RX-JV/GV

W a l l M o u n t e d U n i t

Air Conditioners

Technical Data

w w w . d a i k i n . e u

RX-JV-GV_EN.pdf 1 12/05/2010 8:21:31

Page 2: Air Conditioners Technical Datafavorit-klimatici.com/wp-content/uploads/2010/09/RX-GV_databook.pdf · Piping connections Drain OD mm 18 Gas OD mm 12.7 15.9 Liquid OD mm 6.35 Piping

RX-JV/GV

W a l l M o u n t e d U n i t

Air Conditioners

Technical Data

w w w . d a i k i n . e u

RX-JV-GV_EN.pdf 2 12/05/2010 8:21:48

Page 3: Air Conditioners Technical Datafavorit-klimatici.com/wp-content/uploads/2010/09/RX-GV_databook.pdf · Piping connections Drain OD mm 18 Gas OD mm 12.7 15.9 Liquid OD mm 6.35 Piping

• Split Sky Air • Outdoor Units 1

• Outdoor Units • R-410A • RX-JV/GV

TABLE OF CONTENTSRX-JV/GV

1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Nominal Capacity and Nominal Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

3 Electrical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

4 Capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8Cooling/Heating capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

5 Dimensional drawing & centre of gravity . . . . . . . . . . . . . . . . . . . . . . . 14Dimensional drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14Centre of gravity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

6 Piping diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

7 Wiring diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

8 Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24Sound pressure spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

9 Operation range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

RX-JV-GV_EN.pdf 3 12/05/2010 8:21:49

Page 4: Air Conditioners Technical Datafavorit-klimatici.com/wp-content/uploads/2010/09/RX-GV_databook.pdf · Piping connections Drain OD mm 18 Gas OD mm 12.7 15.9 Liquid OD mm 6.35 Piping

• Outdoor Units • R-410A • RX-JV/GV

• Split Sky Air • Outdoor Units2

1 Features

Outdoor Uni Split Sky RX-JV/GV R-410A • Outdoor units for pair application

• Daikin outdoor units are neat and sturdy and can be mounted easily on a roof or terrace or simply placed against an outside wall.

• Outdoor units are fitted with a swing compressor, renowned for its low noise and high energy efficiency

• “Silent” buttons on the remote control lower the operation sound of the outdoor unit by 3dBA.

• Inverter compressors continuously adjust compressor speed to actual demand, fewer power - consuming starts and stops result in decreased energy consumption (up tot 30%) and more stable temperatures.

RX-JV-GV_EN.pdf 4 12/05/2010 8:21:49

Page 5: Air Conditioners Technical Datafavorit-klimatici.com/wp-content/uploads/2010/09/RX-GV_databook.pdf · Piping connections Drain OD mm 18 Gas OD mm 12.7 15.9 Liquid OD mm 6.35 Piping

• Split Sky Air • Outdoor Units 3

• Outdoor Units • R-410A • RX-JV/GV

2 Specifications

2-1 Nominal Capacity and Nominal Input RX20JV1B RX25JV1B RX35JV1B

For combination indoor units + outdoor units

Indoor Units FTX20JV1B FTX25JV1B FTX35JV1B

Cooling capacity Minimum kW 1.3Btu/h 4,400Kcal/h 1,120

Standard kW 2.0 2.5 3.3Btu/h 6,800 8,500 11,300Kcal/h 1,720 2,150 2,840

Maximum kW 2.6 3.0 3.8Btu/h 8,900 10,200 13,000Kcal/h 2,240 2,580 3,270

Heating capacity Minimum kW 1.3Btu/h 4,400Kcal/h 1,120

Standard kW 2.5 2.8 3.5Btu/h 8,500 9,600 11,900Kcal/h 2,150 2,410 3,010

Maximum kW 3.5 4.0 4.8Btu/h 11,600 13,600 16,400Kcal/h 3,010 3,440 4,130

Piping connections Drain OD mm 18.0Gas OD mm 9.52 Heat insulation Both liquid and gas pipesLiquid OD mm 6.35

Power Input Cooling Nominal kW 0.550 0.730 0.980Heating Nominal kW 0.950 0.690 0.930

For combination indoor units + outdoor units

EER Nominal 3.64 3.42 3.37COP Nominal 4.24 4.06 3.76Energy Label Cooling A

Heating AAnnual energy consumption kWh 275 365 490

2-1 Nominal Capacity and Nominal Input RX50G2V1B RX60G2V1B RX71GV1B

For combination indoor units + outdoor units

Indoor Units FTX50GV1B FTX60GV1B FTX71GV1B

Cooling capacity Max. Btu/h 20,500 22,900 29,000kcal/h 5,160 5,760 7,310kW 6.0 6.7 8.5

Min. Btu/h 5,800 7,800kcal/h 1,460 1,980kW 1.7 2.3

Nom. Btu/h 17,100 20,500 24,200kcal/h 4,300 5,160 6,110kW 5.0 6.0 7.1

Heating capacity Max. Btu/h 26,300 27,300 34,800kcal/h 6,620 6,880 8,770kW 7.7 8.0 10.2

Min. Btu/h 5,800 7,800kcal/h 1,460 1,980kW 1.7 2.3

Nom. Btu/h 19,800 23,900 28,000kcal/h 4,990 6,020 7,050kW 5.8 7.0 8.2

RX-JV-GV_EN.pdf 5 12/05/2010 8:21:49

Page 6: Air Conditioners Technical Datafavorit-klimatici.com/wp-content/uploads/2010/09/RX-GV_databook.pdf · Piping connections Drain OD mm 18 Gas OD mm 12.7 15.9 Liquid OD mm 6.35 Piping

• Outdoor Units • R-410A • RX-JV/GV

• Split Sky Air • Outdoor Units4

2 Specifications

Power Input Cooling Max. kW 2.08 2.40 3.20Min. kW 0.44 0.57Nom. kW 1.55 1.99 2.35

Heating Max. kW 2.53 2.81 3.82Min. kW 0.40 0.52Nom. kW 1.60 2.04 2.55

For combination indoor units + outdoor units

EER Nominal 3.23 3.02COP Nominal 3.63 3.43 3.22Energy Label Cooling A B B

Heating A B CAnnual energy consumption kWh 3000 3350 4250

2-2 Technical Specifications RX20JV1B RX25JV1B RX35JV1B

Casing Colour Ivory WhiteDimensions Unit Height mm 550

Width mm 658Depth mm 275

Packing Height mm 616Width mm 788Depth mm 359

Weight Unit kg 28 28 30Packed Unit kg 31 31 34

Heat Exchanger Dimensions Length mm 670 670 647Nr of Rows 1 1 2Fin Pitch mm 1.4 1.4 1.4Nr of Stages 24 24 24

Tube type Hi-Xa(7)Fin Type Waffle fin

Fan Type PropellerQuantity 1 1 1Air Flow Rate Cooling (High) m³/min 29.2 29.2 27.6

Heating (High) m³/min 26.2 26.2 24.5Cooling (High) cfm 1,030 1,030 975Heating (High) cfm 927 927 865

Motor Quantity 1 1 1Model KFD-280-33-8A

Motor Speed (nominal) Cooling (Low) rpm 720 720 720Cooling (High) rpm 860 860 860Heating (Low) rpm 350 350 350Heating (High) rpm 860 860 860

Fan Motor Output W 33 33 33Motor Model KFD-280-33-8AType Propeller

Compressor Quantity 1 1 1Motor Model 1YC23AEXDA

Type Hermetically sealed swing compressorMotor Output W 750 750 750

Operation Range Cooling Min °CDB 10 10 10Max °CDB 46 46 46

Heating Min °CWB -15 -15 -15Max °CWB 20 20 20

Sound Level (nominal)

Cooling Sound Power dBA 60 60 62Sound Pressure (High)

dBA 46 46 48

Heating Sound Pressure (High)

dBA 47 47 48

Refrigerant Type R-410ACharge kg 0.74 0.74 1.0

2-1 Nominal Capacity and Nominal Input RX50G2V1B RX60G2V1B RX71GV1B

RX-JV-GV_EN.pdf 6 12/05/2010 8:21:49

Page 7: Air Conditioners Technical Datafavorit-klimatici.com/wp-content/uploads/2010/09/RX-GV_databook.pdf · Piping connections Drain OD mm 18 Gas OD mm 12.7 15.9 Liquid OD mm 6.35 Piping

• Split Sky Air • Outdoor Units 5

• Outdoor Units • R-410A • RX-JV/GV

2 Specifications

Refrigerant Oil Type FVC50KCharged Volume l 0.375 0.375 0.375

Piping connections Liquid (OD) Quantity 1 1 1Diameter (OD) mm 6.35 6.35 6.35

Gas Quantity 1 1 1Diameter (OD) mm 9.52 9.52 9.52

Drain Quantity 1 1 1Diameter (OD) mm 18 18 18

Piping Length Maximum m 15 15 15Additional Refrigerant Charge kg/m 0.02(>10m)Installation height difference

Maximum m 12 12 12

Heat Insulation Both liquid and gas pipesStandard Accessories

Item Installation manualQuantity 1 1 1Item Drain plugQuantity 1 1 1

Notes Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19.0°CWB; outdoor temperature: 35°CDB, 24°CWB, refr.pip.length: 5m

Nominal heating capacities are based on: indoor temperature: 20°CDB; outdoor temperature:

7°CDB, 6°CWB, refr.pip.length: 5m

Nominal heating capacities are based on: indoor

temperature:20°CDB, outdoor temperature:7°CDB, 6°CWB,

refr.pip. length 5m

Nominal heating capacities are based on: indoor temperature: 20°CDB; outdoor temperature:

7°CDB, 6°CWB, refr.pip.length: 5m

2-2 Technical Specifications RX50G2V1B RX60G2V1B RX71GV1B

Casing Colour Ivory whiteDimensions Unit Height mm 792 900

Width mm 960 925Depth mm 390

Packing Height mm 735 770Width mm 825 900Depth mm 300 320

Weight Unit kg 48 71Packed Unit kg 53 79

Heat Exchanger Dimensions Length mm 845 857Nr of Rows 2Fin Pitch mm 1.8 1.4Nr of Stages 32 34

Tube type ø8 Hi-XAFin Type Waffle fin

Treatment Anti-corrosion treatment (PE)Fan Type Propeller

Air Flow Rate Cooling (High) m³/min 48.9 50.9 54.5Cooling (Low) m³/min 41.7 42.4 46Cooling (High) cfm 1,727 1,797 1,924Cooling (Low) cfm 1,472 1,497 1,624Heating (High) m³/min 45 46.3 46Heating (Low) m³/min 41.7 42.4 46Heating (High) cfm 1,589 1,635 1,624Heating (Low) cfm 1,472 1,497 1,624

Motor Model KFD-380-50-8CMotor Speed (nominal) Cooling (Low) rpm 670 680 730

Cooling (High) rpm 780 810 860Heating (Low) rpm 670 680 730Heating (High) rpm 720 740 730

Fan Motor Output W 53 66

2-2 Technical Specifications RX20JV1B RX25JV1B RX35JV1B

RX-JV-GV_EN.pdf 7 12/05/2010 8:21:50

Page 8: Air Conditioners Technical Datafavorit-klimatici.com/wp-content/uploads/2010/09/RX-GV_databook.pdf · Piping connections Drain OD mm 18 Gas OD mm 12.7 15.9 Liquid OD mm 6.35 Piping

• Outdoor Units • R-410A • RX-JV/GV

• Split Sky Air • Outdoor Units6

2 Specifications

Compressor Motor Model 2YC36BXD#C 2YC63BXD#AType Hermetically sealed swing compressorMotor Output W 1,20 1,10 1,92

Operation Range Cooling Min °CDB -10Max °CDB 46

Heating Min °CWB -15Max °CWB 18

Sound Level (nominal)

Cooling Sound Power dBA 61 63 66Sound Pressure (High) dBA 47 49 52Sound Pressure (Low) dBA 44 46 49

Heating Sound Pressure (High) dBA 48 49 52Sound Pressure (Low) dBA 45 46 49

Refrigerant Type R-410ACharge kg 1.5

Refrigerant Oil Type FVC50KCharged Volume l 0.650 0.750

Piping connections Drain OD mm 18Gas OD mm 12.7 15.9Liquid OD mm 6.35Piping Length Maximum m 30

Chargeless m 10Additional Refrigerant Charge kg/m 0.020 (for piping length exceeding 10m)Heat Insulation Both liquid and gas pipes

Standard Accessories Drain socket1

Installation manual1

Notes Cooling: indoor temp. 27°CDB, 19.0°CWB; outdoor temp. 35°CDB, 24°CWB; equivalent piping length: 5m

Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 5mSL: The silent fan level of the air flow rate setting

220V;3;230V;4;240V

2-3 Electrical Specifications RX20JV1B RX25JV1B RX35JV1B

Power Supply Name V1Phase 1~Frequency Hz 50 50 50Voltage V 220-230-240

Current Nominal running current (RLA)

Cooling (A) A 2.52 3.52 5.02Heating (A) A 2.62 3.02 4.52

Starting current (cooling/heating) A 2.7 3.7 5.0Wiring connections For Power Supply Quantity 3 3 3

For connection with indoor

Quantity 4 4 4Remark Earth wire included

2-3 Electrical Specifications RX50G2V1B RX60G2V1B RX71GV1B

Power Supply Name V1Phase 1~Frequency Hz 50Voltage V 220-230-240

Current Nominal running current (RLA)

Cooling A 7.040 - 6.750 - 6.450 9.010 - 8.920 - 8.230 10.590 - 10.200 - 9.710Heating A 7.230 - 6.940 - 6.640 9.190 - 8.800 - 8.410 11.420 - 10.930 - 10.440

Wiring connections For Power Supply Quantity 3For connection with indoor

Remark Earth wire included

2-2 Technical Specifications RX50G2V1B RX60G2V1B RX71GV1B

RX-JV-GV_EN.pdf 8 12/05/2010 8:21:50

Page 9: Air Conditioners Technical Datafavorit-klimatici.com/wp-content/uploads/2010/09/RX-GV_databook.pdf · Piping connections Drain OD mm 18 Gas OD mm 12.7 15.9 Liquid OD mm 6.35 Piping

• Split Sky Air • Outdoor Units 7

• Outdoor Units • R-410A • RX-JV/GV

3 Electrical data

3D065911

NOTES

1. RLA is based on the following conditions.Indoor temp. 27°C DB/19°C WB.Outdoor temp. 35°C DB.

2. Maximum allowable voltage variation between phases is 2%.3. Select wire size based on the larger value of MCA.4. Instead of fuse, use circuit breaker.

RX20-35JV

Representative unit combination Power supply Comp OFM IFM

Indoor unit Outdoor unit Hz-Volts Voltage range MCA MFA RHz RLA W FLA W FLA

FTX20JV1B RX20JV1B50 - 220

Max. 50Hz 264VMin. 50Hz 198V 14.5 16 36 2.2 33 0.17 16 0.1250 - 230

50 - 240

FTX25JV1B RX25JV1B50 - 220

Max. 50Hz 264VMin. 50Hz 198V 14.5 16 48 3.2 33 0.17 16 0.1250 - 230

50 - 240

FTX35JV1B RX35JV1B50 - 220

Max. 50Hz 264VMin. 50Hz 198V 14.5 16 70 4.7 33 0.17 16 0.1250 - 230

50 - 240

SYMBOLS

MCA : Min. Circuit Amps (A)MFA : Max. Fuse Amps (A)RLA : Rated Load Amps (A)OFM : Outdoor Fan MotorIFM : Indoor Fan MotorFLA : Full Load Amps (A)W : Fan Motor Rated Output (W)RHz : Rated Operating Frequency (Hz)

RX-JV-GV_EN.pdf 9 12/05/2010 8:21:50

Page 10: Air Conditioners Technical Datafavorit-klimatici.com/wp-content/uploads/2010/09/RX-GV_databook.pdf · Piping connections Drain OD mm 18 Gas OD mm 12.7 15.9 Liquid OD mm 6.35 Piping

• Outdoor Units • R-410A • RX-JV/GV

• Split Sky Air • Outdoor Units8

4 Capacity tables4 - 1 Cooling/Heating capacity tables

RX-JV-GV_EN.pdf 10 12/05/2010 8:21:50

Page 11: Air Conditioners Technical Datafavorit-klimatici.com/wp-content/uploads/2010/09/RX-GV_databook.pdf · Piping connections Drain OD mm 18 Gas OD mm 12.7 15.9 Liquid OD mm 6.35 Piping

• Split Sky Air • Outdoor Units 9

• Outdoor Units • R-410A • RX-JV/GV

4 Capacity tables4 - 1 Cooling/Heating capacity tables

RX-JV-GV_EN.pdf 11 12/05/2010 8:21:50

Page 12: Air Conditioners Technical Datafavorit-klimatici.com/wp-content/uploads/2010/09/RX-GV_databook.pdf · Piping connections Drain OD mm 18 Gas OD mm 12.7 15.9 Liquid OD mm 6.35 Piping

• Outdoor Units • R-410A • RX-JV/GV

• Split Sky Air • Outdoor Units10

4 Capacity tables4 - 1 Cooling/Heating capacity tables

RX-JV-GV_EN.pdf 12 12/05/2010 8:21:50

Page 13: Air Conditioners Technical Datafavorit-klimatici.com/wp-content/uploads/2010/09/RX-GV_databook.pdf · Piping connections Drain OD mm 18 Gas OD mm 12.7 15.9 Liquid OD mm 6.35 Piping

• Split Sky Air • Outdoor Units 11

• Outdoor Units • R-410A • RX-JV/GV

4 Capacity tables4 - 1 Cooling/Heating capacity tablesFTX50GV1B+RX50G2V1B

3D051923C

Cooling 50Hz 220-240VAFR 14.7

BF 0.28

Indoor Outdoor temperature (°C DB)EWB EDB 20 25 30 32 35 40°C °C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI

14.016.018.019.022.024.0

202225273032

5.125.355.585.706.046.27

3.613.553.693.863.713.60

1.191.201.201.211.221.22

4.895.125.355.475.816.04

3.493.433.583.753.623.52

1.301.311.321.321.331.34

4.664.895.125.235.585.81

3.373.323.473.653.523.43

1.421.431.431.441.451.45

4.564.795.025.145.495.72

3.323.273.433.613.493.40

1.461.471.481.481.491.50

4.424.654.88

3.253.213.37

1.531.541.55

4.194.424.654.775.115.34

3.133.103.263.453.353.27

1.651.651.661.661.671.68

5.00 3.55 1.555.355.58

3.433.35

1.561.57

Heating 50Hz 220-240V AFR 16.1

Indoor Outdoor temperature (°C WB)EDB -10 -5 0 6 10°C TC PI TC PI TC PI TC PI TC PI

15.020.022.024.025.027.0

3.903.703.623.543.503.42

1.351.391.401.421.431.44

4.564.364.284.204.164.08

1.421.461.471.481.491.51

5.215.014.934.854.814.73

1.481.521.541.551.561.57

6.00 1.56 6.526.326.246.166.126.04

1.621.651.671.681.691.70

5.80 1.605.725.645.605.52

1.611.631.641.65

NOTES

1. Ratings shown are net capacities which include a deduction for indoor fan motor heat.

2. shows nominal (rated) capacities and power input.3. TC, PI and SHC must be calculated by interpolation using

the figures in the above tables. (Figures out of the tables should not be used for calculation.)

4. About SHC which are not mentioned on the table, please calculate them with around values in direct proportion.

5. Capacities are based on the following conditions.Corresponding refrigerant piping length : 7.5mLevel difference : 0m

6. Air flow rate (AFR) and Bypass factor (BF) are tabulated above table.

SYMBOLS

AFR : Air flow rate (m3/min.)BF : Bypass factorEWB : Entering wet bulb temp. (°C)EDB : Entering dry bulb temp. (°C)TC : Total capacity (kW)SHC : Sensible heat capacity (kW)PI : Power input (kW)

RX-JV-GV_EN.pdf 13 12/05/2010 8:21:50

Page 14: Air Conditioners Technical Datafavorit-klimatici.com/wp-content/uploads/2010/09/RX-GV_databook.pdf · Piping connections Drain OD mm 18 Gas OD mm 12.7 15.9 Liquid OD mm 6.35 Piping

• Outdoor Units • R-410A • RX-JV/GV

• Split Sky Air • Outdoor Units12

4 Capacity tables4 - 1 Cooling/Heating capacity tables

FTX60GV1B+RX60G2V1B

3D051924E

Cooling 50Hz 220-240VAFR 16.2

BF 0.29

Indoor Outdoor temperature (°C DB)EWB EDB 20 25 30 32 35 40°C °C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI

14.016.018.019.022.024.0

202225273032

5.606.426.706.847.257.53

3.944.174.314.494.314.18

1.491.541.541.551.561.57

5.606.146.426.566.977.25

3.944.024.174.364.194.07

1.661.681.691.701.711.72

5.595.866.146.286.696.97

3.943.884.044.234.083.97

1.821.831.841.841.861.86

5.485.756.036.176.586.86

3.883.823.994.184.043.93

1.881.891.901.901.911.92

5.315.595.86

3.793.743.91

1.971.981.99

5.035.315.585.726.146.41

3.643.603.783.983.863.77

2.122.122.132.142.152.16

6.00 4.10 1.996.416.69

3.973.87

2.002.01

Heating 50Hz 220-240V AFR 17.4

Indoor Outdoor temperature (°C WB)EDB -10 -5 0 6 10°C TC PI TC PI TC PI TC PI TC PI

15.020.022.024.025.027.0

4.714.474.374.284.234.13

1.731.771.791.811.821.84

5.505.265.165.075.024.92

1.811.861.871.891.901.92

6.296.055.955.865.815.71

1.891.941.961.981.992.00

7.24 1.99 7.877.637.547.447.397.29

2.062.112.132.142.152.17

7.00 2.046.906.816.766.66

2.062.082.092.10

NOTES

1. Ratings shown are net capacities which include a deduction for indoor fan motor heat.

2. shows nominal (rated) capacities and power input.3. TC, PI and SHC must be calculated by interpolation using

the figures in the above tables. (Figures out of the tables should not be used for calculation.)

4. About SHC which are not mentioned on the table, please calculate them with around values in direct proportion.

5. Capacities are based on the following conditions.(1) Corresponding refrigerant piping length : 7.5m(2) Level difference : 0m

6. Air flow rate (AFR) and Bypass factor (BF) are tabulated above table.

SYMBOLS

AFR : Air flow rate (m3/min.)BF : Bypass factorEWB : Entering wet bulb temp. (°C)EDB : Entering dry bulb temp. (°C)TC : Total capacity (kW)SHC : Sensible heat capacity (kW)PI : Power input (kW)

RX-JV-GV_EN.pdf 14 12/05/2010 8:21:50

Page 15: Air Conditioners Technical Datafavorit-klimatici.com/wp-content/uploads/2010/09/RX-GV_databook.pdf · Piping connections Drain OD mm 18 Gas OD mm 12.7 15.9 Liquid OD mm 6.35 Piping

• Split Sky Air • Outdoor Units 13

• Outdoor Units • R-410A • RX-JV/GV

4 Capacity tables4 - 1 Cooling/Heating capacity tables

FTX71GV1B+RX71GV1B

3D056030C

Cooling 50Hz 220-240VAFR 17.4

BF 0.30

Indoor Outdoor temperature (°C DB)EWB EDB 20 25 30 32 35 40°C °C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI

14.016.018.019.022.024.0

202225273032

5.937.287.938.098.588.91

4.184.674.985.164.954.79

1.641.781.821.831.841.85

5.937.277.607.768.258.58

4.184.664.815.004.814.66

1.861.992.002.002.022.03

5.936.947.277.437.928.25

4.184.484.654.844.674.53

2.072.162.172.182.192.20

5.936.817.137.307.798.12

4.184.414.584.784.614.48

2.162.232.242.252.262.27

5.936.616.94

4.184.314.48

2.292.332.34

5.936.286.616.777.267.59

4.184.144.334.534.394.28

2.502.512.522.522.542.55

7.10 4.69 2.357.597.92

4.534.40

2.372.38

Heating 50Hz 220-240V AFR 19.7

Indoor Outdoor temperature (°C WB)EDB -10 -5 0 6 10°C TC PI TC PI TC PI TC PI TC PI

15.020.022.024.025.027.0

5.525.245.125.014.954.84

2.162.212.242.262.272.29

6.456.166.055.945.885.77

2.262.322.342.362.382.40

7.377.096.986.866.816.69

2.372.422.452.472.482.50

8.48 2.49 9.228.948.838.718.477.92

2.582.632.662.682.682.68

8.20 2.558.097.977.927.80

2.572.602.612.63

NOTES

1. Capacities are based on the following conditions.(1) Corresponding refrigerant piping length : 7.5m(2) Level difference : 0m

2. shows nominal (rated) capacities and power input.

SYMBOLS

AFR : Air flow rate (m3/min.)BF : Bypass factorEWB : Entering wet bulb temp. (°C)EDB : Entering dry bulb temp. (°C)TC : Total capacity (kW)SHC : Sensible heat capacity (kW)PI : Power input (kW)

RX-JV-GV_EN.pdf 15 12/05/2010 8:21:51

Page 16: Air Conditioners Technical Datafavorit-klimatici.com/wp-content/uploads/2010/09/RX-GV_databook.pdf · Piping connections Drain OD mm 18 Gas OD mm 12.7 15.9 Liquid OD mm 6.35 Piping

• Outdoor Units • R-410A • RX-JV/GV

• Split Sky Air • Outdoor Units14

5 Dimensional drawing & centre of gravity5 - 1 Dimensional drawingRX20-35JV

3D058472A

MINIMUM SPACE FOR AIR PASSAGE

Drain outlet( I, D ø 15.9 hose for connectionwith drain joint [option] )

4-holes for anchor bolts( M8 or M10 )

Brand name labelHandle Manufacture’s label

Caution label

In case of removingstop valve cover

Wiringinlet

Serviceport

Outdoor air thermistor

Wall height on air outlet side = less than 1200

Gas stop valve(ø 9.5 cut)

Liquidstop valve(ø 6.4 cut)

RX50-60G

3D051657P

Drain outlet(I.D. ø15.9 hose for connection)

Brand name label

Minimum space for air passage

Outdoor air temperature thermistorWiring inlet Terminal strip with

earth terminal

Name plateIn case of removing

stop valve cover

Liquid stop valve (ø6.4CuT)

Gas stop valve (ø12.7CuT)Service port

4–Holes for anchor bolts(M8 or M10)

Wall height on air outlet side= less than 1200

RX-JV-GV_EN.pdf 16 12/05/2010 8:21:51

Page 17: Air Conditioners Technical Datafavorit-klimatici.com/wp-content/uploads/2010/09/RX-GV_databook.pdf · Piping connections Drain OD mm 18 Gas OD mm 12.7 15.9 Liquid OD mm 6.35 Piping

• Split Sky Air • Outdoor Units 15

• Outdoor Units • R-410A • RX-JV/GV

5 Dimensional drawing & centre of gravity5 - 1 Dimensional drawing

RX-JV-GV_EN.pdf 17 12/05/2010 8:21:51

Page 18: Air Conditioners Technical Datafavorit-klimatici.com/wp-content/uploads/2010/09/RX-GV_databook.pdf · Piping connections Drain OD mm 18 Gas OD mm 12.7 15.9 Liquid OD mm 6.35 Piping

• Outdoor Units • R-410A • RX-JV/GV

• Split Sky Air • Outdoor Units16

5 Dimensional drawing & centre of gravity5 - 2 Centre of gravityRX20-25JV

4D058111C

RX35JV

4D058147C

RX-JV-GV_EN.pdf 18 12/05/2010 8:21:51

Page 19: Air Conditioners Technical Datafavorit-klimatici.com/wp-content/uploads/2010/09/RX-GV_databook.pdf · Piping connections Drain OD mm 18 Gas OD mm 12.7 15.9 Liquid OD mm 6.35 Piping

• Split Sky Air • Outdoor Units 17

• Outdoor Units • R-410A • RX-JV/GV

5 Dimensional drawing & centre of gravity5 - 2 Centre of gravityRX50-60GV

4D051638P

The position of foundation bolt

RX71GV

4D053630D

Position of anchor bolt

RX-JV-GV_EN.pdf 19 12/05/2010 8:21:51

Page 20: Air Conditioners Technical Datafavorit-klimatici.com/wp-content/uploads/2010/09/RX-GV_databook.pdf · Piping connections Drain OD mm 18 Gas OD mm 12.7 15.9 Liquid OD mm 6.35 Piping

• Outdoor Units • R-410A • RX-JV/GV

• Split Sky Air • Outdoor Units18

6 Piping diagram

Heat exchangerthermistor

Outdoor temperature thermistorHeat exchanger

OUTDOOR UNITRX20-25JV

3D058716B

Compressor

Discharge pipe thermistor

ON: Heating

Heating

RX35JV

3D058714B

Heat exchangerthermistor

Outdoor temperature thermistorHeat exchanger

OUTDOOR UNIT

Compressor

Discharge pipe thermistor

Four way

ON: Heating

Heating

RX-JV-GV_EN.pdf 20 12/05/2010 8:21:52

Page 21: Air Conditioners Technical Datafavorit-klimatici.com/wp-content/uploads/2010/09/RX-GV_databook.pdf · Piping connections Drain OD mm 18 Gas OD mm 12.7 15.9 Liquid OD mm 6.35 Piping

• Split Sky Air • Outdoor Units 19

• Outdoor Units • R-410A • RX-JV/GV

6 Piping diagram

RX50-60G

3D051637Q

Heat exchanger

Capillary tube 1

Capillary tube 4

Capillary tube 2 Capillary tube 3

Outdoor unit7.9CuT7.9CuT7.9CuT7.9CuT7.9CuT7.9CuT7.9CuT7.9CuT

12.7CuT

12.7CuT 9.5CuT

7.9CuT

7.9CuT

Muffler

Muffler

7.9CuT

12.7CuT

6.4CuT

7.9CuT

4.0CuT

7.9CuT

4.0CuT

4.0CuT4.0CuT

12.7CuT

(6.4CuT)

(12.7CuT)

Heatexchangerthermistor

Propeller fan

Compressor

Discharge pipe thermistor

Muffler withfilter

Liquidstop valve

Gas stop valve with service port

Field piping

Field piping

Motor operated valve

Filter

Receiver

Muffler

Four way valve on:heating

Outdoor air temperature thermistor

Refrigerant flowCoolingHeating

6.4Cu

T6.4

CuT

6.4Cu

T

9.5Cu

T 6.4CuT

12.7C

uT

RX71GV

3D054593F

Heat exchanger

Receiver

Outdoor unit

7.9CuT7.9CuT7.9CuT7.9CuT7.9CuT7.9CuT7.9CuT7.9CuT

4.0CuT

7.9CuT

9.5CuT

9.5CuT 9.5CuT 9.5CuT 9.5CuT 9.5CuT

12.7C

uT

Liquid

line

stop v

alve

liquid (6.4CuT)

gas (15.9CuT)15.9CuT15.9CuT

15.9CuT

7.9CuT7.9CuT

15.9CuT15.9CuT

15.9C

uT15.9C

uT

7.9Cu

T

Propeller fan

DC fan motor

Header

Motoroperated

valve

Gas linestop valve

Field piping

Field piping

FilterFilterDistributor

Capillary tube

AccumulatorAccumulator

Compressor

Muffler

Discharge pipe thermistor

4-way valveon: heating

Outdoor temperature thermistor

Heat exchanger (condenser) thermistor

Refrigerant flowCoolingHeating

9.5Cu

T9.5

CuT

RX-JV-GV_EN.pdf 21 12/05/2010 8:21:52

Page 22: Air Conditioners Technical Datafavorit-klimatici.com/wp-content/uploads/2010/09/RX-GV_databook.pdf · Piping connections Drain OD mm 18 Gas OD mm 12.7 15.9 Liquid OD mm 6.35 Piping

• Outdoor Units • R-410A • RX-JV/GV

• Split Sky Air • Outdoor Units20

7 Wiring diagram7 - 1 Wiring diagram

RX-JV-GV_EN.pdf 22 12/05/2010 8:21:53

Page 23: Air Conditioners Technical Datafavorit-klimatici.com/wp-content/uploads/2010/09/RX-GV_databook.pdf · Piping connections Drain OD mm 18 Gas OD mm 12.7 15.9 Liquid OD mm 6.35 Piping

• Split Sky Air • Outdoor Units 21

• Outdoor Units • R-410A • RX-JV/GV

7 Wiring diagram7 - 1 Wiring diagramRX50G

3D056095C

Z1C~Z5C Ferrite core LEDA Pilot lampX1M, X2M Terminal strip L LiveY1E Electronic expansion valve coil N NeutralV2, V3, V5, V6, V11 Varistor SW1 Forced operation ON/OFF SW (SW1)SA2 Surge arrester SW4 Local setting SW (SW4)FU1, FU2, FU3 Fuse M1C Compressor motorAC1, AC2 M1F Fan motorU, V, W, X11A, X12A L1R ReactorE1, E2 Q1L Overload protectorHR1, HR2 Connector PM1 Power moduleMRM10, MRM20 PCB1, 2 Printed circuit boardMRC/W Magnetic relay Y1R Reversing solenoid valve coilR1T~R3T Thermistor Sheet metal Terminal strip fixed plateS2~S102 Connector

Field wiring

Powersupply

To indoor unit

indoor

LED A

Sheetmetal

(outdoor) (discharge)(condenser)

Outdoor

RX-JV-GV_EN.pdf 23 12/05/2010 8:21:53

Page 24: Air Conditioners Technical Datafavorit-klimatici.com/wp-content/uploads/2010/09/RX-GV_databook.pdf · Piping connections Drain OD mm 18 Gas OD mm 12.7 15.9 Liquid OD mm 6.35 Piping

• Outdoor Units • R-410A • RX-JV/GV

• Split Sky Air • Outdoor Units22

7 Wiring diagram7 - 1 Wiring diagramRX60G

3D050706K

Z1C~Z4C Ferrite core LEDA Pilot lampX1M, X2M Terminal strip L LiveY1E Electronic expansion valve coil N NeutralV2, V3, V5, V6, V11 Varistor SW1 Forced operation ON/OFF SW (SW1)SA2 Surge arrester SW4 Local setting SW (SW4)FU1, FU2, FU3 Fuse M1C Compressor motorAC1, AC2 M1F Fan motorU, V, W, X11A L1R ReactorE1, E2 Q1L Overload protectorHR1, HR2 Connector PM1 Power moduleMRM10, MRM20 PCB1, 2 Printed circuit boardMRC/W Magnetic relay Y1R Reversing solenoid valve coilR1T~R3T Thermistor Sheet metal Terminal strip fixed plateS2~S102 Connector

Field wiring

Powersupply

To indoor unit

indoor

LED A

Sheetmetal

(outdoor) (discharge)(condenser)

Outdoor

RX-JV-GV_EN.pdf 24 12/05/2010 8:21:53

Page 25: Air Conditioners Technical Datafavorit-klimatici.com/wp-content/uploads/2010/09/RX-GV_databook.pdf · Piping connections Drain OD mm 18 Gas OD mm 12.7 15.9 Liquid OD mm 6.35 Piping

• Split Sky Air • Outdoor Units 23

• Outdoor Units • R-410A • RX-JV/GV

7 Wiring diagram7 - 1 Wiring diagramRX71GV

3D053931J

Z1C~Z7C Ferrite core LEDA Pilot lampX1M, X2M Terminal strip L LiveY1E Electronic expansion valve coil N NeutralV2, V3, V5, V9, V100 Varistor SW1 Forced operation ON/OFF SW (SW1)SA2 Surge arrester SW4 Local setting SW (SW4)FU1, FU2, FU3 Fuse M1C Compressor motorAC1, AC2 M1F Fan motorU, V, W, X11A, X12A L1R ReactorE1, E2 Q1L Overload protectorHR1, HR2 Connector PM1 Power moduleMRM10, MRM20 PCB1, 2 Printed circuit boardMRC/W Magnetic relay Y1R Reversing solenoid valve coilR1T~R3T Thermistor Sheet metal Terminal strip fixed plateS2~S102 Connector

Field wiring

Powersupply

To indoor unit

indoor

LED A

Sheetmetal

(outdoor) (discharge)(condenser)

Outdoor

RX-JV-GV_EN.pdf 25 12/05/2010 8:21:53

Page 26: Air Conditioners Technical Datafavorit-klimatici.com/wp-content/uploads/2010/09/RX-GV_databook.pdf · Piping connections Drain OD mm 18 Gas OD mm 12.7 15.9 Liquid OD mm 6.35 Piping

• Outdoor Units • R-410A • RX-JV/GV

• Split Sky Air • Outdoor Units24

8 Sound data8 - 1 Sound pressure spectrum

NOTES

1 Over All (dB):(B,G,N is already rectified)

2 Measuring place: measure in anechoic room.3 Operation noise differs with operation and ambient conditions.4 Location of microphone.

JISC9612The operation noise measuring method is in accordance with JISC9612

RX20JV

3D059002A

NOTES

1 Over All (dB):(B,G,N is already rectified)

2 Measuring place: measure in anechoic room.3 Operation noise differs with operation and ambient conditions.4 Location of microphone.

JISC9612The operation noise measuring method is in accordance with JISC9612

Octav

e ban

d sou

nd pr

essu

re le

vel d

B (0

dB =

0.00

02μ

bar)

Octav

e ban

d sou

nd pr

essu

re le

vel d

B (0

dB =

0.00

02μ

bar)

Octave band center frequency - IEC (Hz) Octave band center frequency - IEC (Hz)

Scale 50Hz230v (H)

A 46

Scale 50Hz230v (H)

A 47

Approximatethreshold hearing for continuous noise

Approximatethreshold hearing for continuous noise

Cooling Heating

1m 1m

NOTES

1 Over All (dB):(B,G,N is already rectified)

2 Measuring place: measure in anechoic room.3 Operation noise differs with operation and ambient conditions.4 Location of microphone.

JISC9612The operation noise measuring method is in accordance with JISC9612

RX25JV

3D059003A

NOTES

1 Over All (dB):(B,G,N is already rectified)

2 Measuring place: measure in anechoic room.3 Operation noise differs with operation and ambient conditions.4 Location of microphone.

JISC9612The operation noise measuring method is in accordance with JISC9612

Octav

e ban

d sou

nd pr

essu

re le

vel d

B (0

dB =

0.00

02μ

bar)

Octav

e ban

d sou

nd pr

essu

re le

vel d

B (0

dB =

0.00

02μ

bar)

Octave band center frequency - IEC (Hz) Octave band center frequency - IEC (Hz)

Scale 50Hz230v (H)

A 46

Scale 50Hz230v (H)

A 47

Approximatethreshold hearing for continuous noise

Approximatethreshold hearing for continuous noise

Cooling Heating

1m 1m

RX-JV-GV_EN.pdf 26 12/05/2010 8:21:54

Page 27: Air Conditioners Technical Datafavorit-klimatici.com/wp-content/uploads/2010/09/RX-GV_databook.pdf · Piping connections Drain OD mm 18 Gas OD mm 12.7 15.9 Liquid OD mm 6.35 Piping

• Split Sky Air • Outdoor Units 25

• Outdoor Units • R-410A • RX-JV/GV

8 Sound data8 - 1 Sound pressure spectrumRX35JV

3D059004A

NOTES

1 Over All (dB):(B,G,N is already rectified)

2 Measuring place: measure in anechoic room.3 Operation noise differs with operation and ambient conditions.4 Location of microphone.

JISC9612The operation noise measuring method is in accordance with JISC9612

NOTES

1 Over All (dB):(B,G,N is already rectified)

2 Measuring place: measure in anechoic room.3 Operation noise differs with operation and ambient conditions.4 Location of microphone.

JISC9612The operation noise measuring method is in accordance with JISC9612

Octav

e ban

d sou

nd pr

essu

re le

vel d

B (0

dB =

0.00

02μ

bar)

Octav

e ban

d sou

nd pr

essu

re le

vel d

B (0

dB =

0.00

02μ

bar)

Octave band center frequency - IEC (Hz) Octave band center frequency - IEC (Hz)

Scale 50Hz230V (H)

A 48

Scale 50Hz230V (H)

A 48

Approximatethreshold hearing for continuous noise

Approximatethreshold hearing for continuous noise

Cooling Heating

RX50G

3D051717D

NOTES

1 Over All (dB):(B,G,N is already rectified)

2 Measuring place: measured in an echoic room.3 Operation noise differs with operation and ambient conditions.4 Location of microphone.

JIS C 9612The operation noise measuring method is in accordance with JIS C 9612

NOTES

1 Over All (dB):(B,G,N is already rectified)

2 Operation noise differs with operation and ambient conditions.

Octav

e ban

d sou

nd pr

essu

re le

vel d

B (0

dB =

0.00

02μ

bar)

Octav

e ban

d sou

nd pr

essu

re le

vel d

B (0

dB =

0.00

02μ

bar)

Octave band center frequency - IEC (Hz) Octave band center frequency - IEC (Hz)

Scale 50Hz220~240V

A 47

Scale 50Hz220~240V

A 48

Approximatethreshold hearing for continuous noise

Approximatethreshold hearing for continuous noise

Cooling Heating

RX-JV-GV_EN.pdf 27 12/05/2010 8:21:54

Page 28: Air Conditioners Technical Datafavorit-klimatici.com/wp-content/uploads/2010/09/RX-GV_databook.pdf · Piping connections Drain OD mm 18 Gas OD mm 12.7 15.9 Liquid OD mm 6.35 Piping

• Outdoor Units • R-410A • RX-JV/GV

• Split Sky Air • Outdoor Units26

8 Sound data8 - 1 Sound pressure spectrumRX60G

3D051716D

NOTES

1 Over All (dB):(B,G,N is already rectified)

2 Measuring place: measured in an echoic room.3 Operation noise differs with operation and ambient conditions.4 Location of microphone.

JIS C 9612The operation noise measuring method is in accordance with JIS C 9612

NOTES

1 Over All (dB):(B,G,N is already rectified)

2 Operation noise differs with operation and ambient conditions.

Octav

e ban

d sou

nd pr

essu

re le

vel d

B (0

dB =

0.00

02μ

bar)

Octav

e ban

d sou

nd pr

essu

re le

vel d

B (0

dB =

0.00

02μ

bar)

Octave band center frequency - IEC (Hz) Octave band center frequency - IEC (Hz)

Scale 50Hz220~240V

A 49

Scale 50Hz220~240V

A 49

Approximatethreshold hearing for continuous noise

Approximatethreshold hearing for continuous noise

Cooling Heating

RX71GV

3D055789B

NOTES

1 Over All (dB):(B,G,N is already rectified)

2 Measuring place: measured in an anechoic room.3 Operation noise differs with operation and ambient conditions.4 Location of microphone.

JISC9612The operation noise measuring method is in accordance with JISC9612

NOTES

1 Over All (dB):(B,G,N is already rectified)

2 Operation noise differs with operation and ambient conditions.

Octav

e ban

d sou

nd pr

essu

re le

vel d

B (0

dB =

0.00

02μ

bar)

Octav

e ban

d sou

nd pr

essu

re le

vel d

B (0

dB =

0.00

02μ

bar)

Octave band center frequency - IEC (Hz) Octave band center frequency - IEC (Hz)

Scale 50Hz220~240V

A 52

Scale 50Hz220~240V

A 52

Approximatethreshold hearing for continuous noise

Approximatethreshold hearing for continuous noise

Cooling Heating

RX-JV-GV_EN.pdf 28 12/05/2010 8:21:54

Page 29: Air Conditioners Technical Datafavorit-klimatici.com/wp-content/uploads/2010/09/RX-GV_databook.pdf · Piping connections Drain OD mm 18 Gas OD mm 12.7 15.9 Liquid OD mm 6.35 Piping

• Split Sky Air • Outdoor Units 27

• Outdoor Units • R-410A • RX-JV/GV

9 Operation range

RX20-35JV

3D058975A

NOTES

The graphs are based on the following conditions.Equivalent piping length 5mLevel difference 0m

Outdo

or te

mp. (

°C D

B)

Conti

nuou

s ope

ratio

n

Conti

nuou

s ope

ratio

n

Pull-d

own p

eriod

Indoor temp. (°C WB)

Indoor temp. (°C DB)

Cooling

(-15°C DB)

Outdo

or te

mp. (

°C W

B)

RX50-60G

RX71GV

NOTES

The graphs are based on the following conditions.– Equivalent piping length 7.5m– Level difference 0m– Air flow rate High

HeatingCooling

Indoor temp. (°C WB)Indoor temp. (°C DB)

(-15°C DB)

Conti

nuou

s ope

ratio

n

Conti

nuou

s ope

ratio

n

Pull-d

own p

eriod

Outdo

or te

mp. (

°C D

B)

Outdo

or te

mp. (

°C W

B)

3D028318P

RX-JV-GV_EN.pdf 29 12/05/2010 8:21:55

Page 30: Air Conditioners Technical Datafavorit-klimatici.com/wp-content/uploads/2010/09/RX-GV_databook.pdf · Piping connections Drain OD mm 18 Gas OD mm 12.7 15.9 Liquid OD mm 6.35 Piping

Naamloze Vennootschap - Zandvoordestraat 300, B-8400 Oostende - Belgium - www.daikin.eu - BE 0412 120 336 - RPR Oostende

Daikin’s unique position as a manufacturer of air

conditioning equipment, compressors and refrigerants

has led to its close involvement in environmental issues.

For several years Daikin has had the intention to become

a leader in the provision of products that have limited

impact on the environment. This challenge demands the

eco design and development of a wide range of products

and an energy management system, resulting in energy

conservation and a reduction of waste.

Daikin Europe N.V. is participating in the EUROVENT

Certification Programme. Products are as listed in the

EUROVENT Directory of Certified Products.

Daikin products are distributed by:

EE

DE

N1

0-1

00

• C

D •

05

/10

• C

op

yri

gh

t D

aik

in

Th

e p

rese

nt

pu

blic

ati

on

su

pe

rse

de

s E

ED

EN

09

-10

0

Pre

par

ed

in B

elg

ium

by

Lan

no

o (

ww

w.la

nn

oo

pri

nt.

be

), a

com

pan

y w

ho

se c

on

cern

for

the

en

viro

nm

en

t is

se

t in

th

e E

MA

S an

d IS

O 1

40

01

sys

tem

s.

Re

spo

nsi

ble

Ed

ito

r: D

aik

in E

uro

pe

N.V

., Z

an

dv

oo

rde

stra

at

30

0,

B-8

40

0 O

ost

en

de

The present publication is drawn up by way of information only and does not constitute an offer binding

upon Daikin Europe N.V.. Daikin Europe N.V. has compiled the content of this publication to the best of its

knowledge. No express or implied warranty is given for the completeness, accuracy, reliability or fitness for

particular purpose of its content and the products and services presented therein. Specifications are subject