  • 7/25/2019 ACCIONA - Grid Integration Experience CIGRE 2010ID31VER89

    1/23

    ACCIONA WINDPOWERGRID INTEGRATIONEXPERIENCE

    Paris, 26th August 2010

    scar Alonso

    Teresa Arlabn

  • 7/25/2019 ACCIONA - Grid Integration Experience CIGRE 2010ID31VER89

    2/23

    Introduction

    - TSO DSO Grid Requirements:

    - Voltage support: Normal and Transients.- International approach.- Improvements in: turbines and substation controls

    -

    - Steady state features:

    - Reactive power capability

    - Wind Turbine Temperature Optimizer

    - Grid Transient features: Enhanced LV/HV RT capability- Substation General Management System.

    - Future trends: Preliminary research results.

  • 7/25/2019 ACCIONA - Grid Integration Experience CIGRE 2010ID31VER89

    3/23

    1GRID SUPPORT REQUIREMENTS

    - Every country establishes distinct specs.

    - Different requirements for transmission or distribution lines.

    -

    Brief approach to grid operators demands

    - Normal operation small voltage variations.

    - Transients: LVRT and HVRT.

    - Active power limiting.

    - Quality: Flicker, harmonics, unbalance, etc- Protections, metering, etc

    - Coming soon demands: frequency control

  • 7/25/2019 ACCIONA - Grid Integration Experience CIGRE 2010ID31VER89

    4/23

    1GRID SUPPORT REQUIREMENTS

    - 5% voltage steps response in 1 to 5 s.- Reactive power range: +/- 35% Rated Power.

    - Operation on voltage range (PCC): +/- 15%.

    Normal operation demands for Voltage Controls:

    - . .

    Grid disturbances demands:

  • 7/25/2019 ACCIONA - Grid Integration Experience CIGRE 2010ID31VER89

    5/23

    AW changes towards an enhanced grid integration1GRID SUPPORT REQUIREMENTS

    - Turbine level:

    - Increased reactive power range (40%).

    - Efficient reactive power management.

    - Improved LVRT/HVRT techniques.

    - Substation Level:- Improved technology (control & comms).

  • 7/25/2019 ACCIONA - Grid Integration Experience CIGRE 2010ID31VER89

    6/23

    2Main features:- Doubly Fed Induction generator (12 kV):

    - IGBT-Based Power converter

    - Variable Speed

    - Pitch Control

    ACCIONA WINDPOWER TECHNOLOGY:AW1500 / 3000

    AW3000 and AW1500

    iS iPvS Prot. Field bustotal

    Two paths to reach the power grid:

    - Stator

    - Grid side converter

    Two reactive power sources

    12 kV

    DFIG

    3

    ContactorModule

    o u e

    vR

    690V

    voltage

    IGBT-based Back-to-Back

    Power Converter

    Active

    Crowbar

    PsQs PGrid

    QGrid

    Power Converter

    Control Unit (CCU)

    Wind Turbine ControlUnit (PLC)

    Ps_spQs_sp

    Qgrid_sp_gen

    Qtotal_sp

    (or Vsp)

  • 7/25/2019 ACCIONA - Grid Integration Experience CIGRE 2010ID31VER89

    7/23

    3Extended Reactive Power Range: 40%

    Curva Nominal Potencia Activa - Potencia Reactiva/

    Rated Active - Reactive Power curve

    2500

    3000

    Increased generator & power

    GENERATING REACTIVE POWER:AW technology steady state operation features.

    0

    500

    1000

    1500

    2000

    -1

    400

    -1

    200

    -1

    000

    -

    800

    -

    600

    -

    400

    -

    200 0

    200

    400

    600

    800

    1

    000

    1

    200

    1

    400

    Q [kVAr]

    P[kW]

    AW3000

    converter ratings for anincreased reactive powercapability:

    - From 100 kW to rated: up to

    +/-1200kVAr.- Zero active power: +/-500kVA

    available.

  • 7/25/2019 ACCIONA - Grid Integration Experience CIGRE 2010ID31VER89

    8/23

    3Wind Turbine Temperature Optimizer (WTTO)

    Reactive power distributed between stator and grid side converter inorder to minimize losses in the electrical component with the highesttemperature (or higher thermal index, th_x)

    fRe_GridfeStatorfReTotal QQQ += StatorSQ

    x =

    GENERATING REACTIVE POWER:AW technology steady state operation features.

    _MaxStator_

    fRe_GridMax_StatorfRe_SfRe_Total QQxQ +=

    PI controller to determine xs:

    Minimising temperatures or th_x

    - Stator windings: xs should move upwards

    - Rotor windings: xs should move downwards

    xs

    ( )x_ambx_Lim

    x_ambx

    TT

    TTx_th

    =

  • 7/25/2019 ACCIONA - Grid Integration Experience CIGRE 2010ID31VER89

    9/23

    3Wind Turbine Temperature Optimizer (WTTO): Results.

    Comparison: A1: Generating Q by the stator, then

    grid side converter.

    A2: Generating Q by the grid side

    GENERATING REACTIVE POWER:AW technology steady state operation features.

    converter, t en stator.

    Results:

    Lower maximum temperatures.

    Smoother thermal dynamics.

    Higher reliability and availability.

    Enlarged life span.

  • 7/25/2019 ACCIONA - Grid Integration Experience CIGRE 2010ID31VER89

    10/23

    Acciona windpower LVRT curve3GRID DISTURBANCES:AW technology operation features

    AWP technology

    - Changes in the drive train design.

    - Increased power converter ratings.

    - New control techniques.

    How is AW able to offer

    such a response?

  • 7/25/2019 ACCIONA - Grid Integration Experience CIGRE 2010ID31VER89

    11/23

    LVRT / HVRT New Torque and Pitch strategies

    - LV & HV RT based on available active power:depends on the remaining voltage and reactive

    3GRID DISTURBANCES:AW technology operation features

    curren n ec on.- Improved damping system: Available torque is usedto damp oscillations even during grid faults.

    - Fast Pitching: to get a pre-calculated steady anglegiven by the available active power.

  • 7/25/2019 ACCIONA - Grid Integration Experience CIGRE 2010ID31VER89

    12/23

    Max = 1272.12 rpm

    Max = 1246.5 rpm

    88 rpm 38 rpm

    3 Example (LVRT test)- 90% Volt depth and 2s long.-Turbine load 90%.GRID DISTURBANCES:AW technology operation features

    - Longer and deeper voltagedips.

    - Reduction of oscillations andmechanical loads.

  • 7/25/2019 ACCIONA - Grid Integration Experience CIGRE 2010ID31VER89

    13/23

    3LVRT / HVRT New Torque and Pitch strategy: Field tests results

    Reduction of speed oscillationsand mechanical loads.

    GRID DISTURBANCES:AW technology operation features

    New TechniquesPrevious Techniques

  • 7/25/2019 ACCIONA - Grid Integration Experience CIGRE 2010ID31VER89

    14/23

    1 .- Voltage Control Principles

    PLC QSp_Q_Sub

    Wind Turbine

    Sp_Vsub4

    substation

    Sp_Qs (Stator)

    Comms: 200 ms polling cycle

    3VOLTAGE CONTROL

    Sp_QPC (GridSide Converter)

    SUB Sharing

    Q limits

    Grid Analyser

    P, Q, VSubstationmeasures

    (TSOs) (Sp_Vsub)

    PISP_Vsub

    Vmeas

    SP_Q_Sub+

    -

    +Qmax

    -Qmax

    SP_max

    SP_min

    FilterPI-Based Controller

    Parameters:

    KpTiFilter

  • 7/25/2019 ACCIONA - Grid Integration Experience CIGRE 2010ID31VER89

    15/23

    3VOLTAGE CONTROL WAUBRA (AUS)

    2 .- WAUBRA (AUS) Last experience

    - 128 wind turbines model AW1500.

    - POI at 220 kV 2 transformers 220 kV / 66 kV / 150 MW

    - .

    - Two voltage controllers:

    - Transformer 1. 66 kV side.

    - Transformer 2. 66 kV side.

    - Requirements:

    - Response for voltage steps of 5% in less than 5 secs.

    - Reactive capacity +/- 30% Rated Power.

  • 7/25/2019 ACCIONA - Grid Integration Experience CIGRE 2010ID31VER89

    16/23

    3 .- Set point step tests

    Set Point steps

    3VOLTAGE CONTROL WAUBRA (AUS)

    Pink Substation Reactive powerBlue Substation Voltage

    Saturation

  • 7/25/2019 ACCIONA - Grid Integration Experience CIGRE 2010ID31VER89

    17/23

    4.- Transformer Tap changer tests

    Transformer Tap changer test

    3VOLTAGE CONTROL WAUBRA (AUS)

    Pink Substation Reactive powerBlue Substation Voltage

    -

  • 7/25/2019 ACCIONA - Grid Integration Experience CIGRE 2010ID31VER89

    18/23

    5 .- Coordination after LV or HV faults (Now, standard)

    Sub Control Sub ControlTurb Control

    3VOLTAGE CONTROL

    Smoothed reactive power restorationRamp up/down 30 to 50 kVAr/s

    LV event 0.5 s(real measurement)

  • 7/25/2019 ACCIONA - Grid Integration Experience CIGRE 2010ID31VER89

    19/23

    1 .- Improved Voltage control

    - Same control for weak (SCR10).

    4FUTURE DEVELOPMENTS

    - Detection of the grid characteristics:- Fast grid impedance selection method.

    - Fast estimation algorithm of the Thevenin grid voltage.

    - Principle of operation: Steady-state pre-calculated response.- Accurate, robust and safe even with long polling times.

    - Patents pending.

  • 7/25/2019 ACCIONA - Grid Integration Experience CIGRE 2010ID31VER89

    20/23

    4FUTURE DEVELOPMENTS

    1 .- Improved Voltage control (1 2 s response)

    RX grid change (SCR 20 to less than 4!)

    Set Pointchanges

    Grid voltage changes

  • 7/25/2019 ACCIONA - Grid Integration Experience CIGRE 2010ID31VER89

    21/23

    4FUTURE DEVELOPMENTS

    2 .- Wind Park Power Management

    State information sent from every turbine (example, th_x) to thesubstation PLC is used to distribute global set points:

    Reactive power ct ve power

    Improving:- Efficiency- Reliability

  • 7/25/2019 ACCIONA - Grid Integration Experience CIGRE 2010ID31VER89

    22/23

    4FUTURE DEVELOPMENTS

    3 .- Accredited Grid Integration field test report

    Field tests to demonstrate grid code compliance.Certified Laboratory testing and accredited procedure

    (in search of an international acceptability).

    - Current situation: at Turbine level:- LVRT and HVRT according to most exigent grid codes.

    - Quality: Harmonics. Flicker. Etc.

    - Future perspective:

    - Turbine level: Active power management. Islanding, etc- Substation level:

    - Voltage, active power and frequency controls

    - Protections. Harmonics. Flicker. Islanding. Etc.

  • 7/25/2019 ACCIONA - Grid Integration Experience CIGRE 2010ID31VER89

    23/23

    CONCLUSSIONS

    AWP Grid Voltage support :

    AW1500 and AW3000 Turbines:

    Improved LVRT / HVRT behavior.

    Extended Reactive Power range.

    Substation: Accurate and reliable hardware and controls

    (improved close future solutions, R&D benefits).

    Acciona WindPower commitment to demonstrate Full Grid