The range of ABB breakers and switches ranks amongst the most extensive on the market with a full range of innovative solutions for various applications, helping to optimise resources, reduce energy costs, boost productivity. - Moulded case circuit breakers - Air circuit breakers - HRC fuse & Fuse base - Switch disconnector fuse ABB Low voltage Breakers & Switches | ABB’s comprehensive range of breakers and switches 7 - Switch disconnectors - Changeover switches - Manual & Motorized - Auto transfer switches - Cam switches - Cable distribution cabinet - Kabeldon - Fuse gear - Easyline and Inline (Fuse switch disconnector) - Switche disconnector for DC application - Photovoltaic MCCBs ABB’s comprehensive range of breakers and switches 1
72
Embed
ABB’s comprehensive range of breakers and switchesenarayan.com/wp-content/uploads/2016/03/ABB-CATALOGUE.pdf · The range of ABB breakers and switches ... Tmax power distribution
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
The range of ABB breakers and switches ranks amongst the
most extensive on the market with a full range of innovative
solutions for various applications, helping to optimise
resources, reduce energy costs, boost productivity.
- Moulded case circuit breakers
- Air circuit breakers
- HRC fuse & Fuse base
- Switch disconnector fuse
ABB Low voltage Breakers & Switches | ABB’s comprehensive range of breakers and switches 7
- Switch disconnectors
- Changeover switches - Manual & Motorized
- Auto transfer switches
- Cam switches
- Cable distribution cabinet - Kabeldon
- Fuse gear - Easyline and Inline (Fuse switch disconnector)
- Switche disconnector for DC application
- Photovoltaic MCCBs
ABB’s comprehensive range of breakers and switches
1
ArTu. Born certified.
Fully checked and certified (IEC 60439-1 and IEC 61439-1
and 2 Standard) by an external independent organisation
(AcaeLovag), the ArTu switchgear is a synonym of safety and
quality. The certification is the fruit of severe tests carried
out on the whole configuration, consisting of metalwork
structures, circuit-breakers and busbar system.
The ArTu K series switchgear is ideal for primary distribution
switchgear (PowerCenter type) upto 6300A with air and
moulded-case circuit-breakers and any internal segregations
up to Form 4, and for floor-mounted secondary distribution
switchgear with moulded-case and modular circuit-breakers.
The switchgear have been tested for Internal Arc and
Seismic.
8 ArTu. Born certified. | ABB Low voltage Breakers & Switches
1
Emax - Low voltage air circuit breakers
Faults: no problem Extremely simple ModularityCompletely new protection
releases
– CT (Rogowski coil) range of 400 - 6300A (E1,E2,E3,E4 and
E6) with breaking capacity range of 42-150KA
– Configured breakers are now available in E1, E2 and E3
frames
– SACE Emax circuit-breakers and their accessories conform
to the international IEC 60947, EN 60947 CEI EN 60947
and IEC 61000 standards and comply with following EC
directives “Low Voltage Directive” (LVD)
no 73/23 EEC
– “Electromagnetic Compatibility Directive” (EMC) nr. 89/336
EEC
– Complete range of common accessories
– Double insulation
– Same height and depth for the whole range
– Protection releases provide complete set of standard
and grid feeding. ABB has one of the world’s widest product
ranges of measuring and monitoring relays. The CM range is a key
product line of the EPR range.
Electronic products and relays
The product range
3 Power supplies, CP range
Modern power supply units are a vital component in most areas of
energy management and automation technology.
As your global partner in this area, ABB pays close attention to
corresponding requirements. Innovation is the key to the
substantial enlargement of our power supply product range. ABB
offers four different product lines for single and three-phase sup-
plies, output voltages 5/12/24, and 48 VDC in plastic and metal
enclosure, as well as various accessories.
4 Signal converters, CC range and ILPH
The ABB serial data converters allow communication to be
established between units with different communication
standards. In order to assure process continuity, existing systems
must be updated consistently or connected to new devices. Serial
data enables communication to be established if the communi-
cation standard of the existing system and the connected device
vary. As well as converting signals, analog signal converters and
serial data converters can amplify, filter or separate signals.
5 Interface relays and optocouplers, CR range and R500 / 600
Interface relays and optocouplers are widely used in various
industrial applications. As an interface, they link the controller, e.g.
PLC (programmable logic controller), PC or field bus systems to
the sensor/actuator level. Here, they have various functions:
switching AC or DC loads with different resistive, inductive and
capacitive parts, switching voltages from a few mV up to 250
V, switching currents from a few mA up to 16 A, amplification of
weak control signals, electrical isolation of control and load cir-
cuits, and signal multiplying.
6 Logic relays, CL range
CL range logic relays are suitable for small and medium-sized
control tasks and can substitute logic wiring quickly and easily.
Three different ranges are available: stand alone, expandable and
the display systems.
Time relays, CT range
Three ranges of electronic timers provide timing functions for all
applications: the CT-D range with a width of just 17.5 mm; the
CT-E range, the ideal solution for serial applications; and the CT-S
range that has two different types of connection terminals and is
ideally suited for universal use. The CT range has a wide varity of
timing functions (from ON or OFF delay to star-delta changeover).
The time relays are available with output relays, solid-state outputs
and precise direct time adjustment.
1
2
ABB Low voltage Control Products | Electronic products and relays 97
2
ABB Low voltage Control Products | Pilot Devices 105
Pilot Devices Offering
ABB Pilot Devices offers both a Modular and Compact Range of
Pushbuttons. Both feature the same front-of-panel design and
appear consistent when combined.
Modular Range, features a wide range of operators that can be
-
Compact Range features an all-in-one construction and rugged
Pilot Devices
Standard and approvals
IEC / EN 60947-1 Low-voltage switchgear and controlgear - Part 1: General rules
IEC / EN 60947-5-1 Low-voltage switchgear and controlgear - Part 5-1: Control circuit devices and switching elements - Electro-mechanical control circuit devices
IEC / EN 60947-5-5 Low-voltage switchgear and controlgear - Part 5-5: Control circuit devices and switching elements - Electri-
function
IEC / EN 60073
IEC / EN 60529
EN 50013 Low-voltage switchgear and controlgear for industrial -
ticular control switches
DIN 40050-9protection against foreign objects; water and con-
UL 508
CSA C22.2 No 14
Environmental data
Degrees of protection
Pilot device: IEC/EN DIN UL/CSA
Pushbutton IP66, IP67 and IP69K
Selector switch IP66, IP67 and IP69K
Pilot light IP66, IP67 and IP69K
IP66, IP67 and IP69K
IP20
Temperature
Ambient temperature during operation -25 to +70 °C
Storage temperature -40 to +85 °C
Technical data
Cable connections
Operator Cable terminal
PushbuttonSelector switch
Plus-minus Pozidriv No. 2Connectable area:
2
2
Tightening torque
Operators, M22
Pushbutton and selec-tor switch
Cable terminals M3, 0.8 Nm
Pilot light Cable terminals M3.5, 0.9 Nm
Cable terminals M3, 0.8 Nm
Electrical data
Electrical ratings
Contacts
Ratings as per IEC 60947-5-1
Rated insulation volage, Ui 300 V
Rated thermal current, Ith 5 A
Rated operational current, Ieat: 240 V 1 A
Rated operational current, Ie at: 24 Vat: 125 V
0.3 A0.2 A
Ratings as per UL, CSA, NEMA C300 AC
R300 DC
Rated insulation voltage 250 V 250 V
Rated thermal current 2.5 A 1 A
Rated operational current at: 120 Vat: 125 Vat: 240 Vat: 250 V
1.5 A
0.75 A0.22 A
0.11 A
Short circuit protection
gG 10A
Make-and-break contacts
Pushbutton
LED’s (for both compact and modular)
Service life for LED’s means number of service hours until the brightness has been reduced down 50 %. Service life 50 000 h
Over voltage on LED’s 10 % overvolatge is acceptable without affecting the service life
Gloaming light All integrated LEDs have a function built
Mechanical data
Mechanical life
Pushbuttons, selector switches 500 000 operations
50 000 operations
NC
NO
= Closed contact
-1 -2
-3 -4
NC
NO
-1 -2
-3 -4
= Closed contact
Technical data compact range
Modular Range Modular Range
The System pro M compact® – DIN Rail Products
System Pro M
System Pro M is a modular system developed by ABB which,
is capable of meeting the requirements of the most modern
and up-to-date installations for low voltage applications.
MCBs
Miniature circuit-breakers.
RCDs
− Residual current circuit-breakers (RCCBs);
− RCD-blocks;
− Residual current circuit-breakers with overcurrent protec-
tion (RCBOs);
− Residual current relays (modular and front panel) with
external toroid.
Auxiliary elements
A whole range of accessories and auxiliary elements.
SPDs
Surge protective devices.
Protection devices
In addition to MCBs and RCDs, ABB supplies other modular
devices for protection such as fuse holders, fuses, switch
disconnectors, insulation monitoring devices etc.
Command devices
This category includes devices that are operated manually
to command the electric system: contactors, latching relays,
switch-isolators, switches, pushbuttons etc. Typically they
are installed to control lights from severeal points of the
same circuit or to pilot user devices with a high number of
operations.
Load management devices
Overload relays, load management switches, anti black-out
lamps, time switches and the other modular devices in this
category react automatically to variations of parameters and
other events in the system to allow for plant optimisation.
Measurement devices
The range of devices in this category is very wide, including
a great number of auxiliary components and accessories
that make installation in switchboards and consumer units
practical and economic.
Other devices
The System pro M compact® range also includes bells,
transformers, modular sockets etc.
Various accessories
3
ABB Low voltage Enclosures & DIN Rail Products | The System pro M compact® – DIN Rail Products 121
3
Wiring diagram and basic technical specification
printed on the front of the MCB. Save your time -
all important data available right away.
Easy product coding - easy identification
- easy life. Basic technical information
already integrated into the name.
25 mm² cage terminals, a well proven
and reliable technology.
Don’t loose what’s
important for you -
captive screws.
IP20 - finger safety.
Scratch and solvent resistant marking
due to laser printing. Easy identification
of the products in case of maintenance
or replacements.
Laser printed EAN code. Easy integration
into merchandise management systems
and quick identification of devices.
Miniature circuit-breaker (MCB)
SH200M Series
Electrical Data SH200 M
Standards IS/IEC 60898-1
Poles 1P, 2P, 3P, 4P, 1P +N, 3P +N
Tripping Characteristics B, C, D
Rated Curent 0.5A - 63 A
Rated Voltage
1P : 230/400/415 V AC
1P + N : 230 V AC
2…4P : 400/415 V AC
3P + N : 400/415 V AC
Insulation Voltage250 V AC (Phase to Ground)
440 V AC (Phase to Phase)
Max Operating Voltage1P: 253 V AC
2…4P : 440 V AC
Min Operating Voltage 12 V AC
Rated Frequency 50/60 Hz
Rated Short Circuit Capacity 10kA
Energy Limiting Class 3
Over Voltage Category (B,C upto 40A) III
Pollution Degree 2
Rated Impulse withstand Voltage4kV (Test Voltage 6.2kV at Sea Level,
5kV at 2,000 m)
Dielectric Test Voltage 2kV (50/60 Hz, 1 min)
Accessories mountable No
Technical Features
122 Miniature circuit-breaker (MCB) SH200M Series | ABB Low voltage Enclosures & DIN Rail Products
3Safe your time – all important data available
right away.
Easy product name, easy
identification, easy life.
Twin terminal for separate feeding
of busbar and conductor
Captive screws: don’t loose what’s
important for you.
IP20 - finger safety.
Easy identification of the
product and highly resistant
laser marking.
Quick identification thanks to laser printed
EAN marking.
Whatever your application need is –
applicable with a wide range of accessories.
Real contact position indication
Miniature circuit-breaker (MCB)
S200M Series
Electrical Data S200 M
Standards IEC 60947-2, IS/IEC-60898-1
Poles 1P, 2P, 3P, 4P, 1P +N, 3P +N
Tripping Characteristics B, C, D
Rated Curent 0.5A - 63 A
Rated Voltage
1P : 230 / 400 V AC
1P + N : 230 V AC
2…4P : 400 V AC
3P + N : 400 V AC
1P : 60 V DC
2P : 120 V DC
Insulation Voltage250 V AC (Phase to Ground)
500 V AC (Phase to Phase)
Max Operating Voltage1P: 253 V AC
2…4P : 440 V AC
Min Operating Voltage 12 V AC
Rated Frequency 50/60 Hz
Rated Short Circuit Capacity 10kA
Energy Limiting Class (B, C upto 40 A) 3
Over Voltage Category III
Pollution Degree 2
Rated Impulse withstand Voltage4kV (Test Voltage 6.2kV at Sea Level,
CE marking of CompactHome devices warrantsfree circulation and sale inEuropean Union. It isrealized on supplier’sresponsibility, in additionto this marks andapprovals, guaranteefunctioning, compatibilityand safety conforming tonational and internationalStandards.ABB Compact HomeRCDs also obtained thefollowing national andinternational approvals:
Thanks to these approvals,the devices can be usedwithout restriction as devicesfor the world market.
AENOR- ES APCER- PT
GOST- RU
SIRIM- MY
TICKMARK- AULCIE- FR
CCC- CN SABS - ZA PSB - SG
Compact Home
ABB
1
1/4
1
Introduction
Family: F 200 = RCCBs
H for HOME
N° of poles: 2; 4
Current:25A; 40A; 63A
Sensitivity:0,03A, 0,1A …
Indication ofdevice’s ratedvoltage
Indication of shortcircuit coordinationperformance:Im=Idm=1000AInc=6000kA with agL 63A fuse
Wiring diagrams toprevent from awrong connection
Failsafe bi-directional cylinder-liftterminal at top and bottom
Indication of the marks andapprovals the devices have beenobtained
Test button to be tested monthly
Type: AC, A
Black toggle to identify CompactHome range
Laserprint on side of mounting
instruction and of the symbol which means that the circuit-breaker must be thrown awayseparately
ABB identity number for a quicklyidentification of the product
for more information about this products, see the technical catalogue
Compact Home
ABB
1
1/5
Introduction
Cage terminals up and bottom
Family: S 200 = MCBs
H for HOME
N° of poles:1; 1+N; 2; 3; 3+N; 4
Breakingcapacities:T=3kA, L=4.5kA,no-one=6kA
Characteristic: B, C
Rated current:6A; 10A; … 63A
Indication of MCB ratevoltage
Indication of MCBbreaking capacity andlimitation class
Wiring diagrams to prevent wrongconnection on all pole versions
for more information about this products, see the technical catalogue
Compact Home
2
Application sheets
2/1ABB
Index
Basic solution for consumer units installed in a little flat (<35 m2) ..........................................2/2
Advanced solution for consumer units installed in a little flat (<35 m2) ...................................2/3
Basic solution for consumer units installed in a big flat (between 35 and 100 m2) .................2/4
Advanced solution for consumer units installed in a big
flat (between 35 and 100 m2) ..................................................................................................2/6
Basic solution for consumer units installed in an indipendent
in an indipendent house/villa (>100 m2) ................................................................................2/10
Notes for use, special features .............................................................................................2/12
Technical features of MCBs SH 200 series ...........................................................................2/14
2
2/2 ABB
Compact Home
RCCB 25A30mA
1PC 10
1PC 16
Application sheetsBasic solution for consumer units installed ina little flat (<35 m2)
The simplest possible solution:1 RCCB I n=30mA: protection alsoagainst direct contacts2 MCBs: one with In=10A to protectlights circuit and one with In=16A toprotect sockets circuit
2
2/3ABB
Compact Home Application sheetsAdvanced solution for consumer units installed ina little flat (<35 m2)
OVR
RCCB 25A30mA
TSM 2PC 20
1PC 16
RCBO C16 30mA
1PC 16
1PC 16
1PC 10
1 RCCB I n=30mA: protection alsoagainst direct contacts3 MCBs with In=16A protect sockets inthe living room and in the kitchen (e.g.for the oven)1 MCB with In=10A protects lightscircuit of the whole house1 modular bell with built-in voltagetransformer for doorbell’s acousticsignal
In this consumer unit it has beenintroduced a third level of protectionwith an OVR (upstream protectedby a MCB) to protect installation andappliances against transientovervoltage peaks.Bathroom, due to the damp whichcharacterizes it, is considered acritical area: in the suggestedsolution, the dedicated protection of1 RCBO (with In=16A andI n=30mA) improves service’scontinuity and protects bathroom’ssockets against earth-fault current,overloads and short-circuits.
2
2/4 ABB
Compact Home Application sheetsBasic solution for consumer units installed in a big flat(between 35 and 100 m2)
1 MCB used as main switch of theconsumer unit3 RCCBs: one with In=40A protectssockets circuit of the living room,kitchen and laundry-room and twowith In=25A protect respectivelysockets circuit of the bedrooms andbathroom and lights circuit of thewhole house2 MCBs In=10A protect lights circuitsof bedrooms and bathroom separatelyfrom lights circuits of the rest of thehouse6 MCBs In=16A (3 per RCCB) protectsockets1 OVR protects against transientovervoltage peaks
In this consumer unit has beenintroduced some typical function ina modular shape: a voltagetransformer (TS) supplies a bell(SM) for doorbell’s acoustic signaland a buzzer (RM) for emergencyacoustic signal in the bathroom.
2P63A
RCCB 25A30mA
RCCB 40A30mA
RCCB 25A30mA
1PC 10
1PC 10
1PC 16
1PC 16
2PC 20A
1PC 16
TS
1PC 16
1PC 16
1PC 16
OVR RM
SM
2
2/5ABB
Compact Home Application sheetsBasic solution for consumer units installed in a big flat(between 35 and 100 m2)
2
2/6 ABB
Compact Home Application sheetsAdvanced solution for consumer units installed in a big flat(between 35 and 100 m2)
1 MCB used as main switch of theconsumer unit2 RCCBs: one with In=40A protectssockets circuit and electric householdappliances in the kitchen and onewith In=25A protects remainingsockets and all the other devices2 RCBOs protect separately socketscircuits of the bathroom and of thelaundry10 MCBs In=16A or In=10A protectsockets and lights circuits of thehouse1 OVR protects against transientovervoltage peaks1 modular bell with built-in voltagetransformer for doorbell’s acousticsignal1 LSS1/2 for load management
In this consumer unit a DTS-TWS(time switch + twilight switch)allows the time programming of theexternal and entrance lights inrelation to the environmental lightlevel. One E 259 (installation relay),equipped with contact positionindicator, allows the manual controlof the boiler in the bathroom.
RCCB 40A30mA
1PB 10
1PB 10
1PB 10
LSS 1/2
1PB 16
1PB 16
1PB 16
3PB 40
1PB 16
1PB 16
3 PB 16
1PC 16
2PC 20A
TS TM 1PC 16
1PB 16
DTS - TWS
OVR SMRME 259
3P 40A
RCBO B16A 30mA
RCBO B16A 30mA
RCCB 25A30mA
2
2/7ABB
Compact Home Application sheetsAdvanced solution for consumer units installed in a big flat(between 35 and 100 m2)
2
2/8 ABB
Compact Home Application sheetsBasic solution for consumer units installed in an indipendenthouse/villa (>100 m2)
1PC 16
1PC 16
DTS - TWSTS
SM
LSS 1/2
RCBO C 2530 mA
E 200i
RCBO C 1630 mA
RM
1PC 16
1PC 16
1PC 16
1PC 16
E 259
1PC 10
1PC 10
RCCB 40A30mA
4P C 63A
1PC 16
RCCB 4P40A 30mA
RCCB 4P40A 30mA
1PC 16
1PC 16
1PC 16
1PC 10
3 PC 20
OVR
1 MCB used as main switch of theconsumer unit3 RCCBs with In=40A protect socketsand lights circuits of the house2 RCBOs protect separately socketsin the garage and in the swimmingpool13 MCBs In=16A or In=10A protectsockets and lights circuits of thehouse1 OVR protects against transientovervoltage peaks1 modular bell and 1 buzzer foracoustic signals1 DTS-TWS for lights timeprogramming1 E 259 for manual controlling of theboiler
In this consumer unit the E 200i isused as main disconnecting meansof the external circuit (which, forexample, can be used for thesockets or the pump of theswimming pool, always turned offduring the winter). The LSS1/2 is aload shedding switch: it avoids thetripping of the main circuit-breakerthrough switching-off in sequence ofmaximum two not primary loadswhen the preset threshold isexceeded (it could be useful to setrefrigerator as primary load towarrant service’s continuity).
2
2/9ABB
Compact Home Application sheetsBasic solution for consumer units installed in an indipendenthouse/villa (>100 m2)
2
2/10 ABB
Compact Home Application sheetsAdvanced solution for consumer units installed in anindipendent house/villa (>100 m2)
1 MCB used as main switch of theconsumer unit3 RCCBs protect sockets and lightscircuits of the house6 RCBOs protect separately thecritical lines of the house13 MCBs In=16A or In=10A protectsockets and lights circuits of thewhole house1 OVR protects against transientovervoltage peaks1 modular bell and 1 buzzer foracoustic signals1 LSS1/2 for the load management ofthe electric household appliances inthe kitchen1 E 200i separately controls theexternal sockets1 DTS-TWS for lights timeprogramming1 E 259 for manual controlling of theboiler
In the living room, the E 255(latching relay) allows the lightsequential control through a singlepushbutton circuit. The E 232(staircase timer) permits thelighting time delay in the garage,so it is not possible to forget lightturned on.
1PC 10
1PC 10
E 255
E 232 3 PC 20
1PC 16
TS TR 1PC 16
DTS - TWS
SMRM
LSS 1/2
RCBO C 1610mA
RCBO C 1610mA
RCBO C 4030mA
RCBO C 1630mA
RCBO C 2530 mA
E 200i
RCBO C 1630 mA
1PC 16
1PC 16
1PC 16
1PC 16
1PC 16
1PC 16
E 259
1PC 10
1PC 10
RCCB 40A30mA
4P C 63A
1PC 16
RCCB 4P40A 30mA
RCCB 4P40A 30mA
OVR
2
2/11ABB
Compact Home Application sheetsAdvanced solution for consumer units installed in anindipendent house/villa (>100 m2)
The MCB’s Compact Home
are equiped with 25 mm2
cage terminals, a well proven
and reliable technology.
The terminals accept not only
single wires, but as well several
conductors of the same size
e.g. 6 x 1.5 mm2 or even
conductors with different
cross sections e.g. 1 x 6 mm2
and 1 x 2.5mm2.
The cross wiring can easily
be done by inserting the
Compact Home busbars
and then the incoming
wires into one of the
MCB’s terminals.
The terminals accept Compact
Home busbars and conductors up
to 16 mm2 together.
Easy to handle –
When Compact Home
RCCB’s or E 200- isolators
are used as main incomers
the Compact Home busbars
perfectly fit into all possible
combinations.
Compatibility with
pro M compact is given in all
kind of variations like:
Insertion of 1 pro M compact
MCB (e.g. K-characteristic)
into an Installation with
Compact Home components
and Compact Home busbars.
Also the combination of
1 Compact Home MCB with
pro M compact components
and pro M compact busbars
is not a problem.
– Compact Home
2
2/14 ABB
Compact Home Technical featuresof MCBs SH 200 series
SH 200
SH 200 T SH 200 L SH 200
Standards IEC/EN 60898Rated current in A 6 - 40Poles 1, 2, 3, 4, 1+NA, 3+NARated Voltage Ue IEC 1P, 1P+N V 230
IEC 2P, 3P, 3P+N, 4P V 230/400Insulation voltage Ui V 250Max. operating voltage Ub max. IEC AC V 254/440Min. operating voltage Ub min. V 12 V AC - 12 V DCRated frequency Hz 50…60Rated breaking capacity acc. to IEC/EN 60898 ultimate Icn A 3000 4500 6000Rated impulse withstand voltage (1.2/50) Uimp KV 4 (test voltage 6,2. at sea level
5 at 2000 m)Dielectric strength at power freq. for 1 min. KV 2,5Overvoltage category IIIPollution degree 2Thermomagnetic release B: 3 In Im 5 In • • •characterisitic C: 5 In Im 10 In • • •Toggle black sealable in ON-OFF positionElectrical life 10000Mechanical life/operations 20000Protections degree/operations housing IP4X
terminals IP2X
Mechanical shock resistance 30 g - 2 shocks - duration 11 msResistance to vibrations acc. to IEC/EN 60060-2--6 5 g - 20 cycles at frequency
5…150…5 Hz with 0,8 x InTropicalization humid heat °C/RH 28 cycles with 55/95…100acc. to IEC/EN 60068-2 constant climatic conditions °C/RH 23/28 - 40/93 - 55/20
variable climatic conditions °C/RH 25/95 - 40/95Reference temperature for setting of thermal element °C 30Ambient temperature (with daily averages +35°C) IEC °C -25…+55Storage temperature °C -40…+70Terminal type cage terminalTerminal size top/bottom for cable IEC mm2 25/25
UL/CSA AWG 18-4Tightening torque IEC N*m 2.5
UL/CSA in-lbs. 22Tool Nr. 2 PozidrivMounting on DIN rail EN 60715 (35 mm) by
means of fast clip deviceMounting position optionalConnection from top and bottomPole dimensions (H x D x W) mm 85 x 69 x 17.5Pole weight g 125
Electricalfeatures
Mechanicalfeatures
Installation
Dimensionsand weigh
Tripping diagrams
Tripping characterisitc Bacc. to DIN VDE 0641 part 11In = 6 … 40 ASH 200 T / SH 200 L / SH 200
Tripping characterisitc Cacc. to DIN VDE 0641 part 11In = 0.5 … 40 ASH 200 T / SH 200 L / SH 200
2CD
C02
2188
F020
5
2CD
C02
2190
F020
5
2
2/15ABB
� The tripping for the electromagnetic trip are valid for AC 50… 60 Hz.For other frequencies see table below.
� From warm operating condition (After I1 > 1 h resp. 2 h)
Thermal trips � Electromagnetic trips �
acc. to Tripping Test currents: Tripping- Test currents: Tripping-characterisitic Low test High test time hold current trip time
current current surges of at least atI1 I2
1.13 · In > 1 h 3 · In 0.1 s … 45 s 32 A / 0.1 s … 90 s 32 A1.45 · In < 1 h 5 · In < 0,1 s
1.13 · In > 1 h 5 · In 0.1 s … 45 s 32 A / 0.1 s … 30 s 32 A1.45 · In < 1 h 10 · In < 0,1 s
Compact Home
Internal resistances and power losses of the Miniature Circuit-Breakers
Internal resistances per pole in mPower losses per pole in W
Type Rated Range SH 200 T Range SH 200 L Range SH 200current B, C B, C B, CA m W m W m W
The stated tripping values of the electromagnetic trips are valid for afrequency of 50… 60 Hz. In case of frequencies deviating from 50… 60Hz as well as direct current the tripping values are changed by thefactor mentioned below.
The tripping values of the thermal trips are independent of the frequency
Influence of ambient temperature
The thermal trips are calibrated for an ambient temerpature30 °C for B- and C-characteristic.
In the case of temperatures deviating from these values the trippvalues• are reduced in case of higher temperatures• are increased in case of lower temperatures
The electronic tripping is not dependent on temperature
AC DC100 Hz 200 Hz 400 Hz
Factor approx. 1.1 1.2 1.5 1.5
�
�
IEC/EN 60898
2
2/16 ABB
Load data from diagram Calculation Example
Rated current and characteristics of M.C.B. In / B, C 16 A – BContinuous load R 40 °CNumber of M.C.B.´s / Mounting distance N / X 8 pieces / 0 and 8 mm
Load 1 h 1 a resp. 1 b I = In · K 16 · 1.07 = 17.1 A
Continuous load > 1 h I = 0.9 · In · K 0.9 · 16 · 1,07 = 15.4 A
Continuous load, N M.C.B.´s, Distance 0 2 I = 0.9 · K · KN 0.9 · 16 · 1.07 · 0.77 = 11.9 AContinuous load, N M.C.B.´s, Distance X 3 I = 0.9 · K · KX 0.9 · 16 · 1.07 · 0.98 = 15.1 A
Compact Home
Current-carrying capacity of the MCB´s as a function of the ambient temperature
Mutual thermal influence in the case of simultaneous load
MCB´s mounted in a row side bay side MCB´s mounted with a seperating distance X
SK
008
0 Z
93
SK
007
8 Z
93
Max. operating current depending on the ambient temperature of a circuit-breaker in load circuit of characteristics type B, C and D
B, C Ambient temperature T (°C)In (A) -30 -20 -10 0 10 20 30 40 50 606.0 7.7 7.5 7.2 6.9 6.6 6.3 6.0 5.7 5.3 4.9
SH 200 T /SH 200 L / B/C Max. Back-up protectionSH 200 Rated current fuse Main Circuit Breaker S 700
6/8 63 A 100 A10… 32 100 A 100 A
40 125 A 100 A
Max. Back-up protection
Compact Home
Maximum permissible earth-fault loop impedance Zs at U0 = 230 V ̃ �
to ensure compliance with the operation conditions pursuant to IEC 60364-4.Operating time < 0.4 s; at 400 V ˜ < 0.2 s and at > 400 V ˜ < 0.1 sThe instantaneous release of the MCB ensures an operating time of 0.1 s (TN system).Determined according to DIN VDE 0100-520 sheet 2:2002-11 (source impedance = 300 , c = 0.95 and conductortemperature 70 °C = factor 0.8). The internal resistance of the MCB is already included.
SH 200, SH 200 L, SH 200 T
Rated B Ccurrent In A max. Zs max. Zs
6 7.7 3.8
8 – 2.8
10 4.6 2.2
13 3.5 1.7
16 2.9 1.4
20 2.3 1.2
25 1.8 0.9
32 1.4 0.7
40 1.1 0.6
� U0 = rated voltage against earthed conductor; for U0 = 240 V ̃ is Zs · 1.04; for U0 = 127 V ̃ is Zs · 0.55
Take into account the voltage drop:e.g. in the case of a 1.5 mm2 conductor, protected by a B 16 circuit breaker, the maximum cable length is 82 m.If the voltage is below 3%, this would result in a maximum cable length (2-strand) of 17 m.For more details on this topic, get your own copy of the technical information leaflet “Maximum cable lengths”.
Maximum cable length is the case of different voltages and cross sections on request.
2
2/18 ABB
short circuit discrimination in kA
to main circuit breaker S 700 to fuse gL/gG(DIN VDE 0636; IEC 269/3)
SH 200 T B characteristicFunction: protection and control of the circuits against overloads and short-circuits; protection forpeople and big-length cables in TN and IT systems.
Applications: buildings, both residential and commercial
Standard: IEC/EN 60898
Icn=3kA
No. of rated order details bbn price price w'ght pack.poles current 40 16779 1 piece group 1 pc. unit
① UBmax 125 V ... with 2 poles connected in series
Selection tables SH 200 T-BMCBs SH 200 series T3000
B
3/3ABB
3
Compact Home
With disconnecting neutral NA
No. of rated order details bbn price price w'ght pack.poles current 40 16779 1 piece group 1 pc. unit
In A type code order code EAN kg pc.
1 + NA 6 SH 201 T-B 6 NA 2CDS 231 103 R0065 63209 6 0.25 5
10 SH 201 T-B 10 NA 2CDS 231 103 R0105 63212 6 0.25 5
13 SH 201 T-B 13 NA 2CDS 231 103 R0135 63214 0 0.25 5
16 SH 201 T-B 16 NA 2CDS 231 103 R0165 63216 4 0.25 5
20 SH 201 T-B 20 NA 2CDS 231 103 R0205 63218 8 0.25 5
25 SH 201 T-B 25 NA 2CDS 231 103 R0255 63220 1 0.25 5
32 SH 201 T-B 32 NA 2CDS 231 103 R0325 63222 5 0.25 5
40 SH 201 T-B 40 NA 2CDS 231 103 R0405 63224 9 0.25 5
3 + NA 6 SH 203 T-B 6 NA 2CDS 233 103 R0065 63260 7 0.5 1
10 SH 203 T-B 10 NA 2CDS 233 103 R0105 63263 8 0.5 1
13 SH 203 T-B 13 NA 2CDS 233 103 R0135 63265 2 0.5 1
16 SH 203 T-B 16 NA 2CDS 233 103 R0165 63267 6 0.5 1
20 SH 203 T-B 20 NA 2CDS 233 103 R0205 63269 0 0.5 1
25 SH 203 T-B 25 NA 2CDS 233 103 R0255 63271 3 0.5 1
32 SH 203 T-B 32 NA 2CDS 233 103 R0325 63273 7 0.5 1
40 SH 203 T-B 40 NA 2CDS 233 103 R0405 63275 1 0.5 1
B
UBmax
440 V ~60 V ...
UBmax
440 V ~
Selection tables SH 200 T-BMCBs SH 200 series T3000
3/4 ABB
3
Compact Home
C SH 200 T C characteristicFunction: protection and control of the circuits against overloads and short-circuits; protection forresistive and inductive loads with low inrush current.
Applications: buildings, both residential and commercial
Standard: IEC/EN 60898
Icn=3kA
No. of rated order details bbn price price w'ght pack.poles current 40 16779 1 piece group 1 pc. unit
① UBmax 125 V ... with 2 poles connected in series
Selection tables SH 200 T-CMCBs SH 200 series T3000
3/5ABB
3
Compact Home
With disconnecting neutral NA
No. of rated order details bbn price price w'ght pack.poles current 40 16779 1 piece group 1 pc. unit
In A type code order code EAN kg pc.
1 + NA 6 SH 201 T-C 6 NA 2CDS 231 103 R0064 63208 9 0.25 5
8 SH 201 T-C 8 NA 2CDS 231 103 R0084 63210 2 0.25 5
10 SH 201 T-C 10 NA 2CDS 231 103 R0104 63211 9 0.25 5
13 SH 201 T-C 13 NA 2CDS 231 103 R0134 63213 3 0.25 5
16 SH 201 T-C 16 NA 2CDS 231 103 R0164 63215 7 0.25 5
20 SH 201 T-C 20 NA 2CDS 231 103 R0204 63217 1 0.25 5
25 SH 201 T-C 25 NA 2CDS 231 103 R0254 63219 5 0.25 5
32 SH 201 T-C 32 NA 2CDS 231 103 R0324 63221 8 0.25 5
40 SH 201 T-C 40 NA 2CDS 231 103 R0404 63223 2 0.25 5
3 + NA 6 SH 203 T-C 6 NA 2CDS 233 103 R0064 63259 1 0.5 1
8 SH 203 T-C 8 NA 2CDS 233 103 R0084 63261 4 0.5 1
10 SH 203 T-C 10 NA 2CDS 233 103 R0104 63262 1 0.5 1
13 SH 203 T-C 13 NA 2CDS 233 103 R0134 63264 5 0.5 1
16 SH 203 T-C 16 NA 2CDS 233 103 R0164 63266 9 0.5 1
20 SH 203 T-C 20 NA 2CDS 233 103 R0204 63268 3 0.5 1
25 SH 203 T-C 25 NA 2CDS 233 103 R0254 63270 6 0.5 1
32 SH 203 T-C 32 NA 2CDS 233 103 R0324 63272 0 0.5 1
40 SH 203 T-C 40 NA 2CDS 233 103 R0404 63274 4 0.5 1
C
UBmax
440 V ~60 V ...
UBmax
440 V ~
Selection tables SH 200 T-CMCBs SH 200 series T3000
3/6 ABB
3
Compact Home
BSH 200 L B characteristicFunction: protection and control of the circuits against overloads and short-circuits; protection forpeople and big-length cables in TN and IT systems.
Applications: buildings, both residential and commercial
Standard: IEC/EN 60898
Icn=4.5kA
No. of rated order details bbn price price w'ght pack.poles current 40 16779 1 piece group 1 pc. unit
① UBmax 125 V ... with 2 poles connected in series
Selection tables SH 200 L-BMCBs SH 200 series L4500
3/7ABB
3
Compact Home
With disconnecting neutral NA
No. of rated order details bbn price price w'ght pack.poles current 40 16779 1 piece group 1 pc. unit
In A type code order code EAN kg pc.
1 + NA 6 SH 201 L-B 6 NA 2CDS 241 103 R0065 63311 6 0.25 5
10 SH 201 L-B 10 NA 2CDS 241 103 R0105 63314 7 0.25 5
13 SH 201 L-B 13 NA 2CDS 241 103 R0135 63316 1 0.25 5
16 SH 201 L-B 16 NA 2CDS 241 103 R0165 63318 5 0.25 5
20 SH 201 L-B 20 NA 2CDS 241 103 R0205 63320 8 0.25 5
25 SH 201 L-B 25 NA 2CDS 241 103 R0255 63322 2 0.25 5
32 SH 201 L-B 32 NA 2CDS 241 103 R0325 63324 6 0.25 5
40 SH 201 L-B 40 NA 2CDS 241 103 R0405 63326 0 0.25 5
3 + NA 6 SH 203 L-B 6 NA 2CDS 243 103 R0065 63362 8 0.5 1
10 SH 203 L-B 10 NA 2CDS 243 103 R0105 63365 9 0.5 1
13 SH 203 L-B 13 NA 2CDS 243 103 R0135 63367 3 0.5 1
16 SH 203 L-B 16 NA 2CDS 243 103 R0165 63369 7 0.5 1
20 SH 203 L-B 20 NA 2CDS 243 103 R0205 63371 0 0.5 1
25 SH 203 L-B 25 NA 2CDS 243 103 R0255 63373 4 0.5 1
32 SH 203 L-B 32 NA 2CDS 243 103 R0325 63375 8 0.5 1
40 SH 203 L-B 40 NA 2CDS 243 103 R0405 63377 2 0.5 1
B
UBmax
440 V ~60 V ...
UBmax
440 V ~
Selection tables SH 200 L-BMCBs SH 200 series L4500
3/8 ABB
3
Compact Home
C SH 200 L C characteristicFunction: protection and control of the circuits against overloads and short-circuits; protection forresistive and inductive loads with low inrush current.
Applications: buildings, both residential and commercial
Standard: IEC/EN 60898
Icn=4.5kA
No. of rated order details bbn price price w'ght pack.poles current 40 16779 1 piece group 1 pc. unit
① UBmax 125 V ... with 2 poles connected in series
Selection tables SH 200 L-CMCBs SH 200 series L
3/9ABB
3
Compact Home
With disconnecting neutral NA
No. of rated order details bbn price price w'ght pack.poles current 40 16779 1 piece group 1 pc. unit
In A type code order code EAN kg pc.
1 + NA 6 SH 201 L-C 6 NA 2CDS 241 103 R0064 63310 9 0.25 5
8 SH 201 L-C 8 NA 2CDS 241 103 R0084 63312 3 0.25 5
10 SH 201 L-C 10 NA 2CDS 241 103 R0104 63313 0 0.25 5
13 SH 201 L-C 13 NA 2CDS 241 103 R0134 63315 4 0.25 5
16 SH 201 L-C 16 NA 2CDS 241 103 R0164 63317 8 0.25 5
20 SH 201 L-C 20 NA 2CDS 241 103 R0204 63319 2 0.25 5
25 SH 201 L-C 25 NA 2CDS 241 103 R0254 63321 5 0.25 5
32 SH 201 L-C 32 NA 2CDS 241 103 R0324 63323 9 0.25 5
40 SH 201 L-C 40 NA 2CDS 241 103 R0404 63325 3 0.25 5
3 + NA 6 SH 203 L-C 6 NA 2CDS 243 103 R0064 63361 1 0.5 1
8 SH 203 L-C 8 NA 2CDS 243 103 R0084 63363 5 0.5 1
10 SH 203 L-C 10 NA 2CDS 243 103 R0104 63364 2 0.5 1
13 SH 203 L-C 13 NA 2CDS 243 103 R0134 63366 6 0.5 1
16 SH 203 L-C 16 NA 2CDS 243 103 R0164 63368 0 0.5 1
20 SH 203 L-C 20 NA 2CDS 243 103 R0204 63370 3 0.5 1
25 SH 203 L-C 25 NA 2CDS 243 103 R0254 63372 7 0.5 1
32 SH 203 L-C 32 NA 2CDS 243 103 R0324 63374 1 0.5 1
40 SH 203 L-C 40 NA 2CDS 243 103 R0404 63376 5 0.5 1
C
UBmax
440 V ~60 V ...
UBmax
440 V ~
Selection tables SH 200 L-CMCBs SH 200 series L4500
3/10 ABB
3
Compact Home
B SH 200 B characteristicFunction: protection and control of the circuits against overloads and short-circuits; protection forpeople and big-length cables in TN and IT systems.
Applications: buildings, both residential and commercial
Standard: IEC/EN 60898
Icn=6kA
No. of rated order details bbn price price w'ght pack.poles current 40 16779 1 piece group 1 pc. unit
① UBmax 125 V ... with 2 poles connected in series
Selection tables SH 200 BMCBs SH 200 series6000
3/11ABB
3
Compact Home
With disconnecting neutral NA
No. of rated order details bbn price price w'ght pack.poles current 40 16779 1 piece group 1 pc. unit
In A type code order code EAN kg pc.
1 + NA 6 SH 201-B 6 NA 2CDS 211 103 R0065 63081 8 0.25 5
10 SH 201-B 10 NA 2CDS 211 103 R0105 63084 9 0.25 5
13 SH 201-B 13 NA 2CDS 211 103 R0135 63086 3 0.25 5
16 SH 201-B 16 NA 2CDS 211 103 R0165 63088 7 0.25 5
20 SH 201-B 20 NA 2CDS 211 103 R0205 63090 0 0.25 5
25 SH 201-B 25 NA 2CDS 211 103 R0255 63092 4 0.25 5
32 SH 201-B 32 NA 2CDS 211 103 R0325 63094 8 0.25 5
40 SH 201-B 40 NA 2CDS 211 103 R0405 63096 2 0.25 5
3 + NA 6 SH 203-B 6 NA 2CDS 213 103 R0065 63150 1 0.5 1
10 SH 203-B 10 NA 2CDS 213 103 R0105 63153 2 0.5 1
13 SH 203-B 13 NA 2CDS 213 103 R0135 63155 6 0.5 1
16 SH 203-B 16 NA 2CDS 213 103 R0165 63157 0 0.5 1
20 SH 203-B 20 NA 2CDS 213 103 R0205 63159 4 0.5 1
25 SH 203-B 25 NA 2CDS 213 103 R0255 63161 7 0.5 1
32 SH 203-B 32 NA 2CDS 213 103 R0325 63163 1 0.5 1
40 SH 203-B 40 NA 2CDS 213 103 R0405 63165 5 0.5 1
B
UBmax
440 V ~60 V ...
UBmax
440 V ~
Selection tables SH 200 BMCBs SH 200 series6000
3/12 ABB
3
Compact Home
CSH 200 C characteristicFunction: protection and control of the circuits against overloads and short-circuits; protection forresistive and inductive loads with low inrush current.
Applications: buildings, both residential and commercial
Standard: IEC/EN 60898
Icn=6kA
No. of rated order details bbn price price w'ght pack.poles current 40 16779 1 piece group 1 pc. unit
No. of rated order details bbn price price w'ght pack.poles current 40 16779 1 piece group 1 pc. unit
In A type code order code EAN kg pc.
1 + NA 6 SH 201-C 6 NA 2CDS 211 103 R0064 63080 1 0.25 5
8 SH 201-C 8 NA 2CDS 211 103 R0084 63082 5 0.25 5
10 SH 201-C 10 NA 2CDS 211 103 R0104 63083 2 0.25 5
13 SH 201-C 13 NA 2CDS 211 103 R0134 63085 6 0.25 5
16 SH 201-C 16 NA 2CDS 211 103 R0164 63087 0 0.25 5
20 SH 201-C 20 NA 2CDS 211 103 R0204 63089 4 0.25 5
25 SH 201-C 25 NA 2CDS 211 103 R0254 63091 7 0.25 5
32 SH 201-C 32 NA 2CDS 211 103 R0324 63093 1 0.25 5
40 SH 201-C 40 NA 2CDS 211 103 R0404 63095 5 0.25 5
3 + NA 6 SH 203-C 6 NA 2CDS 213 103 R0064 63149 5 0.5 1
8 SH 203-C 8 NA 2CDS 213 103 R0084 63151 8 0.5 1
10 SH 203-C 10 NA 2CDS 213 103 R0104 63152 5 0.5 1
13 SH 203-C 13 NA 2CDS 213 103 R0134 63154 9 0.5 1
16 SH 203-C 16 NA 2CDS 213 103 R0164 63156 3 0.5 1
20 SH 203-C 20 NA 2CDS 213 103 R0204 63158 7 0.5 1
25 SH 203-C 25 NA 2CDS 213 103 R0254 63160 0 0.5 1
32 SH 203-C 32 NA 2CDS 213 103 R0324 63162 4 0.5 1
40 SH 203-C 40 NA 2CDS 213 103 R0404 63164 8 0.5 1
C
UBmax
440 V ~60 V ...
UBmax
440 V ~
Selection tables SH 200 CMCBs SH 200 series6000
3/14 ABB
3
Compact Home
FH 200 AC typeFunction: protection against the effects of sinusoidal alternating earth fault currents; protection againstindirect contacts and additional protection against direct (with I n=30mA) contacts; command andisolation of resistive and inductive circuits.
Application: buildings, both residential and commercial
Standard: IEC/EN 61008
Marking: according to IEC 61008
No. of nominal nominal order details bbn price price w’ght packpoles fault current current 80 12542 1 piece group 1 pc. unit
FH 200 A typeFunction: protection against the effects of sinusoidal alternating and direct pulsating earth fault currents;protection against indirect contacts and additional protection against direct (with I n=30mA) contacts;command and isolation of resistive and inductive circuits.
Application: buildings, both residential and commercial
Standard: IEC/EN 61008
Marking: according to EN 61008
No. of nominal nominal order details bbn price price w’ght packpoles fault current current 80 12542 1 piece group 1 pc. unit
Selection tables FH 200 ACRCCBs FH 200 seriesAC and A type
AC
A
3/15ABB
3
Compact Home Selection tables DS9RCBOs series
DS 941 and DS951, B and C characteristicsFunction: protection against both overload and short circuit currents and earth fault currents; additionalprotection against direct contact (thanks to I n=30mA)
Application: buildings, both residential and commercial
No. of type/class nominal nominal order details bbn price price w’ght pack.poles fault current current 80 12542 1 piece group 1 pc. unit
I n mA In A type code order code EAN kg pc.
RCBOs DS 941, Icn= 4.5kA, B characteristics
1P+N AC 30 10 DS 941 B10 30MA AC 16020015 403104 0.200 1/5
16 DS 941 B16 30MA AC 16020023 403203 0.200 1/5
20 DS 941 B20 30MA AC 16020031 403302 0.200 1/5
25 DS 941 B25 30MA AC 16020049 403401 0.200 1/5
RCBOs DS 941, Icn= 4.5kA, C characteristic
1P+N AC 30 10 DS 941 C10-30MA AC 16020403 406600 0.200 1/5
16 DS 941 C16-30MA AC 16020411 406709 0.200 1/5
20 DS 941 C20-30MA AC 16020429 406808 0.200 1/5
25 DS 941 C25-30MA AC 16020437 406907 0.200 1/5
RCBOs DS 951, Icn=6kA, B characteristic
1P+N AC 30 10 DS 951 B10-30MA AC 16021013 410102 0.200 1/5
16 DS 951 B16-30MA AC 16021021 410201 0.200 1/5
20 DS 951 B20-30MA AC 16021039 410300 0.200 1/5
25 DS 951 B25-30MA AC 16021047 410409 0.200 1/5
RCBOs DS 951, Icn= 6kA, C characteristic
1P+N AC 30 10 DS 951 C10-30MA AC 16021369 413608 0.200 1/5
16 DS 951 C16-30MA AC 16021377 413707 0.200 1/5
20 DS 951 C20-30MA AC 16021385 413806 0.200 1/5
25 DS 951 C25-30MA AC 16021393 413905 0.200 1/5Note: for more information about these products and to know the complete range, see the technical catalogue
3/16 ABB
3
Compact Home busbars and end caps E 200
Type Order Code bbn Pins mm2 Phase sequence End caps Pack unit4016779 pcs.EAN
Compact Home Selection tables E 200Command devicesE 200 switches
E 200 switchesIsolator for panel installation onto DIN rail acc. to DIN EN 60715Mounting depth: 70mmMounting width: per pole = 17.5mm = 1 moduleColour: grey, RAL 7035Colour of switch lever: red RAL 3000 (r); grey RAL 7000 (g)
Special features– Captive screws with recessed/slotted head, Pozidriv size 2– Integrated lay-on edge for labeling system ILS– Locking device as accessories for unauthorized ON/OFF– Approval: VDE, CCC
No. of rated power order details bbn price price w’ght pack.poles voltage loss 4016779 1 piece group 1 pc. unit
Daily program timer switch with DTS 1/1 2CSM 111 000 R0601 506607 0.150 1standby battery (3 years), 1 channel
Digital time switches 2CO contact DTS 7/2 2CSM 122 000 R0601 506805 0.150 1complement, 30 memory location
Twilight switches with sensor LS-1 DTS7/2-TWS 2CSM 122 300 R1351 507307 0,350 1with built-in weekly program timerswitch
Installation relays, Uc=230VAC E 259 R10-230 2CSM111000R0401 532804 0.100 10or 115VDC, 1 NO
Installation relays, Uc=230VAC or E 259 R20-230 2CSM112000R0401 533603 0.100 10115VDC, 2 NO
Latching relays, Uc=230VAC or E 251-230 2CSM 111 000 R0201 530305 0.114 12115VDC, 1 NO
Latching relays, Uc=230VAC or E 252-230 2CSM 112 000 R0201 530800 0.116 12115VDC,2NO
Latching relays, Uc=230VAC or E 255-230 2CSM 119 000 R0201 531302 0.121 12115VDC, series
Latching relays, Uc=230VAC or E 256-230 2CSM 114 000 R0201 531708 0.116 12115VDC, 1 NO + 1NC
Description order details bbn price price w’ght pack.80 12542 1 piece group 1 pc. unit
type code order code EAN kg pc.
Surge protection devices, class II, OVR 1N 40 275 P 2CTB 8139 52 R 11 00 506030 0.220 1Imax=40kA, In=15kA, Up=1.2kV,Un=230V, Uc=275V
Surge protection devices, class II, OVR 3N 40 275 P 2CTB 8139 53 R 11 00 506283 0.220 1Imax=40kA, In=15kA, Up=1.2kV,Un=230V, Uc=275VN.B.: for more information about these products and to know the complete range, see the technical catalogue
2CS
C40
0003
B02
02