IFB 19-16 Oak & Laurel Fire Protection System Upgrades Addendum #1 Page 1 of 1 ADDENDUM #1 & ACKNOWLEDGEMENT To: All Vendors Date: September 21, 2018 Changes to Specifications # Item Description 1 New Oak & Laurel Drawings and Project Information New Oak & Laurel Drawings and Project Information. 2 Modified Submission Due Date Original Submission Due date was September 27 th , 2018 (see page 2 of 14 of the IFB Document as reference). The updated Submission Due Date is now September 28 th , at 2:00 p.m. The information contained herein revises, supplements and/or supersedes the specific parts of the documents referred to and shall be attached to and become part of those documents as if originally forming a part thereof. Except herein as modified, all other provisions of the documents shall remain in full force and, unless otherwise described in this Addendum, shall comply with the requirements originally specified. All other conditions of this IFB will remain in effect. Please direct any questions to [email protected]ADDENDUM #1 & ACKNOWLEDGEMENT (This acknowledgement is required with bid submission) I acknowledge that I have received and reviewed Addendum #1. Company Name (please print) Name (please print) Signature Date This acknowledgement is required with bid submission.
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
IFB 19-16 Oak & Laurel Fire Protection System Upgrades Addendum #1
Page 1 of 1
ADDENDUM #1 & ACKNOWLEDGEMENT
To: All Vendors Date: September 21, 2018
Changes to Specifications
# Item Description
1 New Oak & Laurel Drawings and Project Information
New Oak & Laurel Drawings and Project Information.
2 Modified Submission Due Date
Original Submission Due date was September 27th, 2018 (see page 2 of 14 of the IFB Document as reference). The updated Submission Due Date is now September 28th, at 2:00 p.m.
The information contained herein revises, supplements and/or supersedes the specific parts of the documents referred to and shall be attached to and become part of those documents as if originally forming a part thereof. Except herein as modified, all other provisions of the documents shall remain in full force and, unless otherwise described in this Addendum, shall comply with the requirements originally specified. All other conditions of this IFB will remain in effect.
Remote area number: 1 Remote area location: Basement Occupancy classification: Ordinary Hazard I Density: 0.15 - Gpm/SqFt Area of application: 1500 - SqFt Coverage per sprinkler: 130 max - SqFt Type of sprinklers calculated: Reliable F1FR LO QR UPR 155 Deg F R3622 No. of sprinklers calculated: 15 In-rack demand: n/a - GPM Hose streams: 250 - GPM Total water required (including hose streams): 620.9 - GPM @ 21.1 - Psi Type of system: wet Volume of dry or preaction system: n/a - Gal
Water supply information
Date: 7-6-2018 Location: Hydrant #8, across from Laurel Hall Source: Pennoni Associates Inc.
Name of contractor: AMC FIRE PROTECTION Address: 1803 UNDERWOOD BLVD / / DELRAN, NJ 08075 Phone number: (856) 608-7878 Name of designer: Tyler Mayer Authority having jurisdiction: Notes: (Include peaking information or gridded systems here.)
Computer Programs by Hydratec Inc. Revision: 50.52.1
AMC FIRE PROTECTION Page 2 Rowan Laurel Hall Date 9-19-2018
Computer Programs by Hydratec Inc. Revision: 50.52.1
AMC FIRE PROTECTION Page 3 Rowan Laurel Hall Date 9-19-2018 Fitting Legend Abbrev. Name ½ ¾ 1 1¼ 1½ 2 2½ 3 3½ 4 5 6 8 10 12 14 16 18 20 24
B NFPA 13 Butterfly Valve 0 0 0 0 0 6 7 10 0 12 9 10 12 19 21 0 0 0 0 0 E NFPA 13 90' Standard Elbow 1 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61 Fsp Flow Switch Potter VSR Fitting generates a Fixed Loss Based on Flow G NFPA 13 Gate Valve 0 0 0 0 0 1 1 1 1 2 2 3 4 5 6 7 8 10 11 13 S NFPA 13 Swing Check 0 0 5 7 9 11 14 16 19 22 27 32 45 55 65 T NFPA 13 90' Flow thru Tee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121 Zac Ames 2000SS Fitting generates a Fixed Loss Based on Flow
Units Summary Diameter Units Inches Length Units Feet Flow Units US Gallons per Minute Pressure Units Pounds per Square Inch Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters. Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors of 120 except as noted with *. The fittings marked with a * show equivalent lengths values supplied by manufacturers based on specific pipe diameters and CFactors and they require no adjustment. All values for fittings not marked with a * will be adjusted in the calculation for CFactors of other than 120 and diameters other than Sched 40 per NFPA.
Fittings Used Summary
Computer Programs by Hydratec Inc. Revision: 50.52.1
AMC FIRE PROTECTION Page 4 Rowan Laurel Hall Date 9-19-2018
SUPPLY ANALYSIS Node at Static Residual Available Source Pressure Pressure Flow Pressure Total Demand Required Pressure
TEST 46.0 39 830.0 41.909 620.85 21.054
NODE ANALYSIS
Pressure Discharge Node Tag Elevation Node Type at Node at Node Notes
Remote area number: 2 Remote area location: Level 3 Occupancy classification: Light Hazard Density: 0.10 - Gpm/SqFt Area of application: 1500 - SqFt Coverage per sprinkler: 225 max - SqFt Type of sprinklers calculated: Reliable F1FR QR PEN&HZSW 155 Deg F RA1414 No. of sprinklers calculated: 17 In-rack demand: n/a - GPM Hose streams: 250 - GPM Total water required (including hose streams): 570.1 - GPM @ 35.3 - Psi Type of system: wet Volume of dry or preaction system: n/a - Gal
Water supply information
Date: 7-6-2018 Location: Hydrant #8, across from Laurel Hall Source: Pennoni Associates Inc.
Name of contractor: AMC FIRE PROTECTION Address: 1803 UNDERWOOD BLVD / / DELRAN, NJ 08075 Phone number: (856) 608-7878 Name of designer: Tyler Mayer Authority having jurisdiction: Notes: (Include peaking information or gridded systems here.) &RA1435
Computer Programs by Hydratec Inc. Revision: 50.52.1
AMC FIRE PROTECTION Page 2 Rowan Laurel Hall Date 9-19-2018
Computer Programs by Hydratec Inc. Revision: 50.52.1
AMC FIRE PROTECTION Page 3 Rowan Laurel Hall Date 9-19-2018 Fitting Legend Abbrev. Name ½ ¾ 1 1¼ 1½ 2 2½ 3 3½ 4 5 6 8 10 12 14 16 18 20 24
B NFPA 13 Butterfly Valve 0 0 0 0 0 6 7 10 0 12 9 10 12 19 21 0 0 0 0 0 E NFPA 13 90' Standard Elbow 1 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61 Fsp Flow Switch Potter VSR Fitting generates a Fixed Loss Based on Flow G NFPA 13 Gate Valve 0 0 0 0 0 1 1 1 1 2 2 3 4 5 6 7 8 10 11 13 R * CPVC Coupling Tee - Run 1 1 1 1 1 1 2 2 0 0 0 0 0 0 0 0 0 0 0 0 S NFPA 13 Swing Check 0 0 5 7 9 11 14 16 19 22 27 32 45 55 65 T NFPA 13 90' Flow thru Tee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121 Zac Ames 2000SS Fitting generates a Fixed Loss Based on Flow
Units Summary Diameter Units Inches Length Units Feet Flow Units US Gallons per Minute Pressure Units Pounds per Square Inch Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters. Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors of 120 except as noted with *. The fittings marked with a * show equivalent lengths values supplied by manufacturers based on specific pipe diameters and CFactors and they require no adjustment. All values for fittings not marked with a * will be adjusted in the calculation for CFactors of other than 120 and diameters other than Sched 40 per NFPA.
Fittings Used Summary
Computer Programs by Hydratec Inc. Revision: 50.52.1
AMC FIRE PROTECTION Page 4 Rowan Laurel Hall Date 9-19-2018
SUPPLY ANALYSIS Node at Static Residual Available Source Pressure Pressure Flow Pressure Total Demand Required Pressure
TEST 46.0 39 830.0 42.506 570.1 35.306
NODE ANALYSIS
Pressure Discharge Node Tag Elevation Node Type at Node at Node Notes
Remote area number: 3 Remote area location: Attic Occupancy classification: Light Hazard Density: 0.10 - Gpm/SqFt Area of application: 7 Sprinklers - SqFt Coverage per sprinkler: 8 liner ft - SqFt Type of sprinklers calculated: Reliable F1FR QR UPR 200 Deg F RA1425 No. of sprinklers calculated: 7 In-rack demand: n/a - GPM Hose streams: 250 - GPM Total water required (including hose streams): 355.4 - GPM @ 39.1 - Psi Type of system: dry Volume of dry or preaction system: 252.3 - Gal
Water supply information
Date: 7-6-2018 Location: Hydrant #8, across from Laurel Hall Source: Pennoni Associates Inc.
Name of contractor: AMC FIRE PROTECTION Address: 1803 UNDERWOOD BLVD / / DELRAN, NJ 08075 Phone number: (856) 608-7878 Name of designer: Tyler Mayer Authority having jurisdiction: Notes: (Include peaking information or gridded systems here.)
Computer Programs by Hydratec Inc. Revision: 50.52.1
AMC FIRE PROTECTION Page 2 Rowan Laurel Hall Date 9-19-2018
Computer Programs by Hydratec Inc. Revision: 50.52.1
AMC FIRE PROTECTION Page 3 Rowan Laurel Hall Date 9-19-2018 Fitting Legend Abbrev. Name ½ ¾ 1 1¼ 1½ 2 2½ 3 3½ 4 5 6 8 10 12 14 16 18 20 24
B NFPA 13 Butterfly Valve 0 0 0 0 0 6 7 10 0 12 9 10 12 19 21 0 0 0 0 0 Dvc Dry Vic 768 NXT 3 9 8 17 21 22 50 E NFPA 13 90' Standard Elbow 1 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61 Fsp Flow Switch Potter VSR Fitting generates a Fixed Loss Based on Flow G NFPA 13 Gate Valve 0 0 0 0 0 1 1 1 1 2 2 3 4 5 6 7 8 10 11 13 S NFPA 13 Swing Check 0 0 5 7 9 11 14 16 19 22 27 32 45 55 65 T NFPA 13 90' Flow thru Tee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121 Zac Ames 2000SS Fitting generates a Fixed Loss Based on Flow
Units Summary Diameter Units Inches Length Units Feet Flow Units US Gallons per Minute Pressure Units Pounds per Square Inch Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters. Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors of 120 except as noted with *. The fittings marked with a * show equivalent lengths values supplied by manufacturers based on specific pipe diameters and CFactors and they require no adjustment. All values for fittings not marked with a * will be adjusted in the calculation for CFactors of other than 120 and diameters other than Sched 40 per NFPA.
Fittings Used Summary
Computer Programs by Hydratec Inc. Revision: 50.52.1
AMC FIRE PROTECTION Page 4 Rowan Laurel Hall Date 9-19-2018
SUPPLY ANALYSIS Node at Static Residual Available Source Pressure Pressure Flow Pressure Total Demand Required Pressure
TEST 46.0 39 830.0 44.542 355.41 39.1
NODE ANALYSIS
Pressure Discharge Node Tag Elevation Node Type at Node at Node Notes
Job Name : Rowan Oak Hall Drawing : FP-1 Location : 201 Mulica Hill Rd, Glassboro, NJ 08028 Remote : 1 Contract : n/a Data File : Rowan - Oak - Basement OH.WXF
Computer Programs by Hydratec Inc. Revision: 50.52.1
AMC FIRE PROTECTION Page 1 Rowan Oak Hall Date 9-19-2018
HYDRAULIC CALCULATIONS for
Project name: Rowan Oak Hall Location: 201 Mulica Hill Rd, Glassboro, NJ 08028 Drawing no: FP-1 Date: 9-19-2018
Design
Remote area number: 1 Remote area location: Basement Occupancy classification: Ordinary Hazard I Density: 0.15 - Gpm/SqFt Area of application: 1500 - SqFt Coverage per sprinkler: 130 max - SqFt Type of sprinklers calculated: Reliable F1FR LO QR UPR 155 Deg F R3622 No. of sprinklers calculated: 15 In-rack demand: n/a - GPM Hose streams: 250 - GPM Total water required (including hose streams): 620.9 - GPM @ 21.1 - Psi Type of system: wet Volume of dry or preaction system: n/a - Gal
Water supply information
Date: 7-6-2018 Location: Hydrant #9, across from Oak Hall Source: Pennoni Associates Inc.
Name of contractor: AMC FIRE PROTECTION Address: 1803 UNDERWOOD BLVD / / DELRAN, NJ 08075 Phone number: (856) 608-7878 Name of designer: Tyler Mayer Authority having jurisdiction: Notes: (Include peaking information or gridded systems here.)
Computer Programs by Hydratec Inc. Revision: 50.52.1
AMC FIRE PROTECTION Page 2 Rowan Oak Hall Date 9-19-2018
Computer Programs by Hydratec Inc. Revision: 50.52.1
AMC FIRE PROTECTION Page 3 Rowan Oak Hall Date 9-19-2018 Fitting Legend Abbrev. Name ½ ¾ 1 1¼ 1½ 2 2½ 3 3½ 4 5 6 8 10 12 14 16 18 20 24
B NFPA 13 Butterfly Valve 0 0 0 0 0 6 7 10 0 12 9 10 12 19 21 0 0 0 0 0 E NFPA 13 90' Standard Elbow 1 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61 Fsp Flow Switch Potter VSR Fitting generates a Fixed Loss Based on Flow G NFPA 13 Gate Valve 0 0 0 0 0 1 1 1 1 2 2 3 4 5 6 7 8 10 11 13 S NFPA 13 Swing Check 0 0 5 7 9 11 14 16 19 22 27 32 45 55 65 T NFPA 13 90' Flow thru Tee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121 Zac Ames 2000SS Fitting generates a Fixed Loss Based on Flow
Units Summary Diameter Units Inches Length Units Feet Flow Units US Gallons per Minute Pressure Units Pounds per Square Inch Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters. Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors of 120 except as noted with *. The fittings marked with a * show equivalent lengths values supplied by manufacturers based on specific pipe diameters and CFactors and they require no adjustment. All values for fittings not marked with a * will be adjusted in the calculation for CFactors of other than 120 and diameters other than Sched 40 per NFPA.
Fittings Used Summary
Computer Programs by Hydratec Inc. Revision: 50.52.1
AMC FIRE PROTECTION Page 4 Rowan Oak Hall Date 9-19-2018
SUPPLY ANALYSIS Node at Static Residual Available Source Pressure Pressure Flow Pressure Total Demand Required Pressure
TEST 48.0 36 1150.0 44.164 620.85 21.107
NODE ANALYSIS
Pressure Discharge Node Tag Elevation Node Type at Node at Node Notes
Job Name : Rowan Oak Hall Drawing : FP-5 Location : 201 Mulica Hill Rd, Glassboro, NJ 08028 Remote : 3 Contract : n/a Data File : Rowan - Oak - Level 4 (Attic).WXF
Computer Programs by Hydratec Inc. Revision: 50.52.1
AMC FIRE PROTECTION Page 1 Rowan Oak Hall Date 9-19-2018
HYDRAULIC CALCULATIONS for
Project name: Rowan Oak Hall Location: 201 Mulica Hill Rd, Glassboro, NJ 08028 Drawing no: FP-5 Date: 9-19-2018
Design
Remote area number: 3 Remote area location: Attic Occupancy classification: Light Hazard Density: 0.10 - Gpm/SqFt Area of application: 7 Sprinklers - SqFt Coverage per sprinkler: 8 liner ft - SqFt Type of sprinklers calculated: Reliable F1FR QR UPR 200 Deg F RA1425 No. of sprinklers calculated: 7 In-rack demand: n/a - GPM Hose streams: 250 - GPM Total water required (including hose streams): 355.4 - GPM @ 41.8 - Psi Type of system: dry Volume of dry or preaction system: 267.2 - Gal
Water supply information
Date: 7-6-2018 Location: Hydrant #9, across from Oak Hall Source: Pennoni Associates Inc.
Name of contractor: AMC FIRE PROTECTION Address: 1803 UNDERWOOD BLVD / / DELRAN, NJ 08075 Phone number: (856) 608-7878 Name of designer: Tyler Mayer Authority having jurisdiction: Notes: (Include peaking information or gridded systems here.)
Computer Programs by Hydratec Inc. Revision: 50.52.1
AMC FIRE PROTECTION Page 2 Rowan Oak Hall Date 9-19-2018
Computer Programs by Hydratec Inc. Revision: 50.52.1
AMC FIRE PROTECTION Page 3 Rowan Oak Hall Date 9-19-2018 Fitting Legend Abbrev. Name ½ ¾ 1 1¼ 1½ 2 2½ 3 3½ 4 5 6 8 10 12 14 16 18 20 24
B NFPA 13 Butterfly Valve 0 0 0 0 0 6 7 10 0 12 9 10 12 19 21 0 0 0 0 0 Dvc Dry Vic 768 NXT 3 9 8 17 21 22 50 E NFPA 13 90' Standard Elbow 1 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61 Fsp Flow Switch Potter VSR Fitting generates a Fixed Loss Based on Flow G NFPA 13 Gate Valve 0 0 0 0 0 1 1 1 1 2 2 3 4 5 6 7 8 10 11 13 S NFPA 13 Swing Check 0 0 5 7 9 11 14 16 19 22 27 32 45 55 65 T NFPA 13 90' Flow thru Tee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121 Zac Ames 2000SS Fitting generates a Fixed Loss Based on Flow
Units Summary Diameter Units Inches Length Units Feet Flow Units US Gallons per Minute Pressure Units Pounds per Square Inch Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters. Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors of 120 except as noted with *. The fittings marked with a * show equivalent lengths values supplied by manufacturers based on specific pipe diameters and CFactors and they require no adjustment. All values for fittings not marked with a * will be adjusted in the calculation for CFactors of other than 120 and diameters other than Sched 40 per NFPA.
Fittings Used Summary
Computer Programs by Hydratec Inc. Revision: 50.52.1
AMC FIRE PROTECTION Page 4 Rowan Oak Hall Date 9-19-2018
SUPPLY ANALYSIS Node at Static Residual Available Source Pressure Pressure Flow Pressure Total Demand Required Pressure
TEST 48.0 36 1150.0 46.633 355.41 41.745
NODE ANALYSIS
Pressure Discharge Node Tag Elevation Node Type at Node at Node Notes
Job Name : Rowan Oak Hall Drawing : FP-4 Location : 201 Mulica Hill Rd, Glassboro, NJ 08028 Remote : 2 Contract : n/a Data File : Rowan - Oak - Level 3.WXF
Computer Programs by Hydratec Inc. Revision: 50.52.1
AMC FIRE PROTECTION Page 1 Rowan Oak Hall Date 9-19-2018
HYDRAULIC CALCULATIONS for
Project name: Rowan Oak Hall Location: 201 Mulica Hill Rd, Glassboro, NJ 08028 Drawing no: FP-4 Date: 9-19-2018
Design
Remote area number: 2 Remote area location: Level 3 Occupancy classification: Light Hazard Density: 0.10 - Gpm/SqFt Area of application: 1500 - SqFt Coverage per sprinkler: 225 max - SqFt Type of sprinklers calculated: Reliable F1FR QR PEN&HZSW 155 Deg F RA1414 No. of sprinklers calculated: 16 In-rack demand: n/a - GPM Hose streams: 250 - GPM Total water required (including hose streams): 558.6 - GPM @ 35.7 - Psi Type of system: wet Volume of dry or preaction system: n/a - Gal
Water supply information
Date: 7-6-2018 Location: Hydrant #9, across from Oak Hall Source: Pennoni Associates Inc.
Name of contractor: AMC FIRE PROTECTION Address: 1803 UNDERWOOD BLVD / / DELRAN, NJ 08075 Phone number: (856) 608-7878 Name of designer: Tyler Mayer Authority having jurisdiction: Notes: (Include peaking information or gridded systems here.) &RA1435
Computer Programs by Hydratec Inc. Revision: 50.52.1
AMC FIRE PROTECTION Page 2 Rowan Oak Hall Date 9-19-2018
Computer Programs by Hydratec Inc. Revision: 50.52.1
AMC FIRE PROTECTION Page 3 Rowan Oak Hall Date 9-19-2018 Fitting Legend Abbrev. Name ½ ¾ 1 1¼ 1½ 2 2½ 3 3½ 4 5 6 8 10 12 14 16 18 20 24
B NFPA 13 Butterfly Valve 0 0 0 0 0 6 7 10 0 12 9 10 12 19 21 0 0 0 0 0 E NFPA 13 90' Standard Elbow 1 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61 Fsp Flow Switch Potter VSR Fitting generates a Fixed Loss Based on Flow G NFPA 13 Gate Valve 0 0 0 0 0 1 1 1 1 2 2 3 4 5 6 7 8 10 11 13 R * CPVC Coupling Tee - Run 1 1 1 1 1 1 2 2 0 0 0 0 0 0 0 0 0 0 0 0 S NFPA 13 Swing Check 0 0 5 7 9 11 14 16 19 22 27 32 45 55 65 T NFPA 13 90' Flow thru Tee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121 Zac Ames 2000SS Fitting generates a Fixed Loss Based on Flow
Units Summary Diameter Units Inches Length Units Feet Flow Units US Gallons per Minute Pressure Units Pounds per Square Inch Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters. Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors of 120 except as noted with *. The fittings marked with a * show equivalent lengths values supplied by manufacturers based on specific pipe diameters and CFactors and they require no adjustment. All values for fittings not marked with a * will be adjusted in the calculation for CFactors of other than 120 and diameters other than Sched 40 per NFPA.
Fittings Used Summary
Computer Programs by Hydratec Inc. Revision: 50.52.1
AMC FIRE PROTECTION Page 4 Rowan Oak Hall Date 9-19-2018
SUPPLY ANALYSIS Node at Static Residual Available Source Pressure Pressure Flow Pressure Total Demand Required Pressure
TEST 48.0 36 1150.0 44.845 558.58 35.647
NODE ANALYSIS
Pressure Discharge Node Tag Elevation Node Type at Node at Node Notes