1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced. 2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install the outdoor unit close to the sea shore, contact your local distributor. Cautions on product corrosion Ask a qualified installer or contractor to install this product. Do not try to install the product yourself. Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion. Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or contractor to install those parts and accessories. Use of unauthorised parts and accessories or improper installation of parts and accessories can result in water or refrigerant leakage, electrical shock, fire or explosion. Read the user's manual carefully before using this product. The user's manual provides important safety instructions and warnings. Be sure to follow these instructions and warnings. If you have any enquiries, please contact your local importer, distributor and/or retailer. COOLING ONLY [50Hz] AIR CONDITIONING SYSTEM DIDSI2009 • SERVICE AND SPARE PARTS : Jakarta Selatan, Telp. : 021-2782 5545 Cirebon, Telp. : 0231-880 2760 | Samarinda, Telp. : 0541-252 2889 | Banjarmasin, Tlp. : 0511-326 8168 • TRAINING CENTER : Sunter, Telp. : 021-650 5028 • BRANCH : Bekasi, Telp. :021-2945 0585 Tangerang, Telp. : 021-5314 1195 | Bandung, Telp. : 022-522 5150 | Semarang, Telp. : 024-7660 3221 Yogyakarta, Telp. : 0274-551 321 | Surabaya, Telp. : 031-503 1138 | Denpasar, Telp. : 0361-900 5514 Makassar, Telp. : 0411-805 2691 | Palembang, Telp. : 0711-573 2282 | Pekanbaru, Telp. : 0761-561 139 Medan, Telp. : 061-4200 8866 | Manado, Telp. : 0341-719 1199 Specifications, designs and other content appearing in this brochure are current as of August 2020 but subject to change without notice.
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install the outdoor unit close to the sea shore, contact your local distributor.
Cautions on product corrosion
Ask a qualified installer or contractor to install this product. Do not try to install the product yourself. Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.
Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or contractor to install those parts and accessories. Use of unauthorised parts and accessories or improper installation of parts and accessories can result in water or refrigerant leakage, electrical shock, fire or explosion.
Read the user's manual carefully before using this product. The user's manual provides important safety instructions and warnings. Be sure to follow these instructions and warnings.
If you have any enquiries, please contact your local importer, distributor and/or retailer.
Comparison of cooling seasonal power consumptionbased on average CSPF values
Coo
ling
seas
onal
po
wer
con
sum
ptio
n
New inverter RZFC-D series(average)
Previous non-inverter series(average)
100
65
Note: Value 100 represents the amount of electricity used by a non-inverter model during a similar annual cooling period.
(cassette type)(cassette type)
4.674.10
4.674.29
2.63 2.79
4.67
2.77
5.13
2.69 2.79 2.732.71
6
5
4
3
2
1
0
CSPF values by capacity for cassette models
35%reduction!
What is CSPF?CSPF is the value for the annual total cooling load divided by the annual total power consumption at outdoor air conditions specified by ISO standard.
*CSPF (cooling seasonal performance factor) is a new international energy-efficiency criterion calculated by methods stipulated in ISO 16358-1.
3.10
Throughout the cooling season,Daikin’s new inverter models reduce energy consumptionCompared with previous non-inverter series, the new RZFC-D series uses about 35% less power consumption for quick and effective cooling that reduces electricity bills.
Energy Saving Tota
l cos
t =un
it pr
ice
+ c
ost o
f ele
ctric
ity
Time
InverterNon inverter
Roomtemperature
Time
Too hot
Set temperature
Smalltemperaturefluctuation
Too coldToo cold
Largetemperaturefluctuation
Comfortable
Non inverter
Non inverter
Inverter
Non inverter
Inverter control responds to load changes and causes minor temperature adjustments. Non-inverter control frequently turns ON and OFF in response to load fluctuations or load mismatch and causes large temperature swings.
Cap
acity
Load
0
Non inverter cooling capacity
Inverter cooling capacity
On/Off operation
Lower efficiency
Partial load area
Rated condition
Outdoor ambient temperature (°C)35
Cooling load
Continuous driving without stopping and starting is more fuel efficient.
Highway drivingInverterConstantly stopping and starting consumes energy and is less fuel efficient.
City drivingNon inverterStop, go, stop ...
Recovery point
Inverters save more energy over time
Inverter system consumes less electricity, and soon recovers the difference in initial cost. This results in lower total cost.
Inverter air conditioner can adjust its cooling capacity according to the cooling load. This results in less power consumption.
Inverters operate without repeated ON/OFF operation.
Why is inverter technology economical?Why is inverter technology economical?
Why is inverter technology more comfortable?Why is inverter technology more comfortable?
In response to fluctuating cooling load, Non inverter air conditioners repeatedly perform ON (full-power)/OFF (zero-power) operation. Inverter air conditioners, however, operate at optimal cooling capacity according to the cooling load. Since inverter air conditioners provide required minimum cooling capacity with minimum electrical power, total power consumption can be reduced during cooling period.
When temperature does not fluctuate much, the set temperature is maintained.
Inverter
Benefits of Inverter
43
Durability
100mm or
more
100mm or more 100mm or
more500mm or
more
Microchannel technology utilises superior heat transfer benefits of aluminium to create a more efficient air conditioner.With a new resistance corrosion aluminium alloy, the Daikin microchannel heat exchanger becomes highly durable.A salt spray test has been conducted to demonstrate the corrosion-resistant capability of our products in corrosive environments for a certain period of time.
After undergoing an intensive test, the Daikin microchannel heat exchanger is able to maintain its shape without corrosion, which strongly confirms its durability in a highly corrosive environment.
Microchannel heat exchanger
Outdoor unit installation is possible even with limited space
Test of durability- Testing organization - Testing standard- Result
MTEC ThailandASTM B117
Before testing After testing
Normalobservation
No evidence of corrosion was observed
Undertelescope
Coated circuit boards prevent problems caused by humidity and airborne dust.It also protects against salt contained in sea breezes.Both sides of the PCB in outdoor units are coated.
Coated printed circuit boards(outdoor unit)
In AM and PM peak electricity consumption periods, supply may fluctuate. Built-in low-voltage protection will automatically cut operations. When normal voltage is restored, operation will resume as before.
Automatic protection against low voltage
*FHFC40-85D requires optional adaptor to connect DIII-Net.
Possible to forced OFF and ON/OFF operation using external command
Indoor units (FCFC-D, FHFC100-140D, and FBFC-D) comply with D -Net standards
Design Flexibility
VRV
New indoor unit
Easy connection to DIII-NET and long piping length makes this solution suitable for projects including and SkyAir.
Adaptor notrequired
*Field setting with remote controller
Please see a video of the Micro Channel Heat Exchanger test in Pattaya.
QRspace
Interlock
Duct connection middle static pressure typeRound flow cassette type
Note : 1Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19°CWB; outdoor temp. 35°CDB, 24°CWB. Equiv. refrigeration piping, 7.5 m (horizontal).2Capacities are net, including a deduction for cooling for indoor fan motor heat.3The operation sound is measured in anechoic chamber. If it is measured under the actual installation conditions, it is normally over the set value due to environmental noise and sound reflection.
Note: 1When installing a fresh air intake kit (chamber type), two air outlet corners are closed.2It is recommended that the volume of outdoor air introduced through the kit is limited to 10% of the maximum airflow rate of the indoor unit. Introducing higher quantities will increase the operating sound and may also influence temperature sensing.
3The volume of fresh air for direct installation type is approximately 1% of the indoor unit airflow. The chamber type is recommended when more fresh air is necessary.
4Please order using the names of both components instead of set name.5Filter chamber is required.6Please use in case temperature/humidity inside ceiling may get over 30˚C, 80% RH.
Note : 1Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19°CWB; outdoor temp. 35°CDB, 24°CWB. Equiv. refrigeration piping, 7.5 m (horizontal).2Capacities are net, including a deduction for cooling for indoor fan motor heat.3The operation sound is measured in anechoic chamber. If it is measured under the actual installation conditions, it is normally over the set value due to environmental noise and sound reflection.
21 to 46
14 to 25
CEILING SUSPENDED TYPE
Comfortable airflow travels throughout the roomComfortable airflow travels throughout the room
Note: Remote controller cable is not included and must be obtained locally.
NEW
FHFC100/125/140DV14
FHFC40/50/60/71/85DV14
A signal receiver must be added to the indoor unit.
Wireless remote controller
Wireless remote controller is supplied in a set with a signal receiver.
Signal receiver unit (Installed type)
BRC7GA56Cooling onlyFHFC100-140D
Wireless remote controller is supplied in a set with a signal receiver.
Signal receiver unit (Installed type)
BRC7EA66Cooling onlyFHFC40-85D
Note: 1Wiring for wired remote controller should be obtained locally.2 This optional accessory requires DTA112BA51.3 The indoor unit is equipped standardly with the interface adaptor for SkyAir series. An option is unnecessary.4 Installation box for adaptor PCB (KRP1CA93, KRP1D93A) is necessary.
Note : 1Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19°CWB; outdoor temp. 35°CDB, 24°CWB. Equiv. refrigeration piping, 7.5 m (horizontal)2Capacities are net, including a deduction for cooling for indoor fan motor heat.3External static pressure is changeable in 11 stages by remote controller.4The operation sound is measured in anechoic chamber. If it is measured under the actual installation conditions, it is normally over the set value due to environmental noise and sound reflection.5Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its dust collection efficiency (gravity method) 50% or more.
Note : 1Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19°CWB; outdoor temp. 35°CDB, 24°CWB. Equiv. refrigeration piping, 7.5 m (horizontal)2Capacities are net, including a deduction for cooling for indoor fan motor heat.3External static pressure is changeable in 11 stages by remote controller.4The operation sound is measured in anechoic chamber. If it is measured under the actual installation conditions, it is normally over the set value due to environmental noise and sound reflection.
Note : 1Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19°CWB; outdoor temp. 35°CDB, 24°CWB. Equiv. refrigeration piping, 7.5 m (horizontal)2Capacities are net, including a deduction for cooling for indoor fan motor heat.3External static pressure is changeable in 11 stages by remote controller.4The operation sound is measured in anechoic chamber. If it is measured under the actual installation conditions, it is normally over the set value due to environmental noise and sound reflection.5Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its dust collection efficiency (gravity method) 50% or more.
1.601.0 (Charged for 15 m) 1.35 (Charged for 15 m)
Ivory whiteMicro channel
Hermetically sealed swing type
9.515.9
Both liquid and gas piping
50 (Equivalent length 70)30
VP25 (I.D. 25XO.D. 32)18.0 (Hole) 26.0 (Hole)
14 to 25
21 to 46
Note: 1If installing high efficiency filter and long-life filter to the unit, filter chamber is required.2Wiring for wired remote controller should be obtained locally. 3Mounting plate is necessary for each adaptor marked .
Option List
FBFC40DVM4FBFC50DVM4FBFC60DVM4
FBFC71DVM4FBFC85DVM4
FBFC100DVM4FBFC125DVM4FBFC140DVM4
High-efficiency filter 1
Filter chamber(for rear suction)1
Long-life filter 1
Air discharge adaptor
Adaptor for wiring 3
Wiring adaptor for electrical appendices(2) 3
Central remote controller 6
Unified ON/OFF controller 6
Schedule timer 6
intelligent Touch Controller 6
Service panel
Remote controller
65%
90%
Fresh white
Brown
Wired type 2
Kit name
KAF632C56 KAF632C80 KAF632C160
KAF633C56 KAF633C80 KAF633C160
KDDFP63B56 KDDFP63B80 KDDFP63B160
KDAP25A56A KDAP25A71A KDAP25A140A
KAF631C56 KAF631C80 KAF631C160
KTBJ25K56W KTBJ25K80W KTBJ25K160W
KTBJ25K56F KTBJ25K80F KTBJ25K160F
KTBJ25K56T KTBJ25K80T KTBJ25K160T
KDBD63A160
BRC4C66
BRC2E61
KRP4A98
BRCS01A-4
DCS302CA61
DCS301BA61
DST301BA61
DCS601C51
Shield plate for side plate
Simplified Remote Controller
Cooling
4Up to 2 adaptors can be fixed for each mounting plate.5Only one mounting plate can be installed for each indoor unit.6The indoor unit is equipped standardly with the interface adaptor for SkyAir series. An option is unnecessary.
Note: Remote controller cable is not included and must be obtained locally.
NEW
Option
BRC4C66
A signal receiver must be added to the indoor unit.
Cooling only
Wireless remote controller is supplied in a set with a signal receiver.
Wireless remote controller
Signal receiver unit (Separate type)
1817
4
3
2
1
Temperaturesetting (+/-)
BRC7F635FBRC7EA66BRC7GA56
BRC4C66
Cooling only
REMOTE CONTROLLER
All initial settings can be set from the remote controller. After interior construction is complete, ceiling mounted cassette type can be remotely set without having to use a stepladder to access for manual setting.Setting contents: High ceiling use, air direction, filter type, address for centralised control (group control address is set automatically).
Enables temperature sensing closer to target area for improved comfort. (When using a remote control from another room, temperature-sensor of the indoor unit air inlet must be selected.)
Remote controller is equipped with error code display function. This facilitates service in the unlikely event of a malfunction.
SkyAir shares common control with Heat Reclaim Ventilator and the other Daikin air-conditioning units, thus simplifying interlocking operations.
Easily adaptable to large-scale, high-function, centralised remote control systems.Installing and connecting control wiring between SkyAir and other Daikin air-conditioning equipment is easy.
LCD panel shows operating status in letters, numbers, and motion.Airflow / swing display
Preset temperature / operation mode display
Programming time display
Self-diagnosis function
Displays auto-swing operating status and setting position of air discharge angle.
Displays preset room temperature and operating status (fan, dry, cool).
Operation start and stop time can be set for individual timers up to 72 hours. The LCD also shows when it is time to clean the filter, when changeover is under centralised control, and ventilation/cleaning.
Monitors operating status within the system covering 40 items, and displays a message to indicate as soon as a malfunction occurs.
Optional accessory
BRC2E61NEW
Airflow rate (Fan speed)
Airflow direction
ON/OFF button
Operation mode selectionSimple operation
Using only six buttons, users have direct access to basic functions.This enables them to easily set comfort to their preference.
Intuitive designBy using pictograms, the user-friendly interface enables:
CompactMeasuring only 85 x 85 mm, the new remote controller is extremely compact and complements any interior design.
Overseas guests at hotels to understand functions without having to know a foreign language.
Children and elderly users at home to operate without having to read difficult and hard-to-see commands.
120 mm 120 mm
120 mm 85 mm
85 mm
70 mm
35mm
35mm
Conventional remote controller
Conventional simplifiedremote controllerBRC2E61
Reduced size
Signal receiver unit(Installed type)
BRC7F635F The wireless remote controller is supplied in a set with a signal receiver.Signal receiver unit of installed type is contained inside decoration panel or indoor unit.Shape of signal receiver unit differs according to the indoor unit.
Wired remote controller has built-in temperature-sensor
Wireless remote controller for each indoor unit type
BRC7GA56
Signal receiver unit(Installed type)
Signal receiver unit(Installed type)
BRC7EA66 BRC4C66
Signal receiver unit (Separate type)
Simplified Remote Controller (wired)
Wireless remote controller
OUTDOOR UNIT
Compact Outdoor Unit
Through use of a V-cut propeller fan that imitates the efficiency of the swan, a migratory bird, airflow becomes smooth and loss is reduced.
V-cut Propeller Fan
Technology for energy efficiency
3
2
1
4
Imitating the performance of the swan
(RZFC40-100DVM4/Y14)
RZFC40DVM4RZFC50DVM4RZFC60DVM4RZFC71DVM4
RZFC85DVM4RZFC100DVM4
RZFC71DY14RZFC85DY14RZFC100DY14
RZFC125DY14RZFC140DY14
*Although pumping-down operation allows most of the refrigerant to be recovered in a short period of time, some refrigerant will remain inside the indoor unit and refrigerant piping.Using a refrigerant recovery machine, recover remaining refrigerant from the stop valve service port until the pressure falls to 0.09 MPa. (gauge pressure:-0.011MPa) or less.
(Refrigerant recovery function)Facilitates pump down
*Pump-down function is available for pre-charged refrigerant amount.
Refrigerant cooling helps protect the printed circuit board and maintains high cooling capacity even during high outdoor temperatures.
(RZFC71-140DY14)
Conventional tube and fin coil Micro channel coil
High efficiency by micro channel heat exchangerHigh efficiency by micro channel heat exchanger
Daikin’s unique refrigerant cooling system exhibits high cooling capacity even during high outdoor temperatures.
Refrigerant coolingRefrigerant cooling
Utilizing flat, multi-hole heat exchanger tubes increases the heat exchange area and realizes energy savings.
Flow of refrigerant Flow of refrigerant
Flat, multi-hole aluminium heat exchanger tubes
Conventional heat exchanger
The diameter of the refrigerant channel(holes where refrigerant flows) is approx.1 mm.
The diameter of the refrigerant channel (holes where refrigerant flows) is approx. 7 mm
Approx. 1 mm
Approx. 7 mm
Reduced wind resistance
Micro channel heat exchanger
The flattening of the heat exchanger tubes improves the flow of air and increases heat exchange efficiency.
Energy savings is realised, eliminating the friction and the leakage of refrigerant gas.
Swing bushing Refrigerant gas
Piston by incorporated blade and roller.
Swing compressor High efficiency during partial load operation.
Fan
V-cut propeller fan
A pump-down switch is provided to make it easier to collect refrigerant if the unit is to be moved or layout modified.
Low gas pressure detection functionEffective gas monitoring reduces the labor required for operation, maintenance, and repairs.
Easy Installation and Maintenance
2019
REMOTE CONTROLLER Optional accessory
LCD REMOTE CONTROLLER
Central remote controller
Easily adaptable to large-scale, high-function, centralised remote control system.
Centralised control, with setting as simple as it is with a standardremote controller, of up to 64 groups (1,024 indoor units) is possible.
DCS302CA61 (Option)
With its high functionality, the full colour “all-in-one” graphic controller facilitates management of SkyAir System in a variety of ways.
DCS601C51 (Option)Unified on/off controller
Centralised control of on/off by group or all at once for up to 256 indoor units.
DCS301BA61 (Option)
Schedule timer
Unified control of weekly schedule for up to 1,024 indoor units.
DST301BA61 (Option)
Schedule timer sets on/off time in 1 minute units to be executed twice a day for a week at a time.
System variation to control multiple indoor units
(Command from outside)
Control by 1remote controller
Control pattern Wired remote controller Wireless remote controller
Control by 2remote controllers
Group control
Control by external command
Centralised remotecontrol
Interlock controlwith Heat Reclaim
Ventilator
(Basic system)
Link by remote controller group control.
Zone link control by centralised control.
For control from 2 locations such as in room and control room, exits, etc.
For simultaneous control of up to 16 indoor units.
Centralised control of up to 64 indoor groups from remote locationup to 1 km away.
Control by 1 wireless remote controller and 1 wired remotecontroller (See note 2)
Signal receiver unit installed on indoor unit
Signal receiver unit installed on indoor unit
Heat Reclaim Ventilator for indoor units within a zone is operated by interlocking.Can also be operated independently by remote controller.
Central remote controller (option)
Heat ReclaimVentilator
Can be operated simultaneously or independently by remote controller (set by ventilation mode)
Heat ReclaimVentilator
Central remote controller (option)
Non-polar, double-core (max. wiring length 500 m)
Connects 2 wired remote controllers (See note 1)
Automatic address setting function Automatic address setting function
Signal receiver unit installed on 1 indoor unit
Optional wiring adaptor for electrical appendices is necessary
Central remote controller (option)
Interface adapter for SkyAir series (option) is required (See note 3)
Interface adapter for SkyAir series (option) is required (See note 3)
Can be operated simultaneously by remote controller
Heat ReclaimVentilator
Heat Reclaim Ventilator for indoor units within a zone is operated by interlocking.
Central remote controller (option)
Heat ReclaimVentilator
Operation and monitoring is carried out using the contact signal from the operation control box in the monitoring room. Optional wiring adaptor for
electrical appendices is necessary
Interface adaptor for SkyAir series
DTA112BA51 (Option)Necessary for interface adaptor for SkyAir series with the central remote control units shown at above.
Enables centralised control via connection to a high-speed, DIII-NET communication system, adopted for the Daikin system.
(Command from outside)
The interface adaptor for SkyAir series is required for Ceiling suspended type 40-85 class.
Note: 1BRC2E61 can connect to BRC2E61 only. 2When a wireless remote controller is used, it is not possible to use 2 wireless remote controllers. Combination of BRC2E61 (main) and wireless remote controller (sub) is available. 3FHFC40-85D requires interface adaptor for SkyAir series.
*Except for FDBF and FDLF
Whatever your space, give it the comfort it deserves
*Except for FDBF and FDLF
*Except for FDBF and FDLF
2221
ON / OFF timer
Auto swing
Swing pattern selection
DC fan motor
Switchable fan speed
Auto airflow rate
Two selectable temperature-sensors
High ceiling application
FUNCTIONS
Cooling only
Functionsoverview
2
3
4
5
6
7
8
1
Drain pump mechanism
Pre-charged for up to 10 / 15 m *1
Long-life filter
Filter sign
Low gas pressure detection *1
Emergency operation
Self-diagnosis function
13
14
15
16
17
18
12
High-efficiency filter
Ultra long-life filter
Fresh air intake kit
28
29
27
Auto-restart
Control by 2 remote controllers
Group control by 1 remote controller
External signal forced OFF and ON/OFF operation
External command control *2
Central remote control
Interlock control with Heat Reclaim Ventilator
DIII-NET communication standard
20
21
22
23
24
25
26
19
Anti-bacterial air filter
Mould-proof air filter10
Silver ion anti-bacterial drain pan11
9
2
3
4
5
6
7
8
1
13
14
15
16
17
18
12
28
29
27
20
21
22
23
24
25
26
19
10
11
9
Indoor unit
Outdoor unit
Remotecontroller
BRC2E61
-------
-------
BRC7F635F
Wired
Wireless
Note:*1: For outdoor units. *2: Wiring adaptor for electrical appendices (and installation box) is necessary. *3: Option is requied. *4: For outdoor unit RZFC-DY14 only. *5: It is not possible to use 2 wireless remote controllers. Combination of BRC2E61 (main) and wireless remote controller (sub) is available.
3 step 3 step 2 step 2 step 3 step
3.5m / 4.2m 3.5m 4.3 m
3 step
-------
BRC7EA66
BRC2E61
-------
*3
*4*4 *4
*3
*5
*3
*3
*5 *5
FHFC100-140DV14
RZFC100DVM4RZFC100-140DY14
-------
BRC7GA56
BRC2E61
-------
CEILING SUSPENDED TYPECEILING MOUNTED
CASSETTE TYPE( Round Flow )
FHFC40-85DV14
RZFC40-85DVM4RZFC71/85DY14
FCFC40-140DVM4
RZFC40-100DVM4RZFC71-140DY14
3 step 3 step3 step 3 step 3 step 3 step
*3
*3
*3
*4
*5*5 *5
*4 *4
FBFC40-140DVM4
RZFC40-100DVM4RZFC71-140DY14
-------
BRC4C66
BRC2E61
-------
-------
BRC4C66
BRC2E61
-------
-------
BRC4C66
BRC2E61
-------
DUCT CONNECTION LOW STATIC PRESSURE WIDTH COMPACT TYPE
DUCT CONNECTION LOW STATIC PRESSURE HEIGHT COMPACT TYPE
Note : 1Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB, 24°CWB. Equiv. refrigeration piping, 7.5 m (horizontal).2Capacities are net, including a deduction for cooling for indoor fan motor heat.3The operation sound is measured in anechoic chamber. If it is measured under the actual installation conditions, it is normally over the set value due to environmental noise and sound reflection.
dB(A)
°CDBCertified Operation range
Sound pressurelevel3
Motor outputCompressor
Coil
kWRefrigerant charge (R-410A) kg
dB(A)
Dimensions (HXWXD) mmMachine weight kg
Piping connections
mmLiquid (Flare)mmGas (Flare)mmDrain Indoor unit
Outdoor unit
Outdoorunit
mmMax. interunit piping length m
mMax. installation level difference
Type
Cooling
Ø9.5Ø15.9
50
1,170X900X32097
3050 (Equivalent length 70)
Hermetically sealed scroll typeType Cross fin coil
Ø26.0 (Hole)VP25 (I.DØ25XO.DØ32)
21 to 46
Night quiet mode
3.15 (Charged for 30 m)2.4 3.1
45 46
2.4 3.1
45 46
2.4 3.1
45 46
3.7 (Charged for 30 m)2.4 3.1
45 46
intelligent Touch Controller4
Note: 1Refer to page 20 for the details. 2Required for installing high-efficiency filter unit and ultra long-life filter unit. 3Wiring for wired remote controller to be procured locally.4The indoor unit is equipped standardly with the interface adaptor for SkyAir series. An option is unnecessary. 5Installation box for adaptor PCB (KRP1H98) is necessary.
Option ListKit name
KDJP55B160KDJP55B80
KAFP556B80KAFP557B80KAFP552B80KAFP553B80
KAFP556B160KAFP557B160KAFP552B160KAFP553B160
FCQ71KAVE4 FCQ100KAVE4FCQ50KAVE4 FCQ60KAVE4 FCQ125KAVE4 FCQ140KAVE4Name of option Remark
Chamber type
Decoration panel
Fresh air intake kit1
Central remote controller4
Unified ON/OFF controller4
Schedule timer4
Adaptor for wiring5
Without T-duct jointWith T-duct joint
Direct installation type
Sealing material of air discharge outletPanel spacer
Wiring adaptor for electrical appendices(2)5
Installation box for adaptor PCB
High-efficiency filter unit (including filter chamber)
Hermetically sealed swing typeType Cross fin coil Micro channel
1.76
49
990X940X32065
2.031.9(Charged for 30 m)
Ø9.5Ø15.9
52 54 52 54
3050 (Equivalent length 70)
Ø26.0 (Hole)VP25 (I.DØ25XO.DØ32)
21 to 4673
1.92
49Night quiet mode
1.12
48
595X845X30043
1.351.6(Charged for 30 m)
4544
Outdoor unit
36O° AIRFLOW
GENTLE AIR MOVEMENT WITH ROUND FLOW
SILVER ION ANTI-BACTERIAL DRAIN PAN
ANTI-MOULD & ANTI-BACTERIAL TREATMENTFILTER
SUITABLE FOR HIGH CEILINGS
QUICK & EASY TO INSTALL
FEATURES
27 28
COMPACT MULTI FLOW CEILING MOUNTED CASSETTE TYPE25 35
1 Phase, 220–240 V, 50 Hz2.5
(1.2-3.0)3.4
(1.2-3.7)
0.73 1.103.42 3.09
4.7 (1.7-5.6)
5.8 (1.7-6.0)
8,500(4,100-10,250)
11,600(4,100-12,600)
16,000(5,800-19,100)
19,800(5,800-20,500)
1.62 2.072.90 2.80
FFQ25BV1B4
RKS25AVMG4
FFQ35BV1B4
RKS35AVMG4
50 60
FFQ50BV1B4
RKS50AVMG4
FFQ60BV1B4
RKS60AVMG4
kWPower consumption
ModelName
Indoor unit
Outdoor unit
cfm
286X575X57555X700X700
2.717.5
29.5/24.5 32/25
14 to 23°CWBCertified operation range
Indoorunit
Dimensions(HXWXD) mm
mmSound pressure level2 (H/L) dB(A)
UnitDecoration panel
Machine weightkgkgUnit
Decoration panel
Airflow rate (H/L) 9/6.5 10/6.5317/229 353/229
36/27 41/32
12/8 15/10423/282 529/353
m3/min
Power supply
Note : 1Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB, 24°CWB. Equiv. refrigeration piping, 7.5 m (horizontal).2The operation sound is measured in anechoic chamber. If it is measured under the actual installation conditions, it is normally over the set value due to environmental noise and sound reflection.
Sealing material of air discharge outletPanel spacer
Interface adaptor for SkyAir series
Installation box for adaptor PCB
Replacement long-life filter
Remote sensor (for indoor temperature)
DCS302CA61DCS301BA61
DCS601C51DST301BA61
KRP1BA57KRP4AA53KRCS01-1B
BYFQ60B3W1
BRC1C61
KDBH44BA60KDBQ44BA60A
KDDQ44XA60
DTA112BA51
KRP1BA101
KAFQ441BA60
Note: 1Wiring for wired remote controller to be procured locally.2Installation box for adaptor PCB (KRP1BA101) is necessary. 3This optional accessory requires DTA112BA51.
Option List
Remote controller Wireless type Cooling only
BRC1E62Navigation Remote Controller Wired type1
Wired type1
FFQ25/35/50/60B
COMPACT MULTI FLOW CEILING MOUNTED CASSETTE TYPE
Quiet decor-blending form and easyinstallation in new or old buildingQuiet decor-blending form and easyinstallation in new or old building
Accessory required for indoor unit.
BRC1C61
Wired LCD Remote Controller
Note: Remote controller cable is not included and must be obtained locally.
A signal receiver must be added to the indoor unit.
Wireless LCD remote controller
Signal receiver unit (Installed type)
Wireless remote controller is suppliedin a set with a signal receiver.
BRC7E531W
SIZED TO FIT INSIDE 600mm WIDE CEILING GRIDS
MULTI-FLOW SYSTEM
QUIET, SMALL-DIAMETER FAN
AIR DIRECTION CAN BE SELECTEDACCORDING TO INSTALLATION
Central remote controllerUnified ON/OFF controllerSchedule timer
Wiring adaptor for electrical appendicesWiring adaptor for electrical appendices3
Installation box for adaptor PCB
Option List
Note: 1Wiring for wired remote controller to be procured locally.2The indoor unit is equipped standardly with the interface adaptor for SkyAir series. An option is unnecessary.3Installation box for adaptor PCB(KRP1D93A) is necessary.
Cooling only
FHQ71DAVM4 FHQ100DAVM4 FHQ125DAVM4 FHQ140DAVM4
KRP1BA54DCS601C51
KRP4AA52
KAFP501A80 KAFP501A160
KJB311AAKJB212AA
Remote sensor (for indoor temperature)Electrical box with earth terminal (3 blocks)Electrical box with earth terminal (2 blocks)
Note : 1Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB, 24°CWB. Equiv. refrigeration piping, 7.5 m (horizontal).2Capacities are net, including a deduction for cooling for indoor fan motor heat.3The operation sound is measured in anechoic chamber. If it is measured under the actual installation conditions, it is normally over the set value due to environmental noise and sound reflection.
VP20 (I.DØ20XO.DØ26)
30
Ø9.5Ø15.9
Ø26.0 (Hole)
°CDBCertified operation range
Motor output
CoolingNight quiet mode
CompressorCoil
kWRefrigerant charge (R-410A) kg
dB(A)dB(A)
Sound pressure level3
Dimensions (HXWXD) mm
Machine weight kg
Piping connections
mmLiquid (Flare)mmGas (Flare)mmDrain Indoor unit
Outdoor unit
Outdoorunit
mmMax. interunit piping length m
mMax. installation level difference
Type Hermetically sealed scroll typeType Cross fin coil
Note : 1Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB, 24°CWB. Equiv. refrigeration piping, 7.5 m (horizontal).2Capacities are net, including a deduction for cooling for indoor fan motor heat.3The operation sound is measured in anechoic chamber. If it is measured under the actual installation conditions, it is normally over the set value due to environmental noise and sound reflection.
Ø9.5
49dB(A)Night quiet mode 45
30
Ø15.9
Hermetically sealed swing typeType Micro channel
Ø26.0 (Hole)
1.9 (Charged for 30 m)
21 to 46
50 (Equivalent length 70m)
990X940X32065 73
2.03 1.92
VP13 (O.DØ18 X I.DØ13)
BRC1C61
intelligent Touch Controller2
Note: 1Wiring for wired remote controller to be procured locally.2The indoor unit is equipped standardly with the interface adaptor for SkyAir series. An option is unnecessary.3Installation box for adaptor PCB (KRP4AA93) is necessary.
Option ListName of option Remark
Central remote controller2
Remote controller
Unified ON/OFF controller2
Schedule timer2
Wiring adaptor for electrical appendices3
Electrical box with earth terminal (3 blocks)Electrical box with earth terminal (2 blocks)
Kit nameFAQ100CVEA4
DCS302CA61DCS301BA61DST301BA61DCS601C51KRP4AA51
KJB311AAKJB212AA
Drain-up kit
Installation box for adaptor PCB
Noise filter ( For electromagnetic interface use only)
Note : 1Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB, 24°CWB. Equiv. refrigeration piping, 7.5 m (horizontal)2Capacities are net, including a deduction for cooling for indoor fan motor heat.3External static pressure is changeable in 11 stages by remote controller.4The operation sound is measured in anechoic chamber. If it is measured under the actual installation conditions, it is normally over the set value due to environmental noise and sound reflection.5Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its dust collection efficiency(gravity method) 50% or more.
Note : 1Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB, 24°CWB. Equiv. refrigeration piping, 7.5 m (horizontal)2Capacities are net, including a deduction for cooling for indoor fan motor heat.3The operation sound is measured in anechoic chamber. If it is measured under the actual installation conditions, it is normally over the set value due to environmental noise and sound reflection.
Wiring adaptor for electrical appendicesInstallation box for adaptor PCB
Note: 1Wiring for wired remote controller to be procured locally. 2The indoor unit is equipped standardly with the interface adaptor for SkyAir series. An option is unnecessary.3Installation box for adaptor PCB (KRP4AA95) is necessary.