Acoustics for Hospitals: FGI Guidelines, HCAHPS, and LEED Jeff Boldt KJWW Engineering
68

Acoustics for Hospitals: FGI Guidelines, HCAHPS, and …hesni.org/images/downloads/2013_Annual_Conference/healthcare... · Acoustics for Hospitals: FGI Guidelines, HCAHPS, and LEED

May 02, 2018

Download

Documents

LeKhuong
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Acoustics for Hospitals: FGI Guidelines, HCAHPS, and …hesni.org/images/downloads/2013_Annual_Conference/healthcare... · Acoustics for Hospitals: FGI Guidelines, HCAHPS, and LEED

Acoustics forHospitals: FGI

Guidelines, HCAHPS,and LEED

Jeff BoldtKJWW Engineering

Page 2: Acoustics for Hospitals: FGI Guidelines, HCAHPS, and …hesni.org/images/downloads/2013_Annual_Conference/healthcare... · Acoustics for Hospitals: FGI Guidelines, HCAHPS, and LEED

PresenterJeff Boldt, PE, LEED® AP, HBDPKJWW Engineering (~500 staff)

Principal – Director of Engineering• Voting Member ASHRAE SSPC-90.1

– Chair - 90.1 Healthcare Working Group (WG),Hydronic WG, Elevator WG, Duct Leakage WG

• Member ASHRAE 189.1• Author AEDG Small & Large Healthcare• 2 Years Post-Graduate Acoustical Engineering

– Herriot-Watt University Edinburgh, Scotland– Member FGI Acoustics Working Group

Page 3: Acoustics for Hospitals: FGI Guidelines, HCAHPS, and …hesni.org/images/downloads/2013_Annual_Conference/healthcare... · Acoustics for Hospitals: FGI Guidelines, HCAHPS, and LEED

FGI 2010

Page 4: Acoustics for Hospitals: FGI Guidelines, HCAHPS, and …hesni.org/images/downloads/2013_Annual_Conference/healthcare... · Acoustics for Hospitals: FGI Guidelines, HCAHPS, and LEED

When Guidelinesare Required

Joint CommissionBeginning in January 2011, the JointCommission requires compliance with the2010 Guidelines in its accreditation manuals.

The Joint Commission does not mandateuse of the Guidelines if another state ornational standard is being applied to aproject.

Page 5: Acoustics for Hospitals: FGI Guidelines, HCAHPS, and …hesni.org/images/downloads/2013_Annual_Conference/healthcare... · Acoustics for Hospitals: FGI Guidelines, HCAHPS, and LEED

When Guidelines areRequired

• States that Adopt:– January, 2012 list– Georgia, Iowa, Louisiana,

Massachusetts, New Jersey, New York,Pennsylvania, Virginia, Washington,Wisconsin (ventilation only)

Page 6: Acoustics for Hospitals: FGI Guidelines, HCAHPS, and …hesni.org/images/downloads/2013_Annual_Conference/healthcare... · Acoustics for Hospitals: FGI Guidelines, HCAHPS, and LEED

Who Adopts Now

Page 7: Acoustics for Hospitals: FGI Guidelines, HCAHPS, and …hesni.org/images/downloads/2013_Annual_Conference/healthcare... · Acoustics for Hospitals: FGI Guidelines, HCAHPS, and LEED

FGI Requirements

• At least 14 pages contain acousticalrequirements.

• Virtually no facilities comply with allof the 2010 requirements!

Page 8: Acoustics for Hospitals: FGI Guidelines, HCAHPS, and …hesni.org/images/downloads/2013_Annual_Conference/healthcare... · Acoustics for Hospitals: FGI Guidelines, HCAHPS, and LEED

FGI Requirements

Acoustical Categories• Site Exterior Noise• Speech Privacy• Room Sound Absorption• Room Noise Levels• Isolation Between Rooms• Vibration• Misc. (Helipads, Noise Control, NICU)

Page 9: Acoustics for Hospitals: FGI Guidelines, HCAHPS, and …hesni.org/images/downloads/2013_Annual_Conference/healthcare... · Acoustics for Hospitals: FGI Guidelines, HCAHPS, and LEED

2010 FGI in General

“The planning and design of new healthcare facilities and the retrofitting ofexisting health care facilities shall conformto these Guidelines and all applicablecodes and regulations with respect toexterior environmental sound and interiorsound within all occupied buildingspaces.” (1.2-6.1.1)

Page 10: Acoustics for Hospitals: FGI Guidelines, HCAHPS, and …hesni.org/images/downloads/2013_Annual_Conference/healthcare... · Acoustics for Hospitals: FGI Guidelines, HCAHPS, and LEED

Site Exterior Noise

“Building facade sound isolationperformance shall depend on the siteclassification and shall be as required toprovide acceptable interior sound levels.”(1.2-6.1.2.3) (1.2-4.1.1 proposed for 2014)

Page 11: Acoustics for Hospitals: FGI Guidelines, HCAHPS, and …hesni.org/images/downloads/2013_Annual_Conference/healthcare... · Acoustics for Hospitals: FGI Guidelines, HCAHPS, and LEED

Site Exterior Noise

Noise NOT produced by the facilityA = minimalB = moderateC = significantD = extreme

Façade design depends on category

Page 12: Acoustics for Hospitals: FGI Guidelines, HCAHPS, and …hesni.org/images/downloads/2013_Annual_Conference/healthcare... · Acoustics for Hospitals: FGI Guidelines, HCAHPS, and LEED

Site Exterior Noise

Page 13: Acoustics for Hospitals: FGI Guidelines, HCAHPS, and …hesni.org/images/downloads/2013_Annual_Conference/healthcare... · Acoustics for Hospitals: FGI Guidelines, HCAHPS, and LEED

Hard in Loud Areas

• Standard double-pane glass = STC-32• Thick laminated glass = STC-39• Limits the allowable glazed areas• For B, C or D,

determine exteriornoise usingANSI/ASA S12.9 testfor at least one week.

Page 14: Acoustics for Hospitals: FGI Guidelines, HCAHPS, and …hesni.org/images/downloads/2013_Annual_Conference/healthcare... · Acoustics for Hospitals: FGI Guidelines, HCAHPS, and LEED

Exterior Survey

Page 15: Acoustics for Hospitals: FGI Guidelines, HCAHPS, and …hesni.org/images/downloads/2013_Annual_Conference/healthcare... · Acoustics for Hospitals: FGI Guidelines, HCAHPS, and LEED

Your Exterior Noise

• Based on exterior noise category• Recommends maximum property line

noise levels produced by the facility(Not mandatory)

• Local codes may be more strict– (e.g. Illinois is much stricter)

Page 16: Acoustics for Hospitals: FGI Guidelines, HCAHPS, and …hesni.org/images/downloads/2013_Annual_Conference/healthcare... · Acoustics for Hospitals: FGI Guidelines, HCAHPS, and LEED

You Can Comply!

Page 17: Acoustics for Hospitals: FGI Guidelines, HCAHPS, and …hesni.org/images/downloads/2013_Annual_Conference/healthcare... · Acoustics for Hospitals: FGI Guidelines, HCAHPS, and LEED

Speech Privacy

“Spaces shall bedesigned to meetspeech privacy goalsusing one of the fourspeech privacy ratingmethods as shown inTable 1.2-4.”

(1.2-6.1.6.1) (1.2-4.1.6.1)

Page 18: Acoustics for Hospitals: FGI Guidelines, HCAHPS, and …hesni.org/images/downloads/2013_Annual_Conference/healthcare... · Acoustics for Hospitals: FGI Guidelines, HCAHPS, and LEED

Speech Privacy

* Some changes proposed for 2014

Page 19: Acoustics for Hospitals: FGI Guidelines, HCAHPS, and …hesni.org/images/downloads/2013_Annual_Conference/healthcare... · Acoustics for Hospitals: FGI Guidelines, HCAHPS, and LEED

Sound Absorption

“All normally occupied health care facilityspaces shall incorporate acoustic finishesto achieve design room average soundabsorption coefficients equal to or greaterthan in Table 1.2-1.”(1.2-6.1.3) (1.2-4.1.3)

Page 20: Acoustics for Hospitals: FGI Guidelines, HCAHPS, and …hesni.org/images/downloads/2013_Annual_Conference/healthcare... · Acoustics for Hospitals: FGI Guidelines, HCAHPS, and LEED

Sound Absorption

• Gypsum Board = 0.07• Vinyl Flooring = 0.03

Page 21: Acoustics for Hospitals: FGI Guidelines, HCAHPS, and …hesni.org/images/downloads/2013_Annual_Conference/healthcare... · Acoustics for Hospitals: FGI Guidelines, HCAHPS, and LEED
Page 22: Acoustics for Hospitals: FGI Guidelines, HCAHPS, and …hesni.org/images/downloads/2013_Annual_Conference/healthcare... · Acoustics for Hospitals: FGI Guidelines, HCAHPS, and LEED

Room Noise Levels

“Room noise levels shall fall within thesound level ranges shown for the chosenrating system in Table 1.2-2.”(1.2-6.1.4) (1.2-4.1.4.1)

• Noise levels determined for the unoccupiedroom (w/o operating medical equipment).

Designing within a 10 dBA range is hard!• I believe this requires sound masking.• Proposed to be only maximums for 2014.

Page 23: Acoustics for Hospitals: FGI Guidelines, HCAHPS, and …hesni.org/images/downloads/2013_Annual_Conference/healthcare... · Acoustics for Hospitals: FGI Guidelines, HCAHPS, and LEED

Room Noise LevelsRoom Type NC/RC(N)/RNC dBAPatient Rooms 30 - 40 35 - 45Multiple Occupant Patient Care Areas 35 - 45 40 - 50NICU 25 - 35 30 - 40Operating Rooms* 35 - 45 40 - 50Corridors and Public Spaces 35 - 45 40 - 50Testing/Research Lab, Minimal Speech* 45 - 55 50 - 60Research Lab, Extensive Speech* 40 - 50 45 - 55Group Teaching Lab 35 - 45 40 - 50Doctor's Offices, Exam Rooms 30 - 40 35 - 45Conference Rooms 25 - 35 30 - 40Teleconferencing Rooms ≤ 25 ≤ 30Auditoriums, Large Lecture Rooms 25 - 30 30 - 35* in appendix

Room Noise Levels

Page 24: Acoustics for Hospitals: FGI Guidelines, HCAHPS, and …hesni.org/images/downloads/2013_Annual_Conference/healthcare... · Acoustics for Hospitals: FGI Guidelines, HCAHPS, and LEED

ICU Noise Levels

Page 25: Acoustics for Hospitals: FGI Guidelines, HCAHPS, and …hesni.org/images/downloads/2013_Annual_Conference/healthcare... · Acoustics for Hospitals: FGI Guidelines, HCAHPS, and LEED

Predicting Noise Levels

Page 26: Acoustics for Hospitals: FGI Guidelines, HCAHPS, and …hesni.org/images/downloads/2013_Annual_Conference/healthcare... · Acoustics for Hospitals: FGI Guidelines, HCAHPS, and LEED

OR TestingRecommends40-50 dBA<55 dBA

Too loud, IMO

Page 27: Acoustics for Hospitals: FGI Guidelines, HCAHPS, and …hesni.org/images/downloads/2013_Annual_Conference/healthcare... · Acoustics for Hospitals: FGI Guidelines, HCAHPS, and LEED

Auditorium Testing

Page 28: Acoustics for Hospitals: FGI Guidelines, HCAHPS, and …hesni.org/images/downloads/2013_Annual_Conference/healthcare... · Acoustics for Hospitals: FGI Guidelines, HCAHPS, and LEED

Isolation Between Rooms

“The composite sound transmission class(STCC) rating of demising wall assembliesshall not be less than the ratings indicatedin Table 1.2-3.”(1.2-6.1.5.2) (1.2-4.1.5.2)Table includes floors.

Page 29: Acoustics for Hospitals: FGI Guidelines, HCAHPS, and …hesni.org/images/downloads/2013_Annual_Conference/healthcare... · Acoustics for Hospitals: FGI Guidelines, HCAHPS, and LEED

Isolation Between Rooms

Page 30: Acoustics for Hospitals: FGI Guidelines, HCAHPS, and …hesni.org/images/downloads/2013_Annual_Conference/healthcare... · Acoustics for Hospitals: FGI Guidelines, HCAHPS, and LEED

STCc 35 STCc 45Patient room tocorridor and examroom to corridor• 4-inch stud cavity• 1 layer of 5/8-inch

gypsum each side• 2-inch glass fiber batting• Construction gaps and

electrical boxes sealed

Patient room topatient room

• Additional layer of5/8-inch gypsumto one side ofassembly.

• Viscoelasticadhesive betweenlayers.

Page 31: Acoustics for Hospitals: FGI Guidelines, HCAHPS, and …hesni.org/images/downloads/2013_Annual_Conference/healthcare... · Acoustics for Hospitals: FGI Guidelines, HCAHPS, and LEED

STCc 50 STCc 60Patient room topublic spaceNICU to patientroom or corridor

• Staggered studconstruction oncommon 6-inchplate.

Patient room toservice area

• Staggered-studconstruction onseparate 4-inchplates.

Page 32: Acoustics for Hospitals: FGI Guidelines, HCAHPS, and …hesni.org/images/downloads/2013_Annual_Conference/healthcare... · Acoustics for Hospitals: FGI Guidelines, HCAHPS, and LEED

Vibration

“Vibration levels in the building shall notexceed applicable guidelines and limitsoutlined in this section.”(1.2-6.1.7.2) (1.2-4.1.7.2)

“Vibration should not exceed levels inANSI S2.71.”(A1.2-6.1.7) (A1.2-4.1.7)

Page 33: Acoustics for Hospitals: FGI Guidelines, HCAHPS, and …hesni.org/images/downloads/2013_Annual_Conference/healthcare... · Acoustics for Hospitals: FGI Guidelines, HCAHPS, and LEED

Equipment Vibration

“All fixed building equipment that rotatesor vibrates shall be considered forvibration isolation.”(1.2-6.1.7.2) (1.2-4.1.7.2)

“The types of isolators and isolator staticdeflections shall be as recommended inASHRAE Handbook -HVAC Applications.”(1.2-6.1.7.2(1)) (1.2-4.1.7.2(1))

Page 34: Acoustics for Hospitals: FGI Guidelines, HCAHPS, and …hesni.org/images/downloads/2013_Annual_Conference/healthcare... · Acoustics for Hospitals: FGI Guidelines, HCAHPS, and LEED

Footfall Vibration

“The structural floor shall be designed toavoid footfall vibration levels that exceedthe peak vibration velocities inTable 1.2-5.”(1.2-6.1.7.2 (2)) (1.2-4.1.7.2 (2))(Evaluated per AISC Design Guide 11)

Page 35: Acoustics for Hospitals: FGI Guidelines, HCAHPS, and …hesni.org/images/downloads/2013_Annual_Conference/healthcare... · Acoustics for Hospitals: FGI Guidelines, HCAHPS, and LEED

Footfall Vibration

Page 36: Acoustics for Hospitals: FGI Guidelines, HCAHPS, and …hesni.org/images/downloads/2013_Annual_Conference/healthcare... · Acoustics for Hospitals: FGI Guidelines, HCAHPS, and LEED

Vibration

• Not trivial to comply.• Steel with concrete

slab is predictable.(Heavier constructionthan normal)

• CIP concrete is morelikely to comply.(Prediction duringdesign is difficult.)

Page 37: Acoustics for Hospitals: FGI Guidelines, HCAHPS, and …hesni.org/images/downloads/2013_Annual_Conference/healthcare... · Acoustics for Hospitals: FGI Guidelines, HCAHPS, and LEED

Helipads

• “Facilities with helipads shallincorporate noise mitigation strategiesto meet the acoustic requirements.”

• “Special consideration”required when:• 700 feet or less to patient areas• Pad on top of building• Over two night flights per week

Page 38: Acoustics for Hospitals: FGI Guidelines, HCAHPS, and …hesni.org/images/downloads/2013_Annual_Conference/healthcare... · Acoustics for Hospitals: FGI Guidelines, HCAHPS, and LEED

Noise Control

“Recreation rooms, exercise rooms,equipment rooms, and similar spaceswhere impact noises may be generatedshall not be located directly over patientbed areas or delivery and operatingsuites, unless special provisions aremade to minimize such noise.”(2.1-7.2.2.12)

Page 39: Acoustics for Hospitals: FGI Guidelines, HCAHPS, and …hesni.org/images/downloads/2013_Annual_Conference/healthcare... · Acoustics for Hospitals: FGI Guidelines, HCAHPS, and LEED

NICU

Page 40: Acoustics for Hospitals: FGI Guidelines, HCAHPS, and …hesni.org/images/downloads/2013_Annual_Conference/healthcare... · Acoustics for Hospitals: FGI Guidelines, HCAHPS, and LEED

NICU

“Infant rooms (including airborne infectionisolation rooms), staff work areas, familyareas, and staff lounge and sleepingareas - and the spaces opening ontothem - shall be designed to produceminimal background noise and to containand absorb much of the transient noisethat arises within them.”(2.2-2.10.9.3)

Page 41: Acoustics for Hospitals: FGI Guidelines, HCAHPS, and …hesni.org/images/downloads/2013_Annual_Conference/healthcare... · Acoustics for Hospitals: FGI Guidelines, HCAHPS, and LEED

NICU - Proposed

“Infant rooms (including airborne infectionisolation rooms), staff work areas, familyareas, and staff lounge and sleepingareas - and the spaces opening ontothem - shall be designed to comply withroom noise criteria in Table 1.2-2.”*(2.2-2.10.9.3)

* Quietest area

Page 42: Acoustics for Hospitals: FGI Guidelines, HCAHPS, and …hesni.org/images/downloads/2013_Annual_Conference/healthcare... · Acoustics for Hospitals: FGI Guidelines, HCAHPS, and LEED

NICU

“The combination of continuousbackground sound and operational soundin infant bed rooms and adult sleep areasshall not exceed an hourly Leq of 45 dBAand an hourly L10 of 50 dBA. The Lmax(transient sounds) shall not exceed 65dBA in these rooms/ areas.” *(2.2-2.10.9.3 (1))

* Proposed to be deleted in 2014.

Page 43: Acoustics for Hospitals: FGI Guidelines, HCAHPS, and …hesni.org/images/downloads/2013_Annual_Conference/healthcare... · Acoustics for Hospitals: FGI Guidelines, HCAHPS, and LEED

NICU

“Ceilings shall have a noise reductioncoefficient (NRC) of 0.95 for 80 percent ofthe entire surface area or an average NRCof 0.85 for the entire ceiling, includingreflective and acoustically absorptivesurfaces.”(2.2-2.10.9.1 (2))

Page 44: Acoustics for Hospitals: FGI Guidelines, HCAHPS, and …hesni.org/images/downloads/2013_Annual_Conference/healthcare... · Acoustics for Hospitals: FGI Guidelines, HCAHPS, and LEED

NICU

“Ceilings in infantrooms and adultsleep areas shallhave a ceilingattenuation class(CAC) of 29 orhigher.”(2.2-2.10.9.1 (2))

Page 45: Acoustics for Hospitals: FGI Guidelines, HCAHPS, and …hesni.org/images/downloads/2013_Annual_Conference/healthcare... · Acoustics for Hospitals: FGI Guidelines, HCAHPS, and LEED

NICU Noise

Fire alarms in the infant area should berestricted to flashing lights without anaudible signal. The audible alarm level inother occupied areas must be adjustable.

Page 46: Acoustics for Hospitals: FGI Guidelines, HCAHPS, and …hesni.org/images/downloads/2013_Annual_Conference/healthcare... · Acoustics for Hospitals: FGI Guidelines, HCAHPS, and LEED

NICU Noise

Telephones audiblefrom the infant areashould have adjustableannouncing signals.

Page 47: Acoustics for Hospitals: FGI Guidelines, HCAHPS, and …hesni.org/images/downloads/2013_Annual_Conference/healthcare... · Acoustics for Hospitals: FGI Guidelines, HCAHPS, and LEED

NICU Lighting

• “Provisions shall be made for indirectlighting and high-intensity lighting.”(2.2-2.10.9.2)

• “Electric light sources shall have colorrendering index of no less than 80, afull-spectrum color index of no less than55, and a gamut area of no less than 65and no greater than 100.”(2.2-2.10.9.2)

Page 48: Acoustics for Hospitals: FGI Guidelines, HCAHPS, and …hesni.org/images/downloads/2013_Annual_Conference/healthcare... · Acoustics for Hospitals: FGI Guidelines, HCAHPS, and LEED

NICU Lighting

“No direct ambient lighting shall bepermitted in the infant care space, andany direct ambient lighting used outsidethe infant area shall be located or framedto avoid a direct line of sight from anyinfant to the fixture.”(2.2-2.10.9.2)

Page 49: Acoustics for Hospitals: FGI Guidelines, HCAHPS, and …hesni.org/images/downloads/2013_Annual_Conference/healthcare... · Acoustics for Hospitals: FGI Guidelines, HCAHPS, and LEED

LEED for Healthcare

Up to 2 LEED-HC Points• No prerequisites• 1 point: Sound isolation & privacy per FGI-

2010; room noise levels per FGI-2010• 1 more point: Do items above; acoustical

finishes (calculate or measure); site exteriornoise (comply with SV Guidelines and FGI-2010 envelope requirements)

Page 50: Acoustics for Hospitals: FGI Guidelines, HCAHPS, and …hesni.org/images/downloads/2013_Annual_Conference/healthcare... · Acoustics for Hospitals: FGI Guidelines, HCAHPS, and LEED

HCAHPS• Hospital Consumer Assessment of

Healthcare Provider & Systems• Quarterly standardized assessment, by

adult inpatients, of their perception oftotal quality of care.

Page 51: Acoustics for Hospitals: FGI Guidelines, HCAHPS, and …hesni.org/images/downloads/2013_Annual_Conference/healthcare... · Acoustics for Hospitals: FGI Guidelines, HCAHPS, and LEED

HCAHPS

• Compare Hospitals – TodayYour scores will drive patients to or away fromyour facility.

Page 52: Acoustics for Hospitals: FGI Guidelines, HCAHPS, and …hesni.org/images/downloads/2013_Annual_Conference/healthcare... · Acoustics for Hospitals: FGI Guidelines, HCAHPS, and LEED

Your Best Hospital…

Page 53: Acoustics for Hospitals: FGI Guidelines, HCAHPS, and …hesni.org/images/downloads/2013_Annual_Conference/healthcare... · Acoustics for Hospitals: FGI Guidelines, HCAHPS, and LEED

HCAHPS

• 8 criteria (effectively 6)“Patients who reported that the area aroundtheir room was "Always" quiet at night.”

Page 54: Acoustics for Hospitals: FGI Guidelines, HCAHPS, and …hesni.org/images/downloads/2013_Annual_Conference/healthcare... · Acoustics for Hospitals: FGI Guidelines, HCAHPS, and LEED

Patient Survey Results

Page 55: Acoustics for Hospitals: FGI Guidelines, HCAHPS, and …hesni.org/images/downloads/2013_Annual_Conference/healthcare... · Acoustics for Hospitals: FGI Guidelines, HCAHPS, and LEED

HCAHPS

• Healthcare exit survey cites acoustics& noise as #1 complaint.

• Studies:– Akansel, N (2008)– Gurses & Carayon, (2009)

• Medical machines, equipment, alarms,paging, etc., tops on list. Medicalequipment matters.

Page 56: Acoustics for Hospitals: FGI Guidelines, HCAHPS, and …hesni.org/images/downloads/2013_Annual_Conference/healthcare... · Acoustics for Hospitals: FGI Guidelines, HCAHPS, and LEED

HCAHPS

I am not a reimbursement expert, but herecomes the math …

Page 57: Acoustics for Hospitals: FGI Guidelines, HCAHPS, and …hesni.org/images/downloads/2013_Annual_Conference/healthcare... · Acoustics for Hospitals: FGI Guidelines, HCAHPS, and LEED

HCAHPS MathInpatient $3,000/day bill (CA average)

• HCAHPS 80% quietness vs. 50% quietnessscore

• 1% of reimbursement based on performance(rising to 2% in 2017)

• 70% outcomes / 30% HCAHPS• 80% vs. 50% = 30% improvement• 1 of 6 objective scores (also affects 2 others)• $3,000*1%*30%*30%/6 = $164 per patient

room per year ($328/room-year in 2017)

Page 58: Acoustics for Hospitals: FGI Guidelines, HCAHPS, and …hesni.org/images/downloads/2013_Annual_Conference/healthcare... · Acoustics for Hospitals: FGI Guidelines, HCAHPS, and LEED

Why Improve Acoustics?

• HCAHPS reimbursement– Worth about $1,000 per patient room

• More patients via HACHPS survey– What’s the value?

• More patients via better patientsatisfaction

Page 59: Acoustics for Hospitals: FGI Guidelines, HCAHPS, and …hesni.org/images/downloads/2013_Annual_Conference/healthcare... · Acoustics for Hospitals: FGI Guidelines, HCAHPS, and LEED

Solve FGI & HCAHPS

• Hire an acoustical consultant– Pick one who understands HVAC and

equipment

• Get an audit

Page 60: Acoustics for Hospitals: FGI Guidelines, HCAHPS, and …hesni.org/images/downloads/2013_Annual_Conference/healthcare... · Acoustics for Hospitals: FGI Guidelines, HCAHPS, and LEED

Advance Planning

• Design facility modifications• Staff training• Repeat audit

– Demonstrate improvements for JCAHO oryour AHJ

Page 61: Acoustics for Hospitals: FGI Guidelines, HCAHPS, and …hesni.org/images/downloads/2013_Annual_Conference/healthcare... · Acoustics for Hospitals: FGI Guidelines, HCAHPS, and LEED

This is Not a DIY

• Survey requires expertise and expensiveequipment

• Recommendations need expertise• Follow-up survey needs expertise

Page 62: Acoustics for Hospitals: FGI Guidelines, HCAHPS, and …hesni.org/images/downloads/2013_Annual_Conference/healthcare... · Acoustics for Hospitals: FGI Guidelines, HCAHPS, and LEED

Maybe Later a DIY

• If you have a smart staffer shadow thesurveyor, follow-ups can become DIY ifit is worth the instrument cost, and yourequire the surveyor to train yourshadow.

Page 63: Acoustics for Hospitals: FGI Guidelines, HCAHPS, and …hesni.org/images/downloads/2013_Annual_Conference/healthcare... · Acoustics for Hospitals: FGI Guidelines, HCAHPS, and LEED

What is best ROI?• Education for staff may be the cheapest way

to improve HCAHPS scores• Have the consultant present an acoustics

seminar so your staff understands.• Invite the nurses!

Page 64: Acoustics for Hospitals: FGI Guidelines, HCAHPS, and …hesni.org/images/downloads/2013_Annual_Conference/healthcare... · Acoustics for Hospitals: FGI Guidelines, HCAHPS, and LEED

Test Equipment

Page 65: Acoustics for Hospitals: FGI Guidelines, HCAHPS, and …hesni.org/images/downloads/2013_Annual_Conference/healthcare... · Acoustics for Hospitals: FGI Guidelines, HCAHPS, and LEED

Sound Meters

50 dB 40 dB 35 dB 30dB 20dB-integrates$50 $120 $200 $4,000 ~$10,000

Page 66: Acoustics for Hospitals: FGI Guidelines, HCAHPS, and …hesni.org/images/downloads/2013_Annual_Conference/healthcare... · Acoustics for Hospitals: FGI Guidelines, HCAHPS, and LEED

Summary

• Action now can avoid headaches later.• Acoustical improvements can bring in

more patients now.• Prepare for surveys based on FGI 2010

or 2014.• A few firms can provide your acoustical

needs and integrate them with HVACsystems and medical equipmentselections.

Page 67: Acoustics for Hospitals: FGI Guidelines, HCAHPS, and …hesni.org/images/downloads/2013_Annual_Conference/healthcare... · Acoustics for Hospitals: FGI Guidelines, HCAHPS, and LEED

Questions for you• How many facilities have had acoustical surveys?• How important are HCAHPS scores to you?• Do you plan to wait for a requirement for FGI-2010

compliance, or to comply soon to improve yourperformance and customer satisfaction?

• How much emphasis do you place on the ability ofpatients to sleep?

• Are most of your noise complaints HVAC, medicalequipment, paging, or staff activities?

Page 68: Acoustics for Hospitals: FGI Guidelines, HCAHPS, and …hesni.org/images/downloads/2013_Annual_Conference/healthcare... · Acoustics for Hospitals: FGI Guidelines, HCAHPS, and LEED

Have questions?Contact:Jeff BoldtKJWW Engineering(608) [email protected]