APRIL 2006 OHIO BRASS – AIKEN, SC ® Printed in USA Section 35 Affordable Surge Protection for Superior Transmission and Distribution System Reliability Web: http://www.hubbellpowersystems.com E-mail: [email protected] © Copyright 2006 Hubbell/Ohio Brass NOTE: Because Hubbell has a policy of continuous product improvement, we reserve the right to change design and specifications without notice. ®
20

Affordable Surge Protection for Superior Transmission and ... · cause of arrester failure. ... If a surge related flashover occurs on a line and ... As long as the surge voltage

Apr 19, 2018

Download

Documents

duongxuyen
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Affordable Surge Protection for Superior Transmission and ... · cause of arrester failure. ... If a surge related flashover occurs on a line and ... As long as the surge voltage

APRIL 2006

35-�

OHIO BRASS – AIKEN, SC

®

Printed in USA

Section

35

Affordable Surge Protection for SuperiorTransmission and Distribution System Reliability

Web: http://www.hubbellpowersystems.comE-mail: [email protected]

©Copyright 2006 Hubbell/Ohio Brass

NOTE: Because Hubbell has a policy of continuous product improvement, we reserve the right to change design and specifications without notice.

®

Page 2: Affordable Surge Protection for Superior Transmission and ... · cause of arrester failure. ... If a surge related flashover occurs on a line and ... As long as the surge voltage

APRIL 2006 - REV 6/06 OHIO BRASS – AIKEN, SC

35-�®

Protecta*Lite® INDEX

Page

Introduction ................................................................................................ 3

PROTECTA*LITE Benefits .......................................................................4-5

System Reliability Improvements ............................................................... 6

PROTECTA*LITE Basics ............................................................................. 7

PROTECTA*LITE Selection Step 1 ..........................................................8-9

PROTECTA*LITE Selection Step 2 ......................................................10-11

PROTECTA*LITE Selection Step 3 ......................................................12-17

Catalog Number Composition ..................................................................18

Disconnectors & TOV Performance .........................................................19

Facts & Warranty Information ...................................................................20

©Copyright 2006 Hubbell/Ohio Brass

NOTE: Because Hubbell has a policy of continuous product improvement, we reserve the right to change design and specifications without notice.

Warranty - MaterialHubbell Power Systems, Inc. warrants all products sold by it to be merchantable (as such term is defined in the Uniform Commercial Code) and to be free from defects in material and workmanship. Buyer must notify the Company promptly of any claim under this warranty. The Buyer's exclusive remedy for breach of this warranty shall be the repair or replacement, F.O.B. factory, at the Company's option, of any product defective under the warranty which is returned to the Company within one year from the date of shipment. NO OTHER WARRANTY, WHETHER EXPRESS OR ARISING BY OPERATION OF LAW, COURSE OF DEALING, USAGE OF TRADE OR OTHERWISE IMPLIED, SHALL EXIST IN CONNECTION WITH THE COMPANY'S PRODUCTS OR ANY SALE OR USE THEREOF. The Company shall in no event be liable for any loss of profits or any consequential or special damages incurred by Buyer. The Company's warranty shall run only to the first Buyer of a product from the Company, from the Company's distributor, or from an original equipment manufacturer reselling the Company's product, and is non-assignable and non-transferable and shall be of no force and effect if asserted by any person other than such first Buyer. This warranty applies only to the use of the product as intended by Seller and does not cover any misapplication or misuse of said product.

Warranty - ApplicationHubbell Power Systems, Inc. does not warrant the accuracy of and results from product or system performance recommendations resulting from any engineering analysis or study. This applies regardless of whether a charge is made for the recommendation, or if it is provided free of charge.

Responsibility for selection of the proper product or application rests solely with the purchaser. In the event of errors or inaccuracies determined to be caused by Hubbell Power Systems, Inc. , its liability will be limited to the re-performance of any such analysis or study.

Page 3: Affordable Surge Protection for Superior Transmission and ... · cause of arrester failure. ... If a surge related flashover occurs on a line and ... As long as the surge voltage

APRIL 2006

35-3

OHIO BRASS – AIKEN, SC

®

The Driving Force for PROTECTA*LITE® Systems

In today’s competitive market, power is always in demand. Even the slightest interruption can cost millions of dollars to both you and your custom-ers. Attempts to improve power quality through new line construction can be met with the all too common customer response “not in my back-yard.”

If this is not enough, the need to construct aes-thetically pleasing compact lines that will not adversely impact the landscape can sometimes interfere with a utility‘s ability to effectively shield lines from lightning surges.

Even though these problems may seem complex, Ohio Brass has developed one simple solution that can achieve your surge protection needs for both transmission and distribution lines.

Whether you are interested in upgrades or new line construction, Ohio Brass can build a PROTECTA*LITE system that meets your surge protection needs.

Page 4: Affordable Surge Protection for Superior Transmission and ... · cause of arrester failure. ... If a surge related flashover occurs on a line and ... As long as the surge voltage

APRIL 2006 - REV 6/06 OHIO BRASS – AIKEN, SC

35-�®

The Benefits of the PROTECTA*LITE® System

SYSTEM PROTECTION

Protects line insulation from flashover due to lightning strikes.

When applied at the entrance of a substation, PROTECTA*LITE protects substation equip-ment from lightning surges.

PROTECTA*LITE prevents back-flashovers of lines resulting from poor system grounding.

COMPACT LINE DESIGN

By analyzing the characteristics of your line, Ohio Brass can supply a PROTECTA*LITE system that protects lines from lightning surges without the use of costly and visually unappeal-ing overhead shield wire systems.

PROTECTA*LITE systems help to realize com-pact line designs with ease.

With PROTECTA*LITE, utilities can upgrade lines to higher system voltages without costly insulator change outs requiring more space and possible pole upgrades.

Page 5: Affordable Surge Protection for Superior Transmission and ... · cause of arrester failure. ... If a surge related flashover occurs on a line and ... As long as the surge voltage

APRIL 2006

35-5

OHIO BRASS – AIKEN, SC

®

Additional Benefits of the PROTECTA*LITE® System

PROTECTA*LITE has a lower continuous power loss than any competitive product in the same class.

Reduce RFI/TVI complaints by utilizing PROTECTA*LITE systems.

PROTECTA*LITE arresters are the lowest weight solution for surge protection. This re-duces line loading and possible mishandling during installation.

PROTECTA*LITE can be supplied to fit your system using Ohio Brass insulators and ar-resters.

PROTECTA*LITE does not affect line per-formance when faced with adverse wind and ice conditions.

Testing and 20 years of field experience have demonstrated the PROTECTA*LITE polymer housing is highly resistant to track-ing and other environmental damage.

The PROTECTA*LITE design is highly resis-tant to moisture ingress, which is a leading cause of arrester failure.

Page 6: Affordable Surge Protection for Superior Transmission and ... · cause of arrester failure. ... If a surge related flashover occurs on a line and ... As long as the surge voltage

APRIL 2006 - REV 6/06 OHIO BRASS – AIKEN, SC

35-�®

Here’s what the PROTECTA*LITE® System does for Your System Reliability1

REDUCED RELIABILITY INDICATORS

Utilizing PROTECTA*LITE on transmission and distribution lines can help eliminate SAIDI (CMI, CMO), SAIFI, MAIDI, and MAIFI related to light-ning surges1.

PROTECTA*LITE quickly helps stamp out light-ning surges without the occurrence of nuisance breaker operations that increase MAIFI and MAIDI.

If a surge related flashover occurs on a line and a substation interrupter/breaker fails to oper-ate, the line can be damaged. The ensuing outage can result in the accumulation of SAIDI and SAIFI until power can be re-routed through switching or the line is fixed. PROTECTA*LITE helps present flashover due to lighting surges. Thus, with PROTECTA*LITE, SAIDI or SAIFI related to lightning surges should be reduced or effectively eliminated.

At Ohio Brass, we understand how important system reliability is, so we continually strive to provide you with the best surge protection available. If you have questions, please contact us

at [email protected].

1 Reliability is often expressed in terms of SAIDI (CMI, CMO), SAIFI, MAIDI, and MAIFI. SAIDI – System Average Interruption Duration Index SAIFI – System Average Interruption Frequency Index MAIDI – Momentary Average Interruption Duration Index MAIFI – Momentary Average Interruption Frequency Index

Page 7: Affordable Surge Protection for Superior Transmission and ... · cause of arrester failure. ... If a surge related flashover occurs on a line and ... As long as the surge voltage

APRIL 2006

35-�

OHIO BRASS – AIKEN, SC

®

The theory behind PROTECTA*LITE systems is state of the art. It consists of a special metal-oxide surge arrester in parallel with line insulation.

During a surge, the metal-oxide arrester limits the voltage across the insulation to a value below the insulator flashover voltage. Therefore, the lightning surge current is diverted to ground in a controlled manner and the insulation is left intact. The system works for direct lightning strokes to phase conductors and for backflash attributed to poor grounding and capacitive coupling.

PROTECTA*LITE systems utilize, only the highest quality Metal-Oxide Varistors (MOV) combined with durable, time proven polymer housings.

Since 1988, PROTECTA*LITE systems have reduced interruptions at system voltages from

Cutaway View of Typical Polymer Arrester Module

Stainless SteelTerminal Stud

Stamped Stainless Steel Name-plate

Alloy EP Rubber Housing

Metal Oxide Varistor

Epoxy-Fiberglass Wrap

Metal Oxide Varistor

Live Silicone Interface

Belleville Washer

End Terminal

PROTECTA*LITE® Basics

2.4 to 400 kV. Higher voltage PROTECTA*LITE systems are available.

PROTECTA*LITE systems are available as an assemblies of polymer insulators and arrest-ers, or as an arrester alone. Construction with a PROTECTA*LITE assembly brings with it many advantages and configurations.

PROTECTA*LITE design test reports can be found at: http://www.hubbellpowersystems.com

Click on the yellow Literature Tab, scroll down, and pick the Design Test Reports # EU1290-H link. Pick report .

The next few pages demonstrate three easy steps for specifying the PROTECTA*LITE system that is right for you.

Sectional View of PROTECTA*LITE Arrester

Page 8: Affordable Surge Protection for Superior Transmission and ... · cause of arrester failure. ... If a surge related flashover occurs on a line and ... As long as the surge voltage

APRIL 2006 - REV 6/06 OHIO BRASS – AIKEN, SC

35-�®

STEP 1 For Selecting the Right PROTECTA*LITE® SystemFirst select the correct Maximum Continuous Operating Voltage (MCOV1) for your arrester. Below is a selection guide with the appropriate arrester MCOV for some common system voltages (line to line). This chart also provides the best choice for MCOV based on grounding considerations. All voltage values are expressed in RMS terms.

System Voltage kVSuggested Arrester MCOV (COV)

Effectively Grounded Neutral Circuit

Impedance Grounded or UngroundedNominal Maximum

2.40 2.52 2.55 2.554.16 4.37 2.55 5.104.80 5.04 5.10 5.106.90 7.25 5.10 7.658.32 8.74 5.10 8.4012.00 12.60 7.65 17.0012.47 13.10 7.65 17.0013.20 13.90 8.40 17.0013.80 14.50 8.40 17.0020.78 21.80 12.70 22.0022.86 24.00 15.30 22.0023.00 24.20 15.30 22.0024.94 26.20 15.30 24.0034.50 36.20 22.00 36.5046.00 48.30 29.00 48.0069.00 72.50 42.00 70.00115.00 121.00 70.00 115.00138.00 145.00 84.00 131.00161.00 169.00 98.00 152.00230.00 242.00 140.00 220.00

For higher system voltages, please contact your Hubbell representative for the PROTECTA*LITE application that is right for you.

For effectively grounded systems, the MCOV selected is usually the maximum line to ground voltage of the system. For impedance grounded or ungrounded lines, an arrester MCOV that is closer to 90% of the system voltage should be selected. If your system voltage is not present on this chart, please contact your Hubbell representative.

1 MCOV is also referred to as UC or COV (Continuous Operating Voltage).

Page 9: Affordable Surge Protection for Superior Transmission and ... · cause of arrester failure. ... If a surge related flashover occurs on a line and ... As long as the surge voltage

APRIL 2006

35-�

OHIO BRASS – AIKEN, SC

®

MCOV(kV)

Leakage Distance(in / mm)

Arrester Weight(lbs / kg)

8.4 15.4 / 391 3 / 1.36 17.0 30.8 / 782 6 / 2.72 24.4 46.2 / 1174 9 / 4.08 31.5 61.6 / 1565 12 / 5.44 42.0 77.0 / 1956 15 / 6.80 48.0 92.4 / 2347 18 / 8.16 57.0 107.8 / 2738 21 / 9.53 76.0 138.6 / 3520 27 / 12.25 84.0 154.0 / 3912 30 / 13.61 98.0 184.8 / 4694 36 / 16.33 106.0 200.2 / 5085 39 / 17.69 115.0 215.6 / 5476 42 / 19.05 131.0 246.4 / 6259 48 / 21.77 140.0 261.8 / 6650 51 / 23.13 144.0 277.2 / 7041 54 / 24.49

PROTECTA*LITE® System works by limiting the voltage of a surge below the flashover volt-age of the insulators on your system. As long as the surge voltage is maintained below the flashover voltage of your insulation, the system is unaffected by surges. Below is a listing of the average voltage rise observed when a PROTECTA*LITE System is struck by a fast front (0.5 µs; 10 kA) lightning surge, standard lightning surge (8/20 µs) of varying currents, and a long duration (45 µs) switching surge.

MCOVkV

0.5 µs10 kA (kV)

8/20 µs Maximum Discharge Voltage (kV) 45 µsSS(kV)1.5 kA 3 kA 5 kA 10 kA 20 kA 40 kA

8.4 36.5 26.0 28.0 29.5 32.0 37.5 43.5 23.5 17.0 73.0 52.0 56.0 59.0 64.0 75.0 87.0 47.0 24.4 109.5 78.0 84.0 88.5 96.0 112.5 130.5 70.5 31.5 146.0 104.0 112.0 118.0 128.0 150.0 174.0 94.0 42.0 182.5 130.0 140.0 147.5 160.0 187.5 217.5 117.5 48.0 219.0 156.0 168.0 177.0 192.0 225.0 261.0 141.0 57.0 255.5 182.0 196.0 206.5 224.0 262.5 304.5 164.5 76.0 328.5 234.0 252.0 265.5 288.0 337.5 391.5 211.5 84.0 365.0 260.0 280.0 295.0 320.0 375.0 435.0 235.0 98.0 438.0 312.0 336.0 354.0 384.0 450.0 522.0 282.0106.0 474.5 338.0 364.0 383.5 416.0 487.5 565.5 305.5115.0 511.0 364.0 392.0 413.0 448.0 525.0 609.0 329.0131.0 584.0 416.0 448.0 472.0 512.0 600.0 696.0 376.0140.0 620.5 442.0 476.0 501.5 544.0 637.5 739.5 399.5144.0 657.0 468.0 504.0 531.0 576.0 675.0 783.0 423.0

CHARACTERISTICS OF THE TYPICAL PROTECTA*LITE® SYSTEM (40 MM BLOCK DESIGN)

Page 10: Affordable Surge Protection for Superior Transmission and ... · cause of arrester failure. ... If a surge related flashover occurs on a line and ... As long as the surge voltage

APRIL 2006 - REV 6/06 OHIO BRASS – AIKEN, SC

35-�0®

STEP 2 The BUILDING BLOCKS of the PROTECTA*LITE® System

Ohio Brass surge arresters use only the finest metal oxide varistor (MOV) blocks so that surge energy is conducted to ground without compromising the insulation integrity of your transmis-sion or distribution system. The amount of energy a surge arrester is exposed to is depen-dent on the system. Thus, Ohio Brass manufactures four MOV block diameters to efficiently channel surge energy to ground.

Block diameter determines the amount of energy that an arrester can absorb. The energy absorption capability of the PROTECTA*LITE system is simply the amount of energy that the MOV blocks can absorb without entering a mode of thermo-mechanical arrester failure.

Select the PROTECTA*LITE System energy absorption capability that is correct for your system.

Figure 2 – Four Available PROTECTA*LITE Block Diameters

Not sure which block size to pick? Contact your Hubbell representative. After answer-ing a few simple questions, we will help you determine what energy capability your PROTECTA*LITE arresters need to ensure years of reliable service.

32 mm 40 mm 48 mm 60 mm

Page 11: Affordable Surge Protection for Superior Transmission and ... · cause of arrester failure. ... If a surge related flashover occurs on a line and ... As long as the surge voltage

APRIL 2006

35-��

OHIO BRASS – AIKEN, SC

®

PROTECTA*LITE® ENERGY CAPABILITY CHARACTERISTICS

Characteristics Block Type

Block Diameter 32 mm 40 mm 48 mm 60 mm

ANSI / IEEE C62.11 Class 5 kA 10 kA 10 kA 10 kA

IEC 60099-4 Class 5 kA 1 2 3

Energy Capability - Single Shot (kJ/kVMCOV/COV) 1.4 2.2 3.4 4.9

Energy Capability - Double Shot (kJ/kVMCOV/COV) 3.2 4.7 5.2 7.3

Current Magnitude(Sym Amps RMS)

Test Duration(Cycles)

500 120

2,500 60

5,000 30

10,000 10

20,000 10

Single Shot Energy Capability - The maximum amount of energy that an MOV block can withstand from an instantaneous surge discharge.

Double Shot Energy Capability - The maximum energy that can be discharged to ground from multiple surge events that take place within one min-ute. Lightning surges are typically comprised of multiple discharges.

TYPICAL FAULT CURRENT WITHSTAND RATINGS (40 mm Block)

Example:

If you order a PROTECTA*LITE with the following characteristics:

• 84 kV MCOV

• 48 mm block construction

The energy capability of your PROTECTA*LITE would be as follows:

• Single Shot Capability = = 285.6 kJ

• Double Shot Capability = = 436.8 kJ

3.4kJkV MCOV

5.2kJkV MCOV

x 84kV MCOV

x 84kV MCOV

Page 12: Affordable Surge Protection for Superior Transmission and ... · cause of arrester failure. ... If a surge related flashover occurs on a line and ... As long as the surge voltage

APRIL 2006 - REV 6/06 OHIO BRASS – AIKEN, SC

35-��®

STEP 3 PROTECTA*LITE® Configurations

The examples below illustrate some common PROTECTA*LITE configurations. If you prefer, contact your local Hubbell representative to help you develop a PROTECTA*LITE configuration that meets your needs.

Would you like us to specify an Ohio Brass insulator: Yes No

Suspension 1 Suspension 2 Suspension 3

Suspension 4 Suspension 5

Page 13: Affordable Surge Protection for Superior Transmission and ... · cause of arrester failure. ... If a surge related flashover occurs on a line and ... As long as the surge voltage

APRIL 2006

35-�3

OHIO BRASS – AIKEN, SC

®

Deadend 1

Deadend 2

Deadend 3

When specifying the mounting configuration of your PROTECTA*LITE system, call your Hubbell representative to help you design the system you want.

Page 14: Affordable Surge Protection for Superior Transmission and ... · cause of arrester failure. ... If a surge related flashover occurs on a line and ... As long as the surge voltage

APRIL 2006 - REV 6/06 OHIO BRASS – AIKEN, SC

35-��®

Deadend 4

Deadend 5

Davit Arm

Page 15: Affordable Surge Protection for Superior Transmission and ... · cause of arrester failure. ... If a surge related flashover occurs on a line and ... As long as the surge voltage

APRIL 2006

35-�5

OHIO BRASS – AIKEN, SC

®

Vertical Tangent 1

Horizontal Post Assembly 1

When specifying the mounting configuration of your PROTECTA*LITE system, call your Hubbell representative to help you design the system you want.

Vertical Tangent 2

Page 16: Affordable Surge Protection for Superior Transmission and ... · cause of arrester failure. ... If a surge related flashover occurs on a line and ... As long as the surge voltage

APRIL 2006 - REV 6/06 OHIO BRASS – AIKEN, SC

35-��®

When specifying the mounting configuration of your PROTECTA*LITE system, call your Hubbell representative to help you design the system you want.

Horizontal Post Assembly 2

Horizontal Post Assembly 3

Page 17: Affordable Surge Protection for Superior Transmission and ... · cause of arrester failure. ... If a surge related flashover occurs on a line and ... As long as the surge voltage

APRIL 2006

35-��

OHIO BRASS – AIKEN, SC

®

Bracket Mount Crossarm Mount 1

Crossarm Mount 2 Customer Specified

When specifying the mounting configuration of your PROTECTA*LITE system, call your Hubbell representative to help you design the system you want.

Page 18: Affordable Surge Protection for Superior Transmission and ... · cause of arrester failure. ... If a surge related flashover occurs on a line and ... As long as the surge voltage

APRIL 2006 - REV 6/06 OHIO BRASS – AIKEN, SC

35-��®

COMPOSITION of a PROTECTA*LITE® Catalog Number

Your Turn:

When designing your PROTECTA*LITE system, call your Hubbell representative to help you design the system you want.

PROTECTA*LITE Catalog Number Identifier PROTECTA*LITE Configuration

(Arrester MCOV Specific)

Arrester MCOV(2-98 kV)

These digits will be filled in by Ohio Brass based on your hardware choices from the previous pages.

PROTECTA*LITE Configuration (Arrester MCOV Specific)

Arrester MCOV(100+ kV)

0 – Arrester & Hardware (Stand-a-lone Protecta*Lite)3 – Arrester & Hardware Only (for 6005XX Assemblies)4 – Hardware Only (for 6005XX Assemblies)5 – Matched Arrester, Hardware, and Insulator6 – Hardware Only (From 6000XX Arrester Assembly)

0 – 40 mm Blocks w/ 8.4 kV Modules1 – 40 mm Blocks w/ 10.2 kV Modules2 – 48 mm Blocks (Standard Housing)3 – 32 mm Blocks4 – 48 mm Blocks (Large Housing)5 – 60 mm Blocks

6 0 0 X X X 5 X X X

6 0 X X X X 5 X X X

6 0 5 X X

Page 19: Affordable Surge Protection for Superior Transmission and ... · cause of arrester failure. ... If a surge related flashover occurs on a line and ... As long as the surge voltage

APRIL 2006

35-��

OHIO BRASS – AIKEN, SC

®

PROTECTA*LITE® Disconnectors & TOV PerformancePROTECTA*LITE systems are normally furnished with a disconnector (also called an isolator). The disconnector is connected in series at either the line or ground end of a PROTECTA*LITE arrester. The disconnector reacts to rapid increases in power frequency (60 Hz) current flow through the arrester.

In the rare case event exceeds the capabil-ity of a PROTECTA*LITE, the isolator will disconnect the arrester from the transmis-sion or distribution system. By sacrificing itself, PROTECTA*LITE protects your line from damage attributed to dangerous temporary overvoltage conditions. Furthermore, the disconnector prevents a permanent fault on

your line, while providing a visual indication that the arrester needs to be replaced. For an operational overview of the PROTECTA*LITE disconnector please contact your local Hub-bell Power Systems representative.

The typical temporary overvoltage (TOV) capability of a PROTECTA*LITE arrester is illustrated in the TOV chart below. To use the chart, select the amount of time that the overvoltage event will be present on your line. Then select the overvoltage factor based on that time period, and multiply it by the MCOV of your PROTECTA*LITE System. This is the 60 Hz overvoltage that your PROTECTA*LITE can handle for the time period selected.

For example: A PROTECTA*LITE System with an 84 kV MCOV can handle 84 kV x 1.49 = 125 kV from line to ground for a 10-second period of time.

60 Hz Temporary Overvoltage Capability ofProtecta*Lite Systems

Time (s)60 H

z O

verv

olt

age

(Per

Un

it M

CO

V)

Page 20: Affordable Surge Protection for Superior Transmission and ... · cause of arrester failure. ... If a surge related flashover occurs on a line and ... As long as the surge voltage

APRIL 2006 - REV 6/06 OHIO BRASS – AIKEN, SC

35-�0®

©Copyright 2006 Hubbell/Ohio Brass • 1850 Richland Avenue, East • Aiken, SC 29801

NOTE: Because Hubbell has a policy of continuous product improvement, we reserve the right to change design and specifications without notice.

PROTECTA*LITE® FACTS

PROTECTA*LITE has been improving system reliability for 20 years.

PROTECTA*LITE is the only surge protection system available in a complete package with insulators.

PROTECTA*LITE is available for applications ranging from 2.4 to 400 kV.

PROTECTA*LITE protects lines against troublesome backflash.

PROTECTA*LITE allows for aesthetically pleasing compact line designs.

MEXICO

HUBBELL DE MEXICO, S.A. DE. CVAv. Coyoacan No. 1051Col. Del Valle03100 Mexico, D.F.Phone: 52-55-9151-9999Fax: 52-55-9151-9988e-mail: [email protected]

CANADA

HUBBELL CANADA LP870 Brock Road SouthPickering, Ontario L1W 1Z8Phone: 905-839-1138Fax: 905-831-6353e-mail: [email protected]

UNITED STATES

HUBBELL POWER SYSTEMS, INC.210 N. Allen Centralia, MO 65240-1395Phone: 573-682-5521Fax: 573-682-8714e-mail: [email protected]

More than a quarter million PROTECTA*LITE Systems are guarding distribution and transmission lines worldwide. An additional 15,000,000 PDV and PVR distribution arresters are in service around the globe. PROTECTA*LITE arresters are based on PDV/PVR technology.

Web: http://www.hubbellpowersystems.comE-mail: [email protected]