Top Banner
PSN-PX 10.11.2010 RTU560/RTU211 © ABB Group February 18, 2012 | Slide 1 RTU560/RTU211 Modules 1KGT 150 648 V1.02
67

ABB RTU560 and Modules

Oct 25, 2015

Download

Documents

insan_soft6498

Description of RTU56 Module
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: ABB RTU560 and Modules

PSN-PX 10.11.2010

RTU560/RTU211

© ABB Group February 18, 2012 | Slide 1

RTU560/RTU211Modules

1KGT 150 648 V1.02

Page 2: ABB RTU560 and Modules

ModulesContents

RTU560 rack solutions

� Subracks

� CMUs� CMUs

� I/Os

� Communication modules

� Auxiliary

RTU560/RTU211 DIN rail solutions

� CMUs

� I/Os

� Communication modules

© ABB Group February 18, 2012 | Slide 2

� Communication modules

� Auxiliary

RTU560E

Page 3: ABB RTU560 and Modules

Modules RTU560 rack solution

� 560CSR01

� Available for wall mounting and

Subracks

CMUs

I/Os

Communication

modules

swing frame

� Supports redundant power supplies

� Up to 8 communication modules

� Expansion slot for 560BCU01

� Real time clocks 560RTC01/02/03

� Network modules 560NUS04/12

Auxiliary

© ABB Group February 18, 2012 | Slide 3

� Network modules 560NUS04/12

� No I/O module

Page 4: ABB RTU560 and Modules

NCC(s)

Modules RTU560 rack solution

Subracks

CMUs

I/Os

Communication

modules

560CSR01

1...16 serial lines or

Ethernet links

560PSU02

24 V

5 V

ON

OFF

UE +

UE -

PE

560PSU02

24 V

5 V

ON

OFF

UE +

UE -

PE

560BCU01

ALR

WRN

TSI

TSO

SEB

560CMU05

A

B

1

2

E1

E2

ERR

E

E

560CMU05

A

B

1

2

E1

E2

ERR

E

E

560CMU05

A

B

1

2

E1

E2

ERR

E

E

560CMU05

A

B

1

2

E1

E2

ERR

E

E

560PSU02

24 V

5 V

ON

OFF

UE +

UE -

PE

560PSU02

24 V

5 V

ON

OFF

UE +

UE -

PE

560PSU02

24 V

5 V

ON

OFF

UE +

UE -

PE

560PSU02

24 V

5 V

ON

OFF

UE +

UE -

PE

560BCU01

ALR

WRN

TSI

TSO

SEB

560BCU01

ALR

WRN

TSI

TSO

SEB

560CMU05

A

B

1

2

E1

E2

ERR

E

E

560CMU05

A

B

1

2

E1

E2

ERR

EE

EE

560CMU05

A

B

1

2

E1

E2

ERR

E

E

560CMU05

A

B

1

2

E1

E2

ERR

EE

EE

560CMU05

A

B

1

2

E1

E2

ERR

E

E

560CMU05

A

B

1

2

E1

E2

ERR

EE

EE

560CMU05

A

B

1

2

E1

E2

ERR

E

E

560CMU05

A

B

1

2

E1

E2

ERR

EE

EE

560PSU02

24 V

560PSU02

24 V

560BCU01

ALR

560CMU05

ERR

560CMU05

ERR

560CMU05

ERR

560CMU05

ERR

560PSU02

24 V

560PSU02

24 V

560PSU02

24 V

560PSU02

24 V

560BCU01

ALR

560BCU01

ALR

560CMU05

ERR

560CMU05

ERR

560CMU05

ERR

560CMU05

ERR

560CMU05

ERR

560CMU05

ERR

560CMU05

ERR

560CMU05

ERR

System bus

Distance < 2m

560CSR01 (opt.)

1... 32 subdevice lines

560CSR01

Auxiliary

© ABB Group February 18, 2012 | Slide 4

24 V

5 V

ON

OFF

UE +

UE -

PE

24 V

5 V

ON

OFF

UE +

UE -

PE

ALR

WRN

TSI

TSO

SEB

A

B

1

2

E1

E2

ERR

E

EA

B

1

2

E1

E2

ERR

E

EA

B

1

2

E1

E2

ERR

E

EA

B

1

2

E1

E2

ERR

E

E

24 V

5 V

ON

OFF

UE +

UE -

PE

24 V

5 V

ON

OFF

UE +

UE -

PE

24 V

5 V

ON

OFF

UE +

UE -

PE

24 V

5 V

ON

OFF

UE +

UE -

PE

ALR

WRN

TSI

TSO

SEB

ALR

WRN

TSI

TSO

SEB

A

B

1

2

E1

E2

ERR

E

EA

B

1

2

E1

E2

ERR

EE

EEA

B

1

2

E1

E2

ERR

E

EA

B

1

2

E1

E2

ERR

EE

EEA

B

1

2

E1

E2

ERR

E

EA

B

1

2

E1

E2

ERR

EE

EEA

B

1

2

E1

E2

ERR

E

EA

B

1

2

E1

E2

ERR

EE

EE

1... 32 subdevice lines

(serial or Ethernet) with

1> 32 IEDs per subdevice line

IEDs

Page 5: ABB RTU560 and Modules

ModulesRTU560 rack solution

� 560MPR03 & 560SFR02

� Available for wall mounting (560MPR03) and swing frame

Subracks

CMUs

I/Os

Communication

modules(560MPR03) and swing frame (560SFR02)

� Supports 1 or 2 power supply units (560PSU01/02)

� Up to 8 units 560CMU05 (up to 5,000 data points) or 560CMU02R0002 are supported

� Solely CMU rack with 560CMU02 and 560CMU05

Auxiliary

© ABB Group February 18, 2012 | Slide 5

and 560CMU05

� Mixed configurations with CMU and I/O

� Mixed configurations with 560CMU05 and 560CMU02 (limited to 750 data points in the RTU)

Redundant power supply, 17 slots

Single power supply, 18 slots

Page 6: ABB RTU560 and Modules

ModulesRTU560 rack solution

� 23ET24 and 23TP22

� 23TP22 version for mounting plate mounting

Subracks

CMUs

I/Os

Communication

modulesmounting

� 23ET24 version for swing frame mounting

� 1 slot for power supply (560PSU01/02)

� 19 general purpose slots

� All rack mounted I/O modules

� Real time clocks 560RTC01/02/03

Auxiliary

23ET24

© ABB Group February 18, 2012 | Slide 6

� Up to 2 communication modules

� Communication media interfaces

� Used as

� Basic rack

� I/O extension rack

23TP22

Page 7: ABB RTU560 and Modules

� 560MPR01

� 1 or 2 Slots for 560CMU02 or 560CMU05

ModulesRTU560 rack solution

Subracks

CMUs

I/Os

Communication

modules 560CMU05

� Up to 8 slots for I/O modules

� 24 V DC external power supply

� Extension connector for I/O bus (extension rack, I/O modules 110/220 V DC)

� Alarm and warning contact output

� Separate input for process voltage(48>60 V DC)

Auxiliary

© ABB Group February 18, 2012 | Slide 7

(48>60 V DC)

� Power distribution for monitoring and command voltage

� 23BA22 configurable for 1,5 pole command outputs

� Screw connectors, access from front

Page 8: ABB RTU560 and Modules

ModulesRTU560 rack solution

� 560BCU01 R0001

� Bus Connection Unit for 560 CSR 01

Subracks

CMUs

I/Os

Communication

modules

� Connecting extension

communication rack

� Alarm and warning contacts

� Minute pulse in- and output

� 560BCU02 R0001

� Bus Connection Unit for 23 TP 22

� Alarm and warning contacts

Auxiliary

© ABB Group February 18, 2012 | Slide 8

� Minute pulse in- and output

� 560BCU03 R0002

� Bus Connection Unit for 23 ET 24

� Alarm and warning contacts

� Minute pulse in- and output

Page 9: ABB RTU560 and Modules

ModulesRTU560 rack solution

� 560BCU04 R0001

� Bus Connection Unit for

560MPR03/23TP22

Subracks

CMUs

I/Os

Communication

modules

560MPR03/23TP22

� Basic board for extension of 2 units

560CMU0x

� Alarm and warning contacts

� Minute pulse in- and output

� 560BCU04 R0002

Bus Connection Unit for 560MPR03

Auxiliary

© ABB Group February 18, 2012 | Slide 9

� Bus Connection Unit for 560MPR03

� Extension kit for 10 additional

560CMU0x

� Alarm and warning contacts

� Minute pulse in- and output

Page 10: ABB RTU560 and Modules

ModulesRTU560 rack solution

� 560BCU05 R0001

� Bus Connection Unit for

560SFR02/23ET24

Subracks

CMUs

I/Os

Communication

modules

560SFR02/23ET24

� Basic board for extension of 2 units

560CMU0x

� Alarm and warning contacts

� Minute pulse in- and output

� 560BCU05 R0002

Bus Connection Unit for 560SFR02

Auxiliary

© ABB Group February 18, 2012 | Slide 10

� Bus Connection Unit for 560SFR02

� Extension kit for 10 additional

560CMU0x

� Alarm and warning contacts

� Minute pulse in- and output

Page 11: ABB RTU560 and Modules

ModulesRTU560 rack solution

560CMU05

R0001

560CMU05

R0002

560CMU02

R0001

560CMU02

R0002

Subracks

CMUs

I/Os

Communication

modules

Serial

interfaces

4x RS232 or RS485 4x RS232 or RS485 2x RS232, 1x RS485 2x RS232 or RS485

Ethernet

interfaces

2x 10/100 Base T 2x 10/100 Base T 1x 10/100 Base T 2x 10/100 Base T

Number of

data points

Up to 10,000 data

points (depending on

Up to 10,000 data

points (depending on

Up to 750 data points Up to 750 data points

Auxiliary

© ABB Group February 18, 2012 | Slide 11

data points points (depending on

configuration)

points (depending on

configuration)

Support of Multi-

CMU

Yes Yes No Yes

Page 12: ABB RTU560 and Modules

ModulesRTU560 rack solution

� 560CMU05 R0001 and R0002� Interfaces

� 4 serial interfaces (RS232C or

Subracks

CMUs

I/Os

Communication

modules � 4 serial interfaces (RS232C or RS485)

� 2 Ethernet ports (10/100BaseT) forcommunication to

� Host systems and/or� Subordinated devices and/or� RTU I/O

� CPU� AMD ELAN520 CPU @133MHz� 128 MB flash memory� 64 MB RAM

Auxiliary

© ABB Group February 18, 2012 | Slide 12

� 64 MB RAM

� Web server for diagnosis and maintenance via Ethernet ports

� PLC capable� Bit protocols (Hitachi, Conitel) are

supported only by 560CMU05 R0002

Page 13: ABB RTU560 and Modules

ModulesRTU560 rack solution

� 560CMU02 R0001

� Interfaces

Subracks

CMUs

I/Os

Communication

modules

� 3 serial interfaces (2x RS232, 1x

RS485)

� 1x Ethernet 10/100 BaseT

� 1x IO Bus (RS485, on backside)

� CPU

� AMD ELAN520 CPU @133MHz

� 128 MB flash memory

Auxiliary

© ABB Group February 18, 2012 | Slide 13

� 128 MB flash memory

� 64 MB RAM

� Only one slot width

� Usable in single CMU configurations

� Maximum of 750 data points

Page 14: ABB RTU560 and Modules

ModulesRTU560 rack solution

� 560CMU02 R0002

� Interfaces

Subracks

CMUs

I/Os

Communication

modules

� 2 serial interfaces (RS232 or RS485)

� 2x Ethernet 10/100 BaseT

� 1x IO Bus (RS485, on backside)

� CPU

� AMD ELAN520 CPU @133MHz

� 128 MB flash memory

64 MB RAM

Auxiliary

© ABB Group February 18, 2012 | Slide 14

� 64 MB RAM

� Only one slot width

� Usable in multiple CMU

configurations

� Maximum of 750 data points

Page 15: ABB RTU560 and Modules

ModulesRack I/O modules - Overview

Binary input Binary output Analog input Analog output

23BE23

16 inputs 24>60

23BA20/22

24>60 VDC / 2A

23AE23

0...20 VDC / ±2 / ±5 /

23AA21

±2.5 / ±5 / ±10 /

Subracks

CMUs

I/Os

Communication

modules

VDC / 2mA ±10 / ±20 / ±40mA ±20mA or 4...20mAAuxiliary

© ABB Group February 18, 2012 | Slide 15

Page 16: ABB RTU560 and Modules

Modules RTU560 rack solution

� Binary input board 23BE23

� 16 binary input channels

Subracks

CMUs

I/Os

Communication

modules

� One module for all types of binary

input signals ( single indications,

double point indications, digital

measured values, counters)

� Galvanic insulation by optocouplers

� Input voltage 24...60 VDC,

� LED's for signalization of input

Auxiliary

© ABB Group February 18, 2012 | Slide 16

� LED's for signalization of input

channels

Page 17: ABB RTU560 and Modules

Modules RTU560 rack solution

� Binary output board 23BA20

� 16 binary relay output channels

Subracks

CMUs

I/Os

Communication

modules

� One module for all types of binary

output signals (single commands,

double point commands, setpoint

commands)

� Galvanic insulation by relays

� Output voltage 24...60 VDC

� Switching capacity:

Auxiliary

© ABB Group February 18, 2012 | Slide 17

� Switching capacity:

40 VA (L/R=30ms) @ 60 VDC

� Continuous current: 2A

Page 18: ABB RTU560 and Modules

ModulesRTU560 rack solution

� Command Output monitoring board

23BA22

Usage in combination with 23BA20

Subracks

CMUs

I/Os

Communication

modules

� Usage in combination with 23BA20

� 1 out of n check

� Supervision of up to 32 different

relay types

� Galvanic isolation of the check

circuit

� Suppression of line frequency during

measuring

Auxiliary

© ABB Group February 18, 2012 | Slide 18

measuring

� Monitoring of output duration and

reset in case of fault

� Monitoring of switching voltage

before and during the command

output

Page 19: ABB RTU560 and Modules

ModulesRTU560 rack solution

� Analog input board 23AE23

� 8 differential inputs

Subracks

CMUs

I/Os

Communication

modules

� Input current ± 2 mA, ± 5 mA,

±10 mA, ± 20 mA, ± 40mA

� Input voltage ± 2 VDC,

0...20 VDC

� 12 bit + sign = 4096 steps

� Occupies one slots in RTU560

subrack

Auxiliary

© ABB Group February 18, 2012 | Slide 19

subrack

� Low-pass filter

� Over voltage protection

Page 20: ABB RTU560 and Modules

ModulesRTU560 rack solution

� Analog output board 23AA21

� 2 channels

Subracks

CMUs

I/Os

Communication

modules

� Output current ± 2.5 mA,

± 5 mA, +-10 mA, ± 20 mA or

4...20mA

� 11 bit + sign

� Occupies one slots in RTU560

subrack

Auxiliary

© ABB Group February 18, 2012 | Slide 20

Page 21: ABB RTU560 and Modules

ModulesRTU560 rack solution

Analog line modems Serial optical interfaces Ethernet and optical switches

23WT23/24/25

5/24 VDC

23OK24 560NUS04/12

unmanaged

560NMS24/34

managed/DSL

Subracks

CMUs

I/Os

Communication

modules

Auxiliary

© ABB Group February 18, 2012 | Slide 21

Page 22: ABB RTU560 and Modules

ModulesRTU560 rack solution

� Modem 23WT23

� FSK modem for voice band range

(300-2400 Hz) according to CCITT

Subracks

CMUs

I/Os

Communication

modules

(300-2400 Hz) according to CCITT

V.23

� 2- or 4-wire lines, duplex or half

duplex

� Baudrate 1200 bit/s

� Adjustable by jumpers

� Point to point or multidrop

configurations, in multidrop

configurations up to 10 remote

Auxiliary

© ABB Group February 18, 2012 | Slide 22

configurations up to 10 remote

station in one line

� Disconnect test sockets on front

side

� Only one slot necessary

� R0001: 5 VDC, R0002: 24 VDC

Page 23: ABB RTU560 and Modules

ModulesRTU560 rack solution

� Modem 23WT24

� FSK modem for wide band range

Subracks

CMUs

I/Os

Communication

modules

(300-18000 Hz)

� 2- or 4-wire lines, duplex or half

duplex

� Baudrate: 9600 Baud

� Distances up to 20 km, Point to

point

� Distances up to 10 km, multi-drop

Auxiliary

© ABB Group February 18, 2012 | Slide 23

� Distances up to 10 km, multi-drop

configuration

� Disconnect test sockets on front

side

� Only one slot necessary

Page 24: ABB RTU560 and Modules

ModulesRTU560 rack solution

� Modem 23WT25

� FSK modem in voice band range (300-

2400Hz) according to CCITT

Subracks

CMUs

I/Os

Communication

modules 2400Hz) according to CCITT

� Variants:

R0001: supply voltage 5 VDC

R0002: supply voltage 24 VDC

� 2- or 4-wire lines, duplex or half duplex

� Baudrate 50 bit/s if 24-channel-CCITT-

raster is used, up to 2400 bit/s if one

channel is used

� Digital signal processor (DSP) for

conversion of binary information to voice

Auxiliary

© ABB Group February 18, 2012 | Slide 24

conversion of binary information to voice

band and vice versa

� Point to point or multi-drop

configurations, in multi-drop

configurations carrier can be switched

off

� Disconnect test sockets on front side

Page 25: ABB RTU560 and Modules

ModulesRTU560 rack solution

� Optical coupler 23OK24

� Optic connection of extension

Subracks

CMUs

I/Os

Communication

modules

racks in star or line configuration

� Optic connection of SPA bus

devices point to point or loop

� Optic connection of protection

devices according IEC 60870-5-103

� Glass fiber optic wave length 820

nm

Auxiliary

© ABB Group February 18, 2012 | Slide 25

nm

� ST connector (BFOC 2,5)

� Cable length up to 2600 m

Page 26: ABB RTU560 and Modules

ModulesRTU560 rack solution

� 4 port unmanaged local switch –

560NUS04

� 4 fast Ethernet 10/100 BaseT ports

Subracks

CMUs

I/Os

Communication

modules

� 4 fast Ethernet 10/100 BaseT ports

for LAN port multiplication

� Additional interfaces for diagnosis

and LAN/WAN communication

� Unmanaged

� Auto negotiation 10/100Mbps

� Automatic Cross over detection

� Only for linear networks (no ring

Auxiliary

© ABB Group February 18, 2012 | Slide 26

� Only for linear networks (no ring

configuration)

� No STP/ RSTP supported

� No additional power supply required

� Plug and play – no configuration

required

Page 27: ABB RTU560 and Modules

ModulesRTU560 rack solution

� 4 port switch with 2 x FX – 560NUS12� 2 fast Ethernet 10/100 BaseT ports � 2 SFP cages for fiber optical

Subracks

CMUs

I/Os

Communication

modules � 2 SFP cages for fiber optical interfaces

� Unmanaged� Auto negotiation 10/100Mbps� Automatic cross over detection� Different SFPs

� 560NFO13: mono-mode fiber, up to 15 km

� 560NFO15: mono-mode fiber, up to 40 km

� 560NFO85: multi-mode fiber, up to 2

Auxiliary

© ABB Group February 18, 2012 | Slide 27

� 560NFO85: multi-mode fiber, up to 2 km

� Only for linear networks� No STP/RSTP supported� Media converter to optical Ethernet� Plug and play – no configuration

required

Page 28: ABB RTU560 and Modules

ModulesRTU560 rack solution

� 4 port switch with 2 x DSL 560NMS24

� SDSL interface (Symmetric Digital

Subracks

CMUs

I/Os

Communication

modules

Subscriber Line)

� 4 x fast Ethernet RJ45 ports

� 2 DSL WAN ports for copper

� Bandwidth from 192kbit/s up to

6Mbit/s

� Automatic through-connection in

case of power cut

Auxiliary

© ABB Group February 18, 2012 | Slide 28

case of power cut

� Managed switch

� Ring configuration possible

� NMS34 with 1 DSL port

Page 29: ABB RTU560 and Modules

ModulesRTU560 rack solution

Power supply units Real time clocks

560PSU01/02 560RTC01/02/03

Subracks

CMUs

I/Os

Communication

modules

Auxiliary

© ABB Group February 18, 2012 | Slide 29

Page 30: ABB RTU560 and Modules

ModulesRTU560 rack solution

� Power supply unit 560PSU01

� Input: 24...60 VDC (R0001) or

Subracks

CMUs

I/Os

Communication

modules

110...220 VDC (R0002)

� Output total 44 W,

5 VDC: 0.2 A ...5.5 A and

24 VDC: 0...0.7 A

� 1 LED for 5V, 1 LED for 24 V

signalization

� Electronic power limitation, short

Auxiliary

© ABB Group February 18, 2012 | Slide 30

� Electronic power limitation, short

circuit proof, controlled load

balancing

� Alarm indication relay in case of

failure

Page 31: ABB RTU560 and Modules

ModulesRTU560 rack solution

� Power supply unit 560PSU02

� Input: 48...220 VDC

Subracks

CMUs

I/Os

Communication

modules

� Output total 80 W,

5 VDC: 0>15 A and

24 VDC: 0...0.7 A

� 1 LED for 5V, 1 LED for 24 V

signalization

� Electronic power limitation, short

circuit proof, controlled load

Auxiliary

© ABB Group February 18, 2012 | Slide 31

circuit proof, controlled load

balancing

� Alarm indication relay in case of

failure

� Stipulated for redundant operation

Page 32: ABB RTU560 and Modules

ModulesRTU560 rack solution

� Real time clock 560RTC01/02/03

� 560RTC01: designed for GPS

Subracks

CMUs

I/Os

Communication

modules

receiving

� 560RTC02: designed for long-wave

DCF 77 transmitter receiving

� 560RTC03: IRIG-B time codes

� IRIG-B123

� IRIG-B122

AFNOR NFS 87-500

Auxiliary

© ABB Group February 18, 2012 | Slide 32

� AFNOR NFS 87-500

� IRIG-B003

� IRIG-B002

� AFNOR NFS 87-500 (DC)

Page 33: ABB RTU560 and Modules

ModulesRTU560/RTU211 DIN rail solution

560CMG10 560CIG10Technical data

RTU560 for DIN rail

Technical data

RTU211 for DIN rail

CMUs

Serial interfaces 3

Ethernet 10/100 BaseT 1

Integrated I/Os 16 binary inputs

8 binary outputs

8 analog inputs (mA)

Extension

I/O modules

Binary inputs/outputsAnalogue inputs/outputs

I/Os

Communication

modules

Auxiliary

© ABB Group February 18, 2012 | Slide 33

I/O modulesAnalogue inputs/outputs

Direct analog inputs Optional: fault current detection

Dimensions

W x H x D204 x 105 x 55 mm 230 x 150 x 84 mm

Page 34: ABB RTU560 and Modules

ModulesRTU560/RTU211 DIN rail solution

DIN rail RTU211

23CM61 560CMU01

Technical data

RTU560 for DIN rail

Technical data

RTU211 for DIN rail

CMUs

Serial interfaces 1/4 3

Ethernet 10/100

BaseT

0 1

Integrated I/Os 16 binary inputs

8 binary outputs

Up to 4 of the following modules:

16 binary inputs

8 binary outputs

6 analog inputs (mA)

2 analog outputs

6 temperature sensors

I/Os

Communication

modules

Auxiliary

© ABB Group February 18, 2012 | Slide 34

Extension

I/O modules

Binary inputs/outputs

Analog inputs/outputs

Binary inputs/outputs

Analog inputs/outputs

Direct analog inputs

Optional: Fault current detection

Dimensions

W x H x D

(290 – 400) x 116 x 81 mm (181 – 741) x 116 x 81 mm

Depending on integrated I/Os

Page 35: ABB RTU560 and Modules

� 23CM61

� 512 kByte flash memory

� 256 kByte RAM

ModulesRTU560/RTU211 DIN rail solution

Technical data

RTU560 for DIN rail

Technical data

RTU211 for DIN rail

CMUs

� 256 kByte RAM

� 4 x RS232 ports

� RP570 communication protocols

� IEC 60870-5-101 or DNP3

communication protocols

� Built-in “Local Automation Function”

(LAF)

� Monitoring of system power

I/Os

Communication

modules

Auxiliary

© ABB Group February 18, 2012 | Slide 35

� Monitoring of system power

� Integrated alarm relay

� 16 binary inputs

� 8 binary outputs

� 6 analog inputs

� 1 out of n check

Page 36: ABB RTU560 and Modules

ModulesRTU560/RTU211 DIN rail solution

� RTU211 based on 560CMU01

� 560CMU01

� 3 serial interfaces

Technical data

RTU560 for DIN rail

Technical data

RTU211 for DIN rail

CMUs

� 3 serial interfaces

� 1 ethernet interface

� Up to 4 of the following I/O modules:

� 16 binary inputs

� 8 binary outputs

� 6 analog inputs (mA)

� 2 analog outputs

� 6 temperature sensors

560PSU10

I/Os

Communication

modules

Auxiliary

© ABB Group February 18, 2012 | Slide 36

� 560PSU10

� Total output of approx. 38 W, split to:

� + 5 V DC and 1 A = 5 Watt

� + 15 V DC and 0.5 A = 7.5 Watt

� 15 V DC and 0.5 A = 7.5 Watt

� + 18 V DC and 1A = 18 W

Page 37: ABB RTU560 and Modules

ModulesRTU560/RTU211 DIN rail solution

Binary input Binary output Analog input Analog output

23BI61

16 inputs 24/ 48/ 60 VDC

23BO62/63

3A @ 110 VDC / 3A

23AI60

Analog inputs mA DC

23AO60

Analog output mA DC

Technical data

RTU560 for DIN rail

Technical data

RTU211 for DIN rail

CMUs 16 inputs 24/ 48/ 60 VDC 3A @ 110 VDC / 3A Analog inputs mA DC Analog output mA DC

23BE40

16 inputs 110/ 220/250 VDC

23BA40

50 VA (L/R=40ms) @ 220 VDC / 8A

560CVT02

Analog inputs A/V AC

I/Os

Communication

modules

Auxiliary

© ABB Group February 18, 2012 | Slide 37

23BE50

64 inputs 24/ 48/ 60 VDC

560CVT10

Analog inputs

Page 38: ABB RTU560 and Modules

ModulesRTU560/RTU211 DIN rail solution

� Binary input 23BI61

� 16 binary inputs for single or double

indication, digital measurands,

Technical data

RTU560 for DIN rail

Technical data

RTU211 for DIN rail

CMUs

indication, digital measurands,

pulse counter

� R0001: 24>48 VDC

� R0002: 60>110 VDC

� Grouped with common return per 8

inputs

� One LED per input

I/Os

Communication

modules

Auxiliary

© ABB Group February 18, 2012 | Slide 38

� One LED per input

� 1 ms time resolution

� Length 105 mm

� Housing should be ordered

separately

Page 39: ABB RTU560 and Modules

ModulesRTU560/RTU211 DIN rail solution

� Direct process-interface 23BE40

� 16 binary input channels

Technical data

RTU560 for DIN rail

Technical data

RTU211 for DIN rail

CMUs

� Input Voltage

� 110 VDC: 23BE40 R0011

� 220 VDC: 23BE40 R0012

� Inputs without common

return

� Galvanic insulation by optocouplers

� Input current 1,5 mA (chopped)

I/Os

Communication

modules

Auxiliary

© ABB Group February 18, 2012 | Slide 39

� Oxide film break function for 8

inputs

� LEDs for signalization of input

channels

� Power supply: 24 Vdc

Page 40: ABB RTU560 and Modules

ModulesRTU560/RTU211 DIN rail solution

� 64 binary input module 23BE50

� 64 binary inputs

Technical data

RTU560 for DIN rail

Technical data

RTU211 for DIN rail

CMUs

� Input range: 24>60 VDC

� Input functions as 23BE23

� Groups with common return per 16

inputs

� Galvanic insulation by optical

couplers

LEDs for signalization of each input

I/Os

Communication

modules

Auxiliary

© ABB Group February 18, 2012 | Slide 40

� LEDs for signalization of each input

channel

� Power supply: 24 VDC

� Usable without additional terminals

Page 41: ABB RTU560 and Modules

ModulesRTU560/RTU211 DIN rail solution

� Binary output 23BO62

� 8 binary relay outputs for 1, 1,5 or 2

Technical data

RTU560 for DIN rail

Technical data

RTU211 for DIN rail

CMUs

pole commands

� Isolated outputs

� One LED per output

� High switching capacity:

3A @ 110 VDC

� Continuous current: 3A

I/Os

Communication

modules

Auxiliary

© ABB Group February 18, 2012 | Slide 41

� Length 140 mm

� Housing should be ordered

separately

Page 42: ABB RTU560 and Modules

ModulesRTU560/RTU211 DIN rail solution

� 1 out of n check 23BO63

� 1 out of n supervision in

Technical data

RTU560 for DIN rail

Technical data

RTU211 for DIN rail

CMUs

combination with 23BO62

� High switching capacity up to 110

VDC, 3 A

� Length 70 mm

� Housing should be ordered

separately

I/Os

Communication

modules

Auxiliary

© ABB Group February 18, 2012 | Slide 42

Page 43: ABB RTU560 and Modules

ModulesRTU560/RTU211 DIN rail solution

� Direct process-interface 23BA40

� 16 binary relay output channels

Technical data

RTU560 for DIN rail

Technical data

RTU211 for DIN rail

CMUs

� Outputs without common return

(23BA40 R0011)

� Galvanic insulation by relays

� Switching voltage

max. 250 VDC/AC

� Switching capacity:

50 VA (L/R=40ms) @ 220 VDC

I/Os

Communication

modules

Auxiliary

© ABB Group February 18, 2012 | Slide 43

50 VA (L/R=40ms) @ 220 VDC

� Continuous current: 8A

Page 44: ABB RTU560 and Modules

ModulesRTU560/RTU211 DIN rail solution

� Analog input 23AI60

� 6 analog inputs

Technical data

RTU560 for DIN rail

Technical data

RTU211 for DIN rail

CMUs

� Resolution: 11 bit +sign

� Accuracy class: 0,25

� Ranges: ± 5mA, ± 10 mA,

+20 mA, 4>20 mA, ± VDC, ±

10VDC

� Length: 70 mm

I/Os

Communication

modules

Auxiliary

© ABB Group February 18, 2012 | Slide 44

� Housing should be ordered

separately

Page 45: ABB RTU560 and Modules

ModulesRTU560/RTU211 DIN rail solution

� Direct transducer interface 560CVT02� 3 voltage inputs 110 VAC

� 110 VAC: 560CVT02 R000x

Technical data

RTU560 for DIN rail

Technical data

RTU211 for DIN rail

CMUs � 110 VAC: 560CVT02 R000x(for measurement with voltage transformers)

� 230 VAC: 560CVT02 R001x (for direct voltage measurement at the low voltage side)

� 3 Current Inputs� 1A: 560CVT02 R00x1� 5A: 560CVT02 R00x5

� Accuracy: 0,2%� Calculated values:

I/Os

Communication

modules

Auxiliary

© ABB Group February 18, 2012 | Slide 45

� Calculated values:� Active, reactive, apparent power� Active, reactive energy� Power factor � Frequency � Harmonic distortion (THD)

� Integrated in RTU560 engineering

Page 46: ABB RTU560 and Modules

ModulesRTU560/RTU211 DIN rail solution

� Direct transducer interface 560CVT10� 3 current inputs

� R0011: 1A

Technical data

RTU560 for DIN rail

Technical data

RTU211 for DIN rail

CMUs � R0011: 1A� R0015: 5A

� 3 voltage inputs max. 300V� Accuracy up to 0.2% � Low input burden

� Voltage 0.15VA at 300 V� Current 0.2 VA of rating

� Additional fault current measurement up to 20 x line

� Over current detection

Over Current Detection

Saturation

I/Os

Communication

modules

Auxiliary

© ABB Group February 18, 2012 | Slide 46

� Over current detection� Total harmonic distortion (THD)� PLC applications for voltage dip

detection available� Power supply: 24V DC (± 20%)� MODBUS interface� Integrated in RTU560 engineeringOCx_FV

Phase x Current

Time

Saturation

Over Current detected

Page 47: ABB RTU560 and Modules

ModulesRTU560/RTU211 DIN rail solution

� Analog output 23AO60

� 2 analog outputs for set points

Technical data

RTU560 for DIN rail

Technical data

RTU211 for DIN rail

CMUs

� Resolution: 11 bit +sign

� Accuracy class: 0,25

� Ranges: ± 2,5 mA, ± 5mA, ± 10 m,

± 20 mA, 4>20 mA, ± 1 VDC,

± 10VDC

� Length: 105 mm

I/Os

Communication

modules

Auxiliary

© ABB Group February 18, 2012 | Slide 47

� Housing should be ordered

separately

Page 48: ABB RTU560 and Modules

ModulesRTU560/RTU211 DIN rail solution

Analog line modems Serial optical interfaces

560FSM10/11

18>72 VDC

560FOC40

18...30VDC

23SC60

R008 glass fiber

Technical data

RTU560 for DIN rail

Technical data

RTU211 for DIN rail

CMUs18>72 VDC 18...30VDC

560FOC80

5 VDC

R008 glass fiber

R009 plastic fiberI/Os

Communication

modules

Auxiliary

ABB 560FOC80

© ABB Group February 18, 2012 | Slide 48

Page 49: ABB RTU560 and Modules

Modules RTU560/RTU211 DIN rail solution

� Modem 560FSM10 and 560FSM11

� 560FSM10

Technical data

RTU560 for DIN rail

Technical data

RTU211 for DIN rail

CMUs

� V.23 modem

� Functionality comparable to

23WT23

� Power supply: 18>72 VDC

� 560FSM11 R0001

� 9600 baud modem

Functionality comparable to

I/Os

Communication

modules

Auxiliary

© ABB Group February 18, 2012 | Slide 49

� Functionality comparable to

23WT24

� Power supply: 18..72 VDC

Page 50: ABB RTU560 and Modules

Modules RTU560/RTU211 DIN rail solution

� Serial optical interface 560FOC40 and

560FOC80

Technical data

RTU560 for DIN rail

Technical data

RTU211 for DIN rail

CMUs

� Opto coupler unit

� Power supply:

� 560FOC40: 24 VDC (18..30VDC)

� 560FOC80: 5 VDC

� Support of glass fiber (62,5/125µm)

� BFOC 2,5 connector

I/Os

Communication

modules

Auxiliary

© ABB Group February 18, 2012 | Slide 50

� RS485 electrical interface

� Compatible to 23OK22/24

ABB 560FOC80

Page 51: ABB RTU560 and Modules

Modules RTU560/RTU211 DIN rail solution

� Star coupler 23SC60

� Used to connect decentralize I/O

Technical data

RTU560 for DIN rail

Technical data

RTU211 for DIN rail

CMUs

racks up to 2 km

� Versions for different medias

� R008x: multi mode glass fiber

� R009x: plastic fiber

� 2..5 optical interfaces per housing

available

To be used to connect 23BE40,

I/Os

Communication

modules

Auxiliary

© ABB Group February 18, 2012 | Slide 51

� To be used to connect 23BE40,

23BA40 and 23BE50 to DIN rail

RTUs

Page 52: ABB RTU560 and Modules

ModulesRTU560/RTU211 DIN rail solution

Power supply units

560PSU10 560PSU40

Input 110>220

VDC

560PSU41

Input 24>60 VDC

Output 24 VDC/2,5A

23PU63

Input 24>110 VDC

Output 5V/1A, ±15V/0,

23VG23/24

Technical data

RTU560 for DIN rail

Technical data

RTU211 for DIN rail

CMUs

VDC

Output 24

VDC/2,5A

Output 24 VDC/2,5A Output 5V/1A, ±15V/0,

18V/1A, 24V/0,5A

I/Os

Communication

modules

Auxiliary

© ABB Group February 18, 2012 | Slide 52

Page 53: ABB RTU560 and Modules

ModulesRTU560/RTU211 DIN rail solution

� Power supply 23PSU40/41

� Input voltage

560PSU40: 110>220 VDC

Technical data

RTU560 for DIN rail

Technical data

RTU211 for DIN rail

CMUs

560PSU40: 110>220 VDC

560PSU41: 24>60 VDC

� Max. output power 60 W, 24 VDC:

2,5 A

� 1 LED for voltage supervision

24VDC

� Overload and short-circuit

I/Os

Communication

modules

Auxiliary

© ABB Group February 18, 2012 | Slide 53

protection

� Power good signal available (only

560PSU40)

� Parallel peration possible (only

560PSU40)

Page 54: ABB RTU560 and Modules

Modules RTU560/RTU211 DIN rail solution

� 560PSU10

� 560PSU10: Power supply unit for

RTU560 DIN rail in cooperation with

Technical data

RTU560 for DIN rail

Technical data

RTU211 for DIN rail

CMUs

RTU560 DIN rail in cooperation with

560CMU01

� The 560PSU10 supplies a total

output of approx. 38 W. This is split

to:

� + 5 V DC and 1 A = 5 Watt

� + 15 V DC and 0.5 A = 7.5 Watt

I/Os

Communication

modules

Auxiliary

© ABB Group February 18, 2012 | Slide 54

� 15 V DC and 0.5 A = 7.5 Watt

� + 18 V DC and 1A = 18 W

Page 55: ABB RTU560 and Modules

ModulesRTU560/RTU211 DIN rail solution

� Power supply 23PU63

� 25W power supply

Technical data

RTU560 for DIN rail

Technical data

RTU211 for DIN rail

CMUs

� Input voltage

� 24 – 110 VDC (+/- 20%)

� Output voltage

� 5V 1A (internal usage)

� +/-15V 0,2 A (RS232, AI/AO)

� 18 V 1A (relays, AO)

I/Os

Communication

modules

Auxiliary

© ABB Group February 18, 2012 | Slide 55

� 24V 0,5A (process voltage)

� Used in main module 23CM61 and

together with 23AD64

Page 56: ABB RTU560 and Modules

Modules RTU560/RTU211 DIN rail solution

� Main adapter 23VG23

� Input Voltage 115 / 230 V AC

Technical data

RTU560 for DIN rail

Technical data

RTU211 for DIN rail

CMUs

without switch over

� 24 VDC output voltage

� Power output 48 W

� Output current min. 0.2 A and max.

2 A

� Integrated components:

I/Os

Communication

modules

Auxiliary

© ABB Group February 18, 2012 | Slide 56

� Battery charging device

� Switch over device

� Exhaustive discharge protection

Page 57: ABB RTU560 and Modules

Modules RTU560/RTU211 DIN rail solution

� Main adapter 23VG24

� Input Voltage 115 / 230 V AC

Technical data

RTU560 for DIN rail

Technical data

RTU211 for DIN rail

CMUs

� Power output approx. 240 W

� 24 VDC output voltage

� Output current max. 10 A

I/Os

Communication

modules

Auxiliary

© ABB Group February 18, 2012 | Slide 57

Page 58: ABB RTU560 and Modules

ModulesRTU560E

� Applications:

� Small distribution substations

� Distributed architectures with

decentralized I/O units

� Benefits:

� Cost optimized solution for medium

and small data amounts

� Easy and fast assembling,

mounting and commissioning

© ABB Group February 18, 2012 | Slide 58

mounting and commissioning

� No additional housing needed

� Mounting space for additional

devices

Page 59: ABB RTU560 and Modules

ModulesRTU560E

•General modules

Housing 560HOS80 Multi I/O 560MIO80

© ABB Group February 18, 2012 | Slide 59

Communication Unit 560CMU80 Modem Unit 560MOD8x

Page 60: ABB RTU560 and Modules

ModulesRTU560E

� Housing 560HOS80

� Size: 366mm x 258mm x 310mm

(H x W x D)

� Hinged housing with terminals on

the back-plane

� IP 30

© ABB Group February 18, 2012 | Slide 60

Page 61: ABB RTU560 and Modules

ModulesRTU560E

� Multi I/O board 560MIO80

� 16 binary inputs

� R0001: 24...60 VDC

� R0002: 110...220 VDC

� 8 binary outputs

� R0001: technical data according 23BA20

� R0002:

� Continuous current rating: max. 5 A

� Breaking current (L/R 40ms, 70°C)

� 4 analog inputs

© ABB Group February 18, 2012 | Slide 61

� 4 analog inputs

� Input range

� Input current ± 2 mA, ± 5 mA, ± 10 mA, ± 20 mA, ±

40mA

� Input voltage ± 2 VDC, 0...20 VDC

� Resolution: 12 bit + sign

Page 62: ABB RTU560 and Modules

ModulesRTU560E

� Modems

� 560MOD80

� FSK modem V.23 halfduplex

� 1200 bps

� 560MOD81

� Analog modem, dial up

� Data transfer 300 - 33.600 bps

� 560MOD82

© ABB Group February 18, 2012 | Slide 62

� GSM modem

� Dual band GSM Modul 900/1800 MHz

� Compliant with ETSI GSM phase 2 standard

� Class 4 (2W @ 900 MHz)

� Class 2 (1W @ 1800 MHz)

Page 63: ABB RTU560 and Modules

ModulesRTU560E

� Communication unit 560CMU80

� Communication interfacesAMD

SC400

AMD SCC

85C30Com /

2x5Pol

ModemModem1 / RJ45

Modem2 / RJ45

� CP1, CP2:

2x RS232 interfaces with opt.

modem socket, baudrate 50 –

38400 Baud

� CPA:

1x RS485 baudrate 19200 Baud

� Opt. Ethernet 10BaseT (RJ45)

� 1 MMI (Front Access) RS232

baudrate 38400 Baud

MMI / DB9

CPA / RJ45

FPGA

ASIC

BIOS

+

DIP32

SMSC

37C93x

ISA

-B

US

80C251 +

DualPort

RAM

Compact

RS232

RS485

SMSC

10BaseT /

RJ45

RS232

RS232

CP1 / RJ45

CP2 / RJ45

RS485E-Bus SPB /

DIN41612

ModemModem2 / RJ45

© ABB Group February 18, 2012 | Slide 63

baudrate 38400 Baud

� CPU

� CPU ELAN 400 @ 66MHz

� 16 MB DRAM

� 32 MB compact flash card

Compact

Flash

optional

SMSC

91C94

RJ45

AUI / DB15

PC104-Bus

Page 64: ABB RTU560 and Modules

ModulesRTU560E

� Power supply

� AC/DC converter 560PSU81

� Input voltage: 115...230 VAC

� DC/DC converter 560PSU80

� Input voltage:

� R0001: 24...60 VDC

� R0002: 110...220 VDC

© ABB Group February 18, 2012 | Slide 64

Page 65: ABB RTU560 and Modules

© ABB Group February 18, 2012 | Slide 65

Page 66: ABB RTU560 and Modules

Revisions

Version Description Date

V1.01 New document 30.09.2010

V1.02 Correction of picture file sizes 10.11.2010V1.02 Correction of picture file sizes 10.11.2010

© ABB Group February 18, 2012 | Slide 66

Page 67: ABB RTU560 and Modules