57Sound pressure level4 dB(A) 26 / 32 / 42 26 / 32 / 42 33 / 41 / 49 36 / 44 / 50 31 / 42 / 49NR4 dB(A) 20 / 27 / 37 20 / 27 / 37 28 / 35 / 43 33 / 40 / 44 25 / 36 / 43Fans (LS/MS/HS)Number 1 1 1 2 2

Airflow m³/h 330 / 450 / 720

330 /450 / 720

410 /580 / 830

597 / 928 / 1.313

521 / 877 / 1.268

Electrical Data (LS/MS/HS)Power supply V/Ph/Hz 230V / 1~ / 50HzFan consumption - STD W 8 / 11 / 26 8 / 11 / 26 9 / 23 / 41 9 / 17 / 39 9 / 17 / 23Set Voltage V 3.77/4.39/6.17 3.77/4.39/6.17 4.45/6.03/7.53 3.09/1.44/5.48 3.09/4.11/5.48Electrical heater (max) W 1.500 1.800 2.400 2.800 2.800Water Connections Type Gas male threadedCooling coil (2 tubes cooling or heating / 4 tubes cooling) inches 1/2” 1/2” 3/4” 1” 1”

Heating coil (4 tubes heating) inches 1/2” 1/2” 1/2” - 1/2”Dimensions Casing (LxWxH) mm 571 x 571 x 287 571 x 571 x 287 571 x 571 x 287 1.171 x 571 x 287 1.171 x 571 x 287IryS diffuser (LxWxH) mm 595 x 595 x 40 595 x 595 x 40 595 x 595 x 40 1.195 x 595 x 40 1.195 x 595 x 40WeightUnit weight kg 26 28 29 49 55

technical feature

1 According to Eurovent standard. Air: 27°C DB/19°C WB, Water in: 7°C/12°C.2 According to Eurovent standard. Air: 20°C, Water in: 50°C, same water flow as in cooling.3 Air: 20°C, Water in: 70°C/60°C.4 Sound pressure considering a local of 100 m3, a reverberation time of 0,5 sec and a distance of 1 m.

Page 218: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Water Terminals216

KCO2Minimum water temperature +5°CMaximum water temperature +80°CMaximum operating pressure 10 bars

False ceiling integration Orientable diffusorwith Coanda effect

1-way chilled water cassette Coanda effectkCo2

technical features Cooling Capacity from 1.1 to 8.6 kW Heating Capacity from 1.3 to 3.4 kW

3 sizes

Versions 2-Pipes 2-Pipes/2-Wires 4-Pipes

Configuration Cassette

Product advantages Innovative technical solution for architectural installations Advance aesthetic and harmonious design Designed for suspended ceiling installation Possible gravity condensate evacuation Optimum coanda effect through uniform airflow Adjustable multidirectionnal diffusers with high induction 5 speed AC fan motor Very low acoustic levels Galvanized steel sheet with acoustical insulation Air filtration

main options 3-row coil for optimized cooling performances Electrical heater On-board electronic control Aquanet or terminal block for

wall-mounted control ModBus Communication interface board 2-way or 3-way ON/OFF valve Fresh air intake Condensate drain pump Selection softwar: select KCO2

operating limit (to be confirmed following selection software issue)

hoSPital

1.1-3.3 kW motor eC

1.3-3.4 kW

Page 219: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Water Terminals |

Water term

inals

217

KCO2 60 90 120

Capacities - 2 PIPE (LS/MS/HS)

Cooling1

Total cooling capacity W 880 / 1.060 / 1.500 1.370 / 1.620 / 2.370 1.970 / 2.840 / 3.340Sensible capacity W 660 / 810 / 1.180 1.000 / 1.190 / 1.770 1.440 / 2.110 / 2.510Water flow l/h 163 / 196 / 279 253 / 299 / 437 363 / 525 / 617Water pressure drop kPa 2,4 / 3,3 / 6,1 2,9 / 3,9 / 7,6 6,4 / 12,1 / 16,2

Heating (2) Heating capacity W 1.080 / 1.330 / 1.930 1.600 / 1.910 / 2.860 2.300 / 3.370 / 4.020Capacities - 4 PIPE (LS/MS/HS)

Cooling1

Total cooling capacity W 880 / 1.060 / 1.500 1.370 / 1.620 / 2.370 1.970 / 2.840 / 3.340Sensible capacity W 660 / 810 / 1.180 1.000 / 1.190 / 1.770 1.440 / 2.110 / 2.510Water flow l/h 163 / 196 / 279 253 / 299 / 437 363 / 525 / 617Water pressure drop kPa 2,4 / 3,3 / 6,1 2,9 / 3,9 / 7,6 6,4 / 12,1 / 16,2

Heating3

Heating capacity W 920 / 1.080 / 1.470 1.490 / 1.710 / 2.350 2.120 / 2.870 / 3.300Water flow l/h 79 / 93 / 126 128 / 147 / 202 182 / 247 / 284Water pressure drop kPa 1,6 / 2,1 / 3,6 0,9 / 1,2 / 2,0 2,0 / 3,4 / 4,3

Sound Levels (LS/MS/HS)Sound power level dB(A) 35 / 41 / 52 33 / 36 / 48 35 / 46 / 52Sound pressure level4 dB(A) 26 / 32 / 43 24 / 27 / 39 26 / 37 / 43NR4 dB(A) 22 / 28 / 39 20 / 23 / 35 22 / 33 / 39Fans (LS/MS/HS)Airflow m³/h 140 / 180 / 280 200 / 240 / 380 290 / 440 / 540Electrical Data (LS/MS/HS)Power supply V / Ph / Hz 230V / 1~ / 50HzFan consumption - STD W 16 / 22 / 49 24 / 27 / 44 27 / 42 / 59Electrical heater W 550 1.100 1.400Water ConnectionsType Gas male threadedCooling coil inches 1/2” 1/2” 1/2”Heating coil inches 1/2” 1/2” 1/2”DimensionsCasing (LxWxH) mm 592 x 592 x 309 592 x 970 x 309 592 x 1.192 x 309

technical feature

1 According to Eurovent standard. Air: 27°C BS / 19°C BH , Eau: 7°C/12°C. 2 According to Eurovent standard. Air: 20°C, Water: 70°C/60°C.3 Sound pressure considering a local attenuation of 9 dB for a volume of 100 m3 with a reverberation time of 0,5 sec.

Page 220: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Water Terminals218

KCO2 ECMinimum water temperature +5°CMaximum water temperature +80°CMaximum operating pressure 10 bars

1-way chilled water cassette Coanda effectkCo2 eC

operating limit (to be confirmed following selection software issue)

hoSPital

0.8-3.8 kW motor eC

1.0-4.5 kW

technical features Cooling Capacity from 0.8 to 3.8 kW Heating Capacity from 1.0 to 4.5 kW

3 sizes

Versions 2-Pipes 2-Pipes/2-Wires 4-Pipes

Configuration Cassette

Product advantages EC motor with very long consumption Innovative technical solution for architectural installations Advance aesthetic and harmonious design Designed for suspensed ceilling installation Optimum coanda effect through uniform airflow Adjustable multidirectionnal diffusers High including diffusion grille

main options EC motor Electrical heater On-board electronic control Aquanet or terminal block for

wall-mounted control ModBus Communication interface board 2-way or 3-way ON/OFF valve Fresh air intake Condensate drain pump Select KCO2

False ceiling integration Orientable diffusorwith Coanda effect

Page 221: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Water Terminals |

Water term

inals

219

KCO2 EC 60 90 120

Capacities - 2 PIPE (LS/MS/HS)

Cooling1

Total cooling capacity W 890 / 1.180 / 1.560 1.460 / 2.310 / 3.160 1.870 / 2.780 / 3.750Sensible capacity W 620 / 910 / 1.240 1.070 / 1.730 / 2.410 1.370 / 2.060 / 2.830Water flow l/h 153 / 218 / 291 240 / 428 / 585 346 / 514 / 693Water pressure drop kPa 2,1 / 4,0 / 6,5 3,2 / 7,3 / 12,6 5,8 / 11,7 / 19,8

Heating2 Heating capacity W 1.020 / 1.500 / 2.020 1.720 / 2.790 / 3.850 2.190 / 3.300 / 4.540Capacities - 4 PIPE (LS/MS/HS)

Cooling1

Total cooling capacity W 8.920 / 1.180 / 1.560 1.460 / 2.310 / 3.160 1.870 / 2.780 / 3.750Sensible capacity W 620 / 910 / 1.240 1.070 / 1.730 / 2.410 1.370 / 2.060 / 2.830Water flow l/h 153 / 218 / 291 240 / 428 / 585 346 / 514 / 693Water pressure drop kPa 2,1 / 4,0 / 6,5 3,2 / 7,3 / 12,6 5,8 / 11,7 / 19,8

Heating3

Heating capacity W 870 / 1.180 / 1.520 1.580 / 2.310 / 3.010 2.040 / 2.820 / 3.640Water flow l/h 75 / 101 / 131 136 / 199 / 259 175 / 243 / 313Water pressure drop kPa 1,4 / 2,5 / 3,8 1,0 / 2,0 / 3,1 1,8 / 3,3 / 5,1

Sound Levels (LS/MS/HS)Sound power level dB(A) 35 / 46 / 55 34 / 46 / 56 36 / 48 / 58Sound pressure level4 dB(A) 26 / 37 / 46 25 / 37 / 47 27 / 39 / 49NR4 dB(A) 22 / 33 / 42 21 / 33 / 43 23 / 35 / 45Fans (LS/MS/HS)Airflow m³/h 130 / 205 / 295 215 / 370 / 540 275 / 430 / 620Electrical Data (LS/MS/HS)Power supply V / Ph / Hz 230V / 1~ / 50HzAbsorbed power W 8 / 14 / 29 34 / 46 / 56 36 / 48 / 58Electrical heater W 550 1.100 1.400Water ConnectionsType Gas male threadedCooling coil inches 1/2” 1/2” 1/2”Heating coil inches 1/2” 1/2” 1/2”DimensionsCasing (LxWxH) mm 592 x 592 x 309 592 x 970 x 309 592 x 1.192 x 309

technical feature

1 According to Eurovent standard. Air: 27°C BS / 19°C BH, Eau: 7°C/12°C. 2 According to Eurovent standard. Air: 20°C, Water: 70°C/60°C.3 Sound pressure considering a local attenuation of 9 dB for a volume of 100 m3 with a reverberation time of 0,5 sec.

Page 222: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Water Terminals220

Cooling modeMinimum water temperature +5°CMaximum water temperature +60°C Maximum operating pressure 15 barsHeating modeMinimum indoor air temperature (room/intake/around unit) 6°C/15% RHMaximum indoor air temperature (room/intake/around unit) 32°C/70% RH

High wall chilled water unit cooling and heating haWair

technical features Cooling Capacity from 2.2 to 4.7 kW Heating Capacity from 2.0 to 5.9 kW

4 sizes

Versions 2-Pipes

Configuration High Wall

Product advantages Aesthetic design suitable for home and hotel applications

Silent unit for optimum customer comfort Version with Integrated 3-way valve and IR control Choice between IR or wall-mounted thermostat Coil with hydrophilic fins to improve the condensate flow

Light unit for easy installation Very easy servicing through removable front plate Cleanable synthetic-type air filter

Indoor unit compatible with all Systemair Airwell chilled water production units

main options and accessories RC-08A IR control Terminal block for wall-mounted thermostat Version with 3-way ON/OFF valve 3-speed tangential fan motor Motorized flap

Electro-static anti-bacteria filter Pipe connectors Drilling template

Valve Aquanet control Wall-mounted thermostat

operating limit (to be confirmed following selection software issue)

hotel

2.2-4.7 kW 2.0-5.9 kW

Page 223: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Water Terminals |

Water term

inals

221

HAWAIR HWA007 HWA009 HWA018 HWA022

Capacities Nominal

Cooling1

Total cooling capacity W 1.650 / 1.900 / 2.200 1.700 / 2.000 / 2.900 2.900 / 3.300 / 3.600 3.400 / 4.000 / 4.700Sensible capacity W 1.400 / 1.640 / 1.870 1.500 / 1.700 / 2.400 2.400 / 2.650 / 3.000 2.800 / 3.300 / 3.700Water flow l/h 290 / 320 / 400 310 / 360 / 500 490 / 560 / 620 590 / 690 / 810Water pressure drop kPa 3 / 6 / 10 5 / 10 / 16 20 / 27 / 35 27 / 36 / 50

Heating2 Heating capacity W 2.000 / 2.300 / 2.900 2.050 / 2.350 / 3.700 3.800 / 4.300 / 4.800 4.250 / 4.900 / 5.850Sound Levels (LS/MS/HS)Sound power level dB(A) 36 / 40 / 44 38 / 42 / 48 45 / 48 / 52 50 / 54 / 58Sound pressure lesvel4 dB(A) 24 / 32 / 36 30 / 34 / 40 37 / 40 / 44 42 / 46 / 50NR4 dB(A) 19 / 27 / 31 25 / 29 / 35 32 / 35 / 39 37 / 41 / 45Fans (LS/MS/HS)Number 1 1 1 1Airflow m³/h 320 / 380 / 450 400 / 500 / 600 550 / 650 / 750 650 / 750 / 900Electrical Data (LS/MS/HS)Power supply V/Ph/Hz 230V / 1~ / 50HzFan consumption W 22 / 26 / 28 22 / 26 / 28 25 / 28 / 31 43 / 47 / 58Water Connections Type Gas female threadedCoil inches 1/2” 1/2” 1/2” 1/2”Dimensions

WeightCasing (LxWxH) mm 845 x 275 x 180 845 x 275 x 180 940 x 298 x 200 940 x 298 x 200Unit weight 11 11 13 13

technical feature

1 According to Eurovent standard. Air: 27°C DB/19°C WB, Water in: 7°C/12°C.2 According to Eurovent standard. Air: 20°C, Water in: 50°C, same water flow as in cooling.3 Sound pressure considering a local of 100 m3, a reverberation time of 0,5 sec and a distance of 1 m.

Page 224: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Water Terminals222

Cooling modeMinimum water temperature +5°CMaximum water temperature +90°C Maximum operating pressure 10 barsHeating modeMinimum indoor air temperature (room/intake/around unit) 5°C/15% RHMaximum indoor air temperature (room/intake/around unit) 32°C/70% RH

Pressure ductable fan coil unit cooling and heating duCtYS

technical features Cooling Capacity from 0.5 to 6.8 kW Heating Capacity: from 0.6 to 8.8 kW

5 sizes

Versions 2-Pipes 2 pipes/2-Wires 4-pipes

Configuration Ceiling concealed

Product advantages EC fan motor with very low consumption Very low height (223 mm) Ease of installation and maintenance In-line or same side (U-type) airflow diffusion Static pressure available up to 100 Pa Very low operating acoustical levels Selection of hydraulic and electric service side Configuration flexibility thanks to modular conception Various air intake and discharge configuration: rectangular

or duct connections

main options and accessories EC motor Electrical heater with inserted heating rod On-board electronic control or terminal block for wall-mounted

control ModBus Communication interface board 2-way or 3-way ON/OFF valve Ducted or rectangular plenum for air intake or dischage Fresh air intake Condensate drain pump G2 filter

Many aeraulic configurations

operating limit (to be confirmed following selection software issue)

0.5-6.8 kW motor eC

0.6-8.8 kWoFFiCeS

Fuse holder 2-way or 3-way ON/OFF valve Large choice of controls: Electro-mechanic, electronic,

on-board or wall-mounted IR control Suspension kit and Selection software

Page 225: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Water Terminals |

Water term

inals

223

Performances based on: 1 According to Eurovent standard. Air: 27°C DB / 19°C WB , Water: 7°C/12°C. 2 According to Eurovent standard. Air: 20°C, same water flow as in cooling. 3 According to Eurovent standard. Air: 20°C, Water: 70°C/60°C. 4 Sound pressure considering an hypothetical installation and local attenuation of 21 dB. 5 Energy class according to Eurovent. According to Eurovent standard 6/9 (thermal), 6/10 (airflow) and 8/12 (acoustics).

technical feature

dUCtys dt10 dt15 dt20 dt25 dt40

Capacities - 2 tubes

Cooling1

Total cooling capacity W 597 / 1.567 / 1.890

1.230 /1.700 / 1.970

1.720 /2.230 / 2.460

2.450 /2.810 / 3.260

2.190 /4.680 / 5.490

Sensible capacity W 497 /1.323 / 1.608

1.130 /1.540 / 1.820

1.460 /1.950 / 2.250

1.990 /2.280 / 2.690

1.720 /3.730 / 4.400

Available static pressure Pa 5 / 28 / 48 19 / 50 / 80 26 / 50 / 66 32 / 50 / 66 7 / 50 / 72Water flow l/h 103 / 270 / 325 210 / 290 / 340 305 / 380 / 430 420 / 480 / 565 400 / 854 / 1.002Water pressure drop kPa 1 / 3 / 5 4 / 7 / 9 8 / 13 / 15 16 / 21 / 28 7 / 27 / 36

Heating2 Total heating capacity W 672 /1.884 / 2.359

1.600 /2.260 / 2.790

2.410 /2.930 / 3.100

3.070 /3.600 / 4.020

2.570 /5.430 / 6.340

Capacities - 4 tubes

Cooling1

Total cooling capacity W 591 / 1.522 / 1.826

1.190 /1.610 / 1.920

1.670 /2.190 / 2.390

2.220 /2.730 / 3.010

1.790 /3.760 / 4.450

Sensible capacity W 492 /1.283 / 1.551

1.080 /1.470 / 1.750

1.420 /1.930 / 2.150

1.760 /2.200 / 2.460

1.931 /4.049 / 4.799

Available static pressure Pa 5 / 28 / 48 18 / 50 / 72 25 / 50 / 64 31 / 50 / 55 6 / 50 / 77Water flow l/h 102 / 262 / 314 205 / 280 / 330 290 / 380 / 410 380 / 470 / 520 388 / 804 / 948Water pressure drop kPa 1 / 3 / 5 4 / 7 / 9 8 / 13 / 15 13 / 20 / 23 7 / 24 / 31

Heating3

Total heating capacity W 655 /1.806 / 2.250

2.230 /2.850 / 3.220

3.170 /3.460 / 3.540

3.580 /4.220 / 4.540

3.235 /5.946 / 6.559

Water flow l/h 56 / 156 / 194 190 / 250 / 280 270 / 300 / 310 310 / 365 / 390 279 / 512 / 565Water pressure drop kPa 1 / 4 / 7 6 / 9 / 12 12 / 16 / 17 15 / 21 / 24 2 / 16 / 18

Sound Level (PV/MV/GV)Sound power Inlet + Rad dB(A) 27 / 47 / 53 44 / 52 / 60 50 / 57 / 61 50 / 55 / 61 45 / 58 / 63Sound power Outlet dB(A) 27 / 46 / 52 45 / 56 / 62 48 / 57 / 61 50 / 56 / 61 38 / 59 / 64Sound pressure4 dB(A) 20 / 36 / 41 26 / 35 / 42 28 / 36 / 40 32 / 36 / 43 34 / 44 / 50NR4 <15 / 23 / 30 21 / 30 / 37 23 / 31 / 35 27 / 31 / 38 21 / 35 / 40VentilationAir flow 2-tubes m3/h 90 / 280 / 370 270 / 400 / 505 370 / 520 / 600 440 / 550 / 640 299 / 741 / 915Air flow 4-tubes m3/h 89 / 269 / 350 265 / 380 / 480 360 / 510 / 575 410 / 525 / 595 350 / 812 / 1.008Electrical Data (PV/MV/GV)Alimentation V/Ph/Hz 230V / 1~ / 50Hz-60HzPower consumption W 9 / 14 / 38 8 / 30 / 60 18 / 47 / 72 26 / 41 / 64 10 / 65 / 114Voltage V 2,0 / 7,1 / 9,6 3,8 / 6,0 / 8,2 4,8 / 7,1 / 8,9 3,1 / 3,9 / 4,9 2,1 / 5,5 / 7,1Electric heater W 1.000 600 / 1.000 600 / 1.000 1.000 / 2.000 1.250 / 2.500Energetic Class

2-pipes5FCEER B B B B AFCCOP A A A A A

4-pipes5FCEER B B B B AFCCOP A A A A A

HydraulicType Gas Female threaded Cooling inch 1/2” 1/2” 1/2” 1/2” 1/2”Heating inch 1/2” 1/2” 1/2” 1/2” 1/2”DimensionsL x P x H (hors bac) mm 581 x 540 x 223 581 x 640 x 223 581 x 740 x 223 581 x 840 x 223 603 x 1.140 x 223Weight

kg 14 16 18 20 31

Page 226: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Water Terminals224

Cooling modeMinimum water temperature +5°CMaximum water temperature +60°C Maximum operating pressure 15 barsHeating modeMinimum indoor air temperature (room/intake/around unit) 5°C/15% RHMaximum indoor air temperature (room/intake/around unit) 32°C/70% RH

High static pressure ductable fan coil unit cooling and heating Vh

technical features Cooling Capacity from 2.1 to 28.4 kW Heating Capacity from 3.5 to 33.9 kW 6 sizes

Versions 2-Pipes 2 pipes/2-Wires 4-pipes

Configuration Ceiling concealed

Product advantages Ease of installation and maintenance High static pressure avaiable up to 200 Pa Airflow rate up to 4.650 m³/h Very low operating acoustical levels in low speeds Selection of hydraulic and electric service side Configuration flexibility thanks to modular conception Various air intake configuration: rectangular or duct

connections G3 filter as standard Compliant with ERP directive

main options and accessories Electrical heater with inserted heating rod 2-stage heater available with Aquanet control Selection of 3 speed

Large choice of control: Electro-mechanic, electronic, on-board or wall-mounted

Large choice of control: Electro-mechanic, ModBus Communication interface board

2-way or 3-way ON/OFF valve

3.5-33.9 kW 2.1-28.4 kWFaCtorY

operating limit (to be confirmed following selection software issue)

G4 filter in option Ducted or rectangular plenum for air intake or dischage Fresh air intake Double skin insulation for ERP applications Auxiliary condensate drain pan Condensate drain pump Relay Fuse holder Individual packaging Valve Control IR control Drain pan Condensate drain pump Choice of ducted plenum for air intake or dischage Selection software

Page 227: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Water Terminals |

Water term

inals

225

VH 07 15 18 21 24 27

Capacities - 2 PIPE - Nominal at 50 Pa

Cooling1

Total cooling capacity W 4.560 /5.500 / 5.810

7.080 /11.930 / 13.990

7.860 / 14.430 / 17.560

8.290 /16.130 / 20.180

15.170 /17.240 / 19.720

16.780 /19.400 / 22.640

Sensible capacity W 3.270 /4.150 / 4.470

5.220 /9.610 / 11.890

5.590 /10.840 / 13.660

5.780 /11.690 / 14.940

11.110 /12.790 / 14.890

11.830 /13.780 / 16.240

Water flow l/h 785 /950 / 1.000

1.220 /2.055 / 2.410

1.354 /2.486 / 3.025

1.430 /2.778 / 3.476

2.613 /2.970 / 3.400

2.890 /3.342 / 3.900

Water pressure drop kPa 27 / 39 / 45 8 / 20 / 26 7 / 20 / 28 8 / 29 / 43 13 / 17 / 21 14 / 18 / 23

Heating2 Heating capacity W 5.370 /7.060 / 7.630

8.010 /14.870 / 18.370

8.730 /17.050 / 21.620

9.010 /18.110 / 23.110

18.590 /21.620 / 25.310

19.070 /22.290 / 26.370

Capacities - 2 PIPE - Nominal at 50 Pa

Cooling1

Total cooling capacity W 4.180 /5.020 / 5.300

6.560 /10.460 / 11.990

6.950 /11.570 / 13.500

7.930 /14.760 / 18.100

14.050 /15.790 / 17.810

15.220 /17.300 / 19.790

Sensible capacity W 2.990 /3.740 / 4.020

4.940 /8.840 / 10.810

5.190 /9.540 / 11.810

5.630 /10.970 / 13.860

10.630 /12.160 / 14.040

11.110 /12.800 / 14.910

Water flow l/h 720 /865 / 913

1.130 /1.800 / 2.065

1.200 /1.993 / 2.325

1.366 /2.540 / 3.118

2.420 /2.720 / 3.068

2.622 / 2.980 / 3.410

Water pressure drop kPa 20 / 27 / 30 6 / 13 / 17 7 / 17 / 23 11 / 35 / 51 15 / 19 / 23 13 / 17 / 21

Heating3

Heating capacity W 5.890 /7.470 / 8.050

10.800 /19.190 / 23.380

10.890 /19.190 / 23.370

10.890 /19.190 / 23.370

20.880 /23.600 / 26.950

20.860 /23.590 / 26.920

Water flow l/h 725 / 920 / 990

1.330 /2.360 / 2.880

1.340 /2.360 / 2.875

1.340 /2.360 / 2.875

2.570 /2.900 / 3.320

2.560 /2.900 / 3.310

Water pressure drop kPa 9 / 14 / 16 39 / 109 / 156 24 / 66 / 95 24 / 66 / 95 74 / 93 / 118 46 / 58 / 75

Sound Levels (LS/MS/HS)Sound power level4 dB(A) 54 / 60 / 63 52 / 65 / 72 52 / 65 / 72 52 / 65 / 72 65 / 69 / 72 65 / 69 / 72Sound pressure level5 dB(A) 53 / 59 / 61 52 / 64 / 71 52 / 64 / 71 52 / 64 / 71 63 / 67 / 71 63 / 67 / 71Sound pressure level5 dB(A) 33 / 39 / 42 31 / 44 / 51 31 / 44 / 51 31 / 44 / 51 44 / 48 / 54 44 / 48 / 54NR5 dB(A) 27 / 34 / 37 27 / 40 / 47 27 / 40 / 47 27 / 40 / 47 40 / 44 / 51 40 / 44 / 51Fans (LS/MS/HS)Number 2 2 2 2 2 2Static pressure kPa 30 / 50 / 70 15 / 50 / 90 15 / 50 / 90 15 / 50 / 90 35 / 50 / 75 35 / 50 / 75

Airflow at 50 Pa m³/h 703 /977 / 1.125

960 /2.112 / 2.830

960 /2.112 / 2.830

960 /2.112 / 2.830

2.040 /2.413 / 2.925

2.040 /2.413 / 2.925

Electrical Data (LS/MS/HS)Power supply V/Ph/Hz 230V / 1~ / 50Hz-60HzFan consumption STD W 132 / 182 / 222 180 / 421 / 675 180 / 421 / 675 180 / 421 / 675 420 / 530 / 870 420 / 530 / 870Electrical heater (max) W 2.000 3.000 3.000 3.000 3.000 3.000Water connections

Type Gas Female threaded Gas male threaded

Cooling coil 2-Pipes inches 1/2” 1” 1 1/4” 1 1/4” 1 1/4” 1 1/4”Cooling coil 4-Pipes inches 1/2” 1” 1” 1” 1 1/4” 1 1/4”Heating coil inches 1/2” 3/4” 3/4” 3/4” 3/4” 3/4”Dimensions

Rect-rect (LxWxH) mm 698 x 1.200 x 250

798 x 1.380 x 375

798 x1.380 x 375

798 x1.380 x 375

798 x1.500 x 450

798 x 1.500 x 450

Circ-Circ (LxWxH) mm 1.014 x1.200 x 250 - - - - -

WeightRect-rect (Unit weight) kg 42 63 65 67 76 80Circ-circ (Unit weight) kg 48 - - - - -

technical feature

1 Air: 27°C DB/19°C WB, Water in: 7°C/12°C, 50 Pa external static pressure.2 Air: 20°C, Water in: 50°C, same water flow as in cooling, 50 Pa external static pressure.3 Air: 20°C, Water in: 70°C/60°C, 50 Pa external static pressure.4 According Eurovent standard: Return + radiated sound power level given for a unit with 50 Pa external static pressure in medium speed.5 Sound pressure considering an hypothetical installation and local attenuation of 21 dB.

Page 228: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Water Terminals226

Water Terminal Control

electro-mechanical Control

A full range dedicated to your needs

CMV TBMV TRM-VP TRM-FA

System CMV TBMV TRM-VP TRM-FA TAE 20 AQuASIMP AQuANET2 Pipes Reversible + valves > > > > > >2 Pipes / 2 Wires + valves > > > >2 Pipes / 2 Wires reversible + valves > >4 Pipes + valves > > > > > >No valves > (Not recommended) > > > >ActionChange over Manual Manual Manual Automatic Manual or automatic Manual or automaticFan speed selection Manual Manual Manual Manual Manual Manual or automatic

Fan action Continuous Fan1 Cycling fan2 Continuous fan1 Cycling fan2 Continuous1 or cycling fan2

Continuous1 or cycling fan2

Continuous or cycling fan2

Master/slaves Up to 10 slaves with no additional interface

Up to 15 slaves with only one control device

1 Continuous Fan: Fan runs continuously in cooling or heating mode.2 Cycling Fan: Fan stops and starts with temperature demand.

Page 229: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Water Terminals |

Water term

inals

227

Carte nIU

Carte e-nIU - MOdBUS

rCL Wired remote control Advanced Control Performance Temperature sensor included Display of temperature Selection of the speed LED - On/Off & Default

Managing up to 15 different zone, with a maximum of 80 units.

Programming and control of the temperature indivdualized by zone

Weekly programmation 2 daily ranges configurable by area

This card allow the connection to a Modbus communication protocol.

The nIU card gives an individual adress to each fan coil inside the communication bus system. Manual programmation with DIP Switch

electronic Control

TAE 20 AQUASIMP AQUAnET

OR

µBMS

rC7 infra remote control Advanced Control Performance Temperature sensor included Display of temperature Selection of the speed LED - On/Off & Default

TAE 20

A full range dedicated to your needs

System CMV TBMV TRM-VP TRM-FA TAE 20 AQuASIMP AQuANET2 Pipes Reversible + valves > > > > > >2 Pipes / 2 Wires + valves > > > >2 Pipes / 2 Wires reversible + valves > >4 Pipes + valves > > > > > >No valves > (Not recommended) > > > >ActionChange over Manual Manual Manual Automatic Manual or automatic Manual or automaticFan speed selection Manual Manual Manual Manual Manual Manual or automatic

Fan action Continuous Fan1 Cycling fan2 Continuous fan1 Cycling fan2 Continuous1 or cycling fan2

Continuous1 or cycling fan2

Continuous or cycling fan2

Master/slaves Up to 10 slaves with no additional interface

Up to 15 slaves with only one control device

Page 230: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Water Source Heat Pump

SYSeFtYS 2.1-2.7 kW 2.7-3.2 kW 407C

SYSCWar 1.9-2.7 kW 2.4-3.2 kW 407C Scroll

SYShrW 5.3-30 kW 5.8-38 kW 407C

Page 231: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

CLOSE CONTROL

Water Source Heat Pump |

WaTER SOuRCE

HEaT PumP

229

Product Range Capacity Acoustic Flow rate Pressure Fan Size (LxHxP) mm

SySE

FTyS

EFTyS 2000 2 kW NR 32 at MS

452 m³/h at HS

50Pa at HS EC

900x530x239

EFTyS 2500 2.4 kW NR 34

at MS503 m³/h

at HS 900x530x239

EFTyS 3000 3 kW NR 37

at MS605 m³/h

at HS 900x530x239

SySC

WAR

CWAR 07 1.9 kW NR 37

at MS400 m³/h

at HS

0 Pa EC*

1.138x251x821

CWAR09 2.1 kW NR 38

at MS460 m³/h

at HS 1.138x251x821

CWAR12 2.7 kW NR 40

at MS510 m³/h

at HS 1.138x251x821

SySH

RW

HRW019 5.3 kW NR 42

at MS1.250 m³/h

at HS>50 Pa at HS 900x600x439

HRW027 7.4 kW NR 44

at MS1.185 m³/h

at HS>50 Pa at HS 1.050x660x460

HRW030 8.7 kW NR 43

at MS1.490 m³/h

at HS>100 Pa

at HS 1.050x660x460

HRW036 10.1 kW NR 44

at MS1.580 m³/h

at HS>100 Pa

at HS 1.250x705x513

HRW042 11.4 kW NR 44

at MS2.040 m³/h

at HS>100 Pa

at HS 1.250x705x513

HRW048 12.9 kW NR 47

at MS2.750 m³/h

at HS>100 Pa

at HS 1.250x705x513

HRW060 14.3 kW NR 47

at MS2.840 m³/h

at HS>100 Pa

at HS 1.250x705x513

HRW072 17.1 kW NR 48

at MS3.570 m³/h

at HS>100 Pa

at HS 1.250x705x513

HRW096 21.7 kW NR 56

at HS4.700 m³/h

at HS>100 Pa

at HS 1.680x955x770

HRW120 30 kW NR 57

at HS5.600 m³/h

at HS>200 Pa

at HS 1.680x955x770

Selection guide Water Source Heat Pump

Ideal solution for refurbishment, and R22 units replacement, as well as for new applications.

Advance scroll technology

Rotary or scroll springs compressor

REFRIGERANTOZOnE FrIEndLy

TECHNOLOGy AND RELIABILITy Stantard protective devices: Flow switch/pressostat on hydraulic circuit LP pressure switch Fuse holder

Page 232: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Water Source Heat Pump 230

Product Avantages Measurement of the room air temperature Anti-short cycle to protect the compressor Variable sequential start-up function avoiding a power surge Emergency shut-down / stand-by / night setback Automatic HP reset pressure and/or lack of water flowrate Automatic BP reset pressure Défaut ipsotherme moteur ventilateur Anti-freeze safety function Low temperature limit in cooling/heating mode High temperature limit in cooling/heating mode Antifreeze default in cooling mode Managing of motorized water valves Chaining Modbus

main functions

Digital display On/Off Selection of the working mode Display of the room temperature Display of the room temperature Selection of the speed of the fan A keypad lock function is also available Display LED which shows the operating status of the water

source heat pump Master/slaves control up to 10 units with only one remote

control

Remote control RCL

STORM 2 electronic control system

Page 233: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

CLOSE CONTROL

Water Source Heat Pump |

WaTER SOuRCE

HEaT PumP

231

advanced functianilities modbus communication as a standard 0 -10 V output to control EC motor, 100% modulated Fault

reports of eight different possible machine faults

Four different operating modes for water source heat pumps by selecting the following systems:Thermodynamic cooling and heating operation (RC).Thermodynamic cooling and heating operation or heating operation with an additional electric heater (SH).Thermodynamic cooling operation and electrical heating operation (RH).Thermodynamic cooling operation only (ST).

Main functions Display LED which shows the operating Advanced Control Performances Temperature sensor included Display of temperature Selection of the speed LED - On/Off & Default Infrared remote control RC07

Mini central supervisor µBMS

Main functions

Managing up to 15 different zone, with a maximum of 80 units Programming and control of the temperature indivdualized by

zone Weekly programmation 2 daily ranges configurable by area

Page 234: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Water Source Heat Pump 232

SySEFTyS

Water inlet temperatureCooling

Min 18 °CMax 45°C

HeatingMin 9°CMax 32°C

Return Air temperatureCooling

Min 21°C db / 15°C wbMax 32°C db / 23°C wb

HeatingMin 15°CMax 25°C

Maximum operating pressure 31 bars

Water source heat pumpSYSeFtYS

technical features Cooling Capacity from 1.9 to 3.0 kW Heating Capacity from 2.7 to 3.6 kW

Sizes: 3 models, 1 casings

Versions RC: cooling and heating ST: cooling only SH: cooling and heating or electrical heating RH: cooling and electrical heating

Configuration Horizontal concealed installation

Product advantages A coaxial heat exchanger robust in presence of loaded water An extended working range +9° to +48° High energetical performances, with EC motor and high COP/

EER Coil at the oultet to avoid the installation of a siphon Stand-alone STORM2 electronic control with ModBus

Communication Easy access to components through wide removable panels Many aeraulic and hydraulic configuration to easily replace

the unit alread on site Extended working range through coaxial heat exchanger Acoustical insulation and compressor isolated and mounted

on spring to an optimal acoustical comfort Anti-corrosion treated drain pan Low height < 250 mm

operating limit (to be confirmed following selection software issue)

hotel oFFiCeS

1.9-3.0 kW 407C

2.7-3.6 kW

main options and accessories G2/ M1 filter Electrical heater Quick connector General alarm dry contact Circuit breaker Front or lateral ducted plenum for air discharge Fresh air intake Individual packaging Room sensor Flow switch for low waterflow protection Motorized water valve µBMS mini-supervision station RCL remote control

Page 235: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

CLOSE CONTROL

Water Source Heat Pump |

WaTER SOuRCE

HEaT PumP

233

SySEFTyS FT20 FT25 FT30Total cooling capacity1 W 2.057 2.405 2.983Sensible cooling capacity1 W 1.686 1.983 2.346Heating capacity1 W 2.706 2.997 3.558PerformancesCOP1 4,12 4,17 4,3EER1 3,88 4,13 3,85Fansnominal Airflow m³/h 452 503 605Air filter number / Efficiency 1 / G2 1 / G2 1 / G2Air filter dimensions / Thickness mm 225 x 365 / 20 225 x 365 / 20 225 x 365 / 20Water Connectionsnominal water flow l/h 418 457 623Cutoff water flow vs nominal water flow2 % 43 39 29WPd at nominal water flow kPa 11 13 23WPd at nominal water flow with valve kPa 27 30 44Hydraulic connections inches Male type ISO G 1/2” INTCondensate outlet - external ø mm 16 16 16Electical DataPower supply V / Ph / Hz 230V / 1~ / 50Hz 230V / 1~ / 50Hz 230V / 1~ / 50HzPower input - cooling mode3 W 595 648 879Power input - heating mode3 W 722 785 932Electrical heater4 W 1.200 1.600 2.000Fan maximum current (ESP=0Pa) A 0,85 0,85 1,4Compressor nominal current A 2,8 3,0 4,0Compressor starting current A 16 16 18,9Sound levelsSound power level intake+Rad5 dB(A) 55/57/59 56/58/60 56/58/62Sound power level Discharge5 dB(A) 53/55/56 54/56/58 58/61/65Sound pressure level6 dB(A) 34/36/38 35/37/39 37/40/44NR5 dB(A) 30/32/34 31/34/36 34/37/42DimensionsL x W x H mm 900x530x 240 900x530x240 900x530x240WeightUnit weight kg 48 48 48

technical feature

1 Performances given at nominal conditions. Cooling mode: Tair=27 °C, Twater=30 °C & Heating mode: Tair=20°C, Twater=20°C.2 Protection by flow switch (accessory).3 Absorbed power (compressor + fan) at nominal conditions.4 Electric heating coil is an optional feature available on SH & RH versions.5 Sound power level considering 50Pa available static pressure in high speed, in-line unit configuration with filter.6 Sound pressure considering an hypothetical installation and local attenuation of 21 dB.

Page 236: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Water Source Heat Pump 234

SySHRW 19-72 96-120

Water inlet temperatureCooling

Min 18°C 20°CMax 44°C 48°C

HeatingMin 13°CMax 34°C

Return Air temperatureCooling

Min 21°C BS/15°C BHMax 38°C BS/28°C BH 38°C BS/28°C BH

HeatingMin 15°CMax 27°C 25°C

Maximum operating pressure 31 bars

Water source heat pumpSYShrW

technical features Cooling Capacity from 5.8 to 38.1 kW Heating Capacity from 5.3 to 3.0 kW Refregirant: R407C

Sizes: 10 models, 4 casings Versions RC: cooling and heating ST: cooling only SH: cooling and heating or elctrical heating RH: cooling and electric heating

Configuration Horizontal concealed installation

Product advantages A coaxial heat exchanger robust in presence of loaded water

High efficiency horizontal units with high COP 5 optimized compact casing Easy access to components through wide removable panels In-line or perpenducular air blowing Brazed stainless steelPlate heat exchanger for improved

efficiency Flow switch for antifreeze protection as standard

Bi-flow thermostatic expansion valve as standard Anti-corrosion treated drain pan

Float-type safety system to protect agains condensate overflow

Stand-alone STORM electronic control with RCL remote control

operating limit (to be confirmed following selection software issue)

ShoPPing

5.3-3.0 kW 407C

5.8-38.1 kW Scroll

main options and accessories G2/ M1 filter µBMS-2 mini-supervision station ModBus Communication interface board 3-speed direct drive fan motor (up to 17 kW) or belt-driven

fan with variable pitch pulley (above 17 kW) G2 filter as standard, G3 in option*

15 mm thick thermal and acoustical insulation M1-class fire insulation Electrical heater Motorized water valve General alarm dry contact Disconnect switch*

Front or lateral ducted plenum for air intake*

Fresh air intake Individual packaging*

Room sensor

* Available on some models.

Page 237: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

CLOSE CONTROL

Water Source Heat Pump |

WaTER SOuRCE

HEaT PumP

235

SySHRW 019 027 030 036 042 048 060 072Total cooling capacity W 5.278 7.419 8.691 10.138 11.366 12.965 14.344 17.174Sensible cooling capacity W 4.257 5.824 6.315 7.278 8.849 10.051 10.988 13.536Heating capacity W 5.826 8.342 9.759 11.036 14.422 14.904 16.147 21.500Fansnominal Airflow m³/h 1.250 1.185 1.490 1.580 2.040 2.750 2.840 3.570Motor power W 145 145 210 245 320 550 550 550Fan speeds Nbr 3 3 3 3 3 3 3 3Air filter number/Efficiency 2/G2 2/G2 2/G2 2/G2 2/G2 2/G2 2/G2 2/G2

Air filter dimensions/Thickness mm 365x 300/25

365x 300/25

385x 350/25

385x 350/25

450x 440/25

450x 440/25

450x 440/25

450x 440/25

Water ConnectionsPlate heat exchanger Nbr 1 1 1 1 1 1 1 1nominal water flow1 l/h 920 1.540 1.764 2.030 2.592 2.822 3.348 3.924Cutoff water flow vs nominal water flow % 50 50 47 45 39 38 35 41WPd at nominal water flow1 kPa 13 17 23 25 33 34 40 61WPd at nominal water flow with valve6 kPa 16 23 33 39 55 60 77 112Hydraulic connections inches ISO G 3/4” INT Condensate outlet (external ø) mm 19 19 19 19 19 19 19 19Refrigerant circuitNumber of circuit 1 1 1 1 1 1 1 1Compressor type Rotatif Scroll Scroll Scroll Scroll Scroll Scroll ScrollElectical Data

Power supply V/Ph/Hz 230V / 1~ / 50Hz 400V / 3~N / 50Hz

Power input (cooling mode)4 W 1.557 2.118 2.658 3.044 3.584 4.200 4.989 6.280Power input (heating mode)4 W 1.611 2.332 2.983 3.460 3.920 4.300 5.150 7.347Electrical heater W 2.250 3.750 3.750 4.500 5.500 6.500 7.500 9.000Fan maximum current (ESP=0Pa)7 A 1,5 1,5 2,6 2,4 3,55 4,7 4,7 6,9Compressor nominal current A 6,6 3,7 4,5 5,4 5,7 7 7,5 10,6Compressor starting current A 33 32 40 46 51,5 54 65,5 101Sound levelsSound power level8 dB(A) 51/54/58 54/56/57 53/54/57 53/56/58 54/56/58 55/59/63 55/59/63 57/60/63Sound pressure level9 dB(A) 44/47/51 47/49/50 46/47/50 46/49/51 47/49/51 48/52/56 48/52/56 50/53/56NR9 dB(A) 39/42/46 42/44/45 41/43/45 41/44/46 42/44/46 43/47/49 43/47/49 45/48/51Dimensions

LxWxH mm 900 x 600 x 439

1.050 x 660 x 460

1.050 x 660 x 460

1.050 x 660 x 460

1.250 x 705 x 513

1.250 x 705 x 513

1.250 x 705 x 513

1.250 x 705 x 513

Weight Unit weight kg 80 100 100 112 133 140 144 149

technical feature

1 Nominal cooling capacities based on: Air: 27°C DB/19°C WB, Entering water temperature: 30°C.2 Nominal heating capacities based on: Air: 20°C DB/15°C WB, Entering water temperature: 20°C.3 Protection by differential pressure switch on units HRW 019 to 120.4 Absorbed power (compressor + fan) at nominal conditions.5 Electric heating coil is an optional feature available on SH & RH versions.6 Total water pressure drop with optional water valve fitted.7 fan power supply: 230V/1Ph for HRW 072, 400V/3Ph for HRW 096 & 120.8 Sound power level considering 1,5 m return and discharge duct and unit suspended at 1m. 9 Sound pressure considering an hypothetical installation and local attenuation of 7 dB.* Only with return air plenum.** one RCL is delivery with unit as standard with size 19 to 120.

Page 238: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Water Source Heat Pump 236

SySHRW 096 120Total cooling capacity W 21.743 29.951Sensible cooling capacity W 17.986 24.413Heating capacity W 26.637 38.109Fansnominal Airflow m³/h 4.700 5.600Motor power W 1.100 1.500Fan speeds Nbr - -Air filter number/Efficiency 2/G2 2/G2Air filter dimensions/Thickness mm 620x650/25 620x650/25Water ConnectionsPlate heat exchanger Nbr 1 1nominal water flow1 l/h 4.860 6.408Cutoff water flow vs nominal water flow % 44 30WPd at nominal water flow1 kPa 55 80,5WPd at nominal water flow with valve6 kPa 133 250Hydraulic connections inches ISO G 1 1/4”Condensate outlet (external ø) mm 22 22Refrigerant CircuitNumber of circuit 1 1Compressor type Scroll ScrollElectrical DataPower supply V/Ph/Hz 400V / 3~N / 50Hz 400V / 3~N / 50HzPower input (cooling mode)4 W 6.317 8.547Power input (heating mode)4 W 7.895 10.224Electrical heater W 13.000 16.000Fan maximum current (ESP=0Pa)7 A 2,5 4,1Compressor nominal current A 11,4 14,8Compressor starting current A 111 118Sound LevelsSound power level8 dB(A) 68 69Sound pressure level9 dB(A) 61 62NR9 dB(A) 56 57DimensionsLxWxH mm 1.680 x 955 x 770 1.680 x 955 x 770WeightUnit weight kg 253 262

technical features

1 Nominal cooling capacities based on: Air: 27°C DB/19°C WB, Entering water temperature: 30°C.2 Nominal heating capacities based on: Air: 20°C DB/15°C WB, Entering water temperature: 20°C.3 Protection by differential pressure switch on units HRW 019 to 120.4 Absorbed power (compressor + fan) at nominal conditions.5 Electric heating coil is an optional feature available on SH & RH versions.6 Total water pressure drop with optional water valve fitted.7 Fan power supply: 230V/1Ph for HRW 019 to 072, 400V/3Ph for HRW 096 & 120.8 Sound power level considering 1,5 m return and discharge duct and unit suspended at 1m.9 Sound pressure considering an hypothetical installation and local attenuation of 7 dB.

Page 239: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

CloSe Control

Water SourCe

heat PumP

Page 240: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Water Source Heat Pump 238

SySCWAR

Water inlet temperatureCooling

Min 23°CMax 42°C

HeatingMin 12°CMax 34°C

Return Air temperatureCooling

Min 21°C BS/15°C BHMax 32°C BS/23°C BH

HeatingMin 15°CMax 27°C

Maximum operating pressure 3 bars

Water source heat pumpcooling and heating SYSCWar

operating limit (to be confirmed following selection software issue)

technical features Cooling Capacity from 1.9 to 2.7 kW Heating Capacity from 2.4 to 3.2 kW Refregirant: R407C Sizes: 3 models

Versions RC: cooling and heating CAR: standard with cabinet CARB: low height with cabinet nU: standard without cabinet nUB: low height without cabinet

Configuration Vertical console cabinet Vertical concealed without cabinet

Product advantages A coaxial heat exchanger robust in presence of loaded water

control High efficiency vertical units with high COP Harmonuous and aesthetic RAL9010 painted cabinet design design and elaborate finish enabling harmonious integration Low consumption EC fan motor or 3-speed AC fan motor Stand-alone STORM electronic control with RCL remote control

Brazed stainless steelPlate heat exchanger for improved efficiency

Easy access to components through front panel Ease of installation through selection of service side Direct access to Schrader valves (HP & BP) Flow switch for antifreeze protection as standard Anti-corrosion treated drain pan

hotel oFFiCeS

1.9-2.7 kW 407C

2.4-3.2 kW Scroll

main options G2/ M1 filter µBMS mini-supervision station ModBus Communication interface board L/R Lateral, back or bottom hydrualic connections L/R lateral electrical connection G2 filter 15 mm thick thermal and acoustical insulation LONWorks control Bottom return air with feet or front air intake HP & BP pressure switches General alarm dry contact Disconnect switch

Thermostat

Page 241: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

CLOSE CONTROL

Water Source Heat Pump |

WaTER SOuRCE

HEaT PumP

239

SySCWAR 07 09 12Total cooling capacity W 1.942 2.136 2.743Sensible cooling capacity W 1.526 1.775 2.340Heating capacity W 2.431 2.542 3.156Ventilation nominal Airflow m³/h 400 460 616Motor power W 75 75 75Fan speeds Nbr 3 3 3Air filter number/Efficiency 1/G2Air filter (Front) dimensions/Thickness mm 660x205/6Air filter (Bottom) dimensions/Thickness mm 595x187/6Water ConnectionsPlate heat exchanger Nbr 1nominal water flow1 l/h 428 479 0,171Cutoff water flow vs nominal water flow % 44 40 31WPd at nominal water flow1 kPa 5 3,4 12Hydraulic connections inches ISO G 1/2” INTCondensate outlet (external ø) mm 15x20Refrigerant CircuitNumber of circuit 1Compressor type RotatifElectrical DataPower supply V/Ph/Hz 230V / 1~ / 50HzPower input (cooling mode)4 W 598 647 892Power input (heating mode)4 W 710 720 954Fan maximum current A 0,2 0,25 0,3Compressor nominal current A 2,8 3 4Compressor starting current A 16 16 18,9Sound Levels (LS/MS/HS)Sound power level dB(A) 49/50/51 50/51/53 51/53/54Sound pressure level5 dB(A) 41/42/43 42/43/45 43/45/46NR5 dB(A) 36/37/38 37/38/40 38/40/41Dimensions (LxWxH)Console (STD)6 mm 1.138 x 251 x 821Concealed (STD)6 mm 1.086 x 229 x 769WeightConsole (STD) kg 70 73 75Concealed (STD) kg 55 58 60

technical feature

1 Nominal cooling capacities based on: Air: 27°C DB/19°C WB, Entering water temperature: 30°C.2 Nominal heating capacities based on: Air: 20°C DB/15°C WB, Entering water temperature: 20°C.3 Protection by flow switch on units CW-Ar 007, 009 & 012.4 Absorbed power (compressor + fan) at nominal conditions.5 Sound pressure considering a local of 100 m3, a reverberation time of 0,5 sec and a distance of 1 m.6 Feet included.

Page 242: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Roof Top

han 9.8-31 kW 9.6-30.5 kW 410A Scroll

rooftair 30-108 kW 33-108 kW 410A Scroll

Page 243: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Rooftop |

Roof Top

241

Product Range Capacity Flow rate Pressure Acoustic Power

Size (LxHxP) mm

HAN

HAN 13 13.0 kW 2.640

m3/h 100 Pa 75 dB(A)

1.345 x 95 x 1.320

HAN 15 14.5 kW 2.940

m3/h 170 Pa 75 dB(A)

1.345 x 95 x 1.320

HAN 17 16.8 kW 3.190

m3/h 160 Pa 75 dB(A)

1.345 x 95 x 1.320

HAN 19 18.9 kW 3.860

m3/h 210 Pa 82 dB(A)

1.345 x 95 x 1.320

HAN 25 25.4 kW 4.780

m3/h 240 Pa 82,7 dB(A)

1.420 x 1.320 x 1.445

HAN 31 31.0 kW 5.530

m3/h 250Pa 82,7 dB(A)

1.420 x 1.320 x 1.445

Roof

T@ir

RTL/RTH 30 32.5 kW 5.500

m3/h 400 Pa 84,5 dB(A)

2.484 x1.450 x 1.877

RTL/RTH 40 41.5 kW 7.650

m3/h 400 Pa 84,5 dB(A)

2.484 x1.450 x 1.877

RTL/RTH 50 50.9 kW 9.200

m3/h 400 Pa 88,3 dB(A)

2.484 x1.450 x 1.877

RTL/RTH 60 59.8 kW 11.500

m3/h 450 Pa 82,6 dB(A)

3.400 x 1.771 x 2.227

RTL/RTH 70 67.7 kW 12.500

m3/h 450 Pa 83,3dB(A)

3.400 x 1.771 x 2.227

RTL/RTH 80 84.9 kW 16.500

m3/h 500 Pa 83,8 dB(A)

3.400 x 1.771 x 2.227

RTL/RTH 100

96.6 kW 18.650 m3/h 500 Pa 85,8

dB(A)3.400 x

1.813 x 2.227

RTL/RTH 110

108.4 kW 20.000 m3/h 500 Pa 87,1

dB(A)3.400 x

1.813 x 2.227

Selection guide Rooftop

Page 244: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Rooftop 242

Cooling modeMinimum indoor air temperature 21°C DB/15°C WBMaximum indoor air temperature 32°C DB/23°C WBMinimum outdoor air temperature/with all-season kit 15°C DB/-10°CMaximum outdoor air temperature 50°C DBHeating modeMaximum indoor air temperature 27°C DBMinimum outdoor air temperature -10°CMaximum outdoor air temperature 24°C (16°C for HAN 25)

Rooftop unitcooling and heatinghan

operating limit (for standard unit) (to be confirmed following selection software issue)

technical features Cooling Capacity from 9.8 to 31 kW Heating Capacity from 9.6 to 30.5 kW Refrigerant: R410A Sizes: 6

Product advantages A coaxial heat exchanger robust in presence of loade Weather resistant casing with external panels and drain pan

coated with powder-based epoxy paint colour RAL 7040 Base rail with forklift slots to facilitate transportation and

handling. Technical compartment independent from airstreams allowing

service works to be performed without disturbing the unit operation

High EER and environmentally freindly refrigerant R410A with zero ODP (Ozone Depleting Potentila)

High efficiency scroll compressor with crankcase heater Condenser coils with hydrophilic coated fins to improve

removal of water droplets during defrost cycles Standard microprocessor-based control by CAC controller

main options and accessories G2/ M1 filter Factory-fitted low ambient temperature control to ensure

cooling operation down to -10°C outdoor temperature (All-season)

Synthetic air filter Electric heater Programmable controlller RCW2 to control up to 15 units

with independent set points and programming

9.8-31.0 kW 410a

9.6-30.5 kW Scroll

Page 245: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Rooftop |

Roof Top

243

HAN HAN 13 HAN 15 HAN 17 HAN 19 HAN 25 HAN 31

CoolingCooling capacity kW 13,0 14,5 16,8 18,9 25,4 31,0Power input kW 4,5 4,9 6,0 6,5 8,3 10,0EER 2,88 2,95 2,8 2,9 2,95 3,1

HeatingHeating capacity kW 12,1 14,2 15,8 19,0 24,2 30,5Power input kW 4,3 4,5 5,7 6,0 8,8 9,5COP 2,8 3,1 2,7 3,1 2,75 3,2

CompressorsType Scroll Scroll Scroll Scroll Scroll ScrollNumber 1 1 1 1 1 1VentilationAvailable static pressure Pa 100 170 160 210 240 250

AirflowIndoor fan m³/h 2,640 2,940 3,190 3,860 4,780 5,530Outdoor fan m³/h 9,000 9,000 9,000 9,000 12,000 12,000

Sound Levels*

Lw Outdoor (Configuration A) dB(A) 80,7 79,3 79,3 83,1 84,9 86,4Sound pressure Lp calculated at 1 m dB(A) 76,9 75,5 75,5 79,3 81,1 82,6Sound pressure Lp calculated at 5 m dB(A) 74,8 73,4 73,4 77,2 79,0 80,5Lw Indoor (Configuration B) dB(A) 77,1 75,0 75,0 72,7 78,2 82,7Sound pressure Lp calculated at 1 m dB(A) 73,3 71,2 71,2 68,9 74,4 78,9Sound pressure Lp calculated at 5 m dB(A) 71,2 69,1 69,1 66,8 72,3 76,8Power SupplyPower supply 400V/3N-/50HzFuse rating am A 16 20 20 25 32 32DimensionsLxWxH mm 1,320 x 1,345 x 905 1,420 x 1,445 x 1,320Weight Unit weight kg 219 223 223 243 320 343

technical feature

* Pressure sound level calculated according the following:

Lp = Lw + 10 Log ( Q 4_____ + ___ )4πD² A

Factor Q 2 2 = free field, 4 = against wall, 8 = on cornerV 100 Room volume in m3 (on example, V = 100 m3) Lg = 10T 1 Reverberation time in s lg = 10A 16 A = 0,16 x (V/T) Ht = 2,5D Distance in m

Page 246: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Rooftop 244

Cooling modeMaximum outdoor air temperature 46°CMinimum outdoor air temperature6 20°CHeating modeMaximum outdoor air temperature 21°CMinimum outdoor air temperature -10°C

Rooftair Rooftop unit cooling and heatingrtl/rth 30-110

technical features Cooling Capacity from 32.5 to 108 kW Heating Capacity from 33.3 to 108 kW Refrigerant: R410A Airflow range: from 5.500 to 20.000 m³/h 8 sizes Insulation: 25 mm Glasswool

Product advantages Technical compartments for RTL/RTH 100-110 Weatherproof technical compartment independent from the

airflow with a natural ventilation of the electrical board to stop overheating in summer. All electric cables and wires are protected

Refrigeration system: r410A benefits: best heat transfer and environmental

friendly refrigerant with zero ODP (Ozone Depleting Potential). Stable composition compared to R407C (2 refrigerant mixture instead of 3 with R407C). Temperature glide less than 0,2 K during evaporation, smaller liquid line pipe and lower refrigerant charge.

Refrigeration circuit: cooling only or heat pump version designed to satisfy comfort and commercial applications with scroll compressors for higher efficiency with better resistance to liquid return and less vibration. Crankcase heater on each compressor to eliminate refrigerant migration and improve start up in winter. Tandem compressors on 1-circuit and single compressor on dualcircuits provide 2-stage cooling/ heating capacity. refrigerant brazing, fittings, and indoor coil headers are assembled in one technical compartment to ease service without disturbing unit operation

main options and accessories Filters:

Universal cells’ dimensions mounted on sliding rail for easy service

2 options of flat filters: G4 filter & High efficiency filter G4+F6 compliant with EN 779

operating limit (for standard unit) (to be confirmed following selection software issue)

Factory fitted clogged filter switch wired to the IATC (option) F-damper economizer (r1 and r2 configurations):

economizer allows using the greatest obtainable quantity of outdoor air energy to minimize compressor consumption

Economizer is equipped with 2 counteracting dampers linked together to one proportional actuator wired to IATC

Adjustable minimum position of outdoor air damper to control hygienic ventilation.

The economizer is equipped with sensors wired to the IATC According to control type, 3 combinations of sensors are

available: Sensible, Enthalpy, or, Air quality contro. Additional options:

Standard or ERP conform Roof Curb Antivibration mounts, Smoke detector & Double skin Bi-flow devices (expansion device, filter-dryer, sight glass)

are used on each circuit Outdoor coils designed for low air resistance to reduce axial

fan power consumption and noise level Hydrophilic blue fins provided on outdoor coils (heat pump

version only) for better removal of water droplets on defrost cycle

Holes in the unit floor under the outdoor coils to drain defrost and rain water beyond the roof curb to the roof

Indoor coil (blue fins) allows for commercial or industrial applications with higher dehumidification rate

Extractible drain pan under indoor coil, to allow for hygienic cleaning

Optional low ambient operation kit ensures cooling operation down to -10 °C outdoor temperature

Optional electric heater CH1 & CH2, and, hot water coil

32.5-108 kW 410a

33.3-108 kW Scroll

Page 247: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Rooftop |

Roof Top

245

RTL/RTH 30 40 50 60 70 80 100 110Cooling capacity1 kW 32,5 41,5 50,9 59,8 67,7 84,9 96,6 108,4Power input kW 10,4 12,8 16 18,4 20,9 26 30,9 36,5EER2 3,12 3,3 3,2 3,3 3,2 3,3 3,1 3Power supply 400V - 3ph + N - 50Hz Heat Pump VersionCooling capacity1 kW 32 41 48,6 59 66 83,4 94,8 106,1Power input kW 10,4 12,8 16 18,4 20,9 26 30,9 36,5EER (Cooling mode)2 3,1 3,2 3 3,2 3,2 3,2 3,1 2,9Heating capacity3 kW 33,3 42,9 50,2 58,2 66,5 84 96 108Power input kW 9,5 12,2 15,1 17,8 20,3 24,1 28,5 33,7COP (Heating mode)4 3,5 3,5 3,3 3,3 3,3 3,5 3,4 3,2RefrigerantType HFC 410A Number of circuits 1 1 1 2 2 2 2 2CompressorsNumber of compressors 2 2 2 2 2 2 2 2Assembly type Tandem Tandem Tandem Single Single Single Single SingleCapacity step % 0-50-100 0-50-100 0-50-100 0-50-100 0-50-100 0-50-100 0-50-100 0-50-100 Indoor coilType Copper tubes & aluminium finsNumber of rows 3 3 3 3 3 3 4 4Indoor fanType (standard) Forward curved centrifugalQuantity/Model 1 1/AT 15-15S 1/AT 15-15S 1/ADH 450 1/ADH 450 1/ADH 500 1/ADH 500 1/ADH 500Air flow m³/h 5.500 7.650 9.200 11.500 12.500 16.500 18.650 20.000Nominal static pressure Pa 250 250 250 300 300 350 350 350Motor power kW 1,5 1,5 2,5 5,5 5,5 7,5 7,5 7,5Type (optional) Back curved Forward curved centrifugal Backward curved centrifugalQuantity/Model 1 1/AT 15-15S 1/AT 15-15S 1/RDH 450 1/RDH 450 1/RDH 500 1/RDH 500 1/RDH 500Air flow m³/h 5.500 7.650 9.200 11.500 12.500 16.500 18.650 20.000Nominal static pressure Pa 400 400 400 450 450 500 500 500Motor power kW 2,2 4 5,5 5,5 5,5 7,5 7,5 7,5Outdoor coilType / Number of rows Copper tubes & aluminium fins / 2Outdoor fansType PropellerDiameter mm 610 610 610 610 610 610 800 800Quantity 2 2 2 4 4 4 2 2Fan rotational speed rpm 850 850 850 850 850 850 670 670nominal air flow m³/h 16.000 16.000 16.000 32.000 32.000 32.000 34.000 34.000Total motor power kW 1,14 1,14 1,14 2,28 2,28 2,28 2 2Synthetic Flat Filters (Optional) number of filters 4 4 4 9 9 9 9 9Efficiency/Filter class > 90%/G4 Type Universal cellsSynthetic Flat Filters (Optional) number of filters 4 4 4 9 9 9 9 9Efficiency/Filter class > 90%/F6 Type Universal cellsCasingMin, casing thickness mm 1 1 1 1 1 1 1 1Painting type / RAL Powder coating / 9001Fire resistance class M0 Dimensions & WeightLength mm 2.484 2.484 2.484 3.400 3.400 3.400 3.400 3.400Width mm 1.877 1.877 1.877 2.227 2.227 2.227 2.227 2.227Height mm 1.450 1.450 1.450 1.771 1.771 1.771 1.813 1.813Weight5 kg 600 650 700 1.100 1.150 1.200 1.300 1.350

technical feature

1 Cooling capacity with Eurovent conditions: 35 °C dry bulb outdoor, 27 °C dry bulb/19 °C wet bulb entering indoor.2 EER = Cooling capacity/Effective power input. 3 Heating capacity with Eurovent conditions: 7 °C dry bulb/6 °C wet bulb outdoor, 20 °C entering indoor. 4 COP = Heating capacity/Power input. 5 Without option. 6 For lower outdoor air temperature (-10 °C), in cooling mode, use low ambient kit (optional).

Page 248: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Close control

CW 21 -152 5-150 kW Chiller water

Cd 031 -71 10-22.1 kW 407C Scroll

md 061-202 18.3-64.1 kW 407C Scroll

Cg 010 -055 9.4-65 kW 407C

Page 249: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Close Control |

Close Control

247

Chilled Water Close controlCW 5-152

technical features UndEr version down air flow OVER version air up flow EC fans, backward curved blade Advanced microprocessor control interface user and

semi-graphic LCD display EU4 filters Frontal access for maintenance

accessories and options Adjustable base frame Air delivery plenum Centrifugal fans, backward curved blades Double pannels (sandwich) Electric post-heating coil EU5 or EU7 filters Humidification/dehumidification option LAN connection or remote monitoring systems Rear return air (only for up flow version)

technical feature

CW 5-41 5 8 10 21 31 41Total cooling capacity kW 5,7 7,7 9,8 15,1 25,8 35,5Sensibile cooling capacity kW 4,7 6,2 8 13,8 22,6 30,2nominal air flow m3/s 0,35 0,55 0,54 1,11 1,45 1,81Sound pressure level* (up/down flow) dB(A) 55.5/51.5 55.9/51.9 55.9/51.9 54.5/50.5 56/52 58.5/54.5DimensionsLenght mm 650 650 650 650 840 1.238Width mm 450 450 450 650 650 650Height mm 1.970 1.970 1.970 1.970 1.970 1.970

CW 51-152 51 61 82 102 112 152Total cooling capacity kW 49,8 57,8 83 94,8 110,8 152,8Sensibile cooling capacity kW 42,7 51,1 67,9 78 95,8 128,9nominal air flow m3/s 2,78 3,33 4,86 5,56 6,94 10Sound pressure level* (up/down flow) dB(A) 59/55 61.1/57.5 65/61 63/59 64/60 67/63DimensionsLenght mm 1.428 1.618 1.885 1.885 2.265 2.853Width mm 650 650 860 860 860 860Height mm 1.970 1.970 1.980 1.980 1.980 1.980

* Sound pressure level measured at 2 m from the machine and at 1 m from the ground in free field conditions.

5.0-153.0 kW Chilled water

Page 250: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Close Control 248

Close controlwith remote condenserCd 031-071

technical features UndEr version air down flow OVER version air up flow Centrifugal fan double inlet directely coupled Scroll compressors Advanced microprocessor control interface user and

semi-graphic LCD display EU4 filters Frontal access for maintenance

accessories and options Adjustable base frame Air delivery plenum Double pannels (sandwich) Electric post-heating coil EU5 or EU7 filters Humidification/dehumidification option LAN connection or remote monitoring systems Rear return air (only for up flow version)

technical feature

CD 031-071 031 041 051 061 071Total cooling capacity kW 10 12,8 15,3 20,5 22,1Sensibile cooling capacity kW 9,3 12 13,9 19,3 20,5nominal air flow m3/s 0,75 1,11 1,11 1,67 1,67Sound pressure level* (up/down flow) dB(A) 52/48 55/51 55/51 55/51 56/52DimensionsLenght mm 650 840 840 1.238 1.238Width mm 650 650 650 650 650Height mm 1.970 1.970 1.970 1.970 1.970

* Sound pressure level measured at 2 m from the machine and at 1 m from the ground in free field conditions.

10-22.1 kW 407C

Scroll

Page 251: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Close Control |

Close Control

249

Close controlwith remote condensermd 061-202

technical features UndEr version down air flow OVER version air up flow EC centrifugal fans, backward curved blades Advanced microprocessor control interface user and

semi-graphic LCD display EU4 filters Frontal access for maintenance

accessories and options Adjustable base frame Air delivery plenum Double pannels (sandwich) Electric post-heating coil EU5 or EU7 filters Humidification/dehumidification option LAN connection or remote monitoring systems Rear return air (only for up flow version)

technical feature

MD 061-101 061 071 091 101Total cooling capacity kW 18,3 24,3 28,4 32,9Sensibile cooling capacity kW 17,4 23 26,3 30,5nominal air flow m3/s 1,39 2,08 2,08 2,5Sound pressure level* (up/down Flow) dB(A) 55/51 61.5/57.5 61.5/57.5 60.5/56.5DimensionsLenght mm 860 1.258 1.258 1.448Width mm 860 860 860 860Height mm 1.980 1.980 1.980 1.980

MD 102-202 102 132 152 182 202Total cooling capacity kW 32,3 42,6 48 57,6 64,1Sensibile cooling capacity kW 29,7 39,5 45 54,5 59,2nominal air flow m3/s 2,5 3,61 3,89 4,44 4,44Sound pressure level* (up/down Flow) dB(A) 60.5/56.5 64/60 65/61 67/63 67/63DimensionsLenght mm 1.448 1.885 2.265 2.265 2.265Width mm 860 860 860 860 860Height mm 1.980 1.980 1.980 1.980 1.980

* Sound pressure level measured at 2 m from the machine and at 1 m from the ground in free field conditions.

18.3-64.1 kW 407C

Scroll

Page 252: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Close Control 250

Remote condenser for Close controlCg 010-065

technical features 7 sizes Versions:

BLN and LN Air flow:

Horizontal and vertical accessories and options Head pressure control

technical feature

CG 010-065 BLN 010 015 020 025 035 045 055 065Capacity kW 9,4 12,1 18,4 24,4 30,0 41,8 56,2 65,0Air flow kW 0,9 0,8 1,8 1,7 1,9 4,2 4,0 3,9Lenght mm 780 780 1.380 1.380 1.105 2.005 2.005 2.005Width mm 555 555 555 555 828 828 828 828Height mm 362 362 362 362 428 428 428 428Weight kg 18,0 19,4 34,0 38,8 46,6 76,0 85,3 93,2Sound power level dB(A) 75 75 78 79 75 78 78 78FansQty 1 1 2 2 1 2 2 2Diameter mm 400 400 400 400 500 500 500 500Fans speed rpm 1.430 1.430 1.430 1.430 1.300 1.300 1.300 1.300Power input W 200 200 400 400 680 1.360 1.360 1.360

Air temperature= 32°C.Condensing temperature dew= 52°C.S.H.= 25 K. - S.C.= 3 K.* refer to UnI En 13487.

CG 010-065 LN 010 015 020 025 035 045 055 065Capacity kW 7,7 9,7 15,0 18,7 24,2 35,9 43,2 48,7Air flow kW 0,7 0,6 1,4 1,3 1,3 2,9 2,7 2,6Lenght mm 780 780 1.380 1.380 1.105 2.005 2.005 2.005Width mm 555 555 555 555 828 828 828 828Height mm 362 362 362 362 428 428 428 428Weight kg 18,0 19,4 34,0 38,8 46,6 76,0 85,3 93,2Sound power level dB(A) 65 65 68 68 67 70 70 70FansQty 1 1 2 2 1 2 2 2Diameter mm 400 400 400 400 500 500 500 500Fans speed rpm 940 940 940 940 915 915 915 915Power input W 160 160 320 320 270 540 540 540

9.4-65 kW

407C

Page 253: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Close Control |

Close Control

251

Combination - Close Control remote condenser unit

CG BLN Models CG LN Models

Size Size Size

031 015 020

041 020 025

051 020 025

061 035 035

071 035 045

091 045 045

101 045 055

072 2 x 015 2 x 020

082 2 x 020 2 x 025

102 2 x 020 2 x 025

CLOS

E CO

NTR

OL -

CD

Size Size Size

061 025 035

071 035 045

091 045 045

101 045 055

131 055 065

151 065 085

082 2 x 020 2 x 025

102 2 x 025 2 x 035

132 2 x 035 2 x 035

152 2 x 035 2 x 045

182 2 x 045 2 x 045

202 2 x 045 2 x 055

262 2 x 055 2 x 065

302 2 x 065 2 x 085

CLOS

E CO

NTR

OL -

MD

Page 254: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Direct Expansion

dk/dn 14.5-83 kW 15.7-83.8 kW 407C

Xar + uC 12-55 kW 407C

Xao 8-48.7 kW 407C

Page 255: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

direct expansion

Direct Expansion |

Direct expansion

253

Product Range Capacity Flow rate Acoustic Power Size (LxHxP) mm

Packaged Air

Conditioners Vertical units

Air Cooled Models

X 1200 / uC 34

12 kW 2.000 m3/h

I.U. 51dB(A) 890 x 1.540 x 430O.U. 52 dB(A) 885 x 840 x 825

X 1900 / uC 54

16.2 kW 3.200 m3/h

I.U. 56 dB(A) 1.000 x 1.735 x 500O.U. 53 dB(A) 885 x 840 x 825

X 2450 / uC 74

19.8 kW 4.500 m3/h

I.U. 59 dB(A) 1.300 x 1.840 x 600O.U. 56 dB(A) 1.141 x 840 x 885

X 3250 / uC 104

29.0 kW 5.800 m3/h

I.U. 65 dB(A) 1.530 x 1.830 x 600O.U. 56 dB(A) 1.546 x 840 x 885

X 4650 / uC 74

38.9 kW 9.000 m3/h

I.U. 61 dB(A) 1.715 x 1.970 x 790O.U. 56 dB(A) 1.141 x 840 x 885

X 6450 /uC 104

55 kW 12.000 m3/h

I.U. 69 dB(A) 1.980 x 1.970 x 790O.U. 56 dB(A) 1.546 x 840 x 885

Packaged Air

Conditioners Vertical units Water Cooled

Models

CX 25 8 kW 1.500

m3/h 52 dB(A) 800 x 1.280 x 407

X 1200 AO 15 kW 2.000

m3/h 52 dB(A) 890 x 1.540 x 430

X 1900 AO 18.0 kW 3.200

m3/h 55 dB(A) 1.000 x 1.735 x 500

X 2450 AO 23.0 kW 4.500

m3/h 58 dB(A) 1.300 x 1.840 x 600

X 3250 AO 32.4 kW 5.800

m3/h 64 dB(A) 1.530 x 1.830 x 600

X 4650 AO 45.7 kW 9.000

m3/h 60 dB(A) 1.715 x 1.970 x 790

Ductable Split-

System Air Conditioners

DK / DN 155 14.5 kW 2.850

m3/hI.U. 72 dB(A) 1.410 x 340 x 745O.U. 82 dB(A) 900 x 1.060 x 800

DK / DN 205 19.1 kW 4.500

m3/hI.U. 84 dB(A) 135 x 400 x 1.000O.U. 78 dB(A) 900 x 1.060 x 800

DK / DN 255 21 kW 4.680

m3/hI.U. 84 dB(A) 1.692 x 400 x 1.060O.U. 78 dB(A) 900 x 1.060 x 800

DK / DN 305 28.5 kW 5.760

m3/hI.U. 78 dB(A) 1.690 x 676 x 1.005O.U. 86 dB(A) 1.003 x 1.094 x 1.003

DK / DN 405M 36 kW 7.560

m3/hI.U. 83 dB(A) 1.690 x 676 x 1.005O.U. 83 dB(A) 1.004 x 1.257 x 1.004

DK / DN 405 37.5 kW 7.560

m3/hI.U. 83 dB(A) 1.690 x 676 x 1.005O.U. 87 dB(A) 1.708 x 972 x 1.123

DK / DN 505 44 kW 9.360

m3/hI.U. 84 dB(A) 2.100 x 703 x 1.078O.U. 86 dB(A) 1.708 x 1.171 x 1.123

DK / DN 605 56 kW 9.720

m3/hI.U. 85 dB(A) 2.100 x 703 x 1.078O.U. 86 dB(A) 1.708 x 1.171 x 1.123

DK / DN 755 69.1 kW 12.000

m3/hI.U. 87 dB(A) 2.270 x 795 x 910O.U. 87 dB(A) 2.213 x 1.303 x 1.345

DK / DN 905 83 kW 14.300

m3/hI.U. 87 dB(A) 2.270 x 945 x 910O.U. 87 dB(A) 2.213 x 1.459 x 1.345

Selection guide Direct Expansion

Page 256: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Direct Expansion 254

Cooling modeMinimum indoor air temperature 21°C BS/15°C BHMaximum indoor air temperature 32°C BS/23°C BHMinimum outdoor air temperature/with all-season kit 15°C BS/-10°CMaximum outdoor air temperature 46°C BSHeating modeMaximum indoor air temperature 27°C BSMinimum outdoor air temperature -10°CMaximum outdoor air temperature 24°C BS/18°C BH

Air-air split systemCooling and heatingdk/dn

technical features UndEr version air down flow Cooling Capacity from 14,5 to 83 kW Heating Capacity from 15,7 to 83,8 kW Refrigerant: R407C 12 sizes

Configurations Packaged Split system

Product advantages Adjustable base frame Weather resistant casing with external panels coated with

powder-based epoxy paint colour RAL 7040 Indoor centrifugal fan units for duct netwrok connection High static pressure available Multi-position architecture for horizontal or vertical mounting

(acc. to models) Compact, top discharge outdoor fan units Low noise axial fan Scroll compressor with crankcase heater Electrical, refrigeration and thermal protection devices Phase controller External HP and LP pressure taps Frame and air filter supplied

accessories and options Factory-fitted low ambient temperature control to ensure

cooling operation down to -10°C outdoor temperature (All-season)

Electric heater Programmable controlller RCW2 to control up to 15 units with

independent set points and programming

operating limit (for standard unit) (to be confirmed following selection software issue)

14.5-83 kW 407C

15.7-83.8 kW

Page 257: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

direct expansion

Direct Expansion |

Direct expansion

255

DK-DN DK 155 DK-V 155 DK 205 DK 255

Indoor unitCool only DN 155 DN 155 DN 205 DN 255Reversible DN 155RC DN 155RC DN 205RC DN 255RC

Capacities

CoolingCooling capacity kW 14,5 14,5 19,1 21,0Power input kW 5,8 5,8 7,3 8,6EER 2,5 2,5 2,6 2,4

HeatingHeating capacity kW 15,7 15,7 18,3 21Power input kW 5,8 5,8 6,7 7COP 2,7 2,8 3 2,9

Indoor unit

FanAvailable static pressure Pa 130 110 210 210nominal Airflow m3/h 2.850 2.850 4.500 4.680Airflow range (min/max) m3/h 2.300/3.100 2.300/3.100 3.600/5.000 3.800/5.100

Sound Levels Sound power level dB(A) 73 72 84 84

DimensionsLxWxH mm 1.350 x 745 x 340 1.254 x 972 x 350 1.352 x 1.060 x 400 1.692 x 1.060 x 400Mounting H/V H H/V H H

Weight Unit weight kg 65 77 98 100Outdoor unit

FanNumber of fan 1 1 1 1nominal Airflow m3/h 9.000 9.000 9.000 9.000

Sound Levels Sound power level dB(A) 82 82 78 78Dimensions LxWxH mm 900 x 800 x 1.060 900 x 800 x 1.060 900 x 800 x 1.060 900 x 800 x 1.060Weight Unit weight kg 150 150 164 164Power supplyPower supply V/P/Hz 400V/3~N/50HzPower supply side OutdoorPipe LineSuction pipe diameter < 20m inches 7/8” 7/8” 1-1/8” 1-1/8”Suction pipe diameter > 20m inches 3/4” 3/4” 1-1/8” 1-1/8”Liquid pipe diameter < 20m inches 1/2” 1/2” 1/2” 1/2”Liquid pipe diameter > 20m inches 1/2” 1/2” 5/8” 5/8”Max lenght m 50 50 30 30Max height m 50 50 15 15

technical feature

Page 258: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Direct Expansion 256

DK-DN DK 305 DK 405 M DK 405

Indoor unitCool only DN 305 DN 405 M DN 405Reversible DN 305RC DN 405 MRC DN 405RC

Capacities

CoolingCooling capacity kW 28,5 36,0 37,5Power input kW 11,5 13,9 14,4EER 2,5 2,6 2,6

HeatingHeating capacity kW 27,3 36,0 36,5Power input kW 9,3 13,3 11,9COP 2,7 3 2,9

Indoor unit

FanAvailable static pressure Pa 190 180 180nominal Airflow m3/h 5.760 7.560 7.560Airflow range (min/max) m3/h 4.600/6.300 6.000/8.200 6.000/8.200

Sound Levels Sound power level dB(A) 78 83 83

DimensionsLxWxH mm 1.690 x 1.005 x 676 1.690 x 1.005 x 676 1.690 x 1.078 x 676Mounting H/V H H H

Weight Unit weight kg 150 160 160Outdoor unit

FanNumber of fan 1 1 1nominal Airflow m3/h 9.000 16.000 2x9.000

Sound Levels Sound power level dB(A) 86 83 87Dimensions LxWxH mm 1.003 x 1.003 x 1.094 1.004 x 1.004 x 1.257 1.708 x 1.123 x 972Weight Unit weight kg 187 247 317Power supplyPower supply V/N/Hz 400V / 3~N / 50HzPower supply side OutdoorPipe lineSuction pipe diameter < 20m inches 7/8” 1-3/8” 7/8”Suction pipe diameter > 20m inches 1-1/8” 1-3/8” 7/8”Liquid pipe diameter < 20m inches 5/8” 5/8” 1/2”Liquid pipe diameter > 20m inches 5/8” 5/8” 5/8”Max lenght m 30 30 30Max height m 15 10 15

technical feature

Page 259: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

direct expansion

Direct Expansion |

Direct expansion

257

DK-DN DK 505 DK 605 DK 755 DK 905

Indoor unitCool only DN 505 DN 605 DN 755 DN 905Reversible DN 505RC DN 605RC DN 755RC DN 905RC

Capacities

CoolingCooling capacity kW 44,0 56,0 69,1 83,0Power input kW 16,7 22,5 26,9 33,0EER 2,6 2,5 2,6 2,5

HeatingHeating capacity kW 42,0 57,5 71,0 83,8Power input kW 14,4 22,9 26,4 32,4COP 2,5 2,7 2,6 2,5

Indoor unit

FanAvailable static pressure Pa 520 320 330 460nominal Airflow m3/h 9.360 9.720 12.000 14.300Airflow range (min/max) m3/h 7.500/10.300 7.780/11.000 9.600/13.200 11.440/15.730

Sound Levels Sound power level dB(A) 84 85 87 87

DimensionsLxWxH mm 2.100 x

1.078 x 7032.100 x

1.078 x 7032.208 x

949 x 7952.208 x

949 x 945Mounting H/V H H H H

Weight Unit weight kg 205 209 266 282Outdoor unit

FanNumber of fan 2 2 2 2nominal Airflow m3/h 2x9.000 2x9.000 2x16.000 2x16.000

Sound Levels Sound power level dB(A) 86 86 87 87

Dimensions LxWxH mm 1.708 x 1.123 x 1.171

1.708 x 1.123 x 1.171

2.213 x 1.345 x 1.309

2.213 x 1.345 x 1.459

Weight Unit weight kg 378 405 559 592Power supplyPower supply 400V / 3~N / 50HzPower supply side OutdoorPipe lineSuction pipe diameter < 20m inches 7/8” 1-1/8” 1-1/8” 1-3/8”Suction pipe diameter > 20m inches 7/8” 1-1/8” 1-3/8” 1-3/8”Liquid pipe diameter < 20m inches 1/2” 1/2” 5/8” 5/8”Liquid pipe diameter > 20m inches 5/8” 5/8” 5/8” 5/8”Max lenght m 30 30 30 30Max height m 15 15 15 15

technical feature

Page 260: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Direct Expansion 258

Indoor unitMinimum air temperature (room/intake/around unit) 21°C BS/15°C BHMaximum air temperature (room/intake/around unit) 32°C BS/23°C BHOutdoor unitMinimum air temperature/with all-season kit 15°C BS/-10°CMaximum air temperature 46°C BS

Vertical air cabinetCooling only Xar+uC

technical features Cooling Capacity: from 12 to 55 kW Refrigerant: R407C Size: 6

Configurations Split system

Product advantages Adjustable base frame Easy installation and maintenance Split system with outdoor condenser fan unit Treated air distribution to premise by plenum or duct network Adjustable available static pressure Temperature control by thermostat Electrical, refrigeration and thermal protection devices

accessories and options Room thermostat Electric heater Hot water heating coil ”All season” system (Cooling mode operation) down to

outdoor temperature of -10°C) Remote fault reporting Plenum duct flange Valves Pipe link

operating limit (for standard unit) (to be confirmed following selection software issue)

12-55 kW

407CFaCtorY

Page 261: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

direct expansion

Direct Expansion |

Direct expansion

259

X AR X 1200 AR X 1900 AR X 2450 AR X 3250 AR X 4650 AR X 6450 AR

Cooling

Cooling capacity kW 12,3 16,2 19,8 29,0 38,9 55,0Power input kW 4,1 6,8 8,9 12,6 16,9 24,0EER 3,00 2,38 2,22 2,3 2,3 2,3Cooling circuit 1 1 1 1 2 2

FansAvailable static pressure Pa 200 300 200 200 250 290nominal Airflow m³/h 2.000 3.200 4.500 5.800 9.000 12.000Airflow range (min/max) m³/h 1.500/2.500 2.500/3.800 3.600/5.400 4.600/7.000 7.200/10.800 9.500/14.500Sound levelsSound power level dB(A) 62 68 75 81 77 85Dimensions

LxWxH mm 890 x 430 x 1.540

1.000 x 500 x 1.735

1.300 x 600 x 1.840

1.530 x 600 x 1.840

1.715 x 790 x 1.970

1.980 x 790 x 1.970

Plenum height mm 220 260 350 350 400 400WeightUnit weight kg 136 182 265 350 525 600Outdoor Unit UC 34 UC 54 UC 74 UC 104 UC 74 UC104Condenser unit 1 1 1 1 2 2Fansnominal Airflow m3/h 260 260 350 350 400 400Sound levelsSound power level dB(A) 53 58 61 73 64 76Dimensions

LxWxH mm 885 x 825 x 831

885 x 825 x 831

1.141 x 885 x 831

1.546 x 885 x 893

1.141 x 885 x 831

1.546 x 885 x 893

WeightUnit weight kg 59 68 93 130 93 130Power supplyPower supply 400V / 3~N / 50HzPower supply side Inside Pipe lineSuction pipe diameter inches 1/2” 1/2” 5/8” 3/4” 5/8” 3/4”Liquid pipe diameter inches 3/8” 3/8” 1/2” 5/8” 1/2” 5/8”Max lenght m 45 45 45 45 45 45

technical feature

Page 262: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| Direct Expansion 260

Indoor unitMinimum air temperature 21°C BS/15°C BHMaximum air temperature 32°C BS/23°C BHMinimum water temperature +10°CMaximum water temperature +30°C

Vertical water cabinetcooling onlyXao

technical features Cooling Capacity: from 8 to 45,7 kW Refrigerant: R407C Size: 6

Configurations Monobloc system

Product advantages Easy installation and maintenance

Monobloc system Public or recycled water operation Treated air distribution to premise by plenum or duct network Adjustable available static pressure Temperature control by thermostat Electrical, refrigeration and thermal protection devices

accessories and options Room thermostat Electric heater Hot water heating coil Remote fault reporting Plenum duct flange

operating limit (for standard unit) (to be confirmed following selection software issue)

8.0-45.7 kW

407CFaCtorY

Page 263: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

direct expansion

Direct Expansion |

Direct expansion

261

X AO CX 25 X 1200 AO X 1900 AO X 2450 AO X 3250 AO X 4650 AO

Cooling

Cooling capacity kW 8,0 15,0 18,0 23,0 32,4 45,7Power input kW 2,6 4,2 5,3 7,1 9,8 13,9EER 3,14 3,57 3,4 3,24 3,31 3,29Cooling circuit 1 1 1 1 1 2

FansAvailable static pressure Pa 80 200 250 200 250 250nominal Airflow m³/h 1.500 2.000 3.200 4.500 5.800 9.000

Airflow range (min/max) m³/h 1.160/ 1.750

1.500/ 2.500

2.500/ 3.800

3.600/ 5.400

4.600/ 7.000

7.200/ 10.800

Water Connections

Wasted waterWater flow m3/h 0,34 0,91 0,95 1,45 2 2,8Pressure drop kPa 20 37 30 42 40 18

Recycled waterWater flow m3/h 1,17 3,2 3,05 4,3 5,8 8,3Pressure drop kPa 21 80 65 60 40 56

Sound levels Sound power level dB(A) 64 65 67 74 80 76Power supply

Power supply V/N/Hz 230V/1~/50Hz400V/3~N/50Hz 400V / 3~N / 50Hz

Dimensions

LxWxH mm 800 x 407 x 1.280

890 x 430 x 1.540

1.000 x 500 x 1.735

1.300 x 600 x 1.840

1.530 x 600 x 1.840

1.715 x 790 x 1.970

WeightPlenum height mm 300 220 260 350 350 400Unit weight kg 125 151 199 305 380 565

technical feature

Page 264: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

| HPT Hydrokit262

HPT Hydrokit

technical features 48 sizes Structurally equipped of tank, expansion tank,

pump, filter, control valves, electrical box 6 volumes of the storage tank from 300 to

2.500 liters 14 different pumps models Two versions:

with one or two water pumps Anti freezer protection

3

2

1

11

6 8

4

7

9

10

12

5

13

1 Tank

2 Circulating pump

3 Expansion tank

4 Pressure gauge

5 On/Off valves

6 Safety valve

7 Automatic air vent valve

8 Air vent valve

9 Make-up valve

10 Automatic make-up unit

11 Electrical board

12 Non-return valve (only on version with 2 pumps)

13 Water storage drain

Page 265: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

HPT Hydrokit |

HPT HydrokiT

263

Pumpmodel

Tank volume Wsb1 Wsb2 F.L.I.F.L.A. F.L.A.

Q MIn H Max Q Max H Min Ve(400/3/50) (230/3/50)

lt kg kg kW A A m3/h кPа m3/h кPа lt

A300 186 216 1,1 2,5 4,3 6 188 24 83 25500 208 238 1,1 2,5 4,3 6 188 24 83 25

В300 188 220 1,5 3,2 5,5 6 220 24 122 25500 210 242 1,5 3,2 5,5 6 220 24 122 25

С300 188 220 1,5 3,4 5,9 10 170 45 61 25500 210 242 1,5 3,4 5,9 10 170 45 61 25

D300 191 225 2,2 4,8 8,3 10 230 45 112 25500 213 247 2,2 4,8 8,3 10 230 45 112 25

E300 194 231 3 5,6 9,7 10 230 45 112 25500 215 253 3 5,6 9,7 10 248 45 137 25

F

750 341 428 3 6,2 10,8 30 191 72 103 251000 364 455 3 6,2 10,8 30 191 72 103 251500 513 586 3 6,2 10,8 30 191 72 103 2 x 252500 565 638 3 6,2 10,8 30 191 72 103 3 x 25

G

750 370 485 5,5 11 — 30 308 84 145 251000 392 512 5,5 11 — 30 308 84 145 251500 565 696 5,5 11 — 30 308 84 145 2 x 252500 613 732 5,5 11 — 30 308 84 145 3 x 25

H

750 373 493 5,5 11 — 48 210 108 137 251000 396 520 5,5 11 — 48 210 108 137 251500 569 696 5,5 11 — 48 210 108 137 2 x 252500 617 740 5,5 11 — 48 210 108 137 3 x 25

I

750 377 501 7,5 14,6 — 48 260 120 180 251000 400 528 7,5 14,6 — 48 260 120 180 251500 569 696 7,5 14,6 — 48 260 120 180 2 x 252500 617 740 7,5 14,6 — 48 260 120 180 3 x 25

L

750 377 501 11 21,2 — 48 342 120 249 251000 400 528 11 21,2 — 48 342 120 249 251500 569 696 11 21,2 — 48 342 120 249 2 x 252500 617 740 11 21,2 — 48 342 120 249 3 x 25

M1500 628 814 15 28,6 — 48 405 138 288 2 x 252500 680 866 15 28,6 — 48 405 138 288 3 x 25

О1500 634 826 15 28,6 — 84 330 180 220 2 x 252500 686 878 15 28,6 — 84 330 180 220 3 x 25

P1500 646 850 18,5 34,2 — 84 385 216 220 2 x 252500 698 902 18,5 34,2 — 84 385 216 220 3 x 25

Q1500 660 878 22 40,3 — 84 475 180 325 2 x 252500 712 930 22 40,3 — 84 475 180 325 3 x 25

F.L.I. - Full load power.F.L.A. - Full load current.Q Min - Minimum flow. Q Max - Maximum flow.H Min - Minimum pressure.H Max - Maximum pressure.Wsb1 - Shipping weight with pump.Wsb2 - Shipping weight with two pumps.Ve - Expansion tank capacity.PVe - Tank pressure.PS - Maximum operating pressure.T Min - Minimum water temperature.

PVe PS T Minbar bar °C1,5 3 -10

technical feature

Legend:

Page 266: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Notes

Page 267: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Notes

Page 268: Air Conditioning - uash.com.uauash.com.ua/Air Conditioning catalogue.pdf · Air Conditioning Light Commercial, Commercial and Industrial Fans | Air Handling Units ... Heat Pumps and

Syst

emai

r · d

ecem

ber 2

015

· AIr

CO

ndI

TIO

nIn

G CA

TALO

GUE

GB •

E340

15As

par

t of o

ur o

ngoi

ng p

rodu

ct im

prov

emen

t pro

gram

me,

our

pro

duct

s ar

e su

bjec

t to

chan

ge w

ithou

t prio

r not

ice.

Non

con

trac

tual

pho

tos.

Systemair srlVia XXV Aprile, 2920825 Barlassina (MB) Italy

Tel. +39 0362 680 1Fax +39 0362 680 693

www.systemair.com

Systemair AC SASRoute de Verneuil 27570 Tillières-sur-Avre France

Tel. +33 02 32 60 61 00Fax +33 02 32 32 55 13

www.systemair.fr