• Split Sky Air • Outdoor Units 1
• Outdoor Units • R-410A • RX-JV/GV
TABLE OF CONTENTSRX-JV/GV
1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Nominal Capacity and Nominal Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3 Electrical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
4 Capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8Cooling/Heating capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
5 Dimensional drawing & centre of gravity . . . . . . . . . . . . . . . . . . . . . . . 14Dimensional drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14Centre of gravity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
6 Piping diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
7 Wiring diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
8 Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24Sound pressure spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
9 Operation range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
RX-JV-GV_EN.pdf 3 12/05/2010 8:21:49
• Outdoor Units • R-410A • RX-JV/GV
• Split Sky Air • Outdoor Units2
1 Features
Outdoor Uni Split Sky RX-JV/GV R-410A • Outdoor units for pair application
• Daikin outdoor units are neat and sturdy and can be mounted easily on a roof or terrace or simply placed against an outside wall.
• Outdoor units are fitted with a swing compressor, renowned for its low noise and high energy efficiency
• “Silent” buttons on the remote control lower the operation sound of the outdoor unit by 3dBA.
• Inverter compressors continuously adjust compressor speed to actual demand, fewer power - consuming starts and stops result in decreased energy consumption (up tot 30%) and more stable temperatures.
RX-JV-GV_EN.pdf 4 12/05/2010 8:21:49
• Split Sky Air • Outdoor Units 3
• Outdoor Units • R-410A • RX-JV/GV
2 Specifications
2-1 Nominal Capacity and Nominal Input RX20JV1B RX25JV1B RX35JV1B
For combination indoor units + outdoor units
Indoor Units FTX20JV1B FTX25JV1B FTX35JV1B
Cooling capacity Minimum kW 1.3Btu/h 4,400Kcal/h 1,120
Standard kW 2.0 2.5 3.3Btu/h 6,800 8,500 11,300Kcal/h 1,720 2,150 2,840
Maximum kW 2.6 3.0 3.8Btu/h 8,900 10,200 13,000Kcal/h 2,240 2,580 3,270
Heating capacity Minimum kW 1.3Btu/h 4,400Kcal/h 1,120
Standard kW 2.5 2.8 3.5Btu/h 8,500 9,600 11,900Kcal/h 2,150 2,410 3,010
Maximum kW 3.5 4.0 4.8Btu/h 11,600 13,600 16,400Kcal/h 3,010 3,440 4,130
Piping connections Drain OD mm 18.0Gas OD mm 9.52 Heat insulation Both liquid and gas pipesLiquid OD mm 6.35
Power Input Cooling Nominal kW 0.550 0.730 0.980Heating Nominal kW 0.950 0.690 0.930
For combination indoor units + outdoor units
EER Nominal 3.64 3.42 3.37COP Nominal 4.24 4.06 3.76Energy Label Cooling A
Heating AAnnual energy consumption kWh 275 365 490
2-1 Nominal Capacity and Nominal Input RX50G2V1B RX60G2V1B RX71GV1B
For combination indoor units + outdoor units
Indoor Units FTX50GV1B FTX60GV1B FTX71GV1B
Cooling capacity Max. Btu/h 20,500 22,900 29,000kcal/h 5,160 5,760 7,310kW 6.0 6.7 8.5
Min. Btu/h 5,800 7,800kcal/h 1,460 1,980kW 1.7 2.3
Nom. Btu/h 17,100 20,500 24,200kcal/h 4,300 5,160 6,110kW 5.0 6.0 7.1
Heating capacity Max. Btu/h 26,300 27,300 34,800kcal/h 6,620 6,880 8,770kW 7.7 8.0 10.2
Min. Btu/h 5,800 7,800kcal/h 1,460 1,980kW 1.7 2.3
Nom. Btu/h 19,800 23,900 28,000kcal/h 4,990 6,020 7,050kW 5.8 7.0 8.2
RX-JV-GV_EN.pdf 5 12/05/2010 8:21:49
• Outdoor Units • R-410A • RX-JV/GV
• Split Sky Air • Outdoor Units4
2 Specifications
Power Input Cooling Max. kW 2.08 2.40 3.20Min. kW 0.44 0.57Nom. kW 1.55 1.99 2.35
Heating Max. kW 2.53 2.81 3.82Min. kW 0.40 0.52Nom. kW 1.60 2.04 2.55
For combination indoor units + outdoor units
EER Nominal 3.23 3.02COP Nominal 3.63 3.43 3.22Energy Label Cooling A B B
Heating A B CAnnual energy consumption kWh 3000 3350 4250
2-2 Technical Specifications RX20JV1B RX25JV1B RX35JV1B
Casing Colour Ivory WhiteDimensions Unit Height mm 550
Width mm 658Depth mm 275
Packing Height mm 616Width mm 788Depth mm 359
Weight Unit kg 28 28 30Packed Unit kg 31 31 34
Heat Exchanger Dimensions Length mm 670 670 647Nr of Rows 1 1 2Fin Pitch mm 1.4 1.4 1.4Nr of Stages 24 24 24
Tube type Hi-Xa(7)Fin Type Waffle fin
Fan Type PropellerQuantity 1 1 1Air Flow Rate Cooling (High) m³/min 29.2 29.2 27.6
Heating (High) m³/min 26.2 26.2 24.5Cooling (High) cfm 1,030 1,030 975Heating (High) cfm 927 927 865
Motor Quantity 1 1 1Model KFD-280-33-8A
Motor Speed (nominal) Cooling (Low) rpm 720 720 720Cooling (High) rpm 860 860 860Heating (Low) rpm 350 350 350Heating (High) rpm 860 860 860
Fan Motor Output W 33 33 33Motor Model KFD-280-33-8AType Propeller
Compressor Quantity 1 1 1Motor Model 1YC23AEXDA
Type Hermetically sealed swing compressorMotor Output W 750 750 750
Operation Range Cooling Min °CDB 10 10 10Max °CDB 46 46 46
Heating Min °CWB -15 -15 -15Max °CWB 20 20 20
Sound Level (nominal)
Cooling Sound Power dBA 60 60 62Sound Pressure (High)
dBA 46 46 48
Heating Sound Pressure (High)
dBA 47 47 48
Refrigerant Type R-410ACharge kg 0.74 0.74 1.0
2-1 Nominal Capacity and Nominal Input RX50G2V1B RX60G2V1B RX71GV1B
RX-JV-GV_EN.pdf 6 12/05/2010 8:21:49
• Split Sky Air • Outdoor Units 5
• Outdoor Units • R-410A • RX-JV/GV
2 Specifications
Refrigerant Oil Type FVC50KCharged Volume l 0.375 0.375 0.375
Piping connections Liquid (OD) Quantity 1 1 1Diameter (OD) mm 6.35 6.35 6.35
Gas Quantity 1 1 1Diameter (OD) mm 9.52 9.52 9.52
Drain Quantity 1 1 1Diameter (OD) mm 18 18 18
Piping Length Maximum m 15 15 15Additional Refrigerant Charge kg/m 0.02(>10m)Installation height difference
Maximum m 12 12 12
Heat Insulation Both liquid and gas pipesStandard Accessories
Item Installation manualQuantity 1 1 1Item Drain plugQuantity 1 1 1
Notes Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19.0°CWB; outdoor temperature: 35°CDB, 24°CWB, refr.pip.length: 5m
Nominal heating capacities are based on: indoor temperature: 20°CDB; outdoor temperature:
7°CDB, 6°CWB, refr.pip.length: 5m
Nominal heating capacities are based on: indoor
temperature:20°CDB, outdoor temperature:7°CDB, 6°CWB,
refr.pip. length 5m
Nominal heating capacities are based on: indoor temperature: 20°CDB; outdoor temperature:
7°CDB, 6°CWB, refr.pip.length: 5m
2-2 Technical Specifications RX50G2V1B RX60G2V1B RX71GV1B
Casing Colour Ivory whiteDimensions Unit Height mm 792 900
Width mm 960 925Depth mm 390
Packing Height mm 735 770Width mm 825 900Depth mm 300 320
Weight Unit kg 48 71Packed Unit kg 53 79
Heat Exchanger Dimensions Length mm 845 857Nr of Rows 2Fin Pitch mm 1.8 1.4Nr of Stages 32 34
Tube type ø8 Hi-XAFin Type Waffle fin
Treatment Anti-corrosion treatment (PE)Fan Type Propeller
Air Flow Rate Cooling (High) m³/min 48.9 50.9 54.5Cooling (Low) m³/min 41.7 42.4 46Cooling (High) cfm 1,727 1,797 1,924Cooling (Low) cfm 1,472 1,497 1,624Heating (High) m³/min 45 46.3 46Heating (Low) m³/min 41.7 42.4 46Heating (High) cfm 1,589 1,635 1,624Heating (Low) cfm 1,472 1,497 1,624
Motor Model KFD-380-50-8CMotor Speed (nominal) Cooling (Low) rpm 670 680 730
Cooling (High) rpm 780 810 860Heating (Low) rpm 670 680 730Heating (High) rpm 720 740 730
Fan Motor Output W 53 66
2-2 Technical Specifications RX20JV1B RX25JV1B RX35JV1B
RX-JV-GV_EN.pdf 7 12/05/2010 8:21:50
• Outdoor Units • R-410A • RX-JV/GV
• Split Sky Air • Outdoor Units6
2 Specifications
Compressor Motor Model 2YC36BXD#C 2YC63BXD#AType Hermetically sealed swing compressorMotor Output W 1,20 1,10 1,92
Operation Range Cooling Min °CDB -10Max °CDB 46
Heating Min °CWB -15Max °CWB 18
Sound Level (nominal)
Cooling Sound Power dBA 61 63 66Sound Pressure (High) dBA 47 49 52Sound Pressure (Low) dBA 44 46 49
Heating Sound Pressure (High) dBA 48 49 52Sound Pressure (Low) dBA 45 46 49
Refrigerant Type R-410ACharge kg 1.5
Refrigerant Oil Type FVC50KCharged Volume l 0.650 0.750
Piping connections Drain OD mm 18Gas OD mm 12.7 15.9Liquid OD mm 6.35Piping Length Maximum m 30
Chargeless m 10Additional Refrigerant Charge kg/m 0.020 (for piping length exceeding 10m)Heat Insulation Both liquid and gas pipes
Standard Accessories Drain socket1
Installation manual1
Notes Cooling: indoor temp. 27°CDB, 19.0°CWB; outdoor temp. 35°CDB, 24°CWB; equivalent piping length: 5m
Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 5mSL: The silent fan level of the air flow rate setting
220V;3;230V;4;240V
2-3 Electrical Specifications RX20JV1B RX25JV1B RX35JV1B
Power Supply Name V1Phase 1~Frequency Hz 50 50 50Voltage V 220-230-240
Current Nominal running current (RLA)
Cooling (A) A 2.52 3.52 5.02Heating (A) A 2.62 3.02 4.52
Starting current (cooling/heating) A 2.7 3.7 5.0Wiring connections For Power Supply Quantity 3 3 3
For connection with indoor
Quantity 4 4 4Remark Earth wire included
2-3 Electrical Specifications RX50G2V1B RX60G2V1B RX71GV1B
Power Supply Name V1Phase 1~Frequency Hz 50Voltage V 220-230-240
Current Nominal running current (RLA)
Cooling A 7.040 - 6.750 - 6.450 9.010 - 8.920 - 8.230 10.590 - 10.200 - 9.710Heating A 7.230 - 6.940 - 6.640 9.190 - 8.800 - 8.410 11.420 - 10.930 - 10.440
Wiring connections For Power Supply Quantity 3For connection with indoor
Remark Earth wire included
2-2 Technical Specifications RX50G2V1B RX60G2V1B RX71GV1B
RX-JV-GV_EN.pdf 8 12/05/2010 8:21:50
• Split Sky Air • Outdoor Units 7
• Outdoor Units • R-410A • RX-JV/GV
3 Electrical data
3D065911
NOTES
1. RLA is based on the following conditions.Indoor temp. 27°C DB/19°C WB.Outdoor temp. 35°C DB.
2. Maximum allowable voltage variation between phases is 2%.3. Select wire size based on the larger value of MCA.4. Instead of fuse, use circuit breaker.
RX20-35JV
Representative unit combination Power supply Comp OFM IFM
Indoor unit Outdoor unit Hz-Volts Voltage range MCA MFA RHz RLA W FLA W FLA
FTX20JV1B RX20JV1B50 - 220
Max. 50Hz 264VMin. 50Hz 198V 14.5 16 36 2.2 33 0.17 16 0.1250 - 230
50 - 240
FTX25JV1B RX25JV1B50 - 220
Max. 50Hz 264VMin. 50Hz 198V 14.5 16 48 3.2 33 0.17 16 0.1250 - 230
50 - 240
FTX35JV1B RX35JV1B50 - 220
Max. 50Hz 264VMin. 50Hz 198V 14.5 16 70 4.7 33 0.17 16 0.1250 - 230
50 - 240
SYMBOLS
MCA : Min. Circuit Amps (A)MFA : Max. Fuse Amps (A)RLA : Rated Load Amps (A)OFM : Outdoor Fan MotorIFM : Indoor Fan MotorFLA : Full Load Amps (A)W : Fan Motor Rated Output (W)RHz : Rated Operating Frequency (Hz)
RX-JV-GV_EN.pdf 9 12/05/2010 8:21:50
• Outdoor Units • R-410A • RX-JV/GV
• Split Sky Air • Outdoor Units8
4 Capacity tables4 - 1 Cooling/Heating capacity tables
RX-JV-GV_EN.pdf 10 12/05/2010 8:21:50
• Split Sky Air • Outdoor Units 9
• Outdoor Units • R-410A • RX-JV/GV
4 Capacity tables4 - 1 Cooling/Heating capacity tables
RX-JV-GV_EN.pdf 11 12/05/2010 8:21:50
• Outdoor Units • R-410A • RX-JV/GV
• Split Sky Air • Outdoor Units10
4 Capacity tables4 - 1 Cooling/Heating capacity tables
RX-JV-GV_EN.pdf 12 12/05/2010 8:21:50
• Split Sky Air • Outdoor Units 11
• Outdoor Units • R-410A • RX-JV/GV
4 Capacity tables4 - 1 Cooling/Heating capacity tablesFTX50GV1B+RX50G2V1B
3D051923C
Cooling 50Hz 220-240VAFR 14.7
BF 0.28
Indoor Outdoor temperature (°C DB)EWB EDB 20 25 30 32 35 40°C °C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14.016.018.019.022.024.0
202225273032
5.125.355.585.706.046.27
3.613.553.693.863.713.60
1.191.201.201.211.221.22
4.895.125.355.475.816.04
3.493.433.583.753.623.52
1.301.311.321.321.331.34
4.664.895.125.235.585.81
3.373.323.473.653.523.43
1.421.431.431.441.451.45
4.564.795.025.145.495.72
3.323.273.433.613.493.40
1.461.471.481.481.491.50
4.424.654.88
3.253.213.37
1.531.541.55
4.194.424.654.775.115.34
3.133.103.263.453.353.27
1.651.651.661.661.671.68
5.00 3.55 1.555.355.58
3.433.35
1.561.57
Heating 50Hz 220-240V AFR 16.1
Indoor Outdoor temperature (°C WB)EDB -10 -5 0 6 10°C TC PI TC PI TC PI TC PI TC PI
15.020.022.024.025.027.0
3.903.703.623.543.503.42
1.351.391.401.421.431.44
4.564.364.284.204.164.08
1.421.461.471.481.491.51
5.215.014.934.854.814.73
1.481.521.541.551.561.57
6.00 1.56 6.526.326.246.166.126.04
1.621.651.671.681.691.70
5.80 1.605.725.645.605.52
1.611.631.641.65
NOTES
1. Ratings shown are net capacities which include a deduction for indoor fan motor heat.
2. shows nominal (rated) capacities and power input.3. TC, PI and SHC must be calculated by interpolation using
the figures in the above tables. (Figures out of the tables should not be used for calculation.)
4. About SHC which are not mentioned on the table, please calculate them with around values in direct proportion.
5. Capacities are based on the following conditions.Corresponding refrigerant piping length : 7.5mLevel difference : 0m
6. Air flow rate (AFR) and Bypass factor (BF) are tabulated above table.
SYMBOLS
AFR : Air flow rate (m3/min.)BF : Bypass factorEWB : Entering wet bulb temp. (°C)EDB : Entering dry bulb temp. (°C)TC : Total capacity (kW)SHC : Sensible heat capacity (kW)PI : Power input (kW)
RX-JV-GV_EN.pdf 13 12/05/2010 8:21:50
• Outdoor Units • R-410A • RX-JV/GV
• Split Sky Air • Outdoor Units12
4 Capacity tables4 - 1 Cooling/Heating capacity tables
FTX60GV1B+RX60G2V1B
3D051924E
Cooling 50Hz 220-240VAFR 16.2
BF 0.29
Indoor Outdoor temperature (°C DB)EWB EDB 20 25 30 32 35 40°C °C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14.016.018.019.022.024.0
202225273032
5.606.426.706.847.257.53
3.944.174.314.494.314.18
1.491.541.541.551.561.57
5.606.146.426.566.977.25
3.944.024.174.364.194.07
1.661.681.691.701.711.72
5.595.866.146.286.696.97
3.943.884.044.234.083.97
1.821.831.841.841.861.86
5.485.756.036.176.586.86
3.883.823.994.184.043.93
1.881.891.901.901.911.92
5.315.595.86
3.793.743.91
1.971.981.99
5.035.315.585.726.146.41
3.643.603.783.983.863.77
2.122.122.132.142.152.16
6.00 4.10 1.996.416.69
3.973.87
2.002.01
Heating 50Hz 220-240V AFR 17.4
Indoor Outdoor temperature (°C WB)EDB -10 -5 0 6 10°C TC PI TC PI TC PI TC PI TC PI
15.020.022.024.025.027.0
4.714.474.374.284.234.13
1.731.771.791.811.821.84
5.505.265.165.075.024.92
1.811.861.871.891.901.92
6.296.055.955.865.815.71
1.891.941.961.981.992.00
7.24 1.99 7.877.637.547.447.397.29
2.062.112.132.142.152.17
7.00 2.046.906.816.766.66
2.062.082.092.10
NOTES
1. Ratings shown are net capacities which include a deduction for indoor fan motor heat.
2. shows nominal (rated) capacities and power input.3. TC, PI and SHC must be calculated by interpolation using
the figures in the above tables. (Figures out of the tables should not be used for calculation.)
4. About SHC which are not mentioned on the table, please calculate them with around values in direct proportion.
5. Capacities are based on the following conditions.(1) Corresponding refrigerant piping length : 7.5m(2) Level difference : 0m
6. Air flow rate (AFR) and Bypass factor (BF) are tabulated above table.
SYMBOLS
AFR : Air flow rate (m3/min.)BF : Bypass factorEWB : Entering wet bulb temp. (°C)EDB : Entering dry bulb temp. (°C)TC : Total capacity (kW)SHC : Sensible heat capacity (kW)PI : Power input (kW)
RX-JV-GV_EN.pdf 14 12/05/2010 8:21:50
• Split Sky Air • Outdoor Units 13
• Outdoor Units • R-410A • RX-JV/GV
4 Capacity tables4 - 1 Cooling/Heating capacity tables
FTX71GV1B+RX71GV1B
3D056030C
Cooling 50Hz 220-240VAFR 17.4
BF 0.30
Indoor Outdoor temperature (°C DB)EWB EDB 20 25 30 32 35 40°C °C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14.016.018.019.022.024.0
202225273032
5.937.287.938.098.588.91
4.184.674.985.164.954.79
1.641.781.821.831.841.85
5.937.277.607.768.258.58
4.184.664.815.004.814.66
1.861.992.002.002.022.03
5.936.947.277.437.928.25
4.184.484.654.844.674.53
2.072.162.172.182.192.20
5.936.817.137.307.798.12
4.184.414.584.784.614.48
2.162.232.242.252.262.27
5.936.616.94
4.184.314.48
2.292.332.34
5.936.286.616.777.267.59
4.184.144.334.534.394.28
2.502.512.522.522.542.55
7.10 4.69 2.357.597.92
4.534.40
2.372.38
Heating 50Hz 220-240V AFR 19.7
Indoor Outdoor temperature (°C WB)EDB -10 -5 0 6 10°C TC PI TC PI TC PI TC PI TC PI
15.020.022.024.025.027.0
5.525.245.125.014.954.84
2.162.212.242.262.272.29
6.456.166.055.945.885.77
2.262.322.342.362.382.40
7.377.096.986.866.816.69
2.372.422.452.472.482.50
8.48 2.49 9.228.948.838.718.477.92
2.582.632.662.682.682.68
8.20 2.558.097.977.927.80
2.572.602.612.63
NOTES
1. Capacities are based on the following conditions.(1) Corresponding refrigerant piping length : 7.5m(2) Level difference : 0m
2. shows nominal (rated) capacities and power input.
SYMBOLS
AFR : Air flow rate (m3/min.)BF : Bypass factorEWB : Entering wet bulb temp. (°C)EDB : Entering dry bulb temp. (°C)TC : Total capacity (kW)SHC : Sensible heat capacity (kW)PI : Power input (kW)
RX-JV-GV_EN.pdf 15 12/05/2010 8:21:51
• Outdoor Units • R-410A • RX-JV/GV
• Split Sky Air • Outdoor Units14
5 Dimensional drawing & centre of gravity5 - 1 Dimensional drawingRX20-35JV
3D058472A
MINIMUM SPACE FOR AIR PASSAGE
Drain outlet( I, D ø 15.9 hose for connectionwith drain joint [option] )
4-holes for anchor bolts( M8 or M10 )
Brand name labelHandle Manufacture’s label
Caution label
In case of removingstop valve cover
Wiringinlet
Serviceport
Outdoor air thermistor
Wall height on air outlet side = less than 1200
Gas stop valve(ø 9.5 cut)
Liquidstop valve(ø 6.4 cut)
RX50-60G
3D051657P
Drain outlet(I.D. ø15.9 hose for connection)
Brand name label
Minimum space for air passage
Outdoor air temperature thermistorWiring inlet Terminal strip with
earth terminal
Name plateIn case of removing
stop valve cover
Liquid stop valve (ø6.4CuT)
Gas stop valve (ø12.7CuT)Service port
4–Holes for anchor bolts(M8 or M10)
Wall height on air outlet side= less than 1200
RX-JV-GV_EN.pdf 16 12/05/2010 8:21:51
• Split Sky Air • Outdoor Units 15
• Outdoor Units • R-410A • RX-JV/GV
5 Dimensional drawing & centre of gravity5 - 1 Dimensional drawing
RX-JV-GV_EN.pdf 17 12/05/2010 8:21:51
• Outdoor Units • R-410A • RX-JV/GV
• Split Sky Air • Outdoor Units16
5 Dimensional drawing & centre of gravity5 - 2 Centre of gravityRX20-25JV
4D058111C
RX35JV
4D058147C
RX-JV-GV_EN.pdf 18 12/05/2010 8:21:51
• Split Sky Air • Outdoor Units 17
• Outdoor Units • R-410A • RX-JV/GV
5 Dimensional drawing & centre of gravity5 - 2 Centre of gravityRX50-60GV
4D051638P
The position of foundation bolt
RX71GV
4D053630D
Position of anchor bolt
RX-JV-GV_EN.pdf 19 12/05/2010 8:21:51
• Outdoor Units • R-410A • RX-JV/GV
• Split Sky Air • Outdoor Units18
6 Piping diagram
Heat exchangerthermistor
Outdoor temperature thermistorHeat exchanger
OUTDOOR UNITRX20-25JV
3D058716B
Compressor
Discharge pipe thermistor
ON: Heating
Heating
RX35JV
3D058714B
Heat exchangerthermistor
Outdoor temperature thermistorHeat exchanger
OUTDOOR UNIT
Compressor
Discharge pipe thermistor
Four way
ON: Heating
Heating
RX-JV-GV_EN.pdf 20 12/05/2010 8:21:52
• Split Sky Air • Outdoor Units 19
• Outdoor Units • R-410A • RX-JV/GV
6 Piping diagram
RX50-60G
3D051637Q
Heat exchanger
Capillary tube 1
Capillary tube 4
Capillary tube 2 Capillary tube 3
Outdoor unit7.9CuT7.9CuT7.9CuT7.9CuT7.9CuT7.9CuT7.9CuT7.9CuT
12.7CuT
12.7CuT 9.5CuT
7.9CuT
7.9CuT
Muffler
Muffler
7.9CuT
12.7CuT
6.4CuT
7.9CuT
4.0CuT
7.9CuT
4.0CuT
4.0CuT4.0CuT
12.7CuT
(6.4CuT)
(12.7CuT)
Heatexchangerthermistor
Propeller fan
Compressor
Discharge pipe thermistor
Muffler withfilter
Liquidstop valve
Gas stop valve with service port
Field piping
Field piping
Motor operated valve
Filter
Receiver
Muffler
Four way valve on:heating
Outdoor air temperature thermistor
Refrigerant flowCoolingHeating
6.4Cu
T6.4
CuT
6.4Cu
T
9.5Cu
T 6.4CuT
12.7C
uT
RX71GV
3D054593F
Heat exchanger
Receiver
Outdoor unit
7.9CuT7.9CuT7.9CuT7.9CuT7.9CuT7.9CuT7.9CuT7.9CuT
4.0CuT
7.9CuT
9.5CuT
9.5CuT 9.5CuT 9.5CuT 9.5CuT 9.5CuT
12.7C
uT
Liquid
line
stop v
alve
liquid (6.4CuT)
gas (15.9CuT)15.9CuT15.9CuT
15.9CuT
7.9CuT7.9CuT
15.9CuT15.9CuT
15.9C
uT15.9C
uT
7.9Cu
T
Propeller fan
DC fan motor
Header
Motoroperated
valve
Gas linestop valve
Field piping
Field piping
FilterFilterDistributor
Capillary tube
AccumulatorAccumulator
Compressor
Muffler
Discharge pipe thermistor
4-way valveon: heating
Outdoor temperature thermistor
Heat exchanger (condenser) thermistor
Refrigerant flowCoolingHeating
9.5Cu
T9.5
CuT
RX-JV-GV_EN.pdf 21 12/05/2010 8:21:52
• Outdoor Units • R-410A • RX-JV/GV
• Split Sky Air • Outdoor Units20
7 Wiring diagram7 - 1 Wiring diagram
RX-JV-GV_EN.pdf 22 12/05/2010 8:21:53
• Split Sky Air • Outdoor Units 21
• Outdoor Units • R-410A • RX-JV/GV
7 Wiring diagram7 - 1 Wiring diagramRX50G
3D056095C
Z1C~Z5C Ferrite core LEDA Pilot lampX1M, X2M Terminal strip L LiveY1E Electronic expansion valve coil N NeutralV2, V3, V5, V6, V11 Varistor SW1 Forced operation ON/OFF SW (SW1)SA2 Surge arrester SW4 Local setting SW (SW4)FU1, FU2, FU3 Fuse M1C Compressor motorAC1, AC2 M1F Fan motorU, V, W, X11A, X12A L1R ReactorE1, E2 Q1L Overload protectorHR1, HR2 Connector PM1 Power moduleMRM10, MRM20 PCB1, 2 Printed circuit boardMRC/W Magnetic relay Y1R Reversing solenoid valve coilR1T~R3T Thermistor Sheet metal Terminal strip fixed plateS2~S102 Connector
Field wiring
Powersupply
To indoor unit
indoor
LED A
Sheetmetal
(outdoor) (discharge)(condenser)
Outdoor
RX-JV-GV_EN.pdf 23 12/05/2010 8:21:53
• Outdoor Units • R-410A • RX-JV/GV
• Split Sky Air • Outdoor Units22
7 Wiring diagram7 - 1 Wiring diagramRX60G
3D050706K
Z1C~Z4C Ferrite core LEDA Pilot lampX1M, X2M Terminal strip L LiveY1E Electronic expansion valve coil N NeutralV2, V3, V5, V6, V11 Varistor SW1 Forced operation ON/OFF SW (SW1)SA2 Surge arrester SW4 Local setting SW (SW4)FU1, FU2, FU3 Fuse M1C Compressor motorAC1, AC2 M1F Fan motorU, V, W, X11A L1R ReactorE1, E2 Q1L Overload protectorHR1, HR2 Connector PM1 Power moduleMRM10, MRM20 PCB1, 2 Printed circuit boardMRC/W Magnetic relay Y1R Reversing solenoid valve coilR1T~R3T Thermistor Sheet metal Terminal strip fixed plateS2~S102 Connector
Field wiring
Powersupply
To indoor unit
indoor
LED A
Sheetmetal
(outdoor) (discharge)(condenser)
Outdoor
RX-JV-GV_EN.pdf 24 12/05/2010 8:21:53
• Split Sky Air • Outdoor Units 23
• Outdoor Units • R-410A • RX-JV/GV
7 Wiring diagram7 - 1 Wiring diagramRX71GV
3D053931J
Z1C~Z7C Ferrite core LEDA Pilot lampX1M, X2M Terminal strip L LiveY1E Electronic expansion valve coil N NeutralV2, V3, V5, V9, V100 Varistor SW1 Forced operation ON/OFF SW (SW1)SA2 Surge arrester SW4 Local setting SW (SW4)FU1, FU2, FU3 Fuse M1C Compressor motorAC1, AC2 M1F Fan motorU, V, W, X11A, X12A L1R ReactorE1, E2 Q1L Overload protectorHR1, HR2 Connector PM1 Power moduleMRM10, MRM20 PCB1, 2 Printed circuit boardMRC/W Magnetic relay Y1R Reversing solenoid valve coilR1T~R3T Thermistor Sheet metal Terminal strip fixed plateS2~S102 Connector
Field wiring
Powersupply
To indoor unit
indoor
LED A
Sheetmetal
(outdoor) (discharge)(condenser)
Outdoor
RX-JV-GV_EN.pdf 25 12/05/2010 8:21:53
• Outdoor Units • R-410A • RX-JV/GV
• Split Sky Air • Outdoor Units24
8 Sound data8 - 1 Sound pressure spectrum
NOTES
1 Over All (dB):(B,G,N is already rectified)
2 Measuring place: measure in anechoic room.3 Operation noise differs with operation and ambient conditions.4 Location of microphone.
JISC9612The operation noise measuring method is in accordance with JISC9612
RX20JV
3D059002A
NOTES
1 Over All (dB):(B,G,N is already rectified)
2 Measuring place: measure in anechoic room.3 Operation noise differs with operation and ambient conditions.4 Location of microphone.
JISC9612The operation noise measuring method is in accordance with JISC9612
Octav
e ban
d sou
nd pr
essu
re le
vel d
B (0
dB =
0.00
02μ
bar)
Octav
e ban
d sou
nd pr
essu
re le
vel d
B (0
dB =
0.00
02μ
bar)
Octave band center frequency - IEC (Hz) Octave band center frequency - IEC (Hz)
Scale 50Hz230v (H)
A 46
Scale 50Hz230v (H)
A 47
Approximatethreshold hearing for continuous noise
Approximatethreshold hearing for continuous noise
Cooling Heating
1m 1m
NOTES
1 Over All (dB):(B,G,N is already rectified)
2 Measuring place: measure in anechoic room.3 Operation noise differs with operation and ambient conditions.4 Location of microphone.
JISC9612The operation noise measuring method is in accordance with JISC9612
RX25JV
3D059003A
NOTES
1 Over All (dB):(B,G,N is already rectified)
2 Measuring place: measure in anechoic room.3 Operation noise differs with operation and ambient conditions.4 Location of microphone.
JISC9612The operation noise measuring method is in accordance with JISC9612
Octav
e ban
d sou
nd pr
essu
re le
vel d
B (0
dB =
0.00
02μ
bar)
Octav
e ban
d sou
nd pr
essu
re le
vel d
B (0
dB =
0.00
02μ
bar)
Octave band center frequency - IEC (Hz) Octave band center frequency - IEC (Hz)
Scale 50Hz230v (H)
A 46
Scale 50Hz230v (H)
A 47
Approximatethreshold hearing for continuous noise
Approximatethreshold hearing for continuous noise
Cooling Heating
1m 1m
RX-JV-GV_EN.pdf 26 12/05/2010 8:21:54
• Split Sky Air • Outdoor Units 25
• Outdoor Units • R-410A • RX-JV/GV
8 Sound data8 - 1 Sound pressure spectrumRX35JV
3D059004A
NOTES
1 Over All (dB):(B,G,N is already rectified)
2 Measuring place: measure in anechoic room.3 Operation noise differs with operation and ambient conditions.4 Location of microphone.
JISC9612The operation noise measuring method is in accordance with JISC9612
NOTES
1 Over All (dB):(B,G,N is already rectified)
2 Measuring place: measure in anechoic room.3 Operation noise differs with operation and ambient conditions.4 Location of microphone.
JISC9612The operation noise measuring method is in accordance with JISC9612
Octav
e ban
d sou
nd pr
essu
re le
vel d
B (0
dB =
0.00
02μ
bar)
Octav
e ban
d sou
nd pr
essu
re le
vel d
B (0
dB =
0.00
02μ
bar)
Octave band center frequency - IEC (Hz) Octave band center frequency - IEC (Hz)
Scale 50Hz230V (H)
A 48
Scale 50Hz230V (H)
A 48
Approximatethreshold hearing for continuous noise
Approximatethreshold hearing for continuous noise
Cooling Heating
RX50G
3D051717D
NOTES
1 Over All (dB):(B,G,N is already rectified)
2 Measuring place: measured in an echoic room.3 Operation noise differs with operation and ambient conditions.4 Location of microphone.
JIS C 9612The operation noise measuring method is in accordance with JIS C 9612
NOTES
1 Over All (dB):(B,G,N is already rectified)
2 Operation noise differs with operation and ambient conditions.
Octav
e ban
d sou
nd pr
essu
re le
vel d
B (0
dB =
0.00
02μ
bar)
Octav
e ban
d sou
nd pr
essu
re le
vel d
B (0
dB =
0.00
02μ
bar)
Octave band center frequency - IEC (Hz) Octave band center frequency - IEC (Hz)
Scale 50Hz220~240V
A 47
Scale 50Hz220~240V
A 48
Approximatethreshold hearing for continuous noise
Approximatethreshold hearing for continuous noise
Cooling Heating
RX-JV-GV_EN.pdf 27 12/05/2010 8:21:54
• Outdoor Units • R-410A • RX-JV/GV
• Split Sky Air • Outdoor Units26
8 Sound data8 - 1 Sound pressure spectrumRX60G
3D051716D
NOTES
1 Over All (dB):(B,G,N is already rectified)
2 Measuring place: measured in an echoic room.3 Operation noise differs with operation and ambient conditions.4 Location of microphone.
JIS C 9612The operation noise measuring method is in accordance with JIS C 9612
NOTES
1 Over All (dB):(B,G,N is already rectified)
2 Operation noise differs with operation and ambient conditions.
Octav
e ban
d sou
nd pr
essu
re le
vel d
B (0
dB =
0.00
02μ
bar)
Octav
e ban
d sou
nd pr
essu
re le
vel d
B (0
dB =
0.00
02μ
bar)
Octave band center frequency - IEC (Hz) Octave band center frequency - IEC (Hz)
Scale 50Hz220~240V
A 49
Scale 50Hz220~240V
A 49
Approximatethreshold hearing for continuous noise
Approximatethreshold hearing for continuous noise
Cooling Heating
RX71GV
3D055789B
NOTES
1 Over All (dB):(B,G,N is already rectified)
2 Measuring place: measured in an anechoic room.3 Operation noise differs with operation and ambient conditions.4 Location of microphone.
JISC9612The operation noise measuring method is in accordance with JISC9612
NOTES
1 Over All (dB):(B,G,N is already rectified)
2 Operation noise differs with operation and ambient conditions.
Octav
e ban
d sou
nd pr
essu
re le
vel d
B (0
dB =
0.00
02μ
bar)
Octav
e ban
d sou
nd pr
essu
re le
vel d
B (0
dB =
0.00
02μ
bar)
Octave band center frequency - IEC (Hz) Octave band center frequency - IEC (Hz)
Scale 50Hz220~240V
A 52
Scale 50Hz220~240V
A 52
Approximatethreshold hearing for continuous noise
Approximatethreshold hearing for continuous noise
Cooling Heating
RX-JV-GV_EN.pdf 28 12/05/2010 8:21:54
• Split Sky Air • Outdoor Units 27
• Outdoor Units • R-410A • RX-JV/GV
9 Operation range
RX20-35JV
3D058975A
NOTES
The graphs are based on the following conditions.Equivalent piping length 5mLevel difference 0m
Outdo
or te
mp. (
°C D
B)
Conti
nuou
s ope
ratio
n
Conti
nuou
s ope
ratio
n
Pull-d
own p
eriod
Indoor temp. (°C WB)
Indoor temp. (°C DB)
Cooling
(-15°C DB)
Outdo
or te
mp. (
°C W
B)
RX50-60G
RX71GV
NOTES
The graphs are based on the following conditions.– Equivalent piping length 7.5m– Level difference 0m– Air flow rate High
HeatingCooling
Indoor temp. (°C WB)Indoor temp. (°C DB)
(-15°C DB)
Conti
nuou
s ope
ratio
n
Conti
nuou
s ope
ratio
n
Pull-d
own p
eriod
Outdo
or te
mp. (
°C D
B)
Outdo
or te
mp. (
°C W
B)
3D028318P
RX-JV-GV_EN.pdf 29 12/05/2010 8:21:55
Naamloze Vennootschap - Zandvoordestraat 300, B-8400 Oostende - Belgium - www.daikin.eu - BE 0412 120 336 - RPR Oostende
Daikin’s unique position as a manufacturer of air
conditioning equipment, compressors and refrigerants
has led to its close involvement in environmental issues.
For several years Daikin has had the intention to become
a leader in the provision of products that have limited
impact on the environment. This challenge demands the
eco design and development of a wide range of products
and an energy management system, resulting in energy
conservation and a reduction of waste.
Daikin Europe N.V. is participating in the EUROVENT
Certification Programme. Products are as listed in the
EUROVENT Directory of Certified Products.
Daikin products are distributed by:
EE
DE
N1
0-1
00
• C
D •
05
/10
• C
op
yri
gh
t D
aik
in
Th
e p
rese
nt
pu
blic
ati
on
su
pe
rse
de
s E
ED
EN
09
-10
0
Pre
par
ed
in B
elg
ium
by
Lan
no
o (
ww
w.la
nn
oo
pri
nt.
be
), a
com
pan
y w
ho
se c
on
cern
for
the
en
viro
nm
en
t is
se
t in
th
e E
MA
S an
d IS
O 1
40
01
sys
tem
s.
Re
spo
nsi
ble
Ed
ito
r: D
aik
in E
uro
pe
N.V
., Z
an
dv
oo
rde
stra
at
30
0,
B-8
40
0 O
ost
en
de
The present publication is drawn up by way of information only and does not constitute an offer binding
upon Daikin Europe N.V.. Daikin Europe N.V. has compiled the content of this publication to the best of its
knowledge. No express or implied warranty is given for the completeness, accuracy, reliability or fitness for
particular purpose of its content and the products and services presented therein. Specifications are subject
to change without prior notice. Daikin Europe N.V. explicitly rejects any liability for any direct or indirect
damage, in the broadest sense, arising from or related to the use and/or interpretation of this publication. All
content is copyrighted by Daikin Europe N.V..