This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
AE-9000 User Manual
1
AE-9000 DIGITAL MULTIFUNCTION METER
Automatic Electric Ltd.
Document Number
236-103000-02
May 11, 2010
Revision: AEL/ENG/002
Automatic Electric Ltd. Rectifier house,570, Naigum Cross road,
11. Ordering Information ……………………………………………………………. 29
AE-9000 User Manual
4
1. Introduction The AE-9000 (multifunction meter-MFM ) will compute, store and display
various parameters, in single phase or three phase 3-wire/4 wire systems. Stored
parameters/ data can be accessible to user through RS485 interface.
This document provides detailed steps for the user in order to set-up and operates
the system. The user can also edit the configuration during run time and view the
current configuration details on 7 segment LED display panel using a 5 key
keypad, which are described in this document. The user may also configure and
view parameters remotely via MODBUS communication.
2. Keypad Operation
The keypad for Power Line Monitor consists of total 5 keys.
1. Mode Key (M)
2. Up Navigation Key (▲)
3. Down Navigation Key (▼)
4. Right Navigation Key (►)
5. Enter Key (E)
2.1.Mode Key
Pressing the Mode Key, enables menu for selecting mode of operation from the
following
1. Run Mode
2. Configure Mode
3. Display Previous Energies
4. Select Auto Scroll Pages
5. Testing Mode
Note: Pressing the Mode Key in any of the above mentioned modes display the
mode selection menu again.
2.2.Navigation Keys
The Up Navigation and Down Navigation keys are used to scroll through display
pages in the Run Mode, and increment and decrement the value at current cursor
position in Configuration Mode respectively.
The Right Navigation key is used for scrolling to the immediate right cursor
position from the current cursor position in Configuration Mode and to start auto
scrolling in run mode.
AE-9000 User Manual
5
2.3. Enter key
The Enter Key is used to select a particular menu option in the Mode of Operation
display Page. In Configuration Mode, the key is used to select a menu option as
well as to confirm a particular value to be set.
3. Display The AE-9000 display has different behavior in all the operating modes described as follows:
3.1. Run Mode
In Run Mode, the MFM displays various parameters in separate pages as
follows:
i. Page1: Avg. Voltage, Avg. Current, Avg. Power Factor.
LED Row 1 : 8.8.8.8.
LED Row 2 : 8.8.8.8.
LED Row 3 : 8.8.8.8.
LED’s: V, I, Pf.
ii. Page2: Line to Neutral Voltages of all three phases.
LED Row 1 : 8.8.8.8.
LED Row 2 : 8.8.8.8.
LED Row 3 : 8.8.8.8.
LED’s: V, R, Y, B
iii. Page3: Line to line Voltages of all three phases.
LED Row 1 : 8.8.8.8.
LED Row 2 : 8.8.8.8.
LED Row 3 : 8.8.8.8.
LED’s: V, RY, YB, BR
iv. Page4: Current for all three phases.
LED Row 1 : 8.8.8.8.
LED Row 2 : 8.8.8.8.
LED Row 3 : 8.8.8.8.
LED’s: I, R, Y, B
v. Page5: Avg. Freq., Neutral Current, THD %
LED Row 1 : 8.8.8.8.
AE-9000 User Manual
6
LED Row 2 : 8.8.8.8.
LED Row 3 : 8.8.8.8.
LED’s: F, NI, THD
vi. Page6: Pf. For all three phases.
LED Row 1 : -1.8 8 8
LED Row 2 : -1.8 8 8
LED Row 3 : -1.8 8 8
LED’s: Pf., R, Y, B
vii. Page7: Total Power Active, Apparent, Reactive.
LED Row 1 : 8.8.8.8. (M/k)
LED Row 2 : 8.8.8.8. (M/k)
LED Row 3 : 8.8.8.8. (M/k)
LED’s: TOT, W, VA, VAR
viii. Page8: Total Active Energy (Import+Export).
LED Row 1 : 8.8.8.8.(M/k)
LED Row 2 : 8.8.8.8.
LED Row 3 :
LED’s: Wh, TOT
ix. Page9: Total Reactive Energy (Import+Export).
LED Row 1 : 8.8.8.8. (M/k)
LED Row 2 : 8.8.8.8.
LED Row 3 :
LED’s: VArh, TOT
x. Page10: Total Apparent Energy (Import+Export).
LED Row 1 : 8.8.8.8. (M/k)
LED Row 2 : 8.8.8.8.
LED Row 3 :
LED’s: VAh, TOT
xi. Page11: Total Run Hours (Import+Export).
LED Row 1 : run.h
LED Row 2 : 8.8.8.8.
LED Row 3 :
LED’s: TOT
AE-9000 User Manual
7
xii. Page12: Phase Angle for all three phases.
LED Row 1 : 8.8.8.8.
LED Row 2 : 8.8.8.8.
LED Row 3 : 8.8.8.8.
LED’s: φ, R, Y, B
xiii. Page13: Phasor Angle for all three phases.
LED Row 1 : 8.8.8.8.
LED Row 2 : 8.8.8.8.
LED Row 3 : 8.8.8.8.
LED’s: φ, RY, YB, BR
xiv. Page14: Active Power of all three phases.
LED Row 1 : 8.8.8.8. (M/k)
LED Row 2 : 8.8.8.8. (M/k)
LED Row 3 : 8.8.8.8. (M/k)
LED’s: W, R, Y, B
xv. Page15: Reactive Power of all three phases.
LED Row 1 : 8.8.8.8. (M/k)
LED Row 2 : 8.8.8.8. (M/k)
LED Row 3 : 8.8.8.8. (M/k)
LED’s: VAR, R, Y, B
xvi. Page16: Apparent Power of all three phases.
LED Row 1 : 8.8.8.8. (M/k)
LED Row 2 : 8.8.8.8. (M/k)
LED Row 3 : 8.8.8.8. (M/k)
LED’s: VA, R, Y, B
xvii. Page17: Active Energy (Import).
LED Row 1 : 8.8.8.8.(M/k)
LED Row 2 : 8.8.8.8.
LED Row 3 :
LED’s: Wh, Imp
xviii. Page18: Reactive Energy (Import).
LED Row 1 : 8.8.8.8. (M/k)
AE-9000 User Manual
8
LED Row 2 : 8.8.8.8.
LED Row 3 : LED’s: VArh, Imp
xix. Page19: Apparent Energy (Import).
LED Row 1 : 8.8.8.8. (M/k)
LED Row 2 : 8.8.8.8.
LED Row 3 :
LED’s: VAh, Imp
xx. Page20: Run Hours (Import).
LED Row 1 : run.h
LED Row 2 : 8.8.8.8.
LED Row 3 :
LED’s: Imp
xxi. Page21: Active Energy (Export).
LED Row 1 : 8.8.8.8.(M/k)
LED Row 2 : 8.8.8.8.
LED Row 3 :
LED’s: Wh, Exp
xxii. Page22: Reactive Energy (Export).
LED Row 1 : 8.8.8.8. (M/k)
LED Row 2 : 8.8.8.8.
LED Row 3 :
LED’s: VArh, Exp
xxiii. Page23: Apparent Energy (Export).
LED Row 1 : 8.8.8.8. (M/k)
LED Row 2 : 8.8.8.8.
LED Row 3 :
LED’s: VAh, Exp
xxiv. Page24: Run Hours (Export).
LED Row 1 : run.h
LED Row 2 : 8.8.8.8.
LED Row 3 :
LED’s: Exp
AE-9000 User Manual
9
xxv. Page25: Maximum Demand
LED Row 1 : 8.8.8.8.
LED Row 2 : 8.8.8.8.
LED Row 3 :
LED’s: W, VA
xxvi. Page26: On Hours
LED Row 1 : On.h
LED Row 2 : 8.8.8.8.
LED Row 3 :
The pages can be manually cycled through, by pressing the Navigation Up
and Navigation Down keys in Manual Scroll Mode. The Pages can also be
displayed in auto scroll mode with a scroll rate of 5 sec. per page by default.
The Pages to be displayed in Auto Scroll Mode will be configurable by the
user through Key pad. In manual scroll mode, all pages will be displayed. To
switch from manual scroll mode to auto scroll mode, press the “Right
Navigation”.
3.2.Configure Mode
In the configuration mode, following parameters can be configured to user
selected values. Scroll through the menu using Navigation Up and Navigation
Down keys and press Enter Key to configure the desired parameter. Once
inside the parameter configuration page, user can scroll through the digits
using the Navigation Right key, change the values using Navigation Up and
Navigation Down keys to increment and decrement the value respectively,
and press Enter Key to confirm the value for the selected parameter. Once a
parameter is set, the system goes back to the Configure Mode menu.
i. P h a s e , Single phase. LED Row 1 : PhAS LED Row 2 : 1 Ph.
LED Row 3 :
ii. S t a r connection, Delta connection LED Row 1 : con LED Row 2 : StAr.
LED Row 3 :
iii. CT ratio 1. LED Row 1 : CtPr LED Row 2 : 8.8.8.8.
LED Row 3 : 8.8.8.8
AE-9000 User Manual
10
iv. C T ratio 2.
LED Row 1 : CtSE LED Row 2 : 8.8.8.8.
LED Row 3 : 8.8.8.8
v. P T ratio 1. LED Row 1 : PtPr LED Row 2 : 8.8.8.8.
LED Row 3 : 8.8.8.8
vi. P T ratio 2. LED Row 1 : PtSE LED Row 2 : 8.8.8.8.
LED Row 3 : 8.8.8.8
vii. S cr o l l time. (Min-3 sec to Max-10 sec in 1 sec
steps) LED Row 1 : Scr.t.
LED Row 2 : 8.8.
LED Row 3 :
viii. S et integration time period.(Min.-5 minutes to Max-30 minutes in 1 minute
steps) LED Row 1 : Int.P. LED Row 2 : 8.8.
LED Row 3 :
ix. S e t data logging time period.(Min-1 minute to Max-120 minutes in 1 minute
step) LED Row 1 : LOG.P. LED Row 2 : 8.8.8.
LED Row 3 :
x. RS 48 5 network ID LED Row 1 : n.I.d. LED Row 2 : 8.8 (Hex Value)
LED Row 3 :
xi. R es e t Energies LED Row 1 : rES.E. LED Row 2 : y
LED Row 3 : n
xii. S e t user password. LED Row 1 : PSd. LED Row 2 : 8.8.8.8.
LED Row 3 : 8.8.8.8.
AE-9000 User Manual
11
xiii. S et Date. LED Row 1 : dAtE. LED Row 2 : 8 8.8 8.
LED Row 3 : 8 8 8 8.
xiv. S e t Time. LED Row 1 : tIM. LED Row 2 : 8 8.8 8.
LED Row 3 :
xv. V o l t a ge / Current THD. LED Row 1 : thd LED Row 2 :
LED Row 3 : C
xvi. U AR T baud rate
LED Row 1: b.r.
LED Row 2 : 48.96.
LED Row 3 : 19.38.
3.3. Select Pages for Auto Scroll Display.
In this option, all parameter pages available for display will be shown. The
page number will be shown on LED row1, y/n option on LED row2 and LED
row 3 respectively.
LED Row 1 : <pg. no.>
LED Row 2: on
LED Row 3: off
3.4. Display Previous Energies
In this mode, user can view the Active/Reactive/Apparent Energies, before the
energies w e r e reset. User c a n s c r o l l t h r o u gh the pages using the Up
Navigation and Down Navigation keys.
The pages displayed in this mode are as follows:
i. P a ge 1 : Previous Active Energy (Import).
LED Row 1: Pr.En.
LED Row 2: 8.8.8.8. (M/k)
LED Row 3 : 8.8.8.8.
AE-9000 User Manual
12
LED’s: Wh, Imp
ii. P a ge2 : Previous Reactive Energy (Import).
LED Row 1 : Pr.En.
LED Row 2 : 8.8.8.8. (M/k)
LED Row 3 : 8.8.8.8.
LED’s: VArh, Imp, Lead/Lag
iii. P age3 : Previous Apparent Energy (Import).
LED Row 1 : Pr.En.
LED Row 2 : 8.8.8.8. (M/k)
LED Row 3 : 8.8.8.8.
LED’s: VAh, Imp
iv. P a ge 4 : Previous Run Hours (Import).
LED Row 1 : Pr.En.
LED Row 2 : run.h
LED Row 3 : 8.8.8.8.
LED’s: Imp
v. P a ge 5 : Previous Active Energy(Export).
LED Row 1 : Pr.En.
LED Row 2 : 8.8.8.8. (M/k)
LED Row 3 : 8.8.8.8.
LED’s: Wh, Exp
vi. P a ge 6 : Previous Reactive Energy (Export).
LED Row 1 : Pr.En.
LED Row 2 : 8.8.8.8. (M/k)
LED Row 3 : 8.8.8.8.
LED’s: VArh, Exp
vii. Pa g e 7 : Previous Apparent Energy(Export).
LED Row 1 : Pr.En.
LED Row 2 : 8.8.8.8. (M/k)
LED Row 3 : 8.8.8.8.
LED’s: VAh, Exp
AE-9000 User Manual
13
viii. Page8 : Previous Run Hours (Export).
LED Row 1 : Pr.En.
LED Row 2 : run.h
LED Row 3 : 8.8.8.8.
LED’s: Exp
ix. Pa g e 9 : Previous Total Active Energy (Import + Export).
LED Row 1 : Pr.En.
LED Row 2 : 8.8.8.8. (M/k)
LED Row 3 : 8.8.8.8.
LED’s: Wh, TOT
x. Pa g e 1 0 : Previous Total Reactive Energy (Import+Export).
LED Row 1 : Pr.En.
LED Row 2 : 8.8.8.8. (M/k)
LED Row 3 : 8.8.8.8.
LED’s: VArh, TOT
xi. Pa g e 11 : Previous Total Apparent Energy (Import+Export).
LED Row 1 : Pr.En.
LED Row 2 : 8.8.8.8. (M/k)
LED Row 3 : 8.8.8.8.
LED’s: VAh, TOT
xii. P a ge1 2 : Previous Total Run Hours (Import+Export).
LED Row 1 : Pr.En.
LED Row 2 : run.h
LED Row 3 : 8.8.8.8.
LED’s: TOT
3.5. Testing Mode
Testing mode contains more user selectable options: i. LE D Test ii. M e mo r y Test.
User can scroll to any one option using Navigation Up and Navigation Down
keys, and select the test using Enter key.
i. LE D Test In LED Test, all the display LEDs will light up for 2 seconds, and then will go off for 1 second. After this the system will get back to Testing Mode menu
AE-9000 User Manual
14
page.
ii. M e mo r y Test In memory testing, the data logging memory will be tested, and depending on the result, “Pass” or “Fail” will be displayed on the LEDs for 2 seconds, and
the system will go back to Testing Mode menu.
The Display will be as follows
LED Row 1 : Mry
LED Row 2 : PASS
LED Row 3 :
OR
LED Row 1 : Mry
LED Row 2 : FAIL
LED Row 3 :1/2/3
FAIL 1: BANK 1 fail
FAIL 2: BANK 2 fail
FAIL 3: BOTH bank fail
4. Reference standards
This meter is manufactured according to the following valid standards:
EN 62052-11: 2004 Measurement of electrical energy (a.c.) – general conditions, tests and test
conditions - Part 11: Measuring equipment
EN 62053-21: 2004 Equipments for electrical energy measurement (a.c.) – Special requirements –
Part 21: Static meters for active energy (class 1 and 2)