Aerosol Photometers: The Gold Standard in HEPA Filtration Testing Presented by: Dave Crosby Tim McDiarmid Don Largent Air Techniques International www.ATItest.com [email protected]
198

Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Jan 27, 2016

Download

Documents

lenka

Aerosol Photometers: The Gold Standard in HEPA Filtration Testing. Presented by: Dave Crosby Tim McDiarmid Don Largent Air Techniques International www.ATItest.com [email protected]. Introductions. Agenda. History of Photometry Science of Photometry Applications of Photometry. - PowerPoint PPT Presentation
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Aerosol Photometers:The Gold Standard in HEPA

Filtration TestingPresented by:

Dave Crosby

Tim McDiarmid

Don LargentAir Techniques International

www.ATItest.com

[email protected]

Page 2: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Introductions

Page 3: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Agenda

• History of Photometry

• Science of Photometry

• Applications of Photometry

Page 4: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

History of Photometers & HEPA Filters

Page 5: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

History of Photometers & HEPA Filters

“You can’t have one without the other”

Page 6: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

The photometer was first since there was a need

David Sinclair, Ph.D.

(Nephelometer)

(Not portable and had logarithmic display)

Page 7: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Air Pollution Research 1933

Page 8: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

WW II generated a high priority need

It all started in 1942

Page 9: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Some Key Players

Wendell Anderson, Humphrey Gilbert, Dr. Melvin First

Page 10: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Captured WW II German Gas Masks

• The US had performed no gas mask development since WW 1

• German masks used cellulose asbestos media patented by Dräger Werke in 1933

• Wendell Anderson working with H&V developed media comparable to the German sample

Page 11: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

M10A1 Canister

Page 12: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Tank & APC M-25 Mask

Page 13: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Smoke Penetrometer to test the gas mask paper & filters

Page 14: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

First Linear Photometer

Page 15: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Space Filter

• US military needed filtration of room areas for people and used gas mask media for a pleated filter for larger air flow (1943-1948)

• Know as “Collective Protection”

• Used cardboard spacers between pleats, which had high air flow resistance

Page 16: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Cardboard Pleat

Page 17: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Manhattan Project

• Humphrey Gilbert safety engineer at Los Alamos was sent to Oak Ridge

• Filters used in Manhattan Project were very thick with extremely high pressure drop

• Foresaw need for high efficiency air filters in HVAC systems

Page 18: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Absolute Air Filter

• Gilbert (now with AEC) unhappy with Army Space filter and its limitations

• AEC in 1948 gives Author D. Little a contract to redesign filter and find a supplier

• Walter Smith Ph.D. comes up with corrugated cardboard separator idea

Page 19: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Improved Pleated Filter Design

Page 20: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing
Page 21: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

HEPA Filter Development

• First Air Cleaning Seminar for AEC personnel held June 1951 at Harvard Air Cleaning Laboratory

• First Handbook on Air Cleaning distributed at meeting

• Fires at several weapons plants made need for high temperature and water resistance necessary

Page 22: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Second Air Cleaning Conference held in Ames, IA 1952

Melvin W. First Ph.D.Presented four research papers

Page 23: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Military develops procedures and

Apparatus to test High Efficiency filters and related products

Penetrometers

Q-127 Low Flow

Q-76 Med. Flow

Q-107 High Flow

Rough Handling

Water Repellency

etc.

Page 24: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

HEPA Development for Fire & Water Resistance (1953)

Page 25: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

First HEPA Guide (1961)

Page 26: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Willis Whitfield (1961)

Discovery of Laminar Flow at Sandia National Labs

Page 27: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

SNL Demonstrates Clean Room Concept in Chicago for IES(T)

(1962)

Page 28: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

First “In Place Filter Test”

Page 29: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

First Portable Linear Photometer TDA-2 (1962)

Page 30: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

JM-1000 Photometer (1964)

Page 31: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Next Portable Photometer TDA-2A (1964)

First Scanning Probe

Cabinet covered in white Formica(White Rooms)

Page 32: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Next Portable Photometer TDA-2B (1965-66)

Ergonomic front panel design

Page 33: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

First Commercial Standards (1967)

Page 34: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

First Commercial Standards (1967)

Page 36: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

What is a Filter

Page 37: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Before Photometry…

• What is a Filter?– Filtration Mechanics– MPPS

• How to Test a Filter– Efficiency– Leak (Integrity)

Page 38: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

What is a Filter?

Separation of one phase from another

•Solids or liquids in Air (Home Furnace)

•Solids in liquid (Auto Oil/Gas)

•Liquid in Air (Air oil separators)

•Liquid in liquid (RO)

•Gas in Gas (Activated Carbon)

Page 39: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

What is a Filter?

A Controlled Leak!

Filtration controls the amount of impurity that is allowed to pass.

There is no such thing as a ‘perfect’ filter

(no resistance and 100% efficiency)

Page 40: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Filtration Types

• Materials– Fibers– Fibrous Structures– Micropores

• Performance– High Efficiency– Low Efficiency

Page 41: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

What are we dealing with?

Solids or liquids in Air

&

Fibrous Filters

Other structures are more common in ultra filtration and special applications

Page 42: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Fibrous Filters

• Typically Depth Filters– Filtration throughout media depth– Very low to very high particle removal

• Fibrous Filter Construction– Filter Disks/Pads– Pleated Cartridges– Bags/Pockets

Page 43: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Filtration Mechanics

• Pressure Drop

• Single Filter Efficiency

• Collection Mechanisms

Page 44: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Darcy’s Law

ΔP

Page 45: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Darcy’s Law

Page 46: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Filter Pressure DropP

ress

ure

Dro

p

Linear Pressure Drop Inertial Velocity (Darcy Law) Regime Regime

CLEANROOM

HVAC

Page 47: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Filtration Assumptions

• Fibers are in cross flow

• Particles are ‘collected’ upon contact with fiber

• Uniform fiber diameter

• Uniform particle size

Page 48: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Single Fiber Efficiency

Single Fiber Efficiency

ηs = Particles collected by fiber .

Particles in volume of air geometrically swept out by fiber

Air Volume swept out by fiber

Page 49: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Fiber Structure - HEPA

Page 50: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Particle Collection Mechanics

• Sieving

• Inertial Impaction

• Diffusion

• Interception

Page 51: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Particle Collection: Sieving

Fibers

Particle Flow

Page 52: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Particle Collection: Interception

Page 53: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Particle Collection:Inertial Impaction

Page 54: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Particle Collection: Diffusion

Page 55: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Particle Collection Mechanisms

Page 56: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

High Efficiency Filter MPPS(Most Penetrating Particle Size)

Particle Size

Pen

etr

ati

on

MPPS 0.08 to 0.18µm

Impaction

Diffusion

Page 57: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Filtration isSelective Particle Collection

0000 0

000 000 0

00 000 0 00

000 0000 000

00 0000 000

Small and big particles are more effectively collected

Page 58: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Impact of Flow Rate on Efficiency

Page 59: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

A Filter’s Performance is Determinedat Media Velocity

Media VelocityMedia VelocityFace Velocity

Media Velocity is Lower Than Face Velocity

Page 60: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Consideration in Filter Design

• Penetration or efficiency

• Critical Particle Size

• Pressure Drop or resistance

• (Cost)

Page 61: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Filter Tests

• Efficiency– Media Manufacturer– Filter Manufacturer– 3rd Party Certification

• Leak/Integrity– Filter Manufacturer– Field/In-Situ

Page 62: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Efficiency Testing

• Challenge filter with aerosol at or near the MPPS– This requires a mono-dispersed aerosol (tight distribution)

• Measure upstream and downstream concentration

• Sequential or parallel (simultaneous) measurements

• Efficiency = 1 – Downstream

Upstream

Note: This is a ‘global’ measurement (i.e. entire filter)

Page 63: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Typical Filter EfficiencyTest System

Recommended filter performance test system from IEST RP-CC-0021

Page 64: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

What is a Leak?• Leak is a local measurement.• Leak is generally 5 –10 times the average

penetration at a local spot.• Therefore we do not require a mono-

dispersed challenge aerosol at the MPPS– Easier and less costly to generate larger

particles with a broader distribution.

Page 65: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

A Good Filter Will Allow Few Particles to Penetrate

o o o o o o o o

o o o o o o o o o o o o o o o o o o o o o o o

00 0 0- 0 0 0 00

o o o o o 0

o

Page 66: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Add a Leak and…

o o o o o o o o

o o o o o o o o o o o o o o o o o o o o o o o

00 0 0- 0 0 0 00

o o o 00 o o o o o 0 0

O o o o o o o 0 0o o o

Page 67: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Test for a Leak/Integrity

• Measure local penetration at each sample location to determine:– Filters are not faulty / not been damaged– Filters have been installed properly– There are no leaks in the mounting frame /

between mounting frame and housing– System contains no by-pass of the filter

Page 68: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Leak/Integrity Scanning

Ensure that all parts of filter are within specification

Page 69: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Efficiency vs. Leak/Integrityin General Terms

Efficiency Testing

Leak Testing

Global Local

Determine % Penetration Yes Yes1

Pinpoint Leaks No Yes

Manufacturer Test Yes Yes2

Field Test No Yes

1 – Local % penetration, not overall efficiency2 – Due to variations in the media manufacturing process

Page 70: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Discussion

Page 71: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

When Testing a Filter What are We Looking For?

Page 72: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Let’s Review…

• Particulate penetration as– Efficiency– Leak

• Size of interest?– MPPS from 0.08 to 0.18 micron– Even when looking for a leak?

However…..

Page 73: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

What is a particle?

Page 74: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

The Simplest Particle?

Page 75: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Equivalent Particle Size

• Diameter of a Sphere that has the same magnitude of a chosen Property as the particle In question– Optical Diameter (Eye/microscope)– Scattering Diameter (Light Scattering)– Electric Mobility (Charge On Particle)– Mobility (Diffusion)– Stokes Diameter (Drag Forces)– Aerodynamic Diameter (Settling Speed)

Page 76: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

In Filtration, Collections of Particles Interest Us

• Aerosol Solid/Liquid and Gas (dust, fog)

• Hydrosol Solid/Liquid and Liquid (milk, paint, lotion)

• Foam Gas in Solid or Liquid (sponge, shampoo)

Page 77: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Key Concepts

• Drag Force – proportional dp > 10µm

• Slip Correction for dp < 10µm

• Stopping Distance and Relaxation Time• Settling velocity• Mobility and Electric Mobility• Diffusion and Brownian Motion• Coagulation• Dimensionless Numbers

Page 78: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Units of Measurement in Filtration

• µm Micrometer, 10-6 meter

• Nm Nanometer, 10-9 meter

• A Angstrom Unit, 10-10 meter

1 µm = 1,000 nm = 10,000 A

Some perspective:

1cm is 1000 µm1in = 2.54 cm = 25,400 µm

Page 79: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Item Approximate Particle Diameter

Eye of a Needle 1,230 microns

Beach Sand 100 – 2000 microns

Table salt ~100 microns

Human hair 40 - 300 microns

Talcum powder ~10 microns

Tobacco Smoke 0.01 – 1.0 microns

Bacteria 0.2 - 0.3 microns

Virus <0.005 – 0.05 microns

Particle Sizes of Interest

Page 80: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Typical Particle Sizes0.3um

Page 81: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Another Particle Size Chart

Page 82: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Typical Settling Velocity

Diameter (um) Feet/min

0.1 0.00016

1.0 0.002

10.0 0.59

100 59.2

Page 83: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

How is an Aerosol Characterized?

FrequencyX (range) Raw Data Normalized

0 to 5 100 20

5 to 6 70 70

6 to 8 60 30

Consider this data set

Page 84: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Normalized Frequency Distribution

Y/ΔX

Page 85: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Size Distribution Terms

• Independent variable, X

• Mean Xm

• Standard Deviation, σ

• Mode (peak)

• Median (50th percentile)

Page 86: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Arithmetic Standard Deviation

Page 87: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Geometric Standard Deviation

Page 88: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Particle Size Distribution

• Most Natural Processes are Geometrically Distributed and often multi modal

• Number (count), Surface, or Volume (mass) Distribution are common weightings

Page 89: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Why is this important?

Due to data weighting…

…the 0.3um DOP particle measured in the 50’s is a volume (mass) mean…

…whose number (count) median is actually closer to 0.18um…the MPPS

Page 90: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Geometric vs. Arithmetic

• Consider Geometric as Arithmetic or Linear on a log scale

• Geometric spreads out the lower end

• In Arithmetic, equal differences result in equal spacing

• In Geometric, equal ratios result in equal spacing

Page 91: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Geometric vs. Arithmetic

Equal intervalsArithmetic: 2-1.8 = 1.8-1.6 = … (equal differences)

Geometric: 10/7.48 = 7.48/5.62 = … (equal ratios)

Page 92: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Why Use Log Normal Distributions?

• No Negative Values

• For known distributions, the Means of different weightings can be calculated from the others• For example, Mass (volume) Mean

calculated from Count (number) mean

Page 93: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Number and Volume Weighting

dp Number Counts Volume (πd3/6)1 1,000,000 523,00010 100 523,000100 1 523,000

Page 94: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Key Points to Remember

• Particles come in many shapes and sizes• ALL measurements determine some physical

property and provide an Equivalent Size• In filtration, larger particles settle out and are

not important, particularly cleanrooms• Geometric Distributions (aka Log Normal) are

used to define particle size distributions• Mass and Number weightings are common in

particle measurements

Page 95: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Discussion

Page 96: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Now we know we are looking for particles…

The Light-Particle Interaction

Page 97: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Primary Light-Particle Interactions

• Elastic Scattering– Rayleigh Scattering– MIE Scattering– Phase Shift– Polarization

• Absorbtion

Page 98: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Incident Light

LIGHT PARTICLE INTERACTION

DiffractionReflection

RamanFluorescence

Refraction

Emission

AbsorptionScattering

Page 99: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Common Properties

• Refraction – the apparent change in direction of light due to change in refractive index within one medium or between dissimilar medium

• Reflection – redirection of light at the surface of a material

• Diffraction – bending or deflection of light around a particle

• Polarization – oscillations of the light occurring in a defined plane

Page 100: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Complex Numbers

• (4)1/2 = 2• What is (-1) 1/2 ?• It is defined by the symbol i• A complex number is written as (a - b i)

where the imaginary part is represented by the symbol i

Page 101: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Refractive Index

• Refractive Index of a material is a complex number

Usually given as 2 - 4i

• The imaginary part is due to absorption

Page 102: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Refractive Index of Common Materials

• Quartz 1.54 - 0i• Glass 1.5 to 1.9 - 0i• PSL 1.59 - 0i• Ca Sulfate 1.57 - 0i• Carbon 2.0 – 0.33i• Iron 1.5 – 1.63i

Page 103: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Refraction

Refractive Index = sine r / sine i

i

r

Page 104: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Size and Scattering RegimesSize Rangeof Interest

Page 105: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Elastic Scattering

Redirection of Incident Light without change in wavelength•Refraction – internal to particle, wavelength and composition dependent•Reflection – at surface of particle, dependent on wavelength and composition•Diffraction – external to particle, independent of wavelength and composition

Page 106: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Particle Size Affects Elastic Scattering

• Optical Particle Size (α)α = πd / λ

where:d = particle diameter

λ = wavelength

• Scattering Intensity (Is)

Is = λ2 f(α) where:

f(α) is a size dependent function

Page 107: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Light Scattering

• Particles much smaller (< 0.025um) than the wavelength of light results in Rayleigh Scattering

• Particles comparable to the wavelength of light (0.025> x < 2.5um) results in MIE Scattering

• Much larger particles result in geometric scattering.

Page 108: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Light Scattering

• Particles much smaller (< 0.025um) than the wavelength of light results in Rayleigh Scattering

• Particles comparable to the wavelength of light (0.025> x < 2.5um) results in MIE Scattering

• Much larger particles result in geometric scattering.

Page 109: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Rayleigh Scattering

Page 110: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Rayleigh Scattering

Page 111: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Mie Scattering

Wavelength, λ

Incident light

Page 112: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

MIE Scattering

Page 113: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

MIE Scattering

Page 114: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Discussion

Page 115: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Multiple and Single Particle Sensing and Sensors

Page 116: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Multiple Particle Sensing

• Sampling Volume ≥ 1/number concentration

• Independent of sample volume (measuring a ‘cloud’)

• Precision depends on averaging time (due to variations in the ‘cloud’)

Page 117: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Multiple Particle Sensors

• Extinction (umbrella)– Smoke Meter (soot content in exhaust stack)– Transmissometer (visual ranging)

• Scattering– Intensity (nephelometry)– Backscatter (LIDAR)– Photometry

Page 118: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Photometer

• Aerosol is illuminated by a light source

• Total scattered light is detected by PMT

• Total concentration is measured

Page 119: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Photometer

0 0 00 00 0

0 0 0 0 0

0 0 0 0 0 00 0

Aerosol

Light Source

Focus OpticsCollector Optics

Photodetector

Electronics

Page 120: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Photometer Focal Point

Page 121: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Nephelometer

• Particle density is a function of the light reflected into the detector from the illuminated particles

Page 122: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Multiple Particle Sensors Summary

• Light-Particle interaction results in scattering

• Optical instruments in particle measurement is dependent upon the particle size and scattering properties

• Multiple particle scattering is independent of volume; depends on averaging time.

Page 123: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Single Particle Sensing

• Sample Volume << 1/number concentration

• Requires a precise, known volume of sampled air

• Same as counting events; precision depends on total counts

Page 124: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Single Particle Sensors

• Light attenuation (extinction)

• Scattering (Particle Counters)– Laser– White Light

• Angular Scattering

• Doppler anemometer

Page 125: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Particle Counter

OO

Electronics Light Source

Focus OpticsCollector Optics

Photodetector

Page 126: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Common Particle Counter Challenges

• Multi Valued Response

• Coincidence

• Problems at small particle sizes

Page 127: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Multi Valued Signal

Page 128: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Coincidence

OO

Electronics Light Source

Focus OpticsCollector Optics

Photodetector

Page 129: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Small Particle Detection

• Scattering intensity is very small

• Common Solutions– Increase intensity of light– Change light source wavelength– New techniques?

Page 130: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Small Particle Detection

• Increase Intensity– Improves signal from particles– Increases noise from air molecules

• Reduce the wavelength– Shifts the curves to smaller sizes– Increases noise from molecules

• Reduce the viewing volume

Page 131: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Saturator Vapor

Condensation Nucleus Counter

Aerosol

Alcohol

Condensation Nucleii

Page 132: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Single Particle Sensors Summary

• Most optical measurements are in the MIE regime• Single particle counting requires known volume of

sampled air• Same as counting events; precision depends on total

counts – long sample times at low counts• Problems of coincidence at high concentrations• Non unique response and low signal to noise ratio at

small sizes• Small sizes handled by using smaller wavelengths or

proprietary methods

Page 133: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Photometer vs.Particle Counter vs. CNC

• Photometer– Measures Total Aerosol– Response Linear With Total Aerosol

Volume– Requires Known Aerosol And Relatively

High Concentration– Problems:

• No Particle Size Information• Requires High Concentrations

Page 134: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

• Particle Counter (Laser)– Detects and sizes particles– Counts by size– Measures down to 0.1 μm– Can use any aerosol– Problems:

• Assumes everything measured is a PSL• Multi Valued Response• Coincidence• Problems at small particle sizes• Long sample times to obtain a statistically valid results

Photometer vs.Particle Counter vs. CNC

Page 135: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

• CNC– Particle detector only– Can measure less than 0.05 μm– Problems:

• Requires mono-dispersed aerosol• Counts all particles, noise at bottom end• Long sample times to obtain a statistically valid

results

Photometer vs.Particle Counter vs. CNC

Page 136: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Discussion

Page 137: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Aerosols and Aerosol Generators

Page 138: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

What is a Standard?

• A KNOWN and Universally Accepted value of a physical property or quantity– Meter for measure of length– ◦C for Temperature

Page 139: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Why are Standards Necessary?

• They establish accuracy of measuring instruments

• Calibrate the accuracy of instruments in use– Temperature– Scales– Flow Meters– Photometers– Particle Counters

Page 140: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

How Does this Affect Aerosols?

• A Standard Aerosol has KNOWN properties– Particle Size and Distribution– Concentration– Shape (usually spherical)– Chemistry (inert)– And Refractive Index in our business

Page 141: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Aerosol Standards

• Mono-disperse Aerosol– ‘Single’ size particles σg ≤ 1.4

• Instrument Calibration for PCs• Research & Development

• Near Mono-disperse Aerosol– Narrow distribution 1.4 < σg ≤ 1.6

• Some Production QC Level of accuracy

• Poly-disperse Aerosol– Broad distribution 1.6 < σg

– Industrial measurements

– Instrument verification

– Some instrument calibrations

Page 142: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Mono vs Poly Disperse

Page 143: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Mono vs Poly Disperse

Page 144: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Implication on Size Dispersion

• For a log normal distribution– 95% of the particles are between

Mean σg2

σg2 & Mean

Page 145: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Implication on Size Dispersion

• An aerosol with mean of 0.3um

– σg = 1.2• 95% of particles are between 0.21 & 0.43um

– σg = 2.0• 95% of particles are between 0.075 and 1.2um

Page 146: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Mono vs Poly Disperse

Page 147: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Three Types of Aerosol

• Mono-disperse: σg ≤ 1.4

• Near Mono-disperse: 1.4 < σg ≤ 1.6

• Poly-disperse: 1.6 < σg

Page 148: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Typical Poly-Disperse Aerosol Standards

• Laskin Nozzle

• Wright Nebulizer

• Pneumatic Nebulizer

• Condensation Generators

• Spinning Disk

• Exploding Wire

• Standard Dusts

Page 149: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Laskin NozzleAir

Entrained Liquid

Aerosol

Page 150: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Laskin Nozzle

Page 151: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Laskin Nozzle

Page 152: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Laskin NozzleConcentration Calculations

Output of Laskin Nozzle is defined:

• By # Nozzles @ 20 PSIG

Concentration = # Nozzles x 13,500

Total Flow (cfm)

• By # Jets at 20 PSIG

Concentration = # Nozzles x 3,375

Total Flow (cfm)

*Note: there are 4 jets in a standard Laskin Nozzle

Page 153: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Laskin NozzleConcentration Calculations

• You can calculate the system concentration, if you know: – System Air Volume (CFM)– Number of Laskin Nozzles/Jets at 20 PSIG

• You can calculate the number of nozzles/Jets, if you know:– System Air Volume (CFM)– Desired system concentration

Page 154: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Wright Nebulizer

Page 155: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Pneumatic Nebulizer

Liquid

AerosolCompressed Air

Page 156: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Thermal Condensation Aerosol Generators

Heater O 0 O o 0

Quench Air

VaporAerosol

Liquid

Compressed GasQuench Air

Page 157: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Thermal Aerosol Generator

• Polydispersed • Produces a greater level of aerosol

concentration than pneumatic type nozzle• Applications include higher flow systems• Median particle size is smaller than

pneumatic generation• Output concentration cannot be calculated

as output is variable• Size and distribution shift with

concentration

Page 158: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Ultrasonic Nebulizer

Page 159: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Spinning Disk Particle Generator

Page 160: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Exploding Wire

Page 161: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Test Dusts

• Standard Dust (Arizona Road Dust)– Mainly Silica with

• Mass Mean Diameter of 7 µm

• σg of 3.6

• Specific Gravity of 2.7

– Originally collected from Arizona Desert

Page 162: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Test Dusts

• ASHRAE– Custom blend of:

• 72% ISO 12103-1, A2 Fine Test Dust, • 23% powdered carbon• 5% milled cotton linters

– Attempt to simulate natural dust for HVAC

Page 163: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Test Dusts

• SAE Dusts – automotive filter testing– Fine

• Mass Median Diameter ~ 25µm• No particles > 100µm

– Coarse• Mass Median Diameter ~ 60µm• 10%+ may be larger than 100µm

Page 164: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Common Mono-disperse Aerosol Standards

• Poly Styrene Latex (PSL)

• Vibrating Orifice

• Electrostatic Classification

• Condensation Techniques

Page 165: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

PSL Aerosols

• NIST Traceable PSL Particles– Examples

– Methodology•Atomize PSL in Liquid (water)•Evaporate the liquid•NIST Traceable PSL Aerosol

Page 166: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

PSL Aerosols

Page 167: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Residue & PSL Aerosols

• Impurities in water become small particles

• These particles can be counted as particles in standard aerosol, especially by a CNC

Page 168: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Residue & PSL Aerosols

Assuming a typical 2um atomizer droplet and 10 ppm purity water,

Residue particle size can be computed

10 x 10-6 = (residue dia/drop dia)3

Residue Diameter = 0.04um

Page 169: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Residue Particles

Page 170: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

PSL Aerosols

• Common for Cleanroom Applications• NIST traceable PSLs are expensive• PSLs are easy to aerosolize, but output

concentration is variable• Limited by residue at small sizes• Not available in large sizes• PSL gives excellent optical response• Used as calibration aerosol for particle counters

Page 171: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Electric Mobility Classification

Page 172: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Points to Remember

• Standards are required to verify and calibrate instruments and devices

• A Standard aerosol can be either poly or mono disperse

• R&D standards are more precise and are for laboratory use

• Industrial standards are easier to produce and are widely used

Page 173: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Points to Remember cont’d.

• Poly-disperse aerosols are commonly generated by atomization, nebulization or mechanical means

• Only a few techniques are available to generate very tight, mono-disperse aerosols

• NIST traceable PSLs are generated in small quantities and are very expensive

• PSL concentration output is variable• Residue particles can be a problem in small sizes

Page 174: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Discussion

Page 175: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Photometer Testing Standards & Practices

Page 176: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

What is a “Filter” Testing Standard?

• A DOCUMENTED and Universally Accepted method of obtaining a Qualitative Performance Measurement

Page 177: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Why are Standards Necessary?

• They establish consistent methodology• Provide a guide for understanding and

compensating for variables encountered during practical application

Page 178: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

How Does this Affect Filter Testing?

• A Test Standard defines methods and limits – Aerosol characteristics– System Operating Conditions– Testing protocols

• Allowable Challenge Concentrations

• Sampling Rate

• Maximum “Allowable” Leakage

• Scanning Speed

Page 179: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Standards & Recommended Practices Organizations• AACC (American Association for Contamination Control)

• ISO (International Organization for Standardization)

• BNL (Brookhaven National Laboratory)

• ASTM (American Society for Testing and Materials)

• EN (European Norm)

• IEST (Institute of Environmental Science & Technology)

• ANSI (American National Standards Institute)

• ASME (American Society of Mechanical Engineers)

• DOE (Department of Energy)

Page 180: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Filter Testing Standards• CS-IT (1968) Standard for HEPA filters• CS-2T (1968) Standard for Laminar Flow Clean Air Devices - Installation Leak Test (filter and gaskets)• CS-2T (1968) Standard for Laminar Flow Clean Air Devices - Induction Leak Test (seams and joints)• 14644-3 (2005) Cleanrooms & Associated Environments, Annex B- Test Methods (Informative)• IH62300 (2001) In-Place HEPA Filter testing, Section 6.2 Equipment• EN-1822-2 High Efficiency Air Filters (HEPA & ULPA)-Part 2: Aerosol Production, Measuring Equipment,

Particle Counting Statistics• IES-RP-CC001 HEPA & ULPA Filters• IES-RP-CC006 Testing Cleanrooms• IES-RP-CC007 Testing ULPA Filters• IES-RP-CC034 HEPA & ULPA Filter Leak Tests• Fed Std 209E (1992 by IEST) Most referenced in “Filter” industry was replaced by ISO 14644-1 & 2 in

November 2001• NSF 49:2008 (Annex A:2008) Biosafety Cabinetry: Design, Construction, Performance & Field

Certification-Performance Tests• NSF 49:2008 (Annex F:2008) Biosafety Cabinetry: Design, Construction, Performance & Field

Certification-Field Tests• ASME N509 (2008) Nuclear Power Plant Air-Cleaning Units & Components)• N510 (2007) Testing of Nuclear Air Treatment Systems• N511 (2007) In-Service Testing of Nuclear Air Treatment Heating, Ventilating and Air-Conditioning

Systems• DOE-HDBK-1169, DOE Handbook Nuclear Air Cleaning Handbook, Section 8.6.1 In-Place Testing

Page 181: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Industries Using Photometry

• Pharmaceutical

• Non-pharmaceutical– Civilian

• Nuclear Power

– Military• Nuclear Weapons• Chemical Weapons• Biological Weapons

Page 182: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Photometer vs. Discrete Particle Counter

• 1968 CS-1T Standard for HEPA Filters

Photometer •Upstream challenge aerosol must be at least 27ug/l•Maximum Leakage = 0.01%•Scanning rate = 2 inches per second @ 1 inch from filter face

Particle Counter •No defined method

Page 183: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Photometer vs. Discrete Particle Counter

• 1968 CS-2T Standard for Laminar Flow Clean Air Devices– Installation Leak Test (for filter & gaskets)

Photometer •Upstream challenge aerosol must be at least 27ug/l•Maximum Leakage = 0.01%•Scanning rate = 2 inches per second @ 1 inch from filter face

Particle Counter •No defined method

Page 184: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Photometer vs. Discrete Particle Counter

• 1968 CS-2T Standard for Laminar Flow Clean Air Devices– Induction Leak Test (for seams & joints)

Photometer •Ambient aerosol must be at least 10 E3 above FF•Maximum Leakage = >FF•Scanning rate = 2 inches per second @ 1 inch from joint or seam within clean zone

Particle Counter •Ambient aerosol must be >300K particles/ft3•Maximum leakage >100 counts•Scanning rate = 2 inches per second @ 1 inch from joint or seam within clean zone

Page 185: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Photometer vs. Discrete Particle Counter

• 2005 ISO 14644-3 Cleanrooms & associated controlled environments, Test methods– Installed Filter System Leakage

Photometer •Upstream challenge aerosol of between 20 & 80ug/l•Maximum Leakage = 0.01%•Scanning rate = 2 inches per second @ 1 inch from filter face

Limitations•Efficiency < 99.997% @ MPPS•Oil aerosols allowed•Ability to achieve required concentrations

Particle Counter •Upstream challenge aerosol (Too much detail to list here @ 6 pages) sufficiently high that Np >2 & <10•Maximum leakage = 0.01%•Scanning rate ≤ 3.14 inches per second (varies depending on probe dimensions, Np, sample rate

Page 186: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Photometer vs. Discrete Particle Counter

• 2005 ISO 14644-3 Cleanrooms & associated controlled environments, Test methods– Containment Test

Photometer •Upstream challenge aerosol of between 20 & 80 ug/l•Maximum Leakage = 0.01%•Scanning rate ≤ 2 inches per second at 2 inches from joint, seal or mating surfaces

Limitations•Efficiency < 99.997% @ MPPS•Oil aerosols allowed•Ability to achieve required concentrations

Particle Counter •The greater of:

• ambient count X E103

• > 3.5 E106 particles/m3

•Maximum leakage = ≤ ambient count X E10-2 •Scanning rate ≤ 2 inches per second at 2 inches from joint, seal or mating surfaces

Page 187: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Photometer vs. Discrete Particle Counter

• 2001 IH62300:2001 In-Place HEPA Filter testing

Photometer •Upstream challenge aerosol 104 greater than ambient•Maximum Leakage = 0.03%•Duct measurement-No scan

Particle Counter •No defined method

Page 188: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Photometer vs. Discrete Particle Counter

• IEST-RP-CC006 Testing Cleanrooms

Photometer •Upstream challenge aerosol of between 10 to 20 ug/l•Maximum Leakage = 0.01%•Scanning rate = 2 inches per second @ 1 inch from filter face

Particle Counter •3 x E108 #/m3 @ particle size of interest (10 counts per Appendix B, Exp. 1)•Maximum Leakage = 0.01%•Scanning rate = [(Cc)(Ls)(Fs)(Dp)]÷ [(60)(Np)]Result 3.3 ft/min @ 1 in or 0.65 inches per second (Appendix B, Exp. 1)

Page 189: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Photometer vs. Discrete Particle Counter

• IEST-RP-CC034 HEPA & ULPA Filter Leak Tests

Photometer •Upstream challenge aerosol of between 10 to 90 ug/l•Maximum Leakage = 0.01%•Scanning rate = 2 inches per second @ 1 inch from filter face

Particle Counter •2.8 x E108 #/m3 @ particle size of interest (10 counts per Appendix G, Exp. 1)•Maximum Leakage = 0.01%•Scanning rate = [(2.8)(108)÷1000][(0.0001) (28.3)(1.25)÷(60)(10)]

Result = 1.25 cm/s @ 1 in or 0.5 in/sec (Appendix G, Exp. 1)

Page 190: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Photometer vs. Discrete Particle Counter

• 2008 NSF 49 Biosafety Cabinetry

Particle Counter •No defined method

Photometer •Upstream challenge aerosol of at least 10 ug/l•Maximum Leakage = 0.01%•Scanning rate = 2 inches per second @ 1 inch from filter face

Page 191: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Points to Remember!

• Photometer & particle counter results are not likely to correlate due to the different weighting of the technology used.– Photometry response is mass weighted while

particle response is number weighted.• Filter testing process is the same regardless of

photometer or particle counter use. – Measure upstream challenge– Measure downstream penetration by scanning or

point sampling– Calculate penetration

Page 192: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Points to Remember!

• Filter testing process complexity varies between photometers and particle counters.– Challenge concentration

• Photometers: Variable range of 10-100 ug/l with 10-30 ug/l being typical (Std defined)

• Particle counters: Variable range of 3.0 E105 to 3.0 E108 (Std defined, calculated to achieve desired Np)

– Measure Downstream• Photometers : 0.01% leakage maximum while scanning

rate of 2 inches /second in most cases (Std defined)• Particle counter: 0.01% leakage maximum in most

cases while scanning at a calculated, statistically, determined rate (Std defined)

Page 193: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Points to Remember!

• Calculate Penetration– Photometer: Ratio of upstream challenge to downstream

expressed as a percent– Particle counter: Ratio of upstream challenge to

downstream expressed as a percent

Page 194: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Points to Remember!• Each technology has design strengths and weaknesses which decide where its use is

“reasonable” in filter leakage testing.– Photometer

• Aerosol generator for upstream challenge “oil” aerosol• No diluter necessary for Upstream measurements• Consistent & essentially “Calculation Free” test method• Limited to systems with efficiencies ≤99.997%• Typically consistent results among multiple units• Robust “core” technology

– Particle counter• Aerosol generator required in most cases, but at a lower output• Use of solid or liquid aerosol possible• Ability to test systems to 99.9999% efficiency• Diluter required for upstream sampling• Unit to unit result consistency difficult to achieve• More sensitive detection system results in less-robust instrument

Page 195: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Discussion

Page 196: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Hands On Demo:Photometer Filter Leak

Scanning

Page 197: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Review and Discussion

Page 198: Aerosol Photometers: The Gold Standard in HEPA Filtration Testing

Thank you

David W. Crosby

Tim McDiarmid

Don Largent