Aboveground Storage Tank Compliance Seminar August 16, 2016 By Sam Wilkes, MS, PWS Geo-Environmental Department Manager [email protected] 304-729-9119 1 [email protected] 304-729-9119
15

Aboveground Storage Tank Compliance Seminarstorage.cloversites.com/terradoncorporation/documents/... · 2016-08-17 · Aboveground Storage Tank Compliance Seminar August 16, 2016

May 31, 2020

Download

Documents

dariahiddleston
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Aboveground Storage Tank Compliance Seminarstorage.cloversites.com/terradoncorporation/documents/... · 2016-08-17 · Aboveground Storage Tank Compliance Seminar August 16, 2016

Aboveground Storage Tank Compliance Seminar

August 16, 2016

By

Sam Wilkes, MS, PWS

Geo-Environmental Department Manager

[email protected]

304-729-9119

1 [email protected] 304-729-9119

Page 2: Aboveground Storage Tank Compliance Seminarstorage.cloversites.com/terradoncorporation/documents/... · 2016-08-17 · Aboveground Storage Tank Compliance Seminar August 16, 2016

Summary of Presentation

• Summary of Annual Qualified Inspections• Summary of O&M Inspections• Record Keeping Methods

2 [email protected] 304-729-9119

Page 3: Aboveground Storage Tank Compliance Seminarstorage.cloversites.com/terradoncorporation/documents/... · 2016-08-17 · Aboveground Storage Tank Compliance Seminar August 16, 2016

Inspections PE/API 3 Years (Level 1) 5 Years (Level 2)1st Qualified Inspectionnot already PE/API inspected, under INTERPRETIVE RULE (47CSR 62)

Within 180 days of August 1, 2016

(January 28, 2017)

Within 180 days of August 1, 2016

(January 28, 2017)

Owner Inspections intervening yearsJanuary 1, 2018January 1, 2019

January 1, 2018January 1, 2019January 1, 2020January 1, 2021

PE/API Qualified Inspection January 1, 2020 January 1, 2022

Fit For Service January 1 Annually

Fit, but needs repairsJanuary 1, must submit recommended

repair schedule

Deficient Taken out of services for repairsAnnual WVDEP Certifications filed Electronic Submission System (ESS)

January 1 Annually

Summary Annual Qualified Inspections

3 [email protected] 304-729-9119

Page 4: Aboveground Storage Tank Compliance Seminarstorage.cloversites.com/terradoncorporation/documents/... · 2016-08-17 · Aboveground Storage Tank Compliance Seminar August 16, 2016

Fit, Fit with Repairs, or Deficient?

4 [email protected] 304-729-9119

Page 5: Aboveground Storage Tank Compliance Seminarstorage.cloversites.com/terradoncorporation/documents/... · 2016-08-17 · Aboveground Storage Tank Compliance Seminar August 16, 2016

Annual Inspection Form Summary

• Secondary Containment • Tank Foundation/Support Condition• Tank Construction Material• Tank External Coating• Tank Shell Condition• Tank Manways, Piping and Equipment• Tank Roof• Venting• Electrical Equipment• Poly or Fiberglass Rapped Plastic Tank Inspection • Owner Inquiry

o Leak Detection Method(s) being usedo Vent Testing as required by manufacturero Secondary Containment sufficiently impervious (72 hours)o Cathodic Protection tested yearly

5 [email protected] 304-729-9119

Page 6: Aboveground Storage Tank Compliance Seminarstorage.cloversites.com/terradoncorporation/documents/... · 2016-08-17 · Aboveground Storage Tank Compliance Seminar August 16, 2016

Fit, Fit with Repairs, or Deficient?

6 [email protected] 304-729-9119

Page 7: Aboveground Storage Tank Compliance Seminarstorage.cloversites.com/terradoncorporation/documents/... · 2016-08-17 · Aboveground Storage Tank Compliance Seminar August 16, 2016

Fit, Fit with Repairs, or Deficient?

7 [email protected] 304-729-9119

Page 8: Aboveground Storage Tank Compliance Seminarstorage.cloversites.com/terradoncorporation/documents/... · 2016-08-17 · Aboveground Storage Tank Compliance Seminar August 16, 2016

Summary of O&M Inspections

Item Level 1 AST Level 2 AST

Title 47 CSR Series 63 ASTEffective Date August 1, 2016

O&M Secondary Containment Inspection (47-63-5) 14 days 1 month

Secondary Containment (sufficiently impervious, 72 hours) X X

Release, spill, overflow, or leak X X

Deterioration, accumulation of product, or water X X

Drains secure and closed X X

Rain water must not exceed 10% capacity X X

Retain inspection documentation 12 continuous months

8 [email protected] 304-729-9119

Page 9: Aboveground Storage Tank Compliance Seminarstorage.cloversites.com/terradoncorporation/documents/... · 2016-08-17 · Aboveground Storage Tank Compliance Seminar August 16, 2016

Fit, Fit with Repairs, or Deficient?

9 [email protected] 304-729-9119

Page 10: Aboveground Storage Tank Compliance Seminarstorage.cloversites.com/terradoncorporation/documents/... · 2016-08-17 · Aboveground Storage Tank Compliance Seminar August 16, 2016

Repairs

10 [email protected] 304-729-9119

Page 11: Aboveground Storage Tank Compliance Seminarstorage.cloversites.com/terradoncorporation/documents/... · 2016-08-17 · Aboveground Storage Tank Compliance Seminar August 16, 2016

AST Visual Inspection to 1st Isolation PointLevel 1 Level 2

1 month 1 month

Monitor Leak Detection Methods (Section 10.3) X XVisual Leak Detection (10.3.c) Double Bottomed designed to channel fluids to an observation area X XInterstitial Monitoring (10.3.g) X XLeak Detection Deficiencies June 30, 2017 June 30, 2018

Records must contain: Monitors Name, Monitoring Method(s), Monitoring Date, Results X X

Coatings (rust, blisters, peeling, cracking, coating bond failure) X X

Malfunctioning or deficient equipment Critical repairs 30 days 30 daysRetain Inspection Documentation 12 continuous months

Summary of O&M Inspections

11 [email protected] 304-729-9119

Page 12: Aboveground Storage Tank Compliance Seminarstorage.cloversites.com/terradoncorporation/documents/... · 2016-08-17 · Aboveground Storage Tank Compliance Seminar August 16, 2016

Fit, Fit with Repairs, or Deficient?

12 [email protected] 304-729-9119

Page 13: Aboveground Storage Tank Compliance Seminarstorage.cloversites.com/terradoncorporation/documents/... · 2016-08-17 · Aboveground Storage Tank Compliance Seminar August 16, 2016

Recordkeeping Methods

Inspection Documents Minimum consecutive 12 monthsCustomized Hard Copy Paper Binder to be kept at the facilityElectronic Inspection Sheets in Word Electronic Files to be kept at the facility

Electronic Inspection Sheets in ExcelSpreadsheet style initial and comment area

Electronic files converted to PDF with electronic signature

May be scanned with real signature and kept in PDF format

Ultimately long term files can be kept in database or GIS formats

Annual Inspection forms kept with a photo log and WVDEP certification and maintenance log, if necessary

13 [email protected] 304-729-9119

Page 14: Aboveground Storage Tank Compliance Seminarstorage.cloversites.com/terradoncorporation/documents/... · 2016-08-17 · Aboveground Storage Tank Compliance Seminar August 16, 2016

14 [email protected] 304-729-9119

Page 15: Aboveground Storage Tank Compliance Seminarstorage.cloversites.com/terradoncorporation/documents/... · 2016-08-17 · Aboveground Storage Tank Compliance Seminar August 16, 2016

Discussion and Questions

Sam Wilkes

Geo-Environmental Department Manager

304-729-9119

[email protected]

15 [email protected] 304-729-9119