Top Banner
Hands-On Training ADVANCED MOTOR PROTECTION WITH COMMUNICATION TCU% 53% Avg I 23A Networkable Motor Protection, Control & Energy Monitoring System Publication 0.2/07-11-2012.. All the information provided within this document is property of Carlo Gavazzi & NHP Electrical Engineering Products Pty. Ltd.
51

ADVANCED MOTOR PROTECTION WITH COMMUNICATION · 2013-01-13 · Hands-On Training ADVANCED MOTOR PROTECTION WITH COMMUNICATION TCU% 53% Avg I 23A Networkable Motor Protection, Control

Mar 19, 2020

Download

Documents

dariahiddleston
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: ADVANCED MOTOR PROTECTION WITH COMMUNICATION · 2013-01-13 · Hands-On Training ADVANCED MOTOR PROTECTION WITH COMMUNICATION TCU% 53% Avg I 23A Networkable Motor Protection, Control

Hands-On Training

ADVANCED MOTOR PROTECTION WITH

COMMUNICATION TCU% 53%

Avg I 23A

Networkable Motor Protection,

Control & Energy Monitoring System Publication 0.2/07-11-2012.. All the information provided within this document is property of Carlo Gavazzi & NHP Electrical

Engineering Products Pty. Ltd.

Page 2: ADVANCED MOTOR PROTECTION WITH COMMUNICATION · 2013-01-13 · Hands-On Training ADVANCED MOTOR PROTECTION WITH COMMUNICATION TCU% 53% Avg I 23A Networkable Motor Protection, Control

Hands-On Training Lab

Introduction Welcome to the AmpCom Hands-On Training lab.

AmpCom is a Networkable Motor Protection, Control and Energy Monitoring system that supports

expandable I/O via a modular concept. It supports Modbus Ethernet/TCP and Profibus-DP protocols.

This lab will demonstrate the protection, control and communication features available with

AmpCom. As you complete the exercises in this hands-on session, you will:

Gain experience using AmpCom as a powerful motor protection and control device

Explore the programming and configuration of AmpCom by using the software for different arrangements.

See the benefits of using AmpCom in an intelligent MCC design.

Publication 0.2/07-11-2012.. All the information provided within this document is property of Carlo Gavazzi & NHP Electrical Engineering Products Pty. Ltd.

Page 2

Page 3: ADVANCED MOTOR PROTECTION WITH COMMUNICATION · 2013-01-13 · Hands-On Training ADVANCED MOTOR PROTECTION WITH COMMUNICATION TCU% 53% Avg I 23A Networkable Motor Protection, Control

Hardware This section will list the different components available in the working demos:

DMPU-HMI

Sprecher + Schuh

Contactor

Output LEDs

DMPU-05

Current/Voltage

Measurement Module

HMI Display

DMPU-MBT

Main CPU Module

(Modbus Ethernet/TCP)

Input Control Motor + Load

Simulator

2 x DMPU-R2

I/O Expansion Modules

1 x DMPU-EL

Earth Leakage Module Publication 0.2/07-11-2012.. All the information provided within this document is property of Carlo Gavazzi & NHP Electrical Engineering

Products Pty. Ltd.

Page 3

Page 4: ADVANCED MOTOR PROTECTION WITH COMMUNICATION · 2013-01-13 · Hands-On Training ADVANCED MOTOR PROTECTION WITH COMMUNICATION TCU% 53% Avg I 23A Networkable Motor Protection, Control

Hands-On Training Lab Current/Voltage Measurement Module

This module measures both current (via pass-through) and voltage (voltage inputs are rated to 690V

AC and are available as standard). It also includes two configurable relay outputs. The current and

voltage measurements feedback as well the control of the outputs are done via an RJ11 cable (not

visible in the working demo) to the Main CPU Module. Available in 5A, 10A (split-core) and 65A

versions. Main CPU Module

This module is the brains behind the AmpCom system. It includes a communication port (supports

Modbus Ethernet/TCP or Profibus), 3 x configurable inputs (PTC or Digital) and programming port (to

connect to PC configuration software).

Publication 0.2/07-11-2012.. All the information provided within this document is property of Carlo Gavazzi & NHP Electrical Engineering

Products Pty. Ltd.

Page 4

Page 5: ADVANCED MOTOR PROTECTION WITH COMMUNICATION · 2013-01-13 · Hands-On Training ADVANCED MOTOR PROTECTION WITH COMMUNICATION TCU% 53% Avg I 23A Networkable Motor Protection, Control

I/O Expansion Modules

These modules include 2 x configurable inputs (PTC, PT100 or Digital) and 2 x configurable relay

outputs. They plug into the side of the Main Module and can piggy back up to 10 x expansion

modules.

Up to 10 x expansion modules

Earth Leakage Module

This module allows for sensitive earth leakage current measurement and protection. Connects to the

Main Module or can be piggy backed off any of the I/O Expansion modules.

HMI Display

Fully programmable display to control and monitor the AmpCom system from the front of an MCC

panel.

Please download the AmpCom Technical Catalogue from www.nhp.com.au/AmpCom for a full

selection guide and specification details on the complete range.

Publication 0.2/07-11-2012.. All the information provided within this document is property of Carlo Gavazzi & NHP Electrical Engineering

Products Pty. Ltd.

Page 5

Page 6: ADVANCED MOTOR PROTECTION WITH COMMUNICATION · 2013-01-13 · Hands-On Training ADVANCED MOTOR PROTECTION WITH COMMUNICATION TCU% 53% Avg I 23A Networkable Motor Protection, Control

Hands-On Training Lab

Lab Workshop No. 1 Connecting the working demo to the PC configuration software.

Double click on the Carlo Gavazzi ‘DMPU’ logo .

This will execute the AmpCom PC configuration software. Maximise the window so it takes up the

whole screen.

The software should automatically connect to the AmpCom working demo. You can check this by

looking at the bottom corner of the window and confirming the following message appears:

If this message does not appear, please notify the lab instructor. Publication 0.2/07-11-2012.. All the information provided within this document is property of Carlo Gavazzi & NHP Electrical Engineering

Products Pty. Ltd.

Page 6

Page 7: ADVANCED MOTOR PROTECTION WITH COMMUNICATION · 2013-01-13 · Hands-On Training ADVANCED MOTOR PROTECTION WITH COMMUNICATION TCU% 53% Avg I 23A Networkable Motor Protection, Control

Familiarising yourself with the icons on the main menu screen

Along the top of the window, you will notice several icons: This icon creates a new configuration and lists it in the ‘Configurations’ window.

This icon opens configurations and loads them in the ‘Configurations’ window. This function is

used for configurations not listed in the ‘Configurations’ window (usually a configuration loaded

from another PC). Compatible files will have the ‘.dmpu’ file extension.

This icon will allow you to download configurations to the AmpCom system that are listed in the

‘Configurations’ window. This same icon also allows you to upload configurations from the

AmpCom system and save them in the ‘Configurations’ window.

This icon will allow you to save configurations to a different location on your PC compared to the

default location the software saves files to. Note: Once configurations are created or opened from a

different file location, they are automatically saved to the default location.

This icon is used to modify a configuration. Select a configuration from the ‘Configurations’

window then click on this icon to begin to program your AmpCom device.

This icon will remove configurations in the ‘Configurations’ window and from the default

save location.

Publication 0.2/07-11-2012.. All the information provided within this document is property of Carlo Gavazzi & NHP Electrical Engineering Products Pty. Ltd.

Page 7

Page 8: ADVANCED MOTOR PROTECTION WITH COMMUNICATION · 2013-01-13 · Hands-On Training ADVANCED MOTOR PROTECTION WITH COMMUNICATION TCU% 53% Avg I 23A Networkable Motor Protection, Control

Hands-On Training Lab

This icon will allow you to view a selection of variables and virtual alarms of the connected

AmpCom system. This feature is handy for testing and commissioning to ensure the device is

correctly measuring and activating virtual alarms before it’s connected to the supervisory system.

Just like the ‘Monitoring’ icon, this icon allows you to view the active data-loggers’

stored information in a Excel spread sheet format of the connected AmpCom system. Again handy for

testing and commissioning.

This icon will open another window to allow you perform the following commands to the

connected AmpCom system.

These commands can also be activated through the supervisory system.

This icon will restore the connected AmpCom system to its factory default settings.

This icon will print the selected configuration’s (in the ‘Configurations’ window) saved

parameter sets.

This icon will close down the software.

Publication 0.2/07-11-2012.. All the information provided within this document is property of Carlo Gavazzi & NHP Electrical Engineering

Products Pty. Ltd.

Page 8

Page 9: ADVANCED MOTOR PROTECTION WITH COMMUNICATION · 2013-01-13 · Hands-On Training ADVANCED MOTOR PROTECTION WITH COMMUNICATION TCU% 53% Avg I 23A Networkable Motor Protection, Control

Setting the real-time clock and time zone

Along the top, click on Tools>Clock and time zone

The following window will then appear:

You have the option to manually set the time and date or synchronise with the PC’s time and date.

Click on the ‘Synchronize with PC date and time’ button.

Note: The time and date can also be set via the supervisory system. The DST function allows you to program the Daylight Savings Time. Click the ‘OK’ button.

Publication 0.2/07-11-2012.. All the information provided within this document is property of Carlo Gavazzi & NHP Electrical Engineering

Products Pty. Ltd.

Page 9

Page 10: ADVANCED MOTOR PROTECTION WITH COMMUNICATION · 2013-01-13 · Hands-On Training ADVANCED MOTOR PROTECTION WITH COMMUNICATION TCU% 53% Avg I 23A Networkable Motor Protection, Control

Hands-On Training Lab

Lab Workshop No. 2 Programming a configuration for an AmpCom system

To create a new configuration, click on the icon. You will them be prompted to enter a name for this configuration. Name it ‘AmpCom Lab’ and then

click ‘OK’.

You will now see the ‘AmpCom Lab’ configuration in the ‘Configurations’ window. Make sure this configuration is highlighted then click on the icon to begin to program the

connected AmpCom system.

Publication 0.2/07-11-2012.. All the information provided within this document is property of Carlo Gavazzi & NHP Electrical Engineering

Products Pty. Ltd.

Page 10

Page 11: ADVANCED MOTOR PROTECTION WITH COMMUNICATION · 2013-01-13 · Hands-On Training ADVANCED MOTOR PROTECTION WITH COMMUNICATION TCU% 53% Avg I 23A Networkable Motor Protection, Control

WIZARD a) - Modules Configuration

Once the icon is clicked, the ‘WIZARD a) - Modules Configuration’ window will appear.

In this wizard, you identify the different modules that make up the AmpCom system that is

connected to the software. First select the Main CPU Module - DMPU-MBT.

Publication 0.2/07-11-2012.. All the information provided within this document is property of Carlo Gavazzi & NHP Electrical Engineering

Products Pty. Ltd.

Page 11

Page 12: ADVANCED MOTOR PROTECTION WITH COMMUNICATION · 2013-01-13 · Hands-On Training ADVANCED MOTOR PROTECTION WITH COMMUNICATION TCU% 53% Avg I 23A Networkable Motor Protection, Control

Hands-On Training Lab Select which option/expansion modules are connected to the Main CPU module (DMPU-MBT). Add

these modules in the order from right to left and so they appear the same way as below:

Select the Current/Voltage Measurement Module (DMPU-05) Publication 0.2/07-11-2012.. All the information provided within this document is property of Carlo Gavazzi & NHP Electrical Engineering

Products Pty. Ltd.

Page 12

Page 13: ADVANCED MOTOR PROTECTION WITH COMMUNICATION · 2013-01-13 · Hands-On Training ADVANCED MOTOR PROTECTION WITH COMMUNICATION TCU% 53% Avg I 23A Networkable Motor Protection, Control

Select the Temperature Unit as ‘Celsius”.

This is the unit the PT100 inputs will measure in.

Click the button to resume to the next wizard.

Note: Buttons allow you to move back and forth between the

wizards. Button allows you to save and exit the configuration. Button

will cancel the configuration without saving. WIZARD b) - Communication

This wizard allows you to program the network settings. Since we’re working with the Modbus

Ethernet/TCP the following settings will appear:

Leave these settings as default.

Note: The following setting would appear if the Profibus-DP Main CPU module (DMPU-PRB) was

connected: Publication 0.2/07-11-2012.. All the information provided within this document is property of Carlo Gavazzi & NHP Electrical Engineering

Products Pty. Ltd.

Page 13

Page 14: ADVANCED MOTOR PROTECTION WITH COMMUNICATION · 2013-01-13 · Hands-On Training ADVANCED MOTOR PROTECTION WITH COMMUNICATION TCU% 53% Avg I 23A Networkable Motor Protection, Control

Hands-On Training Lab This wizard also allows you to change the programming port settings. It’s recommended these are left

to the default settings.

Click to proceed to the next wizard. WIZARD c) - DMPU-05 CT and VT parameters

This is where you program the CT ratio. You also have the option to program the VT ratio for higher

voltages. If the DMPU-10 or DMPU-65 were chosen, only the VT ratio setting will appear in this wizard.

The DMPU-05 is designed to be CT driven (with 5A secondary).

In this lab, there are no CTs connected nor are the voltage inputs, so we’ll leave the settings set to

default. Click to proceed to the next wizard.

WIZARD d) - Motor features

This is where you program the motor related parameters. IN [A]: Full load current rating of the motor. Set to ‘1’.

Motor start time [s]: The approximate time the motor takes to reach full speed (load

dependant). Set to ‘5’.

IS49-LR [multiple of IN]: Locked rotor current of the motor. Obtain from the motor

manufacture’s datasheet. Leave the default setting.

ts49-H [s]: Locked rotor time hot. Obtain from the motor manufacture’s datasheet. Leave the

default setting.

ts49-C [s]: Locked rotor time cold. Obtain from the motor manufacture’s datasheet. Leave the

default setting.

k49: Motor service factor. Obtain from the motor manufacture’s datasheet. Leave the

default setting.

Publication 0.2/07-11-2012. All the information provided within this document is property of Carlo Gavazzi & NHP Electrical Engineering

Products Pty. Ltd.

Page 14

Page 15: ADVANCED MOTOR PROTECTION WITH COMMUNICATION · 2013-01-13 · Hands-On Training ADVANCED MOTOR PROTECTION WITH COMMUNICATION TCU% 53% Avg I 23A Networkable Motor Protection, Control

K49-R [s]: Motor cool time during run. Obtain from the motor manufacture’s datasheet.

Leave the default setting.

K49-S [s]: Motor cool time while the motor is stopped. Obtain from the motor manufacture’s

datasheet. Leave the default setting. If any of the following settings cannot be obtained, or are not critical to your process,

they can be programmed based on a pre-defined trip class to determine the thermal capacity of your

motor.

Publication 0.2/07-11-2012. All the information provided within this document is property of Carlo Gavazzi & NHP Electrical Engineering

Products Pty. Ltd.

Page 15

Page 16: ADVANCED MOTOR PROTECTION WITH COMMUNICATION · 2013-01-13 · Hands-On Training ADVANCED MOTOR PROTECTION WITH COMMUNICATION TCU% 53% Avg I 23A Networkable Motor Protection, Control

Hands-On Training Lab Alternatively, if the following parameters are programmed,

but the following parameters cannot be obtained, you can click on the button to estimate these unknown values.

For this lab, click on the button (most common setting for motors).

Click to proceed to the next wizard.

Publication 0.2/07-11-2012. All the information provided within this document is property of Carlo Gavazzi & NHP Electrical Engineering

Products Pty. Ltd.

Page 16

Page 17: ADVANCED MOTOR PROTECTION WITH COMMUNICATION · 2013-01-13 · Hands-On Training ADVANCED MOTOR PROTECTION WITH COMMUNICATION TCU% 53% Avg I 23A Networkable Motor Protection, Control

Lab Workshop No. 3 Programming the Input and Output logic, enabling ANSI protection and instantaneous

warning/protection functions in WIZARD e) - Connections.

There are several ways you can define the behaviour of the AmpCom system.

Pre-defined configurations

The software includes a range of pre-defined configurations for different motor starter types:

Click on the button to view them:

Select DOL starter then click on the button. Publication 0.2/07-11-2012. All the information provided within this document is property of Carlo Gavazzi & NHP Electrical Engineering

Products Pty. Ltd.

Page 17

Page 18: ADVANCED MOTOR PROTECTION WITH COMMUNICATION · 2013-01-13 · Hands-On Training ADVANCED MOTOR PROTECTION WITH COMMUNICATION TCU% 53% Avg I 23A Networkable Motor Protection, Control

Hands-On Training Lab Next, the following window will appear:

This window requires you to assign the inputs and outputs to your preferred method to control the

DOL starter.

The inputs can be assigned to either the digital inputs available with the Main CPU module, I/O

expansion modules, Earth Leakage module, or combination of all.

The output can be assigned to any of the outputs available on the Current/Voltage Measurement

module or the I/O expansion module.

Publication 0.2/07-11-2012. All the information provided within this document is property of Carlo Gavazzi & NHP Electrical Engineering

Products Pty. Ltd.

Page 18

Page 19: ADVANCED MOTOR PROTECTION WITH COMMUNICATION · 2013-01-13 · Hands-On Training ADVANCED MOTOR PROTECTION WITH COMMUNICATION TCU% 53% Avg I 23A Networkable Motor Protection, Control

Click on and from the drop down assign this output to

This output is 15/18 on the Current/Voltage Measurement module and controls the coil on the

upstream Sprecher + Schuh contactor coil.

Click on and from the drop down assign this input to

This input will be acting as a start command for the DOL starter via the DMPU-R2 A-1 pushbutton on the

working demo. Publication 0.2/07-11-2012. All the information provided within this document is property of Carlo Gavazzi & NHP Electrical Engineering

Products Pty. Ltd.

Page 19

Page 20: ADVANCED MOTOR PROTECTION WITH COMMUNICATION · 2013-01-13 · Hands-On Training ADVANCED MOTOR PROTECTION WITH COMMUNICATION TCU% 53% Avg I 23A Networkable Motor Protection, Control

Hands-On Training Lab

Do the same thing for Local Stop and Latch Reset and assign them to 1.R2.2 and 3.EL.1 respectively

from the drop down. 1.R2.2 is the DMPU-R2 A-2 pushbutton and 3.EL.1 is the DMPU-EL C-1

pushbutton on the working demo. Click ‘OK’.

The following function block diagram will appear in the ‘Connections’ window:

This pre-defined configuration automatically enables the ‘Thermal Image 49’ (overload protection) and

the ‘I IMB%’ (current imbalance protection) ANSI protection functions. You have successfully implemented a DOL Starter pre-defined configuration.

Publication 0.2/07-11-2012. All the information provided within this document is property of Carlo Gavazzi & NHP Electrical Engineering

Products Pty. Ltd.

Page 20

Page 21: ADVANCED MOTOR PROTECTION WITH COMMUNICATION · 2013-01-13 · Hands-On Training ADVANCED MOTOR PROTECTION WITH COMMUNICATION TCU% 53% Avg I 23A Networkable Motor Protection, Control

Building a Custom Configuration and saving it as a Pre-Defined Configuration

Highlight the pre-defined configuration by holding down the left mouse button and hovering over all

the function blocks. Then push the DEL button on the keyboard to remove this configuration.

These following steps will highlight how to build a custom DOL starter with the various function

blocks available. Along the side you will notice folders group like the following:

Inputs: Contains the available inputs from the AmpCom system (amount vary depending how

they’re defined in WIZARD a)) and 9 x network inputs.

Note: These inputs can be used to identify when and how to alter the logic’s behaviour when there is an internal fault with the AmpCom system.

Instantaneous variables: Contains all the measurable variables through the AmpCom system. These

individual blocks can be defined to activate as an alarm and force outputs in the AmpCom system to

change state or display alarm signals within the supervisory system.

ANSI: Use these blocks to program and assign the ANSI protection functions to force outputs in the

AmpCom system to change state and display alarm signals through the supervisory system. Counters: Two counters are available to be used within a custom configuration.

Timers: Two on-delay timers are available to be used within a custom configuration.

Internal counters: Starts per hour, estimated time before trip and estimated time before restart

counters can be programed and implemented within a custom configuration.

Digital outputs: Contains the available relay outputs from the AmpCom system (amount varies

depending how they’re defined in WIZARD a)) and ‘Latch Reset’ function block.

Publication 0.2/07-11-2012.. All the information provided within this document is property of Carlo Gavazzi & NHP Electrical Engineering Products Pty. Ltd.

Page 21

Page 22: ADVANCED MOTOR PROTECTION WITH COMMUNICATION · 2013-01-13 · Hands-On Training ADVANCED MOTOR PROTECTION WITH COMMUNICATION TCU% 53% Avg I 23A Networkable Motor Protection, Control

Hands-On Training Lab Note: When the ‘Latch Reset’ function is enabled, it will reset any virtual alarm that is enabled and

latched but no longer active. A virtual alarm is any of the following function block types: Inputs

Instantaneous Variables

ANSI

Counters

Timers

Internal Counters

Logic Functions

Logic functions: Contains truth tables to alter the behaviour of the virtual alarms using ‘AND’, ‘OR’ and

‘NOT’ gate logic.

Double click on the ‘Inputs’ folder and by holding down the left mouse button, drag across the

‘Virtual.1’ function block. The following window will appear: Type ‘Enable Remote Control’ in the ‘Label 1’ section.

Publication 0.2/07-11-2012. All the information provided within this document is property of Carlo Gavazzi & NHP Electrical Engineering

Products Pty. Ltd.

Page 22

Page 23: ADVANCED MOTOR PROTECTION WITH COMMUNICATION · 2013-01-13 · Hands-On Training ADVANCED MOTOR PROTECTION WITH COMMUNICATION TCU% 53% Avg I 23A Networkable Motor Protection, Control

Select ‘active when closed’ from the ‘Type of Al. 1’ drop down.

Type ‘0’ in the ‘ON delay of Al. 1’ section.

Please ensure the settings and information entered looks like the below:

Click ‘OK’. This input has been set up to enable remote or local control via a supervisory system.

We’ll demonstrate this later.

Publication 0.2/07-11-2012.. All the information provided within this document is property of Carlo Gavazzi & NHP Electrical Engineering

Products Pty. Ltd.

Page 23

Page 24: ADVANCED MOTOR PROTECTION WITH COMMUNICATION · 2013-01-13 · Hands-On Training ADVANCED MOTOR PROTECTION WITH COMMUNICATION TCU% 53% Avg I 23A Networkable Motor Protection, Control

Hands-On Training Lab

Drag ‘Virtual.2’ to the window just below the input you’ve have just configured:

Ensure the data is assigned and entered as the following:

Click ‘OK’. This input will act as a start network command for the DOL starter when remote control is enabled (through the supervisory system).

Drag ‘1.R2.1’ function block to the window just below the inputs you’ve have just configured:

Publication 0.2/07-11-2012. All the information provided within this document is property of Carlo Gavazzi & NHP Electrical Engineering Products Pty. Ltd.

Page 24

Page 25: ADVANCED MOTOR PROTECTION WITH COMMUNICATION · 2013-01-13 · Hands-On Training ADVANCED MOTOR PROTECTION WITH COMMUNICATION TCU% 53% Avg I 23A Networkable Motor Protection, Control

Ensure the data is assigned and entered as the following:

Click ‘OK’. This input will act as a start pushbutton command for the DOL starter when local control is enabled (through the supervisory system).

Double click on the ‘Logic Functions’ folder and drag across the ‘Truth table 1’ function block.

A message will pop up and prompt you to derive the logic in a ‘graph’ or ‘truth table’ format’. Click

‘graph’.

Type ‘Enable Start Logic’ in the ‘Label 4’ section and click ‘OK’. We’ll come back to this function block to derive the logic.

Double click on the ‘Counters’ folder and drag across the ‘Counter 1’ function block.

Ensure the data is assigned and entered as the following:

Click ‘OK’.

Publication 0.2/07-11-2012. All the information provided within this document is property of Carlo Gavazzi & NHP Electrical Engineering Products Pty. Ltd.

Page 25

Page 26: ADVANCED MOTOR PROTECTION WITH COMMUNICATION · 2013-01-13 · Hands-On Training ADVANCED MOTOR PROTECTION WITH COMMUNICATION TCU% 53% Avg I 23A Networkable Motor Protection, Control

Hands-On Training Lab

The following functions blocks will be used to define the ‘start’ logic for a DOL starter. More on this later.

Under the ‘Inputs’ folder, drag across the ‘Virtual.3’ function block.

Ensure the data is assigned and entered as the following:

Click ‘OK’.

This input will act as a stop network command for the DOL starter when remote control is enabled (through the supervisory system).

Publication 0.2/07-11-2012. All the information provided within this document is property of Carlo Gavazzi & NHP Electrical Engineering

Products Pty. Ltd.

Page 26

Page 27: ADVANCED MOTOR PROTECTION WITH COMMUNICATION · 2013-01-13 · Hands-On Training ADVANCED MOTOR PROTECTION WITH COMMUNICATION TCU% 53% Avg I 23A Networkable Motor Protection, Control

Drag across the ‘1.R2.2’ function block.

Ensure the data is assigned and entered as the following:

Click ‘OK’.

This input will act as a stop pushbutton command for a DOL starter when local control is enabled (through the supervisory system).

Under the ‘Logic functions’ folder, drag across the ‘Truth Table 2’ function block.

Again select ‘graph’, type ‘Enable Stop Logic’ and click ‘OK’.

Double click on the ‘ANSI’ folder and drag across the ‘Thermal Image 49’ function block.

You will notice this window contains the same parameter settings as the ‘Wizard d)’ section. Type

‘TCU % Trip’ in the ‘Label 9’ section, leave the rest of the settings as they are and click ‘OK’.

Publication 0.2/07-11-2012. All the information provided within this document is property of Carlo Gavazzi & NHP Electrical Engineering Products Pty. Ltd.

Page 27

Page 28: ADVANCED MOTOR PROTECTION WITH COMMUNICATION · 2013-01-13 · Hands-On Training ADVANCED MOTOR PROTECTION WITH COMMUNICATION TCU% 53% Avg I 23A Networkable Motor Protection, Control

Hands-On Training Lab

Under the ‘Inputs’ folder, drag across the ‘Main.1’ function block.

Unlike the pushbutton and network inputs, set the ‘Alarm 1 enable’ from ‘Enabled’ to ‘Enabled and

Latched’.

Type ‘Remote Trip’ next in the ‘Label ‘10’ section. Ensure the rest of the data is assigned and

entered as the following:

Click ‘OK’.

This input has been set up to act as a remote trip. This could be an output from a field device such as a

limit or vibration switch.

Publication 0.2/07-11-2012. All the information provided within this document is property of Carlo Gavazzi & NHP Electrical Engineering Products Pty. Ltd.

Page 28

Page 29: ADVANCED MOTOR PROTECTION WITH COMMUNICATION · 2013-01-13 · Hands-On Training ADVANCED MOTOR PROTECTION WITH COMMUNICATION TCU% 53% Avg I 23A Networkable Motor Protection, Control

The following function blocks will define the ‘stop’ logic for a DOL starter. We’ll come back to

this later.

Under the ‘Inputs’ folder, drag across the ‘Virtual.4’ function block.

Ensure the data is assigned and entered as the following:

Click ‘OK’.

This input will act as a reset network command for the DOL starter when remote control is enabled (through the supervisory system).

Publication 0.2/07-11-2012. All the information provided within this document is property of Carlo Gavazzi & NHP Electrical Engineering Products Pty. Ltd.

Page 29

Page 30: ADVANCED MOTOR PROTECTION WITH COMMUNICATION · 2013-01-13 · Hands-On Training ADVANCED MOTOR PROTECTION WITH COMMUNICATION TCU% 53% Avg I 23A Networkable Motor Protection, Control

Hands-On Training Lab

Drag across the ‘3.EL.1’ function block.

Ensure the data is assigned and entered as the following:

Click ‘OK’.

This input will act as a stop pushbutton command for a DOL starter when local control is enabled (through the supervisory system).

Under the ‘Logic functions’ folder, drag across the ‘Truth Table 3’ function block.

Again select ‘graph’, type ‘Enable Reset Logic’ and click ‘OK’.

The following function blocks will define the ‘stop’ logic for a DOL starter. We’ll come back to

this later.

Publication 0.2/07-11-2012. All the information provided within this document is property of Carlo Gavazzi & NHP Electrical Engineering Products Pty. Ltd.

Page 30

Page 31: ADVANCED MOTOR PROTECTION WITH COMMUNICATION · 2013-01-13 · Hands-On Training ADVANCED MOTOR PROTECTION WITH COMMUNICATION TCU% 53% Avg I 23A Networkable Motor Protection, Control

Double click on the ‘Digital outputs’ folder and drag across the ‘Main.1’ function block. Ensure ‘NO’ is selected as the ‘working mode’, label it as ‘Contactor’ and click ‘OK’. This output will be controlling the contactor operation in the DOL starter. Under the ‘Digital outputs’ folder, drag across the ‘Latch reset’ function block. Click ‘OK’. This will be used to reset any alarms that are enabled and latched but no longer active. Ensure the function blocks are re-arranged as the following:

Publication 0.2/07-11-2012. All the information provided within this document is property of Carlo Gavazzi & NHP Electrical Engineering Products Pty. Ltd.

Page 31

Page 32: ADVANCED MOTOR PROTECTION WITH COMMUNICATION · 2013-01-13 · Hands-On Training ADVANCED MOTOR PROTECTION WITH COMMUNICATION TCU% 53% Avg I 23A Networkable Motor Protection, Control

Hands-On Training Lab To link the function blocks, click on the black bold line with the left mouse button, hold it down and

drag it to another function block’s black bold line.

Note: Function blocks with the black bold line to the right of the function block can only be linked to

function blocks with the black bold line to the left of the function block.

E.g.

Link the ‘Enable Remote Control’ function block to ‘in 1’ of the ‘Enable Start Logic’ function block.

Then link ‘Network Start Input’ and ‘Start Pushbutton Input’ function blocks to ‘in 2’ and ‘in 3’ of the

‘Enable Start Logic’ function block respectively.

Publication 0.2/07-11-2012. All the information provided within this document is property of Carlo Gavazzi & NHP Electrical Engineering Products Pty. Ltd.

Page 32

Page 33: ADVANCED MOTOR PROTECTION WITH COMMUNICATION · 2013-01-13 · Hands-On Training ADVANCED MOTOR PROTECTION WITH COMMUNICATION TCU% 53% Avg I 23A Networkable Motor Protection, Control

Link the ‘Enable Stop Logic’ function block’s output (bold line to the right of this function block) to ‘in 4’ of the ‘Enable Start Logic’ function block.

Proceed to complete the following links: Link ‘Enable Remote Control’ to ‘in 1’ of ‘Enable Stop Logic’. Link ‘Network Stop Input to ‘in 2’ of ‘Enable Stop Logic’. Link ‘Stop Pushbutton Input’ to ‘in 3’ of ‘Enable Stop Logic’. Link ‘TCU % Trip’ to ‘in 4’ of ‘Enable Stop Logic’. Link ‘Remote Trip’ to ‘in 5’ of ‘Enable Stop Logic’.

Publication 0.2/07-11-2012. All the information provided within this document is property of Carlo Gavazzi & NHP Electrical Engineering Products Pty. Ltd.

Page 33

Page 34: ADVANCED MOTOR PROTECTION WITH COMMUNICATION · 2013-01-13 · Hands-On Training ADVANCED MOTOR PROTECTION WITH COMMUNICATION TCU% 53% Avg I 23A Networkable Motor Protection, Control

Hands-On Training Lab Proceed to link: ‘Enable Start Logic’ output to ‘act’ of ‘Motor On’. ‘Enable Stop Logic’ output to ‘rst’ of ‘Motor On’. ‘Motor On’ output to ‘out 1’ of ‘Contactor’. ‘Enable Remote Control’ to ‘in 1’ of ‘Enable Reset Logic’. ‘Network Reset Input’ to ‘in 2’ of ‘Enable Reset Logic’. ‘Reset Pushbutton Input’ to ‘in 3’ of ‘Enable Reset Logic’. ‘Enable Reset Logic’ output to ‘rst’ of ‘Latch Reset’.

Publication 0.2/07-11-2012. All the information provided within this document is property of Carlo Gavazzi & NHP Electrical Engineering Products Pty. Ltd.

Page 34

Page 35: ADVANCED MOTOR PROTECTION WITH COMMUNICATION · 2013-01-13 · Hands-On Training ADVANCED MOTOR PROTECTION WITH COMMUNICATION TCU% 53% Avg I 23A Networkable Motor Protection, Control

Ensure your configuration matches the following:

Now that all the function blocks are linked, the ‘Truth Table’ logic needs to be set. Right click on the ‘Enable Start Logic’ truth table function block. Expand the window and ensure the logic is set as per the following:

Publication 0.2/07-11-2012. All the information provided within this document is property of Carlo Gavazzi & NHP Electrical Engineering Products Pty. Ltd.

Page 35

Page 36: ADVANCED MOTOR PROTECTION WITH COMMUNICATION · 2013-01-13 · Hands-On Training ADVANCED MOTOR PROTECTION WITH COMMUNICATION TCU% 53% Avg I 23A Networkable Motor Protection, Control

Hands-On Training Lab Can you work out how the logic being performed? If not, please ask the lab instructor to explain. Click ‘OK’. Right click on the ‘Enable Stop Logic’ truth table function block. Expand the window and ensure the logic is set as per the following:

Again see if you can identify how the logic is defined. Finally, right click on the ‘Enable Reset Logic’ function block and set the logic as per the following: Click ‘OK’.

Publication 0.2/07-11-2012. All the information provided within this document is property of Carlo Gavazzi & NHP Electrical Engineering

Products Pty. Ltd.

Page 36

Page 37: ADVANCED MOTOR PROTECTION WITH COMMUNICATION · 2013-01-13 · Hands-On Training ADVANCED MOTOR PROTECTION WITH COMMUNICATION TCU% 53% Avg I 23A Networkable Motor Protection, Control

You can now save this configuration as a ‘pre-defined configuration’ for later use. Click on the

button in the bottom right hand corner. The following window will appear:

Click on the , label it ‘Special DOL’ and click ‘OK’. You have successfully created a custom pre-defined configuration. Click the ‘Close’ button.

Building a Custom Configuration from a Pre-defined Configuration

Highlight the custom configuration by holding down the left mouse key and hovering over all

the function blocks. Then push the DEL button on the keyboard to remove this configuration.

Click on the button again, select ‘Special DOL’ from the list and then

click on the button. The window on the following page will appear:

Publication 0.2/07-11-2012. All the information provided within this document is property of Carlo Gavazzi & NHP Electrical Engineering Products Pty. Ltd.

Page 37

Page 38: ADVANCED MOTOR PROTECTION WITH COMMUNICATION · 2013-01-13 · Hands-On Training ADVANCED MOTOR PROTECTION WITH COMMUNICATION TCU% 53% Avg I 23A Networkable Motor Protection, Control

Hands-On Training Lab Note: Expand the window to view the complete configuration

Just as the inputs and outputs were assigned for the ‘DOL starter’ pre-defined configuration

earlier in the lab, we need to do the same with this custom pre-defined configuration. Please assign as per the following: Enable Remote Control – Virtual .1 Network Start Input – Virtual.2 Start Pushbutton Input – 1.R2.1

Network Stop Input – Virtual.3

Stop Pushbutton Input – 1.R2.2

Remote Trip – Main.1

Network Reset Input – Virtual.4

Publication 0.2/07-11-2012. All the information provided within this document is property of Carlo Gavazzi & NHP Electrical Engineering Products Pty. Ltd.

Page 38

Page 39: ADVANCED MOTOR PROTECTION WITH COMMUNICATION · 2013-01-13 · Hands-On Training ADVANCED MOTOR PROTECTION WITH COMMUNICATION TCU% 53% Avg I 23A Networkable Motor Protection, Control

Reset Pushbutton Input – 3.EL.1

Contactor – Main.1

Click ‘OK’.

You will notice this pre-defined configuration is the same configuration you created earlier.

For this configuration, we want to customise it by performing the following:

Double click on the ‘ANSI’ folder and drag across ‘I IMB%’.

Type ‘Current Imbalance Trip’ in the ‘Label 14’ section, leave the rest of the settings as they are and

click ‘OK’.

Note: The default settings for ‘I IMB %’ are if the current imbalance exceeds 50% for a delay time of

3 seconds, this ANSI alarm will activate.

Link the ‘Current Imbalance Trip’ ANSI function block to ‘in 6’ of the ‘Enable Stop Logic’ truth table

function block.

‘in 6’ isn’t defined within the ‘Enable Stop Logic’ truth table function block. Right click on the ‘Enable

Stop Logic’ function block.

Publication 0.2/07-11-2012. All the information provided within this document is property of Carlo Gavazzi & NHP Electrical Engineering Products Pty. Ltd.

Page 39

Page 40: ADVANCED MOTOR PROTECTION WITH COMMUNICATION · 2013-01-13 · Hands-On Training ADVANCED MOTOR PROTECTION WITH COMMUNICATION TCU% 53% Avg I 23A Networkable Motor Protection, Control

Hands-On Training Lab Drag across ‘IN 6’ and link it to the left hand side of the ‘OR’ function block (see below).

Click ‘OK’. Under the ‘Logic Functions’ folder, drag across ‘Truth Table 4’ function block. This time, select ‘truth table’. Label it ‘Enable Stop Logic 2’ and then click OK. Under the ANSI folder, drag across the ‘Leakage Current 64EL’ function block. Set the parameters as per below:

Publication 0.2/07-11-2012. All the information provided within this document is property of Carlo Gavazzi & NHP Electrical Engineering Products Pty. Ltd.

Page 40

Page 41: ADVANCED MOTOR PROTECTION WITH COMMUNICATION · 2013-01-13 · Hands-On Training ADVANCED MOTOR PROTECTION WITH COMMUNICATION TCU% 53% Avg I 23A Networkable Motor Protection, Control

Under the ‘Inputs’ folder, drag across the 2.R2.1 function block.

Ensure the data is assigned and entered as the following:

This input has been configured as a PT100 RTD input. It has been configured so when the input in

measuring above 60°C, it will activate this alarm. The alarm will latch and cannot be reset until the temperature is below 45°C (ensure the ‘alarm enable’ is ‘Enabled and Latched’). This is how the ‘UP Control’ input type is defined.

Click ‘OK’.

Publication 0.2/07-11-2012. All the information provided within this document is property of Carlo Gavazzi & NHP Electrical Engineering Products Pty. Ltd.

Page 41

Page 42: ADVANCED MOTOR PROTECTION WITH COMMUNICATION · 2013-01-13 · Hands-On Training ADVANCED MOTOR PROTECTION WITH COMMUNICATION TCU% 53% Avg I 23A Networkable Motor Protection, Control

Hands-On Training Lab Note: Up Control: When the measured value exceeds the

‘Over Level’ and after the ‘ON delay’ time expires, this

alarm will activate. The alarm will not reset until the

measured valued drops below the ‘Under Level’. Down Control: This input type is the reverse of Up

Control. When the measured value drop below the

‘Under Level’ and after the ‘ON delay’ time expires, this

alarm will activate. This alarm will not reset until the

measure value exceeds the ‘Over Level’.

In Control: This alarm will activate when the measured

value is in between the ‘Under’ and ‘Over’ levels and after

the ‘ON delay’ time expires. This alarm will reset once the

measured value is above the ‘Over Level’ or below the

‘Under Level’.

Out Control: This input type is the reverse of ‘In Control’.

This alarm will activate when the measured value is

outside the ‘Under Level’ or ‘Over Level’ and after the

‘ON delay’ time expires. This alarm will reset only when

the measured value is above the ‘Under Level’ and

below the ‘Over Level’. These ‘Input types’ are available for all instantaneous variables and PT100 inputs’.

Publication 0.2/07-11-2012. All the information provided within this document is property of Carlo Gavazzi & NHP Electrical Engineering Products Pty. Ltd.

Page 42

Page 43: ADVANCED MOTOR PROTECTION WITH COMMUNICATION · 2013-01-13 · Hands-On Training ADVANCED MOTOR PROTECTION WITH COMMUNICATION TCU% 53% Avg I 23A Networkable Motor Protection, Control

Drag across the 2.R2.2 function block.

Ensure the data is assigned and entered as the following:

This time, the ‘Input type’ has been programmed for ‘Out Control’. If the measured temperature

drops below -5°C or exceeds 60°C, this alarm will activate.

Click ‘OK’. The ‘Enable Stop Logic 2’ truth table function block still needs to be defined. It will be defined so it’s coordinated with the ‘Enable Stop Logic’ function block. Link the following: ‘Enable Stop Logic’ output to ‘in 1’ of ‘Enable Stop Logic 2’ ‘Earth Leakage Trip’ to ‘in 2’ of ‘Enable Stop Logic 2’ ‘PT100 Input 1’ to ‘in 3’ of ‘Enable Stop Logic 2’ ‘PT100 Input 2’ to ‘in 4’ of ‘Enable Stop Logic 2’ ‘Enable Stop Logic 2’ output to ‘rst’ of ‘Motor On’ Left click on link between the ‘Enable Stop Logic’ output and ‘rst’ of ‘Motor On’ and then press the DEL button on the keyboard.

Publication 0.2/07-11-2012. All the information provided within this document is property of Carlo Gavazzi & NHP Electrical Engineering

Products Pty. Ltd.

Page 43

Page 44: ADVANCED MOTOR PROTECTION WITH COMMUNICATION · 2013-01-13 · Hands-On Training ADVANCED MOTOR PROTECTION WITH COMMUNICATION TCU% 53% Avg I 23A Networkable Motor Protection, Control

Hands-On Training Lab Left click on link between the ‘Enable Stop Logic’ output and ‘in 4’ of ‘Enable Start Logic’ and then press the DEL button on the keyboard. Link ‘Enable Stop Logic 2’ output to ‘in 4’ of ‘Enable Start Logic’. Right click ‘Enable Start Logic’. You will notice ‘IN 4’ has been replaced by ‘IN 6’. The truth tables will default an input to ‘IN 6’ when it’s deleted from the truth table in the Connections window. Click on ‘IN 6’ and press DEL on the keyboard. Drag across ‘IN 4’ and connect it to the same ‘NOT’ function block ‘IN 6’ was just connected to. Right click on ‘Enable Stop Logic 2’.

For this ‘function block’ we set the logic in a truth table format. Set the all the ‘OUT’ values to ‘1’

(except the first ‘OUT’ value) by clicking on it. Clicking on the ‘OUT’ values toggles them from ‘0’ to ‘1’

and vice versa.

Click ‘OK’.

It is easier and recommended to use the ‘graph’ method to program the ‘truth table’ function blocks.

However, the ‘truth table’ method is also available if this method is preferred.

Click .

You have successfully built a custom configuration from a pre-defined configuration.

Publication 0.2/07-11-2012. All the information provided within this document is property of Carlo Gavazzi & NHP Electrical Engineering Products Pty. Ltd.

Page 44

Page 45: ADVANCED MOTOR PROTECTION WITH COMMUNICATION · 2013-01-13 · Hands-On Training ADVANCED MOTOR PROTECTION WITH COMMUNICATION TCU% 53% Avg I 23A Networkable Motor Protection, Control

Lab Workshop No. 4 Downloading a configuration to an AmpCom system.

Ensure the working demo is still connected to the software by confirming the following is present:

Ensure the saved ‘AmpCom Lab’ configuration listed in the ‘Configurations window’ is highlighted.

Click on the icon.

Select the ‘Export to device’. A warning message may appear - Click ‘OK’.

The software will take a few moments to download the configuration to the working demo.

You have successfully downloaded a configuration the AmpCom system.

Testing and monitoring an AmpCom system with the configuration software.

To view and test that the configuration you just downloaded to the AmpCom system, click on the

icon. The window on the following page will appear:

Publication 0.2/07-11-2012. All the information provided within this document is property of Carlo Gavazzi & NHP Electrical Engineering

Products Pty. Ltd.

Page 45

Page 46: ADVANCED MOTOR PROTECTION WITH COMMUNICATION · 2013-01-13 · Hands-On Training ADVANCED MOTOR PROTECTION WITH COMMUNICATION TCU% 53% Avg I 23A Networkable Motor Protection, Control

Hands-On Training Lab Publication 0.2/07-11-2012. All the information provided within this document is property of Carlo Gavazzi & NHP Electrical Engineering

Products Pty. Ltd.

Page 46

Page 47: ADVANCED MOTOR PROTECTION WITH COMMUNICATION · 2013-01-13 · Hands-On Training ADVANCED MOTOR PROTECTION WITH COMMUNICATION TCU% 53% Avg I 23A Networkable Motor Protection, Control

Along the top, you will notice there are variables grouped as ‘Current’, ‘Voltage’, ‘Power’, ‘Digital

Temperature’ and ‘Operating Values’.

Feel free to view how each tab is structured.

For this lab, we’ll be only focusing on the ‘Current’ and ‘Digital Temperature’ tabs.

Along the right hand side, you will notice all the virtual alarms that have been programmed to the

AmpCom system.

Publication 0.2/07-11-2012. All the information provided within this document is property of Carlo Gavazzi & NHP Electrical Engineering

Products Pty. Ltd.

Page 47

Page 48: ADVANCED MOTOR PROTECTION WITH COMMUNICATION · 2013-01-13 · Hands-On Training ADVANCED MOTOR PROTECTION WITH COMMUNICATION TCU% 53% Avg I 23A Networkable Motor Protection, Control

Hands-On Training Lab Before we begin to test, ensure the following is set for the ‘Control Inputs’ on the working demo:

DMPU main module’s switch No. 1 is in the down position. Ensure both DMPU-R2 B dials and the DMPU-EL C dial are at the 9 o’clock position.

Please also ensure the following is set for the ‘Motor + Load Simulator’ on the working demo

Ensure the U, V & W dials are in the right most positions.

Ensure the LOAD dial on the Motor + Load simulator is in the left most position.

Press the DMPU-EL C input 2 once.

Publication 0.2/07-11-2012. All the information provided within this document is property of Carlo Gavazzi & NHP Electrical Engineering

Products Pty. Ltd.

Page 48

Page 49: ADVANCED MOTOR PROTECTION WITH COMMUNICATION · 2013-01-13 · Hands-On Training ADVANCED MOTOR PROTECTION WITH COMMUNICATION TCU% 53% Avg I 23A Networkable Motor Protection, Control

Click on the ‘Current’ tab within the ‘Monitoring’ window.

Push the DMPU-R2 A input 1. You will notice the following:

The contactor closes LED 1 below the DMPU-05 turns on ‘Motor ON’ virtual alarm become active

To stop the motor, push the DMPU-R2 A input 2. This time you will notice:

The contactor opens LED 1 below the DMPU-05 turns off ‘Motor ON’ virtual alarm become inactive

Start the motor again and begin to rotate the LOAD dial in a clockwise rotation. Rotate it to the 3 o’clock

position. You will begin to see line currents I1, I2 & I3 to increase as well as the average current I+.

You will also notice the TCU % begin to increase. This value represents the ‘Thermal Capacity

Utilised’ of the motor connected. Once it reaches 100%, it will activate the Thermal Image virtual alarm

and consequently drop out the contactor.

Move the LOAD dial to the right most position. The current now being drawn should be around 50A, the

TCU% will rapidly increase and you will notice the following

TCU % Trip virtual alarm will activate

Enable Stop Logic and Enable Stop Logic 2 virtual alarms will activate

Motor On virtual alarm will deactivate Contactor will drop out LED 1 below the DMPU-05 turns off

To start the motor again, we need to reset these virtual alarms. Before we do though, rotate the

LOAD dial to the left most position again.

Push the DMPU-EL C input 2 to reset all the alarms. You will notice all the virtual alarms deactivate.

To simulate a remote trip, push the start button, then move the DMPU main module input 1 switch

in the up direction. You will notice the contactor drop out and the Remote Trip virtual alarm

activate.

Move the switch in the down direction and reset the fault.

To simulate a current imbalance fault, push start, and begin to move the W dial in the anti-clockwise

direction until you read a value > 50% next to IIMB. You will notice after three seconds, the contactor

drops out again. Which virtual alarm is active?

Publication 0.2/07-11-2012. All the information provided within this document is property of Carlo Gavazzi & NHP Electrical Engineering

Products Pty. Ltd.

Page 49

Page 50: ADVANCED MOTOR PROTECTION WITH COMMUNICATION · 2013-01-13 · Hands-On Training ADVANCED MOTOR PROTECTION WITH COMMUNICATION TCU% 53% Avg I 23A Networkable Motor Protection, Control

Hands-On Training Lab

You can also view the temperature feedback values from the PT100 inputs by clicking on the

Digital/Temperature tab. Rotate the DMPU-R2 B input 1 dial in the anti-clockwise direction. You will

notice the temperature begin to increase and once you exceed 60, the PT100 Input 1 virtual alarm

will activate.

You have successfully tested and monitored values from an AmpCom system using the configuration software.

Testing and monitoring an AmpCom system with over a supervisory system.

In the next part of this lab, you will be require to used Adroit SCADA software to monitor and control an AmpCom system.

Adroit natively supports Modbus commands and AmpCom can be easily integrated within its system.

Close the configuration software and double click on the icon. Click ‘OK’.

Double click on the icon. This will open the Adroit User Interface that has been pre-prepared.

Once loaded, click anywhere to proceed.

The following window will then appear:

Publication 0.2/07-11-2012. All the information provided within this document is property of Carlo Gavazzi & NHP Electrical Engineering

Products Pty. Ltd.

Page 50

Page 51: ADVANCED MOTOR PROTECTION WITH COMMUNICATION · 2013-01-13 · Hands-On Training ADVANCED MOTOR PROTECTION WITH COMMUNICATION TCU% 53% Avg I 23A Networkable Motor Protection, Control

To proceed to control the AmpCom system via this software, you will need to click on the ‘Local/Remote’

button and wait for the ‘Local Control Enabled’ status to change to ‘Remote Control Enabled’.

Proceed to start and stop the motor via the software by clicking the buttons and see the different

variables change.

Simulate an Earth Leakage trip by gradually moving the DMPU-EL C dial to the right most position.

Notice the ‘Earth Leakage Current (mA)’ begin to increase. Once it reaches 3000 mA it’ll trip the

contactor after a delay of 1 second.

You have successfully tested and monitored an AmpCom system via a supervisory system.

Contact to lab instructor if you’re interested in finding out more about Adroit.

Publication 0.2/07-11-2012. All the information provided within this document is property of Carlo Gavazzi & NHP Electrical Engineering

Products Pty. Ltd.

Page 51