Top Banner

of 13

Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
  • ABB16.04.2012 VD4 Vacuum circuit-breaker | 1

    VD4 Vacuum circuit-breaker

    ABB AG - Calor Emag Medium Voltage Products

  • ABB16.04.2012 VD4 Vacuum circuit-breaker | 2

    For fixed mounting orwithdrawable on truck

    Performance data

    12 kV, 3150 / 40001) A, 63 kA

    17.5 kV, 3150 / 40001) A, 50 kA

    24 kV, 2500 A, 31.5 kA

    36 kV, 3150 A, 40 kA

    40.5 kV, 3150 A, 40 kA

    Compliance to IEC 62271-100

    1) Breaker for 4000 A with forced cooling

    VD4 Vacuum circuit-breaker

  • ABB16.04.2012 VD4 Vacuum circuit-breaker | 3

    VD4 Vacuum circuit-breaker

    Fields of application inpower supply and industry

    Cable control and protection

    Overhead control and protection

    Transformers and distributionsubstations

    Motor and transformercontrol and protection

    Generator control and protection

    Capacitor bank control and protection

    Long experience in medium voltage!

  • ABB16.04.2012 VD4 Vacuum circuit-breaker | 4

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    VD4 Vacuum circuit-breaker

    Vacuum interrupter(principle structure)

    1 Stem / terminal

    2 Twist protection

    3 Metal bellows

    4 Interrupter lid

    5 Shield

    6 Ceramic insulator

    7 Shield

    8 Contacts

    9 Stem / terminal

    10 Interrupter lid

  • ABB16.04.2012 VD4 Vacuum circuit-breaker | 5

    VD4 Vacuum circuit-breaker

    Embedded pole(Principle structure)

    1 Upper terminal

    2 Vacuum interrupter

    3 Stem

    4 Lower terminal

    5 Flexible connection

    6 Insulated push-rodwith contact force springs

    7 Fixing point

    8 Connection to drive

    1

    2

    3

    4

    5

    6

    7

    8

  • ABB16.04.2012 VD4 Vacuum circuit-breaker | 6

    16 kA

    1250 A

    24 kV

    16 kA

    1250 A

    17.5 kV

    20 kA

    1250 A

    12 kV

    VG5

    25 kA

    2500 A

    24 kV

    31.5 kA

    2500 A

    17.5 kV

    31,5 kA

    2500 A

    12 kV

    VG4-S

    20 kA

    2500 A

    24 kV

    25 kA25 kA

    2500 A1250 A

    17.5 kV17.5 kV

    25 kA25 kA

    2500 A1250 A

    12 kV12 kV

    VG4VGE4

    VD4 Vacuum circuit-breakerVacuum interrupters

  • ABB16.04.2012 VD4 Vacuum circuit-breaker | 7

    50 kA

    3150 A

    12 kV

    VG7

    200 kV BIL

    40 kA

    3150 A

    40.5 kV

    40 kA

    3150 A

    36/40.5 kV

    VG8-S

    31.5 kA

    3150 A

    200 kV BIL36/40.5 kV

    31.5 kA31.5 kA

    3150 A3150 A

    40.5 kV24/36 kV

    31.5 kA40 kA

    3150 A3150 A

    36/40.5 kV12/17.5 kV

    VG8VG6

    VD4 Vacuum circuit-breakerVacuum interrupters

  • ABB16.04.2012 VD4 Vacuum circuit-breaker | 8

    25 kA40 kA40 kA31.5 kA

    1250 A1600 A3150 1) A1250 A24 kV12 / 17.5 kV12 / 17.5 kV12 / 17.5 kV

    P4P3P2PT1

    VD4 Vacuum circuit-breakerEmbedded Poles

    1) 2500 A and 3150 A with heat sink

  • ABB16.04.2012 VD4 Vacuum circuit-breaker | 9

    50 kA40 kA31.5 kA

    3150 1) A2500 A2500 1) A12 / 17.5 kV36 / 40.5 kV24 kV

    P7P6P51) 2500 A and 3150 A with heat sink

    VD4 Vacuum circuit-breakerEmbedded Poles

  • ABB16.04.2012 VD4 Vacuum circuit-breaker | 10

    VD4 Vacuum circuit-breaker

    The switchgearcomplies with the following specifications in according with DIN VDE and relevant IEC publications:

    VDE 0670, part 1000, and IEC 60694

    DIN VDE 0670, part 1,and IEC 62271-100

    1) Test voltage accordingDIN VDE 0670,part 1000, list 2

    2) 4000 A with forcedcooling

    3) 3150 A with forcedcooling in AP technology

    4) Higher valueson request

    5) 360 mm for fixed,280 mm for with-drawable Version

    6) Circuit-breaker withheat sink 616 mm

    7) Withdrawable Version

    8) Circuit-breaker withheat sink 634 mm

    73 - 105

    150 - 275205 - 310450 - 700

    424461 - 599 6)

    / 3

    4080

    1631.5

    Assembled PoleEmbedded Pole

    290 - 350290 - 350100 - 110147 - 26094 - 180260147 - 26094 18073 105kgWeight

    280 / 360 5)328

    895 7) / 1000555 /686 7)

    1575

    280 / 360 5)328

    895 7) / 1000555 / 686 7)

    1575

    210 - 275310

    570 - 700424

    631 - 661

    210 - 275310

    600 - 750459

    608 8)

    210 - 275310

    570 - 700424

    599 6)

    275310750459677

    210 - 275310

    600 - 750459

    608 8)

    210 - 275310

    570 - 700424

    599 6)

    150 - 275205 - 310450 - 700

    424461 - 599 6)

    mmpHabc

    Max. overall dimens-ions (fixed Version)

    / / / / / / / / / Fixed- / withdrawableVersion433333333sRated duration ofshort-circuit 4)

    40100401004080125 4)100158125 4)1004080kARated short-circuitmaking current

    164016401631.550406350401631.5kARated short-circuitbreaking current(symm.)

    63031503)63031503)63025006304000 2)6304000 2)ARated normal current

    50 - 6050 - 6050 6050 6050 60HzRated frequency

    40.5362417.512kVRated voltage 1)

  • ABB16.04.2012 VD4 Vacuum circuit-breaker | 11

    VD4 Vacuum circuit-breaker

    Circuit-breakerson withdrawable unit

    Fixed mounting with additional :

    Truck assembly

    Contact arms with tulip contacts

    Control wiring with plug

    Conversion frame at front

    Advantage by technology and compactness!

  • ABB16.04.2012 VD4 Vacuum circuit-breaker | 12

    VD4 Vacuum circuit-breaker

    Advantages

    Vacuum technology

    Embedded Poles

    Low switching energy

    High numbers of operations

    High reliability(according to DIN EN 61511-1 SIL3)

    Environment friendly material

    Continuously product improvement

    Wide range of accessories