Ablerex Electronics Co., Ltd. Power Abler & Excelsior http://www.ablerex.com.tw Mars RT Pro On-Line Series UPS
Dec 17, 2015
Ablerex Electronics Co., Ltd.Power Abler & Excelsior
http://www.ablerex.com.tw
Mars RT Pro On-Line Series UPS
Ablerex Electronics Co., Ltd.Power Abler & Excelsior
http://www.ablerex.com.twContent
Introduction of MP Series System Block Diagram Product Features Functions Explanations Product Specifications Q&A
Ablerex Electronics Co., Ltd.Power Abler & Excelsior
http://www.ablerex.com.twIntroduction of MP Series
Mars – RT Pro
Model MP 1K( X/C )
2K( X/C )3K( X/C )
Capacity : 1000VA, 2000VA, 3000VAServers in Rack / Tower Convertible
Networking & VOIP Telecom Equipment Sensitive Electronic Equipment in Industrial Environment
Ablerex Electronics Co., Ltd.Power Abler & Excelsior
http://www.ablerex.com.twSystem Block Diagram
True Online Double Conversion for Various Applications
Ablerex Electronics Co., Ltd.Power Abler & Excelsior
http://www.ablerex.com.twProduct Features
True On-line Double Conversion Topology Fully High Performance DSP Control Flexible Rack/Tower Application Input Frequency 45-65Hz Wide Range Input Window from 120~288Vac High Input Power Factor & Low Current THD Programmable Receptacles Versatile Interfaces Options Hot-Swappable Battery Bigger Charger & Extended Battery Connector Galvanic Isolation Transformer Models are Available
Ablerex Electronics Co., Ltd.Power Abler & Excelsior
http://www.ablerex.com.twFunctions Explanations
LED Indicators: 1. Overload2. Fault3. Site Wiring Fault4. Battery Weak/Bad5. Self-test6. Programmable
Outlet17. Programmable
Outlet28. Bypass Mode9. Battery Mode10. Line Mode
Control Keypads: 11. On Key12. Off Key13. Test & Alarm Silence Key
1234567
8910111213
Ablerex Electronics Co., Ltd.Power Abler & Excelsior
http://www.ablerex.com.tw
LED Indicators:LED Indicators: 1. LCD2. Utility 3. Programmable Outlet14. Programmable Outlet25. Bypass Range 6. Fault
Control Keypads:Control Keypads:
7. ON Key &Alarm Silence Key
8. OFF Key9. Function Key10. Down Key11. Up Key12. Enter Key
Ablerex Electronics Co., Ltd.Power Abler & Excelsior
http://www.ablerex.com.tw
Real Panel Explanation (1kVA)
①USB Comm. Port②RS-232 Comm. Port③EPO④External Battery Connector ⑤Socket for connection to AC-power source ⑥Input circuit breaker
⑦Slot for Communications-card option⑧Two Programmable Outlets ⑨Outlets⑩Fan
Ablerex Electronics Co., Ltd.Power Abler & Excelsior
http://www.ablerex.com.tw
Real Panel Explanation (2kVA)
1 USB Comm. Port2 RS-232 Comm. Port3 EPO4 External Battery Connector 5 Socket for connection to AC-power source 6 Input circuit breaker
7 Slot for Communications-card option8 Outlets 9 Two Programmable outlets10 Fan
1
2
3
4
56
7
8910
Ablerex Electronics Co., Ltd.Power Abler & Excelsior
http://www.ablerex.com.tw
Real Panel Explanation (3kVA)
1 USB Comm. Port2 RS-232 Comm. Port3 EPO4 External Battery Connector 5 Socket for connection to AC-power source 6 Input circuit breaker
7 Slot for Communications-card option8 Outlets 9 Two Programmable outlets10 Output Breaker for two Power Programmable
outlets 11 Output circuit breakers12 Fan
1
2
3
4
56
7
89
10 11
12
Ablerex Electronics Co., Ltd.Power Abler & Excelsior
http://www.ablerex.com.twExternal Communication Interface Standard Unit :
RS232 and USB interface
Optional in Slot :
1. WEB/SNMP Card
2. True Relay Contact Card
3. RS485 Card
Ablerex Electronics Co., Ltd.Power Abler & Excelsior
http://www.ablerex.com.tw
Communication Software
Emily
UPSilon 2000
Ablerex Electronics Co., Ltd.Power Abler & Excelsior
http://www.ablerex.com.tw
Emergency Power Off (EPO)
Emergency shutdown control through the EPO
Ablerex Electronics Co., Ltd.Power Abler & Excelsior
http://www.ablerex.com.tw
Hot-Swappable Battery
Removable Battery BankBattery Replacement from Front Panel Without Hazard Risk to
Users
1kVA > 7 min.
2kVA > 7 min
3kVA > 5 min.
Backup Time (Full Load):
Ablerex Electronics Co., Ltd.Power Abler & Excelsior
http://www.ablerex.com.tw
Large Built-in Charger
Fastest Charging Internal Battery to 90% in 3 hours. 1.8A~2.7A Charger Built-in for Immediate Run Time Expansion.
Ablerex Electronics Co., Ltd.Power Abler & Excelsior
http://www.ablerex.com.tw
Solutions for Long RuntimeIncreased Runtime for Critical Applications Extended Runtime Capabilities with Multiple External Battery Bank
(Optional)
UPS 1KVA 2KVA/3KVA
Battery Bank SN
BBC0007 BBC0007 BBC12K0009
Nominal System Voltage
36VDC 72VDC
Dimensions W x D x H, mm
Unit 440 x 650 x 88
Shipping 560 x 833 x 228
Weight, kg
Unit 38 38 44.6
Shipping 46 46 52.6
Ablerex Electronics Co., Ltd.Power Abler & Excelsior
http://www.ablerex.com.tw
LOAD MP-RT 1000 1 x EXB 2 x EXB
140w 01:06:06 05:51:10 10:32:06
280w 00:27:45 03:01:28 05:26:39
420w 00:14:24 02:02:21 03:40:13
560w 00:10:19 01:32:17 02:46:06
700w 00:07:09 01:09:43 02:13:20
MSRT-Pro Series Backup Time (1K)
1
10
100
1000
0 200 400 600 800
Load (VA)Ba
ckup
Tim
e (Mi
nute
)
MSRT-1000
1 x EXB
2 x EXB
Battery Run Times
Ablerex Electronics Co., Ltd.Power Abler & Excelsior
http://www.ablerex.com.tw
LOAD MP-RT 2000 1 x EXB 2 x EXB
280w 01:06:06 03:30:42 05:51:10
560w 00:27:45 01:48:53 03:01:28
840w 00:14:24 01:09:05 02:02:21
1120w 00:10:19 00:52:07 01:32:17
1400w 00:07:09 00:33:59 01:09:43
MSRT-Pro Series Backup Time (2K)
1
10
100
1000
200 400 600 800 1000 1200 1400 1600
Load (VA)Ba
ckup
Tim
e (Mi
nute
) MSRT-2000
1 x EXB
2 x EXB
Battery Run Times
Ablerex Electronics Co., Ltd.Power Abler & Excelsior
http://www.ablerex.com.tw
MSRT-Pro Series Backup Time (3K)
1
10
100
1000
0 500 1000 1500 2000 2500
Load (VA)Ba
ckup
Tim
e (Mi
nute
) MSRT-3000
1 x EXB
2 x EXB
LOAD MP-RT 3000 1 x EXB 2 x EXB
420w 00:59:11 03:08:39 05:14:25
840w 00:19:03 01:37:09 02:41:35
1260w 00:12:11 01:01:34 01:49:02
1680w 00:08:25 00:46:25 01:17:21
2100w 00:05:26 00:30:15 01:02:04
Battery Run Times
Ablerex Electronics Co., Ltd.Power Abler & Excelsior
http://www.ablerex.com.tw
3 4 25
1 1
1.Screw Cover To replace batteries, please remove the screw covers and the screws inside the covers.
2. EXT.BAT. +/- To the DC terminal of the 2nd(or next) battery bank connected.
3. UPS BAT. +/- To the UPS DC terminal or the next battery bank.
4. DC Breaker
1. Over-current Protection Breaker2. To easy swappable battery, please put the position of the breaker in “O” position. In case there is 2nd(or next) battery bank connected with the battery bank, the DC voltage from the UPS Bat.+/- will flow through without any interruption to the 2nd Battery Bank.
5. AC Inlet for Charger
AC Inlet for Charger. Optional.
Front and Rear Panel Descriptions
Ablerex Electronics Co., Ltd.Power Abler & Excelsior
http://www.ablerex.com.tw
Optional External Bypass Switch External Bypass SwitchEasy Installation with ready-to-go inlets & outlets. Break before Make Switch(3ms)
Ablerex Electronics Co., Ltd.Power Abler & Excelsior
http://www.ablerex.com.tw
Operating Illustration
Ablerex Electronics Co., Ltd.Power Abler & Excelsior
http://www.ablerex.com.tw
Programmable Receptacles
Current MonitoringOutput Receptacles Enable/DisableAblerex own-developed software for Windows Platform
Increased runtime for critical applications:Load shedding with programmable outlets.
Ablerex Electronics Co., Ltd.Power Abler & Excelsior
http://www.ablerex.com.twSetting Software
User Personalization
Output Voltage Configurations
UPS Modes
Output Voltage Fine Tuning
Bypass Voltage Tolerances
Synchronized Frequency Window
Company Name
UPS Model
UPS Capacity
Calibration Setting (Manufacturing setting only)
Ablerex Electronics Co., Ltd.Power Abler & Excelsior
http://www.ablerex.com.tw
Outlet Turn On After Turn on UPS
Outlet Turn Off After AC Failure
Outlet Turn On After AC Recovered
Outlet Turn Off When Battery Lower
than
Outlet Turn Off When Overload
Programmable Outlet On/Off
Manual Control Switch
Programmable Outlet Setting
Ablerex Electronics Co., Ltd.Power Abler & Excelsior
http://www.ablerex.com.tw
Internal structure
(2/3kVA)
Internal structure(1kVA)
1/1.5KVA 2KVA 3KVA
Driver Board(1)110V
MPAD2XX MPCD2XX220V
Driver Board(2)110V
N/AMPCD1XX
220V MPCD3XX
Control Board110V
MPAI0XX220V
EMI filter Board110V
MPAF2XX MPCF2XX220V
LED Display 110V MPAM2XX
[B1]加入
Ablerex Electronics Co., Ltd.Power Abler & Excelsior
http://www.ablerex.com.tw
Charger circuit
PFC CHOCK
INVERTER CHOCK
INV
ER
TER
IG
BT
Bo
ost
MO
SFE
T
Wor
k p
ow
er c
ircu
it
PFC
MO
SFE
TP
FC
R
EC
TIFI
ER
Boo
st
Tran
sfor
mer
PF
C C
T
InputRelay
-BUS
+BUS
INV
ER
TER
C
T
Load
CT
Output Relay
External Battery Fuse
PFC Fuse
MPAD2XX PCB (1/1.5KVA)
Ablerex Electronics Co., Ltd.Power Abler & Excelsior
http://www.ablerex.com.tw
Inverter IGBT
Inverter choke
Inverter choke
Charger circuit
Work power
Feedback Relay
MPCD2XX PCB(2K/3KVA)
Ablerex Electronics Co., Ltd.Power Abler & Excelsior
http://www.ablerex.com.tw
Inv
ert
er
ch
ok
e
Inv
ert
er
ch
ok
e
In
ve
rte
r c
ho
ke
Inv
ert
er
ch
ok
e
Inv
ert
er
ch
ok
e
Inv
ert
er
ch
ok
e
Boost MOSFET
PFC IGBT PFC choke
PFC choke
Boost Transformer
+BUS
+BUS
MPCD3XX PCB (2/3KVA -220V System)
Ablerex Electronics Co., Ltd.Power Abler & Excelsior
http://www.ablerex.com.twINPUT
Model MP-RT 1000 MP-RT 1500 MP-RT 2000 MP-RT 3000
Voltage Window120/140/160~288Vac
60/70/80~144Vac
Frequency 45~65Hz
Phase/Wire Single, Line + Neutral + Ground
Power Factor Up to 0.99 at 100% Linear Load
OUTPUT
Rated Voltage 200/208/220/230/240Vac Selectable100/110/115/120/127Vac Selectable
Voltage Regulation ≦ +/-1% until low battery warning
Capacity (VA/W) 1000/700 1500/1050 2000/1400 3000/2100
Rated Power Factor 0.7/0.8* Lagging
Wave Form ≦3% THD at linear load; 7% at Non-linear load≦
Frequency [Synchronized Range] 1Hz or 3Hz
Transfer Time 0ms
Crest Factor 3:1
Efficiency (AC to AC, Normal) Up to 85% Up to 88%
Efficiency (DC to AC) Up to 83% Up to 85%
DC Start Yes
Product Specifications
Ablerex Electronics Co., Ltd.Power Abler & Excelsior
http://www.ablerex.com.tw
BATTERY
Model MP-RT 1000 MP-RT 1500 MP-RT 2000 MP-RT 3000
Backup Time >7 min. >5 min. >7 min. >5 min.
Type Sealed Lead Acid Maintenance Free
Quantity 3pcs 6pcs
Capacity 7.2AH 9AH 7.2AH 9AH
Voltage 36Vdc 72Vdc
Recharge Time 3 hours to 90%
Charger Current 1.8A 2.1A 2.7A
Ablerex Electronics Co., Ltd.Power Abler & Excelsior
http://www.ablerex.com.tw
PHYSICAL
Model MP1000X/MP1000C MP2000X/MP2000C MP3000X/MP3000C
Dimensions ( W x D x H ) mm/inch 440 x132 x405/
17.3x5.2x16440 x176 x520/17.3x7.0x20.5
Input Connection(230Vac Only)
IEC IEC320-C14 IEC320-C20
Output Connection(230Vac Only)
IEC 6 x IEC320-C13 4 x IEC320-C131 x IEC320-C19
Weight (Kgs/lbs)
w/o transformer w/batteries 15.5/34.2 32.0/70.5 33.0/72.7
w/o transformer w/200W 7.9/17.4 16.7/36.8 17.7/39.0
w/transformer w/batteries 22.0/48.6 42.0/92.6 46.0/101.4
w/transformer w/200W 14.4/31.8 26.7/58.9 30.7/67.7
Ablerex Electronics Co., Ltd.Power Abler & Excelsior
http://www.ablerex.com.tw
Q & AQ & A