Top Banner
AC Power Solutions Outdoor Uninterruptible Power Supplies Indoor Uninterruptible Power Supplies Backup Power Solutions Enclosures Batteries Generators Accessories Custom Solutions
56

AC Power Solutions - Alpha Technologies

Feb 09, 2022

Download

Documents

dariahiddleston
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: AC Power Solutions - Alpha Technologies

AC Power Solutions

Outdoor Uninterruptible Power SuppliesIndoor Uninterruptible Power SuppliesBackup Power SolutionsEnclosuresBatteriesGeneratorsAccessoriesCustom Solutions

Page 2: AC Power Solutions - Alpha Technologies

AlphaTechnologiesLtd.

AlphaTechnologiesLtd.develops,manufacturesandmarketsindoorandoutdoorUPSandACBackupPowersolutionsandprovides

market specific products for the Telecom, DataComm, Traffic, Parking, Medical, and Security markets. Alpha also works in partnership

with globally recognized companies to provide customized OEM solutions.

Alpha products and solutions are known for their high-quality, feature-rich systems that are engineered to meet industry requirements and

withstandharshenvironmentalconditions.Sales,service,andmaintenanceisavailablethroughanetworkofdedicatedcenters

worldwide24/7.

AlphaTechnologiesLtd.isamemberofTheAlphaGroup.

TheAlphaGroup

The Alpha Group represents an alliance of independent companies who share a common philosophy – to create world class Total Power

Solutions.

Collectively, The Alpha Group is a leader in the power industry with thirty years of outdoor power expertise, and over two million systems

installed globally. Its members develop and manufacture AC and DC power conversion, protection, and standby products. Applications for

theseproductsincludebroadband,telecom,AC/UPS,commercial,industrial,anddistributedgeneration,foraworldwidecustomerbase.

AlphaGroupcompaniesalsoprovidearangeofinstallation,serviceandmaintenanceservices.

Members of The Alpha Group include Alpha Technologies Inc., Alpha Technologies Ltd., Alpha Energy, Alpha Industrial Power, Argus

Technologies, and G.B. Enterprises.

AboutAlpha

Page 3: AC Power Solutions - Alpha Technologies

Power Solutions for Outdoor and Harsh Environments ......................................... 3

Novus FXM ................................................................................................................. 4

Communications and Monitoring ................................................................................ 5

Novus Micro Secure 100 ............................................................................................. 6

Alpha Novus Micro, Micro XL, Micro XL3 ................................................................... 7

Transfer and Bypass Switches .................................................................................... 8

Batteries and Accessories ...................................................................................... 9

AlphaCell™ Gold and GXL ........................................................................................ 10

AlphaCell™ AGM ...................................................................................................... 12

AlphaCell™ FT .......................................................................................................... 13

AlphaCell™ SMU HR ................................................................................................ 14

Battery Accessories .................................................................................................. 15

Generators ............................................................................................................ 17

AlphaGen™ DCX 3000 ............................................................................................. 18

AlphaGen™ Curbside ............................................................................................... 19

Enclosures ............................................................................................................ 21

Alpha Outdoor Enclosure Side Mount 6 ................................................................... 22

Alpha B4 ................................................................................................................... 23

Flextra P Series ......................................................................................................... 24

Flextra U Series ......................................................................................................... 25

Flextra Z Series ......................................................................................................... 26

Flextra Node.............................................................................................................. 27

Radium Mini Bay ....................................................................................................... 28

Indoor Solutions ................................................................................................... 29

Indoor UPS Topology ................................................................................................ 30

ALI Elite ..................................................................................................................... 32

ALI Elite XL ................................................................................................................ 34

ALI Elite Extended Run Time Battery Pack ............................................................... 35

Pinnacle Plus ............................................................................................................ 36

Pinnacle Plus High Power ......................................................................................... 38

CFR ........................................................................................................................... 40

AlphaMED®............................................................................................................... 43

Comet ....................................................................................................................... 45

Galaxy 4000 .............................................................................................................. 47

Galaxy 3000 .............................................................................................................. 49

Electrical Receptacles .......................................................................................... 51

Service .................................................................................................................. 52

Uninterruptible Power Supply Selection Guide .................................................... 53

Table of Contents

Alpha AC Catalogue 2008 For Prin1 1 7/30/2008 3:02:14 PM

Page 4: AC Power Solutions - Alpha Technologies

Alpha AC Catalogue 2008 For Prin2 2 7/30/2008 3:02:14 PM

Page 5: AC Power Solutions - Alpha Technologies

Power Solutions for Outdoor and Harsh EnvironmentsAlpha Technologies Ltd. specializes in providing AC power solutions for harsh environments. With over 30 years of experience in the global outdoor market, Alpha is positioned as the leader in providing rugged AC powering solutions, including hardened outdoor enclosures, uninterruptible power supply (UPS) modules, specialty batteries, battery accessories and generators to a large and recognizable customer base.

A truly rugged UPS system has many unique characteristics including conformal coated PCBs which protect against exposure to moisture, high levels of humidity and dust, carefully selected components to operate fully in extreme temperatures and boards designed to minimize environmental impact. In addition, products and solutions are designed to meet, outdoor installation, shock and vibration, standards. Systems must be designed to operate under extreme temperature conditions. Because Alpha understands these requirements, the Novus line of outdoor products is capable of withstanding extreme temperatures.

Alpha’s powering solutions also offer superior communications capabilities including remote monitoring via SNMP web-based communication. Real-time alerts and reports on UPS status can be sent to four different email addresses, or can be monitored from your PC, Internet-connected mobile phone or PDA, each with selectable event severity levels to trigger different notifications of events, faults and alarms.

Alpha’s power solutions for harsh environments have been used across the world for the last 30 years, operating with great reliability to ensure that mission-critical applications remain working even in times of unstable and unreliable power.

Alpha AC Catalogue 2008 For Prin3 3 7/30/2008 3:02:14 PM

Page 6: AC Power Solutions - Alpha Technologies

Clean, uninterruptible backup power ensures your system will remain running during power outages

Wide range Automatic Voltage Regulation without going to batteries lengthens battery life, even during periods of surge or sag in the line voltage

External communications via RS-232 port or (optional) Ethernet SNMP interface provides local or remote monitoring and control

Independently programmable and dry contact relays allow tracking and controlling of key functions

Event and alarm logging with time and date stamping simplifies and accelerates troubleshooting

A wide operating temperature range of -40º to 74ºC (-40º to 165ºF) is suitable for the most extreme operating environments

Control and power connection panels can be rotated for mounting and display in any orientation for viewing convenience

Temperature compensated battery charging protects batteries from over charging at extreme temperatures, extending the life of the battery

Novus FXM power modules provide constant, reliable UPS grade backup power management for Traffic, Security, Telecommunications and other applications. The FXM can operate in temperatures of -40°C to 74°C (-40°F to 165°F) supporting your mission critical applications with clean, uninterruptible power. The FXM modules are CSA and UL approved and are adaptable for vertical1 or horizontal orientations as well as rack mounting. Double buck and Double boost is designed into the module to accept a wider input range, providing constant output voltage without switching to system batteries. The FXM’s built-in communications intelligence software reports UPS event status, collects valuable planning and maintenance data, and monitors your site, through a Windows-based GUI. It also offers a real-time clock for statistical analysis and event diagnostics. An optional SNMP Ethernet interface is available for remote monitoring from virtually any internet-supported location.

Agency Compliance

Electrical safety: UL1778, CSA 22.2 No 107.3-03

Marks: CCSAUS /CE*

EMI: Class A FCC/CISPR [EN 50091-2:1995] *CE applies to 230 VAC version only

Power Module: FXM 650 FXM 1100 FXM 2000

North America International North America International North America International

Battery String Voltage: 24VDC/48VDC 24VDC 48VDC 48VDC 48VDC 48VDC

Nominal Voltage: 120VAC 230VAC 120VAC 230VAC 120VAC 230VAC

Nominal Frequency: auto-sensing

Input Current: 8.7A 4.5A 15.5A 8.0A 20.0A 32A

Input Voltage Range: 85-175VAC 150-328VAC 85-175VAC 150-328VAC 85-150VAC 150-281VAC

Output Current: 5.8A 3.0A 9.9A 5.1A 17.9A 9.4A

Output Voltage Regulation +/- 10% over input voltage range

Output power at 50°C: 650W/VA 650W/VA 1100W/VA 1100W/VA 2000W/VA 2000W/VA

WxHxD 17”x3.47”x9”

432x88x229mm

15.5”x5.22”x8.75”

394x133x222mm

15.5”x5.22”x8.75”

394x133x222mm

Weight25lb/30lb for 48V

11kg

35lb

16kg

35lb

16kg

Specifications

Alpha Novus FXM

Outdoor SolutionsNovus FXM 650, 1100, 2000

4

Out

do

or

So

luti

ons

Alpha AC Catalogue 2008 For Prin4 4 7/30/2008 3:02:14 PM

Page 7: AC Power Solutions - Alpha Technologies

Novus User Software

Novus User Software is a graphical user interface (GUI) designed to help Alpha UPS users monitor, control and set various parameters for their UPS systems through a computer using a standard RS-232 connection or through the internet when the UPS is equipped with an Ethernet/SNMP card. Users are able to read and display UPS events, warnings, date, time and relay configurations through this Windows-based environment. The software is an excellent maintenance and troubleshooting tool that automatically updates information every five seconds and records events and warnings with time/date stamps.

Get real-time notification of every alarm and fault that occurs so that you are immediately in a position to take action. Easy to customize to your exact needs, the Ethernet edition allows you to set your own notification preferences via PC and receive notifications to any PC, mobile phone, PDA, or any device that accepts email.

Ethernet/SNMP Card Option - Novus FXM, Novus Micro, Novus Micro Secure

For greater effectiveness, control and communication over your UPS system, choose the Ethernet/SNMP card option that is available for our Novus FXM, Novus Micro and Novus Micro Secure products. The Ethernet/SNMP card is factory installed allowing for communication with the Alpha UPS remotely through a web based interface. The Ethernet/SNMP card is powered by the UPS batteries eliminating the need for an external power source. The communication card is capable of providing notifications to four different email addresses and to devices such as your PC, a mobile phone or PDA. Outgoing notifications can be customized with selectable severity levels and triggered by events, faults and/or alarms.

User’s PC(using Web browser)

SNMP Server

InternetIntranet

On-SiteEthernet

ConnectionEthernet Port

Crossover Cable FXM

UPSFXM

MonitorCard

User’s PC(using Web browser for Ethernet connection to

on-site computer)

Outdoor SolutionsCommunications and Monitoring

5

Outd

oo

r So

lutions

Alpha AC Catalogue 2008 For Prin5 5 7/30/2008 3:02:15 PM

Page 8: AC Power Solutions - Alpha Technologies

Nominal Specifications

Power Module Novus Micro Secure

North America International

Battery String Voltage 24VDC 24VDC

Nominal Voltage 120VAC 230VAC

Nominal Frequency 60Hz 50Hz

Input Current 2.0A 1.0A

Input Voltage Range 85 – 150VAC 154 – 323VAC

Output Current 0.83A @ 120VAC

4.2A @ 24VAC 0.43A @ 230VAC 230VAC

4.2A @ 24VAC 60Hz 50Hz

WxHxD 15”x11.5”x6”

381x292x152mm

Weight (with 4 9Ah batteries)

45lb / 20.4kg

Run Time* 2 hrs 15 mins

* Run time on battery power can vary based on loads, temperature and battery. Other battery options are available.

All weather protection with durable outdoor NEMA 3R rated plastic enclosure

Enhanced battery life with wide-range Automatic Voltage Regulation

Local or remote monitoring and control through RS-232 port or (optional) SNMP Ethernet interface

Tracking and controlling of key functions through independently programmable relays

Simplified troubleshooting through event and alarm logging with time and date stamping

Maximum mounting flexibility for accommodation of space requirements1

The Novus Micro Secure provides constant, reliable backup power for small critical load applications such as security cameras, surveillance systems, WiFi equipment and outdoor lighting. With its NEMA 3R enclosure, this easy-to-install solution includes a UPS power module and battery bank for an all-in-one out-of-the box solution: just wire the inputs, your load and communications (if ordered), and it’s ready for operation. Due to its compact design and light weight, the Micro Secure can be wall or pole mounted (when using the optional pole mounting bracket). The Micro Secure can also be used as a power supply for security camera applications. An optional Ethernet/SNMP interface is available.

1 Mounting brackets sold separately

Agency Compliance

Electrical safety: UL1778, CSA 22.2 No. 107.1

Marks: CCSAUS , CE* EMI: Class A FCC/CISPR, EN50091-1-2, EN60950 *CE applies to 230VAC version only

Alpha Novus Micro Secure 100

Outdoor SolutionsNovus Micro Secure 100

6

Out

do

or

So

luti

ons

Alpha AC Catalogue 2008 For Prin6 6 7/30/2008 3:02:19 PM

Page 9: AC Power Solutions - Alpha Technologies

Clean, uninterruptible backup power ensures your system will remain up and running during power outages

Wide range Automatic Voltage Regulation without going to batteries extends battery life, even during periods of surge or sag in voltage from utility power

External communications via RS-232 port or (optional) Ethernet SNMP interface provides local or remote monitoring control

Independently programmable control and report relays allow tracking and controlling of key functions1

User-friendly LCD display allows "at-a-glance" monitoring and troubleshooting2

Event and alarm logging with time and date stamping simplifies and accelerates troubleshooting

A wide operating temperature range of -40º to 74ºC (-40º to 165ºF)3 is suitable for most extreme operating environments

Temperature compensated battery charging protects batteries from over charging at extreme temperatures

The Alpha Novus Micro line provides constant reliable backup power in 300VA or 1000VA models for use in Access Control, Security, Parking, Public Utility and Telecommunications applications. This all-in-one solution is comprised of a NEMA 3R outdoor rated enclosure, an uninterruptible power supply module and battery bank. Batteries selection is based on the application and run time requirements. Be sure to order the appropriate battery connector kit for your specific application. The Novus Micro can withstand harsh outdoor conditions operating in temperatures of -40°C to 74°C (-40°F to 165°F) to support your mission critical applications with clean, uninterruptible power. Optional Battery Heater Mats provide heat to the batteries and are recommended for optimal performance in cold climates. For extended run time applications, the XL or XL3 provide space to accommodate additional batteries.

Nominal Specifications

Power Module: Novus Micro 300 Novus Micro 1000

North America International North America International

Battery String Voltage 24VDC 24VDC 48VDC 48VDC

Nominal Voltage 120 VAC 230VAC 120VAC 230VAC

Nominal Frequency 60Hz 50Hz 60Hz 50Hz

Input Current 5.4A 2.8A 14A 7.3A

Input Voltage Range 85-175VAC 150- 328VAC 85-175VAC 150- 328VAC

Output Current 2.5A 1.3A 8.3A 4.3A

Output Voltage Regulation +/- 10% over input voltage range

Output Power @50°C 300W/VA 300W/VA 1000W/VA 1000W/VA

Run Time* 2 x 50Ah batteries - 2 hrs 12 mins 4 x 18Ah batteries - 26 mins

* Run time on battery power can vary based on loads, temperature and battery. Other battery options are available.

Dimensions (W x H x D) Novus Micro 14.1” x 19.7” x 11.6” 358 x 500 x 294 mm

Novus Micro XL 14.1” x 30.6” x 11.6” 358 x 776 x 294 mm

Novus Micro XL3 14.1” x 52.4” x 11.6” 358 x 1330 x 294 mm

Weight (without batteries) 43.4 lb / 19.7 kg 49.8 lb / 19.7 kg 69.2 lb / 22.6 kg

Agency Compliance

Electrical safety: UL1778, CSA 22.2 No. 107.3,

EN50091-1-2, EN60950

EMI: Level A FCC, CISPR22, EN55022

Marks: CCSAUS , CE* *CE applies to 230VAC version only

Novus Micro Novus Micro XL Novus Micro XL3

Alpha Novus Micro 1000

1 This feature is available on the Novus Micro 300 model only2 This feature is optional for the Novus Micro 300 model3 This applies to the UPS module only. Batteries may require a heater mat at lower temperatures. Output power derates after 50ºC

Outdoor SolutionsAlpha Novus Micro, Micro XL, Micro XL3

7

Outd

oo

r So

lutions

Alpha AC Catalogue 2008 For Prin7 7 7/30/2008 3:02:23 PM

Page 10: AC Power Solutions - Alpha Technologies

Alpha offers a range of transfer and bypass switches as part of its total power solutions package. These switches allow for power to be seamlessly migrated between utility line to battery backup or generator.

Alpha Automatic Transfer Switch

120V/30A 230V/16A Alpha’s Automatic Transfer Switch acts as a fail-safe device by switching the critical load to the utility line should a fault occur in the UPS. The ATS ensures that clean power is always provided to the critical load, ensuring that your mission-critical equipment always remains running in the event of an outage. This transfer switch also includes a standard manual bypass switch which eliminates costly equipment downtime while servicing the UPS or replacing the batteries.

Alpha Automatic Generator Transfer Switch

120V/30A 230V/16A Alpha’s Automatic Generator Transfer Switch automatically transfers the input to the UPS from the utility line to a portable AC generator. The GTS allows the generator to recharge the batteries and ensure your applications remain in operation during extended power outages. For manually connecting or disconnecting a generator, a standard switch is included.

Alpha Maintenance Bypass Switch

120V 230V Option not available Alpha’s Maintenance Bypass Switch allows the user to manually bypass the UPS system for service or routine maintenance.

Other Mounting Options

Wall mount kit – Part number 740-756-21 Rack mount kit – Part number 593-364-P4

Automatic Transfer Switch

Automatic Generator Transfer Switch

Alpha Maintenance Bypass Switch

Mounting Options

Outdoor SolutionsTransfer and Bypass Switches

8

Out

do

or

So

luti

ons

Alpha AC Catalogue 2008 For Prin8 8 7/30/2008 3:02:35 PM

Page 11: AC Power Solutions - Alpha Technologies

Batteries & AccessoriesAlpha offers a comprehensive line of AlphaCellTM batteries in a number of sizes and technologies to support your outdoor applications. Included in our battery line are AGM and Gel batteries that offer extended runtime and warranty configurations. Our Gel Cell batteries last longer and are more reliable because of their excellent heat displacement characteristics. Independently tested, AlphaCellTM GXL batteries come with a full replacement non-prorated warranty. These batteries have seven to eight years of expected life and trouble free performance offering reduced maintenance costs. Our AGM batteries are also available to support a variety of applications. Both models are ready with 100% out of the box capacity.

In addition to our battery offerings, Alpha also has accessories to complement your battery installation or support your battery testing needs.

Alpha AC Catalogue 2008 For Prin9 9 7/30/2008 3:02:35 PM

Page 12: AC Power Solutions - Alpha Technologies

Valve Regulated Lead Acid (sealed) batteries

Designed for indoor, outdoor standby applications

100% out-of-box runtime capacity

Maintenance-free threaded inserts

100% replacement warranty

Alpha offers a wide selection of sealed VRLA-AGM and VRLA-Gel batteries to provide power to a number of applications. Gel batteries provide good thermal dissipation to help ensure the best performance for you application. Alpha’s standby battery offering includes six different models incorporating four unique battery technologies, ensuring optimal performance for all outdoor powering applications. These batteries provide improved performance, longer runtimes and extended service life.

BatteriesAlphaCellTM Gold & GXL

10

Bat

teri

es a

nd A

cces

sori

es

AlphaCell™ Gold & GXL

Alpha AC Catalogue 2008 For Prin10 10 7/30/2008 3:02:41 PM

Page 13: AC Power Solutions - Alpha Technologies

General Specifications

Model 215 GOLD-HP 190 GOLD-HP 210 GXL 180 GXL 165 GXL 85 GXL-HP

Heat resistance Extreme Extreme High High High Extreme

TerminalsThreaded insert 1/4” - 20 UNC

Threaded insert 1/4” - 20 UNC

Threaded Insert 1/4” - 20 UNC

Threaded Insert 1/4” - 20 UNC

Threaded Insert 10-32 UNF

Typical Runtime (minutes) 215 190 210 180 165 85

Cells Per Unit 6 6 6 6 6 6

Voltage Per Unit 12.8 12.8 12.8 12.8 12.8 12.8

Conductance Value 1175 1100 1175 1100 1000 600

Max. Discharge Current (A) 900 900 900 900 800 600

Short Circuit Current (A) 2800 2600 2800 2600 2500 2200

10 Second Volts @ 100A 11.4 11.3 11.4 11.3 11.2 10.8

Impedance @ 60Hz (Ohms) 0.005 0.005 0.005 0.005 0.0055 0.0065

Capacity at 20hrs (to 1.75VPC) 107Ah 95Ah 106Ah 94Ah 86Ah 50Ah

BCI Group Size 31 31 31 31 27 22

Mechanical Specifications

Weight (lb/kg) 72/32.7 66/30 72/32.7 66/30 63/28.6 39.6/18

Height w/ Terminals (in/mm) 8.48/215.4 8.48/215.4 8.48/215.4 8.48/215.4 9.05/229.8 8.09/205.6

Width (in/mm)* 13.42/340.9 13.42/340.09 13.42/340.09 13.42/340.09 12.5/317.8 8.99/228.3

Depth (in/mm)* 6.80/172.7 6.80/172.7 6.80/172.7 6.80/172.7 6.83/173.4 5.47/138.9

Operating Temperature Range

Discharge-40 to 71°C (-40 to 160°F)

-40 to 71°C (-40 to 160°F)

-40 to 71°C (-40 to 160°F)

-40 to 71°C (-40 to 160°F)

-40 to 71°C (-40 to 160°F)

-40 to 71°C (-40 to 160°F)

Charge (with temp compensation)

-23 to 60°C (-9.4 to 140°F)

-23 to 60°C (-9.4 to 140°F)

-23 to 60°C (-9.4 to 140°F)

-23 to 60°C (-9.4 to 140°F)

-23 to 60°C (-9.4 to 140°F)

-23 to 60°C (-9.4 to 140°F)

Float Charging Voltage (VDC) 13.5 to 13.8 13.5 to 13.8 13.5 to 13.8VDC 13.5 to 13.8VDC 13.5 to 13.8VDC 13.5 to 13.8VDC

AC Ripple Charger 0.5% RMS or 1.5% of float charge voltage recommended for best results. Max. allowed = 4% P-P

*: Dimensions at top of battery For information on the warranties please contact your sales rep.

Current Discharge Ratings Table in Amps (end Voltage 1.75VPC)

Hours 1 2 3 4 6 8 10 12 20 24 48 72 100

215 Gold 67.8 40.5 29.1 22.9 16.1 12.6 10.2 8.7 5.46 4.61 Call Call Call

210 GXL 66.3 39.6 28.5 22.4 15.8 12.3 10 8.54 5.34 4.51 Call Call Call

190 Gold 64.5 37.1 26.6 20.8 14.6 11.4 9.4 7.9 4.96 4.2 2.2 1.5 1.08

180 GXL 61.2 35.2 25.2 19.7 13.9 10.8 8.9 7.5 4.7 4 2.1 1.4 1.03

85 GXL-HP 33.2 18.8 13.3 10.4 7.34 5.7 4.68 3.97 2.5 2.12 1.11 0.76 0.56

165 GXL 55.9 32.8 23.5 18.4 12.9 10.0 8.2 6.9 4.3 3.7 1.9 1.29 0.94

BatteriesAlphaCellTM Gold & GXL

11

Batteries and

Accesso

ries

Alpha AC Catalogue 2008 For Prin11 11 7/30/2008 3:02:42 PM

Page 14: AC Power Solutions - Alpha Technologies

Specifications

Model: 135 AGM-P 160 AGM

Silver Alloy: AGM-P N/A

CA/SN Alloy: N/A N/A

Typical Runtime (minutes)2: 135 160

Cells Per Unit: 6 6

Voltage Per Unit: 12.8 12.8

Conductance Value: 1125 1300

Max. Discharge Current (A): 800 800

Short Circuit Current (A): 3100 3300

10 Second Volts @ 100A: 11.5 11.6

Ohms Impedance 60Hz: 0.005 0.004

Capacity at 20hrs: (to 1.75VPC) 75Ah 88Ah

BCI Group size: 24 27

Weight (lb/kg): 54.8/24.9 62/28

Height w/ terminals (in/mm): 8.02/203.6 9.05/229.8

Width (in/mm)4: 10.26/260.5 12.57/317.8

Depth (in/mm)4: 6.83/173.4 6.83/173.4

Operating Temperature Range

Discharge: -40 to 71˚C -40 to 71˚C

(-40 to 160˚F) (-40 to 160˚F)

Charge (with temp compensation): -23 to 60˚C -23 to 60˚C

(-9.4 to 140˚F) (-9.4 to 140˚F)

Float Charging Voltage (VDC): 13.5 to 13.8 13.5 to 13.8

AC Ripple Charger:0.5% RMS or 1.5% of float charge voltage recommended for best results. Max. allowed = 4%

1 Warranty varies by country and region. Consult your sales person for details.2 Runtimes calculated using a 25A DC constant current load with voltage discharge to 1.75V/cell @ 25˚C.3 L-Type: applies to 210/180/165 GXL and AGM models. Copper Alloy 10-32 Insert: applies to 85 GXL only. Copper Alloy 1/4" insert applies to 135 GXL only.4 Dimensions at top of battery.

BatteriesAlphaCell™ AGM

Designed for indoor, outdoor standby applications

100% out-of-box runtime capacity

Maintenance-free threaded inserts

100% replacement warranty

Convenient carrying handle standard on all models

12

Bat

teri

es a

nd A

cces

sori

es

AlphaCell™ AGM

Alpha AC Catalogue 2008 For Prin12 12 7/30/2008 3:02:44 PM

Page 15: AC Power Solutions - Alpha Technologies

BatteriesAlphaCell™ FT

Front terminals with protective covers

Valve regulated lead acid batteries

Long life gel batteries can be used outdoors

Ideal for telecom and cable applications

Alpha enhances its AlphaCellTM battery family to include the sealed FT series of front terminal batteries for cable television and telecommunication applications. The AlphaCellTM FT series are designed for long life. Benefits of these new batteries include: central gassing system, hinged front covers, integral flame arrestor, recyclable lead and plastics and low self-discharge rates. These batteries come with a handle for carrying convenience.

General Specifications

Model 195 GXL-FT 225 AGM-FK

Service Life Extended Extended

Sealed VRLA Valve Regulated Lead acid Valve Regulated Lead acid

Heat resistant High Moderate

Hydrogen Emission Low Low

Terminals 16mm Insert M6 thread 16mm Insert M6 thread

Typical Runtime (minutes) 195 225

Cells Per Unit 6 6

Voltage Per Unit 12.8 12.8

Conductance Value 1200 1400

Max. Discharge Current (A) 400 400

Short Circuit Current (A) 3000 3100

10 Second Volts @ 100A 10.8 11.2

Impedance @ 60Hz (Ohms) 0.0041 0.0045

Capacity at 20hrs (to 1.75VPC) 110Ah 88Ah

Mechanical Specifications

Weight (lb/kg) 76.29/34.52 75.14/34

Height w/ Terminals (in/mm) 11.22/285 11.22/285

Width (in/mm)* 4.33/110 4.33/110

Depth (in/mm)* 15.55/395 15.55/395

Operating Temperature Range

Discharge -40 to 71°C (-40 to 160°F) -40 to 71°C (-40 to 160°F)

Charge (with temp compensation) -20 to 50°C (-4 to 122°F) -20 to 50°C (-4 to 122°F)

Float Charging Voltage (VDC)Float 2.27 to 2.30VPC @25°C cycling 2.35VPC@25°C

Float 2.27 to 2.30VPC @25°C cycling 2.35VPC@25°C

AC Ripple Charger 0.5% RMS or 1.5% of float charge voltage recommended for best results. Max. allowed = 4% P-P

*: Dimensions at top of battery For information on the warranties please contact your sales rep.

Current Discharge Ratings Table in Amps (end Voltage 1.75VPC)

Hours 1 2 3 4 6 8 10 12 20 24 48 72 100

195 GXL-FT 71.1 38.0 26.8 21.1 15.2 12.0 9.92 8.48 5.50 4.60 2.31 1.56 1.13

225 AGM-FT 81.00 43.10 30.30 23.70 16.70 12.90 10.40 8.90 5.70 4.80 2.43 1.62 1.18

13

Batteries and

Accesso

ries

AlphaCell™ FT

Alpha AC Catalogue 2008 For Prin13 13 7/30/2008 3:02:45 PM

Page 16: AC Power Solutions - Alpha Technologies

BatteriesAlphaCell™ SMU-HR

High Rate Discharge VRLA Battery

Power range available in 12V with capacities from 9 to 135Ah

Optimized grid for high power density

Upright, side or end mounting

Thermally welded case to cover bond eliminates leakage

Optional flame retardant ABS casing to UL94-VO

100% replacement warranty

The AlphaCell™ SMU-HR, with Absorbed Glass Mat (AGM) technology, is a high discharge rate VRLA battery specifically designed for uninterruptible power supplies, power generation, and switchgear applications. Low calcium grid alloy reduces gassing to extend battery life. This high rate discharge cycle battery is available in 12V with capacities from 9 to 135Ah.

General Specifications

Type Valve Regulated Lead Acid

Range of Capacity 9 to 35Ah

Recommended Float Voltage 13.5VPC @ 20°C (68°F)

Operating Temperature Nominal 25°C (77°F) NOTE: can operate at higher temperature up to 74°C (165°F) but degrades life of battery

Terminal Type Threaded Copper Insert

Optional UL 94 VO Flame Retardants Casing

For information on warranties please contact your sales rep.

14

Bat

teri

es a

nd A

cces

sori

es

AlphaCell™ SMU-HR

Alpha AC Catalogue 2008 For Prin14 14 7/30/2008 3:02:47 PM

Page 17: AC Power Solutions - Alpha Technologies

Battery Heater Mats

Low temperatures can compromise battery performance by reducing runtimes and slowing down the recharge rate. Battery Heater Mats combat these negative effects for better battery performance in cold conditions. In extreme environments, battery damage can result if battery heater mats are not used.Thermostat Specifications:Turns on when temperature falls below 5°C/41°F Turns off when temperature rises above 15°C/59°F

AlphaGuard™ Battery Charge Management System

AG-CMT-4 AlphaGuard™ Charge Management SC, 48V String – including Battery interface cable

The AlphaGuard is a battery charge management system that monitors and protects your batteries for runtime optimization and longer battery life. CSA and UL approved, AlphaGuard allows you to replace single batteries rather than the whole string. It spreads charge voltage equally across batteries to maximize battery life and compensates for battery differences as they age.Also available: AlphaGuard Potted Version for Below Grade Applications. The potted version is ideal for applications where batteries are installed under ground or subject to damp conditions or possible immersion.

Note: For some applications Alpha offers an extended battery warranty when AlphaGuard is used. Contact your Alpha representative for complete details.

Battery Testing Equipment

Alpha’s battery testing equipment provides accurate information about the status of installed standby batteries allowing you to budget for early detection of failed or degraded batteries and for replacements with confidence.A fast, reliable and affordable testing process. Conductance testing is coupled with a simple utility load test – arms the operator with the quality of data necessary to know the status of installed standby batteries, allowing for detection and replacement before failure occurs and puts backup during an outage at risk.

AlphaGuard™ Battery Charge Management System

Battery Heater Mats

Celltron Essential Battery Testing Equipment

AlphaGuard™ Potted version

Battery Accessories

15

Batteries and

Accesso

ries

Alpha AC Catalogue 2008 For Prin15 15 7/30/2008 3:02:52 PM

Page 18: AC Power Solutions - Alpha Technologies

Alpha AC Catalogue 2008 For Prin16 16 7/30/2008 3:02:52 PM

Page 19: AC Power Solutions - Alpha Technologies

GeneratorsAlpha offers portable and stationary DC generators for extra long back up power runtimes. Completely enclosed and water resistant for safe operation in the field, the AlphaGen™ is quiet, convenient, and extremely economical. Its oversized metal gas tank can provide extended runtimes of up to 20 hours.

Alpha AC Catalogue 2008 For Prin17 17 7/30/2008 3:02:52 PM

Page 20: AC Power Solutions - Alpha Technologies

Accessories

30’ Output Interface 10’ P/N 875-324-22 30’ P/N 875-324-20 50’ P/N 875-324-21

Ring Lug Battery Interface

P/N 874-946-21

Alligator Clamp Battery Interface P/N 874-946-20

Y-Adaptor Battery P/N 874-946-22

DCX 3000 (front view) DCX 3000 with optional Wheel Kit and Locking Handle

GeneratorsAlphaGenTM DCX 3000

Part Number: 041-028-10

Engine:Honda GX 200 6.5hp, Air-cooled, OHV, Single cylinder, Manual recoil starting, Manual choke

Rated Power: 2800W continuous, 3000W max.

Alternator:Permanent Magnet, brushless, bearingless

Dual range selector

36V:39.5Vdc nominal at generator output connector

48V:52.5Vdc nominal at generator output connector

Output Regulation: 1Vdc

Control Features:Automatic Voltage Regulation Electronic Governor Over current Protection Analog voltmeter with back light

Cable Interface: Anderson type SBE-80 connector

Fuel Tank: 3.4 gallon metal tank with level gauge

Runtime

@ 25% Load: 20 hrs

@ 80% Load: 10 hrs

@ 100% Load: 7.2 hrs

Noise: Approx. 58dBA @ 7m under full load

Frame: Fully Enclosed

Dry Weight: Less than 118lb (53.5kg)

Dimensions (in/mm):22.4H x 18.9W x 25.8D / 569H x 480W x 655D

Agency:CSA C22.2 No. 100-95, 107.1-01, 107.2-M89, 0.4 FCC part 15B Class A

Required Accessories

Output Interface Cable: Available in 10’, 30’ or 50’ lengths

Battery Interface Cable:Choose Ring Lung, Heavy-Duty Alligator Clamp, or Y-adapter*

* Connects the power supply’s battery input directly to the generator

General Specifications

DCX 3000

18

Gen

erat

ors

Portable DC technology generator

Automatic Transfer Switch (ATS) not required

No need to disconnect or reconnect power supply to utility power

Selectable output for 36 or 48VDC operation up to 3000W

Super quiet operation only 58dBA @ 7m/22ft

Alpha expands its generator line to include a portable 3.0kW DC gasoline generator. The compact, lightweight AlphaGen generator is designed specifically for powering cable television, telecommunications, broadband and traffic applications that do not have integrated generators as a primary component of the power system.

The portable generator incorporates several technological advantages including: 36 or 48V selectable dual voltage output based on Permanent Magnet Generator (PMG) technology, 3000W of power, and oversized fuel tank for up to 20hrs of runtime at 25% load or 7.2hrs at 100% load.

Additional features include a convenient front panel with a keyed on/off switch, output connector, output indicators, voltmeter, fuel valve and engine choke.

Alpha AC Catalogue 2008 For Prin18 18 7/30/2008 3:03:02 PM

Page 21: AC Power Solutions - Alpha Technologies

All Models Configuration Options:

Gas Inlet Pressure:0.5 to 2 PSI Inlet Pressure (Contact Alpha Engineering for additional supply resources)

Ign Charger Voltage: 13.5VdcIgn Charger Current: 6A max.

Remote Interface Length:75ft typical. Distance depends upon installation, de-rating and wire gauge.

Agency Compliance:UL1778, UL2200, NFPA 37/54/58 and 70, CSA C22.2 No.107.1, EMC/FCC Part 15 Class A

Fuel System, Controls

& Monitoring:

The controls and fuel system meet applicable sections of NFPA 37, 54 and 58 for automatic unattended operation of remotely located generators. Full System Control and Status Monitoring included.

Sensors: Gas Hazard, Pad Shear, Water Intrusion & Tamper

Safety Shutdowns:

• Low Oil Pressure • Over Temp • Low Fuel Pressure Shutdown (Propane only) • Water Intrusion • Pad Shear • Gas Hazard (Propane or Natural Gas) • Over-Speed • Over-Crank

Optional Feature:Cold Start Kit: Provides additional starting capability at temperatures below -18°C / 0°F.

Optional Accessories

DCX-PG-WK: Portable Generator Wheel Kit (P/N 745-793-20)

DCX-PG-HANDLE: Locking Handle (P/N 745-792-20)

AG-PG-TOOL: Punch Tool Kit For Enclosures (P/N 745-131-20)

AG-PG-UK: Enclosure Upgrade Kit (P/n 745-131-21)

AG-CAB-KIT:Cable Bag With Cable And Key Lanyard (P/N 745-764-21-001)

Output Rating: 3.5kW 5.0kW 7.5kW

DC Output Voltage: 39.0V ±0.5V @ no load 36V config 39.0V ±0.5V @ no load 36V config 52.0V ±0.5V @ no load 48V config52.0V ±0.5V @ no load 48V config 52.0V ±0.5V @ no load 48V config 104.0V ±0.5V @ no load 96V config

DC Output Load Regulation:

0.5V 0.5V 0.5V

Output Current:39.0V @ 90A max. / 52.0V @ 67A max.

39.0V @ 128A max. / 52.0V @ 96A max.

52.0V @ 144A max. / 104V @ 72A max.

Engine: 398cc, Air cooled, Single OHV 10.5hp (using natural gas fuel)RPM: (Variable Speed): 2800 to 3600RPM 2800 to 3600RPM 2800 to 3600RPM

Model: CE-3x2 CE-9x2 CE-3x2 CE-9x2 PN-6x

Height (in/cm): 44/111.2 52/132.1 44/111.2 52/132.1 39/99 (57/144 with optional pedestal)Width (in/cm): 26/66 52/132.1 26/66 52/132.1 39.25/100Depth (in/cm): 24/61 24/61 24/61 24/61 24/61Weight (lb/kg): 383/174 413/187 383/174 413/187 338/174 (370/168 with optional pedestal)

CE-3XL

Generators AlphaGen™ Curbside

CE-3x2 3.5 or 5kW CE-9x2 3.5 or 5kW

CE-3/9G Propane Storage for Generator

(For 3.5 and 5kW)

PN-6x 7.5kW (PN-6x is not compatible with CE-3/9G)

General Specifications

19

Generato

rs

Cost effective extended runtime solution

Quiet operation, small size, and low profile

Designed for stand-alone or collocated applications

Meets UL2200, NFPA 37, 54, 58 & 70 standards

The AlphaGen Curbside generator system incorporates industry leading power technology to provide a stand-along power solution for curbside or remote applications. The Curbside line offers natural gas or propane powered generators, exclusive audible noise baffling, remote status monitoring features, and durable weather resistant enclosures. An optional cold start kit for extreme cold temperature is available as are enclosures for propane storage.

Alpha AC Catalogue 2008 For Prin19 19 7/30/2008 3:03:09 PM

Page 22: AC Power Solutions - Alpha Technologies

Alpha AC Catalogue 2008 For Prin20 20 7/30/2008 3:03:09 PM

Page 23: AC Power Solutions - Alpha Technologies

EnclosuresAlpha’s hardened outdoor enclosures protect power modules, batteries, and components from harsh environmental conditions and unauthorized access. Our enclosures come in a variety of configurations including side mount, ground mount, or pole mount designs. Alpha can also custom design and manufacture enclosures with specific features for unique applications.

Alpha AC Catalogue 2008 For Prin21 21 7/30/2008 3:03:09 PM

Page 24: AC Power Solutions - Alpha Technologies

EnclosuresAlpha Outdoor Enclosure Side Mount 6

Alpha Outdoor Enclosure Side Mount 6

Stand Alone or Side Mount enclosure

Can be installed on any existing ground/pad mount enclosure

Engineered to minimize temperature differential between batteries

Powder coat finish provides excellent corrosion protection

Available in clear coat, sea foam green, pine green and gray

Alpha’s Flextra Special Purpose side mount outdoor rated enclosures provide secure and cost effective method of adding standby capacity to any installed ground/pad mount enclosure. For optimum battery life, Flextra Side Mount enclosures have been engineered to minimize the temperature differential between batteries located within the existing enclosure and batteries in the side mount enclosure.

The Flextra B4 can be mounted on either the right or the left side of the existing enclosure and has room for 4 x 210Ah AlphaCell™ Batteries. The Flextra B4 kit includes the enclosure and door, key set, and all necessary mounting hardware and installation instructions.

Dimensions (in/mm): 19.5W x 48H x 8.75D/495W x 219H x 222W

22

Enc

losu

res

Alpha AC Catalogue 2008 For Prin22 22 7/30/2008 3:03:17 PM

Page 25: AC Power Solutions - Alpha Technologies

EnclosuresAlpha B4

Side Mount enclosure

Can be installed on any existing ground/pad mount enclosure

Engineered to minimize temperature differential between batteries

Powder coat finish provides excellent corrosion protection

Available in clear coat, sea foam green, pine green and gray

Alpha’s B4 side mount outdoor rated enclosure provide secure and cost effective method of adding standby capacity to any installed ground/pad mount enclosure. For optimum battery life, the Side Mount enclosure has been engineered to minimize the temperature differential between batteries located within the existing enclosure and batteries in the side mount enclosure.

The B4 can be mounted on either the right or the left side of the existing enclosure and has room for 4 x 210Ah AlphaCell™ Batteries. The B4 kit includes the enclosure and door, key set, and all necessary mounting hardware and installation instructions.

Dimensions (in/mm): 19.5W x 48H x 8.75D/495W x 219H x 222W

B4

23

Enclo

sures

Alpha AC Catalogue 2008 For Prin23 23 7/30/2008 3:03:18 PM

Page 26: AC Power Solutions - Alpha Technologies

EnclosuresFlextra P Series

Universal Mount enclosure

Aluminum welded construction

Pole mounting brackets included

Removable, lockable doors and easy open lids

Durable, powder coat finish

Slide trays for batteries

The P Series is a single power supply enclosure supporting distributed power architectures and used for pole or wall mount installations. The power supply is positioned in a compartment separate from and above the batteries to maximize convection cooling. Ideal for use in all climates, each enclosure includes a high magnetic circuit breaker, studs to mount optional Maintenance Bypass Switch and a cooling fan.

P6 P8

P4

Flextra Universal Mount Enclosures Extended Standby

P4 P6 P8

Dimensions (in/mm): 30.25W x 24.75H x 16.0D 768W x 629H x 406D

24.25W x 36.75H x 14.0D 615W x 933H x 355D

30.25W x 36.88H x 16.0D 768W x 937H x 406D

Weight (lb/kg) 57/26 68/31 121/55

Battery Capacity 4 6 8

Pole Mount Bracket

Powder Coat Finish

All Aluminum Const.

Removable Door/Lid

Door Prop Rod

Battery Slide Tray 1 2 2

120V 20A or 240V 15A Breaker

Duplex/Quad AC

Local Remote Indicator Light

Enclosure Cooling Fan

Storm Hood

Battery Heater Mat

Internal Service Entrance

Breaker Box

Factory Installed Breaker Box

LA-P+

Standard Features Available Options

Note: Color options available. *P6 is only pole or wall mountable

24

Enc

losu

res

Alpha AC Catalogue 2008 For Prin24 24 7/30/2008 3:03:20 PM

Page 27: AC Power Solutions - Alpha Technologies

EnclosuresFlextra U Series

Ground/Pad Mount enclosure

Aluminum welded construction

Removable, lockable doors and easy open lids

Durable, powder coat finish

Slide trays for batteries

The U Series is a single power supply enclosure supporting distributed power architectures and used for ground or pad mount installations. The power supply is positioned in a compartment separate from and above the batteries to maximize convection cooling. Ideal for use in all climates, each enclosure includes a high magnetic circuit breaker, studs to mount optional Maintenance Bypass Switch and a cooling fan.

U6 U8

U4

Flextra Ground/Pad Mount Enclosures

U4 U6 U8

Dimensions (in/mm): 30.25W x 24.75H x 16.0D 768W x 629H x 406D

24.25W x 36.75H x 14.0D 615W x 933H x 355D

30.25W x 36.88H x 16.0D 768W x 937H x 406D

Weight (lb/kg) 57/26 68/31 121/55

Battery Capacity 4 6 8

Powder Coat Finish

All Aluminum Const.

Removable Door/Lid

Battery Slide Tray 1 2 2

120V 20A or 240V 15A Breaker

Duplex/Quad AC Recept.

Local Remote Indicator Light

Enclosure Cooling Fan

Battery Heater Mat

LA-P+

AC Output Indicator Light

Pedestal Extension

External Meter Base

Internal Breaker Box

External Breaker Box

Security Bar Kit

Standard Features Available Options

25

Enclo

sures

Alpha AC Catalogue 2008 For Prin25 25 7/30/2008 3:03:24 PM

Page 28: AC Power Solutions - Alpha Technologies

EnclosuresFlextra Z Series

Extreme conditions enclosure

Meets Telcordia Seismic Zone-4 standard

NEMA 3R outdoor rated enclosure

Simple, flexible options for pole, wall, ground or pedestal installations

Wide temperature range -40˚C to +50˚C

Alpha’s Flextra Extreme enclosures provide protection to outdoor UPS systems used in extreme climates. Four and eight battery configurations are available and an optional generator can be used for extended runtimes. Flexible power, runtime and voltage configurations make the Flextra Extreme the best choice for powering outdoor applications around the world. An optional maintenance bypass feature allows for easy and efficient battery and UPS replacement.

Standard FeaturesInput/Output Surge ProtectionIntelligent buck/boost operation for greater protectionHot swappable UPS and batteriesNoise suppression, FCC Class BMultiple mounting configurations Rugged, outdoor weather resistant constructionLockable enclosureNRTL/CSA/CE approved

8 Battery System also includes: Telcordia Zone 4 approved with Battery Retention Bar Telcordia salt fog tested, 14 day operational Telcordia approved Door Restraint

Enclosure SpecificationsDimensions 4 Battery 8 Battery

Width (in/mm): 24/610 31/788Height (in/mm): 36/914 37/956Depth (in/mm): 14/56 16/407Weight (lb/kg)**: 350/158 812/368Finish: Powder coat white over aluminum

* Backup time depends on load, battery, and operating temperature. Optional DC Generator provides up to 100hrs backup.** Weight dependent upon internal battery choice.

Note: The W8 enclosure is resistant to the harshest weather conditions.

26

Enc

losu

res

Flextra Z

Alpha AC Catalogue 2008 For Prin26 26 7/30/2008 3:03:26 PM

Page 29: AC Power Solutions - Alpha Technologies

EnclosuresFlextra Node

Ground/Pad Mount node

Rugged outdoor enclosure available in 3.0 and 5.0kVA configurations

Incorporates Alpha CFR power module, Alpha bypass switch and batteries

Provides complete input to output isolation with superior surge and lightning protection

Additional battery and generators cabinets available

Alpha’s Flextra Node Ground/Pad Mount Enclosures provide superior backup power protection for outdoor mission critical applications. Designed to meet or exceed the safety standards established by UL, CSA, CE and VDE, the enclosures set the standard for effective outdoor powering. The input power factor correction brings low power-factor loads to near unity, reducing electric utility costs. Fully compatible with AlphaGenTM Curbside, Alpha’s outdoor line of natural gas or propane generators, to provide longer runtimes.

Enclosure Configurations

N3

1 power module 1 bypass switch 1 battery string

Dual N3

1 power module 1 bypass switch 4 battery strings

N3

Options:

Battery Heater Mat (BHM)

Manual Transfer Switch (MTS)

Meter Head

Standby Generator

Propane Storage Cabinet

Remote Generator Interface Kit

27

Enclo

sures

Alpha AC Catalogue 2008 For Prin27 27 7/30/2008 3:03:29 PM

Page 30: AC Power Solutions - Alpha Technologies

Integrated Telecom grade environmentally controlled UPS system

Front and rear accessible 19’” or 23” equipment racks

46 RMU capacity

High capacity AC or DC air conditioner options

Field replaceable fans

NEMA 3R and 4X configurations available

Agency certified

As advanced voice, video and data fiber based services are deployed deeper into the broadband network, the need for reliable, attractive, modular transition nodes increases. The Radium MiniBay supports a wide range of applications including bulk power to CATV hub and secondary hub requirements. Also ideal for remote optical transition applications including optical amplification, downstream DWDM demultiplexing, narrowcast combining and return path aggregation providing services to remote communities.

The MiniBay reduces operational costs by locating the electronics where needed and avoids the recurring costs of maintaining a real-estate intensive building. Alpha’s field power services group provides turnkey installations, turn-up and test services.

Environmental Rating:

NEMA 3R when configured with door mounted fans and filter system. NEMA 4X when configured with heat exchanger or air conditioning system.

Seismic Rating:Consult factory. A seismic rating is based on a set system configuration with defined mounting locations and equipment types.

Design Standards:Following NEC & Telcordia Technologies (Bellcore) GR-487, GR-63 and GR-108 guidelines.

Compliance:Third party approval from National Recognized Testing laboratory (NRTL).

Material: High strength corrosion resistant aluminumFinish: Almond color powdercoat finish

Weight & Dimensions

Weight (lb/kg) Dimensions (in/cm):

Equipment Enclosure:

195/88.532D x 44H x 30W / 81.3D x 106.7H x 76.2W

Battery Storage Module:

130/5932D x 14H x 30W / 81.3D x 35.6H x 76.2W

Riser Module: 102/46.332D x 14H x 30W / 81.3D x 35.6H x 76.2W

Side Chamber SC1:

100/45.412D x 72H x 32W / 30.5D x 81.3H x 131.1W

Side Chamber SC2:

89/40.412D x 72H x 32W / 30.5D x 81.3H x 131.1W

Fans and Filters

The most basic thermal management system supporting the MiniBay utilizes conformal-coated, variable speed and alarm monitored fans with electrostatic air filters providing up to 500W thermal dissipation. This configuration has a NEMA 3R rating.

Variable speed controlled DC fans continue to operate during a utility outage

Conformal-coated fans

Electrostatic and washable air filters

Field replaceable fans

Heat Exchanger An airtight rear door and a heat exchanger equipped hinged front door providing over 500W thermal dissipation. With a 500W load, the internal ambient temperature will not exceed 15 to 27°F above external ambient. With a 250W load, the internal ambient temperature will not exceed 7°C or 12.6°F above external ambient. This configuration has a NEMA 4X rating.

Heat exchanger heat pipe technology provides efficient thermal transfer

Minimizes internal temperature rise above external ambient

Variable speed controlled DC fans continue to operate during a utility outage

Field replaceable fansDC Air Conditioner

For applications requiring the most reliable below ambient cooling and dehumidifying system for supporting seamless performance through extended utility outages. Cooling capacity 878W dissipated at 43°C outdoor ambient allowing a Maximum* internal ambient of 40°C / 104°F.

Variable speed brushless motor 24/48Vdc compressor system assures optimum efficiency over the full range of thermal loading and ambient temperatures

3,000BTU @ 43°C/110°F rating

Redundant conformal-coated fans have >50,000hrs of life and low voltage disconnect circuitry

AC Air Conditioner

Ideal for applications requiring cooling and dehumidifying with little or no standby runtime performance. Cooling capacity 1464W dissipated at 43°C outdoor ambient allowing a Maximum* internal ambient of 40°C / 104°F.

5,000BTU @ 43°C/110°F rating

Washable electrostatic filters

240Vac* Reducing the internal dissipated heat load reduces internal ambient.

EnclosuresRadium MiniBay

Specifications

MiniBay with Fiber Management

28

Enc

losu

res

Radium MiniBay

Alpha AC Catalogue 2008 For Prin28 28 7/30/2008 3:03:31 PM

Page 31: AC Power Solutions - Alpha Technologies

Indoor SolutionsAlpha Technologies offers three lines of single phase indoor Uninterruptible Power Supplies (UPS), providing customers with a range of standard and optional features to meet their specific UPS needs. This includes entry level line interactive models, full featured double conversion products and controlled ferroresonant designs for the most robust applications. All lines are offered in tower and rack mount configurations. An additional indoor UPS family, part of our controlled ferroresonant line is designed specifically for medical and healthcare applications.

We also offer three phase indoor UPS solutions.

Alpha AC Catalogue 2008 For Prin29 29 7/30/2008 3:03:31 PM

Page 32: AC Power Solutions - Alpha Technologies

Diagrams below will help you understand the different topologies used in our indoor UPS products.

Line InteractiveIn normal operation, when AC line voltage is present, power is filtered for voltage spikes and output voltage is regulated. Some electricity is used to keep the batteries fully charged. When the AC line voltage is lost or falls outside the input range, AC power is supplied from the batteries through the inverter.

Advantages of line-interactive topology:

• Automatic Voltage Regulation (AVR)

• Lower electricity consumption (less costly to operate) – More efficient because less power conversion is performed when acceptable AC input is present.

• Higher reliability – Lower component count and lower operating temperatures.

Double conversionIn normal operation, all incoming AC power is rectified to DC power, supplying the DC bus. The output inverter then inverts the DC power to AC power to support the critical loads. When the AC input is lost or goes out of range, the UPS draws power from its battery so that AC output is not affected. Because the AC input with it’s spikes, voltage blips and anomalies is first converted to DC, there is less need for using the battery when these AC input variances occur. Less battery usage preserves battery capacity for extended outages, and preserves battery service life.

30

Ind

oo

r S

olu

tio

ns

Indoor SolutionsUPS Topology

Alpha AC Catalogue 2008 For Prin30 30 7/30/2008 3:03:31 PM

Page 33: AC Power Solutions - Alpha Technologies

Double conversion continuedReducing battery service life and the cost associated with it can offset the advantage of the lower initial purchase and operating costs of a line-interactive UPS thus making the overall cost similar. Situations that might call for a double-conversion on-line UPS are those that require power factor correction (PFC), small physical size, or some types of medical equipment or instrumentation.

Advantages of double-conversion topology:

• Operates less often from battery when the input voltage is highly distorted or wildly fluctuating

• Power factor correction (PFC) provided, regardless of load type

• More compact and lightweight, especially at higher power levels

Controlled Ferroresonant

The Ferro Resonant Topology is similar to a Line Interactive topology with the addition of a ferro resonant transformer to offer constant output voltage regardless of the state of the input voltage. In both normal mode and battery mode, all output is first filtered through a ferro resonant transformer isolating the output. This also provides for a seamless transfer to UPS power and offers galvanic isolation to isolate charge carrying particles from functional section of the system. Auto Voltage Regulation (AVR) is managed through Buck & Boost Mode.

Advantages of controlled ferro resonant topology:

• Best spike & surge protection with output isolation

• Zero transfer time

• Good MTBF as inverter is used in Standby mode

• Batteries are not used in a brown out condition

31

Indo

or S

olutio

ns

Indoor SolutionsUPS Topology

Alpha AC Catalogue 2008 For Prin31 31 7/30/2008 3:03:31 PM

Page 34: AC Power Solutions - Alpha Technologies

1000 VA to 3000 VA models

Line interactive, pure sine wave technology

High speed microprocessor controlled

Advanced Automatic Voltage Regulation

Smart battery management

Hot swappable batteries

XL models for longer run times

The ALI Elite Uninterruptible Power Supply (UPS), in tower or rack mount configurations, is a microprocessor-controlled, pure sine wave, line interactive UPS featuring advanced Auto Voltage Regulation (AVR) with boost and buck. The AVR provides a wider input voltage operating range that results in fewer transfers to battery power thus extending battery life. All Alpha ALI Elite models include graphical interface, user-friendly software capable of safe unattended PC shutdown. Additional features include: smart battery management programming to optimally charge a battery based on it’s specific charging sequence, automatic frequency selection, smart communication, a robust inverter that works with a variety of external battery packs for extended run time applications, a customizable graphical user interface displaying UPS status, TCP/IP based power management and an optional Ethernet/SNMP interface. The ALI Elite is designrd to work in applications supporting servers, telecom equipment, voice and data networks or where there is a need for indoor, line interactive backup power.

Line InteractiveALI Elite

ALI Elite tower configuration

32

Ind

oo

r S

olu

tio

ns

ALI Elite rack configuration

Alpha AC Catalogue 2008 For Prin32 32 7/30/2008 3:03:34 PM

Page 35: AC Power Solutions - Alpha Technologies

General Specifications

AC Input

Voltage: 120V nominal

Voltage Range: ±25%

Frequency: 50/60Hz ±5% (auto sensing)

AC Output

Voltage (Selectable): 100/110/120V

Frequency: 50 or 60Hz ±0.5% when on battery

Regulation: Increase of 15% if input voltage is -9 to -25% from nominal

Decrease of 15% if input is 9 to 25% from nominal

Spike Protection: 320Joules, 2ms

EMI/RFI Filtering: 10dB at 0.15MHz, 50dB at 30Mhz

Overload Capacity: 110% for 20sec, 125% for 5sec

Transfer Time: 2 to 4ms, including detection time

Waveform: Sine wave

Nominal Specifications

Model

Tower ALI Elite 1000T ALI Elite 1500T ALI Elite 2000T ALI Elite 3000T

Part Number: 017-747-110 017-747-115 017-747-120 017-747-130

Rack Mount: ALI Elite 1000RM ALI Elite 1500RM ALI Elite 2000RM ALI Elite 3000RM

Part Number: 017-747-61 017-747-65 017-747-62 017-747-63

Capacity (VA/W): 1000VA/600W 1500VA/900W 2000VA/1200W 3000VA/1800W

Input Plug: NEMA 5-15P NEMA 5-15P NEMA L5-20P NEMA L5-30P

Input Protection Fuse Fuse Breaker 20A Breaker 30A

Audible Noise: <40dBA @ 1m <40dBA @ 1m <40dBA @ 1m <40dBA @ 1m

Receptacles

Tower: 4 NEMA 5-15R 6 NEMA 5-15R 6 NEMA 5-20R 4 NEMA 5-15R, 1 NEMA 5-30R

Rack Mount: 4 NEMA 5-15R 4 NEMA 5-15R 4 NEMA 5-20R 4 NEMA 5-15R, 1 NEMA 5-30R

Battery

DC Voltage: 24V 36V 48V 48V

Battery Runtimes* Tower and Rack

Runtime @ 100% Load: 3min 3min 3min 7min

Runtime @ 50% Load: 13min 13min 13min 21min

Mechanical

Tower

(in): 5.5W x 17.2D x 8.3H 6.7W x 17.7D x 8.9H 6.7W x 17.7D x 8.9H 6.7W x 22.8D x 16.9H

(mm) 140W x 436D x 210H 170W x 450D x 226H 170W x 450D x 226H 170W x 580D x 430H

Weight (lb/kg): 33.0/15 55.1/25 66.1/30 80/36

Approx. Ship Weight (lb/kg): 35.0/16 59.5/27 70.5/32 83.7/38

Rack Mount

(in): 16.9W x 15.0D x 5.1H 16.9W x 15.0D x 5.1H 16.9W x 15.0D x 5.1 16.9W x 22.1D x 7.0H

(mm): 429.3W x 381D x 130H 429.3W x 381D x 130H 429.3W x 381D x 130 429.3W x 560D x 178H

Weight (lb/kg): 44/20 57.3/26 61.7/28 75/34

Approx. Ship Weight (lb/kg): 48/22 63.4/28.8 68.5/31.1 79.3/36

*rounded to the nearest minute

Battery

Recharge Time: <5hrs to 90% recharge of internal batteries only Type: Valve Regulated Lead Acid (VRLA) No extended battery packs (available on XL models only) Interface

Front Panel Indicators: LED display–load level and battery capacity Audible Alarm: On battery–Slow beep, low battery–rapid beep, overload–continuous Communications: RS-232 with optional external SNMP

Environment

Operating Temperature: 0 to 40°C Storage Temperature: -20 to 48°C Altitude: 3500m above sea level Humidity: 0 to 95% non-condensing Safety: UL, CSA

Warranty

UPS Module and Battery:Competitive warranties included. Contact your sales representative for further details.

Line InteractiveALI Elite

33

Indo

or S

olutio

ns

Alpha AC Catalogue 2008 For Prin33 33 7/30/2008 3:03:34 PM

Page 36: AC Power Solutions - Alpha Technologies

General Specifications

AC Input

Voltage: 120V nominalVoltage Range: ±25%Frequency: 50/60 Hz ±5% (auto sensing)

AC Output

Voltage (Selectable): 100/110/120VFrequency: 50 or 60Hz ±0.5% when on batteryRegulation: ±10% nominalSpike Protection: 320 Joules, 2msEMI/RFI Filtering: 10dB at 0.15MHz, 50dB at 30mHzOverload Capacity: 125% for 10min, 150% for 10secTransfer Time: 2 to 4ms, including detection timeWaveform: Sine wave

Battery

Recharge Time: <5hrs to 90% recharge of internal batteries onlyType: Valve Regulated Lead Acid (VRLA)

Extended battery connectors included Extended battery packs available

InterfaceFront Panel Indicators: LED display – load level and battery

capacity.Audible Alarm: On battery – Slow beep, low battery – rapid

beep, overload – continuousCommunications: RS-232 with optional ethernet/SNMP.

EnvironmentOperating Temperature:

0 to 40°C

Storage Temperature: -20 to 48°CAltitude: 3500m above sea levelHumidity: 0 to 95% non-condensingSafety: UL, CSA

Warranty UPS Module and Battery:

Competitive warranties included. Contact your sales representative for further details.

Line InteractiveALI Elite XL

All the same features and benefits of the ALI Elite with the capability of longer run times.

Nominal Specifications

Model

Tower: ALI Elite 1000TXL ALI Elite 1500TXL ALI Elite 2000TXL ALI Elite 3000TXL

Part Number: 017-747-210 017-747-215 017-747-220 017-747-230

Rack Mount: ALI Elite 1000RMXL ALI Elite 1500RMXL ALI Elite 2000RMXL ALI Elite 3000RMXL

Part Number: 017-747-81 017-747-85 017-747-82 017-747-83

Capacity VA/W: 1000VA/600W 1500VA/900W 2000VA/1200W 3000VA/1800W

Input Plug: NEMA 5-15P NEMA 5-15P NEMA L5-20P NEMA L5-30P

Input Protection: Fuse Fuse Breaker Breaker

Audible Noise: <40dBA @ 1m <45dBA @ 1m <45dBA @ 1m <45dBA @ 1m

Receptacles

Tower: 6 NEMA 5-15R 6 NEMA 5-15R 6 NEMA 5-20R 4 NEMA 5-15R, 1 NEMA 5-30R

Rack Mount: 6 NEMA 5-15R 6 NEMA 5-15R 6 NEMA 5-20R 4 NEMA 5-15R, 1 NEMA 5-30R

Battery

DC Voltage: 24V 36V 48V 48V

Mechanical

Tower

(in): 6.7W x 17.7D x 8.9H 6.7W x 18.9D x 16.9H 6.7W x 18.9 x 16.9H 6.7W x 21.6D x 16.9H

(mm): 170.2W x 449.6D x 226.1H 170.2W x 480.1D x 429.3H 170.2W x 480.1D x 429.3H 170.2W x 548.6D x 429.3H

Weight (lb/kg): 66/30 94.8/46 110.2/50 125.7/57

Approx. Ship Weight (lb/kg): 70.5/32 108/49 116/53 132/60

Rack Mount

(in): 16.9W x 22.0D x 5.1H 16.9W x 22.0D x 5.1H 16.9W x 22.0D x 5.1H 16.9W x 22.0D x 7.0H

(mm): 429.3W x 558.2D x 129.5H 429.3W x 558.2D x 129.5H 429.3W x 558.2D x 129.5H 429.3W x 558.2D x 177.8H

Weight (lb/kg): 41.9/19 52.9/24 59.5/27 103.6/47

Approx. Ship Weight (lb/kg): 46.2/21 57.3/26 63.7/29 108/49

34

Ind

oo

r S

olu

tio

ns

Alpha AC Catalogue 2008 For Prin34 34 7/30/2008 3:03:35 PM

Page 37: AC Power Solutions - Alpha Technologies

Line InteractiveAli Elite XL

Specifications

Battery Pack: ALIBP700/1000T ALIBP1500T ALIBP2/3000T

Alpha Part Number: 033-747-07 033-747-10 033-747-20

Dimensions (in): 6.7W x 18.9D x 8.5H 6.7W x 18.9D x 8.5H 6.7W x 18.9D x 8.5H

(mm): 170.2W x 480.1D x 215.9H 170.2W x 480.1D x 215.9H 170.2W x 480.1D x 215.9H

Weight (lb/kg): 69.4/31.5 56.2/25.5 69.4/31.5

Approx. Ship Weight (lb/kg): 73.9/33.5 60.6/27.5 73.9/33.5

Specifications

Battery Pack: ALIBP700/1000RM ALIBP1500RM ALIBP2/3000RM

Alpha Part Number: 033-747-08 033-747-12 033-747-22

Dimensions (in): 16.9W x 15.7D x 5.1H 16.9W x 15.7D x 5.1H 16.9W x 15.7D x 5.1H

(mm): 429.3W x 398.8D x 129.5H 429.3W x 398.8D x 129.5H 429.3W x 398.8D x 129.5H

Weight (lb/kg): 64.5/29.65 64.5/29.65 64.5/29.65

Approx. Ship Weight (lb/kg): 72.6/32.95 72.6/32.95 72.6/32.95

ALI Elite Extended Run Time Battery PackThe ALI Elite also has optional battery packs to further extend your run time during a power failure. Review the table below to find a solution to best fit your needs.

Battery Runtimes*

ALI Elite 1000 TXL/RMXL ALI Elite 1500 TXL/RMXL ALI Elite 2000 TXL/RMXL ALI Elite 2000 TXL/RMXL

Tower at 50% Load

UPS: 36 min 53 min 53 min 29 min

1 EBP: 202 min 123 min 123 min 78 min

2 EBP: 369 min 202 min 202 min 123 min

Tower at 100% Load

UPS: 12 min 19 min 19 min 9 min

1 EBP: 92 min 53 min 53 min 29 min

2 EBP: 163 min 92 min 92 min 53 min

Rack at 50% Load

UPS: 36 min 16 min 16 min 15 min

1 EBP: 212 min 126 min 102 min 66 min

2 EBP: 416 min 248 min 189 min 120 min

Rack at 100% Load

UPS: 13 min 6 min 6 min 5 min

1 EBP: 97 min 54 min 40 min 26 min

2 EBP: 179 min 111 min 86 min 52 min

*rounded to the nearest minute

ALI Elite XL

35

Indo

or S

olutio

ns

Alpha AC Catalogue 2008 For Prin35 35 7/30/2008 3:03:36 PM

Page 38: AC Power Solutions - Alpha Technologies

General Specifications

AC Input

Voltage Range: 80 to 144V at full load, 60 to 144V at 40% load (120V Units)

Frequency: 50/60Hz ±5% (auto sensing)

AC Output

Voltage (selectable): 100/110/115/120/127V (PIN 1000 to 3K)

Frequency: 50 or 60Hz ±0.5% when on battery

Receptacle Segments: 2 – software controllable

Voltage THD, Linear Load: <3%

Crest Factor: 3:1

Overload Capacity: 125% for 1min, 150% for 10sec

Transfer Time: 0ms

Extended Battery

Recharge Time:

Type:

<4hrs to 90% recharge on internal battery

Valve Regulated Lead Acid (VRLA)

Extended battery connection included.

Extended battery packs available

Interface

Front Panel Indicators: LCD display/input/output volts, frequency, load level, battery capacity, online/eco mode

Audible Alarm: On Battery – 5 second interval, UPS fault – continuous

Communications: RS-232, communications expansion slot, USB standard (Options: AS400 Card,

UPS LAN Card)

Environment

Operating Temperature: 0 to 40°C

Storage Temperature: -20 to 50°C

Altitude: 3500m above sea level

Humidity: 0 to 95%, non-condensing

Audible Noise: <40dBA at 1m

Safety: UL, CSA

EMC (EMS/EMI): IEC 61000-4. FCC Part 15, CISPR22

High Efficiency Mode: >95% efficient when selected

Double ConversionPinnacle Plus

1000VA to 3000VA models to meet your power needs

True online, double conversion operation (zero transfer time)

Internal Static Bypass: no extra parts to buy for complete operation

Power factor correction: minimize energy consumption

Optional Ethernet SNMP communications interface: monitor from anywhere

Hot swappable batteries: no downtime

The Pinnacle Plus Uninterruptible Power Supply (UPS), in tower or rack mount configurations provides safe, clean, reliable power protection to data and voice networking equipment, telecommunication systems, servers and other mission-critical applications. The Pinnacle Plus offers an advanced fully microprocessor controlled technology that quickly reacts to varying output conditions and continually offers pure sine wave power to critical equipment with zero transfer time. The advanced, scalable battery charger shortens the battery recharge time while prolonging the life of the battery. With true RS-232 & USB two-way communication that sends signals to both the network and computer, the Pinnacle Plus can be monitored, shut down, or programmed with an on/off date, using its own software. Simplified control circuits make it light, easy to control, and reliable due to the reduction of internal components.

Pinnacle Plustower configuration

Pinnacle Plus rack configuration

36

Ind

oo

r S

olu

tio

ns

Alpha AC Catalogue 2008 For Prin36 36 7/30/2008 3:03:37 PM

Page 39: AC Power Solutions - Alpha Technologies

37

Nominal Specifications

ModelTower: PINNACLE Plus 1000T PINNACLE Plus 1500T PINNACLE Plus 2000T PINNACLE Plus 3000TPart Number: 017-751-10 017-751-15 017-751-20 017-751-30Rack Mount 2U: PINNACLE Plus 1000RM PINNACLE Plus 1500RM PINNACLE Plus 2000RM PINNACLE Plus 3000RMPart Number: 017-751-122 017-751-17 017-751-22 071-751-32Capacity (VA/W): 1000VA/700W 1500VA/1050W 2000VA/1400W 3000VA/2100WInput Plug: NEMA 5-15P NEMA 5-15P NEMA L5-20P NEMA L5-30PInput Protection: Circuit Breaker 12A Circuit Breaker 15A Circuit Breaker 20A Circuit Breaker 30AReceptaclesTower: 6 NEMA 5-15R 6 NEMA 5-15R 10 NEMA 5-20R, 1NEMA L5-20R 10 NEMA 5-15R, 1 NEMA L5-30RRack Mount: 6 NEMA 5-15R 6 NEMA 5-15R 2 NEMA 5-20R, 1 NEMA L5-20R 2 NEMA 5-15R, 1 NEMA L5-30RBatteryDC Voltage: 36V 36V 72V 72VMechanicalTowerDimensions (in): 6W x 16.5D x 9.4H 6W x 16.5D x 9.4H 8.9W x 16.7D x 14.2H 8.9W x 16.7D x 14.2H (mm): 152.4W x 419.1D x 238.8H 152.4W x 419.1D x 238.8H 226.1W x 424.2D x 360.7H 226.1W x 424.2D x 360.7HNet Weight (lb/kg): 35.3/17.1 37.5/17.7 68.3/33.8 72.8/35.6Approx. Ship Weight. (lb/kg):

40/18.9 41.8/19.5 73.9/36 78.1/38

Rack MountDimensions (in): 16.9W x 16.7D x 3.3H 16.9W x 16.7D x 3.3H 16.9W x 25D x 3.3H 16.9W x 25D x 3.3H (mm): 429.3W x 424.2D x 83.8H 429.3W x 424.2D x 83.8H 429.3W x 609.6D x 83.8H 429.3W x 609.6D x 83.8HNet Weight (lb/kg): 37.5/18.7 39.7/19.1 70.6/33.6 72.8/34.3Approx. Ship Weight (lb/kg):

42.5/21.6 44.2/21.7 74.4/36.7 78.5/38.3

Battery Runtimes*Tower at 50% LoadUPS: 18min 14min 18min 14min1 EBP: 148min 92min 80min 50min2 EBP: 310min 205min 150min 93minTower at 100% LoadUPS: 6min 5min 6min 5min1 EBP: 69min 38min 33min 19min2 EBP: 150min 80min 69min 40minRack at 50% LoadUPS: 18min 14min 18min 14min1 EBP: 148min 92min 80min 50min2 EBP: 310min 205min 150min 93minRack at 100% LoadUPS: 6min 5min 6min 5min1 EBP: 69min 38min 33min 19min2 EBP: 150min 80min 69min 40min

*rounded to the nearest minute

Double ConversionPinnacle Plus

Indo

or S

olutio

ns

Alpha AC Catalogue 2008 For Prin37 37 7/30/2008 3:03:38 PM

Page 40: AC Power Solutions - Alpha Technologies

38 General Specifications

AC Input

Voltage Range: 180 to 276 VAC

Frequency: 50/60Hz ±5% (auto sensing)

AC Output

Voltage (selectable): 200/208/220/230/240

Frequency: 50 or 60Hz ±0.5% when on battery

Receptacle Segments: 2 – software controllable

Voltage THD, Linear Load: <3%

Crest Factor: 3:1

Overload Capacity: 125% for 1min, 150% for 10sec

Transfer Time: 0ms

Extended Battery

Recharge Time:

Type:

<4hrs to 90% recharge on internal battery

Valve Regulated Lead Acid (VRLA)

Extended battery connection included.

Extended battery packs available

Interface

Front Panel Indicators: LCD display/input/output volts, frequency, load level, battery capacity, online/eco mode

Audible Alarm: On Battery – 5 second interval, UPS fault – continuous

Communications: RS-232, communications expansion slot, USB standard (Options: AS400 Card,

UPS LAN Card)

Environment

Operating Temperature: 0 to 40°C

Storage Temperature: -20 to 50°C

Altitude: 3500m above sea level

Humidity: 0 to 95%, non-condensing

Audible Noise: <40dBA at 1m

Safety: UL, CSA

EMC (EMS/EMI): IEC 61000-4. FCC Part 15, CISPR22

High Efficiency Mode: >95% efficient when selected

Double ConversionPinnacle Plus High Power

6000, 10,000 and 12,000W/VA models to meet every power need

True online, double conversion operation (zero transfer time)

Internal Static Bypass: no extra parts to buy for complete operation

Power factor correction: minimize energy consumption

Optional Ethernet SNMP communications interface: monitor from anywhere

Hot swappable batteries: no downtime

The Pinnacle Plus Uninterruptible Power Supply (UPS), in tower or rack mount configurations provides safe, clean, reliable power protection to data and voice networking equipment, telecommunication systems, servers and other mission-critical applications. The Pinnacle Plus offers an advanced fully microprocessor controlled technology that quickly reacts to varying output conditions and continually offers pure sine wave power to critical equipment with zero transfer time. The advanced, scalable battery charger shortens the battery recharge time while prolonging the life of the battery. With true RS-232 two-way communication that sends signals to both the network and computer, the Pinnacle Plus can be monitored, shut down, or programmed with an on/off date, using its own software. Simplified control circuits make it light, easy to control, and reliable due to the reduction of internal components.

Pinnacle Plus High Powertower configuration(available Q4, 2008)

Ind

oo

r S

olu

tio

ns

Alpha AC Catalogue 2008 For Prin38 38 7/30/2008 3:03:38 PM

Page 41: AC Power Solutions - Alpha Technologies

Extended Run Time Battery Pack Specifications for Pinnacle Plus Tower

Battery Pack: PINBP1000/1500T PINBP1000/1500T PINBP2/3000T PINBP2/3000T PINBP6000T PINBP10000/12000T

Alpha P.N.: 033-751-10 033-751-10 033-751-20 033-751-20 033-751-400 017-751-311

Dimensions (in): 8.9W x 16.7D x 14.2H 8.9W x 16.7D x 14.2H 8.9W x 16.7D x 14.2H 8.9W x 16.7D x 14.2H 10.2W x 27.4D x 22.4H13.5W x 24.1D x 25.9H/ 13.5W x 24.5D x 25.96H

(mm): 226W x 424D x 360H 226W x 424D x 360H 226W x 424D x 360H 226W x 424D x 360H 258W x 697D x 570H344W x 613D x 657H/ 344W x 623D x 657H

Weight (lb/kg): 92.6/42 92.6/42 92.6/42 92.6/42 Contact Alpha Contact Alpha

Approx. Ship Weight (lb/kg):

98.1/44.5 98.1/44.5 98.1/44.5 98.1/44.5 Contact Alpha Contact Alpha

Extended Run Time Battery Pack Specifications for Pinnacle Plus Rack Mount

Battery Pack: PINBP1000/1500RM PINBP1000/1500RM PINBP2/3000RM PINBP2/3000RM

Alpha Part Number: 033-751-12 033-751-12 033-751-22 033-751-22

Dimensions (in): 16.9 x 25 x 3.3H 16.9 x 25 x 3.3H 16.9 x 25 x 3.3H 16.9 x 25 x 3.3H

(mm): 429.3W x 635D x 83.8H 429.3W x 635D x 83.8H 429.3W x 635D x 83.8H 429.3W x 635D x 83.8H

Weight (lb/kg): 95.9/43.5 95.9/43.5 95.9/43.5 95.9/43.5

Approx. Ship Weight (lb/kg): 101.4/46 101.4/46 101.4/46 101.4/46

Double ConversionPinnacle Plus High Power

ModelTower PINNACLE Plus 6000T PINNACLE Plus 10000T PINNACLE Plus 12000TPart Number: 017-751-400 017-751-300 017-751-580Capacity (VA/W): 6000VA/4200W 10000VA/7000W 12000VA/8400W Input Plug: Terminal Block Terminal Block Terminal BlockInput Protection: Circuit Breaker Circuit Breaker Circuit BreakerReceptaclesTower: Terminal Block Terminal Block Terminal BlockBatteryDC Voltage: 240V 240V 240V MechanicalTowerDimensions (in): 10.1W x 23.2D x 22.4H 10.1W x 27.2D x 28.2H 13.5W x 27.2D x 34.6H(mm): 257.8W x 699.8D x 699.4H 324.4W x 739.2D x 729.4 H 342W x 690D x 903HNet Weight (lb/kg): 209 / 95 332 / 151 435 / 198Approx. Ship Weight (lb/kg): Contact Alpha Contact Alpha Contact AlphaBattery RuntimesTower at 50% LoadUPS: 19min 37min 53minTower at 100% LoadUPS: 6min 13min 19min

39

Indo

or S

olutio

ns

Alpha AC Catalogue 2008 For Prin39 39 7/30/2008 3:03:38 PM

Page 42: AC Power Solutions - Alpha Technologies

One of the highest MTBF in the UPS industry - lowers total cost of ownership

Complete input to output isolation provides complete surge and lightning protection for sensitive loads

The CFR’s microprocessor design provides efficiency ratings up to 92%, saving energy

Features a RS-232 communication port and is SNMP and modem compatible for monitoring from any Internet connection location

Alpha CFR Uninterruptible Power Supplies (UPS) meet or exceed the safety standards established by UL, CSA, CE and VDE. The Alpha CFR UPS is one of the most reliable UPS systems available, with a wide variety of plug and receptacle options to meet your unique connection requirements. Input current waveform correction eliminates overheating effects of non-linear load current harmonics. Input power-factor correction brings low power-factor loads to near unity, reducing electric utility costs. The CFR Series sets the standard for the effective powering of non-linear or actively regulated loads, while providing superior surge and noise rejection. Power ratings of 1000VA to 15kVA available.

Controlled Ferroresonant CFR®

CFR Series

40

Ind

oo

r S

olu

tio

ns

Alpha AC Catalogue 2008 For Prin40 40 7/30/2008 3:03:39 PM

Page 43: AC Power Solutions - Alpha Technologies

Common Specifications

Operating Input Voltage Range: -23 to 10%

Input Frequency Operating Range: ±1.4Hz

Input Power Factor 0.95 to 0.99

Input Current THD: 5% Typical

Output Waveform: Pure sine wave

Output Voltage Regulation: ±1%

Typical Output Voltage THD: <5% 600VA to 5kVA

Inverter Frequency Stability: ±0.1%

Spike Attenuation: 2000 to 1

Lightning & Surge Protection: ANSI C62.41-1980

(IEEE 587)

Operating Temperature: 0 to 40°C (32 to 104°F)

Audible Noise: 40dBA Typical @ 1m

Communications

All Alpha CFR products feature RS-232 communication ports and are SNMP and modem compatible.

The following is a list of optional communication, monitoring and control products:

SNMP Agent: Furnishes real time UPS/power status to Network Power Management Software.

Intelligent Interface Device (I2D): Front panel LCD readout provides vital UPS system information at the touch of a key.

EBP Options

Alpha’s plug-in External Battery Packs provide extended backup for all CFR models. All battery packs are shipped fully assembled and include interconnecting cables. Longer runtimes are obtained by cascading additional battery cabinets.

Available for:

CFR 1000

Battery Pack 24V EBP 24A EPB 24C EBP 24E Width (in/mm): 8.5/216 8.5/216 8.5/216 Height (in/mm): 4.5/114 10.5/267 21.5/546

Depth (in/mm): 15.5/39424.0/610

28.0/711

Weight (lb/kg): 39/18 127/58 312/141 Capacity (Ah): 17 66 176

Available for:

CFR 1500, 2500, 3000

Battery Pack 48V EBP 48A EBP 48E Width (in/mm): 8.5/216 8.5/216 Height (in/mm): 10.5/267 21.5/546 Depth (in/mm): 10.5/267 21.5/546 Weight (lb/kg): 127/58 312/141 Capacity (Ah): 33 88

Application Specific Models

CFR-NT: Specifically designed to be compatible with Northern Telecom Meridian telephone switches and other telephony products

CFR-E: 50Hz configuration

Plug and Receptacle Diagram5-15P 5-15R CS63615-30P 5-30R Terminal

Block5-20P 5-20R British5-50P L5-15R SchukoL5-15P L5-20R Australian

L5-30P L5-30R L6-30P L6-20R L6-30R

Available for:

CFR 5000

Battery Pack 48V EBP 48M EBP 1275-48B Width (in/mm): 8.5/216 22.0/660 Height (in/mm): 21.5/564 30.3/770 Depth (in/mm): 28.0/711 31.5/800 Weight (lb/kg): 312/141 905/411 Capacity (Ah): 88 264

Controlled Ferroresonant CFR®

41

Indo

or S

olutio

ns

Alpha AC Catalogue 2008 For Prin41 41 7/30/2008 3:03:41 PM

Page 44: AC Power Solutions - Alpha Technologies

Nominal Specifications

Model Number:CFR 1000CFR 1000 E

CFR 1500CFR 1500 ECFR 1500 NT

CFR 2000CFR 2000 ECFR 2000 NT

CFR 2500CFR 2500 ECFR 2500 NT

CFR 3000CFR 3000 ECFR 3000 NT

CFR 5000CFR 5000 ECFR 5000 NT

Output Power Rating: 1000VA 1500VA 2000VA 2500VA 3000VA 5000VA750W 1000W 1334W 1667W 2000W 3750W

60Hz Models (CFR, CFR-NT & CFR-M)Input Voltage (VAC) Nominal: 120 120/208/240 120/208/240 120/208/240 120/208/240 120/208/240Output Voltage (VAC) Nominal: 120 120/208/240 120/208/240 120/208/240 120/208/240 120/208/24050Hz Models (CFR-E)Input/Output Voltage (VAC) Nominal: 230 230 230 230 230 230 Typical Efficiency -AC/AC 100% Load: 90% 90% 90% 90% 90% 90%Typical Heat Output - Line Mode: 284 BTU/h 427 BTU/h 398 BTU/h 636 BTU/h 758 BTU/h 1425 BTU/h MechanicalWidth (in/mm): 8.5/216 8.5/216 8.5/216 8.5/216 8.5/216 12/305Height (in/mm): 10/254 21/533 21/533 21/533 21/533 22.5 /569 Depth (in/mm): 20/508 22.5/571 22.5/571 22.5/571 29.5/749 29.4/74760Hz Weight (lb/kg): 92/42 151/69 171/78 185/84 283/128 375/170 60Hz Ship Weight (lb/kg): 97/44 162/73 182/83 200/91 312/142 453/20650Hz Weight (lb/kg): 93.42 163/74 181/82 190/86 313/142 381/173 50Hz Ship Weight (lb/kg): 98/44 174/79 192/87 205/93 332/151 477/216Internal Battery Runtime 100%*: 12min 18min 15min 10min 27min 12minInternal Battery Recharge Time: (To 80% of Capacity)

5hrs typical 5hrs typical 5hrs typical 5hrs typical 5hrs typical 5hrs typical

Extended Battery Runtime Options*A. External Battery Pack (EBP): EBP 24A EBP 48A EBP 48A EBP 48A EBP 48A EBP 48M Total Runtime**: 32min 1hr 39min 1hr 10min 52min 1hr 15min 1hr 15minB. External Battery Pack (EBP): EBP 24C EBP 48E EBP 48E EBP 48E EBP 48E EBP 1275-48B Total Runtime**: 2hrs 12min 3hrs 45min 2hrs 48min 2hrs 10min 2hrs 30min 3hrs 44minC. External Battery Pack (EBP): EBP 24E Total Runtime**: 5hrs 12min 60Hz Power Connector Options†

Input: CFR, CFR-C, CFR-M, CFR-RM Models:

5-15P5-15PL5-15P T. B.

5-20PL5-20P T. B.

5-30PL5-30PL6-30PT. B.

5-30PL5-30PL6-30PTerminal Block

5-50PCS6361L6-30P***Terminal Block

CFR-NT Models: N/A L6-30R L6-30R L6-30R L6-30 L6-30Output: CFR, CFR-C, CFR-M, CFR-RM Models:

5-15R

L5-15R

5-15R 5-20R6-20R L5-15R L5-20R L5-30R L6-20R 5-30RL6-30R T. B.

5-15R 5-20R6-20R L5-15R L5-20R L5-30R L6-20R 5-30RL6-30R T. B.

5-15R 5-20R6-20R L5-15R L5-20R L5-30R L6-20R 5-30RL6-30R T. B.

5-15R5-20R6-20RL5-15RL5-20RL5-30RL6-20R5-30RL6-30RTerminal Block

5-15R5-20R6-20RL5-15RL5-20RL5-30RL6-20R5-30RL6-30RTerminal Block

CFR-NT Models: N/A 5-15R 2-L6-30R

5-15R 2-L6-30R

5-15R 2-L6-30R

5-15R2-L6-30R

5-15R3-L6-30R

50Hz Power Connector Options†Input /Output: CFR-E Models: British

SchukoAustralian

BritishSchukoAustralian

BritishSchukoAustralian

BritishSchukoAustralianT.B.

BritishSchukoAustralianT.B.

BritishSchukoAustralianT.B.

Output Power Connector Configuration Options: 1) Any 2 single or 2 duplex receptacles 1) Any combination of 3 or less duplex receptacles 2) Any combination of 2 or less single receptacles 3) Any duplex receptacle with any single receptacle 4) Single terminal blockUPS Warranty: 24 month limited warrantyBattery: 24 month limited warranty* Battery runtimes are calculated at 100% rated loads and will vary according to battery age, loads, temperature and other factors.** Total runtime include the internal batteries and the External Battery Pack (EBP) at 100% load.† Refer to Plug and Receptacle Diagram on last page.

Controlled Ferroresonant CFR®

42

Ind

oo

r S

olu

tio

ns

Alpha AC Catalogue 2008 For Prin42 42 7/30/2008 3:03:42 PM

Page 45: AC Power Solutions - Alpha Technologies

Maximum power protection for complete isolation and uninterruptible power, assuring the ongoing performance of sensitive medical equipment

Meets demanding UL 60601-1 medical safety standards, allowing use in most medical and healthcare environments

Low current leakage supports patient vicinity equipment

Optional external battery packs greatly extend backup time

Generator compatibility meets even the longest runtime requirements

Clean, safe reliable power is critical to the health care industry. The AlphaMED® is the answer. The AlphaMED® ensures clean, reliable power, pure sine wave output power to within one percent of the nominal voltage requirement and meets the most stringent lowest leakage current requirements in the industry. Sophisticated medical equipment such as ultrasound systems, film processors, laboratory systems, and other health care devices need optimal power protection, as well as a low audible noise level. The AlphaMED® external battery packs greatly extend the backup time (up to 8 hours) allowing users to work through power outages and disturbances without interruption, rather than shutting down critical medical equipment.

Featuring an intelligent user interface, the AlphaMED® provides information and power management capacity on stand-alone or network configuration. RS-232 port, Ethernet/SNMP compatibility and remote call-out paging adds to the UPS’s advanced communications functions. Each unit comes with an automatic self-test capability and can provide an orderly, unattended shutdown of medical systems in the event of an extended power outage.

AlphaMED

AlphaMED back panel

Controlled Ferroresonant - Health CareAlphaMED®

43

Indo

or S

olutio

ns

Alpha AC Catalogue 2008 For Prin43 43 7/30/2008 3:03:43 PM

Page 46: AC Power Solutions - Alpha Technologies

Available for:

CFR 1500, 2500, 3000

Battery Pack 48V EBP 48A EBP 48E EBP 1275-48RWidth (in/mm): 8.5/216 8.5/216 22.0/660Height (in/mm): 10.5/267 21.5/546 30.3/770Depth (in/mm): 10.5/267 21.5/546 31.5/800Weight (lb/kg): 127/58 312/141 905/411Capacity (Ah): 33 88 264

Nominal Specifications

Model Number: AlphaMED® 1000 AlphaMED® 1000E

AlphaMED® 1500 AlphaMED® 1500E

AlphaMED® 2000 AlphaMED® 2000E

AlphaMED® 2500 AlphaMED® 2500E

AlphaMED® 3000

AlphaMED® 3000EOutput Power Rating: 1000VA / 750W 1500VA / 1000W 2000VA / 1334W 2500VA / 1667W 3000VA / 2000WInput/Output Voltage (VAC) Nominal:

120 230

120/208/240* 230

120/208/240* 230

120/208/240* 230

120/208/240* 230

Typical Efficiency - AC/AC 100% Load:

90% 90% 90% 90% 90%

Typical THD: 5% 5% 5% 5% 5%Typical Heat Output - Line Mode:

427BTU/h 398BTU/h 636BTU/h 758BTU/h

Audible Noise at 1m: <38dBA <38dBA <39dBA <39dBA <39dBAWaveform: sine sine sine sine

Noise Attenuation

Common Mode (100k to 1MHz):

-120dB -120dB -120dB -120dB -120dB

Normal Mode (100k to 1MHz): -60 dB -60dB -60dB -60dB -60dBOperation Temperature (˚F/˚C): 32 to 104/0 to 40 32 to 104/0 to 40 32 to 104/0 to 40 32 to 104/0 to 40 32 to 104/0 to 40Mechanical

Width (in/mm): 8.5/216 8.5/216 8.5/216 8.5/216 8.5/216Height (in/mm): 10/254 21/533 21/533 21/533 21/533Depth (in/mm): 20/508 22.5/571 22.5/571 22.5/571 29.5/749Weight (lb/kg): 92/42 151/69 171/78 185/84 283/128Internal Battery Runtime**: 18min 15min 10min 27minMax. Battery Charger Current: 3A 3A 3A 3A 3ABattery Recharge Time: 5 hrs typical 5hrs typical 5hrs typical 5hrs typical 5hrs typicalExtended Battery Run Time Options* A. External Battery Pack (EBP): EBPA EBP 48A EBP 48A EBP 48A EBP 48A Total Runtime***: 1hr 39min 1hr 10min 52min 1hr 15minB. External Battery Pack (EBP): EBPA EBP 48E EBP 48E EBP 48E EBP 48E Total Runtime***: 3hrs 45min 2hrs 48min 2hrs 10min 2hrs 30min

* Factory configured** Battery runtimes are calculated at 100% load and will vary according to battery age, loads, temperature and other factors.*** Total runtime include the internal batteries and the External Battery Pack (EBP).

Agency Compliance

Marks: CSA 107.1-01, CAN/CSA 601.1-M90

Safety: UL 1778 (2nd Edition), UL Std No 60601-1 (1st Edition)

Power Connector Options

Input: Hospital Grade NEMA STD:

Output: Hospital Grade NEMA STD:

Output Power Connector Configuration Options

1) Any combination of 3 or less duplex receptacles. 2) Any combination of 2 or less single receptacles. 3) Any duplex receptacle with any single receptacle. 4) Single terminal block. (Other Configurations may be available)

EBP Options Alpha’s plug-in External Battery Packs provide extended backup for all CFR models.

All battery packs are shipped fully assembled and include interconnecting cables.

Longer runtimes are obtained by cascading additional battery cabinets.

Controlled Ferroresonant - Health CareAlphaMED®

44

Ind

oo

r S

olu

tio

ns

Alpha AC Catalogue 2008 For Prin44 44 7/30/2008 3:03:45 PM

Page 47: AC Power Solutions - Alpha Technologies

True on-line topology

Very high efficiency

Transformerless technology

Dual input power sources for optimum reliability

Digital Power Quality IGBT inverter technology

Advanced battery management for maximum battery life

Generator friendly

Compact footprint

Network based software for multi-server control

SNMP manageable

Graphical User Interface with color touch screen

Scalable power levels

Whether you are protecting a large server farm or air traffic control tower, the COMET UPS has proven to be the most reliable solution for mid-range power protection applications. The COMET uses a true on-line topology regenerating 100% of the output power to guarantee complete isolation and protection from all utility power problems. Combined with features like 95% efficiency, less than 3.5% output distortion and unique Digital Power Quality IGBT inverter technology the COMET also boasts some of the most favorable specifications of any UPS. Trusted by IT professionals as the industry standard solution, COMET has now become one of the best selling UPSs in its class.

Three PhaseComet

Comet

45

Indo

or S

olutio

ns

Alpha AC Catalogue 2008 For Prin45 45 7/30/2008 3:03:46 PM

Page 48: AC Power Solutions - Alpha Technologies

Nominal Specifications

Model: 50 Series 80 Series 150 SeriesOutput Power: 40kVA/32kW 50kVA/40kW 65kVA/52kW 80kVA/64kW 100kVA/80kW 125kVA/100kW 150kVA/120kWInput Voltage (VAC L-L): 208 480 480 600 208 480 480 600 208 480 480 600 208 480 480 600 208 480 480 600 208 480 480 600 208 480 480 600Output Voltage (VAC L-L): 208 208 480 208 208 208 480 208 208 208 480 208 208 208 480 208 208 208 480 208 208 208 480 280 208 208 480 208

AC Input (With Standard Input Filter)Max. Current (A): 131 57 57 45 164 71 71 56 212 92 92 74 261 113 113 91 301 128 125 107 371 158 154 129 444 182 182 154

ByPass InputNominal Current (A): 111 48 48 39 139 60 60 48 180 78 78 63 222 96 96 77 256 109 106 91 316 134 130 109 378 160 155 131

AC OutputNominal Current (A): 111 111 48 111 139 139 60 139 180 180 78 180 222 222 96 222 278 278 120 278 347 347 150 347 416 416 180 416

DC LineNominal Voltage (VDC) @ 25°C: 432 432 432 432 432 432 432 432 432 432 432 432 432 432 432 432 432 432 432 432 432 432 432 432 432 432 432 432Float Voltage (VDC) @ 25°C: 490 490 490 490 490 490 490 490 490 490 490 490 490 490 490 490 490 490 490 490 490 490 490 490 490 490 490 490End of Discharge (VDC) @ 25°C: 361 361 361 361 361 361 361 361 361 361 361 361 361 361 361 361 361 361 361 361 361 361 361 361 361 361 361 361Max. Amps (VDC) @ Cutoff: 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123 123

UPS Mechanical SpecificationsDepth (in): 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34Depth (cm): 86 86 86 86 86 86 86 86 86 86 86 86 86 86 86 86 86 86 86 86 86 86 86 86 86 86 86 86Height (in): 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67 67Height (cm): 170 170 170 170 170 170 170 170 170 170 170 170 170 170 170 170 170 170 170 170 170 170 170 170 170 170 170 170

Single Input1

Installed Weight (lb): 1760 1360 880 2460 1760 1360 880 2460 2115 1590 970 2690 2115 1590 970 2690 3400 2450 1450 3400 3400 2450 1450 3400 3400 2450 1450 3400Installed Weight (kg): 798 617 399 1274 798 617 399 1274 964 721 440 1503 959 721 440 1503 1542 1111 658 1542 1542 1111 658 1542 1542 1111 658 1542Installed Width (in): 33 33 33 59 33 33 33 59 33 33 33 59 33 33 33 59 69 43 43 69 69 43 43 69 69 43 43 69Installed Width (cm): 84 84 84 150 84 84 84 150 84 84 84 150 84 84 84 150 175 109 109 175 175 109 109 175 175 109 109 175

Dual Input2

Added Installed Weight (lb): 1110 — — 1650 1100 — — 1650 1100 — — 1650 1100 — — 1650 1100 — — 1650 1100 — — 1650 1100 — — 1650Added Installed Weight (kg): 499 — — 748 499 — — 748 499 — — 748 499 — — 748 726 — — 748 726 — — 748 726 — — 748Total Installed Width (in): 59 33 33 85 59 33 33 85 59 33 33 85 59 33 33 85 95 43 43 95 95 43 43 95 95 43 43 95Total Installed Width (cm): 150 84 84 216 150 84 84 216 150 84 84 216 150 84 84 216 241 109 109 241 241 109 109 241 241 109 109 241

System Efficiencies@ 100% Load (%): 90 90 93 90 90 90 93 90 91 92 94 91 91 91 94 91 91 93 95 91 90 92 95 90 90 92 94 90@ 75% Load (%): 90 91 94 90 90 91 94 90 91 92 94 91 91 91 94 91 91 93 95 91 91 93 95 91 90 92 95 90@ 50% Load (%): 89 90 93 89 89 90 93 89 91 92 94 91 91 91 94 91 89 91 94 89 90 92 94 90 90 93 95 90

Full Load Heat DissipationBTU/hr. (x 1000): 16.9 15.2 10.3 16.9 16.9 15.2 10.3 16.9 17.6 15.4 11.3 17.6 21.6 18.9 13.9 21.6 28.3 22.3 15.4 28.3 38.2 30.7 20.8 38.2 50.7 41.6 26.3 50.7Watts (x 1000): 4.9 4.4 3 4.9 4.9 4.4 3 4.9 5.2 4.5 3.3 5.2 6.3 5.5 4 6.3 8.3 6.5 4.5 8.3 11.2 8.9 6.1 11.2 14.9 12.2 7.7 14.9

Note: Adjacent battery pack width not included with UPS.1. Single Input feeds both the Bypass and the Inverter.2. Dual input has separate feed for both the Bypass and the Inverter. Weight to be added. Auxiliary cabinet included where required.

Battery Pack Options

RuntimesBattery Type Qty. per Cabinet 40kVA (min) 50kVA (min) 65kVA (min) 80kVA (min) 100kVA (min) 125kVA (min) 150kVA (min)NPX 150R: 36 12 10 6 — — — — UPS 12-270F: 36 28 23 17 12 8 5 — UPS 12-370F: 36 45 36 25 20 15 10 7UPS 12-475F: 36 65 52 36 28 19 13 9UPS 12-270F: 72 73 60 45 31 25 18 13.5UPS 12-370F: 72 100 80 60 46 36 26 21UPS 12-270F: 108 110 90 72 56 42 31 25UPS 12-475F: 72 150 120 94 60 56 37 30UPS 12-370F: 108 195 156 115 76 60 46 36UPS 12-475F: 108 250 198 145 92 69 60 51Note: Runtimes are listed at full load.

Battery Mechanical Specifications: NPX 150R UPS 12-270F UPS 12-30F UPS 12-475FWeight (lb/kg): 1878/852 2750/1247 3380/1533 4100/1860Width (in/cm): 26/66 32/81 48/122 48/122

For additional information about the AlphaSource 6000 (225 to 800kVA) please contact your local sales representative.

Three PhaseComet

46

Ind

oo

r S

olu

tio

ns

Alpha AC Catalogue 2008 For Prin46 46 7/30/2008 3:03:48 PM

Page 49: AC Power Solutions - Alpha Technologies

Power ranges 40, 50, 65 and 75kVA

True online double conversion technology

IGBT rectifier

Low UPS to generator sizing

Power surge stabilization system

SNMP and network based power management options

Power factor corrected input SNMP and network based power management options

The Galaxy 4000 is designed for data center grade power protection in critical environments. Features include fault tolerant architecture to protect loads and the UPS unit during unintended faults, easy and quick to install, user-friendly graphical interface, web based monitoring options, and front only access. The IGBT rectifier minimizes input harmonics and power factor corrected input reduces installation costs due to smaller cabling and generator costs. The Galaxy 4000’s unique fault tolerant architecture safely manager output faults without compromising the UPS, while the Digital Power Quality Management System provides precision voltage regulation on a consistent bases. The UPS is also available as a UL 924 system for emergency lighting applications.

Galaxy 4000

Optional Features

RS232/RS485 serial interfaceEthernet/SNMP web card connection kitExternal maintenance bypass with interlockInternal maintenance bypassSeismic brackets42 pole distribution

Three PhaseGalaxy 4000

47

Indo

or S

olutio

ns

Alpha AC Catalogue 2008 For Prin47 47 7/30/2008 3:03:51 PM

Page 50: AC Power Solutions - Alpha Technologies

Nominal Specifications

Output Power Rating: 40kVA 50kVA 65kVA 75kVA

Input

Voltage: 208V 208V 208V 208V

Frequency: 60Hz (±5%) 60Hz (±5%) 60Hz (±5%) 60Hz (±5%)

Power Factor: >0.98 >0.98 >0.98 >0.98

Current Distortion (THD): >3% >3% >3% >3%

Current (A @ 208V): 102 127 166 191

Output

Voltage: 208V 208V 208V 208V

Frequency: 60Hz (±1 to 4% selectable) 60Hz (±1 to 4% selectable) 60Hz (±1 to 4% selectable) 60Hz (±1 to 4% selectable)

Transient Response: ±5% for 0 to 100% to 0% ±5% for 0 to 100% to 0% ±5% for 0 to 100% to 0% ±5% for 0 to 100% to 0%

Voltage Distortion THD: <1% L-L and L-N <1% L-L and L-N <1% L-L and L-N <1% L-L and L-N

Inverter Overload:130% for 1min 145% for 45sec

130% for 1min 145% for 45sec

130% for 1min 145% for 45sec

130% for 1min 145% for 45sec

Bypass Overload: 10x nominal current 10x nominal current 10x nominal current 10x nominal current

Output Current (A @ 208V): 111 139 180 208

Heat Rejection (max. BTUs): 14900 18700 24200 28000

Runtimes @ 100% Load

1 x 285W/Cell: 12 9 6 -

1 x 370W/Cell: 20 14 9 8

1 x 500W/Cell: 28 22 15 11

2 x 370W/Cell: 47 36 25 22

2 x 500W/Cell: 67 52 38 31

3 x 500W/Cell: 98 85 60 53

4 x 500W/Cell: 136 115 85 72

Mechanical Specifications

Standard Cabinet

Dimensions (in): 33.5W x 72.1H x 35.6D 33.5W x 72.1H x 35.6D 33.5W x 72.1H x 35.6D 33.5W x 72.1H x 35.6D

(mm): 851W x 1831H x 904D 851W x 1831H x 904D 851W x 1831H x 904D 851W x 1831H x 904D

Weight (lb/kg): 1235/560 1235/560 1235/560 1235/560

Battery Cabinet

Dimensions (in): 26.5W x 72.1H x 33.5D 26.5W x 72.1H x 33.5D 26.5W x 72.1H x 33.5D 26.5W x 72.1H x 33.5D

(mm): 673W x 1831H x 851D 673W x 1831H x 851D 673W x 1831H x 851D 673W x 1831H x 851D

Weight (lb/kg): 2045/928 2045/928 2045/928 2045/928

Second Battery Cabinet

Dimensions (in): 33.5W x 72.1H x 33.5D 33.5W x 72.1H x 33.5D 33.5W x 72.1H x 33.5D 33.5W x 72.1H x 33.5D

(mm): 851W x 1831H x 851D 851W x 1831H x 851D 851W x 1831H x 851D 851W x 1831H x 851D

Weight (lb/kg): 2745/1245 2745/1245 2745/1245 2745/1245

Standards:ISO 9001, UL 1778, cUL , FCC Part 15, subpart J, Class A, NEMA PE 1, NEMA 250, NFPA 70, IEC 10000 (801) level 4, OSHA

Three PhaseGalaxy 4000

48

Ind

oo

r S

olu

tio

ns

Alpha AC Catalogue 2008 For Prin48 48 7/30/2008 3:03:52 PM

Page 51: AC Power Solutions - Alpha Technologies

Power ranges 10, 15, 20 and 30kVA

True online technology

Network-based power management

Input Power Factor Correction (PFC)

All-in-one complete solution

The Galaxy 3000 is the uninterruptible power supply design for mid-range data center enterprise level applications. The Galaxy 3000 delivers the optimum level of reliability, availability and scalability demanded by the new generation of critical enterprise applications. Clearly separated from the crowd by its robust Ultra High Availability Topology (UHAT), the Galaxy reacts to any circumstance in an inherently safe way to protect the critical load.

The true all-in-one design incorporates every feature into one compact cabinet, including animated graphical user interface, power factor corrected input, batteries and space for four communication cards. Combined with a scalable design, dual power feed option and generator friendly technology, the AlphaSource Galaxy is truly a quantum leap forward in critical power protection.

Galaxy 3000

Standard Features

Input distribution management

Digital power quality management system (PWM/IGBT inverter)

Step load voltage stabilization

Intelligent battery management system

Fault tolerant architecture

Scalable architecture (10 & 20kVA models)

No extra cabinet for isolation transformer

Integrated battery bank

Low audible noise fans (<53dBA)

Casters with leveling feet

Network based software for multi-server control

Dry contact i/o card

SNMP manageable

4 color graphic display with multilingual user interface

Bottom or top entry

Integrated maintenance bypass

Four communications ports

12 month warranty

Optional Features

Matching power distribution unit (84 circuits)

EIA232 / EIA485 serial interface

Ethernet/SNMP network connection kit

Dual input

External maintenance bypass

Input isolation transformer

Three PhaseGalaxy 3000

49

Indo

or S

olutio

ns

Alpha AC Catalogue 2008 For Prin49 49 7/30/2008 3:03:52 PM

Page 52: AC Power Solutions - Alpha Technologies

Nominal Specifications

Output Power Rating: 10kVA 15kVA 20kVA 30kVA

Input

Voltage: 208/220/480/600 208/220/480/600 208/220/480/600 208/220/480/600

Frequency: 60Hz (-25 to 8%) 60Hz (-25 to 8%) 60Hz (-25 to 8%) 60Hz (-25 to 8%)

Power Factor: >0.99 >0.99 >0.99 >0.99

Current Distortion (THD): >3% >3% >3% >3%

Current (A @ 208V): 26 46 61 91

Breaker (@ 208): 40 60 80 125

Output

Voltage: 208 (220/480/600) 208 (220/480/600) 208 (220/480/600) 208 (220/480/600)

Frequency;60Hz (±1 to 4% selectable)

60Hz (±1 to 4% selectable)

60Hz (±1 to 4% selectable)

60Hz (±1 to 4% selectable)

Transient Response: ±3% for 0 to 100% to 0% ±3% for 0 to 100% to 0% ±3% for 0 to 100% to 0% ±3% for 0 to 100% to 0%

Voltage Distortion THD: <3% L-L and L-N <3% L-L and L-N <3% L-L and L-N <3% L-L and L-N

Inverter Overload: 120% for 1min 120% for 1min 120% for 1min 120% for 1min

Bypass Overload: 10x nominal current 10x nominal current 10x nominal current 10x nominal current

Output Current (A @ 208V): 28 42 56 83

Heat Rejection (max. BTUs): 4100 6100 8200 12200

Batteries

Backup Time (minutes)1: 11/39/60 7/22/35/55 15/24/38 8/12/21

Mechanical Specifications

Standard Cabinet

Dimensions (in): 32.8W x 62.4H x 35.5D 32.8W x 62.4H x 35.5D 32.8W x 62.4H x 35.5D 32.8W x 62.4H x 35.5D

(cm): 83.8W x 158.5H x 90.2D 83.8W x 158.5H x 90.2D 83.8W x 158.5H x 90.2D 83.8W x 158.5H x 90.2D

Weight2 (lb/kg): 2.065/0.94 2.065/0.94 2.065/0.94 2.065/0.94

Micro Cabinet3

Dimensions (in): 23W x 48.5H x 33.5D 23 W x 48.5 H x 33.5 D — —

(cm): 58.4W x 123.2H x 90.2D 58.4W x 123.2H x 90.2D — —

Weight (lb/kg): 2.065/0.94 2.065/0.94 — —

Auxiliary Cabinets

Maintenance Bypass Cabinet (in): 23W x 62.4H x 35.5D 23W x 62.4H x 35.5D 23W x 62.4H x 35.5D 23W x 62.4H x 35.5D

(cm): 58.4W x 158.5H x 90.2D 58.4W x 158.5H x 90.2D 58.4W x 158.5H x 90.2D 58.4W x 158.5H x 90.2D

Output Voltage Transformer (in): 23W x 62.4H x 35.5D 23W x 62.4H x 35.5D 23W x 62.4H x 35.5D 23W x 62.4H x 35.5D

(cm): 58.4W x 158.5H x 90.2D 58.4W x 158.5H x 90.2D 58.4W x 158.5H x 90.2D 58.4W x 158.5H x 90.2D

Distribution Cabinet (24 to 42 pole)(in): 23W x 62.4H x 35.5D 23W x 62.4H x 35.5D 23W x 62.4H x 35.5D 23W x 62.4H x 35.5D

(cm): 58.4W x 158.5H x 90.2D 58.4W x 158.5H x 90.2D 58.4W x 158.5H x 90.2D 58.4W x 158.5H x 90.2D

Weight (lb/kg): 780/353.8 780/353.8 780/353.8 780/353.8

Standards: UL 1778, cUL , FCC Class A parts, 15 sub part J Class A, IEC 1000 level 4, IEEE C62.41-B3, NEC, ISO 9001

1 11/7min battery times only applicable for micro cabinet. 2 Weight will vary based on battery runtime and input volt options.3 Micro Cabinet only available in 208/208V. External maintenance bypass distribution options not available with micro cabinet.

Three PhaseGalaxy 3000

50

Ind

oo

r S

olu

tio

ns

Alpha AC Catalogue 2008 For Prin50 50 7/30/2008 3:03:52 PM

Page 53: AC Power Solutions - Alpha Technologies

Receptacle Information

Electrical receptacles, outlets, and wall sockets are used in a variety of residential, general-purpose, commercial, industrial, laboratory, and hospital applications. Several blade or pin types are available. Straight (non-locking) electrical receptacles are inserted at a right angle to the plane of the matching device face. By contrast, locking receptacles fix or lock a plug in place when the plug is inserted and then rotated. Electrical receptacles provide maximum voltage and maximum current ratings. Typically, devices are designed for either single-phase or three-phase power.

Below are diagrams to help identify plugs and receptacles for your electrical applications

X

G

X

GG

X

G

XX

YG

YG

X

Y Y Y Y

X

G

WY W Y

G

X

W/Y

X

G

X

GW/Y

NEMA CONFIGURATIONS FOR PLUGS AND RECEPTACLES

Non-Locking Plugs and Receptacles

Locking Plugs and Receptacles

15 Ampere 20 Ampere 30 Ampere 50 Ampere

15 Ampere 20 Ampere 30 Ampere 50 Ampere

Receptacle ReceptaclePlug Plug Receptacle Plug Receptacle Plug

Receptacle ReceptaclePlug Plug Receptacle Plug Receptacle Plug

125 V

250 V

125 V

250 V

125 /250 V

AlphaP/N

AlphaP/N

AlphaP/N

AlphaP/N

AlphaP/N

5-15R531-003-10531-002-10531-013-10

L6-15P530-202-10531-203-10

5-15P530-001-10

6-15R531-004-10

L5-15R531-201-10

L6-15R531-202-10

L6-20R531-205-10

L14-20R L14-20P530-205-10

L6-20P530-206-10

L6-30R531-207-10

L6-30P530-208-10

L5-15P530-201-10

L5-20R531-203-10

L5-20P530-204-10

L5-30R531-206-10

L5-30P530-207-10 531-208-10

531-209-10 530-210-10

530-209-10

6-15P530-002-10

6-20R531-008-10

6-20P530-004-10

6-30R531-010-10

6-30P530-006-10

6-50R531-012-10

6-50P530-008-10

5-20R531-006-10

5-20R531-005-10

6-20R531-007-10

5-20P530-003-10

5-30R531-009-10

5-30P530-005-10

5-50R531-011-10

5-50P530-007-10

For Canadian Customers Only

For Canadian Customers Only

EEMAC Configuration

EEMAC Configuration

(Not NEMA Config)

(Not NEMA Config)

Electrical Receptacles

51

Electrical R

eceptacles

Alpha AC Catalogue 2008 For Prin51 51 7/30/2008 3:03:53 PM

Page 54: AC Power Solutions - Alpha Technologies

Building upon its suite of products, Alpha now offers a range of service solutions designed to meet your needs.

Extended Warranty:

Alpha extended warranties are available from the time of initial purchase through to the expiry of the product’s original warranty period. One or three year extensions offer all the terms and conditions of the original equipment warranty, for both the UPS and batteries in your system, with battery coverage offered on a prorated basis due to the nature of wear they sustain over time.

To purchase an extended warranty, or to make a claim against the initial product warranty, you will first need to ensure your products are registered. Additionally, product registration automatically extends your initial warranty period for an additional three months. Please note extended warranties are only available to the original registered purchaser. Register your products at www.alpha.com/productregistration

Field Service Contracts:

Enjoy convenience and peace-of-mind with an annual, prepaid, on site service plan and ensure all your service needs throughout the year are covered. Alpha offers two levels of service plans:

Alpha Basic Plan:A trained Alpha field service representative is available to you during regular business hours and will respond to service requests at your location by the next business day.

Alpha Emergency Plan:An Alpha field service representative is available to you during regular business hours and will respond to service requests at your location within four hours (not available in all areas).

Whether you choose the Alpha Basic Plan or the Alpha Emergency Plan you can rest assured you are covered. Alpha service plans ensure the people and parts will always be on hand. to provide the services you need when you need them most (not available in all areas). Both service plans include: • Unlimited technical phone support • All parts and labor • Travel expenses • All costs associated with equipment service

* battery replacement is offered on a prorated basis due to the nature of wear they sustain over time

Optional Coverage:

The purchase of an extended warranty or field service contract also enables you to benefit from valuable service options. Scheduled Preventative Maintenance ensures your backup solutions are always operating at optimum levels. An annual preventative maintenance visit from an Alpha representative includes: • Confirm proper installation of UPS • Clean or replace air filters • Test individual cells for voltage and impedance • Clean, inspect and test complete solution (inverters, transformers, switches and other components) • Perform thermal scan of solution using IR thermographs

Battery Renewal allows you to budget for battery replacement. When your batteries need replacing, Alpha will cover the cost.

Our Commitment:

Alpha Technologies is committed to providing service programs that ensure power integrity throughout the service life of you Alpha product.

Service

52

Ser

vice

Alpha AC Catalogue 2008 For Prin52 52 7/30/2008 3:03:53 PM

Page 55: AC Power Solutions - Alpha Technologies

UninterruptiblePowerSupplySelectionGuide

To help us design an Uninterruptible Power Supply (UPS) solution for your specific application, please review the following questions prior

to contacting your Alpha representative.

TypeofApplication:

PBX, Cell Site, Server, Traffic, Parking, Security, Medical or other.

Environment:

Indoor: Controlled environment, air conditioned, dust free

Outdoor: Non-controlled environment

Minimum ambient temperature surrounding the UPS

Maximum ambient temperature surrounding the UPS

Geographic Location where the UPS is located (Country, City/Town)

Power Requirements:

Volt-amps (VA) or Watts required by load

Input voltage to UPS and Output voltage(s) to load

Frequency (Hz) 50 or 60

Backup Time Required:

The amount of time in hours or minutes the UPS will operate on batteries when the utility power fails

Mounting Configuration:

For Indoor Applications: Rack, Tower

For Outdoor Applications: Pole, Ground (Is a pedestal required?), or Wall

Configuration Requirements:

Input plug type or terminal block

Output receptacle types or terminal block

Accessories:

Bypass Switch (Auto/Manual), Ethernet/SNMP, Battery Heater Mats, Battery Management System

Warranty:

Is extended warranty required? Special servicing needs?

Quantities:

Number of units required and when

SelectionGuide

Page 56: AC Power Solutions - Alpha Technologies

Alpha Technologies Due to continuing product development, Alpha reserves the right to change specifications without notice. Copyright © 2008 Alpha Technologies Inc. All Rights Reserved. Alpha is a registered trademark of Alpha Technologies. 048-160-10 (07/2008)

www.alpha.com

Argus TechnologiesUSA/Canada+ 1 604 436 5900

Alpha Technologies Europe Ltd.United Kingdom +44 1279 501110

Alpha Technologies GmbHGermany+ 49 9122 79889 0

AlphaTec Ltd.Republic of Cyprus+357 25 375675

Alphatec BalticsLithuania+370 5 213 8822

Alpha TechnologiesFrance+33 141 900 707

AlphaTEK oooRussia+7 495 916 1854

Alpha TechnologiesPR China+852 2736 8663

Alpha Technologies Ltd.4084 McConnell CourtBurnaby BC V5A 3N7Canada+ 1 800 667 8743 (toll free)+ 1 604 430 1476 (Canada)+ 1 360 647 2360 (USA)

Visit www.alpha.com for additional information.

member of The Group™